Attachment 8 Drawings 521-21-106_Part7.pdf

PDF 8 MB Posted

Attached to
Y1DA--521-21-106 | Medical Gas Systems
Solicitation number
36C24725R0020
Issued by

About this file

This is a set of electrical drawings for the Birmingham VA Medical Center showing floor plans from ground level through 8th floor that detail electrical system layouts, including locations of life safety branch panels, conduit routing, and other electrical components. The drawings are part of a medical gas systems project (521-21-106) and were prepared by West Point Engineers LLC.

The drawings include detailed electrical layouts for Areas A through G across multiple floors, with specific attention to life safety branch panels (designated as "LS" panels), conduit routing, and electrical equipment locations. General notes indicate requirements for coordination with hospital area naming, electrical legend references, and penetration sealing requirements. The drawings emphasize maintaining medical gas services throughout construction and include specifications for electrical connections related to medical gas system components. Key details show power distribution, emergency circuits, and life safety branch circuitry required to support the medical gas system infrastructure.

View the file

Other files

File Type Posted
36C24725R0020 0008.docx DOCX document
36C24725R0020 0007.docx DOCX document
36C24725R0020 0006.docx DOCX document
Attachment 0005B_Med Gas Annual Inspection 2024.pdf PDF
36C24725R0020 0005.docx DOCX document
Attachment 0005A_RFI Clarifications.docx DOCX document
36C24725R0020 0004.pdf PDF
Attachment 0003A_RFI Answers_36C24725R0020.docx DOCX document
36C24725R0020 0003.docx DOCX document
Attachment 0003B_Asbestos Inspection Report_36C24725R0020.pdf PDF
Attachment 0003C_Photos_36C24725R0020.zip ZIP file
36C24725R0020 0002.docx DOCX document
Attachment 0002 - PROPOSAL PREPARATION AND EVALUATION INFORMATION_Rev1 521-21-106.pdf PDF
Site Visit Attendance Sheet 521-21-106.pdf PDF
36C24725R0020_0001.pdf PDF
Attachment 8 Drawings 521-21-106_Part6.pdf PDF
Attachment 8 Drawings 521-21-106_Part2.pdf PDF
Attachment 7 Specifications 521-21-106.pdf PDF
Attachment 8 Drawings 521-21-106_Part5.pdf PDF
Attachment 8 Drawings 521-21-106_Part4.pdf PDF
36C24725R0020_RFP.pdf PDF
Attachment 6 INVOICING.docx DOCX document
Attachment 1 Experience Modification Rate Form.pdf PDF
Attachment 8 Drawings 521-21-106_Part1.pdf PDF
Attachment 3 Past Performance Questionnaire -PPQ.docx DOCX document
Attachment 8 Drawings 521-21-106_Part3.pdf PDF
Attachment 4 Itemized Cost Breakdown.xlsx XLSX spreadsheet
Attachment 5 Wage Determination AL20250087 1.3.2025.pdf PDF
Attachment 2 VAAR 852.219-75 Jan 2023 Deviation.pdf PDF
Show all 29

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

E-07

BVG

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

BIRMINGHAM

VA MEDICAL

CENTER

U.S. Department of Veterans Affairs

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

ELECTRICAL

1ST FLOOR: AREA B

MMF

AutoCAD SHX Text 16a

AutoCAD SHX Text

AutoCAD SHX Text M

AutoCAD SHX Text L1

AutoCAD SHX Text L

AutoCAD SHX Text V

AutoCAD SHX Text M

AutoCAD SHX Text I

AutoCAD SHX Text J

AutoCAD SHX Text K

AutoCAD SHX Text M

AutoCAD SHX Text N

AutoCAD SHX Text O

AutoCAD SHX Text P

AutoCAD SHX Text Q

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text U

AutoCAD SHX Text V

AutoCAD SHX Text W

AutoCAD SHX Text I1

AutoCAD SHX Text

BID DOCUMENTS FOR CONSTRUCTION

AutoCAD SHX Text

FULLY SPRINKLERED

AutoCAD SHX Text

REPLACE/UPGRADE MEDICAL GAS SYSTEM

AutoCAD SHX Text 521-21-106

AutoCAD SHX Text 07-07-2023

AutoCAD SHX Text

700 S. 19TH STREET, BIRMINGHAM, AL. 35233

AutoCAD SHX Text

BIRMINGHAM VA MEDICAL CENTER

AutoCAD SHX Text

AutoCAD SHX Text

KEY PLAN: 1ST FLOOR

AutoCAD SHX Text N

AutoCAD SHX Text

DRAWING SCALE: 1/8" = 1' - 0"

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text KEY NOTES (NEW WORK) 1. EXISTING MASTER ALARM PANEL TO BE DEMOLISHED AFTER EXISTING MASTER ALARM PANEL TO BE DEMOLISHED AFTER INSTALLATION OF NEW MASTER ALARM PANEL ON BASEMENT LEVEL. COORDINATE WORK WITH PHASING PLANS AND OTHER TRADES. REMOVE PANEL, CONDUIT, AND CONDUCTORS BACK TO SOURCE.

AutoCAD SHX Text

AutoCAD SHX Text GENERAL NOTES A. KEY PLAN AREA NAMING DOES NOT CORRESPOND TO HOSPITAL KEY PLAN AREA NAMING DOES NOT CORRESPOND TO HOSPITAL AREA NAMING. B. REFER TO SHEET E-00 FOR ELECTRICAL LEGEND, GENERAL NOTES, REFER TO SHEET E-00 FOR ELECTRICAL LEGEND, GENERAL NOTES, AND ABBREVIATIONS. C. MEDICAL GAS SERVICES TO THE HOSPITAL MUST BE MAINTAINED MEDICAL GAS SERVICES TO THE HOSPITAL MUST BE MAINTAINED THROUGHOUT THE CONSTRUCTION PERIOD. D. BEFORE BEGINNING WORK, THE CONTRACTOR SHALL REFER TO THE BEFORE BEGINNING WORK, THE CONTRACTOR SHALL REFER TO THE ARCHITECTURAL DRAWINGS FOR THE PHASING PLAN. ALSO, SEE THE LIFE SAFETY AND INFECTION CONTROL (ICRA) PLANS. E. COORDINATE DIVISIONS 26 & 27 WORK WITH OTHER TRADES AS COORDINATE DIVISIONS 26 & 27 WORK WITH OTHER TRADES AS INDICATED OR REQUIRED. F. ALL WORK SHALL COMPLY WITH LATEST EDITION OF NFPA70, ALL WORK SHALL COMPLY WITH LATEST EDITION OF NFPA70, NFPA72, NFPA99, NFPA101, NEC & ALL FEDERAL, STATE & LOCAL REGULATIONS. G. ALL PENETRATIONS THROUGH FLOORS, RATED WALLS AND ALL PENETRATIONS THROUGH FLOORS, RATED WALLS AND PARTITIONS SHALL BE SEALED WITH UL APPROVED FIRE SEALANT MATERIAL TO MAINTAIN FIRE RATING FOR THE SEPARATION. H. SOME CIRCUITS AFFECTED BY THE WORK INDICATED ON THIS SHEET SOME CIRCUITS AFFECTED BY THE WORK INDICATED ON THIS SHEET MAY FEED OTHER AREAS OUTSIDE THE SCOPE OF THIS PROJECT. THE CONTRACTOR SHALL MAINTAIN CIRCUIT CONTINUITY AT ALL TIMES TO AREAS OUTSIDE THE SCOPE OF WORK. ANY POWER OUTAGES MUST BE COORDINATED IN ADVANCE WITH THE COR.

FDC

E-08

BVG

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

BIRMINGHAM

VA MEDICAL

CENTER

U.S. Department of Veterans Affairs

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

ELECTRICAL

2ND FLOOR: AREA A & D

MMF

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

BID DOCUMENTS FOR CONSTRUCTION

AutoCAD SHX Text

FULLY SPRINKLERED

AutoCAD SHX Text

REPLACE/UPGRADE MEDICAL GAS SYSTEM

AutoCAD SHX Text 521-21-106

AutoCAD SHX Text 07-07-2023

AutoCAD SHX Text

700 S. 19TH STREET, BIRMINGHAM, AL. 35233

AutoCAD SHX Text

BIRMINGHAM VA MEDICAL CENTER

AutoCAD SHX Text

AutoCAD SHX Text N

AutoCAD SHX Text

DRAWING SCALE: 1/8" = 1' - 0"

AutoCAD SHX Text

KEY PLAN: 2ND FLOOR

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text F

AutoCAD SHX Text D

AutoCAD SHX Text G

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text H

AutoCAD SHX Text G

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text G

AutoCAD SHX Text

AP 2-1

AutoCAD SHX Text GENERAL NOTES A. KEY PLAN AREA NAMING DOES NOT CORRESPOND TO HOSPITAL KEY PLAN AREA NAMING DOES NOT CORRESPOND TO HOSPITAL AREA NAMING. B. REFER TO SHEET E-00 FOR ELECTRICAL LEGEND, GENERAL NOTES, REFER TO SHEET E-00 FOR ELECTRICAL LEGEND, GENERAL NOTES, AND ABBREVIATIONS. C. MEDICAL GAS SERVICES TO THE HOSPITAL MUST BE MAINTAINED MEDICAL GAS SERVICES TO THE HOSPITAL MUST BE MAINTAINED THROUGHOUT THE CONSTRUCTION PERIOD. D. BEFORE BEGINNING WORK, THE CONTRACTOR SHALL REFER TO THE BEFORE BEGINNING WORK, THE CONTRACTOR SHALL REFER TO THE ARCHITECTURAL DRAWINGS FOR THE PHASING PLAN. ALSO, SEE THE LIFE SAFETY AND INFECTION CONTROL (ICRA) PLANS. E. COORDINATE DIVISIONS 26 & 27 WORK WITH OTHER TRADES AS COORDINATE DIVISIONS 26 & 27 WORK WITH OTHER TRADES AS INDICATED OR REQUIRED. F. ALL WORK SHALL COMPLY WITH LATEST EDITION OF NFPA70, ALL WORK SHALL COMPLY WITH LATEST EDITION OF NFPA70, NFPA72, NFPA99, NFPA101, NEC & ALL FEDERAL, STATE & LOCAL REGULATIONS. G. ALL PENETRATIONS THROUGH FLOORS, RATED WALLS AND ALL PENETRATIONS THROUGH FLOORS, RATED WALLS AND PARTITIONS SHALL BE SEALED WITH UL APPROVED FIRE SEALANT MATERIAL TO MAINTAIN FIRE RATING FOR THE SEPARATION. H. SOME CIRCUITS AFFECTED BY THE WORK INDICATED ON THIS SHEET SOME CIRCUITS AFFECTED BY THE WORK INDICATED ON THIS SHEET MAY FEED OTHER AREAS OUTSIDE THE SCOPE OF THIS PROJECT. THE CONTRACTOR SHALL MAINTAIN CIRCUIT CONTINUITY AT ALL TIMES TO AREAS OUTSIDE THE SCOPE OF WORK. ANY POWER OUTAGES MUST BE COORDINATED IN ADVANCE WITH THE COR.

AutoCAD SHX Text KEY NOTES (NEW WORK) 1. NEW AREA ALARM PANEL. NEW AREA ALARM PANEL. PROVIDE 120V LIFE-SAFETY POWER FROM PANEL "LS22D." 20A BRANCH CIRCUIT, (2)#12 & (1)#12 G. IN 3/4" C. REFER TO PANEL SCHEDULE ON THIS SHEET. NEW ALARM PANEL TO BE INSTALLED ADJACENT TO THE EXISTING AND READY FOR FINAL CONNECTIONS PRIOR TO THE REMOVAL OF THE EXISTING PANEL. COORDINATE WORK WITH OTHER TRADES. 2. EXISTING ELECTRICAL PANEL "LS22D." REFER TO PANEL EXISTING ELECTRICAL PANEL "LS22D." REFER TO PANEL SCHEDULE ON THIS SHEET.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

LS22D-8

LS22D

FACP

E-09

BVG

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

BIRMINGHAM

VA MEDICAL

CENTER

U.S. Department of Veterans Affairs

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

ELECTRICAL

3RD FLOOR: AREA B

MMF

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

BID DOCUMENTS FOR CONSTRUCTION

AutoCAD SHX Text

FULLY SPRINKLERED

AutoCAD SHX Text

REPLACE/UPGRADE MEDICAL GAS SYSTEM

AutoCAD SHX Text 521-21-106

AutoCAD SHX Text 07-07-2023

AutoCAD SHX Text

700 S. 19TH STREET, BIRMINGHAM, AL. 35233

AutoCAD SHX Text

BIRMINGHAM VA MEDICAL CENTER

AutoCAD SHX Text

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text F

AutoCAD SHX Text D

AutoCAD SHX Text G

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text

DRAWING SCALE: 1/8" = 1' - 0"

AutoCAD SHX Text

KEY PLAN: 3RD FLOOR

AutoCAD SHX Text R

AutoCAD SHX Text Q

AutoCAD SHX Text P

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text

AutoCAD SHX Text I

AutoCAD SHX Text J

AutoCAD SHX Text K

AutoCAD SHX Text M

AutoCAD SHX Text N

AutoCAD SHX Text O

AutoCAD SHX Text P

AutoCAD SHX Text Q

AutoCAD SHX Text I1

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text GENERAL NOTES A. KEY PLAN AREA NAMING DOES NOT CORRESPOND TO HOSPITAL KEY PLAN AREA NAMING DOES NOT CORRESPOND TO HOSPITAL AREA NAMING. B. REFER TO SHEET E-00 FOR ELECTRICAL LEGEND, GENERAL NOTES, REFER TO SHEET E-00 FOR ELECTRICAL LEGEND, GENERAL NOTES, AND ABBREVIATIONS. C. MEDICAL GAS SERVICES TO THE HOSPITAL MUST BE MAINTAINED MEDICAL GAS SERVICES TO THE HOSPITAL MUST BE MAINTAINED THROUGHOUT THE CONSTRUCTION PERIOD. D. BEFORE BEGINNING WORK, THE CONTRACTOR SHALL REFER TO THE BEFORE BEGINNING WORK, THE CONTRACTOR SHALL REFER TO THE ARCHITECTURAL DRAWINGS FOR THE PHASING PLAN. ALSO, SEE THE LIFE SAFETY AND INFECTION CONTROL (ICRA) PLANS. E. COORDINATE DIVISIONS 26 & 27 WORK WITH OTHER TRADES AS COORDINATE DIVISIONS 26 & 27 WORK WITH OTHER TRADES AS INDICATED OR REQUIRED. F. ALL WORK SHALL COMPLY WITH LATEST EDITION OF NFPA70, ALL WORK SHALL COMPLY WITH LATEST EDITION OF NFPA70, NFPA72, NFPA99, NFPA101, NEC & ALL FEDERAL, STATE & LOCAL REGULATIONS. G. ALL PENETRATIONS THROUGH FLOORS, RATED WALLS AND ALL PENETRATIONS THROUGH FLOORS, RATED WALLS AND PARTITIONS SHALL BE SEALED WITH UL APPROVED FIRE SEALANT MATERIAL TO MAINTAIN FIRE RATING FOR THE SEPARATION. H. SOME CIRCUITS AFFECTED BY THE WORK INDICATED ON THIS SHEET SOME CIRCUITS AFFECTED BY THE WORK INDICATED ON THIS SHEET MAY FEED OTHER AREAS OUTSIDE THE SCOPE OF THIS PROJECT. THE CONTRACTOR SHALL MAINTAIN CIRCUIT CONTINUITY AT ALL TIMES TO AREAS OUTSIDE THE SCOPE OF WORK. ANY POWER OUTAGES MUST BE COORDINATED IN ADVANCE WITH THE COR.

AutoCAD SHX Text

MAP-2

AutoCAD SHX Text

AutoCAD SHX Text

LS23G-18

AutoCAD SHX Text

LS23G

AutoCAD SHX Text KEY NOTES (NEW WORK) 1. NEW MASTER ALARM PANEL #2. NEW MASTER ALARM PANEL #2. PROVIDE 120V LIFE-SAFETY POWER FROM PANEL "LS23G." 20A BRANCH CIRCUIT, (2)#12 & (1)#12 G. IN 3/4" C. REFER TO PANEL SCHEDULE ON THIS SHEET. NEW ALARM PANEL TO BE INSTALLED ADJACENT TO THE EXISTING AND READY FOR FINAL CONNECTIONS PRIOR TO THE REMOVAL OF THE EXISTING PANEL. COORDINATE WORK WITH OTHER TRADES. 2. EXISTING ELECTRICAL PANEL "LS23G." REFER TO PANEL EXISTING ELECTRICAL PANEL "LS23G." REFER TO PANEL SCHEDULE ON THIS SHEET.

E-10

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

BIRMINGHAM

VA MEDICAL

CENTER

U.S. Department of Veterans Affairs

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

ELECTRICAL

3RD FLOOR: AREA F & G

MMF

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text

BID DOCUMENTS FOR CONSTRUCTION

AutoCAD SHX Text

FULLY SPRINKLERED

AutoCAD SHX Text

REPLACE/UPGRADE MEDICAL GAS SYSTEM

AutoCAD SHX Text 521-21-106

AutoCAD SHX Text 07-07-2023

AutoCAD SHX Text

700 S. 19TH STREET, BIRMINGHAM, AL. 35233

AutoCAD SHX Text

BIRMINGHAM VA MEDICAL CENTER

AutoCAD SHX Text

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text F

AutoCAD SHX Text D

AutoCAD SHX Text G

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text

DRAWING SCALE: 1/8" = 1' - 0"

