ATTACHMENT VIII - Vet House CTI - 2019 - Aadco Alarm BUILDING 42 CSR.pdf

PDF 226 KB Posted

Attached to
Z1DA--Upgrade Fire Alarm System 583-26-221
Solicitation number
36C25025B0039
Issued by

About this file

This document is an Inspection and Testing Form for a fire alarm system at the Veteran's House located at 2669 Cold Springs Road, Indianapolis, IN, completed by Aadco Alarms & Communication Systems on October 12, 2019. The comprehensive form details the fire alarm system's technical specifications, including a Silent Knight IFP-2000 panel with 9 circuits, 16 manual stations, 46 photo detectors, 6 heat detectors, 4 waterflow switches, and 12 supervisory switches. The system uses digital transmission and is configured for annual service, with 22 horns, 6 strobes, and 18 horn/strobe devices across multiple floors and rooms.

The inspection was conducted from 9:00 a.m. to 11:30 a.m., with notifications sent to the monitoring entity (General Emergency) and building management (Gabe Hobbs). The system uses a primary 120V power supply with a 20-amp breaker and a secondary power supply of two 12V sealed lead-acid batteries with a 7AH rating. All initiating and supervisory devices were visually and functionally tested, with no operational issues noted. The testing was performed in accordance with applicable NFPA standards, and the system was restored to normal operation at 11:30 a.m. on the same day.

View the file

Other files

File Type Posted
36C25025B0039 0006.docx DOCX document
VAAR 852.219-75.docx DOCX document
Clarification.pdf PDF
36C25025B0039 0005.docx DOCX document
36C25025B0039 0004.docx DOCX document
36C25025B0039 0003.docx DOCX document
RFI clarification responses.pdf PDF
Sign in sheet.pdf PDF
36C25025B0039 0002.docx DOCX document
Wage Determination updated.pdf PDF
VHA ICRA 1.3_Final.pdf PDF
36C25025B0039 0001.docx DOCX document
ATTACHMENT V - 2021 BUILD 1 LIFE SAFETY DRAWINGS.pdf PDF
ATTACHMENT XIII - SOLE SOURCE SIEMENS PANEL.pdf PDF
ATTACHMENT IX - Build 43 Coumadin Clinic -Fire Alarm Layout BUILDING 43 CSR.pdf PDF
ATTACHMENT VI - Building 7-CSR - Fire Protection BUILDING 7 CSR.pdf PDF
36C25025B0039_1.docx DOCX document
ATTACHMENT XI - WAGE DETERMINATION.pdf PDF
ATTACHMENT III - FA System Equipment Inventory.pdf PDF
ATTACHMENT XII - LIMITATIONS ON SUBCONTRACTING CERTIFICATE OF COMPLIANCE.pdf PDF
ATTACHMENT VII - Annual CTI 2019 Building 9 - Aadco Alarm BUILDING 9 CSR.pdf PDF
ATTACHMENT IV - VA 583-13-104 FIRE ALARM AS-BUILTS.pdf PDF
ATTACHMENT XIV - RFI FORM.docx DOCX document
ATTACHMENT II - FIRE ALARM DEVICE LOCATION LIST.pdf PDF
ATTACHMENT X - 583-26-221 Upgrade Fire Alarm System - Combined Specifications - Bid Alt.pdf PDF
ATTACHMENT I - Fire-Life Safety System Inspection Testing and Maintenance Certificate_121723.pdf PDF
Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

115 North 2nd Avenue, Beech Grove, IN 46107 (317) 781-7680

Aadco Alarms & Communication Systems

INSPECTION AND TESTING FORM

DATE: 10-12-19

TIME: 9:00a.m.

SERVICE ORGANIZATION PROPERTY NAME (USER)

NAME: Aadco Alarms & Communications NAME: Veteran's House

ADDRESS: 115 North 2nd Avenue, Beech Grove, IN 46107

ADDRESS:

2669 Cold Springs Rd.

Indianapolis, IN. 46222

REPRESENTATIVE: Adam Petty OWNER CONTACT: Gabe Hobbs

LICENSE NO.: N/A TELEPHONE: 317-716-1347

MONITORING ENTITY APPROVING AGENCY

CONTACT: General Emergency CONTACT: N/A

TELEPHONE: 925-8919 TELEPHONE: N/A

MONITORING ACCOUNT REF. NO: 01-02-2604

TYPE TRANSMISSION SERVICE

McCulloh Weekly

Multiplex Monthly

Digital Quarterly

Reverse Priority Semiannually

RF Annually

Other (Specify) Other (Specify)

N/A N/A

PANEL MFG: Silent Knight MODEL NO.: IFP-2000

CIRCUIT STYLES: Y

NO. OF CIRCUITS: 9

SOFTWARE REV.: N/A

LAST DATE SYSTEM HAD ANY SERVICE PERFORMED: N/A

LAST DATE THAT ANY SOFTWARE OR CONFIGUARATION WAS REVISED: N/A

ALARM-INITIATING DEVICES AND CIRCUIT INFORMATION

QTY OF CIRCUIT STYLE

16 Y MANUAL STATIONS

N/A N/A ION DETECTORS

46 Y PHOTO DETECTORS

N/A N/A DUCT DETECTORS

6 Y HEAT DETECTORS

4 Y WATERFLOW SWITCHES

12 Y SUPERVISORY SWITCHES

N/A N/A OTHER (SPECIFY):

N/A

ALARM INDICATING APPLIANCES AND CIRCUIT INFORMATION

QTY OF CIRCUIT STYLE

N/A N/A BELLS

22 N/A HORNS

N/A N/A CHIMES

6 Y STROBES

N/A N/A SPEAKERS

18 Y OTHER (SPECIFY):

Horn/Strobe

NO. OF ALARM INDICATING CIRCUITS: 8

ARE CIRCUITS SUPERVISED? YES NO

SUPERVISORY SIGNAL INITIATING DEVICES AND CIRCUIT INFORMATION

QTY OF CIRCUIT STYLE

N/A N/A BUILDING TEMP.

N/A N/A SITE WATER TEMP.

N/A N/A SITE WATER LEVEL

N/A N/A FIRE PUMP POWER

N/A N/A FIRE PUMP RUNNING

INSPECTION, TESTING, AND MAINTENANCE

QTY OF CIRCUIT STYLE

N/A N/A FIRE PUMP AUTO POSITION

N/A N/A FIRE PUMP OR PUMP CONTOLLER

N/A N/A FIRE PUMP RUNNING

N/A N/A GENERATOR IN AUTO POSITION

N/A N/A GENERATOR OR CONTROLLER TROUBLE

N/A N/A SWITCH TRANSFER

N/A N/A GENERATOR ENGINE RUNNING

OTHER:

N/A

SIGNALING LINE CIRCUITS

Quantity and style (See NFPA 72, Table 3-6) of signaling line circuits connected to system:

Quantity: 1 Style(s) Y

SYSTEM POWER SUPPLIES

a. Primary (Main): Nominal Voltage 120 , Amps 15

Overcurrent Protection: Type Breaker , Amps 20

Location (Panel Number): Not Given , Amps N/A

SYSTEM POWER SUPPLIES

b. Secondary (Standby):

2 x 12V D.C. Storage Battery: Amp-Hr. Rating 7AH

Calculated capacity to operate system, in hours: X 24 60

N/A Engine-driven generator dedicated to fire alarm system:

Location of fuel storage: N/A

TYPE BATTERY

Dry Cell

Nickel-Cadmium

Sealed Lead-Acid

Lead-Acid

Other (Specify):

N/A

c. Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:

N/A Emergency system described in NFPA 70, Article 700 N/A Legally required standby described in NFPA 70, Article 701

N/A

Optional standby system described in NFPA 70, Article 702, which also meets the performance requirements of Article 700 or 701.

PRIOR TO ANY TESTING

NOTIFICATIONS ARE MADE: YES NO WHO TIME

MONITORING ENTITY General Emergency 9:00a.m.

BUILDING OCCUPANTS N/A N/A

BUILDING MANAGEMENT Gabe Hobbs 9:00a.m.

