This document provides details for a federal contract solicitation for construction services. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 22 is seeking offers for Project 644-20-201 "Electronic Health Records Modernization (EHRM) Infrastructure Upgrades" to be performed at the VA Phoenix Healthcare System located at 650 East Indian School Road in Phoenix, Arizona. The work includes general construction, alterations, mechanical and electrical work, utility systems, necessary demolition and removal of existing structures with a total value between $10,000,000 and $20,000,000. All work must be performed according to applicable building codes and specifications. This procurement is set aside as 100% for Service-Disabled Veteran-Owned Small Businesses listed on the Vendor Information Pages database. An Invitation for Bid will be issued on June 3, 2021 via sam.gov and a site visit will be scheduled. Offers are due by August 3, 2021. The point of contact for this solicitation is Steven J. Covell.

View the file

Other files for this federal contract opportunity

Show all 20

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

EI001

ELECTRICAL ABBREVIATIONS,

SYMBOLS, AND LEGENDS

04.28.202105.26.2021

GENERAL

SHEET 24 of 421

TYPICAL DETAILS

Concourse Federal Group 11755 Wilshire Blvd, Suite 1250 Los Angeles CA 90025

EHRM INFRASTRUCTURE

UPGRADES -

PVAHCS - Carl T Hayden Medical Center 650 E Indian School Road Phoenix AZ 85012

644-20-201

Revisions: Date:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMP

321 4 5 6 7 8 9 10

BI

M

Ph oe ni x

EH

R M

/6

-2 0-

BL

D

G

8_ A.

rv t

9/ 6/

0:

:4

AM

CCSTEAM

4365 E. PECOS RD. - GILBERT, AZ. 85295

(602) 619-9710 - VOICE

OLYMPUS CONSTRUCTION MANAGEMENT

GENERAL NOTES:

KEYED NOTES:

04.01.2021

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

FRONT OF RACKS

7'-0"

FINISHED FLR

DOUBLE SIDED VERTICAL

CABLE MANAGEMENT

EQUIPMENT RACK

TO TRAY KIT

RACK USING RACK

MOUNT CABLETRAY TO

CABLOFIL 12"Wx4"D

LC

LC

3/8" THREADED ROD

TO DECK ABOVE

PENETRATIONS.

6" AFF

SYSTEM TO FIRESTOP THROUGH

6" MAX AFF. USE QUALIFIED

TERMINATE STUBS

4"C. (TYP)

RACK TO RUNWAY KIT

6' ON CENTER

MOUNT TRAPEZE EVERY

HANGING CLIP (TYP 2)

TRAPEZE

HUBBELL 24"W x 2"D

PLYWOOD, PAINTED WITH

3/4"x4'x8' FIRE RATED

TYP 3 PER ROW

MTD 5" AFF. (FBOT)

RETARDANT PAINT AND

TWO COATS OF FIRE

5"

BRACKET

TERMINATION

SPLICE WASHER

KIT (TYP 4)

7'-0"

TERMINATION

BRACKET

RACKS (STATION)

TO TELECOM

CABLEXIT

TYP 3 PER ROW

24"

TYP

HUBBELL 24"W x 2"D

3/4"x4'x8' FIRE RATED

PLYWOOD, PAINTED WITH

TWO COATS OF FIRE

RETARDANT PAINT AND

FINISHED FLR

6"

MTD 5" AFF. (FBOT)

2" .75"3.25"

6"

4"C. (TYP)

TERMINATE STUBS

6" MAX AFF. USE QUALIFIED

SYSTEM TO FIRESTOP THROUGH

PENETRATIONS.

STI FIRESTOP

SEE SHEET T802 FOR DETAILS

SCALE:

T8.1

CABLETRAY TO EQUIPMENT RACK DETAIL AT WALL

NTS SCALE:

T8.1

EQUIPMENT RACK TYPICAL SIDE ELEVATION

NTS

SUPPORT GROUNDING CABLE

CLIP EVERY 2.5 FEET TO

** USE PLASTIC CABLE

EACH SECTION OF CABLETRAY

** USE ONE GROUNDING LUG WITH

GROUNDING LUG

12" X 4" CABLETRAY

FAST SPLICE

NOTE:

SIDE OF CABLETRAY.

USE TWO (2) SPLICES ON EACH

PRE-PRINTED UNIQUE

LABELS 6 INCHES FROM TERMINATION, BOTH

PRE-PRINTED UNIQUE WRAPAROUND ADHESIVE

ENDS OF ALL LOW VOLTAGE CABLE.

XXX-YZZ

XXX

XXX

XXX

ADHESIVE WRAPAROUND LABEL

LABEL SEQUENCE: TR(#)-PATCH(#)PORT(#)

SCALE:

T8.1

CABLE LABELING DETAIL

NTS

SCALE:

T8.1

FAST SPLICE DETAIL

NTS

PRE-PRINTED UNIQUE

ADHESIVE WRAPAROUND LABEL

XXX-YZZ

TN501

04.28.202105.26.2021

SHEET 25 of 421

FOOTER

11 12"

16"16"

TO CABLE BASKET

1 IN. CONDUIT

SCALE: SCALE:

EMT CONDUIT WITH BUSHED ENDS

FIRE SEAL BY CONDUIT INSTALLER

APPROVED PLENUM RATED CABLE

3" MAX

FIRE SEAL WITH APPROVED

CAULK OR PUTTY BY CABLE

INSTALLER

SCALE:

A

A

SECTION A-A

24" O.C.

SCALE:

CABLE BASKET

(TYP.)

LAY-IN CEILING

FIRESTOP ASSEMBLY

SEE DETAIL 3/T802

4" (MIN)

T802

CABLE BASKET/CABLE BASKET THRU WALL SECTION - FIRESTOP - STI SERIES 44

NTS

T802

THRU WALL FIRESTOP ASSEMBLY - - STI SERIES 44

NTS

T802

CONDUIT THRU FIRE RATED WALL - SECTION

NTS

T802

STANDARD NETWORK OUTLET

NTS

COMMUNICATIONS OUTLET BOX

4-11/16"Wx4-11/16"Hx2-1/8"D

SQUARE BOX RACO 265 W/SINGLE

DEVICE COVER (OR EQUAL)

LEVEL OF FINISHED

FLOOR

SCALE:

CABLOFIL 12" X 4" CABLE

BASKET

3/8"-16 ALL THREADED ROD W/

THREADED ROD PROTECTOR

SCALE:

5/16-18 X 2 1/4" J-BOLT

W/ 5/16-18 HEX NUTS AND LOCK WASHERS

CABLOFIL 12" X 4" CABLE

BASKET

T802

CABLE BASKET - WALL MOUNTING ANGLE

NTS

T802

CABLE BASKET SUPPORT - SINGLE

NTS

TYPICAL DETAILS

Concourse Federal Group 11755 Wilshire Blvd, Suite 1250 Los Angeles CA 90025

EHRM INFRASTRUCTURE

UPGRADES -

PVAHCS - Carl T Hayden Medical Center 650 E Indian School Road Phoenix AZ 85012

644-20-201

Revisions: Date:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMP

321 4 5 6 7 8 9 10

BI

M

Ph oe ni x

EH

R M

/6

-2 0-

BL

D

G

8_ A.

rv t

9/ 6/

0:

:4

AM

CCSTEAM

4365 E. PECOS RD. - GILBERT, AZ. 85295

(602) 619-9710 - VOICE

OLYMPUS CONSTRUCTION MANAGEMENT

GENERAL NOTES:

KEYED NOTES:

04.01.2021

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED TN502

04.28.202105.26.2021

SHEET 26 of 421

SCALE: SCALE:

5/16-18 X 2 1/4" J-BOLT

W/ 5/16-18 HEX NUTS AND LOCK WASHERS

CABLE RUNWAY

CABLE RUNWAY

5/16-18 X 2 1/4" J-BOLT

W/ 5/16-18 HEX NUTS AND LOCK WASHERS

ANGULAR WALL

SUPPORT BRACKET

NOTES:

1. BRACKET SPACING 8' O.C. 2' @ THE CORNERS.

2. ATTACH TO DRYWALL W/ 1/2" X 2 1/2" MUSHROOM HEAD

TOGGLE BOLT.

3. ATTACH TO CONCRETE W/ 1/2" HOLLOW SET DROP IN

ANCHOR, 1/2" X 1" HEX HEAD FLANGE SCREW.

SCALE:

SCALE:

CABLE RUNWAY

CABLE RUNWAY

BUTT SPLICE KIT

JUNCTION

SPLICE KIT

THREADED ROD COVER

SCALE:

NOTES:

1. HANGER SPACING 5' O.C.

T803

CABLE RUNWAY - THREADED ROD HANGER

NTS

T803

CABLE RUNWAY - BUTT SPLICE

NTS

T803

CABLE RUNWAY - JUNCTION SPLICE

NTS

T803

CABLE RUNWAY - TRIANGULAR SUPPORT BRACKET

NTS

T803

CABLE RUNWAY - WALL MOUNTING ANGLE

NTS

TYPICAL DETAILS

Concourse Federal Group 11755 Wilshire Blvd, Suite 1250 Los Angeles CA 90025

EHRM INFRASTRUCTURE

UPGRADES -

PVAHCS - Carl T Hayden Medical Center 650 E Indian School Road Phoenix AZ 85012

644-20-201

Revisions: Date:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMP

321 4 5 6 7 8 9 10

BI

M

Ph oe ni x

EH

R M

/6

-2 0-

BL

D

G

8_ A.

rv t

9/ 6/

0:

:4

AM

CCSTEAM

4365 E. PECOS RD. - GILBERT, AZ. 85295

(602) 619-9710 - VOICE

OLYMPUS CONSTRUCTION MANAGEMENT

GENERAL NOTES:

KEYED NOTES:

04.01.2021

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED TN503

04.28.202105.26.2021

SHEET 27 of 421

TYPICAL DETAILS

Concourse Federal Group 11755 Wilshire Blvd, Suite 1250 Los Angeles CA 90025

EHRM INFRASTRUCTURE

UPGRADES -

PVAHCS - Carl T Hayden Medical Center 650 E Indian School Road Phoenix AZ 85012

644-20-201

Revisions: Date:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMP

321 4 5 6 7 8 9 10

BI

M

Ph oe ni x

EH

R M

/6

-2 0-

BL

D

G

8_ A.

rv t

9/ 6/

0:

:4

AM

CCSTEAM

4365 E. PECOS RD. - GILBERT, AZ. 85295

(602) 619-9710 - VOICE

OLYMPUS CONSTRUCTION MANAGEMENT

REFERENCE ARCHITECTURAL AND ELECTRICAL SHEETS FOR ALL DOOR TYPES,

ENCLOSURES, FRAME DETAILS AND PATHWAYS. DETAILS SHOWN ON THIS SHEET ARE

DIAGRAMMATIC ONLY AND TO BE USED AS REFERENCE FOR TERMINATION PURPOSES

ONLY.

GENERAL NOTES:

ONE (1) COMPOSITE CABLE FOR CARD READER, RTE AND DOOR CONTACTS:

1. ONE (1) 18/4

2. TWO (1) 22/4

3. ONE (1) 22/6

KEYED NOTES:

04.01.2021

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

FINISH CEILING

FINISH FLOOREXTERIOR VIEW

FINISH CEILING

FINISH FLOORINTERIOR VIEW

JUNCTION

BOX

TO ACCESS

CONTROL HEAD-END

JUNCTION

BOX

DUAL

AUTHENTICATION

CARD READER AND

PIN NUMBER

(EXTERIOR)

TO ACCESS

CONTROL HEAD-END

(1) 3 4"C

BY OTHERS

(1) 3 4"C

BY OTHERS

(1) 3 4"C

BY OTHERS

ELECTRIFIED HINGE AND

CRASH BAR (PROVIDED BY

OTHERS) ELECTRIC HINGE

(1) 3 4"C

BY OTHERS

(1) 3 4"C

BY OTHERS

ELECTRIC HINGE

(1) 3 4"C

BY OTHERS

(1) 3 4"C

BY OTHERS

FINISH CEILING

FINISH FLOOR

DUAL

AUTHENTICATION

CARD READER AND

PIN NUMBER

(EXTERIOR)

FINISH CEILING

FINISH FLOOR

ELECTRIC STRIKE

(PROVIDED BY

OTHERS)

INTERIOR VIEW EXTERIOR VIEW

ELECTRIC STRIKE

(PROVIDED BY

OTHERS)

JUNCTION

BOX

TO ACCESS

CONTROL HEAD-END

(1) 3 4"C

DROP ABOVE CEILING

DOOR CONTACT

(1) 3 4"C

DROP ABOVE CEILING

DOOR CONTACT

SCALE:

T8.3

DUAL CARD ACCESS DOOR TYPICAL DETAIL

NTS

SCALE:

T8.3

SINGLE CARD ACCESS DOOR TYPICAL DETAIL

NTS

TN504

04.28.202105.26.2021

SHEET 28 of 421

FIBER OPTIC BACKBONE RISER

DIAGRAM - BUILDING 1Concourse Federal Group

11755 Wilshire Blvd, Suite 1250 Los Angeles CA 90025

EHRM INFRASTRUCTURE

UPGRADES -

PVAHCS - Carl T Hayden Medical Center 650 E Indian School Road Phoenix AZ 85012

644-20-201

Revisions: Date:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMP

321 4 5 6 7 8 9 10

BI

M

Ph oe ni x

EH

R M

/6

-2 0-

BL

D

G

8_ A.

rv t

9/ 6/

0:

:4

AM

CCSTEAM

4365 E. PECOS RD. - GILBERT, AZ. 85295

(602) 619-9710 - VOICE

OLYMPUS CONSTRUCTION MANAGEMENT

FIRST FLOOR

SECOND FLOOR

THIRD FLOOR

FOURTH FLOOR

FIFTH FLOOR

SIXTH FLOOR

DATA CENTER

TR

1411 (1609A)

TR

S000A

TR

E104D

TR

TRS-200A

TR

TRS-300A

TR

TRS-400A

TR

TRS-500A

TR

TRS-600A

BASEMENT LEVEL

TR

TRN-200A

TR

TRN-300A

TR

TRN-400A

TR

1321A

TR

TR

C185

TR

TR

K132

TR

K131

3 1

2 2 2 2 4

DO NOT TERMINATE BUNDLED CABLES IN EACH CLOSET. MULTIPLE FIBER OPTIC CABLES

ARE BUNDLES AND PASSED THROUGH TR STACKS (ROOMS) TO SERVE MULTIPLE

FLOORS. PROVIDE AND INSTALL ONE (1) 24-STRAND ARMORED SM FIBER OPTIC CABLE

TO EACH TR.

BACKBONE FIBER 'A' AND 'B' ARE TO BE ROUTED WITHIN SEPARATE CONDUIT

PATHWAYS AND DISTRIBUTED FROM SEPARATE ENDS OF EACH TR

TR

C221

TR

C321

TR

C421A

1 1

1 1

1 1

TR

DCC4B

TR

C612

TR

C129

GENERAL NOTES:

ONE (1) EACH 24-STRAND OM4 ARMORED MULTI-MODE & 12-STRAND OS1

ARMORED SINGLE MODE FIBER OPTIC CABLE.

TWO (2) EACH 24-STRAND OM4 ARMORED MULTI-MODE & 12-STRAND OS1

ARMORED SINGLE MODE FIBER OPTIC CABLE.

THREE (3) EACH 24-STRAND OM4 ARMORED MULTI-MODE & 12-STRAND OS1

ARMORED SINGLE MODE FIBER OPTIC CABLE.

FOUR (4) EACH 24-STRAND OM4 ARMORED MULTI-MODE & 12-STRAND OS1

ARMORED SINGLE MODE FIBER OPTIC CABLE.

FIVE (5) EACH 24-STRAND OM4 ARMORED MULTI-MODE & 12-STRAND OS1

ARMORED SINGLE MODE FIBER OPTIC CABLE.

SIX (6) EACH 24-STRAND OM4 ARMORED MULTI-MODE & 12-STRAND OS1

ARMORED SINGLE MODE FIBER OPTIC CABLE.

SEVEN (7) EACH 24-STRAND OM4 ARMORED MULTI-MODE & 12-STRAND OS1

ARMORED SINGLE MODE FIBER OPTIC CABLE.

EIGHT (8) EACH 24-STRAND OM4 ARMORED MULTI-MODE & 12-STRAND OS1

ARMORED SINGLE MODE FIBER OPTIC CABLE.

ONE (1) EACH 24-STRAND OM4 ARMORED MULTI-MODE & 12-STRAND OS1

(UNDERFLOOR).

KEYED NOTES:

04.01.2021

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

FIBER 'A'

FIBER 'A' FIBER 'B'

FIBER 'B'

FIBER 'B'

FIBER 'B'

FIBER 'B'

FIBER 'B' FIBER 'A'

FIBER 'B'

FIBER 'A'

FIBER 'A'

FIBER 'B'

FIBER 'B'

FIBER 'B'

FIBER 'A'

FIBER 'B'FIBER 'B'

FIBER 'A' FIBER 'B' FIBER 'A'

FIBER 'B'

FIBER 'A/B'

FIBER 'A'/'B' FIBER 'A'/'B' FIBER 'A'/'B' FIBER 'A'/'B' FIBER 'A'/'B'

FIBER 'A/B'

FIBER 'A'/'B'

FIBER 'A'/'B'

FIBER 'A/B'

TN601

04.28.202105.26.2021

SHEET 29 of 421

FIBER OPTIC BACKBONE RISER

DIAGRAM - BUILDINGS 2 / 8Concourse Federal Group

11755 Wilshire Blvd, Suite 1250 Los Angeles CA 90025

EHRM INFRASTRUCTURE

UPGRADES -

PVAHCS - Carl T Hayden Medical Center 650 E Indian School Road Phoenix AZ 85012

644-20-201

Revisions: Date:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMP

321 4 5 6 7 8 9 10

BI

M

Ph oe ni x

EH

R M

/6

-2 0-

BL

D

G

8_ A.

rv t

9/ 6/

0:

:4

AM

CCSTEAM

4365 E. PECOS RD. - GILBERT, AZ. 85295

(602) 619-9710 - VOICE

OLYMPUS CONSTRUCTION MANAGEMENT

FIRST FLOOR

DATA CENTER

TR

1411 (1609A)

TR

A2446

TR

A2208

TR

A1034

TR

A0115

BUILDING 1

TR

A2021

TRTR

A1218

TRTR

A1428

TR

BUILDING 8

TR

A0600

SECOND FLOOR

BASEMENT LEVEL

DO NOT TERMINATE BUNDLED CABLES IN EACH CLOSET. MULTIPLE FIBER OPTIC CABLES

ARE BUNDLES AND PASSED THROUGH TR STACKS (ROOMS) TO SERVE MULTIPLE

FLOORS. PROVIDE AND INSTALL ONE (1) 24-STRAND ARMORED SM FIBER OPTIC CABLE

TO EACH TR.

BACKBONE FIBER 'A' AND 'B' ARE TO BE ROUTED WITHIN SEPARATE CONDUIT

PATHWAYS AND DISTRIBUTED FROM SEPARATE ENDS OF EACH TR

GENERAL NOTES:

TWO (2) EACH 24-STRAND OM4 ARMORED MULTI-MODE & 12-STRAND OS1

ARMORED SINGLE MODE FIBER OPTIC CABLE.

FOUR (4) EACH 24-STRAND OM4 ARMORED MULTI-MODE & 12-STRAND OS1

ARMORED SINGLE MODE FIBER OPTIC CABLE.

SIX (6) EACH 24-STRAND OM4 ARMORED MULTI-MODE & 12-STRAND OS1

ARMORED SINGLE MODE FIBER OPTIC CABLE.

