COLDWATER DWGS VOL 3of5 - PLUMB PT 2+MECH.pdf
PDF 3 MB Posted
- Solicitation number
- RFQ 171 200000000290 4
- Issued by
- Barry County, Michigan
About this file
This is a technical drawing document for the Coldwater water treatment facility project, specifically Volume 3 of 5 covering plumbing and mechanical systems. The document is prepared by Jones & Henry Engineers, Ltd., and contains detailed schematic and construction drawings for a water filtration, treatment, and distribution system. The project includes installation of multiple filtration units (Filters A, B, and C), water softening equipment, backwash systems, and associated piping infrastructure. Key components include a 3,450-gallon backwash holding tank, hydropneumatic storage tanks, multiple ball valves and backflow preventers, chemical metering systems for sodium hypochlorite (NaOCl), and comprehensive plumbing networks for raw water, filtered water, softened water, and waste streams. The drawings specify pipe sizes ranging from 0.5 inches to 4 inches, elevations for various connection points, and detailed installation requirements for floor sleeves, wall penetrations, and equipment supports.
The technical specifications include HVAC requirements with two electric unit heaters (EUH-1 and EUH-2) rated at 15.0 kilowatts and 1,330 cubic feet per minute each, one exhaust fan (EF-1) with 1,500 cubic feet per minute capacity, and intake louvers with motorized backdraft dampers. General notes emphasize contractor responsibility for field verification, equipment coordination with manufacturers, installation per code requirements, vibration isolation, and completion of all testing before insulation application. The drawings indicate equipment furnished under CSI divisions 46 61 21 (filtration equipment) and 46 61 22 (softening equipment), with remaining piping, supports, and installation performed by the contractor. All materials specified are to be stainless steel or galvanized construction suitable for water treatment applications, with detailed schedules provided for mounting heights, drain slopes, and safety equipment including emergency eyewash stations.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
4"x3" REDUCER
4" TYPE D
FLOOR SLEEVE
4" BACKWASH WASTE TO
LAGOON. ENCASE IN 6"
CONCRETE UNDER BUILDING.
4" FILTER
EFFLUENT ℄ EL. 989.37
3" FINISHED
WATER ℄ EL. 989.15
48"Ø
BLADDER
TANK
BRINE TANK
SECTION A-A
Scale: 3/8" = 1'-0"
SECTION B-B
Scale: 3/8" = 1'-0"
BACKWASH
PUMP
ONLINE AND SPARE
NaOCl METERING PUMPS
EMERGENCY
EYE WASH &
HOSE
3" FINISHED
WATER ℄ EL. 999.01
(2) 3" TYPE D
FLOOR SLEEVE
4" BACKWASH
SUPPLY ℄ EL. 998.51
3" FINISHED WATER3" RAW WATER
3" RAW
WATER ℄ EL. 999.01
3" RAW
WATER ℄ EL. 999.01
4" BACKWASH
SUPPLY ℄ EL. 998.51
4" BACKWASH/WELL
WASTE
3" FINISHED
WATER ℄ EL. 999.01
3" BACKFLOW
PREVENTER
1-1/2" DRAIN LINE FROM BFP.
INDIRECTLY DISCHARGE TO
FLOOR DRAIN
1/2" SOLUTION TUBE AND CORP
STOP. UPSTREAM OF STATIC MIXER
FINISHED WATER METER
SOFTENER CONTROL
PANEL
M
3,450 GAL
BACKWASH
HOLDING TANK
OVERHEAD
DOOR
MOP SINK
BFV-201A BFV-201B BFV-201C
BFV-217A BFV-217B BFV-217C
BFV-011A
BFV-014A
BFV-011B
BFV-014B
BFV-011C
BFV-014C
BFV-013A
BFV-015A
BFV-013B
BFV-015B
BFV-013C
BFV-015C
BFV-012A BFV-012B BFV-012C
FFE = 988.26
FFE = 988.26
1/2" RAW AND FINISHED
WATER PVC SAMPLE LINES
AND SMOOTH NOSE
BRASS SAMPLE VALVES
4" TEE
B-2
1/2" AIR RELEASE VALVE.
PIPE DRAINS TO MOP SINK.
1/2" AIR RELEASE
VALVES. PIPE DRAINS
TO MOP SINK.
1/2" PVC FOR NaOCl FEED
3" OVERFLOW ℄ EL. 998.51
FFE = 1000.26
1/2" FLEXIBLE TUBE
TO EACH SOFTENER
FILTRATION SKID AND CONNECTION FLANGES
PROVIDED BY 46 61 21 MANUFACTURER
FILTRATION SKID AND
CONNECTION FLANGES
PROVIDED BY 46 61 21
MANUFACTURER
FILTRATION SKID AND CONNECTION FLANGES
PROVIDED BY 46 61 21 MANUFACTURER
SOFTENING SYSTEM SKID PROVIDED
BY 46 61 22 MANUFACTURER
PIPE HANGERS
PIPE HANGER WITH
LATERAL SUPORT ANGLE.
SEE DETAIL 10, SHEET S501.
GALV. ANGLE WALL
BRACKET WITH GALV.
U-BOLT (TYP.)
WALL BRACKET
(TYP.)
WALL BRACKET AT
6'-0" MAX. (TYP.)
WALL BRACKET
(TYP.)
PIPE HANGERS
PIPE HANGER WITH
LATERAL SUPORT ANGLE.
SEE DETAIL 10, SHEET S501.
NOTE:
NOT ALL PIPE SUPPORTS ARE SHOWN.
PROVIDE 3" AND 4" PIPE SUPPORTS AT
6'-0" C/C MAXIMUM.
Jones & Henry Engineers, Ltd.
Fluid thinking...
www.JHeng.com
R
Scott Goodsell Rectangle
Scott Goodsell Typewritten Text
NTS
STANCHION PIPE SIZE SEE
SCHEDULE
ADJUSTABLE PIPE SADDLE SUPPORT
WITH U-BOLT, TOLCO FIG. 318 OR
EQUAL.
SERVICE PIPE
9"x3 8"x9"
10"x5 8"x10"
12"x5 8"x12"
12"x3 4"x12"
4" To 12"
14" To 16"
18" To 36"
2" To 31
2"
FLOOR
NOTES:
1. HOT DIP GALVANIZE STANCHIONS AFTER FABRICATION.
2. FOR STANCHION PIPES AT BASE ELBOWS, SUBSTITUTE A MOUNTING PLATE FOR THE
SADDLE SUPPORT WITH U-BOLT THAT IS SHOWN IN THE ABOVE DETAIL.
MOUNTING PLATE SHALL BE DRILLED TO MATCH BOLT HOLE PATTERN PROVIDED IN
BASE ELBOW. MOUNTING PLATE SHALL BE A MINIMUM OF 12" THICK.
EXPANSION ANCHOR BOLTS SEE
SCHEDULE
1" NON-SHRINK GROUT
BASE PLATE
SEE SCHEDULE
Service Pipe Size Base Plate
Size
WELD ALL AROUND
STANCHION PIPE SUPPORT DETAIL
1" G ro ut
HSS 3.500"x0.216"
HSS 4.500"x0.237"
HSS 6.625"x0.280"
HSS 2.875"x0.203"
Stanchion Pipe Size
12'
12'
12'
12'
Maximum Distance Between Stanchions
8'-0"
8'-0"
8'-0"
7'-6"
Maximum Stanchion Height
4" Dia. w/43
4" Emb.
4" Dia. w/ 8" Emb.
8" Dia. w/ 4" Emb.
Anchor Bolt Size
8" Dia. w/ 4" Emb.
M ax im um
S ta nc hi on H ei gh t
NTS
FILL W/NON-METALLIC
NON SHRINK GROUT
(2) LAYERS 15# FELT
PAPER
REPLACE MASONRY AS
REQUIRED
EXISTING MASONRY WALL
BREAK OUT MASONRY TO
MORTAR JOINT
SEALANT
NEW MASONRY WALL
NOTE:
FOR EXTERIOR WALLS, FACE COURSES TO BE MASONRY AND MIDDLE COURSE
TO BE FILLED WITH FIBERGLASS INSULATION.
PIPE SLEEVE THRU EXISTING OR
NEW MASONRY WALL
TYPE F
1" M in
NTS
INSIDE WALL
STAINLESS STEEL BOLTS
SERVICE PIPE
NOTE:
1. EXISTING WALLS SHALL BE CORE DRILLED.
2. CONCRETE SHALL BE WORKED IN AND VIBRATED TO ELIMINATE
ALL VOIDS IN CONCRETE - IF VOIDS DO REMAIN, FILL WITH GROUT
BEFORE INSTALLING PIPE AND RUBBER SEALS.
3. UNLESS OTHERWISE SHOWN ON THE DRAWINGS ALL INTERIOR
WALL PENETRATIONS SHALL USE TYPE C PIPE SLEEVE.
SHEET METAL OR LAMINATED FIBER CONCRETE FORM ADEQUATELY BRACED IN FIELD
AND STRIPPED OUT BEFORE INSTALLING PIPE, EXCEPT IN MASONRY WHERE SLEEVE
SHALL BE 3 16" STEEL AND SHALL BE INSTALLED WITH MASONRY. CONTRACTOR MAY
USE A THERMOPLASTIC WALL SLEEVE, CENTURY-LINE SLEEVE BY THUNDERLINE
CORP., OR EQUAL, TO BE LEFT IN PLACE.
PIPE SLEEVE
TYPE C
MODULAR MECHANICAL TYPE SEAL
OF INTERLOCKING SYNTHETIC
RUBBER LINKS
NTS
PIPE OR DUCT
FOR SQUARE OR RECTANGULAR
OPENINGS, USE 1 4" STEEL SLEEVE SIZE 1"
LARGER THAN DUCT OR 1" LARGER THAN
FLANGE.
NOTE TO DESIGNER:
THIS TYPE OF SEAL IS NOT WATERTIGHT AND WILL LEAK TO
FLOOR BELOW DURING WASHDOWNS. SPECIFY TYPE G FOR
WATERTIGHT.
ROUND EXPANDING FOAM ROPE
GASKET. PLACE 12" BELOW TOP OF
SLEEVE & APPLY SEALANT (WHEN
SLEEVE IS ONE SIZE LARGER THAN
SERVICE PIPE ONLY)
FINISHED
FLOOR SLAB
FOUR CONCRETE
ANCHORS
NOTE:
THRU EXISTING FLOORS WHERE TYPE "D" FLOOR SLEEVES ARE CALLED
OUT, THE CONTRACTOR SHALL CORE FLOOR AND CAULK AS SHOWN,
ELIMINATING THE STEEL SLEEVE.
STANDARD WEIGHT STEEL PIPE
SLEEVE ONE SIZE LARGER THAN
PIPE OR 1" LARGER THAN
FLANGE
FLOOR SLEEVE
TYPE D
1"
1'- 4"
3'-0"
1'-4"
CHEMICAL METERING PUMP STAND
ATTACH TO WALL WITH 5 16"X21
2"
ADHESIVE ANCHOR (6 REQUIRED)
4" TOP PLATE GLUED AND
BOLTED TO FRAMES
L 11 2"X11
2"X1 4"
(TYPICAL OF 2)
2"X1
4" ⅊
(TYP. BOTH ENDS)
L 2"X2"X1 4"
(TYP. BOTH ENDS)
NOTES:
1. ALL MATERIALS AND ANCHORS SHALL BE FRP.
2. TOP OF PUMP STAND ASSEMBLY TO BE 4'-0" ABOVE FINISHED FLOOR.
3. BOLT PUMPS TO TOP PLATE PER MANUFACTURE RECOMMENDATIONS.
2"Ø FRP BOLTS AND GLUED
CONNECTION TO FRAMES
NTS
Jones & Henry Engineers, Ltd.
Fluid thinking...
www.JHeng.com
R
Scott Goodsell Rectangle
Scott Goodsell
NTS
2" P-TRAP
2" CISP AUXILIARY DRAIN
FINISH FLOOR
ZURN Z-1012-3" DEEP SEAL TRAP
W/ADJ. C.O. OR EQUAL
CAST IRON FLOOR DRAIN
ZURN # Z-511 OR EQUAL
NTS
FINISHED FLOOR CLEANOUT C.O.
EQUIPMENT DRAIN DETAILTYPE B FLOOR DRAIN DETAIL
3"
EYE/FACE WASH DETAIL
1/2" TEMPERED WATER
1/2" RECOIL HOSE, 12 FT.
SPRAY HEAD/YOKE
ASSEMBLY
NTSNTS
TEST COCKS
(TYPICAL)
RELOCATE ALL TEST COCKS TO
BRACKET IF NOT LESS THAN 5'-0"
ABOVE FINISH FLOOR (TYP)
PRESSURE REDUCER IF
REQ'D. WITH OVERFLOW
NTS
STRAINER
TAP OR VALVE
SIZE LINES
EQUIPMENT DRAIN
(DOUBLE CHECK TYPE SHOWN)
STAINLESS STEEL FLASHING
W/CLAMPING RING BY PIPE
INSTALLER
PRE - MOLDED PIPE SEAL
W/STAINLESS STEEL CLAMPING
RING
VENT COLLAR &
SEALANT
CAULK
ROOFING BY OTHERS
NOTE:
PIPE & CONDUIT SIMILAR (METAL
SLEEVE NOT REQUIRED)
BACKFLOW PREVENTER DETAILVENT PIPE DETAIL
2" A ir G ap
4" VTR
CO
MS
2" EQUIPMENT DRAIN
FROM BACKWASH
SUPPLY PUMP
8" 8" 8" 8"
8"
3"3"
3"
PLUMBING PLAN
Scale: 1/4" = 1'-0"
CO
TO EXISTING SANITARY. SEE
SITE PLAN C101 FOR CONT.
EMERGENCY
EYE/FACE WASH
WATER HEATER MOUNTED
ON SHELF ABOVE MOP SINK
CO
4" VTR
FD
ED
MS
FD
DWV (DRAIN, WASTE, AND VENT) ISOMETRIC
NTS
3"
8"
3"
3"
3"
8"
3"
3"
2" EQUIP. DRAIN FROM
BACKFLOW PREVENTER
ED
4"
3" VENT STACK
WITH CLEANOUT
2"
3"
CO
3"
FD
8"
3"
6" SOFTENER
WASTE DRAIN
8"
CO
6" SOFTENER
WASTE DRAIN
FD
3"
WALL MOUNT ASSEMBLY
DUST COVERS
VALVE TRIGGER
H C
NTS
MOP SINK DETAIL
FINISHED
FLOOR DRAIN
MOP HANGER SPOUT BRACE
SPOUT WITH HOSE END
AND PAILHOOK
SERVICE FAUCET WITH
VACUUM BREAKER
3" DIA. P-TRAP
METAL EDGE
ASSE 1072 BARRIER-TYPE
TRAP SEAL PROTECTION
DEVICE
ASSE 1072 BARRIER-TYPE
TRAP SEAL PROTECTION
DEVICE
NTS
THERMOSTATIC MIXING VALVE DETAIL
ASSE 1069 THERMOSTATIC
MIXING VALVE
HOT WATER
INLET
COLD WATER
INLET
BALL VALVE BALL VALVE
TEMPERED WATER
OUTLET TO EMERGENCY
EYE/FACE WASH UNIT
TEMPERATURE
GAUGE
FD 6"
2"
8"
FD
8" 2"
NTS
SMALL ELECTRIC WATER HEATER DETAIL
SMALL ELECTRIC
WATER HEATER
ISOLATION VALVE
(TYP)
NOTE:
INSTALL UNITS ON A 4 INCH CONCRETE PAD WHEN
FLOOR MOUNTED OR METAL SHELF WHEN WALL
MOUNTED.
DRAIN VALVE
ROUTE T&P VALVE DISCHARGE TO
6 INCHES AFF OR TO FLOOR DRAIN
P&T RELIEF VALVE (SET BY
MANUFACTURER)
FULL SIZE OF VALVE OUTLET
DIELECTRIC
UNION (TYP)
COLD WATER
INLET
HOT WATER
OUTLET
MOUNT TOP + 42
INCHES
MS
DOMESTIC WATER ISOMETRIC
NTS
EMERGENCY EYE/FACE
WASH UNIT
8"
THERMOSTATC
MIXING
VALVE
3" FINISHED WATER
1"
CONNECT DOWNSTREAM
OF WATER METER
T&P VALVE
3/4" DISCHARGE
TO MOP SINK
ELECTRIC WATER
HEATER
1/ 2"
1/ 2"
3/ 4"
3/4"
1"
1/2"
WF
1/2"
1/ 2"
1/2"
3/4"
THERMAL
EXPANSION
TANK
3/4"
THERMAL
EXPANSION
TANK
FLOOR DRAIN EL. = 988.17
(TYP. OF 3)
KEYED HOSE BIBB
NTS
FREEZELESS HOSE BIBB DETAIL
DRAIN PORT
INTEGRAL
VACUUM
BREAKER
INLET
WALL CLAMP
DRAIN SPOUT
INTEGRAL
VACUUM
BREAKER
TEE KEY
CONNECTION
FREEZELESS
HOSE BIBB
ASSEMBLY FREEZELESS HOSE
BIBB ASSEMBLY
TEE KEY
CONNECTION
BUILDING WALL
FRONT VIEW
SIDE VIEW
EXIT BUILDING AT
INV. EL. = 986.50
Jones & Henry Engineers, Ltd.
Fluid thinking...
www.JHeng.com
R
Scott Goodsell Rectangle
Scott Goodsell
3" RAW WATER
FROM WELL
N aO
Cl
4" BACKWASH EFFLUENT
4" FILTERED WATER3" SOFTENED WATER
HYDROPNEUMATIC
TANK
3" FINISHED WATER
TO EXISTING
MECHANICAL ROOM
SOFTENER
BU
ILD
IN
G
FE-1
DRAIN
BFV-303A
BACKWASH
SUPPLY PUMP
BACKWASH
SUPPLY
TANK
SOFTENER
4" S
O
FT
EN
ER
IN
FL
U
EN
T
4" B
AC
KW
AS
H
IN
FL
U
EN
T
2" SOFTENER
BYPASS VALVE
BFV-319
3" BACKWASH
SUPPLY TANK FILL LINE
RAW WATER
SAMPLE TAP
4"x3"
REDUCER
FINISHED WATER
SAMPLE TAP
NPW TO BUILDING
3" BACKFLOW
PREVENTER
4"
FI
LT
ER
ED
W
AT
ER
4" RAW WATER
BU
ILD
IN
G
B-3
4" B
AC
KW
AS
H
E
FF
LU
EN
T
4" BACKWASH EFFLUENT
4" RAW WATER
STATIC MIXER
1-1/2" SOFTENER
BACKWASH WASTE
TO SANITARY
3" RAW WATER TO WASTE
BFV-201A
ARV
AIR
RELEASE
DIFFERENTIAL
PRESSURE
SWITCH
4" FILTERED WATER
BFV-217A
SAMPLE
BFV-012A
BFV-015A
4" BACKWASH INFLUENT
BFV-111A
BFV-013A
BFV-014A
DRAIN
BFV-201B
ARV
AIR
RELEASE
DIFFERENTIAL
PRESSURE
SWITCH
BFV-217B
SAMPLE
BFV-012B
BFV-015B
BFV-111B
BFV-013B
BFV-014B
DRAIN
BFV-201C
ARV
AIR
RELEASE
DIFFERENTIAL
PRESSURE
SWITCH
BFV-217C
SAMPLE
BFV-012C
BFV-015C
BFV-111C
BFV-013C
BFV-014C
4" BACKWASH EFFLUENT
4" FILTERED WATER
4" BACKWASH INFLUENT
3" R
AW
W
AT
ER
T O
W
AS
TE
FILTER A FILTER B FILTER C
4"x3"
REDUCER
B-2
B-1
ARV
4"x3"
REDUCER
ARV
ARV
BU
ILD
IN
G
P-1
BACKWASH SUPPLY EQUIPMENT
FURNISHED UNDER 46 61 21
ALL SOFTENER EQUIPMENT
FURNISHED UNDER 46 61 22
ALL FILTER EQUIPMENT
FURNISHED UNDER 46 61 21
FKV-126B
FKV-126A
SLV-149B
SLV-149A
3" TEE WITH FITTING FOR
PRESSURE TRANSDUCER
CONNECTION
4" S
O
FT
EN
ER
IN
FL
U
EN
T
BY CONTRACTORBY OTHERS
REGENERATION/BACKWASH PROVIDED
FROM SOFTENED WATER EFFLUENT OF
ADJACENT TANK. MFR TO PROVIDE PIPING
AND ACCESSORIES.
Jones & Henry Engineers, Ltd.
Fluid thinking...
www.JHeng.com
R
Scott Goodsell Rectangle
Scott Goodsell
FDFD
Xref X:\Drawings-Eng\3D Solids Library\P-CONTROL_G_LIGHT.dwg
Xref X:\Drawings-Eng\3D Solids Library\P-CONTROL_G_LIGHT.dwg
HVAC GENERAL NOTES
1. PROVIDE ALL MATERIAL, EQUIPMENT, AND PERFORM ALL LABOR REQUIRED TO INSTALL COMPLETE AND OPERABLE HVAC SYSTEMS AS INDICATED ON THE DRAWINGS, AS SPECIFIED, AND AS REQUIRED BY CODE.
2. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS IN THE FIELD AND SHALL REPORT DISCREPANCIES, IF ANY, TO THE ENGINEER FOR CLARIFICATION PRIOR TO STARTING ANY WORK.
3. EXACT LOCATION OF ALL EQUIPMENT AND ACCESSORIES SHALL BE VERIFIED IN THE FIELD. EQUIPMENT SIZES AND LOCATIONS ARE APPROXIMATE. ACTUAL DIMENSIONS TO BE DETERMINED BY EQUIPMENT FURNISHED.
4. INSTALL ALL HVAC EQUIPMENT AND APPURTENANCES IN ACCORDANCE WITH MANUFACTURER'S
RECOMMENDATIONS, CONTRACT DOCUMENTS, AND APPLICABLE CODES AND REGULATIONS.
5. THE CONTRACTOR SHALL PERFORM ALL CUTTING, CORE DRILLING, CHIPPING, AND PATCHWORK AS
REQUIRED.
6. ALL SURFACES DAMAGED IN THE COURSE OF THE WORK SHALL BE RESTORED TO THE ORIGINAL CONDITION AND IN ACCORDANCE TO DRAWINGS AND SPECIFICATIONS. LOCATIONS AND SIZES OF ALL FLOOR, WALL, AND ROOF OPENINGS SHALL BE COORDINATED WITH THE OTHER TRADES.
7. ALL OPENINGS IN FIRE WALLS DUE TO DUCTWORK, PIPING, CONDUITS, ETC., SHALL BE FIRE STOPPED WITH A
PRODUCT SIMILAR TO 3M OR EQUAL.
8. ALL MATERIALS SHALL BE AS PER THE DRAWINGS AND SPECIFICATIONS AND SHALL BE APPROVED BY THE
ENGINEER PRIOR TO ITS INSTALLATION.
9. ALL WORK SHALL BE COORDINATED WITH OTHER TRADES DURING INSTALLATION.
10. EQUIPMENT SIZES AND LOCATIONS ARE APPROXIMATE. ACTUAL DIMENSIONS TO BE DETERMINED BY
EQUIPMENT FURNISHED.
11. CONCRETE HOUSEKEEPING PADS TO SUIT HVAC EQUIPMENT SHALL BE SIZED AND LOCATED BY THE HVAC
CONTRACTOR. PADS SHALL BE FURNISHED AND INSTALLED BY THE GENERAL CONTRACTOR. COORDINATE FINAL EQUIPMENT SIZE AND LOCATION OF HOUSEKEEPING PADS WITH THE GENERAL CONTRACTOR.
MINIMUM CONCRETE PAD THICKNESS SHALL BE 6 INCHES. PAD SHALL EXTEND BEYOND THE EQUIPMENT A
MINIMUM OF 6 INCHES ON EACH SIDE.
12. COORDINATE ALL EQUIPMENT CONNECTIONS WITH MANUFACTURERS' CERTIFIED DRAWINGS. COORDINATE AND PROVIDE ALL DUCT AND PIPING TRANSITIONS REQUIRED FOR FINAL EQUIPMENT CONNECTIONS FURNISHED EQUIPMENT. FIELD VERIFY AND COORDINATE ALL DUCT AND PIPING DIMENSIONS BEFORE
FABRICATION.
13. PROVIDE VIBRATION ISOLATION FOR ALL HVAC EQUIPMENT TO PREVENT TRANSMISSION OF VIBRATION TO
BUILDING STRUCTURE.
14. WHERE TWO OR MORE ITEMS OF THE SAME TYPE OF EQUIPMENT ARE REQUIRED, THE PRODUCT OF ONE
MANUFACTURER SHALL BE USED.
15. ALL AIR CONDITIONING CONDENSATE DRAIN PIPING FROM EQUIPMENT SHALL BE PIPED FULL SIZE OF THE
UNIT DRAIN OUTLET SLOPED 1/8 INCH PER FOOT.
16. FOR INTERLOCKING WIRING SCHEMATICS SEE ELECTRICAL DRAWINGS.
17. ALL CONTROL WIRING AND CONDUIT SHALL COMPLY WITH THE NATIONAL ELECTRIC CODE AND DIVISION 16
OF THE SPECIFICATIONS.
18. THERMOSTATS AND OTHER CONTROL COMPONENTS SHALL BE MOUNTED 5'-0" A.F.F. UNLESS OTHERWISE
NOTED.
19. ALL TESTS SHALL BE COMPLETED BEFORE ANY HVAC EQUIPMENT OR PIPING INSULATION IS APPLIED.
HVAC ABBREVIATIONS
EF - EXHAUST FAN
EUH - ELECTRIC UNIT HEATER
L - LOUVER
T - THERMOSTAT
ELECTRIC UNIT HEATER SCHEDULE
TAG
EUH-1 WELL & FILTRATION BUILDING
LOCATION
HORIZONTAL
OUTPUT CAPACITY
(KW)
15.0 1330 32 45
HP
1/15
ELECTRICAL
(V/PH/HZ)
208/3/60 CHROMALOX
MAKE MODEL
HD3D-1500
NOTES
1, 2, 3, 4, 5
TAG
EF-1 WELL & FILTRATION BUILDING
LOCATION AIRFLOW
(CFM)
E.S.P.
(IN W.C.)
0.25 BELT
DRIVE
ELECTRICAL
HP
1/3
(V/PH/HZ)
208/1/60
MAKE
LOREN COOK
MODEL
120W4B
NOTES
1, 2, 3, 4, 5, 6
NOTES:
1. INSTALL PER MANUFACTURERS INSTRUCTIONS.
2. PROVIDE NEMA 4X, HOSEDOWN TYPE, STAINLESS STEEL CONSTRUCTION UNIT WITH UL LISTED DISCONNECT
SWITCH NEMA 4X RATED.
3. PROVIDE WALL MOUNT, TYPE 304 STAINLESS STEEL, SWIVEL BRACKET FOR UNIT MOUNTING.
4. PROVIDE 120 VOLT, SINGLE STAGE, WALL MOUNTED THERMOSTAT, NEMA 4X, CHROMALOX TYPE
WCRT-100.
5. USE MANUFACTURER/MODEL SHOWN OR APPROVED EQUAL. (SEE SPECIFICATIONS FOR APPROVED
MANUFACTURER ALTERNATIVES.)
NOTES:
1. PROVIDE INTEGRAL PRE-WIRED NEMA 4X RATED DISCONNECT SWITCH.
2. PROVIDE WITH SQUARE GRAVITY BACKDRAFT DAMPER SQUARE WALL GRILLE.
3. PROVIDE WITH EPOXY UV FINISH.
4. PROVIDE WITH ALUMINUM BIRDSCREEN.
5. PROVIDE SPARE BELT SET.
6. USE MANUFACTURER/MODEL SHOWN OR APPROVED EQUAL. (SEE SPECIFICATIONS FOR
APPROVED MANUFACTURER ALTERNATIVES.)
AIRFLOW
DISCHARGE
AIRFLOW
(CFM)
TEMP. RISE
(DEGREE F)
THROW
(FT)
EUH-2 WELL & FILTRATION BUILDING HORIZONTAL 15.0 1330 32 45 1/15 208/3/60 CHROMALOX HD3D-1500 1, 2, 3, 4, 5
FAN SCHEDULE
CENTRIFUGAL WALL MOUNT
TYPE
ELECTRIC UNIT HEATER DETAIL
UNIT HEATER SHALL BE
SECURED TO WALL WITH
WALL MOUNT SWIVEL
BRACKET
ELECTRIC
UNIT HEATERMOTOR HOUSING
ADJUSTABLE
BLADES
WALL MOUNT
SWIVEL BRACKET
NTS
GRAVITY TYPE
BACKDRAFT DAMPER
WALL GRILLE
BUILDING WALL
CENTRIFUGAL WALL
EXHAUST FAN
ATTACH TO WALL PER
MANUFACTURERS
INSTRUCTIONS
CENTRIFUGAL WALL EXHAUST FAN DETAIL
TAG
L-1 INTAKE
SERVICE TYPE
STATIONARY 24"x32" 1500
FREE AREA
(SQ. FT.)
3.89 RUSKIN
MAKE MODEL
ELf6375DXH
NOTES
1, 2, 3, 4, 5, 6
NOTES:
1. 6 INCH DEEP, FIXED DRAINABLE BLADE, 6063T5 EXTRUDED ALUMINUM CONSTRUCTION.
2. KYNAR OR FLUOROPOLYMER FINISH ON ENTIRE LOUVER AND BIRDSCREEN. COLOR TO BE
SELECTED BY OWNER.
3. BIRDSCREEN MOUNTED ON INTERIOR.
4. PROVIDE WITH 6 INCH DEEP, INSULATED BLADE, RUSKIN MODEL TED50TX, 24" x32"
MOTORIZED BACKDRAFT DAMPER, 6063T6 ALUMINUM CONSTRUCTION.
5. TWO POSITION, SPRING RETURN, NEMA 4X RATED, 120/1/60 MOTOR ACTUATOR.
6. USE MANUFACTURER/MODEL SHOWN OR APPROVED EQUAL. (SEE SPECIFICATIONS FOR
APPROVED MANUFACTURER ALTERNATIVES.)
SIZE
(IN.)
AIRFLOW
(CFM)
WELL & FILTRATION BUILDING
LOCATION
WELL & FILTRATION BUILDING
EUH-1
EUH-1
70° F
EF-1
85° F TT
VENTILATION (EF-1/L-1 & L-2) SEQUENCE OF OPERATION:
VENTILATION FOR THE WELL AND FILTRATION BUILDING SHALL BE PROVIDED BY EXHAUST FAN EF-1 AND INTAKE LOUVERS L-1 WITH MOTORIZED BACKDRAFT DAMPER. EF-1 SHALL BE CONTROLLED BY A HAND-OFF-AUTO SWITCH. IN THE HAND POSITION, THE EXHAUST FAN MOTOR IS ACTIVATED. IN THE AUTO POSITION, A SINGLE TEMPERATURE WALL MOUNTED THERMOSTAT OR HUMIDISTAT SHALL CYCLE THE FAN MOTOR. L-1 AND MOTORIZED BACKDRAFT DAMPER SHALL PROVIDE MAKE-UP AIR FOR EF-1. THE MOTORIZED BACKDRAFT DAMPER SHALL BE ACTIVATED OPEN WHENEVER THE EXHAUST FAN MOTOR IS ACTIVATED. WHENEVER THE EXHAUST FAN MOTOR IS DEACTIVATED, THE MOTORIZED BACKDRAFT DAMPER
SHALL BE DEACTIVATED AND GO TO THE CLOSED POSITION.
HEATING (EUH-1 & EUH-2) SEQUENCE OF OPERATION:
SINGLE TEMPERATURE, WALL MOUNTED THERMOSTAT MAINTAINS SPACE TEMPERATURE BY CYCLING UNIT HEATNG
ELEMENTS AND FAN SIMULTANEOUSLY.
WELL & FILTRATION BUILDING AIRFLOW AND
CONTROL SCHEMATIC
L-1
1500 CFM
MD
EF-1
CFM
EUH-2
EUH-2
70° FT
HVAC PLAN
Scale: 1/4" = 1'-0"
EUH-1 MOUNT
BOTTOM 8'-0" AFF
L-1 MOUNT TOP
7'-4" AFF
EUH-2 MOUNT
BOTTOM 8'-0" AFF
EF-1 MOUNT TOP
OF WALL OPENING
9'-4" AFF GRAVITY
BACKDRAFT
DAMPER
SQUARE
WALL
GRILLE
T
T
T
EUH-1 T-STAT
EUH-2
T-STAT
EF-1
T-STAT
LOUVER SCHEDULE
EF-1
60% RH H
CAULK
CAULK
EXTENDED SILL NOTES:
1. LOUVER TO BE ASSEMBLED AT LOUVER
MANUFACTURER FACTORY.
2. CLIP ANGLES AND EXTENDED SILL TO BE
PROVIDED BY LOUVER MANUFACTURER.
3. INSTALLATION OF LOUVER TO BE IN
ACCORDANCE WITH LOUVER
MANUFACTURER'S RECOMMENDATIONS.
NTS
TYPICAL LOUVER/DAMPER DETAIL
CLIP ANGLE CLIP ANGLE (TYP.)
RUBBER GASKET (TYP.)
MOTORIZED BACKDRAFT
DAMPERSTATIONARY
LOUVER
BIRD
SCREEN
DUCTWORK
BUILDING
WALL/STRUCTURE
Jones & Henry Engineers, Ltd.
Fluid thinking...
www.JHeng.com
R
Scott Goodsell Rectangle
Scott Goodsell
| COLDWATER P301 |
| COLDWATER P501 |
| COLDWATER P502 |
| COLDWATER P601 |