Attachment B - Final Construction Plans - METCOM 911.pdf
PDF 11 MB Posted
- Solicitation number
- S-C25102-00014407
- Issued by
- Marion County, Oregon
About this file
This document is a comprehensive set of engineering and construction plans for the Marion County METCOM911 public safety communications facility located at 1060 Mt Hood Ave in Woodburn, Oregon. The project involves modifying an existing public safety communications infrastructure by installing new equipment on an existing 150-foot monopole tower, including antennas with associated ancillary equipment and a new 10'x12' equipment shelter. The proposed work includes installing microwave antennas with specific azimuths, an ice bridge, and associated ground space modifications. The project is being managed by Marion County Public Works, with Cushing Civil Engineers serving as the engineering firm of record.
The design documents detail technical specifications for the communication site, including grounding plans, electrical one-line diagrams, equipment shelter exterior and interior elevations, and RF tower appurtenance details. The plans specify equipment from manufacturers like CommScope and Daikin, with precise measurements and installation requirements. The project appears to be funded through Marion County and involves upgrading existing communication infrastructure to enhance public safety communication capabilities. The engineering plans demonstrate a comprehensive approach to site modification, including considerations for electrical systems, grounding, antenna placement, and structural integrity, with careful attention to technical specifications and industry standards.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SHEET INDEX
FROM MARION COUNTY PUBLIC WORKS BUILDING:
1. GET ON I-5 N IN SALEM FROM CORDON RD NE AND HAZELGREEN
RD NE
9 MIN (4.9 MI)
2. MERGE ONTO I-5 N
10.9 MI
3. TAKE EXIT 271 FOR OR-214/OR-219 TOWARD WOODBURN/MOLALLA
0.3 MI
4. TURN RIGHT ONTO OR-214 S/HILLSBORO-SILVERTON HWY NE.
PASS BY DAIRY QUEEN GRILL & CHILL (ON THE RIGHT IN 0.2 MI)
1.8 MI
5. TURN RIGHT AND TAKE ANOTHER RIGHT TURN. DESTINATION WILL
BE ON THE RIGHT.
262 FT
EST. TIME: 26 MINS.
EST. MILEAGE: 18.1 MI
COVER
SHEET
SHEET NUMBER:
SHEET TITLE:
PROJECT INFORMATION PROJECT INFORMATION CONTINUED DRIVING DIRECTIONS
VICINITY MAP
PROPERTY OWNER:
CITY OF WOODBURN
270 MONTGOMERY ST
WOODBURN, OR 97071
JURISDICTION:
CITY OF WOODBURN
COUNTY:
MARION
PROJECT LOCATION:
*LAT: N 45° 09'03.4" (45.150950)
*LONG: W 122°50'36.5" (-122.843472)
*GROUND ELEVATION (ASML) = 186'±
*INFORMATION OBTAINED FROM GOOGLE EARTH
UTILITY PROVIDERS:
TELCO PROVIDER: N/A
POWER PROVIDER: PORTLAND GENERAL ELECTRIC
T-1
PROJECT AREA:
TOTAL COMPOUND AREA - 200 SQ FEET ±
ACCESS DRIVE AND PARKING - EXISTING
TOTAL - 200 SQ FEET ±
LOCATOR MAP
LICENSURE:
DRAWING INFORMATION:
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
07-19-24 SITE SKETCH
10-29-24 PRELIMINARY ZONING DRAWINGS
09-25-25
PRELIMINARY CONSTRUCTION DRAWINGS
10-13-25 FINAL CONSTRUCTION DRAWINGS
PROJECT INFORMATION:
12725 SW MILLIKAN WAY
SUITE 300
BEAVERTON, OR 97005
(503) 387-5331 www.cushingcivilengineers.com
Cushing
Civil Engineers
Civil Engineers
MARION COUNTY
METCOM911
1060 MT HOOD AVE
WOODBURN, OR 97071
PROJECT DESCRIPTION
SITE NAME:
METCOM911
1060 MT HOOD AVE, WOODBURN, OR 97071
CONSTRUCTION SUBMITTAL:
T-1 COVER SHEET
EX-1 EXISTING CONDITIONS
G-1 GENERAL NOTES
ER-1 GRADING & EROSION CONTROL PLAN
ER-2 GRADING & EROSION CONTROL DETAILS
C-1 OVERALL SITE PLAN
C-2 ENLARGED SITE PLAN
C-3 ELEVATIONS
C-4 COMPOUND DETAILS
C-5 HVAC DETAILS
C-6 EQUIPMENT SHELTER FOUNDATION PLAN
E-1 SITE GROUNDING PLAN & DETAILS
E-2 GROUNDING DETAILS I
E-3 GROUNDING DETAILS II
RF-1.0 RF TOWER APPURTENANCES I
RF-1.1 RF TOWER APPURTENANCES II
SHELTER ONE PREFABRICATED SHELTER DRAWINGS
(REFER TO STATE OF OREGON BUILDING CODES
DIVISION FOR STATE INSIGNIA):
SH-1 EQUIPMENT SHELTER EXTERIOR ELEVATIONS
SH-2 EQUIPMENT SHELTER INTERIOR ELEVATIONS
SH-3 ELECTRICAL ONE-LINE DRAWING
SH-4 ELECTRICAL PANEL SCHEDULE
SCALE: NTS SCALE: NTS
PROJECT LOCATION
PROJECT LOCATION
1. PROPOSED MODIFICATION OF AN EXISTING PUBLIC SAFETY
COMMUNICATIONS FACILITY FOR MARION COUNTY, OREGON.
2. PROPOSED INSTALLATION OF THE FOLLOWING EQUIPMENT ON AN
EXISTING 150' MONOPOLE TOWER:
* ANTENNAS W/ ASSOCIATED ANCILLARY EQUIPMENT
3. PROPOSED INSTALLATION OF THE FOLLOWING EQUIPMENT
WITHIN EXISTING GROUND SPACE:
* (1) 10'x12' EQUIPMENT SHELTER
* (1) ICE BRIDGE
ZONING:
P/SP (SPECIAL AGRICULTURE)
PARCEL NUMBER(S) & AREA:
ACCOUNT #: 108697
TAXLOT #: 051W08CB04800
399,009.6 SQ FEET±
9.16 ACRES±
GENERAL INFORMATION:
1. TRAFFIC IS UNAFFECTED
2. SIGNAGE AT SITE IS PROPOSED
3. SITE IS UNMANNED AND HANDICAP ACCESS IS NOT REQUIRED
CODE INFORMATION:
1. IBC-2018 INTERNATIONAL BUILDING CODE
2. NEC-2017 NATIONAL ELECTRIC CODE
3. 2019 OREGON STRUCTURAL SPECIALTY CODE
4. 2017 NFPA 58 CODE
5. OCCUPANCY GROUP: U
6. CONSTRUCTION TYPE: II-B
TOWER OWNER:
METCOM911
1060 MT HOOD AVE
WOODBURN, OR 97071
APPLICANT:
MARION COUNTY PUBLIC WORKS
5155 SILVERTON RD NE
SALEM, OR 97305
CONTACT:
BRIAN NICHOLAS
(503) 588-7943 bnicholas@co.marion.or.us
PROJECT MANAGER:
PATRICK HOOVER
(971) 295-0152 phoover@rtspnw.com
CONSTRUCTION
MANAGER:
PATRICK HOOVER
(971) 295-0152 phoover@rtspnw.com
ZONING CONTACT:
CUSHING CIVIL ENGINEERS
12725 SW MILLIKAN WAY, STE 300
BEAVERTON, OR 97005
CONTACT:
ROB HOWE
(503) 387-5331 rob@cushingcivilengineers.com
ENGINEER OF RECORD:
CUSHING CIVIL ENGINEERS
12725 SW MILLIKAN WAY, STE 300
BEAVERTON, OR 97005
CONTACT:
KENNY MCMANAWAY
(503) 387-5331 kenny@cushingcivilengineers.com
KamalThapa Snapshot
EXISTING
CONDITIONS
EX-1
SHEET NUMBER:
SHEET TITLE:
LICENSURE:
DRAWING INFORMATION:
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
07-19-24 SITE SKETCH
10-29-24 PRELIMINARY ZONING DRAWINGS
09-25-25
PRELIMINARY CONSTRUCTION DRAWINGS
10-13-25 FINAL CONSTRUCTION DRAWINGS
PROJECT INFORMATION:
12725 SW MILLIKAN WAY
SUITE 300
BEAVERTON, OR 97005
(503) 387-5331 www.cushingcivilengineers.com
Cushing
Civil Engineers
Civil Engineers
MARION COUNTY
METCOM911
1060 MT HOOD AVE
WOODBURN, OR 97071
2 SITE PHOTO
11X17 SCALE: 1" = 24' 22X34 SCALE: 1" = 12' EXISTING CONDITIONS 1
EX-1
NOTE:
THIS IS NOT A SURVEY; ALL EXISTING
INFORMATION IS PROVIDED BY GIS &
SIDE WALK NOTES.
SCALE: NTS
(EX) 150'-0" MONOPOLE
TOWER TO REMAIN
(EX) BUILDING, TYP
(EX) ICE BRIDGE BY
OTHERS TO REMAIN
(EX) ELECTRICAL/DATA
ROOM INSIDE BUILDING
CENTER LINE
PROPERTY LINE
NUMBER
OTHERWISE
WATERPROOF
VERIFY IN FIELD
WITHOUT
WINDOW
VINYL TILE
VERTICAL
UNLESS NOTED
TOP OF MASONRY
TOP OF CONCRETE
SHEET VINYL
TYPICAL
THROUGH
SUSPENDED
STRUCTURAL
STAINLESS STEEL
SPECIFICATION
ROUGH OPENING
SQUARE
SIMILAR
REQUIRED
W/O
GA
GC
GALV
FT
FLR
FLUOR
FIN
EXT
EX
GAUGE
GENERAL CONTRACTOR
GALVANIZE(D)
FLUORESCENT
FOOT
FLOOR
FINISH
EXTERIOR
EXISTING
PRESSURE TREATED
OUTSIDE DIAMETER
PAIRPR
PROP
PROJ
PT
PROPERTY
PROJECT
OPP
OC, o/c
OPG
OD
OPPOSITE
OPENING
ON CENTER
AT
WP
C P L L
AND
ANGLE
GROUNDGRND
AIR CONDITIONINGA/C
REQ'D
CONTINUOUSCONT
DWG
EL, ELEV
E.W.
EQUIP
EQ
ELECT
EA
E
DIAG
DIM
DN
DTL, DETL
DIA, Ø
DBL
DRAWING
ELEVATION
EACH WAY
EQUIPMENT
EQUAL
ELECTRICAL
EACH
EAST
DIAGONAL
DETAIL
DOWN
DIMENSION
DIAMETER
DOUBLE
CONST
CONC
CLR
CLG
BLK
B/S
BMR
BLDG
AWG
ASTM
APPROX
AFF
ADJ
CONSTRUCTION
BUILDING STANDARD
BASE MOBILE RADIO
CONCRETE
CLEAR
CEILING
BLOCK
AMERICAN WIRE GAUGE
TESTING & MATERIALS
AMERICAN SOCIETY FOR
APPROXIMATELY
ABOVE FINISH FLOOR
BUILDING
ADJUSTABLE
T.O.C.
NOT IN CONTRACT
NOT APPLICABLE
MINIMUMMIN
N
NTS
NIC
NA
MISC
NORTH
NOT TO SCALE
MISCELLANEOUS
MET, MTL
MECH
MGR
MFR
LB(S)
MAX
MANAGER
MANUFACTURER
MECHANICAL
METAL
MAXIMUM
POUND(S)
VERT
WIN
W/ W
VT
VIF
WEST
WITH
U.N.O.
T.O.M.
TYP
GYPSUM WALL BOARD
HVAC
IN
INSUL
INT
INFO
I.D.
INCH
INTERIOR
INSULATION
INFORMATION
INSIDE DIA.
HORIZ
HARD'WD
HT
HR
GYP BD
GWB
HORIZONTAL
HARDWOOD
HEIGHT
HOUR
GYPSUM BOARD
SQ
TNND
THRU
SUSP
STRUCT
S.V.
SS
STL
TINNED
STEEL
SPEC
S
SHT
SIM
RM
R.O.
SOUTH
SHEET
ROOM
ANTENNA AMPLIFIERLNA
OVERHEAD POWEROHP
UNDRGRND POWERUGP
OVERHEAD TELCOOHT
UNDRGRND TELCOUGT
HEATING, VENTING AND
AIR CONDITIONING
1. DRAWINGS ARE NOT TO BE SCALED, WRITTEN DIMENSIONS TAKE PRECEDENCE, THIS SET OF
DOCUMENTS IS INTENDED TO BE USED FOR DIAGRAMMATIC PURPOSED ONLY, UNLESS
NOTED OTHERWISE. THE GENERAL CONTRACTOR'S SCOPE OF WORK SHALL INCLUDE
FURNISHING ALL MATERIALS, EQUIPMENT, LABOR AND ANY REQUIREMENTS DEEMED
NECESSARY TO COMPLETE INSTALLATION AS DESCRIBED IN THE DRAWINGS AND OWNER'S
PROJECT MANUAL.
2. THE CONTRACTOR IS RESPONSIBLE FOR ALL DIMENSIONS AND STANDARDIZED DETAILS THAT
REQUIRE MODIFICATIONS DUE TO ACTUAL FIELD CONDITIONS AND REQUIREMENTS MUST BE
SUBMITTED TO AND APPROVED BY OWNERS REPRESENTATIVE PRIOR TO START OF WORK.
3. PRIOR TO THE SUBMISSION OF BIDS, CONTRACTORS INVOLVED SHALL VISIT THE JOB SITE TO
FAMILIARIZE THEMSELVES WITH ALL CONDITIONS AFFECTING THE PROPOSED PROJECT.
CONTRACTORS SHALL VISIT THE CONSTRUCTION SITE WITH THE CONSTRUCTION/CONTRACT
DOCUMENTS TO VERIFY FIELD CONDITIONS AND CONFIRM THAT THE PROJECT WILL BE
ACCOMPLISHED AS SHOWN. PRIOR TO PROCEEDING WITH CONSTRUCTION, ANY ERRORS,
OMISSIONS, OR DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE
ARCHITECT/ENGINEER VERBALLY AND IN WRITING.
4. THE GENERAL CONTRACTOR SHALL RECEIVE WRITTEN AUTHORIZATION TO PROCEED WITH
CONSTRUCTION PRIOR TO STARTING WORK ON ANY ITEM NOT CLEARLY DEFINED BY THE
CONSTRUCTION DRAWINGS/CONTRACT DOCUMENTS.
5. THE CONTRACTOR SHALL SUPERVISE AND DIRECT THE PROJECT DESCRIBED IN THE
CONTRACT DOCUMENTS. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR ALL
CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES, SAFETY, AND PROCEDURES
FOR COORDINATING ALL PORTIONS OF THE WORK UNDER THE CONTRACT.
6. THE CONTRACTOR SHALL INSTALL ALL EQUIPMENT AND MATERIALS ACCORDING TO
MANUFACTURER'S/VENDOR'S SPECIFICATIONS UNLESS NOTED OTHERWISE OR WHERE
LOCAL CODES OR ORDINANCES TAKE PRECEDENCE.
7. ALL WORK PERFORMED ON THE PROJECT AND MATERIALS INSTALLED SHALL BE IN STRICT
ACCORDANCE WITH ALL APPLICABLE CODES, REGULATIONS, AND ORDINANCES.
CONTRACTOR SHALL GIVE ALL NOTICES AND COMPLY WITH ALL LAWS, ORDINANCES, RULES,
REGULATIONS AND LAWFUL ORDERS OF ANY PUBLIC AUTHORITY, MUNICIPAL AND UTILITY
COMPANY SPECIFICATIONS, AND LOCAL AND STATE JURISDICTIONAL CODES BEARING ON THE
PERFORMANCE OF THE WORK.
8. THE CONTRACTOR SHALL PROVIDE, AT THE PROJECT SITE, A FULL SET OF CONSTRUCTION
DOCUMENTS UPDATED WITH THE LATEST REVISIONS INVOLVED WITH THE PROJECT. THIS
SET IS A VALID CONTRACT DOCUMENT ONLY IF THE TITLE SHEET IS STAMPED IN RED INK "FOR
CONSTRUCTION" AND EACH SUCCESSIVE SHEET BEARS THE ARCHITECT'S/ENGINEER'S
SIGNED WET STAMP.
9. THE CONTRACTOR IS RESPONSIBLE FOR ADEQUATELY BRACING AND PROTECTING ALL WORK
DURING CONSTRUCTION AGAINST DAMAGE, BREAKAGE, COLLAPSE, ETC. ACCORDING TO
APPLICABLE CODES, STANDARDS, AND GOOD CONSTRUCTION PRACTICES. THE
STRUCTURAL COMPONENTS OF ADJACENT CONSTRUCTION OR FACILITIES ARE NOT TO BE
ALTERED BY THE CONSTRUCTION PROJECT UNLESS NOTED OTHERWISE.
10. THE CONTRACTOR SHALL MEET ALL OSHA REQUIREMENTS FOR ALL INSTALLATIONS.
11. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL DAMAGES TO THE EXISTING
CONSTRUCTION AND REPAIR ALL DAMAGES TO EQUAL OR BETTER NEW CONSTRUCTION. THE
CONTRACTOR SHALL NOTIFY THE PROJECT MANAGER OF ANY DAMAGE TO THE BUILDING
SITE OR ANY ADJACENT STRUCTURES AROUND THE PROJECT. THE OWNERS
REPRESENTATIVE SHALL BE SOLE AND FINAL JUDGE AS TO THE QUALITY OF THE REPAIRED
CONSTRUCTION. ANY ADDITIONAL MODIFICATIONS WHICH MUST BE MADE SHALL BE MADE AT
THE CONTRACTOR'S EXPENSE.
12. WHERE NEW PAVING, CONCRETE SIDEWALKS OR PATHS MEET EXISTING CONSTRUCTION, THE
CONTRACTOR SHALL MATCH THE EXISTING PITCH, GRADE, AND ELEVATION SO THE ENTIRE
STRUCTURE SHALL HAVE A SMOOTH TRANSITION.
13. THE CONTRACTOR SHALL MODIFY THE EXISTING FLOORS, WALL, CEILING, OR OTHER
CONSTRUCTION AS REQUIRED TO GAIN ACCESS TO AREAS FOR ALL MECHANICAL, PLUMBING,
ELECTRICAL, OR STRUCTURAL MODIFICATIONS. WHERE THE EXISTING CONSTRUCTION
DOORS, PARTITIONS, CEILING, ETC., ARE TO BE REMOVED, MODIFIED, OR REARRANGED OR
WHERE THE EXPOSED OR HIDDEN MECHANICAL, ELECTRICAL, SYSTEMS ARE ADDED OR
MODIFIED, THE GENERAL CONTRACTOR SHALL REPAIR, PATCH AND MATCH ALL EXISTING
CONSTRUCTION AND FINISHES OF ALL FLOORS WALLS AND CEILINGS. WHERE CONCRETE
MASONRY CONSTRUCTION IS MODIFIED, THE CONTRACTOR SHALL TOOTH IN ALL NEW
CONSTRUCTION TO MATCH THE EXISTING BOND. WHERE CONCRETE CONSTRUCTION IS
MODIFIED, THE CONTRACTOR SHALL VERIFY THE EXACT DETAILS TO BE USED FOR
CONSTRUCTION. ALL WORK SHALL BE COVERED UNDER THE GENERAL CONTRACT.
14. IF CONTRACTOR OR SUBCONTRACTOR FIND IT NECESSARY TO DEVIATE FROM ORIGINAL
APPROVED PLANS, THEN IT IS THE CONTRACTOR'S AND THE SUBCONTRACTOR'S
RESPONSIBILITY TO PROVIDE THE PROJECT MANAGER WITH 4 COPIES OF THE PROPOSED
CHANGES FOR HIS APPROVAL BEFORE PROCEEDING WITH THE WORK. IN ADDITION THE
CONTRACTOR AND SUBCONTRACTORS SHALL BE RESPONSIBLE FOR PROCURING ALL
NECESSARY APPROVALS FROM THE BUILDING AUTHORITIES FOR THE PROPOSED CHANGES
BEFORE PROCEEDING WITH THE WORK. THE CONTRACTOR AND SUBCONTRACTORS SHALL
BE RESPONSIBLE FOR PROCURING ALL NECESSARY INSPECTIONS AND APPROVALS FROM
BUILDING AUTHORITIES DURING THE EXECUTION OF THE WORK.
15. CONTRACTOR TO PROVIDE A PORTABLE FIRE EXTINGUISHER WITH A RATING OF NOT LESS
THAN 2-A OR 2-A10BC WITHIN 75 FEET TRAVEL DISTANCE TO ALL PORTIONS OF PROJECT
AREA DURING CONSTRUCTION.
16. THIS IS AN ESSENTIAL FACILITY THEREFORE SHALL STRICTLY MEET ALL APPLICABLE CODE
AND JURISDICTIONAL REQUIREMENTS.
1. RUBBISH, STUMPS, DEBRIS, STICKS, STONES AND OTHER REFUSE SHALL BE REMOVED
FROM THE SITE AND DISPOSED OF LEGALLY UNLESS OTHERWISE REQUIRED TO BE LEFT AS
DEFINED BY LAND/PROPERTY OWNER.
2. THE SITE SHALL BE GRADED TO CAUSE SURFACE WATER TO FLOW AWAY FROM THE
EQUIPMENT, EQUIPMENT SHELTER, GENERATOR, FUEL TANK, TOWER AREAS, AND
ADJACENT BUILDINGS, ETC.
3. NO FILL OR EMBANKMENT MATERIAL SHALL BE PLACED ON FROZEN GROUND. FROZEN
MATERIALS, SNOW OR ICE SHALL NOT BE PLACED IN ANY FILL OR EMBANKMENT.
4. THE SUBGRADE SHALL BE COMPACTED AND BROUGHT TO A SMOOTH UNIFORM GRADE
PRIOR TO THE CRUSHED STONE APPLICATION. FABRIC USE AS REQUIRED.
5. ALL APPLICABLE LOCATES SHALL BE PERFORMED PRIOR TO TO ANY EXCAVATION OR SITE
GRADING. ALL EXISTING ACTIVE SEWER, WATER, GAS, ELECTRIC, AND OTHER UTILITIES
WHERE ENCOUNTERED IN THE WORK, SHALL BE PROTECTED AT ALL TIMES, AND WHERE
REQUIRED FOR THE PROPER EXECUTION OF THE WORK, SHALL BE RELOCATED AS
DIRECTED BY ENGINEERS. EXTREME CAUTION SHOULD BE USED BY THE CONTRACTOR
WHEN EXCAVATING OR PIER DRILLING AROUND OR NEAR UTILITIES. CONTRACTOR SHALL
PROVIDE SAFETY TRAINING FOR THE WORKING CREW.
6. ALL EXISTING INACTIVE SEWER, WATER, GAS, ELECTRIC AND OTHER UTILITIES, WHICH
INTERFERE WITH THE EXECUTION OF THE WORK, SHALL BE REMOVED AND SHALL BE
CAPPED, PLUGGED OR OTHERWISE DISCONTINUED AT POINTS WHICH WILL NOT INTERFERE
WITH THE EXECUTION OF THE WORK, SUBJECT TO THE APPROVAL OF ENGINEERING.
7. THE AREAS OF THE PROPERTY DISTURBED BY THE WORK AND NOT COVERED BY THE
BUILDING, DRIVEWAY OR CRUSHED STONE, SHALL BE GRADED TO A UNIFORM SLOPE,
FERTILIZED, SEEDED, AND COVERED WITH MULCH AS SPECIFIED IN THE SPECIFICATION
LANDSCAPE WORK..
8. BEDDING MATERIAL FOR UTILITY LINES, CULVERTS AND PIPING: CLEAN SAND, MEDIUM TP
COARSE, SUB ROUNDED NATURAL RIVER OR BANK SAND, WASHED, FREE OF SILT OR CLAY,
LOAM, FRIABLE OR SOLUBLE MATERIALS, AND ORGANIC MATTER; GRADED IN
ACCORDANCE WITH THE FOLLOWING GRAIN SIZE DISTRIBUTION:
9. BMP'S FOR TEMPORARY EROSION/SEDIMENTATION CONTROL SHALL BE IMPLEMENTED PER
LOCAL, CITY OR COUNTY GUIDELINES AND PER PLAN IF APPLICABLE.
1. ALL CONCRETE WORK SHALL BE IN ACCORDANCE WITH THE ACI 301, ACI 318 AND THE
SPECIFICATION CAST-IN-PLACE CONCRETE.
2. ALL CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS
(UNO).
3. REINFORCING STEEL SHALL CONFORM TO ASTM A 615, GRADE 60, DEFORMED UNLESS NOTED
OTHERWISE. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A 185 WELDED STEEL WIRE
FABRIC UNLESS NOTED OTHERWISE. SPLICES CLASS "B" AND ALL HOOKS SHALL BE
STANDARD (UNO).
4. THE FOLLOWING MINIMUM CONCRETE COVER SHALL BE PROVIDED FOR REINFORCING STEEL
UNLESS SHOWN OTHERWISE ON DRAWINGS: CONCRETE CAST AGAINST EARTH - 3 IN.
CONCRETE EXPOSED TO EARTH OR WEATHER:
#6 AND LARGER ..........................2 IN.
#5 AND SMALLER & WWF ...........1-1/2 IN.
5. A 1/2" TROWELED RADIUS SHALL BE PROVIDED AT ALL EXPOSED EDGES OF CONCRETE (UNO).
HOLES TO RECEIVE EXPANSION/WEDGE ANCHORS SHALL BE 1/8" LARGER IN DIAMETER THAN
THE ANCHOR BOLT, DOWEL OR ROD AND SHALL CONFORM TO MFR RECOMMENDATION FOR
EMBEDMENT DEPTH OR AS SHOWN ON THE DRAWINGS. AVOID CUTTING EXISTING REBAR
WHEN DRILLING HOLES IN THE ELEVATED SLAB.
6. INSTALLATION OF CONCRETE EXPANSION AND WEDGE ANCHOR, SHALL BE PER
MANUFACTURER'S WRITTEN RECOMMENDED PROCEDURES.
7. FLOAT SURFACE SHALL BE A SMOOTH FINISH. SURFACE SHALL BE FREE OF ALL OBVIOUS
DEPRESSIONS. SURFACE SHALL BE SLOPED AT 2% TO PROMOTE DRAINAGE AWAY FROM
EQUIPMENT.
17. THE CONTRACTOR SHALL PERFORM WORK DURING SITE/PROPERTY OWNER'S PREFERRED
HOURS TO AVOID DISTURBING NORMAL BUSINESS.
18. SEAL ALL PENETRATIONS THROUGH FIRE-RATED AREAS WITH U.L. LISTED OR FIRE MARSHAL
APPROVED MATERIALS AS APPLICABLE TO THIS FACILITY AND OR PROJECT SITE.
19. CONTRACTOR SHALL BE RESPONSIBLE FOR UTILITY LOCATES, SCHEDULING, COORDINATING
SPECIAL AND BUILDING DEPARTMENT INSPECTIONS.
21. ROUTING OF ALL CONDUITS, CABLES, CABLE TRAYS ETC ARE INDICATED AS PROPOSED
LOCATION ONLY. CONFIRM THE EXACT LOCATION AND ROUTING WITH THE ON SITE PROJECT
MANAGER PRIOR TO STARTING WORK.
AGL ABOVE GRADE LEVEL
GENERAL NOTES CONTINUED:
CONCRETE NOTES:
GENERAL NOTES:
SITE WORK NOTES:
60-90
0-45 0-25 0-2
0-2NO. 200 MESH
NO. 100 MESH
NO. 16 MESH
NO. 8 MESH
NO. 4 MESH
PERCENT PASSINGSIEVE SIZE
SYMBOLS LEGEND
ABBREVIATIONS LEGEND
GENERAL
NOTES
G-1
SHEET NUMBER:
SHEET TITLE:
C-4
REVISION
KEY NOTE DETAIL
REFERENCE ELEVATION
SECTION REFERENCE
ELEVATION DATUM POINT
A C-3
GA
GC
GALV
FT
FLR
FIN
EXT
DWG
E.W.
EQ
EA
E
DIAG
DIM
DN
DBL
CLR
CLG
BLK
B/S
BMR
BLDG
AWG
LB(S)
MAX
IN
INT
INFO
I.D.
HT
HR
GWB
LNA
SYMBOLS LEGEND
10. ALL SITE DESIGN AND CONSTRUCTION MUST COMPLY WITH INDUSTRY STANDARDS AND BE
ALIGNED WITH BMP GUIDELINES AS TECHNICALLY APPLICABLE. EACH SITE MUST BE PM
APPROVED BEFORE IT SHALL BE CONSIDERED COMPLETE AND ACCEPTED.
11. IF INADVERTENT DISCOVERIES OF NATIVE AMERICAN CULTURAL MATERIALS OR HUMAN
REMAINS ARE MADE DURING CONSTRUCTION, ALL WORK SHOULD CEASE AND POTENTIALLY
AFFECTED TRIBES, AS WELL AS THE STATE HISTORIC PRESERVATION OFFICE, SHOULD BE
NOTIFIED IMMEDIATELY.
1. ALL ANTENNAS, LINES AND RELATED INSTALLATION HARDWARE TO BE PROVIDED BY THE
LAND MOBILE COMMUNICATIONS PROVIDER.
2. ALL HARDWARE (NUTS AND BOLTS) BE TIGHTENED AND TORQUED IN ACCORDANCE WITH
THE TOWER MANUFACTURER'S AND STRUCTURAL ENGINEER'S SPECIFICATIONS.
3. VERIFICATION THAT THE TOWER/POLE CAN SUPPORT THE PROPOSED ANTENNA LOADING
IS TO BE DONE BY OTHERS.
4. PROVIDE SUPPORTS FOR THE ANTENNA COAX CABLES TO THE ELEVATION OF ALL INITIAL
AND FUTURE ANTENNAS. ANTENNA COAX CABLES ARE TO BE SUPPORTED AND
RESTRAINED AT THE CENTERS SUITABLE TO THE MANUFACTURER'S REQUIREMENTS.
