AMENDMENT 0003 - ATTACHMENT MI903 - Mechanical and Electrical Schedules.pdf
PDF 280 KB Posted
- Attached to
- Z2DZ--644-20-201 EHRM Phoenix Construction Federal contract opportunity
- Solicitation number
- 36C26221B0007_1
About this file
This document contains mechanical and electrical schedules for the EHRM Infrastructure Upgrades project at the VA Phoenix Healthcare System located in Phoenix, Arizona. The schedules specify the mechanical equipment, electrical components, and ductwork required for the project, including ductless split fan coil units, air cooled condensing units, supply terminal units, steam humidifiers, diffusers, grilles, and registers. Contractor shall furnish all labor, materials, equipment, and services to install and commission the mechanical and electrical systems according to the specifications in the schedules.
A related federal contract opportunity was also provided. The VA is soliciting bids for construction services for the EHRM Infrastructure Upgrades project under Solicitation Number 36C26221B0007_1. The project scope includes general construction, alterations, mechanical and electrical work, and utility system upgrades. The construction value is estimated between $10-20 million. The solicitation will be issued on June 3, 2021 via beta.sam.gov as a 100% SDVOSB set-aside. A site visit will also be scheduled. The point of contact listed is Steven Covell at the VA Network Contracting Office 22 in Long Beach, California.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C26221B0007 AMENDMENT 0004 7-13-21.pdf | ||
| 36C26221B0007 AMENDMENT 0003 7-07-21.pdf | ||
| 36C26221B0007 AMENDMENT 0002 7-02-21.pdf | ||
| 36C26221B0007 AMENDMENT 0001 6-30-21.pdf | ||
| Attachment B_ Wage Determination.pdf | ||
| Attachment D2_ Drawings 2 of 12.pdf | ||
| Attachment D3_ Drawings 3 of 12.pdf | ||
| Attachment D5_ Drawings 5 of 12.pdf | ||
| Attachment D9_ Drawings 9 of 12.pdf | ||
| 36C26221B0007_1.docx | DOCX document | |
| Attachment D6_ Drawings 6 of 12.pdf | ||
| Attachment D7_ Drawings 7 of 12.pdf | ||
| Attachment D8_ Drawings 8 of 12.pdf | ||
| Attachment C_ Specifications.pdf | ||
| Attachment A_ Campus Map.pptx | PPTX presentation | |
| Attachment D1_ Drawings 1 of 12.pdf | ||
| Attachment D12_ Drawings 12 of 12.pdf | ||
| Attachment D4_ Drawings 4 of 12.pdf | ||
| Attachment D10_ Drawings 10 of 12.pdf | ||
| Attachment D11_ Drawings 11 of 12.pdf |
Show all 20
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DISCONNECTSTARTER
SIZE
SIZE FEEDER
BREAKERCIRCUIT #
NOTES
UNIT
ELECTRICAL
(MBH)
COMBINATION
NO.
TYPESENS.TOTAL (CFM)NO. MODELMANUFACTURER
COOLING CAPACITYAIR FLOW
MECHANICAL
DUCTLESS SPLIT FAN COIL UNIT SCHEDULE
FLA
PHASE
VOLTAGE/
TONS
NOMINAL
CONFIGURATION
MECHANICAL CONTRACTOR TO PROVIDE MANUFACTURER'S BACNET WIRED WALL THERMOSTAT AND LG PREMTBVC0.
UNIT SHALL BE SET TO COOLING ONLY.
(4)#12+(1)#12 IN 34"C
NOISE CRITERIA NC = 50.
(BTU/HR)
TOTAL
HEATING CAPACITY
(LB/HR)
TOTAL
HUMIDIFIER
PRESSURE
STATIC
(IN WC)
MOTOR
FAN
(HP)
MINIMUM
GPM
WEIGHT
(LBS)
AC-1-1 1.5 --706 LSN180HSV5LGSPLIT-SYSTEM WALL HUNG-- 10.918.0 1208V/1Ø 0.4A
NOTES
SIZE
FEEDER
(DEG. F) SIZEDISCONNECTSTARTERPHASENO.RLANO.
TEMP.TONSNO.
BREAKER
CIRCUIT #
COMBINATION
MCA
VOLTAGE /MODEL
MANF.
COMPRESSORAMBIENTNOMINALUNIT
ELECTRICALMECHANICAL
DUCTLESS SPLIT AIR COOLED CONDENSING UNITS
TYPE
FAN COIL UNIT
ASSOCIATED EER REFRIGERANT
FANS
COND.
NO. OF
OUTDOOR TYPE AIR COOLED CONDENSING UNITS TO SERVE DEDICATED INDOOR DX COOLING UNIT.
REFRIGERANT LINE SET TO BE SIZED AND PROVIDED BY THE MANUFACTURER. INSULATE SUCTION LINE AND COAT EXTERIOR WITH U.V. PROTECTION. MECHANICAL CONTRACTOR TO VERIFY EXACT REFRIGERANT ROUTE AND REFERENCE MANUFACTURER'S REFRIGERANT LONG LINE REQUIREMENTS.
PROVIDE A HOUSEKEEPING CURB OR PAD AND COOPER B-LINE DURA-BLOK ROOF PIPE SUPPORTS SPACED APART AT A MAXIMUM OF 4 FEET ITERVALS .
REFER TO ELECTRICAL PLANS
NOTES:
CU-1-1 1 1.5 115.0 R-410A AC-1-1 LG LSU180HSV5 208/1Ø 13.01 11012.58
(LBS)
WEIGHT
(MBH)
MFR. PROVIDED CIRCUITED THRU CU
MFR. PROVIDED
4544 5
CU-1-2 1 1.5 115.0 R-410A LG 208/1Ø1 110 2 3MFR. PROVIDED 4544 5
CU-1-3 1 2.0 115.0 R-410A LG 208/1Ø1 110 2 3MFR. PROVIDED 4544 5
CU-2-1 1 1.5 115.0 R-410A LG 208/1Ø1 110 2 3MFR. PROVIDED 4544 5
CU-14-1 1 1.5 115.0 R-410A LG 208/1Ø1 110 2 3MFR. PROVIDED 4544 5
CU-21-1 1 3.0 115.0 R-410A LG 208/1Ø1 110 2 3MFR. PROVIDED 4544 5
CU-23-1 1 1.5 115.0 R-410A LG 208/1Ø1 110 2 3MFR. PROVIDED 4544 5
CU-23-2 1 1.5 115.0 R-410A LG 208/1Ø1 110 2 3MFR. PROVIDED 4544 5
CU-24-1 1 1.5 115.0 R-410A LG 208/1Ø1 110 2 3MFR. PROVIDED 4544 5
CU-27-1 1 1.5 115.0 R-410A LG 208/1Ø1 110 2 3MFR. PROVIDED 4544 5
CU-29-1 1 2.0 115.0 R-410A LG 208/1Ø1 110 2 3MFR. PROVIDED 4544 5
AC-1-2 1.5 -- LGSPLIT-SYSTEM WALL HUNG-- 10.918.0 208V/1Ø 0.4A 30MFR. PROVIDED CIRCUITED THRU CU 3
AC-1-3 2.0 -- LGSPLIT-SYSTEM WALL HUNG-- 17.820.2 208V/1Ø 0.4A 46MFR. PROVIDED CIRCUITED THRU CU 3
AC-2-1 1.5 -- LGSPLIT-SYSTEM WALL HUNG-- 10.918.0 208V/1Ø 0.4A 30MFR. PROVIDED CIRCUITED THRU CU 3
AC-14-1 1.5 -- LGSPLIT-SYSTEM WALL HUNG-- 10.918.0 208V/1Ø 0.4A 30MFR. PROVIDED CIRCUITED THRU CU 3
AC-21-1 3.0 -- LGSPLIT-SYSTEM WALL HUNG-- 21.830.3 208V/1Ø 0.4A 46MFR. PROVIDED CIRCUITED THRU CU 3
AC-23-1 1.5 -- LGSPLIT-SYSTEM WALL HUNG-- 10.918.0 208V/1Ø 0.4A 30MFR. PROVIDED CIRCUITED THRU CU 3
AC-23-2 1.5 -- LGSPLIT-SYSTEM WALL HUNG-- 10.918.0 208V/1Ø 0.4A 30MFR. PROVIDED CIRCUITED THRU CU 3
AC-24-1 1.5 -- LGSPLIT-SYSTEM WALL HUNG-- 10.918.0 208V/1Ø 0.4A 30MFR. PROVIDED CIRCUITED THRU CU 3
AC-27-1 1.5 -- LGSPLIT-SYSTEM WALL HUNG-- 10.918.0 208V/1Ø 0.4A 30MFR. PROVIDED CIRCUITED THRU CU 3
AC-29-1 2.0 -- LGSPLIT-SYSTEM WALL HUNG-- 17.820.2 208V/1Ø 0.4A 46MFR. PROVIDED CIRCUITED THRU CU 3
MODEL NO.MANF.(IN. W.C.)
PRESSURE
STATICMINIMUM
AIRFLOW
(CFM)(CFM)
AIRFLOW
MAXIMUM
(INCHES)
SIZENO.
INLETUNIT
MECHANICAL
SUPPLY TERMINAL UNIT SCHEDULE
POWER FOR CONTROLS
VOLTAGE/
PHASE
DISCONNECT CIRCUIT BREAKER FEEDER
SIZESIZE
EMER
POWER
POWER
(VA)
ELECTRICAL
NOTESL.W.T.
(DEG. F.)
VALVE
TYPE(FT. HD)
W.P.D.FLOW
(GPM)(DEG. F.)
E.W.T.L.A.T.
(DEG. F.)(DEG. F.)
E.A.T.
(BTU/HR)
HEAT OUTPUT
HEATING COIL
NO SDVPRICEVAV-1-1 4008" DIA 0.3 120V / 1Ø 15 TOGGLE
REFER TO ELECTRICAL DRAWINGS FOR DETAILS.1
1 1 2
NO SDVPRICEVAV-1-2 8" DIA 0.3 120V / 1Ø 15 TOGGLE 1 1
NO SDVPRICEVAV-8-1 8" DIA 0.3 120V / 1Ø 15 TOGGLE 1 1
NO SDVPRICEVAV-8-2 8" DIA 0.3 120V / 1Ø 15 TOGGLE 1 1
NO SDVPRICEVAV-8-3 8" DIA 0.3 120V / 1Ø 15 TOGGLE 1 1
NO SDVPRICEVAV-8-4 10" DIA 0.3 120V / 1Ø 15 TOGGLE 1 1
NO SDVPRICEVAV-8-5 10" DIA 0.3 120V / 1Ø 15 TOGGLE 1 1
NO SDVPRICEVAV-8-6 8" DIA 0.3 120V / 1Ø 15 TOGGLE 1 1
MANUFACTURERMODEL NUMBERFINISHMATERIALLOCATION & MOUNTINGAIR PATTERNNECK SIZEFACE SIZE(FRAME SIZE)UNIT NO.
MECHANICAL
DIFFUSER, GRILLE, & REGISTER SCHEDULE
AIRFLOW, CFM
MODULE SIZE
1 REFER TO REFLECTED CEILING PLAN SURFACE TYPE. SURFACE TYPE MAY BE A LAY-IN CEILING TILE.
PROVIDE WITH SQUARE TO ROUND ADAPTOR.
REFER TO DRAWINGS FOR THROW PATTERNS.
PROVIDE WITH SQUARE TO ROUND ADAPTER, UNLESS LOCATED IN HARD CEILINGS. THEN NECK SIZE SHALL MATCH FACE SIZE.
IF IN HARD CEILING THEN PROVIDE WITH PLASTER FRAME.
INCLUDE SOUND INSULATED RETURN AIR BOOT.
NOTES:
RG-1 - 11100 -1250 22" X 12" 20" x 10" PRICEWHITEALUMINUM56
TG-1 - 1101 - 200 10" x 4" PRICEWHITEALUMINUM56 60
3SD-1 WHITE RECTANGULAR DIFFUSER W/ LOUVERED FACE1000 - 1400 PRICESMD2 1 5
SD-2 WHITE101 - 200 PRICESMD2
22" x 22" 18" x 18"24" x 24"
4-WAY
RETURN GRILLE; 45 DEG. FIXED DEFLECTION; 3/4" BLADE
SPACING; BLADES PARALLEL TO FLOOR.20" x 10"
RETURN GRILLE; 45 DEG. FIXED DEFLECTION; 3/4" BLADE
SPACING; BLADES PARALLEL TO FLOOR.10" x 4"12" x 6"
REFER TO ELECTRICAL POWER PLAN FOR INFORMATION.
MECHANICAL CONTRACTOR TO PROVIDE PROBE TOOL, DRI-STEEM DESCALE SOLUTION, SHOCK ARRESTERS, WATER FILTER, UNIONS, SPILL FUNNEL, DRANE KOOLER, AIR PROVING SWITCH, SDU, AND AIR GAP.
PROVIDE BACNET COMMUNICATION CARD.
COMPLY WITH ARI 640, "COMMERCIAL AND INDUSTRIAL HUMIDIFIERS." ELECTRICAL COMPONENTS, DEVICES, AND ACCESSORIES SHALL BE LISTED AND LABELED AS DESIGNED IN NFPA 70 ARTICLE 100 BY A TESTING AGENCY ACCEPTABLE TO AUTHORITIES HAVING JURISDICTION AND MARKED FOR INTENDED USE.
PROVIDE A PIPE DRIP TROUGH FOR ALL EXPOSED WATER PIPES. SLANT TROUGH 18" PER FOOT AWAY FROM ELECTRONICS.
PROVIDE MANUFACTURER'S HIGH CAPACITY HIGH TEMP CONDENSATE PUMP DOWNSTREAM OF DRANE KOOLER.
UNITS H1-7 REQUIRED TO HAVE DISPERSION MOUNTED IN DUCTWORK, SEE FLOOR PLANS FOR MORE INFORMATION.
NOTES:
MECHANICAL
UNIT CAPACITY MANF. MODEL VOLTAGE/ kW
NO. (LBS/HR) NO. PHASE
STEAM HUMIDIFIER WITH DISTRIBUTION UNIT SCHEDULE (ELECTRIC-TO-STEAM TYPE)
ELECTRICAL
SIZESIZEFUSE
WEIGHT
FEEDERBREAKERCIRCUIT #
COMBINATION
DISCONNECT
ROOM
SETPOINT
(RELATIVE
HUMIDITY)
HIGH LIMIT DISCHARGE AIR
SETPOINT (RELATIVE
HUMIDITY)
SERVICE
6 DRI-STEEM VAPOR MIST - 2 120/1Ø45% 80% TELECOM ROOM
CURRENT
DRAW
(AMPS)
16.7
NOTES
1 2 3110
(OPERATING)
(LBS)
--2.0 REFER TO ELECTRICAL PLANS 4 5--
D.B. R.H.
O.A. CONDITIONS
32F 7%
WIDTH HEIGHT
DUCT
CFM % O.A.
-- -- 706 30%
ENT. DISTRIBUTOR
TEMP. R.H.
LVG. DISTRIBUTOR
TEMP. R.H.
68F 45%
MAX
36" @ 68F
ABSOROPTION
DISTANCE
H 1-1
H 1-2
H 1-3
H 1-4
H 1-5
H 1-6
H 1-7
H 1-8
H 1-9
H 1-10
H 1-11
H 1-12
H 1-13
H 1-14
H 1-15
H 2-1
H 8-1
H 8-2
H 8-3
H 8-4
H 8-5
H 8-6
H 8-7
H 8-8
H 14-1
H 21-1
H 23-1
H 23-2
H 24-1
H 27-1
H 28-1
H 29-1
H 31-1
H 31-2
H 34-1
H 34-2
ALUMINUM
ALUMINUM
1 2
1 2
1 2
1 2
1 2
1 2
1 2
1 2
1 2
1 2
POWER
EMERGENCY
NO
TG-2 - 1201-350 10" x 6" PRICEWHITEALUMINUM56 60
RETURN GRILLE; 45 DEG. FIXED DEFLECTION; 3/4" BLADE
SPACING; BLADES PARALLEL TO FLOOR.10" x 6"12" x 8"
H 37-1
RG-2 - 11000 -1200 24" X 24" 22" x 22" PRICEWHITEALUMINUM56 10A RETURN GRILLE WITH PERFORATED FACE, 3/16 DIA HOLES.22" x 22"
LSN180HSV5
LSN240HLV
LSN180HSV5
LSN180HSV5
LSN360HLV
LSN180HSV5
LSN180HSV5
LSN180HSV5
LSN180HSV5
13.0
23.0
13.0
13.0
23.0
13.0
13.0
13.0
13.0
23.0
LSU180HSV5
LSU240HSV5
LSU180HSV5
LSU180HSV5
LSU360HLV
LSU180HSV5
LSU180HSV5
LSU180HSV5
LSU180HSV5
12.58
12.50
12.58
12.58
8.20
12.58
12.58
12.58
12.58
12.50
AC-1-2
AC-1-3
AC-2-1
AC-14-1
AC-21-1
AC-23-1
AC-23-2
AC-24-1
AC-27-1
AC-29-1
12" x 12" 10" x 10" 8" DIA 1 5 RECTANGULAR DIFFUSER W/ LOUVERED FACE
SD-3 WHITE351-600 PRICESMD2 4-WAY ALUMINUM1 5 RECTANGULAR DIFFUSER W/ LOUVERED FACE12" DIA 18" x 18"24" x 24"
RG-3 - 1201-400 PRICEWHITEALUMINUM56 10A RETURN GRILLE WITH PERFORATED FACE, 3/16 DIA HOLES.12" x 12" 10" x 10" 10" DIA
PROVIDE (4)#12 +(1)#12 IN 34"C2
AC-1-4 2.0 -- LGSPLIT-SYSTEM WALL HUNG-- 17.820.2 208V/1Ø 0.4A 46MFR. PROVIDED CIRCUITED THRU CU 3 1 2 4706 LSN240HLV
CU-1-4 1 2.0 115.0 R-410A LG 208/1Ø1 110 2 3MFR. PROVIDED 4544 5 12523.0LSU240HSV512.50 AC-1-4
LSN240HLV
LSU240HSV5
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans
Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMP
321 4 5 6 7 8 9 10
SHEET OF
EHRM INFRASTRUCTURE
UPGRADES
644-20-201
Revisions: Date:
TL 602.606.7432
Phoenix, AZ 85012
3300 N. Central Ave, STE 1520 www.dheengineering.com
Job Number: 00961.00
Concourse Federal Group 123 S. Royal Street Alexander, VA 22314
04.01.2021 KYNJ
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
PVAHCS - Carl T Hayden Medical Center
650 E Indian School Road Phoenix AZ 85012
MECHANICAL AND ELECTRICAL
SCHEDULES