Attachment 9 - 01 00 00.H - Appendix H - J2237038 Montrose ACM Ld Pnt InspRpt Final 8-21-2023.pdf

PDF 9 MB Posted

Attached to
Z2DA--620-22-700 Electronic Health Record Modernization Infrastructure Upgrades - Franklin Delano Roosevelt VA Hospital, Montrose, NY
Solicitation number
RFP-36C77626R0033
Issued by

About this file

This is a Supplemental Asbestos Inspection and Lead Paint Testing Report for the Montrose VA Medical Center (Franklin Delano Roosevelt VA Hospital) located at 2094 Albany Post Road, Montrose, New York. The report was prepared by Terracon Consultants, Inc. for Triple C - The A&E Group LLC on August 21, 2023, to support planned Electronic Health Record Modernization (EHRM) renovation activities. The inspection was conducted on June 13, 14, 15, and 28, 2023, by New York State-certified asbestos inspector Megan Cruz and EPA-certified Lead Inspector/Risk Assessor across 14 buildings and 91 specified rooms within the medical center campus.

The inspection identified multiple asbestos-containing materials (ACM) and lead paint across the surveyed areas. The asbestos assessment collected 273 layered bulk samples from 91 homogeneous areas of suspect ACM, with samples analyzed by Scientific Analytical Institute using polarized light microscopy via New York State methods 198.1, 198.4, and 198.6. Materials tested included vinyl floor tiles (VFT), carpet mastics, ceiling tile mastics, linoleum, transite board, and various mastic adhesives, with asbestos concentrations ranging from non-detected levels to 87% by weight. Lead paint testing utilized X-ray fluorescence (XRF) analysis to measure lead content on drywall, plaster walls, and metal radiators, with high lead content concentrations identified (≥1.0 mg/cm²) in Buildings 3 and 6. The report specifies that any identified ACM impacted by renovation activities must be properly removed and disposed of prior to construction in accordance with federal, state, local regulations, and VA specifications.

View the file

Other files

File Type Posted
Amend 5 - B04.20260330.pdf PDF
Amend 5 - B15.20260330.pdf PDF
Amend 5 - B02.20260330.pdf PDF
Amend 5 - B28.20260330.pdf PDF
Amend 5 - B19.20260330.pdf PDF
Amend 5 - B18.20260330.pdf PDF
Amend 5 - B17.20260330.pdf PDF
Amend 5 - B06.20260330.pdf PDF
Amend 5 - B52.20260330.pdf PDF
Amend 5 - SITE.20260330.pdf PDF
Amend 5 - B16.20260330.pdf PDF
Amendment 5 - 36C77626R0033 0005.pdf PDF
Amend 5 - B01.20260330.pdf PDF
Original attachments 18-21 B06-B13.zip ZIP file
Amend 5 - B27.20260330.pdf PDF
Original attachments 22-29 B14-B28.zip ZIP file
Original attachments 13-17 B01-B05.zip ZIP file
Amend 5 - B03.2020330.pdf PDF
Amend 5 - B05.20260330.pdf PDF
Amend 5 - B14.20260330.pdf PDF
Amend 5 - B20.20260330.pdf PDF
Original attachments 1-12.zip ZIP file
Amend 5 - B26.20260330.pdf PDF
5-4 - RFI TRACKING SHEET.pdf PDF
Amend 5 - B29.20260330.pdf PDF
Amend 5 - B12.20260330.pdf PDF
Amend 5 - B13.20260330.pdf PDF
Amend 5 - B31.20260330.pdf PDF
Amend 5 - B07.20260330.pdf PDF
Amendment 4 - 36C77626R0033 0004.pdf PDF
Clause 52.222-90 ADDRESSING DEI DISCRIMINATION BY FEDERAL CONTRACTORS - APR 2026.pdf PDF
ATTACHMENT 12A - Summary.Log.Add01_20260410.pdf PDF
ATTACHMENT 14 - Montrose.EHRM.Addendum.01.B02.20260330.pdf PDF
ATTACHMENT 16 - Montrose.EHRM.Addendum.01.B04.20260330.pdf PDF
ATTACHMENT 33A - 00 41 13.10 - Construction Estimate Breakdown Template.xlsx XLSX spreadsheet
ATTACHMENT 1 - SPECS - 620-22-700.Montrose.EHRM.Spec.IFC.20260410.pdf PDF
RFI TRACKING SHEET - SOLICITATION 36C77626R0033.pdf PDF
ATTACHMENT 31 - Montrose.EHRM.Addendum.01.B31.20260330.pdf PDF
ATTACHMENT 21 - Montrose.EHRM.Addendum.01.B13.20260330.pdf PDF
ATTACHMENT 32 - Montrose.EHRM.Addendum.01.B52.20260330.pdf PDF
ATTACHMENT 24 - Montrose.EHRM.Addendum.01.B16.20260330.pdf PDF
ATTACHMENT 7 - 01 00 00.F - Appendix F - VHA PCRA 2024 1.1 Final.Template Fillable.pdf PDF
ATTACHMENT 33 - Montrose.EHRM.Addendum.01.Site.20260330.pdf PDF
ATTACHMENT 28A - Montrose.EHRM.Addendum.01.B27.20260330.pdf PDF
ATTACHMENT 30 - Montrose.EHRM.Addendum.01.B29.20260330.pdf PDF
ATTACHMENT 2 - 01 00 00.A - Appendix A - OIT-InfrastrucStdTelecomSpaces.pdf PDF
ATTACHMENT 29 - Montrose.EHRM.Addendum.01.B28.20260330.pdf PDF
ATTACHMENT 22 - Montrose.EHRM.Addendum.01.B14.20260330.pdf PDF
ATTACHMENT 26A - Montrose.EHRM.Addendum.01.B19.20260330.pdf PDF
ATTACHMENT 11 - 01 00 00.I - Appendix I - K9245005 VAMC EHRM Montrose NY GeoReport 4.12.2024.pdf PDF
Show 40 more

Latest 50 of 112 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Supplemental Asbestos Inspection and Lead Paint Testing Report Montrose VA Medical Center

2094 Albany Post Road

Montrose, New York 10548

August 21, 2023 | Terracon Project No. J2237038

Prepared for:

Triple C - The A&E Group LLC Laramie, Wyoming 82070

Prepared by:

Terracon Consultants, Inc.

South Plainfield, New Jersey 07080

4081 Hadley Road, Unit B

South Plainfield, NJ 07080

P (908) 546-6161

F (908) 546-6160

Terracon.com

Facilities | Environmental | Geotechnical | Materials

August 21, 2023

Triple C - The A&E Group LLC 410 E. Grand Avenue, Suite 201C Laramie, Wyoming 82070

Attn: Mr. Mat Perkins P: (307) 460-2054 E: mat.perkins@triplecaeg.com

Re: Supplemental Asbestos Inspection and Lead Paint Testing Report EHRM Project at Montrose VA Medical Center 2094 Albany Post Road Montrose, New York 10548 Terracon Project No. J2237038

Dear Mr. Perkins:

Terracon Consultants – NY, Inc. (Terracon) is pleased to submit the attached report for the above-referenced site to Triple C - The A&E Group LLC. The purpose of this report is to present the results of supplemental asbestos inspection and lead paint testing scope of services performed on June 13, 14, 15, and 28, 2023 to augment a previous survey performed by another environmental consultant. The scope of services was conducted in general accordance with Terracon Proposal No. PJ2237038, dated May 5, 2023, in preparation for the planned renovation project for the electronic health records modernization (EHRM). The VAMC is transitioning to a new electronic health record (HER) system-the software that stores health information and tracks all aspects of patient care. The new system connects VAMC facilities with the Department of Defense, the US Coast Guard, and participating community care providers, allowing clinicians to easily access a Veteran’s full medical history in one location.

We understand that our scope of services was requested due to planned renovation of specific rooms within the Montrose VA Medical Center located at the above-referenced address.

Terracon Consultants, Inc. 4081 Hadley Rd. , Ste. B South Plainfield, NJ 07080

P (908) 546-6161 ter racon.com

As a result of the asbestos and lead paint inspection, both asbestos-containing materials (ACM), materials containing asbestos, and lead paint (LP) were identified at the site. Please refer to the report for further details.

