KALA_Update_Fuel_Storage_Updated_Drawings_0005.pdf
PDF 1 MB Posted
- Attached to
- KALA 248432 construct a fuel farm and dispensing
- Solicitation number
- 140P2024R0069
About this file
This document is a set of technical drawings and specifications for a fuel farm and dispensing system to serve the Kalaupapa settlement. The drawings depict the layout, components, and requirements for installing 4 above-ground 5,000-gallon gasoline tanks, 1 above-ground 5,000-gallon diesel tank, a concrete pad and shelter, dispensing and tracking system, mechanical and electrical connections, and site infrastructure. Key details include:
The fuel farm will include UL2085 protected fuel tanks, a central fuel level and leak monitoring system, spill containment, tank access ladders, reinforced concrete tank saddle bases, stainless steel fuel piping, and a pedestal-mounted fuel tracking system with keypad or card reader. The dispensing system will have 2-product, 2-hose fuel dispensers, suction pumps, and leak detection monitoring. The project also involves site work such as extending electrical service, installing lights and bollards, and constructing a compacted aggregate access road. The National Park Service is the federal agency overseeing this project.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DIESEL FUEL ABOVE
GROUND UL2085
STORAGE TANK,
5,000-GALLON
MINIMUM CAPACITY
GASOLINE FUEL
ABOVE GROUND
STORAGE TANK
UL 2085, 5,000-GALLON
MINIMUM CAPACITY
(TYP OF 4)
OUTLINE OF
CONCRETE PEDESTAL
(TYP OF 8)
OUTLINE OF
CONCRETE PEDESTAL
OUTLINE OF
STRUCTURE ROOF
ABOVE
FUEL DISPENSER,
2-PRODUCT, 2-HIGH
HOSE, 1-SIDED
REMOTE ALARM
HORN & LIGHT
BOLLARD, CONCRETE
FILLED (TYP)
11'-10"
(TYP) 4' MIN
(TYP)
EMERGENCY FUEL SHUT-OFF
BUTTON, MOUNT AT 48"
ABOVE FINISHED GRADE, MAX
OVERALL FUEL FARM
TANK ARRANGEMENT
ABOVE
NFPA PORTABLE FIRE
EXTINGUISHER 80B:C IN
CABINET WITH SIGNAGE ABOVE.
REMOTE ALARM
ACKNOWLEDGE
PANEL
AUTOMATIC TANK
GAUGE AND LEAK
MONITORING SYSTEM
CONTROLLER
PEDESTAL MOUNTED
FUEL TRACKING
SYSTEM
GASOLINE FUEL
ABOVE GROUND
UL2085 STORAGE TANK,
5,000-GALLON MINIMUM
CAPACITY (TYP OF 4).
TOTAL 20,000-GALLONS
DIESEL FUEL ABOVE
GROUND UL2085
STORAGE TANK,
TOTAL 5,000-GALLON
MINIMUM CAPACITY
1 2 3 41
NOTE: ALL FUEL TANKS SHALL BE
CLASSIFIED AS PROTECTED TANKS
(UL 2085) AS DEFINED BY NFPA 30
AND 30A.
NFPA 30A PORTABLE FIRE
EXTINGUISHER, DRY CHEMICAL
80B:C TYPE IN CABINET WITH
SIGNAGE ABOVE
NOTES:
1. ALL ABOVEGROUND TANKS SHALL BE UL2085, PROTECTED TANKS
FOR GASOLINE AND DIESEL FUEL STORAGE IN ACCORDANCE
WITH NFPA 30 AND 30A.
A. PROVIDE CENTRAL FUEL LEVEL AND LEAK MONITORING
SYSTEM FOR EACH TANK.
B. PROVIDE FUEL FILL SPILL CONTAINMENT BOX FACTORY
WELDED TO ROAD FRONTING FACE.
C. PROVIDE TOP OF TANK ACCESS LADDER IN COMPLIANCE WITH
OSHA REQUIREMENTS.
2. PROVIDE REINFORCED STRUCTURALLY DESIGNED CONCRETE
BASE FOR TANK SADDLE, RATED FOR FILLED WEIGHT OF ALL
TANKS. CONTRACTOR SHALL COORDINATE TANK SADDLE
LOCATION AND STRUCTURAL CONCRETE BASE WITH ACTUAL
FUEL STORAGE TANKS PROVIDED.