KEYED NOTES:

04.01.2021

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

FIBER 'A/B'

FIBER 'A/B'

FIBER 'A/B'

FIBER 'A/B'FIBER 'A/B'FIBER 'A/B'

FIBER 'A/B'

FIBER 'A/B'

FIBER 'A/B'

FIBER 'A/B'

TN602

04.28.202105.26.2021

SHEET 30 of 421

Phoenix VA Healthcare System Carl T. Hayden Medical Center

650 E Indian School Rd, Phoenix AZ 85012

Indian School RdIndian School Rd

E Osborn Rd

N C en tr a l A ve

N th S t

N th

S t

N th

S t

E Camelback Rd

E Meadowbrook Ave

Grand Canal

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMP

321 4 5 6 7 8 9 10

DEPARTMENT OF VETERNS AFFAIRS

100% CD SUBMISSION

SITE MAPDESIGN TEAM

SHEET OF

SHEET INDEX

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

B

IM

/P h o e n ix

E H

R M

/6

-2

-2

B

L D

G

A .r v t

/2

/2

:1

:3

P

M

01-GI001

COVER SHEET

Concourse Federal Group

123 S. Royal Street

Alexandria, VA 22314

EHRM INFRASTRUCTURE

UPGRADES 01

05.26.2021

PVAHCS - Carl T Hayden Medical Center 650 E Indian School Road Phoenix AZ 85012

EHRM INFRASTRUCTURE UPGRADES

MAY 26, 2021

PVAHCS - Carl T Hayden Medical Center

644-20-201

Building 01

N

OWNER

Phoenix VA Health Care System, Carl T. Hayden Medical Center James Larson, Contracting Officer Representative james.larson2@va.gov

VA Network 22 Contracting Office, Long Beach, CA Steven Covell, Contracting Officer steve.covell@va.gov

ARCHITECT/PRIME CONTRACT

Concourse Federal Group 123 S. Royal Street Alexandria, Virginia 22314

Tim Hower, PE, PMP, MBA, Project Manager thower@awensolutions.com Ann Turner, Deputy Project Manager aturner@awensolutions.com Gene Klow, Principal Architect gklow@awensolutions.com Clark Garrett, AIA, NCARB, CSI, CDT cgarrett@awensolutions.com Christy Winson, NCIDQ, Interior Designer cwinson@awensolutions.com Matt Shuba, AIA mshuba@awensolutions.com Dawn Harrington dharrington@awensolutions.com Anna Kim akim@awensolutions.com Caz Rebach crebach@awensolutions.com Marshall Contino, Concourse A|E Vice President mcontino@awensolutions.com

STRUCTURAL ENGINEER

Gregory P Luth & Associates, Inc 3350 Scott Blvd, Santa Clara, CA 95054

Greg Luth greg@gplainc.com Trupti Sonavane, AIA trupti@gplainc.com Bala Surampudi bala@gplainc.com

FIRE PROTECTION

Coffman Engineers 8171 Maple Lawn Blvd #250, Fulton, MD 20759

Scott Knight, PE, Engineer scott.knight@coffman.com

MECHANICAL/ELECTRICAL ENGINEER

DHE Engineering 3300 N. Central Ave. 3300 Tower Suite, 1520, Phoenix, AZ 85012

Nate Jones, P.E., Principal, Electrical Engineer njones@dheeng.com Kory Young, EIT, Senior Mechanical Engineer kyoung@dheeng.com Jasper Lim, Electrical Engineer jlim@dheeng.com

LOW-VOLTAGE DESIGN

Olympus Construction Management 4365 E Pecos Rd Ste 120, Gilbert, AZ 85295

Chris Stowers, Project Manager chris.stowers@olympusCM.com

SEE SHEET 01-GI002 FOR SHEET INDEX

Revisions: Date: 05.26.2021 SHEET 31 of 421

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMP

321 4 5 6 7 8 9 10

SHEET OF

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

B

IM

/P h o e n ix

E H

R M

/6

-2

-2

B

L D

G

A .r v t

/2

/2

:1

:3

P

M

01-GI002

GENERAL NOTES, CODE

REQUIREMENTS, AND SHEET INDEXConcourse Federal Group

123 S. Royal Street

Alexandria, VA 22314

EHRM INFRASTRUCTURE

UPGRADES 01

05.26.2021

PVAHCS - Carl T Hayden Medical Center 650 E Indian School Road Phoenix AZ 85012

644-20-201

BUILDING CLASSIFICATION:

BASIC OCCUPANCY GROUP(S):

(NFPA 101 6.1.5)

OCCUPANCY GROUP I

CONSTRUCTION TYPE:

(EXISTING)

TYPE II 222, SPRINKLERED

BASIC ALLOWABLE AREA:

(222 FULLY SPRINKLERED)

OCCUPANCY GROUP I-2 – UNLIMITED

ACTUAL HEIGHT

8 STORY HOSPITAL + PARTIAL BASEMENT

MINIMUM FIRE RESISTIVE REQUIREMENTS:

(NFPA 220, TABLE 4.1.1) (APPLICABLE ELEMENTS)

ELEMENT RATING

STRUCTURAL FRAME 2-HOUR (Y710, U424)

STRUCTURAL FRAME, SUPPORTING ROOF ONLY 1-HOUR (Y710, U424)

FLOORS AND FLOOR/CEILINGS 2-HOUR (H505)

ROOFS AND ROOF/CEILINGS 1-HOUR (H505)

HORIZONTAL EXIT 2-HOUR

SMOKE BARRIER (COMPARTMENTS) 1/2-HOUR

HAZARDOUS AREA SEPARATIONS 1-HOUR

SOILED LINEN ROOMS 1-HOUR

STORAGE ROOMS > 100 SF 1-HOUR

CORRIDORS

(NFPA 101 CHAPTER 38.3.6.1)

EXCEPTION 3, WITHIN BUILDINGS PROTECTED THROUGHOUT

BY AN APPROVED AUTOMATIC SPRINKLER SYSTEM, 1-HOUR

FIRE RESISTANCE RATING IS NOT REQUIRED.

STEEL FIREPROOFING; SQUARE AND RETANGULAR HSS

1. SPRAY-APPLIED FIRE RESISTIVE MATERIALS: UL Y710

2. ENCAPSULATED IN 2-HR WALL CONSTRUCTION: UL U424

3. ENCAPSULATED IN 2-HR FLOOR/CEILING CONSTRUCTION: UL H505

MAXIMUM TRAVEL DISTANCE TO EXITS

(NFPA 101, CHAPTER 39)

TRAVEL DISTANCE 200-FEET

COMMON PATH OF TRAVEL 100-FEET

DEAD-END CORRIDOR 50-FEET

FIRE SUPPRESSION

THE FACILITY WILL BE FULLY SPRINKLERED PER NFPA 13

HANDHELD FIRE SPRINKLERS WILL BE INSTALLED IN EACH IDF ROOM

OCCUPANT LOAD CALCULATIONS:

(PER NFPA 101, Table 7.3.1.2)

BUSINESS USE: 150 SF/OCC

INPATIENT TREATMENT DEPARTMENTS: 250 SF/OCC

SLEEPING DEPARTMENTS: 120 SF/OCC

AMBULATORY HEALTH CARE: 150 SF/OCC

USE 120 SF PER OCCUPANT (MOST RESTRICTIVE)

EXISTING EXIT SYSTEM CAPACITY

BASEMENT: ~49,633 SF, NO ADDED AREA

1ST FLOOR: ~67,120 SF (WINGS C, D, & E), NO ADDED AREA

2ND FLOOR: ~55,715 SF (WINGS C, D, & E), 677 ADDED AREA

EXISTING OCC LOAD: 465, ADDED OCC LOAD: 6

EXISTING STAIR CAPACITY FACTOR: 465x0.3=139.5 EXISTING DOOR CAPACITY FACTOR: 465x0.2=93.0*

EXISTING CAPACITY: 210 (STAIRS 1, 2, 3, 6, & 7) (*FROM DR WIDTH)

ADDED CAPACITY FACTOR: 6x0.2=1.2, THERFORE OK

3RD FLOOR: ~55,678 SF (WINGS C, D, & E), 677 ADDED AREA

EXISTING OCC LOAD: 464, ADDED OCC LOAD: 6

EXISTING STAIR CAPACITY FACTOR: 464x0.3=139.2 EXISTING DOOR CAPACITY FACTOR: 464x0.2=92.8*

EXISTING CAPACITY: 210 (STAIRS 1, 2, 3, 6, & 7) (*FROM DR WIDTH)

ADDED CAPACITY FACTOR: 6x0.2=1.2, THERFORE OK

4TH FLOOR: ~55,678 SF (WINGS C, D, & E), 677 ADDED AREA

EXISTING OCC LOAD: 464, ADDED OCC LOAD: 6

EXISTING STAIR CAPACITY FACTOR: 464x0.3=139.2 EXISTING DOOR CAPACITY FACTOR: 464x0.2=92.8*

EXISTING CAPACITY: 210 (STAIRS 1, 2, 3, 6, & 7) (*FROM DR WIDTH)

ADDED CAPACITY FACTOR: 6x0.2=1.2, THERFORE OK

5TH FLOOR: ~30,654 SF (WINGS C, & D, 321 ADDED AREA

EXISTING OCC LOAD: 256, ADDED OCC LOAD: 3

EXISTING STAIR CAPACITY FACTOR: 256x0.3=76.8 EXISTING DOOR CAPACITY FACTOR: 465x0.2=51.2*

EXISTING CAPACITY: 126 (STAIRS 1, 2, & 3) (*FROM DR WIDTH)

ADDED CAPACITY FACTOR: 3x0.2=0.6, THERFORE OK

6TH FLOOR: ~30,654 SF (WINGS C, & D, 321 ADDED AREA

EXISTING OCC LOAD: 256, ADDED OCC LOAD: 3

EXISTING STAIR CAPACITY FACTOR: 256x0.3=76.8 EXISTING DOOR CAPACITY FACTOR: 465x0.2=51.2*

EXISTING CAPACITY: 126 (STAIRS 1, 2, & 3) (*FROM DR WIDTH)

ADDED CAPACITY FACTOR: 3x0.2=0.6, THERFORE OK

STAIR 1: 48" WIDE, 42" DOOR STAIR 2: 48" WIDE, 42" DOOR

STAIR 3: 48" WIDE, 42" DOOR STAIR 6: 60" WIDE, 42" DOOR

STAIR 7: 48" WIDE, 42" DOOR

EXPANDED SMOKE COMPARTMENT ZONES

2ND FLOOR

SMOKE ZONE 2DC: ~6,8198 SF (INCLUDES ADDED SOUTH TR TOWER)

SMOKE ZONE 2E: ~15,687 SF (NO SLEEPING) (INCLUDES ADDED NORTH TR TOWER)

3RD FLOOR

SMOKE ZONE 3DC: ~6,8198 SF (NO SLEEPING) (INCLUDES ADDED SOUTH TR TOWER)

SMOKE ZONE 3E: ~17,753 SF (NO SLEEPING) (INCLUDES ADDED NORTH TR TOWER)

4TH FLOOR

SMOKE ZONE 4DC: ~8,703 SF (NO SLEEPING) (INCLUDES ADDED SOUTH TR TOWER)

SMOKE ZONE 4E: ~8,748 SF (NO SLEEPING) (INCLUDES ADDED NORTH TR TOWER)

5TH FLOOR

SMOKE ZONE 5DC: ~7,067 SF (NO SLEEPING) (INCLUDES ADDED SOUTH TR TOWER)

6TH FLOOR

SMOKE ZONE 6D: ~16,407 SF (NO SLEEPING) (INCLUDES ADDED SOUTH TR TOWER)

GENERAL

1. ALL WORK PERFORMED SHALL COMPLY WITH THE CONTRACT DOCUMENTS, DRAWINGS, AND

PROJECT MANUAL, INCLUDING THESE GENERAL NOTES. THE CONTRACTOR SHALL

COORDINATE THE INTENT OF THE GENERAL NOTES WITH ALL TRADES. ALL WORK

PERFORMED SHALL COMPLY WITH CODES, LAWS, ORDINANCES, RULES, AND REGULATIONS

OF PUBLIC AUTHORITIES GOVERNING THE WORK.

2. THE PROJECT MANUAL, BOUND SEPARATELY, IS A PART OF THE CONTRACT DOCUMENTS.

3. THE ORGANIZATION OF THE DRAWINGS AND PROJECT MANUAL SHALL NOT CONTROL THE

CONTRACTOR IN DIVIDING THE WORK AMONG SUBCONTRACTORS OR IN ESTABLISHING THE

EXTENT OF WORK TO BE PERFORMED BY ANY TRADE.

4. CONSTRUCTION, WORKMANSHIP, AND MATERIALS SHALL CONFORM TO THE 2015 IBC AND

CURRENT VA STANDARDS.

5. THE CONTRACTOR SHALL NOTIFY THE COR AND AOR WHERE A CONFLICT OR DISCREPANCY

OCCURS BETWEEN THE CONTRACT DOCUMENT AND ANY OTHER PORTION OF THE

CONTRACT DOCUMENTS, FIELD CONDITIONS OR WHERE ANY CONDITIONS ARISE NOT

COVERED BY THESE DOCUMENTS WHEREIN WORK WILL NOT COMPLY WITH THE

REQUIREMENTS OF THE IBC.

6. THESE DRAWINGS INDICATE IN GENERAL THE PROJECT IN TERMS OF ARCHITECTURAL

DESIGN INTENT, THE DIMENSIONS OF THE BUILDING, THE MAJOR ARCHITECTURAL ELEMENTS

AND TYPE OF STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS. THE DRAWINGS DO

NOT NECESSARILY INDICATE OR DESCRIBE ALL WORK REQUIRED FOR FULL PERFORMANCE

AND COMPLETION OF THE REQUIREMENTS OF THE CONTRACT DOCUMENTS. AS INDICATED

OR DESCRIBED, THE CONTRACTOR SHALL FURNISH ALL ITEMS REQUIRED FOR THE PROPER

EXECUTION AND COMPLETION OF THE WORK.

7. REFER TO MECHANICAL, PLUMBING, ELECTRICAL AND TELECOMMUNICATIONS DRAWINGS

AND SPECIFICATIONS FOR ARCHITECTURAL ROUTING OF CONDUIT, PIPING, DUCTWORK ETC.

AT UNDERSIDE OF CONCRETE SLABS. ROUTING SHALL BE ORTHOGONAL, AND LIKE ITEMS

TO BE GANGED AND TO RUN PARALLEL WITH EVEN SPACING TYPICAL. EXACT ROUTING

SHALL BE DETERMINED BY THE CONTRACTOR, AND LAYOUT SHOP DRAWINGS SUBMITTED

FOR ARCHITECTURAL REVIEW AND APPROVAL PRIOR TO INSTALLATION. CONTRACTOR

SHALL VERIFY SIZES AND LOCATIONS OF ALL MECHANICAL EQUIPMENT PADS AND BASES AS

WELL AS POWER AND WATER OR DRAIN INSTALLATIONS WITH EQUIPMENT MANUFACTURERS

BEFORE PROCEEDING WITH THE WORK. CHANGES TO ACCOMMODATE FIELD CONDITIONS

OR SUBSTITUTIONS SHALL BE MADE AT NO ADDITIONAL COST.

8. ALL SYMBOLS AND ABBREVIATIONS USED ON THE DRAWINGS ARE CONSIDERED TO BE

CONSTRUCTION STANDARDS. IF THE CONTRACTOR HAS QUESTIONS REGARDING SAME, OR

THEIR EXACT MEANING, THE ARCHITECT SHALL BE NOTIFIED FOR CLARIFICATION.

9. THE CONTRACTOR SHALL COORDINATE ALL MECHANICAL FLOOR/WALL SLEEVES AND

SHAFTS IN CONCRETE SLABS/WALLS WITH MECHANICAL, PLUMBING, FIRE PROTECTION,

ELECTRICAL, STRUCTURAL AND ARCHITECTURAL DRAWINGS AND DISCREPANCIES, IF ANY,

TO BE BROUGHT TO NOTICE OF THE ENGINEER PRIOR TO EXECUTION OF WORK.

10. COORDINATE WORK WITH COR, INCLUDING SCHEDULING TIME AND LOCATIONS FOR

DELIVERIES, BUILDING ACCESS, USE OF BUILDING SERVICES AND FACILITIES, AND USE OF

ELEVATORS. MINIMIZE DISTURBANCE OF BUILDING FUNCTIONS AND OCCUPANTS.

11. THE CONTRACTOR SHALL CONDUCT THEIR OWN SITE SURVEY OF THE EXISTING GROUND

AND CURB ELEVATIONS (LEVELS) AND REPORT ACTUAL ELEVATIONS (LEVELS) TO THE

ENGINEER.

12. CONTRACTOR'S SHOP DRAWINGS SHOULD INDICATE ACTUAL ELEVATIONS (LEVELS).

13. ALL ELEVATIONS (LEVELS) ARE IN FEET AND INCHES.

14. ALL DIMENSIONS ARE IN FEET AND INCHES AND ANGLES IN DEGREES UNLESS OTHERWISE

NOTED.

15. ONLY WRITTEN DIMENSIONS IN ALL CASES SHALL BE FOLLOWED.

16. ALL EXISTING OR PROPOSED ELEVATIONS (LEVELS) AND DIMENSIONS, ON SITE AND ON

DRAWINGS MUST BE CHECKED AND VERIFIED BY THE CONTRACTOR BEFORE THE

PREPARATION OF SHOP DRAWINGS OR COMMENCEMENT OF ANY ITEM OF WORK ON THE

SITE.

17. ARCHITECTURAL DRAWINGS MUST ALWAYS BE READ IN CONJUNCTION WITH ALL OTHER

RELEVANT SERVICES DRAWINGS AND CONTRACT DOCUMENTS. ANY DISCREPANCY

BETWEEN THESE DRAWINGS AND DOCUMENTS SHOULD BE REPORTED TO THE COR AND

ARCHITECT FOR CLARIFICATION AND VERIFICATION.

18. ALL ALUMINUM TRIMS SHALL BE POWDER COATED FINISH.

19. REFER SCHEDULE OF WALL TYPES FOR DIFFERENT WALL SITUATIONS.

20. ALL SHAFT WALLS TO PROVIDE FOR 2 HRS. FIRE RATING.

21. ALL SHAFTS SHALL BE SEALED AT BOTTOM & TOP TO PROVIDE 2 HRS. FIRE RATING.

22. ALL FIRE DOORS SHALL HAVE SMOKE SEAL INTEGRAL WITH IT.

23. ALL PLUMBING AND HVAC OPENINGS IN FIRE RATED WALLS & SLABS SHALL BE PROVIDED

WITH FIRE SMOKE SEALS OF THE SAME FIRE RATING AS OF THE WALLS & SLABS THEY

PENETRATE THROUGH.

24. CONTRACTOR SHALL LOCATE AND INSTALL ALL ACCESS PANEL IN THE GYPSUM BOARD

CEILING AND WALLS FOR SERVICES ACCESS.

25. FOR AREAS WITHOUT SUSPENDED CEILING HAVING EXPOSED SLAB AND BEAMS, WALL

FINISH MATERIAL SHALL BE FROM FLOOR LEVEL TO BOTTOM OF SLAB LEVEL. (UNLESS

NOTED OTHERWISE)

26. THE CONTRACTOR SHALL SUBMIT SAMPLES AND SHOP DRAWINGS FOR ALL WORKS WITH

ALL NECESSARY DETAILS AND DESIGN INFORMATION FOR APPROVAL.

27. NOTES APPEARING ON VARIOUS DRAWINGS FOR DIFFERENT SYSTEMS AND MATERIALS ARE

TO BE REVIEWED, COORDINATED AND ARE TO BE APPLIED TO ALL RELATED DRAWINGS AND

DETAILS.

FIRE PROTECTION

1. ALL OPENINGS IN SLABS AT MECHANICAL ROOMS (INCLUDING SPACES LEFTOVER IN THE

SHAFTS AFTER INSTALLATION OF DUCTS) MUST BE SEALED OFF WITH NON-COMBUSTIBLE

MATERIALS TO MAINTAIN THE REQUIRED FIRE-RATING CONTINUITY OF THE FLOOR

CONSTRUCTION. CONTRACTOR SHALL SUBMIT SHOP-DRAWINGS FOR APPROVAL FOR ALL

SUCH CASES.

2. ALL OPENINGS AT SLABS, WALLS SHALL BE SEALED OFF (FILLED) WITH NON-COMBUSTIBLE

MATERIALS TO MAINTAIN THE REQUIRED FIRE RATING CONTINUITY OF THE FLOOR, WALL

CONSTRUCTION. ALL HOLES, INCLUDING THOSE FOR MECHANICAL, AND ELECTRICAL

FACILITIES WHICH ARE LOCATED ON FLOOR SLAB, PARTITIONS AND WALLS MUST BE FILLED

WITH NON-COMBUSTIBLE MATERIALS TO PROVIDE REQUIRED FIRE RATING AND SHALL BE

SEALED AGAINST PASSAGE OF SMOKE AND FLAME.

3. A FINISH OR FIRE RATING INDICATION ON A WALL SHALL MEAN THE ENTIRE LENGTH OF WALL

IS TO BE FINISHED OR FIRE RATED.

4. FIRE RATED ASSEMBLIES SHALL BE PER TABLE 721.1(1), GENERIC ASSEMBLIES OF GYPSUM

HANDBOOK, OR HAVE ICC APPROVAL.

5. PENETRATIONS OF FIRE RESISTANCE-RATED HORIZONTAL ASSEMBLIES AND FIRE

RESISTANCE RATED WALLS SHALL COMPLY WITH SECTION 714 OF THE IBC, INCLUDING FIRE

DAMPERS AND SMOKE DAMPERS WHERE REQUIRED.

6. MEMBRANE PENETRATIONS BY LISTED ELECTRICAL OUTLET BOXES ARE PERMITTED

PROVIDED SUCH BOXES HAVE BEEN TESTED FOR USE IN FIRE-RESISTANCE-RATED

ASSEMBLIES AND THE BOX DOES NOT EXCEED 1/8" UNLESS LISTED OTHERWISE.

METAL WORKS

1. ALL MILD STEEL WORKS SHOWN ON THE CONTRACT DRAWINGS/DETAILS SHALL BE PRIMED

AND SHALL BE PAINTED WITH TWO COATS OF EPOXY PAINT.

2. STEEL ELEMENTS NOT SHOWN IN THE CONTRACT DRAWINGS BUT ARE DEEMED NECESSARY

FOR THE SATISFACTORY COMPLETION OF THE WORKS SHALL BE GALVANIZED STEEL

PRIMED & PAINTED WITH TWO COATS OF EPOXY PAINT FOR ALL INTERIOR SITUATIONS AND

STAINLESS STEEL (#316) FOR ALL EXTERIOR SITUATIONS.