AutoCAD SHX Text

KEY PLAN: 3RD FLOOR

AutoCAD SHX Text GENERAL NOTES A. KEY PLAN AREA NAMING DOES NOT CORRESPOND TO HOSPITAL KEY PLAN AREA NAMING DOES NOT CORRESPOND TO HOSPITAL AREA NAMING. B. REFER TO SHEET E-00 FOR ELECTRICAL LEGEND, GENERAL NOTES, REFER TO SHEET E-00 FOR ELECTRICAL LEGEND, GENERAL NOTES, AND ABBREVIATIONS. C. MEDICAL GAS SERVICES TO THE HOSPITAL MUST BE MAINTAINED MEDICAL GAS SERVICES TO THE HOSPITAL MUST BE MAINTAINED THROUGHOUT THE CONSTRUCTION PERIOD. D. BEFORE BEGINNING WORK, THE CONTRACTOR SHALL REFER TO THE BEFORE BEGINNING WORK, THE CONTRACTOR SHALL REFER TO THE ARCHITECTURAL DRAWINGS FOR THE PHASING PLAN. ALSO, SEE THE LIFE SAFETY AND INFECTION CONTROL (ICRA) PLANS. E. COORDINATE DIVISIONS 26 & 27 WORK WITH OTHER TRADES AS COORDINATE DIVISIONS 26 & 27 WORK WITH OTHER TRADES AS INDICATED OR REQUIRED. F. ALL WORK SHALL COMPLY WITH LATEST EDITION OF NFPA70, ALL WORK SHALL COMPLY WITH LATEST EDITION OF NFPA70, NFPA72, NFPA99, NFPA101, NEC & ALL FEDERAL, STATE & LOCAL REGULATIONS. G. ALL PENETRATIONS THROUGH FLOORS, RATED WALLS AND ALL PENETRATIONS THROUGH FLOORS, RATED WALLS AND PARTITIONS SHALL BE SEALED WITH UL APPROVED FIRE SEALANT MATERIAL TO MAINTAIN FIRE RATING FOR THE SEPARATION. H. SOME CIRCUITS AFFECTED BY THE WORK INDICATED ON THIS SHEET SOME CIRCUITS AFFECTED BY THE WORK INDICATED ON THIS SHEET MAY FEED OTHER AREAS OUTSIDE THE SCOPE OF THIS PROJECT. THE CONTRACTOR SHALL MAINTAIN CIRCUIT CONTINUITY AT ALL TIMES TO AREAS OUTSIDE THE SCOPE OF WORK. ANY POWER OUTAGES MUST BE COORDINATED IN ADVANCE WITH THE COR.

AutoCAD SHX Text

AP 3-1

AutoCAD SHX Text

AutoCAD SHX Text

LS23C-5

AutoCAD SHX Text

LS23C

AutoCAD SHX Text KEY NOTES (NEW WORK) 1. NEW AREA ALARM PANEL. NEW AREA ALARM PANEL. PROVIDE 120V LIFE-SAFETY POWER FROM PANEL "LS23C." 20A BRANCH CIRCUIT, (2)#12 & (1)#12 G. IN 3/4" C. REFER TO PANEL SCHEDULE ON THIS SHEET. NEW ALARM PANEL TO BE INSTALLED ADJACENT TO THE EXISTING AND READY FOR FINAL CONNECTIONS PRIOR TO THE REMOVAL OF THE EXISTING PANEL. COORDINATE WORK WITH OTHER TRADES. 2. EXISTING ELECTRICAL PANEL "LS23C." REFER TO PANEL EXISTING ELECTRICAL PANEL "LS23C." REFER TO PANEL SCHEDULE ON THIS SHEET.

E-11

BVG

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

BIRMINGHAM

VA MEDICAL

CENTER

U.S. Department of Veterans Affairs

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

ELECTRICAL

4TH FLOOR: AREA B - NEW WORK

MMF

AutoCAD SHX Text U

AutoCAD SHX Text Q

AutoCAD SHX Text P

AutoCAD SHX Text R

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text W

AutoCAD SHX Text N

AutoCAD SHX Text M

AutoCAD SHX Text K

AutoCAD SHX Text J

AutoCAD SHX Text I

AutoCAD SHX Text V

AutoCAD SHX Text I´

AutoCAD SHX Text H

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text H

AutoCAD SHX Text

AutoCAD SHX Text V

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text P

AutoCAD SHX Text S

AutoCAD SHX Text Q

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text M

AutoCAD SHX Text

AutoCAD SHX Text

BID DOCUMENTS FOR CONSTRUCTION

AutoCAD SHX Text

FULLY SPRINKLERED

AutoCAD SHX Text

REPLACE/UPGRADE MEDICAL GAS SYSTEM

AutoCAD SHX Text 521-21-106

AutoCAD SHX Text 07-07-2023

AutoCAD SHX Text

700 S. 19TH STREET, BIRMINGHAM, AL. 35233

AutoCAD SHX Text

BIRMINGHAM VA MEDICAL CENTER

AutoCAD SHX Text

AutoCAD SHX Text

DRAWING SCALE: 1/8" = 1' - 0"

AutoCAD SHX Text B

AutoCAD SHX Text G

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text

KEY PLAN: 4TH FLOOR

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text GENERAL NOTES A. KEY PLAN AREA NAMING DOES NOT CORRESPOND TO HOSPITAL KEY PLAN AREA NAMING DOES NOT CORRESPOND TO HOSPITAL AREA NAMING. B. REFER TO SHEET E-00 FOR ELECTRICAL LEGEND, GENERAL NOTES, REFER TO SHEET E-00 FOR ELECTRICAL LEGEND, GENERAL NOTES, AND ABBREVIATIONS. C. MEDICAL GAS SERVICES TO THE HOSPITAL MUST BE MAINTAINED MEDICAL GAS SERVICES TO THE HOSPITAL MUST BE MAINTAINED THROUGHOUT THE CONSTRUCTION PERIOD. D. BEFORE BEGINNING WORK, THE CONTRACTOR SHALL REFER TO THE BEFORE BEGINNING WORK, THE CONTRACTOR SHALL REFER TO THE ARCHITECTURAL DRAWINGS FOR THE PHASING PLAN. ALSO, SEE THE LIFE SAFETY AND INFECTION CONTROL (ICRA) PLANS. E. COORDINATE DIVISIONS 26 & 27 WORK WITH OTHER TRADES AS COORDINATE DIVISIONS 26 & 27 WORK WITH OTHER TRADES AS INDICATED OR REQUIRED. F. ALL WORK SHALL COMPLY WITH LATEST EDITION OF NFPA70, ALL WORK SHALL COMPLY WITH LATEST EDITION OF NFPA70, NFPA72, NFPA99, NFPA101, NEC & ALL FEDERAL, STATE & LOCAL REGULATIONS. G. ALL PENETRATIONS THROUGH FLOORS, RATED WALLS AND ALL PENETRATIONS THROUGH FLOORS, RATED WALLS AND PARTITIONS SHALL BE SEALED WITH UL APPROVED FIRE SEALANT MATERIAL TO MAINTAIN FIRE RATING FOR THE SEPARATION. H. SOME CIRCUITS AFFECTED BY THE WORK INDICATED ON THIS SHEET SOME CIRCUITS AFFECTED BY THE WORK INDICATED ON THIS SHEET MAY FEED OTHER AREAS OUTSIDE THE SCOPE OF THIS PROJECT. THE CONTRACTOR SHALL MAINTAIN CIRCUIT CONTINUITY AT ALL TIMES TO AREAS OUTSIDE THE SCOPE OF WORK. ANY POWER OUTAGES MUST BE COORDINATED IN ADVANCE WITH THE COR.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

LS24DA

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text KEY NOTES (NEW WORK) 1. NEW NITROGEN MANIFOLD BOX. RE-USE EXISTING 120V NEW NITROGEN MANIFOLD BOX. RE-USE EXISTING 120V BRANCH CIRCUIT CONDUCTORS. 2. NEW AREA ALARM PANEL. NEW AREA ALARM PANEL. PROVIDE 120V LIFE-SAFETY POWER FROM PANEL "LS24DA." 20A BRANCH CIRCUIT, (2)#12 & (1)#12 G. IN 3/4" C. REFER TO PANEL SCHEDULE ON THIS SHEET. 3. EXISTING ELECTRICAL PANEL "LS24DA." REFER TO PANEL EXISTING ELECTRICAL PANEL "LS24DA." REFER TO PANEL SCHEDULE ON THIS SHEET. 4. WITHIN O.R. CORRIDORS, AND LOCATIONS INDICATED ON THIS WITHIN O.R. CORRIDORS, AND LOCATIONS INDICATED ON THIS SHEET WITHIN THE OPERATING ROOMS, E.C. SHALL COORDINATE REMOVAL, REPLACEMENT OR TEMPORARY SUSPENSION OF EXISTING ELECTRICAL DEVICES IN CEILING WITH OTHER TRADES.

AutoCAD SHX Text

AP 4-8

AutoCAD SHX Text

LS24DA-7

E-12

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

BIRMINGHAM

VA MEDICAL

CENTER

U.S. Department of Veterans Affairs

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

ELECTRICAL

5TH FLOOR: AREA A

MMF

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text L

AutoCAD SHX Text L

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 21.5

AutoCAD SHX Text

BID DOCUMENTS FOR CONSTRUCTION

AutoCAD SHX Text

FULLY SPRINKLERED

AutoCAD SHX Text

REPLACE/UPGRADE MEDICAL GAS SYSTEM

AutoCAD SHX Text 521-21-106

AutoCAD SHX Text 07-07-2023

AutoCAD SHX Text

700 S. 19TH STREET, BIRMINGHAM, AL. 35233

AutoCAD SHX Text

BIRMINGHAM VA MEDICAL CENTER

AutoCAD SHX Text

AutoCAD SHX Text

DRAWING SCALE: 1/8" = 1' - 0"

AutoCAD SHX Text N

AutoCAD SHX Text

KEY PLAN: 5TH FLOOR

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text G

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text KEY NOTES (DEMOLITION) A. EXISTING ALARM PANEL TO BE REMOVED, POWER SHALL BE EXISTING ALARM PANEL TO BE REMOVED, POWER SHALL BE DISCONNECTED AND CONDUCTORS LEFT IN PLACE ABOVE CEILING FOR FUTURE USE BY VA. CONTRACTOR SHALL PERFORM CIRCUIT TRACING TO DETERMINE SOURCE PANEL AND CIRCUIT. DISCONNECT POWER FROM ALARM PANEL AND PROVIDE JUNCTION BOX WITH COVER ABOVE CEILING FOR TERMINATION OF EXISTING CONDUCTORS. LABEL JUNCTION BOX WITH SOURCE PANEL AND CIRCUIT NUMBER. COORDINATE WORK WITH OTHER TRADES.

AutoCAD SHX Text GENERAL NOTES A. KEY PLAN AREA NAMING DOES NOT CORRESPOND TO HOSPITAL KEY PLAN AREA NAMING DOES NOT CORRESPOND TO HOSPITAL AREA NAMING. B. REFER TO SHEET E-00 FOR ELECTRICAL LEGEND, GENERAL NOTES, REFER TO SHEET E-00 FOR ELECTRICAL LEGEND, GENERAL NOTES, AND ABBREVIATIONS. C. MEDICAL GAS SERVICES TO THE HOSPITAL MUST BE MAINTAINED MEDICAL GAS SERVICES TO THE HOSPITAL MUST BE MAINTAINED THROUGHOUT THE CONSTRUCTION PERIOD. D. BEFORE BEGINNING WORK, THE CONTRACTOR SHALL REFER TO THE BEFORE BEGINNING WORK, THE CONTRACTOR SHALL REFER TO THE ARCHITECTURAL DRAWINGS FOR THE PHASING PLAN. ALSO, SEE THE LIFE SAFETY AND INFECTION CONTROL (ICRA) PLANS. E. COORDINATE DIVISIONS 26 & 27 WORK WITH OTHER TRADES AS COORDINATE DIVISIONS 26 & 27 WORK WITH OTHER TRADES AS INDICATED OR REQUIRED. F. ALL WORK SHALL COMPLY WITH LATEST EDITION OF NFPA70, ALL WORK SHALL COMPLY WITH LATEST EDITION OF NFPA70, NFPA72, NFPA99, NFPA101, NEC & ALL FEDERAL, STATE & LOCAL REGULATIONS. G. ALL PENETRATIONS THROUGH FLOORS, RATED WALLS AND ALL PENETRATIONS THROUGH FLOORS, RATED WALLS AND PARTITIONS SHALL BE SEALED WITH UL APPROVED FIRE SEALANT MATERIAL TO MAINTAIN FIRE RATING FOR THE SEPARATION. H. SOME CIRCUITS AFFECTED BY THE WORK INDICATED ON THIS SHEET SOME CIRCUITS AFFECTED BY THE WORK INDICATED ON THIS SHEET MAY FEED OTHER AREAS OUTSIDE THE SCOPE OF THIS PROJECT. THE CONTRACTOR SHALL MAINTAIN CIRCUIT CONTINUITY AT ALL TIMES TO AREAS OUTSIDE THE SCOPE OF WORK. ANY POWER OUTAGES MUST BE COORDINATED IN ADVANCE WITH THE COR.

