COLDWATER DWGS VOL 5of5 - ELEC PT 2.pdf
PDF 5 MB Posted
- Solicitation number
- RFQ 171 200000000290 4
- Issued by
- Barry County, Michigan
About this file
This is an electrical design drawing document for a water treatment system installation project at a Welcome Center facility. The drawing details the electrical infrastructure, control systems, and mechanical room layout for a water filtration and softening system upgrade. The project involves the installation of multiple water treatment vessels, control panels, pumps, solenoid valves, and associated electrical components including a main control panel (MCP-291), filter control panel (CFP-131), backwash supply pump control panel, well pump control panel with variable frequency drive, and an OmniSite Crystal Ball station monitor. The system incorporates digital and analog monitoring capabilities with 4-20 mA feedback signals, multiple sensors including flow totalizers, pressure transducers, and level switches, and 208VAC 3-phase and 120VAC single-phase electrical distribution. The drawing specifies conduit sizing ranging from 3/4 inch to 2-1/2 inch and identifies cable types and quantities required for system interconnection.
The document outlines significant removal and relocation work including disconnection and removal of an existing 208/120V panel, removal of all conduit and wiring associated with chemical feed, filters, softener, and brine equipment, and relocation of a water heater with extension of power and control wires to its new location. The contractor is responsible for installation of a new precision digital PD2-6200 flow totalizer remote display, extension of circuit wiring to new panel D, and connection of terminals in the existing panel enclosure. The plans reference multiple related drawings (E601-E605) and note that conduit and wiring for filter and softener equipment will be provided by the manufacturer (ADEDGE), while remaining work falls under contractor responsibility. The project is located in mechanical room 108 of the Welcome Center facility with floor plans provided at 1/4-inch scale.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
208VAC 3PH
PANEL-E
CKT 25-27-29
LSH-316
LSL-317
PIT-302
BFV-319
BACKWASH SUPPLY PUMP
CONTROL PANEL
MCP-291
MAIN CONTROL PANEL
APU-26
ON FILTER SKID
208V 1PH
PANEL-E
CKT-9
CFP-131
ANALOG 4-20 mA
ANALOG 4-20 mA FEEDBACK
WATER INLET BFV-011A
SERVICE OUTLET BFV-012A
BACKWASH INLET BFV-013A
BACKWASH OUTLET BFV-014A
RINSE OUTLET BFV-015A
MAIN RAW INLET BFV-201A
MAIN BW INLET BFV-217A
VESSEL "201A" FIT-251A
WATER INLET BFV-011B
SERVICE OUTLET BFV-012B
BACKWASH INLET BFV-013B
BACKWASH OUTLET BFV-014B
RINSE OUTLET BFV-015B
MAIN RAW INLET BFV-201B
MAIN BW INLET BFV-217B
VESSEL "201B" FIT-251B
WATER INLET BFV-011C
SERVICE OUTLET BFV-012C
BACKWASH INLET BFV-013C
BACKWASH OUTLET BFV-014C
RINSE OUTLET BFV-015C
MAIN RAW INLET BFV-201C
MAIN BW INLET BFV-217C
VESSEL "201C" FIT-251C
JB-292
JUNCTION BOX
APUIX
ON SOFTENER SKID
VESSEL "126A" FIT-252A
FLECK VALVE FKV-126A
INLET SOLENOID SLV-149A
FIT-253
PT-263
PT-264
BFV-227
FLECK VALVE FKV-126B
INLET SOLENOID SLV-149B
VESSEL "126B" FE-252B
DIGITAL
DIGITAL
ANALOG 4-20mA
120VAC CONTROL
DIGITAL PUMP CONTROL + FEEDBACK
BW SUPPLY PUMP P-303
BW ISOLATION VALVE
BFV-303A
CONDUIT AND WIRING BY FILTER & SOFTENER MANUFACTURER (ADEDGE)
CONDUIT AND WIRING BY CONTRACTOR
SYSTEM INLET PT-261
SYSTEM OUTLET PT-262
PT-1 BLADDER
TANK
AN
AL
O G
-2
0m A
19 20
WELL PUMP
CONTROL PANEL/VFD
OMNISITE
CRYSTAL BALL
STATION MONITOR
DOOR ACCESS
CONTROLLER
ANALOG 4-20 mA 2
ANALOG 4-20 mA 3
DIGITAL
DIGITAL
DIGITAL 4
DIGITAL
DIGITAL 9
DIGITAL 7
DIGITAL 8
3 2
Jones & Henry Engineers, Ltd.
Fluid thinking...
www.JHeng.com
R
Scott Goodsell Rectangle
Scott Goodsell Typewritten Text
CABLE NO.
