Attachment D7_ Drawings 7 of 12.pdf

PDF 19 MB Posted

Attached to
Z2DZ--644-20-201 EHRM Phoenix Construction Federal contract opportunity
Solicitation number
36C26221B0007_1
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 22

About this file

This document provides details for a federal solicitation seeking construction services. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 22 is soliciting bids for Project 644-20-201, "Electronic Health Records Modernization (EHRM) Infrastructure Upgrades" at the VA Phoenix Healthcare System located in Phoenix, Arizona. The project scope includes general construction, alterations, mechanical and electrical work, utility systems, necessary demolition and removal of existing structures. The magnitude of this construction project is estimated between $10,000,000 to $20,000,000. This procurement is set aside only for Service-Disabled Veteran-Owned Small Businesses listed in the Vendor Information Pages database. An Invitation for Bid will be issued on June 3, 2021 via sam.gov. A site visit will also be scheduled. Interested parties should contact the named contracting specialist for any additional details.

View the file

Other files for this federal contract opportunity

Show all 20

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

STOR

D627B

ABAN TR

D627A

TOILET

D612B

OFFICE

PROVIDER

D627

ROOM

C603D

SIGNAL

C611

ABAN TR

C612

TOILET

C622B

TOILET

STORAGE FILES

D639

TR ELEC

TRS-600C

TR

TRS-600A

CLOSET

TR MECH

TRS-600B

WAITING

C6D-11

25 2726

F1

01-EP402

F1

01-EL402

1 7 11 20 2117 18 18.6

G

L

A

S

R

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans

Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMP

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

644-20-201

Revisions: Date:

TL 602.606.7432

Phoenix, AZ 85012

3300 N. Central Ave, STE 1520 www.dheengineering.com

Job Number: 00961.00

Concourse Federal Group 123 S. Royal Street Alexander, VA 22314

PLAN KEY

N

04.01.2021 JLZG

A

R I Z O N A U

S

A

Re g st e r ed

E R

IT

I

D a t

S e d

C

A T E N

O e i gn _ _ _ _ _ _ _ _ _

F C

Expires 03-31-2024 i Pr o ession f al Engneer i

ZACHARY

GOLDSWORTHY

(E l c t rica e l)

72942

04 01

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

PVAHCS - Carl T Hayden Medical Center

650 E Indian School Road Phoenix AZ 85012

ELECTRICAL POWER PLAN -

6TH FLOOR

01-E106

10 10 20 30 40 50 60

3/64" = 1'-0"

FEETSCALE

04.28.202105.26.2021 SHEET 167 of 421

05.26.2021 SHEET 168 of 421

ABAN TR

D01B

PUMP ROOM

TR

TRS-000A

TR MECH

TRS-000B

TR ELEC

TRS-000C

OS

OS

AA

A A

ET1HB-1 NT1HB-1

OS

A

A

TR

TRS-100A

TOILET

E102

TOILET

E103

TR ELEC

TRS-100C

OFFICE

D102

TR MECH

TRS-100B

CLEAN INTILITY

C116

OS

OS

A A

A

NT1H1-1 ET1H1-1

A

OS

TR

TRS-200A

TR MECH

TRS-200B

ABAN TR

2CD8A

TR ELEC

TRS-200C

OS

OS

A A

A A

A

NT1H2-1 ET1H2-1

A

OS

TOILET

D338

TR

TRS-300A

TR-ELEC

TRS-300C

TR MECH

TRS-300B

OS

OS

A A

A A

A

NT1H3-1 ET1H3-1

A

OS

LIGHTING NOTES:

1. UNLESS OTHERWISE NOTED, COORDINATE EXACT

MOUNTING HEIGHTS OF ALL DEVICES WITH ARCHITECTURAL

INTERIOR ELEVATIONS.

2. WHERE OCCUPANCY SENSORS ARE DEPICTED, PROVIDE

AND INSTALL POWER TO LOCAL ROOM LIGHTING THROUGH

DEVICE PER ASSOCIATED INSTALLATION DETAIL.

3. ALL NEW LIGHT FIXTURES TO BE MOUNTED 8' A.F.F.

LIGHTING KEY NOTES:

NOT USED.

XX

XX

LIGHTING NOTES:

1. UNLESS OTHERWISE NOTED, COORDINATE EXACT

MOUNTING HEIGHTS OF ALL DEVICES WITH ARCHITECTURAL

INTERIOR ELEVATIONS.

2. WHERE OCCUPANCY SENSORS ARE DEPICTED, PROVIDE

AND INSTALL POWER TO LOCAL ROOM LIGHTING THROUGH

DEVICE PER ASSOCIATED INSTALLATION DETAIL.

3. ALL NEW LIGHT FIXTURES TO BE MOUNTED 8' A.F.F.

LIGHTING KEY NOTES:

NOT USED.

XX

XX

LIGHTING NOTES:

1. UNLESS OTHERWISE NOTED, COORDINATE EXACT

MOUNTING HEIGHTS OF ALL DEVICES WITH ARCHITECTURAL

INTERIOR ELEVATIONS.

2. WHERE OCCUPANCY SENSORS ARE DEPICTED, PROVIDE

AND INSTALL POWER TO LOCAL ROOM LIGHTING THROUGH

DEVICE PER ASSOCIATED INSTALLATION DETAIL.

3. ALL NEW LIGHT FIXTURES TO BE MOUNTED 8' A.F.F.

LIGHTING KEY NOTES:

NOT USED.

XX

XX

LIGHTING NOTES:

1. UNLESS OTHERWISE NOTED, COORDINATE EXACT

MOUNTING HEIGHTS OF ALL DEVICES WITH ARCHITECTURAL

INTERIOR ELEVATIONS.

2. WHERE OCCUPANCY SENSORS ARE DEPICTED, PROVIDE

AND INSTALL POWER TO LOCAL ROOM LIGHTING THROUGH

DEVICE PER ASSOCIATED INSTALLATION DETAIL.

3. ALL NEW LIGHT FIXTURES TO BE MOUNTED 8' A.F.F.

LIGHTING KEY NOTES:

NOT USED.

XX

XX

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans

Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMP

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

644-20-201

Revisions: Date:

TL 602.606.7432

Phoenix, AZ 85012

3300 N. Central Ave, STE 1520 www.dheengineering.com

Job Number: 00961.00

Concourse Federal Group 123 S. Royal Street Alexander, VA 22314

PLAN KEY

N

04.01.2021 JLZG

A

R I Z O N A U

S

A

Re g st e r ed

E R

IT

I

D a t

S e d

C

A T E N

O e i gn _ _ _ _ _ _ _ _ _

F C

Expires 03-31-2024 i Pr o ession f al Engneer i

ZACHARY

GOLDSWORTHY

(E l c t rica e l)

72942

04 01

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

PVAHCS - Carl T Hayden Medical Center

650 E Indian School Road Phoenix AZ 85012

01-EL401

C1 ELECTRICAL LIGHTING PLAN - BASEMENT

1/4" = 1'-0" C5 ELECTRICAL LIGHTING PLAN - 1ST FLOOR

1/4" = 1'-0"

F1 ELECTRICAL LIGHTING PLAN - 2ND FLOOR

1/4" = 1'-0" F5 ELECTRICAL LIGHTING PLAN - 3RD FLOOR

1/4" = 1'-0"

ENLARGED ELECTRICAL LIGHTING

PLANS SOUTH TR TOWER

04.28.202105.26.2021 SHEET 169 of 421

D456

TR ELEC

TRS-400C

TR

TRS-400A

TR MECH

TRS-400B

OS

OS

A A

A A

A

NT1H4-1 ET1H4-1

A

OS

TR

TRS-500A

TR MECH

TRS-500B

TR- ELEC

TRS-500C

CLOSET

D539A

OFFICE

D540A

OS

OS

A A

A A

A

NT1H5-1 ET1H5-1

A

OS

STORAGE FILES

D639

TR ELEC

TRS-600C

TR

TRS-600A

CLOSET

TR MECH

TRS-600B

OS

OS

A A

A A

A

NT1H6-1 ET1H6-1

A

CLOSET

D539E

SHAFT

LIGHTING NOTES:

1. UNLESS OTHERWISE NOTED, COORDINATE EXACT

MOUNTING HEIGHTS OF ALL DEVICES WITH ARCHITECTURAL

INTERIOR ELEVATIONS.

2. WHERE OCCUPANCY SENSORS ARE DEPICTED, PROVIDE

AND INSTALL POWER TO LOCAL ROOM LIGHTING THROUGH

DEVICE PER ASSOCIATED INSTALLATION DETAIL.

3. ALL NEW LIGHT FIXTURES TO BE MOUNTED 8' A.F.F.

LIGHTING KEY NOTES:

NOT USED.

XX

XX

LIGHTING NOTES:

1. UNLESS OTHERWISE NOTED, COORDINATE EXACT

MOUNTING HEIGHTS OF ALL DEVICES WITH ARCHITECTURAL

INTERIOR ELEVATIONS.

2. WHERE OCCUPANCY SENSORS ARE DEPICTED, PROVIDE

AND INSTALL POWER TO LOCAL ROOM LIGHTING THROUGH

DEVICE PER ASSOCIATED INSTALLATION DETAIL.

3. ALL NEW LIGHT FIXTURES TO BE MOUNTED 8' A.F.F.

LIGHTING KEY NOTES:

NOT USED.

XX

XX

LIGHTING NOTES:

1. UNLESS OTHERWISE NOTED, COORDINATE EXACT

MOUNTING HEIGHTS OF ALL DEVICES WITH ARCHITECTURAL

INTERIOR ELEVATIONS.

2. WHERE OCCUPANCY SENSORS ARE DEPICTED, PROVIDE

AND INSTALL POWER TO LOCAL ROOM LIGHTING THROUGH

DEVICE PER ASSOCIATED INSTALLATION DETAIL.

3. ALL NEW LIGHT FIXTURES TO BE MOUNTED 8' A.F.F.

LIGHTING KEY NOTES:

NOT USED.

