Addendum No. 01 Dwgs 1 of 2_20200723.pdf

PDF 4 MB Posted

Attached to
591/19213. CDP; Coldwater WC - Ctr Well & Filtration Sys Rplc
Solicitation number
RFQ 171 200000000290 4
Issued by
Barry County, Michigan

About this file

This is Addendum No. 01 to a construction project for a water treatment facility, consisting of detailed engineering drawings and specifications. The addendum includes a site plan, grounding plan, electrical plan, and lighting plan for a new treatment building and associated infrastructure improvements. The project scope encompasses installation of a new 3-inch raw water line, new well, 8-inch sanitary sewer line with cleanout connections, 4-inch backwash waste pipe, new treatment building construction, removal of existing trees and sidewalks, installation of new chain link fence, concrete driveway (approximately 1,870 square feet), concrete splash pad, slide gate, concrete bollards, widened concrete pavement, and abandonment of an existing well per specification section 33 29 00. The site plan indicates multiple elevation points ranging from 983.00 to 991.0 feet, lagoon specifications with a maximum water level of 987.00 feet and freeboard of 1 foot, and requirements for silt fence installation and driveway backwash drying bed.

The electrical and grounding specifications detail requirements for a main control panel (MCP-291), multiple disconnect switches for various equipment including backwash control, water heater, well pump controller, and roll-up door systems, as well as specialized equipment such as metering pumps, filter skid, softener skid, and flow meters. Grounding requirements include installation of copper-clad steel core ground rods, exothermic connections to new and existing grounding rings, building pad rebar (UFER ground), and metal roof bonding in compliance with NEC Article 250 ohmic requirements. Lighting specifications call for LED heavy industrial fixtures (Holophane model), outdoor soffit LED fixtures with motion sensors, and emergency lighting with 90-minute battery backup. All conduit in the building addition shall be PVC-coated rigid galvanized steel, and all electrical enclosures must be NEMA 4X rated. The addendum was issued on July 23, 2020.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

UG-EL

EC

UG-EL

EC

UG-EL

EC

UG-EL

EC

UG-EL

EC

X

X

X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

ST

ST

ST

ST

ST

ST

ST

ST

ST

ST

ST

ST

ST

ST

ST

ST

ST

ST

S

S

S

S

S S

S S

ST

8" SANITARY

EXIT BUILDING AT

INV. EL. = 986.50

NEW

TREATMENT

BUILDING

4" BACKWASH

WASTE PIPE

3" FINISHED

WATER (MIN.

5'-0" BURY)

NEW 3" RAW

WATER LINE

NEW WELL.

SEE DETAIL

THIS SHEET.

8" SANITARY

NEW BRUSH LINE. REMOVE

TREES AS REQUIRED FOR

NEW LAGOON EXCAVATION

NEW CHAIN

LINK FENCE

X X

X X

X X

X

X X

X

1:1

1:1

1:1

1:1

4'-0"

SCALE: 1" = 20'-0"

SA

SA

BORING

LOCATION 2

BORING LOCATION 1

4' WIDE CONCRETE

SPLASH PAD. SEE

DETAILS SHEET C501

8" CLEANOUT

CONNECT TO EXISTING 8"

SANITARY. CUT EXISTING

FOR NEW 8"x8" WYE AND

INSTALL CLEANOUT.

EX. INV. EL. = 985.89

A

A

ABANDON EXISTING WELL

PER SPEC SECTION 33 29 00

8" CO

EXISTING

MECHANICAL

ROOM

BY

OTHERS

BY

CONTRACTOR

SITE PLAN

NEW WATER AND SANITARY TO

BE D.I.P. AND ENCASED IN 6"

CONCRETE UNDER DRIVEWAY.

EL. = 990.8

EL. = 989.6 EL. = 988.5

EL. = 987.510'-0" MIN.

WIDTH DRIVEWAY

BACKWASH

DRYING

BED

INSTALL SILT FENCE PER

DETAIL ON SHEET C501

X X

X NEW 8'

SLIDE GATE

NEW CONCRETE

BOLLARDS (TYP. OF 4)

MATCH

EXISTING

ELEVATION

REMOVE EXISTING SIDEWALK

AND REPLACE WITH WIDENED

6" CONCRETE PAVEMENT DETAIL

SHOWN ON SHEET C501

EL. = 991.0

EL. = 990.7

EL. = 991.0

EL. = 990.5

EL. = 990.8

EL. = 989.8

EL. = 988.8

EL. = 987.9

EL. = 990.4

REMOVE EXISTING

YARD HYDRANT

SAW CUT

EXISTING

SIDEWALK

NEW 6" CONCRETE DRIVE

APPROX. 1,870 S.F.

CW

CW

4' 5' 15' 5' 4'

EXISTING EXISTING

T/O LAGOON BIRM

EL. 988.00

1' FREEBOARD

MAX. WATER LEVEL

EL. 987.00

NTS

SECTION A-A

B/O LAGOON

EL. 983.00

Jones & Henry Engineers, Ltd.

Fluid thinking...

www.JHeng.com

R

GROUNDING PLAN

Scale: 1/4" = 1'-0"

4"x2" GROUND BAR

NOTES:

1. ALL GROUNDING CONNECTIONS OF NEW AND EXISTING

GROUNDING RINGS, NEW BUILDING PAD REBAR (UFER)

AND METAL ROOF SHALL BE EXOTHERMIC.

2. APPLY BONDING JUMPERS TO ROOF AS NEEDED FOR

ELECTRICAL CONTINUITY.

3. INSTALL NEW GROUNDING RING AT SAME DEPTH AND

DISTANCE FROM WALL AS EXISTING.

4. ALL GROUND RODS SHALL BE COPPER-CLAD STEEL CORE.

NUMBER OF GROUND RODS SHOWN IS AN

APPROXIMATION. CONTRACTOR SHALL FURNISH AND

INSTALL GROUND RODS AS NECESSARY TO MEET NEC

ARTICLE 250 OHMIC REQUIREMENTS.

5. ALL GROUNDING CONDUCTORS SHALL BE #4/0 AWG

BARE STRANDED COPPER.

TO METAL ROOF

TO METAL ROOF

UFER GROUND

(TYP. OF 2)

EXISTING GROUND RING

EXISTING GROUND RING

COPPER-CLAD STEEL

CORE GROUND ROD

(TYP. - SEE NOTE 4)

SE

E

N O

TE

(TY

P.

FDFD

TO PANEL-E

Jones & Henry Engineers, Ltd.

Fluid thinking...

ELECTRICAL PLAN

Scale: 1/4" = 1'-0"

MAIN CONTROL

PANEL (MCP-291)

AND DISCONNECT.

SEE NOTE 3

LIGHTING PLAN

Scale: 1/4" = 1'-0"

EUH-1 DISCONNECT

(NON-FUSED)

SEE NOTE 2

BACKWASH CONTROL

PANEL AND DISCONNECT

(NON-FUSED)

SEE NOTES 1, 3

EYEWASH WATER HEATER

DISCONNECT (NON-FUSED)

EF-1 DISCONNECT

SEE NOTE 2

WELL PUMP CONTROLLER FURNISHED

BY WELL PUMP SUPPLIER. SEE NOTE 3

ROLL UP DOOR DISCONNECT

(NON-FUSED)

(ABOVE)

ZS1 DOOR STRIKE FLOAT SWITCH

LS-1 (BELOW) SEE NOTE 4

OMNISITE STATION

MONITOR

PANEL-E

208/120V 3PH 4W

NOTES:

1. CONTRACTOR TO FURNISH AND INSTALL THIS ITEM AND ITS UNISTRUT FRAME FOR FLOOR

MOUNTING.

2. DISCONNECT SWITCH FURNISHED AND INSTALLED BY VENDOR.

3. SEE RISER DIAGRAM, DRAWING E603.

4. DOOR SUPPLIER TO PROVIDE ACCESS CONTROLLER ELECTRIC STRIKE. COORDINATE WIRING

WITH DOOR SUPPLIER. ELECTRIC STRIKE IS TO BE ACTIVATED BY THE FLOAT SWITCH OR THE

ACCESS CONTROLLER.

5. REMOVE ALL CIRCUITS FROM STORAGE ROOM PANELBOARD AND RE-CIRCUIT FROM

PANEL-E. REMOVE POWER FEED AND CONDUIT TO PANELBOARD BACK TO THE SOURCE.

REMOVE ALL INTERNALS OF PANELBOARD AND LEAVE EMPTY BOX FOR SUE BY OWNER.

6. REPLACE AND RE-CIRCUIT STORAGE ROOM LUMINAIRES AS SHOWN. COORDINATE

LOCATION WITH ARCHITECTURAL DRAWINGS SO LUMINAIRES ARE PLACED BETWEEN

SHELVING UNITS.

7. ALL CONDUIT IN BUILDING ADDITION SHALL BE PVC COATED RIGID GALVANIZED STEEL.

8. ALL ELECTRIC ENCLOSURES OF BUILDING ADDITION SHALL BE NEMA 4X.

MANUAL ON/OFF LIGHT

SWITCH: COOPER X-SWITCH

CAT. NO. AH7810XC000

T/FIXTURE @ 12'-0" AFF

(TYP.)

SOFTENER PANEL

SEE NOTE 3

SOFTENER DISCONNECT

SEE NOTE 1

EUH-2 DISCONNECT (NON-FUSED)

SEE NOTE 2

EF-1 H-O-A

SEE NOTE 1

LIGHT FIXTURE SCHEDULE

TYPE DESCRIPTION

L1 LED INTERIOR HEAVY INDUSTRIAL, ENCLOSED AND GASKETED STRIP FIXTURE

HOLOPHANE CAT. NO. EMX-L48-6000LM-FGCL-WD-MVOLT-40K-80CRI-CR-DWHXD

48"Lx5.1"Wx4.6"H, 6248 LUMENS, 39.5 WATTS, FLAT CLEAR GLASS LENS, NON-DIMMING, 80CRI, CORROSION RESISTANT WHITE FINISH, 120-277V 50/60Hz

SWITCH

E1

E2

E3

MANUAL ON/OFF MOTOR CONTROL SWITCH, NEMA 4x, 30A, 600V COOPER X-SWITCH CAT. NO AH7810XC00 5"Wx6"Hx3.56"D

REMOTE SINGLE LED LIGHT

NICOR MWOS-REMOTE

LED EMERGENCY LIGHT FOR INDOOR/OUTDOOR USE

NICOR CAT. NO. EML6-1-UNV-WH

120/277VAC, 2.4W, 90-MINUTE NiCAD BATTERY, ABS CORROSION RESISTANT WHITE ENCLOSURE

LED COMBO EXIT SIGN AND EMERGENCY LIGHT

NICOR CAT. NO. ECL1-10-UNV-WH-R-2-R

120/277VAC, 2.9W, 90-MINUTE NiCAD BATTERY, RED LETTERS, ABS CORROSION RESISTANT

WHITE ENCLOSURE FOR USE WITH ONE REMOTE HEAD

DOOR STRIKE AND ACCESS

CONTROLLER FURNISHED

BY DOOR SUPPLIER

PT-1

SEE NOTE 3

PIT-302

LSL-317

LSH-316

BFV-319

NOTE 3

METERING PUMPS

(CFP-131) NOTE 3

FINSHED WATER FLOW METER,

FE-1, MOUNTED IN PIPING AT

10'-3" AFF

M

FILTER SKID

SOFTENER SKIDBRINE TANK

BLADDER

TANK

BACKWASH

SUPPLY PUMP

BACKWASH

HOLDING TANK

JB-292

JUNCTION BOX

SEE NOTE 3

L2 OUTDOOR SOFFIT LED FIXTURE WITH MOTION SENSOR

DEKOR TYPE SPOT LIGHT WITH 20° - 30° BEAM ANGLE,

33 LUMEN, TRANSFORMER

FILTER SKID

SOFTENER SKID

BACKWASH

SUPPLY PUMP

L-1

MOTORIZED LOUVER

EF-1

NOTE 3

POSITION SWITCH

REMOTE FLOW TRANSMITTER FT-1

DEDICATED COMPRESSOR

RECEPTICALE

EXISTING HEATER

(TYP. 2)

EXISTING RECEPTACLE

(TYP. 4)

ROLL UP DOOR

DISCONNECT

(NON-FUSED)

SEE NOTE 6

(TYP. OF 6)

EXISTING PANELBOARD

FLUSH MOUNTED

SEE NOTE 5

BUILDING ADDITION

SEE NOTES 6, 7

EXISTING BUILDING

STORAGE

ROOM

STORAGE

ROOM

TO PANEL-E

CKT. 1

TO PANEL-E

CKT. 38

1 1

Jones & Henry Engineers, Ltd.

Fluid thinking...