230923 Direct Digital Control (DDC) System for HVAC cc_0005.pdf

PDF 323 KB Posted

Attached to
ANTI 225963 Rehabilitate Antietam Visitor Center
Solicitation number
140P2020R0080
Issued by

About this file

This document is a solicitation for the rehabilitation of the Antietam Visitor Center. The National Park Service is seeking contractors to rehabilitate the visitor center located at Antietam National Battlefield in Maryland. Key details include rehabilitation of the building interior and exhibits, replacement of HVAC and electrical systems, and installation of universal design features. The solicitation number is 140P2020R0080 and responses are due by May 22, 2022. Pricing will be fixed price with a period of performance from June 2022 to December 2023. The anticipated award date is June 2022.

View the file

Other files

File Type Posted
Sol_140P2020R0080_Amd_0007.pdf PDF
REMAINING RFI Questions and Answers_0006.pdf PDF
Sol_140P2020R0080_Amd_0006.pdf PDF
1977 Restroom Renovation 302_41007A-PLNS_ELEV_0005.pdf PDF
Temp Visitor Center Life Safety Markup_07.24.2020_0005.pdf PDF
ANTI 225963 Final Q and A Amend 05_0005.pdf PDF
Sol_140P2020R0080_Amd_0005.pdf PDF
Sol_140P2020R0080_Amd_0004.pdf PDF
ANTI 225963 Site Visit Attendees July 02 2020_0003.pdf PDF
Sol_140P2020R0080_Amd_0003.pdf PDF
B09_ Amend 01 140P2020R0080_0002.pdf PDF
Sol_140P2020R0080_Amd_0002.pdf PDF
B11_ANTI 225963_PreBid_Agenda_0002.pdf PDF
Sol_140P2020R0080_Amd_0001.pdf PDF
B08_Attach 03 Drawings Vol 1 of 2.pdf PDF
B08_Attach 01 Specifications Vol 1 of 2.pdf PDF
B08_Attach 02 Specifications Vol 2 of 2.pdf PDF
B08_Attach 04 Drawings Vol 2 of 2.pdf PDF
B08_Attach 05 Appendix.pdf PDF
B08_140P2020R0080.pdf PDF
B08_Attach 06 Solit_PSP_Vol_II_PriceSched.xlsx XLSX spreadsheet
B08_Attach 08 Wage Decision 06-04-2020.pdf PDF
B08_Attach 13 Solit_PSP_Vol_II_GenRefs ANTI 225963.doc DOC document
B08_Attach 10 Solit_PSP_Vol_I_PastPerf_REQD ANTI 225963.doc DOC document
B08_Attach 14 Solit_PSP_Vol_II_SubKPlanForm_REQD ANTI 225963.doc DOC document
B08_Attach 09 Solit_PSP_Vol_I_Exp_REQD ANTI 225963.docx DOCX document
B08_Attach 11 SF24-16d.pdf PDF
Sol_140P2020R0080.pdf PDF
B08_Attach 07 Virtual Site Visit Floor Plans.pdf PDF
B08_Attach 15 Solit_PSP_Vol_II_HazMat ANTI 225963.doc DOC document
B08_Attach 12 Solit_PSP_Vol_II_Equals ANTI 225963.doc DOC document
Show all 31

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ANTI – 225963

05222020

23 09 23 - 1

DIRECT DIGITAL CONTROL (DDC) SYSTEM FOR HVAC

SECTION 23 09 23 - DIRECT DIGITAL CONTROL (DDC) SYSTEM FOR HVAC

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. DDC system for monitoring and controlling of HVAC systems.

2. Delivery of selected control devices to equipment and systems manufacturers for factory installation and to HVAC systems installers for field installation.

B. Related Requirements:

1. Refer to contract drawings for Sequence of Operation.

2. Communications Cabling:

a. Section 27 15 13 "Communications Copper Horizontal Cabling" for balanced twisted pair communications cable.

3. Raceways:

a. Section 26 05 33 "Raceways and Boxes for Electrical Systems" for raceways for low-voltage control cable.

b. Section 27 05 28 "Pathways for Communications Systems" for raceways for balanced twisted pair cabling and optical fiber cable.

1.2 DEFINITIONS

A. Algorithm: A logical procedure for solving a recurrent mathematical problem. A prescribed set of well-defined rules or processes for solving a problem in a finite number of steps.

B. Analog: A continuously varying signal value, such as current, flow, pressure, or temperature.

C. BACnet Specific Definitions:

1. BACnet: Building Automation Control Network Protocol, ASHRAE 135. A communications protocol allowing devices to communicate data over and services over a network.

2. BACnet Interoperability Building Blocks (BIBBs): BIBB defines a small portion of BACnet functionality that is needed to perform a particular task. BIBBs are combined to build the BACnet functional requirements for a device.

3. BACnet/IP: Defines and allows using a reserved UDP socket to transmit BACnet messages over IP networks. A BACnet/IP network is a collection of one or more IP subnetworks that share the same BACnet network number.

4. BACnet Testing Laboratories (BTL): Organization responsible for testing products for compliance with ASHRAE 135, operated under direction of BACnet International.

5. PICS (Protocol Implementation Conformance Statement): Written document that identifies the particular options specified by BACnet that are implemented in a device.

23 09 23 - 2

DIRECT DIGITAL CONTROL (DDC) SYSTEM FOR HVAC

D. Binary: Two-state signal where a high signal level represents ON" or "OPEN" condition and a low signal level represents "OFF" or "CLOSED" condition. "Digital" is sometimes used interchangeably with "Binary" to indicate a two-state signal.

E. Controller: Generic term for any standalone, microprocessor-based, digital controller residing on a network, used for local or global control. Three types of controllers are indicated: Network Controller, Programmable Application Controller, and Application-Specific Controller.

