This document is a Structural Fire Deficiency Log for the National Park Service, detailing fire protection system issues across multiple buildings in the BEPA (Bering Land Bridge National Preserve) park in Alaska. The log records 12 specific deficiencies identified in 2023 across different locations including a Maintenance Auto Shop, Duplex buildings, Tok Bunk House, and Bear Park Visitor Center. Deficiencies span multiple systems such as sprinkler systems (SP), fire pumps (FP), backflow preventers (BP), and fire alarms (FA), with recommended repairs ranging from replacing gauges and test cocks to addressing fire pump water leakage and low alarm bell signage. Total estimated repair costs for these deficiencies amount to approximately $25,450, with the most expensive repair being an $18,000 fire pump repair at the Bear Park Visitor Center. The log includes detailed technical observations, references to NFPA standards, and recommendations for specialized technical intervention.

View the file

Other files for this federal contract opportunity

Show all 20

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Park Response Year of

Finding

Date

Deficiency

Corrected

Park

FMSS

Location # Building Name/Description System

FMSS

Asset # Location Deficiency Description Recommendation/Required Repair Additional Comments

Deficiency

Cost

2023 BEPA 1234 Maintenance Auto Shop SP 1437 Whole System

(Fire Pump) Flow from one sprinkler does not turn on.

Adjust fire pump start pressure (nps would not allow stating fire pump activation causes flooding of c-camp cabins)

Deficiency also noted in fire pump report with additional information noted. NPS

2023 BEPA 1234 Maintenance Auto Shop FP 1437 Controller Set point for pump to turn on is too low.

(nps staff would not allow adjusting this) -turn up fire pump psi start pressure so systems are properly supplied.

NFPA 20 or NFPA 25 Reference: 8.1.1

FPE Comment: Concur with finding. In order for a fire pump to start automatically from a single sprinkler head operating with minimal delay, the fire pump start pressure should be 10-15 psi (max) lower than the static pressure in the sprinkler system.

NPS

2023 BEPA 1616 Duplex 1616 A, B SP 6437 Guage on system is over 5 years old. Replace system guage x1. $200.00

2023 BEPA 1616 Duplex 1616 A, B BP 6437 Test Cocks #1 and #3 corroded closed and cannot open.

Replace test cocks and re-test $250.00

2023 BEPA 4545 Tok Bunk House BP 3473 (Serial A009764, Febco 2") Check #1 and #2 leaked.

Apply rebuild kit to backflow preventer and retest.

$850.00

2023 BEPA 4545 Tok Bunk House SP 3473 Antifreeze in system has a freezing point of 10°F.

Replace antifreeze to have a lower freezing point of -17°F $2,000.00

2023 BEPA 4545 Tok Bunk House FA 3474 Throughout building dB levels low in some apartments

Replace horn/strobes

Similar to KATM comments, would bring to compliance during renovation or system replacement, not necessarily requred as standalone effort

Existing structures, meeting the intent of the requirements. Follow up with Tuazon and Regional

Fire Coor.

$1,200.00

2023 BEPA 4545 Tok Bunk House FA 3474 FACP No allen key or glass rods to restore pull stations available.

Place allen keys and glass rods at the panel. $100.00

2023 BEPA 4545 Tok Bunk House FA 3474

AC Panel in

Mechanical

Room

No breaker lock on circuit breaker supplying primary power to fire alarm control panel.

Install circuit breaker lock. NPS

2023 BEPA 4545 Tok Bunk House FA 3474

Phone line dialer connected FACP

Phone line dialer not sending signals to Nome

Police Department monitoring station.

Troubleshoot. Check phone line for active/functional status.

Recommend

NPS coordinate with utility

2023 BEPA 4545 Tok Bunk House SP 3474 Pipe shows signs of glycerin leaking at threaded fittings.

Pull piping and apply new pipe dope and tape. $1,500.00

2023 BEPA 7777 Duplex 123 A, B BP 7326 (Serial 11240, Watts 2") Check #2 leaks.

Apply rebuild kit to backflow preventer and retest.

Replacement per 2020 inspection report $850.00

2023 BEPA 7777 Duplex 123 A, B SP 7326 Exterior Wall Missing alarm bell and FDC signage.

Provide alarm bell and FDC signage on exterior wall.

$400.00

2023 2018 BEPA 7777 Duplex 123 A, B SP 7326 Bathroom Two missing escutcheons (chrome, semi-recessed).

Replace. $150.00

2023 BEPA 8832 Bear Park Visitor Center FP 8736 Fire Pump Excessive water spraying from packing, bolts were seized and could not adjust.

Re-pack the pump and put new bolts in.

NFPA reference 25 8.3.2.9

FPE Recommendation: Fire pump repairs require specialized technicians/tools/parts. The existing fire pump is an Aurora 150 gpm at 45 PSI centrifugal vertical inline from Talco Fire Systems. ITM service providers may need to obtain fire pump service and parts from them.

$18,000.00

Travel Expenses

PARK TOTAL