This document contains questions and answers related to a solicitation for the rehabilitation of the Antietam Visitor Center. Key details include that the solicitation is from the National Park Service for renovations including new exhibits, mechanical and electrical systems. The project involves renovations to restrooms, offices and other spaces as well as the addition of a temporary visitor center during construction. Bidders had questions about the scope of work clarifying requirements for items like plaster removal, stone repairs, flashing materials and HVAC controls. Other questions addressed responsibilities for temporary utilities, allowances and whether subcontracted labor rates apply.
View the file
Other files
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CHOH
151201
Question
Answer
I am interested in bidding this project and was able to download the documents but I do not see any architectural pages. Do you know if these are available?
There are architectural sheets. I am not sure why this Contractor wasn't able to download them.
The architectural sheets are at the end of Volume 1.
Is an MDE permit required, and, if so, has it been obtained by
NPS?
AE RESPOINSE: NPS is in the process of acquiring all required permits. Plans and calculations were submitted by the A/E to MDE for review on 6/22; as of the date of this email, comments or revisions from MDE on the application have not been received.
We are an 8(a), Woman Owned, Hub Zone business, and we plan to self‐perform a minimum of 30% of the work on this contract. Are we required to prepare a small business participation plan? No. Small Business Participation Plans are only required for Large Businesses.
May we present primary and alternate candidates for the key personnel roles? Please present primary candidates only.
Reference note D05 / A4. Shall we price the plaster removal as containing ACM?
AE RESPONSE: No. The existing plaster above the Bookstore ceiling should be removed, but per the
Hazardous Materials (HazMat) drawings, the plaster material has NOT been identified as containing
ACM. Note D05 should be revised to read “EXISTING PLASTER CEILING (CONCEALED ABOVE
EXISTING ACOUSTIC PANEL CEILING) TO BE REMOVED”.
We would like to confirm that the Safety Manager’s resume(s) should be presented twice (in Subfactor 2B – Safety and in
Subfactor 3B – Key Personnel).
The Safety Manager's resume only needs to be submitted once. List that person in both places and note that the resume is provided.
Factor 4 states that PPIRS evaluation reports can be submitted in lieu of PPQs. Can CPARs (Contractor Performance
Assessment Reporting System reports) also be submitted in lieu of PPQs?
PPIRS is a companion system to CPARS. It receives the completed CPARS report cards, including contractor comments, as well as other statistical reports on smaller‐value contracts.
Completed/Final reports from either the CPARS system or PPIRS system will be considered. Draft reports may carry less weight. Past Performance information for projects submitted as examples of
Past Experience is requested.
We are finding it difficult to get in contact with Contracting
Officers for PPQs requests due to COVID‐19 closures. Are we able to submit previously completed PPQs?
Yes.
Subfactor 2A – Management Approach is limited to 4 pages. Do the 4 pages include Quality Control, Organization Chart and
Description, Business Practices Unique to this Project and
Location, and Subfactor 2B – Safety?
The 4 page limit applies to the Management Approach only. In this narrative please address Quality
Control, Organization Chart and Description, and Business Practices Unique to this Project and
Location. Subfactor 2B ‐ Safety should be addressed as a separate subfactor. There is no page limit listed for Subfactor 2B use your judgment.
Subfactor 2A states that the information in the section should be narrative format. Should the organizational chart in this section also be in narrative format or is a diagram acceptable? NPS RESPONSE: An organizational chart is acceptible however we do want to see the qualifications of key personnel
Can the 4 pages for the Management Approach and the 6 pages for the Technical Approach be double‐sided? These will be submitted electronically and will be single sided.
Small business requirements – Page 21 of 192 of the solicitation, Special Clause H.4 part (b) states – “The contractor shall ensure a minimum 20% of the total contract value is performed by Small Business.” The first page of the Small
Business Subcontracting Plan states that the goal for Small
Business Concerns is 43%. Please clarify which is correct.
SMALL BUSINESS PARTICIPATION: Small business participation on Page 22, SPECIAL CLAUSE H.4:
Requires a minimum of 20% of the total contract value to be performed by small business. If at any point during the performance of the contract it becomes apparent that the goals will not be met a recovery plan will be requested and if upon contract completion the required % is not obtained it will be appropriately documented in the past performance record. / Separately from Special Clause
H.4, see also Page 58, SMALL BUSINESS SUBCONTRACTING: The goals set in FAR 52.219‐9 are set for all Government agencies. If you are a large business and are requested to submit a subcontracting plan as the apparent successful offeror, the plan should demonstrate the contractor’s proposed subcontracting percentages as they relate to the proposed amount and the small business goals identified in the solicitation. If at any point during the performance of the contract it becomes apparent that the goals will not be met, the appropriate supporting documentation shall be provided to demonstrate the good faith effort. The contractor will not be considered in breach of the contract.
Will the NPS be removing existing furniture and artifacts prior to demolition activities in the existing VC? AE RESPONSE: Other than the entry desk, all exhibits and furniture will be removed. The entry desk is the Contractor's responsibility
Will exhibit drawings be issue prior to bid? There is likely to be coordination work required with the work under this contract. No. Exhibit drawings are still in progress but should be available by sometime in January. The design teams for construction drawings and exhibit design did coordinate the two. As soon as they are available, the exhibit design documents will be provided upon Contracting Officer's approval.
Section 1/A22 shows new elevator footing and pit wall installed underneath the existing stairwell. Please clarify how this is to be accomplished.
