Attachment_7_-_Steam_Humidifier_Quick_Start_Installation_Guide.pdf
PDF 3 MB Posted
- Attached to
- Modify Humidification System at OKX Federal contract opportunity
- Solicitation number
- 1305M326Q0464
About this file
This is a Quick Start Installation Guide for the Nortec EL Electrode Steam Humidifier, a commercial humidification system manufactured by Condair. The guide provides technical installation instructions for contractors and system integrators responsible for deploying the equipment.
The document covers four primary installation domains: mounting, steam distribution, plumbing, and electrical connections. For mounting, the humidifier requires wall or structural surface installation with specific clearances (minimum 24 inches from ground, 6 inches on sides where recommended) and must be positioned close to the steam distributor to minimize heat loss. The unit weighs 45-120 pounds depending on size and requires proper lifting equipment. Steam distribution requires copper or stainless steel tubing exclusively, with minimum 12-inch vertical rise before bends and a constant slope (minimum 10° upslope or 2° downslope). Steam lines must be insulated with minimum 1-inch pipe insulation, include condensate traps at 15-foot intervals, and maintain backpressure below 5.5 inches of water column. Plumbing specifications mandate cold potable water supply (150-1200 micro-seimens/cm conductivity, pH 7-7.5) at 30-80 psig with optional 5-micron filtration, and drain lines require minimum 7/8-inch internal diameter with 1.2° minimum downslope. Electrical installation must be performed by licensed electricians in accordance with local and national codes, with external fused disconnect switches required near the unit and all cables entering through appropriate cable glands or grommets. Low-voltage terminal connections support blower packs, external monitoring devices, humidity sensors, and control signals at specified terminal points.
View the file
Other files for this federal contract opportunity
Show all 15
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Humidification and Evaporative Cooling
NORTEC
Quick Start Installation Guide Nortec EL Electrode Steam Humidifier
| Overview | 2 |
| Mounting | 3 |
| Installation Requirements | 3 |
| Standard Mounting | 4 |
| Steam Distribution | 5 |
| Installation Requirements | 5 |
| Plumbing | 6 |
| Water and Drainage Requirements | 6 |
| Electrical | 7 |
| Installation Requirements | 7 |
| External Power Connections | 7 |
| Safety Chain and Control Signal Connections | 8 |
8_
B_
EN
_18 11_
No rte c-E L_
QS
G
2 Nortec EL
Overview min. 10 ft ( 3m)
B or min. 8-10 ft (
2.4-3m) n
1, 2
2, 3
| 1 | High limit On/Off humidistat (external safety chain) |
| 2 | Humidity sensor or modulating humidistat (used for control of the space in the return duct, high limit in the supply duct) |
| 3 | On/Off humidistat (used for humidity control) |
| 4 | Steam line |
| 5 | Electrical disconnect, high voltage supply |
| 6 | Drain line |
| 7 | Air gap funnel (with optional trap) |
| 8 | Water supply |
| 9 | Condensate line |
| 10 | Steam distributor |
| 11 | Air proving switch (external safety chain) |
| 12 | Supply air duct |
| 13 | Return air duct |
3Nortec EL
Mounting
Installation Requirements
1. The location of the humidifier depends largely on the steam distri-bution system. The required minimum clearances are shown on the right. The table below shows the required minimum clearances for a Nortec EL Space humidifier.
2. When choosing the location of the humidifier, install it as close as possible to the steam distributor to minimize heat loss through the steam line.
3. When possible, install the humidifier below the steam distributor.
Make sure that the selected location permits proper routing of steam and condensate lines.
4. Allow adequate clearances around the humidifier for ease of mainte-nance. Although the Nortec EL humidifier requires no side clearance, Condair recommends minimum clearances of 6 in (150 mm) on the sides. A clearance of 24 in (610 mm) between the humidifier and the ground is required. Observe all local and national installation codes. Condair is not responsible for any installation code violations.
5. Do not mount the humidifier on hot surfaces, or surfaces that can freeze, or near vibrating components, or on the floor. In addition, the mounting surface must be able to withstand temperatures of 140-158°F (60-70°C) that can be generated during operation of the humidifier.
6. The humidifier should be mounted on a wall or other suitable surface that offers a sufficiently high load-bearing capacity.
7. The Nortec EL humidifier should be installed in a drip-proof location within buildings, where the ambient temperature is 41-104°F (5-40°C) and the relative humidity is 5-95% (non-condensing).
WD
H
0 in
(0 mm) m in
. 2 in (6 m m m in
. 1 5.
in
(4 m m min. 36 in (915 mm)
0 in
(0 mm)
Minimum Clearances – Nortec EL Space Humidifier
Capacity 5 lb/h (2.3 kg/h)
10 lb/h (4.5 kg/h)
20 lb/h (9 kg/h)
30 lb/h (13.6 kg/h)
50 lb/h (22.7 kg/h)
75 lb/h (34.0 kg/h)
100 lb/h (45.4 kg/h)
Low Speed Dimension
"A" (minimum)
9 in (0.23 m)
18 in (0.46 m)
75 in (1.91 m)
86 in (2.19 m)
174 in (4.42 m)
189 in (4.81 m)
248 in (6.3 m)
Dimension "B"
(minimum)
12 in (0.31 m)
48 in (1.22 m)
84 in (2.14 m)
High Speed
Dimension "A"
(minimum)
6 in (0.16 m)
60 in (1.53 m)
71 in (1.81 m)
132 in (3.36 in)
153 in (3.89 m)
218 in (5.54 m)
Dimension "B"
(minimum)
12 in (0.31 m)
Dimension "C"
(minimum)
86.5 in (2.2 m)
Dimension "D"
(suggested)
12 in (0.31 m)
30 in (0.77 m)
B
C
D
D
A
4 Nortec EL
Mounting continued...
Standard Mounting
1. Locate 2×4 wooden studs or equivalent support in the mounting surface, and mark the attachment points “A” and “B” at the desired position with the help of a level.
2. Install 1/4×2 in lag bolts (supplied by others) at attachment points “A”. Use longer screws if going through drywall or other structural material into the mounting surface. Allow the heads of the screws to extend 0.25 in (5 mm) from the mounting surface so that the humidifier can be installed on the bolts.
| 3. | Remove the door panels from the humidifier. |
| 4. | Carefully raise and install the humidifier onto the installed lag bolts. |
| 5. | Align the humidifier with the help of a level, then tighten the lag bolts. |
| 6. | Install additional lag bolts (supplied by others) into the mounting |
surface at attachment points “B”, and fasten securely.
7. Reinstall the door panels, and fasten them securely.
Refer to “Mounting the Humidifier” in the Installation Manual (Condair document number 2582302) for other mounting arrangements, including OSHPD (seismic) mounting arrangement.
WARNING!
Heavy object – risk of injury! The small humidifier weighs 45 lb (20 kg), and the large humidifier weights 120 lb (54 kg). Use an appropriate lifting device, or request assistance to raise the humidifier into position.
Dimension Housing Size
Small Medium Large
X 12.0 in (305 mm)
16.0 in (406 mm)
16.0 in (406 mm)
Y 17.6 in (446 mm)
20.7 in (526 mm)
16.8 in (426 mm)
X
A
A
A
B
B
B
X
Y
Large Nortec EL humidifier shown.
1 Lag bolt
5Nortec EL
Steam Distribution
Installation Requirements
1. Use steam line made of copper or stainless steel tube exclusively, or use a Condair steam hose for short distances. Steam line made of any other material may adversely affect the operation of the humidifier, and will void the warranty. Refer to the table below for steam line sizing.
2. To prevent excessive backpressure in the steam cylinder, the steam line must not have any restrictions.
3. The steam line must run straight up from the humidifier minimum 12 in (300 mm) before any bends.
4. The steam line must have a constant slope – minimum upslope of 10°, or minimum downslope of 2°.
5. Do not merge steam lines, except at the steam distributor. Use a Condair adaptor designed for the purpose.
| 6. | Insulate the steam line with minimum 1 in (25 mm) pipe insulation. |
| 7. | Support the steam line so there is no load on the humidifier. |
8. Install condensate lines at all low points and horizontal-to-vertical transitions in the steam line. The condensate line should always connect to a full size “Tee” connector, and have a minimum con-stant downslope of 1.2°. The trap should be located minimum 12 in (300 mm) below the connector, and have a minimum height of 8 in (200 mm).
9. Use 3/8 in (9.5 mm) Condair condensate hose, or 1/4 in (6.5 mm) Med-L copper tube or 3/8 in (9.5 mm) stainless steel tube for condensate traps.
| 10. | Install condensate traps every 15 ft (4.5 m) in the steam line. |
| 11. | Upon completion of installation, purge the steam and condensate |
lines to remove any contaminants or construction material.
12. Prime the condensate traps with water.
Refer to “Steam Line Connections“ in the Installation Manual for other details.
o o
12 in (300 mm)
2 in (50 mm)
12 in (300 mm)
½ in (12 mm)
Minimum Upslope
Minimum Downslope 1.2 o
1 in (25 mm)
48 in (1.2 m)
1.2 o
1 in (25 mm)
48 in (1.2 m)
Min.
12 in
(300 mm)
8 in (200 mm)
Min.
12 in
(300 mm)
8 in (200 mm)
Minimum Downslope
Minimum Downslope
Nortec
EL
Model
Steam Line Sizing
Maximum Equiv.
Length
MED-L
Copper Tube Stainless Steel Tube Steam Losses
EL005 7 ft (2 m) 3/4 in (20 mm)
7/8 in × 0.049 wall
(22 mm × 1.25 mm wall)
0.06 lb/h/ft (0.09 kg/h/m)EL010 12 ft (3.5 m)
EL020 17 ft (5 m)
EL030 22 ft (6.5 m)
EL050 43 ft (13 m) 1-1/2 in (40 mm)
1-3/4 in × 0.065 wall (45 mm × 1.65 mm wall)
0.11 lb/h/ft (0.18 kg/h/m)EL075
EL100
47 ft (14 m)
EL150*
EL200*
50 ft (15 m) 1-1/2 in (40 mm)
1-3/4 in × 0.065 wall (45 mm × 1.65 mm wall)
Condair Steam Hose
EL005-
EL030
10 ft (3 m)
P/N 1328810 – 7/8 in (22 mm) 0.1 lb/h/ft (0.15 kg/h/m)
EL050-
EL200
10 ft (3 m)
P/N 1328820 – 1-3/4 in (45 mm) 0.15 lb/h/ft (0.22 kg/h/m)
* Use a single steam line for each steam cylinder. Do not combine lines except at a distributor, and only if using the steam cylinders in parallel.
Refer to the Installation Manual for over-sized steam lines for longer steam runs.
WARNING!
Risk of serious injury or damage to equipment!
Restrictions in the steam line can cause excess build-up of backpressure which can result in serious burn injuries or damage to equipment. Backpressure should not exceed
5.5 in H2O (1.36 kPa).
6 Nortec EL
Plumbing
Water and Drainage Requirements
1. All water supply and drain connections must be installed to local plumbing codes.
2. The water supply line should be minimum 1/2 in (12.7 mm) in diameter, with a shutoff valve and a union fitting.
3. The water supply to the humidifier must be cold potable drinking water (and not RO or DI water). The conductivity of the water should be 150-1200 micro-seimens/cm (hardness 0-12 gpg, when Silica is between 0-4 ppm, 0-3 gpg when Silica is between 4-14 ppm;
Silica content above 14 ppm is not recommended). pH should be between 7 and 7.5.
4. The water supply should be filtered to 5 μm (optional, but recommend-ed), surge-free and pressure regulated to 30-80 psig (207-550 kPa).
Water temperature should be 34-104°F (1-40°C).
5. The air gap funnel should be located away from the control cabinet to keep any rising steam from damaging the electrical components in the cabinet. The drain piping should have a minimum internal diameter of 7/8 in (22 mm).
6. The flexible bent hose exiting the humidifier should be connected to a drain line with a minimum internal diameter of 7/8 in (22 mm) and secured with clamps.
7. The drain line should be as short as possible, and have a constant minimum downslope of 1 in/48 in (1.2°) to the funnel without touching its sides or bottom. Use stainless steel or plastic pipe suitable for temperatures up to 212°F (100°C).
8. Drain lines from large humidifiers with dual steam cylinders must empty into separate air gap funnels before connecting to the drain.
Combined drain line minimum 1.5 in (38 mm) I.D.
9. Upon completion of installation, flush the water supply and drain lines to clear out any debris in the lines. Check the strainer in the fill valve to ensure it is clear of all debris.
Refer to “Water Connections” in the Installation Manual for other details.
CAUTION!
Risk of damage to the plastic threads of the fill valve. Hand-tighten the NPT adaptor to the fill valve.
| 1 | Drain canal, 1-3/16 in (30 mm) O.D. |
| 2 | Hose clamp (supplied) |
| 3 | Flexible bent hose (supplied) |
| 4 | Drain line, minimum 7/8 in (22 mm) I.D. |
| 5 | Water supply line, minimum 1/2 in (12.7 mm) |
| 6 | Adaptor, 3/4 BSPP to 1/2 in NPT (supplied) |
| 7 | Inlet, fill valve (3/4 in BSPP plastic threads) | |
| 8 | Air gap funnel (and optional trap) | |
| 9 | Shutoff valve | |
| 10 | Filter, 5 μm (optional, but recommended) | |
| 11 | Union fitting |
7Nortec EL
Electrical
Installation Requirements
1. All wiring must only be done by a licensed electrician in accordance with the wiring diagram (refer to the Installation Manual), and local and national codes.
2. An external dedicated fused disconnect switch must be installed close to the unit to allow for power interruption during servicing and/ or maintenance. The fusing must not exceed the maximum circuit protection shown on the specification label. The optional internal fusing is not a substitute for an external disconnect switch.
3. The humidifier should only be connected to primary power (main power) after all installation work has been completed.
4. All cables must enter the control cabinet in the humidifier through appropriate cable glands or grommets, and must be properly secured to prevent fraying, or become a tripping hazard.
Refer to “Electrical Connections” in the Installation Manual for other details.
DANGER!
Risk of electric shock! The Condair humidifier is mains powered, and should only be wired by a licensed electrician.
CAUTION!
Risk of damage to electronic components in the control cabinet due to ESD (electrostatic discharge). Refer to ANSI/ESD-S20.20 for appropriate measures to prevent damage to electronic components.
External Power Connections
E x te rn a l
X s s s
L
L
L
E x te rn a l
X s s s
L
L
L
| 1 | External fused disconnect switch |
| 2 | Terminal block, power supply (XO) |
| 3 | Internal primary fuse, optional |
Single-phase
Three-phase
8 Nortec EL
Electrical continued...
Safety Chain and Control Signal Connections
1. If a blower pack is installed, then connect it to terminal points “8” and “9” on the low voltage terminal strip. Make sure that no other wires are connected to these terminal points. If using multiple blower packs, make sure that they are connected in series. Install a jumper between terminal points “8” and “9” if a blower pack is not used.
2. Connect external monitoring devices (for example, high limit humi-distat, air proving switch, etc.) in series to terminal points “1” and “2” on the low voltage terminal strip. Install a jumper between terminal points “1” and “2” if external monitoring devices are not used (not recommended).
3. Connect an external humidity sensor input or direct demand modulating input to terminal points “3” and “4” on the low voltage terminal strip. Do not connect multiple modulating signals to the same modulating input on the humidifier. If necessary, a second modulating signal can be connected to terminal point “5” and “3”, using terminal point “3” as common. Note: If the cable shielding is already connected to a potential or a grounded conductor, do not connect it to terminal point “3”.
4. If a 24 V On/Off humidistat is used, connect the input to the terminal points “4” and “6” on the low voltage terminal strip. When connecting a 24 V On/Off humidistat, set the jumper JP1 on the driver board to 24 V (so that terminal point “6” will output 24 VDC).
5. If an external On/Off input is used to control the humidifier, connect it to connector X11 on the driver board.
CAUTION!
Risk of damage to internal component. DO NOT apply voltage to low voltage terminal strip terminal points “1” and “2” through the contacts of the external On/Off devices.
max φ Δp
E x te rn a l
Blower pack
GND
10/24 Vdc (+) Limit signal
(+) Control signal (-) Signal
Safety loop
J
P
V
V
LV
5 4
| 1 | Modulating demand or humidity sensor signal (additional) |
| 2 | Modulating demand or humidity sensor signal |
| 3 | 24 V On/Off humidistat (jumper JP1 must be set to 24 V) |
| 4 | High limit humidistat |
| 5 | Air proving switch |
| 6 | Jumper |
| 7 | Low voltage terminal strip |
| 8 | Blower pack |
Notes
All information contained in this Quick Start Guide is for general information purposes only. For complete Condair installation/oper-ation recommendations for your Condair equipment, please refer to the installation manual for your specific system, accessories, and components.
All electrical connections must be installed in accordance with local and national electrical code requirements by a licensed electrician.
All water supply and drain line connections must be installed in accordance with local plumbing codes by a licensed plumber.
Condair does not accept any liability for installations of humidity equipment installed by unqualified personnel or the use of parts/com-ponents/equipment that are not authorized or approved by Condair.
USA 835 Commerce Park Drive, Ogdensburg, NY 1366-2209 Canada 2740 Fenton Road, Ottawa, Ontario K1T 3T7
1.866.667.8321 na.info@condair.com
| Overview |
| Mounting |
| Installation Requirements |
| Standard Mounting |
| Steam Distribution |
| Installation Requirements |
| Plumbing |
| Water and Drainage Requirements |
| Electrical |
| Installation Requirements |
| External Power Connections |
| Safety Chain and Control Signal Connections |
File details come from the government source that posted it. Updated .