XX

XX

LIGHTING NOTES:

1. UNLESS OTHERWISE NOTED, COORDINATE EXACT

MOUNTING HEIGHTS OF ALL DEVICES WITH ARCHITECTURAL

INTERIOR ELEVATIONS.

2. WHERE OCCUPANCY SENSORS ARE DEPICTED, PROVIDE

AND INSTALL POWER TO LOCAL ROOM LIGHTING THROUGH

DEVICE PER ASSOCIATED INSTALLATION DETAIL.

3. ALL NEW LIGHT FIXTURES TO BE MOUNTED 8' A.F.F.

LIGHTING KEY NOTES:

NOT USED.

XX

XX

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans

Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMP

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

644-20-201

Revisions: Date:

TL 602.606.7432

Phoenix, AZ 85012

3300 N. Central Ave, STE 1520 www.dheengineering.com

Job Number: 00961.00

Concourse Federal Group 123 S. Royal Street Alexander, VA 22314

PLAN KEY

N

04.01.2021 JLZG

A

R I Z O N A U

S

A

Re g st e r ed

E R

IT

I

D a t

S e d

C

A T E N

O e i gn _ _ _ _ _ _ _ _ _

F C

Expires 03-31-2024 i Pr o ession f al Engneer i

ZACHARY

GOLDSWORTHY

(E l c t rica e l)

72942

04 01

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

PVAHCS - Carl T Hayden Medical Center

650 E Indian School Road Phoenix AZ 85012

01-EL402

C1 ELECTRICAL LIGHTING PLAN - 4TH FLOOR

1/4" = 1'-0" C5 ELECTRICAL LIGHTING PLAN - 5TH FLOOR

1/4" = 1'-0"

F1 ELECTRICAL LIGHTING PLAN - 6TH FLOOR

1/4" = 1'-0" F5 ELECTRICAL LIGHTING PLAN - 7TH FLOOR

1/4" = 1'-0"

ENLARGED ELECTRICAL LIGHTING

PLANS SOUTH TR TOWER

04.28.202105.26.2021 SHEET 170 of 421

TR

TRN-200A

TR ELEC

TRN-200C TR MECH

TRN-200B

OS OS

AA

AA

A

ET2H2-1

NT2H2-1

A

A A

OS

TR

TRN-300A

TR MECH

TRN-300BTR ELEC

TRN-300V

ET2H3-1

NT2H3-1

OS OS

AA

AA

A

A

A A

OS

TR

TRN-400A

TR MECH

TRN-400B

TR ELEC

TRN-400C

ET2H4-1

NT2H4-1

OS OS

AA

AA

A

A

A A

OS

PUMP HOUSE 1

A

OS

LIGHTING NOTES:

1. UNLESS OTHERWISE NOTED, COORDINATE EXACT

MOUNTING HEIGHTS OF ALL DEVICES WITH ARCHITECTURAL

INTERIOR ELEVATIONS.

2. WHERE OCCUPANCY SENSORS ARE DEPICTED, PROVIDE

AND INSTALL POWER TO LOCAL ROOM LIGHTING THROUGH

DEVICE PER ASSOCIATED INSTALLATION DETAIL.

3. ALL NEW LIGHT FIXTURES TO BE MOUNTED 8' A.F.F.

LIGHTING KEY NOTES:

NOT USED.

XX

XX

LIGHTING NOTES:

1. UNLESS OTHERWISE NOTED, COORDINATE EXACT

MOUNTING HEIGHTS OF ALL DEVICES WITH ARCHITECTURAL

INTERIOR ELEVATIONS.

2. WHERE OCCUPANCY SENSORS ARE DEPICTED, PROVIDE

AND INSTALL POWER TO LOCAL ROOM LIGHTING THROUGH

DEVICE PER ASSOCIATED INSTALLATION DETAIL.

3. ALL NEW LIGHT FIXTURES TO BE MOUNTED 8' A.F.F.

LIGHTING KEY NOTES:

NOT USED.

XX

XX

LIGHTING NOTES:

1. UNLESS OTHERWISE NOTED, COORDINATE EXACT

MOUNTING HEIGHTS OF ALL DEVICES WITH ARCHITECTURAL

INTERIOR ELEVATIONS.

2. WHERE OCCUPANCY SENSORS ARE DEPICTED, PROVIDE

AND INSTALL POWER TO LOCAL ROOM LIGHTING THROUGH

DEVICE PER ASSOCIATED INSTALLATION DETAIL.

3. ALL NEW LIGHT FIXTURES TO BE MOUNTED 8' A.F.F.

LIGHTING KEY NOTES:

NOT USED.

XX

XX

LIGHTING NOTES:

1. UNLESS OTHERWISE NOTED, COORDINATE EXACT

MOUNTING HEIGHTS OF ALL DEVICES WITH ARCHITECTURAL

INTERIOR ELEVATIONS.

2. WHERE OCCUPANCY SENSORS ARE DEPICTED, PROVIDE

AND INSTALL POWER TO LOCAL ROOM LIGHTING THROUGH

DEVICE PER ASSOCIATED INSTALLATION DETAIL.

3. ALL NEW LIGHT FIXTURES TO BE MOUNTED 8' A.F.F.

LIGHTING KEY NOTES:

CONNECT NEW LIGHT FIXTURE TO EXISTING POWER IN AREA

FEEDING EXISTING LIGHT FIXTURES.

XX

XX

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans

Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMP

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

644-20-201

Revisions: Date:

TL 602.606.7432

Phoenix, AZ 85012

3300 N. Central Ave, STE 1520 www.dheengineering.com

Job Number: 00961.00

Concourse Federal Group 123 S. Royal Street Alexander, VA 22314

PLAN KEY

N

04.01.2021 JLZG

A

R I Z O N A U

S

A

Re g st e r ed

E R

IT

I

D a t

S e d

C

A T E N

O e i gn _ _ _ _ _ _ _ _ _

F C

Expires 03-31-2024 i Pr o ession f al Engneer i

ZACHARY

GOLDSWORTHY

(E l c t rica e l)

72942

04 01

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

PVAHCS - Carl T Hayden Medical Center

650 E Indian School Road Phoenix AZ 85012

01-EL403

C1 ELECTRICAL LIGHTING PLAN - 2ND FLOOR

1/4" = 1'-0"

C6 ELECTRICAL LIGHTING PLAN - 3RD FLOOR

1/4" = 1'-0"

F6 ELECTRICAL LIGHTING PLAN - 5TH FLOOR

1/4" = 1'-0"F1 ELECTRICAL LIGHTING PLAN - 4TH FLOOR

1/4" = 1'-0"

ENLARGED ELECTRICAL LIGHTING

PLANS NORTH TR TOWER

04.28.202105.26.2021 SHEET 171 of 421

1321A

ALCOVE

1321B

STAIR

VENDING

SEATING

HRS

LIGHTING NOTES:

1. UNLESS OTHERWISE NOTED, COORDINATE EXACT

MOUNTING HEIGHTS OF ALL DEVICES WITH ARCHITECTURAL

INTERIOR ELEVATIONS.

2. PROVIDE MINIMUM 1100 LUMEN EMERGENCY BATTERY

PACKS IN ALL FIXTURES NOTED AS EMERGENCY. PROVIDE

WITH UNSWITCHED SENSING/CHARGING CIRCUIT PER

DETAIL SHEET.

3. PROVIDE AND INSTALL POWER TO EXIT SIGNS FROM LOCAL

ROOM LIGHTING BRANCH CIRCUIT AHEAD OF SWITCHING.

4. PROVIDE AND INSTALL POWER TO NIGHT LIGHTS (NL) FROM

LOCAL ROOM LIGHTING BRANCH CIRCUIT AHEAD OF

SWITCHING.

5. WHERE OCCUPANCY SENSORS ARE DEPICTED, PROVIDE

AND INSTALL POWER TO LOCAL ROOM LIGHTING THROUGH

DEVICE PER ASSOCIATED INSTALLATION DETAIL.

LIGHTING KEY NOTES:

XXXXXX1

LIGHTING NOTES:

1. UNLESS OTHERWISE NOTED, COORDINATE EXACT

MOUNTING HEIGHTS OF ALL DEVICES WITH ARCHITECTURAL

INTERIOR ELEVATIONS.

2. PROVIDE MINIMUM 1100 LUMEN EMERGENCY BATTERY

PACKS IN ALL FIXTURES NOTED AS EMERGENCY. PROVIDE

WITH UNSWITCHED SENSING/CHARGING CIRCUIT PER

DETAIL SHEET.

3. PROVIDE AND INSTALL POWER TO EXIT SIGNS FROM LOCAL

ROOM LIGHTING BRANCH CIRCUIT AHEAD OF SWITCHING.

4. PROVIDE AND INSTALL POWER TO NIGHT LIGHTS (NL) FROM

LOCAL ROOM LIGHTING BRANCH CIRCUIT AHEAD OF

SWITCHING.

5. WHERE OCCUPANCY SENSORS ARE DEPICTED, PROVIDE

AND INSTALL POWER TO LOCAL ROOM LIGHTING THROUGH

DEVICE PER ASSOCIATED INSTALLATION DETAIL.

LIGHTING KEY NOTES:

EXISTING LIGHT FIXTURES IN ROOM TO REMAIN.1

TR 105

HKC

1150A

OFFICE

1153C

OFFICE

STAIR

ABAN TR

MEN

1219B

WOMEN

1229A

BREAK ROOM

PHYS

PSYCH/PSYCH

ASSISTANT

PROG ASSIST

TR

1221A

OFFICE

CORRIDOR

LIGHTING NOTES:

1. UNLESS OTHERWISE NOTED, COORDINATE EXACT

MOUNTING HEIGHTS OF ALL DEVICES WITH ARCHITECTURAL

INTERIOR ELEVATIONS.

2. PROVIDE MINIMUM 1100 LUMEN EMERGENCY BATTERY

PACKS IN ALL FIXTURES NOTED AS EMERGENCY. PROVIDE

WITH UNSWITCHED SENSING/CHARGING CIRCUIT PER

DETAIL SHEET.

3. PROVIDE AND INSTALL POWER TO EXIT SIGNS FROM LOCAL

ROOM LIGHTING BRANCH CIRCUIT AHEAD OF SWITCHING.

4. PROVIDE AND INSTALL POWER TO NIGHT LIGHTS (NL) FROM

LOCAL ROOM LIGHTING BRANCH CIRCUIT AHEAD OF

SWITCHING.

5. WHERE OCCUPANCY SENSORS ARE DEPICTED, PROVIDE

AND INSTALL POWER TO LOCAL ROOM LIGHTING THROUGH

DEVICE PER ASSOCIATED INSTALLATION DETAIL.

LIGHTING KEY NOTES:

EXISTING LIGHT FIXTURES IN ROOM TO REMAIN.1

LIGHTING NOTES:

1. UNLESS OTHERWISE NOTED, COORDINATE EXACT

MOUNTING HEIGHTS OF ALL DEVICES WITH ARCHITECTURAL

INTERIOR ELEVATIONS.

2. PROVIDE MINIMUM 1100 LUMEN EMERGENCY BATTERY

PACKS IN ALL FIXTURES NOTED AS EMERGENCY. PROVIDE

WITH UNSWITCHED SENSING/CHARGING CIRCUIT PER

DETAIL SHEET.

3. PROVIDE AND INSTALL POWER TO EXIT SIGNS FROM LOCAL

ROOM LIGHTING BRANCH CIRCUIT AHEAD OF SWITCHING.

4. PROVIDE AND INSTALL POWER TO NIGHT LIGHTS (NL) FROM

LOCAL ROOM LIGHTING BRANCH CIRCUIT AHEAD OF

SWITCHING.

5. WHERE OCCUPANCY SENSORS ARE DEPICTED, PROVIDE

AND INSTALL POWER TO LOCAL ROOM LIGHTING THROUGH

DEVICE PER ASSOCIATED INSTALLATION DETAIL.

LIGHTING KEY NOTES:

DEMOLISH EXISTING LIGHT FIXTURES IN ROOM.

CONNECT NEW LIGHT FIXTURES TO EXISTING CIRCUIT IN AREA

MADE AVAILABLE FROM DEMOLITION.

OFFICE

D106I

CORRIDOR

C100H

TR

C185

P TOILET

C183

TRIAGE

C140

ED-XX

C139E

OFFICE

D106K

OFFICE

D106

G

18.6

G

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans

Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMP

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

644-20-201

Revisions: Date:

TL 602.606.7432

Phoenix, AZ 85012

3300 N. Central Ave, STE 1520 www.dheengineering.com

Job Number: 00961.00

Concourse Federal Group 123 S. Royal Street Alexander, VA 22314

PLAN KEY

N

04.01.2021 JLZG

A

R I Z O N A U

S

A

R eg st e r ed

E

R

IT

I

D a t

S e d

C

A T E N

O e i gn _ _ _ _ _ _ _ _ _

F C

Expires 03-31-2024 i Pr o ession f al Engneer i

ZACHARY

GOLDSWORTHY

(E l c t rica e l)

72942

04 01

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

PVAHCS - Carl T Hayden Medical Center

650 E Indian School Road Phoenix AZ 85012

ENLARGED ELECTRICAL LIGHTING

PLANS

01-EL404

2 2 4 6 8 10

1/4" = 1'-0"

FEETSCALE

C6 ELECTRICAL LIGHTING PLAN - ROOM 1151

1/4" = 1'-0"

F6 ELECTRICAL LIGHTING PLAN - ROOM 1221A

1/4" = 1'-0"F1 ELECTRICAL LIGHTING PLAN -ROOM C185

1/4" = 1'-0"

C1 ELECTRICAL LIGHTING PLAN - ROOM 1321A

1/4" = 1'-0"

04.28.202105.26.2021 SHEET 172 of 421

LIGHTING NOTES:

1. UNLESS OTHERWISE NOTED, COORDINATE EXACT

MOUNTING HEIGHTS OF ALL DEVICES WITH ARCHITECTURAL

INTERIOR ELEVATIONS.

2. PROVIDE MINIMUM 1100 LUMEN EMERGENCY BATTERY

PACKS IN ALL FIXTURES NOTED AS EMERGENCY. PROVIDE

WITH UNSWITCHED SENSING/CHARGING CIRCUIT PER

DETAIL SHEET.

3. PROVIDE AND INSTALL POWER TO EXIT SIGNS FROM LOCAL

ROOM LIGHTING BRANCH CIRCUIT AHEAD OF SWITCHING.

4. PROVIDE AND INSTALL POWER TO NIGHT LIGHTS (NL) FROM

LOCAL ROOM LIGHTING BRANCH CIRCUIT AHEAD OF

SWITCHING.

5. WHERE OCCUPANCY SENSORS ARE DEPICTED, PROVIDE

AND INSTALL POWER TO LOCAL ROOM LIGHTING THROUGH

DEVICE PER ASSOCIATED INSTALLATION DETAIL.

LIGHTING KEY NOTES:

CONNECT NEW LIGHT FIXTURE TO EXISTING CIRCUIT PREVIOUSLY

FEEDING DEMOLISHED FIXTURE IN AREA.

TR

K132

BREAK

ROOM

K134

TLT

K131A

2 BED

K131

2 BED

K129

TLT

K129A

HKC

K128

A

TR

K132

BREAK

ROOM

K134

TLT

K131A

2 BED

K131

2 BED

K129

TLT

K129A

HKC

K128 1

LIGHTING DEMOLITION GENERAL NOTES:

1. WHERE DEVICES ARE SHOWN TO BE DEMOLISHED IN WALLS

THAT ARE SHOWN TO REMAIN, REMOVE BOX, CONDUIT, AND

CONDUCTORS BACK TO SOURCE. ABANDON CONDUIT IN

WALL. PATCH WALL AND PAINT TO MATCH EXISTING. IF

THERE ARE OTHER DEVICES REMAINING ON THE BRANCH

CIRCUIT, PROTECT THE INTEGRITY OF THE CIRCUIT AND

MAINTAIN POWER TO THE DEVICES.

2. DEVICES OR LUMINAIRES BEING DEMOLISHED SHALL BE

PRESENTED TO OWNER FOR SALVAGE. IF UNWANTED

DISPOSE OF DEVICES, FIXTURE, AND/OR LAMPS PROPERLY.

DEMOLISH EXISTING LIGHT FIXTURE IN ROOM.

LIGHTING DEMOLITION KEY NOTES:

G

G

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans

Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMP

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

644-20-201

Revisions: Date:

TL 602.606.7432

Phoenix, AZ 85012

3300 N. Central Ave, STE 1520 www.dheengineering.com

Job Number: 00961.00

Concourse Federal Group 123 S. Royal Street Alexander, VA 22314

PLAN KEY

N

04.01.2021 JLZG

A

R I Z O N A U

S

A

Re g st e r ed

E

R

IT

I

D a t

S e d

C

A T E N

O e i gn _ _ _ _ _ _ _ _ _

F C

Expires 03-31-2024 i Pr o ession f al Engneer i

ZACHARY

GOLDSWORTHY

(E l c t rica e l)

72942

04 01

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

PVAHCS - Carl T Hayden Medical Center

650 E Indian School Road Phoenix AZ 85012

ENLARGED ELECTRICAL LIGHTING

PLANS

01-EL405.1

F6 ELECTRICAL LIGHTING PLAN - FIRST FLOOR - ROOM K132

1/4" = 1'-0"

2 2 4 6 8 10

1/4" = 1'-0"

FEETSCALE

C6

DEMOLITION

ELECTRICAL LIGHTING PLAN - FIRST FLOOR - ROOM K132

04.28.202105.26.2021 SHEET 173 of 421

K232

TOILET

K231A

CONFERENCE

K234

TOILET

K229A

HKC

K228

A

LIGHTING NOTES:

1. UNLESS OTHERWISE NOTED, COORDINATE EXACT

MOUNTING HEIGHTS OF ALL DEVICES WITH ARCHITECTURAL

INTERIOR ELEVATIONS.

2. PROVIDE MINIMUM 1100 LUMEN EMERGENCY BATTERY

PACKS IN ALL FIXTURES NOTED AS EMERGENCY. PROVIDE

WITH UNSWITCHED SENSING/CHARGING CIRCUIT PER

DETAIL SHEET.

3. PROVIDE AND INSTALL POWER TO EXIT SIGNS FROM LOCAL

ROOM LIGHTING BRANCH CIRCUIT AHEAD OF SWITCHING.

4. PROVIDE AND INSTALL POWER TO NIGHT LIGHTS (NL) FROM

LOCAL ROOM LIGHTING BRANCH CIRCUIT AHEAD OF

SWITCHING.

5. WHERE OCCUPANCY SENSORS ARE DEPICTED, PROVIDE

AND INSTALL POWER TO LOCAL ROOM LIGHTING THROUGH

DEVICE PER ASSOCIATED INSTALLATION DETAIL.

LIGHTING KEY NOTES:

CONNECT NEW LIGHT FIXTURE TO EXISTING CIRCUIT IN AREA

PREVIOUSLY FEEDING DEMOLISHED LIGHT FIXTURE.

LIGHTING DEMOLITION GENERAL NOTES:

1. WHERE DEVICES ARE SHOWN TO BE DEMOLISHED IN WALLS

THAT ARE SHOWN TO REMAIN, REMOVE BOX, CONDUIT, AND

CONDUCTORS BACK TO SOURCE. ABANDON CONDUIT IN

WALL. PATCH WALL AND PAINT TO MATCH EXISTING. IF

THERE ARE OTHER DEVICES REMAINING ON THE BRANCH

CIRCUIT, PROTECT THE INTEGRITY OF THE CIRCUIT AND

MAINTAIN POWER TO THE DEVICES.

2. DEVICES OR LUMINAIRES BEING DEMOLISHED SHALL BE

PRESENTED TO OWNER FOR SALVAGE. IF UNWANTED

DISPOSE OF DEVICES, FIXTURE, AND/OR LAMPS PROPERLY.

DEMOLISH EXISTING LIGHT FIXTURE IN AREA.

LIGHTING DEMOLITION KEY NOTES:

TR

K232

TOILET

K231A

CONFERENCE

K234

TOILET

K229A

HKC

K228

G

G

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans

Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMP

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

644-20-201

Revisions: Date:

TL 602.606.7432

Phoenix, AZ 85012

3300 N. Central Ave, STE 1520 www.dheengineering.com

Job Number: 00961.00

Concourse Federal Group 123 S. Royal Street Alexander, VA 22314

PLAN KEY

N

04.01.2021 JLZG

A

R I Z O N A U

S

A

Re g st e r ed

E

R

IT

I

D a t

S e d

C

A T E N

O e i gn _ _ _ _ _ _ _ _ _

F C

Expires 03-31-2024 i Pr o ession f al Engneer i

ZACHARY

GOLDSWORTHY

(E l c t rica e l)

72942

04 01

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

PVAHCS - Carl T Hayden Medical Center

650 E Indian School Road Phoenix AZ 85012

ENLARGED ELECTRICAL LIGHTING

PLANS

01-EL406.1

2 2 4 6 8 10

1/4" = 1'-0"

FEETSCALE

E6 ELECTRICAL LIGHTING PLAN - SECOND FLOOR - ROOM K232

1/4" = 1'-0"E1

DEMOLITION

ELECTRICAL LIGHTING PLAN - SECOND FLOOR - ROOM K232

04.28.202105.26.2021 SHEET 174 of 421

PUMP HOUSE 2

PUMP HOUSE 2

LIGHTING NOTES:

1. UNLESS OTHERWISE NOTED, COORDINATE EXACT

MOUNTING HEIGHTS OF ALL DEVICES WITH ARCHITECTURAL

INTERIOR ELEVATIONS.

2. PROVIDE MINIMUM 1100 LUMEN EMERGENCY BATTERY

PACKS IN ALL FIXTURES NOTED AS EMERGENCY. PROVIDE

WITH UNSWITCHED SENSING/CHARGING CIRCUIT PER

DETAIL SHEET.

3. PROVIDE AND INSTALL POWER TO EXIT SIGNS FROM LOCAL

ROOM LIGHTING BRANCH CIRCUIT AHEAD OF SWITCHING.

4. PROVIDE AND INSTALL POWER TO NIGHT LIGHTS (NL) FROM

LOCAL ROOM LIGHTING BRANCH CIRCUIT AHEAD OF

SWITCHING.

5. WHERE OCCUPANCY SENSORS ARE DEPICTED, PROVIDE

AND INSTALL POWER TO LOCAL ROOM LIGHTING THROUGH

DEVICE PER ASSOCIATED INSTALLATION DETAIL.

LIGHTING KEY NOTES:

CONNECT NEW LIGHT FIXTURE TO EXISTING CIRCUIT FEEDING

EXISTING LIGHT FIXTURES ON THE SAME FLOOR.

S

R

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans

Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMP

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

644-20-201

Revisions: Date:

TL 602.606.7432

Phoenix, AZ 85012

3300 N. Central Ave, STE 1520 www.dheengineering.com

Job Number: 00961.00

Concourse Federal Group 123 S. Royal Street Alexander, VA 22314

PLAN KEY

N

04.01.2021 JLZG

A

R I Z O N A U

S

A

Re g st e r ed

E

R

IT

I

D a t

S e d

C

A T E N

O e i gn _ _ _ _ _ _ _ _ _

F C

Expires 03-31-2024 i Pr o ession f al Engneer i

ZACHARY

GOLDSWORTHY

(E l c t rica e l)

72942

04 01

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

PVAHCS - Carl T Hayden Medical Center

650 E Indian School Road Phoenix AZ 85012

ENLARGED ELECTRICAL LIGHTING

PLAN

01-EL406.2

2 2 4 6 8 10

1/4" = 1'-0"

FEETSCALE

E6 ELECTRICAL LIGHTING PLAN - DATA CENTER ROOF

04.28.202105.26.2021 SHEET 175 of 421

D01B

CART WASH

D05

PUMP ROOM

TR

TRS-000A

TR MECH

TRS-000B

TR ELEC

TRS-000C

OFFICE

D05A

ET1LBET1HB

T-ET1B

EDT

NDT NT1LB NT1LB

T-NT1B

NT1LB-3

NT1LB-1

ET1LB-1

ET1LB-2/4/6 NT1LB-2/4/6

HU

1-6

CONDENSATE

PUMP

FCU

1-0

CU

1-0

ET1LB-8/10/12 NT1LB-5/7/9

NT1LB-10

NT1LB-8

NT1HB-2/4/6

NT1HB-8/10/12

ET1LB-3

TR

TRS-100A

TOILET

E102

TOILET

E103

TR ELEC

TRS-100C

OFFICE

D102

TR MECH

TRS-100B

NT1L1 NT1H1

XFMR

-ET11

NT1L1-1

ET1L1-1

NT1L1-8/10/12

ET1L1-2/4/6

CU

1-1

HU

1-7

FCU

1-1

CONDENSATE

PUMP

(TOP)

(BOTTOM)

NT1L1-2/4/6

ET1L1-8/10/12

ET1H1 ET1L1

XFMR

-NT11

NT1L1-14

NT1L1-3

NT1L1-5

NT1H1-2/4/6

NT1H1-8/10/12

ET1L1-3

TR

TRS-200A

TR MECH

TRS-200B

ABAN TR

2CD8A

TR ELEC

TRS-200C

NT1H2

ET1H2

T-ET12

ET1L2

NT1L2

T-NT12

FCU

1-2

NT1L2-1

NT1L2-7

ET1L2-1

ET1L2-2/4/6

ET1L2-8/10/12

NT1L2-2/4/6

CONDENSATE

PUMP

CU

1-2

HU

1-8 NT1L2-14

NT1L2-8/10/12

NT1L2-9

NT1H2-2/4/6

NT1H2-8/10/12

ET1L2-3

6 xCU xEQUIPMENT

CHILLER

TOILET

D338

TR

TRS-300A

TR-ELEC

TRS-300C

TR MECH

TRS-300B

NT1H3

ET1H3

T-ET13

T-NT13

ET1L3

NT1L3

NT1L3-1

ET1L3-8/10/12 NT1L3-8/10/12

NT1L3-2/4/6ET1L3-2/4/6

INDOOR

CONDENSER

HU

1-9

CONDENSATE

PUMP

CU

1-3

FCU

1-3

ET1L3-1

NT1L3-3

ET1L3-14/16/18 NT1L3-14/16/18

NT1L3-5

NT1H3-2/4/6

NT1H3-8/10/12

ET1L3-3

1. REFER TO "ME" SERIES SHEETS FOR ELECTRICAL WORK ASSOCIATED WITH

MECHANICAL LOADS (INDICATED WITH ). COORDINATE INSTALLATION OF

DISCONNECTS (WITHIN SITE OF LOADS) WITH ALL TRADES TO MEET MINIMUM

WORKING SPACE REQUIREMENTS (NEC 110.26).

2. UNLESS OTHERWISE NOTED, COORDINATE EXACT MOUNTING HEIGHTS OF ALL

DEVICES WITH ARCHITECTURAL INTERIOR ELEVATIONS.

POWER & SYSTEMS GENERAL NOTES:

POWER & SYSTEMS KEY NOTES:

PROVIDE NEW GROUND BAR WITH CU #6 MIN. PROVIDE EACH RACK

WITH RBB. BOND RBB TO SBB, LAN SWITCHES WITH DEDICATED

BONDING CONDUCTOR TO RACK.

45KVA XFMR T-E1B TO BE STACKED ON TOP OF 45KVA XFMR T-N1B.

45KVA XFMRS TO BE SUSPENDED ON UNISTRUT STRUCTURE FROM

CEILING.

PROVIDE NEMA L21-30R LOCKING RECEPTACLE.

PROVIDE JUNCTION BOX FOR DOOR & SECURITY POWER FROM

INDICATED CIRCUIT.

PROVIDE 120V CONNECTION TO FAN COIL UNIT CONDENSATE PUMP

WITH THERMAL TOGGLE. COORDINATE EXACT MOUNTING WITH

MECHANICAL CONTRACTOR.

1. REFER TO "ME" SERIES SHEETS FOR ELECTRICAL WORK ASSOCIATED WITH

MECHANICAL LOADS (INDICATED WITH ). COORDINATE INSTALLATION OF

DISCONNECTS (WITHIN SITE OF LOADS) WITH ALL TRADES TO MEET MINIMUM

WORKING SPACE REQUIREMENTS (NEC 110.26).

2. UNLESS OTHERWISE NOTED, COORDINATE EXACT MOUNTING HEIGHTS OF ALL

DEVICES WITH ARCHITECTURAL INTERIOR ELEVATIONS.

POWER & SYSTEMS GENERAL NOTES:

POWER & SYSTEMS KEY NOTES:

PROVIDE NEW GROUND BAR WITH CU #6 MIN. PROVIDE EACH RACK WITH RBB.

BOND RBB TO SBB, LAN SWITCHES WITH DEDICATED BONDING CONDUCTOR

TO RACK.

PROVIDE NEMA L21-30R LOCKING RECEPTACLE.

NOT USED.

NEW TRANSFORMER TO BE MOUNTED ABOVE PANELS SUPPORTED BY

UNISTRUT STRUCTURE.

PROVIDE JUNCTION BOX FOR DOOR & SECURITY POWER FROM INDICATED

CIRCUIT.

PROVIDE 120V CONNECTION TO FAN COIL UNIT CONDENSATE PUMP WITH

THERMAL TOGGLE. COORDINATE EXACT MOUNTING WITH MECHANICAL

CONTRACTOR.

1. REFER TO "ME" SERIES SHEETS FOR ELECTRICAL WORK ASSOCIATED WITH

MECHANICAL LOADS (INDICATED WITH ). COORDINATE INSTALLATION OF

DISCONNECTS (WITHIN SITE OF LOADS) WITH ALL TRADES TO MEET MINIMUM

WORKING SPACE REQUIREMENTS (NEC 110.26).

2. UNLESS OTHERWISE NOTED, COORDINATE EXACT MOUNTING HEIGHTS OF ALL

DEVICES WITH ARCHITECTURAL INTERIOR ELEVATIONS.

POWER & SYSTEMS GENERAL NOTES:

POWER & SYSTEMS KEY NOTES:

PROVIDE NEW GROUND BAR WITH CU #6 MIN. PROVIDE EACH RACK WITH RBB.

BOND RBB TO SBB, LAN SWITCHES WITH DEDICATED BONDING CONDUCTOR TO

RACK.

45KVA XFMR T-E12 TO BE STACKED ON TOP OF 45KVA XFMR T-N12.

PROVIDE NEMA L21-30R LOCKING RECEPTACLE.

PROVIDE JUNCTION BOX FOR DOOR & SECURITY POWER FROM INDICATED

CIRCUIT.

PROVIDE 120V CONNECTION TO FAN COIL UNIT CONDENSATE PUMP WITH

THERMAL TOGGLE. COORDINATE EXACT MOUNTING WITH MECHANICAL

CONTRACTOR.

RELOCATED EXISTING MECHANICAL EQUIPMENT. EXTEND EXISTING CONDUITS

AND CONDUCTORS AS REQUIRED.

1. REFER TO "ME" SERIES SHEETS FOR ELECTRICAL WORK ASSOCIATED WITH

MECHANICAL LOADS (INDICATED WITH ). COORDINATE INSTALLATION OF

DISCONNECTS (WITHIN SITE OF LOADS) WITH ALL TRADES TO MEET MINIMUM

WORKING SPACE REQUIREMENTS (NEC 110.26).

2. UNLESS OTHERWISE NOTED, COORDINATE EXACT MOUNTING HEIGHTS OF ALL

DEVICES WITH ARCHITECTURAL INTERIOR ELEVATIONS.

POWER & SYSTEMS GENERAL NOTES:

POWER & SYSTEMS KEY NOTES:

PROVIDE NEW GROUND BAR WITH CU #6 MIN. PROVIDE EACH RACK WITH RBB.

BOND RBB TO SBB, LAN SWITCHES WITH DEDICATED BONDING CONDUCTOR

TO RACK.

45KVA XFMR T-E13 TO BE STACKED ON TOP OF 45KVA XFMR T-N13.

PROVIDE NEMA L21-30R LOCKING RECEPTACLE.

PROVIDE NEMA L21-20R LOCKING RECEPTACLE.

PROVIDE JUNCTION BOX FOR DOOR & SECURITY POWER FROM INDICATED

CIRCUIT.

PROVIDE 120V CONNECTION TO FAN COIL UNIT CONDENSATE PUMP WITH

THERMAL TOGGLE. COORDINATE EXACT MOUNTING WITH MECHANICAL

CONTRACTOR.

A

R I Z O N A U

S

A

Re g st e r ed

E R

IT

I

D a t

S e d

C

A T E N

O e i gn _ _ _ _ _ _ _ _ _

F C

Expires 03-31-2024 i Pr o ession f al Engneer i

ZACHARY

GOLDSWORTHY

(E l c t rica e l)

72942

04 20

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans

Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMP

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

644-20-201

Revisions: Date:

TL 602.606.7432

Phoenix, AZ 85012

3300 N. Central Ave, STE 1520 www.dheengineering.com

Job Number: 00961.00

Concourse Federal Group 123 S. Royal Street Alexander, VA 22314

PLAN KEY

N

04.01.2021 JLZG

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

PVAHCS - Carl T Hayden Medical Center

650 E Indian School Road Phoenix AZ 85012

ENLARGED ELECTRICAL POWER

PLANS SOUTH IDF TOWER

01-EP401

4 ELECTRICAL POWER PLAN - 3RD FLOOR

1/4" = 1'-0"3 ELECTRICAL POWER PLAN - 2ND FLOOR

1/4" = 1'-0"

2 ELETRICAL POWER PLAN - 1ST FLOOR

1/4" = 1'-0"1 ELECTRICAL POWER PLAN - BASEMENT

04.28.202105.26.2021 SHEET 176 of 421

D456

TR ELEC

TRS-400C

TR

TRS-400A

TR MECH

TRS-400B

NT1H4

ET1H4

T-ET14

T-NT14

ET1L4

NT1L4

ET1L4-8/10/12NT1L4-1

ET1L4-1

ET1L4-2/4/6

NT1L4-7

NT1L4 -2/4/6

NT1L4 -8/10/12

ET1L4-14/16/18

HU

1-10

CONDENSATE

PUMP

INDOOR

CONDENSER

FCU

1-4

NT1L4-3

NT1L4-5

NT1L4 -14/16/18

NT1H4 -8/10/12

NT1H4 -2/4/6

ET1L4-3 4

STORAGE FILES

D639

TR ELEC

TRS-600C

TR

TRS-600A

CLOSET

TR MECH

TRS-600B

NT1H6

ET1H6

T-ET16

ET1L6

NT1L6

T-NT16

ET1L6-8/10/12

ET1L6-2/4/6

NT1L6-1

ET1L6-1

NT1L6-7

HU

1-12

CONDENSATE PUMP

CU

1-6

FCU

1-6

NT1L6-8/10/12

ET1L6-14/16/18

NT1L6-14/16/18

NT1L6-3

NT1L6-5

NT1L6-2/4/6

NT1H6-2/4/6

NT1H6-8/10/12

ET1L6-3

CLOSET

D539E

SHAFT

1. REFER TO "ME" SERIES SHEETS FOR ELECTRICAL WORK ASSOCIATED WITH

MECHANICAL LOADS (INDICATED WITH ). COORDINATE INSTALLATION OF

DISCONNECTS (WITHIN SITE OF LOADS) WITH ALL TRADES TO MEET MINIMUM

WORKING SPACE REQUIREMENTS (NEC 110.26).

2. UNLESS OTHERWISE NOTED, COORDINATE EXACT MOUNTING HEIGHTS OF ALL

DEVICES WITH ARCHITECTURAL INTERIOR ELEVATIONS.

POWER & SYSTEMS GENERAL NOTES:

XX

POWER & SYSTEMS KEY NOTES:

PROVIDE NEW GROUND BAR WITH CU #6 MIN. PROVIDE EACH RACK WITH RBB.

BOND RBB TO SBB, LAN SWITCHES WITH DEDICATED BONDING CONDUCTOR

TO RACK.

PROVIDE NEMA L21-30R LOCKING RECEPTACLE.

PROVIDE NEMA L21-20R LOCKING RECEPTACLE.

PROVIDE JUNCTION BOX FOR DOOR & SECURITY POWER FROM INDICATED

CIRCUIT.

PROVIDE 120V CONNECTION TO FAN COIL UNIT CONDENSATE PUMP WITH

THERMAL TOGGLE. COORDINATE EXACT MOUNTING WITH MECHANICAL

CONTRACTOR.

1. REFER TO "ME" SERIES SHEETS FOR ELECTRICAL WORK ASSOCIATED WITH

MECHANICAL LOADS (INDICATED WITH ). COORDINATE INSTALLATION OF

DISCONNECTS (WITHIN SITE OF LOADS) WITH ALL TRADES TO MEET MINIMUM

WORKING SPACE REQUIREMENTS (NEC 110.26).

2. UNLESS OTHERWISE NOTED, COORDINATE EXACT MOUNTING HEIGHTS OF ALL

DEVICES WITH ARCHITECTURAL INTERIOR ELEVATIONS.

POWER & SYSTEMS GENERAL NOTES:

XX

POWER & SYSTEMS KEY NOTES:

PROVIDE NEW GROUND BAR WITH CU #6 MIN. PROVIDE EACH RACK WITH RBB.

BOND RBB TO SBB, LAN SWITCHES WITH DEDICATED BONDING CONDUCTOR

TO RACK.

PROVIDE NEMA L21-30R LOCKING RECEPTACLE.

PROVIDE NEMA L21-20R LOCKING RECEPTACLE.

PROVIDE JUNCTION BOX FOR DOOR & SECURITY POWER FROM INDICATED

CIRCUIT.

PROVIDE 120V CONNECTION TO FAN COIL UNIT CONDENSATE PUMP WITH

THERMAL TOGGLE. COORDINATE EXACT MOUNTING WITH MECHANICAL

CONTRACTOR.

1. REFER TO "ME" SERIES SHEETS FOR ELECTRICAL WORK ASSOCIATED WITH

MECHANICAL LOADS (INDICATED WITH ). COORDINATE INSTALLATION OF

DISCONNECTS (WITHIN SITE OF LOADS) WITH ALL TRADES TO MEET MINIMUM

WORKING SPACE REQUIREMENTS (NEC 110.26).

2. UNLESS OTHERWISE NOTED, COORDINATE EXACT MOUNTING HEIGHTS OF ALL

DEVICES WITH ARCHITECTURAL INTERIOR ELEVATIONS.

POWER & SYSTEMS GENERAL NOTES:

XX

POWER & SYSTEMS KEY NOTES:

PROVIDE NEW GROUND BAR WITH CU #6 MIN. PROVIDE EACH RACK WITH

RBB. BOND RBB TO SBB, LAN SWITCHES WITH DEDICATED BONDING

CONDUCTOR TO RACK.

PROVIDE NEMA L21-30R LOCKING RECEPTACLE.

PROVIDE NEMA L21-20R LOCKING RECEPTACLE.

PROVIDE JUNCTION BOX FOR DOOR & SECURITY POWER FROM INDICATED

CIRCUIT.

PROVIDE 120V CONNECTION TO FAN COIL UNIT CONDENSATE PUMP WITH

THERMAL TOGGLE. COORDINATE EXACT MOUNTING WITH MECHANICAL

CONTRACTOR.

1. REFER TO "ME" SERIES SHEETS FOR ELECTRICAL WORK ASSOCIATED WITH

MECHANICAL LOADS (INDICATED WITH ). COORDINATE INSTALLATION OF

DISCONNECTS (WITHIN SITE OF LOADS) WITH ALL TRADES TO MEET MINIMUM

WORKING SPACE REQUIREMENTS (NEC 110.26).

2. UNLESS OTHERWISE NOTED, COORDINATE EXACT MOUNTING HEIGHTS OF ALL

DEVICES WITH ARCHITECTURAL INTERIOR ELEVATIONS.

POWER & SYSTEMS GENERAL NOTES:

XX

POWER & SYSTEMS KEY NOTES:

NOT USED.1

TR

TRS-500A

TR MECH

TRS-500B

TR- ELEC

TRS-500C

CLOSET

D539A

OFFICE

D540A

NT1H5

ET1H5

T-ET15

T-NT15

ET1L5

NT1L5

ET1L5-8/10/12 NT1L5-8/10/12

ET1L5-2/4/6

NT1L5-2/4/6

NT1L5-1

ET1L5-1

ET1L5-14/16/18

NT1L5-14/16/18

HU

1-11

CONDENSATE

PUMP

INDOOR

CONDENSER

CU

1-5

FCU

1-5

NT1L5-5

NT1L5-3

NT1H5-2/4/6

NT1H5-8/10/12

ET1L5-3

A

R I Z O N A U

S

A

Re g st e r ed

E R

IT

I

D a t

S e d

C

A T E N

O e i gn _ _ _ _ _ _ _ _ _

F C

Expires 03-31-2024 i Pr o ession f al Engneer i

ZACHARY

GOLDSWORTHY

(E l c t rica e l)

72942

04 20

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans

Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMP

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

644-20-201

Revisions: Date:

TL 602.606.7432

Phoenix, AZ 85012

3300 N. Central Ave, STE 1520 www.dheengineering.com

Job Number: 00961.00

Concourse Federal Group 123 S. Royal Street Alexander, VA 22314

PLAN KEY

N

04.01.2021 JLZG

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

PVAHCS - Carl T Hayden Medical Center

650 E Indian School Road Phoenix AZ 85012

ENLARGED ELECTRICAL POWER

PLANS SOUTH IDF TOWER

01-EP402

F6 ELECTRICAL POWER PLAN - 7TH FLOOR

1/4" = 1'-0"F1 ELECTRICAL POWER PLAN - 6TH FLOOR

1/4" = 1'-0"

C6 ELETRICAL POWER PLAN - 5TH FLOOR

1/4" = 1'-0"C1 ELECTRICAL POWER PLAN - 4TH FLOOR

04.28.202105.26.2021 SHEET 177 of 421

*05.26.2021 SHEET 178 of 421

04.28.202105.26.2021 SHEET 179 of 421

1. REFER TO "ME" SERIES SHEETS FOR ELECTRICAL WORK

ASSOCIATED WITH MECHANICAL LOADS (INDICATED WITH ).

COORDINATE INSTALLATION OF DISCONNECTS (WITHIN SITE OF

LOADS) WITH ALL TRADES TO MEET MINIMUM WORKING SPACE

REQUIREMENTS (NEC 110.26).

2. UNLESS OTHERWISE NOTED, COORDINATE EXACT MOUNTING

HEIGHTS OF ALL DEVICES WITH ARCHITECTURAL INTERIOR

ELEVATIONS.

CONNECT NEW VAV BOX TO EXISTING CIRCUIT IN AREA FEEDING

EXISTING VAV CONTROLS IN AREA.

UPSIZE EXISTING CONDUIT, FEEDERS AND CONDUIT TO 1 SET OF

(4)#1 + (1)#8 IN 1-1/2"C. REPLACE EXISTING CIRCUIT BREAKER

UPSTREAM FEEDING THE PANEL AND MAIN CIRCUIT BREAKER IN

THE PANEL TO 100A.

TR

K132

BREAK

ROOM

K134

TLT

K131A

2 BED

K131

2 BED

K129

TLT

K129A

HKC

K128

VAV

1-1

HU

1-5LC1A-20

LC1A-17

G

HD1 (CBP#23)

LC1A

(CBP#24)

LD1

(CBP#25)

LP1

(CBP#26)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans

Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMP

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

644-20-201

Revisions: Date:

TL 602.606.7432

Phoenix, AZ 85012

3300 N. Central Ave, STE 1520 www.dheengineering.com

Job Number: 00961.00

Concourse Federal Group 123 S. Royal Street Alexander, VA 22314

PLAN KEY

N

04.01.2021 JLZG

A

R I Z O N A U

S

A

Re g st e r ed

E

R

IT

I

D a t

S e d

C

A T E N

O e i gn _ _ _ _ _ _ _ _ _

F C

Expires 03-31-2024 i Pr o ession f al Engneer i

ZACHARY

GOLDSWORTHY

(E l c t rica e l)

72942

04 01

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

PVAHCS - Carl T Hayden Medical Center

650 E Indian School Road Phoenix AZ 85012

ENLARGED ELECTRICAL POWER

PLANS

01-EP405.1

F6 ELECTRICAL POWER PLAN - ROOM K132

1/4" = 1'-0"

2 2 4 6 8 10

1/4" = 1'-0"

FEETSCALE

F6.1 ELECTRICAL POWER PLAN - ROOM L-115

04.28.202105.26.2021 SHEET 180 of 421

DATA CENTER

CARTS

CARTS

KITCHEN

1606BKITCHEN

1606B xACU01A0111609 xACU01A0211609 xACU01A0311609

DEMOLISH EXISTING DEVICE INDICATED. DEMOLISH ALL

ASSOCIATED BOXES, RACEWAY, AND CONDUCTORS BACK TO

SOURCE OR TO THE EXTENT OF WHICH THE INTEGRITY OF ANY

DEVICES SHARING SUCH BOXES, RACEWAY, CABLES, OR

CONDUCTORS ARE MAINTAINED (ie. ADJACENT UNAFFECTED

SPACES OR DEVICES ON SAME CIRCUIT).

PRESERVE EXISTING FEEDERS AND CIRCUITS FOR RE-USE ON NEW

CRAC UNITS.

1. THE CONTRACTOR SHALL NOTE THIS IS A 24/7 FLOOR 1

TRAUMA CENTER WITH CRITICAL CARE PATIENT OCCUPANCY

AT ALL TIMES. SHUTDOWN OF ANY SYSTEMS WITHOUT THE

OWNERS/CONSTRUCTION SUPERVISOR'S WRITTEN CONSENT

WILL NOT BE TOLERATED.

2. DEMOLITION DRAWINGS ARE BASED UPON FIELD

OBSERVATION AND EXISTING OWNER PROVIDED RECORD

DRAWINGS. DEVICES INDICATED ARE FOR REFERENCE IN

ASSISTING THE CONTRACTOR IN DETERMINING THE DENSITY

OF DEMOLITION SCOPE REQUIRED. THE CONTRACTOR SHALL

VERIFY EXACT CONDITIONS IN FIELD. ANY NOTEWORTHY

DISCREPANCIES SHALL BE REVIEWED WITH THE OWNER &

ARCHITECT/ENGINEER PRIOR TO COMMENCEMENT OF

REMOVAL.

3. RE-LABEL ALL SPARE BREAKERS RESULTANT FROM

DEMOLITION AND PLACE BREAKER IN THE "OFF" POSITION.

PRIORITIZE THE RE-USE OF EXISTING SPARE BREAKERS FOR

NEW LOADS INDICATED ON EACH RESPECTIVE PANEL PRIOR

TO PROVIDING NEW. RECORD ALL NEW SPARES OR NEW

LOADS IN AS-BUILT DOCUMENTS AND PROVIDE UPDATED

TYPED PANELBOARD SCHEDULES.

4. WHERE DEVICES ARE SHOWN TO BE DEMOLISHED IN WALLS

THAT ARE SHOWN TO REMAIN, REMOVE BOX, CONDUIT, AND

CONDUCTORS BACK TO SOURCE. ABANDON CONDUIT IN

WALL. PATCH WALL AND PAINT TO MATCH EXISTING. IF

THERE ARE OTHER DEVICES REMAINING ON THE BRANCH

CIRCUIT, PROTECT THE INTEGRITY OF THE CIRCUIT AND

MAINTAIN POWER TO THE DEVICES.

5. DEVICES BEING DEMOLISHED SHALL BE PRESENTED TO

OWNER FOR SALVAGE. IF UNWANTED DISPOSE OF DEVICES

PROPERLY.

R R

1. REFER TO "ME" SERIES SHEETS FOR ELECTRICAL WORK

ASSOCIATED WITH MECHANICAL LOADS (INDICATED WITH ).

COORDINATE INSTALLATION OF DISCONNECTS (WITHIN SITE OF

LOADS) WITH ALL TRADES TO MEET MINIMUM WORKING SPACE

REQUIREMENTS (NEC 110.26).

2. UNLESS OTHERWISE NOTED, COORDINATE EXACT MOUNTING

HEIGHTS OF ALL DEVICES WITH ARCHITECTURAL INTERIOR

ELEVATIONS.

REUSE EXISTING FEEDERS PREVIOUSLY FEEDING DEMOLISHED

CRAC UNITS.

DATA CENTER

CARTS

KITCHEN

1606B

CRAC

1-3

CRAC

1-2

CRAC

1-1

PUMP ROOM

ELEC

ELEC

D01A

STAIR 1

BBP

BBL

BEE

BBLE (SEC 2)

BBLE (SEC 1)

1. REFER TO "ME" SERIES SHEETS FOR ELECTRICAL WORK

ASSOCIATED WITH MECHANICAL LOADS (INDICATED WITH ).

COORDINATE INSTALLATION OF DISCONNECTS (WITHIN SITE OF

LOADS) WITH ALL TRADES TO MEET MINIMUM WORKING SPACE

REQUIREMENTS (NEC 110.26).

2. UNLESS OTHERWISE NOTED, COORDINATE EXACT MOUNTING

HEIGHTS OF ALL DEVICES WITH ARCHITECTURAL INTERIOR

ELEVATIONS.

PANEL BEE FEEDING EXISTING CRAC UNIT #3. CIRCUITS TO BE

REUSED FOR NEW CRAC UNIT.

1. REFER TO "ME" SERIES SHEETS FOR ELECTRICAL WORK

ASSOCIATED WITH MECHANICAL LOADS (INDICATED WITH ).

COORDINATE INSTALLATION OF DISCONNECTS (WITHIN SITE OF

LOADS) WITH ALL TRADES TO MEET MINIMUM WORKING SPACE

REQUIREMENTS (NEC 110.26).

2. UNLESS OTHERWISE NOTED, COORDINATE EXACT MOUNTING

HEIGHTS OF ALL DEVICES WITH ARCHITECTURAL INTERIOR

ELEVATIONS.

PANEL B-COMP 2 FEEDING EXISTING CRAC UNIT #1 & #2. CIRCUITS

TO BE REUSED FOR NEW CRAC UNIT.

B-COMP 2

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans

Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMP

321 4 5 6 7 8 9 10

SHEET OF

EHRM INFRASTRUCTURE

UPGRADES

644-20-201

Revisions: Date:

TL 602.606.7432

Phoenix, AZ 85012

3300 N. Central Ave, STE 1520 www.dheengineering.com

Job Number: 00961.00

Concourse Federal Group 123 S. Royal Street Alexander, VA 22314

PLAN KEY

N

04.01.2021 JLZG

A

R I Z O N A U

S

A

Re g st e r ed

E

R

IT

I

D a t

S e d

C

A T E N

O e i gn _ _ _ _ _ _ _ _ _

F C

Expires 03-31-2024 i Pr o ession f al Engneer i

ZACHARY

GOLDSWORTHY

(E l c t rica e l)

72942

04 01

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

PVAHCS - Carl T Hayden Medical Center

650 E Indian School Road Phoenix AZ 85012

ENLARGED ELECTRICAL POWER

PLANS

01-EP405.2

F6 ELECTRICAL POWER PLAN - DATA CENTER

1/4" = 1'-0"F1 DEMOLITION ELECTRICAL POWER PLAN - DATA CENTER

1/4" = 1'-0"

2 2 4 6 8 10

1/4" = 1'-0"

FEETSCALE

F6.1 ELECTRICAL POWER PLAN - PANEL BEE - BASEMENT LEVEL

1/4" = 1'-0"

F6.2 ELECTRICAL POWER PLAN - PANEL BEE - BASEMENT LEVEL

04.28.202105.26.2021 SHEET 181 of 421

COORDINATE INSTALLATION OF DISCONNECTS (WITHIN SITE OF

LOADS) WITH ALL TRADES TO MEET MINIMUM WORKING SPACE

REQUIREMENTS (NEC 110.26).

2. UNLESS OTHERWISE NOTED, COORDINATE EXACT MOUNTING

HEIGHTS OF ALL DEVICES WITH ARCHITECTURAL INTERIOR

ELEVATIONS.

POWER & SYSTEMS GENERAL NOTES:

POWER & SYSTEMS KEY NOTES:

POWER FOR PUMPS FROM PANEL NT2L2 LOCATED IN NEW TOWER.

REFER TO PANEL SCHEDULES FOR MORE INFORMATION.

PROVIDE INTEGRAL RECEPTACLE.

PROVIDE CONNECTION FROM NEW ENCLOSURE TO EXISTING

LIGHTNING PROTECTION SYSTEM. AIR TERMINAL TO BE MOUNTED

ON SIDE OF ENCLOSURE.

PUMP HOUSE 2

PUMP HOUSE 2

P 1-6

P 1-5

VFD

1-5

VFD

1-6

S

R

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans

Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMP

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

644-20-201

Revisions: Date:

TL 602.606.7432

Phoenix, AZ 85012

3300 N. Central Ave, STE 1520 www.dheengineering.com

Job Number: 00961.00

Concourse Federal Group 123 S. Royal Street Alexander, VA 22314

PLAN KEY

N

04.01.2021 JLZG

A

R I Z O N A U

S

A

Re g st e r ed

E

R

IT

I

D a t

S e d

C

A T E N

O e i gn _ _ _ _ _ _ _ _ _

F C

Expires 03-31-2024 i Pr o ession f al Engneer i

ZACHARY

GOLDSWORTHY

(E l c t rica e l)

72942

04 01

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

PVAHCS - Carl T Hayden Medical Center

650 E Indian School Road Phoenix AZ 85012

ENLARGED ELECTRICAL POWER

PLAN

01-EP405.3

4 4 8 12 16 20

1/8" = 1'-0"

FEETSCALE

F6 ELECTRICAL POWER PLAN - DATA CENTER ROOF

1/8" = 1'-0"

04.28.202105.26.2021 SHEET 182 of 421

COORDINATE INSTALLATION OF DISCONNECTS (WITHIN SITE OF

LOADS) WITH ALL TRADES TO MEET MINIMUM WORKING SPACE

REQUIREMENTS (NEC 110.26).

2. UNLESS OTHERWISE NOTED, COORDINATE EXACT MOUNTING

HEIGHTS OF ALL DEVICES WITH ARCHITECTURAL INTERIOR

ELEVATIONS.

POWER & SYSTEMS GENERAL NOTES:

POWER & SYSTEMS KEY NOTES:

REFER TO SHEET EJ601-ELECTRICAL ONE-LINE DIAGRAM FOR

PUMP ELECTRICAL INFORMATION. COORDINATE CONNECTION WITH

R.O. SCOPE IN BUILDING 2.

CONTRACTOR SHALL ENSURE NEW R.O. WATER STORAGE TANK

AND ANCILLARY EQUIPMENT DOES NOT IMPEDE ON EXISTING

ELECTRICAL EQUIPMENT CLEARANCE.

BDH-3

BDL-3

BDH-2

BDL-2

01-BB-NH1

BDH-1

BDH-4

BDL-1

01-BB-ESWBD2

ECB-PNL-K2

ATS-01BATSG4

ELLIPTICAL RO WATER

STORAGE TANK

ULTRAVIOLET

ASSEMBLY

RE-PRESSURIZATION

PUMPS (15HP)

(TYP. 2)

BPEE

BLCE

BPCE

B-D

01-BB-LH1

01-BB-EH1

01-BB-NL2

T

01-BB-EL3

01-BB-EL2

01-BB-EL1

01-BB-NL1

P

P

01-BB-EL1-9

VFD VFD

01-BB-EL3-11

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans

Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMP

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

644-20-201

Revisions: Date:

TL 602.606.7432

Phoenix, AZ 85012

3300 N. Central Ave, STE 1520 www.dheengineering.com

Job Number: 00961.00

Concourse Federal Group 123 S. Royal Street Alexander, VA 22314

PLAN KEY

N

04.01.2021 JLZG

A

R I Z O N A U

S

A

R eg st e r ed

E

R

IT

I

D a t

S e d

C

A T E N

O e i gn _ _ _ _ _ _ _ _ _

F C

Expires 03-31-2024 i Pr o ession f al Engneer i

ZACHARY

GOLDSWORTHY

(E l c t rica e l)

72942

04 01

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

PVAHCS - Carl T Hayden Medical Center

650 E Indian School Road Phoenix AZ 85012

ENLARGED ELECTRICAL POWER

PLANS

01-EP406

F1 ELECTRICAL POWER PLAN - ROOM 0119

1/4" = 1'-0"

2 2 4 6 8 10

1/4" = 1'-0"

FEETSCALE

04.28.202105.26.2021 SHEET 183 of 421

K232

TOILET

K231A

CONFERENCE

K234

TOILET

K229A

HKC

K228

VAV

1-2

1. REFER TO "ME" SERIES SHEETS FOR ELECTRICAL WORK

ASSOCIATED WITH MECHANICAL LOADS (INDICATED WITH ).

COORDINATE INSTALLATION OF DISCONNECTS (WITHIN SITE OF

LOADS) WITH ALL TRADES TO MEET MINIMUM WORKING SPACE

REQUIREMENTS (NEC 110.26).

2. UNLESS OTHERWISE NOTED, COORDINATE EXACT MOUNTING

HEIGHTS OF ALL DEVICES WITH ARCHITECTURAL INTERIOR

ELEVATIONS.

POWER & SYSTEMS GENERAL NOTES:

POWER & SYSTEMS KEY NOTES:

PROVIDE DISCONNECT SWITCH. EXTEND CONDUITS AND

CONDUCTORS FROM JUNCTION BOX FEEDING EXISTING VAV

BOXES WITHIN THE VICINITY.

POWER & SYSTEMS DEMOLITION GENERAL NOTES:

POWER & SYSTEMS DEMOLITION KEY NOTES:

DEMOLISH EXISTING DEVICE INDICATED. DEMOLISH ALL

ASSOCIATED BOXES, RACEWAY, AND CONDUCTORS BACK TO

SOURCE OR TO THE EXTENT OF WHICH THE INTEGRITY OF ANY

DEVICES SHARING SUCH BOXES, RACEWAY, CABLES, OR

CONDUCTORS ARE MAINTAINED (ie. ADJACENT UNAFFECTED

SPACES OR DEVICES ON SAME CIRCUIT).

EXISTING RECEPTACLES SERVING WALL MOUNTED RACK SHALL

REMAIN.

1. THE CONTRACTOR SHALL NOTE THIS IS A 24/7 FLOOR 1

TRAUMA CENTER WITH CRITICAL CARE PATIENT OCCUPANCY

AT ALL TIMES. SHUTDOWN OF ANY SYSTEMS WITHOUT THE

OWNERS/CONSTRUCTION SUPERVISOR'S WRITTEN CONSENT

WILL NOT BE TOLERATED.

2. DEMOLITION DRAWINGS ARE BASED UPON FIELD

OBSERVATION AND EXISTING OWNER PROVIDED RECORD

DRAWINGS. DEVICES INDICATED ARE FOR REFERENCE IN

ASSISTING THE CONTRACTOR IN DETERMINING THE DENSITY

OF DEMOLITION SCOPE REQUIRED. THE CONTRACTOR SHALL

VERIFY EXACT CONDITIONS IN FIELD. ANY NOTEWORTHY

DISCREPANCIES SHALL BE REVIEWED WITH THE OWNER &

ARCHITECT/ENGINEER PRIOR TO COMMENCEMENT OF

REMOVAL.

3. RE-LABEL ALL SPARE BREAKERS RESULTANT FROM

DEMOLITION AND PLACE BREAKER IN THE "OFF" POSITION.

PRIORITIZE THE RE-USE OF EXISTING SPARE BREAKERS FOR

NEW LOADS INDICATED ON EACH RESPECTIVE PANEL PRIOR

TO PROVIDING NEW. RECORD ALL NEW SPARES OR NEW

LOADS IN AS-BUILT DOCUMENTS AND PROVIDE UPDATED

TYPED PANELBOARD SCHEDULES.

4. WHERE DEVICES ARE SHOWN TO BE DEMOLISHED IN WALLS

THAT ARE SHOWN TO REMAIN, REMOVE BOX, CONDUIT, AND

CONDUCTORS BACK TO SOURCE. ABANDON CONDUIT IN

WALL. PATCH WALL AND PAINT TO MATCH EXISTING. IF

THERE ARE OTHER DEVICES REMAINING ON THE BRANCH

CIRCUIT, PROTECT THE INTEGRITY OF THE CIRCUIT AND

MAINTAIN POWER TO THE DEVICES.

5. DEVICES BEING DEMOLISHED SHALL BE PRESENTED TO

OWNER FOR SALVAGE. IF UNWANTED DISPOSE OF DEVICES

PROPERLY.

TR

K232

TOILET

K231A

CONFERENCE

K234

TOILET

K229A

HKC

K228

G

G

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans

Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMP

321 4 5 6 7 8 9 10

SHEET OF

EHRM INFRASTRUCTURE

UPGRADES

644-20-201

Revisions: Date:

TL 602.606.7432

Phoenix, AZ 85012

3300 N. Central Ave, STE 1520 www.dheengineering.com

Job Number: 00961.00

Concourse Federal Group 123 S. Royal Street Alexander, VA 22314

PLAN KEY

N

04.01.2021 JLZG

A

R I Z O N A U

S

A

Re g st e r ed

E

R

IT

I

D a t

S e d

C

A T E N

O e i gn _ _ _ _ _ _ _ _ _

F C

Expires 03-31-2024 i Pr o ession f al Engneer i

ZACHARY

GOLDSWORTHY

(E l c t rica e l)

72942

04 01

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

PVAHCS - Carl T Hayden Medical Center

650 E Indian School Road Phoenix AZ 85012

01-EP406.1

2 2 4 6 8 10

1/4" = 1'-0"

FEETSCALE

E6 ELECTRICAL POWER PLAN - ROOM K232

1/4" = 1'-0"E1

DEMOLITION

ELECTRICAL POWER PLAN - ROOM K232

1/4" = 1'-0"

ELECTRICAL POWER PLANS -

2ND FLOOR

04.28.202105.26.2021 SHEET 184 of 421

1. REFER TO "ME" SERIES SHEETS FOR ELECTRICAL WORK ASSOCIATED WITH

MECHANICAL LOADS (INDICATED WITH ). COORDINATE INSTALLATION OF

DISCONNECTS (WITHIN SITE OF LOADS) WITH ALL TRADES TO MEET MINIMUM

WORKING SPACE REQUIREMENTS (NEC 110.26).

2. UNLESS OTHERWISE NOTED, COORDINATE EXACT MOUNTING HEIGHTS OF ALL

DEVICES WITH ARCHITECTURAL INTERIOR ELEVATIONS.

POWER & SYSTEMS GENERAL NOTES:

XX

POWER & SYSTEMS KEY NOTES:

NOT USED.1

SHOPS STORAGE

ENGINEERING

RECORDS

D800A

ELEVATOR

MACHINE ROOM

D800 P

1-2

P 1-1

VFD

1-1

VFD

1-2

NT1L6-9

10 11 12

K

L

K.5

J

A

R I Z O N A U

S

A

Re g st e r ed

E R

IT

I

D a t

S e d

C

A T E N

O e i gn _ _ _ _ _ _ _ _ _

F C

Expires 03-31-2024 i Pr o ession f al Engneer i

ZACHARY

GOLDSWORTHY

(E l c t rica e l)

72942

04 20

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans

Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMP

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

644-20-201

Revisions: Date:

TL 602.606.7432

Phoenix, AZ 85012

3300 N. Central Ave, STE 1520 www.dheengineering.com

Job Number: 00961.00

Concourse Federal Group 123 S. Royal Street Alexander, VA 22314

PLAN KEY

N

04.01.2021 JLZG

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

PVAHCS - Carl T Hayden Medical Center

650 E Indian School Road Phoenix AZ 85012

ENLARGED POWER PLANS NORTH

AND SOUTH IDF TOWERS

01-EP408

F1 ELECTRICAL POWER PLAN - 8TH FLOOR

04.28.202105.26.2021 SHEET 185 of 421

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans

Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMP

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

644-20-201

Revisions: Date:

TL 602.606.7432

Phoenix, AZ 85012

3300 N. Central Ave, STE 1520 www.dheengineering.com

Job Number: 00961.00

Concourse Federal Group 123 S. Royal Street Alexander, VA 22314

04.01.2021 JLZG

A

R I Z O N A U

S

A

R eg st e r ed

E

R

IT

I

D a t

S e d

C

A T E N

O e i gn _ _ _ _ _ _ _ _ _

F C

Expires 03-31-2024 i Pr o ession f al Engneer i

ZACHARY

GOLDSWORTHY

(E l c t rica e l)

72942

04 01

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

PVAHCS - Carl T Hayden Medical Center

650 E Indian School Road Phoenix AZ 85012

ELECTRICAL PANEL SCHEDULES

01-EK601

04.28.202105.26.2021 SHEET 186 of 421

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans

Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMP

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

644-20-201

Revisions: Date:

TL 602.606.7432

Phoenix, AZ 85012

3300 N. Central Ave, STE 1520 www.dheengineering.com

Job Number: 00961.00

Concourse Federal Group 123 S. Royal Street Alexander, VA 22314

04.01.2021 JLZG

A

R I Z O N A U

S

A

R eg st e r ed

E

R

IT

I

D a t

S e d

C

A T E N

O e i gn _ _ _ _ _ _ _ _ _

F C

Expires 03-31-2024 i Pr o ession f al Engneer i

ZACHARY

GOLDSWORTHY

(E l c t rica e l)

72942

04 01

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

PVAHCS - Carl T Hayden Medical Center

650 E Indian School Road Phoenix AZ 85012

ELECTRICAL PANEL SCHEDULES

01-EK602

04.28.202105.26.2021 SHEET 187 of 421

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans

Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMP

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

644-20-201

Revisions: Date:

TL 602.606.7432

Phoenix, AZ 85012

3300 N. Central Ave, STE 1520 www.dheengineering.com

Job Number: 00961.00

Concourse Federal Group 123 S. Royal Street Alexander, VA 22314

04.01.2021 JLZG

A

R I Z O N A U

S

A

R eg st e r ed

E

R

IT

I

D a t

S e d

C

A T E N

O e i gn _ _ _ _ _ _ _ _ _

F C

Expires 03-31-2024 i Pr o ession f al Engneer i

ZACHARY

GOLDSWORTHY

(E l c t rica e l)

72942

04 01

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

PVAHCS - Carl T Hayden Medical Center

650 E Indian School Road Phoenix AZ 85012

ELECTRICAL PANEL SCHEDULES

01-EK603

04.28.202105.26.2021 SHEET 188 of 421

04.28.202105.26.2021 SHEET 189 of 421

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans

Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMP

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

644-20-201

Revisions: Date:

TL 602.606.7432

Phoenix, AZ 85012

3300 N. Central Ave, STE 1520 www.dheengineering.com

Job Number: 00961.00

Concourse Federal Group 123 S. Royal Street Alexander, VA 22314

04.01.2021 JLZG

A

R I Z O N A U

S

A

R eg st e r ed

E

R

IT

I

D a t

S e d

C

A T E N

O e i gn _ _ _ _ _ _ _ _ _

F C

Expires 03-31-2024 i Pr o ession f al Engneer i

ZACHARY

GOLDSWORTHY

(E l c t rica e l)

72942

04 01

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

PVAHCS - Carl T Hayden Medical Center

650 E Indian School Road Phoenix AZ 85012

ELECTRICAL PANEL SCHEDULES

01-EK605

JLPN04.28.202105.26.2021 SHEET 190 of 421

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans

Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMP

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

644-20-201

Revisions: Date:

TL 602.606.7432

Phoenix, AZ 85012

3300 N. Central Ave, STE 1520 www.dheengineering.com

Job Number: 00961.00

Concourse Federal Group 123 S. Royal Street Alexander, VA 22314

04.01.2021 JLZG

A

R I Z O N A U

S

A

R eg st e r ed

E

R

IT

I

D a t

S e d

C

A T E N

O e i gn _ _ _ _ _ _ _ _ _

F C

Expires…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .