This document is the solicitation for project ANTI 225963 to rehabilitate the Antietam National Battlefield Visitor Center. The solicitation is being issued by the National Park Service National Office and involves standard construction and renovation services including general contracting, HVAC, plumbing and electrical work. The estimated value is between $5 million and $10 million. The response due date is February 15, 2023 and the period of performance will be 18 months. The place of performance is the Antietam National Battlefield in Sharpsburg, Maryland.
View the file
Other files
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Antietam National Battlefield Sharpsburg, MD
Rehabilitate Antietam Visitor Center
ANTI – 225963
PROJECT SPECIFICATIONS
FINAL CONSTRUCTION DOCUMENTS
Volume 2 of 2
NATIONAL PARK SERVICE
DENVER SERVICE CENTER
FINAL CONSTRUCTION DOCUMENTS
May 22, 2020
ANTI - 225963
05222020
00 01 10 - 1
TABLE OF CONTENTS
DOCUMENT 00 01 10 – TABLE OF CONTENTS
VOLUME 1 of 2
SECTION
NUMBER SECTION TITLE
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS
000107 SEALS PAGE (NOT INCLUDED)
DIVISION 01 - GENERAL REQUIREMENTS
011100 SUMMARY OF WORK
012600 CONTRACT MODIFICATION PROCEDURES
012700 DEFINITION OF CONTRACT LINE ITEMS
013100 PROJECT MANAGEMENT AND COORDINATION
013216 CONSTRUCTION SCHEDULE
013233 PHOTOGRAPHIC DOCUMENTATION FOR HISTORIC PRESERVATION
PROJECTS
013323 SUBMITTAL PROCEDURES
013513.22 ARCHEOLOGICAL PROTECTION
013523 SAFETY REQUIREMENTS
013591 HISTORIC PRESERVATION TREATMENT PROCEDURES
014000 QUALITY REQUIREMENTS
014200 REFERENCE STANDARDS
015000 TEMPORARY FACILITIES AND CONTROLS
015639 TEMPORARY TREE AND PLANT PROTECTION
015719.11 INDOOR AIR QUALITY MANAGEMENT
015719.12 NOISE AND ACOUSTICS MANAGEMENT
015723 TEMPORARY STORM WATER POLLUTION PREVENTION
016700 PRODUCT REQUIREMENTS
017329 CUTTING AND PATCHING
017340 EXECUTION
017419 CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL
017700 CLOSEOUT PROCEDURES
017823 OPERATION AND MAINTENANCE DATA
017900 DEMONSTRATION AND TRAINING
018113 SUSTAINABLE DESIGN REQUIREMENTS FOR NON LEED™ PROJECTS
019114 TOTAL BUILDING COMMISSIONING
DIVISION 02 - EXISTING CONDITIONS
024119 SELECTIVE DEMOLITION
028214 ASBESTOS ABATEMENT
028313 LEAD-BASED PAINT ABATEMENT
028444 HAZARDOUS WASTE REMOVAL AND DISPOSAL
00 01 10 - 2
DIVISION 03 - CONCRETE
033000 CAST-IN-PLACE CONCRETE
035416 HYDRAULIC CEMENT UNDERLAYMENT
DIVISION 04 - MASONRY
040140.61 STONE REPAIR
040140.62 STONE REPOINTING
042200 CONCRETE UNIT MASONRY
044313.13 ANCHORED STONE MASONRY VENEER
DIVISION 05 - METALS
051200 STRUCTURAL STEEL FRAMING
052100 STEEL JOIST FRAMING
053100 STEEL DECKING
055000 METAL FABRICATIONS
055213 PIPE AND TUBE RAILINGS
055313 BAR GRATINGS
057300 DECORATIVE METAL RAILINGS
DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES
061053 MISCELLANEOUS ROUGH CARPENTRY
061600 SHEATHING
062013 EXTERIOR FINISH CARPENTRY
064023 INTERIOR ARCHITECTURAL WOODWORK
064113 WOOD-VENEER-FACED ARCHITECTURAL CABINETS
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
071113 BITUMINOUS DAMPPROOFING
071619 METAL OXIDE WATERPROOFING
072100 THERMAL INSULATION
072726 FLUID-APPLIED MEMBRANE AIR BARRIERS
074646 FIBER-CEMENT SIDING
075419 POLYVINYL-CHLORIDE (PVC) ROOFING
076200 SHEET METAL FLASHING AND TRIM
078413 PENETRATION FIRESTOPPING
078446 FIRE-RESISTIVE JOINT SYSTEMS
079200 JOINT SEALANTS
DIVISION 08 - OPENINGS
081113 HOLLOW METAL DOORS AND FRAMES
081416 FLUSH WOOD DOORS
083113 ACCESS DOORS AND FRAMES
083516 FOLDING GRILLES
084113 ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS
086200 UNIT SKYLIGHTS
087100 DOOR HARDWARE
088000 GLAZING
00 01 10 - 3
089119 FIXED LOUVERS
DIVISION 09 - FINISHES
092116.23 GYPSUM BOARD SHAFT WALL ASSEMBLIES
092216 NON-STRUCTURAL METAL FRAMING
092420 PLASTER REPAIR
092900 GYPSUM BOARD
093013 CERAMIC TILING
095113 ACOUSTICAL PANEL CEILINGS
095433 LINEAR WOOD CEILINGS
096340 STONE FLOORING
096513 RESILIENT BASE AND ACCESSORIES
096519 RESILIENT TILE FLOORING
096813 TILE CARPETING
099113 EXTERIOR PAINTING
099123 INTERIOR PAINTING
DIVISION 10 - SPECIALTIES
102113.19 PLASTIC TOILET COMPARTMENTS
102800 TOILET ACCESSORIES
104413 FIRE PROTECTION CABINETS
104416 FIRE EXTINGUISHERS
107353 TRELLIS SUNSHADE
DIVISION 11 - EQUIPMENT
113013 RESIDENTIAL APPLIANCES
DIVISION 12 - FURNISHINGS
122413 ROLLER WINDOW SHADES
123661.19 QUARTZ AGGLOMERATE COUNTERTOPS
124813.13 ENTRANCE FLOOR MATS
124843.23 ANTI-FATIGUE FLOOR MATS
DIVISION 13 - SPECIAL CONSTRUCTION
133423 MODULAR BUILDINGS
DIVISION 14 - CONVEYING EQUIPMENT
142400 HYDRAULIC ELEVATORS
00 01 10 - 4
VOLUME 2 of 2
DIVISION 21 - FIRE SUPPRESSION
210517 SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING
210518 ESCUTCHEONS FOR FIRE-SUPPRESSION PIPING
210529 HANGERS AND SUPPORTS FOR FIRE SUPPRESSION PIPING AND EQUIPMENT
210553 IDENTIFICATION FOR FIRE-SUPPRESSION PIPING AND EQUIPMENT
211119 FIRE DEPARTMENT CONNECTIONS
211313 WET-PIPE SPRINKLER SYSTEMS
DIVISION 22 - PLUMBING
