ATTACHMENT VIII - Vet House CTI - 2019 - Aadco Alarm BUILDING 42 CSR.pdf
PDF 226 KB Posted
- Attached to
- Z1DA--Upgrade Fire Alarm System 583-26-221
- Solicitation number
- 36C25025B0039
About this file
This document is an Inspection and Testing Form for a fire alarm system at the Veteran's House located at 2669 Cold Springs Road, Indianapolis, IN, completed by Aadco Alarms & Communication Systems on October 12, 2019. The comprehensive form details the fire alarm system's technical specifications, including a Silent Knight IFP-2000 panel with 9 circuits, 16 manual stations, 46 photo detectors, 6 heat detectors, 4 waterflow switches, and 12 supervisory switches. The system uses digital transmission and is configured for annual service, with 22 horns, 6 strobes, and 18 horn/strobe devices across multiple floors and rooms.
The inspection was conducted from 9:00 a.m. to 11:30 a.m., with notifications sent to the monitoring entity (General Emergency) and building management (Gabe Hobbs). The system uses a primary 120V power supply with a 20-amp breaker and a secondary power supply of two 12V sealed lead-acid batteries with a 7AH rating. All initiating and supervisory devices were visually and functionally tested, with no operational issues noted. The testing was performed in accordance with applicable NFPA standards, and the system was restored to normal operation at 11:30 a.m. on the same day.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
115 North 2nd Avenue, Beech Grove, IN 46107 (317) 781-7680
Aadco Alarms & Communication Systems
INSPECTION AND TESTING FORM
DATE: 10-12-19
TIME: 9:00a.m.
SERVICE ORGANIZATION PROPERTY NAME (USER)
NAME: Aadco Alarms & Communications NAME: Veteran's House
ADDRESS: 115 North 2nd Avenue, Beech Grove, IN 46107
ADDRESS:
2669 Cold Springs Rd.
Indianapolis, IN. 46222
REPRESENTATIVE: Adam Petty OWNER CONTACT: Gabe Hobbs
LICENSE NO.: N/A TELEPHONE: 317-716-1347
MONITORING ENTITY APPROVING AGENCY
CONTACT: General Emergency CONTACT: N/A
TELEPHONE: 925-8919 TELEPHONE: N/A
MONITORING ACCOUNT REF. NO: 01-02-2604
TYPE TRANSMISSION SERVICE
McCulloh Weekly
Multiplex Monthly
Digital Quarterly
Reverse Priority Semiannually
RF Annually
Other (Specify) Other (Specify)
N/A N/A
PANEL MFG: Silent Knight MODEL NO.: IFP-2000
CIRCUIT STYLES: Y
NO. OF CIRCUITS: 9
SOFTWARE REV.: N/A
LAST DATE SYSTEM HAD ANY SERVICE PERFORMED: N/A
LAST DATE THAT ANY SOFTWARE OR CONFIGUARATION WAS REVISED: N/A
ALARM-INITIATING DEVICES AND CIRCUIT INFORMATION
QTY OF CIRCUIT STYLE
16 Y MANUAL STATIONS
N/A N/A ION DETECTORS
46 Y PHOTO DETECTORS
N/A N/A DUCT DETECTORS
6 Y HEAT DETECTORS
4 Y WATERFLOW SWITCHES
12 Y SUPERVISORY SWITCHES
N/A N/A OTHER (SPECIFY):
N/A
ALARM INDICATING APPLIANCES AND CIRCUIT INFORMATION
QTY OF CIRCUIT STYLE
N/A N/A BELLS
22 N/A HORNS
N/A N/A CHIMES
6 Y STROBES
N/A N/A SPEAKERS
18 Y OTHER (SPECIFY):
Horn/Strobe
NO. OF ALARM INDICATING CIRCUITS: 8
ARE CIRCUITS SUPERVISED? YES NO
SUPERVISORY SIGNAL INITIATING DEVICES AND CIRCUIT INFORMATION
QTY OF CIRCUIT STYLE
N/A N/A BUILDING TEMP.
N/A N/A SITE WATER TEMP.
N/A N/A SITE WATER LEVEL
N/A N/A FIRE PUMP POWER
N/A N/A FIRE PUMP RUNNING
INSPECTION, TESTING, AND MAINTENANCE
QTY OF CIRCUIT STYLE
N/A N/A FIRE PUMP AUTO POSITION
N/A N/A FIRE PUMP OR PUMP CONTOLLER
N/A N/A FIRE PUMP RUNNING
N/A N/A GENERATOR IN AUTO POSITION
N/A N/A GENERATOR OR CONTROLLER TROUBLE
N/A N/A SWITCH TRANSFER
N/A N/A GENERATOR ENGINE RUNNING
OTHER:
N/A
SIGNALING LINE CIRCUITS
Quantity and style (See NFPA 72, Table 3-6) of signaling line circuits connected to system:
Quantity: 1 Style(s) Y
SYSTEM POWER SUPPLIES
a. Primary (Main): Nominal Voltage 120 , Amps 15
Overcurrent Protection: Type Breaker , Amps 20
Location (Panel Number): Not Given , Amps N/A
SYSTEM POWER SUPPLIES
b. Secondary (Standby):
2 x 12V D.C. Storage Battery: Amp-Hr. Rating 7AH
Calculated capacity to operate system, in hours: X 24 60
N/A Engine-driven generator dedicated to fire alarm system:
Location of fuel storage: N/A
TYPE BATTERY
Dry Cell
Nickel-Cadmium
Sealed Lead-Acid
Lead-Acid
Other (Specify):
N/A
c. Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:
N/A Emergency system described in NFPA 70, Article 700 N/A Legally required standby described in NFPA 70, Article 701
N/A
Optional standby system described in NFPA 70, Article 702, which also meets the performance requirements of Article 700 or 701.
PRIOR TO ANY TESTING
NOTIFICATIONS ARE MADE: YES NO WHO TIME
MONITORING ENTITY General Emergency 9:00a.m.
BUILDING OCCUPANTS N/A N/A
BUILDING MANAGEMENT Gabe Hobbs 9:00a.m.
OTHER (SPECIFY) N/A N/A
AHJ (NOTIFED) OF ANY IMPAIRMENTS N/A N/A
SYSTEM TESTS AND INSPECTIONS
TYPE VISUAL FUNCTIONAL COMMENTS
CONTROL PANEL N/A
INTERFACE EQ. N/A
LAMPS/LEDS N/A
FUSES N/A
PRIMARY POWER SUPPLY N/A
TROUBLE SIGNALS N/A
DISCONNECT SWITCHES N/A
GROUND FAULT MONITORING N/A
SECONDARY POWER
TYPE VISUAL FUNCTIONAL COMMENTS
BATTERY CONDITON Good
LOAD VOLTAGE 26.1
DISCHARGE TEST 26.8
CHARGER TEST 27.0
SPECIFIC GRAVITY
TRANSIENT SUPPRESSORS
REMOTE ANNUNCIATORS N/A
NOTIFICATION APPLIANCES
AUDIBLE N/A
VISUAL N/A
SPEAKERS N/A
VOICE CLARITY N/A
INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS
LOCATION
DEVICE
TYPE
VISUAL
CHECK
FUNCTIONAL
TEST
FACTORY
SETTING
MEAS.
SETTING
PASS
FAIL
M001 1ST FL SOUTH ENTRANCE MPS N/A N/A
M002 1ST FL SOUTH STAIR
ENTRANCE MPS N/A N/A
M003 PRIMARY RECALL M.M. N/A N/A
M004 ALT RECALL M.M. N/A N/A
M005 FIREHAT RECALL M.M. N/A N/A
M006 ATTIC DRY SYSTEM M.M. N/A N/A
M007 ATTIC SYSTEM LOW AIR M.M. N/A N/A
M008 1ST FL WEST ENTRANCE MPS N/A N/A
M009 1ST FL EAST ENTRANCE MPS N/A N/A
M010 1ST FL NORTH STAIR
ENTRANCE MPS N/A N/A
M011 1ST FL NORTH ENTRANCE MPS N/A N/A
M012 1ST FL RISER ROOM TAMPER M.M. N/A N/A
M013 2ND FL RISER TAMPER M.M. N/A N/A
M014 1ST FL RISER TAMPER M.M. N/A N/A
M015 BASEMENT RISER M.M. N/A N/A
M016 BACKFLOW TAMPER M.M. N/A N/A
M017 BACKFLOW TAMPER M.M. N/A N/A
M018 2ND FL RISER WATERFLOW M.M. N/A N/A
M019 1ST FL RISER WATERFLOW M.M. N/A N/A
M020 BASEMENT RISER
WATERFLOW M.M. N/A N/A
M021 OUTSIDE NORTH PIV M.M. N/A N/A
M022 BASEMENT SOUTH STAIR MPS N/A N/A
M023 BASEMENT NORTH STAIR MPS N/A N/A
M024 2ND FL SOUTH STAIR MPS N/A N/A
M025 2ND FL MIDDLE STAIR MPS N/A N/A
M026 2ND FL NORTH STAIR MPS N/A N/A
S001 1ST FL ELECTRICAL RM PHOTO N/A N/A
S002 1ST FL RM 120 PHOTO N/A N/A
S003 1ST FL RM 121 PHOTO N/A N/A
S004 1ST FL RM 119 PHOTO N/A N/A
COMMENTS: MPS= manual pull station HEAT= thermal detector
M.M.= monitor module
PHOTO= photo smoke detector
TYPE
VISUAL
CHECK
FUNCTIONAL
TEST
FACTORY
SETTING
S005 1ST FL RM 117 PHOTO N/A N/A
S006 1ST FL ELEVATOR EQUIP RM HEAT N/A N/A
S007 1ST FL ELEVATOR EQUIP RM PHOTO N/A N/A
S008 1ST FL ELEVATOR LOBBY PHOTO N/A N/A
S009 1ST FL RM 125 PHOTO N/A N/A
S010 1ST FL RM 127 PHOTO N/A N/A
S011 1ST FL RM 129 PHOTO N/A N/A
S012 1ST FL MECHANICAL RM PHOTO N/A N/A
S013 1ST FL RM 128 PHOTO N/A N/A
S014 1ST FL RM 126 PHOTO N/A N/A
S015 1ST FL RM 124 PHOTO N/A N/A
S016 1ST FL KITCHEN PHOTO N/A N/A
S017 1ST FL DINING RM PHOTO N/A N/A
S018 1ST FL CORRIDOR 107 PHOTO N/A N/A
S019 1ST FL RM 114 PHOTO N/A N/A
S020 1ST FL RM 116 PHOTO N/A N/A
S021 1ST FL RM 118 PHOTO N/A N/A
S022 BASEMENT STORAGE 005
SOUTH PHOTO N/A N/A
S023 BASEMENT STORAGE 005
NORTH PHOTO N/A N/A
S024 BASEMENT ELEVATOR LOBBY PHOTO N/A N/A
S025 BASEMENT FITNESS RM PHOTO N/A N/A
S026 BASEMENT STORAGE 003 PHOTO N/A N/A
S027 2ND FL STORAGE HEAT N/A N/A
S028 2ND FL RM 208 PHOTO N/A N/A
S029 2ND FL RM 206 PHOTO N/A N/A
S030 2ND FL RM 204 PHOTO N/A N/A
S031 2ND FL RM 212 PHOTO N/A N/A
S032 2ND FL RM 213 PHOTO N/A N/A
S033 2ND FL RM 214 PHOTO N/A N/A
S034 2ND FL RM 216 PHOTO N/A N/A
COMMENTS: N/A
TYPE
VISUAL
CHECK
FUNCTIONAL
TEST
FACTORY
SETTING
S035 2ND FL RM 218 PHOTO N/A N/A
S036 2ND FL RM 220 PHOTO N/A N/A
S037 2ND FL UTILITY RM HEAT N/A N/A
S038 2ND FL RM 219 PHOTO N/A N/A
S039 2ND FL RM 217 PHOTO N/A N/A
S040 2ND FL RM 215 PHOTO N/A N/A
S041 2ND FL RM 211 PHOTO N/A N/A
S042 2ND FL CORRIDOR PHOTO N/A N/A
S043 2ND FL ELEVATOR LOBBY PHOTO N/A N/A
S044 2ND FL RM 203 PHOTO N/A N/A
S045 2ND FL RM 205 PHOTO N/A N/A
S046 2ND FL RM 207 PHOTO N/A N/A
S047 BASEMENT MECH RM HEAT N/A N/A
COMMENTS:
EMERGENCY COMMUNICATIONS EQUIPMENT
TYPE VISUAL FUNCTIONAL COMMENTS
PHONE SET N/A
PHONE JACKS N/A
OFF-HOOK INDICATOR N/A
AMPLIFIER(S) N/A
TONE GENERATOR(S) N/A
CALL IN SIGNAL N/A
SYSTEM PERFORMANCE N/A
N/A
INTERFACE EQUIPMENT
TYPE
VISUAL
OPERATION
SIMULATED OPERATION
(SPECIFY) N/A
(SPECIFY) N/A
(SPECIFY) N/A
SPECIAL HAZARD SYSTEMS
(SPECIFY) N/A
(SPECIFY) N/A
(SPECIFY) N/A
SPECIAL PROCEDURES:
COMMENTS: N/A
ON/OFF PREMISES MONITORING:
TYPE YES NO TIME COMMENTS
ALARM SIGNAL 9:00a.m. N/A
ALARM RESTORAL 11:30a.m. N/A
TROUBLE SIGNAL 9:00a.m. N/A
SUPERVISORY SIGNAL 9:00a.m. N/A
SUPERVISORY RESTORAL 11:30a.m. N/A
NOTIFICATIONS THAT TESTING IS COMPLETE:
TYPE YES NO TIME COMMENTS
BUILDING MANAGEMENT 11:30a.m. N/A
MONITORING AGENCY 11:30a.m. N/A
BUILDING OCCUPANTS N/A N/A
OTHER (SPECIFY) N/A N/A
N/A N/A
THE FOLLOWING DID NOT OPERATE CORRECTLY: N/A
SYSTEM RESTORED TO NORMAL OPERATION: DATE 10-12-19 TIME 11:30a.m.
THIS TESTING WAS PERFORMED IN ACCORDANCE WITH
APPLICABLE NFPA STANDARDS.
NAME OF INSPECTOR: Adam Petty
DATE: 10-12-19 TIME: 11:30a.m.
SIGNATURE:
NAME OF OWNER OR REPRESENTATIVE: Gabe Hobbs
DATE: 10-12-19 TIME: 11:30a.m.
SIGNATURE:
COMPANY:
REVIEWED BY: