FY22
COMS Service Calls | Requested between 10/1/21 - 9/30/22
| Work Request Code | Work Request Status | Work Request Priority | Problem Type | Site Code | Building Code | Floor Code | Room Code | Problem Location | Work Description | Craftspersons Notes | Equipment Code | Repair Type | Cause Code | Date Work Requested | Due Date | Date Work Completed |
| 36871 | Closed | 1 | COMS|CUP | CENTRAL | 316 | Mech Rm. Boiler/Chiller Rm. | After Hours- B316 Mech Rm/Cer Rm.- (2) smoke detectors t off 1 cer shut down- POC x | 10/4 - On 9/30 cer pped. was notified and responded on 10/1. It was determined that the snubber unit overhea and pped the cer. A replacement was ordered that morning and is expec to be ivered to on 10/5. Technic replace the unit as soon as it is received. Update. technic arrived with p and installed. Unit heating up oil overnight and be tes after coog fan is installed ow. Esa completion is 10/5. AMS 10/5 - wired up coog fan and s cer for testing. Cer s and picked up load smoothly. Comple. AMS | CH-316-1 | REPLACED | EQUIP FAILURE | 10/1/21 | 10/5/21 | 10/5/21 | ||
| 36872 | Closed | 2 | COMS|FIRE SYSTEMS | CENTRAL | 316 | Mech Rm. Boiler/Chiller Rm. | After hours- Fire Inspector- B316 Mech rm. Cer/Boiler rm. Smoke Detectors- L1 & 2n- POC x | 10/4 - Smoke detectors were the result of an actual nt. No action necessary. Cer #1 had an eleccal snubber failure that caused smoke. Complete. AMS | NA | NO REPAIR NEEDED | EQUIP FAILURE | 10/1/21 | 10/4/21 | 10/4/21 | ||
| 36873 | Closed | 3 | COMS|PEST CONTROL | CENTRAL | 300 | LFA | After Hours- B300 LFA care- reques mouse traps- POC x | 10/04- Set up glue boards in corners of LFA in B300. KM | NA | PERFORMED | PROB NOT FOUND | 10/1/21 | 10/12/21 | 10/4/21 | ||
| 36874 | Closed | 2 | COMS|FIRE SYSTEMS | CENTRAL | 315 | After Hours- Fire Inspectors- B315 Trouble came in and restored (AM-50-1, A Node 12, n Voice output fail).- POC x | 10/4 - Checked el and it is in a normal condition at the present e. Complete. AMS | PERFORMED | PROB NOT FOUND | 10/1/21 | 10/4/21 | 10/4/21 | ||||
| 36875 | Closed | 2 | COMS|PEST CONTROL | CENTRAL | 300 | 1 | LFA Twaddler room | Pse bait once again for ants in the twaddler room. Yester they returned.- POC x- CI2DB | 10/1 - Placed bait and glue boards in room under refrigerator where ant activity was found. Complete. AMS | NA | PERFORMED | WEAR | 10/1/21 | 10/4/21 | 10/1/21 | |
| 36877 | Closed | 3 | COMS|ELECTRICAL (LTG) | CENTRAL | 315 | 1 | Side wall - Lab 1 | I would like to submit a work request for the foling: FAA Work Request (re: TSL-): Emergency light on side wall in op. pse replace battery or light (TSL-) Location: Building 315, Lab 1 If you have any questions (re: TSL-), pse contact at 609-650-, at 609-813-, or XXX at 609-813-. | 10/05- found bad emergency light, replaced with new. KM | NA | REPAIR | WEAR | 10/1/21 | 10/12/21 | 10/5/21 | |
| 36878 | Closed | 3 | COMS|ELECTRICAL (LTG) | CENTRAL | 318 | EMRL Lab | I would like to submit a work request for the foling: FAA Work Request (re: TSL-): Exit light above door is not illuting , pse install an illuting exit sign over door in accorce with current code (TSL-) Location: Building 318, EMRL Lab If you have any questions (re: TSL-), pse contact at 609-650-, at 609-813-, or XXX at 609-813-. | 10/05- Responded and found that lab currently has a paper sign. An illu sign was nr installed and require power to be run. Completing request with our e and submitting new coms/can request. KM | NA | REPAIR | PROB NOT FOUND | 10/1/21 | 10/12/21 | 10/5/21 | ||
| 36879 | Closed | 2 | COMS|ELECTRICAL (LTG) | CENTRAL | 315 | Lab 5 | I would like to submit a work request for the foling: FAA Work Request (re: TSL-): activation lr on wall moun emergency light broke off during test. cannot test battery/light. pse replace light (TSL-) Location: Building 315, Lab 5 If you have any questions (re: TSL-), pse contact at 609-650-, at 609-813-, or XXX at 609-813-.- CI2DB | 10/1 - Replaced emergency light with new LED type. (#) Test button did not affect operation of light. Complete. AMS | NA | REPLACED | WEAR | 10/1/21 | 10/4/21 | 10/1/21 | ||
| 36880 | Closed | 2 | COMS|HVACR | CENTRAL | 374 | IED Build Lab | I would like to submit a work request for the foling: FAA Work Request (re: TSL-): nsation drip from twork above (TSL-) Location: Building 374, IED Build Lab If you have any questions (re: TSL-), pse contact at 609-650-, at 609-813-, or XXX at 609-813-.- Ci2CUP | 10/4 - Investiga on 10/1 and there was no nsation drip at that e. Is has to do with humidity and uninsula drop from air handler which the TSL is aware of. The Govt was loo into fixing it last year. Complete. AMS | NA | PERFORMED | PROB NOT FOUND | 10/1/21 | 10/4/21 | 10/4/21 | ||
| 36881 | Closed | 3 | COMS|MATERIAL HANDLING | CENTRAL | 306 | Front Office | Request to pick up 5 monitors from B306 ft office and iver to B305 Loading dock, Room C231- POC x | 10/07- Comple per request. KM | NA | LOGISTICS-MOVE | MOVE | 10/1/21 | 10/12/21 | 10/7/21 | ||
| 36882 | Closed | 2 | COMS|LOCKSMITH | CENTRAL | 374 | Lab A | I would like to submit a work request for the foling: FAA Work Request (re: TSL-): Overhead door does not alarm when activa (TSL-) Location: Building 374, Lab A If you have any questions (re: TSL-), pse contact at 609-650-, at 609-813-, or XXX at 609-813-.- CI2CUP | 10/4 - ON 10/1 investiga and found exor ste wor but horn is not. y and came over and determined they have to order a new unit. New unit ETA is 3-4 weeks. Esa completion is 11/1. AMS 10/*20 - ON 10/18 replaced and tes (2) Gentex Mo #WGEC24-75PPW horn stes. Complete. AMS | NA | REPLACED | EQUIP FAILURE | 10/1/21 | 11/1/21 | 10/20/21 | ||
| 36883 | Closed | 2 | COMS|LOCKSMITH | CENTRAL | 374 | Lab B | I would like to submit a work request for the foling: FAA Work Request (re: TSL-): Overhead door furthest from blast door does not alarm when activa. Also, safety bar on bot of door is very hard to activate to rrse motion (TSL-) Location: Building 374, Lab B If you have any questions (re: TSL-), pse contact at 609-650-, at 609-813-, or XXX at 609-813-.CI2CUP | 10/4 - On 10/1 investiga and found safety edge not wor. Alarm is is being addressed on WR 3. Ordg new safety edge and cord. 2 weeks ivery. Completion date is 10/20. AMS 10/14- Maal came in. Installed new safety air edge and cord. KM | NA | REPAIR | EQUIP FAILURE | 10/1/21 | 10/20/21 | 10/14/21 | ||
| 36884 | Closed | 4 | COMS|UTILITY MARK OUT | OFFCAMPUS | 70 | N/A | B70, west side of northeast-most comm tower | Pse provide a utility -out for the area imtely west of the north- comm tower at the Building 70 site for a concrete pad installation. The location is indica on the attached map. | 10-05- - Comple eleccal out for indica area on attached map. (wef) 10/8 - Comple plum -out. No known water or sewer in area. Complete. AMS | NA | OPERATIONAL SUPPORT | PROB NOT FOUND | 10/1/21 | 10/12/21 | 10/8/21 | |
| 36886 | Closed | 3 | COMS|MATERIAL HANDLING | CENTRAL | 316 | 3 | Jobshop, Col I5 | Pse remove two bro crs from the Jobshop, Building 316, third floor, I-5. Both crs are ed as bro.- POC Al x | 10/05- Comple per request. KM | NA | LOGISTICS-MOVE | MOVE | 10/1/21 | 10/12/21 | 10/5/21 | |
| 36887 | Closed | 3 | COMS|LOCKSMITH | CENTRAL | 305 | Back hallway | I have a locked Hon file cabinet loca in the back way of B305. It is 18” w 5 drawer high beige. Can the lock open it and make a key if there isn’t one inside the cabinet? POC -I can be contac at 609-317- | 10/12- Loca cabinet, opened, made keys and left inside cabinet. KM | NA | REPAIR | WEAR | 10/1/21 | 10/12/21 | 10/12/21 | ||
| 36890 | Closed | 3 | COMS|MATERIAL HANDLING | CENTRAL | 300 | 2 | Lab #12 | B300 2nd floor Lab #12 needs to have Comms. pick up one dumpster dropped ier this week. This one filled with metal debris and needs to be brought to building 206 for recycg. Enter Door #14 2nd floor. The c are loca in LAB 12. Just to the left when entg door#14. Also, Lab between n C27 & C28. POC / X / 630-818- cell. | 10/08- Comple per request. KM | NA | LOGISTICS-MOVE | MOVE | 10/1/21 | 10/12/21 | 10/8/21 | |
| 36891 | Closed | 3 | COMS|ELECTRICAL (LTG) | CENTRAL | 300 | Auditorium | B300 Auditorium. There are nine (9) safety lights moun on stair risers that are out. Some on both side of the a. Bring all lights back to wor order. POC = X / 630-818- cell | 10/08- Replaced 5 40 w led and 5 40w tube bulbs. KM | NA | REPAIR | WEAR | 10/1/21 | 10/12/21 | 10/8/21 | ||
| 36892 | Closed | 3 | COMS|ELECTRICAL (LTG) | CENTRAL | 300 | 2 | Main hallway | B300 2nd floor n way. Wall moun can light near n K33 is out. Bring light back to wor order. POC = X 433 / 630-818- cell | 10/07- Replaced 2 42Wcfl. KM | NA | REPAIR | WEAR | 10/1/21 | 10/12/21 | 10/7/21 | |
| 36893 | Closed | 3 | COMS|ELECTRICAL (LTG) | CENTRAL | 300 | 2 | Main hallway, near column H23 | B300 2nd floor n way. Wall moun can light near n H23 is out. Bring light back to wor order. POC = X 433 / 630-818- cell | 10/07- Replaced 2 42wcfl. KM | NA | REPAIR | WEAR | 10/1/21 | 10/12/21 | 10/7/21 | |
| 36894 | Closed | 3 | COMS|ELECTRICAL (LTG) | CENTRAL | 300 | 2 | 2WR05 | Women's room | B300 2nd floor Women’s Room 2WR05 has lights that are out. Bring all lights back to wor order. POC = X 433 / 630-818- cell | 10/07- Replaced 2 F25T8CW. KM | NA | REPAIR | WEAR | 10/1/21 | 10/12/21 | 10/7/21 |
| 36895 | Closed | 3 | COMS|LOCKSMITH | CENTRAL | 300 | 2 | 2WR05 | Women's room | B300 2nd floor Women’s Room 2WR05. Door ss shut need the hydraulic door closer adjus or replaced. Hydraulic fluid is drip down the door on the inside. Bring door back to wor order. POC = X 433 / 630-818-7 cell | 10/12- Supply and install new door closer. KM | NA | REPAIR | WEAR | 10/1/21 | 10/12/21 | 10/12/21 |
| 36896 | Closed | 3 | COMS|ELECTRICAL (LTG) | CENTRAL | 300 | 2 | main hallway near column G29 | B300 2nd floor n way near n G29. Wall moun can is not wor. Bring light back to wor order. POC = X / 630-818- cell | 10/08- Replaced 2 42wcfl. KM | NA | REPAIR | WEAR | 10/1/21 | 10/12/21 | 10/8/21 | |
| 36897 | Closed | 3 | COMS|ELECTRICAL (LTG) | CENTRAL | 300 | 2 | Elevator Bank “B”. | B300 2nd floor Eltor lobby for Eltor Bank “B”. ceiling can light when exiting eltor is out. Bring light back to wor order. POC = X 433 -630-818- cell. | 10/08- Replaced 2 42wcfl. KM | NA | REPAIR | WEAR | 10/1/21 | 10/12/21 | 10/8/21 | |
| 36898 | Closed | 3 | COMS|ELECTRICAL (LTG) | CENTRAL | 300 | 3 | main hallway across from column J24 | B300 3rd floor n way ac from n J24 has a can light out. Bring light back to wor order. POC = X / 630-818- cell. | 10/07- Replaced 1 42wcfl. KM | NA | REPAIR | WEAR | 10/1/21 | 10/12/21 | 10/7/21 | |
| 36899 | Closed | 3 | COMS|ELECTRICAL (LTG) | CENTRAL | 300 | 3 | main hallway across from column J27 | B300 3rd floor n way ac from n J27 has a can light out. Bring light back to wor order. POC = X / 630-818- cell. | 10/07- Replaced 1 42wcfl. KM | NA | REPAIR | WEAR | 10/1/21 | 10/12/21 | 10/7/21 | |
| 36900 | Closed | 3 | COMS|ELECTRICAL (LTG) | CENTRAL | 300 | 3 | main hallway across from column K30 | B300 3rd floor n way ac from n K30 has a can light out. Bring light back to wor order. POC = X / 630-818-. | 10/12- Replaced 1 42w bulb and 1 42w ast. KM | NA | REPAIR | WEAR | 10/1/21 | 10/12/21 | 10/12/21 | |
| 36903 | Closed | 3 | COMS|ELECTRICAL (LTG) | CENTRAL | 300 | 3 | 3WR01 | Women's room | B300 3rd Women’s Room 3WR01. Soffit light not wor. Bring all lights back to wor order. POC = X / 630-818- cell. | 10/07- Replaced 2 F25T8CW. KM | NA | REPAIR | WEAR | 10/1/21 | 10/12/21 | 10/7/21 |
| 36904 | Closed | 3 | COMS|MATERIAL HANDLING | CENTRAL | 300 | 1 | 1N235 | From 305 Loc 300 1st room 1N235 Name CALL FIRST 4 fedex e. boxes | 10/05- Comple per request. KM | NA | LOGISTICS-MOVE | MOVE | 10/1/21 | 10/12/21 | 10/5/21 | |
| 36905 | Closed | 3 | COMS|MATERIAL HANDLING | R&D | 296 | From 305 Loc 296 Name P 2 fedex g. boxes | 10/04- Comple per request. KM | NA | LOGISTICS-MOVE | MOVE | 10/1/21 | 10/12/21 | 10/4/21 | |||
| 36907 | Stopped-Closed | 3 | COMS|MATERIAL HANDLING | WEST | 270 | From 305 Loc 270 Name P 8 boxes | NULL | 10/1/21 | 10/12/21 | |||||||
| 36908 | Closed | 3 | COMS|MATERIAL HANDLING | CENTRAL | 300 | 3 | Col G21 | From 305 Loc 300 3 g 21 Name P 2 fedex e. boxes | 10/04- Comple per request. KM | NA | LOGISTICS-MOVE | MOVE | 10/1/21 | 10/12/21 | 10/4/21 | |
| 36913 | Closed | 3 | COMS|VEHICLES | CENTRAL | 318 | Warehouse | I would like to submit a work request for the foling: FAA Work Request (re: TSL-): ISS Motor Pool: TSL building 318 fork lift 13- L/P Sr#85 engine running rough. bog's down while going up . pse service engine. (TSL-) Location: Building 318, 318 Warehouse If you have any questions (re: TSL-), pse contact at 609-650-, at 609-813-, or XXX at 609-813-. | 10/08- After ng the fuel supply from k to engine, found kink behind air cner t. Replaced hose. KM | FKLFTP-0005 | REPAIR | EQUIP FAILURE | 10/1/21 | 10/12/21 | 10/8/21 | ||
| 36914 | Closed | 2 | COMS|PLUMBING | CENTRAL | 300 | 1 | Col H16, work area sink | Plem: Clogged sink Location: B300.1.H16- work area sink. POC x- call before co-CI2DB | 10/4 - ON 10/1 unclogged sink drain. Complete. AMS | NA | PERFORMED | WEAR | 10/1/21 | 10/4/21 | 10/4/21 | |
| 36916 | Closed | 3 | COMS|ELECTRICAL (LTG) | R&D | 211 | 1 | Hallway | Request to check (2) lights in B211 way that is not wor- POC x | 10/04- Replaced 2 T8 bulbs. KM | NA | REPAIR | WEAR | 10/1/21 | 10/12/21 | 10/4/21 | |
| 36917 | Stopped-Closed | 3 | COMS|PAINTING | R&D | 211 | 1 | hallway downstairs | Request to paint B211 1st floor way down- POC x | 10/06- Eled DM regarding the poor pning on this request and this is not a way, it is a heavily popula eleccal equipment room. KM 10/14- Stop per NZ. KM | 10/1/21 | 10/12/21 | |||||
| 36918 | Closed | 3 | COMS|HVACR | CENTRAL | 319 | DES Lab | I would like to submit a work request for the foling: FAA Work Request (re: TSL-): TSL building 319 DES/Trace lab has just received a AAON #ASM5 Handheld service tool to prog the AAON HVAC units in both lab's. Pse have ISS HVAC serves tech come out to to go over operation and where to locate the progra tool. t you (TSL-) Location: Building 319, DES Lab If you have any questions (re: TSL-), pse contact at 609-650-, at 609-813-, or XXX at 609-813-. *Pse reply with the work request classification ll with the work request number. | 10/12- Met with rep and t over use of handheld unit. KM | NA | PERFORMED | PROB NOT FOUND | 10/1/21 | 10/12/21 | 10/12/21 | ||
| 36919 | Closed | 4 | COMS|PAINTING | CENTRAL | 300 | 1 | 1N235 | B300, 1st floor, SECTR Lab, Secure Room Vestibule | Touch Up paint is reques in the SECTR Lab vestibule area (aka the Secure Room) in B300, 1st floor next to Imaging Technologies dept. The paint used is by / Ultra Spec 500/Inor Flat Finish/ Color: OC-131 "W Down". There is about 250 sf of area to be pain. Contact the requestor " - x" to discuss specifics as well as access to the area since the space needs special access to get in. | 10/18- We have left messages for the POC. Waiting for call back for access. KM 10/21- Scheduled for site visit on 10/25 and work tentatively work scheduled for 10/27. Target 10/28. KM 10/27- Matched paint, ordered, spackled, sanded, vacuumed and pain. KM | NA | REPAIR | WEAR | 10/1/21 | 10/18/21 | 10/27/21 |
| 36920 | Closed | 3 | COMS|FIRE PERMIT | CENTRAL | 316 | 2 | 2MRA | Need Burn Permit for HVAC work on AHU-7 in meical room. F is aware. | 10/05- Inspec area, isd permit. KM | NA | PERFORMED | PROB NOT FOUND | 10/4/21 | 10/13/21 | 10/5/21 | |
| 36921 | Closed | 3 | COMS|UTILITY MARK OUT | CENTRAL | 300 | 1 | 1N551 | Pse is a work request for a utility out for the area on the attached map. If you have any questions pse contact me. POC / (856) 904- Cell tc | 10/8 - On 10/7 comple eleccal -out for the VOR v feeder from taxiway "A" to the VOR. Complete. AMS | NA | OPERATIONAL SUPPORT | PROB NOT FOUND | 10/4/21 | 10/13/21 | 10/8/21 | |
| 36922 | Closed | 3 | COMS|CUP | CENTRAL | 300 | 3 | Column Q-19 | AFTER HOURS Checked under floor for water- alarm bee on round POC tc | 10/4 - ON 10/2 checked under floor. No water found. Blew out nsate e. Complete. AMS | NA | PERFORMED | PROB NOT FOUND | 10/4/21 | 10/13/21 | 10/4/21 | |
| 36923 | Closed | 4 | COMS|MATERIAL HANDLING | CENTRAL | 300 | 4 | Col L24 | Pse have the 30 monitors unboxed and have the 15 Varidesks unboxed and place in the cubes at B300, 4th floor, Col L24 area.. POC (609) 266-. This is a secure area and locked. I be there on Thurs 9am-10am Pse call first. | 10/07- Spoke with POC and this take place on 10/12 sting at 9-10am. KM 10/12- Comple per request. KM | NA | LOGISTICS-MOVE | MOVE | 10/4/21 | 10/8/21 | 10/12/21 | |
| 36924 | Closed | 2 | COMS|PEST CONTROL | CENTRAL | 300 | N/A | Exterior area near dumpster | Set trap to catch ra n near dumpster area. | 10/4 - Set box trap in the vicinity of the dumpster. take a week or 2 to catch anything. Esa completion is 10/15. AMS 10/10 - On 10/5 checked trap. No catch, 10/6 checked trap, no catch, 10/7 checked trap, no catch. 10/8 removed trap. No animal caught. AMS 10/13 - No further action ta. Ra have moved on. Complete. AMS | NA | PERFORMED | WEAR | 10/4/21 | 10/15/21 | 10/13/21 | |
| 36925 | Closed | 2 | COMS|PEST CONTROL | WEST | 284 | 1 | Breakroom | Pest Control- Having mice is. POC x- CI2DB | 10/4 - Set snap traps and glue boards in breakroom where mice were n. Complete. AMS | NA | PERFORMED | WEAR | 10/4/21 | 10/5/21 | 10/4/21 | |
| 36926 | Closed | 2 | COMS|PLUMBING | CENTRAL | 300 | 1 | LFA | The wa hine in LFA is not wor again POC CI2DB tc | 10/4 - Farinelli be in at 6AM Tues morning to investigate prior to students arriving. AMS 10/5 - Ran unit and had no iss at that e. As per she moved door switch and washer s wor. Opened and closed door numerous es with no iss. Need plem to happen again to properly troubleshoot. Complete. AMS | PERFORMED | PROB NOT FOUND | 10/4/21 | 10/5/21 | 10/5/21 | ||
| 36928 | Closed | 4 | COMS|MATERIAL HANDLING | CENTRAL | 305 | 1 | Loading Dock | Pse pick up (6) pallets of equipment from B305 Loading dock and iver to B300, 3rd floor, Col C27 ( put equipment against wall of TPC Lab)- Request for October 6th, . POC Like in (609) 515-, pse call before co. | 10/07- comple per request. KM | NA | LOGISTICS-MOVE | MOVE | 10/4/21 | 10/7/21 | 10/7/21 | |
| 36929 | Closed | 3 | COMS|CAN INTERIOR EXTERIOR | CENTRAL | 300 | 2 | 2W837 | Column L-27 | I would like to request to have the foling services for Conf. Room 300/2/L27 (2W837): Remove projector (ve projector in room) Remove & dispose projection screen and housing Replace ceiling tiles that are damaged from the projector and projection screen Remove audio box and cable chase Remove speakers & cable chase (ve speakers in room) Remove fire ste light on the wall – there’s already a smoke detector with fire ste light in the ceiling Paint conf. room and repair as best as you can any damage to the walls – be advised the walls in this conf. room are LMT walls Pick up 55” TV monitor & TV mount from Imaging Technologies Office (F11) iver 55” TV monitor & TV mount to Conf. Room L27 Run power ½ way up the wall Install TV mount Install 55” TV monitor and if possible run HDMI cable down to the bot of the wall. Similar to all the other TV monitor installs in the other conf. rooms I undersd that the LMT walls create a chge. Although, & I are not at Tech. Center ry , & I make ourselves available to meet with anyone before the work is performed. If you have any questions feel free to contact me on my cell 609.709.. tc | 10/12- Work is in progress but due to the number of trades lumped onto this request and the order of work, Target date is 10/26. KM; 10/13 - fire inspectors secured system, unwired ste light and removed wiring from wall, installed bk plate and placed system back to normal - daj ivered TV. Removed projector, screen, replaced ceiling tiles that were needed, removed audio box and cable chase, removed speakers and cables. Left speakers and projector in room. Schedug elecc and TV mount. KM 10/19- TV scheduled for 10/21 then painting. Targeting 10/29. If cost exceeds $, request be stopped. KM 10/28- painting is comple. Returning for power. Labor at .17, getting maal cost. KM 10/28- Outlet complete as well as all work on request. KM | NA | UPGRADE-MODIFICATION | NEW INSTALLATION | 10/4/21 | 10/13/21 | 10/29/21 |
| 36930 | Closed | 3 | COMS|CAN INTERIOR EXTERIOR | CENTRAL | 316 | 4 | 4E163 | Column D-15 Rm 419 | I would like to request to have the foling services for Conf. Room 316/4/D15 (4E163)-Rm. 419: I would like to swap out the 55”TV and have it stalled in the Conf. Room next door (Rm. 420), then have a 70” TV monitor installed. Remove 55” TV monitor & mount from wall iver 55” TV monitor & mount next door to Conf. Room 420 Remove shelf mount be TV Repair any holes left from shelf mount Paint the TV wall Pick up 70” TV monitor and mount from Imaging Tech. Office (F10) iver 70” TV monitor & mount to Conf. Room 316/4/D15 – Rm. 419 Install TV mount & 70” TV monitor Run HDMI cable through wall (similar to other Conf. Room installs) Although, & I are not at Tech. Center ry , & I make ourselves available to meet with anyone before the work is performed. If you have any questions feel free to contact me on my cell 609.709.. tc | 10/12- Work is in progress but due to the number of trades lumped onto this request and the order of work, Target date is 10/26. KM ivered TVs. Swapped out tv and mount. Removed shelf, repaired holes. Schedug paint and HDMI Cable. KM 10/19- TV scheduled for 10/21 then painting. Targeting 10/29. If we get to $, request be stopped and sent to IDIQ. KM 10/21- Eleccal work complete. Painting scheduled to st ow. KM 10/22- Paint complete. All work on request complete. KM 10/25- Visi Room 419, attached pic. TV wall was pain per request. Room 420 has areas where the screen was removed that need paint howr, painting was not specified on the request for Room 420 and we were not aware of what the master p was for that room. Spoke with HK. Re-completing this request with no additional work necessary. KM | NA | UPGRADE-MODIFICATION | NEW INSTALLATION | 10/4/21 | 10/13/21 | 10/25/21 |
| 36931 | Closed | 3 | COMS|CAN INTERIOR EXTERIOR | CENTRAL | 316 | 4 | 4E165 | Column D-15 rm 420 | I would like to request to have the foling services for Conf. Room 316/4/D15 (4E165)-Rm. 420: Remove projector (ve projector in room) Remove & dispose projection screen and housing Replace ceiling tiles that are damaged from the projector and projection screen Remove speakers from the wall (ve in room) Bk out eleccal plate on the wall Run elecc power to middle of the wall with quad outlet Install TV mount Install 55” TV monitor Run HDMI cable through the wall (similar to other Conf. Rm installs) Although, & I are not at Tech. Center ry , & I make ourselves available to meet with anyone before the work is performed. If you have any questions feel free to contact me on my cell 609.709.. tc | 10/12- Work is in progress but due to the number of trades lumped onto this request and the order of work, Target date is 10/26. KM 10/15- Removed projector, left in room, removed screen, replaced ceiling tiles that were needed, removed speakers and left in room. Schedug elecc, TV install. TV in room. KM 10/19- TV scheduled for 10/21. Targeting 10/22. If we get to $, request be stopped and sent to IDIQ. KM 10/21- Eleccal work comple. All items complete. KM | NA | INSTALLATION | NEW INSTALLATION | 10/4/21 | 10/13/21 | 10/21/21 |
| 36932 | Closed | 3 | COMS|ELECTRICAL (PWR) | R&D | 206 | N/A | Pse generate a work request to have an elecc identify underground wire exposed while digging at B-206. POC / Cell: 609-289- tc | 10/4 - Found abaned Romex wire in the ground that has been de-energized years ago. Cut wire and removed for contractor to proceed with asphalt work. Complete. AMS | PERFORMED | OLD | 10/4/21 | 10/13/21 | 10/4/21 | |||
| 36933 | Closed | 3 | COMS|PLUMBING | R&D | 206 | N/A | Pse generate a work request to have a plumber out to B-206 and identify some valves. POC / Cell: 609-289- tc | 10/5 - ON 10/4 identified valves as reques. Complete. AMS | NA | OPERATIONAL SUPPORT | PROB NOT FOUND | 10/4/21 | 10/13/21 | 10/5/21 | ||
| 36936 | Closed | 4 | COMS|GENERATORS | R&D | 208 | Pse pump out rening fuel from generator diesel k on Fry morning (10/8) POC / 609-774- Mobile tc | 10/5 - as per , this is being placed on hold to perform 10/13 or 10/14 due to date reques is not feasible due to upco PPO and scheduled pre-work load for e. Arrangements have been made with requestor and d. - target of completion is 10/15 - daj 10/14- We 't have the means to pump this out and move it to a generator with enough capacity to take it. We are getting a quote from Riggins to pump it out and pump it into the BCP generator. Target date be 10/22. KM 10/22- We haven't received a quote from Riggins. Sent fol up el. Pu Target to 10/29. KM 10/26- Spoke with from Riggins. Still waiting for quote and schedule. Target is N/A until we can lock this down. KM 11/02- 94 gallons B201, 57 gallons Magnum 1 at B70, 12 gallons B206 forklift. KM | NA | PERFORMED | PROB NOT FOUND | 10/4/21 | 10/12/21 | 11/2/21 | |||
| 36939 | Closed | 2 | COMS|LEAK | R&D | 291E | Admin area over Todd Burkes cubicle | We previously submit a work request for a water k co from the ceiling in the Building 291E Admin area over s cubicle. That area is still water and we have a t can catg the water. Pse send someone to make a permanent repair. T you. Your Point of Contact (POC) for this work request be: , 609-813- (office) 609-335- (cell) Or , 609-813- (office) 609-335- (cell) CI2DB tc | 10/5 - On 10/4 investiga and found ceiling dry and no water drip from diffuser. T can on desk was completely empty and dry. This have been a humidity is at the e of the submission but nothing was found. Complete. AMS | NA | PERFORMED | PROB NOT FOUND | 10/4/21 | 10/5/21 | 10/5/21 | ||
| 36940 | Closed | 3 | COMS|MATERIAL HANDLING | R&D | 291M | I would like to place a work request to have TWO full barrels of indusal waste picked up from Building 291M and TWO new barrels dropped off. Your Point of Contact (POC) for this work request be: , 609-813- (office) 609-335- (cell) Or , 609-813- (office) 609-335- (cell) tc | 10/08- Comple per request. KM | NA | LOGISTICS-MOVE | MOVE | 10/4/21 | 10/13/21 | 10/8/21 | |||
| 36941 | Closed | 3 | COMS|MATERIAL HANDLING | CENTRAL | 305 | 1 | Loading Dock | Pse pick up 3 or 4 packages from B305 Loading dock and iver to B211, 1st floor, Test Cell #2- POC x | 10/07- Comple per request. KM | NA | LOGISTICS-MOVE | MOVE | 10/4/21 | 10/13/21 | 10/7/21 | |
| 36942 | Closed | 2 | COMS|SECURITY SYSTEMS | CENTRAL | 350 | Flight e camera #1 is off e. Bldg 350. POC 609-204- CI2DB tc | 10/4 - Made arrangements to further troubleshoot video loss on Flighte 1 camera using bucket truck at 6AM on 10/5. Plem is not with or Video-Edge software. AMS 10/5 - Reset inor power supply at 2 floor ops end and tes. Complete. AMS | NA | PERFORMED | EQUIP FAILURE | 10/4/21 | 10/5/21 | 10/5/21 | |||
| 36943 | Closed | 3 | COMS|MATERIAL HANDLING | CENTRAL | 305 | 1 | TSF Loading dock | Pse pick up 1 big glass package from bldg.305 TSF loading dock and iver it to bldg.300 1st fl. room 1N235 X tc | 10/08- Comple per request. KM | NA | LOGISTICS-MOVE | MOVE | 10/4/21 | 10/13/21 | 10/8/21 | |
| 36944 | Closed | 3 | COMS|ENVIRONMENTAL | CENTRAL | 301 | Hanger | Pse submit a WR for the Hazardous Waste Specist, s, to wit the pickup of hazardous waste at Building 301 (Hangar) and sign the fest. The hauler be on site the foling dates: Mon 10/04: (one truck at 9:00 AM) (Pse note this pickup already occurred, but is included for documentation.) Tues 10/05: (one truck at 9:00 AM) Pse meet the hauler at the SOC building to escort on site to Building 300. The e is TBD. confirm the onsite e and for the ’s information to s for reference. Pse contact at X- or .@faa.gov for more information. tc | 10/13 - comple as per work description - daj | NA | OPERATIONAL SUPPORT | PROB NOT FOUND | 10/4/21 | 10/13/21 | 10/13/21 | ||
| 36946 | Closed | 3 | COMS|WATER | CENTRAL | 305 | 1 | A079 | Pse generate the foling work request for COMs. Requesting the Water Treatment Pt Operator assist i with ta Legionella from throughout the base. pg occur on Tues, October 5th and Thurs, October 7th. i identify ple locations, provide access to each building, and l out once they are ta. POC tc | 10/7 - All ta and left with i to be shipped to the lab. Complete. AMS | NA | OPERATIONAL SUPPORT | PROB NOT FOUND | 10/4/21 | 10/13/21 | 10/7/21 | |
| 36948 | Closed | 3 | COMS|MATERIAL HANDLING | CENTRAL | 305 | 1 | TSF Loading dock | Pse pick up 1 spill kit from bldg. 305 TSF loading dock and iver it to bldg.204 x Cell 609 513- POC tc | 10/07- Comple per request. KM | NA | LOGISTICS-MOVE | MOVE | 10/4/21 | 10/13/21 | 10/7/21 | |
| 36949 | Closed | 3 | COMS|PAINTING | R&D | 296 | N/A | Requesting a WR be submit to repaint 2 handicap par spaces at B-296 POC tc | 10/07- Comple per request. KM | NA | REPAIR | WEAR | 10/4/21 | 10/13/21 | 10/7/21 | ||
| 36950 | Closed | 2 | COMS|TEMP CUP | CENTRAL | 300 | 1 | LFA Office | Pse increase the temperature in the LFA office 2 degrees. The wall therat d 68 and my digital one d 67 degrees during ps of the . It definitely felt cooler than 68 degrees. POC CI2CUP tc | 10/5 - On 10/4 adjus setpoints on VAV box as reques. Monitored for desired ge. Complete. AMS | NA | PERFORMED | WEAR | 10/4/21 | 10/5/21 | 10/5/21 | |
| 36952 | Closed | 3 | COMS|MATERIAL HANDLING | R&D | 211A | Garage | Pick up shelf at loc 211a garage & take to loc 70 Name P 1 shelf | 10/08- Comple per request. KM | NA | LOGISTICS-MOVE | MOVE | 10/5/21 | 10/14/21 | 10/8/21 | ||
| 36953 | Closed | 3 | COMS|MATERIAL HANDLING | CENTRAL | 300 | 3 | Col F19 | From 305 Loc 300 3 f 19 Name P 7 theon pallets | 10/07- Comple per request. KM | NA | LOGISTICS-MOVE | MOVE | 10/5/21 | 10/14/21 | 10/7/21 | |
| 36954 | Closed | 3 | COMS|CUP | CENTRAL | 300 | 5 | Mech Rm. #4, AC-2 R/F | After Hours- B300, 5th fl, Mech Room #4, AC-2 R/F- AC-2 return fan needed belts- POC x | 10/5 - Replaced belts on return fan. Complete. AMS | NA | REPLACED | WEAR | 10/5/21 | 10/14/21 | 10/5/21 | |
| 36955 | Closed | 3 | COMS|CUP | CENTRAL | 300 | 5 | Mech Rm. #4, AC-2 | After Hours- B300, 5th fl, Mech room #4 AC-2 supply fan needed belts- POC x | 10/5 - Replaced belts. Complete. AMS | NA | REPLACED | WEAR | 10/5/21 | 10/14/21 | 10/5/21 | |
| 36956 | Closed | 2 | COMS|ELECTRICAL (PWR) | N/A | N/A | Main Substation | After Hours- n Substation- Tie breaker closed, Breaker 52-3 open due to power loss- POC x | 10/5 - ACE experienced a brief outage on the FAATC 200 side tap 69kv e during a lightning storm. In turn this caused the 12kv 52-3 n to open and the 52-2 tie to close at the n substation. This single sourced the us at the 12kv ll. Placed the us back to the preferred double sourced configuration via ADS switches and 12kv n and n tie breakers after inspection. Comple. AMS | NA | PERFORMED | WEATHER | 10/5/21 | 10/6/21 | 10/5/21 | ||
| 36957 | Closed | 2 | COMS|GENERATORS | CENTRAL | 303 | After Hours- B303 "ATS meical failure" Gens still running after outage.- POC x | 10/5 - Found meical failure at ATS sferring to emergency power. Reset ATS and gens powered down. ATS is scheduled for replacement, ATS-16. Complete. AMS | NA | PERFORMED | WEATHER | 10/5/21 | 10/6/21 | 10/5/21 | |||
| 36958 | Stopped-Closed | 2 | COMS|SECURITY SYSTEMS | N/A | N/A | Gate AOA 13 | After Hours - Gate AOA 13- Gate not wor- POC Security x | 10/6 - On 10/5 Found gate inoperable after storm. Determined that (2) motherboards for gate operators need to be replaced a with bates, AC adapter, card reader, loop modules and speakers. Still investigating a loop module on outgoing side. Replaced (1) RDR-2 board and (1) EDS 24v DC power supply provided by government. Repairs oing. Collecting costs for repair and loop module replacement to submit as IDIQ due to cost. Esa completion is 10/8. AMS 10/7 - T&M number is 29. Stopped. AMS | NA | WEATHER | 10/5/21 | 10/8/21 | ||||
| 36959 | Closed | 2 | COMS|PLUMBING | OFFCAMPUS | 176 | 1 | Pse replace the water heater at B176. Plumbers are aware, no need to call out. | 10/5 - Replaced water heater. Put in service and checked. Complete. AMS | REPLACED | EQUIP FAILURE | 10/5/21 | 10/6/21 | 10/5/21 | |||
| 36960 | Closed | 2 | COMS|SECURITY SYSTEMS | WEST | 11 | Air Guard side by main gate | After Hours- B11 Air Guard side by n gate. Trouble on Fire el- POC Security x | 10/5 - Investiga and found negative ground. Checked entire building for water ks. Rang building to if ground t away. Negative ground still there. Pulled each zone card, trouble sed. Turned off each zone card and trouble cred. Put el back to normal operating condition and trouble came back. Needs further investigation. Pably due to power is this morning which affec AOA gate as well. Esa completion is 10/8. AMS 10/8 - Troubleshooting indicates the board be bad. know for certain by Wednes if needed and availability/ETA. el is powered up but it has a negative ground. Esa completion is 10/13. AMS 10/13 - Continued troubleshooting system Removed ry device and ground did not cr. Board is the plem but it is operational at this e. It shows a trouble alarm but it alarm if needed. The system is so old it is obsolete and a replacement board is not available. check old spare Sit Knight ps to if we have one. Otherwise the system needs to be replaced with a newer version. Esa completion is 10/19. AMS 10/14 Continued troubleshooting. We do not have any spare ps and the board is definitely bad. el needs to be replaced but it is operational at this e. Complete. AMS | NA | TEMPORARY REPAIR | EQUIP FAILURE | 10/5/21 | 10/19/21 | 10/14/21 | ||
| 36961 | Closed | 2 | COMS|FIRE SYSTEMS | CENTRAL | 316 | UPS room | After Hours- B316 UPS room- ACU-2 in alarm- POC x | 10/5 - Responded to call. Verified location from CUP. This device is not p of building alarm system. Complete. AMS | NA | NO REPAIR NEEDED | PROB NOT FOUND | 10/5/21 | 10/6/21 | 10/5/21 | ||
| 36962 | Closed | 2 | COMS|HVACR | CENTRAL | 315 | Roof | After Hours- B315 Roof- RTU #2 pped- POC x | 10/5 - Reset unit after power outage. Complete. AMS | NA | PERFORMED | WEATHER | 10/5/21 | 10/6/21 | 10/5/21 | ||
| 36964 | Closed | 2 | COMS|TEMP CUP | CENTRAL | 300 | 1 | LFA infant room | Pse decrease Infant room temperature. It is sitting at 71 degrees. Pse decrease to 69 degrees.- POC x- CI2CUP | 10/5 - Res AC-6 after power outage. Complete. AMS | NA | PERFORMED | WEATHER | 10/5/21 | 10/6/21 | 10/5/21 | |
| 36966 | Closed | 2 | COMS|CUP | CENTRAL | 300 | 3 | Column F-29 CRAC-55 | CRAC-55 is in alarm, Water under floor POC CI2DB tc | 10/6 - On 10/5 checked unit. No water found under floor. Reset unit. There was a bro belt found. ged belts. Complete. AMS | PERFORMED | PROB NOT FOUND | 10/5/21 | 10/6/21 | 10/6/21 | ||
| 36967 | Closed | 3 | COMS|PLUMBING | R&D | 287 | 2 | Water fountain | Pse adjust the f of water on the water fountain to a higher ll B-287 2 POC tc | 10/7 - Adjus ure as reques. Complete. AMS | ADJUSTMENT | WEAR | 10/5/21 | 10/14/21 | 10/7/21 | ||
| 36969 | Closed | 3 | COMS|ROADS | R&D | 206 | N/A | REQUEST TO HAVE THE 30 YARD T DUMPSTER PICKED UP AND EMPTIED AT BUILDING 206.- POC X | 10/12- Comple per request. KM | NA | PERFORMED | PROB NOT FOUND | 10/5/21 | 10/14/21 | 10/12/21 | ||
| 36970 | Stopped-Closed | 3 | COMS|MECHANICAL (GEN) | CENTRAL | 305 | 1 | Loading dock office area | Requesting a WR be submit to remove ure sensitive adhesive from concrete floor where the carpet was just removed at B-305 loading dock office area. (11’x20’)- POC x | 10/14- Removed glue per request. KM 10/19- Returned and used acetone to soften and scrape adhesive. return ow once dry to check again. KM 10/25- Spoke with HK. We have ed Goof Off, Acetone, soap and water, the steam hine (which ks and does not heat). HK spoke with carpet comy who d meical removal is only method they know of. Waiting to hear back from HK. KM 10/25- Per HK, look into grinding. get quote on hine rental. Target is N/A. KM 10/28- Note: this be DB as it is modification per DM. Rep scheduled to look at job Mon to advise whether this harm the grinder and recommend sealer. This job exceed $ and be sent to IDIQ once we have that information and cost. KM 11/03- Received quote to, attached. Sending to IDIQ. KM 11/04- T&M 26. Stop. KM 11/08- Per HK, completing with our e. KM | NA | PERFORMED | PROB NOT FOUND | 10/5/21 | 10/14/21 | 11/8/21 | |
| 36972 | Closed | 3 | COMS|CAN ELECTRICAL | CENTRAL | 318 | 1 | I would like to submit a work request for the foling: FAA Work Request (re: TSL-): Exit light above door is not illuting , pse install an illuting exit sign over door in accorce with current code (TSL-) Location: Building 318, EMRL Lab Must run power for sign. If you have any questions (re: TSL-), pse contact at 609-650-, at 609-813-, or XXX at 609-813-. | 10/22- This request was just approved to. We make a site visit next week to assess and then schedule the work. KM 10/28- Ordg supplies. Target date 11/9. KM 11/09- Last note still relnt. KM 11/09- Installed new lit exit sign. KM | NA | INSTALLATION | NEW INSTALLATION | 10/5/21 | 10/14/21 | 11/9/21 | ||
| 36974 | Closed | 3 | COMS|PAINTING | R&D | 201 | N/A | Parking lot | I would like to submit a wr for repainting the par lot es at B-201. Poc p. x-. | 10/14- Prepped, pain per request. KM | NA | REPAIR | WEAR | 10/5/21 | 10/14/21 | 10/14/21 | |
| 36975 | Closed | 3 | COMS|PAINTING | R&D | 201 | N/A | I would like to submit a wr for repainting bs and fire hydrants at B-201. Poc p. x-. | 10/7- Prepped, primed and pain. KM | NA | REPAIR | WEAR | 10/5/21 | 10/14/21 | 10/7/21 | ||
| 36976 | Closed | 3 | COMS|MATERIAL HANDLING | CENTRAL | 300 | Loading Dock | I need a work order to have 2 pallets and 2 dumpster cs brought over to building 203 from 300 loading dock . is aware of what the items are.- POC x | 10/07- Comple per request. KM | NA | LOGISTICS-MOVE | MOVE | 10/5/21 | 10/14/21 | 10/7/21 | ||
| 36978 | Closed | 2 | COMS|SECURITY SYSTEMS | CENTRAL | 300 | 1 | Dispatch | Monitor C t to Blue screen, Can not get the tool bar or any cameras to go to the Monitor B-300 1 Disch POC CI2DB tc | 10/6 - Reprogmed work station. Complete. AMS | NA | PERFORMED | WEAR | 10/5/21 | 10/6/21 | 10/6/21 | |
| 36995 | Closed | 3 | COMS|FIRE SYSTEMS | CENTRAL | 319 | I would like to submit a work request for the foling: FAA Work Request (re: TSL-): while cning out old LD3 storage containers in the TSL, Facilities pernel loca 5 old fire extinguishers 2 - 5lb ABC and 3 - A water & air ure. Next e ISS fire folks are in the area could they pse come by the TSL and pick them up. Pse , Chase or (TSL-) Location: Building 319, Other If you have any questions (re: TSL-), pse contact at 609-650-, at 609-813-, or XXX at 609-813-. | 10/14- Comple per request. KM | NA | PERFORMED | PROB NOT FOUND | 10/5/21 | 10/14/21 | 10/14/21 | |||
| 36996 | Closed | 2 | COMS|HVACR | CENTRAL | 320 | 1 | PIV office | It is hot and humid and not air circulation in the PIV office in B-320 POC CI2CUP tc | 10/6 - ON 10/5 responded to call. Found coog setpoint set to 74 deg. ged to 71 deg. per requestor. On 10/6 checked with requestor. All OK at this e. Complete. AMS | NA | ADJUSTMENT | WEAR | 10/5/21 | 10/6/21 | 10/6/21 | |
| 37001 | Closed | 2 | COMS|ELECTRICAL (PWR) | CENTRAL | 320 | 1 | AFTER HOURS Recess lighting out POC tc | 10/6 - ged bad photo eye and re-ped as necessary. Complete. AMS | NA | REPLACED | WEAR | 10/6/21 | 10/7/21 | 10/6/21 | ||
| 37002 | Closed | 2 | COMS|SECURITY SYSTEMS | N/A | N/A | Gate 13 outbound | AFTER HOURS Gate 13 outbound sk open POC R tc | 10/6 - Cup Operator investiga and reset gate on overnight. It was wor again. The ANG has gates intentionally left open and md because of their n gate being inoperable. Complete. AMS | NA | PERFORMED | WEATHER | 10/6/21 | 10/7/21 | 10/7/21 | ||
| 37003 | Closed | 3 | COMS|EXCESS PROPERTY | CENTRAL | 300 | 3 | 3S323 | 300 3 L24 3W852 | Remove All Excess Property: Number of Assets: 27 EA POC: 5- P/U Location: 300 3 L24 3W852 Unrequired FAA peral property, reassigning, reutilizing and/or disposing of excess and surplus FAA peral property must be e using the Federal Aviation Administration FAA Reutilization and Disposition Process & procedure guide. All FAA Property on the WJHTC must go through this process with the final disposition location to the Property Disposal office loca in building #206. Building 206 is open for receiving excess property Tuess and Thurss! AITS/USD Ref# 0/1, 0/2 | 10/08- Comple per request. KM | NA | LOGISTICS-MOVE | MOVE | 10/6/21 | 10/15/21 | 10/8/21 |
| 37004 | Closed | 2 | COMS|HVACR | R&D | 287 | 1 | Stairwell | We have a unit heater in the first floor stairwell of building 287. Pse disch an HVAC or plum tech to investigate POC CI2DB tc | 10/6 - Replaced hose cap to drain on unit heater and tightened boiler drain handle. Complete. AMS | ADJUSTMENT | WEAR | 10/6/21 | 10/7/21 | 10/6/21 | ||
| 37005 | Closed | 2 | COMS|ELECTRICAL (PWR) | CENTRAL | 300 | 1 | Electrical closet 1-1 | Request a fan for to at B300, 1st floor , Col G7, Eleccal closet 1-1. Too hot. . - POC x, (609) 402-- CI2DB | 10/6 - Exhaust fan is bad. Turned over to eleccs to address. Room has door open and cool air co from adjacent space. Temp is at this e. Elecc determined fan motor is bad. Ordered replacement motor. Esa completion is 10/15 until update received from vendor. AMS 10/13 - Motor is discontinued. Ordered replacement fan and motor. Esa completion is 10/22. AMS 10/19- Installed new fan. KM | NA | REPLACED | EQUIP FAILURE | 10/6/21 | 10/22/21 | 10/19/21 | |
| 37006 | Closed | 3 | COMS|MATERIAL HANDLING | CENTRAL | 300 | 1 | Column M-35 old library, near auditorium | FROM 305 LOADING DOCK LOC 300 1 M35 LS703 (Old Library, near Auditorium) NAME: T P: 5- 2 SK tc | 10/08- Comple per request. KM | NA | LOGISTICS-MOVE | MOVE | 10/6/21 | 10/15/21 | 10/8/21 | |
| 37007 | Closed | 3 | COMS|HVACR | N/A | N/A | Both are located on the FAA Ramp Wash Rack. | The FAA has a heater/air conditioner used by their B727 "R & D 40". Both are loca on the FAA p Wash Rack. On inspection found unit totally inoperative. Found a fuse bn. Replaced fuse. AC works but no heat. Found an overtemperature sensor srely coded and falg ap. We would like for you to troubleshoot and repair. The unit I beli was purchased from Sunbelt Rentals. It is a e Mo #TSC120F4R0A0. Serial #9L. The unit is a 480 VAC 3 ph. It has its own disconnect on the power els next to the trailer ed UAS-CMD1. Building 325 is in ft of the aircraft. POC 856-404- tc | 10/8 - Investigate unit and found heater element bad. Ordered new unit. Esa 6-8 weeks ivery. Esa completion is 12/1. AMS 10/26 No update on ETA. AMS 11/9 - Replacement heater section received. Replaced and ged fuses. tes unit. Complete. AMS | NA | REPLACED | EQUIP FAILURE | 10/6/21 | 10/15/21 | 11/9/21 | ||
| 37008 | Closed | 3 | COMS|PAINTING | AOA | 158 | N/A | Parking lot of K-9 Buildings 158 & 157 | I would like to generate a work request to have the bollards repain (safety yel) at K-9 building 158 and 157. I beli there are is a total of 8. This is a routine request and need to be e on any Mon as it is our shut down for routine ntenance. POC 609-664- tc | 10/12- this work has to be scheduled on a ntenance Mon. Pning for 10/18 weather dependent with a target of 10/19 if weather is acceptable. KM 10/18- Spoke with bb, this work is rescheduled to 10/25. KM 10/25- Prepped, primed and pain per request. KM | NA | REPAIR | WEAR | 10/6/21 | 10/15/21 | 10/25/21 | |
| 37009 | Closed | 2 | COMS|LOCKSMITH | CENTRAL | 315 | 1 | The door is not closing, and it is a secured area from the Aum going into the Office area. - POC Security (609) 813--CI2DB | 10/7 - Adjus sker and tes reader. Complete. AMS | NA | ADJUSTMENT | WEAR | 10/6/21 | 10/7/21 | 10/7/21 | ||
| 37011 | Closed | 3 | COMS|MATERIAL HANDLING | WEST | 270A | N/A | Pse remove pallets on the surrounding area of bldg. 270A. POC 787-667- tc | 10/07- Comple per request. KM | NA | LOGISTICS-MOVE | MOVE | 10/6/21 | 10/15/21 | 10/7/21 | ||
| 37012 | Closed | 3 | COMS|CAN INTERIOR EXTERIOR | AOA | 311D | Repair the T-11 wall and make it weather proof. The area in need of repair is loca by the entry way of Bldg. 311D. The T-11 has separa from the fe and exposing the inside of the shed to the outside elements. | 10/14 - craftsper to cont site visit and determine maal list - target date to be provided thereafter - daj 10/15- Repaired wall. KM | NA | REPAIR | WEAR | 10/6/21 | 10/15/21 | 10/15/21 | |||
| 37013 | Closed | 2 | COMS|LOCKSMITH | CENTRAL | 300 | 3 | 3W869 | COl K22 | Locked out of office at B300, 3rd floor, Col K22, 3W869, and cipher lock battery is dead. -POC (609) 513-- CI2DB | 10/7 - On 10/6 removed and replaced battery pack. Cred battery alarm. Complete. AMS | NA | REPLACED | WEAR | 10/6/21 | 10/7/21 | 10/7/21 |
| 37014 | Closed | 3 | COMS|CAN INTERIOR EXTERIOR | AOA | 311B | Provide and install a sign to read: PUMP HOUSE then install the sign by the ft door of Bldg. 311B Pump House. The POC for this request is Adkis, x | 10/14 - site visit to obtain measurements and maal - target date to be upda when ps are ordered - daj 10/19- Signs are ordered. Targeting 11/01 pending arrival. KM 10/27- Installed sign. KM | NA | INSTALLATION | NEW INSTALLATION | 10/6/21 | 10/15/21 | 10/27/21 | |||
| 37015 | Closed | 3 | COMS|CAN INTERIOR EXTERIOR | AOA | 311B | Provide and install a sign to read: SHED. Then install the sign under the bldg. sign that reads "311B". The POC for this request is Adkis, x. | 10/14 - site visit to obtain measurements and maal - target date to be upda when ps are ordered - daj 10/19- Signs are ordered. Targeting 11/01 pending arrival. KM 10/27- Installed sign. KM | NA | INSTALLATION | NEW INSTALLATION | 10/6/21 | 10/15/21 | 10/27/21 | |||
| 37016 | Closed | 2 | COMS|PEST CONTROL | CENTRAL | 351 | 1 | EM shop | We have a cet is in the USCG EM shop of bldg. 351. POC 609-204- CI2DB tc | 10/7 - On 10/6 trea all areas for cets and set glue boards in all corners and rooms. Complete. AMS | NA | PERFORMED | WEAR | 10/6/21 | 10/7/21 | 10/7/21 | |
| 37017 | Closed | 2 | COMS|SECURITY SYSTEMS | CENTRAL | 301 | AOA Gate #3 | B301 AOA Gate #3 intercom is not wor- POC x- CI2DB | 10 6 - Plem with the speakerp is the p wire from B301 to B300. Ext. # is . I relayed the information to the p group. Complete. AMS | NO REPAIR NEEDED | EQUIP FAILURE | 10/6/21 | 10/7/21 | 10/6/21 | |||
| 37019 | Closed | 3 | COMS|MATERIAL HANDLING | CENTRAL | 305 | 1 | TSF Loading dock | Pse pick up 1 skid of supplies from bldg.305 TSF loading dock and iver it to bldg.300 1stfl.col. F-8 X Cell 609 703- POC tc | 10/08- Comple per request. KM | NA | LOGISTICS-MOVE | MOVE | 10/6/21 | 10/15/21 | 10/8/21 | |
| 37022 | Closed | 3 | COMS | CENTRAL | 300 | 2 | Column D-26 | Pse pick up two large en boxes and pallet from B-300 2 D-26 and take them to B-305 1 TSF loading dock POC 609-230- tc | 10/15- Comple per request. KM | NA | 10/6/21 | 10/15/21 | 10/15/21 | |||
| 37023 | Closed | 3 | COMS|MATERIAL HANDLING | CENTRAL | 301 | Room 305 | From 305 Loc 301 Rm 305 Name es P 1 pallet tc | 10/08- Comple per request. KM | NA | LOGISTICS-MOVE | MOVE | 10/6/21 | 10/15/21 | 10/8/21 | ||
| 37029 | Closed | 2 | COMS|TEMP CUP | CENTRAL | 316 | 2 | 2N704 | middle of columns I-8.3, I-6, J-6 and J9. | Pse adjust temperature. my cube at the tech center, 2N704, north side of building 316, 2nd floor is cold. Can we get the heat turned up? Some of the therats in the area are reading 64 degrees. My cube is in the middle of ns I-8.3, I-6, J-6 and J9. - POC x- CI2DB | 10/8 - On 10/7 Adjus Therats. Complete. | ADJUSTMENT | WEAR | 10/7/21 | 10/8/21 | 10/8/21 | |
| 37030 | Closed | 2 | COMS|PEST CONTROL | CENTRAL | 315 | Annex- Small Bulk Lab | I would like to submit a work request for the foling: FAA Work Request (re: TSL-): It has been repor to me from the onsite itorial staff that we have a few skunks living underneath the Building 315 x - Small Bulk Lab. Pse set a trap to capture and remove from the TSL Complex. (TSL-) Location: Building 315, 315 x If you have any questions (re: TSL-), pse contact at 609-650-, at 609-813-, or XXX at 609-813-.- CI2DB | 10/8 - Trap being set and monitored for activity again. take a couple weeks to catch any and all skunks. Esa completion is 10/22. AMS 10/18- Set trap on 10/7, removed on 10/8, reset on 10/12. Inspec daily 10/13-15. Removed on 10/15, no animal caught. KM | NA | PERFORMED | PROB NOT FOUND | 10/7/21 | 10/22/21 | 10/18/21 | ||
| 37031 | Closed | 2 | COMS|PLUMBING | CENTRAL | 306 | Pse tighten the faucet in the men's bathroom in the utility shop. Boyer aware, no need to call out. | 10/ 8 - Checked faucet. It is old and coded at mounting nuts. Unable to tighten. Ordered new faucet. Esa completion is 10/15. AMS 10/13 - On 10/12 removed old faucet and installed new. Complete. AMS | NA | REPLACED | OLD | 10/7/21 | 10/15/21 | 10/13/21 | |||
| 37032 | Closed | 2 | COMS|FIRE SYSTEMS | CENTRAL | 300 | 2 | Column B-18 | Trouble alarm Node 18 L1S064 and are aware POC tc | 10/7 - Responded to call. Checked detector, trouble had restored by arrival. el is normal. Complete. AMS | NA | NO REPAIR NEEDED | PROB NOT FOUND | 10/7/21 | 10/8/21 | 10/7/21 | |
| 37033 | Closed | 3 | COMS|LOCKSMITH | N/A | N/A | Pse submit a work request to the lock for the creation and record of the attached referenced key. Also, pse print and attach the request form to the work order. POC upon completion. | 10/12- Cut key, sd and ivered to POC. Logged in software. KM | NA | REPAIR | PROB NOT FOUND | 10/7/21 | 10/18/21 | 10/12/21 | |||
| 37034 | Closed | 2 | COMS|SECURITY SYSTEMS | AOA | 158 | Card reader #209 | After Hours- B158 card reader #209 - Security getting code forced door West ence on P system- POC Security x | 10/8 - Investiga plem. door secure. We are wor with FAA to cr or reset the Pegasus system. Esa completion is 10/15. AMS 10/13 - On 10/12 plem resolved itself after weed power outage restoration. Complete. AMS | NA | PERFORMED | EQUIP FAILURE | 10/7/21 | 10/15/21 | 10/13/21 | ||
| 37035 | Closed | 2 | COMS|PLUMBING | R&D | 292 | After Hours- B292 /running urinal- POC x | 10/7 - Cned out flushometer. Complete. AMS | NA | CLEANING | WEAR | 10/7/21 | 10/8/21 | 10/7/21 | |||
| 37036 | Closed | 2 | COMS|ELECTRICAL (PWR) | CENTRAL | 318 | TSL Gen Rm. | After Hours- B318 TSL Gen. Rm. POR for Exh. Fan on BAS- POC x | 10/8 - Troubleshot unit. Found it needed to be reprogmed. Complete. AMS | ADJUSTMENT | WEAR | 10/7/21 | 10/8/21 | 10/8/21 | |||
| 37037 | Closed | 2 | COMS|PEST CONTROL | R&D | 206 | back office area | Pest Control - There is a dead mouse in 206 back office area.- POC x- CI2DB | 10/7 - Removed trap with dead mouse and set new trap. Complete. AMS | NA | PERFORMED | WEAR | 10/7/21 | 10/8/21 | 10/7/21 | ||
| 37041 | Closed | 3 | COMS|ROADS | R&D | 206 | N/A | Request to have the 30 yard t dumpster packed down at building 206.- POC x | 10/08- Comple per request. KM | NA | PERFORMED | PROB NOT FOUND | 10/7/21 | 10/18/21 | 10/8/21 | ||
| 37042 | Closed | 2 | COMS|PLUMBING | R&D | 208 | 1 | Pse repair the k on the Extrol k. aware, no need to call out. | 10/7 - Replaced pipe and valve to k. Complete. AMS | NA | REPLACED | OLD | 10/7/21 | 10/8/21 | 10/7/21 | ||
| 37043 | Closed | 2 | COMS|PLUMBING | WEST | 270 | 1 | Pse fix the n on the kit drain. aware, no need to call out. | 10/8 - On 10/7 unclogged drain and tightened trap nuts. Complete. AMS | NA | REPAIR | WEAR | 10/7/21 | 10/8/21 | 10/8/21 | ||
| 37047 | Closed | 3 | COMS|ELECTRICAL (PWR) | CENTRAL | 362 | N/A | Main Sub transformer yard | Replace Hem bottle on 200 side Serve system. AL is aware | 10/7 - Installed new hem bottle on monitor. Complete. AMS | XFMROIL-0042 | PERFORMED | WEAR | 10/7/21 | 10/18/21 | 10/7/21 | |
| 37051 | Closed | 3 | COMS|MATERIAL HANDLING | R&D | 206 | 1 | Pse pick up 3 fans from B206 and bring to B316 for the outage. Ander is POC. | 10-10- - Comple per request. (wef) | NA | LOGISTICS-MOVE | MOVE | 10/7/21 | 10/18/21 | 10/10/21 | ||
| 37052 | Closed | 3 | COMS|PAINTING | CENTRAL | 300 | 1 | 1N292 | Pse submit a work order for the Paint Shop to paint two 20”x16” aluminum signs w on one side. They have the maal. POC x My location is B300 1N292 (metal shop). tc | 10/12- Prepped, primed, and pain. KM | NA | REPAIR | WEAR | 10/7/21 | 10/18/21 | 10/12/21 | |
| 37053 | Closed | 3 | COMS|MATERIAL HANDLING | CENTRAL | 306 | Pse sport 33 fans and 3 AC units from 308 to the B300 loading dock. iver to locations as they are tagged. | 10-10- - Comple per request. (wef) | NA | LOGISTICS-MOVE | MOVE | 10/7/21 | 10/18/21 | 10/10/21 | |||
| 37054 | Closed | 2 | COMS|PEST CONTROL | CENTRAL | 300 | ROOF | Pse remove a wasp nest on the roof near Sub C. aware of location, no need to call out. | 10/7 - Trea wasp nest on roof near sub-c. Knocked down rens of nest as well. Complete. AMS | NA | PERFORMED | WEAR | 10/7/21 | 10/8/21 | 10/7/21 | ||
| 37055 | Closed | 2 | COMS|ELECTRICAL (LTG) | CENTRAL | 300 | Stairwell #3 between 1 and 2 floor | The light is out on the fixture and the fixture is ma noise B-300 Stairwell #3 between floors 1 & 2 POC CI2CUP tc | 10/8 - ged lights in stairwell. Used (6) F32T8CW tubes. Complete. AMSW | NA | REPLACED | WEAR | 10/7/21 | 10/8/21 | 10/8/21 | ||
| 37056 | Closed | 3 | COMS|MATERIAL HANDLING | WEST | 270 | From 305 Loc 270 Name P 2 cases & 2 boxes tc | 10/08- Comple per request. KM | NA | LOGISTICS-MOVE | MOVE | 10/7/21 | 10/18/21 | 10/8/21 | |||
| 37057 | Closed | 3 | COMS|MATERIAL HANDLING | CENTRAL | 301 | Room 305 | From 305 Loc 301 rm 305 Name P 5 fedex g. boxes | 10-10- - Comple per request. (wef) | LOGISTICS-MOVE | MOVE | 10/7/21 | 10/18/21 | 10/10/21 | |||
| 37058 | Closed | 3 | COMS|MATERIAL HANDLING | CENTRAL | 300 | 2 | Col E27 | From 305 Loc 300 2 e 27 Name P 5 Suno boxes | 10-10- - Comple per request. (wef) | LOGISTICS-MOVE | MOVE | 10/7/21 | 10/18/21 | 10/10/21 |