Terracon appreciates the opportunity to provide this service to Triple C - The A&E Group LLC.

If you have any questions regarding this report, please contact the undersigned at (860) 566- 9001.

Sincerely, Terracon Consultants – NY, Inc.

Megan E. Starace Joseph A. Tussey Senior Staff Scientist Authorized Project Reviewer

Supplemental Asbestos Inspection and Lead Paint Testing Report Montrose VA Medical Center | Montrose, New York

Facilities | Environmental | Geotechnical | Materials

Table of Contents

1.0 INTRODUCTION

1.1 Project Objective

1.2 Reliance

2.0 PROJECT DESCRIPTION

3.0 FIELD ACTIVITIES

3.1 Asbestos Inspection

3.1.1 Visual Assessment

3.1.2 Physical Assessment

3.1.3 Asbestos Sample Collection

3.2 Limited Lead Paint Inspection

4.0 REGULATORY OVERVIEW

4.1 Asbestos

4.2 Lead Paint

5.0 FINDINGS AND RECOMMENDATIONS

5.1 Asbestos

5.2 Lead Paint

6.0 LIMITATIONS/GENERAL COMMENTS

APPENDICES

APPENDIX A Asbestos & Lead Paint Sample Summaries

APPENDIX B Analytical Laboratory Reports

APPENDIX C Licenses and Certifications

APPENDIX D Photographs

APPENDIX E Sample Location Sketches

Facilities | Environmental | Geotechnical | Materials 1

1.0 INTRODUCTION

Terracon Consultants, Inc. (Terracon) conducted a Supplemental Asbestos Inspection and Lead Paint Sampling regarding project-specific areas to be renovated at the Montrose VA Medical Center located at 2094 Albany Post Road in Montrose, New York. The supplemental inspection was performed to augment the original survey performed by another environmental consultant. The asbestos inspection scope of services was conducted on June 13, 14, 15, and 28, 2023 by a New York State-certified asbestos inspector and the lead paint inspection was conducted on June 13, 14, 15, and 28, 2023 by an EPA-certified Lead Inspector/Risk Assessor in general accordance with Terracon Proposal No. PJ2237038, dated May 5, 2023. Accessible interior building components within Client-specified rooms of concern were inspected, and homogeneous areas of suspect asbestos-containing materials (ACM) were visually identified and documented for the purpose of subsequent sample collection and laboratory analysis to determine asbestos-content. Although reasonable effort was made to inspect accessible suspect materials, additional suspect but un-sampled materials could be located in walls, in voids, or in other concealed areas. An X-ray fluorescence (XRF) analyzer to measure the lead content of various painted components in the Client-specified rooms.

1.1 Project Objective

We understand our scope of services was requested due to planned EHRM renovations at the Montrose VA Medical Center. Asbestos inspections are required prior to renovation and demolition activities to satisfy requirements of the United States Environmental Protection Agency (USEPA) 40 Code of Federal Regulations (CFR) Part 61, Subpart M, the National Emission Standards for Hazardous Air Pollutants (NESHAP) regulation. The purpose of the lead inspection was to provide general information so that contractors who disturb paints with lead can take the appropriate actions to comply with US Occupational Safety and Health Administration (OSHA) regulation 29 CFR 1926.62 – Lead in Construction.

1.2 Reliance

This report is for the exclusive use of Triple C - The A&E Group LLC for the project being discussed. Reliance by any other party on this report is prohibited without written authorization of Terracon and the Client. Reliance on this report by the Client and all authorized parties will be subject to the terms, conditions, and limitations stated in the proposal, this report, and the Agreement for Services. The limitations of liability defined in the Agreement for Services is the aggregate limit of Terracon’s liability to the Client.

2.0 PROJECT DESCRIPTION

The site is a large medical center campus with multiple buildings. However, our scope of services was limited to the following rooms in the following buildings which were understood are planned for EHRM renovation impacts:

Facilities | Environmental | Geotechnical | Materials 2

Building 1: Rooms 14, 15, 15A, 15B, 122, 123, 218, 219, 307, and 308

Building 3: Rooms 051M04, 149, and 243A

Building 4: Rooms 12, 15F, 130, 131, 227, and 249

Building 5: Rooms 13G, 19B, 110, and 110A

Building 6: Rooms 01, 01A, 01B, 20, 101A, 104, 105, 131, 201A, and 205

Building 7: Rooms 4, 11, 11B, 19A, 19B, 20, 147, 148, 242, and 243

Building 12: Rooms 18A, 137, and 237

Building 14: Rooms 1A, 2, 102, and 201C

Building 15: Rooms 12, 142, and 242

Building 27: Rooms 02, 13, 13A, 20, and 21

Building 28: Room 112

Building 52: Room 120

3.0 FIELD ACTIVITIES

3.1 Asbestos Inspection

The asbestos inspection was conducted by Ms. Megan Cruz, a New York State-certified asbestos inspector on June 13, 14, 15, and 28, 2023. A copy of Ms. Cruz’s asbestos inspector accreditation is attached as Appendix C. The inspection was conducted in general accordance with the sample collection protocols established in USEPA 40 CFR Part 763, Subpart E, Section 763.86, AHERA. A summary of survey activities is provided below.

3.1.1 Visual Assessment

Inspection activities were initiated with visual observation of the accessible project-specific areas referenced above to identify homogeneous areas of suspect ACM. A homogeneous area (HA) consists of building materials that appear similar throughout in terms of color and texture with consideration given to the date of application.

3.1.2 Physical Assessment

A physical assessment of each HA of suspect ACM was conducted to assess the friability and condition of the materials. A friable material is defined by the USEPA as a material which can be crumbled, pulverized, or reduced to powder by hand pressure when dry. Friability was assessed by physically touching suspect materials.

Facilities | Environmental | Geotechnical | Materials 3

3.1.3 Asbestos Sample Collection

Based on the results of the visual observation, bulk samples from suspect ACM were collected in general accordance with USEPA AHERA sampling protocols. Samples of suspect materials were collected from randomly selected locations in each homogeneous area. Bulk samples were collected using wet methods as applicable to reduce the potential for fiber release.

Samples were placed in sealable containers and labeled with unique sample numbers using an indelible marker.

The selection of sample locations and frequency of sampling were based on Terracon’s observations and the assumption that like materials in the same area are homogeneous in content.

Terracon collected a total of 273 layered bulk samples from 91 homogeneous areas of suspect ACM. A summary of suspect ACM samples collected during the inspection is included as Appendix A and photos associated with the ACM samples are in Appendix D. Sample locations are indicated on excerpts from Client-provided plans in Appendix E.

Bulk samples were submitted under chain of custody to Scientific Analytical Institute, Inc.

(SAI) of Greensboro, North Carolina for analysis. Friable material samples were analyzed by polarized light microscopy (PLM) via New York State (NYS) method 198.1 and non-friable organically bound (NOB) material samples were analyzed by PLM NOB via NYS method 198.6.

Additionally, NOB samples with inconclusive results (<1% asbestos) via PLM NOB were additionally analyzed by transmission electron microscopy (TEM) via NYS method 198.4. SAI is accredited for bulk asbestos analysis under the National Voluntary Laboratory Accreditation Program (NVLAP), accreditation number 200664-0

3.2 Lead Paint Testing

The lead paint testing was conducted on June 13, 14, 15, and 28, 2023 by EPA-certified Lead Inspector/Risk Assessor Ms. Megan Cruz (Certification #: LBP-I-1224177-1). Terracon visually assessed the interior of project-specific rooms at the Montrose VA Medical Center to identify apparent unique combinations of suspect lead paint (LP). A unique combination of paint is based on paint color, building component and substrate. Assessment was conducted throughout visually accessible areas of the tenant space. A visual assessment of each unique combination of suspect LP was conducted to assess the condition of the paint. Based on results of the visual observation, Terracon performed limited LP measurements utilizing a direct read X-ray fluorescence (XRF) analyzer to measure the lead content of painted components. Two

(2) paint chip samples were additionally collected for confirmation and were submitted to SAI for analysis.