HEALTHCARE

OCCUPANCY

E-13

BVG

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

BIRMINGHAM

VA MEDICAL

CENTER

U.S. Department of Veterans Affairs

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

ELECTRICAL

6TH FLOOR: AREA A

MMF

AutoCAD SHX Text I

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text L

AutoCAD SHX Text L

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

BID DOCUMENTS FOR CONSTRUCTION

AutoCAD SHX Text

FULLY SPRINKLERED

AutoCAD SHX Text

REPLACE/UPGRADE MEDICAL GAS SYSTEM

AutoCAD SHX Text 521-21-106

AutoCAD SHX Text 07-07-2023

AutoCAD SHX Text

700 S. 19TH STREET, BIRMINGHAM, AL. 35233

AutoCAD SHX Text

BIRMINGHAM VA MEDICAL CENTER

AutoCAD SHX Text

AutoCAD SHX Text

DRAWING SCALE: 1/8" = 1' - 0"

AutoCAD SHX Text N

AutoCAD SHX Text

KEY PLAN: 6TH FLOOR

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text G

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text GENERAL NOTES A. KEY PLAN AREA NAMING DOES NOT CORRESPOND TO HOSPITAL KEY PLAN AREA NAMING DOES NOT CORRESPOND TO HOSPITAL AREA NAMING. B. REFER TO SHEET E-00 FOR ELECTRICAL LEGEND, GENERAL NOTES, REFER TO SHEET E-00 FOR ELECTRICAL LEGEND, GENERAL NOTES, AND ABBREVIATIONS. C. MEDICAL GAS SERVICES TO THE HOSPITAL MUST BE MAINTAINED MEDICAL GAS SERVICES TO THE HOSPITAL MUST BE MAINTAINED THROUGHOUT THE CONSTRUCTION PERIOD. D. BEFORE BEGINNING WORK, THE CONTRACTOR SHALL REFER TO THE BEFORE BEGINNING WORK, THE CONTRACTOR SHALL REFER TO THE ARCHITECTURAL DRAWINGS FOR THE PHASING PLAN. ALSO, SEE THE LIFE SAFETY AND INFECTION CONTROL (ICRA) PLANS. E. COORDINATE DIVISIONS 26 & 27 WORK WITH OTHER TRADES AS COORDINATE DIVISIONS 26 & 27 WORK WITH OTHER TRADES AS INDICATED OR REQUIRED. F. ALL WORK SHALL COMPLY WITH LATEST EDITION OF NFPA70, ALL WORK SHALL COMPLY WITH LATEST EDITION OF NFPA70, NFPA72, NFPA99, NFPA101, NEC & ALL FEDERAL, STATE & LOCAL REGULATIONS. G. ALL PENETRATIONS THROUGH FLOORS, RATED WALLS AND ALL PENETRATIONS THROUGH FLOORS, RATED WALLS AND PARTITIONS SHALL BE SEALED WITH UL APPROVED FIRE SEALANT MATERIAL TO MAINTAIN FIRE RATING FOR THE SEPARATION. H. SOME CIRCUITS AFFECTED BY THE WORK INDICATED ON THIS SHEET SOME CIRCUITS AFFECTED BY THE WORK INDICATED ON THIS SHEET MAY FEED OTHER AREAS OUTSIDE THE SCOPE OF THIS PROJECT. THE CONTRACTOR SHALL MAINTAIN CIRCUIT CONTINUITY AT ALL TIMES TO AREAS OUTSIDE THE SCOPE OF WORK. ANY POWER OUTAGES MUST BE COORDINATED IN ADVANCE WITH THE COR.

AutoCAD SHX Text

AP 6-3

AutoCAD SHX Text

AutoCAD SHX Text

LS26E-4

AutoCAD SHX Text

LS26E

AutoCAD SHX Text KEY NOTES (NEW WORK) 1. NEW AREA ALARM PANEL. NEW AREA ALARM PANEL. PROVIDE 120V LIFE-SAFETY POWER FROM PANEL "LS26E." 20A BRANCH CIRCUIT, (2)#12 & (1)#12 G. IN 3/4" C. REFER TO PANEL SCHEDULE ON THIS SHEET. 2. EXISTING ELECTRICAL PANEL "LS26E." REFER TO PANEL EXISTING ELECTRICAL PANEL "LS26E." REFER TO PANEL SCHEDULE ON THIS SHEET.

AutoCAD SHX Text

AutoCAD SHX Text

AP 6-4

AutoCAD SHX Text

LS26E-5

E-14

BVG

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

BIRMINGHAM

VA MEDICAL

CENTER

U.S. Department of Veterans Affairs

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

ELECTRICAL

6TH FLOOR: AREA B

MMF

AutoCAD SHX Text 16a

AutoCAD SHX Text

AutoCAD SHX Text V

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text Q

AutoCAD SHX Text L

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text N

AutoCAD SHX Text M

AutoCAD SHX Text O

AutoCAD SHX Text P

AutoCAD SHX Text

AutoCAD SHX Text

BID DOCUMENTS FOR CONSTRUCTION

AutoCAD SHX Text

FULLY SPRINKLERED

AutoCAD SHX Text

REPLACE/UPGRADE MEDICAL GAS SYSTEM

AutoCAD SHX Text 521-21-106

AutoCAD SHX Text 07-07-2023

AutoCAD SHX Text

700 S. 19TH STREET, BIRMINGHAM, AL. 35233

AutoCAD SHX Text

BIRMINGHAM VA MEDICAL CENTER

AutoCAD SHX Text

AutoCAD SHX Text

DRAWING SCALE: 1/8" = 1' - 0"