WELL PUMP FAIL1
FUNCTION
WELL PUMP SPEED2
WELL PUMP SPEED SET POINT3
WELL PUMP START/STOP4
WELL PUMP RUNNING5
WELL PUMP IN AUTO6
DOOR OPEN7
FLOOR FLOAT SWITCH8
WELL PUMP RUNNING9
BACKWASH PUMP RUNNING
BACKWASH HIGH DIFFERENTIAL PRESSURE
FILTER HIGH DIFFERENTIAL PRESSURE
FILTER CONTROL PANEL SYSTEM ALARM
FILTER (RESERVED - TBD)
SOFTENER HIGH DIFFERENTIAL PRESSURE
SOFTENER CONTROL PANEL SYSTEM ALARM
SOFTENER (RESERVED - TBD)
10 CFP-131
11 CFP-131 FEEDBACK
12 PT-1 BLADDER TANK
13 BACKWASH PUMP CONTROL/FEEDBACK
14 LSH-316
15 LSL-317
16 PIT-302
17 BFV-319
18 SOFTENER
CABLE TYPE (BELDEN NO.)
2/C 16 AWG (8620)
2/C 18 AWG (8760)
2/C 16 AWG (8620)
10/C 16 AWG (8622)
2/C 18 AWG TSP (8760)
6/C 16 AWG (8621)
2/C 16 AWG (8620)
4/C 18 AWG SHIELDED (9418)
5/C 16 AWG (9620)
38/C 14 AWG [COMPRISED OF (3) TYPE 8629 + (1) TYPE 8627]
5 TSP 18 AWG (9774)
3/C 14 AWG (8627)
CONDUIT NO.
AND SIZE
2/C 18 AWG (8760)
2/C 16 AWG (8620)
2/C 16 AWG (8620)
2/C 16 AWG (8620)
2/C 16 AWG (8620)
2/C 18 AWG TSP (8760)
2/C 18 AWG TSP (8760)
2/C 16 AWG TSP (8620)
SOFTENER
SOFTENER
5 1"
4 1-1/2"
1 3/4"
6 3/4"
11 3/4"
7 3/4"
10 3/4"
2 2-1/2"
3 1"
12 1"
14 1"
13 3/4"
3/4"
3/4"
Jones & Henry Engineers, Ltd.
Fluid thinking...
www.JHeng.com
R
Scott Goodsell Rectangle
Scott Goodsell Typewritten Text
EXISTING STORAGE ROOM
Scale: 1/4" = 1'-0"
WELCOME CENTER - EXISTING ENLARGED MECH. RM. 108 FLOOR PLAN
SCALE: 1/4" = 1'-0"
WELCOME CENTER - MECH. ROOM 108 REMOVAL PLAN
SCALE: 1/4" = 1'-0"
(SEE NOTE 3)
(SEE NOTE 3)
NOTES:
1. WATER HEATER RELOCATED BY OTHERS. CONTRACTOR TO EXTEND POWER AND CONTROL
WIRES TO NEW LOCATION.
2. LOCATE NEW PRECISION DIGITAL PD2-6200 FLOW TOTALIZER REMOTE DISPLAY ON WALL
NEAR DOOR. SEE FLOWMETER DIAGRAM, DRAWING E603.
3. CONTRACTOR TO REMOVE JUNCTION BOX AND ALL CONDUIT, POWER AND CONTROL
WIRES OF CHEMICAL FEED, FILTERS, SOFTENER, AND BRINE EQUIPMENT.
4. SEE RISER DIAGRAM, DRAWING E603.
5. REMOVE EXISTING PANEL BREAKERS, BUS WORK AND FEEDER FROM PANEL MOP IN
WELCOME CENTER ELECTRIC ROOM. INSTALL TERMINALS IN EXISTING PANEL ENCLOSURE
AND CONNECT TO EXISTING CIRCUIT BRANCH WIRING. EXTEND CIRCUIT WIRING TO NEW
PANEL 'D'.
6. EXISTING 208/120V PANEL IS TO HAVE ALL LOADS FROM IT DISCONNECTED. REMOVE
INCOMING POWER CABLES AND CONDUIT OF PANEL BACK TO ITS SOURCE. REMOVE ALL
POWER CABLES AND CONDUIT TO ITS LOADS WHICH WILL BE RECIRCUITED FROM NEW
PANEL-E. REMOVE ALL INTERIOR COMPONENTS OF EXISTING PANEL AND LEAVE BOX FOR
OWNER'S USE.
EXISTING HEATER
TO REMAIN
(TYP. 2)
EXISTING RECEPTACLE
(TYP. 4)
EXISTING
208/120V PANEL
SEE NOTE 6.
EXISTING LIGHT FIXTURE
TO BE RELOCATED. SEE
DRAWING E102. (TYP. 6)
FLOW TOTALIZER
REMOTE DISPLAY
(SEE NOTE 2)
WATER HEATER
(RELOCATED)
SEE NOTE 1
J
W.H.
A-10
WATER HEATER PREVIOUS
LOCATION (SEE NOTE 1)
Jones & Henry Engineers, Ltd.
Fluid thinking...
www.JHeng.com
R
| COLDWATER M101 |
| Electrical |
| COLDWATER E001 |
| COLDWATER E101 |
| COLDWATER E102 |
| COLDWATER E601 |
| COLDWATER E602 |
| COLDWATER E603 |
| COLDWATER E604 |
| COLDWATER E605 |