About this file
This document is a detailed inventory spreadsheet listing fire protection systems across 12 National Parks in Alaska. The spreadsheet provides comprehensive information about fire alarm signaling systems, fire sprinkler systems, backflow preventers, fire suppression systems, and fire pumps located in various buildings within parks such as Denali, Glacier Bay, Katmai, Kenai Fjords, Klondike Gold Rush, Lake Clark, Wrangell-St. Elias, and others.
The inventory includes specific details for each asset, such as geographic area, park system, FMSS location number, building name, approximate building square footage, asset description, quantity, and notable comments. Many entries specify system types like addressable or conventional fire alarm systems, wet or dry pipe sprinkler systems, residential or commercial configurations, and additional details like clean agent systems, monitoring services, and backflow preventer characteristics. The document appears to be supporting a forthcoming fire protection systems inspection and testing contract (Solicitation Number 140P9725Q0013) for the National Park Service Alaska Region, covering a comprehensive assessment of fire protection infrastructure across these parks.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Geographic
Area in the
Park
Park
System to be
Inspected
Backflow
Preventer
COMMENTS
FMSS
Location
Number
FMSS Location Name
Approx.
Building sq.footage
Asset Asset Description Quantity Unit of
Measure
NOTES
Nome BELA Qty 2 42596 0000412 Duplex 203 A, B 2,741 347326 Fire Sprinkler System, Wet Pipe, 2.0 IN, FRX71 1.00 EA
Nome BELA Qty 2 42599 0000456 Duplex 205 A, B 2,741 347346 Fire Sprinkler System, Wet Pipe, 1.5 IN, FRX74 1.00 EA
Nome BELA 42605 00BUNK01 Bunk House--Nome 4,592 347309 Fire Alarm Signaling System, Conventional, NonRestorable, Government Monitoring Service, FA76, Diale1.00 EA
Nome BELA Qty 2 42605 00BUNK01 Bunk House--Nome 4,592 347310 Fire Sprinkler System, Wet Pipe, 2.0 IN, FRX76 1.00 EA BCKFLTYP - Reduced
Pressure Zone
Nome BELA 229446 207 E 5th Duplex A, B 2,700 TBD Perform inspection & inventory as part of FY25 contract 1.00 EA
Nome BELA 229446 207 E 5th Duplex A, B 2,700 TBD Perform inspection & inventory as part of FY25 contract 1.00 EA
Frontcountry DENA 1499 HQ Upfront Office B110 Historic 224 1475059 Fire Alarm Signaling System, Addressable, Government Monitoring Service1.00 EA
Frontcountry DENA 1501 HQ Administration Office B123 1,010 1475062 Fire Alarm Signaling System, Addressable, Government Monitoring Service1.00 EA
Frontcountry DENA 1502 HQ Barn Office B106 Historic 800 1475370 Fire Alarm Signaling System, Addressable, Government Monitoring Service1.00 EA
Frontcountry DENA 1505 HQ Kennels B105 Historic 1,275 1475395 Fire Alarm Signaling System, Addressable, Government Monitoring Service1.00 EA
Frontcountry DENA 1509 HQ Resources Management Addition
(non-historic) B118 3,828 1475409 Fire Alarm Signaling System, Addressable, Restorable, Government Monitoring Service1.00 EA
Frontcountry DENA 1509 HQ Resources Management Addition
(non-historic) B118 3,828 1475413 Fire Sprinkler System, Wet Pipe, fed from sprinkler riser in 1509 1.00 EA
Frontcountry DENA Visual Only, Reports to Panel in Loc 1509
HQ Resources Office and Conference
Room B102 Historic 2,665 1475567 Fire Alarm Signaling System, Addressable, Restorable, Government Monitoring Service1.00 EA
Visual Only, Reports to Panel in Loc 1509
Frontcountry DENA Visual Only, Reports to Panel in Loc 1509.
HQ Resources Office and Conference
Room B102 Historic 2,665 1475570 Fire Sprinkler System, Wet Pipe, 3.0 IN 1.00 EA
Visual Only, Reports to Panel in Loc 1509. BCKFLTYP -
Double-check
Frontcountry DENA 1511 HQ Interpretation Office B101 Historic 2,432 1475573 Fire Alarm Signaling System, Addressable, Government Monitoring Service1.00 EA
Frontcountry DENA 1511 HQ Interpretation Office B101 Historic 2,432 1475575 Fire Sprinkler System, Wet Pipe, 2.0 IN 1.00 EA BCKFLTYP - Reduced
Pressure Zone
Frontcountry DENA 1512 HQ Commercial Services Office B103
Historic 1,048 1475578 Fire Alarm Signaling System, Addressable, Government Monitoring Service1.00 EA
Frontcountry DENA 1512 HQ Commercial Services Office B103
Historic 1,048 1475580 Fire Sprinkler System, Wet Pipe, 2.0 IN 1.00 EA
BCKFLTYP - Reduced
Pressure Zone
Frontcountry DENA 1514 HQ Headquarters Office B21 Historic 3,138 1475583 Fire Alarm Signaling System, Addressable, Government Monitoring Service1.00 EA
Frontcountry DENA 1515 Maintenance Auto Shop B164 19,961 1475586 Fire Alarm Signaling System, Addressable, Government Monitoring Service1.00 EA
Frontcountry DENA 1515 Maintenance Auto Shop B164 19,961 1475587 Fire Sprinkler System, Dry Pipe, 4.0 IN 1.00 EA BCKFLTYP - Double-check
Frontcountry DENA 1515 Maintenance Auto Shop B164 19,961 1475588 Fire Pump System, Electric Motor Drive, 500.0 GPM, 50.0 HP 1.00 EA 500 GPM Pump
Frontcountry DENA 1518 HQ Rock House Residence P111 Historic 1,187 1475811 Smoke Alarm System, Hardwired Interconnected, HQ Rock House P111 Historic1.00 EA
Frontcountry DENA 1518 HQ Rock House Residence P111 Historic 1,187 1475817 Fire Sprinkler System, Residential, 2.0 IN, HQ Rock House P111 1.00 EA BCKFLTYP - Reduced
Pressure Zone
Frontcountry DENA 1520 HQ Area 3 Plex Garage B217 661 1475818 Fire Alarm Signaling System, Addressable, NonRestorable, Government Monitoring Service1.00 EA
Frontcountry DENA 1521 HQ Apartments P12 A & B Historic 2,131 1475819 Fire Alarm Signaling System, Addressable, Government Monitoring Service1.00 EA
Frontcountry DENA 1521 HQ Apartments P12 A & B Historic 2,131 1475822 Fire Sprinkler System, Residential, 2.0 IN 1.00 EA BCKFLTYP - Reduced
Pressure Zone
Frontcountry DENA 1522 HQ Apartments P13 A & B Historic 2,131 1475823 Fire Alarm Signaling System, Addressable, Government Monitoring Service1.00 EA
Frontcountry DENA 1522 HQ Apartments P13 A & B Historic 2,131 1475826 Fire Sprinkler System, Residential, 2.0 IN 1.00 EA BCKFLTYP - Reduced
Pressure Zone
Frontcountry DENA 1523 HQ John House B112 Historic 375 1475590 Fire Alarm Signaling System, Addressable, Government Monitoring Service, EST-3, John House B1121.00 EA
Frontcountry DENA 1526 HQ Superintendents Residence P23 A&B
Historic 3,386 1475827 Fire Alarm Signaling System, Addressable, Restorable, Government Monitoring Service, HQ Supt.'s Res.1.00 EA
Installed in FY22 with initial test to satisfy 2022 requirement
Frontcountry DENA 1526 HQ Superintendents Residence P23 A&B
Historic 3,386 1762085 Fire Sprinkler System, Wet Pipe, 1.0 IN, HQ Supt.'s Res P231.00 EA
Installed in FY22 with initial test to satisfy 2022 requirement
Park
Park
System to be
Inspected
Backflow
Preventer
COMMENTS
FMSS
Location
Number
FMSS Location Name
Approx.
Building sq.footage
Asset Asset Description Quantity Unit of
Measure
NOTES
Frontcountry DENA 1527 HQ Residence P251 2,551 1475832 Fire Alarm Signaling System, Addressable, NonRestorable, Government Monitoring Service1.00 EA
Frontcountry DENA 1527 HQ Residence P251 2,551 1475838 Fire Sprinkler System, Residential, 2.0 IN 1.00 EA wye double check valve
Frontcountry DENA 1528 HQ Human Resources Office B107
Historic 497 1475591 Fire Alarm Signaling System, Addressable, Government Monitoring Service1.00 EA
Frontcountry DENA 1530 HQ Panabode Residence S169 1,043 1475843 Fire Alarm Signaling System, Addressable, Restorable, Government Monitoring Service1.00 EA
Frontcountry DENA 1530 HQ Panabode Residence S169 1,043 1475845 Fire Sprinkler System, Residential, 1.0 IN 1.00 EA BCKFLTYP - Reduced
Pressure Zone
Frontcountry DENA 1531 HQ Panabode Residence S170 1,043 1475847 Fire Alarm Signaling System, Addressable, Government Monitoring Service1.00 EA
Frontcountry DENA 1533 HQ IT Building B53 2,528 1475594 Fire Alarm Signaling System, Addressable, Restorable, Government Monitoring Service1.00 EA
Frontcountry DENA 1533 HQ IT Building B53 2,528 1475595 Fixed Fire Suppression System, Clean Agent System, Restorable1.00 EA Clean Agent System. FM2000 -
Fike/Ecaro
Frontcountry DENA 1535 HQ Duplex P252 A & B 3,664 1475850 Fire Alarm Signaling System, Addressable, NonRestorable, Government Monitoring Service1.00 EA
Frontcountry DENA 1535 HQ Duplex P252 A & B 3,664 1475855 Fire Sprinkler System, Residential, 1.5 IN 1.00 EA wye double check valve
Frontcountry DENA 1537 HQ Boiler/Steam Plant B54 1,885 1475858 Fire Alarm Signaling System, Addressable, Government Monitoring Service1.00 EA
Frontcountry DENA 1537 HQ Boiler/Steam Plant B54 1,885 1475860 Fire Sprinkler System, Wet Pipe, 3.0 IN 1.00 EA BCKFLTYP - Double-check
Frontcountry DENA 1539 HQ 6-plex Apartment P51 13,117 1475864 Fire Alarm Signaling System, Addressable, Government Monitoring Service1.00 EA
Frontcountry DENA 1541 HQ Residence P34 2,136 1475867 Fire Alarm Signaling System, Addressable, NonRestorable, Government Monitoring Service1.00 EA
Frontcountry DENA 1541 HQ Residence P34 2,136 1475871 Fire Sprinkler System, Residential, 2.0 IN 1.00 EA BCKFLTYP - Reduced
Pressure Zone
Frontcountry DENA 1542 HQ Residence P26 2,197 1475872 Fire Alarm Signaling System, Addressable, NonRestorable, Government Monitoring Service1.00 EA
Frontcountry DENA 1542 HQ Residence P26 2,197 1475877 Fire Sprinkler System, Residential, 2.0 IN 1.00 EA BCKFLTYP - Reduced
Pressure Zone
Frontcountry DENA 1544 HQ Residence P28 2,194 1475878 Fire Alarm Signaling System, Addressable, NonRestorable, Government Monitoring Service1.00 EA
Frontcountry DENA 1544 HQ Residence P28 2,194 1475881 Fire Sprinkler System, Residential, 2.0 IN 1.00 EA BCKFLTYP - Reduced
Pressure Zone
Frontcountry DENA 1545 HQ Residence P27 2,189 1475884 Fire Alarm Signaling System, Addressable, NonRestorable, Government Monitoring Service1.00 EA
Frontcountry DENA 1545 HQ Residence P27 2,189 1475886 Fire Sprinkler System, Residential, 2.0 IN 1.00 EA BCKFLTYP - Reduced
Pressure Zone
Frontcountry DENA 2189 Maintenance B&U Building B380 14,770 1475888 Fire Alarm Signaling System, Addressable, 1 Ea., B&U Building B3801.00 EA
Frontcountry DENA 2189 Maintenance B&U Building B380 14,770 1475891 Fire Sprinkler System, Wet Pipe, 4.0 IN 1.00 EA BCKFLTYP - Double-check
Frontcountry DENA 18821 HQ Residence P171 2,723 1475937 Fire Alarm Signaling System, Addressable, Government Monitoring Service1.00 EA
West District DENA 18908 Toklat Duplex S243 896 1475943 Fire Sprinkler System, Residential, 1.5 IN, Toklat Duplex S243 1.00 EA
West District DENA 18914 Toklat Duplex S244 896 1475946 Fire Sprinkler System, Residential 1.00 EA
Talkeetna DENA 18918 Talkeetna Walter Harper Ranger Station, B249 5,513 1475959 Fire Alarm Signaling System, Conventional, NonRestorable, Commercial Monitoring Service1.00 EA
Talkeetna DENA 18918 Talkeetna Walter Harper Ranger Station, B249 5,513 1475960 Fire Sprinkler System, Dry Pipe, 4.0 IN 1.00 EA BCKFLTYP - Double-check
West District DENA 19134 Toklat Upper Shower House ADA B241 1,144 1475970 Fire Sprinkler System, Wet Pipe 1.00 EA
West District DENA 19135 Toklat Duplex S242 896 1475973 Fire Sprinkler System, Residential 1.00 EA
West District DENA 62098 Eielson Visitor Center B199 7,692 1475975 Fire Alarm Signaling System, Addressable, Restorable, None 1.00 EA
West District DENA 62098 Eielson Visitor Center B199 7,692 1475977 Fire Sprinkler System, Wet Pipe, Glycol 1.00 EA BCKFLTYP - Double-check
West District DENA 64382 Toklat Dorm S545 1,942 1475978 Fire Alarm Signaling System, Conventional, None 1.00 EA
West District DENA 64382 Toklat Dorm S545 1,942 1475981 Fire Sprinkler System, Residential 1.00 EA Self-contained
Park
Park
System to be
Inspected
Backflow
Preventer
COMMENTS
FMSS
Location
Number
FMSS Location Name
Approx.
Building sq.footage
Asset Asset Description Quantity Unit of
Measure
NOTES
Frontcountry DENA 86493 Murie Science and Learning Center MSLC
B547 5,126 1475986 Fire Alarm Signaling System, Addressable, Restorable, Government Monitoring Service1.00 EA
Frontcountry DENA 86493 Murie Science and Learning Center MSLC
B547 5,126 1475987 Fixed Fire Suppression System, Clean Agent System, Restorable1.00 EA
Clean Agent System. FM2000 -
Fike/Ecaro
Frontcountry DENA Qty 2 Qty. 2 located in Mech
Room and at Riser 86493
Murie Science and Learning Center MSLC
B547 5,126 1475989 Fire Sprinkler System, Wet Pipe, 2.5 IN, Glycol 1.00 EA
BCKFLTYP - Double-check
Qty. 2 located in Mech Room and at Riser
Frontcountry DENA
Park will assist with 3 highest detectors in lobby/entry
86498 Denali Visitor Center B548 13,991 1475992 Fire Alarm Signaling System, Addressable, Restorable, Government Monitoring Service1.00 EA
Frontcountry DENA 86498 Denali Visitor Center B548 13,991 1475994 Fire Sprinkler System, Dry Pipe, 4.0 IN, ~48 dry pendent sprinklers1.00 EA BCKFLTYP - Double-check
Frontcountry DENA 86499 Denali Visitor Center Book Store B550 2,556 1484362 Fire Alarm Signaling System, Addressable, Restorable, Government Monitoring Service, DVC Book Store B5501 EA
Frontcountry DENA 86499 Denali Visitor Center Book Store B550 2,556 1339827 Fire Sprinkler System, Dry Pipe, Covers 2,556 sf, DVC Book Store B5501 EA
West District DENA 111419 Eielson Utility Building B200 1,370 1475998 Fire Alarm Signaling System, Addressable, Restorable, None, Reports to FACP in 620981.00 EA
West District DENA Shared BP (use Loc.
62098) 111419 Eielson Utility Building B200 1,370 1476000 Fire Sprinkler System, Wet Pipe 1.00 EA Shared BP (use Loc. 62098)
Frontcountry DENA 226504 Shaffer Building B570 6,912 1476004 Fire Alarm Signaling System, Addressable, Government Monitoring Service1.00 EA
Frontcountry DENA QTY. 2 Two Clean Agent
Systems.
226504 Shaffer Building B570 6,912 1476005 Fixed Fire Suppression System, Clean Agent System, Restorable, [QTY. 2]2.00 EA
Two Clean Agent Systems.
FM2000 - Fike/Ecaro
Frontcountry DENA 226504 Shaffer Building B570 6,912 1476007 Fire Sprinkler System, Wet Pipe, 2.0 IN 1.00 EA BCKFLTYP - Double-check
Frontcountry DENA 226504 Shaffer Building B570 6,912 1476008 Fire Sprinkler System, Dry Pipe 1.00 EA
Frontcountry DENA 226507 Over and Out Building B911 (Shaffer
Annex) 2,747 1476016 Fire Alarm Signaling System, Addressable, Government Monitoring Service1.00 EA
Frontcountry DENA 243278 HQ Area The Afterthought Residence
P640 1,696 1476018 Fire Alarm Signaling System, Addressable, Restorable, Government Monitoring Service1.00 EA
Frontcountry DENA 243278 HQ Area The Afterthought Residence
P640 1,696 1476019 Fire Sprinkler System, Wet Pipe, 2.0 IN 1.00 EA
BCKFLTYP - Reduced
Pressure Zone
Bettles GAAR 42593 00000104 BTTH House 104 1,345 TBD Perform inspection & inventory as part of FY25 contract 1.00 EA
Bettles GAAR 42593 00000104 BTTH House 104 1,345 1776415 Fire Sprinkler System, Residential, BTTH House 104 1.00 EA
Bettles GAAR 42593 00000104 BTTH House 104 1,345 1787790 Fire Pump System, Electric Motor Drive, 1.5 HP, BTTH House 1041.00 EA
Bettles GAAR 42598 00000106 BTTH House 106 1,512 TBD Perform inspection & inventory as part of FY25 contract 1.00 EA System installed in 2021. 1"
Double Check, Watts
Bettles GAAR 42598 00000106 BTTH House 106 1,512 1750888 Fire Sprinkler System, Wet Pipe, 1.0 IN, Crawl Space BP, BTTH House 1061.00 EA System installed in 2021. 1"
Double Check, Watts
Bettles GAAR 42602 00000107 BTTH House 107 1,512 TBD Perform inspection & inventory as part of FY25 contract 1.00 EA System installed in 2021. 1"
Double Check, Ames
Bettles GAAR 42602 00000107 BTTH House 107 1,512 1750889 Fire Sprinkler System, Wet Pipe, 1.0 IN, BTTH House 107 1.00 EA System installed in 2021. 1"
Double Check, Ames
Bettles GAAR 43084 00000109 BTTH House 109 1,734 TBD Perform inspection & inventory as part of FY25 contract 1.00 EA System installed in 2021. 1"
Double Check, Ames
Bettles GAAR 43084 00000109 BTTH House 109 1,734 1750891 Fire Sprinkler System, Wet Pipe, 1.0 IN, BTTH House 109 1.00 EA System installed in 2021. 1"
Double Check, Ames
Bettles GAAR 43086 00000110 BTTH House 110 1,608 TBD Perform inspection & inventory as part of FY25 contract 1.00 EA System installed in 2021. 1"
Double Check, Watts
Bettles GAAR 43086 00000110 BTTH House 110 1,608 1750890 Fire Sprinkler System, Wet Pipe, 1.0 IN, BTTH House 110 1.00 EA System installed in 2021. 1"
Double Check, Watts
Marion Creek GAAR 43508 00000201 MACB-Ranger residence
(C1) 1,940 TBD Perform inspection & inventory as part of FY25 contract
Marion Creek GAAR 43508 00000201 MACB-Ranger residence
(C1) 1,940 TBD Perform inspection & inventory as part of FY25 contract
Marion Creek GAAR 43509 00000202 MACH-Transient housing
(C2) 1,400 TBD Perform inspection & inventory as part of FY25 contract
Marion Creek GAAR 43509 00000202 MACH-Transient housing
(C2) 1,400 TBD Perform inspection & inventory as part of FY25 contract
Bettles GAAR 88477 BTTB - 113 Visitor Center/Office 3,532 1477361 Fire Alarm Signaling System, Conventional, Commercial Monitoring Service, Dialer Not Programmed for1.00 EA
Bettles GAAR 88477 BTTB - 113 Visitor Center/Office 3,532 1057428 Fire Sprinkler System, Wet Pipe, Glycol, Basement Wet System,, Antifreeze 1st Floor/Attic1.00 EA
Bettles GAAR 88477 BTTB - 113 Visitor Center/Office 3,532 1477363 Fire Pump System, Electric Motor Drive, 150.0 GPM, 7.5 HP, Tank Water Supply1.00 EA 150 GPM Pump
Bartlett Cove GLBA 42545 HQ - Resource Management / Ranger
Office Building GBA06 3,549 1477376 Fire Alarm Signaling System, Conventional, None, Edwards EST-3X, GBA061.00 EA
Bartlett Cove GLBA 42545 HQ - Resource Management / Ranger
Office Building GBA06 3,549 1168372 Fire Sprinkler System, Dry Pipe, 4.0 IN, GBA06 1.00 EA Double-check
Bartlett Cove GLBA 42548 UC - Power Plant Building GBA08 11,520 1475415 Fire Alarm Signaling System, Conventional, Commercial Monitoring Service, Edwards EST-3X, GBA081.00 EA
Bartlett Cove GLBA 42548 UC - Power Plant Building GBA08 11,520 1477745 Fire Sprinkler System, Dry Pipe, 6.0 IN, GBA06 1.00 EA Double-check
Bartlett Cove GLBA 42551 HQ - Headquarters Building GBA12 5,027 1477755 Fire Alarm Signaling System, Addressable, Other, 7 Photo and 2 Duct Smoke Detectors1.00 EA
Park
Park
System to be
Inspected
Backflow
Preventer
COMMENTS
FMSS
Location
Number
FMSS Location Name
Approx.
Building sq.footage
Asset Asset Description Quantity Unit of
Measure
NOTES
Bartlett Cove GLBA 42565 HQ - Headquarters Emergency Cache
Building GBA89 661 224646 Fire Sprinkler System, Wet Pipe, 1.5 IN, GBA89 1.00 EA Double-check
Bartlett Cove GLBA 42573 HA - Quarters GBQ03 1,688 344135 Fire Sprinkler System, Residential, 2.0 IN, Glycerin, GBQ03 1.00 EA Reduced Pressure Zone
Bartlett Cove GLBA 42576 HA - Quarters GBQ04 1,168 344143 Fire Sprinkler System, Residential, 2.0 IN, Glycerin, GBQ04 1.00 EA Reduced Pressure Zone
Bartlett Cove GLBA 42578 HA - Quarters GBQ05 1,887 344152 Fire Sprinkler System, Residential, 2.0 IN, Glycerin, NFPA 13R, GBQ051.00 EA Reduced Pressure Zone
Bartlett Cove GLBA 42580 HA - Quarters Duplex GBQ09 3,074 344166 Fire Sprinkler System, Residential, 2.0 IN, Glycerin, GBQ09 1.00 EA Reduced Pressure Zone
Gustavus GLBA 42583 GA - Gustavus FAA Cottage GBQ20 1,170 1121928 Fire Sprinkler System, Residential, 2.0 IN, Glycerin, GBQ20 1.00 EA Reduced Pressure Zone
Gustavus GLBA 42586 GA - Gustavus FAA Cottage GBQ21 1,170 1121930 Fire Sprinkler System, Residential, 2.0 IN, Glycerin, GBQ21 1.00 EA Reduced Pressure Zone
Gustavus GLBA 42587 GA - Gustavus FAA Cottage GBQ22 1,170 1121931 Fire Sprinkler System, Residential, 2.0 IN, Glycerin, GBQ22 1.00 EA Reduced Pressure Zone
Bartlett Cove GLBA 42590 HA - Quarters GBQ75 Apartment Building 2,914 225117 Fire Alarm Signaling System, Conventional, Commercial Monitoring Service, Edwards EST-3X, GBQ751.00 EA
Bartlett Cove GLBA 42590 HA - Quarters GBQ75 Apartment Building 2,914 224713 Fire Sprinkler System, Dry Pipe, 2.0 IN, GBQ75 1.00 EA Double-check
Bartlett Cove GLBA 42601 HA - Quarters GBQ76 Apartment Building 3,736 225095 Fire Alarm Signaling System, Conventional, Commercial Monitoring Service, Edwards EST-3X, GBQ761.00 EA
Bartlett Cove GLBA 42601 HA - Quarters GBQ76 Apartment Building 3,736 225090 Fire Sprinkler System, Dry Pipe, 2.0 IN, GBQ76 1.00 EA Double-check
Bartlett Cove GLBA 42606 HA - Quarters GBQ77 Apartment Building 2,812 225475 Fire Alarm Signaling System, Conventional, Commercial Monitoring Service, Edwards EST-3X, GBQ771.00 EA
Bartlett Cove GLBA 42606 HA - Quarters GBQ77 Apartment Building 2,812 225160 Fire Sprinkler System, Dry Pipe, 2.0 IN, GBQ77 1.00 EA Double-check
Bartlett Cove GLBA 42610 HA - Quarters GBQ80 1,868 225972 Fire Sprinkler System, Residential, 1.0 IN, NFPA 13R, GBQ80 1.00 EA Double-check
Bartlett Cove GLBA 42615 HA - Quarters Duplex GBQ81 1,320 225902 Fire Sprinkler System, Residential, 1.0 IN, Glycol, NFPA 13R, GBQ811.00 EA Reduced Pressure Zone
Bartlett Cove GLBA 42618 HA - Quarters Duplex GBQ82 1,320 225945 Fire Sprinkler System, Residential, 1.0 IN, Glycol, NFPA 13R, GBQ821.00 EA Reduced Pressure Zone
Bartlett Cove GLBA 42620 HA - Quarters Duplex GBQ83 1,320 225934 Fire Sprinkler System, Residential, 1.0 IN, Glycol, NFPA 13R, GBQ831.00 EA Reduced Pressure Zone
Gustavus GLBA 61189 GA - Gustavus Water Plant Building
GBA61
404 1121932 Fire Sprinkler System, Wet Pipe, 2.0 IN, GBA61 1.00 EA Double-check
Bartlett Cove GLBA 70959 MA - Maintenance Support Building
GBA99
19,200 1475408 Fire Alarm Signaling System, Addressable, Restorable, Commercial Monitoring Service1.00 EA
Bartlett Cove GLBA 70959 MA - Maintenance Support Building
GBA99
19,200 1475419 Fire Sprinkler System, Wet Pipe, 4.0 IN, Other, Heated Structure 1.00 EA Double-check
Bartlett Cove GLBA 73442 WT - Water Plant Building GBA15 1,960 1477852 Fire Sprinkler System, Wet Pipe, 6.0 IN 1.00 EA Double-check
Bartlett Cove GLBA QTY. 2 Dry Chemical, Qty. 2 73458 UC - Fuel / Gasoline Pump Building
GBA87
209 1477857
Fixed Fire Suppression System, Dry Chemical Suppression
System, Restorable, [QTY. 2]
2.00 EA
Dry Chemical, Qty. 2 (one inside and one outside), Combined Report Installed in
Bartlett Cove GLBA QTY. 2 Dry Chemical, Qty. 2 73460 UC - Oil Storage Building GBA92 621 1710099 Fixed Fire Suppression System, Dry Chemical Suppression
System, [QTY. 2]
2.00 EA Dry Chemical, Qty. 2
Bartlett Cove GLBA 92317 PD - Huna Tribal House - GBA140 3,500 1670706 Fire Alarm Signaling System, Addressable, Restorable, Other, Edwards EST-3X, GBA1401.00 EA Has ASD sample system w 8 ports
Bartlett Cove GLBA 92317 PD - Huna Tribal House - GBA140 3,500 1670711 Fire Sprinkler System, Dry Pipe, 10.0 IN, GBA140 1.00 EA Double-check, Victaulic
Bartlett Cove GLBA 92867 TA - Water Tank Fire Pump Building
GBA11
160 1477859 Fire Alarm Signaling System, Conventional, Other 1.00 EA
Bartlett Cove GLBA 92867 TA - Water Tank Fire Pump Building
GBA11
160 1478712 Fire Sprinkler System, Wet Pipe 1.00 EA
Bartlett Cove GLBA
Test outlets on back of building
92867 TA - Water Tank Fire Pump Building
GBA11
160 1477858 Fire Pump System, Electric Motor Drive, 500.0 GPM, 40.0 HP 1.00 EA
500 GPM, Test outlets on back of building
Bartlett Cove GLBA Visual Only, Reports to Panel in Loc. 92317 247506 PD - Huna Tribal House Annex - GBA137 800 1670697 Fire Alarm Signaling System, Addressable, Restorable, GBA137, Reports to Panel in Loc. 923171.00 EA
Visual Only, Reports to Panel in Loc. 92317
Bartlett Cove GLBA Visual Only, Riser in
Loc. 92317 247506 PD - Huna Tribal House Annex - GBA137 800 1670682 Fire Sprinkler System, Dry Pipe, GBA137, Riser in Loc. 92317 1.00 EA
Visual Only, Riser in Loc.
92317
King Salmon KATM 1168 KS - King Salmon Quadplex Q51 5,280 256172 Fire Sprinkler System, Wet Pipe, 2.0 IN, KS Quadplex Q51 1.00 EA Double-check
King Salmon KATM 38428 KS B19 Utility Plant Building 2,016 1477618 Fire Sprinkler System, Wet Pipe, 3.0 IN, No Antifreeze Used, Not Sprinkled, Jockey BP1.00 EA
NOT SPRINKLED, Pipe (no heads), Has Backflow
Preventer Only. Ames, Double
Check, Jockey Pump Backlow, 1.25"
King Salmon KATM 38428 KS B19 Utility Plant Building 2,016 1477635 Fire Pump System, Electric Motor Drive, 150.0 GPM, 15.0 HP 1.00 EA 150 GPM Pump
Brooks Camp KATM 88200 VRAA-SHOP W-1 4,546 1027356 Fire Alarm Signaling System, Addressable, Restorable, None, Dialer not Connected1.00 EA
King Salmon KATM 93634 KS - King Salmon Housing Rainbow
Ridge Road FAA158 2,549 351579 Fire Alarm Signaling System, Conventional, NonRestorable, KS Q1581.00 EA
King Salmon KATM 93634 KS - King Salmon Housing Rainbow
Ridge Road FAA158 2,549 1693229 Fire Sprinkler System, Wet Pipe, 1.0 IN, FAA158 1.00 EA
Installed in 2017. Ames, Double Check, 1"
King Salmon KATM 93637 KS - Seasonal and Transient Dormitory
Q01 6,800 1477625 Fire Alarm Signaling System, Conventional, NonRestorable, Government Monitoring Service1.00 EA
Park
Park
System to be
Inspected
Backflow
Preventer
COMMENTS
FMSS
Location
Number
FMSS Location Name
Approx.
Building sq.footage
Asset Asset Description Quantity Unit of
Measure
NOTES
King Salmon KATM 93637
KS - Seasonal and Transient Dormitory
Q01 (previously B70, use Q01 Dormitory on report)
6,800 1028959 Fire Sprinkler System, Wet Pipe, 3.0 IN, No Antifreeze Used, B70 Dorm1.00 EA
King Salmon KATM 93639 KS B10 King Salmon Maintenance
Building 4,500 1449581 Fire Alarm Signaling System, Addressable, Restorable, Government Monitoring Service, Fire Alarm Sign1.00 EA
King Salmon KATM 93639 KS B10 King Salmon Maintenance
Building 4,500 1739192 Fire Pump System, Electric Motor Drive, 250.0 GPM, 17.2 HP, 215.01.00 EA 250 GPM Pump
King Salmon KATM 101238 KS - King Salmon Duplex FAA162/163 3,941 1009402 Fire Alarm Signaling System, Conventional, NonRestorable, Annunciators and Horns INOPERABLE, KS-Q1621.00 EA
Brooks Camp KATM 101238 KS - King Salmon Duplex FAA162/163 3,941 1693231 Fire Sprinkler System, Wet Pipe, 1.0 IN, FAA162/163 1.00 EA Installed in 2017. Ames, Double Check, 1"
King Salmon KATM 101239 KS - King Salmon Housing White Sox
Way FAA150 2,100 1009266 Fire Alarm Signaling System, Conventional, NonRestorable, KS FAA1501.00 EA
King Salmon KATM 101239 KS - King Salmon Housing White Sox
Way FAA150 2,100 1693233 Fire Sprinkler System, Wet Pipe, 1.0 IN, FAA150 1.00 EA
Installed in 2017. Ames, Double Check, 1"
King Salmon KATM 102827 KS - King Salmon Duplex FAA143/144 3,941 1009357 Fire Alarm Signaling System, Conventional, NonRestorable, KS-Q142/1431.00 EA
King Salmon KATM 102827 KS - King Salmon Duplex FAA143/144 3,941 1693237 Fire Sprinkler System, Wet Pipe, 1.0 IN, FAA143/144 1.00 EA Installed in 2017. Ames, Double Check, 1"
Brooks Camp KATM 225709 VH - Valley Road Housing Bunk House
VR10
1,245 1739191 Fire Alarm Signaling System, Addressable, Government Monitoring Service, Bell and Strobe, VR101.00 EA
Brooks Camp KATM 225709 VH - Valley Road Housing Bunk House
VR10
1,245 1601417 Fire Sprinkler System, Wet Pipe, 1.0 IN, VR10 1.00 EA
King Salmon KATM 230268 KS - King Salmon Housing Rainbow
Ridge Road FAA164 2,011 1027784 Fire Alarm Signaling System, Conventional, NonRestorable, FAA 1641.00 EA
King Salmon KATM 230268 KS - King Salmon Housing Rainbow
Ridge Road FAA164 2,011 1693239 Fire Sprinkler System, Wet Pipe, 1.0 IN, FAA164 1.00 EA
Installed in 2017. Ames, Double Check, 1"
King Salmon KATM 230269 KS - King Salmon Housing Mosquito
Coast Road FAA139 2,100 1027783 Fire Alarm Signaling System, Conventional, NonRestorable, FAA 1391.00 EA
King Salmon KATM 230269 KS - King Salmon Housing Mosquito
Coast Road FAA139 2,100 1693243 Fire Sprinkler System, Wet Pipe, 1.0 IN, FAA139 1.00 EA
Installed in 2017. Ames, Double Check, 1"
Brooks Camp KATM 234791 VR02 Valley Road Area Utility Building 840 1477628 Fire Alarm Signaling System, Conventional, CO Detector and strobe present, VR021.00 EA
King Salmon KATM 241900 KS - King Salmon Housing FAA161 2,100 1449813 Fire Alarm Signaling System, Conventional, NonRestorable, KS FAA1611.00 EA
King Salmon KATM 241900 KS - King Salmon Housing FAA161 2,100 1693244 Fire Sprinkler System, Wet Pipe, 1.0 IN, FAA161 1.00 EA Installed in 2017. Ames, Double Check, 1"
King Salmon KATM 254692 KS - King Salmon Duplex FAA136/137 3,941 1764864 Fire Alarm Signaling System, Conventional, NonRestorable, FAA 136/1371.00 EA
King Salmon KATM 254693 KS - King Salmon Housing FAA147 3,084 1764868 Fire Alarm Signaling System, Conventional, NonRestorable, KS Housing FAA1471.00 EA
King Salmon KATM 256333 KS King Salmon FAA Comserfac (aka FAA 303) 2,601 1787821 Fire Sprinkler System, Wet Pipe, 4.0 IN, KS FAA Comserfac (aka FAA 303)1.00 EA
King Salmon KATM 256333 KS King Salmon FAA Comserfac (aka FAA 303) 2,601 1787817 Fire Alarm Signaling System, Conventional, NonRestorable, None, KS FAA Comserfac (aka FAA 303)1.00 EA
King Salmon KATM 258859 KS - King Salmon Duplex 134 1,450 1787814 Fire Alarm Signaling System, Conventional, NonRestorable, None, FAA 135A1.00 EA
King Salmon KATM 258860 KS - King Salmon Residence 149 2,035 1787815 Fire Alarm Signaling System, Conventional, NonRestorable, None, FAA 1491.00 EA
King Salmon KATM 258861 KS - King Salmon Residence 138 2,071 1787816 Fire Alarm Signaling System, Conventional, NonRestorable, None, FAA 1381.00 EA
King Salmon KATM 258862 KS - King Salmon Utility Building #301 2,208 1787823 Fire Sprinkler System, Wet Pipe, 2.5 IN, KS Utility Building #301 1.00 EA
King Salmon KATM 258862 KS - King Salmon Utility Building #301 2,208 1787818 Fire Alarm Signaling System, Conventional, NonRestorable, None, KS Utility Building #3011.00 EA
King Salmon KATM 258863 KS - King Salmon Water Treatment Plant Building #52 2,061 1787820 Fire Sprinkler System, Wet Pipe, 4.0 IN, KS WTP #52 1.00 EA
King Salmon KATM 258863 KS - King Salmon Water Treatment Plant Building #52 2,061 1787819 Fire Alarm Signaling System, Conventional, Restorable, None, KS WTP #521.00 EA
Park
Park
System to be
Inspected
Backflow
Preventer
COMMENTS
FMSS
Location
Number
FMSS Location Name
Approx.
Building sq.footage
Asset Asset Description Quantity Unit of
Measure
NOTES
Seward KEFJ 1039 DT: Visitor Center 4,257 1739091 Fire Alarm Signaling System, Addressable, Restorable, Government Monitoring Service, DT: Visitor Cen1.00 EA
Seward KEFJ 1039 DT: Visitor Center 4,257 1737808 Fire Sprinkler System, Wet Pipe, 4.0 IN, DT: Visitor Center 1.00 EA Ames, Colt 200, 4" RJ-2650
Seward KEFJ 1039 DT: Visitor Center 4,257 1739108 Fire Sprinkler System, Dry Pipe, 4.0 IN, DT: Visitor Center 1.00 EA see asset #1737808
Seward KEFJ 99895 DT: Park Head Quarters Building 8,088 1477348 Fire Alarm Signaling System, Addressable, Restorable, Commercial Monitoring Service, DT: Park HQ Bui1.00 EA
Seward KEFJ 99895 DT: Park Head Quarters Building 8,088 1464595 Fixed Fire Suppression System, Clean Agent System, Restorable, FM-200 System; DT: Park HQ Building1.00 EA
Seward KEFJ 99895 DT: Park Head Quarters Building 8,088 1477351 Fire Sprinkler System, Wet Pipe, 2.5 IN, DT: Park HQ Building 1.00 EA
Skagway KLGO 68537 White Pass Depot Visitor Center 6,162 344995 Fire Alarm Signaling System, Conventional, NonRestorable, 22 standard and 1 duct Heat Detectors1.00 EA
Skagway KLGO 68537 White Pass Depot Visitor Center 6,162 1020922 Fire Extinguishing Sys, Dry Pipe, 6162 SF, White Pass Depot (Visitor Center)1.00 EA
Skagway KLGO Visual Only, Riser in
Loc. 68537 68538 White Pass Admin. Building 6,642 1157776 Fire Sprinkler System, Dry Pipe, Shared with Loc. 68537, White Pass Admin. Builiding1.00 EA
Visual Only, Riser in Loc.
68537
Skagway KLGO 68540 Boas Tailor & Furrier Shop 1,632 345125 Fire Alarm Signaling System, Conventional, NonRestorable, Government Monitoring Service1.00 EA
Skagway KLGO 68540 Boas Tailor & Furrier Shop 1,632 1157779 Fire Sprinkler System, Dry Pipe, Riser in Loc. #232875, Boas Tailor & Furrier Shop1.00 EA
Skagway KLGO 68542 Boss Bakery 987 1475879 Fire Alarm Signaling System, Addressable, Restorable, Government Monitoring Service1.00 EA
Skagway KLGO 68542 Boss Bakery 987 170259 Fire Sprinkler System, Dry Pipe, 4.0 IN, Boss Bakery 1.00 EA
Skagway KLGO 68543 Verbauwhedes Cigar Store and
Confectionary 690 344955 Fire Alarm Signaling System, Addressable, Restorable, Government Monitoring Service1.00 EA
Skagway KLGO 68543 Verbauwhedes Cigar Store and
Confectionary 690 1157780 Fire Sprinkler System, Dry Pipe, Riser in Loc. 232875, Verb. Cigar Store1.00 EA
Skagway KLGO Visual Only, Reports to Panel in Loc. 68543 68545 Verbauwhedes Cribs 401 1475922 Fire Alarm Signaling System, Addressable, Report to Panel at Loc685431.00 EA
Visual Only, Reports to Panel in Loc. 68543
Skagway KLGO Visual Only, Riser in
Loc. 232875 68545 Verbauwhedes Cribs 401 1021160 Fire Sprinkler System, Dry Pipe, Riser in Loc. 232875, Verb Crib 1.00 EA
Visual Only, Riser in Loc.
232875
Skagway KLGO 68547 Peniel Mission QMIS#00000001 2,113 339150 Fire Alarm Signaling System, Conventional, NonRestorable, Government Monitoring Service, Peniel Miss1.00 EA
Skagway KLGO 68547 Peniel Mission QMIS#00000001 2,113 1157788 Fire Sprinkler System, Dry Pipe, 4.0 IN, Peniel Mission QMIS#000000011.00 EA
Skagway KLGO Visual Only, Reports to Panel in Loc. 88521 68631 Pantheon Saloon 2,269 341946 Fire Alarm Signaling System, Conventional, NonRestorable, Reports to Panel in Loc.885211.00 EA
Visual Only, Reports to Panel in Loc. 88521
Skagway KLGO Visual Only, Riser in
Loc. 88521 68631 Pantheon Saloon 2,269 1157787 Fire Sprinkler System, Dry Pipe, System Riser in Loc. 88521, Pantheon Saloon1.00 EA
Visual Only, Riser in Loc.
88521
Skagway KLGO 68636 Pacific Clipper Line Office 2,414 344980 Fire Alarm Signaling System, Addressable, Connects to Panel in Loc. 68655, Pacific Clipper1.00 EA
Skagway KLGO Visual Only, (sprinkler is part of 68651) 68636 Pacific Clipper Line Office 2,414 1157777 Fire Sprinkler System, Dry Pipe, Riser in Loc. 232875, Pacific Clipper Line Office1.00 EA
Skagway KLGO Visual only, Reports to
Panel in 68647 68642
Moore House Outbuilding A (Chicken
Coop) 231 1476184 Fire Alarm Signaling System, Conventional, NonRestorable, Reports to Panel Loc686471.00 EA
Visual only, Reports to Panel in
Loc. 68647
Skagway KLGO N/A no SP, backflow only 68642 Moore House Outbuilding A (Chicken
Coop) 231 1021266 Fire Sprinkler System, Dry Pipe, 2.5 IN, Moore House Outbuilding A (Chicken Coop)1.00 EA
No Suppression System, Has
Backflow Preventer Only.
Ames/DC/2.5 inch
Skagway KLGO 68647 James Bernard (Ben) Moore House 1,660 340107 Fire Alarm Signaling System, Conventional, NonRestorable, Government Monitoring Service1.00 EA
Skagway KLGO Visual Only, Riser in
Loc. 68642 68647 James Bernard (Ben) Moore House 1,660 1477202 Fire Sprinkler System, Dry Pipe, Riser in Loc. 68642, Moore House1.00 EA
Visual Only, Riser in Loc.
68642
Skagway KLGO Visual Only, Reports to Panel in 68647 68648 Captain William Moore Cabin 255 1477205 Fire Alarm Signaling System, Conventional, NonRestorable, Report to Panel in Loc. 686471.00 EA
Visual Only, Reports to Panel in
Loc. 68647
Skagway KLGO Visual Only, Riser in
Loc. 68642 68648 Captain William Moore Cabin 255 1157782 Fire Sprinkler System, Dry Pipe, Riser in Loc. 68642, Captain William Moore Cabin1.00 EA
Visual Only, Riser in Loc.
68642
Skagway KLGO 68651 Mascot Saloon 3,750 345798 Fire Alarm Signaling System, Conventional, NonRestorable, Government Monitoring Service, Count Inclu1.00 EA
Skagway KLGO 68651 Mascot Saloon 3,750 1157778 Fire Sprinkler System, Dry Pipe, Riser in Loc. #232875, Mascot Saloon1.00 EA
Skagway KLGO 68653 Lynch & Kennedy Haberdashery & Dry
Goods Store 3,512 345010 Fire Alarm Signaling System, Addressable, Restorable, Government Monitoring Service1.00 EA
Skagway KLGO 68653 Lynch & Kennedy Haberdashery & Dry
Goods Store 3,512 1157783 Fire Sprinkler System, Dry Pipe, 4.0 IN, Lynch & Kennedy Haberdashery & Dry Goods Store1.00 EA
Skagway KLGO 68653 Lynch & Kennedy Haberdashery & Dry
Goods Store 3,512 1479951 Fire Sprinkler System, Deluge, 2.0 IN, Lynch & Kennedy Haberdashery & Dry Goods Store1.00 EA
Skagway KLGO Visual Only, Reports to Panel in Loc. 68636 68655 Hern Liquor Store 430 1477282 Fire Alarm Signaling System, Addressable, Restorable, Government Monitoring Service1.00 EA
Visual Only, Reports to Panel in Loc. 68636
Skagway KLGO Visual Only, Riser in
Loc. 232875 68655 Hern Liquor Store 430 1021269 Fire Sprinkler System, Dry Pipe, Riser in Loc. 232875, Hern Liquor Store1.00 EA
Visual Only, Riser in Loc.
232875
Skagway KLGO 68658 Martin Itjen House 840 341967 Fire Alarm Signaling System, Addressable, Restorable, Government Monitoring Service, Martin Itjen hs1.00 EA
Skagway KLGO 68658 Martin Itjen House 840 1157785 Fire Sprinkler System, Dry Pipe, 2.5 IN, Martin Itjen House 1.00 EA
Skagway KLGO 68668 Maintenance Shop 5,564 341725 Fire Alarm Signaling System, Conventional, NonRestorable, Government Monitoring Service, Dialers to1.00 EA
Skagway KLGO 68668 Maintenance Shop 5,564 1157792 Fire Sprinkler System, Dry Pipe, 4.0 IN, Maintenance Shop 1.00 EA Watts/A32660/RP
Park
Park
System to be
Inspected
Backflow
Preventer
COMMENTS
FMSS
Location
Number
FMSS Location Name
Approx.
Building sq.footage
Asset Asset Description Quantity Unit of
Measure
NOTES
Skagway KLGO Visual Only, (alarm is part of 68668) 68676 Maintenance Garage 1,560 1477314 Fire Alarm Signaling System, Conventional, NonRestorable, Reports to Panel in Loc. 686681.00 EA
Visual Only, (alarm is part of
68668 maintenance shop)
Skagway KLGO Visual Only, (sprinkler is part of 68668) 68676 Maintenance Garage 1,560 1021267 Fire Sprinkler System, Dry Pipe, Extension of Loc. 68668 Dry Pipe, Maintenance Garage1.00 EA
Visual Only, (sprinkler is part of
68668 maintenance shop)
Skagway KLGO 68688 Duplex QMIS#00000006 (old name Admin
Site Dorm QMIS#00000006) 2,336 1157790 Fire Sprinkler System, Residential, 2.0 IN, Admin Site Dorm QMIS#000000061.00 EA
Skagway KLGO 88521 Red Front 2,554 1477323 Fire Alarm Signaling System, Conventional, NonRestorable, Government Monitoring Service, 26 standard1.00 EA
Skagway KLGO 88521 Red Front 2,554 1021246 Fire Sprinkler System, Dry Pipe, 4.0 IN, Riser Valve 2 EA, Shared with Loc. 68311, Red Front1.00 EA Ames/2000SS/4 inch
Skagway KLGO
Visual Only, (sprinkler and alarm are in
68668)
100314 Curatorial Storage Building 1,620 1021268 Fire Sprinkler System, Dry Pipe, Share with and Riser in Loc. 68668, Curitorial Building1.00 EA Visual Only, (sprinkler is part of
68668 maintenance shop)
Skagway KLGO Visual Only, Reports to Panel in Loc. 68658 108751 Jeff. Smith's Parlor Museum Building 990 1018197 Fire Alarm Signaling System, Addressable, Commercial Monitoring Service, Jeff. Smith's Parlor Museum1.00 EA
Visual Only, Reports to Panel in Loc. 68658
Skagway KLGO Visual Only, Riser located in 68658 108751 Jeff. Smith's Parlor Museum Building 990 1018188 Fire Sprinkler System, Dry Pipe, 3.0 IN, Riser in Loc. #68658, Jeff. Smith's Parlor Museum1.00 EA
Visual Only, Riser located in
68658
Skagway KLGO 108753 Arctic Meat Company 2,948 1011383 Fire Alarm Signaling System, Arctic Meat Company protects 228477 YMCA1.00 EA
Skagway KLGO 108753 Arctic Meat Company 2,948 1011382 Fire Sprinkler System, Dry Pipe, 4.0 IN, Other, Arctic Meat Company protects 228477 YMCA1.00 EA
Skagway KLGO
Visual Only, Reports to Panel in Loc.
115478
115476 Cedar House QMIS#00000008 1,238 see
1670975
Fire Alarm Signaling System, Addressable, Honeywell Silent knight Cedar House Garage
1.00 EA
Visual Only, Reports to Panel in Loc. 115478; installed in
Skagway KLGO Visual Only, Riser in
Loc. 115478 115476 Cedar House QMIS#00000008 1,238 1440928 Fire Sprinkler System, Dry Pipe, Cedar House (system in garage)1.00 EA
Visual Only, Riser in Loc.
115478; installed in 2017
Skagway KLGO 115478 Cedar House Garage 672 1670975 Fire Alarm Signaling System, Addressable, Honeywell Silent knight Cedar House Garage
1.00 EA
Skagway KLGO 115478 Cedar House Garage 672 1440939 Fire Sprinkler System, Dry Pipe, Cedar House Garage;
installed in 2017
1.00 EA Forward Flow Capable
Park
Park
System to be
Inspected
Backflow
Preventer
COMMENTS
FMSS
Location
Number
FMSS Location Name
Approx.
Building sq.footage
Asset Asset Description Quantity Unit of
Measure
NOTES
Skagway KLGO
Visual Only, Reports to Panel in Loc.
108753
228477 YMCA Building 1,890 1015783 Alarm Sys, Fire, YMCA Building, Panel in 108753 Arctic Meat Co.1.00 EA
Visual Only, Reports to Panel in Loc. 108753; Installed in
Skagway KLGO ???
Visual Only, Riser in
Loc. 108753
BP serves both the
Arctic MC and the YMCA
228477 YMCA Building 1,890 1015782 Fire Sprinkler System, Dry Pipe, YMCA Building, Riser in 108753 Arctic Meat Co.1.00 EA Visual Only, Riser in Loc. 108753.
Ames/2000SS/4 inch
Skagway KLGO pit for 68651 Mascot
Saloon SP 232875 Mascot Saloon Complex Valve Pit Shed 106 1101081 Fire Sprinkler System, Dry Pipe, 4.0 IN, 3 Sprinkler Tree Riser 1.00 EA
Skagway KLGO 236885 4th Avenue Dorm QMIS#00KLGO10 4,917 1776410 Fire Alarm Signaling System, Addressable, Restorable, Government Monitoring Service, 4th Avenue Dorm1.00 EA
Skagway KLGO 236885 4th Avenue Dorm QMIS#00KLGO10 4,917 1756424 Fire Sprinkler System, Preaction, 6.0 IN, 2 Fire Sys. but 1 BFP, 4th Avenue Dorm1.00 EA
Skagway KLGO 236885 4th Avenue Dorm QMIS#00KLGO10 4,917 1776409 Fire Sprinkler System, Dry Pipe, 6.0 IN, 2 Fire Sys. but 1 BFP, 4th Avenue Dorm1.00 EA
Skagway KLGO Visual Only, Riser in
Loc. 68658 241353
Jeff. Smith's Parlor Museum Utility
Building 105 1480671
Fire Sprinkler System, Dry Pipe, 3.0 IN, Riser in Loc.
#68658, Jeff.
Smith's Parlor Museum UtilityBu
1.00 EA
Visual Only, Riser in Loc.
68658
Port Alsworth LACL 94890 PA-19 Reboubt Duplex 1,212 1173618 Fire Sprinkler System, Residential, 1.5 IN, Wet Pipe Shot Gun Riser.1.00 EA
Port Alsworth LACL 94905 PA-17 Tanalian Duplex 1,212 1173614 Fire Sprinkler System, Residential, 1.5 IN, Wet Pipe Shot Gun Riser1.00 EA
Port Alsworth LACL 94906 PA-18 Iliamna Duplex 1,212 1173616 Fire Sprinkler System, Residential, 1.5 IN, Wet Pipe Shot Gun Riser.1.00 EA
Sitka SITK
Vesda
System requiring canned smoke
Has Vesda System requiring canned smoke 64367
Sitka National Historical Park Visitor
Center 13,240 345995
Fire Alarm Signaling System, Addressable, Commercial
Monitoring Service, Vesda
1.00 EA
Has Vesda System requiring canned smoke [Alarm panel replaced 2021]
Sitka SITK 64367 Sitka National Historical Park Visitor
Center 13,240 289699 Fire Sprinkler System, Dry Pipe, 6.0 IN, Automatic Sprinkler, Unheated Totem Hall1.00 EA
Sitka SITK 64367 Sitka National Historical Park Visitor
Center 13,240 1475636 Fire Sprinkler System, Wet Pipe, 6.0 IN, Automatic Sprinkler 1.00 EA
Sitka SITK
Vesda
System requiring canned smoke
Has Vesda System requiring canned smoke
64372 Russian Bishop's House 7,800 164168 Fire Alarm Signaling System, Addressable, Commercial Monitoring Service, Vesda + Silent Knight 51041.00 EA Has Vesda System requiring canned smoke
Sitka SITK 64372 Russian Bishop's House 7,800 164164 Fire Extinguishing Sys, Dry Pipe, 7800 SF, Russian Bishop's 1.00 EA
Sitka SITK 64374 Priests' Quarters 1,651 1478418 Fire Alarm Signaling System, Addressable, Commercial Monitoring Service (includes #164170 Smoke, EST2)1.00 EA [Alarm panel replaced 2021]
Sitka SITK 64374 Priests' Quarters 1,651 164185 Fire Sprinkler System, Dry Pipe, 2.5 IN, Preist Quarters 1.00 EA
Sitka SITK 64540 The Old School 1,399 164182 Fire Alarm Signaling System, Addressable, Commercial Monitoring Service, Interface to GEM-P32001.00 EA [Alarm panel replaced 2021]
Sitka SITK 64540 The Old School 1,399 164184 Fire Extinguishing Sys, Dry Pipe, 1280 SF, Old School House 1.00 EA
Kotzebue WEAR 42579 Residence 154 B SFU Corner House 419 1693108 Fire Sprinkler System, Residential, 1.0 IN, Glycol, Residence 154 B1.00 EA Installed in 2016 - verify inventory
Kotzebue WEAR 42579 Residence 154 B SFU Corner House 419 1739385 Fire Pump System, Electric Motor Drive, 1.5 HP, Residence 154B1.00 EA Installed in 2016 - verify inventory
Kotzebue WEAR 84667 Northwest Arctic Heritage Center 19,750 1475561 Fire Alarm Signaling System, Addressable, Restorable, Government Monitoring Service1.00 EA
Kotzebue WEAR 84667 Northwest Arctic Heritage Center 19,750 1475562 Fixed Fire Suppression System, Clean Agent System, Restorable, HFC-227ea Clean agent1.00 EA Clean Agent System
Kotzebue WEAR 84667 Northwest Arctic Heritage Center 19,750 1475564 Fire Sprinkler System, Wet Pipe, Storage Tank/Fire Pump in Mech Room1.00 EA
Kotzebue WEAR 84667 Northwest Arctic Heritage Center 19,750 1139570 Fire Pump System, Electric Motor Drive, 250.0 GPM, 17.2 HP, 215JP Motor Size1.00 EA 250 GPM Pump
Kotzebue WEAR 108797 Duplex 297 C, D 2,545 1478582 Fire Sprinkler System, Residential, 2.0 IN 1.00 EA
Kotzebue WEAR 237769 Automotive Shop 297E 1,644 1475524 Fire Alarm Signaling System, Addressable, Restorable, Government Monitoring Service1.00 EA
Kotzebue WEAR 244067 Duplex 152 A, B 2,200 1475559 Fire Sprinkler System, Residential, 1.25 IN 1.00 EA
Kotzebue WEAR 10108795 Residence 297B, SFU 1,585 1475554 Fire Sprinkler System, Residential, 2.0 IN 1.00 EA
Kennecott WRST 12008 BPKNHLX Kennecott Mill Building 34,470 1692533
Fire Alarm Signaling System, Addressable, Restorable, Commercial Monitoring Service, Monitored by (analog)
Guardian Security
1.00 EA
Kennecott WRST 12009 BPKNHLX Kennecott Leach Plant 23,245 1692537
Fire Alarm Signaling System, Addressable, Restorable, Commercial Monitoring Service, Monitored by (analog)
Guardian Security
1.00 EA
Kennecott WRST 12010 BPKNHLX Kennecott Machine Shop 4,100 1692541 Fire Alarm Signaling System, Addressable, Restorable, Commercial Monitoring Service, Monitored by (a1.00 EA
Kennecott WRST 12011 BPKNHLX Kennecott School New 1,160 1692547 Fire Alarm Signaling System, Addressable, Restorable, Commercial Monitoring Service, Monitored by (a1.00 EA
Kennecott WRST 12012 BPKNHLX Kennecott West Bunkhouse 11,384 1692552 Fire Alarm Signaling System, Addressable, Restorable, Commercial Monitoring Service, Monitored by (a1.00 EA
Kennecott WRST 12013 BPKNHLX Kennecott Recreation Hall 2,027 1692618 Fire Alarm Signaling System, Addressable, Restorable, Commercial Monitoring Service, Monitored by (a1.00 EA
Kennecott WRST 12013 BPKNHLX Kennecott Recreation Hall 2,027 1692621 Fire Sprinkler System, Wet Pipe, 2 Sprinklers, Butterball Slow Close BB-SC 100, Drained in Winter1.00 EA
Kennecott WRST 12013 BPKNHLX Kennecott Recreation Hall 2,027 1692623 Fire Pump System, Electric Motor Drive, 50.0 GPM, 3.0 HP 1.00 EA 50 GPM Pump
Park
Park
System to be
Inspected
Backflow
Preventer
COMMENTS
FMSS
Location
Number
FMSS Location Name
Approx.
Building sq.footage
Asset Asset Description Quantity Unit of
Measure
NOTES
Kennecott WRST 12014 BPKNHLX Kennecott Store Warehouse 13,980 1692624 Fire Alarm Signaling System, Addressable, Restorable, Commercial Monitoring Service, Monitored by (a1.00 EA
Kennecott WRST 12014 BPKNHLX Kennecott Store Warehouse 13,980 1692628 Fire Sprinkler System, Wet Pipe, 2 Sprinklers, Butterball Slow Close BB-SC 100, Drained in Winter1.00 EA
Kennecott WRST 12014 BPKNHLX Kennecott Store Warehouse 13,980 1692631 Fire Pump System, Electric Motor Drive, 50.0 GPM, 3.0 HP 1.00 EA 50 GPM Pump
Kennecott WRST 12015 BPKNHLX Kennecott General Managers
Office 2,175 1692634 Fire Alarm Signaling System, Addressable, Restorable, Commercial Monitoring Service, Monitored by (a1.00 EA
Kennecott WRST 12018 BPKNHLX Kennecott Power Plant 12,882 1692637 Fire Alarm Signaling System, Addressable, Restorable, Commercial Monitoring Service, Monitored by (a1.00 EA
Kennecott WRST 12021 BPKNHLX Kennecott Refriger Plant 778 1692640 Fire Alarm Signaling System, Addressable, Restorable, Commercial Monitoring Service, Monitored by (a1.00 EA
Kennecott WRST 32646 BPKNHLX Kennecott Old School 963 1692646 Fire Alarm Signaling System, Addressable, Restorable, Commercial Monitoring Service, Monitored by (a1.00 EA
Copper
Center WRST 32888 BP HQ COMFORT STATION 816 530555 Fire Extinguishing System,, Dry Pipe, Comfort Station 1.00 EA
Copper
Center WRST 32889 BPVC HQ VISITOR CENTER 7,462 349623 Fire Alarm Signaling System, Addressable, Restorable, Commercial Monitoring Service, Monitored by Gu1.00 EA
Copper
Center WRST 32889 BPVC HQ VISITOR CENTER 7,462 303916 Fire Extinguishing System, 2535 SF, Dry Pipe , HQVisitor Center 1.00 EA
Copper
Center
WRST
Visual Only, Reports to Panel in Loc. 32889 32890 BP HQ EXHIBIT BUILDING 1,680 1475407 Fire Alarm Signaling System, Addressable, Restorable, Panel Loc328891.00 EA
Visual Only, Reports to Panel in Loc. 32889
Copper
Center WRST 32890 BP HQ EXHIBIT BUILDING 1,680 530554 Fire Extinguishing System, 1816.00 SF, Dry Pipe, Exhibit bldg. 1.00 EA
Copper
Center WRST 32891 BP HQ THEATER 1,620 1475042 Fire Alarm Signaling System, Addressable, Restorable, Commercial Monitoring Service, Panel Loc32889.1.00 EA
Copper
Center WRST 32891 BP HQ THEATER 1,620 530553 Fire Extinguishing System,, Dry Pipe, HQ Theater 1.00 EA
Copper
Center WRST 32892 BA HQ ADMINISTRATIVE MAIN OFFICE 7,369 349486 Fire Alarm Signaling System, Addressable, Restorable, Commercial Monitoring Service, Dialer for 32881.00 EA
Copper
Center WRST 32892 BA HQ ADMINISTRATIVE MAIN OFFICE 7,369 334202 Fire Extinguishing System, Dry Pipe , HQ Main Office 1.00 EA
Copper
Center WRST 32892 BA HQ ADMINISTRATIVE MAIN OFFICE 7,369 1475421 Fire Sprinkler System, Wet Pipe 1.00 EA
Park
Park
System to be
Inspected
Backflow
Preventer
COMMENTS
FMSS
Location
Number
FMSS Location Name
Approx.
Building sq.footage
Asset Asset Description Quantity Unit of
Measure
NOTES
Copper
Center WRST 32893 BA HQ UTILITY BUILDING 1,756 349537 Fire Alarm Signaling System, Addressable, Restorable, Commercial Monitoring Service, Dialer Loc328921.00 EA
Copper
Center
WRST
BP is in the fire pump pit
32893 BA HQ UTILITY BUILDING 1,756 1475051
Fire Sprinkler System, Dry Pipe includes #349523
Compressor
1.00 EA Fire Pump Pit, Watts 909, 2"
Copper
Center
WRST 32893 BA HQ UTILITY BUILDING 1,756 349545
Fire Pump System, Electric Motor Drive, 500.0 GPM, 45.0
HP includes #349531 Pump Disconnect and #349535
Pump Controller (update asset specs for 349535 with BP)
1.00 EA 500 GPM Pump
Copper
Center
WRST
system being converted to dry pipe?
38167
BQ GLENNALLEN DOI HOUSING A
DUPLEX
3,998 1475512 Fire Sprinkler System, Residential, 2.0 IN 1.00 EA system being converted to dry pipe summer 2022. PMIS
#309467
Copper
Center
WRST
system being converted to dry pipe?
38171
BQ GLENNALLEN DOI HOUSING B
FOURPLEX
5,764 349661 Fire Sprinkler System, Residential, 2.0 IN, Fire Water Pump, GLN 4plex1.00 EA system being converted to dry pipe summer 2022. PMIS
#309467
Kennecott WRST 82316
UELEC KENNECOTT ALTERNATIVE
ELECTRIC
160 1776608 Fixed Fire Suppression System, Dry Chemical Suppression System, Restorable, UELEC KENNECOTT ALTERNAT1.00 EA
Copper
Center
WRST 86005 BP HQ AHTNA CULTURAL CENTER 2,418 1474892
Fire Alarm Signaling System, Addressable, Restorable, Commercial Monitoring Service, Dialer Loc32892
1.00 EA
Copper
Center
WRST
system being converted to dry pipe?
86005 BP HQ AHTNA CULTURAL CENTER 2,418 1474897 Fire Sprinkler System, Wet Pipe, 3.0 IN 1.00 EA system being converted to dry pipe summer 2022. PMIS
#309467
Kennecott WRST 92090 BPKNHLX Kennecott Dairy Barn 2,688 1692661 Fire Alarm Signaling System, Addressable, Restorable, Commercial Monitoring Service, Monitored by (a1.00 EA
Kennecott WRST
Note: Location has changed from 226549
(2/5/25)
106846 Generator Bldg (Silk Stocking) 84 1692668
Fixed Fire Suppression System, Dry Chemical Suppression
System, NonRestorable, 2 - 212F glass bulb links, 1 manual release station, actuator gas cartridge
1.00 EA Dry Chemical
Kennecott WRST Alarm for 226549 &
82316 226549
BQKN KENNECOTT SILK STOCKING
COTTAGE 32D(32-19) GARAGE
287 1692665 Fire Alarm Signaling System, Conventional, Restorable, Commercial Monitoring Service, Monitored by 1.00 EA
Detection system for 226549 garage and 82316 generator system
Eagle YUCH 109243 00000101 EA Employee Housing Hilltop
House 1,209 1170273 Fire Sprinkler System, Residential, 1.5 IN, Glycol, Hilltop House 1.00 EA
Eagle YUCH 109243 00000101 EA Employee Housing Hilltop
House 1,209 1278699 Fire Pump System, Electric Motor Drive, 1.5 HP, Hilltop House 1.00 EA
KEY: Alarm
System
Sprinkler, Suppression
System
Backflow
Preventer
Clean
Agent/CO2
/Special
Hazards
Fire Pump
File details come from the government source that posted it. Updated .