AutoCAD SHX Text N

AutoCAD SHX Text

KEY PLAN: 6TH FLOOR

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text G

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text U

AutoCAD SHX Text P

AutoCAD SHX Text O

AutoCAD SHX Text Q

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text N

AutoCAD SHX Text M

AutoCAD SHX Text V

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text V

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text Q

AutoCAD SHX Text

AutoCAD SHX Text N

AutoCAD SHX Text O

AutoCAD SHX Text P

AutoCAD SHX Text GENERAL NOTES A. KEY PLAN AREA NAMING DOES NOT CORRESPOND TO HOSPITAL KEY PLAN AREA NAMING DOES NOT CORRESPOND TO HOSPITAL AREA NAMING. B. REFER TO SHEET E-00 FOR ELECTRICAL LEGEND, GENERAL NOTES, REFER TO SHEET E-00 FOR ELECTRICAL LEGEND, GENERAL NOTES, AND ABBREVIATIONS. C. MEDICAL GAS SERVICES TO THE HOSPITAL MUST BE MAINTAINED MEDICAL GAS SERVICES TO THE HOSPITAL MUST BE MAINTAINED THROUGHOUT THE CONSTRUCTION PERIOD. D. BEFORE BEGINNING WORK, THE CONTRACTOR SHALL REFER TO THE BEFORE BEGINNING WORK, THE CONTRACTOR SHALL REFER TO THE ARCHITECTURAL DRAWINGS FOR THE PHASING PLAN. ALSO, SEE THE LIFE SAFETY AND INFECTION CONTROL (ICRA) PLANS. E. COORDINATE DIVISIONS 26 & 27 WORK WITH OTHER TRADES AS COORDINATE DIVISIONS 26 & 27 WORK WITH OTHER TRADES AS INDICATED OR REQUIRED. F. ALL WORK SHALL COMPLY WITH LATEST EDITION OF NFPA70, ALL WORK SHALL COMPLY WITH LATEST EDITION OF NFPA70, NFPA72, NFPA99, NFPA101, NEC & ALL FEDERAL, STATE & LOCAL REGULATIONS. G. ALL PENETRATIONS THROUGH FLOORS, RATED WALLS AND ALL PENETRATIONS THROUGH FLOORS, RATED WALLS AND PARTITIONS SHALL BE SEALED WITH UL APPROVED FIRE SEALANT MATERIAL TO MAINTAIN FIRE RATING FOR THE SEPARATION. H. SOME CIRCUITS AFFECTED BY THE WORK INDICATED ON THIS SHEET SOME CIRCUITS AFFECTED BY THE WORK INDICATED ON THIS SHEET MAY FEED OTHER AREAS OUTSIDE THE SCOPE OF THIS PROJECT. THE CONTRACTOR SHALL MAINTAIN CIRCUIT CONTINUITY AT ALL TIMES TO AREAS OUTSIDE THE SCOPE OF WORK. ANY POWER OUTAGES MUST BE COORDINATED IN ADVANCE WITH THE COR.

AutoCAD SHX Text

AP 6-6

AutoCAD SHX Text

AutoCAD SHX Text

LS26F-22

AutoCAD SHX Text

LS26F

AutoCAD SHX Text KEY NOTES (NEW WORK) 1. NEW AREA ALARM PANEL. NEW AREA ALARM PANEL. PROVIDE 120V LIFE-SAFETY POWER FROM PANEL "LS26F." 20A BRANCH CIRCUIT, (2)#12 & (1)#12 G. IN 3/4" C. REFER TO PANEL SCHEDULE ON THIS SHEET. NEW ALARM PANEL TO BE INSTALLED ADJACENT TO THE EXISTING AND READY FOR FINAL CONNECTIONS PRIOR TO THE REMOVAL OF THE EXISTING PANEL. COORDINATE WORK WITH OTHER TRADES. 2. EXISTING ELECTRICAL PANEL "LS26F." REFER TO PANEL EXISTING ELECTRICAL PANEL "LS26F." REFER TO PANEL SCHEDULE ON THIS SHEET.

E-15

BVG

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

BIRMINGHAM

VA MEDICAL

CENTER

U.S. Department of Veterans Affairs

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

ELECTRICAL

7TH FLOOR: AREA D&E

MMF

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text H

AutoCAD SHX Text G

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text B

AutoCAD SHX Text F

AutoCAD SHX Text F´

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text F´

AutoCAD SHX Text G

AutoCAD SHX Text H

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text

BID DOCUMENTS FOR CONSTRUCTION

AutoCAD SHX Text

FULLY SPRINKLERED

AutoCAD SHX Text

REPLACE/UPGRADE MEDICAL GAS SYSTEM

AutoCAD SHX Text 521-21-106

AutoCAD SHX Text 07-07-2023

AutoCAD SHX Text

700 S. 19TH STREET, BIRMINGHAM, AL. 35233

AutoCAD SHX Text

BIRMINGHAM VA MEDICAL CENTER

AutoCAD SHX Text

AutoCAD SHX Text

DRAWING SCALE: 1/8" = 1' - 0"

AutoCAD SHX Text N

AutoCAD SHX Text

KEY PLAN: 7TH FLOOR

AutoCAD SHX Text A

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text

MATCH LINE AREA "D" - THIS SHEET

AutoCAD SHX Text GENERAL NOTES A. KEY PLAN AREA NAMING DOES NOT CORRESPOND TO HOSPITAL KEY PLAN AREA NAMING DOES NOT CORRESPOND TO HOSPITAL AREA NAMING. B. REFER TO SHEET E-00 FOR ELECTRICAL LEGEND, GENERAL NOTES, REFER TO SHEET E-00 FOR ELECTRICAL LEGEND, GENERAL NOTES, AND ABBREVIATIONS. C. MEDICAL GAS SERVICES TO THE HOSPITAL MUST BE MAINTAINED MEDICAL GAS SERVICES TO THE HOSPITAL MUST BE MAINTAINED THROUGHOUT THE CONSTRUCTION PERIOD. D. BEFORE BEGINNING WORK, THE CONTRACTOR SHALL REFER TO THE BEFORE BEGINNING WORK, THE CONTRACTOR SHALL REFER TO THE ARCHITECTURAL DRAWINGS FOR THE PHASING PLAN. ALSO, SEE THE LIFE SAFETY AND INFECTION CONTROL (ICRA) PLANS. E. COORDINATE DIVISIONS 26 & 27 WORK WITH OTHER TRADES AS COORDINATE DIVISIONS 26 & 27 WORK WITH OTHER TRADES AS INDICATED OR REQUIRED. F. ALL WORK SHALL COMPLY WITH LATEST EDITION OF NFPA70, ALL WORK SHALL COMPLY WITH LATEST EDITION OF NFPA70, NFPA72, NFPA99, NFPA101, NEC & ALL FEDERAL, STATE & LOCAL REGULATIONS. G. ALL PENETRATIONS THROUGH FLOORS, RATED WALLS AND ALL PENETRATIONS THROUGH FLOORS, RATED WALLS AND PARTITIONS SHALL BE SEALED WITH UL APPROVED FIRE SEALANT MATERIAL TO MAINTAIN FIRE RATING FOR THE SEPARATION. H. SOME CIRCUITS AFFECTED BY THE WORK INDICATED ON THIS SHEET SOME CIRCUITS AFFECTED BY THE WORK INDICATED ON THIS SHEET MAY FEED OTHER AREAS OUTSIDE THE SCOPE OF THIS PROJECT. THE CONTRACTOR SHALL MAINTAIN CIRCUIT CONTINUITY AT ALL TIMES TO AREAS OUTSIDE THE SCOPE OF WORK. ANY POWER OUTAGES MUST BE COORDINATED IN ADVANCE WITH THE COR.

AutoCAD SHX Text KEY NOTES (NEW WORK) 1. NEW AREA ALARM PANEL. NEW AREA ALARM PANEL. PROVIDE 120V LIFE-SAFETY POWER FROM PANEL "LS27A." 20A BRANCH CIRCUIT, (2)#12 & (1)#12 G. IN 3/4" C. REFER TO PANEL SCHEDULE ON THIS SHEET. NEW ALARM PANEL TO BE INSTALLED ADJACENT TO THE EXISTING AND READY FOR FINAL CONNECTIONS PRIOR TO THE REMOVAL OF THE EXISTING PANEL. COORDINATE WORK WITH OTHER TRADES. 2. EXISTING ELECTRICAL PANEL "LS27A." REFER TO PANEL EXISTING ELECTRICAL PANEL "LS27A." REFER TO PANEL SCHEDULE ON THIS SHEET.

AutoCAD SHX Text

AutoCAD SHX Text

LS27A

AutoCAD SHX Text

AutoCAD SHX Text

LS27A-1

AP 7-1

UNDER

RENOVATION ´

E-16

BVG

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

BIRMINGHAM

VA MEDICAL

CENTER

U.S. Department of Veterans Affairs

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

ELECTRICAL

8TH FLOOR: AREA D&E

MMF

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text F´

AutoCAD SHX Text G

AutoCAD SHX Text H

AutoCAD SHX Text

AutoCAD SHX Text A

AutoCAD SHX Text

BID DOCUMENTS FOR CONSTRUCTION

AutoCAD SHX Text

FULLY SPRINKLERED

AutoCAD SHX Text

REPLACE/UPGRADE MEDICAL GAS SYSTEM

AutoCAD SHX Text 521-21-106

AutoCAD SHX Text 07-07-2023

AutoCAD SHX Text

700 S. 19TH STREET, BIRMINGHAM, AL. 35233

AutoCAD SHX Text

BIRMINGHAM VA MEDICAL CENTER

AutoCAD SHX Text

AutoCAD SHX Text

DRAWING SCALE: 1/8" = 1' - 0"

AutoCAD SHX Text N

AutoCAD SHX Text

KEY PLAN: 8TH FLOOR

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text F

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text H

AutoCAD SHX Text G

AutoCAD SHX Text B

AutoCAD SHX Text F´

AutoCAD SHX Text GENERAL NOTES A. KEY PLAN AREA NAMING DOES NOT CORRESPOND TO HOSPITAL KEY PLAN AREA NAMING DOES NOT CORRESPOND TO HOSPITAL AREA NAMING. B. REFER TO SHEET E-00 FOR ELECTRICAL LEGEND, GENERAL NOTES, REFER TO SHEET E-00 FOR ELECTRICAL LEGEND, GENERAL NOTES, AND ABBREVIATIONS. C. MEDICAL GAS SERVICES TO THE HOSPITAL MUST BE MAINTAINED MEDICAL GAS SERVICES TO THE HOSPITAL MUST BE MAINTAINED THROUGHOUT THE CONSTRUCTION PERIOD. D. BEFORE BEGINNING WORK, THE CONTRACTOR SHALL REFER TO THE BEFORE BEGINNING WORK, THE CONTRACTOR SHALL REFER TO THE ARCHITECTURAL DRAWINGS FOR THE PHASING PLAN. ALSO, SEE THE LIFE SAFETY AND INFECTION CONTROL (ICRA) PLANS. E. COORDINATE DIVISIONS 26 & 27 WORK WITH OTHER TRADES AS COORDINATE DIVISIONS 26 & 27 WORK WITH OTHER TRADES AS INDICATED OR REQUIRED. F. ALL WORK SHALL COMPLY WITH LATEST EDITION OF NFPA70, ALL WORK SHALL COMPLY WITH LATEST EDITION OF NFPA70, NFPA72, NFPA99, NFPA101, NEC & ALL FEDERAL, STATE & LOCAL REGULATIONS. G. ALL PENETRATIONS THROUGH FLOORS, RATED WALLS AND ALL PENETRATIONS THROUGH FLOORS, RATED WALLS AND PARTITIONS SHALL BE SEALED WITH UL APPROVED FIRE SEALANT MATERIAL TO MAINTAIN FIRE RATING FOR THE SEPARATION. H. SOME CIRCUITS AFFECTED BY THE WORK INDICATED ON THIS SHEET SOME CIRCUITS AFFECTED BY THE WORK INDICATED ON THIS SHEET MAY FEED OTHER AREAS OUTSIDE THE SCOPE OF THIS PROJECT. THE CONTRACTOR SHALL MAINTAIN CIRCUIT CONTINUITY AT ALL TIMES TO AREAS OUTSIDE THE SCOPE OF WORK. ANY POWER OUTAGES MUST BE COORDINATED IN ADVANCE WITH THE COR.

AutoCAD SHX Text P

AutoCAD SHX Text

AutoCAD SHX Text

LS28A-1

AutoCAD SHX Text

LS28A

AutoCAD SHX Text KEY NOTES (NEW WORK) 1. NEW AREA ALARM PANEL. NEW AREA ALARM PANEL. PROVIDE 120V LIFE-SAFETY POWER FROM PANEL "LS28A." 20A BRANCH CIRCUIT, (2)#12 & (1)#12 G. IN 3/4" C. REFER TO PANEL SCHEDULE ON THIS SHEET. NEW ALARM PANEL TO BE INSTALLED ADJACENT TO THE EXISTING AND READY FOR FINAL CONNECTIONS PRIOR TO THE REMOVAL OF THE EXISTING PANEL. COORDINATE WORK WITH OTHER TRADES. 2. EXISTING ELECTRICAL PANEL "LS28A." REFER TO PANEL EXISTING ELECTRICAL PANEL "LS28A." REFER TO PANEL SCHEDULE ON THIS SHEET.

Sheets and Views
(07) 1-B
Sheets and Views
(08) 2-A&D
Sheets and Views
(09) 3-B
Sheets and Views
(10) 3-F&G
Sheets and Views
(11) 4-B
Sheets and Views
(12) 5-A
Sheets and Views
(13) 6-A
Sheets and Views
(14) 6-B
Sheets and Views
(15) 7-D&E
Sheets and Views
(16) 8-D&E

File details come from the government source that posted it. Updated .