Facilities | Environmental | Geotechnical | Materials 4

4.0 REGULATORY OVERVIEW

4.1 Asbestos

The asbestos NESHAP (40 CFR Part 61, Subpart M) regulates asbestos fiber emissions and asbestos waste disposal practices. The asbestos NESHAP regulation also requires the identification and classification of existing ACM according to friability prior to demolition or renovation activity. Friable ACM is a material containing more than 1% asbestos that, when dry, can be crumbled, pulverized, or reduced to powder by hand pressure. All friable ACM is considered regulated asbestos containing material (RACM).

The asbestos NESHAP regulation classifies material subject to demolition or renovation as either RACM, Category I non-friable ACM, or Category II non-friable ACM. RACM includes all friable ACM (pre-disturbance), along with Category I non-friable ACM that becomes friable (during disturbance), and Category I non-friable ACM subject to sanding, grinding, cutting, or abrading, or Category II non-friable ACM with a high probability of becoming crumbled, pulverized, or reduced to powder by forces expected to act on the material during disturbance.

Category I non-friable ACM are exclusively asbestos-containing packings, gaskets, resilient floor coverings, and asphalt roofing products that contain more than 1% asbestos. Category II non-friable ACM are all other non-friable materials (other than Category I non-friable ACM) that contain more than 1% asbestos. Category II non-friable ACM generally includes (but is not limited to) cementitious material such as: cement pipes, cement siding, cement panels, glazing, mortar, and grouts.

Asbestos activities are regulated by the New York Department of Labor (NYDOL) under the New York Regulations Industrial Code Rule 56 (12 NYCRR Part 56) which enforces NESHAP.

The owner or operator must provide New York State Asbestos Control Bureau with written notification at least 10 calendar days prior to the commencement of asbestos abatement activities that will disturb RACM in amounts greater than or equal to 160 square feet or 260 linear feet.

The NYDOL enforces the Occupational Safety and Health Administration (OSHA) standards at 29 CFR 1910.1001 and 29 CFR 1926.1101, which regulates employee exposure to asbestos.

The OSHA standard requires that employee exposure to airborne asbestos fibers be maintained at or below 0.1 fibers per cubic centimeter of air (0.1 f/cc) as an eight-hour time weighted average (TWA) and not exceed 1.0 fibers per cubic centimeter of air (1.0 f/cc) over a 30-minute time period known as an excursion limit (EL). The TWA and EL are known as OSHA’s permissible exposure limits (PELs). The OSHA standard classifies construction and maintenance activities which could disturb ACM and specifies work practices and precautions which employers must follow when engaging in each class of regulated work.

Facilities | Environmental | Geotechnical | Materials 5

4.2 Lead Paint

As applicable to this project, lead is regulated by OSHA. OSHA regulates lead exposure to workers. For the purpose of the OSHA lead standard, lead includes metallic lead, inorganic lead compounds, and organic lead soaps. A synopsis of the OSHA regulations (29 CFR 1926.62) and the applicability are described below.

The OSHA Lead Standard for Construction (29 CFR 1926.62) applies to construction work where an employee may be occupationally exposed to lead. Work related to construction, alteration, or repair (including painting and decorating) is included. The lead-in-construction standard applies to any detectable concentration of lead in paint, as even small concentrations of lead can result in unacceptable employee exposures depending upon on the method of removal and other workplace conditions. Under this standard, construction includes, but is not limited to, the following:

Demolition or salvage of structures where lead or materials containing lead are present.

Removal or encapsulation of materials containing lead.

New construction, alteration, repair, or renovation of structures, substrates, or portions containing lead, or materials containing lead.

Installation of products containing lead.

Lead contamination/emergency clean-up.

Transportation, disposal, storage, or containment of lead or materials containing lead on the site or location at which construction activities are performed; and, Maintenance operations associated with construction activities described above.

Facilities | Environmental | Geotechnical | Materials 6

5.0 FINDINGS AND RECOMMENDATIONS

5.1 Asbestos

As a result of sampling and laboratory analysis regarding the project-specific rooms, the materials listed below were identified to contain asbestos.

HA

No.

Material Description

Material Locations

% & Type Asbestos

Condition/ NESHAP Category

Estimated Quantity

Black Vinyl Floor Tile

(VFT)

Building 1 - Rooms 307, 2.1% Chrysotile (tile)

Good/Category I Non- Friable

280 Square Feet (SF) None Detected

(ND) (black mastic)

4 9"x 9" Red VFT

Building 1 - Rooms 308, 307, 21 218, 9

1.4% Chrysotile (tile) Good/Category I Non-

Friable

500 SF

ND (black mastic)

Gray Radiator

Caulking

Building 1 - Rooms 122, 123, 218, 219, 307, 3.6% Chrysotile Good/Category II Non-

Friable

14 SF

Gray Transite and

Black Mastic Behind Radiator

Building 1 - Rooms 122, 123, 218, 219, 307, 24% Chrysotile (Transite)

Good/Category II Non- Friable

600 SF

1.4% Chrysotile

(mastic) Good/Category II Non-

Friable

Brown Mastic Associated with Non- ACM 12"x12" Yellow

VFT

Building 1 - Rooms 218, 1.6% Chrysotile (brown mastic)

Good/Category I Non- Friable 280 SF

Gray Caulking Behind

Radiator Building 3 - Room 243A

4.8% Chrysotile Good/Category II Non-

Friable

2 SF

Gray Transite and

Black Mastic Behind Radiator

Building 3 - Room 243A

14% Chrysotile (Transite)

Good/Category II Non- Friable

100 SF

4.8% Chrysotile

(mastic) Good/Category II Non-

Friable

Beige Mastic Under Non-ACM 12”x12” Gray Speckled VFT and Under Non-ACM 18”x18” Marbled VFT and Non-ACM Beige

Mastic

Building 3 – Room 243

0.32% Chrysotile Good/Not Regulated by NESHAP; However, Regulated by OSHA

80 SF

Facilities | Environmental | Geotechnical | Materials 7

HA

No.

Material Description

Material Locations

% & Type Asbestos

Condition/ NESHAP Category

Estimated Quantity

Beige Mastic Under Non-ACM 12”x12”

White VFT with Gray Speckles

Building 3 – Room 149

0.0072% Chrysotile

Good/Not Regulated by NESHAP; However, 140 SF

Black and Yellow Mastic Under Non-

ACM 12”x12” Speckled Cream VFT

Building 5 – Room 110 0.28% Chrysotile

Good/Not Regulated by NESHAP; However, Regulated by OSHA

180 SF

Brown Caulking Behind Radiator

Building 5 - Room 110

1.5% Chrysotile (Transite)

Good/Category II Non- Friable

2 SF

Gray Transite and

Black Mastic Behind Radiator

Building 5 - Room 110

17% Chrysotile (Transite)

Good/Category II Non- Friable

100 SF

1.1% Chrysotile

(mastic) Good/Category II Non-

Friable

Yellow Mastic Associated with Non-

ACM 12”x12” Light Brown Mottled VFT

Building 7 – Room 11

0.73% Chrysotile Good/Not Regulated by NESHAP; However, Regulated by OSHA

140 SF

Yellow Mastic Under

Non-ACM HA 35

Building 7 – Rooms 11, 20, 147, 242, 243

0.68% Chrysotile Good/Not Regulated by NESHAP; However, Regulated by OSHA

420 SF

41 Pipe Insulation Building 7 - Rooms 04, 11, 11B

44% Amosite and 11% Chrysotile

Good/Friable RACM 61 LF

Pipe Fitting Insulation

Associated with HA

Building 7 - Rooms 04, 11, 11B

44% Amosite and 27% Chrysotile

Good/Friable RACM 13 LF

Brown Caulking Behind Radiator

Building 7 - Rooms 147, 148, 242, 3.4% Chrysotile Good/Category II Non-

Friable

10 SF

Gray Transite and

Black Mastic Behind Radiator

Building 7 - Rooms 147, 148, 242, 1.1% Chrysotile (Transite)

Good/Category II Non- Friable

500 SF

15% Chrysotile

(mastic) Good/Category I Non-

Friable

Black Leveling

Compound - Under Non-ACM HA 35

Building 7 - Rooms 11, 20, 147, 6.7% Chrysotile Good/Category I Non-

Friable

450 SF

56 Yellow Carpet Mastic Building 12

– Rooms 147, 237

0.0097% Chrysotile

Good/Not Regulated by NESHAP; However, Regulated by OSHA

290 SF

Black VFT and Black Mastic - Under Non-

ACM HA 56

Building 12

- Rooms 137, 237

5.8% Chrysotile (tile) Good/Category I Non-

Friable

180 SF

1.6% Chrysotile (mastic)

Facilities | Environmental | Geotechnical | Materials 8

No.

Material Description

Material Locations

% & Type Asbestos

Condition/ NESHAP Category

Estimated Quantity

Red VFT and Black

Mastic - Under Non-

ACM HA 56

Building 12

– Rooms 137, 237

6.5% Chrysotile (tile) Good/Category I Non-

Friable

180 SF

1.3% Chrysotile (mastic)

Brown Caulking Behind Radiator

Building 12

- Rooms 137, 237

3% Chrysotile Good/Category II Non-

Friable

4.5 SF

Gray Transite and

Black Mastic Behind Radiator

Building 12

- Rooms 137, 237

11% Chrysotile (Transite)

Good/Category II Non- Friable

200 SF

2.1% Chrysotile

(mastic) Good/Category II Non-

Friable

Black Mastic Associated with Non-

ACM 12"x12" Gray Mottled VFT

Building 14

- Room 102

3.1% Chrysotile

Good/Category I Non- Friable

200 SF

Brown Caulking Behind Radiator

Building 14

- Rooms

102, 201C 4.4% Chrysotile

Good/Category II Non- Friable

7 SF

Gray Transite and

Black Mastic Behind Radiator

Building 14

- Rooms

102, 201C

14% Chrysotile (Transite)

Good/Category II Non- Friable

400 SF

1.6% Chrysotile

(mastic) Good/Category II Non-

Friable

75 Yellow Carpet Mastic Building 27

– Room 02

0.36% Chrysotile Good/Not Regulated by NESHAP; However, Regulated by OSHA

300 SF

Brown 9"x9" VFT and Black Mastic Under

HA 75

Building 27

- Room 02

9.7% Chrysotile (tile) Good/Category I Non-

Friable

130 SF

1.2% Chrysotile (mastic)

Gray Radiator

Caulking

Building 27

- Rooms 02, 20, 21 3% Chrysotile

Good/Category II Non- Friable

9 SF

Transite Board with

Black Mastic

Building 27

- Rooms 02, 20, 21

12% Chrysotile (Transite)

Good/Category II Non- Friable

400 SF

1.6% Chrysotile

(mastic) Good/Category II Non-

Friable

Yellow and Black Mastic Associated with Non-ACM 12”x12” Gray VFT

Building 27

– Room 02

0.74% Chrysotile Good/Not Regulated by NESHAP; However, Regulated by OSHA

300 SF

Green and Black Mastic Associated with Non-ACM 18”x18” Beige VFT

Building 52

– Room 120

0.32% Chrysotile Good/Not Regulated by NESHAP; However, 130 SF

Facilities | Environmental | Geotechnical | Materials 9

No.

Material Description

Material Locations

% & Type Asbestos

Condition/ NESHAP Category

Estimated Quantity

Yellow Mastic Under

Non-ACM False Wood

VFT

Building 28

– Room 112

0.0075% Chrysotile

Good/Not Regulated by NESHAP; However, Regulated by OSHA

133 SF

Beige 12"x12" VFT and Yellow Mastic

Under Non-ACM HA

Building 28

- Room 112

5.8% Chrysotile (tile) Good/Category I Non-

Friable

133 SF

1.2% Chrysotile (mastic)

Black VFT and Black Mastic Under ACM

HA 87 and Non-ACM

HA89

Building 28

- Room 112

18% Chrysotile (tile)

Good/Category I Non- Friable (Tile); Mastic

Not Regulated by NESHAP; However, Regulated by OSHA

133 SF

0.037% Chrysotile

(mastic)

In addition, the following materials are assumed to contain >1% asbestos (not sampled to avoid irreparable damage, inaccessible, or based on results above):

Material Description Material Location Estimated Quantity

Terrazzo Floor

Building 1: Rooms 218, 219, and 307 90 SF

Building 4: Room 012 40 SF

Building 5: Rooms 110 and 110A 40 SF

Building 6: Room 01 285 SF

Building 7: Rooms 11 and 242 60 SF

Building 12: Room 237 15 SF

Building 15: Rooms 142, 242 40 SF

Building 27: Rooms 02, 20, and 21 150 SF

Gray Radiator Caulking Building 28: Room 112 5 SF

Transite Board with Black Mastic

Building 28: Room 112 200 SF

An asbestos sample locations and results summary is included in Appendix A and the laboratory analytical report is included in Appendix B. Photos are included of the ACM identified in Appendix D.

If any identified ACM will be impacted by renovation activities, they will need to be properly removed and disposed prior to renovation activities in accordance with applicable federal, state, and local regulations, as well as in accordance with VA specifications.

5.2 Lead Paint

15133 Stamp

Facilities | Environmental | Geotechnical | Materials 10

In summary, the high lead content XRF testing results (e.g., ≥1.0 mg/cm2) were identified to correspond with the following painted components:

Building 3

Drywall Walls, Building 6

Plaster Walls and, Metal Radiators

Building 3

Drywall Walls, In summary, the low lead content XRF testing results (e.g., <1.0 mg/cm2) were identified to correspond with the following painted components:

Building 1

Drywall Walls and Ceilings, Metal Radiators, and Metal Ceiling Panels.

Building 3

Drywall Walls and Ceilings, Metal Radiators, and Metal Ceiling Panels.

Building 4

Drywall Walls and Ceilings, Metal Radiators, Metal Ceiling Panels, and Concrete Ceilings and Floors.

Building 5

Drywall Walls and Ceilings, Plaster Walls and Ceilings, Metal Radiators, Brick Wall, and Concrete Ceilings.

Building 6

Drywall Walls and Ceilings, Plaster Walls and Ceilings, Wood Walls, Brick Walls, CMU Wall, Metal Radiators, Facilities | Environmental | Geotechnical | Materials 11

Ceiling Tiles, and Concrete Ceilings and Floors.

Building 7

Drywall Walls and Ceilings, Plaster Walls and Ceilings, CMU Wall, Metal Radiators, and Ceiling Tiles.

Building 12

Drywall Walls, Plaster Walls and Ceilings, Brick Walls, CMU Wall, and Metal Radiators.

Building 14

Drywall Walls, Plaster Walls and Ceilings, Brick Walls, CMU Wall, Metal Radiators, Metal Ceiling Panels, and Ceiling Tiles.

Building 15

Drywall Walls, Plaster Walls, and Metal Ceiling Panels.

Building 27

Plaster Walls and Ceilings, Metal Radiators, and Concrete Floors.

Building 52

Plaster Walls and Ceilings, Metal Radiators, and Metal Ceiling Panels.

The XRF instrument testing data is included in Appendix A.

Facilities | Environmental | Geotechnical | Materials 12

In addition, to the XRF samples, two (2) paint samples were analyzed, and the analytical lab results are included in the above table. Laboratory report and chain of custody form is included in Appendix B.

6.0 LIMITATIONS/GENERAL COMMENTS

This supplemental asbestos inspection and lead paint testing scope of services were conducted in a manner consistent with the level of care and skill ordinarily exercised by members of the profession currently practicing under similar conditions in the same locale. The results, findings, conclusions, and recommendations expressed in this report are based on conditions observed during our site visit. The information contained in this report is relevant to the date on which this inspection was performed and should not be relied upon to represent conditions at a later date. This report has been prepared on behalf of and exclusively for use by Triple C

- The A&E Group LLC for specific application to their project as discussed. This report is not a bidding document. Contractors or consultants reviewing this report must draw their own conclusions regarding actual quantities present and any further investigation or remediation deemed necessary. Terracon does not warrant the work of regulatory agencies, laboratories, or other third-parties supplying information which may have been used in the preparation of this report. No warranty, express or implied is made.

15133 Stamp

15133 Stamp

Supplemental Asbestos Inspection and Lead Paint Sampling Report

August 21, 2023 | Terracon Project No. J2237038

Facilities | Environmental | Geotechnical | Materials

APPENDIX A

Montrose VA Medical Center

2094 Albany Post Road, Montrose, New York

Asbestos Sample Location Summary

HA No. Material Description Sample Number Sample Location Lab Results (% & Type Asbestos)

PLM 198.1 TEM 198.4

12"x12" Orange-Speckled VFT with Clear Mastic

1-A Building 1 - Room 308 None Detect (ND) (tile)

None Detect

(ND)

12"x12" Orange-Speckled VFT with Clear Mastic

1-B Building 1 - Room 308 ND (mastic) ND

12"x12" Orange-Speckled VFT with Clear Mastic

2-A Building 1 - Room 308 ND (tile) ND

12"x12" Orange-Speckled VFT with Clear Mastic

2-B Building 1 - Room 307 ND (mastic) ND

12"x12" Orange-Speckled VFT with Clear Mastic

3-A Building 1 - Room 308 ND (tile) ND

12"x12" Orange-Speckled VFT with Clear Mastic

3-B Building 1 - Room 219 ND (mastic) ND

Yellow Carpet Mastic 4 Building 1 - Room 307 ND ND

Yellow Carpet Mastic 5 Building 1 - Room 307 ND ND

Yellow Carpet Mastic 6 Building 1 - Room 219 ND ND

Black VFT with Black

Mastic 7-A Building 1 - Room 307

2.1% Chrysotile

(tile)

N/A

August 21, 2023 | Terracon Project No. J2237038

Facilities | Environmental | Geotechnical | Materials

HA No. Material Description Sample Number Sample Location Lab Results (% & Type Asbestos)

PLM 198.1 TEM 198.4

Black VFT with Black Mastic

7-B Building 1 - Room 307 ND (mastic) ND

Black VFT with Black Mastic

8-A Building 1 - Room 307

NA/PS (tile) N/A

Black VFT with Black Mastic

8-B Building 1 - Room 307

ND (mastic) ND

Black VFT with Black Mastic

9-A Building 1 - Room 219 NA/PS (tile) N/A

Black VFT with Black Mastic

9-B Building 1 - Room 219 ND (mastic) ND

9"x9" Red VFT with Black Mastic

10-A Building 1 - Room 308

1.4% Chrysotile

(tile)

N/A

9"x9" Red VFT with Black Mastic

10-B Building 1 - Room 307 ND (mastic) ND

9"x9" Red VFT with Black Mastic

11-A Building 1 - Room 307

NA/PS (tile) N/A

9"x9" Red VFT with Black Mastic

11-B Building 1 - Room 307

ND (mastic) ND

9"x9" Red VFT with Black Mastic

12-A Building 1 - Room 219 NA/PS (tile) N/A

9"x9" Red VFT with Black Mastic

12-B Building 1 - Room 219 ND (mastic) ND

August 21, 2023 | Terracon Project No. J2237038

Facilities | Environmental | Geotechnical | Materials

HA No. Material Description Sample Number Sample Location Lab Results (% & Type Asbestos)

PLM 198.1 TEM 198.4

Gray Radiator Caulking 13 Building 1 - Room 308

3.6% Chrysotile

N/A

Gray Radiator Caulking 14 Building 1 - Room 307 NA/PS N/A

Gray Radiator Caulking 15 Building 1 - Room 219 NA/PS N/A

Gray Transite and Black Mastic Behind Radiator

16-A Building 1 - Room 308

24% Chrysotile

(Transite ®)

N/A

Gray Transite and Black Mastic Behind Radiator

16-B Building 1 - Room 308

1.4% Chrysotile (mastic)

N/A

Gray Transite and Black Mastic Behind Radiator

17-A Building 1 - Room 307

NA/PS

(Transite ®) N/A

Gray Transite and Black Mastic Behind Radiator

17-B Building 1 - Room 307

NA/PS

(mastic) N/A

Gray Transite and Black Mastic Behind Radiator

18-A Building 1 - Room 219

NA/PS

(Transite ®) N/A

Gray Transite and Black Mastic Behind Radiator

18-B Building 1 - Room 219

NA/PS

(mastic) N/A

Dark Gray Floor Grout 19 Building 1 - Room 219 ND N/A

Dark Gray Floor Grout 20 Building 1 - Room 015 ND N/A

Dark Gray Floor Grout 21 Building 1 - Room 015 ND N/A

Gray Floor Tile Bedding 22 Building 1 - Room 015 ND N/A

Gray Floor Tile Bedding 23 Building 1 - Room 015 ND N/A

Gray Floor Tile Bedding 24 Building 1 - Room 015 ND N/A

August 21, 2023 | Terracon Project No. J2237038

Facilities | Environmental | Geotechnical | Materials

HA No. Material Description Sample Number Sample Location Lab Results (% & Type Asbestos)

PLM 198.1 TEM 198.4

Dark Gray Floor Tile Bedding

25 Building 1 - Room 015 ND N/A

Dark Gray Floor Tile Bedding

26 Building 1 - Room 015A ND N/A

Dark Gray Floor Tile Bedding

27 Building 1 - Room 015A ND N/A

12"x12" Yellow VFT with Brown Mastic

28-A Building 1 - Room 219 ND (tile) ND

12"x12" Yellow VFT with Brown Mastic

28-B Building 1 - Room 219

1.6% Chrysotile (mastic)

N/A

12"x12" Yellow VFT with Brown Mastic

29-A Building 1 - Room 219 ND (tile) ND

12"x12" Yellow VFT with Brown Mastic

29-B Building 1 - Room 219

NA/PS

(mastic) N/A

12"x12" Yellow VFT with Brown Mastic

30-A Building 1 - Room 218 ND (tile) ND

12"x12" Yellow VFT with Brown Mastic

30-B Building 1 - Room 218

NA/PS

(mastic) N/A

Yellow and Green Carpet Mastic

31-A Building 1 - Room 218 ND ND

Yellow and Green Carpet Mastic

31-B Building 1 - Room 218 ND ND

Yellow and Green Carpet

32-A Building 1 - Room 218 ND ND

August 21, 2023 | Terracon Project No. J2237038

Facilities | Environmental | Geotechnical | Materials

HA No. Material Description Sample Number Sample Location Lab Results (% & Type Asbestos)

PLM 198.1 TEM 198.4

Yellow and Green Carpet Mastic

32-B Building 1 - Room 218 ND ND

Yellow and Green Carpet Mastic

33-A Building 1 - Room 218 ND ND

Yellow and Green Carpet Mastic

33-B Building 1 - Room 218 ND ND

Gray Speckled VFT with Black Mastic

34-A Building 1 - Room 122 ND (tile) ND

Gray Speckled VFT with Black Mastic

34-B Building 1 - Room 122 ND (mastic) ND

Gray Speckled VFT with Black Mastic

35-A Building 1 - Room 122 ND (tile) ND

Gray Speckled VFT with Black Mastic

35-B Building 1 - Room 122 ND (mastic) ND

Gray Speckled VFT with Black Mastic

36-A Building 1 - Room 122 ND (tile) ND

Gray Speckled VFT with Black Mastic

36-B Building 1 - Room 122 ND (mastic) ND

Brown Floor Tile Grout 37 Building 1 - Room 123 ND N/A

Brown Floor Tile Grout 38 Building 1 - Room 123 ND N/A

Brown Floor Tile Grout 39 Building 1 - Room 123 ND N/A

Off-White Floor Tile Bedding

40 Building 1 - Room 123 ND N/A

Off-White Floor Tile Bedding

41 Building 1 - Room 123 ND N/A

August 21, 2023 | Terracon Project No. J2237038

Facilities | Environmental | Geotechnical | Materials

HA No. Material Description Sample Number Sample Location Lab Results (% & Type Asbestos)

PLM 198.1 TEM 198.4

Off-White Floor Tile Bedding

42 Building 1 - Room 123 ND N/A

Gray Caulking Behind Radiator

43 Building 3 - Room 243A 4.8%

Chrysotile N/A

Gray Caulking Behind Radiator

44 Building 3 - Room 243A NA/PS N/A

Gray Caulking Behind Radiator

45 Building 3 - Room 243A NA/PS N/A

Gray Transite and Black Mastic Behind Radiator

46-A Building 3 - Room 243A

14% Chrysotile

(Transite ®)

