B08_Attach_(2)_KALA_248432_FINAL_DRAWINGS_rev3.pdf

PDF 9 MB Posted

Attached to
KALA 248432 construct a fuel farm and dispensing
Solicitation number
140P2024R0069
Issued by

About this file

This document appears to be a set of technical drawings and specifications for constructing a fuel farm and dispensing system for the Kalaupapa settlement within the National Park Service (NPS) jurisdiction.

The key details include: installation of (4) 5,000 gallon above ground gasoline fuel storage tanks, (1) 5,000 gallon above ground diesel tank, fuel dispensing and tracking system, concrete pad and shelter, mechanical connections, underground data and electrical service, lighting, bollards, and access road. The project aims to serve the entire Kalaupapa settlement's fuel needs. The drawings provide detailed specifications for the tank configurations, piping, fuel dispensers, monitoring systems, and other site infrastructure. The related federal contract opportunity solicitation number is 140P2024R0069, issued by the NPS National Office, with a description to "construct a fuel farm and dispensing system" for the Kalaupapa settlement.

View the file

Other files

File Type Posted
Sol_140P2024R0069_Amd_0009.pdf PDF
3_Wage_Determination_HI20240001_11152024_0009.pdf PDF
Barge_Off_Load_2_0008.png PNG image
Barge_Off_load_0008.png PNG image
Sol_140P2024R0069_Amd_0008.pdf PDF
Barge_Off_Load_3_0008.png PNG image
Additional_Question_and_Answer_from_KALA_Fuel_Farm_project_0007.docx DOCX document
Sol_140P2024R0069_Amd_0007.pdf PDF
B11_Site_visit_Attendees_0006.pdf PDF
Sol_140P2024R0069_Amd_0006.pdf PDF
Sol_140P2024R0069_Amd_0005.pdf PDF
PM-PS_Consolodated_QA_RFI_log_NPS_Responses_0005.pdf PDF
KALA_Update_Fuel_Storage_Updated_Drawings_0005.pdf PDF
SECTION_33_56_10_-_AST_and_accessories_2024_0823_0005.pdf PDF
B08_Attach_7_Title_II_100__Final_Consultation_Letter_0004.pdf PDF
Consolodated_QA_RFI_log_NPS_Partial_Responses_0004.pdf PDF
Sol_140P2024R0069_Amd_0004.pdf PDF
B08_Attach_8__Title_II_100__Final_Drawings_with_Geotech_Info_0004.pdf PDF
Sol_140P2024R0069_Amd_0003.pdf PDF
Sol_140P2024R0069_Amd_0002.pdf PDF
Sol_140P2024R0069_Amd_0001.pdf PDF
B08_Attach_(3)_WD_HI20240001_dtd_20240719.pdf PDF
B08_Attach_(4)_Deliverables_LmtOnSubconRpt_REQD.xlsx XLSX spreadsheet
Sol_140P2024R0069.pdf PDF
B08_Attach_(1)KALA_248432_FINAL_SPECS.pdf PDF
B08_Attach_(5)_Solit_PSP_Vol_I_PastPerf_REQD.docx DOCX document
B08_Attach_(6)_Solit_PSP_Vol_II_GenRefs.doc DOC document
Show all 27

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Test Pit: TP-1

National Park Service (NPS)

Kalaupapa Fueling Station

Molokai'i Island, HI

Driller: National Park Service

Drill Method: Backhoe excavator, test pit

Sample Method: Bulk

Borehole Diameter: 5' x 10'

Figure: 1.1

MFA Job #:

Client:

629-011

MASON

Location: N 21°11'23.84" W 156°58'45.15"

Date/Time Begin : 06/10/21 @ 09:43

Date/Time Finish : 06/10/21 @ 11:50

Logged By: EN

Surface Conditions: Grass

Material Description

Bulk Sample: 1' bgs and 5' bgs

ML Brown sandy silt interbedded with highly weathered basaltic cobbles and boulders

GM Grades to red/brown silty gravel w/ sand interbedded with highly weathered basaltic cobbles and boulders

RX

Grey/blue igeneous basaltic rock, lightly weathered, lightly fractured

Excavation terminated upon excavator refusal at

5' bgs

Tests Performed

Gradation

Note: Pocket penetrometer (PP) readings taken in soft materials

PP: >4.5 TSF

PP: 3.5 TSF

Checked By: RTI

G W

T n o t e n c o u n t e r e d

S a m p l e

B l o w s p e r

F o o t

I n c h e s

D r i v e n

R e c o v e r y

D e p t h

F t

R e c o v e r e d

R

Q D

S a m p l e

M e t h o d

U S

C S o i l

C l a s s i f i c a t i o n

Test Pit: TP-2

National Park Service (NPS)

Kalaupapa Fueling Station

Molokai'i Island, HI

Driller: National Park Service

Drill Method: Backhoe excavator, test pit

Sample Method: Bulk

Borehole Diameter: 5' x 10'

Figure: 1.2

MFA Job #:

Client:

629-011

MASON

Location: N 21°11'23.86" W 156°58'44.38"

Date/Time Begin : 06/10/21 @ 12:00

Date/Time Finish : 06/10/21 @ 12:38

Logged By: EN

Surface Conditions: Grass

Material Description

Bulk Sample: 1' bgs and 5' bgs

ML Brown sandy silt interbedded with highly weathered basaltic cobbles and boulders

GM Grades to red/brown silty gravel w/ sand interbedded with highly weathered basaltic cobbles and boulders

RX

Grey/blue igeneous basaltic rock, lightly weathered, lightly fractured

Excavation terminated upon excavator refusal at

5' bgs

Tests Performed

Gradation

Note: Pocket penetrometer (PP) readings taken in soft materials

PP: 3,25 TSF

PP: >4.5 TSF

PP: 2.0 TSF

Checked By: RTI

G W

T n o t e n c o u n t e r e d

S a m p l e

B l o w s p e r

F o o t

I n c h e s

D r i v e

R e c o v e r y

D e p t h

F t

R e c o v e r e d

R

Q D

S a m p l e

M e t h o d

U S

C i l

C l a s s i f i c a t i

License Expiration Date 4/30/2024

Signature

THIS WORK WAS PREPARED BY ME OR

UNDER MY SUPERVISION AND

CONSTRUCTION OF THIS PROJECT

WILL BE UNDER MY OBSERVATION.

DE

NNIS I HIROTA

HAWAI I , U .S. A

LICENSED

PROFESSIONAL

ENGINEER

No. 3377-C

LFA

S

C.

LAND

O

LICENSED A

U.S.A

I,IAW

No.10544

SURVEYOR

MM

RO

H

E

PROFESSIONAL

A

L

ROMMEL C. OFALSA

Licensed Professional Land Surveyor

Certificate No. 10544 Exp. 04/30/24

This work was prepared by me or under my supervision

S

C.

LAND

O

LICENSED A

U.S.A

I,IAW

No.10544

SURVEYOR

MM

RO

H

E

PROFESSIONAL

A

L

ROMMEL C. OFALSA

Licensed Professional Land Surveyor

Certificate No. 10544 Exp. 04/30/24

S

C.

LAND

O

LICENSED A

U.S.A

I,IAW

No.10544

SURVEYOR

MM

RO

H

E

PROFESSIONAL

A

L

ROMMEL C. OFALSA

Licensed Professional Land Surveyor

Certificate No. 10544 Exp. 04/30/24

S

C.

LAND

O

LICENSED A

U.S.A

I,IAW

No.10544

SURVEYOR

MM

RO

H

E

PROFESSIONAL

A

L

ROMMEL C. OFALSA

Licensed Professional Land Surveyor

Certificate No. 10544 Exp. 04/30/24

S

C.

LAND

O

LICENSED A

U.S.A

I,IAW

No.10544

SURVEYOR

MM

RO

H

E

PROFESSIONAL

A

L

ROMMEL C. OFALSA

Licensed Professional Land Surveyor

Certificate No. 10544 Exp. 04/30/24

S

C.

LAND

O

LICENSED A

U.S.A

I,IAW

No.10544

SURVEYOR

MM

RO

H

E

PROFESSIONAL

A

L

ROMMEL C. OFALSA

Licensed Professional Land Surveyor

Certificate No. 10544 Exp. 04/30/24

Signature

THIS WORK WAS PREPARED BY ME OR

UNDER MY SUPERVISION AND

CONSTRUCTION OF THIS PROJECT

WILL BE UNDER MY OBSERVATION.

DE

NNIS I HIROTA

HAWAI I , U .S. A

LICENSED

PROFESSIONAL

ENGINEER

No. 3377-C

Signature

THIS WORK WAS PREPARED BY ME OR

UNDER MY SUPERVISION AND

CONSTRUCTION OF THIS PROJECT

WILL BE UNDER MY OBSERVATION.

DE

NNIS I HIROTA

HAWAI I , U .S. A

LICENSED

PROFESSIONAL

ENGINEER

No. 3377-C

DSGN. DRWN. CHKD. APPD.

THIS WORK WAS PREPARED BY ME OR

UNDER MY SUPERVISION AND

CONSTRUCTION OF THIS PROJECT WILL

BE UNDER MY OBSERVATION.

Signature Expiration Date of the License 04/30/24

S1

GENERAL NOTES AND

TYPICAL DETAILS

UNDER MY SUPERVISION AND

CONSTRUCTION OF THIS PROJECT WILL

BE UNDER MY OBSERVATION.

Signature Expiration Date of the License 04/30/24

S2

TYPICAL DETAILS

UNDER MY SUPERVISION AND

CONSTRUCTION OF THIS PROJECT WILL

BE UNDER MY OBSERVATION.

Signature Expiration Date of the License 04/30/24

SECTION RIGID FRAME

S4

THIS WORK WAS PREPARED BY ME OR

UNDER MY SUPERVISION AND

CONSTRUCTION OF THIS PROJECT WILL

BE UNDER MY OBSERVATION.

Signature Expiration Date of the License 04/30/24

SECTIONS

S5

DIESEL FUEL ABOVE

GROUND UL2085

STORAGE TANK,

5,000-GALLON

MINIMUM CAPACITY

GASOLINE FUEL

ABOVE GROUND

STORAGE TANK

UL 2085, 5,000-GALLON

MINIMUM CAPACITY

(TYP OF 4)

OUTLINE OF

CONCRETE PEDESTAL

(TYP OF 8)

OUTLINE OF

CONCRETE PEDESTAL

OUTLINE OF

STRUCTURE ROOF

ABOVE

FUEL DISPENSER,

2-PRODUCT, 2-HIGH

HOSE, 1-SIDED

REMOTE ALARM

HORN & LIGHT

BOLLARD, CONCRETE

FILLED (TYP)

11'-10"

(TYP) 4' MIN

(TYP)

EMERGENCY FUEL SHUT-OFF

BUTTON, MOUNT AT 48"

ABOVE FINISHED GRADE, MAX

OVERALL FUEL FARM

TANK ARRANGEMENT

ABOVE

NFPA PORTABLE FIRE

EXTINGUISHER 80B:C IN

CABINET WITH SIGNAGE ABOVE.

REMOTE ALARM

ACKNOWLEDGE

PANEL

AUTOMATIC TANK

GAUGE AND LEAK

MONITORING SYSTEM

CONTROLLER

PEDESTAL MOUNTED

FUEL TRACKING

SYSTEM

GASOLINE FUEL

ABOVE GROUND

UL2085 STORAGE TANK,

5,000-GALLON MINIMUM

CAPACITY (TYP OF 4).

TOTAL 20,000-GALLONS

DIESEL FUEL ABOVE

GROUND UL2085

STORAGE TANK,

TOTAL 5,000-GALLON

MINIMUM CAPACITY

1 2 3 41

NOTE: ALL FUEL TANKS SHALL BE

CLASSIFIED AS PROTECTED TANKS

(UL 2085) AS DEFINED BY NFPA 30

AND 30A.

NFPA 30A PORTABLE FIRE

EXTINGUISHER, DRY CHEMICAL

80B:C TYPE IN CABINET WITH

SIGNAGE ABOVE

NOTES:

1. ALL ABOVEGROUND TANKS SHALL BE UL2085, PROTECTED TANKS

FOR GASOLINE AND DIESEL FUEL STORAGE IN ACCORDANCE

WITH NFPA 30 AND 30A.

A. PROVIDE CENTRAL FUEL LEVEL AND LEAK MONITORING

SYSTEM FOR EACH TANK.

B. PROVIDE FUEL FILL SPILL CONTAINMENT BOX FACTORY

WELDED TO ROAD FRONTING FACE.

C. PROVIDE TOP OF TANK ACCESS LADDER IN COMPLIANCE WITH

OSHA REQUIREMENTS.

2. PROVIDE REINFORCED STRUCTURALLY DESIGNED CONCRETE

BASE FOR TANK SADDLE, RATED FOR FILLED WEIGHT OF ALL

TANKS. CONTRACTOR SHALL COORDINATE TANK SADDLE

LOCATION AND STRUCTURAL CONCRETE BASE WITH ACTUAL

FUEL STORAGE TANKS PROVIDED.

3. ANCHOR FUEL TANKS TO CONCRETE BASE IN ACCORDANCE WITH

TANK MANUFACTURER'S RECOMMENDATIONS.

4. COORDINATE ALL TANK GROUNDING WORK WITH ELECTRICAL

CONTRACTOR PRIOR TO START OF ANY WORK.

5. FUEL DISPENSER PUMP SHALL CONNECT TO THE PEDESTAL

MOUNTED FUEL TRACKING SYSTEM. TRACKING SYSTEM SHALL

HAVE KEYPAD ENTRY OR MAGNETIC CARD SWIPE FUEL TRACKING

HARDWARE-SOFTWARE COMPLETE WITH INTERFACING PANEL,

CONTROL WIRING AND POWER. BOTTOM OF FUEL DISPENSER

CONTROLLER AND TANK MONITORING CONTROL PANEL SHALL BE

3'-6" ABOVE TOP OF SLAB, OUTSIDE OF CLASS 1 DIV 2 HAZARDOUS

AREA LIMITS.

6. ROUTE TANK VENT LINE TO CLEAR ANY OBSTRUCTION AND

TERMINATE MINIMUM 12-FT ABOVE FINISHED GRADE (TYP).

7. ALL FUEL PIPING SHALL BE BLACK STEEL, SCHEDULE 40 (TYP).

8. PROVIDE IN WEATHER RESISTANT CABINET PORTABLE FIRE

EXTINGUISHER 80 B:C TYPE IN ACCORDANCE WITH NFPA 30A,

SECTION 9.2.5.2.

16'0 8'4'

OVERALL FUEL FARM STORAGE TANK PLAN

SOUTH

TRUE NORTH

WEST

REFERENCE NORTH

EAST

SYMBOL ABBRV. DESCRIPTION

LIST OF ABBREVIATIONS & SYMBOLS

DN DOWN

VALVE, ISOLATION

ABOVEGROUND TANKS

ABOVEGROUND STORAGE TANKAST

MINIMUMMIN

GALLONGAL

VALVE, BALL

VALVE, CHECK

FUEL, SUPPLY (TO DISPENSER) FS

FUEL, FILL FF

PIPE SUPPORTPS

CLEAR SPACE OUTLINE, MINIMUM

TYPICALTYP

SCHEDULE (PIPE)SCH

CLR

16'0 8'4'

OVERALL FUEL FARM STORAGE TANK ARRANGEMENT

Signature Expiration Date of License

4/30/2024

This work was prepared by me or under my supervision and construction of this project will be under my observation.

4'

MINIMUM

CLEAR

(TYP)

25'-4"

GASOLINE FUEL ABOVE

GROUND UL 2085,

5,000-GALLON MINIMUM

CAPACITY TANK

(TYP OF 4)

DIESEL FUEL ABOVE

GROUND UL 2085,

5,000-GALLON MINIMUM

CAPACITY TANK

5' MINIMUM

CLEAR

14'-10"

SADDLE

BASE

CENTERLINE

20'

7'-10"

2"FS SCH40, DN

WITH BALL VALVE

ON VERTICAL(TYP)

2"FS SCH40,

(TYP) ROUTE 2"FS HEADER

UNDER TANK

(TYP)

3"FILL SCH40,

UP (TYP)

SPILL CONTAINMENT

BOX (TYP)

FUEL DISPENSER PAD5,000-GAL UL2085

AST FUEL TANK

(TYP OF 4)

B M2 M2B

M2 M2

TANK ELEVATION A

(TYP)

A M2 M3

TANK

ELEVATION

(TYP) B

M2 M3

TANK SADDLE

CONCRETE

PEDESTAL (TYP)

C M2 S302

TANK ELEVATION B

(TYP) B

M2 M3

1½" FS (DIESEL)2" FS (GASOLINE)

FILL PORT WITH SPILL

CONTAINMENT BOX,

TANK MOUNTED

20'

7'-10"

OSHA LADDER,

TANK ACCESS

OUTLINE OF

MINIMUM LADDER

CLEAR SPACE

3'

OUTLINE OF CLEAR

SPACE3'

14'-10"

CENTER

LINE OF

TANK

BASE

SADDLE,

SEE

NOTE 2

TANK INTERSTIAL

SPACE

10'

CENTERLINE OF

LIFTING LUG (TYP)

2", SCH40, DN TO 2",

SCH40 FUEL

DISPENSER

HEADER

8'0 4'2'

FUEL FARM EQUIPMENT PLAN

NOTES:

SOUTH

TRUE NORTH

WEST

REFERENCE NORTH

EAST

8'0 4'2'

AST FUEL TANK (TYPICAL)

5,000-GALLON UL 2085

A M2 M2

B M2 M2

C M2 M3B

M2 M2

1. ALL ABOVEGROUND TANKS SHALL BE UL2085, PROTECTED TANKS

FOR GASOLINE AND DIESEL FUEL STORAGE IN ACCORDANCE

WITH NFPA 30 AND 30A.

A. PROVIDE CENTRAL FUEL LEVEL AND LEAK MONITORING

SYSTEM FOR EACH TANK.

B. PROVIDE FUEL FILL SPILL CONTAINMENT BOX FACTORY

WELDED TO ROAD FRONTING FACE.

C. PROVIDE TOP OF TANK ACCESS LADDER IN COMPLIANCE WITH

OSHA REQUIREMENTS.

2. PROVIDE REINFORCED STRUCTURALLY DESIGNED CONCRETE

BASE FOR TANK SADDLE, RATED FOR FILLED WEIGHT OF ALL

TANKS. CONTRACTOR SHALL COORDINATE TANK SADDLE

LOCATION AND STRUCTURAL CONCRETE BASE WITH ACTUAL

FUEL STORAGE TANKS PROVIDED.

3. ANCHOR FUEL TANKS TO CONCRETE BASE IN ACCORDANCE WITH

TANK MANUFACTURER'S RECOMMENDATIONS.

4. COORDINATE ALL TANK GROUNDING WORK WITH ELECTRICAL

CONTRACTOR PRIOR TO START OF ANY WORK.

5. FUEL DISPENSER PUMP SHALL CONNECT TO THE PEDESTAL

MOUNTED FUEL TRACKING SYSTEM. TRACKING SYSTEM SHALL

HAVE KEYPAD ENTRY OR MAGNETIC CARD SWIPE FUEL TRACKING

HARDWARE-SOFTWARE COMPLETE WITH INTERFACING PANEL,

CONTROL WIRING AND POWER. BOTTOM OF FUEL DISPENSER

CONTROLLER AND TANK MONITORING CONTROL PANEL SHALL BE

3'-6" ABOVE TOP OF SLAB, OUTSIDE OF CLASS 1 DIV 2 HAZARDOUS

AREA LIMITS.

6. ROUTE TANK VENT LINE TO CLEAR ANY OBSTRUCTION AND

TERMINATE MINIMUM 12-FT ABOVE FINISHED GRADE (TYP).

7. ALL FUEL PIPING SHALL BE BLACK STEEL, SCHEDULE 40 (TYP).

8. PROVIDE IN WEATHER RESISTANT CABINET PORTABLE FIRE

EXTINGUISHER 80 B:C TYPE IN ACCORDANCE WITH NFPA 30A,

SECTION 9.2.5.2.

Signature Expiration Date of License

4/30/2024

This work was prepared by me or under my supervision and construction of this

1'-8"

FUEL

DISPENSER

BASE PLATE

PEDESTAL

MOUNTED FUEL

TRACKING

SYSTEM

FUEL HOSE, 1 FOR

EACH PRODUCT

(TYP OF 2)

BASE PLAN

ELEVATION

OUTLINE OF SUMP

BELOW

7"

DIESEL,

INLET

MOUNTING SLOT

(TYP OF 6)

ELECTRICAL

CONDUIT (TYP

OF 4)

GASOLINE,

INLET

SUCTION PUMPS,

1 FOR EACH

PRODUCT

(TYP OF 2)

FUEL HOSE, FRONT

OPTION

(TYP OF 2)

FUEL DISPENSER, TWO-PRODUCT, TWO

HOSE, ONE-SIDED STAND, HIGH HOSE

CONFIGURATION WITH TWO SUCTION

PUMPS FOR STANDARD FLOW RATES,

BENNETT 3000 SERIES OR EQUAL

FUEL TRACKING INTERFACE PANEL WITH

KEYPAD, MAGNETIC CARD SWIPE AND

RECEIPT OPTION, FUEL FORCE

EXACTA-C-P OR EQUAL

AUTOMATIC NOZZLES WITH SWIVELS

AMD BREAKAWAYS

FUEL HOSE, HIGH HOSE CONFIGURATION

FUEL HOSE CONNECTION STANDARD

LOCATION, ONE ON EACH SIDE

FUEL HOSE CONNECTION, FRONT

LOCATION OPTION

SHEAR-IMPACT VALVE (TYP OF 2)

DISPENSER BASE, BACK SIDE

CONNECTION

(BASE CONNECTION TEMPLATE SHOWN

FOR CONNECTION REQUIREMENTS)

FRP BASE SUMP-CONTAINMENT, ONE

PIECE FOR 2 PRODUCT INLET

SUCTION PUMP, EACH PRODUCT, 2HP

(TYP OF 2)

DISPENSER CONCRETE PAD

ITEM DESCRIPTION

22 23

GASDIESEL

FUEL PRICE PER

GALLON INDICATOR

(TYP OF 2)

FILL BOX, TANK MOUNTED WITH SPILL CONTAINMENT, 24"H X

24"W X 19"D. PROVIDE FUEL PIPING FROM BOX TO FUEL FILL

HEADER (TYP)

LEAK PROBE, INTERSTITIAL SPACE, 2" FPT

FUEL FILL, 3" FPT FROM FILL BOX

FUEL FILL TO TANK, 3" FPT

TANK INVENTORY PROBE WITH SENSOR FOR WATER & FUEL

OUTLET, 2" FPT

ANTI-SIPHON VALVE; FOOT VALVE, DOUBLE POPPET

LIFTING LUG (TYP OF 2), 120-INCHES O.C.

PRIMARY EMERGENCY VENT, 8"Ø

MANWAY, 20"Ø WITH INSPECTION PORT

SECONDARY EMERGENCY VENT, 8"Ø ID

VENT WITH RAIN CAP

CLOCK GAUGE WITH INLINE BALL VALVE

(ROTATE TO FACE LADDER)

OVERFILL PREVENTION VALVE, FLOAT OPERATED

(TYP OF 2, EACH TANK)

DROP TUBE, 4"Ø ID (TYP OF 2)

INVENTORY SENSOR, FOR FUEL AND WATER

INTERSTITIAL SPACE LEAK SENSOR

GROUND LUG, FAR SIDE OF EACH TANK SADDLE

TOP FILL PORT, SPILL CONTAINER AND INSPECTION PORT

4'

OUTLINE

OF DOOR

SWING

TOP OF

COMPACTED

AGGREGATE

PROTECTED TANK

UL 2085

5,000-GALLON AST

7'-11"

ITEM DESCRIPTION

ACCESS

LADDER,

OSHA

20"OUTLINE OF

CONCRETE SADDLE

SUPPORT

(TYP OF 2 EACH)

12'

MINIMUM

14'-10"

20" MIN CLR

STEEL SADDLE

BASE

OUTER TANK,

7'-10" DIAMETER

INNER TANK,

6'-10" DIAMETER

16"

20'-0"

MIN CLR

7'-10"

SPILL CONTAINMENT

BOX

C M3 S302

3"FF SHOWN

HIGHER FOR

CLARITY

AST SADDLE

BASEPLATE 1

M3 M5

AUTOMATIC TANK GAUGING

AND LEAK DETECTOR

CONTROLLER

UNDERGROUND

FUEL PIPING

MONITORING

PORT (TYP OF 2)

1½"FS (DIESEL),

UNDERGROUND PIPE WITH

SECONDARY CONTAINMENT,

SLOPED (TYP)

3' CLEAR

(TYP)

FUEL DISPENSER,

2-PRODUCT, 2-HIGH

HOSE, 1-SIDED

1"FS DIESEL

FUEL, UP

1"FS

GASOLINE

FUEL, UP

PS-2

(TYP)

M3 M5

3" VENT

1½"FS, DOWN

TO HEADER

BELOW

D M3 M3

1½" BLIND

FLANGE

1½"FS (DIESEL),

ABOVEGROUND

HEADER (TYP)

OUTLINE OF DISPENSER

CONCRETE PAD

2"FS

(GASOLINE)

2" BLIND

FLANGE

1½" FS, DIESEL,

(2"FS FOR

GASOLINE)

REMOTE ALARM

HORN AND LIGHT

REMOTE ALARM

ACKNOWLEDGE PANEL

PEDESTAL

MOUNTED FUEL

TRACKING SYSTEM

4'0 2'1'

FUEL DISPENSER - HIGH HOSE TWO PRODUCT

4'0 2'1'

5,000 GALLON UL 2085 AST (TYP)

NOTES:

FUEL DISPENSER PAD

4'0 2'1'

5,000-GALLON UL 2085 AST (TYP)

4'0 2'1'

ELEVATION BELEVATION A

C M2 M3

A M2 M3

B M2 M3

D M3 M3

1. ALL ABOVEGROUND TANKS SHALL BE UL2085, PROTECTED TANKS

FOR GASOLINE AND DIESEL FUEL STORAGE IN ACCORDANCE

WITH NFPA 30 AND 30A.

A. PROVIDE CENTRAL FUEL LEVEL AND LEAK MONITORING

SYSTEM FOR EACH TANK.

B. PROVIDE FUEL FILL SPILL CONTAINMENT BOX FACTORY

WELDED TO ROAD FRONTING FACE.

C. PROVIDE TOP OF TANK ACCESS LADDER IN COMPLIANCE WITH

OSHA REQUIREMENTS.

2. PROVIDE REINFORCED STRUCTURALLY DESIGNED CONCRETE

BASE FOR TANK SADDLE, RATED FOR FILLED WEIGHT OF ALL

TANKS. CONTRACTOR SHALL COORDINATE TANK SADDLE

LOCATION AND STRUCTURAL CONCRETE BASE WITH ACTUAL

FUEL STORAGE TANKS PROVIDED.

3. ANCHOR FUEL TANKS TO CONCRETE BASE IN ACCORDANCE WITH

TANK MANUFACTURER'S RECOMMENDATIONS.

4. COORDINATE ALL TANK GROUNDING WORK WITH ELECTRICAL

CONTRACTOR PRIOR TO START OF ANY WORK.

5. FUEL DISPENSER PUMP SHALL CONNECT TO THE PEDESTAL

MOUNTED FUEL TRACKING SYSTEM. TRACKING SYSTEM SHALL

HAVE KEYPAD ENTRY OR MAGNETIC CARD SWIPE FUEL TRACKING

HARDWARE-SOFTWARE COMPLETE WITH INTERFACING PANEL,

CONTROL WIRING AND POWER. BOTTOM OF FUEL DISPENSER

CONTROLLER AND TANK MONITORING CONTROL PANEL SHALL BE

3'-6" ABOVE TOP OF SLAB, OUTSIDE OF CLASS 1 DIV 2 HAZARDOUS

AREA LIMITS.

6. ROUTE TANK VENT LINE TO CLEAR ANY OBSTRUCTION AND

TERMINATE MINIMUM 12-FT ABOVE FINISHED GRADE (TYP).

7. ALL FUEL PIPING SHALL BE BLACK STEEL, SCHEDULE 40 (TYP).

8. PROVIDE IN WEATHER RESISTANT CABINET PORTABLE FIRE

EXTINGUISHER 80 B:C TYPE IN ACCORDANCE WITH NFPA 30A,

SECTION 9.2.5.2.

Signature Expiration Date of License

4/30/2024

This work was prepared by me or under my supervision and construction of this

FUEL SYSTEM DIAGRAM

LOW POINT

(TYP) FUEL PIPE LEAK

OBSERVATION

MONITORING PORT

(TYP OF 2)

GAS

GAS

GAS

GAS

LEGEND

BALL VALVE

CHECK VALVE, SWING

FLEXIBLE CONNECTION

QUICK DISCONNECT

WITH DUST CAP

UNION

DIESEL

UNION (TYP)

BALL VALVE (TYP)

FLEXIBLE

CONNECTOR

(TYP)

2"FS (GASOLINE)

WITH SECONDARY

CONTAINMENT

SLOPE (TYP)

DISPENSER

SUMP

MONITORING

PORT COVER

(TYP OF 2)

FUEL DISPENSER,

HIGH HOSE, TWO

PRODUCT

1"FS DRAIN VALVE ON

VERTICAL BEFORE

CONNECTION TO

HEADER (TYP)

FS PS-1 ON

CONCRETE

PEDESTAL (TYP) 2

M4 M5

NOTE: REFER TO ELEVATION B,

SHEET M3 DESCRIPTION OF

TANK ACCESSORIES

3"FF, SCH40

(TYP)

2"FS (GASOLINE)

SCH40, SHOWN

OFFSET FROM TANK

FOR CLARITY (TYP)

NOTES:

6' (TYP)

4' (TYP)

D M4 M3

1. ALL ABOVEGROUND TANKS SHALL BE UL2085, PROTECTED TANKS

FOR GASOLINE AND DIESEL FUEL STORAGE IN ACCORDANCE

WITH NFPA 30 AND 30A.

A. PROVIDE CENTRAL FUEL LEVEL AND LEAK MONITORING

SYSTEM FOR EACH TANK.

B. PROVIDE FUEL FILL SPILL CONTAINMENT BOX FACTORY

WELDED TO ROAD FRONTING FACE.

C. PROVIDE TOP OF TANK ACCESS LADDER IN COMPLIANCE WITH

OSHA REQUIREMENTS.

2. PROVIDE REINFORCED STRUCTURALLY DESIGNED CONCRETE

BASE FOR TANK SADDLE, RATED FOR FILLED WEIGHT OF ALL

TANKS. CONTRACTOR SHALL COORDINATE TANK SADDLE

LOCATION AND STRUCTURAL CONCRETE BASE WITH ACTUAL

FUEL STORAGE TANKS PROVIDED.

3. ANCHOR FUEL TANKS TO CONCRETE BASE IN ACCORDANCE WITH

TANK MANUFACTURER'S RECOMMENDATIONS.

4. COORDINATE ALL TANK GROUNDING WORK WITH ELECTRICAL

CONTRACTOR PRIOR TO START OF ANY WORK.

5. FUEL DISPENSER PUMP SHALL CONNECT TO THE PEDESTAL

MOUNTED FUEL TRACKING SYSTEM. TRACKING SYSTEM SHALL

HAVE KEYPAD ENTRY OR MAGNETIC CARD SWIPE FUEL TRACKING

HARDWARE-SOFTWARE COMPLETE WITH INTERFACING PANEL,

CONTROL WIRING AND POWER. BOTTOM OF FUEL DISPENSER

CONTROLLER AND TANK MONITORING CONTROL PANEL SHALL BE

3'-6" ABOVE TOP OF SLAB, OUTSIDE OF CLASS 1 DIV 2 HAZARDOUS

AREA LIMITS.

6. ROUTE TANK VENT LINE TO CLEAR ANY OBSTRUCTION AND

TERMINATE MINIMUM 12-FT ABOVE FINISHED GRADE (TYP).

7. ALL FUEL PIPING SHALL BE BLACK STEEL, SCHEDULE 40 (TYP).

8. PROVIDE IN WEATHER RESISTANT CABINET PORTABLE FIRE

EXTINGUISHER 80 B:C TYPE IN ACCORDANCE WITH NFPA 30A,

SECTION 9.2.5.2.

Signature Expiration Date of License

4/30/2024

This work was prepared by me or under my supervision and construction of this project will be under my

LEAK DETECTION MONITORING SYSTEM SCHEMATIC DIAGRAM

TANK LEVEL

PROBE

(LEVEL

SIGNAL)

TANK LEVEL

PROBE

(LEVEL

SIGNAL)

CONTAINMENT

SUMP SENSOR

TANK

INTERSTITIAL

SENSOR

TANK

INTERSTITIAL

SENSOR

ABOVE GROUND DIESEL TANK ABOVE GROUND GASOLINE TANK

(TYPICAL OF 4)

POWER - 120V/1PH/60HZ

POWER - 120V/1PH/60HZ

REMOTE ALARM PANEL

WITH LIGHT & HORN

AUTOMATIC TANK GAUGING

AND LEAK DETECTOR

MONITOR PANEL WITH TOUCH

SCREEN INTERFACE, MOUNT

WITH TOP OF PANEL AT 48"

ABOVE FINISHED FLOOR, MAX.

INTEGRAL

PRINTER

24V SIGNAL,

(TYP)

A M4 M4

B M4 M4

SEQUENCE OF OPERATIONS FOR LEAK DETECTION AND

MONITORING SYSTEM:

FUEL LEVEL DETECTION:

1. MONITORING PANEL CONTINUOUSLY MONITORS TANK FUEL LEVEL IN EACH TANK.

UPON LOW LEVEL DETECTION, AN AUDIBLE AND VISIBLE ALARM IS TRIGGERED AND

THE MONITORING PANEL DISPLAY INDICATES SOURCE OF ALARM.

2. UPON HIGH LEVEL DETECTION INDICATING AN OVERFILL CONDITION, AN AUDIBLE AND

VISUAL ALARM IS TRIGGERED AND THE MONITORING PANEL DISPLAY INDICATES

SOURCE OF ALARM.

3. ALARM CONDITIONS AT INDIVIDUAL TANKS CONTINUE TO SHOW AT THE MONITORING

PANEL UNTIL THE CONDITION IS CORRECTED.

4. FUEL LEVEL ABOVE LOW LEVEL ALARM AND BELOW HIGH LEVEL ALARM SHALL IN

INDICATED AS NORMAL CONDITION ON THE MONITORING PANEL.

WATER LEVEL DETECTION:

1. MONITORING PANEL CONTINUOUSLY MONITORS WATER LEVEL IN EACH TANK. UPON

HIGH WATER LEVEL DETECTION, AN AUDIBLE AND VISIBLE ALARM IS TRIGGERED AND

THE MONITORING PANEL DISPLAY INDICATES SOURCE OF ALARM.

2. ALARM CONDITIONS AT INDIVIDUAL TANKS CONTINUE TO SHOW AT THE MONITORING

PANEL UNTIL THE CONDITION IS CORRECTED.

INTERSTITIAL LEAK DETECTION:

1. MONITORING PANEL CONTINUOUSLY MONITORS FOR INTERSTITIAL LEAKS. UPON

LEAK DETECTION, AN AUDIBLE AND VISIBLE ALARM IS TRIGGERED AND THE

MONITORING PANEL DISPLAY INDICATES SOURCE OF ALARM.

2. ALARM CONDITIONS AT INDIVIDUAL TANKS CONTINUE TO SHOW AT THE MONITORING

PANEL UNTIL THE CONDITION IS CORRECTED.

CONTAINMENT SUMP SENSOR:

1. MONITORING PANEL CONTINUOUSLY MONITORS FOR LEAKS IN THE CONTAINMENT

SUMP. UPON LIQUID DETECTION (FUEL OR WATER), AN AUDIBLE AND VISIBLE ALARM

IS TRIGGERED AND THE MONITORING PANEL DISPLAY INDICATES SOURCE OF ALARM.

2. ALARM CONDITIONS AT INDIVIDUAL TANKS CONTINUE TO SHOW AT THE MONITORING

PANEL UNTIL THE CONDITION IS CORRECTED.

REMOTE MONITORING:

1. PROVIDE MONITORING PANEL WITH WEB-ENABLED INTERFACE TO ALLOW FOR

REMOTE MONITORING OF STATUS AND ALARM CONDITIONS FROM A COMPUTER

STATION LOCATED AT THE POLICE STATION.

2. COORDINATE WITH THE INTERNET SERVICE PROVIDER TO ENSURE COMPATIBILITY

WITH THE CABLE MODEM BEING PROVIDED.

1½"FS (DIESEL)

SCH40, SHOWN

OFFSET FROM TANK

FOR CLARITY

2"x1½" REDUCER

ETHERNET CONNECTION TO CABLE MODEM

1½"FS (DIESEL)

WITH SECONDARY

CONTAINMENT

REMOTE ALARM PANEL

ALARM ACKNOWLEDGE &

RESET BUTTON, MOUNT WITH

TOP OF BOX AT 48" ABOVE

FINISHED FLOOR, MAX.

13"

2"

7'-1"

4'-11"

6"

(TYP)

1-1/4"Ø

(TYP OF 3)

20" MIN

CLEAR

BOTTOM OF

AST (TYP)

TOP OF

FINISH

GRADE

3"

12"SLOTTED HEAVY

UNISTRUT

1-5/8" SQUARE

FS PIPE WITH CLAMP.

SIZE AS INDICATED

ON PLANS.

3/8"Ø X 1-5/8"

EMBEDDED

ANCHOR (TYP)

CONCRETE

PEDESTAL

FACE

BASE PLATE AT AST PEDESTAL

WITH HEAVY DUTY STRUT

HEIGHT SADDLE

PS-2, ADJUSTABLE

"A"Ø SS

PIPE SADDLE (GALV)

"GRINNELL" FIG 264

"B"Ø SS

2 "

"A" "B"

1 "2 "- 3 " "

"C"

"B"Ø SS FLG

"C"Ø SS

D/2

"D"

OR EQUAL

12"2

C

PIPE DIA

LEVELING

GROUT 3/4"

MIN

CONCRETE

BASE

AST SADDLE

FS, SCH40 PIPE

ABOVE GROUND (TYP)

PS-1, PIPE CLAMP

OUTLINE OF

AST SADDLE

GROUND TERMINATION

CONTAINMENT ABOVE

SECONDARY

PRIMARY FUEL LINE,

FRP SECONDARY

CONTAINMENT PIPE

ELASTOMERIC

TERMINATION BOOT

SIZE AS INDICATED ON PLANS

FRP SECONDARY

CONTAINMENT PIPE

ELASTOMERIC

TERMINATION BOOT

SECURE WITH

STAINLESS STEEL

BAND CLAMPS

Signature Expiration Date of License

4/30/2024

This work was prepared by me or under my supervision and construction of this project will be under my observation.

NOTE: VERIFY ANCHOR BOLT

HOLE LOCATIONS WITH BASE

PLATE ACTUALLY PROVIDED.

COVER
T2 - Scope of Work, Abbreviations, Symbols, Notes, and Drawings Index
T3 - Soil Logs
A1 - Site Plan
C1 - Construciton Notes
C2 - General Site and Topographic Survey Plan
C3 - Topographic Survey Plan 1
C4 - Topographic Survey Plan 2
C5 - Topographic Survey Plan 3
C6 - Topographic Survey Plan 4
C7 - Topographic Survey Plan 5
C8 - Site Layout Plan
C9 - Site Grading Plan
S1 - General Notes and Typical Details
S2 - Typical Details
S3 - Foundation and Roof Framing Plans
S4 - Section Rigid Frame
S5 - Sections
A2 - Fuel Farm Plan
A3 - Enlarged Shelter Plan, Roof Plan, Sections, Typ Sections
A4 - Shelter Exterior Elevations
A5 - Details
M1 - Overall Fuel Farm Storage Tank Plan
M2 - Equipment Plan and Typical Above Ground Storage Tank
M3 - AST Elevation and Fuel Dispenser Detail
M4 - Fuel System Diagram
M5 - Details
E1 - Electrical Notes and Legend
E2 - One-line Diagram and Panel Schedules
E3 - Fuel Farm Electrical Site Plan
E4 - Fuel Farm Site Plan
E5 - Lighting Plan and Metering Elevation