Bid Package - Section G - Contract Drawings_Prado Regional Park Drilling New Irrigation Well~1.pdf

PDF 1 MB Posted

Attached to
Prado Regional Park Drilling Irrigation Well Project
Solicitation number
SPD127-SPDAD-6517
Issued by
San Bernardino County, California

About this file

Summary: Bid Package - Section G - Contract Drawings for Prado Regional Park Drilling New Irrigation Well

This document constitutes Section G (Contract Drawings) of the bid package for the Prado Regional Park Drilling Irrigation Well Project in California. The project involves the drilling and installation of a new irrigation well at Prado Regional Park to support the park's irrigation infrastructure and water supply needs. The contract drawings section provides detailed technical specifications, site plans, and engineering designs necessary for contractors to understand the scope of work, well drilling requirements, and construction specifications. These drawings serve as the contractual basis for bid preparation and subsequent project execution, ensuring all bidders have access to identical technical information and design standards for accurate cost estimation and project delivery.

The contract drawings define the technical requirements, including well depth specifications, casing requirements, pump installation details, and connection points to the existing irrigation system. All bidders must utilize these standardized drawings for their proposals to ensure consistency and comparability of bids. The drawings function as binding contract documents upon award, establishing the baseline expectations for construction quality, materials, and installation methodology. Contractors are required to comply with all dimensions, details, and specifications depicted in the drawings, and any deviations must be submitted as formal change orders with appropriate justification and cost adjustments.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SECTION G

CONTRACT DRAWINGS

Prado Regional Park Drilling New Irrigation Well

FOR

16700 Euclid Ave, Chino, Ca,91708

PROJECT NO.: 30.30.0200

APPENDIX A

Prado Regional Park Well Drilling Bid Package

• Figure 1 – Well Location Map

• Figure 2 – Preliminary Design, Prado Regional Park Well

• Table 1 – Preliminary Well Design Summary

• Example Camera Tube Connection Box

• Example Geologic Logs Showing Expected Geology k8593 Text Box

SECTION G - FIGURES & EXHIBITS

L2834 Rectangle xx

EXISTING

AGRICULTURAL

WELL

PARK ROAD EAST

ACCESS ROAD

EU

C

LI

D

A

VE

N U

E

M COMBS WAY

NEW PROPOSED PRADO REGIONAL PARK WELL

PRADO LAKE

OVERFLOW

PARKING

PARK ENTRANCE STATION

PARK

OFFICE

PARK ROAD WEST

PARKING LOT 7

PARKING LOT 8

1/

/2

3:

:3

PM

C

:\U

SE

R S\

R U

BE

N

.L U

G O

\D C

\A C

C D

O C

S\

TE

TR

A

TE

C

H

IN

C \2

-0

-2

P

R

AD

O W

EL

L

D

ES

IG

N

\P R

O

JE

C T

FI

LE

S\ C

AD

\C

O N

C

EP

TU

AL

\E X

2-

AC

C

ES

S

AN

D W

EL

L

LO

C

AT

IO

N S.

D W

G

LU

G

O , R

U

BE

N www.tetratech.com

DESN:

PROJ:

DATE:

Bar Measures 1 inch

C op yr ig ht : T et ra

T ec h

Figure

200-01299-26002SAN BERNARDINO COUNTY

PRADO LAKE PRELIMINARY WELL DESIGN JANUARY 2026

RL

160 East Via Verde, Suite 240 San Dimas, California, 91773

Phone: (909) 305-2930

SCALE:

200' 400'

1'' = 400'

PARK ACCESS AND WELL LOCATIONS

N

LEGEND:

SITE ACCESS PATHING

NOTES:

FINAL SIZE AND INTERVAL OF FILTER PACK AND WELL CASING PERFORATION

WILL BE DETERMINED BASED ON RESULTS OF PILOT BOREHOLE DRILLING

S.S. = STAINLESS STEEL

FINAL DEPTH OF BOREHOLE AND WELL CASING TO BE DETERMINED BASED

ON RESULTS OF PILOT BOREHOLE DRILLING

CONDUCTOR CASING DEPTH TO BE DETERMINED BASED ON SITE

CONDITIONS ENCOUNTERED

OD = OUTSIDE DIAMETER

ID = INSIDE DIAMETER

DIA = DIAMETER

FILLET WELD

3/8" (TYP)

1'

5/16" THICK x 2" WIDE

GUIDES - INSTALL AT 90°

POINTS AND AT INTERVALS

NOT GREATER THAN 40'

BLANK CASING

HALF PIPE SECTIONS

4" DIA PIPE, 5/16" WALL

THICKNESS (TYP) INSTALL

AT 90° POINTS ONLY ON TOP

OR BOTTOM NON-PERFORATED

ENDS AT INTERVALS NOT GREATER

THAN 40'

LOUVERED SCREEN

FILLET WELD

5/16" (TYP)

NOT TO SCALE

CASING CENTRALIZERSA

NOTE: ALL CENTRALIZER AND WELDING MATERIALS TO

LOUVERED CASING BLANK CASING

EXTEND 3" OUT FROM

CASING WALL (TYP)

BE THE SAME TYPE AS THE CASING MATERIAL.

30°(TYP)

EXTEND 3" OUT FROM

CASING WALL (TYP)

WELD 1/4" 304 L S.S. STEEL COVER

PLATE PER SPECIFICATIONS

42" DIA CONDUCTOR BOREHOLE (MIN)

SAND CEMENT (10.3 SACK TYPE II) SEAL

18-5/8" OD x 1/4" WALL THICKNESS 304 L S.S.

BLANK CASING

NOMINAL 2-1/2" SCH 40 304 L S.S.

GRAVEL FEED TUBE (TO 65' BGS)

SAND CEMENT (10.3 SACK TYPE II) SEAL

FOR CONDUCTOR CASING

GROUND LEVEL (DRILLING)

FINISH GROUND SURFACE

NOT TO SCALE

PRELIMINARY WELL DETAIL

4'

INSTALL S.S. CENTRALIZERS (TYP)

PER DETAIL AND SPECIFICATIONS

A

NOMINAL 26" DIA BOREHOLE

3-1/2'

18-5/8" OD x 1/4" WALL THICKNESS 304 L S.S.

0.060" SLOT FUL-FLO LOUVERED SCREEN

18-5/8" OD x 1/4" WALL THICKNESS 304 L S.S.

BLANK CASING AND WELDED BOTTOM CAP

PRADO REGIONAL PARK WELL

515'

50'

36" OD 5/16" WALL THICKNESS

MILD STEEL CONDUCTOR

CASING TO 50'

NOMINAL 30" DIA BOREHOLE

#8/16 FILTER PACK (TYP)

55' 60' 65'

100'

180'

200'

210'

300'

380'

490'

500'

5' OF BENTONITE SEAL

(3/8" BENTONITE CHIPS)

5' OF TRANSITION SAND

(12 x 20)

3" ID SCHEDULE 40 304 L S.S.

SOUNDING/CAMERA TUBE

(TO 195' BGS)

#8/16 FILTER PACK (TYP)

18-5/8" OD x 1/4" WALL THICKNESS 304 L S.S.

0.060" SLOT FUL-FLO LOUVERED SCREEN

BGS = BELOW GROUND SURFACE

CHECKED BY:

DESIGNED BY: DRAWN BY:

DESCRIPTIONREV. DATE APP'D

DATE:

TWO WORKING DAYS BEFORE YOU DIG

Call: TOLL FREE

Underground Service Alert

PLANS APPROVED BY: PLANS PREPARED UNDER SUPERVISION OF

R.C.E.

EXP.EXP.DATE: DATE:R.C.E.

DL

CP

PRADO RP WELL

P:

\A

C

AD

\0

3-

7-

SA

N B\

A.

dw g

La st sa ve d:

C

H R

IS

TI

N A.

PA

U

G H

PRELIMINARY DESIGN

01/16/26

PRADO REGIONAL PARK

NEW WATER IRRIGATION SOURCE

Don Lee Stamp

Depth Interval (feet bgs)

Conductor Borehole 0 - 52 42 nominal Conductor Casing +1 - 50 32 O.D. (5/16-inch wall thickness, mild steel) Pilot Borehole 52 - 515 17.5 nominal (maximum) Final Borehole (Upper) 52 - 210 30 nominal Final Borehole (Lower) 210 - 515 26 nominal

+4 – 100 (blank) 18-5/8 O.D. (1/4-inch wall thickness, 314L S.S.)

100 – 180 (screen) 18-5/8 O.D. Ful-Flo Louvered (1/4-inch wall thickness, 314L S.S.)

180 – 200 (blank) 18-5/8 O.D. (1/4-inch wall thickness, 314L S.S.)

200 – 300 (screen) 18-5/8 O.D. Ful-Flo Louvered (1/4-inch wall thickness, 314L S.S.)

300 – 380 (blank) 18-5/8 O.D. (1/4-inch wall thickness, 314L S.S.)

380 – 490 (screen) 18-5/8 O.D. Ful-Flo Louvered (1/4-inch wall thickness, 314L S.S.)

490 – 500 (blank) 18-5/8 O.D. (1/4-inch wall thickness, 314L S.S.)

Gravel Make-Up Tube +3-1/2 – 65 (blank) 2-1/2 nominal (Schedule 40, 304L S.S.)

Camera Tube +3-1/2 - 195 3 nominal (Schedule 40, 304L S.S.)

Notes:

bgs – below ground surface

I.D. – inside diameter

O.D. – outside diameter

S.S. – stainless steel

Description Diameter (inches)/ Material

Table 1 Preliminary Well Design Summary

Prado Regional Park Well

Well Casing

Example Camera Tube Connection Box

File details come from the government source that posted it. Updated .