3. ANCHOR FUEL TANKS TO CONCRETE BASE IN ACCORDANCE WITH
TANK MANUFACTURER'S RECOMMENDATIONS.
4. COORDINATE ALL TANK GROUNDING WORK WITH ELECTRICAL
CONTRACTOR PRIOR TO START OF ANY WORK.
5. FUEL DISPENSER PUMP SHALL CONNECT TO THE PEDESTAL
MOUNTED FUEL TRACKING SYSTEM. TRACKING SYSTEM SHALL
HAVE KEYPAD ENTRY OR MAGNETIC CARD SWIPE FUEL TRACKING
HARDWARE-SOFTWARE COMPLETE WITH INTERFACING PANEL,
CONTROL WIRING AND POWER. BOTTOM OF FUEL DISPENSER
CONTROLLER AND TANK MONITORING CONTROL PANEL SHALL BE
3'-6" ABOVE TOP OF SLAB, OUTSIDE OF CLASS 1 DIV 2 HAZARDOUS
AREA LIMITS.
6. ROUTE TANK VENT LINE TO CLEAR ANY OBSTRUCTION AND
TERMINATE MINIMUM 12-FT ABOVE FINISHED GRADE (TYP).
7. ALL FUEL PIPING SHALL BE TYPE 304 STAINLESS STEEL,
SCHEDULE 40 (TYP).
8. PROVIDE IN WEATHER RESISTANT CABINET PORTABLE FIRE
EXTINGUISHER 80 B:C TYPE IN ACCORDANCE WITH NFPA 30A,
SECTION 9.2.5.2.
16'0 8'4'
OVERALL FUEL FARM STORAGE TANK PLAN
SOUTH
TRUE NORTH
WEST
REFERENCE NORTH
EAST
SYMBOL ABBRV. DESCRIPTION
LIST OF ABBREVIATIONS & SYMBOLS
DN DOWN
VALVE, ISOLATION
ABOVEGROUND TANKS
ABOVEGROUND STORAGE TANKAST
MINIMUMMIN
GALLONGAL
VALVE, BALL
VALVE, CHECK
FUEL, SUPPLY (TO DISPENSER) FS
FUEL, FILL FF
PIPE SUPPORTPS
CLEAR SPACE OUTLINE, MINIMUM
TYPICALTYP
SCHEDULE (PIPE)SCH
CLR
16'0 8'4'
OVERALL FUEL FARM STORAGE TANK ARRANGEMENT
Signature Expiration Date of License
4/30/2024
This work was prepared by me or under my supervision and construction of this project will be under my observation.
4'
MINIMUM
CLEAR
(TYP)
25'-4"
GASOLINE FUEL ABOVE
GROUND UL 2085,
5,000-GALLON MINIMUM
CAPACITY TANK
(TYP OF 4)
DIESEL FUEL ABOVE
GROUND UL 2085,
5,000-GALLON MINIMUM
CAPACITY TANK
5' MINIMUM
CLEAR
14'-10"
SADDLE
BASE
CENTERLINE
20'
7'-10"
2"FS SCH40, DN
WITH BALL VALVE
ON VERTICAL(TYP)
2"FS SCH40,
(TYP) ROUTE 2"FS HEADER
UNDER TANK
(TYP)
3"FILL SCH40,
UP (TYP)
SPILL CONTAINMENT
BOX (TYP)
FUEL DISPENSER PAD5,000-GAL UL2085
AST FUEL TANK
(TYP OF 4)
B M2 M2B
M2 M2
TANK ELEVATION A
(TYP)
A M2 M3
TANK
ELEVATION
(TYP) B
M2 M3
TANK SADDLE
CONCRETE
PEDESTAL (TYP)
C M2 S302
TANK ELEVATION B
(TYP) B
M2 M3
1½" FS (DIESEL)2" FS (GASOLINE)
FILL PORT WITH SPILL
CONTAINMENT BOX,
TANK MOUNTED
20'
7'-10"
OSHA LADDER,
TANK ACCESS
OUTLINE OF
MINIMUM LADDER
CLEAR SPACE
3'
OUTLINE OF CLEAR
SPACE3'
14'-10"
CENTER
LINE OF
TANK
BASE
SADDLE,
SEE
NOTE 2
TANK INTERSTIAL
SPACE
10'
CENTERLINE OF
LIFTING LUG (TYP)
2", SCH40, DN TO 2",
SCH40 FUEL
DISPENSER
HEADER
8'0 4'2'
FUEL FARM EQUIPMENT PLAN
NOTES:
SOUTH
TRUE NORTH
WEST
REFERENCE NORTH
EAST
8'0 4'2'
AST FUEL TANK (TYPICAL)
5,000-GALLON UL 2085
A M2 M2
B M2 M2
C M2 M3B
M2 M2
1. ALL ABOVEGROUND TANKS SHALL BE UL2085, PROTECTED TANKS
FOR GASOLINE AND DIESEL FUEL STORAGE IN ACCORDANCE
WITH NFPA 30 AND 30A.
A. PROVIDE CENTRAL FUEL LEVEL AND LEAK MONITORING
SYSTEM FOR EACH TANK.
B. PROVIDE FUEL FILL SPILL CONTAINMENT BOX FACTORY
WELDED TO ROAD FRONTING FACE.
C. PROVIDE TOP OF TANK ACCESS LADDER IN COMPLIANCE WITH
OSHA REQUIREMENTS.
2. PROVIDE REINFORCED STRUCTURALLY DESIGNED CONCRETE
BASE FOR TANK SADDLE, RATED FOR FILLED WEIGHT OF ALL
TANKS. CONTRACTOR SHALL COORDINATE TANK SADDLE
LOCATION AND STRUCTURAL CONCRETE BASE WITH ACTUAL
FUEL STORAGE TANKS PROVIDED.
3. ANCHOR FUEL TANKS TO CONCRETE BASE IN ACCORDANCE WITH
TANK MANUFACTURER'S RECOMMENDATIONS.
4. COORDINATE ALL TANK GROUNDING WORK WITH ELECTRICAL
CONTRACTOR PRIOR TO START OF ANY WORK.
5. FUEL DISPENSER PUMP SHALL CONNECT TO THE PEDESTAL
MOUNTED FUEL TRACKING SYSTEM. TRACKING SYSTEM SHALL
HAVE KEYPAD ENTRY OR MAGNETIC CARD SWIPE FUEL TRACKING
HARDWARE-SOFTWARE COMPLETE WITH INTERFACING PANEL,
CONTROL WIRING AND POWER. BOTTOM OF FUEL DISPENSER
CONTROLLER AND TANK MONITORING CONTROL PANEL SHALL BE
3'-6" ABOVE TOP OF SLAB, OUTSIDE OF CLASS 1 DIV 2 HAZARDOUS
AREA LIMITS.
6. ROUTE TANK VENT LINE TO CLEAR ANY OBSTRUCTION AND
TERMINATE MINIMUM 12-FT ABOVE FINISHED GRADE (TYP).
7. ALL FUEL PIPING SHALL BE TYPE 304 STAINLESS STEEL,
SCHEDULE 40 (TYP).
8. PROVIDE IN WEATHER RESISTANT CABINET PORTABLE FIRE
EXTINGUISHER 80 B:C TYPE IN ACCORDANCE WITH NFPA 30A,
SECTION 9.2.5.2.
Signature Expiration Date of License
4/30/2024
This work was prepared by me or under my supervision and construction of this
1'-8"
FUEL
DISPENSER
BASE PLATE
PEDESTAL
MOUNTED FUEL
TRACKING
SYSTEM
FUEL HOSE, 1 FOR
EACH PRODUCT
(TYP OF 2)
BASE PLAN
ELEVATION
OUTLINE OF SUMP
BELOW
7"
DIESEL,
INLET
MOUNTING SLOT
(TYP OF 6)
ELECTRICAL
CONDUIT (TYP
OF 4)
GASOLINE,
INLET
SUCTION PUMPS,
1 FOR EACH
PRODUCT
(TYP OF 2)
FUEL HOSE, FRONT
OPTION
(TYP OF 2)
FUEL DISPENSER, TWO-PRODUCT, TWO
HOSE, ONE-SIDED STAND, HIGH HOSE
CONFIGURATION WITH TWO SUCTION
PUMPS FOR STANDARD FLOW RATES,
BENNETT 3000 SERIES OR EQUAL
FUEL TRACKING INTERFACE PANEL WITH
KEYPAD, MAGNETIC CARD SWIPE AND
RECEIPT OPTION, FUEL FORCE
EXACTA-C-P OR EQUAL
AUTOMATIC NOZZLES WITH SWIVELS
AMD BREAKAWAYS
FUEL HOSE, HIGH HOSE CONFIGURATION
FUEL HOSE CONNECTION STANDARD
LOCATION, ONE ON EACH SIDE
FUEL HOSE CONNECTION, FRONT
LOCATION OPTION
SHEAR-IMPACT VALVE (TYP OF 2)
DISPENSER BASE, BACK SIDE
CONNECTION
(BASE CONNECTION TEMPLATE SHOWN
FOR CONNECTION REQUIREMENTS)
FRP BASE SUMP-CONTAINMENT, ONE
PIECE FOR 2 PRODUCT INLET
SUCTION PUMP, EACH PRODUCT, 2HP
(TYP OF 2)
DISPENSER CONCRETE PAD
ITEM DESCRIPTION
22 23
GASDIESEL
FUEL PRICE PER
GALLON INDICATOR
(TYP OF 2)
FILL BOX, TANK MOUNTED WITH SPILL CONTAINMENT, 24"H X
24"W X 19"D. PROVIDE FUEL PIPING FROM BOX TO FUEL FILL
HEADER (TYP)
LEAK PROBE, INTERSTITIAL SPACE, 2" FPT
FUEL FILL, 3" FPT FROM FILL BOX
FUEL FILL TO TANK, 3" FPT
TANK INVENTORY PROBE WITH SENSOR FOR WATER & FUEL
OUTLET, 2" FPT
ANTI-SIPHON VALVE; FOOT VALVE, DOUBLE POPPET
LIFTING LUG (TYP OF 2), 120-INCHES O.C.
PRIMARY EMERGENCY VENT, 8"Ø
MANWAY, 20"Ø WITH INSPECTION PORT
SECONDARY EMERGENCY VENT, 8"Ø ID
VENT WITH RAIN CAP
CLOCK GAUGE WITH INLINE BALL VALVE
(ROTATE TO FACE LADDER)
OVERFILL PREVENTION VALVE, FLOAT OPERATED
(TYP OF 2, EACH TANK)
DROP TUBE, 4"Ø ID (TYP OF 2)
INVENTORY SENSOR, FOR FUEL AND WATER
INTERSTITIAL SPACE LEAK SENSOR
GROUND LUG, FAR SIDE OF EACH TANK SADDLE
TOP FILL PORT, SPILL CONTAINER AND INSPECTION PORT
4'
OUTLINE
OF DOOR
SWING
TOP OF
COMPACTED
AGGREGATE
PROTECTED TANK
UL 2085
5,000-GALLON AST
7'-11"
ITEM DESCRIPTION
ACCESS
LADDER,
OSHA
20"OUTLINE OF
CONCRETE SADDLE
SUPPORT
(TYP OF 2 EACH)
12'
MINIMUM
14'-10"
20" MIN CLR
STEEL SADDLE
BASE
OUTER TANK,
7'-10" DIAMETER
INNER TANK,
6'-10" DIAMETER
16"
20'-0"
MIN CLR
7'-10"
SPILL CONTAINMENT
BOX
C M3 S302
3"FF SHOWN
HIGHER FOR
CLARITY
AST SADDLE
BASEPLATE 1
M3 M5
AUTOMATIC TANK GAUGING
AND LEAK DETECTOR
CONTROLLER
UNDERGROUND
FUEL PIPING
MONITORING
PORT (TYP OF 2)
1½"FS (DIESEL),
UNDERGROUND PIPE WITH
SECONDARY CONTAINMENT,
SLOPED (TYP)
3' CLEAR
(TYP)
FUEL DISPENSER,
2-PRODUCT, 2-HIGH
HOSE, 1-SIDED
1"FS DIESEL
FUEL, UP
1"FS
GASOLINE
FUEL, UP
PS-2
(TYP)
M3 M5
2" VENT
1½"FS, DOWN
TO HEADER
BELOW
D M3 M3
1½" BLIND
FLANGE
1½"FS (DIESEL),
ABOVEGROUND
HEADER (TYP)
OUTLINE OF DISPENSER
CONCRETE PAD
2"FS
(GASOLINE)
2" BLIND
FLANGE
1½" FS, DIESEL,
(2"FS FOR
GASOLINE)
REMOTE ALARM
HORN AND LIGHT
REMOTE ALARM
ACKNOWLEDGE PANEL
PEDESTAL
MOUNTED FUEL
TRACKING SYSTEM
4'0 2'1'
FUEL DISPENSER - HIGH HOSE TWO PRODUCT
4'0 2'1'
5,000 GALLON UL 2085 AST (TYP)
NOTES:
FUEL DISPENSER PAD
4'0 2'1'
5,000-GALLON UL 2085 AST (TYP)
4'0 2'1'
ELEVATION BELEVATION A
C M2 M3
A M2 M3
B M2 M3
D M3 M3
1. ALL ABOVEGROUND TANKS SHALL BE UL2085, PROTECTED TANKS
FOR GASOLINE AND DIESEL FUEL STORAGE IN ACCORDANCE
WITH NFPA 30 AND 30A.
A. PROVIDE CENTRAL FUEL LEVEL AND LEAK MONITORING
SYSTEM FOR EACH TANK.
B. PROVIDE FUEL FILL SPILL CONTAINMENT BOX FACTORY
WELDED TO ROAD FRONTING FACE.
C. PROVIDE TOP OF TANK ACCESS LADDER IN COMPLIANCE WITH
OSHA REQUIREMENTS.
2. PROVIDE REINFORCED STRUCTURALLY DESIGNED CONCRETE
BASE FOR TANK SADDLE, RATED FOR FILLED WEIGHT OF ALL
TANKS. CONTRACTOR SHALL COORDINATE TANK SADDLE
LOCATION AND STRUCTURAL CONCRETE BASE WITH ACTUAL
FUEL STORAGE TANKS PROVIDED.
3. ANCHOR FUEL TANKS TO CONCRETE BASE IN ACCORDANCE WITH
TANK MANUFACTURER'S RECOMMENDATIONS.
4. COORDINATE ALL TANK GROUNDING WORK WITH ELECTRICAL
CONTRACTOR PRIOR TO START OF ANY WORK.
5. FUEL DISPENSER PUMP SHALL CONNECT TO THE PEDESTAL
MOUNTED FUEL TRACKING SYSTEM. TRACKING SYSTEM SHALL
HAVE KEYPAD ENTRY OR MAGNETIC CARD SWIPE FUEL TRACKING
HARDWARE-SOFTWARE COMPLETE WITH INTERFACING PANEL,
CONTROL WIRING AND POWER. BOTTOM OF FUEL DISPENSER
CONTROLLER AND TANK MONITORING CONTROL PANEL SHALL BE
3'-6" ABOVE TOP OF SLAB, OUTSIDE OF CLASS 1 DIV 2 HAZARDOUS
AREA LIMITS.
6. ROUTE TANK VENT LINE TO CLEAR ANY OBSTRUCTION AND
TERMINATE MINIMUM 12-FT ABOVE FINISHED GRADE (TYP).
7. ALL FUEL PIPING SHALL BE TYPE 304 STAINLESS STEEL,
SCHEDULE 40 (TYP).
8. PROVIDE IN WEATHER RESISTANT CABINET PORTABLE FIRE
EXTINGUISHER 80 B:C TYPE IN ACCORDANCE WITH NFPA 30A,
SECTION 9.2.5.2.
Signature Expiration Date of License
4/30/2024
This work was prepared by me or under my supervision and construction of this
FUEL SYSTEM DIAGRAM
LOW POINT
(TYP) FUEL PIPE LEAK
OBSERVATION
MONITORING PORT
(TYP OF 2)
GAS
GAS
GAS
GAS
LEGEND
BALL VALVE
CHECK VALVE, SWING
FLEXIBLE CONNECTION
QUICK DISCONNECT
WITH DUST CAP
UNION
DIESEL
UNION (TYP)
BALL VALVE (TYP)
FLEXIBLE
CONNECTOR
(TYP)
2"FS (GASOLINE)
WITH SECONDARY
CONTAINMENT
SLOPE (TYP)
DISPENSER
SUMP
MONITORING
PORT COVER
(TYP OF 2)
FUEL DISPENSER,
HIGH HOSE, TWO
PRODUCT
FS PS-1 ON
CONCRETE
PEDESTAL (TYP) 2
M4 M5
NOTE: REFER TO ELEVATION B,
SHEET M3 DESCRIPTION OF
TANK ACCESSORIES
3"FF, SCH40
(TYP)
2"FS (GASOLINE)
SCH40, SHOWN
OFFSET FROM TANK
FOR CLARITY (TYP)
NOTES:
6' (TYP)
4' (TYP)
D M4 M3
1. ALL ABOVEGROUND TANKS SHALL BE UL2085, PROTECTED TANKS
FOR GASOLINE AND DIESEL FUEL STORAGE IN ACCORDANCE
WITH NFPA 30 AND 30A.
A. PROVIDE CENTRAL FUEL LEVEL AND LEAK MONITORING
SYSTEM FOR EACH TANK.
B. PROVIDE FUEL FILL SPILL CONTAINMENT BOX FACTORY
WELDED TO ROAD FRONTING FACE.
C. PROVIDE TOP OF TANK ACCESS LADDER IN COMPLIANCE WITH
OSHA REQUIREMENTS.
2. PROVIDE REINFORCED STRUCTURALLY DESIGNED CONCRETE
BASE FOR TANK SADDLE, RATED FOR FILLED WEIGHT OF ALL
TANKS. CONTRACTOR SHALL COORDINATE TANK SADDLE
LOCATION AND STRUCTURAL CONCRETE BASE WITH ACTUAL
FUEL STORAGE TANKS PROVIDED.
3. ANCHOR FUEL TANKS TO CONCRETE BASE IN ACCORDANCE WITH
TANK MANUFACTURER'S RECOMMENDATIONS.
4. COORDINATE ALL TANK GROUNDING WORK WITH ELECTRICAL
CONTRACTOR PRIOR TO START OF ANY WORK.
5. FUEL DISPENSER PUMP SHALL CONNECT TO THE PEDESTAL
MOUNTED FUEL TRACKING SYSTEM. TRACKING SYSTEM SHALL
HAVE KEYPAD ENTRY OR MAGNETIC CARD SWIPE FUEL TRACKING
HARDWARE-SOFTWARE COMPLETE WITH INTERFACING PANEL,
CONTROL WIRING AND POWER. BOTTOM OF FUEL DISPENSER
CONTROLLER AND TANK MONITORING CONTROL PANEL SHALL BE
3'-6" ABOVE TOP OF SLAB, OUTSIDE OF CLASS 1 DIV 2 HAZARDOUS
AREA LIMITS.
6. ROUTE TANK VENT LINE TO CLEAR ANY OBSTRUCTION AND
TERMINATE MINIMUM 12-FT ABOVE FINISHED GRADE (TYP).
7. ALL FUEL PIPING SHALL BE TYPE 304 STAINLESS STEEL,
SCHEDULE 40 (TYP).
8. PROVIDE IN WEATHER RESISTANT CABINET PORTABLE FIRE
EXTINGUISHER 80 B:C TYPE IN ACCORDANCE WITH NFPA 30A,
SECTION 9.2.5.2.
Signature Expiration Date of License
4/30/2024
This work was prepared by me or under my supervision and construction of this project will be under my
LEAK DETECTION MONITORING SYSTEM SCHEMATIC DIAGRAM
TANK LEVEL
PROBE
(LEVEL
SIGNAL)
TANK LEVEL
PROBE
(LEVEL
SIGNAL)
CONTAINMENT
SUMP SENSOR
TANK
INTERSTITIAL
SENSOR
TANK
INTERSTITIAL
SENSOR
ABOVE GROUND DIESEL TANK ABOVE GROUND GASOLINE TANK
(TYPICAL OF 4)
POWER - 120V/1PH/60HZ
POWER - 120V/1PH/60HZ
REMOTE ALARM PANEL
WITH LIGHT & HORN
AUTOMATIC TANK GAUGING
AND LEAK DETECTOR
MONITOR PANEL WITH TOUCH
SCREEN INTERFACE, MOUNT
WITH TOP OF PANEL AT 48"
ABOVE FINISHED FLOOR, MAX.
INTEGRAL
PRINTER
24V SIGNAL,
(TYP)
A M4 M4
B M4 M4
SEQUENCE OF OPERATIONS FOR LEAK DETECTION AND
MONITORING SYSTEM:
FUEL LEVEL DETECTION:
1. MONITORING PANEL CONTINUOUSLY MONITORS TANK FUEL LEVEL IN EACH TANK.
UPON LOW LEVEL DETECTION, AN AUDIBLE AND VISIBLE ALARM IS TRIGGERED AND
THE MONITORING PANEL DISPLAY INDICATES SOURCE OF ALARM.
2. UPON HIGH LEVEL DETECTION INDICATING AN OVERFILL CONDITION, AN AUDIBLE AND
VISUAL ALARM IS TRIGGERED AND THE MONITORING PANEL DISPLAY INDICATES
SOURCE OF ALARM.
3. ALARM CONDITIONS AT INDIVIDUAL TANKS CONTINUE TO SHOW AT THE MONITORING
PANEL UNTIL THE CONDITION IS CORRECTED.
4. FUEL LEVEL ABOVE LOW LEVEL ALARM AND BELOW HIGH LEVEL ALARM SHALL IN
INDICATED AS NORMAL CONDITION ON THE MONITORING PANEL.
WATER LEVEL DETECTION:
1. MONITORING PANEL CONTINUOUSLY MONITORS WATER LEVEL IN EACH TANK. UPON
HIGH WATER LEVEL DETECTION, AN AUDIBLE AND VISIBLE ALARM IS TRIGGERED AND
THE MONITORING PANEL DISPLAY INDICATES SOURCE OF ALARM.
2. ALARM CONDITIONS AT INDIVIDUAL TANKS CONTINUE TO SHOW AT THE MONITORING
PANEL UNTIL THE CONDITION IS CORRECTED.
INTERSTITIAL LEAK DETECTION:
1. MONITORING PANEL CONTINUOUSLY MONITORS FOR INTERSTITIAL LEAKS. UPON
LEAK DETECTION, AN AUDIBLE AND VISIBLE ALARM IS TRIGGERED AND THE
MONITORING PANEL DISPLAY INDICATES SOURCE OF ALARM.
2. ALARM CONDITIONS AT INDIVIDUAL TANKS CONTINUE TO SHOW AT THE MONITORING
PANEL UNTIL THE CONDITION IS CORRECTED.
CONTAINMENT SUMP SENSOR:
1. MONITORING PANEL CONTINUOUSLY MONITORS FOR LEAKS IN THE CONTAINMENT
SUMP. UPON LIQUID DETECTION (FUEL OR WATER), AN AUDIBLE AND VISIBLE ALARM
IS TRIGGERED AND THE MONITORING PANEL DISPLAY INDICATES SOURCE OF ALARM.
2. ALARM CONDITIONS AT INDIVIDUAL TANKS CONTINUE TO SHOW AT THE MONITORING
PANEL UNTIL THE CONDITION IS CORRECTED.
REMOTE MONITORING:
1. PROVIDE MONITORING PANEL WITH WEB-ENABLED INTERFACE TO ALLOW FOR
REMOTE MONITORING OF STATUS AND ALARM CONDITIONS FROM A COMPUTER
STATION LOCATED AT THE POLICE STATION.
2. COORDINATE WITH THE INTERNET SERVICE PROVIDER TO ENSURE COMPATIBILITY
WITH THE CABLE MODEM BEING PROVIDED.
1½"FS (DIESEL)
SCH40, SHOWN
OFFSET FROM TANK
FOR CLARITY
2"x1½" REDUCER
ETHERNET CONNECTION TO CABLE MODEM
1½"FS (DIESEL)
WITH SECONDARY
CONTAINMENT
REMOTE ALARM PANEL
ALARM ACKNOWLEDGE &
RESET BUTTON, MOUNT WITH
TOP OF BOX AT 48" ABOVE
FINISHED FLOOR, MAX.
| 240826 S1 |