Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate
For
Indianapolis VAMC Building 1 1481 W 10th St
Indianapolis, IN 46202
Veterans Fire and Life Safety has performed this inspection and testing service in compliance with The Joint Commission/VHA Standards. The inspection/testing frequencies adhered to for this service have been performed in accordance with The Joint Commission/VHA Clarification Memorandum on EC & LS Standards effective January 31, 2021
Inspection Completion Date Dec 17, 2023
Building: Indianapolis VAMC Building 1 Company: Vets Fire & Life Safety Contact: Stephen Poynts Contact: Jonathan Long
Title: Electrical Supervisor Title: Field Tech Fire Alarm Testing Report
Page of 1 287 Executive Summary
Vets Fire & Life Safety Download Date: 01/11/2024
Executive Summary Generated by: BuildingReports.com
Building Information Building: Indianapolis VAMC Building 1 Contact: Stephen Poynts
Address: 1481 W 10th St Phone: 317-554-0001
Address: Fax:
City/State/ZIP Code: Indianapolis, IN 46202 Mobile:
Country: United States of America Email:
Inspection Performed By Company: Vets Fire & Life Safety Inspector: Jonathan Long
Address: 7 Sherri Lane Phone: 618-581-9068
Address: Fax:
City/State/ZIP Code: St Peters, MO 63376 Mobile:
Country: United States of America Email: jonathan.long@vflsc.com
System Control Unit Manufacturer: Siemens Inspection Date: 09/20/2023 IDC Style:
Model Number: Install Date: 09/12/2022 SLC Style:
Software Version: Version Date: 09/12/2022 NAC Style:
Location: 6th Elevator Lobby Current Protection:
Central Station Signal Verification Type: Mfg: Siemens Model #:
Test Time/Date: 10/27/23 7:50:16 AM Restore Time: 36 sec Note:
Page of 2 287
Vets Fire & Life Safety Download Date: 01/11/2024
Inspection Completion Date: Dec 17, 2023 Building: Indianapolis VAMC Building 1 EC 02.03.05 EP 01 Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; and room temperature supervisory. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(b-g)
Devices Tested This
Quarter Pass Fail Tested YTD
(2023) Untested YTD
(2023) Total
Quantity Supervisory Device 0 0 0 4 0 4
EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11)
Devices Tested This
Quarter Pass Fail Tested YTD
(2023) Untested YTD
(2023) Total
Quantity Tamper Switch 158 158 0 158 0 158
Waterflow Switch 140 140 0 140 0 140
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)
Devices Tested This
Quarter Pass Fail Tested YTD
(2023) Untested YTD
(2023) Total
Quantity Duct Detector 24 24 0 131 11 142
Heat Detector 25 18 7 34 0 34
Pull Station 0 0 0 225 1 226
Smoke Detector 55 55 0 653 31 684
EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)
Devices Tested This
Quarter Pass Fail Tested YTD
(2023) Untested YTD
(2023) Total
Quantity Releasing Device 0 0 0 192 0 192
Speaker 0 0 0 145 5 150
Speaker/Strobe 1 0 1 711 6 717
Strobe 0 0 0 249 4 253
EC 02.03.05 EP 05 Annual test of fire alarm equipment for notifying off-site fire responders. NFPA 72 (2022) Table 14.4.3.2 (4)
Devices Tested This
Quarter Pass Fail Tested YTD
(2023) Untested YTD
(2023) Total
Quantity Communicator 1 1 0 1 0 1
Monitor Device 0 0 0 0 7 7
EC 02.03.05 EP 11 For automatic sprinkler systems: Every 12 months, the hospital tests fire pumps under flow. Fire pump supervisory signals for pump running and pump power loss are tested annually. NFPA 25 (2023) 8.3.3
Devices Tested This
Quarter Pass Fail Tested YTD
(2023) Untested YTD
(2023) Total
Quantity
Page of 3 287
Vets Fire & Life Safety Download Date: 01/11/2024
EC 02.03.05 EP 11 For automatic sprinkler systems: Every 12 months, the hospital tests fire pumps under flow. Fire pump supervisory signals for pump running and pump power loss are tested annually. NFPA 25 (2023) 8.3.3
Fire Pump Power 1 1 0 1 0 1
Fire Pump Running 1 1 0 1 0 1
Fire Pump Trouble 0 0 0 0 1 1
EC 02.03.05 EP 18 Operation of fire and smoke dampers to verify full closure. NFPA 90A-2024: 5.4.8; NFPA
80-2022: 19.5; NFPA 105-2022: 7.6.2
Devices Tested This
Quarter Pass Fail Tested YTD
(2023) Untested YTD
(2023) Total
Quantity Damper Control 4 4 0 4 0 4
EC 02.03.05 EP 19 Annual test of automatic smoke-detection shutdown devices for air-handling equipment.
NFPA 90A (2024) 6.4.1
Devices Tested This
Quarter Pass Fail Tested YTD
(2023) Untested YTD
(2023) Total
Quantity Duct Detector 24 24 0 131 11 142
Fan Shutdown 61 61 0 68 6 74
LS 02.01.34 EP 02 Protected master fire alarm control panel
Devices Tested This
Quarter Pass Fail Tested YTD
(2023) Untested YTD
(2023) Total
Quantity Control Panel 0 0 0 3 0 3
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4
Devices Tested This
Quarter Pass Fail Tested YTD
(2023) Untested YTD
(2023) Total
Quantity Battery 18 18 0 84 2 86
Kitchen Hood 0 0 0 0 6 6
Power Supply 25 25 0 46 1 47
Pre-Action System 0 0 0 0 1 1
Programmable Relay 1 1 0 1 0 1
Remote Test Switch 0 0 0 3 0 3
Special Control 0 0 0 0 14 14
LS 02.01.50 EP 07 Annual - Elevators are fully equipped and protected
Devices Tested This
Quarter Pass Fail Tested YTD
(2023) Untested YTD
(2023) Total
Quantity Elevator 29 23 6 29 0 29
Total Device Count: 2979
Page of 4 287
Vets Fire & Life Safety Download Date: 01/11/2024
Certification
Company: Vets Fire & Life Safety Building: Indianapolis VAMC Building 1
Inspector: Jonathan Long Contact: Stephen Poynts
Page of 5 287 Discrepancy Report
Vets Fire & Life Safety Download Date: 01/11/2024
Discrepancy Report Generated by: BuildingReports.com
Building: Indianapolis VAMC Building 1 Control Panel: 3 The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.
Device Type Manufacturer ModelNumber Date Qty Items listed for Recall or Replacement/Upgrade
No items found during this inspection.
ScanID Location Problem Address Reference
EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11) Waterflow Switch
208963499 3rd A-WING RM. A-
3001 STAIRWELL #10 WATERFLOW
Failed Test 3-0-30-18 NFPA72 14.2.2.3.1
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Pull Station
208963438 2nd A-WING STAIR #9 Failed to Report 3-0-29-1 NFPA72 14.2.2.3.1
Code References NFPA72 14.2.2.3.1 System deficiencies shall be corrected.
Building: Indianapolis VAMC Building 1 Control Panel: 4 The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.
Device Type Manufacturer ModelNumber Date Qty Items listed for Recall or Replacement/Upgrade
No items found during this inspection.
ScanID Location Problem Address Reference
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Smoke Detector
208963611 6th A-WING BY RM. A-6045 Programming Error
4-0-60-33 NFPA72 10.10.1
208963612 6th A-WING BY RM. A-6110 Programming Error
4-0-60-34 NFPA72 10.10.1
javascript:editViewDevice('208963499');
javascript:editViewDevice('208963438');
javascript:editViewDevice('208963611');
javascript:editViewDevice('208963612');
Page of 6 287
Vets Fire & Life Safety Download Date: 01/11/2024
Code References NFPA72 10.10.1 Priority alarm signals, fire alarm signals, carbon monoxide alarm signals, supervisory signals, pre-alarm signals, and trouble signals shall be distinctively and descriptively annunciated.
Building: Indianapolis VAMC Building 1 Control Panel: 5 The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.
Device Type Manufacturer ModelNumber Date Qty Items listed for Recall or Replacement/Upgrade
No items found during this inspection.
ScanID Location Problem Address Reference
EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11) Tamper Switch
208963717 8th A-WING BY PASS.
ELEV LOBBY N. VALVE TAMPER
Failed Operation 5-0-79-43 NFPA72 14.2.2.3.1
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Heat Detector
208963707 9th A-WING
ELEV PENTHOUSE CENTER HEAT
Failed Operation 5-0-79-30 NFPA72 14.2.2.3.1
208963711 9th A-WING ELEV PENTHOUSE HEAT Failed Operation 5-0-79-34 NFPA72 14.2.2.3.1
208963728 9th A-WING ELEV PENTHOUSE S.E. Failed Operation 5-0-79-56 NFPA72 14.2.2.3.1
208963729 9th A-WING ELEV PENTHOUSE S.E. Failed Operation 5-0-79-57 NFPA72 14.2.2.3.1
208963730 9th A-WING ELEV PENTHOUSE S.E. Failed Operation 5-0-79-58 NFPA72 14.2.2.3.1
208963723 9th A-WING ELEV PENTHOUSE S.
E. (ELEV. 13)
Failed Operation 5-0-79-51 NFPA72 14.2.2.3.1
208963710 9th A-WING ELEV PENTHOUSE S. HEAT Failed Operation 5-0-79-33 NFPA72 14.2.2.3.1
Pull Station
208963793 8th A-WING BY RM. A-8118 Failed to Report 5-0-89-57 NFPA72 14.2.2.3.1
LS 02.01.50 EP 07 Annual - Elevators are fully equipped and protected Elevator
208963706 9th A-WING ELEV PENTHOUSE CENTER Failed Operation 5-0-79-29 NFPA72 14.2.2.3.1
208963724 9th A-WING ELEV PENTHOUSE S.E. Failed to Report 5-0-79-52 NFPA72 14.2.2.3.1
208963725 9th A-WING ELEV PENTHOUSE S.E. Failed to Report 5-0-79-53 NFPA72 14.2.2.3.1
208963726 9th A-WING ELEV PENTHOUSE S.E. Failed to Report 5-0-79-54 NFPA72 14.2.2.3.1
208963714 9th A-WING ELEV PENTHOUSE S.W. Failed Operation 5-0-79-39 NFPA72 14.2.2.3.1
208963712 9th A-WING ELEV PENTHOUSE S.W. Failed to Report 5-0-79-35 NFPA72 14.2.2.3.1 javascript:editViewDevice('208963717');
javascript:editViewDevice('208963707');
javascript:editViewDevice('208963711');
javascript:editViewDevice('208963728');
javascript:editViewDevice('208963729');
javascript:editViewDevice('208963730');
javascript:editViewDevice('208963723');
javascript:editViewDevice('208963710');
javascript:editViewDevice('208963793');
javascript:editViewDevice('208963706');
javascript:editViewDevice('208963724');
javascript:editViewDevice('208963725');
javascript:editViewDevice('208963726');
javascript:editViewDevice('208963714');
javascript:editViewDevice('208963712');
Page of 7 287
Vets Fire & Life Safety Download Date: 01/11/2024
Code References NFPA72 14.2.2.3.1 System deficiencies shall be corrected.
Building: Indianapolis VAMC Building 1 Control Panel: 6 The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.
Device Type Manufacturer ModelNumber Date Qty Items listed for Recall or Replacement/Upgrade
No items found during this inspection.
ScanID Location Problem Address Reference
EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11) Waterflow Switch
208963983 Basement BSMT. C-WING STAIRWELL
#1 WATERFLOW
Failed Test 6-0-107-46 NFPA72 14.2.2.3.1
208964512 5th 5TH FL. C-WING S.W. Penthouse Waterflow
Failed Test 6-0-151-46 NFPA72 14.2.2.3.1
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Duct Detector
208964309 3rd 3RD FL. C-WING RM C-
3118 ROOF AHU #41 DD
Failed Operation 6-0-131-12 NFPA72 14.2.2.3.1
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4 Remote Test Switch
208964384 4th 4TH FL E-WING AHU. #53
TEST SWITCH
Failed Operation 6-0-140-16 NFPA72 14.2.2.3.1
208964389 4th 4TH FL. E-WING AHU. #53 TEST
SWITCH
Failed Operation 6-0-140-21 NFPA72 14.2.2.3.1
208964386 4th 4TH FL. E-WING AHU. #53
TEST SWITCH
Failed Operation 6-0-140-18 NFPA72 14.2.2.3.1
Code References NFPA72 14.2.2.3.1 System deficiencies shall be corrected.
Building: Indianapolis VAMC Building 1 Control Panel: 8 - Siemens The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.
Device Type Manufacturer ModelNumber Date Qty Items listed for Recall or Replacement/Upgrade
No items found during this inspection.
javascript:editViewDevice('208963983');
javascript:editViewDevice('208964512');
javascript:editViewDevice('208964309');
javascript:editViewDevice('208964384');
javascript:editViewDevice('208964389');
javascript:editViewDevice('208964386');
Page of 8 287
Vets Fire & Life Safety Download Date: 01/11/2024
ScanID Location Problem Address Reference
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Duct Detector
208964713 10th 10TH FL. C-WING ROOF W.
LADDER TO 9FL. AHU. #12
Failed Operation 8-0-190-1 NFPA72 14.2.2.3.1
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4 Battery
208965070 1st A Wing Elevator Lobby Failed Test 8-12V-7AH NFPA72 Table
14.4.3.2 (9)
208965071 1st A Wing Elevator Lobby Failed Test 8-12V-7AH NFPA72 Table
14.4.3.2 (9)
208965054 3rd E Wing Room 3063 Failed Test 8-12V-7AH NFPA72 Table
14.4.3.2 (9)
208965055 3rd E Wing Room 3063 Failed Test 8-12V-7AH NFPA72 Table
14.4.3.2 (9)
208965104 4th Room 4049 Failed Test 8-12V-35AH NFPA72 Table
14.4.3.2 (9)
208965105 4th Room 4049 Failed Test 8-12V-35AH NFPA72 Table
14.4.3.2 (9)
208965040 6th Elevator Lobby Failed Test 8-12V-35AH NFPA72 Table
14.4.3.2 (9)
208965041 6th Elevator Lobby Failed Test 8-12V-35AH NFPA72 Table
14.4.3.2 (9)
208965086 8th Room 8046 Failed Test 8-12V-7AH NFPA72 Table
14.4.3.2 (9)
208965087 8th Room 8046 Failed Test 8-12V-7AH NFPA72 Table
14.4.3.2 (9)
Code References NFPA72 14.2.2.3.1 System deficiencies shall be corrected.
NFPA72 Table 14.4.3.2 (9) Replace any battery cell/unit if the temperature is greater than 18F above ambient. Replace the battery when any cell/unit measures a voltage less than 13.26 volts. Replace the battery when any cell/unit has an internal ohmic value outside of the acceptable range.
Building: Indianapolis VAMC Building 1 Control Panel: 9 The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.
Device Type Manufacturer ModelNumber Date Qty Items listed for Recall or Replacement/Upgrade
No items found during this inspection.
ScanID Location Problem Address Reference
EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) javascript:editViewDevice('208964713');
javascript:editViewDevice('208965070');
javascript:editViewDevice('208965071');
javascript:editViewDevice('208965054');
javascript:editViewDevice('208965055');
javascript:editViewDevice('208965104');
javascript:editViewDevice('208965105');
javascript:editViewDevice('208965040');
javascript:editViewDevice('208965041');
javascript:editViewDevice('208965086');
javascript:editViewDevice('208965087');
Page of 9 287
Vets Fire & Life Safety Download Date: 01/11/2024
ScanID Location Problem Address Reference Speaker/Strobe
208965987 Basement BY C-B120 Damaged/Worn 9-B-5 AV-4 NFPA72 14.2.2.3.1
Code References NFPA72 14.2.2.3.1 System deficiencies shall be corrected.
javascript:editViewDevice('208965987');
Page of 10 287 Proposed Solutions Report
Vets Fire & Life Safety Download Date: 01/11/2024
Proposed Solutions Report Generated by: BuildingReports.com
Building: Indianapolis VAMC Building 1 Control Panel: 3 The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.
ScanID Location Solution Model # Cost Fix
EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11)
Waterflow Switch 208963499 3rd A-WING RM. A-
3001 STAIRWELL #10 WATERFLOW
Replace T/M
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)
Pull Station 208963438 2nd A-WING STAIR #9 Investigate MSI-10B/-20B T/M
Building: Indianapolis VAMC Building 1 Control Panel: 4 The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.
ScanID Location Solution Model # Cost Fix
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)
Smoke Detector 208963611 6th A-WING BY RM. A-6045 Correct PE-11 T/M 208963612 6th A-WING BY RM. A-6110 Correct PE-11 T/M
Building: Indianapolis VAMC Building 1 Control Panel: 5 The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.
ScanID Location Solution Model # Cost Fix
EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11)
Tamper Switch 208963717 8th A-WING BY PASS.
ELEV LOBBY N. VALVE TAMPER
Replace T/M
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)
Heat Detector 208963707 9th A-WING
ELEV PENTHOUSE CENTER HEAT
Investigate FPT-11 T/M
Page of 11 287
Vets Fire & Life Safety Download Date: 01/11/2024
Building: Indianapolis VAMC Building 1 Control Panel: 5 The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.
ScanID Location Solution Model # Cost Fix
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)
Heat Detector 208963711 9th A-WING ELEV PENTHOUSE HEAT Investigate FPT-11 T/M 208963728 9th A-WING ELEV PENTHOUSE S.E. Investigate FPT-11 T/M 208963729 9th A-WING ELEV PENTHOUSE S.E. Investigate FPT-11 T/M 208963730 9th A-WING ELEV PENTHOUSE S.E. Investigate FPT-11 T/M 208963723 9th A-WING ELEV PENTHOUSE S.
E. (ELEV. 13)
Investigate FPT-11 T/M
208963710 9th A-WING ELEV PENTHOUSE S. HEAT Investigate FPT-11 T/M
Pull Station 208963793 8th A-WING BY RM. A-8118 Investigate MSI-10B/-20B T/M
LS 02.01.50 EP 07 Annual - Elevators are fully equipped and protected
Elevator 208963706 9th A-WING ELEV PENTHOUSE CENTER Investigate T/M 208963724 9th A-WING ELEV PENTHOUSE S.E. Investigate T/M 208963725 9th A-WING ELEV PENTHOUSE S.E. Investigate T/M 208963726 9th A-WING ELEV PENTHOUSE S.E. Investigate T/M 208963714 9th A-WING ELEV PENTHOUSE S.W. Investigate T/M 208963712 9th A-WING ELEV PENTHOUSE S.W. Investigate T/M
Building: Indianapolis VAMC Building 1 Control Panel: 6 The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.
ScanID Location Solution Model # Cost Fix
EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11)
Waterflow Switch 208963983 Basement BSMT. C-WING STAIRWELL
#1 WATERFLOW
Replace T/M
208964512 5th 5TH FL. C-WING S.W. Penthouse Waterflow
Replace T/M
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)
Duct Detector 208964309 3rd 3RD FL. C-WING RM C-
3118 ROOF AHU #41 DD
Investigate PE-11 T/M
Page of 12 287
Vets Fire & Life Safety Download Date: 01/11/2024
Building: Indianapolis VAMC Building 1 Control Panel: 6 The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.
ScanID Location Solution Model # Cost Fix
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4
Remote Test Switch 208964384 4th 4TH FL E-WING AHU. #53 TEST SWITCH Investigate T/M 208964389 4th 4TH FL. E-WING AHU. #53 TEST
SWITCH
Investigate T/M
208964386 4th 4TH FL. E-WING AHU. #53
TEST SWITCH
Investigate T/M
Building: Indianapolis VAMC Building 1 Control Panel: 8 - Siemens The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.
ScanID Location Solution Model # Cost Fix
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)
Duct Detector 208964713 10th 10TH FL. C-WING ROOF W.
LADDER TO 9FL. AHU. #12
Investigate PE-11 T/M
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4
Battery 208965070 1st A Wing Elevator Lobby Replace Battery T/M 208965071 1st A Wing Elevator Lobby Replace Battery T/M 208965054 3rd E Wing Room 3063 Replace Battery T/M 208965055 3rd E Wing Room 3063 Replace Battery T/M 208965104 4th Room 4049 Replace Battery T/M 208965105 4th Room 4049 Replace Battery T/M 208965040 6th Elevator Lobby Replace Battery T/M 208965041 6th Elevator Lobby Replace Battery T/M 208965086 8th Room 8046 Replace Battery T/M 208965087 8th Room 8046 Replace Battery T/M
Page of 13 287
Vets Fire & Life Safety Download Date: 01/11/2024
Building: Indianapolis VAMC Building 1 Control Panel: 9 The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.
ScanID Location Solution Model # Cost Fix
EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices.
NFPA 72 (2022) Table 14.4.3.2 (22)
Speaker/Strobe 208965987 Basement BY C-B120 Replace T/M
PO #: (none) T/M
Page of 14 287 Notes & Recommendations
Vets Fire & Life Safety Download Date: 01/11/2024
Notes & Recommendations Generated by: BuildingReports.com
Building: Indianapolis VAMC Building 1 Control Panel: 1 The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.
Note Device Type Location Comment ScanID
EC 02.03.05 EP 01 Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device;
water temperature supervisory; and room temperature supervisory. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(b-g)
1 Supervisory Device Basement GARAGE B-LEVEL RISER
RM. LOW AIR
208963331
Testing Done By Others 2 Supervisory Device Basement GARAGE B-LEVEL RISER
RM. LOW AIR
208963332
Testing Done By Others 3 Supervisory Device Basement GARAGE B-LEVEL RISER
RM. LOW AIR
208963333
Testing Done By Others
EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table
14.4.3.2 (17)(10)(a) & (17)(11)
4 Waterflow Switch Basement RISER STAIRWELL
#12 WATERFLOW
Passed 208963321
Recommend having flow switch turned down
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)
5 Duct Detector Basement A-WING RM. A-B148
N. AHU. #30 D.D.
208963272
Untestable Do To Being Inaccessible 6 Duct Detector Basement A-WING RM. A-B148
N. AHU. #30 D.D.
208963273
Untestable Do To Being Inaccessible 7 Duct Detector Basement A-WING RM. A-B148 O
/S S. STORAGE RM. AHU. #27
208963266
Untestable Do To Being Inaccessible 8 Duct Detector Basement A-WING RM. A-B148 O
/S S. STORAGE RM. AHU. #27
208963268
Untestable Do To Being Inaccessible 9 Duct Detector Basement A-WING RM. A-B148 S.
STORAGE RM. AHU. #26 D.D.
208963265
Untestable Do To Be Inaccessible 10 Duct Detector Basement A-WING RM. A-B148 S.
STORAGE RM. AHU. #26 D.D.
208963267 javascript:editViewDevice('208963331');
javascript:editViewDevice('208963332');
javascript:editViewDevice('208963333');
javascript:editViewDevice('208963321');
javascript:editViewDevice('208963272');
javascript:editViewDevice('208963273');
javascript:editViewDevice('208963266');
javascript:editViewDevice('208963268');
javascript:editViewDevice('208963265');
javascript:editViewDevice('208963267');
Page of 15 287
Vets Fire & Life Safety Download Date: 01/11/2024
Note Device Type Location Comment ScanID Untestable Do To Being Inaccessible 11 Duct Detector Basement A-WING RM. A-
B148 BOTTOM OF RAMP AHU. #28 D.D.
208963269
Untestable Do To Being Inaccessible 12 Duct Detector Basement A-WING RM. A-
B148 BOTTOM OF RAMP AHU. #28 D.D.
208963270
Untestable Do To Being Inaccessible 13 Duct Detector Basement A-WING RM. A-
B148 CENTER AHU. #29 D.D.
208963271
Untestable Do To Being Inaccessible 14 Duct Detector Basement A-WING RM. A-
B148 CENTER AHU. #29 D.D.
208963279
Untestable Do To Being Inaccessible 15 Duct Detector Basement B-WING BY RM. B-
B043 AHU. #31 D.D.
Passed 208963234
Duct detector for AHU 31 which are located in B wing by room B403. The duct detector shut down circuit disconnected from both detectors. Re landed the shutdown circuit on both duct detectors and verified the unit shut down when the circuit went from closed to open.
16 Duct Detector Basement B-WING BY RM. B-
B044 AHU. #31 D.D.
Passed 208963233
Duct detector for AHU 31 which are located in B wing by room B403. The duct detector shut down circuit disconnected from both detectors. Re landed the shutdown circuit on both duct detectors and verified the unit shut down when the circuit went from closed to open.
17 Duct Detector Basement C-WING RM. C-B110 AHU #9 Passed 208963828 Shuts Down Unit 18 Smoke Detector Basement A-WING FREIGHT ELEV
LOBBY ABOVE F.A.C.P.
Passed 208963292
Recalls To Primary Floor 19 Smoke Detector Basement A-WING FREIGHT ELEV. LOBBY Passed 208963308
Recalls To Primary Floor 20 Smoke Detector Basement A-WING PASS. ELEV. LOBBY Passed 208963309
Recalls To Primary Floor 21 Smoke Detector Basement A-WING RM. AB-139 N. Passed 208963251
Comes In As A Supervisory 22 Smoke Detector Basement A-WING RM. AB-139 S. Passed 208963250
Comes In As A Supervisory 23 Smoke Detector Basement B-WING RM. B-B038 S.
W. UNDER FLOOR
208963223
Testing Done By Others 24 Smoke Detector Basement B-WING RM. B-B038 208963220
Testing Done By Others 25 Smoke Detector Basement C-WING N.E. GEN. RM N. 208963862
Construction Area 26 Smoke Detector Basement C-WING N.E. GEN. RM S. 208963863 javascript:editViewDevice('208963269');
javascript:editViewDevice('208963270');
javascript:editViewDevice('208963271');
javascript:editViewDevice('208963279');
javascript:editViewDevice('208963234');
javascript:editViewDevice('208963233');
javascript:editViewDevice('208963828');
javascript:editViewDevice('208963292');
javascript:editViewDevice('208963308');
javascript:editViewDevice('208963309');
javascript:editViewDevice('208963251');
javascript:editViewDevice('208963250');
javascript:editViewDevice('208963223');
javascript:editViewDevice('208963220');
javascript:editViewDevice('208963862');
javascript:editViewDevice('208963863');
Page of 16 287
Vets Fire & Life Safety Download Date: 01/11/2024
Note Device Type Location Comment ScanID Construction Area 27 Smoke Detector Basement LEVEL B PARKING
GARAGE ELEV. G1
Passed 208963320
Recalls To Primary Floor 28 Smoke Detector Basement LEVEL B PARKING
GARAGE ELEV. G2
Passed 208963319
Recalls To Primary Floor 29 Smoke Detector Basement LEVEL C PARKING
GARAGE ELEV. G1
Passed 208963336
Recalls To Primary Floor 30 Smoke Detector Basement LEVEL C PARKING
GARAGE ELEV. MECH. RM.
Passed 208963337
Recalls To Primary Floor 31 Smoke Detector Basement LEVEL C PARKING
GARAGE ELEV. MECH. RM.
Passed 208963338
Recalls To Primary Floor 32 Smoke Detector Basement LEVEL C PARKING
GARAGE ELEV. G2
Passed 208963314
Recalls To Primary Floor 33 Duct Detector 3rd 130-45 3RD FL. C-WING MECH. RM.
C- 3152 Passed 208964300
Shuts Down Unit 34 Duct Detector 3rd 3RD FL. C-WING AHU #58 DD RM. C-
Passed 208964304
Shuts Down Unit 35 Duct Detector 4th 4TH FL. C-WING AHU. #59 RM. C- Passed 208964434
Shuts Down Unit 36 Duct Detector 5th 5TH FL. C-WING
SW PENTHOUSE AHU #43 DD
Passed 208964469
Shuts Down Unit 37 Duct Detector 6th 6TH FL. C-WING MECH. RM. C-
000 AHU. #56 D.D.
Passed 208964566
Shuts Down Unit
EC 02.03.05 EP 19 Annual test of automatic smoke-detection shutdown devices for air-handling equipment.
NFPA 90A (2024) 6.4.1
38 Fan Shutdown Basement A-WING RM. A-B148
E. WALL METASYS AHU. #29
208963286
Untestable Do To Being Inaccessible 39 Fan Shutdown Basement A-WING RM. A-B148
E. WALL METASYS AHU. #30
208963285
Untestable Do To Being Inaccessible 40 Fan Shutdown Basement A-WING RM. A-B148 S.
WALL METASYS AHU. #26
208963289
Untestable Do To Being Inaccessible 41 Fan Shutdown Basement A-WING RM. A-B148 S.E. 208963288 javascript:editViewDevice('208963320');
javascript:editViewDevice('208963319');
javascript:editViewDevice('208963336');
javascript:editViewDevice('208963337');
javascript:editViewDevice('208963338');
javascript:editViewDevice('208963314');
javascript:editViewDevice('208964300');
javascript:editViewDevice('208964304');
javascript:editViewDevice('208964434');
javascript:editViewDevice('208964469');
javascript:editViewDevice('208964566');
javascript:editViewDevice('208963286');
javascript:editViewDevice('208963285');
javascript:editViewDevice('208963289');
javascript:editViewDevice('208963288');
Page of 17 287
Vets Fire & Life Safety Download Date: 01/11/2024
Note Device Type Location Comment ScanID
WALL METASYS AHU. #27
Untestable Do To Being Inaccessible 42 Fan Shutdown Basement A-WING RM. A-B148
S. WALL METASYS AHU. #28
208963287
Untestable Do To Being Inaccessible
Building: Indianapolis VAMC Building 1 Control Panel: 3 The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.
Note Device Type Location Comment ScanID
EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table
14.4.3.2 (17)(10)(a) & (17)(11) 43 Waterflow Switch 3rd A-WING RM. A-
3001 STAIRWELL #10 WATERFLOW
Failed Test 208963499
We will provide quote for 3" waterflow switch
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) 44 Smoke Detector 1st PARKING GARAGE ELEV. LOBBY Passed 208963476
Recalls To Primary Floor 45 Duct Detector 2nd A-WING RM. A-2003
E. CENTER AHU. #32 D.D.
Passed 208963462
Shuts Down Unit 46 Duct Detector 2nd A-WING RM. A-2003 S.E. AHU. #32 D.
D.
Passed 208963460
Shuts Down Unit 47 Duct Detector 2nd A-WING RM. A-2003 S.W. AHU. #32 D.
D.
Passed 208963459
Shuts Down Unit 48 Duct Detector 2nd A-WING RM. A-2003 S.W. AHU. #32 D.
D.
Passed 208963461
Shuts Down Unit 49 Pull Station 2nd A-WING STAIR #9 Failed to Report 208963438
Did Not Send Signal To FACP 50 Smoke Detector 2nd A-WING FREIGHT ELEV. Lobby Passed 208963442
Recalls To Primary Floor 51 Smoke Detector 2nd A-WING
PARKING GARAGE ELEV. SHAFT
Passed 208963463
Recalls To Primary Floor 52 Smoke Detector 2nd A-WING PASS. ELEV. Lobby Passed 208963441
Recalls To Primary Floor 53 Duct Detector 3rd A-WING RM. A-3001 N.
W. (BY WALL) AHU. #36 D.D.
Passed 208963488
Shuts Down Unit 54 Duct Detector 3rd A-WING RM. A-3001 N.W. AHU. #35 D. Passed 208963490 javascript:editViewDevice('208963287');
javascript:editViewDevice('208963499');
javascript:editViewDevice('208963476');
javascript:editViewDevice('208963462');
javascript:editViewDevice('208963460');
javascript:editViewDevice('208963459');
javascript:editViewDevice('208963461');
javascript:editViewDevice('208963438');
javascript:editViewDevice('208963442');
javascript:editViewDevice('208963463');
javascript:editViewDevice('208963441');
javascript:editViewDevice('208963488');
javascript:editViewDevice('208963490');
Page of 18 287
Vets Fire & Life Safety Download Date: 01/11/2024
Note Device Type Location Comment ScanID D.
Shuts Down Unit 55 Duct Detector 3rd A-WING RM. A-3001 N.W. AHU. #35 D.
D.
Passed 208963491
Shuts Down Unit 56 Duct Detector 3rd A-WING RM. A-3001 N.W. AHU. #36 D.
D.
Passed 208963489
Shuts Down Unit 57 Duct Detector 3rd A-WING RM. A-3001 S. AHU. #33A D.D. Passed 208963497
Shuts Down Unit 58 Duct Detector 3rd A-WING RM. A-3001 S. AHU. #33A D.D. Passed 208963505
Shuts Down Unit 59 Duct Detector 3rd A-WING RM. A-3001 S. AHU. #33B D.D. Passed 208963496
Shuts Down Unit 60 Duct Detector 3rd A-WING RM. A-
3001 CENTER AHU. #34B D.D.
Passed 208963492
Shuts Down Unit 61 Duct Detector 3rd A-WING RM. A-
3001 CENTER S. AHU. #34A D.D.
Passed 208963493
Shuts Down Unit 62 Duct Detector 3rd A-WING RM. A-
3001 CENTER S. AHU. #34A D.D.
Passed 208963495
Shuts Down Unit 63 Duct Detector 3rd A-WING RM. A-
3001 CENTER S. AHU. #34B D.D.
Passed 208963494
Shuts Down Unit 64 Duct Detector 3rd A-WING RM. A-
3001 CENTER W. AHU. #33B D.D.
Passed 208963504
Shuts Down Unit 65 Smoke Detector 3rd A-WING FREIGHT ELEV. LOBBY Passed 208963487
Recalls To Primary Floor 66 Smoke Detector 3rd A-WING PASS. ELEV. LOBBY Passed 208963486
Recalls To Primary Floor 67 Smoke Detector 4th A-WING FREIGHT ELEV. LOBBY Passed 208963515
Recalls To Primary Floor 68 Smoke Detector 4th A-WING PASS. ELEV. LOBBY Passed 208963514
Recalls To Primary Floor 69 Duct Detector 5th A-WING RM. A-5001 S.W. AHU. #37A D.
D.
Passed 208963573
Shuts Down Unit 70 Duct Detector 5th A-WING RM. A-5001 S. AHU. #37A D.D. Passed 208963568
Device had a wire on shutdown but when traced away from DD, the wires did not land on anything and were wire nutted in a junction box by unit.
71 Duct Detector 5th A-WING RM. A-5001 S. AHU. #37B D.D. Passed 208963567 javascript:editViewDevice('208963491');
javascript:editViewDevice('208963489');
javascript:editViewDevice('208963497');
javascript:editViewDevice('208963505');
javascript:editViewDevice('208963496');
javascript:editViewDevice('208963492');
javascript:editViewDevice('208963493');
javascript:editViewDevice('208963495');
javascript:editViewDevice('208963494');
javascript:editViewDevice('208963504');
javascript:editViewDevice('208963487');
javascript:editViewDevice('208963486');
javascript:editViewDevice('208963515');
javascript:editViewDevice('208963514');
javascript:editViewDevice('208963573');
javascript:editViewDevice('208963568');
javascript:editViewDevice('208963567');
Page of 19 287
Vets Fire & Life Safety Download Date: 01/11/2024
Note Device Type Location Comment ScanID Device had a wire on shutdown but when traced away from DD, the wires did not land on anything and were wire nutted in a junction box by unit.
72 Duct Detector 5th A-WING RM. A-
5001 CENTER AHU. #37C D.D.
Passed 208963566
Device had a wire on shutdown but when traced away from DD, the wires did not land on anything and were wire nutted in a junction box by unit.
73 Duct Detector 5th A-WING RM. A-
5001 CENTER AHU. #38 D.D.
Passed 208963565
Shuts Down Unit 74 Duct Detector 5th A-WING RM. A-5001 CENTER N.
W. AHU. #39 D.D.
Passed 208963562
Shuts Down Unit 75 Duct Detector 5th A-WING RM. A-5001 CENTER N.
W. AHU. #39 D.D.
Passed 208963563
Shuts Down Unit 76 Duct Detector 5th A-WING RM. A-
5001 CENTER W. AHU. #38 D.D.
Passed 208963564
Shuts Down Unit 77 Smoke Detector 5th A-WING FREIGHT ELEV. LOBBY Passed 208963560
Recalls To Primary Floor 78 Smoke Detector 5th A-WING PASS. ELEV. LOBBY Passed 208963559
Recalls To Primary Floor
Building: Indianapolis VAMC Building 1 Control Panel: 4 The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.
Note Device Type Location Comment ScanID
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) 79 Duct Detector 6th A-WING RM. A-5005
AHU. #46 BY COLUMN D-13 D.D.
Passed 208963627
Shuts Down Unit 80 Duct Detector 6th A-WING RM. A-6144 CENTER W. AHU.
#42 D.D.
Passed 208963604
When the wires are removed from NC contact nothing happens. Could not follow wires due to it being in conduit and hitting junction boxes on the way to the units controller, but this would mean the wires are not landed properly on the units controller.
81 Duct Detector 6th A-WING RM. A-6144 N. AHU. #42 D.D. Passed 208963602 Unit failed to shutdown, but when removing the wire from the NC contact, the unit shutdown. This would mean that the DD is bad and needs to be replaced. Inspector did not see the device change state properly 82 Duct Detector 6th A-WING RM. A-6144 S.E. AHU. #46 D.
D.
Passed 208963626
Shuts Down Unit 83 Duct Detector 6th A-WING RM. A-6144 S.W. AHU. #46 D.
D.
Passed 208963628 javascript:editViewDevice('208963566');
javascript:editViewDevice('208963565');
javascript:editViewDevice('208963562');
javascript:editViewDevice('208963563');
javascript:editViewDevice('208963564');
javascript:editViewDevice('208963560');
javascript:editViewDevice('208963559');
javascript:editViewDevice('208963627');
javascript:editViewDevice('208963604');
javascript:editViewDevice('208963602');
javascript:editViewDevice('208963626');
javascript:editViewDevice('208963628');
Page of 20 287
Vets Fire & Life Safety Download Date: 01/11/2024
Note Device Type Location Comment ScanID Shuts Down Unit 84 Duct Detector 6th A-WING RM. A-
6144 CENTER E. AHU. #46 D.D.
Passed 208963629
Shuts Down Unit 85 Smoke Detector 6th A-WING BY RM. A-6045 Programming Error 208963611
Comes in As A Damper 86 Smoke Detector 6th A-WING BY RM. A-6110 Programming Error 208963612
Comes In As A Damper 87 Smoke Detector 6th A-WING FREIGHT ELEV. LOBBY Passed 208963580
Recalls To Primary Floor 88 Smoke Detector 6th A-WING PASS. ELEV. LOBBY Passed 208963581
Recalls To Primary Floor
Building: Indianapolis VAMC Building 1 Control Panel: 5 The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.
Note Device Type Location Comment ScanID
EC 02.03.05 EP 01 Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device;
water temperature supervisory; and room temperature supervisory. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(b-g) 89 Supervisory Device Basement BLDG. 1 C-WING E. BSMT
LOW AIR
208963884
Testing Done By Others
EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table
14.4.3.2 (17)(10)(a) & (17)(11) 90 Waterflow Switch Basement D-WING BY STAIR
#8 WATERFLOW
Passed 208963822
Recommend turning down the flow switch 91 Tamper Switch 8th A-WING BY PASS.
ELEV LOBBY N. VALVE TAMPER
Failed Operation 208963717
We will provide a quote for (1) new tamper switch
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) 92 Duct Detector Basement C-WING EDUCATION AHU. #8 D.
D.
Passed 208963835
Shuts Down Unit 93 Duct Detector Basement D-WING RM. D-B004
AHU. #13 N.W. CORNER (ABOVE)
Passed 208963796
Shuts Down Unit 94 Duct Detector Basement D-WING RM. D-B004
CENTER AHU. #14 D.D.
Passed 208963801
Shuts Down Unit 95 Duct Detector Basement D-WING RM. D-B004
CENTER AHU. #14 D.D.
Passed 208963820 javascript:editViewDevice('208963629');
javascript:editViewDevice('208963611');
javascript:editViewDevice('208963612');
javascript:editViewDevice('208963580');
javascript:editViewDevice('208963581');
javascript:editViewDevice('208963884');
javascript:editViewDevice('208963822');
javascript:editViewDevice('208963717');
javascript:editViewDevice('208963835');
javascript:editViewDevice('208963796');
javascript:editViewDevice('208963801');
javascript:editViewDevice('208963820');
Page of 21 287
Vets Fire & Life Safety Download Date: 01/11/2024
Note Device Type Location Comment ScanID Shuts Down Unit 96 Duct Detector Basement D-WING RM. D-B004 N.E.
AHU. #15 (ABOVE) D.D.
Passed 208963799
Shuts Down Unit 97 Duct Detector Basement D-WING RM. D-B004 N.W.
AHU. #13 D.D.
Passed 208963800
Shuts Down Unit 98 Duct Detector Basement D-WING RM. D-B004 N.W.
AHU. #13 D.D.
Passed 208963802
Shuts Down Unit 99 Duct Detector Basement D-WING RM. D-B004 N.
W. AHU. #15 D.D.
Passed 208963821
Shuts Down Unit 100 Pull Station Basement C-WING N.E. GEN. RM. 208963861 Construction Area 101 Smoke Detector Basement BSMT. D-WING RM. DB-010 Passed 208963901 Comes In As A Supervisory 102 Smoke Detector Basement C-WING RM. CB-
017 UNDER FLOOR
208963872
Testing Done By Others 103 Smoke Detector Basement C-WING RM. CB-
017 UNDER FLOOR
208963873
Testing Done By Others 104 Smoke Detector Basement D-WING D-B004 ELEV.
MECH. RM. D-B005
Passed 208963807
Recalls To Primary Floor 105 Smoke Detector Basement D-WING ELEV.
LOBBY BY STAIR #7
Passed 208963810
Recalls To Primary Floor 106 Smoke Detector Basement D-WING ELEV. LOBBY Passed 208963808 Recalls To Primary Floor 107 Duct Detector 7th A-WING O/S RM. A-7141 AHU. #50 D.D. Passed 208963648 Shuts Down Unit 108 Duct Detector 7th A-WING O/S RM. A-7141 AHU. #50 D.D. Passed 208963650 Shuts Down Unit 109 Duct Detector 7th A-WING RM. A-7092 (A-
7091) AHU. #49 D.D.
Passed 208963652
Shuts Down Unit 110 Duct Detector 7th A-WING RM. A-7092 (A-
7091) AHU. #49 D.D.
Passed 208963654
Shuts Down Unit 111 Duct Detector 7th A-WING RM. A-7141 AHU. #50 D.D. Passed 208963646 Shuts Down Unit 112 Smoke Detector 7th A-WING FREIGHT ELEV. LOBBY Passed 208963683 javascript:editViewDevice('208963799');
javascript:editViewDevice('208963800');
javascript:editViewDevice('208963802');
javascript:editViewDevice('208963821');
javascript:editViewDevice('208963861');
javascript:editViewDevice('208963901');
javascript:editViewDevice('208963872');
javascript:editViewDevice('208963873');
javascript:editViewDevice('208963807');
javascript:editViewDevice('208963810');
javascript:editViewDevice('208963808');
javascript:editViewDevice('208963648');
javascript:editViewDevice('208963650');
javascript:editViewDevice('208963652');
javascript:editViewDevice('208963654');
javascript:editViewDevice('208963646');
javascript:editViewDevice('208963683');
Page of 22 287
Vets Fire & Life Safety Download Date: 01/11/2024
Note Device Type Location Comment ScanID Recalls To Primary Floor 113 Smoke Detector 7th A-WING FREIGHT ELEV LOBBY Passed 208963660 Recalls To Primary Floor 114 Smoke Detector 7th A-WING PASS. ELEV. LOBBY Passed 208963684 Recalls To Primary Floor 115 Duct Detector 8th A-WING FL. A-WING RM A-
8125 AHU. #50 D.D.
Passed 208963768
Shuts Down Unit 116 Duct Detector 8th A-WING NURSES STATION AHU. #49 D.
D.
Passed 208963787
Shuts Down Unit 117 Duct Detector 8th A-WING RM. A-8024 AHU #49 D.D. Passed 208963789 Shuts Down Unit 118 Duct Detector 8th A-WING RM. A-8086 AHU. #50 D.D. Passed 208963757 Shuts Down Unit 119 Duct Detector 8th A-WING RM. A-8086 AHU #49 D.D. Passed 208963744 Shuts Down Unit 120 Duct Detector 8th A-WING RM. A-8086 AHU #49 D.D. Passed 208963749 Shuts Down Unit 121 Duct Detector 8th A-WING RM. A-8086 AHU #49 D.D. Passed 208963750 Shuts Down Unit 122 Duct Detector 8th A-WING RM. A-8086 AHU #50 D.D. Passed 208963733 Shuts Down Unit 123 Duct Detector 8th A-WING RM. A-8086 AHU #50 D.D. Passed 208963736 Shuts Down Unit 124 Duct Detector 8th A-WING RM. A-8086 AHU #50 D.D. Passed 208963738 Shuts Down Unit 125 Duct Detector 8th A-WING RM. A-8086 AHU #50 D.D. Passed 208963740 Shuts Down Unit 126 Duct Detector 8th A-WING RM. A-8086 AHU #50 D.D. Passed 208963742 Shuts Down Unit 127 Duct Detector 8th A-WING RM. A-8087 AHU #49 D.
D. (IN WALL)
Passed 208963753
Shuts Down Unit 128 Duct Detector 8th A-WING RM. A-8118 AHU #49 D.D. Passed 208963791 Shuts Down Unit 129 Pull Station 8th A-WING BY RM. A-8118 Failed to Report 208963793 Did not send signal to FACP 130 Smoke Detector 8th A-WING FREIGHT ELEV. LOBBY Passed 208963694 Recalls To Primary Floor 131 Smoke Detector 8th A-WING FREIGHT ELEV. SHAFT Passed 208963695 Recalls To Primary Floor 132 Smoke Detector 8th A-WING FREIGHT ELEV LOBBY Passed 208963779 javascript:editViewDevice('208963660');
javascript:editViewDevice('208963684');
javascript:editViewDevice('208963768');
javascript:editViewDevice('208963787');
javascript:editViewDevice('208963789');
javascript:editViewDevice('208963757');
javascript:editViewDevice('208963744');
javascript:editViewDevice('208963749');
javascript:editViewDevice('208963750');
javascript:editViewDevice('208963733');
javascript:editViewDevice('208963736');
javascript:editViewDevice('208963738');
javascript:editViewDevice('208963740');
javascript:editViewDevice('208963742');
javascript:editViewDevice('208963753');
javascript:editViewDevice('208963791');
javascript:editViewDevice('208963793');
javascript:editViewDevice('208963694');
javascript:editViewDevice('208963695');
javascript:editViewDevice('208963779');
Page of 23 287
Vets Fire & Life Safety Download Date: 01/11/2024
Note Device Type Location Comment ScanID Recalls To Primary Floor 133 Smoke Detector 8th A-WING PASS. ELEV. LOBBY Passed 208963691 Recalls To Primary Floor 134 Smoke Detector 8th A-WING PASS. ELEV. SHAFT N. Passed 208963692 Recalls To Primary Floor 135 Smoke Detector 8th A-WING PASS. ELEV. SHAFT S. Passed 208963693 Recalls To Primary Floor 136 Duct Detector 9th A-WING ELEV. PENTHOUSE N.
E. AHU. #39 D.D.
Passed 208963701
Shuts Down Unit 137 Duct Detector 9th A-WING ELEV PENTHOUSE S.
E. AHU. #39 D.D.
Passed 208963703
Shuts Down Unit 138 Heat Detector 9th A-WING
ELEV PENTHOUSE CENTER HEAT
Failed Operation 208963707
Did Not Send Signal To FACP 139 Heat Detector 9th A-WING ELEV PENTHOUSE S.E. Failed Operation 208963728 Did Not Shunt Trip Elevator 140 Heat Detector 9th A-WING ELEV PENTHOUSE S.E. Failed Operation 208963729 Did Not Send Signal To FACP 141 Heat Detector 9th A-WING ELEV PENTHOUSE S.E. Failed Operation 208963730 Did Not Send Signal To FACP 142 Heat Detector 9th A-WING ELEV PENTHOUSE S.
E. (ELEV. 13)
Failed Operation 208963723
Did Not Send Signal To FACP 143 Heat Detector 9th A-WING ELEV PENTHOUSE S. HEAT Failed Operation 208963710 Did Not Send Signal To FACP 144 Smoke Detector 9th A-WING
ELEV. PENTHOUSE CENTER W.
Passed 208963696
Recalls To Primary Floor 145 Smoke Detector 9th A-WING
ELEV PENTHOUSE CENTER S.
Passed 208963704
Recalls To Primary Floor
EC 02.03.05 EP 05 Annual test of fire alarm equipment for notifying off-site fire responders. NFPA 72 (2022) Table 14.4.3.2 (4) 146 Monitor Device Basement C-WING RM. CB-017 ALARM 208963865 Testing Done By Others 147 Monitor Device Basement C-WING RM. CB-017 PANEL 208963868 Testing Done By Others 148 Monitor Device Basement C-WING RM. CB-
017 SUPERVISORY
208963867
Testing Done By Others 149 Monitor Device Basement C-WING RM. CB-017 TROUBLE 208963866 Testing Done By Others javascript:editViewDevice('208963691');
javascript:editViewDevice('208963692');
javascript:editViewDevice('208963693');
javascript:editViewDevice('208963701');
javascript:editViewDevice('208963703');
javascript:editViewDevice('208963707');
javascript:editViewDevice('208963728');
javascript:editViewDevice('208963729');
javascript:editViewDevice('208963730');
javascript:editViewDevice('208963723');
javascript:editViewDevice('208963710');
javascript:editViewDevice('208963696');
javascript:editViewDevice('208963704');
javascript:editViewDevice('208963865');
javascript:editViewDevice('208963868');
javascript:editViewDevice('208963867');
javascript:editViewDevice('208963866');
Page of 24 287
Vets Fire & Life Safety Download Date: 01/11/2024
Note Device Type Location Comment ScanID
EC 02.03.05 EP 11 For automatic sprinkler systems: Every 12 months, the hospital tests…