F. Control System Integrator: An entity that assists in expansion of existing enterprise system and support of additional operator interfaces to I/O being added to existing enterprise system.

G. COV: Changes of value.

H. DDC System Provider: Authorized representative of, and trained by, DDC system manufacturer and responsible for execution of DDC system Work indicated.

I. Distributed Control: Processing of system data is decentralized and control decisions are made at subsystem level. System operational programs and information are provided to remote subsystems and status is reported back. On loss of communication, subsystems shall be capable of operating in a standalone mode using the last best available data.

J. DOCSIS: Data-Over Cable Service Interface Specifications.

K. Gateway: Bidirectional protocol translator that connects control systems that use different communication protocols.

L. HLC: Heavy load conditions.

M. I/O: System through which information is received and transmitted. I/O refers to analog input (AI), binary input (BI), analog output (AO) and binary output (BO). Analog signals are continuous and represent control influences such as flow, level, moisture, pressure, and temperature. Binary signals convert electronic signals to digital pulses (values) and generally represent two-position operating and alarm status. "Digital," (DI and (DO), is sometimes used interchangeably with "Binary," (BI) and (BO), respectively.

N. I/P: Current to pneumatic.

O. LAN: Local area network.

P. LNS: LonWorks Network Services.

Q. LON Specific Definitions:

1. FTT-10: Echelon Transmitter-Free Topology Transceiver.

2. LonMark: Association comprising suppliers and installers of LonTalk products.

Association provides guidelines for implementing LonTalk protocol to ensure interoperability through a standard or consistent implementation.

3. LonTalk: An open standard protocol developed by the Echelon Corporation that uses a "Neuron Chip" for communication. LonTalk is a register trademark of Echelon.

4. LonWorks: Network technology developed by Echelon.

23 09 23 - 3

DIRECT DIGITAL CONTROL (DDC) SYSTEM FOR HVAC

5. Node: Device that communicates using CEA-709.1-C protocol and that is connected to a CEA-709.1-C network.

6. Node Address: The logical address of a node on the network, consisting of a Domain number, Subnet number, and Node number. "Node number" portion of an address is a number assigned to device during installation, is unique within a subnet, and is not a factory-set unique Node ID.

7. Node ID: A unique 48-bit identifier assigned at factory to each CEA-709.1-C device.

Sometimes called a "Neuron ID."

8. Program ID: An identifier (number) stored in a device (usually EEPROM) that identifies node manufacturer, functionality of device (application and sequence), transceiver used, and intended device usage.

9. Standard Configuration Property Type (SCPT): Pronounced "skip-it." A standard format type maintained by LonMark International for configuration properties.

10. Standard Network Variable Type (SNVT): Pronounced "snivet." A standard format type maintained by LonMark used to define data information transmitted and received by individual nodes. "SNVT" is used in two ways. It is an acronym for "Standard Network Variable Type" and is often used to indicate a network variable itself (i.e., it can mean "a network variable of a standard network variable type").

11. Subnet: Consists of a logical grouping of up to 127 nodes, where logical grouping is defined by node addressing. Each subnet is assigned a number, which is unique within a Domain. See "Node Address."

12. TP/FT-10: Free Topology Twisted Pair network defined by CEA-709.3 and is most common media type for a CEA-709.1-C control network.

13. TP/XF-1250: High-speed, 1.25-Mbps, twisted-pair, doubly terminated bus network defined by "LonMark Interoperability Guidelines" typically used only to connect multiple TP/FT-10 networks.

14. User-Defined Configuration Property Type (UCPT): Pronounced "U-Keep-It." A Configuration Property format type that is defined by device manufacturer.

15. User-Defined Network Variable Type (UNVT): Network variable format defined by device manufacturer. UNVTs create non-standard communications that other vendors' devices may not correctly interpret and may negatively impact system operation. UNVTs are not allowed.

R. Low Voltage: As defined in NFPA 70 for circuits and equipment operating at less than 50 V or for remote-control, signaling power-limited circuits.

S. Mobile Device: A data-enabled phone or tablet computer capable of connecting to a cellular data network and running a native control application or accessing a web interface.

T. Modbus TCP/IP: An open protocol for exchange of process data.

U. MS/TP: Master-slave/token-passing, IEE 8802-3. Datalink protocol LAN option that uses twisted-pair wire for low-speed communication.

V. MTBF: Mean time between failures.

W. Network Controller: Digital controller, which supports a family of programmable application controllers and application-specific controllers, that communicates on peer-to-peer network for transmission of global data.

23 09 23 - 4

DIRECT DIGITAL CONTROL (DDC) SYSTEM FOR HVAC

X. Network Repeater: Device that receives data packet from one network and rebroadcasts it to another network. No routing information is added to protocol.

Y. Peer to Peer: Networking architecture that treats all network stations as equal partners.

Z. POT: Portable operator's terminal.

AA. PUE: Performance usage effectiveness.

BB. RAM: Random access memory.

CC. RF: Radio frequency.

DD. Router: Device connecting two or more networks at network layer.

EE. Server: Computer used to maintain system configuration, historical and programming database.

FF. TCP/IP: Transport control protocol/Internet protocol.

GG. UPS: Uninterruptible power supply.

HH. USB: Universal Serial Bus.

II. User Datagram Protocol (UDP): This protocol assumes that the IP is used as the underlying protocol.

JJ. VAV: Variable air volume.

KK. WLED: White light emitting diode.

1.3 PREINSTALLATION MEETINGS

A. Preinstallation Conference: Conduct conference at Project site.

1.4 ACTION SUBMITTALS

A. Multiple Submissions:

1. If multiple submissions are required to execute work within schedule, first submit a coordinated schedule clearly defining intent of multiple submissions. Include a proposed date of each submission with a detailed description of submittal content to be included in each submission.

2. Clearly identify each submittal requirement indicated and in which submission the information will be provided.

3. Include an updated schedule in each subsequent submission with changes highlighted to easily track the changes made to previous submitted schedule.

B. Product Data: For each type of product include the following:

1. Construction details, material descriptions, dimensions of individual components and profiles, and finishes.

23 09 23 - 5

DIRECT DIGITAL CONTROL (DDC) SYSTEM FOR HVAC

2. Operating characteristics, electrical characteristics, and furnished accessories indicating process operating range, accuracy over range, control signal over range, default control signal with loss of power, calibration data specific to each unique application, electrical power requirements, and limitations of ambient operating environment, including temperature and humidity.

3. Product description with complete technical data, performance curves, and product specification sheets.

4. Installation, operation and maintenance instructions including factors effecting performance.

5. Bill of materials of indicating quantity, manufacturer, and extended model number for each unique product.

a. Workstations.

b. Servers.

c. Printers.

d. Gateways.

e. Routers.

f. Protocol analyzers.

g. DDC controllers.

h. Enclosures.

i. Electrical power devices.

j. UPS units.

k. Accessories.

l. Instruments.

m. Control dampers and actuators.

n. Control valves and actuators.

6. When manufacturer's product datasheets apply to a product series rather than a specific product model, clearly indicate and highlight only applicable information.

7. Each submitted piece of product literature shall clearly cross reference specification and drawings that submittal is to cover.

C. Software Submittal:

1. Cross-referenced listing of software to be loaded on each operator workstation, server, gateway, and DDC controller.

2. Description and technical data of all software provided, and cross-referenced to products in which software will be installed.

3. Operating system software, operator interface and programming software, color graphic software, DDC controller software, maintenance management software, and third-party software.

4. Include a flow diagram and an outline of each subroutine that indicates each program variable name and units of measure.

5. Listing and description of each engineering equation used with reference source.

6. Listing and description of each constant used in engineering equations and a reference source to prove origin of each constant.

7. Description of operator interface to alphanumeric and graphic programming.

8. Description of each network communication protocol.

9. Description of system database, including all data included in database, database capacity and limitations to expand database.

23 09 23 - 6

DIRECT DIGITAL CONTROL (DDC) SYSTEM FOR HVAC

10. Description of each application program and device drivers to be generated, including specific information on data acquisition and control strategies showing their relationship to system timing, speed, processing burden and system throughout.

11. Controlled Systems: Instrumentation list with element name, type of device, manufacturer, model number, and product data. Include written description of sequence of operation including schematic diagram.

D. Sustainable Design Submittals:

1. ENERGY STAR: Product Data for indicated products, showing compliance with requirements for ENERGY STAR product labeling.

2. Product Data: For adhesives, indicating VOC content.

3. Laboratory Test Reports: For adhesives, indicating compliance with requirements for low-emitting materials.

E. Shop Drawings:

1. General Requirements:

a. Include cover drawing with Project name, location, Owner, Architect, Contractor and issue date with each Shop Drawings submission.

b. Include a drawing index sheet listing each drawing number and title that matches information in each title block.

2. Include plans, elevations, sections, and mounting details where applicable.

3. Include details of product assemblies. Indicate dimensions, weights, loads, required clearances, method of field assembly, components, and location and size of each field connection.

4. Detail means of vibration isolation and show attachments to rotating equipment.

5. Plan Drawings indicating the following:

a. Screened backgrounds of walls, structural grid lines, HVAC equipment, ductwork, and piping.

b. Room names and numbers with coordinated placement to avoid interference with control products indicated.

c. Each desktop workstation, server, gateway, router, DDC controller, control panel instrument connecting to DDC controller, and damper and valve connecting to DDC controller, if included in Project.

d. Exact placement of products in rooms, ducts, and piping to reflect proposed installed condition.

e. Network communication cable and raceway routing.

f. Information, drawn to scale, of 1/8” = 1-0”.

g. Proposed routing of wiring, cabling, conduit, and tubing, coordinated with building services for review before installation.

6. Schematic drawings for each controlled HVAC system indicating the following:

a. I/O points labeled with point names shown. Indicate instrument range, normal operating set points, and alarm set points. Indicate fail position of each damper and valve, if included in Project.

23 09 23 - 7

DIRECT DIGITAL CONTROL (DDC) SYSTEM FOR HVAC

b. I/O listed in table format showing point name, type of device, manufacturer, model number, and cross-reference to product data sheet number.

c. A graphic showing location of control I/O in proper relationship to HVAC system.

d. Wiring diagram with each I/O point having a unique identification and indicating labels for all wiring terminals.

e. Unique identification of each I/O that shall be consistently used between different drawings showing same point.

f. Elementary wiring diagrams of controls for HVAC equipment motor circuits including interlocks, switches, relays, and interface to DDC controllers.

g. Narrative sequence of operation.

h. Graphic sequence of operation, showing all inputs and output logical blocks.

7. Control panel drawings indicating the following:

a. Panel dimensions, materials, size, and location of field cable, raceways, and tubing connections.

b. Interior subpanel layout, drawn to scale and showing all internal components, cabling and wiring raceways, nameplates, and allocated spare space.

c. Front, rear, and side elevations and nameplate legend.

d. Unique drawing for each panel.

8. DDC system network riser diagram indicating the following:

a. Each device connected to network with unique identification for each.

b. Interconnection of each different network in DDC system.

c. For each network, indicate communication protocol, speed and physical means of interconnecting network devices, such as copper cable type, or optical fiber cable type. Indicate raceway type and size for each.

d. Each network port for connection of an operator workstation or other type of operator interface with unique identification for each.

9. DDC system electrical power riser diagram indicating the following:

a. Each point of connection to field power with requirements (volts/phase//hertz/amperes/connection type) listed for each.

b. Each control power supply including, as applicable, transformers, power-line conditioners, transient voltage suppression and high filter noise units, DC power supplies, and UPS units with unique identification for each.

c. Each product requiring power with requirements (volts/phase//hertz/amperes/connection type) listed for each.

d. Power wiring type and size, race type, and size for each.

10. Monitoring and control signal diagrams indicating the following:

a. Control signal cable and wiring between controllers and I/O.

b. Point-to-point schematic wiring diagrams for each product.

11. Color graphics indicating the following:

a. Itemized list of color graphic displays to be provided.

23 09 23 - 8

DIRECT DIGITAL CONTROL (DDC) SYSTEM FOR HVAC

b. For each display screen to be provided, a true color copy showing layout of pictures, graphics, and data displayed.

c. Intended operator access between related hierarchical display screens.

F. System Description:

1. Full description of DDC system architecture, network configuration, operator interfaces and peripherals, servers, controller types and applications, gateways, routers and other network devices, and power supplies.

2. Complete listing and description of each report, log and trend for format and timing, and events which initiate generation.

3. System and product operation under each potential failure condition including, but not limited to, the following:

a. Loss of power.

b. Loss of network communication signal.

c. Loss of controller signals to inputs and outpoints.

d. Operator workstation failure.

e. Server failure.

f. Gateway failure.

g. Network failure

h. Controller failure.

i. Instrument failure.

j. Control damper and valve actuator failure.

4. Complete bibliography of documentation and media to be delivered to Government.

5. Description of testing plans and procedures.

6. Description of Government training.

G. Delegated-Design Submittal: For DDC system products and installation indicated as being delegated.

1. Supporting documentation showing DDC system design complies with performance requirements indicated, including calculations and other documentation necessary to prove compliance.

2. Schedule and design calculations for control dampers and actuators.

a. Flow at Project design and minimum flow conditions.

b. Face velocity at Project design and minimum airflow conditions.

c. Pressure drop across damper at Project design and minimum airflow conditions.

d. AMCA 500-D damper installation arrangement used to calculate and schedule pressure drop, as applicable to installation.

e. Maximum close-off pressure.

f. Leakage airflow at maximum system pressure differential (fan close-off pressure).

g. Torque required at worst case condition for sizing actuator.

h. Actuator selection indicating torque provided.

i. Actuator signal to control damper (on, close, or modulate).

j. Actuator position on loss of power.

k. Actuator position on loss of control signal.

23 09 23 - 9

DIRECT DIGITAL CONTROL (DDC) SYSTEM FOR HVAC

3. Schedule and design calculations for control valves and actuators.

a. Flow at Project design and minimum flow conditions.

b. Pressure-differential drop across valve at Project design flow condition.

c. Maximum system pressure-differential drop (pump close-off pressure) across valve at Project minimum flow condition.

d. Design and minimum control valve coefficient with corresponding valve position.

e. Maximum close-off pressure.

f. Leakage flow at maximum system pressure differential.

g. Torque required at worst case condition for sizing actuator.

h. Actuator selection indicating torque provided.

i. Actuator signal to control damper (on, close or modulate).

j. Actuator position on loss of power.

k. Actuator position on loss of control signal.

4. Schedule and design calculations for selecting flow instruments.

a. Instrument flow range.

b. Project design and minimum flow conditions with corresponding accuracy, control signal to transmitter, and output signal for remote control.

c. Extreme points of extended flow range with corresponding accuracy, control signal to transmitter, and output signal for remote control.

d. Pressure-differential loss across instrument at Project design flow conditions.

e. Where flow sensors are mated with pressure transmitters, provide information for each instrument separately and as an operating pair.

1.5 INFORMATIONAL SUBMITTALS

A. Coordination Drawings:

1. Plan drawings and corresponding product installation details, drawn to scale, on which the following items are shown and coordinated with each other, using input from installers of the items involved:

a. Product installation location shown in relationship to room, duct, pipe and equipment.

b. Structural members to which products will be attached.

c. Wall-mounted instruments located in finished space showing relationship to light switches, fire-alarm devices and other installed devices.

d. Size and location of wall access panels for products installed behind walls and requiring access.

2. Reflected ceiling plans and other details, drawn to scale, on which the following items are shown and coordinated with each other, using input from installers of the items involved:

a. Ceiling components.

b. Size and location of access panels for products installed above inaccessible ceiling assemblies and requiring access.

c. Items penetrating finished ceiling including the following:

1) Lighting fixtures.

23 09 23 - 10

DIRECT DIGITAL CONTROL (DDC) SYSTEM FOR HVAC

2) Air outlets and inlets.

3) Speakers.

4) Sprinklers.

5) Access panels.

6) Motion sensors.

7) Pressure sensors.

8) Temperature sensors and other DDC control system instruments.

B. Qualification Data:

1. Systems Provider Qualification Data:

a. Resume of project manager assigned to Project.

b. Resumes of application engineering staff assigned to Project.

c. Resumes of installation and programming technicians assigned to Project.

d. Resumes of service technicians assigned to Project.

e. Brief description of past project including physical address, floor area, number of floors, building system cooling and heating capacity, and building's primary function.

f. Description of past project DDC system, noting similarities to Project scope and complexity indicated.

g. Names of staff assigned to past project that will also be assigned to execute work of this Project.

h. Owner contact information for past project including name, phone number, and e-mail address.

i. Contractor contact information for past project including name, phone number, and e-mail address.

j. Architect and Engineer contact information for past project including name, phone number, and e-mail address.

2. Manufacturer's qualification data.

3. Testing agency's qualifications data.

C. Welding certificates.

D. Product Certificates:

1. Data Communications Protocol Certificates: Certifying that each proposed DDC system component complies with ASHRAE 135.

2. Data Communications Protocol Certificates: Certifying that each proposed DDC system component complies with LonWorks.

E. Preconstruction Test Reports: For each separate test performed.

F. Source quality-control reports.

G. Field quality-control reports.

H. Sample Warranty: For manufacturer's warranty.

23 09 23 - 11

DIRECT DIGITAL CONTROL (DDC) SYSTEM FOR HVAC

1.6 CLOSEOUT SUBMITTALS

A. Operation and Maintenance Data: For DDC system to include in emergency, operation, and maintenance manuals.

1. In addition to items specified in Section 01 78 23 "Operation and Maintenance Data," include the following:

a. Project Record Drawings of as-built versions of submittal Shop Drawings provided in electronic PDF format.

b. Testing and commissioning reports and checklists of completed final versions of reports, checklists, and trend logs.

c. As-built versions of submittal Product Data.

d. Names, addresses, e-mail addresses, and 24-hour telephone numbers of Installer and service representatives for DDC system and products.

e. Operator's manual with procedures for operating control systems including logging on and off, handling alarms, producing point reports, trending data, overriding computer control, and changing set points and variables.

f. Programming manuals with description of programming language and syntax, of statements for algorithms and calculations used, of point database creation and modification, of program creation and modification, and of editor use.

g. Engineering, installation, and maintenance manuals that explain how to:

1) Design and install new points, panels, and other hardware.

2) Perform preventive maintenance and calibration.

3) Debug hardware problems.

4) Repair or replace hardware.

h. Documentation of all programs created using custom programming language including set points, tuning parameters, and object database.

i. Backup copy of graphic files, programs, and database on electronic media such as DVDs.

j. List of recommended spare parts with part numbers and suppliers.

k. Complete original-issue documentation, installation, and maintenance information for furnished third-party hardware including computer equipment and sensors.

l. Complete original-issue copies of furnished software, including operating systems, custom programming language, operator workstation software, and graphics software.

m. Licenses, guarantees, and warranty documents.

n. Recommended preventive maintenance procedures for system components, including schedule of tasks such as inspection, cleaning, and calibration; time between tasks; and task descriptions.

o. Government training materials.

1.7 MAINTENANCE MATERIAL SUBMITTALS

A. Furnish extra materials and parts that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.

B. Include product manufacturers' recommended parts lists for proper product operation over four -year period following warranty period. Parts list shall be indicated for each year.

23 09 23 - 12

DIRECT DIGITAL CONTROL (DDC) SYSTEM FOR HVAC

C. Furnish parts, as indicated by manufacturer's recommended parts list, for product operation during one -year period following warranty period.

D. Furnish quantity indicated of matching product(s) in Project inventory for each unique size and type of following:

1. Network Controller: One.

2. Programmable Application Controller: One.

3. Application-Specific Controller: One.

4. Temperature Sensor and Transmitter: One.

1.8 QUALITY ASSURANCE

A. DDC System Manufacturer Qualifications:

1. Nationally recognized manufacturer of DDC systems and products.

2. DDC systems with similar requirements to those indicated for a continuous period of five years within time of bid.

3. DDC systems and products that have been successfully tested and in use on at least five past projects.

4. Having complete published catalog literature, installation, operation, and maintenance manuals for all products intended for use.

5. Having full-time in-house employees for the following:

a. Product research and development.

b. Product and application engineering.

c. Product manufacturing, testing, and quality control.

d. Technical support for DDC system installation training, commissioning, and troubleshooting of installations.

e. Government operator training.

B. DDC System Provider Qualifications:

1. Authorized representative of, and trained by, DDC system manufacturer.

2. In-place facility located within 50 miles of Project.

3. Demonstrated past experience with installation of DDC system products being installed for period within five consecutive years before time of bid.

4. Demonstrated past experience on five projects of similar complexity, scope, and value.

5. Each person assigned to Project shall have demonstrated past experience.

6. Staffing resources of competent and experienced full-time employees that are assigned to execute work according to schedule.

7. Service and maintenance staff assigned to support Project during warranty period.

8. Product parts inventory to support on-going DDC system operation for a period of not less than 5 years after Substantial Completion.

9. DDC system manufacturer's backing to take over execution of Work if necessary to comply with requirements indicated. Include Project-specific written letter, signed by manufacturer's corporate officer, if requested.

C. Testing Agency Qualifications: Member company of NETA.

1. Testing Agency's Field Supervisor: Certified by NETA to supervise on-site testing.

23 09 23 - 13

DIRECT DIGITAL CONTROL (DDC) SYSTEM FOR HVAC

1.9 PRECONSTRUCTION TESTING

A. Preconstruction Testing Service: Government will engage a qualified testing agency to perform preconstruction testing on field mockups.

1. Include test assemblies representative of proposed materials and construction.

2. Build mockup at testing agency facility using personnel, materials, and methods of construction that will be used at Project site.

3. Notify Contracting Officer seven days in advance of dates and times of tests.

1.10 WARRANTY

A. Manufacturer's Warranty: Manufacturer and Installer agree to repair or replace products that fail in materials or workmanship within specified warranty period.

1. Failures shall be adjusted, repaired, or replaced at no additional cost or reduction in service to Government.

2. Include updates or upgrades to software and firmware if necessary to resolve deficiencies.

a. Install updates only after receiving Government's written authorization.

3. Warranty service shall occur during normal business hours and commence within 24 hours of Government's warranty service request.

4. Warranty Period: Two years from date of Substantial Completion.

a. For Gateway: Two-year parts and labor warranty for each.

PART 2 - PRODUCTS

2.1 DDC SYSTEM MANUFACTURERS

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1. Honeywell International Inc.

2. Invensys Building Systems.

3. Johnson Controls, Inc.

4. Schneider Electric USA, Inc.

5. Siemens Industry, Inc., Building Technologies Division.

2.2 DDC SYSTEM DESCRIPTION

A. Microprocessor-based monitoring and control including analog/digital conversion and program logic. A control loop or subsystem in which digital and analog information is received and processed by a microprocessor, and digital control signals are generated based on control algorithms and transmitted to field devices to achieve a set of predefined conditions.

1. DDC system shall consist of a high-speed, peer-to-peer network of distributed DDC controllers, other network devices, operator interfaces, and software.

23 09 23 - 14

DIRECT DIGITAL CONTROL (DDC) SYSTEM FOR HVAC

B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

2.3 WEB ACCESS

A. DDC system shall be web based.

1. Web-Based Access to DDC System:

a. DDC system software shall be based on server thin-client architecture, designed around open standards of web technology. DDC system server shall be accessed using a web browser over DDC system network, using Government's LAN, and remotely over Internet through Government's LAN.

b. Intent of thin-client architecture is to provide operators complete access to DDC system via a web browser. No special software other than a web browser shall be required to access graphics, point displays, and trends; to configure trends, points, and controllers; and to edit programming.

c. Web access shall be password protected.

2. Web-Compatible Access to DDC System:

a. Workstation shall perform overall system supervision and configuration, graphical user interface, management report generation, and alarm annunciation.

b. DDC system shall support web browser access to building data. Operator using a standard web browser shall be able to access control graphics and change adjustable set points.

c. Web access shall be password protected.

2.4 PERFORMANCE REQUIREMENTS

A. Delegated Design, Qualified Professional Engineer: Engage a qualified professional engineer, as defined in Section 01 40 00 "Quality Requirements," to design DDC system to satisfy requirements indicated.

B. Delegated Design, Qualified Professional: Engage a qualified professional to design DDC system to satisfy requirements indicated.

1. System Performance Objectives:

a. DDC system shall manage HVAC systems.

b. DDC system control shall operate HVAC systems to achieve optimum operating costs while using least possible energy and maintaining specified performance.

c. DDC system shall respond to power failures, HVAC equipment failures, and adverse and emergency conditions encountered through connected I/O points.

d. DDC system shall operate while unattended by an operator and through operator interaction.

e. DDC system shall record trends and transaction of events and produce report information such as performance, energy, occupancies, and equipment operation.

23 09 23 - 15

DIRECT DIGITAL CONTROL (DDC) SYSTEM FOR HVAC

C. Surface-Burning Characteristics: Products installed in ducts, equipment, and return-air paths shall comply with ASTM E84; testing by a qualified testing agency. Identify products with appropriate markings of applicable testing agency.

1. Flame-Spread Index: 25 or less.

2. Smoke-Developed Index: 50 or less.

D. DDC System Speed:

1. Response Time of Connected I/O:

a. AI point values connected to DDC system shall be updated at least every five seconds for use by DDC controllers. Points used globally shall also comply with this requirement.

b. BI point values connected to DDC system shall be updated at least every five seconds for use by DDC controllers. Points used globally shall also comply with this requirement.

c. AO points connected to DDC system shall begin to respond to controller output commands within two second(s). Global commands shall also comply with this requirement.

d. BO point values connected to DDC system shall respond to controller output commands within two second(s). Global commands shall also comply with this requirement.

2. Display of Connected I/O:

a. Analog point COV connected to DDC system shall be updated and displayed at least every 10 seconds for use by operator.

b. Binary point COV connected to DDC system shall be updated and displayed at least every 10 seconds for use by operator.

c. Alarms of analog and digital points connected to DDC system shall be displayed within 30 seconds of activation or change of state.

d. Graphic display refresh shall update within four seconds.

e. Point change of values and alarms displayed from workstation to workstation when multiple operators are viewing from multiple workstations shall not exceed graphic refresh rate indicated.

E. Network Bandwidth: Design each network of DDC system to include at least 30 percent available spare bandwidth with DDC system operating under normal and heavy load conditions indicated.

Calculate bandwidth usage, and apply a safety factor to ensure that requirement is satisfied when subjected to testing under worst case conditions.

F. DDC System Data Storage:

1. Include capability to archive not less than 24 consecutive months of historical data for all I/O points connected to system, including alarms, event histories, transaction logs, trends and other information indicated.

23 09 23 - 16

DIRECT DIGITAL CONTROL (DDC) SYSTEM FOR HVAC

2. Local Storage:

a. Provide workstation with data storage indicated. Server(s) shall use IT industry standard database platforms and be capable of functions described in "DDC Data Access" Paragraph.

3. Cloud Storage:

a. Provide application-based and web browser interfaces to configure, upload, download, and manage data, and service plan with storage adequate to store all data for term indicated. Cloud storage shall use IT industry standard database platforms and be capable of functions described in "DDC Data Access" Paragraph.

G. DDC Data Access:

1. When logged into the system, operator shall be able to also interact with any DDC controller connected to DDC system as required for functional operation of DDC system.

2. System(s) shall be used for application configuration; for archiving, reporting and trending of data; for operator transaction archiving and reporting; for network information management; for alarm annunciation; and for operator interface tasks and controls application management.

H. Future Expandability:

1. DDC system size shall be expandable to an ultimate capacity of at least two times total I/O points indicated.

2. Additional DDC controllers, I/O and associated wiring shall be all that is needed to achieve ultimate capacity. Initial network infrastructure shall be designed and installed to support ultimate capacity.

3. Operator interfaces installed initially shall not require hardware and software additions and revisions for ultimate capacity.

I. Input Point Displayed Accuracy: Input point displayed values shall meet following end-to-end overall system accuracy, including errors associated with meter, sensor, transmitter, lead wire or cable, and analog to digital conversion.

1. Temperature, Dry Bulb:

a. Air: Within 0.5 deg F.

b. Space: Within 0.5 deg F.

c. Outdoor: Within 1 deg F.

2. Temperature, Wet Bulb:

a. Air: Within 0.5 deg F.

b. Space: Within 0.5 deg F.

c. Outdoor: Within 1 deg F.

J. Precision of I/O Reported Values: Values reported in database and displayed shall have following precision:

23 09 23 - 17

DIRECT DIGITAL CONTROL (DDC) SYSTEM FOR HVAC

K. DDC System Reliability:

1. Design, install and configure DDC controllers, gateways, routers, and to yield a MTBF of at least 40,000 hours, based on a confidence level of at least 90 percent. MTBF value shall include any failure for any reason to any part of products indicated.

2. If required to comply with MTBF indicated, include DDC system and product redundancy to maintain DCC system, and associated systems and equipment that are being controlled, operational and under automatic control.

3. Critical systems and equipment that require a higher degree of DDC system redundancy than MTBF indicated shall be indicated on Drawings.

L. Electric Power Quality:

1. Power-Line Surges:

a. Protect susceptible DDC system products connected to ac power circuits from power-line surges to comply with requirements of IEEE C62.41.

b. Do not use fuses for surge protection.

c. Test protection in the normal mode and in the common mode, using the following two waveforms:

1) 10-by-1000-mic.sec. waveform with a peak voltage of 1500 V and a peak current of 60 A.

2) 8-by-20-mic.sec. waveform with a peak voltage of 1000 V and a peak current of 500 A.

2. Power Conditioning:

a. Protect susceptible DDC system products connected to ac power circuits from irregularities and noise rejection. Characteristics of power-line conditioner shall be as follows:

1) At 85 percent load, output voltage shall not deviate by more than plus or minus 1 percent of nominal when input voltage fluctuates between minus 20 percent to plus 10 percent of nominal.

2) During load changes from zero to full load, output voltage shall not deviate by more than plus or minus 3 percent of nominal.

3) Accomplish full correction of load switching disturbances within five cycles, and 95 percent correction within two cycles of onset of disturbance.

4) Total harmonic distortion shall not exceed 3-1/2 percent at full load.

3. Ground Fault: Protect products from ground fault by providing suitable grounding.

Products shall not fail due to ground fault condition.

M. Backup Power Source:

1. HVAC systems and equipment served by a backup power source shall have associated DDC system products that control such systems and equipment also served from a backup power source.

23 09 23 - 18

DIRECT DIGITAL CONTROL (DDC) SYSTEM FOR HVAC

N. UPS:

1. DDC system products powered by UPS units shall include the following:

a. Desktop workstations.

b. Printers.

c. Servers.

d. Gateways.

e. DDC controllers, except application-specific controllers.

O. Continuity of Operation after Electric Power Interruption:

1. Equipment and associated factory-installed controls, field-installed controls, electrical equipment, and power supply connected to building normal and backup power systems shall automatically return equipment and associated controls to operating state occurring immediately before loss of normal power, without need for manual intervention by operator when power is restored either through backup power source or through normal power if restored before backup power is brought online.

2.5 SYSTEM ARCHITECTURE

A. Minimum Data Transfer and Communication Speed:

1. LAN Connecting Operator Workstations and Network Controllers: 100 Mbps.

2. LAN Connecting Programmable Application Controllers: 1000 kbps.

3. LAN Connecting Application-Specific Controllers: 115,000 bps.

B. DDC system shall consist of dedicated and separated LANs that are not shared with other building systems and tenant data and communication networks.

C. System architecture shall be modular and have inherent ability to expand to not less than two times system size indicated with no impact to performance indicated.

D. System architecture shall perform modifications without having to remove and replace existing network equipment.

E. Number of LANs and associated communication shall be transparent to operator. All I/O points residing on any LAN shall be capable of global sharing between all system LANs.

F. System design shall eliminate dependence on any single device for system alarm reporting and control execution. Each controller shall operate independently by performing its' own control, alarm management and historical data collection.

G. Special Network Architecture Requirements:

1. Air-Handling Systems: For control applications of an air-handling system that consists of air-handling unit(s) and VAV terminal units, include a dedicated LAN of application-specific controllers serving VAV terminal units connected directly to controller that is controlling air-handling system air-handling unit(s). Basically, create a DDC system LAN that aligns with air-handling system being controlled.

23 09 23 - 19

DIRECT DIGITAL CONTROL (DDC) SYSTEM FOR HVAC

2.6 DDC SYSTEM OPERATOR INTERFACES

A. Operator Means of System Access: Operator shall be able to access entire DDC system through any of multiple means, including, but not limited to, the following:

1. Desktop and portable workstation with hardwired connection through LAN port.

2. Portable operator terminal with hardwired connection through LAN port.

3. Portable operator workstation with wireless connection through LAN router.

4. Mobile device and application with secured wireless connection through LAN router or cellular data service.

5. Remote connection through web access.

B. Access to system, regardless of operator means used, shall be transparent to operator.

C. Network Ports: For hardwired connection of desktop or portable workstation. Network port shall be easily accessible, properly protected, clearly labeled, and installed at the following locations:

1. Each mechanical equipment room.

2. Security system command center.

3. Fire-alarm system command center.

D. Desktop Workstations:

1. Connect to DDC system Level one LAN through a communications port directly on LAN or through a communications port on a DDC controller.

2. Able to communicate with any device located on any DDC system LAN.

E. Portable Workstations:

1. Connect to DDC system Level one LAN through a communications port directly on LAN or through a communications port on a DDC controller.

2. Able to communicate with any device located on any DDC system LAN.

3. Connect to DDC system Level three LAN through a communications port on an application-specific controller, or a room temperature sensor connected to an application-specific controller.

4. Connect to system through a wireless router connected to Level one LAN.

5. Connect to system through a cellular data service.

6. Portable workstation shall be able to communicate with any device connected to any system LAN regardless of point of physical connection to system.

7. Monitor, program, schedule, adjust set points, and report capabilities of I/O connected anywhere in system.

8. Have dynamic graphic displays that are identical to desktop workstations.

F. POT:

1. Connect DDC controller through a communications port local to controller.

2. Able to communicate with any DDC system controller that is directly connected or connected to DDC system.

23 09 23 - 20

DIRECT DIGITAL CONTROL (DDC) SYSTEM FOR HVAC

G. Mobile Device:

1. Connect to system through a wireless router connected to LAN and cellular data service.

2. Able to communicate with any DDC controller connected to DDC system using a dedicated application and secure web access.

H. Critical Alarm Reporting:

1. Operator-selected critical alarms shall be sent by DDC system to notify operator of critical alarms that require immediate attention.

2. DDC system shall send alarm notification to multiple recipients that are assigned for each alarm.

3. DDC system shall notify recipients by any or all means, including e-mail, text message and prerecorded phone message to mobile and landline phone numbers.

2.7 NETWORKS

A. Acceptable networks for connecting workstations, mobile devices, and network controllers include the following:

1. IP.

2. IEEE 8802-3, Ethernet.

B. Acceptable networks for connecting programmable application controllers include the following:

1. IP.

2. IEEE 8802-3, Ethernet.

C. Acceptable networks for connecting application-specific controllers include the following:

1. IP.

2. IEEE 8802-3, Ethernet.

2.8 NETWORK COMMUNICATION PROTOCOL

A. Network communication protocol(s) used throughout entire DDC system shall be open to Government and available to other companies for use in making future modifications to DDC system.

B. ASHRAE 135 Protocol:

1. ASHRAE 135 communication protocol shall be sole and native protocol used throughout entire DDC system.

2. DDC system shall not require use of gateways except to integrate HVAC equipment and other building systems and equipment, not required to use ASHRAE 135 communication protocol.

3. If used, gateways shall connect to DDC system using ASHRAE 135 communication protocol and Project object properties and read/write services indicated by interoperability schedule.

4. Operator workstations, controllers and other network devices shall be tested and listed by BACnet Testing Laboratories.

23 09 23 - 21

DIRECT DIGITAL CONTROL (DDC) SYSTEM FOR HVAC

C. Industry Standard Protocols:

1. DDC system shall use any one or a combination of the following industry standard protocols for network communication while complying with other DDC system requirements indicated:

a. ASHRAE 135.

2. Operator workstations and network controllers shall communicate through ASHRAE 135 protocol.

3. Portions of DDC system networks using ASHRAE 135 communication protocol shall be an open implementation of network devices complying with ASHRAE 135. Network devices shall be tested and listed by BACnet Testing Laboratories.

4. Gateways shall be used to connect networks and network devices using different protocols.

2.9 DDC SYSTEM WIRELESS NETWORKS

A. Use Zigbee an open industry standard and technology used by multiple DDC system manufacturers’ technology to create a wireless mesh network to provide wireless connectivity for network devices at multiple system levels including communications from programmable application controllers and application-specific controllers to temperature sensors and from network controllers to programmable application controllers and application-specific controllers.

B. Installer shall design wireless networks to comply with DDC system performance requirements indicated. Wireless network devices shall co-exist on same network with hardwired devices.

C. Hardwired controllers shall be capable of retrofit to wireless devices with no special software.

D. A wireless coordinator shall provide a wireless interface between programmable application controllers, application-specific controllers, and network controllers.

E. Wireless Coordinators:

1. Each wireless mesh network shall use wireless coordinator(s) for initiation and formation of network.

2. Use direct sequence spread spectrum RF technology.

3. Operate on the 2.4-GHz ISM Band.

4. Comply with IEEE 802.15.4 for low-power, low duty-cycle RF transmitting systems.

5. FCC compliant to 47 CFR 15, Subpart B, Class A.

6. Operate as a bidirectional transceiver with sensors and routers to confirm and synchronize data transmission.

7. Capable of communication with sensors and routers up to a maximum distance of 250 feet in line of sight.

8. Include visual indicators to provide diagnostic information required for operator verification of operation.

F. Wireless Routers:

1. Each wireless mesh network shall use wireless routers with any controller to provide a wireless interface to a network controller, through a wireless coordinator.

2. Use direct sequence spread spectrum RF technology.

23 09 23 - 22

DIRECT DIGITAL CONTROL (DDC) SYSTEM FOR HVAC

3. Operate on the 2.4-GHz ISM Band.

4. Comply with IEEE 802.15.4 for low-power, low duty-cycle RF transmitting systems.

5. FCC compliant to 47 CFR 15, Subpart B, Class A.

6. Operate as a bidirectional transceiver with other mesh network devices to ensure network integrity.

7. Capable of communication with other mesh network devices at a maximum distance of

250 feet in line of sight.

8. Include indication for use in commissioning and troubleshooting.

G. Wireless Temperature Sensors:

1. Wireless temperature sensors shall sense and transmit room temperatures, temperature set point, room occupancy notification and low battery condition to an associated router.

2. Use direct sequence spread spectrum RF technology.

3. Operate on the 2.4-GHz ISM Band.

4. Comply with IEEE 802.15.4 for low-power, low duty-cycle RF transmitting systems.

5. FCC compliant to CFR 15, Subpart B, Class A.

6. Include set point adjustment between 55 to 85 deg F.

7. Multiple sensors shall be able to report to a router connected to a DDC controller…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .