Attachment_9_-_Steam_Distribution_Installation_Manual.pdf
PDF 498 KB Posted
- Attached to
- Modify Humidification System at OKX Federal contract opportunity
- Solicitation number
- 1305M326Q0464
About this file
This is a Steam Distribution Installation Manual for Condair-manufactured steam distributors (ASD/BSD/CSD/RSD/SSD models). The manual provides comprehensive guidance for receiving, unpacking, and installing steam distribution equipment used in humidification systems.
The manual specifies equipment capacity limits for each distributor model: ASD 10 at 22 lbs/hr (10 kg/hr), ASD at 25 lbs/hr (11 kg/hr), BSD at 35 lbs/hr (16 kg/hr), CSD at 115 lbs/hr (53 kg/hr), RSD at 10 lbs/hr (4.5 kg/hr), and SSD at 10 lbs/hr (4.5 kg/hr). The manual provides detailed material recommendations for steam and condensate lines, with specific sizing guidelines based on load and run length. For short runs below 10 feet, Condair steam hose, copper tube, or stainless steel tube are acceptable; for runs exceeding 10 feet, copper or stainless steel tubing is required. Steel piping is not recommended due to corrosion concerns. The installation instructions address both horizontal and vertical airflow configurations, with specific spacing, clearance, and positioning requirements for each distributor type. Condensate return guidelines mandate individual trapping of all distributors, proper drainage slope (2 inches per foot rising, ½ inch per foot falling), and regular trap placement at 20-foot intervals. The manual includes detailed diagrams for drain tee configuration, distributor mounting positions, and minimum clearance distances. Spare parts are identified by part number for inlet and end cap assemblies. The warranty covers two years from installation or 30 months from manufacture date, limited to replacement parts F.O.B. the factory, and excludes consequential damage, freezing damage, and improper installation or maintenance.
View the file
Other files for this federal contract opportunity
Show all 15
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Steam
Distribution Installation Manual Includes installation instructions for steam distributions ASD/BSD/CSD/RSD/SSD.
1506117-D| 11 OCT 2018
Important: Read and save these instructions. This guide to be left with equipment owner.
Thank you for choosing Condair.
Proprietary Notice
This document and the information disclosed herein are proprietary data of Condair Ltd. Neither this document nor the information contained herein shall be reproduced, used, or disclosed to others without the written authorization of Condair Ltd., except to the extent required for installation or maintenance of recipient’s equipment.
Liability Notice
Condair does not accept any liability for installations of humidity equipment installed by unqualified personnel or the use of parts/components/equipment that are not authorized or approved by Condair.
Copyright Notice
© Condair Ltd. All rights reserved.
INSTALLATION DATE (MM/DD/YYYY)
MODEL #
SERIAL #
CYLINDER #
INSTALLATION DATE (MM/DD/YYYY)
MODEL #
SERIAL #
CYLINDER #
Contents
2 Installation
2 Receiving and Unpacking
2 Pre-Installation
2 Steam Line Installation
3 Condensate Return Guidelines for Main
Steam Lines
4 Distributor Mounting
10 Spare Parts
11 Warranty
Steam Line Distribution Installation Manual | 2
Installation
Receiving and Unpacking Equipment
Check packing slip to ensure ALL material has been delivered.
All material shortages are to be reported to Condair within 48 hours from receipt of goods. Condair assumes no responsibility for any material shortages beyond this point.
Inspect shipping boxes for damage and note on shipping waybill accordingly.
After unpacking, inspect equipment for damage and if damage is found, notify the shipper promptly.
All Condair products are shipped on an F.O.B. factory basis. Any and all damage, breakage, or loss claims are to be made directly to the shipping company.
Each distributor is provided with: installation manual, one hose cuff, and two hose clamps.
Pre-Installation Check
Ensure the total capacity of the humidifier is not higher than the allowable maximum steam capacity of the distributors used.
ASD 10: 22 lbs/hr (10 kg/hr)
ASD: 25 lbs/hr (11 kg/hr)
BSD: 35 lbs/hr (16 kg/hr)
CSD: 115 lbs/hr (53 kg/hr)
RSD: 10lbs/hr (4.5 kg/hr)
SSD: 10 lbs/hr (4.5 kg/hr)
Steam Line Installation
Condair steam hose should only be used on short steam runs below 10 feet.
Ensure that no condensate produced in the steam line will remain trapped. Steam naturally flows upward and condensate naturally flows downward.
See material recommended for use in the chart below. To eliminate the metal corrosion, Condair does not recommend the use of steel piping.
Consult the following pages for step by step distributor installation starting with Figure 1.
Consult the charts below for steam and condensate sizing guidelines when using steam distributors.
3 | Steam Line Distribution Installation Manual
Table 1: Steam Line Material
Steam Hose Copper Tube Stainless Steel Tube
Short run < 10 feet (3 m)
Long run > 10 feet (3 m)
DI/RO Water
Table 2: Recommended Material and Size for Steam Run
Load Steam Run Steam Line Material Steam Line Description lb/hr kg/hr ft m
0-30 0-13 0-10 0-3 Copper Tube ¾” MED-L Tubing (7/8” O.D)
0-30 0-13 10+ 3+ Copper Tube 1” MED-L Tubing (1 1/8” O.D)
0-30 0-13 0-10 0-3 Stainless Steel Tube 7/8” Tube x 0.049” Thick
0-30 0-13 10+ 3+ Stainless Steel Tube 1 1/8” Tube x 0.49” Thick
30-100 13-45 0-20 0-6 Copper Tube 1 ½” MED-L Tubing (1 5/8” O.D)
30-100 13-45 20+ 6+ Copper Tube 2” MED-L Tubing (2 1/8” O.D.)
30-100 13-45 0-20 0-6 Stainless Steel Tube 1 ¾” Tube x 0.065” Thick
30-100 13-45 20+ 6+ Stainless Steel Tube 2” Tube x 0.065” Thick
Please note that options shown in bold-italic font require that reducers be used at both ends. These extra-large sizes are to allow for better condensation removal in long steam runs. These sizes will not permit you to use hose coupling to connect yourself to either humidifier or distributors.
Table 3: Recommended Condensate Line at Distributor(s)
Dispersion Method Condensate Hose Copper Tube Stainless Steel Tube
1 x Steam Distributor 3/8” Condair 1328840 ¼” MED-L Tubing (3/8” O.D.) 3/8” Tube 0.049 thick
3 x Steam Distributor 3/8” Condair 1328840 ½” MED-L Tubing (7/8” O.D.) 5/8” Tube 0.049” thick
* When using more than one distributor, the condensate line should be trapped before joined together.
Steam Line Distribution Installation Manual | 4
Condensate Return Guidelines for Main Steam Lines
Use vertical condensate leg of distributor only. Do not over-tighten clamp.
Condensate traps on steam mains must be located at all low points in the system, at each elevation change and or directional change.
Horizontal runs of steam must rise 2” per foot (10°) when flow is going upwards away from condensate trap, and fall ½” per foot (2°) when flow is going downwards towards a condensate trap.
In a horizontal run of the steam main, condensate traps must be located at regular intervals of 20 feet.
The condensate trap itself is a section of piping connected to the bottom of the main. A full size tee must be used to create a condensate trap to allow the condensate to fall away from the steam flow.
Vertical drop of the condensate trap should be 1.5 times the diameter of the steam main but no less than 12”.
A P-trap should be installed at the bottom of the condensate trap. The center to center trap height should be 2” greater than duct static pressure.
All distributors must be individually trapped.
Figure 1: Drain Tee
5 | Steam Line Distribution Installation Manual
Figure 2: Distributor Mounting
Steam Line Distribution Installation Manual | 6
Figure 3: Vertical Airflow
7 | Steam Line Distribution Installation Manual
Always align distributor holes so that steam is discharged upwards to ensure condensate will remain in the distributor.
X Min. H Min.
ASD 3” (76 mm) 8” (203 mm)
BSD 4” (102 mm) 10” (254 mm)
CSD 5” (127 mm) 14” (356 mm)
RSD 3” (76 mm) 8” (203 mm)
SSD* 3” (76 mm) 8” (203 mm)
* SSD distributors can only be installed with upward airflow in vertical duct applications. Refer to C2 on the next page.
ASD Ф 1.5” (38 mm)
BSD Ф 1.5” (38 mm)
CSD Ф 2.0” (51 mm)
A Min. B Min.
ASD 5” 3”
BSD 6” 4”
CSD 9” 5”
Figure 4: Horizontal Airflow
Steam Line Distribution Installation Manual | 8
Figure 5: Vertical Airflow
* SSD distributors can only be installed with upward airflow in vertical duct applications.
WARNING
These installation guidelines apply for duct velocities under 2000 ft/min (610 m/min), please consult factory for higher velocities.
Please make sure no obstacles (elbow, filter, or diffuser) are located after the distributor in the direction of the airflow closer than the absorption distance calculated for your application.
Unless you know the exact absorption distance required for the steam absorption into the air steam, the distributor should be located at least 8-10 ft (2-3 m) away from any obstacle it may condense on (elbow, diffuser, filter, etc.).
9 | Steam Line Distribution Installation Manual
Figure 6: Distributor Mounting – Horizontal & Vertical Flow
Figure 7: Distributor Mounting
Steam Line Distribution Installation Manual | 10
Figure 8: Spare Parts
ASD & BSD
2595149 – Distributor End Cap Assembly
CSD
2584395 – Distributor End Cap Assembly
ASD & BSD
2584393 – Distributor Inlet Assembly
CSD
2584394 – Distributor Inlet Assembly
11 | Steam Line Distribution Installation Manual
Warranty
Condair Inc. and/or Condair Ltd. (hereinafter collectively referred to as THE COMPANY), warrant for a period of two years after installation or 30 months from manufacturer’s ship date, whichever date is earlier, that THE COMPANY’s manufactured and assembled products, not otherwise expressly warranted, are free from defects in material and workmanship. No warranty is made against corrosion, deterioration, or suitability of substituted materials used as a result of compliance with government regulations.
THE COMPANY’s obligations and liabilities under this warranty are limited to furnishing replacement parts to the customer, F.O.B. THE COMPANY’s factory, providing the defective part(s) is returned freight prepaid by the customer. Parts used for repairs are warranted for the balance of the term of the warranty on the original humidifier or 90 days, whichever is longer.
The warranties set forth herein are in lieu of all other warranties expressed or implied by law. No liability whatsoever shall be attached to THE COMPANY until said products have been paid for in full and then said liability shall be limited to the original purchase price for the product. Any further warranty must be in writing, signed by an officer of THE COMPANY.
THE COMPANY’s limited warranty on accessories, not of the companies manufacture, such as controls, humidistats, pumps, etc. is limited to the warranty of the original equipment manufacturer from date of original shipment of humidifier.
THE COMPANY makes no warranty and assumes no liability unless the equipment is installed in strict accordance with a copy of the catalog and installation manual in effect at the date of purchase and by a contractor approved by THE COMPANY to install such equipment.
THE COMPANY makes no warranty and assumes no liability whatsoever for consequential damage or damage resulting directly from misapplication, incorrect sizing or lack of proper maintenance of the equipment.
THE COMPANY makes no warranty and assumes no liability whatsoever for damage resulting from freezing of the humidifier, supply lines, drain lines, or steam distribution systems.
THE COMPANY retains the right to change the design, specification and performance criteria of its products without notice or obligation
U.S.A.
1860 Renaissance Blvd.
Sturtevant, WI 53177
826 Proctor Avenue
Ogdensburg, NY 13669
CANADA
2740 Fenton Road
Ottawa, Ontario K1T 3T7
TEL: 1.866.667.8321
EMAIL: na.info@condair.com WEBSITE: www.condair.com
File details come from the government source that posted it. Updated .