SITE WORK NOTES CONTINUED:
TOWER/POLE NOTES:
LICENSURE:
DRAWING INFORMATION:
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
07-19-24 SITE SKETCH
10-29-24 PRELIMINARY ZONING DRAWINGS
09-25-25
PRELIMINARY CONSTRUCTION DRAWINGS
10-13-25 FINAL CONSTRUCTION DRAWINGS
PROJECT INFORMATION:
12725 SW MILLIKAN WAY
SUITE 300
BEAVERTON, OR 97005
(503) 387-5331 www.cushingcivilengineers.com
Cushing
Civil Engineers
Civil Engineers
MARION COUNTY
METCOM911
1060 MT HOOD AVE
WOODBURN, OR 97071
P PROPOSED
WATER
CENTERLINE
COAX
POWER/TELCO
TELCO
COAX COAX
EASEMENT
PROPERTY LINE
GAS
UNDERGROUND POWER
CEDAR FENCE
CHAINLINK FENCE
W W
OVERHEAD POWER
G G G G G G
OHP OHP OHP OHP OHP
LPG LPG LPG LPG
PROPANE
SUBJECT PROPERTY LINE
DESIGN LOADS:
CALL 1-800-332-2344 48 HOURS BEFORE YOU DIG. OREGON LAW REQUIRES YOU TO FOLLOW
OAR 952-001-0010 THRU 952-001-0090. COPIES ARE AVAILABLE AT THE OREGON UTILITY
NOTIFICATION CENTER 503-232-1987
ATTENTION (OREGON SITES ONLY):
ROOF SNOW LOAD DATA - GROUND SNOW LOAD: 66 PSF*
FLAT-ROOF SNOW LOAD: N/A
SNOW EXPOSURE FACTOR: N/A
SNOW LOAD IMPORTANCE FACTOR: N/A
THERMAL FACTOR: N/A
WIND DESIGN DATA - ULTIMATE DESIGN WIND SPEED: 107 MPH*
RISK CATEGORY: IV
WIND EXPOSURE: C*
INTERNAL PRESSURE COEFFICIENT: N/A
DESIGN WIND PRESSURES;
WIND LOAD HORIZONTAL (MWFRS):N/A
WIND LOAD (UPLIFT) (MWFRS): N/A
EARTHQUAKE DESIGN DATA - RISK CATEGORY: IV
SEISMIC IMPORTANCE FACTOR: N/A
MAPPED SPECTRAL RESPONSE ACCEL-
ERATION PARAMETERS;
SS 0.93*
S1 0.36*
SITE CLASS: D*
DESIGN SPECTRAL RESPONSE ACCEL-
ERATION PARAMETERS;
SDS 0.77*
SD1 0.52*
SEISMIC DESIGN CATEGORY: D
BASIC SEISMIC FORCE-RESISTING
SYSTEM- BEARING WALL
DESIGN BASE SHEAR: N/A
SEISMIC RESPONSE COEFFICIENT: N/A
RESPONSE MODIFICATION COEFFICIENT: N/A
ANALYSIS PROCEDURE USED: N/A
GEOTECHNICAL INFORMATION - ALLOWABLE BEARING CAPACITY: N/A
*INFORMATION OBTAINED FROM ASCE 7 HAZARD TOOL
GRADING & EROSION
CONTROL PLAN
ER-1
SHEET NUMBER:
SHEET TITLE:
LICENSURE:
DRAWING INFORMATION:
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
07-19-24 SITE SKETCH
10-29-24 PRELIMINARY ZONING DRAWINGS
09-25-25
PRELIMINARY CONSTRUCTION DRAWINGS
10-13-25 FINAL CONSTRUCTION DRAWINGS
PROJECT INFORMATION:
12725 SW MILLIKAN WAY
SUITE 300
BEAVERTON, OR 97005
(503) 387-5331 www.cushingcivilengineers.com
Cushing
Civil Engineers
Civil Engineers
MARION COUNTY
METCOM911
1060 MT HOOD AVE
WOODBURN, OR 97071
11X17 SCALE: 1" = 12' 22X34 SCALE: 1" = 6' GRADING & EROSION CONTROL PLAN 1
EROSION CONTROL NOTES:
1. OWNER OR DESIGNATED PERSON SHALL BE RESPONSIBLE FOR PROPER INSTALLATION AND MAINTENANCE OF ALL EROSION AND SEDIMENT CONTROL MEASURES, IN ACCORDANCE WITH LOCAL, STATE, AND FEDERAL REGULATIONS.
2. THE IMPLEMENTATION OF THESE ESC PLANS AND CONSTRUCTION, MAINTENANCE, REPLACEMENT, AND UPGRADING OF THESE ESC FACILITIES IS THE RESPONSIBILITY OF THE CONTRACTOR UNTIL ALL CONSTRUCTION IS COMPLETED AND APPROVED BY THE LOCAL JURISDICTION, AND VEGETATION/LANDSCAPING IS ESTABLISHED. THE DEVELOPER SHALL BE RESPONSIBLE FOR MAINTENANCE AFTER THE PROJECT IS APPROVED UNTIL THE LOTS ARE SOLD.
3. THE BOUNDARIES OF THE CLEARING LIMITS SHOWN ON THIS PLAN SHALL BE CLEARLY MARKED IN THE FIELD PRIOR TO CONSTRUCTION. DURING THE CONSTRUCTION PERIOD, NO DISTURBANCE BEYOND THE CLEARING LIMITS SHALL BE PERMITTED. THE MARKINGS SHALL BE MAINTAINED BY THE APPLICANT/CONTRACTOR FOR THE DURATION OF
CONSTRUCTION.
4. THE ESC FACILITIES SHOWN ON THIS PLAN MUST BE CONSTRUCTED IN CONJUNCTION WITH ALL CLEARING AND GRADING ACTIVITIES, AND IN SUCH A MANNER AS TO INSURE THAT SEDIMENT AND SEDIMENT LADEN WATER DOES
NOT ENTER THE DRAINAGE SYSTEM, ROADWAYS, OR VIOLATE APPLICABLE WATER STANDARDS.
5. THE ESC FACILITIES SHOWN ON THIS PLAN ARE MINIMUM REQUIREMENTS FOR ANTICIPATED SITE CONDITIONS.
DURING CONSTRUCTION PERIODS, THESE ESC FACILITIES SHALL BE UPGRADED AS NEEDED FOR UNEXPECTED STORM EVENTS AND TO ENSURE THAT SEDIMENT AND SEDIMENT LADEN WATER DOES NOT LEAVE THE SITE.
6. THE ESC FACILITIES SHALL BE INSPECTED DAILY BY THE APPLICANT/CONTRACTOR AND MAINTAINED AS NECESSARY
TO ENSURE THEIR CONTINUED FUNCTIONING.
7. AT NO TIME SHALL SEDIMENT BE ALLOWED TO ACCUMULATE MORE THAN 1/3 THE BARRIER HEIGHT. ALL CATCH BASINS AND CONVEYANCE LINES SHALL BE CLEANED PRIOR TO PAVING. THE CLEANING OPERATIONS SHALL NOT
FLUSH SEDIMENT-LADEN WATER INTO THE DOWNSTREAM SYSTEM.
8. STABILIZED GRAVEL ENTRANCES SHALL BE INSTALLED AT THE BEGINNING OF CONSTRUCTION AND MAINTAINED FOR THE DURATION OF THE PROJECT. ADDITIONAL MEASURES MAY BE REQUIRED TO INSURE THAT ALL PAVED AREAS
ARE KEPT CLEAN FOR THE DURATION OF THE PROJECT.
9. STORM DRAIN INLETS, BASINS, AND AREA DRAINS SHALL BE PROTECTED UNTIL PAVEMENT SURFACES ARE
COMPLETED AND/OR VEGETATION IS RE-ESTABLISHED.
10. PAVEMENT SURFACES AND VEGETATION ARE TO BE PLACED AS RAPIDLY AS POSSIBLE.
11. SEEDING SHALL BE PERFORMED NO LATER THAN SEPTEMBER 1 FOR EACH PHASE OF CONSTRUCTION.
12. IF THERE ARE EXPOSED SOILS OR SOILS NOT FULLY ESTABLISHED FROM OCTOBER 1ST THROUGH APRIL 30TH, THE
WET WEATHER EROSION PREVENTION MEASURES WILL BE IN EFFECT. SEE THE EROSION PREVENTION AND
SEDIMENT CONTROL PLANNING AND DESIGN MANUAL (CHAPTER 4) FOR REQUIREMENTS.
13. NO EXPOSED, BARE SOILS SHALL REMAIN UNSTABILIZED FOR MORE THAN TWO DAYS DURING THE PERIOD OCTOBER 1 THROUGH APRIL 30 OR FOR MORE THAN SEVEN DAYS DURING THE PERIOD OF MAY 1 THROUGH SEPTEMBER 30.
ALL DISTURBED SOIL SURFACES SHALL BE STABILIZED BY A SUITABLE APPLICATION OF "BEST MANAGEMENT
PRACTICES".
14. WHERE FEASIBLE, NO MORE THAN 500 FEET OF TRENCH SHALL BE OPEN AT ONE TIME. EXCAVATED MATERIAL SHALL BE PLACED ON THE UPHIL SIDE OF TRENCHES PROVIDED IT DOES NOT CONFLICT WITH SAFETY
REQUIREMENTS.
15. THE DEVELOPER SHALL REMOVE ESC MEASURES WHEN VEGETATION IS FULLY ESTABLISHED.
4 GENERAL NOTES SCALE: NTS
2SCALE: NTS
3SCALE: NTS CUT/ FILL QUANTITIES
UNADJUSTED CUT/ FILL QUANTITIES
STRIPPING ORGANICS FOR COMPOUND;
CUT = 0 CU. YD.
STRIPPING FOR ACCESS ROAD AND PARKING;
CUT = 0 CU. YD.
PROPOSED COMPOUND AREA;
CUT = 0 CU. YD.
FILL = 0 CU. YD.
PROPOSED ACCESS ROAD AND PARKING;
CUT = 0 CU. YD.
FILL = 0 CU. YD.
PROPOSED TOWER FOUNDATION;
EXCAVATION = EXISTING
APPROX. TOTAL AREA OF DISTURBANCE OF PROPOSED GRADING = EXISTING
NOT USED
±49 LF OF (P) SILT FENCE
SEE SHEET ER-2 FOR DETAIL
EXISTING GRADE
PROPOSED GRADE
TEMPORARY SILT FENCE
CONSTRUCTION ENTRANCE
FLOW DIRECTION
GROUND ELEVATION
LEGEND
250'
GRADING & EROSION
CONTROL DETAILS
ER-2
SHEET NUMBER:
SHEET TITLE:
LICENSURE:
DRAWING INFORMATION:
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
07-19-24 SITE SKETCH
10-29-24 PRELIMINARY ZONING DRAWINGS
09-25-25
PRELIMINARY CONSTRUCTION DRAWINGS
10-13-25 FINAL CONSTRUCTION DRAWINGS
PROJECT INFORMATION:
12725 SW MILLIKAN WAY
SUITE 300
BEAVERTON, OR 97005
(503) 387-5331 www.cushingcivilengineers.com
Cushing
Civil Engineers
Civil Engineers
MARION COUNTY
METCOM911
1060 MT HOOD AVE
WOODBURN, OR 97071
SEDIMENT FENCE NOTES:
1. THE FILTER FABRIC FENCE SHALL BE INSTALLED TO FOLLOW THE CONTOURS WHERE FEASIBLE. THE FENCE POSTS SHALL BE SPACED A MAXIMUM OF 6'
APART AND DRIVEN SECURELY INTO THE GROUND A MINIMUM OF 24”.
2. THE FILTER FABRIC SHALL BE PURCHASED IN A CONTINUOUS ROLL CUT TO THE LENGTH OF THE BARRIER TO AVOID USE OF JOINTS. WHEN JOINTS ARE NECESSARY, FILTER CLOTH SHALL BE SPLICED TOGETHER ONLY AT A SUPPORT POST, WITH A MINIMUM 6” OVERLAP, AND BOTH ENDS SECURELY FASTENED TO THE POST, OR OVERLAP 2” X 2” POSTS AND ATTACH AS SHOWN ON DETAIL SHEET 4-3A OF THE EROSION CONTROL MANUAL.
3. THE FILTER FABRIC SHALL HAVE A MINIMUM VERTICAL BURIAL OF 6”. ALL EXCAVATED MATERIAL FROM FILTER FABRIC INSTALLATION SHALL BE
BACKFILLED AND COMPACTED ALONG THE ENTIRE DISTURBED AREA.
4. STANDARD OR HEAVY-DUTY FILTER FABRIC FENCES SHALL HAVE MANUFACTURED STITCHED LOOPS FOR 2” X 2” POST INSTALLATION. STITCHED LOOPS
SHALL BE INSTALLED ON THE UP HILLSIDE OF THE SLOPED AREA.
5. FILTER FABRIC FENCES SHALL BE REMOVED WHEN THEY HAVE SERVED THEIR USEFUL PURPOSE, BUT NOT BEFORE THE UPSLOPE AREA HAS BEEN
PERMANENTLY PROTECTED AND STABILIZED.
6. FILTER FABRIC FENCES SHALL BE INSPECTED BY APPLICANT/CONTRACTOR IMMEDIATELY AFTER EACH RAINFALL AND AT LEAST DAILY DURING
PROLONGED RAINFALL. ANY REQUIRED REPAIRS SHALL BE MADE IMMEDIATELY.
3SCALE: NTS
2SCALE: NTS
4SCALE: NTS
1SCALE: NTS
TOE OF
SLOPE
PL
PL
H/5 BUT 2' MINIMUM
AND NEED NOT EXCEED
20' MAXIMUM
TOE OF
SLOPE
H/5 BUT 2'
MINIMUM
AND NEED
NOT
EXCEED 10'
MAXIMUM
NATURAL OR
FINISH GRADE
INTERCEPTOR DRAIN
(IF REQUIRED)
H
NATURAL OR
FINISH GRADE
CUT OR
FILL SLOPE
GRAVEL CONSTRUCTION ENTRANCE TEMPORARY SEDIMENT FENCE
PLASTIC SHEETING SETBACKS AND DRAINAGE DIMENSIONS
© 2025 Microsoft Corporation © 2025 Maxar ©CNES (2025) Distribution Airbus DS
OVERALL
SITE PLAN
C-1
SHEET NUMBER:
SHEET TITLE:
LICENSURE:
DRAWING INFORMATION:
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
07-19-24 SITE SKETCH
10-29-24 PRELIMINARY ZONING DRAWINGS
09-25-25
PRELIMINARY CONSTRUCTION DRAWINGS
10-13-25 FINAL CONSTRUCTION DRAWINGS
PROJECT INFORMATION:
12725 SW MILLIKAN WAY
SUITE 300
BEAVERTON, OR 97005
(503) 387-5331 www.cushingcivilengineers.com
Cushing
Civil Engineers
Civil Engineers
MARION COUNTY
METCOM911
1060 MT HOOD AVE
WOODBURN, OR 97071
22X34 SCALE: 1" = 50' OVERALL SITE PLAN 111X17 SCALE: 1" = 100'
TAXLOT #: 051W08CB04800
ZONING: P/SP
TAXLOT #: 051W08BC00601
ZONING: P/SP
TAXLOT #: 051W08CB04901
ZONING: IL
TAXLOT #: 051W08CB04700
ZONING: P/SP
ZONING: RM
TAXLOT #: 051W08CB04500
ZONING: RM
N
F
R
O
N
T
S
T
M O
U N
T H
O O
D A
V E
NOTE:
THIS IS NOT A SURVEY; ALL EXISTING
INFORMATION IS PROVIDED BY GIS &
SIDE WALK NOTES.
PROPOSED PROJECT AREA
SEE SHEET C-2 FOR DETAILS
11X17 SCALE: 1" = 28' 22X34 SCALE: 1" = 14' ENLARGED SITE PLAN 1
ENLARGED
SITE PLAN
C-2
SHEET NUMBER:
SHEET TITLE:
LICENSURE:
DRAWING INFORMATION:
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
07-19-24 SITE SKETCH
10-29-24 PRELIMINARY ZONING DRAWINGS
09-25-25
PRELIMINARY CONSTRUCTION DRAWINGS
10-13-25 FINAL CONSTRUCTION DRAWINGS
PROJECT INFORMATION:
12725 SW MILLIKAN WAY
SUITE 300
BEAVERTON, OR 97005
(503) 387-5331 www.cushingcivilengineers.com
Cushing
Civil Engineers
Civil Engineers
MARION COUNTY
METCOM911
1060 MT HOOD AVE
WOODBURN, OR 97071
1,2 C-3
(EX) 150'-0" MONOPOLE TOWER;
SEE SHEET C-3 FOR ELEVATIONS
(EX) ICE BRIDGE TO REMAIN
(EX) BUILDING
(EX) EQUIPMENT INSIDE
ELECTRICAL/DATA ROOM
BY OTHERS, TYP
(EX) ELECTRICAL/DATA ROOM
(EX) TREE TO
BE REMOVED
(P) 10'x12' EQUIPMENT SHELTER;
SEE SHEET SH-1 THRU SH-4 FOR DETAIL
(EX) TREE TO BE REMOVED
(EX) TREE, TYP
(P) ±33.5 LF ICE BRIDGE;
SEE SHEET C-4 FOR DETAIL
NOTES:
1. TOWER INFO SHOWN FOR CONCEPTUAL USE ONLY.
SEE TOWER STRUCTURAL DESIGN BY OTHERS.
2. THIS IS NOT A SURVEY ALL EXISTING INFORMATION IS
PROVIDED BY GIS, SURVEY & SITE WALK NOTES.
3. PROPOSED AND EXISTING ANTENNAS NOT SHOWN
FOR CLARITY.
8'
'-6
(P) SHELTER FOUNDATION;
SEE SHEET C-6 FOR DETAIL
(P) DAIKIN SPLIT HVAC TO BE PROVIDED
BY CONTRACTOR, TYP OF (2);
SEE SHEET C-5 FOR DETAIL
ELECTRICAL SERVICE TBD
COAX
LICENSURE:
DRAWING INFORMATION:
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
07-19-24 SITE SKETCH
10-29-24 PRELIMINARY ZONING DRAWINGS
09-25-25
PRELIMINARY CONSTRUCTION DRAWINGS
10-13-25 FINAL CONSTRUCTION DRAWINGS
PROJECT INFORMATION:
12725 SW MILLIKAN WAY
SUITE 300
BEAVERTON, OR 97005
(503) 387-5331 www.cushingcivilengineers.com
Cushing
Civil Engineers
Civil Engineers
MARION COUNTY
METCOM911
1060 MT HOOD AVE
WOODBURN, OR 97071
11X17 SCALE: 1" = 20' 22X34 SCALE: 1" = 10'EXISTING WEST ELEVATION 1 11X17 SCALE: 1" = 20'PROPOSED WEST ELEVATION 222X34 SCALE: 1" = 10'
ELEVATIONS
C-3
SHEET NUMBER:
SHEET TITLE:
(EX) TOWER TOP ±150.0' AGL
(BY OTHERS)
GROUND LEVEL (GL) GROUND LEVEL (GL)
(EX) 150'-0" MONOPOLE TOWER
TO REMAIN
(EX) BUILDING TO REMAIN
(EX) 150'-0" MONOPOLE TOWER
(EX) BUILDING
(EX) ANTENNA BY OTHERS, TYP
(EX) ANTENNA BY OTHERS, TYP
(EX) TOWER TOP ±150.0' AGL
(BY OTHERS)
(P) 4'Ø MICROWAVE ANTENNA;
COMMSCOPE - VHLPX4-11W
AZIMUTH = 160.63°
(TO EASTVIEW LANE)
(P) 4'Ø MICROWAVE ANTENNA;
COMMSCOPE - VHLPX4-11W
AZIMUTH = 347.31°
(TO PARRETT MOUNTAIN)
(P) ANTENNA CL ±135.0' AGL
(P) ANTENNA CL ±114.0' AGL
(P) ICE BRIDGE (P) EQUIPMENT SHELTER
NOTES:
1. TOWER INFO SHOWN FOR CONCEPTUAL USE ONLY. SEE
TOWER STRUCTURAL REPORT FOR DETAIL.
2. LOADING INFORMATION PROVIDED BY TAIT COMMUNICATIONS.
(P) COAX CABLE
COMPOUND
DETAILS
C-4
SHEET NUMBER:
SHEET TITLE:
LICENSURE:
DRAWING INFORMATION:
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
07-19-24 SITE SKETCH
10-29-24 PRELIMINARY ZONING DRAWINGS
09-25-25
PRELIMINARY CONSTRUCTION DRAWINGS
10-13-25 FINAL CONSTRUCTION DRAWINGS
PROJECT INFORMATION:
12725 SW MILLIKAN WAY
SUITE 300
BEAVERTON, OR 97005
(503) 387-5331 www.cushingcivilengineers.com
Cushing
Civil Engineers
Civil Engineers
MARION COUNTY
METCOM911
1060 MT HOOD AVE
WOODBURN, OR 97071
SCALE: NTS
1SCALE: NTS
STOOP SECTION DETAIL
3SCALE: NTS
ICE BRIDGE DETAIL 4SCALE: NTS
SIGN DETAILS POWER LINE TRENCH
SIGN NOTES:
1. SIGN MATERIAL: 18GA
ALUMINUM
2. LETTERING COLOR =
BLACK / WHITE
3. BACKGROUND COLOR =
WHITE / BLUE
7"
SIGN NOTES:
1. SIGN MATERIAL: 18GA
ALUMINUM
2. LETTERING COLOR =
BLACK
3. BACKGROUND COLOR =
WHITE / RED
12"
SIGN NOTES:
1. SIGN MATERIAL: 18GA
ALUMINUM
2. LETTERING COLOR =
BLACK
3. BACKGROUND COLOR =
YELLOW
36" OC MAX
10'-0" OC MAX
FIELD VERIFY
12"
2"CLR.
2'-0"
CLR MIN.
COAX BRIDGE: 14 GA.
GALV. GRIPSTRUT 24"
WIDTH, 2" PLANK 14 GA.
SUPPORT COLUMN: 4"Ø
O.D. GALV. SCHED. 40
POST @ 10'-0" O.C. MAX
CROWN TO DRAIN; TYP.
FOOTING
MUST BE 6"
BELOW
FROST LINE,
TYP.
SIDE ELEVATIONFRONT ELEVATION
NOTE: GROUND COAX BRIDGE PER THE REQUIREMENTS
OF THE NEC STANDARDS - SEE DETAIL 1/E-2
COAX SUPPORT BLOCKS
AT 3'-0" MAX O.C.
EDGE OF
SHELTER
20" UNISTRUT W/ NUT
AND WASHER EACH
SIDE/ EACH LEVEL AS
REQUIRED
12"Ø X 48" DEEP CONC.
FOOTING; TYPICAL
COAX BRIDGE-(2) 24" WIDE
SAFETY GRATED WAVE
GUIDE BRIDGE CHANNEL,
OR APPROVED EQUAL
DUAL POST 24" ICE
BRIDGE KIT SITE PRO1
PART# 4B24D OR
APPROVED EQUAL
8"
2-1/2"
1-1/2"
8" x 8" x 1/2" PLATE
SUPPORT PIPE
1/2"Ø HILTI-KWIK-BOLT-TZ
SS EXPANSION ANCHOR
MIN 2" EMBED (TYP. OF 4)
5/16 TYP
8" x 8" x 1/2" PLATE
CONC. SLAB (IF
REQUIRED)
B
ICE-BRIDGE
SUPPORT POST
SECTION B
BASE PLATE - OPTIONAL
PIPE TO CONC
ATTACHMENT
7"
MARION COUNTY
1/4" PER FOOT SLOPE
(BROOM FINISH)
6" CONCRETE SLAB
(2,500 PSI) W/
#4 BARS @ 12" O.C.
EACH WAY 3" CLR
SHELTER DOOR &
FLOOR BY OTHERS
4'x4' CONCRETE
STOOP
CRUSHED AGGREGATE
EXISTING GROUND
SHELTER FOUNDATION BY OTHERS
3"
6"
MIN
3"
FINISH GRADE
3/4" CHAMFER
ON EDGES
6" STEP
" E
LE
CT
RI
CA
L P
RI
MA
RY
" E
LE
CT
RI
CA
L S
EC
ON
DA
RY
2'- 6"
T O
3'- 6"
±4
±4
12" MIN
CLEAR
24"±
WARNING TAPE
FINISH GRADE
UNEXCAVATED EARTH
COMPACTED FILL
(85% IN LANDSCAPED AREAS,
95% IN PAVED AREAS)
ELECTRICAL CONDUIT(S); 3"Ø
MIN, SCHEDULE 40 PVC, OR
AS SHOWN ON PLAN
COMPACTED SANDNOTES:
1. EXCAVATE TO REQUIRED DEPTH.
2. VERIFY ALL TRENCHING REQUIREMENTS PER LOCAL UTILITIES.
3. CONTRACTOR TO PROVIDE (1) 300 POUND NYLON PULL CORD
AND CONDUCTORS AS REQUIRED PER CONDUIT.
CONTRACTOR TO VERIFY WITH
MARION COUNTY PM IF SPARE
CONDUIT TO BE PLACED IN
TRENCH FOR FUTURE
HVAC DETAILS
C-5
SHEET NUMBER:
SHEET TITLE:
LICENSURE:
DRAWING INFORMATION:
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
07-19-24 SITE SKETCH
10-29-24 PRELIMINARY ZONING DRAWINGS
09-25-25
PRELIMINARY CONSTRUCTION DRAWINGS
10-13-25 FINAL CONSTRUCTION DRAWINGS
PROJECT INFORMATION:
12725 SW MILLIKAN WAY
SUITE 300
BEAVERTON, OR 97005
(503) 387-5331 www.cushingcivilengineers.com
Cushing
Civil Engineers
Civil Engineers
MARION COUNTY
METCOM911
1060 MT HOOD AVE
WOODBURN, OR 97071
DAIKIN HEAT PUMP - FTX36NVJU / RX36NMVJUA 2SCALE: NTS CONDENSING UNIT WALL MOUNT1SCALE: NTS
EQUIPMENT
SHELTER
FOUNDATION PLAN
C-6
SHEET NUMBER:
SHEET TITLE:
LICENSURE:
DRAWING INFORMATION:
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
07-19-24 SITE SKETCH
10-29-24 PRELIMINARY ZONING DRAWINGS
09-25-25
PRELIMINARY CONSTRUCTION DRAWINGS
10-13-25 FINAL CONSTRUCTION DRAWINGS
PROJECT INFORMATION:
12725 SW MILLIKAN WAY
SUITE 300
BEAVERTON, OR 97005
(503) 387-5331 www.cushingcivilengineers.com
Cushing
Civil Engineers
Civil Engineers
MARION COUNTY
METCOM911
1060 MT HOOD AVE
WOODBURN, OR 97071
1SCALE: NTS EQUIPMENT SHELTER FOUNDATION PLAN
(2) #5 CONT. @
MID HT. OF FTG.
#5 @ 12" O.C., EA. TYP.
SEC
A
22"
TROWELED FINISH
#5 @ 12" EW
(BOTH DIRECTIONS)
#5 BARS @
5" O.C. @ TOP
& BOTT., (TYP)
2'-0"
(SEE NOTE 9)
3/4" MINUS CRUSHED
ROCK (COMPACTED 95%)
(SEE NOTE 8)
±6
GEOTEXTILE FABRIC
(SEE NOTE 8)
1"
CHAMFER
STRUCTURAL FILL UNDER SHELTER
SLAB AND UNDER GRADE BEAMS
(SEE NOTE 5 AND NOTE 10)
6"
1/2" PREFORMED JOINT FILLER & SEALER, TYP
2-3/8"
CLR
3" CLR
(TYP)
8" CLR
(TYP)
2-3/8"
CLR
#3 TIES @
12" O.C. (TYP)
3/4" MINUS CRUSHED
ROCK (COMPACTED 95%)
(SEE NOTE 8)
5"
PROPOSED VAPOR BARIER
(SEE NOTE 7)
NOTES:
1. ULTIMATE COMPRESSIVE STRENGTH OF CONCRETE AT 28 DAYS SHALL BE 3000 PSI, UNLESS
OTHERWISE SPECIFIED.
2. REINFORCING BARS SHALL BE DEFORMED BARS CONFORMING TO ASTM A615 "DEFORMED
AND PLAIN BILLET STEEL BARS FOR CONCRETE REINFORCEMENT," LATEST EDITION, GRADE
60.
3. LAP LENGTH FOR SPLICES SHALL NOT BE LESS THAN CLASS B SPLICE, UNLESS OTHERWISE
SPECIFIED. WELDING OF REINFORCEMENT WILL NOT BE PERMITTED.
4. CONTRACTOR MAY USE EARTH FORMS FOR UNEXPOSED CONCRETE WHERE SOIL IS FIRM
AND STABLE. EARTH FORMS SHALL BE TRENCHED NEATLY AND ACCURATELY. SIDES OF
FOUNDATIONS, WHERE EARTH SLOUGHS, SHALL BE FORMED. EARTH FORMS SHALL BE
TAMPED FIRM, AND CLEANED OF ALL DEBRIS AND LOOSE MATERIAL, BEFORE DEPOSITING
CONCRETE.
5. STRUCTURAL FILL USED FOR SITE GRADING SHALL BE FREE FROM TOP SOIL, ORGANIC
CONTAMINATED SOIL, AND ROCK FRAGMENTS HAVING A MAXIMUM DIMENSION GREATER
THAN 3 INCHES. MATERIAL SHALL BE CLEAN AND SHALL BE SUBJECT TO THE FOLLOWING
RESTRICTIONS.
SILT CLAYS OR SANDY CLAY
PLASTICITY INDEX 10 TO 24
LIQUID LIMIT <45
CLAYEY SANDS OR SLIGHTLY CLAYEY SILTY SANDS
PLASTICITY INDEX 3 TO 15
LIQUID LIMIT <35
6. MINIMUM CONCRETE COVER FOR REINFORCEMENT SHALL BE 3 INCHES FOR CONCRETE
CAST AGAINST AND PERMANENTLY EXPOSED EARTH AND 1-1/2 INCHES FOR TOP BARS ON
SIDEWALK AND SHELTER FOUNDATIONS.
7. VAPOR BARRIER SHALL BE VAPORBLOCK 10, OR APPROVED EQUAL.
8. CRUSHED ROCK AND GEOTEXTILE FABRIC IN THE COMPOUND AREA SHALL MEET THE
REQUIREMENTS OF DETAIL 3 ON DWG C-5 AND ALL APPLICABLE GRADING NOTES.
9. IN INSTANCES WHERE ROCK IS ENCOUNTERED AT LESS THAN 2'-0", CONCRETE MAY BEAR
ON THE ROCK.
10. PAINT SHEAR PLATES WITH COLD GALV.
SECTION A
FOUNDATION PLAN
UFER GROUND, SEE
ELECTRICAL SHEETS
FINISH GRADE
CONCRETE SLAB
14'
1'
(TYP)
10'x12' EQUIPMENT SHELTER
SHELTER FOUNDATION
SHELTER TIE-DOWN, TYP
PER STANDARD TIE-DOWN DETAIL THIS SHEET
SAW CUT CONTROL JOINTS
1/8" WIDE AND 1 1/4" DEEP,
JUST AFTER SET FIRM
USING EARLY ENTRY SAW
12"
STANDARD TIE-DOWN DETAIL
NOTES:
1. TIEDOWN HARDWARE:
1.1. CLAMP PLATE, 3/8"x3"x4" GALV. STEEL
1.2. 1/2" BEVEL WASHER
1.3. ANCHOR BOLT- 1/2-10x12" HEX HEAD
1.4. 1/2"-10 HEAVY HEX NUT BY OTHERS.
±9"
SITE GROUNDING
PLAN & DETAILS
E-1
SHEET NUMBER:
SHEET TITLE:
LICENSURE:
DRAWING INFORMATION:
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
07-19-24 SITE SKETCH
10-29-24
PRELIMINARY ZONING DRAWINGS
09-25-25 PRELIMINARY CONSTRUCTION DRAWINGS
10-13-25 FINAL CONSTRUCTION DRAWINGS
PROJECT INFORMATION:
12725 SW MILLIKAN WAY
SUITE 300
BEAVERTON, OR 97005
(503) 387-5331 www.cushingcivilengineers.com
Cushing
Civil Engineers
Civil Engineers
MARION COUNTY
METCOM911
1060 MT HOOD AVE
WOODBURN, OR 97071
11X17 SCALE: 1" = 8' 22X34 SCALE: 1" = 4' SITE COMPOUND GROUNDING PLAN 1
SCALE: NTS 3 SCALE: NTS 2 TERRADYNE ELECTROLYTIC GROUND ELECTRODE
GENERAL NOTES:
1. ALL INSTALLATIONS ARE TO BE FIELD VERIFIED.
2. GROUND CONDUCTORS ARE TO BE BURIED AT A MINIMUM 30" BELOW
GRADE OR 6" BELOW FREEZE LINE, WHICHEVER IS GREATER.
3. ALL BELOW GRADE GROUNDING CONDUCTORS ARE TO BE ENCOMPASSED
IN A 2" X 4" BED OF SOIL ENHANCEMENT MATERIAL.
4. BONDS TO FENCE POSTS ARE TO BE MADE AT 12" ABOVE GRADE WHERE
APPLICABLE.
5. NO CONDUCTOR SHALL HAVE A BEND IN RADIUS OF LESS THAN 12" AND
SHALL NOT EXCEED 90 DEGREES.
6. TERRADYNE ELECTROLYTIC GROUND ELECTRODES ARE NOT TO SHARE
THE SAME TRENCH AS GROUNDING CONDUCTOR, NOR RUN IN A PARALLEL
PATH TO THE CONDUCTOR.
7. ALL GROUND SYSTEMS ARE TO BE MADE COMMON.
8. ALL BONDS ARE TO BE COATED WITH ANTI-OXIDATION COMPOUND.
9. WHERE STANDARD GROUND ELECTRODES ARE UNABLE TO BE DRIVEN, 12"
X 12" X 1/8" COPPER GROUND PLATES SHALL BE INSTALLED 30" BELOW
FINISHED GRADE & ENCOMPASSED IN 50LBS OF TERRAFILL SOIL
ENHANCEMENT MATERIAL.
LEGEND:
TERRADYNE TG-100L-H36-2T-36-4F-P SERIES
ELECTRODE W/ INSPECTION WELL
EXOTHERMIC WELD
MECHANICAL CONNECTION
5/8" X 10' COPPER CLAD GROUND ELECTRODE
5/8" X 10' COPPER CLAD GROUND ELECTRODE
WITH INSPECTION SLEEVE
#2 TINNED SOLID COPPER CONDUCTOR
SOIL ENHANCEMENT DETAIL
POLYMER TEST WELL
4"
M
I N
#2 TINNED BARE
COPPER
CONDUCTOR
TERRAFILL SOIL
ENHANCEMENT
MATERIAL
TERRAFILL SOIL
ENHANCEMENT MATERIAL
(DISTRIBUTED EQUALLY)
EXOTHERMIC WELD (AT FACTORY)
#2 TINNED BARE COPPER
CONDUCTOR (AT FACTORY)
36" VERTICAL RISER
EXOTHERMIC WELD TO GROUND RING
20' HORIZONTAL ELECTRODE SHFT
VENTILATION PORT
(NOTE: PORT SHALL NOT BE
COVERED IN EARTH)
(P) PROPOSED BOND TO ANTENNA AND
TOWER EQUIPMENT PER MANUF'S
REQUIREMENTS AND INDUSTRY STANDARDS
ASSUMED BUILDING GROUNDING
TIE SHELTER GROUND RING AND
ASSUMED BUILDING GROUNDING
TOGETHER IN 2 PLACES
(P) BOND TO SHELTER EQUIPMENT (HVAC,
ELECTRIC SERVICE) TYP - PER MANUF'S
REQUIREMENTS AND NEC STANDARDS
TIE SHELTER GROUND RING AND TOWER
GROUND RING TOGETHER IN 2 PLACES
(P) SHELTER GROUND RING
(P) 5/8" X 10' COPPER CLAD GROUND
ELECTRODE TYP - 20' MAX SPACING
(P) 5/8" X 10' COPPER CLAD GROUND
ELECTRODE WITH INSPECTION SLEEVE TYP
ASSUMED TOWER GROUND RING
(P) BOND TO WAVEGUIDE BRIDGE
SUPPORT - PER MANUF'S
REQUIREMENTS AND NEC STANDARDS
TGB
MGB
SHELTER HALO
EGB(P) #2 TINNED SOLID BARE COPPER CONDUCTOR
BURIED AT 30" BELOW FINSIHED GRADE -
ENCOMPASSED IN A 4" X 2" BED OF TERRAFILL SOIL
ENHANCEMENT MATERIAL - TYP. (REF: DETAIL 2)
ONLY FOR
REFERENCE
GROUNDING
DETAILS I
E-2
SHEET NUMBER:
SHEET TITLE:
LICENSURE:
DRAWING INFORMATION:
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
07-19-24 SITE SKETCH
10-29-24
PRELIMINARY ZONING DRAWINGS
09-25-25 PRELIMINARY CONSTRUCTION DRAWINGS
10-13-25 FINAL CONSTRUCTION DRAWINGS
PROJECT INFORMATION:
12725 SW MILLIKAN WAY
SUITE 300
BEAVERTON, OR 97005
(503) 387-5331 www.cushingcivilengineers.com
Cushing
Civil Engineers
Civil Engineers
MARION COUNTY
METCOM911
1060 MT HOOD AVE
WOODBURN, OR 97071
GROUND TO TOWER
GROUND AND WEATHER
PROOFING KITS, INSTALL
BELOW ANTENNAS, (TYP.)
GROUND TAIL,
(TYP.) GROUNDED
UNISTRUT OR
TRAPEZE
NOTE: WEATHER PROOF ALL FEED LINE CONNECTIONS
AND GROUNDS PER NEC STANDARDS AND PER
ATTACHED WEATHER PROOFING DRAWING
NOTE: NOT GC
RX
MULTICOUPLER
* CONTRACTOR TO PROVIDE STUB UP (TYP.)
GENERAL NOTES
ALL ANTENNAS, LINES AND RELATED
INSTALLATION HARDWARE TO BE
PROVIDED BY THE LAND MOBILE
COMMUNICATIONS PROVIDER.
25MM SQ. CSA (#4 AWG) OR
COARSER BARE COPPER
CONDUCTOR OR STEEL
REINFORCING BAR OR ROD,
NOT LESS THAN 0.5" Ø AND AT
LEAST 20' LONG
GROUNDING
ELECTRODE
CONDUCTOR
CONNECTION
LISTED FOR
THE PURPOSE
FOUNDATION
IN DIRECT
CONTACT
WITH EARTH
±2" MIN.
NOTE: FOR REFERENCE ONLY
NONMETALLIC
PROTECTIVE
SLEEVE
NEW
GROUND
RING
BOND
EQUIPMENT
TO NEW
GROUND RING
AND UFER
FOR ALL NEW
CONCRETE
PADS
COAX CABLE GROUNDING
KITS
ANTENNA MOUNT GROUND
NOTE:
1. DO NOT BOND AIR TERMINAL OR
LIGHTNING ROD TO AGB
2. AGB GROUND BAR TO BE PLATED.
AGB TO BE BONDED DIRECTLY TO
TOWER.
HARGER 1/4"X4"X20" TIN PLATED
GROUNDING BAR #TGBIA14412M OR
SIMILAR PER NEC AGB GROUNDING
6SCALE: NTS GROUND BAR DETAILS STANDARD RX GROUNDING SCHEMATICS
3SCALE: NTS
FEED LINE CABLE GROUNDING
NOTES
1. TYP. FOR ALL GROUND WIRES FOR
ELECT. AND OTHER EQUIPMENT.
2. THE ENTIRE LUG AND AREA TO BE
SPRAYED WITH CLEAR LACQUER OR
COLD GALVANIZING SPRAY.
3. GROUND LEADS TO BE EXOTHERMIC
WELDED TO GROUND RING.
4. AGB IS BONDED TO TOWER.
MGB (AT BASE OF TOWER AND EQUIPMENT)
= EXOTHERMIC
AGB (AT ANTENNAS)
TYPE GR
TYPE GT
TYPE VV
TYPE GY
TYPE VS
TYPE TA
TYPE VN
TYPE GL
TYPE VB
TYPE PT
TYPE NC
TYPE SS
5/8" X 10' COPPER CLAD STEEL GROUND ROD, TO
BE PLACED ON CENTER 10' ALONG CONDUCTOR
EXOTHERMIC TYPE "GT"4
MAIN CONDUCTOR, COPPER CABLE
EXOTHERMIC TYPE "NC"
NOTE: BENDS SHOWN ON GROUND TAILS AND GROUND CONNECTION WIRES ARE FOR
ILLUSTRATION PURPOSES ONLY. AVOID EXCESSIVE BENDS. WIRES TO BE AS
STRAIGHT AS POSSIBLE; INSTALL DIRECT FROM EQUIPMENT TO GROUND POINT.
ALL GROUNDING DESIGN, SPECIFICATIONS, AND CONSTRUCTION METHODS
SHALL COMPLY WITH THE MOTOROLA R56 "STANDARDS AND GUIDELINES FOR
COMMUNICATION SITES".
EXOTHERMIC CONNECTION
MECHANICAL CONNECTION
2SCALE: NTS
TYPICAL EXOTHERMIC CONNECTION DETAILS
NOTE: ALL GROUNDING
DESIGN, SPECIFICATIONS,
AND CONSTRUCTION
METHODS SHALL COMPLY
WITH THE MOTOROLA R56
"STANDARDS AND GUIDELINES
FOR COMMUNICATION SITES".
FIGURE 6FIGURE 5FIGURE 4FIGURE 3FIGURE 2FIGURE 1
2"
BUSS BAR OR FLAT SURFACE
OF EQUIP. / WIREWAY
REMOVE PAINT (IF
PRESENT) AND APPLY
ANTIOXIDANT COMPOUND
3/8" S.S LOCKWASHER
(TYP.)
3/8" S.S. HEXNUT 3/8" X 1" S.S
HEXBOLT
HARGER TIN PLATED GROUNDING BAR #TGBIA14412M
(OR EQUAL) WITH HOLE PATTERN, STANDOFF
INSULATORS AND MOUNTING BRACKETS AS SHOWN
#2 SOLID BARE TINNED
COPPER WIRE TO
GROUND RING -
PROVIDE (2) PER MGB
COAX CABLE GROUNDING KITS WITH
LONG BARREL COMPRESSION LUGS,
INSTALLED BY CONTRACTOR.
GROUND ROD DETAIL 4SCALE: NTS
#6 GROUND LEAD
TWO HOLE
COMPRESSION
CRIMP LUG (#6) TO
GROUND BAR
ADJUSTABLE
BAND CLAMP
GROUNDING
CLAMP
ADJUSTABLE BAND
CLAMP
1/4" 20 HARDWARE
#6 GROUND LEAD
'SCOTCH' 23 TAPE
OVER VINYL TAPE
PUTTY TAPE
GROUNDING
STRAP ASSEMBLY
GROUNDING
CLAMP
1SCALE: NTS
TOWER TOP AMPLIFIER
ANTENNA, (TYP.)
'N' MALE CONNECTORS
(WEATHERPROOF)
GROUND AND WEATHER
PROOFING KITS, INSTALL
BELOW ANTENNAS, (TYP.)
GROUND TAIL, (TYP.)
AGB MOUNTED TO
TOWER DIRECTLY
BELOW ANTENNAS,
BY OTHERS
SEE * NOTE
'DIN' MALE CONNECTORS
(WEATHERPROOF)
TGB MOUNTED
TO BASE OF
TOWER, BY
OTHERS
SEE * NOTE
GROUND AND WEATHERPROOFING
KITS, LOCATED NEAR EQUIPMENT,
(TYP.)
#2 THW GREEN (TYP)
MOUNT EGB ON
SHELTER, BY
OTHERS
SEE * NOTE
BOND EGB TO GROUND RING
- #2 SOLID BARE TINNED
COPPER (TYP ALL MGB'S)
SHELTER GROUNDING RINGTOWER GROUNDING RING
EQUIPMENT JUMPER
CABLE, SEE SHEETS
RF-1 AND RF-2 FOR
DETAILS
EQUIPMENT
SHELTER
LDF4-5DB
APPROX. 3 FT.
'DIN' MALE CONNECTOR
'DIN' FEMALE CONNECTOR
BOND ALL
EQUIPMENT TO
MGB - #2 THW
GREEN (TYP)
GROUND FROM
MGB TO
EQUIPMENT
RACK
GROUND
UNISTRUT OR
TRAPEZE TO
MGB
MGB IN
SHELTER,
BY
OTHERS
SEE *
NOTE
LIGHTENING
ARRESTOR
'DIN' FEMALE
TO ANTENNA
AND 'N' FEMALE
TO EQUIPMENT.
HARD
MOUNTED TO
GROUNDED
UNISTRUT.
PASS DC UP TO
15 V TO POWER
TTA
FSJ4-50B
APPROX. 40 FT.
'N'
CONNECTORS
'DIN' MALE
CONNECTORS
'DIN' MALE
CONNECTORS
LDF4-50B
APPROX. 6 FT.
EACH LEG TO SITE RING 2 LOCATIONS TO
SITE RING
#2 STRD. GREEN
INSULATED WIRE TWO HOLE COMPRESSION
CRIMP LUG (#2) DETAIL IS TYP.
OF TWO NUTS & BOLTS
5SCALE: NTS UFER DETAIL
AGB MOUNTED TO
TOWER AT EVERY
75', BY OTHERS
SEE * NOTE
ONLY FOR
REFERENCE
ONLY FOR
REFERENCE
GROUNDING
DETAILS II
E-3
SHEET NUMBER:
SHEET TITLE:
LICENSURE:
DRAWING INFORMATION:
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
07-19-24 SITE SKETCH
10-29-24
PRELIMINARY ZONING DRAWINGS
09-25-25 PRELIMINARY CONSTRUCTION DRAWINGS
10-13-25 FINAL CONSTRUCTION DRAWINGS
PROJECT INFORMATION:
12725 SW MILLIKAN WAY
SUITE 300
BEAVERTON, OR 97005
(503) 387-5331 www.cushingcivilengineers.com
Cushing
Civil Engineers
Civil Engineers
MARION COUNTY
METCOM911
1060 MT HOOD AVE
WOODBURN, OR 97071
'N' MALE CONNECTOR
WEATHERPROOF
MICROWAVE (TYP.)
TGB AT BASE OF
TOWER, BY
OTHERS
SEE * NOTE
WEATHERPROOF
ELLIPTICAL FEED LINE
MOUNT EGB ON
SHELTER, BY
OTHERS
SEE * NOTE
LIGHTNING
ARRESTOR GROUND
FROM
BUILDING
TO
EQUIPMENT
RACK
'DIN' MALE CONNECTOR
'DIN' FEMALE CONNECTOR
GROUND UNISTRUT OR TRAPEZE TO MGB
FEED LINE
WEATHERPROOF
GROUND
TO TOWER
GPS UNITS
TGB AT BASE
OF TOWER,
BY OTHERS
SEE * NOTE
MGB, BY
OTHERS
SEE * NOTE
MOUNT EGB
ON
SHELTER, BY
OTHERS
SEE * NOTE
'N' MALE
CONNECTOR
GROUND FROM
BUILDING TO
EQUIPMENT
GROUND UNISTRUT OR
TRAPEZE TO MGB
FEED LINE
'N' MALE CONNECTOR
SHELTER GROUNDING RING
TOWER GROUNDING RING
EACH LEG TO SITE RING
2 LOCATIONS TO
SITE RING
MGB, BY
OTHERS
SEE * NOTE
TX
COMBINER
OR
STATION
EXOTHERMIC CONNECTION
MECHANICAL CONNECTION
EXOTHERMIC CONNECTION
MECHANICAL CONNECTION
TRAK
REFERENCE
STANDARD
PORT
ZETRON
MODEL 620
2SCALE: NTS1
SCALE: NTS SHELTER GROUNDING RING
TOWER GROUNDING RING
EACH LEG TO SITE RING
2 LOCATIONS TO
SITE RING
GROUND TO TOWER
TYPICAL MICROWAVE ANTENNA GROUNDING SCHEMATICS TYPICAL GPS ANTENNA GROUNDING SCHEMATICS
NOTE:
TOWER INFO SHOWN FOR CONCEPTUAL
USE ONLY. SEE TOWER STRUCTURAL
REPORT BY OTHERS.
GROUND MW MOUNT TO AGB
DRAWING INFORMATION:
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
07-19-24 SITE SKETCH
10-29-24
PRELIMINARY ZONING DRAWINGS
09-25-25 PRELIMINARY CONSTRUCTION DRAWINGS
10-13-25 FINAL CONSTRUCTION DRAWINGS
PROJECT INFORMATION:
12725 SW MILLIKAN WAY
SUITE 300
BEAVERTON, OR 97005
(503) 387-5331 www.cushingcivilengineers.com
Cushing
Civil Engineers
Civil Engineers
MARION COUNTY
METCOM911
1060 MT HOOD AVE
WOODBURN, OR 97071
RF TOWER
APPURTENANCES I
RF-1.0
SHEET NUMBER:
SHEET TITLE:
LOCATION INFORMATION
COUNTY MARION COUNTY
STREET ADDRESS 1060 MT HOOD AVE
CITY WOODBURN STATE OR
ZIP CODE 97071
LATITUDE (DEC.)/(DEG) 45.150950 / 45° 09'03.4" N
LONGITUDE (DEC.)/(DEG) -122.843472 / 122°50'36.5" W
SITE INFORMATION
SITE NAME METCOM911
TOWER INFORMATION
STRUCTURE MONOPOLE TOWER MANUFACTURER SABRE
TOWER OWNER METCOM SERIAL/MODEL # 07 07143
GROUND ELEVATION ±186' # OF APPURTENANCE -
# OF LEGS - HIGHEST POINT W/ ANT -
TOWER HEIGHT W/O ANT 150'
NOTE:
INFORMATION FROM TAIT COMMUNICATIONS' DOCUMENT
DATED 08/13/2025 PROVIDED BY MARION COUNTY.
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
07-19-24 SITE SKETCH
10-29-24
PRELIMINARY ZONING DRAWINGS
09-25-25 PRELIMINARY CONSTRUCTION DRAWINGS
10-13-25 FINAL CONSTRUCTION DRAWINGS
PROJECT INFORMATION:
12725 SW MILLIKAN WAY
SUITE 300
BEAVERTON, OR 97005
(503) 387-5331 www.cushingcivilengineers.com
Cushing
Civil Engineers
Civil Engineers
MARION COUNTY
METCOM911
1060 MT HOOD AVE
WOODBURN, OR 97071
RF TOWER
APPURTENANCES II
RF-1.1
SHEET NUMBER:
SHEET TITLE:
NOTE: MODEL SHOWN IS PRELIMINARY AND SUBJECT TO CHANGE UPON FINAL RF CONFIGURATION.
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
07-19-24 SITE SKETCH
10-29-24 PRELIMINARY ZONING DRAWINGS
09-25-25 PRELIMINARY CONSTRUCTION DRAWINGS
10-13-25 FINAL CONSTRUCTION DRAWINGS
PROJECT INFORMATION:
12725 SW MILLIKAN WAY
SUITE 300
BEAVERTON, OR 97005
(503) 387-5331 www.cushingcivilengineers.com
Cushing
Civil Engineers
Civil Engineers
MARION COUNTY
METCOM911
1060 MT HOOD AVE
WOODBURN, OR 97071
EQUIPMENT
SHELTER EXTERIOR
ELEVATIONS
SH-1
SHEET NUMBER:
SHEET TITLE:
NOTE:
INFORMATION…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .