COLDWATER DWGS VOL 4of5 - ELEC PT 1.pdf

PDF 4 MB Posted

Attached to
591/19213. CDP; Coldwater WC - Ctr Well & Filtration Sys Rplc
Solicitation number
RFQ 171 200000000290 4
Issued by
Barry County, Michigan

About this file

This is an electrical construction drawing set for a cold water treatment building project, specifically Volume 4 of 5 covering electrical Part 1. The document provides comprehensive electrical design specifications and installation requirements for a new treatment facility, including detailed single-line diagrams, electrical site plans, grounding plans, lighting plans, and panel schedules. The drawings specify equipment installations such as a 250-ampere main panel (Panel-D), flow totalizer with remote display, OmniSite station monitor, lighting fixtures, disconnects, and various control systems. The project involves coordination between multiple systems including backwash control, water softener operations, well pump controllers, and emergency lighting provisions. All electrical work must comply with NEC Article 250 requirements for grounding, and specific conduit sleeve types are mandated for penetrations through concrete walls and floors based on classified versus non-classified area designations.

The drawings establish detailed technical specifications for electrical installation, including conductor sizes (such as #4/0 AWG bare stranded copper for grounding conductors and 250 MCM copper feeders), equipment ratings (480Y/277V at 12470 volts with 1000 kVA capacity), and specific product requirements including Holophane LED fixtures, Nicor emergency lighting, Cooper X-Switch controls, and Siemens S4 panelboards. Multiple notes clarify contractor responsibilities for furnishing and installing specified equipment, coordinating with equipment vendors and suppliers (such as well pump and door suppliers), and extending existing circuit wiring to new panels. The project requires adherence to fire resistance requirements, bonding of roof elements for electrical continuity, and installation of copper-clad steel core ground rods as necessary to meet NEC ohmic requirements, with all exothermic connections for grounding rings and building pad rebar (UFER) grounds.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

E

E

E

E

S

A

S

A

NEW

TREATMENT

BUILDING

2"COLD WATER

S

A

S

A

S

A

S

A

S

A

C

W

C

W

C

W

C

W

C

W

EXISTING MDP IN ELEC.

ROOM 106

FLOW TOTALIZER

REMOTE DISPLAY

PANEL-D 208/120V

AND OMNISITE STATION

MONITIOR

ELECTRICAL SITE PLAN

SCALE 1" = 20'

SCHEMATIC LEGEND

OL

MOTOR STARTER OVERLOAD RELAY N.C.

CONTACT

CONTROL RELAY COIL

CR - INSTANTANEOUS CONTROL RELAY

TR - TIME DELAY RELAY

CONTACTOR COIL

M - MOTOR STARTER CONTACTOR

MF - MOTOR STARTER FORWARD CONTACTOR

MR - MOTOR STARTER REVERSE CONTACTOR

ML - MOTOR STARTER LOW SPEED CONTACTOR

MH - MOTOR STARTER HIGH SPEED CONTACTOR

SC - MOTOR STARTER STARTING CONTACTOR

RC - MOTOR STARTER RUN CONTACTOR

BP - BYPASS CONTACTOR

CC - CAPACITOR CONTACTOR

LC - LIGHTING CONTACTOR

IC - ISOLATION CONTACTOR

C - GENERAL CONTACTOR

INDICATES ITEMS IN A SEPARATE

COMMON ENCLOSURE

3 - POSITION, MAINTAINED ACTION

SELECTOR SWITCH

H - O - A: HAND-OFF-AUTOMATIC

L - O - R: LOCAL-OFF-REMOTE

PCS: PLANT CONTROL SYSTEM

PLC: PROGRAMMABLE LOGIC CONTROLLER

LIQUID LEVEL SWITCH CLOSES ON

RISING LEVEL

H A

XOO

XR

XY

OOX

LIQUID LEVEL SWITCH OPENS

ON RISING LEVEL

SINGLE-LINE DIAGRAM LEGEND

40A

30A

FRS-R -30

30A

480Y/277V

12470

1000KVA

GROUND CONNECTION

FUSED DISCONNECT SWITCH.

(SWITCH SIZE, FUSE TYPE AND FUSE SIZE AS

SHOWN)

UNFUSED DISCONNECT SWITCH

(SWITCH SIZE AS SHOWN)

THERMAL-MAGNETIC CIRCUIT BREAKER OR MOTOR

CIRCUIT PROTECTOR-MCP

(TRIP SIZE AS SHOWN)

THREE PHASE AC MOTOR

(HORSEPOWER AS SHOWN)

VARIABLE FREQUENCY DRIVE WITH A BY-PASS OPTION (SHOWN WITH

INTEGRAL EXTERNAL DISCONNECT HANDLE)

LIGHTING OR POWER TRANSFORMER,THREE PHASE

UNLESS NOTED OTHERWISE (CONNECTION, SIZE &

RATING AS SHOWN)

SINGLE PHASE AC MOTOR

(HORSEPOWER AS SHOWN)

VFD BP

ELECTRICAL PLAN LEGEND

DENSITY TRANSMITTER

LOAD CELL

GROUND ROD WITH CADWELD CONNECTION

TRANSMITTER SENSING ELEMENT - LEVEL, FLOW, DENSITY, PRESSURE, ANALYSIS

TEMPERATURE TRANSMITTER

PRESSURE TRANSMITTER

LEVEL TRANSMITTER

FLOW TRANSMITTER

BOX - JUNCTION, TERMINAL, PULL OR HAND HOLE

LIMIT (POSITION) SWITCH

PRESSURE SWITCH

TEMPERATURE SWITCH (I.E. MOTOR THERMO PROTECTOR)

SPEED SWITCH

CONVEYOR CABLE SWITCH

SOLENOID

ANALYSIS TRANSMITTER (I.E. OXYGEN, TURBIDITY)

INDICATOR - PRESSURE, FLOW, LEVEL, DENSITY, ANALYSIS

THERMOSTAT

LEVEL SWITCH

FLOW SWITCH

MOISTURE SWITCH

VIBRATION SWITCH

HEATER IN MOTOR

TORQUE SWITCH

GAS DETECTOR WITH CONTROL PANEL (GAS TYPE AS SHOWN)

PHOTOELECTRIC CELL

THERMOCOUPLE

PNEUMATIC VALVE OPERATOR

CURRENT TO PRESSURE TRANSDUCER

THREE-WAY TOGGLE SWITCH

DISCONNECT SWITCH (SEE SINGLE LINE DIAGRAM FOR SIZE & TYPE)

LIGHTING PANEL 120/208V OR 120/240V

DISTRIBUTION PANEL 480V OR 480Y/277V

EMERGENCY LIGHTING FIXTURE, (2-HEAD SHOWN)

DUPLEX RECEPTACLE

CONDUIT EXPOSED

CONDUIT CONCEALED

CONDUIT IN CONCRETE DUCT BANK

DIRECT BURIAL CABLE

DOUBLE POLE TOGGLE SWITCH

SINGLE POLE TOGGLE SWITCH

CONDUIT TURNS DOWN

CONDUIT TURNS UP

HOMERUN

CONDUIT TEE

CADWELD CONNECTION

SINGLE RECEPTACLE

CAPPED CONDUIT (FUTURE USE)

JB

FT

LT

PT

TT

AT

PI

DT

ZS

PS

TS

CS

SS

FS

LS

NS

OS

VS

LE

S

T

H

PC

G

T

V

G GROUND WIRE

E 1

LC

MOTOR STARTER ABBREVIATIONS

FVNR - FULL VOLTAGE, NON-REVERSING

FVR - FULL VOLTAGE REVERSING

TS1W - TWO SPEED, ONE WINDING

TS2W - TWO SPEED, TWO WINDING

TSR1W - TWO SPEED REVERSING, ONE WINDING TSR2W - TWO

SPEED REVERSING, TWO WINDING

GENERAL ELECTRICAL ABBREVIATIONS

PVC - POLYVINYL CHLORIDE

RGS - RIGID GALVANIZED STEEL

PVC/RGS - PVC COATED RGS

8. FOR BELOW GRADE CONDUIT PENETRATIONS THROUGH EXISTING

EXTERIOR CONCRETE WALLS, PROVIDE TYPE A CONDUIT SLEEVE

FOR PVC CONDUIT. FOR RGS OR PVC-COATED RGS CONDUIT,

PROVIDE TYPE B CONDUIT SLEEVE THROUGH CONCRETE WALLS,

AND TYPE C CONDUIT SLEEVE THROUGH EXISTING CONCRETE

WALLS.

9. FOR ABOVE GRADE CONDUIT PENETRATIONS THROUGH EXTERIOR

CONCRETE WALLS, PROVIDE TYPE C CONDUIT SLEEVE. FOR

MASONRY WALLS PROVIDE TYPE F CONDUIT SLEEVE.

10. FOR CONDUIT PENETRATIONS THROUGH EXISTING CONCRETE

FLOORS AND WALLS BETWEEN ADJACENT NON-CLASSIFIED

(NON-HAZARDOUS) AREAS, PROVIDE TYPE C CONDUIT SLEEVES

FOR ALL CONDUIT TYPES. FOR SIMILAR PENETRATIONS THROUGH

CONCRETE FLOORS AND WALLS, PROVIDE TYPE D CONDUIT

SLEEVES FOR ALL CONDUIT TYPES.

11. FOR CONDUIT PENETRATIONS THROUGH CONCRETE FLOORS AND

WALLS SEPARATING CLASSIFIED (HAZARDOUS) AREAS FROM

NON-CLASSIFIED (NON-HAZARDOUS) AREAS, PROVIDE TYPE G

CONDUIT SLEEVES. FOR SIMILAR PENETRATIONS THROUGH

MASONRY WALLS, PROVIDE TYPE H CONDUIT SLEEVE. FOLLOW

MECHANICAL SEAL MANUFACTURER'S RECOMMENDATIONS TO

MEET 3-HOUR FIRE RESISTANCE REQUIREMENTS.

12. LEGENDS ARE FOR REFERENCE ONLY AND DOES NOT MEAN THAT

ALL ITEMS ARE USED.

ELECTRICAL NOTES

1. STRUCTURAL MATERIALS ARE NOT SHOWN ON ELECTRICAL DRAWINGS.

REFER TO ARCHITECTURAL AND STRUCTURAL DRAWINGS.

2. ALL ELECTRICAL EQUIPMENT ELEVATIONS SHOWN ARE TO BOTTOM OF

DEVICE OR PANEL, UNLESS OTHERWISE NOTED.

3. NUMBER SHOWN (I.E.11735), INDICATES A SPECIFICATION REFERENCE FOR

ITEMS OTHER THAN DIVISION 16. THE ELECTRICAL ITEM UNDER THIS

REFERENCE IS SUPPLIED BY ANOTHER PART OF THE CONTRACT. UNLESS

OTHERWISE NOTED IN THAT SPECIFICATION, THE CONTRACTOR SHALL

INSTALL AND WIRE THE ITEM PER THE DRAWINGS AND DIVISION 16

SPECIFICATIONS.

4. CONTROL WIRING SHALL CONFORM TO ALL REQUIREMENTS AS SHOWN

ON THE P & ID DRAWINGS WHETHER SHOWN ON THE ELECTRICAL

DRAWINGS OR NOT.

5. WHERE LINES ARE SHOWN CONNECTING ELECTRICAL EQUIPMENT, THEY

ARE NOT INTENDED AS CONDUIT ROUTING. CONTRACTOR SHALL ROUTE

ALL CONDUIT RUNS (SHOWN OR NOT) PER DIVISION 16 SPECIFICATIONS.

6. WP INDICATES WATERPROOF. LETTER ON OR NEXT TO LIGHT FIXTURE

INDICATES TYPE, PER SECTION 16510. NUMBER WITH LIGHT FIXTURE OR

RECEPTACLE INDICATES CIRCUIT NUMBER.

7. GFCI INDICATES A CIRCUIT BREAKER OR RECEPTACLE WITH A 6 MA

GROUND FAULT CIRCUIT INTERRUPTER. GFEPD INDICATES A CIRCUIT

BREAKER OR RECEPTACLE WITH A 30 MA GROUND FAULT EQUIPMENT

PROTECTION DEVICE.

Jones & Henry Engineers, Ltd.

Fluid thinking...

www.JHeng.com

R

Scott Goodsell Rectangle

Scott Goodsell Typewritten Text

GROUNDING PLAN

Scale: 1/4" = 1'-0"NOTES:

1. ALL GROUNDING CONNECTIONS OF NEW AND EXISTING

GROUNDING RINGS, NEW BUILDING PAD REBAR (UFER)

AND METAL ROOF SHALL BE EXOTHERMIC.

2. APPLY BONDING JUMPERS TO ROOF AS NEEDED FOR

ELECTRICAL CONTINUITY.

3. INSTALL NEW GROUNDING RING AT SAME DEPTH AND

DISTANCE FROM WALL AS EXISTING.

4. ALL GROUND RODS SHALL BE COPPER-CLAD STEEL CORE.

NUMBER OF GROUND RODS SHOWN IS AN

APPROXIMATION. CONTRACTOR SHALL FURNISH AND

INSTALL GROUND RODS AS NECESSARY TO MEET NEC

ARTICLE 250 OHMIC REQUIREMENTS.

5. ALL GROUNDING CONDUCTORS SHALL BE #4/0 AWG

BARE STRANDED COPPER.

TO METAL ROOF

TO METAL ROOF

UFER GROUND

(TYP. OF 2)

EXISTING GROUND RING

EXISTING GROUND RING

COPPER-CLAD STEEL

CORE GROUND ROD

(TYP. - SEE NOTE 4)

SE

E

N O

TE

(TY

P.

FDFD

4"x2" GROUND BAR

Jones & Henry Engineers, Ltd.

Fluid thinking...

www.JHeng.com

R

Scott Goodsell Rectangle

Scott Goodsell

ELECTRICAL PLAN

Scale: 1/4" = 1'-0"

LIGHTING PLAN

Scale: 1/4" = 1'-0"

EUH-1 DISCONNECT

(NON-FUSED)

SEE NOTE 2

BACKWASH CONTROL

PANEL AND DISCONNECT

(NON-FUSED)

SEE NOTES 1, 3

EYEWASH WATER HEATER

DISCONNECT (NON-FUSED)

EF-1 DISCONNECT

SEE NOTE 2

WELL PUMP CONTROLLER FURNISHED

BY WELL PUMP SUPPLIER. SEE NOTE 3

ROLL UP DOOR DISCONNECT

(NON-FUSED)

(ABOVE)

ZS1 DOOR STRIKE FLOAT SWITCH

LS-1 (BELOW) SEE NOTE 5

OMNISITE STATION

MONITOR

PANEL-E

208/120V 3PH 4W

NOTES:

1. CONTRACTOR TO FURNISH AND INSTALL THIS ITEM AND ITS UNISTRUT FRAME FOR FLOOR

MOUNTING.

2. DISCONNECT SWITCH FURNISHED AND INSTALLED BY VENDOR.

3. SEE RISER DIAGRAM, DRAWING E603.

4. DOOR SUPPLIER TO PROVIDE ACCESS CONTROLLER ELECTRIC STRIKE. COORDINATE WIRING

WITH DOOR SUPPLIER. ELECTRIC STRIKE IS TO BE ACTIVATED BY THE FLOAT SWITCH OR THE

ACCESS CONTROLLER.

5. REMOVE EXISTING PANEL BREAKERS, BUS WORK AND FEEDER FROM PANEL MOP IN

WELCOME CENTER ELECTRIC ROOM. INSTALL TERMINALS IN EXISTING PANEL ENCLOSURE

AND CONNECT TO EXISTING CIRCUIT BRANCH WIRING. EXTEND CIRCUIT WIRING TO NEW

PANEL 'D'.

MANUAL ON/OFF LIGHT

SWITCH: COOPER X-SWITCH

CAT. NO. AH7810XC000

TO PANEL-E

CKT. 1

T/FIXTURE @ 12'-0" AFF

(TYP.)

SOFTENER PANEL

SEE NOTE 3

SOFTENER DISCONNECT

SEE NOTE 1

EUH-2 DISCONNECT (NON-FUSED)

SEE NOTE 2

EF-1 H-O-A

SEE NOTE 1

LIGHT FIXTURE SCHEDULE

TYPE DESCRIPTION

L1 LED INTERIOR HEAVY INDUSTRIAL, ENCLOSED AND GASKETED STRIP FIXTURE

HOLOPHANE CAT. NO. EMX-L48-6000LM-FGCL-WD-MVOLT-40K-80CRI-CR-DWHXD

48"Lx5.1"Wx4.6"H, 6248 LUMENS, 39.5 WATTS, FLAT CLEAR GLASS LENS, NON-DIMMING, 80CRI, CORROSION RESISTANT WHITE FINISH, 120-277V 50/60Hz

SWITCH

E1

E2

E3

MANUAL ON/OFF MOTOR CONTROL SWITCH, NEMA 4x, 30A, 600V COOPER X-SWITCH CAT. NO AH7810XC00 5"Wx6"Hx3.56"D

REMOTE SINGLE LED LIGHT

NICOR MWOS-REMOTE

LED EMERGENCY LIGHT FOR INDOOR/OUTDOOR USE

NICOR CAT. NO. EML6-1-UNV-WH

120/277VAC, 2.4W, 90-MINUTE NiCAD BATTERY, ABS CORROSION RESISTANT WHITE ENCLOSURE

LED COMBO EXIT SIGN AND EMERGENCY LIGHT

NICOR CAT. NO. ECL1-10-UNV-WH-R-2-R

120/277VAC, 2.9W, 90-MINUTE NiCAD BATTERY, RED LETTERS, ABS CORROSION RESISTANT

WHITE ENCLOSURE FOR USE WITH ONE REMOTE HEAD

DOOR STRIKE AND ACCESS

CONTROLLER FURNISHED

BY DOOR SUPPLIER

PT-1

SEE NOTE 3

PIT-302

LSL-317

LSH-316

BFV-319

NOTE 3

METERING PUMPS

(CFP-131) NOTE 3

FINSHED WATER FLOW METER,

FE-1, MOUNTED IN PIPING AT

12'-0" AFF

M

FILTER SKID

SOFTENER SKIDBRINE TANK

BLADDER

TANK

BACKWASH

SUPPLY PUMP

BACKWASH

HOLDING TANK

L2 OUTDOOR SOFFIT LED FIXTURE WITH MOTION SENSOR

DEKOR TYPE SPOT LIGHT WITH 20° - 30° BEAM ANGLE,

33 LUMEN, TRANSFORMER

BACKWASH

SUPPLY PUMP

MAIN CONTROL

PANEL (MCP-291)

AND DISCONNECT.

SEE NOTE 3

FILTER SKID

SOFTENER SKID

JB-292

JUNCTION BOX

SEE NOTE 3

L-1

MOTORIZED LOUVER

EF-1

NOTE 3

POSITION SWITCH

REMOTE FLOW TRANSMITTER FT-1

DEDICATED COMPRESSOR

RECEPTICALE

EXISTING HEATER

(TYP. 2)

EXISTING RECEPTACLE

(TYP. 4)

ROLL UP DOOR

DISCONNECT

(NON-FUSED)

SEE NOTE 5

(TYP. OF 6)

Jones & Henry Engineers, Ltd.

Fluid thinking...

www.JHeng.com

R

Scott Goodsell Rectangle

Scott Goodsell

PANEL-D SCHEDULE

MDP (EXISTING)

ELECTRICAL ROOM

208/120V 3PH 4W

SIEMENS S4

MAIN BUS

600A 3P

250A 208V 3P

(4) 250 MCM CU + 4 AWG GND

2-1/2" C

PANEL-D

208/120V 3PH 4W

250A MAIN LUGS ONLY

ONE LINE DIAGRAM

Jones & Henry Engineers, Ltd.

Fluid thinking...

www.JHeng.com

R

Scott Goodsell Rectangle

Scott Goodsell

20A

PANEL-B (EXISTING)

208/120V 3PH 4W

ELECTRIC ROOM 106

(2) 12 AWG CU + 12 AWG GND

1 (+)

2 (-)

6 (mA+)

4 (COM)

2/C 16 AWG TSP

1/2" C

PRECISION DIGITAL PD2-6200

FLOW TOTALIZER

REMOTE DISPLAY

MAIN/MECH ROOM 108

27 (-)

26 (+)+

6 (S1) BROWN

5 (E1) BROWN

7 (E2) WHITE

8 (S2) WHITE

4 (GND) GREEN

5 (E1)BROWN

7 (E2)WHITE

4 (GND)GREEN

37 (E) YELLOW

37 (E)YELLOW

36 (S) YELLOW

GND

GND

1 (L+/L)

2 (L-/N)

FIT/FE

PROLINE PROMAG W 400

WALL MOUNTED

REMOTE VERSION

FLOW METER TRANSMITTER

PROLINE PROMAG W 400

FLOW METER SENSOR

HOUSING

ELECTRODE CABLE

SUPPLIED BY VENDOR

COIL CURRENT CABLE

SUPPLIED BY VENDOR

(2) 12 AWG CU + 12 AWG GND

3/4" C

20A

PANEL-E

208/120V 3PH 4W

FLOW METER DIAGRAM

G N

G

L

20A PANEL-E

208/120V 3PH 4W

COAXIAL CABLE

OMNISITE OUTDOOR PHANTOM

ANTENNA BRACKET KIT W/ COAX

CABLE (S-CBL-CX-ABRK10)

OMNISITE CRYSTAL

BALL MONITOR

MONITOR INPUTS:

WELL PUMP RUNNING

BACKWASH PUMP RUNNING

FLOW METER (PULSE TOTALIZING)

ALARM INPUTS:

FLOOR FLOAT SWITCH

DOOR OPEN

BACKWASH HIGH DIFFERENTIAL PRESSURE

FILTER HIGH DIFFERENTIAL PRESSURE

FILTER CONTROL PANEL SYSTEM ALARM

FILTER (RESERVED - TBD)

SOFTENER HIGH DIFFERENTIAL PRESSURE

SOFTENER CONTROL PANEL SYSTEM ALARM

SOFTENER (RESERVED - TBD)

WELL PUMP FAIL

MONITOR PANEL DIAGRAM

(2) 12 AWG CU + 12 AWG GND

3/4" C

Jones & Henry Engineers, Ltd.

Fluid thinking...

www.JHeng.com

R

Scott Goodsell Rectangle

Scott Goodsell

COLDWATER M101
Electrical
COLDWATER E001
COLDWATER E101
COLDWATER E102
COLDWATER E601
COLDWATER E602
COLDWATER E603
COLDWATER E604
COLDWATER E605

File details come from the government source that posted it. Updated .