B08_Sect_C_attach1_Specifications_4pgs.pdf
PDF 119 KB Posted
- Attached to
- HVAC REFURBISHMENT CU-9_NHOTIC Federal contract opportunity
- Solicitation number
- 140L4326R0032
About this file
This document is a Specifications section (Section C) of a federal contract solicitation for HVAC system replacement at the Bureau of Land Management's National Historic Oregon Trail Interpretive Center in Baker City, Oregon.
The work involves refurbishing an existing 10-ton Johnson Controls Series 20 Split System outdoor air-cooled heat pump unit (Model J10PCC00A4ALB2, R-410A, 460V-3Phase-60Hz). The contractor must furnish all labor, supervision, equipment, transportation, supplies, and materials to complete demo and replacement of outdoor condensing coils, fan motors, filter-drier, refrigerant recharge, and testing of mechanical components. All replacement equipment and parts must be exact OEM replacements or custom-manufactured equivalents compatible with the existing Johnson Controls unit and compliant with commercial industry standards. The condensing coils must feature copper tube construction with aluminum fins, fan motors must be OEM equivalents, and the filter-drier must be UL-listed, sealed-type (Catch All or equivalent), bidirectional units capable of filtering moisture, foreign matter, acids, sludge, and varnish. Work location is 22267 US Highway 86, Baker City, OR 97814, with regular business hours Monday through Friday, 9:00 a.m. to 5:00 p.m. PST, excluding federally observed holidays. The on-site point of contact is Maintenance Worker Pete Heredia at (541) 523-1840.
Execution requirements include EPA Section 608-compliant refrigerant recovery with logged weights, condenser coil removal and replacement, fan motor replacement with new run capacitors, fan blade inspection and replacement if micro-cracks are found, and filter-drier installation using continuous nitrogen purge (2–3 PSI). Mechanical inspection must include insulation resistance testing on compressor motor windings, acid and moisture testing on compressor oil, reversing valve solenoid coil resistance inspection, service valve verification, and inspection of isolation grommets and structural framing. Electrical work includes replacing primary compressor contactors, tightening all terminals, inspecting wiring insulation, and cleaning the base pan. Pressure testing, evacuation, and commissioning must include 400 PSI nitrogen pressurization held for 30 minutes minimum for zero pressure drop verification, deep vacuum pulling to below 500 microns held for 15 minutes with pump isolated, virgin or certified reclaimed refrigerant charging to factory specifications adjusted for line-set volume, and operational data recording including volts, amps, ambient temperature, subcooling, and superheat measurements in both heating and cooling modes. Field quality control requires pressure testing per ASME B31.5 to 400 PSI using dry nitrogen and final leak detection at 27-inches vacuum and 400 PSI with zero leakage tolerance. Contractor shall set initial temperature set points and instruct operating personnel on controls adjustment.
Submittals require three copies of manufacturer's literature, product and installation warranties, and complete testing and inspection documentation signed by the installer and Contracting Officer Representative, submitted to the BLM Vale District Office, 100 Oregon Street, Vale, OR 97918, with 5 working days allowed for government review and approval prior to installation. All parts and equipment must be UL-listed and factory-tested with product warranties of at least one year and installation service provider warranties of minimum one year against defects in installation and workmanship. The Contracting Officer Representative and/or Project Inspector will conduct periodic inspections, and work performed according to Section C specifications will be considered acceptable for payment.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attach_2_Contractor_Questions_and_Answers_2pgs_0002.pdf | ||
| Attach_4_Revised_Specifications_4pgs_0002.pdf | ||
| Attach_5_Additional_Clause_and_Provision_Option_Item_1pg_0002.pdf | ||
| Attach_1_Site_Visit_Attendance_Record_1pg_0002.pdf | ||
| Sol_140L4326R0032_Amd_0002.pdf | ||
| Attach_3_Revised_RFP_Amend2_140L4326R0032_47pgs_0002.pdf | ||
| B09_Amend_2_SF30_140L4326R0032_0002.pdf | ||
| B09_Amend_1_Sol_140L4326R0032_0001.pdf | ||
| Sol_140L4326R0032_Amd_0001.pdf | ||
| Sol_140L4326R0032.pdf | ||
| B08_Sect_C_attach3_Floor_Plan_Drawing_1pg.pdf | ||
| B01_Synopsis_HVAC_Refurbishment_CU-9.pdf | ||
| B08_RFP_140L4326R0032_HVAC_Refurbishment_CU-9_(2).pdf | ||
| B08_Sect_C_attach2_Map_1pg.pdf | ||
| B08_Sect_J_attach4_CWD_OR20260002_5pgs.pdf |
Show all 15
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SECTION C JORDAN VALLEY GUARD STATION
SPECIFICATIONS HVAC SYSTEM REPLACEMENT
SECTION C – SPECIFICATIONS
C.1.0 GENERAL
C.1.1 DESCRIPTION OF WORK - Furnish all necessary labor, supervision, equipment, transportation, supplies, and materials to refurbish existing 10- Ton outdoor air-cooled heat pump unit. Work shall include demo and replacement of outdoor condensing coils, fan motors, filter-drier, refrigerant recharge, and testing and inspection of mechanical components required to ensure a fully operational heat pump unit.
C.1.2 LOCATION: Work is located at the Bureau of Land Management
National Historic Oregon Trail Interpretive Center, 22267 US Hwy 86, Baker City, OR. 97814.
C.1.3 SPECIAL REQUIREMENTS: Regular business hours are Monday through Friday, 9:00 am – 5:00 pm (PST), except for federally observed holidays. The point of contact on site will be the Maintenance Worker, Pete Heredia. Work Phone (541) 523-1840.
C.2.0 PRODUCTS
C.2.1 Existing Outdoor Unit (CU-9):
MANUFACTURER
A. Outdoor Air-Cooled Heat Pump Unit:
a. Johnson Controls Series 20 Split System
• Model J10PCC00A4ALB2
• 10-Ton, 11.0 EER/11.4 IEER/11.8 IPLV, R-410A Heat Pump,
• 2-Pipe R-410A, 460V-3Phase-60Hz,
• Copper Tube/Aluminum Fin Condenser Coil
• Phase Monitor
• Low ambient Control
C.2.2 General: All replacement equipment and parts shall be manufactured and designed for compatibility with the existing Johnson Controls outdoor condensing unit and in accordance with commercial industry standards.
A. Outdoor Unit Condensing Coils:
Shall be exact OEM replacement coils or custom-manufactured to be installed in the existing outdoor unit. Outdoor coils shall be copper tube construction with aluminum fins, bonded to the tubes by mechanical expansion, factory tested under high pressure to insure leak proof construction.
B. Fan Motors:
Shall be exact OEM replacement or manufactured and designed to be installed in the existing outdoor condensing unit.
C. Filter-Drier:
Shall be UL listed of the sealed type (Catch All or equivalent), bi-directional, and capable of filtering out moisture, foreign matter, acids, sludge, and/or varnish due to oil decomposition.
C.3.0 EXECUTION
C.3.1 Refrigerant Management & Component Replacement
Recover existing refrigerant into certified cylinders per EPA Section 608 regulations. Log recovered weights. Remove degraded condenser coils.
Install new OEM-spec or approved equivalent aluminum-fin/copper-tube condensing coils. Replace all condenser fan motors with new OEM equivalents. Install new matching run capacitors. Inspect, clean, and balance existing fan blades; replace blades if structural micro-cracks are found. Cut out existing liquid line and suction line filter-driers. Braze in new, highly absorbent oversized filter-driers using a continuous nitrogen purge (2–3 PSI) to prevent internal oxidation.
C.3.2 Mechanical Inspection & Diagnostic Testing
Perform insulation resistance testing (megohmmeter) on compressor motor windings. Conduct an acid and moisture test on the compressor oil.
Inspect the reversing valve solenoid coil resistance and physically test valve sliding operation. Check all service valves for tight shutoff and mechanical integrity. Inspect compressor rubber isolation grommets, fan motor mounts, and base pan structural framing for cracking, degradation, or excessive vibration.
C.3.3 Electrical Restorations
Replace all primary compressor contactors. Tighten all high- and low-voltage electrical terminals. Inspect wiring insulation for brittleness or heat damage. Clean debris from the base pan.
C.3.4 Pressure Testing, Evacuation, and Commissioning
Pressurize the system with dry nitrogen to 400 PSI. Hold for a minimum of 30 minutes to verify zero pressure drop. Pull a deep vacuum using a calibrated micron gauge. The system must drop below 500 microns and hold for 15 minutes with the pump isolated (vacuum decay test). Weigh in a virgin or certified reclaimed refrigerant charge to exact factory specifications, adjusting for the existing line-set volume. Start the unit and record operational data. Measure volts, amps, ambient temperature, subcooling, and superheat in both heating and cooling modes.
C.4.0 FIELD QUALITY CONTROL
A. Pressure Test: Test refrigeration system in accordance with ASME B31.5. Pressure test system with dry nitrogen to 400 PSI . Perform final tests at 27-inches vacuum and 400 PSI using electronic leak detector. Test to no leakage.
B. System Start-Up: Contractor shall set initial temperature set points and instruct operating personnel in adjustment of set-points and controls.
C.5.0 SUBMITTALS: Contractor shall submit the following to the Bureau of
Land Management, Vale District Office, 100 Oregon Street, Vale, OR.
97918, for approval prior to installation. Allow 5 working days for government review and approval. Submit 3 copies of the following:
A. Manufacturer’s Literature: Technical data for outdoor air-cooled heat pump condensing coils and all components replaced/installed on this project.
B. Warranties (Product and Installation) C. Testing and Inspection Documentation (complete with Installer and
COR signatures)
C.6.0 QUALITY ASSURANCE: All parts and equipment shall be Underwriter’s
Laboratory (UL) listed and factory tested to ensure field operation.
Product warranty shall be the best commercially available, but not less than 1 year. Installation service provider shall provide a minimum one-year warranty against defects in installation and workmanship.
C.7.0 LAYOUT: See attached drawings.
SECTION E – INSPECTION AND ACCEPTANCE
E.1.0 INSPECTION: The Contracting Officer Representative (COR) and/or
Project Inspector (PI) will make periodic inspections as a basis for payments. The Contractor is encouraged to observe inspections while they are being made and have a supervisor on site to confer with the COR.
E.2.0 ACCEPTANCE: Work performed according to the specifications outlined in Section C will be considered acceptable for payment purposes.
SECTION J - DRAWINGS
J.1.0 Drawings: Shall consist of two sheets.
Sheet 1 of 2: NHOTIC Vicinity Map Sheet 2 of 2: NHOTIC Maint. Bldg. Floor Plan