AE RESPONSE: The intention is to have the top of the new elevator pit foundation wall become the new support of the existing stair on grade. The elevator pit wall at the southeast face of the pit wall is to step up (from the Exhibit Floor Level to the First Floor level) along the bottom of the existing concrete stair in order to support it. In constructing this, the edge of the stair will be slightly undermined, and the Contractor will need to install sheeting and shoring to prevent soil loss below the stair. The new concrete wall would then be poured with a stepped profile to follow the underside of the slab and any gaps between the top of the concrete wall and the underside of the existing stair slab should be packed tight with blocking or non‐shrink grout. The shelf on which the stair slab will sit will be 4” wide to allow room for the 8” CMU wall to be built on top of the concrete pit wall. Please note that given that this is a stair on grade, this is believed to be the most cost effective approach, however, there is a bit of risk of movement. Should the stair move slightly it could be easily repaired. Alternatively at the Contractor’s option, the edge of the existing stair could be underpinned, which might slightly reduce risk of movement. The work described in this response should be included in the Base Bid.
The bid form identifies item 5 option 4 as systems control allowance. Spec section 012700 definition of contract line items does not include this item 5. Section 012601 par 1.2 allowances does not address item 5. Please identify the allowance amount to be carried in the bid for item 5 option 4.
AE RESPONSE: Provide a price for CLIN Item 5, Option 4 as noted in the in the Contract Price
Schedule. CLIN item 5, Option 4 should be the price for the compatible Controls System to support any combination of the PV array areas noted in Option 1, Option 2, and Option 3, and to provide a fully functional PV system with connection to the building electrical system.
Government Acceptance Period: Box 13.d. of the SF 1442 shows: d. Offers providing less than _____0________ calendar days for Government acceptance after the date offers are due will not be considered and will be rejected . Offerors must list the number of days in Box 17 (page 2) of the SF 1442.
Is this (that is, “0”) the correct government acceptance period?
This number should be 90 calendar days.
There is no specification for HVAC temperature controls, is there a facility control manufacture that must be used for this work?
AE RESPONSE: Specification Section 23 09 23 ‐ DIRECT DIGITAL CONTROL (DDC) SYSTEM FOR HVAC has been added to the Project Specification, and is attached.
Drawing S4 indicates that the trellis is by others but there is a specification Section 107353 for this work. Is the trellis a part of this project to be included under the base bid? NPS RESPONSE: Trellis work is part of the base bid.
1. is a BAS workstation required to be provided under this contract, and if yes, please provide a specification for workstation and software, location of workstation, and specification of which systems it should monitor/control
A/E RESPONSE: Specification Section 23 09 23 ‐ DIRECT DIGITAL CONTROL (DDC) SYSTEM FOR HVAC, which includes information on workstation requirements, has been added to the Project
Specification, and is attached.
what is the purpose and specification for the BAS control panel shown on Detail 1, M7? A/E RESPONSE: Specification Section 23 09 23 ‐ DIRECT DIGITAL CONTROL (DDC) SYSTEM FOR HVAC has been added to the Project Specification, and is attached.
Building Automation Controls are shown on the drawings however there is no specification. Is this intentional? A/E RESPONSE: Specification Section 23 09 23 ‐ DIRECT DIGITAL CONTROL (DDC) SYSTEM FOR HVAC has been added to the Project Specification, and is attached.
Please confirm a chain of custody is required for the millwork materials, as stated in 01 67 00 and 01 81 13. A/E RESPONSE: Yes, chain of custody documentation is required per the Specifications.
Please provide a color for the SS‐1 Corian product.
NPS RESPONSE: Color samples shall be provided as a submittal from which NPS will select a color.
Drawing sheet 71 of 195 A5 Titled Temporary Visitor Center
Plan and Notes shows dimensions of this structure as 70’ x 98’.
Specification Division 13 – Special Construction 133423
Modular Building and drawing notation #7 stipulates that product could be a purchase or lease item. These dimensions as shown leaves no alternative but to purchase this modular temporary structure. In lieu of utilizing fleet goods, which could
ONLY be obtain from a new production. Would it be acceptable to provide this temporary modular structure dimensioned slightly different but maintaining the configurated floor plan
NPS RESPONSE: Yes. The Contractor may submit a proposed design which may vary from the plan but which is close to the space and configuration shown.
Will this temporary visitors center modular structure require a fire suppression sprinkler system as it exceeds 5000 sf.? Due to
CORVID 19, we were unable to ascertain any definitive information, on this matter, from the Maryland State Fire
Marshal’s Office.
A fire suppression system is not required.
A/E RESPONSE: The National Park Service (NPS) is the authority having jurisdiction (AHJ) for this project, not the Maryland State Fire Marshal. NFPA 1 (Sections 4.4 & 4.5) and NFPA 101 (Sections
12.3.5, 36.3.5, 38.3.5) are the Fire Code and Life Safety Code for this project and building as adopted by NPS Directive NPS‐58. NFPA 1 and NFPA 101 does not require automatic sprinkler protection for extinguishment for life safety for this temporary non‐separated multiple occupancy (Assembly, Business and Mercantile) use building and NPS directives do not require automatic sprinklers to satisfy any property protection requirements.
Additionally, as a clarification to Specification Section 13 34 23 ‐ Modular Buildings, Item 2.2.V.13: A fully functional and com;liant fire detection and alarm system with complete smoke and fire detection shall be provided by the Contractor for all rooms and spaces per NFPA 72 and 101.
Monitoring and supervision of this temporary facility shall be provided by an approved communicator compatible with the Federal MegaCenter requirements.
“Each Volume shall be submitted in separate email attachments”. Is the government looking for offerors to submit two separate emails, one with a combined Volume I and the other with a combined Volume II? Or is it looking for two separate emails for each Volume, with each Volume’s content split into separate or individual email attachments—with no consolidation of Volume contents into a single PDF? The government is looking for an attachement for volume I and an attachment for volume II. These can be sent in one email or in multiple emails depending on size.
What all is to be submitted on bid day besides the Bid Form and
Bid Bond AND do we submit to the
CS_DSC_Proposal_Submission@nps.gov.agenda address?
Please see Section L.
Will you please clarify what % is required for MBE and/or SBE?
Also, is there a MBE form to submit or letter we should submit stating MBE will be met? See Solicitation requirements.
Will you please confirm the time difference in Denver is 2 hours and that the bid is to be submitted at 2:00PM Denver time? Submission times listed are in Mountain Time zone. See the Solicitation Form SF1442 Box 13, as
Amended.
Does a UX monitoring firm need to be onsite whenever underground work is being done? This is a very expensive item if required. Or, do we just submit a UXO Plan?
The Contractor will be required to submit an historic preservation plan. In that plan, address how the contractor will monitor and report arecheological finds during construction. The Contractor will not be required to have a full time archeological monitor on site during ground disturbing work.
NPS did an arecheological survey during design.
Sheet S4: Detail 2 Roof Framing Plan – Note states Trellis by
Others. Please confirm that the trellis is by others and not by the General Contractor.
A/E RESPONSE: All trellises are to be included in the overall scope of the General Contractor. The intent of this note is that the trellises are not depicted in detail on the Structural Drawings. They should be provided in the configuration, material, and member sizes indicated on the Architectural
Drawings, with the “. . . MANUFACTURER TO PROVIDE LOADS IMPARTED FOR REVIEW” by the
Structural Engineer, as noted.
Sheet S4: Detail 1 Level 02 Framing Plan – Note states New Stair including top landing by Others. Please confirm that the stair and landing is by others and not by the General Contractor.
A/E RESPONSE: The intent of this note is that the top stair landing is to be included in the overall scope of the General Contractor, and should be provided by the stair manufacturer utilizing a similar support system as the stair. See Architectural Drawings for additional information.
Could you please provide a Geotechnical Report for this project. NPS Response: No geotechnical report was developed for this project.
As per Sheet #128 (P1) DEMOLITION NOTES: Note #1 – To accurately bid this portion, can the Owner please release the as‐ build drawings of the existing plumbing system? Or, confirm the old and new systems are similar in fixture counts and pipe lengths/sizes?
A/E RESPONSE: As built drawings are not available, and during the on site survey most of the existing plumbing sanitary and domestic water piping for the existing restrooms were concealed in hard ceilings and tiled walls. To clarify the demolition scope, the following written description has been provided to describe the extent of demolition per area of the building: Existing 3/4" domestic cold water serving an existing hose bibb located on the west wall of the Auditorium as indicated on plumbing drawings.
Existing specific plumbing items to be removed in the project scope include, but are not limited to, the items below:
Existing Mechanical Room:
‐Remove all existing domestic water piping, fittings, valves and associated components up to the water service entrance. Cap existing incoming water service for future connection.
‐Remove existing domestic water heater and expansion tank.
Existing Kitchenette/Pantry:
‐Remove existing sink fixture.
‐Remove existing all associated domestic water piping.
‐Remove existing sanitary and vent piping.
Existing Women’s and Men’s Restrooms:
‐Remove all existing plumbing fixtures ‐ Women’s (5 water closets, 3 or 4 lavatories in counter) / Men’s (4 water closets, 4 urinals, 3 or 4 lavatories in counter).
‐Remove all existing domestic water piping, fittings, valves and associated components.
‐Remove all existing sanitary and vent piping and drains.
Existing Janitor Closet (adjacent to Auditorium):
‐Remove existing service sink.
‐Remove all existing domestic water piping, fittings, valves and associated components.
‐Remove all existing sanitary and vent piping and drains.
Existing Lobby area:
‐Remove existing drinking fountain on northwest lobby wall as shown on Drawing A2
‐Remove existing cold water supply and waste which is located in the Mechanical Room.
Existing Mechanical Closet on lower level:
‐Remove existing clearwater sump basin, pump and piping.
Existing Roof
‐Remove existing roof (2) drains and associated piping.
In addition, NPS Drawing 302 41,007A (Sheet 2 of 4) from the 1977 Restroom Renovation, which graphically depicts plumbing fixture layouts in the Toilet Room area, has been provided (attached) FOR INFORMATION ONLY. This drawing appears to be mostly accurate in terms of overall fixture locations, with the following exceptions:
‐In the Men’s and Women’s Toilet Rooms, the individual wall‐mounted lavatories have been replaced with a continuous counter with built‐ in, recessed lavatories. Also, the small lavatories shown in the accessible toilet stalls are no longer provided.
1) As per Sheet #128 (P1) DEMOLITION NOTES: Note #1 says to
“Leave debris and disconnected equipment on floor for removal”. Can you please clarify who is responsible for removing the demolished material and equipment?
A/E Response: The portion of Note #1 cited above should be disregarded. Removal of debris and disconnected equipment should be included in the Base Bid.
ADDITIONAL ITEM: Although not a response to a bidder question, the following item is added to clarify construction at the Office Wing:
At Wall Sections 1, 2, and 3/A15, 4&5/A19, and Plan Details 1 through 8/A18, widen cavity between the CMU backup and the back face of the stone base by 1” in order to achieve consistent dimensioning, create a wider cavity, and create a greater change of plane between the outside face of siding above and the outside face of the stone base below (currently 1/2”, revised to 1 1/2”). The following dimensions are affected:
‐Detail 4/A19 ‐ Dimension of from outside face of CMU backup to outside face of stone base to be revised from 7 1/8” to 8”.