OTHER (SPECIFY) N/A N/A

AHJ (NOTIFED) OF ANY IMPAIRMENTS N/A N/A

SYSTEM TESTS AND INSPECTIONS

TYPE VISUAL FUNCTIONAL COMMENTS

CONTROL PANEL N/A

INTERFACE EQ. N/A

LAMPS/LEDS N/A

FUSES N/A

PRIMARY POWER SUPPLY N/A

TROUBLE SIGNALS N/A

DISCONNECT SWITCHES N/A

GROUND FAULT MONITORING N/A

SECONDARY POWER

TYPE VISUAL FUNCTIONAL COMMENTS

BATTERY CONDITON Good

LOAD VOLTAGE 26.1

DISCHARGE TEST 26.8

CHARGER TEST 27.0

SPECIFIC GRAVITY

TRANSIENT SUPPRESSORS

REMOTE ANNUNCIATORS N/A

NOTIFICATION APPLIANCES

AUDIBLE N/A

VISUAL N/A

SPEAKERS N/A

VOICE CLARITY N/A

INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS

LOCATION

DEVICE

TYPE

VISUAL

CHECK

FUNCTIONAL

TEST

FACTORY

SETTING

MEAS.

SETTING

PASS

FAIL

M001 1ST FL SOUTH ENTRANCE MPS N/A N/A

M002 1ST FL SOUTH STAIR

ENTRANCE MPS N/A N/A

M003 PRIMARY RECALL M.M. N/A N/A

M004 ALT RECALL M.M. N/A N/A

M005 FIREHAT RECALL M.M. N/A N/A

M006 ATTIC DRY SYSTEM M.M. N/A N/A

M007 ATTIC SYSTEM LOW AIR M.M. N/A N/A

M008 1ST FL WEST ENTRANCE MPS N/A N/A

M009 1ST FL EAST ENTRANCE MPS N/A N/A

M010 1ST FL NORTH STAIR

ENTRANCE MPS N/A N/A

M011 1ST FL NORTH ENTRANCE MPS N/A N/A

M012 1ST FL RISER ROOM TAMPER M.M. N/A N/A

M013 2ND FL RISER TAMPER M.M. N/A N/A

M014 1ST FL RISER TAMPER M.M. N/A N/A

M015 BASEMENT RISER M.M. N/A N/A

M016 BACKFLOW TAMPER M.M. N/A N/A

M017 BACKFLOW TAMPER M.M. N/A N/A

M018 2ND FL RISER WATERFLOW M.M. N/A N/A

M019 1ST FL RISER WATERFLOW M.M. N/A N/A

M020 BASEMENT RISER

WATERFLOW M.M. N/A N/A

M021 OUTSIDE NORTH PIV M.M. N/A N/A

M022 BASEMENT SOUTH STAIR MPS N/A N/A

M023 BASEMENT NORTH STAIR MPS N/A N/A

M024 2ND FL SOUTH STAIR MPS N/A N/A

M025 2ND FL MIDDLE STAIR MPS N/A N/A

M026 2ND FL NORTH STAIR MPS N/A N/A

S001 1ST FL ELECTRICAL RM PHOTO N/A N/A

S002 1ST FL RM 120 PHOTO N/A N/A

S003 1ST FL RM 121 PHOTO N/A N/A

S004 1ST FL RM 119 PHOTO N/A N/A

COMMENTS: MPS= manual pull station HEAT= thermal detector

M.M.= monitor module

PHOTO= photo smoke detector

TYPE

VISUAL

CHECK

FUNCTIONAL

TEST

FACTORY

SETTING

S005 1ST FL RM 117 PHOTO N/A N/A

S006 1ST FL ELEVATOR EQUIP RM HEAT N/A N/A

S007 1ST FL ELEVATOR EQUIP RM PHOTO N/A N/A

S008 1ST FL ELEVATOR LOBBY PHOTO N/A N/A

S009 1ST FL RM 125 PHOTO N/A N/A

S010 1ST FL RM 127 PHOTO N/A N/A

S011 1ST FL RM 129 PHOTO N/A N/A

S012 1ST FL MECHANICAL RM PHOTO N/A N/A

S013 1ST FL RM 128 PHOTO N/A N/A

S014 1ST FL RM 126 PHOTO N/A N/A

S015 1ST FL RM 124 PHOTO N/A N/A

S016 1ST FL KITCHEN PHOTO N/A N/A

S017 1ST FL DINING RM PHOTO N/A N/A

S018 1ST FL CORRIDOR 107 PHOTO N/A N/A

S019 1ST FL RM 114 PHOTO N/A N/A

S020 1ST FL RM 116 PHOTO N/A N/A

S021 1ST FL RM 118 PHOTO N/A N/A

S022 BASEMENT STORAGE 005

SOUTH PHOTO N/A N/A

S023 BASEMENT STORAGE 005

NORTH PHOTO N/A N/A

S024 BASEMENT ELEVATOR LOBBY PHOTO N/A N/A

S025 BASEMENT FITNESS RM PHOTO N/A N/A

S026 BASEMENT STORAGE 003 PHOTO N/A N/A

S027 2ND FL STORAGE HEAT N/A N/A

S028 2ND FL RM 208 PHOTO N/A N/A

S029 2ND FL RM 206 PHOTO N/A N/A

S030 2ND FL RM 204 PHOTO N/A N/A

S031 2ND FL RM 212 PHOTO N/A N/A

S032 2ND FL RM 213 PHOTO N/A N/A

S033 2ND FL RM 214 PHOTO N/A N/A

S034 2ND FL RM 216 PHOTO N/A N/A

COMMENTS: N/A

TYPE

VISUAL

CHECK

FUNCTIONAL

TEST

FACTORY

SETTING

S035 2ND FL RM 218 PHOTO N/A N/A

S036 2ND FL RM 220 PHOTO N/A N/A

S037 2ND FL UTILITY RM HEAT N/A N/A

S038 2ND FL RM 219 PHOTO N/A N/A

S039 2ND FL RM 217 PHOTO N/A N/A

S040 2ND FL RM 215 PHOTO N/A N/A

S041 2ND FL RM 211 PHOTO N/A N/A

S042 2ND FL CORRIDOR PHOTO N/A N/A

S043 2ND FL ELEVATOR LOBBY PHOTO N/A N/A

S044 2ND FL RM 203 PHOTO N/A N/A

S045 2ND FL RM 205 PHOTO N/A N/A

S046 2ND FL RM 207 PHOTO N/A N/A

S047 BASEMENT MECH RM HEAT N/A N/A

COMMENTS:

EMERGENCY COMMUNICATIONS EQUIPMENT

TYPE VISUAL FUNCTIONAL COMMENTS

PHONE SET N/A

PHONE JACKS N/A

OFF-HOOK INDICATOR N/A

AMPLIFIER(S) N/A

TONE GENERATOR(S) N/A

CALL IN SIGNAL N/A

SYSTEM PERFORMANCE N/A

N/A

INTERFACE EQUIPMENT

TYPE

VISUAL

OPERATION

SIMULATED OPERATION

(SPECIFY) N/A

(SPECIFY) N/A

(SPECIFY) N/A

SPECIAL HAZARD SYSTEMS

(SPECIFY) N/A

(SPECIFY) N/A

(SPECIFY) N/A

SPECIAL PROCEDURES:

COMMENTS: N/A

ON/OFF PREMISES MONITORING:

TYPE YES NO TIME COMMENTS

ALARM SIGNAL 9:00a.m. N/A

ALARM RESTORAL 11:30a.m. N/A

TROUBLE SIGNAL 9:00a.m. N/A

SUPERVISORY SIGNAL 9:00a.m. N/A

SUPERVISORY RESTORAL 11:30a.m. N/A

NOTIFICATIONS THAT TESTING IS COMPLETE:

TYPE YES NO TIME COMMENTS

BUILDING MANAGEMENT 11:30a.m. N/A

MONITORING AGENCY 11:30a.m. N/A

BUILDING OCCUPANTS N/A N/A

OTHER (SPECIFY) N/A N/A

N/A N/A

THE FOLLOWING DID NOT OPERATE CORRECTLY: N/A

SYSTEM RESTORED TO NORMAL OPERATION: DATE 10-12-19 TIME 11:30a.m.

THIS TESTING WAS PERFORMED IN ACCORDANCE WITH

APPLICABLE NFPA STANDARDS.

NAME OF INSPECTOR: Adam Petty

DATE: 10-12-19 TIME: 11:30a.m.

SIGNATURE:

NAME OF OWNER OR REPRESENTATIVE: Gabe Hobbs

DATE: 10-12-19 TIME: 11:30a.m.

SIGNATURE:

COMPANY:

REVIEWED BY:

File details come from the government source that posted it. Updated .