COLDWATER DWGS VOL 4of5 - ELEC PT 1.pdf
PDF 4 MB Posted
- Solicitation number
- RFQ 171 200000000290 4
- Issued by
- Barry County, Michigan
About this file
This is an electrical construction drawing set for a cold water treatment building project, specifically Volume 4 of 5 covering electrical Part 1. The document provides comprehensive electrical design specifications and installation requirements for a new treatment facility, including detailed single-line diagrams, electrical site plans, grounding plans, lighting plans, and panel schedules. The drawings specify equipment installations such as a 250-ampere main panel (Panel-D), flow totalizer with remote display, OmniSite station monitor, lighting fixtures, disconnects, and various control systems. The project involves coordination between multiple systems including backwash control, water softener operations, well pump controllers, and emergency lighting provisions. All electrical work must comply with NEC Article 250 requirements for grounding, and specific conduit sleeve types are mandated for penetrations through concrete walls and floors based on classified versus non-classified area designations.
The drawings establish detailed technical specifications for electrical installation, including conductor sizes (such as #4/0 AWG bare stranded copper for grounding conductors and 250 MCM copper feeders), equipment ratings (480Y/277V at 12470 volts with 1000 kVA capacity), and specific product requirements including Holophane LED fixtures, Nicor emergency lighting, Cooper X-Switch controls, and Siemens S4 panelboards. Multiple notes clarify contractor responsibilities for furnishing and installing specified equipment, coordinating with equipment vendors and suppliers (such as well pump and door suppliers), and extending existing circuit wiring to new panels. The project requires adherence to fire resistance requirements, bonding of roof elements for electrical continuity, and installation of copper-clad steel core ground rods as necessary to meet NEC ohmic requirements, with all exothermic connections for grounding rings and building pad rebar (UFER) grounds.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
E
E
E
E
S
A
S
A
NEW
TREATMENT
BUILDING
2"COLD WATER
S
A
S
A
S
A
S
A
S
A
C
W
C
W
C
W
C
W
C
W
EXISTING MDP IN ELEC.
ROOM 106
FLOW TOTALIZER
REMOTE DISPLAY
PANEL-D 208/120V
AND OMNISITE STATION
MONITIOR
ELECTRICAL SITE PLAN
SCALE 1" = 20'
SCHEMATIC LEGEND
OL
MOTOR STARTER OVERLOAD RELAY N.C.
CONTACT
CONTROL RELAY COIL
CR - INSTANTANEOUS CONTROL RELAY
TR - TIME DELAY RELAY
CONTACTOR COIL
M - MOTOR STARTER CONTACTOR
MF - MOTOR STARTER FORWARD CONTACTOR
MR - MOTOR STARTER REVERSE CONTACTOR
ML - MOTOR STARTER LOW SPEED CONTACTOR
MH - MOTOR STARTER HIGH SPEED CONTACTOR
SC - MOTOR STARTER STARTING CONTACTOR
RC - MOTOR STARTER RUN CONTACTOR
BP - BYPASS CONTACTOR
CC - CAPACITOR CONTACTOR
LC - LIGHTING CONTACTOR
IC - ISOLATION CONTACTOR
C - GENERAL CONTACTOR
INDICATES ITEMS IN A SEPARATE
COMMON ENCLOSURE
3 - POSITION, MAINTAINED ACTION
SELECTOR SWITCH
H - O - A: HAND-OFF-AUTOMATIC
L - O - R: LOCAL-OFF-REMOTE
PCS: PLANT CONTROL SYSTEM
PLC: PROGRAMMABLE LOGIC CONTROLLER
LIQUID LEVEL SWITCH CLOSES ON
RISING LEVEL
H A
XOO
XR
XY
OOX
LIQUID LEVEL SWITCH OPENS
ON RISING LEVEL
SINGLE-LINE DIAGRAM LEGEND
40A
30A
FRS-R -30
30A
480Y/277V
12470
1000KVA
GROUND CONNECTION
FUSED DISCONNECT SWITCH.
(SWITCH SIZE, FUSE TYPE AND FUSE SIZE AS
SHOWN)
UNFUSED DISCONNECT SWITCH
(SWITCH SIZE AS SHOWN)
THERMAL-MAGNETIC CIRCUIT BREAKER OR MOTOR
CIRCUIT PROTECTOR-MCP
(TRIP SIZE AS SHOWN)
THREE PHASE AC MOTOR
(HORSEPOWER AS SHOWN)
VARIABLE FREQUENCY DRIVE WITH A BY-PASS OPTION (SHOWN WITH
INTEGRAL EXTERNAL DISCONNECT HANDLE)
LIGHTING OR POWER TRANSFORMER,THREE PHASE
UNLESS NOTED OTHERWISE (CONNECTION, SIZE &
RATING AS SHOWN)
SINGLE PHASE AC MOTOR
(HORSEPOWER AS SHOWN)
VFD BP
ELECTRICAL PLAN LEGEND
DENSITY TRANSMITTER
LOAD CELL
GROUND ROD WITH CADWELD CONNECTION
TRANSMITTER SENSING ELEMENT - LEVEL, FLOW, DENSITY, PRESSURE, ANALYSIS
TEMPERATURE TRANSMITTER
PRESSURE TRANSMITTER
LEVEL TRANSMITTER
FLOW TRANSMITTER
BOX - JUNCTION, TERMINAL, PULL OR HAND HOLE
LIMIT (POSITION) SWITCH
PRESSURE SWITCH
TEMPERATURE SWITCH (I.E. MOTOR THERMO PROTECTOR)
SPEED SWITCH
CONVEYOR CABLE SWITCH
SOLENOID
ANALYSIS TRANSMITTER (I.E. OXYGEN, TURBIDITY)
INDICATOR - PRESSURE, FLOW, LEVEL, DENSITY, ANALYSIS
THERMOSTAT
LEVEL SWITCH
FLOW SWITCH
MOISTURE SWITCH
VIBRATION SWITCH
HEATER IN MOTOR
TORQUE SWITCH
GAS DETECTOR WITH CONTROL PANEL (GAS TYPE AS SHOWN)
PHOTOELECTRIC CELL
THERMOCOUPLE
PNEUMATIC VALVE OPERATOR
CURRENT TO PRESSURE TRANSDUCER
THREE-WAY TOGGLE SWITCH
DISCONNECT SWITCH (SEE SINGLE LINE DIAGRAM FOR SIZE & TYPE)
LIGHTING PANEL 120/208V OR 120/240V
DISTRIBUTION PANEL 480V OR 480Y/277V
EMERGENCY LIGHTING FIXTURE, (2-HEAD SHOWN)
DUPLEX RECEPTACLE
CONDUIT EXPOSED
CONDUIT CONCEALED
CONDUIT IN CONCRETE DUCT BANK
DIRECT BURIAL CABLE
DOUBLE POLE TOGGLE SWITCH
SINGLE POLE TOGGLE SWITCH
CONDUIT TURNS DOWN
CONDUIT TURNS UP
HOMERUN
CONDUIT TEE
CADWELD CONNECTION
SINGLE RECEPTACLE
CAPPED CONDUIT (FUTURE USE)
JB
FT
LT
PT
TT
AT
PI
DT
ZS
PS
TS
CS
SS
FS
LS
NS
OS
VS
LE
S
T
H
PC
G
T
V
G GROUND WIRE
E 1
LC
MOTOR STARTER ABBREVIATIONS
FVNR - FULL VOLTAGE, NON-REVERSING
FVR - FULL VOLTAGE REVERSING
TS1W - TWO SPEED, ONE WINDING
TS2W - TWO SPEED, TWO WINDING
TSR1W - TWO SPEED REVERSING, ONE WINDING TSR2W - TWO
SPEED REVERSING, TWO WINDING
GENERAL ELECTRICAL ABBREVIATIONS
PVC - POLYVINYL CHLORIDE
RGS - RIGID GALVANIZED STEEL
PVC/RGS - PVC COATED RGS
8. FOR BELOW GRADE CONDUIT PENETRATIONS THROUGH EXISTING
EXTERIOR CONCRETE WALLS, PROVIDE TYPE A CONDUIT SLEEVE
FOR PVC CONDUIT. FOR RGS OR PVC-COATED RGS CONDUIT,
PROVIDE TYPE B CONDUIT SLEEVE THROUGH CONCRETE WALLS,
AND TYPE C CONDUIT SLEEVE THROUGH EXISTING CONCRETE
WALLS.
9. FOR ABOVE GRADE CONDUIT PENETRATIONS THROUGH EXTERIOR
CONCRETE WALLS, PROVIDE TYPE C CONDUIT SLEEVE. FOR
MASONRY WALLS PROVIDE TYPE F CONDUIT SLEEVE.
10. FOR CONDUIT PENETRATIONS THROUGH EXISTING CONCRETE
FLOORS AND WALLS BETWEEN ADJACENT NON-CLASSIFIED
(NON-HAZARDOUS) AREAS, PROVIDE TYPE C CONDUIT SLEEVES
FOR ALL CONDUIT TYPES. FOR SIMILAR PENETRATIONS THROUGH
CONCRETE FLOORS AND WALLS, PROVIDE TYPE D CONDUIT
SLEEVES FOR ALL CONDUIT TYPES.
11. FOR CONDUIT PENETRATIONS THROUGH CONCRETE FLOORS AND
WALLS SEPARATING CLASSIFIED (HAZARDOUS) AREAS FROM
NON-CLASSIFIED (NON-HAZARDOUS) AREAS, PROVIDE TYPE G
CONDUIT SLEEVES. FOR SIMILAR PENETRATIONS THROUGH
MASONRY WALLS, PROVIDE TYPE H CONDUIT SLEEVE. FOLLOW
MECHANICAL SEAL MANUFACTURER'S RECOMMENDATIONS TO
MEET 3-HOUR FIRE RESISTANCE REQUIREMENTS.
12. LEGENDS ARE FOR REFERENCE ONLY AND DOES NOT MEAN THAT
ALL ITEMS ARE USED.
ELECTRICAL NOTES
1. STRUCTURAL MATERIALS ARE NOT SHOWN ON ELECTRICAL DRAWINGS.
REFER TO ARCHITECTURAL AND STRUCTURAL DRAWINGS.
2. ALL ELECTRICAL EQUIPMENT ELEVATIONS SHOWN ARE TO BOTTOM OF
DEVICE OR PANEL, UNLESS OTHERWISE NOTED.
3. NUMBER SHOWN (I.E.11735), INDICATES A SPECIFICATION REFERENCE FOR
ITEMS OTHER THAN DIVISION 16. THE ELECTRICAL ITEM UNDER THIS
REFERENCE IS SUPPLIED BY ANOTHER PART OF THE CONTRACT. UNLESS
OTHERWISE NOTED IN THAT SPECIFICATION, THE CONTRACTOR SHALL
INSTALL AND WIRE THE ITEM PER THE DRAWINGS AND DIVISION 16
SPECIFICATIONS.
4. CONTROL WIRING SHALL CONFORM TO ALL REQUIREMENTS AS SHOWN
ON THE P & ID DRAWINGS WHETHER SHOWN ON THE ELECTRICAL
DRAWINGS OR NOT.
5. WHERE LINES ARE SHOWN CONNECTING ELECTRICAL EQUIPMENT, THEY
ARE NOT INTENDED AS CONDUIT ROUTING. CONTRACTOR SHALL ROUTE
ALL CONDUIT RUNS (SHOWN OR NOT) PER DIVISION 16 SPECIFICATIONS.
6. WP INDICATES WATERPROOF. LETTER ON OR NEXT TO LIGHT FIXTURE
INDICATES TYPE, PER SECTION 16510. NUMBER WITH LIGHT FIXTURE OR
RECEPTACLE INDICATES CIRCUIT NUMBER.
7. GFCI INDICATES A CIRCUIT BREAKER OR RECEPTACLE WITH A 6 MA
GROUND FAULT CIRCUIT INTERRUPTER. GFEPD INDICATES A CIRCUIT
BREAKER OR RECEPTACLE WITH A 30 MA GROUND FAULT EQUIPMENT
PROTECTION DEVICE.
Jones & Henry Engineers, Ltd.
Fluid thinking...
www.JHeng.com
R
Scott Goodsell Rectangle
Scott Goodsell Typewritten Text
GROUNDING PLAN
Scale: 1/4" = 1'-0"NOTES:
1. ALL GROUNDING CONNECTIONS OF NEW AND EXISTING
GROUNDING RINGS, NEW BUILDING PAD REBAR (UFER)
AND METAL ROOF SHALL BE EXOTHERMIC.
2. APPLY BONDING JUMPERS TO ROOF AS NEEDED FOR
ELECTRICAL CONTINUITY.
3. INSTALL NEW GROUNDING RING AT SAME DEPTH AND
DISTANCE FROM WALL AS EXISTING.
4. ALL GROUND RODS SHALL BE COPPER-CLAD STEEL CORE.
NUMBER OF GROUND RODS SHOWN IS AN
APPROXIMATION. CONTRACTOR SHALL FURNISH AND
INSTALL GROUND RODS AS NECESSARY TO MEET NEC
ARTICLE 250 OHMIC REQUIREMENTS.
5. ALL GROUNDING CONDUCTORS SHALL BE #4/0 AWG
BARE STRANDED COPPER.
TO METAL ROOF
TO METAL ROOF
UFER GROUND
(TYP. OF 2)
EXISTING GROUND RING
EXISTING GROUND RING
COPPER-CLAD STEEL
CORE GROUND ROD
(TYP. - SEE NOTE 4)
SE
E
N O
TE
(TY
P.
FDFD
4"x2" GROUND BAR
Jones & Henry Engineers, Ltd.
Fluid thinking...
www.JHeng.com
R
Scott Goodsell Rectangle
Scott Goodsell
ELECTRICAL PLAN
Scale: 1/4" = 1'-0"
LIGHTING PLAN
Scale: 1/4" = 1'-0"
EUH-1 DISCONNECT
(NON-FUSED)
SEE NOTE 2
BACKWASH CONTROL
PANEL AND DISCONNECT
(NON-FUSED)
SEE NOTES 1, 3
EYEWASH WATER HEATER
DISCONNECT (NON-FUSED)
EF-1 DISCONNECT
SEE NOTE 2
WELL PUMP CONTROLLER FURNISHED
BY WELL PUMP SUPPLIER. SEE NOTE 3
ROLL UP DOOR DISCONNECT
(NON-FUSED)
(ABOVE)
ZS1 DOOR STRIKE FLOAT SWITCH
LS-1 (BELOW) SEE NOTE 5
OMNISITE STATION
MONITOR
PANEL-E
208/120V 3PH 4W
NOTES:
1. CONTRACTOR TO FURNISH AND INSTALL THIS ITEM AND ITS UNISTRUT FRAME FOR FLOOR
MOUNTING.
2. DISCONNECT SWITCH FURNISHED AND INSTALLED BY VENDOR.
3. SEE RISER DIAGRAM, DRAWING E603.
4. DOOR SUPPLIER TO PROVIDE ACCESS CONTROLLER ELECTRIC STRIKE. COORDINATE WIRING
WITH DOOR SUPPLIER. ELECTRIC STRIKE IS TO BE ACTIVATED BY THE FLOAT SWITCH OR THE
ACCESS CONTROLLER.
5. REMOVE EXISTING PANEL BREAKERS, BUS WORK AND FEEDER FROM PANEL MOP IN
WELCOME CENTER ELECTRIC ROOM. INSTALL TERMINALS IN EXISTING PANEL ENCLOSURE
AND CONNECT TO EXISTING CIRCUIT BRANCH WIRING. EXTEND CIRCUIT WIRING TO NEW
PANEL 'D'.
MANUAL ON/OFF LIGHT
SWITCH: COOPER X-SWITCH
CAT. NO. AH7810XC000
TO PANEL-E
CKT. 1
T/FIXTURE @ 12'-0" AFF
(TYP.)
SOFTENER PANEL
SEE NOTE 3
SOFTENER DISCONNECT
SEE NOTE 1
EUH-2 DISCONNECT (NON-FUSED)
SEE NOTE 2
EF-1 H-O-A
SEE NOTE 1
LIGHT FIXTURE SCHEDULE
TYPE DESCRIPTION
L1 LED INTERIOR HEAVY INDUSTRIAL, ENCLOSED AND GASKETED STRIP FIXTURE
HOLOPHANE CAT. NO. EMX-L48-6000LM-FGCL-WD-MVOLT-40K-80CRI-CR-DWHXD
48"Lx5.1"Wx4.6"H, 6248 LUMENS, 39.5 WATTS, FLAT CLEAR GLASS LENS, NON-DIMMING, 80CRI, CORROSION RESISTANT WHITE FINISH, 120-277V 50/60Hz
SWITCH
E1
E2
E3
MANUAL ON/OFF MOTOR CONTROL SWITCH, NEMA 4x, 30A, 600V COOPER X-SWITCH CAT. NO AH7810XC00 5"Wx6"Hx3.56"D
REMOTE SINGLE LED LIGHT
NICOR MWOS-REMOTE
LED EMERGENCY LIGHT FOR INDOOR/OUTDOOR USE
NICOR CAT. NO. EML6-1-UNV-WH
120/277VAC, 2.4W, 90-MINUTE NiCAD BATTERY, ABS CORROSION RESISTANT WHITE ENCLOSURE
LED COMBO EXIT SIGN AND EMERGENCY LIGHT
NICOR CAT. NO. ECL1-10-UNV-WH-R-2-R
120/277VAC, 2.9W, 90-MINUTE NiCAD BATTERY, RED LETTERS, ABS CORROSION RESISTANT
WHITE ENCLOSURE FOR USE WITH ONE REMOTE HEAD
DOOR STRIKE AND ACCESS
CONTROLLER FURNISHED
BY DOOR SUPPLIER
PT-1
SEE NOTE 3
PIT-302
LSL-317
LSH-316
BFV-319
NOTE 3
METERING PUMPS
(CFP-131) NOTE 3
FINSHED WATER FLOW METER,
FE-1, MOUNTED IN PIPING AT
12'-0" AFF
M
FILTER SKID
SOFTENER SKIDBRINE TANK
BLADDER
TANK
BACKWASH
SUPPLY PUMP
BACKWASH
HOLDING TANK
L2 OUTDOOR SOFFIT LED FIXTURE WITH MOTION SENSOR
DEKOR TYPE SPOT LIGHT WITH 20° - 30° BEAM ANGLE,
33 LUMEN, TRANSFORMER
BACKWASH
SUPPLY PUMP
MAIN CONTROL
PANEL (MCP-291)
AND DISCONNECT.
SEE NOTE 3
FILTER SKID
SOFTENER SKID
JB-292
JUNCTION BOX
SEE NOTE 3
L-1
MOTORIZED LOUVER
EF-1
NOTE 3
POSITION SWITCH
REMOTE FLOW TRANSMITTER FT-1
DEDICATED COMPRESSOR
RECEPTICALE
EXISTING HEATER
(TYP. 2)
EXISTING RECEPTACLE
(TYP. 4)
ROLL UP DOOR
DISCONNECT
(NON-FUSED)
SEE NOTE 5
(TYP. OF 6)
Jones & Henry Engineers, Ltd.
Fluid thinking...
www.JHeng.com
R
Scott Goodsell Rectangle
Scott Goodsell
PANEL-D SCHEDULE
MDP (EXISTING)
ELECTRICAL ROOM
208/120V 3PH 4W
SIEMENS S4
MAIN BUS
600A 3P
250A 208V 3P
(4) 250 MCM CU + 4 AWG GND
2-1/2" C
PANEL-D
208/120V 3PH 4W
250A MAIN LUGS ONLY
ONE LINE DIAGRAM
Jones & Henry Engineers, Ltd.
Fluid thinking...
www.JHeng.com
R
Scott Goodsell Rectangle
Scott Goodsell
20A
PANEL-B (EXISTING)
208/120V 3PH 4W
ELECTRIC ROOM 106
(2) 12 AWG CU + 12 AWG GND
1 (+)
2 (-)
6 (mA+)
4 (COM)
2/C 16 AWG TSP
1/2" C
PRECISION DIGITAL PD2-6200
FLOW TOTALIZER
REMOTE DISPLAY
MAIN/MECH ROOM 108
27 (-)
26 (+)+
6 (S1) BROWN
5 (E1) BROWN
7 (E2) WHITE
8 (S2) WHITE
4 (GND) GREEN
5 (E1)BROWN
7 (E2)WHITE
4 (GND)GREEN
37 (E) YELLOW
37 (E)YELLOW
36 (S) YELLOW
GND
GND
1 (L+/L)
2 (L-/N)
FIT/FE
PROLINE PROMAG W 400
WALL MOUNTED
REMOTE VERSION
FLOW METER TRANSMITTER
PROLINE PROMAG W 400
FLOW METER SENSOR
HOUSING
ELECTRODE CABLE
SUPPLIED BY VENDOR
COIL CURRENT CABLE
SUPPLIED BY VENDOR
(2) 12 AWG CU + 12 AWG GND
3/4" C
20A
PANEL-E
208/120V 3PH 4W
FLOW METER DIAGRAM
G N
G
L
20A PANEL-E
208/120V 3PH 4W
COAXIAL CABLE
OMNISITE OUTDOOR PHANTOM
ANTENNA BRACKET KIT W/ COAX
CABLE (S-CBL-CX-ABRK10)
OMNISITE CRYSTAL
BALL MONITOR
MONITOR INPUTS:
WELL PUMP RUNNING
BACKWASH PUMP RUNNING
FLOW METER (PULSE TOTALIZING)
ALARM INPUTS:
FLOOR FLOAT SWITCH
DOOR OPEN
BACKWASH HIGH DIFFERENTIAL PRESSURE
FILTER HIGH DIFFERENTIAL PRESSURE
FILTER CONTROL PANEL SYSTEM ALARM
FILTER (RESERVED - TBD)
SOFTENER HIGH DIFFERENTIAL PRESSURE
SOFTENER CONTROL PANEL SYSTEM ALARM
SOFTENER (RESERVED - TBD)
WELL PUMP FAIL
MONITOR PANEL DIAGRAM
(2) 12 AWG CU + 12 AWG GND
3/4" C
Jones & Henry Engineers, Ltd.
Fluid thinking...
www.JHeng.com
R
Scott Goodsell Rectangle
Scott Goodsell
| COLDWATER M101 |
| Electrical |
| COLDWATER E001 |
| COLDWATER E101 |
| COLDWATER E102 |
| COLDWATER E601 |
| COLDWATER E602 |
| COLDWATER E603 |
| COLDWATER E604 |
| COLDWATER E605 |
File details come from the government source that posted it. Updated .