N/A

Gray Transite and Black Mastic Behind Radiator

46-B Building 3 - Room 243A

0.76% Chrysotile (mastic)

0.21% Chrysotile

Gray Transite and Black Mastic Behind Radiator

47-A Building 3 - Room 243A

NA/PS

(Transite ®) N/A

Gray Transite and Black Mastic Behind Radiator

47-B Building 3 - Room 243A

4.8% Chrysotile (mastic)

N/A

Gray Transite and Black Mastic Behind Radiator

48-A Building 3 - Room 243A

NA/PS

(Transite ®) N/A

Gray Transite and Black Mastic Behind Radiator

48-B Building 3 - Room 243A

NA/PS

(mastic) N/A

18"x18" Marbled VFT with Beige Mastic - Top Layer

49-A Building 3 - Room 243A ND (tile) ND

August 21, 2023 | Terracon Project No. J2237038

Facilities | Environmental | Geotechnical | Materials

HA No. Material Description Sample Number Sample Location Lab Results (% & Type Asbestos)

PLM 198.1 TEM 198.4

18"x18" Marbled VFT with Beige Mastic - Top Layer

49-B Building 3 - Room 243A ND (mastic) ND

18"x18" Marbled VFT with Beige Mastic - Top Layer

50-A Building 3 - Room 243A ND (tile) ND

18"x18" Marbled VFT with Beige Mastic - Top Layer

50-B Building 3 - Room 243A ND (mastic) ND

18"x18" Marbled VFT with Beige Mastic - Top Layer

51-A Building 3 - Room 243A ND (tile) ND

18"x18" Marbled VFT with Beige Mastic - Top Layer

51-B Building 3 - Room 243A ND (mastic) ND

12"x12" Gray Speckled VFT with Beige Mastic -

2nd Layer 52-A Building 3 - Room 243A ND (tile) ND

12"x12" Gray Speckled VFT with Beige Mastic -

2nd Layer 52-B Building 3 - Room 243A ND (mastic) ND

12"x12" Gray Speckled VFT with Beige Mastic -

2nd Layer 53-A Building 3 - Room 243A ND (tile) ND

12"x12" Gray Speckled VFT with Beige Mastic -

2nd Layer 53-B Building 3 - Room 243A ND (mastic) ND

12"x12" Gray Speckled VFT with Beige Mastic -

2nd Layer 54-A Building 3 - Room 243A ND (tile) ND

August 21, 2023 | Terracon Project No. J2237038

Facilities | Environmental | Geotechnical | Materials

HA No. Material Description Sample Number Sample Location Lab Results (% & Type Asbestos)

PLM 198.1 TEM 198.4

12"x12" Gray Speckled VFT with Beige Mastic -

2nd Layer

54-B Building 3 - Room 243A ND (mastic) 0.32%

Chrysotile

Off-White Speckled Terrazzo - Bottom Layer

55 Building 3 - Room 243A ND ND

Off-White Speckled Terrazzo - Bottom Layer

56 Building 3 - Room 243A ND ND

Off-White Speckled Terrazzo - Bottom Layer

57 Building 3 - Room 149

ND ND

Black Leveling Compound - Bottom

Layer

58 Building 3 - Room 243A 10%

Chrysotile N/A

Black Leveling Compound - Bottom Layer

59 Building 3 - Room 243A NA/PS N/A

Black Leveling Compound - Bottom Layer

60 Building 3 - Room 149

NA/PS N/A

12"x12" White VFT with Gray Speckled and Beige

Mastic - Top Layer 61-A Building 3 - Room 149 ND (tile) ND

12"x12" White VFT with Gray Speckled and Beige

Mastic - Top Layer 61-B Building 3 - Room 149 ND (mastic) ND

August 21, 2023 | Terracon Project No. J2237038

Facilities | Environmental | Geotechnical | Materials

HA No. Material Description Sample Number Sample Location Lab Results (% & Type Asbestos)

PLM 198.1 TEM 198.4

12"x12" White VFT with Gray Speckled and Beige

Mastic - Top Layer 62-A Building 3 - Room 149 ND (tile) ND

12"x12" White VFT with Gray Speckled and Beige

Mastic - Top Layer 62-B Building 3 - Room 149 ND (mastic) ND

12"x12" White VFT with Gray Speckled and Beige

Mastic - Top Layer 63-A Building 3 - Room 149 ND (tile) ND

12"x12" White VFT with Gray Speckled and

Beige Mastic - Top Layer

63-B Building 3 - Room 149 ND (mastic) 0.0072%

18"x18" Brown Marbled VFT with Off-White Mastic

- Top Layer 64-A Building 3 - Room 051M04 ND (tile) ND

18"x18" Brown Marbled VFT with Off-White Mastic

- Top Layer 64-B Building 3 - Room 051M04 ND (mastic) ND

18"x18" Brown Marbled VFT with Off-White Mastic

- Top Layer 65-A Building 3 - Room 051M04 ND (tile) ND

18"x18" Brown Marbled VFT with Off-White Mastic

- Top Layer 65-B Building 3 - Room 051M04 ND (mastic) ND

August 21, 2023 | Terracon Project No. J2237038

Facilities | Environmental | Geotechnical | Materials

HA No. Material Description Sample Number Sample Location Lab Results (% & Type Asbestos)

PLM 198.1 TEM 198.4

18"x18" Brown Marbled VFT with Off-White Mastic

- Top Layer 66-A Building 3 - Room 051M04 ND (tile) ND

18"x18" Brown Marbled VFT with Off-White Mastic

- Top Layer 66-B Building 3 - Room 051M04 ND (mastic) ND

12"x12" Off-White VFT with Specks and Beige Mastic - Bottom Layer

67-A Building 3 - Room 051M04 ND (tile) ND

12"x12" Off-White VFT with Specks and Beige Mastic - Bottom Layer

67-B Building 3 - Room 051M04 ND (mastic) ND

12"x12" Off-White VFT with Specks and Beige Mastic - Bottom Layer

68-A Building 3 - Room 051M04 ND (tile) ND

12"x12" Off-White VFT with Specks and Beige Mastic - Bottom Layer

68-B Building 3 - Room 051M04 ND (mastic) ND

12"x12" Off-White VFT with Specks and Beige Mastic - Bottom Layer

69-A Building 3 - Room 051M04 ND (tile) ND

12"x12" Off-White VFT with Specks and Beige Mastic - Bottom Layer

69-B Building 3 - Room 051M04 ND (mastic) ND

August 21, 2023 | Terracon Project No. J2237038

Facilities | Environmental | Geotechnical | Materials

HA No. Material Description Sample Number Sample Location Lab Results (% & Type Asbestos)

PLM 198.1 TEM 198.4

12"x12" Off-White VFT with Dots and Black and Yellow Mastic - Top Layer

70-A Building 4- Room 130 ND (tile) ND

12"x12" Off-White VFT with Dots and Black and Yellow Mastic - Top Layer

70-B Building 4- Room 130 ND (mastic) ND

12"x12" Off-White VFT with Dots and Black and Yellow Mastic - Top Layer

71-A Building 4- Room 130 ND (tile) ND

12"x12" Off-White VFT with Dots and Black and Yellow Mastic - Top Layer

71-B Building 4- Room 130 ND (mastic) ND

12"x12" Off-White VFT with Dots and Black and Yellow Mastic - Top Layer

72-A Building 4- Room 130 ND (tile) ND

12"x12" Off-White VFT with Dots and Black and Yellow Mastic - Top Layer

72-B Building 4- Room 130 ND (mastic) ND

Gray Leveling Compound - Bottom Layer Under HAs

24 & 27

73 Building 4- Room 130

ND N/A

Gray Leveling Compound - Bottom Layer Under HAs

24 & 27

74 Building 4 - Room 012 ND N/A

August 21, 2023 | Terracon Project No. J2237038

Facilities | Environmental | Geotechnical | Materials

HA No. Material Description Sample Number Sample Location Lab Results (% & Type Asbestos)

PLM 198.1 TEM 198.4

Gray Leveling Compound - Bottom Layer Under HAs

24 & 27

75 Building 4 - Room 227 ND N/A

Gray Speckled Vinyl Sheet Flooring with Beige Mastic

76-A Building 4 - Room 131 ND (sheet flooring)

ND

Gray Speckled Vinyl Sheet Flooring with Beige Mastic

76-B Building 4 - Room 131 ND (mastic) ND

Gray Speckled Vinyl Sheet Flooring with Beige Mastic

77-A Building 4 - Room 249 ND (sheet flooring)

ND

Gray Speckled Vinyl Sheet Flooring with Beige Mastic

77-B Building 4 - Room 249 ND (mastic) ND

Gray Speckled Vinyl Sheet Flooring with Beige Mastic

78-A Building 4 - Room 249 ND (sheet flooring)

ND

Gray Speckled Vinyl Sheet Flooring with Beige Mastic

78-B Building 4 - Room 249 ND (mastic) ND

12"x12" Green VFT with Black Dots and Yellow

Mastic

79-A Building 4 - Room 227 ND (tile) ND

12"x12" Green VFT with Black Dots and Yellow

Mastic

79-B Building 4 - Room 227 ND (mastic) ND

12"x12" Green VFT with Black Dots and Yellow

80-A Building 4 - Room 227 ND (tile) ND

August 21, 2023 | Terracon Project No. J2237038

Facilities | Environmental | Geotechnical | Materials

HA No. Material Description Sample Number Sample Location Lab Results (% & Type Asbestos)

PLM 198.1 TEM 198.4

12"x12" Green VFT with Black Dots and Yellow

Mastic

80-B Building 4 - Room 227 ND (mastic) ND

12"x12" Green VFT with Black Dots and Yellow

Mastic

81-A Building 4 - Room 227 ND (tile) ND

12"x12" Green VFT with Black Dots and Yellow

Mastic

81-B Building 4 - Room 227 ND (mastic) ND

Light Gray 12"x12" VFT with Colored Specks and

Yellow Mastic

82-A Building 4 - Room 12 ND (tile) ND

Light Gray 12"x12" VFT with Colored Specks and

Yellow Mastic

82-B Building 4 - Room 12 ND (mastic) ND

Light Gray 12"x12" VFT with Colored Specks and

Yellow Mastic

83-A Building 4 - Room 12 ND (tile) ND

Light Gray 12"x12" VFT with Colored Specks and

Yellow Mastic

84- B Building 4 - Room 12 ND (mastic) ND

Light Gray 12"x12" VFT with Colored Specks and

Yellow Mastic

84-A Building 4 - Room 12 ND (tile) ND

August 21, 2023 | Terracon Project No. J2237038

Facilities | Environmental | Geotechnical | Materials

HA No. Material Description Sample Number Sample Location Lab Results (% & Type Asbestos)

PLM 198.1 TEM 198.4

Light Gray 12"x12" VFT with Colored Specks and

Yellow Mastic

84- B Building 4 - Room 12 ND (mastic) ND

Brown Ceiling Tile Mastic 85 Building 5 - Room 110 ND ND

Brown Ceiling Tile Mastic 86 Building 5 - Room 110 ND ND

Brown Ceiling Tile Mastic 87 Building 5 - Room 110 ND ND

Blue Carpet Glue 88 Building 5 - Room 110 ND ND

Blue Carpet Glue 89 Building 5 - Room 110 ND ND

Blue Carpet Glue 90 Building 5 - Room 110 ND ND

12"x12" Speckled Cream VFT with Black and Yellow

Mastic

91-A Building 5 - Room 110, Under

HA 30

ND (tile) ND

12"x12" Speckled Cream VFT with Black and Yellow

Mastic

91-B Building 5 - Room 110, Under

HA 30

ND (mastic) ND

12"x12" Speckled Cream VFT with Black and Yellow

Mastic

92-A Building 5 - Room 110, Under

HA 30

ND (tile) ND

12"x12" Speckled Cream VFT with Black and Yellow Mastic

92- B Building 5 - Room 110, Under HA 30 ND (mastic)

0.28% Chrysotile

12"x12" Speckled Cream VFT with Black and Yellow

Mastic

93-A Building 5 - Room 110, Under

HA 30

ND (tile) ND

August 21, 2023 | Terracon Project No. J2237038

Facilities | Environmental | Geotechnical | Materials

HA No. Material Description Sample Number Sample Location Lab Results (% & Type Asbestos)

PLM 198.1 TEM 198.4

12"x12" Speckled Cream VFT with Black and Yellow Mastic

93-B Building 5 - Room 110, Under HA 30 ND (mastic)

0.003% Chrysotile

Brown Caulking Behind Radiator

94 Building 5 - Room 110 1.5%

Chrysotile N/A

Brown Caulking Behind Radiator

95 Building 5 - Room 110 NA/PS N/A

Brown Caulking Behind Radiator

96 Building 5 - Room 110 NA/PS N/A

Gray Transite and Black Mastic Behind Radiator

97-A Building 5 - Room 110 17%

Chrysotile N/A

Gray Transite and Black Mastic Behind Radiator

97- B Building 5 - Room 110

0.65% Chrysotile (mastic)

0.48% Chrysotile

Gray Transite and Black Mastic Behind Radiator

98-A Building 5 - Room 110

NA/PS

(Transite®) N/A

Gray Transite and Black Mastic Behind Radiator

98- B Building 5 - Room 110

0.8% Chrysotile (mastic)

0.42% Chrysotile

Gray Transite and Black Mastic Behind Radiator

99-A Building 5 - Room 110

NA/PS

(Transite®) N/A

Gray Transite and Black Mastic Behind Radiator

99- B Building 5 - Room 110

1.1% Chrysotile

August 21, 2023 | Terracon Project No. J2237038

Facilities | Environmental | Geotechnical | Materials

HA No. Material Description Sample Number Sample Location Lab Results (% & Type Asbestos)

PLM 198.1 TEM 198.4

12"x12" Light Brown Mottled VFT with Yellow

Mastic

100-A Building 7 - Room 20 ND (tile) ND

12"x12" Light Brown Mottled VFT with Yellow

Mastic

100- B Building 7 - Room 20 ND (mastic) ND

12"x12" Light Brown Mottled VFT with Yellow

Mastic

101-A Building 7 - Room 20 ND (tile) ND

12"x12" Light Brown Mottled VFT with Yellow

Mastic

101- B Building 7 - Room 20 ND (mastic) ND

12"x12" Light Brown Mottled VFT with Yellow

Mastic

102-A Building 7 - Room 20 ND (tile) ND

12"x12" Light Brown Mottled VFT with Yellow

Mastic

102- B Building 7 - Room 20 ND (mastic) 0.73%

Chrysotile

12"x12" Off-White VFT with Gray Specks

103-A Building 7 - Room 20 ND (tile) ND

12"x12" Off-White VFT with Gray Specks

103- B Building 7 - Room 20 ND (mastic) ND

12"x12" Off-White VFT with Gray Specks

104-A Building 7 - Room 11 ND (tile) ND

12"x12" Off-White VFT with Gray Specks

104- B Building 7 - Room 11 ND (mastic) ND

August 21, 2023 | Terracon Project No. J2237038

Facilities | Environmental | Geotechnical | Materials

HA No. Material Description Sample Number Sample Location Lab Results (% & Type Asbestos)

PLM 198.1 TEM 198.4

12"x12" Off-White VFT with Gray Specks

105-A Building 7 - Room 147 ND (tile) ND

12"x12" Off-White VFT with Gray Specks

105- B Building 7 - Room 147 ND (mastic) ND

Yellow Mastic Under HA 35 106 Building 7 - Room 20

Yellow Mastic Under HA

107 Building 7 - Room 147

ND

0.028%

Chrysotile

Yellow Mastic Under HA

108 Building 7 - Room 243

0.68%

Chrysotile

Black Mastic Under HA 35 109 Building 7 - Room 11 ND ND

Black Mastic Under HA 35 110 Building 7 - Room 11 ND ND

Black Mastic Under HA 35 111 Building 7 - Room 148

Gray Floor Tile Bedding 112 Building 7 - Room 11B ND N/A

Gray Floor Tile Bedding 113 Building 7 - Room 11B ND N/A

Gray Floor Tile Bedding 114 Building 7 - Room 11B ND N/A

Light Gray Floor Tile Bedding

115 Building 7 - Room 19B ND N/A

Light Gray Floor Tile Bedding

116 Building 7 - Room 19B ND N/A

August 21, 2023 | Terracon Project No. J2237038

Facilities | Environmental | Geotechnical | Materials

HA No. Material Description Sample Number Sample Location Lab Results (% & Type Asbestos)

PLM 198.1 TEM 198.4

Light Gray Floor Tile Bedding

117 Building 7 - Room 19B ND N/A

Dark Gray Floor Tile Grout 118 Building 7 - Room 19B ND N/A

Dark Gray Floor Tile Grout 119 Building 7 - Room 19B ND N/A

Dark Gray Floor Tile Grout 120 Building 7 - Room 19A

Pipe Insulation 121 Building 7 - Room 04 ND N/A

Pipe Insulation 122 Building 7 - Room 11

44% Amosite 11%

Chrysotile

N/A

Pipe Insulation 123 Building 7 - Room 11B NA/PS N/A

Pipe Fittings 124 Building 7 - Room 04

44% Amosite 27%

Chrysotile

N/A

Pipe Fittings 125 Building 7 - Room 11 NA/PS N/A

Pipe Fittings 126 Building 7 - Room 11B NA/PS N/A

Brown Caulking Behind Radiator

127 Building 7 - Room 147 3.4%

Chrysotile N/A

Brown Caulking Behind Radiator

128 Building 7 - Room 147 NA/PS N/A

Brown Caulking Behind Radiator

129 Building 7 - Room 242 NA/PS N/A

Gray Transite and Black Mastic Behind Radiator

130-A Building 7 - Room 147

ND

(Transite®)

August 21, 2023 | Terracon Project No. J2237038

Facilities | Environmental | Geotechnical | Materials

HA No. Material Description Sample Number Sample Location Lab Results (% & Type Asbestos)

PLM 198.1 TEM 198.4

Gray Transite and Black Mastic Behind Radiator

130- B Building 7 - Room 147

15% Chrysotile (mastic)

N/A

Gray Transite and Black Mastic Behind Radiator

131-A Building 7 - Room 147

1.1% Chrysotile

(Transite®)

N/A

Gray Transite and Black Mastic Behind Radiator

131- B Building 7 - Room 147

NA/PS

(mastic) N/A

Gray Transite and Black Mastic Behind Radiator

132-A Building 7 - Room 242

NA/PS

(Transite®) N/A

Gray Transite and Black Mastic Behind Radiator

132- B Building 7 - Room 242

NA/PS

(mastic) N/A

Black Leveling Compound - Under HA

133 Building 7 - Room 147 6.7%

Chrysotile N/A

Black Leveling Compound - Under HA

134 Building 7 - Room 147 NA/PS N/A

Black Leveling Compound - Under HA

135 Building 7 - Room 242

NA/PS N/A

Off-White VFT with Specks and Black Mastic - Under

HA 35

136-A Building 7 - Room 148 ND (tile) ND

August 21, 2023 | Terracon Project No. J2237038

Facilities | Environmental | Geotechnical | Materials

HA No. Material Description Sample Number Sample Location Lab Results (% & Type Asbestos)

PLM 198.1 TEM 198.4

Off-White VFT with Specks and Black Mastic - Under

HA 35

136- B Building 7 - Room 148 ND (mastic) ND

Off-White VFT with Specks and Black Mastic - Under

HA 35

137-A Building 7 - Room 148 ND (tile) ND

Off-White VFT with Specks and Black Mastic - Under

HA 35

137- B Building 7 - Room 148 ND (mastic) ND

Off-White VFT with Specks and Black Mastic - Under

HA 35

138-A Building 7 - Room 148 ND (tile) ND

Off-White VFT with Specks and Black Mastic - Under

HA 35

138- B Building 7 - Room 148 ND (mastic) ND

White Top Coat and Gray Base Coat Plaster

139-A Building 5 - Room 110 (ceiling) ND (top coat) ND

White Top Coat and Gray Base Coat Plaster

139- B Building 5 - Room 110 (ceiling) ND (base coat) ND

White Top Coat and Gray Base Coat Plaster

140-A Building 5 - Room 110A

(ceiling) ND (top coat) ND

White Top Coat and Gray Base Coat Plaster

140- B Building 5 - Room 110A

(ceiling) ND (base coat) ND

White Top Coat and Gray Base Coat Plaster

141-A Building 5 - Room 110A

(ceiling) ND (top coat) ND

August 21, 2023 | Terracon Project No. J2237038

Facilities | Environmental | Geotechnical | Materials

HA No. Material Description Sample Number Sample Location Lab Results (% & Type Asbestos)

PLM 198.1 TEM 198.4

White Top Coat and Gray Base Coat Plaster

141- B Building 5 - Room 110A

(ceiling) ND (base coat) ND

Yellow Carpet Mastic 142 Building 7 - Room 243 ND ND

Yellow Carpet Mastic 143 Building 7 - Room 243 ND ND

Yellow Carpet Mastic 144 Building 7 - Room 243 ND ND

White Top Coat and Gray Base Coat Plaster

145-A Building 7 - Room 242 (wall) ND (top coat) ND

White Top Coat and Gray Base Coat Plaster

145- B Building 7 - Room 242 (wall) ND (base coat) ND

White Top Coat and Gray Base Coat Plaster

146-A Building 7 - Room 242 (wall) ND (top coat) N/A

White Top Coat and Gray Base Coat Plaster

146- B Building 7 - Room 242 (wall) ND (base coat) N/A

White Top Coat and Gray Base Coat Plaster

147-A Building 7 - Room 242 (wall) ND (top coat) N/A

White Top Coat and Gray Base Coat Plaster

147- B Building 7 - Room 242 (wall) ND (base coat) N/A

12"x12" Off-White VFT with Blue/Gray Speckles, Black and Yellow Mastic, and White Leveling Compound

148-A Building 6 - Room 201A ND (tile) ND

August 21, 2023 | Terracon Project No. J2237038

Facilities | Environmental | Geotechnical | Materials

HA No. Material Description Sample Number Sample Location Lab Results (% & Type Asbestos)

PLM 198.1 TEM 198.4

12"x12" Off-White VFT with Blue/Gray Speckles, Black and Yellow Mastic, and White Leveling Compound

148- B Building 6 - Room 201A ND (mastic) ND

12"x12" Off-White VFT with Blue/Gray Speckles, Black and Yellow Mastic, and White Leveling Compound

149-A Building 6 - Room 205 ND (tile) ND

12"x12" Off-White VFT with Blue/Gray Speckles, Black and Yellow Mastic, and White Leveling Compound

149- B Building 6 - Room 205 ND (mastic) ND

12"x12" Off-White VFT with Blue/Gray Speckles, Black and Yellow Mastic, and White Leveling Compound

150-A Building 6 - Room 101A ND (tile) ND

12"x12" Off-White VFT with Blue/Gray Speckles, Black and Yellow Mastic, and White Leveling Compound

150- B Building 6 - Room 101A ND (mastic) ND

51 Yellow Carpet Mastic 151 Building 6 - Room 104 ND ND

August 21, 2023 | Terracon Project No. J2237038

Facilities | Environmental | Geotechnical | Materials

HA No. Material Description Sample Number Sample Location Lab Results (% & Type Asbestos)

PLM 198.1 TEM 198.4

Yellow Carpet Mastic 152 Building 6 - Room 104 ND ND

Yellow Carpet Mastic 153 Building 6 - Room 104 ND ND

12"x12" White VFT with Gray Speckles and Black and Yellow Mastic

154-A Building 6 - Room 131 ND (tile) ND

12"x12" White VFT with Gray Speckles and Black and Yellow Mastic

154- B Building 6 - Room 131 ND (mastic) ND

12"x12" White VFT with Gray Speckles and Black and Yellow Mastic

155-A Building 6 - Room 131 ND (tile) ND

12"x12" White VFT with Gray Speckles and Black and Yellow Mastic

15…