3. ALL WELDED STEEL JOINTS SHALL BE GRINDED SMOOTH, PRIMED & PAINTED.

4. ALL WELDING SHALL BE OF SUITABLE TYPE TO STEEL WORKS.

EXTERIOR ENVELOPE

1. THE EXTERIOR WALL AS SHOWN SHALL BE COMPLETE SYSTEM INCLUDING ALL HOT DIPPED

GALVANIZED STEEL SUPPORTS, STIFFENERS, FASTENERS, SEALANT, JOINERY, MISC, PIECES, AND MATERIAL THICKNESS AS REQUIRED TO FORM HIGH QUALITY SYSTEM IN ACCORDANCE

WITH THE SPECIFICATIONS AND THE PROFILES SHOWN.

2. DETAILS NOT SHOWN ARE SIMILAR IN CHARACTER TO THOSE DETAILED. WHERE SPECIFIC

DIMENSIONS, DETAILS OR DESIGN INTENT CANNOT BE DETERMINED, CONSULT THE COR AND

ARCHITECT BEFORE PROCEEDING WITH WORK.

3. ALL DETAILS ARE TO BE COORDINATED WITH THE STRUCTURAL FRAMING, INTERIOR

FINISHES AND OTHER RELATED BUILDING COMPONENTS IN ORDER TO PROVIDE A COMPLETE

ENCLOSURE OF FINISH MATERIALS.

4. THE ANCHORAGE ANGLES, SHAPES AND DETAILS ARE SUGGESTIVE AND ARE TO BE

ENGINEERED AND DETAILED AS REQUIRED. THE CONTRACTOR IS TO COORDINATE ALL

ANCHORAGE DETAILS WITH APPROPRIATE TRADES.

5. ALL FASTENERS ARE TO BE CONCEALED, EXCEPT AS SPECIFICALLY SHOWN. ALL BUTT

JOINTS ARE TO HAVE CONCEALED BACK-UP ROD WITH CAPTIVE SEALANT.

6. ATTACHMENT AND DETAILS FOR THE EXTERIOR WALL AND EXTERIOR GLASS SYSTEMS ARE

SHOWN SCHEMATICALLY AND TOGETHER WITH THE SPECIFICATIONS AND THE PROFILES

SHOWN ARE INTENDED TO ESTABLISH PERFORMANCE AND MATERIAL QUALITIES DESIRED.

THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DEVELOPMENT OF FINAL EXTERIOR

WALL DETAILS TO ACCOMMODATE THE FABRICATION, ERECTION AND INSTALLATION OF THE

WORK IN ACCORDANCE WITH THE DESIGN INTENT SHOWN.

7. SEALANT DRAINAGE SYSTEM GASKETS AND WATERPROOFING MEMBRANE SHALL BE

ASSEMBLED IN SUCH A MANNER TO PROVIDE A HIGH-QUALITY WEATHERPROOF BUILDING

ENCLOSURE.

8. COLOR OF SEALANT SHALL MATCH ADJACENT MATERIALS OR AS SPECIFIED BY THE

ARCHITECT.

9. COORDINATE LOCATION OF EXTERIOR WALL ANCHORS, SEALANT POSITIONS WITH

ADJACENT WORK INCLUDING MATERIALS AND OTHER CONTIGUOUS SEALANTS.

10. ALL DISSIMILAR METALS SHALL BE EFFECTIVELY ISOLATED FROM EACH OTHER AS

REQUIRED TO PREVENT MOLECULAR BREAKDOWN.

ARCHITECTURAL GENERAL NOTES CODE ANALYSIS

SHEET

NUMBER SHEET NAME

13-ELECTRICAL

01-E100 ELECTRICAL POWER PLAN - BASEMENT

01-E101 ELECTRICAL POWER PLAN - 1ST FLOOR

01-E102 ELECTRICAL POWER PLAN - 2ND FLOOR

01-E103 ELECTRICAL POWER PLAN - 3RD FLOOR

01-E104 ELECTRICAL POWER PLAN - 4TH FLOOR

01-E105 ELECTRICAL POWER PLAN - 5TH FLOOR

01-E106 ELECTRICAL POWER PLAN - 6TH FLOOR

01-E107 ELECTRICAL POWER PLAN - 7TH FLOOR

01-EL401 ENLARGED ELECTRICAL LIGHTING PLANS SOUTH TR

TOWER

01-EL402 ENLARGED ELECTRICAL LIGHTING PLANS SOUTH TR

TOWER

01-EL403 ENLARGED ELECTRICAL LIGHTING PLANS NORTH TR

TOWER

01-EL404 ENLARGED ELECTRICAL LIGHTING PLANS

01-EL405.1 ENLARGED ELECTRICAL LIGHTING PLANS

01-EL406.1 ENLARGED ELECTRICAL LIGHTING PLANS

01-EL406.2 ENLARGED ELECTRICAL LIGHTING PLANS

01-EP401 ENLARGED ELECTRICAL POWER PLANS SOUTH TR

TOWER

01-EP402 ENLARGED ELECTRICAL POWER PLANS SOUTH TR

TOWER

01-EP403 ENLARGED ELECTRICAL POWER PLANS NORTH TR

TOWER

01-EP404 ENLARGED ELECTRICAL POWER PLANS

01-EP405.1 ENLARGED ELECTRICAL POWER PLANS

01-EP405.2 ENLARGED ELECTRICAL POWER PLANS

01-EP405.3 ENLARGED ELECTRICAL POWER PLANS

01-EP406 ENLARGED ELECTRICAL POWER PLANS

01-EP406.1 ELECTRICAL POWER PLANS - 2ND FLOOR

01-EP408 ENLARGED POWER PLANS NORTH AND SOUTH TR

TOWERS

01-EK601 ELECTRICAL PANEL SCHEDULES

01-EK602 ELECTRICAL PANEL SCHEDULES

01-EK603 ELECTRICAL PANEL SCHEDULES

01-EK604 ELECTRICAL PANEL SCHEDULES

01-EK605 ELECTRICAL PANEL SCHEDULES

01-EK606 ELECTRICAL PANEL SCHEDULES

01-EK607 ELECTRICAL PANEL SCHEDULES

01-EK608 ELECTRICAL PANEL SCHEDULES

01-EK609 ELECTRICAL PANEL SCHEDULES

01-EK610 ELECTRICAL PANEL SCHEDULES

01-EK611 ELECTRICAL PANEL SCHEDULES

01-EJ601 ELECTRICAL ONE-LINE DIAGRAM - CRITICAL

01-EJ602 ELECTRICAL ONE-LINE DIAGRAM - NORMAL

15-TELECOMMUNICATIONS

01-TN100 TELECOM AND SECURITY PLAN - BASEMENT

01-TN101 TELECOM AND SECURITY PLAN - 1ST FLOOR

01-TN102 TELECOM AND SECURITY PLAN - 2ND FLOOR

01-TN103 TELECOM AND SECURITY PLAN - 3RD FLOOR

01-TN104 TELECOM AND SECURITY PLAN - 4TH FLOOR

01-TN105 TELECOM AND SECURITY PLAN - 5TH FLOOR

01-TN106 TELECOM AND SECURITY PLAN - 6TH FLOOR

01-TN401 ENLARGED PLANS SOUTH TR TOWER

01-TN402 ENLARGED PLANS SOUTH TR TOWER

01-TN403 ENLARGED PLANS NORTH TR TOWER

01-TN404 ENLARGED PLANS

01-TN405 ENLARGED PLANS

01-TN406 RACK ELEVATIONS

01-TN407 RACK ELEVATIONS

01-TN408 RACK ELEVATIONS

01-TN409 RACK ELEVATIONS

01-TN410 RACK ELEVATIONS

TOTAL SHEETS IN SUB-SET: 185

SHEET

NUMBER SHEET NAME

09-FIRE ALARM

01-FA151 FIRE ALARM PLAN - 1ST FLOOR

01-FA152 FIRE ALARM PLAN - 2ND FLOOR

01-FA153 FIRE ALARM PLAN - 3RD FLOOR

01-FA154 FIRE ALARM PLAN - 4TH FLOOR

01-FA155 FIRE ALARM PLAN - 5TH FLOOR

01-FA156 FIRE ALARM PLAN - 6TH FLOOR

09-FIRE PROTECTION

01-FP150 FIRE PROTECTION PLAN - BASEMENT

01-FP151.1 FIRE PROTECTION PLAN - 1ST FLOOR

01-FP151.2 FIRE PROTECTION PLAN - 1ST FLOOR

01-FP151.3 FIRE PROTECTION PLAN - 1ST FLOOR

01-FP151.4 FIRE PROTECTION PLAN - 1ST FLOOR

01-FP152 FIRE PROTECTION PLAN - 2ND FLOOR

01-FP153 FIRE PROTECTION PLAN - 3RD FLOOR

01-FP154 FIRE PROTECTION PLAN - 4TH FLOOR

01-FP155 FIRE PROTECTION PLAN - 5TH FLOOR

01-FP156 FIRE PROTECTION PLAN - 6TH FLOOR

10-PLUMBING

01-P100 PLUMBING PIPING PLAN - BASEMENT

01-P101 PLUMBING PIPING PLAN - 1ST FLOOR

01-P102 PLUMBING PIPING PLAN - 2ND FLOOR

01-P103 PLUMBING PIPING PLAN - 3RD FLOOR

01-P104 PLUMBING PIPING PLAN - 4TH FLOOR

01-P105 PLUMBING PIPING PLAN - 5TH FLOOR

01-P106 PLUMBING PIPING PLAN - 6TH FLOOR

01-P107 PLUMBING PIPING PLAN - 7TH FLOOR

01-PP401 ENLARGED PLUMBING PIPING PLANS SOUTH TR

TOWER

01-PP402 ENLARGED PLUMBING PIPING PLANS SOUTH TR

TOWER

01-PP403 ENLARGED PLUMBING PIPING PLANS NORTH TR

TOWER

01-PP404 ENLARGED PLUMBING PLANS

01-PP405.1 ENLARGED PLUMBING PLANS

01-PP405.2 ENLARGED PLUMBING PLANS

01-PP407 ENLARGED PLUMBING PIPING PLANS

01-PD401 ENLARGED PLUMBING DRAIN AND VENT PLANS

SOUTH TR TOWER

01-PD402 ENLARGED PLUMBING DRAIN AND VENT PLANS

SOUTH TR TOWER

01-PD403 ENLARGED PLUMBING DRAIN AND VENT PLANS

NORTH TR TOWER

12-MECHANICAL

01-M100 MECHANICAL HVAC OVERALL PLAN - BASEMENT

01-M101 MECHANICAL HVAC OVERALL PLAN - 1ST FLOOR

01-M102 MECHANICAL HVAC OVERALL PLAN - 2ND FLOOR

01-M103 MECHANICAL HVAC OVERALL PLAN - 3RD FLOOR

01-M104 MECHANICAL HVAC OVERALL PLAN - 4TH FLOOR

01-M105 MECHANICAL HVAC OVERALL PLAN - 5TH FLOOR

01-M106 MECHANICAL HVAC OVERALL PLAN - 6TH FLOOR

01-M107 MECHANICAL HVAC OVERALL PLAN - 7TH FLOOR

01-MH152 MECHANICAL HVAC PLAN - 2ND FLOOR

01-MD401 ENLARGED DEMOLITION MECHANICAL HVAC PLANS

SOUTH TR TOWER

01-MH401 ENLARGED MECHANICAL HVAC PLANS SOUTH TR

TOWER

01-MH402 ENLARGED MECHANICAL HVAC PLANS SOUTH TR

TOWER

01-MH403 ENLARGED MECHANICAL HVAC PLANS NORTH TR

TOWER

01-MH404 ENLARGED MECHANICAL HVAC PLANS - 1ST FLOOR

01-MH405.1 ENLARGED MECHANICAL HVAC PLANS - 1ST FLOOR

01-MH405.2 ENLARGED MECHANICAL HVAC PLANS - 1ST FLOOR

01-MH405.3 ENLARGED MECHANICAL HVAC PLANS - 1ST FLOOR

01-MP401 ENLARGED MECHANICAL PIPING PLANS SOUTH TR

TOWER

01-MP402 ENLARGED MECHANICAL PIPING PLANS SOUTH TR

TOWER

01-MP403.1 ENLARGED MECHANICAL PIPING PLANS NORTH TR

TOWER

01-MP403.2 ENLARGED DEMOLITION MECHANICAL HVAC PLANS

SOUTH TR TOWER

01-MP404 ENLARGED MECHANICAL PIPING PLANS - 1ST FLOOR

01-MP405.1 ENLARGED MECHANICAL PIPING PLANS - 2ND FLOOR

01-MP405.2 MECHANICAL PIPING PLANS - DATA CENTER

01-MP405.3 MECHANICAL PIPING PLANS - 2ND FLOOR

SHEET

NUMBER SHEET NAME

01-GENERAL

01-GI001 COVER SHEET

01-GI002 GENERAL NOTES, CODE REQUIREMENTS, AND

SHEET INDEX

01-GC001 SEQUENCING NOTES

01-GC100 SEQUENCING PLAN - BASEMENT

01-GC101 SEQUENCING PLAN - 1ST FLOOR

01-GC102 SEQUENCING PLAN - 2ND FLOOR

01-GC103 SEQUENCING PLAN - 3RD FLOOR

01-GC104 SEQUENCING PLAN - 4TH FLOOR

01-GC105 SEQUENCING PLAN - 5TH FLOOR

01-GC106 SEQUENCING PLAN - 6TH FLOOR

01-GC107 SEQUENCING PLAN - 7TH FLOOR

01-GC121 SMOKE COMPARTMENTALIZATION PLAN - 1ST FLOOR

01-GC122 SMOKE COMPARTMENTALIZATION PLAN - 2ND

FLOOR

01-GC123 SMOKE COMPARTMENTALIZATION PLAN - 3RD

FLOOR

01-GC124 SMOKE COMPARTMENTALIZATION PLAN - 4TH FLOOR

01-GC125 SMOKE COMPARTMENTALIZATION PLAN - 5TH FLOOR

01-GC126 SMOKE COMPARTMENTALIZATION PLAN - 6TH FLOOR

07-STRUCTURAL

01-SG001 GENERAL NOTES

01-SG002 LEGEND, SHEET LIST & ABBREVIATIONS

01-SG003 LOAD KEY

01-SG004 AXONOMETRIC VIEW

01-SF103 REFERENCE PLAN - 3RD FLOOR

01-SF151 ENLARGED REFERENCE PLAN - 3RD FLOOR

01-SF351 SOUTH TR TOWER SECTIONS AND ELEVATIONS

01-SF352 NORTH TR TOWER SECTIONS AND ELEVATIONS

01-SF401 SOUTH IDF TOWER PLAN

01-SF402 NORTH IDF TOWER PLAN

01-SF501 STEEL POD DETAILS

01-SF502 STEEL STRONGBACK DETAILS

01-SF503 CFS DETAILS

01-SF504 CONCRETE DETAILS

01-SF505 EQUIPMENT ANCHORAGE DETAILS

08-ARCHITECTURAL

01-AE100 REFERENCE PLAN - BASEMENT

01-AE101 REFERENCE PLAN - 1ST FLOOR

01-AE102 REFERENCE PLAN - 2ND FLOOR

01-AE103 REFERENCE PLAN - 3RD FLOOR

01-AE104 REFERENCE PLAN - 4TH FLOOR

01-AE105 REFERENCE PLAN - 5TH FLOOR

01-AE106 REFERENCE PLAN - 6TH FLOOR

01-AE107 REFERENCE PLAN - 7TH FLOOR

01-AE108 REFERENCE PLAN - PENTHOUSE

01-AE201 EXTERIOR ELEVATIONS

01-AE202 EXTERIOR ELEVATIONS

01-AE351 SOUTH TOWER SECTIONS

01-AE352 NORTH TOWER SECTIONS

01-AE361 ENLARGED SECTIONS

01-AE362 ENLARGED SECTIONS

01-AE363 ENLARGED SECTIONS

01-AE371 ENLARGED SECTIONS

01-AD404 ENLARGED DEMOLITION PLANS

01-AD405 ENLARGED DEMOLITION PLANS

01-AE401 ENLARGED PLANS SOUTH TR TOWER

01-AE402 ENLARGED PLANS SOUTH TR TOWER

01-AE403 ENLARGED PLANS NORTH TR TOWER

01-AE404 ENLARGED PLANS

01-AE405 ENLARGED PLANS

01-AE406 ENLARGED PLANS

01-AE411 PLAN DETAILS

01-AE451 INTERIOR ELEVATIONS

01-AE452 INTERIOR ELEVATIONS

01-AE453 INTERIOR ELEVATIONS

01-AE454 INTERIOR ELEVATIONS

01-AE511 EXTERIOR DETAILS

01-AE512 EXTERIOR DETAILS

01-AE513 ROOF DETAILS

01-AE521 DOOR DETAILS

01-AE531 WALL TYPES

01-AE532 FIRE PROTECTION DETAILS

01-AE533 INTERIOR DETAILS

01-AE601 SCHEDULES

01-AE901 PERSPECTIVE VIEW

SHEET INDEX

Revisions: Date:

ABATEMENT SCHEDULE

ROOM

~AREA MATERIAL DISCRIPTION

NUMBER NAME

B01 - 1ST FLOOR

1151 TR 105 73 SF 12"x12" BEIGE/BROWN FLOOR TILE

1220 ABAN TR 25 SF 12"x12" BEIGE/BROWN FLOOR TILE

1321A TR 51 SF 12"x12" BEIGE/BROWN FLOOR TILE

C185 TR 79 SF 12"x12" BEIGE/BROWN FLOOR TILE

K132 TR 64 SF 12"x12" BEIGE/BROWN FLOOR TILE

B01 - 2ND FLOOR

2212A ABAN TR 26 SF 12"x12" BEIGE/BROWN FLOOR TILE

D241A ABAN TR 29 SF 12"x12" BEIGE/BROWN FLOOR TILE

E202B ABAN TR 21 SF 12"x12" BEIGE/BROWN FLOOR TILE

K232 TR 56 SF 12"x12" BEIGE/BROWN FLOOR TILE

B01 - 3RD FLOOR

D305D ABAN TR 27 SF 12"x12" BEIGE/BROWN FLOOR TILE

B01 - 4TH FLOOR

4317B ABAN TR 27 SF 12"x12" BEIGE/BROWN FLOOR TILE

D434B ABAN TR 24 SF 12"x12" BEIGE/BROWN FLOOR TILE

B01 - 5TH FLOOR

D535A ABAN TR 26 SF 12"x12" BEIGE/BROWN FLOOR TILE

05.26.2021 SHEET 32 of 421

BUILDING 01, PREPATORY WORK

1. RELOCATE HVAC UNITS ON SECOND FLOOR LOW ROOF

2. NEW RO SKID IN CENTRAL PLAN

3. RO LOOP FROM BASEMENT TO BOTH TOWERS

4. RO LOOP FROM BASEMENT OF BUILDING 1 TO IDF ROOMS IN BUILDINGS 8 & 34

5. RO TANK & PUMPS IN BASEMENT

6. PRE-FAB ROOF PENTHOUSE ON ROOF ADJACENT TO NORTH TOWER

7. PRE-FAB ROOF PENTHOUSE ON ROOF ABOVE DATA CENTER

8. PUMPS/VFDS IN NEW PENTHOUSES

BUILDING 01, GROUP 1, FLOORS B - 1

1. INSTALL TEMPORARY INFECTION CONTROL PRECAUTIONS (CLASS II)

2. DEMO CONCTRUCTION TO FACILITATE NEW LAYOUT

3. CONSTRUCT WALLS, GYPSUM BOARD ONE SIDE

4. MEP ROUGH-INS

A. CONDUIT, WIRING, PANELS, & TRANSFORMERS

B. CONDENSATE LINES

C. CONNECTION TO (E) CHILLED WATER IN BASEMENT & 7TH FLOOR FOR THE SOUTH TOWER,

5TH FLOOR (ROOF) FOR NORTH TOWER

D. CONNECTION TO RO WATER FROM NEW RO SKID

5. COMPLETE GYPSUM BOARD

6. DOORS

7. INTERIOR FINISHES

A. PLYWOOD BACKBOARDS

B. PAINT

C. FLOORING

8. MEP FINISH WORK

A. FAN COIL, CONDENSING UNITS, & HUMIDIFIERS

B. MECHANICAL DEVICES & CONTROLS

C. ELECTRICAL DEVICES

9. MEP STARTUP AND TESTING & BALANCE

A. POWER CONNECTIONS

10. TELECOMMUNICATIONS

A. BUILD-OUT OF NEW IDF CLOSETS INCLUDING:

a. EQUIPMENT RACKS AND GROUNDING

b. OVERHEAD BASKET TRAY AND GROUNDING

B. SINGLE-MODE FIBER OPTIC CABLING FROM EXISTING DATA CENTER

C. (MDF) TO EACH NEW IDF CLOSET.

D. IDENTIFY AND LOCATE ALL EXISTING STATION CABLING FROM EACH DEPARTMENT OR

SERVING ZONE.

E. IDENTIFY AND LOCATE ALL EXISTING WIRELESS ACCESS POINT LOCATIONS FROM EACH

DEPARTMENT OR SERVING ZONE.

F. NEW HORIZONTAL CABLING FROM EXISTING STATION LOCATIONS TO NEW IDF.

G. TERMINATE ALL STATION CABLING WITHIN THE IDF AND MAKE ROOM RACK READY FOR

CUT-OVER.

H. DURING EVENING HOURS (AS SCHEDULED WITH DEPARTMENTS) DEMO EXISTING STATION

LOCATIONS AND REPLACE WITH PRE-PULLED “RACK READY” CABLING. TERMINATE AT

STATION END – PERFORM END TO END TESTING.

I. DEMO ALL EXISTING STATION CABLING FROM STATION TO OLD IDF LOCATIONS.

J. A/E AND OI&T TO PERFORM FINAL PUNCH LIST AND SITE WALK FOR APPROVAL.

K. UPON ACCEPTANCE, PROVIDE TO CONTRACTING OFFICER RECORD DOCUMENTS

INCLUDING:

a. RECORD DRAWINGS IN PDF AND DWG (2019 OR NEWER) FORMAT

b. TEST RESULTS IN FLW (FLUKE) AND PDF FORMAT BACKBONE FIBER

BUILDING 01, GROUP 2, FLOORS 2 - 6

1. DEMO ROOFING & SLOPED TOPPING AT TOWER FOOTPRINT

2. CONSTRUCT TOWER BASE CURBS

3. INSTALL VERTICAL STRONGBACKS (~2 DAYS)

4. INSTALL TEMPORARY INFECTION CONTROL PRECAUTIONS (CLASS IV)

5. CUT OPENINGS IN EXTERIOR WALL FOR DOORS INTO IDF TOWER

6. ERECT TOWER PODS (2 ON NORTH TOWER, 3 ON THE SOUTH TOWER) (~4 DAYS)

7. INFILL METAL STUDS (~5 DAYS)

8. TOWER EXTERIOR SKIN, ROOF, AND FLASHING (WEATHERTIGHT) (~15 DAYS)

9. MEP ROUGH-INS (10 DAYS)

A. CONDUIT, WIRING, PANELS, & TRANSFORMERS

B. CONDENSATE LINES

C. ROOF DRAINAGE

D. CONNECTION TO (E) CHILLED WATER IN BASEMENT & 7TH FLOOR FOR THE SOUTH TOWER,

5TH FLOOR (ROOF) FOR NORTH TOWER

E. CONNECTION TO RO WATER FROM NEW RO SKID

10. INTERIOR FINISHES (~10 DAYS)

A. GYPSUM BOARD

B. PLYWOOD BACKBOARDS

C. PAINT

D. FLOORING

11. MEP FINISH WORK

A. FAN COIL, CONDENSING UNITS, & HUMIDIFIERS

B. MECHANICAL DEVICES & CONTROLS

C. ELECTRICAL DEVICES

12. MEP STARTUP AND TESTING & BALANCE

A. POWER CONNECTIONS

13. TELECOMMUNICATIONS

A. BUILD-OUT OF NEW IDF CLOSETS INCLUDING:

a. EQUIPMENT RACKS AND GROUNDING

b. OVERHEAD BASKET TRAY AND GROUNDING

B. SINGLE-MODE FIBER OPTIC CABLING FROM EXISTING DATA CENTER

C. (MDF) TO EACH NEW IDF CLOSET.

D. IDENTIFY AND LOCATE ALL EXISTING STATION CABLING FROM EACH DEPARTMENT OR

SERVING ZONE.

E. IDENTIFY AND LOCATE ALL EXISTING WIRELESS ACCESS POINT LOCATIONS FROM EACH

DEPARTMENT OR SERVING ZONE.

F. NEW HORIZONTAL CABLING FROM EXISTING STATION LOCATIONS TO NEW IDF.

G. TERMINATE ALL STATION CABLING WITHIN THE IDF AND MAKE ROOM RACK READY FOR

CUT-OVER.

H. DURING EVENING HOURS (AS SCHEDULED WITH DEPARTMENTS) DEMO EXISTING STATION

LOCATIONS AND REPLACE WITH PRE-PULLED “RACK READY” CABLING. TERMINATE AT

STATION END – PERFORM END TO END TESTING.

I. DEMO ALL EXISTING STATION CABLING FROM STATION TO OLD IDF LOCATIONS.

J. A/E AND OI&T TO PERFORM FINAL PUNCH LIST AND SITE WALK FOR APPROVAL.

K. UPON ACCEPTANCE, PROVIDE TO CONTRACTING OFFICER RECORD DOCUMENTS

INCLUDING:

a. RECORD DRAWINGS IN PDF AND DWG (2019 OR NEWER) FORMAT

b. TEST RESULTS IN FLW (FLUKE) AND PDF FORMAT BACKBONE FIBER

BUILDING 01, GROUP 3, IDF ROOMS 1151, 1221A, 1321A, C185, K131 & K231

1. CONTAIN WORK AREA TO INSIDE ROOMS

2. INSTALL TEMPORARY INFECTION CONTROL PRECAUTIONS (CLASS VARIES SEE TABLE TO THE

RIGHT)

3. CONSTRUCT WALLS, GYPSUM BOARD ONE SIDE

4. MEP ROUGH-INS

A. CONDUIT & WIRING

B. CONDENSATE LINES

C. VAV & ASSOCITED DUCTWORK

D. CONNECTION TO RO WATER FROM NEW RO SKID

5. COMPLETE GYPSUM BOARD

6. DOORS

7. INTERIOR FINISHES

A. PLYWOOD BACKBOARDS

B. PAINT

C. FLOORING

8. MEP FINISH WORK

A. VAV BOX & HUMIDIFIER

B. MECHANICAL DEVICES & CONTROLS

C. ELECTRICAL DEVICES

9. MEP STARTUP AND TESTING & BALANCE

A. POWER CONNECTIONS

10. TELECOMMUNICATIONS

A. IDENTIFY AND LOCATE ALL EXISTING CAT5 STATION CABLING

B. IDENTIFY AND LOCATE ALL EXISTING WIRELESS ACCESS POINT LOCATIONS

C. INSTALL ALL NEW HORIZONTAL CABLING FROM LOCATIONS THAT ARE REQUIRING UPGRADE

(CAT5 AND WAP) TO IDF.

D. INSTALL NEW EQUIPMENT RACKS (AS NOTED)

E. TERMINATE ALL STATION CABLING WITHIN THE IDF AND MAKE ROOM RACK READY FOR CUT-

OVER.

F. DURING EVENING HOURS (AS SCHEDULED WITH DEPARTMENTS) DIVISION 27 CONTRACTOR

TO DEMO EXISTING STATION LOCATIONS AND REPLACE WITH PRE-PULLED “RACK READY”

CABLING. TERMINATE AT STATION END – PERFORM END TO END TESTING.

G. A/E AND OI&T TO PERFORM FINAL PUNCH LIST AND SITE WALK FOR APPROVAL.

H. UPON ACCEPTANCE, PROVIDE TO CONTRACTING OFFICER RECORD DOCUMENTS INCLUDING:

a. RECORD DRAWINGS IN PDF AND DWG (2019 OR NEWER) FORMAT

b. TEST RESULTS IN FLW (FLUKE) AND PDF FORMAT

BUILDING 01, GROUP 5, DATA CENTER

1. INSTALL PRE-FAB ROOF PENTHOUSE ON ROOF ABOVE DATA CENTER

2. INSTALL & CONNECT PUMPS/VFDS IN NEW PENTHOUSE

3. INSTALL TEMPORARY INFECTION CONTROL PRECAUTIONS (CLASS II)

4. MEP ROUGH-INS

A. CONDUIT & WIRING

5. DEMOLITION THROUGH THE DOUBLE DOORS PLAN SOUTH WILL GIVE THE MOST SPACE. REMOVE

THE LIEBERT UNIT CLOSEST TO THE DOUBLE DOORS AND ITS ASSOCIATED CONDENSING UNIT

AND REFRIGERANT PIPING ON THE ROOF FIRST.

6. BRING IN NEW DIRECT EXPANSION LIEBERT(CRAC-1-1) AND INSTALL ITS ASSOCIATED

CONDENSER(CRCU-1-1) ON ROOF IN SIMILAR LOCATION TO PREVIOUSLY REMOVED CONDENSER.

7. INSTALL WATER PIPING THAT WILL SERVE CRAC-1-2 & CRAC-1-3 ON THE ROOF WITH PUMPS AND

OTHER COMPONENTS AND ROUTE PIPING AS SHOWN ON MECH AND ARCHITECTURAL PLANS

DOWN TO FIRST FLOOR OUTSIDE THE DATA CENTER. THEN ROUTE PIPING BENEATH RAISED

FLOOR TO ANTICIPATED LOCATIONS OF NEW WATER COOLED LIEBERT UNITS.

8. REMOVE LIEBERT UNIT CLOSEST TO THE SINGLE DOOR, IT IS THE UNIT THAT IS FURTHEST PLAN

NORTH. ALSO REMOVE ITS ASSOCIATED CONDENSER ON THE ROOF ALONG WITH ITS

REFRIGERANT PIPING.

9. INSTALL NEW CRAC-1-2 WATER COOLED LIEBERT IN PLACE OF LASTLY REMOVED LIEBERT

CLOSEST TO THE SINGLE DOOR LEADING TO THE OFFICE SPACE. CONNECT TO WATER PIPING

THAT WAS PREVIOUSLY INSTALLED.

10. TO REMOVE THE LAST MIDDLE LIEBERT UNIT, IT WILL REQUIRE EXTRA COORDINATION WITH THE IT DEPARTMENT. IT IS POSSIBLE THE RACK IN FRONT OF THE MIDDLE LIEBERT WILL PROHIBIT IT

FROM BEING REMOVED SO THE RACK WILL NEED TO BE TEMPORARILY RELOCATED. ONCE THE

RACK IS RELOCATED, REMOVE THE MIDDLE LIEBERT, REFRIGERANT PIPING, AND CONDENSER ON

THE ROOF.

11. INSTALL LAST WATER COOLED LIEBERT CRAC-1-3 IN PLACE OF LASTLY REMOVED LIEBERT AND

CONNECT TO WATER PIPING THAT WAS PREVIOUSLY INSTALLED.

12. THE IT RACK THAT WAS TEMPORARILY RELOCATED CAN NOW BE RETURNED TO ITS ORIGINAL

POSITION.

13. DURING THE CONSTRUCTION, MAINTAIN N+1 REDUNDANCY FOR THE CRAC UNITS. (2) OF THE

UNITS MUST BE OPERATIONAL AT ALL TIMES.

14. MEP FINISH WORK

A. MECHANICAL DEVICES & CONTROLS

B. ELECTRICAL DEVICES

15. MEP STARTUP AND TESTING & BALANCE

A. POWER CONNECTIONS

16. TELECOMMUNICATIONS

A. IDENTIFY AND LOCATE ALL EXISTING CAT5 STATION CABLING

B. IDENTIFY AND LOCATE ALL EXISTING WIRELESS ACCESS POINT LOCATIONS

C. INSTALL ALL NEW HORIZONTAL CABLING FROM LOCATIONS THAT ARE REQUIRING UPGRADE

(CAT5 AND WAP) TO IDF.

D. INSTALL NEW EQUIPMENT RACKS (AS NOTED)

E. TERMINATE ALL STATION CABLING WITHIN THE IDF AND MAKE ROOM RACK READY FOR CUT-

OVER.

F. DURING EVENING HOURS (AS SCHEDULED WITH DEPARTMENTS) DIVISION 27 CONTRACTOR

TO DEMO EXISTING STATION LOCATIONS AND REPLACE WITH PRE-PULLED “RACK READY”

CABLING. TERMINATE AT STATION END – PERFORM END TO END TESTING.

G. A/E AND OI&T TO PERFORM FINAL PUNCH LIST AND SITE WALK FOR APPROVAL.

H. UPON ACCEPTANCE, PROVIDE TO CONTRACTING OFFICER RECORD DOCUMENTS INCLUDING:

a. RECORD DRAWINGS IN PDF AND DWG (2019 OR NEWER) FORMAT

b. TEST RESULTS IN FLW (FLUKE) AND PDF FORMAT

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMP

321 4 5 6 7 8 9 10

SHEET OF

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

B

IM

/P h o e n ix

E H

R M

/6

-2

-2

B

L D

G

A .r v t

/2

/2

:1

:2

P

M

01-GC001

SEQUENCING NOTES

Concourse Federal Group

123 S. Royal Street

Alexandria, VA 22314

EHRM INFRASTRUCTURE

UPGRADES 01

05.26.2021

PVAHCS - Carl T Hayden Medical Center 650 E Indian School Road Phoenix AZ 85012

644-20-201

BLDG/FLOOR

ROOM

NUMBER

ROOM NAME

INFECTION CONTROL ASSESSMENT

ACTIVITY

TYPE

RISK

GROUP

REQUIREMENTS

ABANDONED

B01 - BASEMENT D01B ABAN TR TYPE B LOW CLASS II

B01 - 1ST FLOOR 1220 ABAN TR TYPE B MEDIUM CLASS II

B01 - 1ST FLOOR 1411 ABAN TR TYPE B MEDIUM CLASS II

B01 - 1ST FLOOR C129 ABAN TR TYPE B HIGH CLASS II

B01 - 1ST FLOOR D138 ABAN TR TYPE B MEDIUM CLASS II

B01 - 1ST FLOOR E104B ABAN TR TYPE B MEDIUM CLASS III

B01 - 2ND FLOOR 2212A ABAN TR TYPE B MEDIUM CLASS II

B01 - 2ND FLOOR 2234A ABAN TR TYPE B MEDIUM CLASS II

B01 - 2ND FLOOR C221A ABAN TR TYPE B HIGH CLASS II

B01 - 2ND FLOOR D241A ABAN TR TYPE B MEDIUM CLASS II

B01 - 2ND FLOOR E202B ABAN TR TYPE B HIGHEST CLASS III / IV

B01 - 3RD FLOOR 3329A ABAN TR TYPE B LOW CLASS II

B01 - 3RD FLOOR 3412A ABAN TR TYPE B LOW CLASS II

B01 - 3RD FLOOR C321 ABAN TR TYPE B HIGHEST CLASS III / IV

B01 - 3RD FLOOR D305B ABAN TR TYPE B MEDIUM CLASS II

B01 - 3RD FLOOR D305D ABAN TR TYPE B HIGH CLASS II

B01 - 3RD FLOOR D340 ABAN TR TYPE B HIGHEST CLASS III / IV

B01 - 4TH FLOOR 4215A ABAN TR TYPE B LOW CLASS II

B01 - 4TH FLOOR 4317B ABAN TR TYPE B LOW CLASS II

B01 - 4TH FLOOR C421A ABAN TR TYPE B HIGHEST CLASS III / IV

B01 - 4TH FLOOR D434B ABAN TR TYPE B HIGH CLASS II

B01 - 4TH FLOOR D456 ABAN TR TYPE B HIGH CLASS II

B01 - 5TH FLOOR D535A ABAN TR TYPE B HIGH CLASS II

B01 - 5TH FLOOR DCC4B ABAN TR TYPE B HIGH CLASS II

B01 - 6TH FLOOR C612 ABAN TR TYPE B LOW CLASS II

B01 - 6TH FLOOR D627A ABAN TR TYPE B HIGH CLASS II

GROUP 1 - SOUTH TOWER BASEMENT, 1ST FLOOR

B01 - BASEMENT TRS-000A TR TYPE C LOW CLASS II

B01 - BASEMENT TRS-000B TR MECH TYPE C LOW CLASS II

B01 - BASEMENT TRS-000C TR ELEC TYPE C LOW CLASS II

B01 - 1ST FLOOR TRS-100A TR TYPE C MEDIUM CLASS III

B01 - 1ST FLOOR TRS-100B TR MECH TYPE C MEDIUM CLASS III

B01 - 1ST FLOOR TRS-100C TR ELEC TYPE C MEDIUM CLASS III

GROUP 2 - NORTH AND SOUTH TOWERS, 2ND FLOOR AND ABOVE

B01 - 2ND FLOOR TRN-200A TR TYPE D HIGH CLASS IV

B01 - 2ND FLOOR TRN-200B TR MECH TYPE D HIGH CLASS IV

B01 - 2ND FLOOR TRN-200C TR ELEC TYPE D HIGH CLASS IV

B01 - 2ND FLOOR TRS-200A TR TYPE D HIGH CLASS IV

B01 - 2ND FLOOR TRS-200B TR MECH TYPE D HIGHEST CLASS IV

B01 - 2ND FLOOR TRS-200C TR ELEC TYPE D HIGH CLASS IV

B01 - 3RD FLOOR TRN-300A TR TYPE D HIGH CLASS IV

B01 - 3RD FLOOR TRN-300B TR MECH TYPE D HIGH CLASS IV

B01 - 3RD FLOOR TRN-300C TR ELEC TYPE D HIGH CLASS IV

B01 - 3RD FLOOR TRS-300A TR TYPE D HIGHEST CLASS IV

B01 - 3RD FLOOR TRS-300B TR MECH TYPE D HIGHEST CLASS IV

B01 - 3RD FLOOR TRS-300C TR ELEC TYPE D HIGHEST CLASS IV

B01 - 4TH FLOOR TRN-400A TR TYPE D HIGH CLASS IV

B01 - 4TH FLOOR TRN-400B TR MECH TYPE D HIGH CLASS IV

B01 - 4TH FLOOR TRN-400C TR ELEC TYPE D HIGH CLASS IV

B01 - 4TH FLOOR TRS-400A TR TYPE D HIGH CLASS IV

B01 - 4TH FLOOR TRS-400B TR MECH TYPE D HIGH CLASS IV

B01 - 4TH FLOOR TRS-400C TR ELEC TYPE D HIGH CLASS IV

B01 - 5TH FLOOR TRS-500A TR TYPE D HIGH CLASS IV

B01 - 5TH FLOOR TRS-500B TR MECH TYPE D HIGH CLASS IV

B01 - 5TH FLOOR TRS-500C TR ELEC TYPE D HIGH CLASS IV

B01 - 6TH FLOOR TRS-600A TR TYPE D HIGH CLASS IV

B01 - 6TH FLOOR TRS-600B TR MECH TYPE D HIGH CLASS IV

B01 - 6TH FLOOR TRS-600C TR ELEC TYPE D HIGH CLASS IV

GROUP 3

B01 - 1ST FLOOR 1151 TR 105 TYPE B LOW CLASS IV

B01 - 1ST FLOOR 1221A TR TYPE C MEDIUM CLASS III

B01 - 1ST FLOOR 1231A

N/S

CORRIDOR

B01 - 1ST FLOOR 1321A TR TYPE B MEDIUM CLASS II

B01 - 1ST FLOOR C185 TR TYPE B HIGHEST CLASS III / IV

B01 - 1ST FLOOR K132 TR TYPE C HIGH CLASS III / IV

B01 - 2ND FLOOR K232 TR TYPE C HIGH CLASS III / IV

1. REFER TO SHEET GI101 FOR ADDITIONAL INFORMATION.

2. REFER TO SHEET GI003 FOR INFECTION CONTROL NOTES.

3. EXIT PATH SHALL BE MAINTAINED DURING DEMOLITION AND CONSTRUCTION.

4. FACILITY MUST REMAIN OPEN AND OPERATIONAL THROUGHOUT CONSTRUCTION- COORDINATE

ALL UTILITY SERVICE INTERRUPTIONS WITH THE VA FACILITY MANAGER.

5. WHERE TEMPORARY CONSTRUCTION BARRIER PARTITIONS ARE BUILT IN THE EXISTING

CORRIDORS, PARALLEL WITH THE CORRIDOR WALLS, PROVIDE 6 FEET MINIMUM EGRESS WIDTH

WHERE SERVING PATIENTS AND 44 INCHES ELSEWHERE.

6. THE WORK GROUPS LISTED BELOW IDENTIFY WORK OF SIMILAR NATURE WITHIN THE BUILDING

AND SHALL NOT CONTROL THE CONTRACTOR IN ESTABLISHING THE SEQUENCING OF WORK.

CONTRACTOR SHALL ORGANIZE WORK TO LIMIT DISRUPTION OF DEPARTMENTS.

7. CONSTRUCTION PROJECT ACTIVITY TYPES ( PER ASHE INFECTION CONTROL RISK

ASSESSMENT MATRIX) AND PRECAUTION CLASS AS LISTED BELOW. REFER TO SPECIFICATION

SECTION 01 35 25 FOR INFECTION CONTROL REQUIREMENTS. POTENTIAL IMPACT BASED ON

UNITS ABOVE, BELOW AND SURROUNDING THE CONSTRUCTION WORK AREA.

8. INFECTION CONTROL ASSESSMENT SHALL BE VERIFIED BY FACILITES IC COMMITTEE

A. APPROVAL WILL BE REQURED WHEN THE CONSTRUCTION ACTIVITY AND RISK LEVEL

INDICATE THAT CLASS III OR CLASS IV CONTROL…