This document is an Inspection and Testing Form for a fire alarm system at the V.A. Building 9 located at 2669 Cold Springs Road in Indianapolis, Indiana. The form, completed by Aadco Alarms & Communication Systems on 9-12-19, details a comprehensive inspection of the fire alarm system, which includes a Siemens panel with 4 circuits using digital transmission. The system has 8 manual stations, 13 photo detectors, 2 heat detectors, 4 waterflow switches, and 4 supervisory switches. The inspection verified the visual and functional status of various system components, including control panel, interface equipment, lamps/LEDs, power supplies, and notification appliances. The system uses sealed lead-acid batteries and was tested in accordance with applicable NFPA standards, with the system being restored to normal operation at 1:00 p.m. on the inspection date. The inspection was performed by Adam Petty and witnessed by Gabe Hobbs from the V.A. facility.
View the file
Other files for this federal contract opportunity
Show all 26
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Aadco Alarms & Communication Systems
INSPECTION AND TESTING FORM
DATE: 9-12-19
TIME: 11:00pa.m.
SERVICE ORGANIZATION
NAME: Aadco Alarms & Communications
ADDRESS: 115 North 2nd Avenue, Beech Grove, IN 46107
REPRESENTATIVE: Adam P
LICENSE NO.: N/A
MONITORING ENTITY
CONTACT: General Emergency
TELEPHONE: (317)925-8919
MONITORING ACCOUNT REF. NO: 01-02-2604
TYPE TRANSMISSION
PROPERTY NAME (USER)
NAME: V.A. Blda. 9
ADDRESS:
2669 Cold Springs Road Indianapolis, IN 46222
OWNER CONTACT: Gabe Hobbs
TELEPHONE: (317)988-4089
APPROVING AGENCY
CONTACT: N/A
TELEPHONE: N/A
SERVICE
❑ McCulloh ❑ Weekly
❑ Multiplex ❑ Monthly
® Digital ❑ Quarterly
❑ Reverse Priority ❑ Semiannually
❑ RF ® Annually
❑ Other (Specify) ❑ Other (Specify)
N/A N/A
PANEL MFG: Siemens MODEL NO.
CIRCUIT STYLES: 4 & Y
NO. OF CIRCUITS: 4
SOFTWARE REV.: N/A
LAST DATE SYSTEM HAD ANY SERVICE PERFORMED: N/A
LAST DATE THAT ANY SOFTWARE OR CONFIGUARATION WAS REVISED
FC-901
N/A
115 North 2nd Avenue, Beech Grove, IN 46107 (317) 781-7680 1
~►aaco iarms & communication ystems
ALARM-INITIATING DEVICES AND CIRCUIT INFORMATION
QTY OF CIRCUIT STYLE
8 4 MANUAL STATIONS
N/A N/A ION DETECTORS
13 4 PHOTO DETECTORS
N/A N/A DUCT DETECTORS
2 4 HEAT DETECTORS
4 4 WATERFLOW SWITCHES
4 4 SUPERVISORY SWITCHES
N/A N/A OTHER (SPECIFY):
N/A
ALARM INDICATING APPLIANCES AND CIRCUIT INFORMATION
QTY OF CIRCUIT STYLE
N/A N/A BELLS
N/A N/A HORNS
N/A N/A CHIMES
4 Y STROBES
N/A N/A SPEAKERS
15 Y OTHER (SPECIFY):
Horn/Strobe
NO. OF ALARM INDICATING CIRCUITS: 3
ARE CIRCUITS SUPERVISED? EYES ❑ NO
SUPERVISORY SIGNAL INITIATING DEVICES AND CIRCUIT INFORMATION
QTY OF CIRCUIT STYLE
N/A N/A BUILDING TEMP.
N/A N/A SITE WATER TEMP.
N/A N/A SITE WATER LEVEL
N/A N/A FIRE PUMP POWER
N/A N/A FIRE PUMP RUNNING
115 North 2nd Avenue, Beech Grove, IN 46107 (317) 781-7680 2 i►~►aaco Alarms & communication systems
INSPECTION, TESTING, AND MAINTENANCE
CIRCUIT STYLE
N/A FIRE PUMP AUTO POSITION
N/A FIRE PUMP OR PUMP CONTOLLER
N/A FIRE PUMP RUNNING
N/A GENERATOR IN AUTO POSITION
N/A GENERATOR OR CONTROLLER TROUBLE
N/A SWITCH TRANSFER
N/A GENERATOR ENGINE RUNNING
OTHER:
N/A
QTY OF
N/A
N/A
N/A
N/A
N/A
N/A
N/A
SIGNALING LINE CIRCUITS
Quantity and style (See NFPA 72, Table 3-6) of signaling line circuits connected to system:
Quantity: 1 Style(s) 4
a. Primary (Main): Nominal Voltage
Overcurrent Protection: Type
Location (Panel Number):
SYSTEM POWER SUPPLIES
Breaker
N/A
SYSTEM POWER SUPPLIES
Amps 20
Amps 20
Amos N/A
b. Secondary (Standby):
2 X 12V.D.C. 2 X 12V.D.C. Storage Battery: Amp-Hr. Rating 12 / 7
Calculated capacity to operate system, in hours: X 24 60
N/A Engine-driven generator dedicated to fire alarm system:
Location of fuel storage: N/A
TYPE BATTERY
❑ Dry Cell
❑ Nickel-Cadmium
® Sealed Lead-Acid
❑ Lead-Acid
❑ Other (Specify):
N/A
c. emergency or standby system useo as a bacKup to primary power supply, instead of using a secondary power supply:
N/A Emergency system described in NFPA 70, Article 700
N/A Legally required standby described in NFPA 70, Article 701
Optional standby system described in NFPA 70, Article 702, which also meets the performance N/A requirements of Article 700 or 701.
115 North 2nd Avenue, Beech Grove, IN 46107 (317) 781-7680 3
PRIOR TO ANY TESTING
NOTIFICATIONS ARE MADE: YES NO WHO TIME
MONITORING ENTITY ® ❑ General Emergency 11:00pa.m.
BUILDING OCCUPANTS ❑ ® N/A N/A
BUILDING MANAGEMENT ® ❑ Gabe Hobbs 11:00pa.m.
OTHER (SPECIFY) ❑ ® N/A N/A
AHJ (NOTIFED) OF ANY IMPAIRMENTS ❑ ® N/A N/A
SYSTEM TESTS AND INSPECTIONS
TYPE
CONTROL PANEL
INTERFACE EQ.
LAMPS/LEDS
FUSES
PRIMARY POWER SUPPLY
TROUBLE SIGNALS
DISCONNECT SWITCHES
GROUND FAULT MONITORING
SECONDARY POWER
TYPE
BATTERY CONDITON
LOAD VOLTAGE
DISCHARGE TEST
CHARGER TEST
SPECIFIC GRAVITY
TRANSIENT SUPPRESSORS
REMOTE ANNUNCIATORS
NOTIFICATION APPLIANCES
AUDIBLE
VISUAL
SPEAKERS
VOICE CLARITY
VISUAL FUNCTIONAL COMMENTS
® ® N/A
® ® N/A
® ® N/A
❑ N/A
® ® N/A
® ® N/A
❑ ❑ N/A
® ® N/A
VISUAL FUNCTIONAL COMMENTS
® ® Good
26.1
26.6
27.0
LI
® ® N/A
® ® N/A
® ® N/A
❑ ❑ N/A
❑ ❑ N/A
115 North 2nd Avenue, Beech Grove, IN 46107 (317) 781-7680 4
INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS
DEVICE VISUAL FUNCTIONAL FACTORY MEAS.
LOCATION TYPE CHECK TEST SETTING SETTING PASS FAIL
1-1 W. BSMT. RISER WATERFLOW HTRI-D ® ® N/A N/A ® ❑
1-1 W. BSMT. RISER VALVE TAMPER HTRI-D ® ® N/A N/A ® El
1-3 W. BSMT. WEST OP921 ® ® 1.08-2.72 N/A ® ❑
1-4 W. BSMT. EAST OP921 ® ® 1.08-2.72 N/A ® ❑
1-5 W. BSMT. EAST H1921 ® ® N/A N/A ® ❑
1-6 E. BSMT. WEST H1921 ® ® N/A N/A ® El
1-7 E. BSMT. WEST OP921 ® ® 1.08-2.72 N/A ® ❑
1-8 E. BSMT. EAST OP921 ® ® 1.08-2.72 N/A ® El 1-16 1ST FLR. N. MAIN ENTRY HMS-S ® ® N/A N/A ® El
1-17 1ST FLR. N. MAIN ENTRY OP921 ® ® 1.08-2.72 N/A ® El
1-18 W. BSMT. RISER 1ST FLR.
WATERFLOW HTRI-D ® N/A N/A ® ❑
1-18 W. BSMT. RISER 1ST FLR. VALVE
TAMPER HTRI-D N/A N/A ® ❑
1-19 1ST FLR. S.W. ENTRY OP921 ® ® 1.08-2.72 N/A Z ❑
1-20 1ST FLR. S.W. ENTRY HMS-S ® ® N/A N/A ® El 1-21 1ST FLR. S.E. ENTRY OP921 ® ® 1.08-2.72 N/A ® El
1-22 1ST FLR. S.E. ENTRY HMS-S ® ® N/A N/A ® ❑
1-31 2ND FLR. CENTER STAIR OP921 ® ® 1.08-2.72 N/A ® El 1-32 2ND FLR. CENTER STAIR HMS-S ® ® N/A N/A ® El
1-33 2ND FLR. CENTER OP921 ® ® 1.08-2.72 N/A ® ❑
1-34 W. BSMT. RISER 2ND FLR.
WATERFLOW HTRI-D ® N/A N/A ® ❑
1-34 W. BSMT. RISER 2ND FLR.
VALVE TAMPER HTRI-D ® ® N/A N/A ® El
1-352ND FLR. WEST STAIR HMS-S ® ® N/A N/A ® El
1-36 2ND FLR. WEST STAIR OP921 ® ® 1.08-2.72 N/A ® ❑
1-37 2ND FLR. EAST STAIR OP921 ® ® 1.08-2.72 N/A ® El
1-38 2ND FLR. EAST STAIR HMS-S ® ® N/A N/A ® El
1-46 W. BSMT. RISER ATTIC
® ❑ WATERFLOW HTRI-D N/A N/A
1-46 W. BSMT. RISER VALVE
® ® ® El TAMPER HTRI-D N/A N/A
1-47 WEST ATTIC HMS-S ® ® N/A N/A ® El
1-48 WEST ATTIC OP921 ® ® 1.08-2.72 N/A ® El
1-49 EAST ATTIC HMS-S ® ® N/A N/A ® El
1-50 EAST ATTIC OP921 ® ® 1.08-2.72 N/A ® El
COMMENTS:
115 North 2nd Avenue, Beech Grove, IN 46107 (317) 781-7680 5
EMERGENCY COMMUNICATIONS EQUIPMENT
TYPE VISUAL FUNCTIONAL COMMENTS
PHONE SET ❑ ❑ N/A
PHONE JACKS El ❑ N/A
OFF-HOOK INDICATOR ❑ ❑ N/A
AMPLIFIER(S) El El N/A
TONE GENERATOR(S) ❑ ❑ N/A
CALL IN SIGNAL El ❑ N/A
SYSTEM PERFORMANCE El ❑ N/A
El El N/A
INTERFACE EQUIPMENT
DEVICE
TYPE VISUAL OPERATION SIMULATED OPERATION
(SPECIFY) N/A ❑ El El
(SPECIFY) N/A El El El
(SPECIFY) N/A ❑ El ❑
SPECIAL HAZARD SYSTEMS
(SPECIFY) N/A El El ❑
(SPECIFY) N/A El ❑ ❑
(SPECIFY) N/A ❑ ❑ El
SPECIAL PROCEDURES:
Put Vet. House on test first.
COMMENTS: N/A
115 North 2nd Avenue, Beech Grove, IN 46107 (317) 781-7680 6
ON/OFF PREMISES MONITORING:
TYPE YES NO TIME COMMENTS
ALARM SIGNAL ® ❑ 11:00pa.m. N/A
ALARM RESTORAL ® ❑ 1:00p.m. N/A
TROUBLE SIGNAL ® ❑ 11:00pa.m. N/A
SUPERVISORY SIGNAL ® ❑ 11:00pa.m. N/A
SUPERVISORY RESTORAL ® ❑ 1:00p.m. N/A
NOTIFICATIONS THAT TESTING IS COMPLETE:
TYPE
BUILDING MANAGEMENT
MONITORING AGENCY
BUILDING OCCUPANTS
OTHER (SPECIFY)
THE FOLLOWING DID NOT OPERATE CORRECTLY:
NO TIME
❑ 1:00p.m
❑ N/A
❑ N/A
❑ N/A
❑ N/A
N/A
COMMENTS
N/A
N/A
N/A
N/A
N/A
SYSTEM RESTORED TO NORMAL OPERATION:
DATE
9-12-19
TIME
1:00p.m.
THIS TESTING WAS PERFORMED IN ACCORDANCE WITH
APPLICABLE NFPA STANDARDS.
NAME OF INSPECTOR:
DATE:
SIGNATURE:
NAME OF OWNER OR REPRESENTATIVE
DATE:
SIGNATURE:
Adam Petty
9-12-19
Gabe Hobbs
9-12-19
TIME: 1:00p.m.
TIME: 1:00p.m.
COMPANY:
REVIEWED BY:
115 North 2nd Avenue, Beech Grove, IN 46107 (317) 781-7680 7
| Page 1 |
| Page 2 |
| Page 3 |
| Page 4 |
| Page 5 |
| Page 6 |
| Page 7 |