COLDWATER DWGS VOL 5of5 - ELEC PT 2.pdf

PDF 5 MB Posted

Attached to
591/19213. CDP; Coldwater WC - Ctr Well & Filtration Sys Rplc
Solicitation number
RFQ 171 200000000290 4
Issued by
Barry County, Michigan

About this file

This is an electrical design drawing document for a water treatment system installation project at a Welcome Center facility. The drawing details the electrical infrastructure, control systems, and mechanical room layout for a water filtration and softening system upgrade. The project involves the installation of multiple water treatment vessels, control panels, pumps, solenoid valves, and associated electrical components including a main control panel (MCP-291), filter control panel (CFP-131), backwash supply pump control panel, well pump control panel with variable frequency drive, and an OmniSite Crystal Ball station monitor. The system incorporates digital and analog monitoring capabilities with 4-20 mA feedback signals, multiple sensors including flow totalizers, pressure transducers, and level switches, and 208VAC 3-phase and 120VAC single-phase electrical distribution. The drawing specifies conduit sizing ranging from 3/4 inch to 2-1/2 inch and identifies cable types and quantities required for system interconnection.

The document outlines significant removal and relocation work including disconnection and removal of an existing 208/120V panel, removal of all conduit and wiring associated with chemical feed, filters, softener, and brine equipment, and relocation of a water heater with extension of power and control wires to its new location. The contractor is responsible for installation of a new precision digital PD2-6200 flow totalizer remote display, extension of circuit wiring to new panel D, and connection of terminals in the existing panel enclosure. The plans reference multiple related drawings (E601-E605) and note that conduit and wiring for filter and softener equipment will be provided by the manufacturer (ADEDGE), while remaining work falls under contractor responsibility. The project is located in mechanical room 108 of the Welcome Center facility with floor plans provided at 1/4-inch scale.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

208VAC 3PH

PANEL-E

CKT 25-27-29

LSH-316

LSL-317

PIT-302

BFV-319

BACKWASH SUPPLY PUMP

CONTROL PANEL

MCP-291

MAIN CONTROL PANEL

APU-26

ON FILTER SKID

208V 1PH

PANEL-E

CKT-9

CFP-131

ANALOG 4-20 mA

ANALOG 4-20 mA FEEDBACK

WATER INLET BFV-011A

SERVICE OUTLET BFV-012A

BACKWASH INLET BFV-013A

BACKWASH OUTLET BFV-014A

RINSE OUTLET BFV-015A

MAIN RAW INLET BFV-201A

MAIN BW INLET BFV-217A

VESSEL "201A" FIT-251A

WATER INLET BFV-011B

SERVICE OUTLET BFV-012B

BACKWASH INLET BFV-013B

BACKWASH OUTLET BFV-014B

RINSE OUTLET BFV-015B

MAIN RAW INLET BFV-201B

MAIN BW INLET BFV-217B

VESSEL "201B" FIT-251B

WATER INLET BFV-011C

SERVICE OUTLET BFV-012C

BACKWASH INLET BFV-013C

BACKWASH OUTLET BFV-014C

RINSE OUTLET BFV-015C

MAIN RAW INLET BFV-201C

MAIN BW INLET BFV-217C

VESSEL "201C" FIT-251C

JB-292

JUNCTION BOX

APUIX

ON SOFTENER SKID

VESSEL "126A" FIT-252A

FLECK VALVE FKV-126A

INLET SOLENOID SLV-149A

FIT-253

PT-263

PT-264

BFV-227

FLECK VALVE FKV-126B

INLET SOLENOID SLV-149B

VESSEL "126B" FE-252B

DIGITAL

DIGITAL

ANALOG 4-20mA

120VAC CONTROL

DIGITAL PUMP CONTROL + FEEDBACK

BW SUPPLY PUMP P-303

BW ISOLATION VALVE

BFV-303A

CONDUIT AND WIRING BY FILTER & SOFTENER MANUFACTURER (ADEDGE)

CONDUIT AND WIRING BY CONTRACTOR

SYSTEM INLET PT-261

SYSTEM OUTLET PT-262

PT-1 BLADDER

TANK

AN

AL

O G

-2

0m A

19 20

WELL PUMP

CONTROL PANEL/VFD

OMNISITE

CRYSTAL BALL

STATION MONITOR

DOOR ACCESS

CONTROLLER

ANALOG 4-20 mA 2

ANALOG 4-20 mA 3

DIGITAL

DIGITAL

DIGITAL 4

DIGITAL

DIGITAL 9

DIGITAL 7

DIGITAL 8

3 2

Jones & Henry Engineers, Ltd.

Fluid thinking...

www.JHeng.com

R

Scott Goodsell Rectangle

Scott Goodsell Typewritten Text

CABLE NO.