220513 COMMON MOTOR REQUIREMENTS FOR PLUMBING EQUIPMENT
220517 SLEEVES AND SLEEVE SEALS FOR PLUMBING PIPING
220518 ESCUTCHEONS FOR PLUMBING PIPING
220523.12 BALL VALVES FOR PLUMBING PIPING
220523.14 CHECK VALVES FOR PLUMBING PIPING
220529 HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT
220553 IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT
220719 PLUMBING PIPING INSULATION
220800 COMMISSIONING OF PLUMBING
221116 DOMESTIC WATER PIPING
221119 DOMESTIC WATER PIPING SPECIALTIES
221123.13 DOMESTIC-WATER PACKAGED BOOSTER PUMPS
221316 SANITARY WASTE AND VENT PIPING
221319 SANITARY WASTE PIPING SPECIALTIES
221319.13 SANITARY DRAINS
221343 FACILITY PACKAGED SEWAGE PUMPING STATIONS
221423 STORM DRAINAGE PIPING SPECIALTIES
221429 SUMP PUMPS
223200 DOMESTIC WATER FILTRATION EQUIPMENT
223300 ELECTRIC, DOMESTIC-WATER HEATERS
223500 DOMESTIC-WATER HEAT EXCHANGERS
224213.13 COMMERCIAL WATER CLOSETS
224213.16 COMMERCIAL URINALS
224216.13 COMMERCIAL LAVATORIES
224216.16 COMMERCIAL SINKS
224713 DRINKING FOUNTAINS
DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)
230513 COMMON MOTOR REQUIREMENTS FOR HVAC EQUIPMENT
230517 SLEEVES AND SLEEVE SEALS FOR HVAC PIPING
230518 ESCUTCHEONS FOR HVAC PIPING
230529 HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
230548.13 VIBRATION CONTROLS FOR HVAC
230553 IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT
230593 TESTING, ADJUSTING, AND BALANCING FOR HVAC
230713 DUCT INSULATION
00 01 10 - 5
230719 HVAC PIPING INSULATION
230800 COMMISSIONING OF HVAC
233113 METAL DUCTS
233300 AIR DUCT ACCESSORIES
233346 FLEXIBLE DUCTS
233713 DIFFUSERS, REGISTERS, AND GRILLES
233416 CENTRIFUGAL HVAC FANS
237433 DEDICATED OUTDOOR-AIR UNITS
238129 VARIABLE-REFRIGERANT-FLOW HVAC SYSTEMS
238239.13 CABINET UNIT HEATERS
238239.19 WALL AND CEILING UNIT HEATERS
238313 RADIANT-HEATING ELECTRIC CABLES
DIVISION 26 - ELECTRICAL
260519 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
260526 GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
260529 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
260533 RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS
260543 UNDERGROUND DUCTS AND RACEWAYS FOR ELECTRICAL SYSTEMS
260544 SLEEVES AND SLEEVE SEALS FOR ELECTRICAL RACEWAYS AND CABLING
260553 IDENTIFICATION FOR ELECTRICAL SYSTEMS
260573.13 SHORT-CIRCUIT STUDIES
260573.19 ARC-FLASH HAZARD ANALYSIS
260923 LIGHTING CONTROL DEVICES
260936 MODULAR DIMMING CONTROLS
260943 NETWORK LIGHTING CONTROLS
262416 PANELBOARDS
262713 ELECTRICITY METERING
262726 WIRING DEVICES
262813 FUSES
262816 ENCLOSED SWITCHES AND CIRCUIT BREAKERS
263100 PHOTOVOLTAIC SYSTEM COLLECTORS
264113 LIGHTNING PROTECTION FOR STRUCTURES
265119 LED INTERIOR LIGHTING
265213 EMERGENCY AND EXIT LIGHTING
DIVISION 27 - COMMUNICATIONS
270526 GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS
270528 PATHWAYS FOR COMMUNICATIONS SYSTEMS
270529 HANGERS AND SUPPORTS FOR COMMUNICATIONS SYSTEMS
270536 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS
270543 UNDERGROUND PATHWAYS AND STRUCTURES FOR COMMUNICATION
SYSTEMS
270544 SLEEVES AND SLEEVE SEALS FOR COMMUNICATIONS PATHWAYS AND CABLING
270553 IDENTIFICATION FOR COMMUNICATIONS SYSTEMS
271100 COMMUNICATIONS EQUIPMENT ROOM FITTINGS
271116 COMMUNICATIONS RACKS, FRAMES, AND ENCLOSURES
00 01 10 - 6
271313 COMMUNICATIONS COPPER BACKBONE CABLING
271323 COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING
271333 COMMUNICATIONS COAXIAL BACKBONE CABLING
271513 COMMUNICATIONS COPPER HORIZONTAL CABLING
271533 COMMUNICATIONS COAXIAL HORIZONTAL CABLING
275116 PUBLIC ADDRESS SYSTEMS
275123.20 COMMERCIAL INTERCOMMUNICATIONS AND PROGRAM SYSTEMS
DIVISION 28 - ELECTRONIC SAFETY AND SECURITY
282000 VIDEO SURVEILLANCE
283100 INTRUSION DETECTION
284621.11 ADDRESSABLE FIRE-ALARM SYSTEMS
DIVISION 31 - EARTHWORK
311000 SITE CLEARING
312000 EARTH MOVING
315000 EXCAVATION SUPPORT AND PROTECTION
DIVISION 32 - EXTERIOR IMPROVEMENTS
321216 ASPHALT PAVING
321217 SPECIAL ASPHALT PAVING
321313 CONCRETE PAVING
321373 CONCRETE PAVING JOINT SEALANTS
321400 UNIT PAVING
321723 PAVEMENT MARKINGS
323300 SITE FURNISHINGS
329100 PLANTING SOIL
329200 TURF AND GRASSES
329300 PLANTS
DIVISION 33 - UTILITIES
330500 COMMON WORK RESULTS FOR UTILITIES
330507.23 JACKING AND BORING
334100 STORM UTILITY DRAINAGE PIPING
334600 SUBDRAINAGE
END OF TABLE OF CONTENTS
21 05 17 - 1
SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING
SECTION 21 05 17 - SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Sleeves.
2. Sleeve-seal systems.
3. Sleeve-seal fittings.
4. Grout.
1.2 ACTION SUBMITTALS
A. Product Data: For each type of product.
1.3 INFORMATIONAL SUBMITTALS
A. Field quality-control reports.
PART 2 - PRODUCTS
2.1 SLEEVES
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Advance Products & Systems, Inc.
2. CALPICO, Inc.
3. GPT; an EnPro Industries company.
B. Cast-Iron Pipe Sleeves: Cast or fabricated of cast or ductile iron and equivalent to ductile-iron pressure pipe, with plain ends and integral waterstop.
C. Steel Pipe Sleeves: ASTM A 53, Type E, Grade B, Schedule 40, galvanized, with plain ends and integral welded waterstop collar.
D. Galvanized-Steel Sheet Sleeves: 0.0239-inch minimum thickness; round tube closed with welded longitudinal joint.
E. PVC Pipe Sleeves: ASTM D 1785, Schedule 40.
F. Molded-PVC Sleeves: With nailing flange for attaching to wooden forms.
G. Molded-PE or -PP Sleeves: Removable, tapered-cup shaped, and smooth outer surface with nailing flange for attaching to wooden forms.
21 05 17 - 2
SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING
2.2 SLEEVE-SEAL SYSTEMS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Advance Products & Systems, Inc.
2. CALPICO, Inc.
3. GPT; an EnPro Industries company.
4. Metraflex Company (The).
5. Proco Products, Inc.
B. Description:
1. Modular sealing-element unit, designed for field assembly, for filling annular space between piping and sleeve.
2. Designed to form a hydrostatic seal of 20 psig minimum.
3. Sealing Elements: EPDM-rubber interlocking links shaped to fit surface of pipe. Include type and number required for pipe material and size.
4. Pressure Plates: Composite plastic or stainless steel.
5. Connecting Bolts and Nuts: Stainless steel of length required to secure pressure plates to sealing elements.
2.3 SLEEVE-SEAL FITTINGS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Advance Products & Systems, Inc.
2. CALPICO, Inc.
3. GPT; an EnPro Industries company.
4. Metraflex Company (The).
5. Proco Products, Inc.
B. Description: Manufactured plastic, sleeve-type, waterstop assembly made for imbedding in concrete slab or wall.
C. Plastic or rubber waterstop collar with center opening to match piping OD.
2.4 GROUT
A. Description: Nonshrink, for interior and exterior sealing openings in non-fire-rated walls or floors.
B. Standard: ASTM C 1107, Grade B, post-hardening and volume-adjusting, dry, hydraulic-cement grout.
C. Design Mix: 5000-psi, 28-day compressive strength.
D. Packaging: Premixed and factory packaged.
21 05 17 - 3
SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING
PART 3 - EXECUTION
3.1 SLEEVE INSTALLATION
A. Install sleeves for piping passing through penetrations in floors, partitions, roofs, and walls.
B. For sleeves that will have sleeve-seal system installed, select sleeves of size large enough to provide 1-inch annular clear space between piping and concrete slabs and walls.
1. Sleeves are not required for core-drilled holes.
C. Install sleeves in concrete floors, concrete roof slabs, and concrete walls as new slabs and walls are constructed.
1. Permanent sleeves are not required for holes in slabs formed by molded-PE or -PP sleeves.
2. Cut sleeves to length for mounting flush with both surfaces.
a. Exception: Extend sleeves installed in floors of mechanical equipment areas or other wet areas 2 inches above finished floor level.
3. Using grout, seal space outside of sleeves in slabs and walls without sleeve-seal system.
D. Install sleeves for pipes passing through interior partitions.
1. Cut sleeves to length for mounting flush with both surfaces.
2. Install sleeves that are large enough to provide 1/4-inch annular clear space between sleeve and pipe or pipe insulation.
3. Seal annular space between sleeve and piping or piping insulation; use joint sealants appropriate for size, depth, and location of joint.
E. Fire-Resistance-Rated Penetrations, Horizontal Assembly Penetrations, and Smoke Barrier Penetrations: Maintain indicated fire or smoke rating of walls, partitions, ceilings, and floors at pipe penetrations. Seal pipe penetrations with fire- and smoke-stop materials. Comply with requirements for firestopping and fill materials specified in Section 07 84 13 "Penetration Firestopping."
3.2 SLEEVE-SEAL-SYSTEM INSTALLATION
A. Install sleeve-seal systems in sleeves in exterior concrete walls and slabs-on-grade at service piping entries into building.
B. Select type, size, and number of sealing elements required for piping material and size and for sleeve ID or hole size. Position piping in center of sleeve. Center piping in penetration, assemble sleeve-seal system components, and install in annular space between piping and sleeve. Tighten bolts against pressure plates that cause sealing elements to expand and make a watertight seal.
3.3 SLEEVE-SEAL-FITTING INSTALLATION
A. Install sleeve-seal fittings in new walls and slabs as they are constructed.
21 05 17 - 4
SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING
B. Assemble fitting components of length to be flush with both surfaces of concrete slabs and walls.
Position waterstop flange to be centered in concrete slab or wall.
C. Secure nailing flanges to concrete forms.
D. Use grout, to seal the space around outside of sleeve-seal fittings.
3.4 FIELD QUALITY CONTROL
A. Perform the following tests and inspections:
1. Leak Test: After allowing for a full cure, test sleeves and sleeve seals for leaks. Repair leaks and retest until no leaks exist.
B. Sleeves and sleeve seals will be considered defective if they do not pass tests and inspections.
C. Prepare test and inspection reports.
3.5 SLEEVE AND SLEEVE-SEAL SCHEDULE
A. Use sleeves and sleeve seals for the following piping-penetration applications:
1. Exterior Concrete Walls above Grade:
a. Piping Smaller Than NPS 6: Steel pipe sleeves.
b. Piping NPS 6 and Larger: Steel pipe sleeves.
2. Exterior Concrete Walls below Grade:
a. Piping NPS 6 and Larger: Steel pipe sleeves with sleeve-seal system.
1) Select sleeve size to allow for 2-inch annular clear space between piping and sleeve for installing sleeve-seal system.
3. Concrete Slabs-on-Grade:
a. Piping NPS 6 and Larger: Steel pipe sleeves with sleeve-seal system.
1) Select sleeve size to allow for 2-inch annular clear space between piping and sleeve for installing sleeve-seal system.
4. Concrete Slabs above Grade:
a. Piping Smaller Than NPS 6: Steel pipe sleeves.
b. Piping NPS 6 and Larger: Steel pipe sleeves.
5. Interior Partitions:
a. Piping Smaller Than NPS 6: Steel pipe sleeves.
b. Piping NPS 6 and Larger: Galvanized-steel sheet sleeves.
21 05 17 - 5
SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING
END OF SECTION 21 05 17
© 2019 by the American Institute of Architects and EYP Inc.
Warning: This AIA MasterSpec based document is protected by U.S. Copyright Law and International Treaties. It was created by licensee EYP Inc. for Antietam National Battlefield Visitor Center Rehabilitation, National Park Service. A valid, current MasterSpec license is required for editing or use of this document.
21 05 17 - 6
SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING
21 05 18 - 1
ESCUTCHEONS FOR FIRE-SUPPRESSION PIPING
SECTION 21 05 18 - ESCUTCHEONS FOR FIRE-SUPPRESSION PIPING
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Escutcheons.
2. Floor plates.
1.2 ACTION SUBMITTALS
A. Product Data: For each type of product.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. BrassCraft Manufacturing Co.; a Masco company.
2. Dearborn Brass.
3. Jones Stephens Corp.
4. Keeney Manufacturing Company (The).
5. Mid-America Fittings, Inc.
6. ProFlo; a Ferguson Enterprises, Inc. brand.
2.2 ESCUTCHEONS
A. One-Piece, Steel Type: With polished, chrome-plated or polished brass finish and setscrew fastener.
B. One-Piece, Cast-Brass Type: With polished, chrome-plated or polished brass finish and setscrew fastener.
C. One-Piece, Deep-Pattern Type: Deep-drawn, box-shaped steel or brass with polished, chrome-plated finish and spring-clip fasteners.
D. One-Piece, Stamped-Steel Type: With polished, chrome-plated finish and spring-clip fasteners.
E. Split-Plate, Stamped-Steel Type: With polished, chrome-plated finish; concealed hinge; and spring-clip fasteners.
2.3 FLOOR PLATES
A. Split Floor Plates: Steel with concealed hinge.
21 05 18 - 2
ESCUTCHEONS FOR FIRE-SUPPRESSION PIPING
PART 3 - EXECUTION
3.1 INSTALLATION
A. Install escutcheons for piping penetrations of walls, ceilings, and finished floors.
B. Install escutcheons with ID to closely fit around pipe, tube, and insulation of piping and with OD that completely covers opening.
1. Escutcheons for New Piping:
a. Piping with Fitting or Sleeve Protruding from Wall: One-piece, deep pattern.
b. Bare Piping at Wall and Floor Penetrations in Finished Spaces: One-piece steel with polished, chrome-plated or polished brass finish.
c. Bare Piping at Wall and Floor Penetrations in Finished Spaces: One-piece cast brass with polished, chrome-plated or polished brass finish.
d. Bare Piping at Ceiling Penetrations in Finished Spaces: One-piece steel with polished, chrome-plated finish.
e. Bare Piping at Ceiling Penetrations in Finished Spaces: One-piece cast brass with polished, chrome-plated finish.
f. Bare Piping in Unfinished Service Spaces: One-piece stamped steel or split-plate, stamped steel with concealed hinge with polished, chrome-plated finish.
g. Bare Piping in Equipment Rooms: One-piece stamped steel or split-plate, stamped steel with concealed hinge with polished, chrome-plated finish.
C. Install floor plates for piping penetrations of equipment-room floors.
D. Install floor plates with ID to closely fit around pipe, tube, and insulation of piping and with OD that completely covers opening.
1. New Piping: One-piece, floor plate.
3.2 FIELD QUALITY CONTROL
A. Using new materials, replace broken and damaged escutcheons and floor plates.
END OF SECTION 21 05 18
Warning: This AIA MasterSpec based document is protected by U.S. Copyright Law and International Treaties. It was created by licensee EYP Inc. for Antietam National Battlefield Visitor Center Rehabilitation, National Park Service. A valid, current MasterSpec license is required for
21 05 29 - 1
HANGERS AND SUPPORTS FOR FIRE SUPPRESSION PIPING AND
EQUIPMENT
SECTION 21 05 29 - HANGERS AND SUPPORTS FOR FIRE SUPPRESSION PIPING AND
EQUIPMENT
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Metal pipe hangers and supports.
2. Trapeze pipe hangers.
3. Metal framing systems.
4. Thermal hanger-shield inserts.
5. Fastener systems.
6. Equipment supports.
B. Related Requirements:
1. Section 05 50 00 "Metal Fabrications" for structural-steel shapes and plates for trapeze hangers for pipe and equipment supports.
1.2 ACTION SUBMITTALS
A. Product Data: For each type of product.
B. Shop Drawings: Signed and sealed by a qualified professional engineer. Show fabrication and installation details and include calculations for the following:
1. Trapeze pipe hangers.
2. Metal framing systems.
3. Equipment supports.
C. Delegated-Design Submittal: For trapeze hangers indicated to comply with performance requirements and design criteria, including analysis data signed and sealed by the qualified professional engineer responsible for their preparation.
1. Detail fabrication and assembly of trapeze hangers.
2. Include design calculations for designing trapeze hangers.
1.3 INFORMATIONAL SUBMITTALS
A. Welding certificates.
1.4 QUALITY ASSURANCE
A. Structural-Steel Welding Qualifications: Qualify procedures and personnel according to
AWS D1.1.
21 05 29 - 2
HANGERS AND SUPPORTS FOR FIRE SUPPRESSION PIPING AND
EQUIPMENT
B. Pipe Welding Qualifications: Qualify procedures and operators according to 2015 ASME Boiler and Pressure Vessel Code, Section IX.
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. Delegated Design: Engage a qualified professional engineer, as defined in Section 01 40 00 "Quality Requirements," to design trapeze pipe hangers and equipment supports.
B. Structural Performance: Hangers and supports for fire-suppression piping and equipment shall withstand the effects of gravity loads and stresses within limits and under conditions indicated according to ASCE/SEI 7.
1. Design supports for multiple pipes, including pipe stands, capable of supporting combined weight of supported systems, system contents, and test water.
2. Design equipment supports capable of supporting combined operating weight of supported equipment and connected systems and components.
C. NFPA Compliance: Comply with NFPA 13.
D. UL Compliance: Comply with UL 203.
2.2 METAL PIPE HANGERS AND SUPPORTS
A. Carbon-Steel Pipe Hangers and Supports:
1. Description: Factory-fabricated components, NFPA approved, UL listed, or FM approved for fire-suppression piping support.
2. Galvanized Metallic Coatings: Pregalvanized or hot-dip galvanized.
3. Hanger Rods: Continuous-thread rod, nuts, and washer made of stainless steel.
2.3 TRAPEZE PIPE HANGERS
A. Description: MSS SP-58, Type 59, shop- or field-fabricated pipe-support assembly, made from structural-carbon-steel shapes, with NFPA-approved, UL-listed, or FM-approved carbon-steel hanger rods, nuts, saddles, and U-bolts.
2.4 METAL FRAMING SYSTEMS
A. MFMA Manufacturer Metal Framing Systems:
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. B-line, an Eaton business.
b. Flex-Strut Inc.
c. G-Strut.
d. Haydon Corporation.
21 05 29 - 3
HANGERS AND SUPPORTS FOR FIRE SUPPRESSION PIPING AND
EQUIPMENT
e. Thomas & Betts Corporation; A Member of the ABB Group.
f. Unistrut; Part of Atkore International.
g. Wesanco, Inc.
2. Description: Shop- or field-fabricated pipe-support assembly, made of steel channels, accessories, fittings, and other components for supporting multiple parallel pipes.
3. Standard: Comply with MFMA-4, factory-fabricated components for field assembly.
4. Channels: Continuous slotted carbon-steel channel with inturned lips.
5. Channel Width: Selected for applicable load criteria.
6. Channel Nuts: Formed or stamped nuts or other devices designed to fit into channel slot and, when tightened, prevent slipping along channel.
7. Hanger Rods: Continuous-thread rod, nuts, and washer made of Stainless Steel.
8. Metallic Coating: No coating.
B. Non-MFMA Manufacturer Metal Framing Systems:
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Anvil International.
b. Carpenter & Paterson, Inc.
c. Empire Industries, Inc.
d. ERICO International Corporation.
e. PHD Manufacturing, Inc.
2. Description: Shop- or field-fabricated pipe-support assembly, made of steel channels, accessories, fittings, and other components for supporting multiple parallel pipes.
3. Standard: Comply with MFMA-4, factory-fabricated components for field assembly.
4. Channels: Continuous slotted carbon-steel channel with inturned lips.
5. Channel Width: Select for applicable load criteria.
6. Channel Nuts: Formed or stamped nuts or other devices designed to fit into channel slot and, when tightened, prevent slipping along channel.
7. Hanger Rods: Continuous-thread rod, nuts, and washer made of stainless steel.
8. Metallic Coating: No coating.
2.5 THERMAL HANGER-SHIELD INSERTS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Carpenter & Paterson, Inc.
2. Clement Support Services.
3. ERICO International Corporation.
4. National Pipe Hanger Corporation.
5. Pipe Shields Inc.
6. Piping Technology & Products, Inc.
7. Rilco Manufacturing Co., Inc.
8. Value Engineered Products, Inc.
21 05 29 - 4
HANGERS AND SUPPORTS FOR FIRE SUPPRESSION PIPING AND
EQUIPMENT
B. Insulation-Insert Material: Water-repellent-treated, ASTM C 533, Type I calcium silicate with 100-psi ASTM C 552, Type II cellular glass with 100-psi or ASTM C 591, Type VI, Grade 1 polyisocyanurate with 125-psi minimum compressive strength.
C. For Trapeze or Clamped Systems: Insert and shield shall cover entire circumference of pipe.
D. For Clevis or Band Hangers: Insert and shield shall cover lower 180 degrees of pipe.
E. Insert Length: Extend 2 inches beyond sheet metal shield for piping operating below ambient air temperature.
2.6 FASTENER SYSTEMS
A. Powder-Actuated Fasteners: NFPA-approved, UL-listed, or FM-approved threaded-steel stud, for use in hardened portland cement concrete, with pull-out, tension, and shear capacities appropriate for supported loads and building materials where used.
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Hilti, Inc.
b. ITW Ramset/Red Head; Illinois Tool Works, Inc.
c. MKT Fastening, LLC.
d. Simpson Strong-Tie Co., Inc.
B. Mechanical-Expansion Anchors: NFPA-approved, UL-listed, or FM-approved, insert-wedge-type anchors, for use in hardened portland cement concrete; with pull-out, tension, and shear capacities appropriate for supported loads and building materials where used.
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. B-line, an Eaton business.
b. Empire Tool and Manufacturing Co., Inc.
c. Hilti, Inc.
d. ITW Ramset/Red Head; Illinois Tool Works, Inc.
e. MKT Fastening, LLC.
2. Indoor Applications: Stainless steel.
3. Outdoor Applications: Stainless steel.
2.7 EQUIPMENT SUPPORTS
A. Description: NFPA-approved, UL-listed, or FM-approved, welded, shop- or field-fabricated equipment support, made from structural-carbon-steel shapes.
2.8 MATERIALS
A. Aluminum: ASTM B 221.
21 05 29 - 5
HANGERS AND SUPPORTS FOR FIRE SUPPRESSION PIPING AND
EQUIPMENT
B. Carbon Steel: ASTM A 1011.
C. Structural Steel: ASTM A 36, carbon-steel plates, shapes, and bars; black and galvanized.
D. Stainless Steel: ASTM A 240.
E. Grout: ASTM C 1107, factory-mixed and -packaged, dry, hydraulic-cement, nonshrink and nonmetallic grout, suitable for interior and exterior applications.
1. Properties: Nonstaining, noncorrosive, and nongaseous.
2. Design Mix: 5000-psi, 28-day compressive strength.
PART 3 - EXECUTION
3.1 APPLICATION
A. Comply with requirements in Section 07 84 13 "Penetration Firestopping" for firestopping materials and installation, for penetrations through fire-rated walls, ceilings, and assemblies.
3.2 HANGER AND SUPPORT INSTALLATION
A. Metal Pipe-Hanger Installation: Comply with installation requirements of approvals and listings.
Install hangers, supports, clamps, and attachments as required to properly support piping from building structure.
B. Metal Trapeze Pipe-Hanger Installation: Comply with MSS SP-58. Arrange for grouping of parallel runs of horizontal piping, and support together on field-fabricated trapeze pipe hangers.
1. Pipes of Various Sizes: Support together and space trapezes for smallest pipe size, or install intermediate supports for smaller-diameter pipes as specified for individual pipe hangers.
2. Field fabricate from ASTM A 36 carbon-steel shapes selected for loads being supported.
Weld steel according to AWS D1.1.
C. Metal Framing System Installation: Arrange for grouping of parallel runs of piping, and support together on field-assembled metal strut systems.
D. Thermal Hanger-Shield Installation: Install in pipe hanger or shield for insulated piping.
E. Fastener System Installation:
1. Install powder-actuated fasteners for use in lightweight concrete or concrete slabs less than 4 inches thick in concrete, after concrete is placed and completely cured. Use operators that are licensed by powder-actuated tool manufacturer. Install fasteners according to powder-actuated tool manufacturer's operating manual. Install in accordance with approvals and listings.
2. Install mechanical-expansion anchors in concrete, after concrete is placed and completely cured. Install fasteners according to manufacturer's written instructions. Install in accordance with approvals and listings.
21 05 29 - 6
HANGERS AND SUPPORTS FOR FIRE SUPPRESSION PIPING AND
EQUIPMENT
F. Install hangers and supports complete with necessary attachments, inserts, bolts, rods, nuts, washers, and other accessories.
G. Equipment Support Installation: Fabricate from welded-structural-steel shapes.
H. Install hangers and supports to allow controlled thermal and seismic movement of piping systems, to permit freedom of movement between pipe anchors, and to facilitate action of expansion joints, expansion loops, expansion bends, and similar units.
I. Install lateral bracing with pipe hangers and supports to prevent swaying.
J. Install building attachments within concrete slabs or attach to structural steel. Install additional attachments at concentrated loads, including valves, flanges, and strainers, NPS 2-1/2 and larger and at changes in direction of piping. Install concrete inserts before concrete is placed; fasten inserts to forms, and install reinforcing bars through openings at top of inserts.
K. Load Distribution: Install hangers and supports, so that piping live and dead loads and stresses from movement will not be transmitted to connected equipment.
L. Pipe Slopes: Install hangers and supports to provide indicated pipe slopes and to not exceed maximum pipe deflections allowed by ASME B31.9 for building services piping.
M. Insulated Piping:
1. Attach clamps and spacers to piping.
a. Piping Operating Above Ambient Air Temperature: Clamp may project through insulation.
b. Piping Operating Below Ambient Air Temperature: Use thermal hanger-shield insert with clamp sized to match OD of insert.
c. Do not exceed pipe stress limits allowed by ASME B31.9 for building services piping.
2. Install MSS SP-58, Type 39 protection saddles if insulation without vapor barrier is indicated. Fill interior voids with insulation that matches adjoining insulation.
a. Option: Thermal hanger-shield inserts may be used. Include steel weight-distribution plate for pipe NPS 4 and larger if pipe is installed on rollers.
3. Install MSS SP-58, Type 40 protective shields on cold piping with vapor barrier. Shields shall span an arc of 180 degrees.
a. Option: Thermal hanger-shield inserts may be used. Include steel weight-distribution plate for pipe NPS 4 and larger if pipe is installed on rollers.
4. Shield Dimensions for Pipe: Not less than the following:
a. NPS 1/4 to NPS 3-1/2: 12 inches long and 0.048 inch thick.
b. NPS 4: 12 inches long and 0.06 inch thick.
c. NPS 5 and NPS 6: 18 inches long and 0.06 inch thick.
21 05 29 - 7
HANGERS AND SUPPORTS FOR FIRE SUPPRESSION PIPING AND
EQUIPMENT
d. NPS 8 to NPS 14: 24 inches long and 0.075 inch thick.
e. NPS 16 to NPS 24: 24 inches long and 0.105 inch thick.
5. Pipes NPS 8 and Larger: Include wood or reinforced calcium-silicate-insulation inserts of length at least as long as protective shield.
6. Thermal Hanger Shields: Install with insulation of same thickness as piping insulation.
3.3 EQUIPMENT SUPPORTS
A. Fabricate structural-steel stands to suspend equipment from structure overhead or to support equipment above floor.
B. Grouting: Place grout under supports for equipment, and make bearing surface smooth.
C. Provide lateral bracing, to prevent swaying, for equipment supports.
3.4 METAL FABRICATIONS
A. Cut, drill, and fit miscellaneous metal fabrications for trapeze pipe hangers and equipment supports.
B. Fit exposed connections together to form hairline joints. Field weld connections that cannot be shop welded because of shipping size limitations.
C. Field Welding: Comply with AWS D1.1 procedures for shielded, metal arc welding; appearance and quality of welds; and methods used in correcting welding work; and with the following:
1. Use materials and methods that minimize distortion and develop strength and corrosion resistance of base metals.
2. Obtain fusion without undercut or overlap.
3. Remove welding flux immediately.
4. Finish welds at exposed connections, so no roughness shows after finishing and so contours of welded surfaces match adjacent contours.
3.5 ADJUSTING
A. Hanger Adjustments: Adjust hangers to distribute loads equally on attachments and to achieve indicated slope of pipe.
B. Trim excess length of continuous-thread hanger and support rods to 1-1/2 inches.
3.6 PAINTING
A. Touchup: Clean field welds and abraded, shop-painted areas. Paint exposed areas immediately after erecting hangers and supports. Use same materials as those used for shop painting. Comply with SSPC-PA 1 requirements for touching up field-painted surfaces.
1. Apply paint by brush or spray to provide a minimum dry film thickness of 2.0 mils.
21 05 29 - 8
HANGERS AND SUPPORTS FOR FIRE SUPPRESSION PIPING AND
EQUIPMENT
B. Galvanized Surfaces: Clean welds, bolted connections, and abraded areas, and apply galvanizing-repair paint to comply with ASTM A 780.
3.7 HANGER AND SUPPORT SCHEDULE
A. Specific hanger and support requirements are in Sections specifying piping systems and equipment.
B. Comply with NFPA requirements for pipe-hanger selections and applications that are not specified in piping system Sections.
C. Use hangers and supports with galvanized metallic coatings for piping and equipment that will not have field-applied finishes.
D. Use nonmetallic coatings on attachments for electrolytic protection where attachments are in direct contact with copper tubing.
E. Use carbon-steel pipe hangers and supports metal trapeze pipe hangers and metal framing systems and attachments for general service applications.
F. Use stainless-steel pipe hangers and stainless-steel attachments for hostile environment applications.
G. Use thermal hanger-shield inserts for insulated piping and tubing.
H. Horizontal-Piping Hangers and Supports: Comply with NFPA requirements. Unless otherwise indicated and except as specified in piping system Sections, install the following types:
1. Adjustable, Steel Clevis Hangers (MSS Type 1): For suspension of noninsulated or insulated, stationary pipes NPS 1/2 to NPS 30.
2. Steel Pipe Clamps (MSS Type 4): For suspension of NPS 1/2 to NPS 24 if little or no insulation is required.
3. Adjustable, Swivel-Ring Band Hangers (MSS Type 10): For suspension of noninsulated, stationary pipes NPS 1/2 to NPS 8.
4. Split Pipe Ring with or without Turnbuckle Hangers (MSS Type 11): For suspension of noninsulated, stationary pipes NPS 3/8 to NPS 8.
5. Extension Hinged or Two-Bolt Split Pipe Clamps (MSS Type 12): For suspension of noninsulated, stationary pipes NPS 3/8 to NPS 3.
6. U-Bolts (MSS Type 24): For support of heavy pipes NPS 1/2 to NPS 30.
7. Pipe Saddle Supports (MSS Type 36): For support of pipes NPS 4 to NPS 36, with steel-pipe base stanchion support and cast-iron floor flange or carbon-steel plate.
8. Pipe Stanchion Saddles (MSS Type 37): For support of pipes NPS 4 to NPS 36, with steel-pipe base stanchion support and cast-iron floor flange or carbon-steel plate, and with U-bolt to retain pipe.
9. Adjustable Pipe Saddle Supports (MSS Type 38): For stanchion-type support for pipes NPS 2-1/2 to NPS 36 if vertical adjustment is required, with steel-pipe base stanchion support and cast-iron floor flange.
21 05 29 - 9
HANGERS AND SUPPORTS FOR FIRE SUPPRESSION PIPING AND
EQUIPMENT
I. Vertical-Piping Clamps: Unless otherwise indicated and except as specified in piping system Sections, install the following types:
1. Extension Pipe or Riser Clamps (MSS Type 8): For support of pipe risers NPS 3/4 to
NPS 24.
2. Carbon- or Alloy-Steel Riser Clamps (MSS Type 42): For support of pipe risers NPS 3/4 to NPS 24 if longer ends are required for riser clamps.
J. Hanger-Rod Attachments: Comply with NFPA requirements.
K. Building Attachments: Comply with NFPA requirements. Unless otherwise indicated and except as specified in piping system Sections, install the following types:
1. Steel or Malleable-Concrete Inserts (MSS Type 18): For upper attachment to suspend pipe hangers from concrete ceiling.
2. C-Clamps (MSS Type 23): For structural shapes.
3. Side-Beam Brackets (MSS Type 34): For sides of steel or wooden beams.
L. Saddles and Shields: Comply with NFPA requirements. Unless otherwise indicated and except as specified in piping system Sections, install the following types:
1. Steel-Pipe-Covering Protection Saddles (MSS Type 39): To fill interior voids with insulation that matches adjoining insulation.
2. Protection Shields (MSS Type 40): Of length recommended in writing by manufacturer to prevent crushing insulation.
3. Thermal Hanger-Shield Inserts: For supporting insulated pipe.
M. Comply with NFPA requirements for trapeze pipe-hanger selections and applications that are not specified in piping system Sections.
N. Comply with MFMA-103 for metal framing system selections and applications that are not specified in piping system Sections.
O. Use mechanical-expansion anchors instead of building attachments where required in concrete construction.
END OF SECTION 21 05 29
© 2019 by the American Institute of Architects and EYP Inc.
Warning: This AIA MasterSpec based document is protected by U.S. Copyright Law and International Treaties. It was created by licensee EYP Inc. for Antietam National Battlefield Visitor Center Rehabilitation, National Park Service. A valid, current MasterSpec license is required for
21 05 29 - 10
HANGERS AND SUPPORTS FOR FIRE SUPPRESSION PIPING AND
EQUIPMENT
21 05 53 - 1
IDENTIFICATION FOR FIRE-SUPPRESSION PIPING AND EQUIPMENT
SECTION 21 05 53 - IDENTIFICATION FOR FIRE-SUPPRESSION PIPING AND EQUIPMENT
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Equipment labels.
2. Pipe labels.
3. Stencils.
4. Valve tags.
1.2 ACTION SUBMITTALS
A. Product Data: For each type of product.
B. Samples: For color, letter style, and graphic representation required for each identification material and device.
C. Equipment-Label Schedule: Include a listing of all equipment to be labeled and the proposed content for each label.
D. Valve Schedules: Valve numbering scheme.
PART 2 - PRODUCTS
2.1 EQUIPMENT LABELS
A. Metal Labels for Equipment:
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Brady Corporation.
b. Brimar Industries, Inc.
c. Carlton Industries, LP.
d. Champion America.
e. Craftmark Pipe Markers.
f. emedco.
g. Kolbi Pipe Marker Co.
h. LEM Products Inc.
i. Marking Services, Inc.
j. Seton Identification Products.
2. Material and Thickness: Brass, 0.032 inch or anodized aluminum, 0.032 inch thick, with predrilled holes for attachment hardware.
3. Letter Color: Black or white.
21 05 53 - 2
4. Background Color: Red.
5. Minimum Label Size: Length and width vary for required label content, but not less than
2-1/2 by 3/4 inch.
6. Minimum Letter Size: 1/4 inch for name of units if viewing distance is less than 24 inches, 1/2 inch for viewing distances up to 72 inches, and proportionately larger lettering for greater viewing distances. Include secondary lettering two-thirds to three-fourths the size of principal lettering.
7. Fasteners: Stainless-steel self-tapping screws.
8. Adhesive: Contact-type permanent adhesive, compatible with label and with substrate.
B. Label Content: Include equipment's Drawing designation or unique equipment number, Drawing numbers where equipment is indicated (plans, details, and schedules), and the Specification Section number and title where equipment is specified.
C. Equipment-Label Schedule: For each item of equipment to be labeled, on 8-1/2-by-11-inch bond paper. Tabulate equipment identification number and identify Drawing numbers where equipment is indicated (plans, details, and schedules) and the Specification Section number and title where equipment is specified. Equipment schedule shall be included in operation and maintenance data.
2.2 PIPE LABELS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Actioncraft Products, Inc.; a division of Industrial Test Equipment Co., Inc.
2. Brady Corporation.
3. Brimar Industries, Inc.
4. Carlton Industries, LP.
5. Champion America.
6. Craftmark Pipe Markers.
7. emedco.
8. Kolbi Pipe Marker Co.
9. LEM Products Inc.
10. Marking Services Inc.
11. Seton Identification Products.
B. General Requirements for Manufactured Pipe Labels: Preprinted, color-coded, with lettering indicating service and showing flow direction according to ASME A13.1.
C. Pretensioned Pipe Labels: Precoiled, semirigid plastic formed to cover full circumference of pipe and to attach to pipe without fasteners or adhesive.
D. Self-adhesive Pipe Labels: Printed plastic with contact-type, permanent-adhesive backing.
E. Pipe-Label Contents: Include identification of piping service using same designations or abbreviations as used on Drawings, pipe size, and an arrow indicating flow direction.
1. Flow-Direction Arrows: Integral with piping-system service lettering to accommodate both directions or as separate unit on each pipe label to indicate flow direction.
2. Lettering Size: Size letters according to ASME A13.1 for piping.
21 05 53 - 3
F. Pipe-Label Colors:
1. Background Color: Safety Red.
2. Letter Color: White.
2.3 STENCILS
A. Stencils for Piping:
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Brimar Industries, Inc.
b. Carlton Industries, LP.
c. Champion America.
d. Craftmark Pipe Markers.
e. Kolbi Pipe Marker Co.
f. Marking Services Inc.
2. Lettering Size: Size letters according to ASME A13.1 for piping.
3. Stencil Material: Aluminum.
4. Stencil Paint: Safety Red, exterior, gloss, alkyd enamel. Paint may be in pressurized spray-can form.
5. Identification Paint: White, exterior, alkyd enamel. Paint may be in pressurized spray-can form.
2.4 VALVE TAGS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Actioncraft Products, Inc.; a division of Industrial Test Equipment Co., Inc.
2. Brady Corporation.
3. Brimar Industries, Inc.
4. Carlton Industries, LP.
5. Champion America.
6. Craftmark Pipe Markers.
7. emedco.
8. Kolbi Pipe Marker Co.
9. LEM Products Inc.
10. Marking Services Inc.
11. Seton Identification Products.
B. Description: Stamped or engraved with 1/4-inch letters for piping-system abbreviation and 1/2-inch numbers.
1. Tag Material: Brass, 0.032 inch or anodized aluminum, 0.032 inch thick, with predrilled holes for attachment hardware.
2. Fasteners: Brass wire-link chain.
3. Valve-Tag Color: Safety Red.
4. Letter Color: White.
21 05 53 - 4
C. Valve Schedules: For each piping system, on 8-1/2-by-11-inch bond paper. Tabulate valve number, piping system, system abbreviation (as shown on valve tag), location of valve (room or space), normal-operating position (open, closed, or modulating), and variations for identification.
Mark valves for emergency shutoff and similar special uses.
1. Valve-tag schedule shall be included in operation and maintenance data.
PART 3 - EXECUTION
3.1 PREPARATION
A. Clean piping and equipment surfaces of incompatible primers, paints, and encapsulants, as well as dirt, oil, grease, release agents, and other substances that could impair bond of identification devices.
3.2 GENERAL INSTALLATION REQUIREMENTS
A. Coordinate installation of identifying devices with completion of covering and painting of surfaces where devices are to be installed.
B. Coordinate installation of identifying devices with locations of access panels and doors.
C. Install identifying devices before installing acoustical ceilings and similar concealment.
3.3 EQUIPMENT LABEL INSTALLATION
A. Install or permanently fasten labels on each major item of mechanical equipment.
B. Locate equipment labels where accessible and visible.
3.4 PIPE LABEL INSTALLATION
A. Piping: Painting of piping is specified in Section 09 91 23 "Interior Painting."
B. Stenciled Pipe-Label Option: Stenciled labels may be provided instead of manufactured pipe labels, at Installer's option. Install stenciled pipe labels, complying with ASME A13.1, on each piping system.
1. Identification Paint: Use for contrasting background.
2. Stencil Paint: Use for pipe marking.
C. Pipe-Label Locations: Locate pipe labels where piping is exposed or above accessible ceilings in finished spaces; machine rooms; accessible maintenance spaces such as shafts, tunnels, and plenums; and exterior exposed locations as follows:
1. Near each valve and control device.
2. Near each branch connection excluding short takeoffs. Where flow pattern is not obvious, mark each pipe at branch.
3. Near penetrations and on both sides of through walls, floors, ceilings, and inaccessible enclosures.
21 05 53 - 5
4. At access doors, manholes, and similar access points that permit a view of concealed piping.
5. Near major equipment items and other points of origination and termination.
6. Spaced at maximum intervals of 50 feet along each run. Reduce intervals to 25 feet in areas of congested piping and equipment.
7. On piping above removable acoustical ceilings. Omit intermediately spaced labels.
D. Directional Flow Arrows: Arrows shall be used to indicate direction of flow in pipes including pipes where flow is allowed in both directions.
3.5 VALVE-TAG INSTALLATION
A. Install tags on valves and control devices in fire-suppression piping systems. List tagged valves in a valve-tag schedule.
B. Valve-Tag Application Schedule: Tag valves according to size, shape, and with captions similar to those indicated in "Valve-Tag Size and Shape" Subparagraph below:
1. Valve-Tag Size and Shape:
a. Wet-Pipe Sprinkler System: 2 inches, round.
END OF SECTION 21 05 53
© 2019 by the American Institute of Architects and EYP Inc.
Warning: This AIA MasterSpec based document is protected by U.S. Copyright Law and International Treaties. It was created by licensee EYP Inc. for Antietam National Battlefield Visitor Center Rehabilitation, National Park Service. A valid, current MasterSpec license is required for
21 05 53 - 6
21 11 19 - 1
FIRE-DEPARTMENT CONNECTIONS
SECTION 21 11 19 - FIRE-DEPARTMENT CONNECTIONS
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Yard-type fire-department connections.
1.2 ACTION SUBMITTALS
A. Product Data: For each type of product.
1. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for each fire-department connection.
PART 2 - PRODUCTS
2.1 YARD-TYPE FIRE-DEPARTMENT CONNECTION
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Elkhart Brass Mfg. Co., Inc.
2. Fire Protection Products, Inc.
3. Fire-End & Croker Corporation.
4. GMR International Equipment Corporation.
5. Guardian Fire Equipment, Inc.
6. Potter Roemer LLC.
7. Wilson & Cousins Inc.
B. Standard: UL 405.
C. Type: Exposed, freestanding.
D. Pressure Rating: 175 psig minimum.
E. Body Material: Corrosion-resistant metal.
F. Inlets: Brass with threads according to NFPA 1963 and matching local fire-department sizes and threads. Include extension pipe nipples, brass lugged swivel connections, and check devices or clappers.
G. Caps: Brass, lugged type, with gasket and chain.
H. Escutcheon Plate: Round, brass, floor type.
I. Outlet: Bottom, with pipe threads.
21 11 19 - 2
FIRE-DEPARTMENT CONNECTIONS
J. Number of Inlets: Two.
K. Sleeve: Brass.
L. Sleeve Height: 18 inches.
M. Escutcheon Plate Marking: Similar to "AUTO SPKR."
N. Finish, Including Sleeve: Polished chrome plated.
O. Outlet Size: NPS 4.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine conditions, with Installer present, for compliance with requirements for installation tolerances and other conditions affecting performance of fire-department connections.
B. Examine roughing-in for fire-suppression standpipe system to verify actual locations of piping connections before fire-department connection installation.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 INSTALLATION
A. Install two protective pipe bollards on sides of each fire-department connection. Comply with requirements for bollards in Section 05 50 00 "Metal Fabrications."
B. Install automatic (ball-drip) drain valve at each check valve for fire-department connection.
END OF SECTION 21 11 19
Warning: This AIA MasterSpec based document is protected by U.S. Copyright Law and International Treaties. It was created by licensee EYP Inc. for Antietam National Battlefield Visitor Center Rehabilitation, National Park Service. A valid, current MasterSpec license is required for
21 13 13 - 1
WET-PIPE SPRINKLER SYSTEMS
SECTION 21 13 13 - WET-PIPE SPRINKLER SYSTEMS
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Pipes, fittings, and specialties.
2. Cover system for sprinkler piping.
3. Specialty valves.
4. Sprinklers.
5. Alarm devices.
6. Manual control stations.
7. Control panels.
8. Pressure gauges.
B. Related Requirements:
1. Section 21 11 19 "Fire Department Connections" for exposed-, flush-, and yard-type fire department connections.
2. Section 28 46 21.11 “Addressable Fire-Alarm Systems” for connections to fire alarm system.
1.2 DEFINITIONS
A. Standard-Pressure Sprinkler Piping: Wet-pipe sprinkler system piping designed to operate at working pressure of 175-psig maximum.
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product.
1. Include rated capacities, operating characteristics, electrical characteristics, and furnished specialties and accessories.
B. Shop Drawings: For wet-pipe sprinkler systems.
1. Include plans, elevations, sections, and attachment details.
2. Include diagrams for power, signal, and control wiring.
C. Delegated-Design Submittal: For wet-pipe sprinkler systems indicated to comply with performance requirements and design criteria, including analysis data signed and sealed by the qualified professional engineer responsible for their preparation.
21 13 13 - 2
WET-PIPE SPRINKLER SYSTEMS
1.4 INFORMATIONAL SUBMITTALS
A. Coordination Drawings: Sprinkler systems, drawn to scale, on which the following items are shown and coordinated with each other, using input from…