‐Detail 4/A18 ‐ Dimensions to be revised as follows: 7” dimension to be revised to 8”; 1’‐4 1/4” dimension to be revised to 1’‐5 1/4”; 4 7/8” dimension to be revised to 3 7/8”.
‐Detail 5/A18 ‐ 1’‐4 1/4” dimension to be revised to 1’‐5 1/4”.
‐Detail 6/A18 ‐ Dimensions to be revised as follows: 7” dimension to be revised to 8”; 1’‐4 1/4” dimension to be revised to 1’‐5 1/4”; 3” dimension to be revised to 4”; 1” dimension (cavity) to be revised to 2”.
‐Detail 2/A15 – 1 5/8” dimension from face of sheathing to face of stone base (below extended sill) to be revised to 2 5/8”.
Reference: Drawing L9 detail 5 ‐ Drawing L9 detail 5 note stated
“contractor to install government furnished bench”. Please confirm that the note is correct., we’re just required to install the bench provided by the government.
NPS RESPONSE: The note is correct. Yes, the bench will be provided by the Government.
Sheet T4 has a note “Existing AV Rack to be Relocated”. Please clarify if this is part of the scope of this contract or part of the exhibit scope of work. NPS RESPONSE: This is part of the scope of the Contract.
Sheet S5 shows the locations of the PV panels and has a note regarding the support details “…Contractor to provide pricing for reinforcement as a unit cost. All field conditions to be verified…”. Please clarify how the costs for the post supports are to be addressed. Is this to be included with the alternates?
Or will this be handled separately after field conditions have been verified and a design has been made?
A/E RESPONSE: Contractor to provide cost for the support posts as indicated in the CD's. Refer to
Details 8 & 9 on Drawing S8 for specific details. If existing conditions are determined to be different than that shown, Contractor shall notify COR and provide justification for additional costs. Note:
the design and engineering of the PV support rails (mounted to the support posts) and panels are a delegated design to be provided by the Contractor with each PV option.
Section 040140.61 – subsection 3.3.A states “At locations indicated, remove stone that has deteriorated…”. There are no locations indicated on the exterior elevations for stone repair/replacement. Please clarify.
A/E RESPONSE: From A/E's general field observations, there are no areas where the stone appears to be deteriorated enough to warrant removal and reinstallation. In the course of the performing the work the Contractor may identify areas that require this work, or may want to remove stone to facilitate other aspects of the work (installing flashing and roofing, adding a new exterior wall). This
Specification section will govern in these instances.
Who is responsible for the cost of the temp service to the temporary visitors center, specifically the installation of the pole and OH lines? Who pays for the power usage by the visitors center over the course of the project?
A/E RESPONSE: Contractor shall coordinate with and pay local utility provider for the installation of the temporary power service (including meter) and associated infrastructure. NPS will pay monthly utility bills.
Would NPS entertain the idea of a wood framed building built on site for the temporary Visitors Center if it meets all of the remaining specification requirements?
NPS RESPONSE: Yes
For the new UG electrical and telecom service, we assume that the bidder carries conduit only for telecom, conduit, transformer pad and the secondary feeders from the transformer to the electrical room only with the transformer and primary feeders to the transformer from the pole by the power company. Please confirm this and that the power company fees are paid for by NPS.
A/E RESPONSE: All associated costs for electrical service to be Contactor's responsibility. NPS will only pay the monthly electricity bill for the Temporary Visitor Center, and eventually the monthly electricity bill for the renovated Visitor Center after NPS takes occupancy.
Note on C6 calls out a water valve and meter per Washington
County standards. Is this by the water company paid for by NPS or by the bidders utilities sub?
A/E RESPONSE: Contractor shall furnish and install water valve and water meter per Washington
County standards. Contractor shall coordinate with the local utility and pay any utility fees associated with temporary and permanent water service connections for the Temporary Visitor
Center and the Main Visitor Center.
Is it the intent of the documents to require full abatement and removal of lead based paint, or only remove where needed to perform the new construction.
A/E RESPONSE: All locations containing Lead Based Paint (LBP) are to be abated. Please refer to the
HazMat Drawings (H Series) included in the Construction Documents, specifically the LBP table on
Sheet H6 and the Legend and First Level Plan on Drawing H6, for locations where LBP is identified as being present.
Are the new monitors shown on Elevation 5/A26 by bidders or are we providing mounts only?
Contractor is to provide and install the following:
1)Lobby a.(2) 55” monitors and (2) ceiling hung, “pipe‐type” brackets.
i.Basis of design for the monitors shall be Samsung QN55Q80TAFXZC or Sony XBR‐55X950G, in selecting an equal product the following items should be taken into account: LED/QLED/Full LED
(OLED should be avoided to prevent static image burn in), HDMI 1080p ports and ethernet connection capability.
ii.Moun ng for both monitors shall be a pipe‐type bracket supported from ceiling structure above, the mount shall be capable of housing the cables to the TV as well as providing swivel and tilt capabilities. Basis of Design: Peerless‐AV Model PLCM‐UNL(‐CP) Universal Ceiling Mounts iii.Blocking as required in ceiling cavity.
b.The Contractor shall provide cabling connec vity to each of the monitors. At the desk there are
(2) AV outlets which are intended to provide an HDMI cable to each of the TV’s. The Contractor shall provide HDMI cabling from this wall plate stubbed into the wall behind the front desk. This cable shall be routed to above the ceiling and shall be brought down to the TV via the pipe for the TV mount. Additionally, Each TV shall have a Category 6A Cable brought down from the ceiling outlet to the TV via the mounting bracket.
c. The exact location and mounting of these monitors may need to be further coordinated with the separate NIC Exhibit Design package if directed by the COR.
2)Conference Room a.(1) 55” monitor and wall mounted bracket. Basis of Design for the monitor shall be Samsung
QN55Q80TAFXZC or Sony XBR‐55X950G. In selecting an equal product, the following items should be taken into account: HDMI 1080p ports and ethernet connection capability. The mounting bracket
Basis of Design shall be: Peerless‐AV model: SP850 b.Blocking as required in wall cavity.
c.The Contractor shall provide a recessed PAC box located behind the TV mount. This PAC box shall have power, Data outlets, and additional AV connectivity with the floor box as per the drawings.
There don’t appear to be any requirements on the Plumbing
Drawings to replace or reset the Auditorium roof drains in the new gutter. See 5/A20. If the gutter is built cut out around existing drains, there is a potential for leakage into the wall cavity on the outside wall. Should bidders carry the cost to pull the drain body, build the gutter, then reset the drain body and basket so that drains are installed correctly?
A/E RESPONSE: The design intent is to remove the existing gutters and downspouts at the
Auditorium and restore roof drainage to a condition similar to the original configuration. Three new
4" dia. terne coated copper downspouts are to connect to the three new 4" dia. canopy drains within the new gutter as shown on 1/A7 and 5/A20, and will run vertically down within the three projecting wood facade "chase" elements that project from the face of the stone wall as shown on
4/A9, and then daylight after running below the bottom of these elements to three new concrete splash blocks, all items to be provided by the Contractor. See attached Sketch SK‐A‐01.
Please confirm that the chase wall assembly on the Auditorium exterior is existing. See 5/A20 and 3/A31. A/E RESPONSE: Confirmed. It is existing.
Should bidders carry the PV access walk pads as an alternate as well as the PV panels? A/E RESPONSE: Yes.
Note D5 on A4 calls out a potentially ACM containing ceiling above the existing ACT ceiling. This is not identified on the
Hazmat plan. Should bidders ignore this or carry it in their abatement costs?
A/E RESPONSE: The existing plaster above the Bookstore ceiling should be removed, but per the
Hazardous Materials (HazMat) drawings, the plaster material has NOT been identified as containing
ACM. Note D05 should be revised to read “EXISTING PLASTER CEILING (CONCEALED ABOVE
EXISTING ACOUSTIC PANEL CEILING) TO BE REMOVED”.
How much of the soffit assembly on 2/A21 is existing? We assume that the header and cladding, the soffit and cladding are existing and that we add the roof blocking and 3/4" sloped plywood, the fascia piece under the coping , the coping and the roof insulation and membrane. Please confirm.
A/E RESPONSE: Confirmed. Items shaded in grey are existing, items not shaded are new. The current condition includes a gutter and vertical wood fascia piece behind it, which altered the original fascia condition; after the gutter is removed, the profile of the fascia will be restored to the original sloping condition through removal and replacement of the vertical piece which will be hidden behind the coping. At the Contractor's option, the entire sloping fascia piece can be provided as new.
The shade spec calls for a 3% light filtering shade fabric, as does the finish schedule on the plans. However the cross section for the shade on A36 calls for a blackout shade. Please confirm what fabric should be used.
A/E RESPONSE: The information in the Specification and the Finish Schedule is correct. The note on
Detail 8/A36 should be revised to read “Roller Window Shade” instead of "Blackout Shade".
Please confirm only Offices #112, 113, 114, Bookstore #119 and
Office #120 are the only rooms to receive shades. Vestibule
#101, Lobby #102, and Hallway #103 will NOT receive shades.
A/E RESPONSE: Confirmed.
Why are the electrical floor heaters and snow melt system included in the mechanical equipment schedule? A/E RESPONSE: Mechanical Engineers sized the floor heaters and snow melt system and indicated it on those drawings. Contractor shall coordinate between trades as necessary.
Note 4 Drawing E4 calls for the Contractor to pay Potomac
Edison for installation of electrical utility. Can an allowance be established that all bidders can use? If not, has any contact been made during design that would yield a point of contact at
Potomac Edison that bidders can contact to get an estimation of these fees?
A/E RESPONSE: EYP has been in contact with Potomac Edison and asked for the estimate to be prepared. Please coordinate and contact Matt Voorhaar, mvoorhaar@firstenergycorp.com, 301‐
7906‐306, and reference Work Request #60180358 Notification #752153762.
A sidewall sprinkler head detail is shown on 2/FP4. No sidewall sprinkler heads are shown on floor plans. Where is this detail used? A/E RESPONSE: Sidewall sprinklers are provided at Vestibule 101 and Lobby 102.
Are Antietam Broadband costs to be included by bidders or is
NPS picking up these costs?
A/E RESPONSE: All associated costs for the Telecom service to be coordinated by the Contractor with Antietam Broadband and provided by the Contractor. NPS will only pay the monthly telecom bill for the Temporary Visitor Center, and eventually the monthly telecom bill for the renovated
Visitor Center after NPS takes occupancy.
A form was supplied for the bid bond, but not for the P&P bond. Is there a particular form that you would like for us to use for the P&P bond, or is there an AIA form to use for the
P&P bond?
Performance and Payment bonds are only required in accordance with Solicitation Form SF1442 Box
12.a and 12.b.
Regarding attached flashing: Spec calls for Asphalt flashing and specifies Advance Coppersealtite 2000. Coppersealtite is a non‐ asphalt flashing. The other flashing specified, Hohmann C‐Coat is no longer manufactured because it has asphalt on it and it melts at high temperatures. The replacement flashing is
Hohmann C‐fab na, non‐asphalt. A/E RESPONSE: This question is similar to Bidder Question 113 below; please refer to response to that question.
Contract specifications liner #233113 Para 2.4 calls out Closed
Cell liner with perforated inner wall But ductwork execution calls out fibrous type no perf 1” thick ? (Please Advise)
A/E RESPONSE: Lining shall be as specified in Paragraph 2.4. Paragraph 3.8.E.4 describes methodology for cleaning fibrous duct liner. This paragraph is not applicable since the specified lining is closed cell type.
In Addition, drawing M2 Titled Mechanical Legends and
Abbreviations clearly shows dotted lines as indicator of liner nowhere on contract drawings except details does it show sound line? (Please Advise) A/E RESPONSE: Lining shall be provided as depicted in Detail 1 on Sheet M8. Note that the Contract
Documents are inclusive of floor plans, details and Specifications.
Pertaining to Unit Masonry Work Division 4 section 042200‐15 paragraph 3.12 “Corrective Work” (a) Removal and replacement of exist wall unit masonry due to cracks, discoloration requires some bid parameters as a percentage or a square foot area should allowed which would be included as part of the base bid. What percent should be allowed? (b)
Removal of loose mortar or discoloration or deteriorated mortar requiring repointing should have an allowance of so many linear feet to be included as part of the base bid. How many linear feet should be allowed?
A/E Response: Referenced Specification Section 04 2200 is for Concrete Unit Masonry (CMU). On this project, all new CMU is used as backup and is a concealed condition. The requirements of paragraph 3.12 Corrective Work stand as written in terms of installation of new CMU and corrective measures to be taken if it is installed in a defective manner. No percentages or linear feet need to be listed.
Please provide a drawing showing any req'd condensate wast piping serving the VRF system equipment.
A/E RESPONSE: Please refer to keynotes on Drawing M6 for instructions on routing of condensate piping from FCU's.
On Drawing A41 “Finish Legend” ST‐I Pennsylvania Flagstone, please provide manufacturer, size, color, and thickness. A/E RESPONSE: Intent is for Contractor to match the existing flagstone. Contractor shall provide samples for approval by COR.
Please confirm that signage is not a part of the contract. If so, please provide specification and a signage legend.
A/E RESPONSE: Exterior, pin‐mounted building identification signage as shown on Elevation 4/A9 is to be included in the Base Building bid ‐ this signage is to match the existing pin‐mouned signage in height and font, color to be selected by COR from manufacturer's full standard color range. Interior code‐required signage should also be provided in the Base Building bid. Include this signage (at
Bathrooms, Utility Rooms, and Elevator) at the following 15 locations: Men's Restroom 104, Women's Restroom 105, Family Restroom 106, Storage Room 107, Janitor Closet 108, Plumbing
Room 117, Electrical Room 118, Mechanical Room 003, Storage Room 004, Telecom Room 006, at all three elevator entrances, plus two extra signs at locations to be determined. Provide signage schedule for review by COR. Other interior building signage, including signage at other rooms, is NIC and will be provided via a separate Exhibit Design package. The aesthetic design of the Code‐
Required signage which is in this Contract may need to coordinate with the signage in the separate
Exhibit Design package at the direction of the COR. Signage in the Base Bid is to comply with all applicable provisions of the 2015 Architectural Barriers Act (ABA) Standards. Signage to be 9" square minimum and have raised lettering, symbols, and braille characters having uniform faces, sharp corners, and precisely formed lines and profiles. Acrylic signs to have composite‐sheet thickness of 1/4" thick, up to three colors with contrasting raised letters/symbols, non‐glare sheen, colors as selected by COR from manufacturer's full range. Provide three text lines for Room Number, Room Name, and one line TBD. Finish perimeter of sign panel smooth. Edge condition to be square cut, corner condition in elevation to be round. Mounting by tamper‐proof screws, four total, one in each corner, or two‐face tape as directed by COR. Provide manufacturer's standard sign assemblies with raised letters/symbols using the applique process, with plastic letter and symbols of a contrasting colors permanently fused to a flat plastic sign panel.
Please indicate what manufacturers will be required to furnish and install all HVAC Temperature Controls? A/E RESPONSE: Specification for BAS system will be issued as an amendment by NPS.
Since all existing ductwork and HVAC equipment is new for this project, please delete specification section 23 31 13, 3.8. Since all ductwork will be new and we plan to keep all open‐ends of ductwork shrink wrapped and dust free during construction.
A/E RESPONSE: While there is not existing ductwork to remain in the project, item 3.8 of
Specification section 23 3113 is applicable to the cleaning of new ductwork prior to testing, adjusting and balancing. Contractor shall meet the intent of providing clean ductwork. If alternate method to duct cleaning is being proposed, Contractor shall submit that propposed method to the COR for approval.
Please provide a detail showing the rough‐in of the new in‐floor radiant heating system. A/E RESPONSE: Refer to publicly available product data, including Installation Guide and
Instructions, for the product referenced in the Electric Floor Heater Schedule. The mat is typically installed on thinset above the concrete subfloor, with the stone flooring installed above. Install radiant heating mats above thinset mortar specifically manufactured for this purpose to ensure maximum contact, above he concrete subfloor. Thickset mortar and stone to be installed above the mat, provide good contact with the mat with no air gaps. Test mat per Specification section 225963 and per manufacturer’s instructions.
Drawing A6, Keynote 22 reference a new GWB soffit in the exhibit rooms but there is no location shown on this drawing.
Please confirm that this soffit is only required at the area shown at 3/A13 and 1/A12.
A/E RESPONSE: Confirmed. Keynote 22 is incorrectly keyed on Drawing A6 (keynote is shown at the northwest window in the Bookstore, and should read D22). Please see 1/A12, 3/A13, and RCP 1/A34 for location of these soffits.
Please confirm that the contractor is not responsible for any work associated with items noted as FF&E in the contract documents.
A/E RESPONSE: FFE is to be provided and installed by NPS, and is primarily furniture or office equipment. Examples of Contractor furnished, Contractor installed (CFCI) equipment identified on the drawings include, but are not limited to, Breakroom refrigerator, dishwasher, and microwave.
Drawing A9, Keynote 81 notes that the existing plywood fascia is to be repaired as required. Please clarify anticipated scope of the repair work and if it is to exceed the General Note #2 requirement of scraping and repainting these areas.
A/E RESPONSE: See Details included in Drawing Set, including those on Sheets A17, A20, A21, and
A23, for specific alterations to existing fascias. Also, please note that on Elevation 2/A9, the existing northwest fascia at the Auditorium is correctly identified with Keynote 81 (existing fascia to be repaired), however a detail is not provided. This fascia needs to be rebuilt with new materials to achieve the same fascia configuration as shown in Detail 5/A20, but without the gutter. Also on
Elevation 2/A9, at the New Office Addition, the new fascia is incorrectly identified by Keynote 81
(existing fascia to be repaired), this should be W26 (new fascia). At the Observation Room, all four fascias are to be re‐built as indicated in Details on A17 and A20. In response to this bidder question, in addition to the repairs discussed above, provide an allowance included in the Base Bid for removal and/or repair of 20% of existing plywood fascias and soffits to remain with new Cedar‐
Faced Plywood to match existing, which will cover any potential repairs that may be required.
Please note that General Note #2 regarding requirement for scraping and repainting also applies.
Specification 123661.19, 2.2.F states that quartz counters should be installed without joints. Please confirm this requirement as the proposed front information desk layout of the Silestone (SS‐2) does not allow for a seamless installation.
A/E RESPONSE: Preference would be for as few seams as possible, or no seams. If seams are required due to the limitations of the materials, Contractor shall submit proposed joint locations in shop drawing for approval by COR.
Aside from the specification (275116) and speaker locations shown on drawings T6 & T7, there is not sufficient information provided to bid a complete system. Please provide clarification regarding design intent and basis of design for specified equipment.
A/E RESPONSE: The intent was to provide new speakers in the locations shown with connections to the relocated head end system. The control zones should be the same as the existing system. The
Contractor shall be responsible to obtain the existing zone information prior to demolition of the existing system.
Aside from the specification (275123) there is not sufficient information provided to bid a complete system. Please provide clarification regarding design intent and basis of design for specified equipment.
A/E RESPONSE: The intent was to provide new speakers in the locations shown with connections to the relocated head end system. The control zones should be the same as the existing system. The
Contractor shall be responsible to obtain the existing zone information prior to demolition of the existing system.
Is the EC responsible for providing and installing the TMGB, TGBs and TBB as required for the project? A/E RESPONSE: The TMGB, TGB and TBB's shall be provided by the Contractor, coordination of the work between trades shall be performed as necessary. The final connection of these components of the telecom systems shall be performed by a licensed Electrician.
Is innerduct (Flexible Pathway) required for fiber cables if armored fiber cables are used? A/E RESPONSE: Innerduct is not required.
Are Arlington Cable Loops an acceptable cable support system instead of J‐Hooks?
A/E RESPONSE: The Contractor shall meet requirements within the Specifications for any product used.
Is the EC responsible for providing and installing cable tray as required outside of the Telecommunications Rooms? A/E RESPONSE: The cable trays shall be provided by the Contractor, coordination of the work between trades shall be performed as necessary.
Is the EC responsible for providing and installing the tele‐power poles?
A/E RESPONSE: Telecom/Power Poles are existing to remain. For the Telecom portion, the
Contractor shall provide the ductbank stubbed up at the base of the existing Telecom pole. Please clarify the question if it is not referring to these exterior poles.
Is the EC responsible for providing and installing sleeves for the telecommunications cabling? A/E RESPONSE: The sleeves shall be provided by the Contractor, coordination of the work between trades shall be performed as necessary. The final bonding for any Telecom components to the grounding system shall be performed by a licensed Electrician.
For 18" ladder tray used inside the telecommunications rooms, is Chatsworth part number acceptable 1050‐718
A/E RESPONSE: All parts of the Telecommunications pathways need to conform to the Division 27
Specifications. Product submittals are required for Telecom components.
Is the GC responsible for providing and installing Plywood in the
Telecommunications Rooms?
A/E RESPONSE: The plywood shall be provided by the Contractor, coordination of the work between trades shall be performed as necessary.
Please provide part number and manufacturer for the required rack mounted Power Strips.
A/E RESPONSE: The Contractor shall submit a rack mounted power strip that conforms to the requirements within the Div. 27 Specifications.
Are Chatsworth 19" Equipment Racks acceptable? They are not listed as a manufacturer, but they are listed as an acceptable manufacturer for cabinets.
A/E RESPONSE: As long as the rack selected meets the requirements for floor mounted racks, Chatsworth is an acceptable alternative manufacturer
Specification calls for "BNC" type connectors, is this correct as most new Coaxial cable(s) are terminated using "F" type connectors? A/E RESPONSE: Final connector types shall be coordinated with AV selections.
Is EC responsible for providing Weatherproof housings for telecommunications outlets per Telecom Symbols
A/E RESPONSE: The weatherproof housing shall be provided by the Contractor, coordination of the work between trades shall be performed as necessary.
"FB1" Telecom Symbol indicates 4 data cables are to be provided and terminated on jacks but indicates that the faceplate is a 2 port. Should this be a 4 port faceplate or two (2)
2 port faceplates?
A/E RESPONSE: The note on the legend is a typo ‐ Detail 4 on drawing T9 shows a single (4) port faceplate. However if the floor box that is selected has the means to provide the power and data required it shall be acceptable to use (2) 2‐port faceplates. The Contractor shall have the flexibility for means and methods as long as data and power requirements are met.
91 Please provide Color of WLAN Category 6A cables. A/E RESPONSE: WLAN CAT 6A color shall be blue.
93 Please provide color of AV TV Category 6A cables. A/E RESPONSE: AV CAT 6A color shall be blue.
There are two (2) Half Shaded outlets on the exterior wall of
Room 001 that did not have a "dot" or a" 4" next to them. How many cables should be provided? A/E RESPONSE: Each outlet shall have (2) CAT 6A cables.
Should all floor boxes receive OSP Category 6A cabling? A/E RESPONSE: The intent for the floor box was to have conduit buried inside the slab. Running the
CAT 6A cable within this conduit would not require OSP cabling. Standard CAT 6A cabling would be sufficient.
There is a Ceiling "AV 4" symbol in the middle of the
Auditorium Room 110. How many and what types of cable should it receive?
A/E RESPONSE: The AV symbol is used to indicate that the ceiling outlet is for the projector. The
Standard NPS cable requirement is (4) CAT6A cables.
There is a note against three (3) ceiling "2" locations in the
Lobby Room 102 indicating that this is for TV locations. Should these receive 1 Data and 1 Coax as a "TV" outlet?
A/E RESPONSE: The symbols shown on the floor plans provided incorrect guidance. The intent was for Data cables to be provided from the ceiling down to the TV's. The AV outlets on the wall were intended to provide HDMI direct input into the monitor from the Lobby desk. The proposed solution is to stub the HDMI cables into the wall behind the TV and route to above the ceiling and utilize the mounting bracket down to the TV.
Drawing T6 indicates there are three (3) four data outlets and a
"FB1" outlet. T8 detail there indicates there are two (2) Half shaded triangles, a "M1" outlet, a "AV" outlet and a "FB1” outlet. Please provide what is needed in this conference room as the two drawings do not agree. A/E RESPONSE: There should be (3) total Data outlets, where the M1 is indicated there should be a
(3)rd data outlet in the PAC box behind the monitor. This is the layout indicated on T6.
Drawing T1 indicates that all cabling is to be Category 6A but drawing T8 Detail A indicates Category 6 angled patch panels. Is cabling Category 6A or Category 6? A/E RESPONSE: This is a typo. Patch Panel should be CAT 6A to match cabling requirements.
Who is responsible for providing the KVM1 unit in the equipment rack? If it is the telecom contractor, please provide make and model.
A/E RESPONSE: Contractor shall provide a KVM unit that is compatible with the Security system selected.
Who is responsible for providing and installing the 2U UPS
Unit? If it is the telecom contractor, please provide make and model.
A/E RESPONSE: The Contractor shall be responsible for providing a UPS within the rack which meets the requirements listed in the Div. 27 Specifications. The A/E does not identify which work is done by the Contractor and which work is done by their subcontractor(s).
103 How many FSR1 Racks are required? A/E RESPONSE: The drawing indicates (1) FSR1 Rack.
Drawing T12 indicates that a 12 strand MM fiber is to be run from a wall fiber enclosure to a rack mounted fiber enclosure in
FSR1 rack. Please provide rating of fiber (OM1, OM2, OM3 or
OM4). A/E RESPONSE: Contractor shall utilize OM3 or OM4 Fiber.
Drawing T8 Detail A indicates that the 1RU fiber shelf will have
(2) 12 strand adapter panels. If only one (1) 12 strand fiber is being routed from the electrical room, why do you need two adapter panels?
A/E RESPONSE: Contractor shall provide (1) 12 strand adapter panel and fill unused space with a blank panel.
Who is providing and installing the wall mounted Fiber enclosure in the electrical room for the termination of the incoming service provided by Antietam Broadband?
A/E RESPONSE: Antietam Broadband is providing and installing this enclosure. The Contractor would then be responsible to extend fiber from this enclosure to the Telecom Room.
Is a Chatsworth 6" Channel depth equipment rack per 66353‐
703 acceptable?
EYP RESPONSE: As long as the rack selected meets the requirements for floor mounted racks, Chatsworth is an acceptable alternative manufacturer. Any equipment that meets the required salient features may be submitted as an "equal" for approval. If the equipment does not meet the requirements of the Specifications it may be rejected.
Drawings do not indicate if cable tray is required and what type and size of cable tray is required. Please clarify.
A/E RESPONSE: Drawing T6 does show 12"x4" basket cable tray (see room 102 for tag).
Are Horizontal wire managers needed with angled patch panels?
A/E RESPONSE: Angled Category 6 Patch panels is a typo. Utilize standard patch panels conforming to Div. 27 Specifications.
Bosch is listed in some of the product specifications as manufacturer. Can a complete Bosch system be provided?
A/E RESPONSE: As long as the Specifications are met for the security system and the complete Bosch system can perform the desired Video system operations then a complete Bosch system is acceptable.
Can we provide one input to the elevator controller and have all cabs respond or is the IDS system expected to interface with each cab controller?
A/E RESPONSE: The intent was to provide (1) input to the controller. As there is only one elevator cab on the project with front and back doors, we are not totally clear on this question ‐ please advise if additional clarification is required.
Please provide appropriate wage rate for Telecommunications, Sound System and Security Installers.