WELL PUMP FAIL1

FUNCTION

WELL PUMP SPEED2

WELL PUMP SPEED SET POINT3

WELL PUMP START/STOP4

WELL PUMP RUNNING5

WELL PUMP IN AUTO6

DOOR OPEN7

FLOOR FLOAT SWITCH8

WELL PUMP RUNNING9

BACKWASH PUMP RUNNING

BACKWASH HIGH DIFFERENTIAL PRESSURE

FILTER HIGH DIFFERENTIAL PRESSURE

FILTER CONTROL PANEL SYSTEM ALARM

FILTER (RESERVED - TBD)

SOFTENER HIGH DIFFERENTIAL PRESSURE

SOFTENER CONTROL PANEL SYSTEM ALARM

SOFTENER (RESERVED - TBD)

10 CFP-131

11 CFP-131 FEEDBACK

12 PT-1 BLADDER TANK

13 BACKWASH PUMP CONTROL/FEEDBACK

14 LSH-316

15 LSL-317

16 PIT-302

17 BFV-319

18 SOFTENER

CABLE TYPE (BELDEN NO.)

2/C 16 AWG (8620)

2/C 18 AWG (8760)

2/C 16 AWG (8620)

10/C 16 AWG (8622)

2/C 18 AWG TSP (8760)

6/C 16 AWG (8621)

2/C 16 AWG (8620)

4/C 18 AWG SHIELDED (9418)

5/C 16 AWG (9620)

38/C 14 AWG [COMPRISED OF (3) TYPE 8629 + (1) TYPE 8627]

5 TSP 18 AWG (9774)

3/C 14 AWG (8627)

CONDUIT NO.

AND SIZE

2/C 18 AWG (8760)

2/C 16 AWG (8620)

2/C 16 AWG (8620)

2/C 16 AWG (8620)

2/C 16 AWG (8620)

2/C 18 AWG TSP (8760)

2/C 18 AWG TSP (8760)

2/C 16 AWG TSP (8620)

SOFTENER

SOFTENER

5 1"

4 1-1/2"

1 3/4"

6 3/4"

11 3/4"

7 3/4"

10 3/4"

2 2-1/2"

3 1"

12 1"

14 1"

13 3/4"

3/4"

3/4"

Jones & Henry Engineers, Ltd.

Fluid thinking...

www.JHeng.com

R

Scott Goodsell Rectangle

Scott Goodsell Typewritten Text

EXISTING STORAGE ROOM

Scale: 1/4" = 1'-0"

WELCOME CENTER - EXISTING ENLARGED MECH. RM. 108 FLOOR PLAN

SCALE: 1/4" = 1'-0"

WELCOME CENTER - MECH. ROOM 108 REMOVAL PLAN

SCALE: 1/4" = 1'-0"

(SEE NOTE 3)

(SEE NOTE 3)

NOTES:

1. WATER HEATER RELOCATED BY OTHERS. CONTRACTOR TO EXTEND POWER AND CONTROL

WIRES TO NEW LOCATION.

2. LOCATE NEW PRECISION DIGITAL PD2-6200 FLOW TOTALIZER REMOTE DISPLAY ON WALL

NEAR DOOR. SEE FLOWMETER DIAGRAM, DRAWING E603.

3. CONTRACTOR TO REMOVE JUNCTION BOX AND ALL CONDUIT, POWER AND CONTROL

WIRES OF CHEMICAL FEED, FILTERS, SOFTENER, AND BRINE EQUIPMENT.

4. SEE RISER DIAGRAM, DRAWING E603.

5. REMOVE EXISTING PANEL BREAKERS, BUS WORK AND FEEDER FROM PANEL MOP IN

WELCOME CENTER ELECTRIC ROOM. INSTALL TERMINALS IN EXISTING PANEL ENCLOSURE

AND CONNECT TO EXISTING CIRCUIT BRANCH WIRING. EXTEND CIRCUIT WIRING TO NEW

PANEL 'D'.

6. EXISTING 208/120V PANEL IS TO HAVE ALL LOADS FROM IT DISCONNECTED. REMOVE

INCOMING POWER CABLES AND CONDUIT OF PANEL BACK TO ITS SOURCE. REMOVE ALL

POWER CABLES AND CONDUIT TO ITS LOADS WHICH WILL BE RECIRCUITED FROM NEW

PANEL-E. REMOVE ALL INTERIOR COMPONENTS OF EXISTING PANEL AND LEAVE BOX FOR

OWNER'S USE.

EXISTING HEATER

TO REMAIN

(TYP. 2)

EXISTING RECEPTACLE

(TYP. 4)

EXISTING

208/120V PANEL

SEE NOTE 6.

EXISTING LIGHT FIXTURE

TO BE RELOCATED. SEE

DRAWING E102. (TYP. 6)

FLOW TOTALIZER

REMOTE DISPLAY

(SEE NOTE 2)

WATER HEATER

(RELOCATED)

SEE NOTE 1

J

W.H.

A-10

WATER HEATER PREVIOUS

LOCATION (SEE NOTE 1)

Jones & Henry Engineers, Ltd.

Fluid thinking...

www.JHeng.com

R

COLDWATER M101
Electrical
COLDWATER E001
COLDWATER E101
COLDWATER E102
COLDWATER E601
COLDWATER E602
COLDWATER E603
COLDWATER E604
COLDWATER E605

File details come from the government source that posted it. Updated .