Attachment 8 Drawings 521-21-106_Part6.pdf

PDF 8 MB Posted

Attached to
Y1DA--521-21-106 | Medical Gas Systems
Solicitation number
36C24725R0020
Issued by

About this file

This file contains engineering drawings for medical gas, vacuum, and electrical systems at the Birmingham VA Medical Center. The drawings include detailed schedules and diagrams for area alarm panels, master alarm panels, gas control panels, medical vacuum and laboratory vacuum systems, medical air systems, and oral evacuation systems. The electrical drawings show floor plans for various areas including sub-basement, basement, and ground floor with panel schedules and circuit details.

The drawings specifically outline medical gas alarm monitoring systems, including zone valve boxes and alarm panels on different floors. Panel schedules indicate monitoring points for oxygen, nitrous oxide, nitrogen, medical air, and vacuum systems. Electrical drawings show power distribution and circuit layouts supporting the medical gas infrastructure, with detailed panel schedules showing circuit breaker configurations and load calculations. The drawings are part of project number 521-21-106 for the VA Medical Center's medical gas system replacement/upgrade and appear to be construction documents prepared by West Point Engineers LLC.

View the file

Other files

File Type Posted
36C24725R0020 0008.docx DOCX document
36C24725R0020 0007.docx DOCX document
36C24725R0020 0006.docx DOCX document
Attachment 0005B_Med Gas Annual Inspection 2024.pdf PDF
36C24725R0020 0005.docx DOCX document
Attachment 0005A_RFI Clarifications.docx DOCX document
36C24725R0020 0004.pdf PDF
Attachment 0003A_RFI Answers_36C24725R0020.docx DOCX document
36C24725R0020 0003.docx DOCX document
Attachment 0003B_Asbestos Inspection Report_36C24725R0020.pdf PDF
Attachment 0003C_Photos_36C24725R0020.zip ZIP file
36C24725R0020 0002.docx DOCX document
Attachment 0002 - PROPOSAL PREPARATION AND EVALUATION INFORMATION_Rev1 521-21-106.pdf PDF
Site Visit Attendance Sheet 521-21-106.pdf PDF
36C24725R0020_0001.pdf PDF
Attachment 8 Drawings 521-21-106_Part2.pdf PDF
Attachment 7 Specifications 521-21-106.pdf PDF
Attachment 8 Drawings 521-21-106_Part5.pdf PDF
Attachment 8 Drawings 521-21-106_Part4.pdf PDF
36C24725R0020_RFP.pdf PDF
Attachment 6 INVOICING.docx DOCX document
Attachment 8 Drawings 521-21-106_Part7.pdf PDF
Attachment 1 Experience Modification Rate Form.pdf PDF
Attachment 8 Drawings 521-21-106_Part1.pdf PDF
Attachment 3 Past Performance Questionnaire -PPQ.docx DOCX document
Attachment 8 Drawings 521-21-106_Part3.pdf PDF
Attachment 4 Itemized Cost Breakdown.xlsx XLSX spreadsheet
Attachment 5 Wage Determination AL20250087 1.3.2025.pdf PDF
Attachment 2 VAAR 852.219-75 Jan 2023 Deviation.pdf PDF
Show all 29

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PG-49

BVG JDF

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

BIRMINGHAM

VA MEDICAL

CENTER

U.S. Department of Veterans Affairs

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

PLUMBING: MEDICAL GAS

SCHEDULES

AutoCAD SHX Text

BID DOCUMENTS FOR CONSTRUCTION

AutoCAD SHX Text

FULLY SPRINKLERED

AutoCAD SHX Text

REPLACE/UPGRADE MEDICAL GAS SYSTEM

AutoCAD SHX Text 521-21-106

AutoCAD SHX Text 07-07-2023

AutoCAD SHX Text

700 S. 19TH STREET, BIRMINGHAM, AL. 35233

AutoCAD SHX Text

BIRMINGHAM VA MEDICAL CENTER

AutoCAD SHX Text

AutoCAD SHX Text

MASTER ALARM PANEL SCHEDULE

AutoCAD SHX Text

1. REFER TO PLUMBING SPECIFICATIONS REFER TO PLUMBING SPECIFICATIONS 2. DEMOLITION OF EXISTING MASTER ALARM PANELS SHALL BE CONCURRENT WITH THE INSTALLATION OF THE NEW DEMOLITION OF EXISTING MASTER ALARM PANELS SHALL BE CONCURRENT WITH THE INSTALLATION OF THE NEW MASTER ALARM PANELS. 3. PLUMBING CONTRACTOR SHALL CONSULT WITH THE GENERAL TRADES CONTRACTOR AND COR FOR ALARM PANEL PLUMBING CONTRACTOR SHALL CONSULT WITH THE GENERAL TRADES CONTRACTOR AND COR FOR ALARM PANEL SIGNAGE. GC TO PROVIDE ALL SIGNAGE. 4. MAP-1 SHALL HAVE A SINGLE BINARY INPUT TO THE BAS FOR GENERAL ALARM ONLY.MAP-1 SHALL HAVE A SINGLE BINARY INPUT TO THE BAS FOR GENERAL ALARM ONLY.

AutoCAD SHX Text

LOCATION

AutoCAD SHX Text

MEDICAL GAS MONITORED

AutoCAD SHX Text

AREA SERVED

AutoCAD SHX Text

MFGR

AutoCAD SHX Text

NOTES

AutoCAD SHX Text B103A

AutoCAD SHX Text

O-MA-MV-NO-N-WAGD

AutoCAD SHX Text

SEE PLANS

AutoCAD SHX Text

AMICO

AutoCAD SHX Text 1,2,3,4

AutoCAD SHX Text

TAG

AutoCAD SHX Text

MAP-1

AutoCAD SHX Text

TAG

AutoCAD SHX Text

FLOOR SERVED

AutoCAD SHX Text

ZONE VALVE BOX

AutoCAD SHX Text

MEDICAL GAS MONITORED

AutoCAD SHX Text

MFGR

AutoCAD SHX Text

MODEL

AutoCAD SHX Text

NOTES

AutoCAD SHX Text

AREA ALARM PANEL SCHEDULE

AutoCAD SHX Text

AP G-1

AutoCAD SHX Text

GROUND FLOOR

AutoCAD SHX Text

O-MV

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

A3AC-U-OV

AutoCAD SHX Text

AP G-2

AutoCAD SHX Text

GROUND FLOOR

AutoCAD SHX Text

O-MA-MV

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

A3AR-U-OAV

AutoCAD SHX Text

AP 1-1

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

A3AC-U-OAV

AutoCAD SHX Text

AP 1-2

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

AP 1-3

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

AP 1-5

AutoCAD SHX Text

O-NO-MV

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

AP 1-7

AutoCAD SHX Text

O-MV

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

AP 1-9

AutoCAD SHX Text

1ST FLOOR

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

EXISTING

AutoCAD SHX Text

AP 2-1

AutoCAD SHX Text O

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

A3AR-U-O

AutoCAD SHX Text

AP 2-2

AutoCAD SHX Text

O-MV

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

EXISTING

AutoCAD SHX Text

AP 2-3

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

AP 2-5

AutoCAD SHX Text

O-MV

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

AP 2-6

AutoCAD SHX Text

O-MV

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

AP 2-7

AutoCAD SHX Text

O-MV

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

AP 2-8

AutoCAD SHX Text

O-MA-MV

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

AP 2-9

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

AP 2-11

AutoCAD SHX Text

2ND FLOOR

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

A3AC-U-O

AutoCAD SHX Text

ZVB 3-1

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

ZVB 3-3

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

ZVB 3-4

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

ZVB 3-6

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

ZVB 3-7

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

ZVB 3-9

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

ZVB 3-10

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

3RD FLOOR

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

TAG

AutoCAD SHX Text

FLOOR SERVED

AutoCAD SHX Text

MEDICAL GAS MONITORED

AutoCAD SHX Text

MFGR

AutoCAD SHX Text

MODEL

AutoCAD SHX Text

NOTES

AutoCAD SHX Text

AP 4-1

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

AP 4-2

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

AP 4-3

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

AP 4-4

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

EXISTING

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

AP 5-1

AutoCAD SHX Text

5TH FLOOR

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

AP 5-2

AutoCAD SHX Text

5TH FLOOR

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

AP 5-3

AutoCAD SHX Text

5TH FLOOR

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

AP 6-1A

AutoCAD SHX Text

O-MA-MV

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

AP 6-2

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

AP 6-4

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

AP 6-5

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

AP 6-6

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

AP 6-7

AutoCAD SHX Text

6TH FLOOR

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

AP 7-1

AutoCAD SHX Text

7TH FLOOR

AutoCAD SHX Text O

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

AP 7-2

AutoCAD SHX Text

7TH FLOOR

AutoCAD SHX Text

O-MV

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

AP 8-1

AutoCAD SHX Text

8TH FLOOR

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

4TH FLOOR

AutoCAD SHX Text

4TH FLOOR

AutoCAD SHX Text

4TH FLOOR

AutoCAD SHX Text

4TH FLOOR

AutoCAD SHX Text

4TH FLOOR

AutoCAD SHX Text

3RD FLOOR

AutoCAD SHX Text

3RD FLOOR

AutoCAD SHX Text

3RD FLOOR

AutoCAD SHX Text

3RD FLOOR

AutoCAD SHX Text

3RD FLOOR

AutoCAD SHX Text

3RD FLOOR

AutoCAD SHX Text

3RD FLOOR

AutoCAD SHX Text

3RD FLOOR

AutoCAD SHX Text

3RD FLOOR

AutoCAD SHX Text

3RD FLOOR

AutoCAD SHX Text

2ND FLOOR

AutoCAD SHX Text

2ND FLOOR

AutoCAD SHX Text

2ND FLOOR

AutoCAD SHX Text

2ND FLOOR

AutoCAD SHX Text

2ND FLOOR

AutoCAD SHX Text

2ND FLOOR

AutoCAD SHX Text

2ND FLOOR

AutoCAD SHX Text

2ND FLOOR

AutoCAD SHX Text

1ST FLOOR

AutoCAD SHX Text

1ST FLOOR

AutoCAD SHX Text

1ST FLOOR

AutoCAD SHX Text

1ST FLOOR

AutoCAD SHX Text

1ST FLOOR

AutoCAD SHX Text

O-MA-MV

AutoCAD SHX Text

O-MA-MV

AutoCAD SHX Text

O-MA-MV

AutoCAD SHX Text

O-MA-MV

AutoCAD SHX Text

MV-O

AutoCAD SHX Text

O-MV

AutoCAD SHX Text O

AutoCAD SHX Text

MV

AutoCAD SHX Text

O-MA-MV

AutoCAD SHX Text

O-MA-MV

AutoCAD SHX Text

O-MA-MV

AutoCAD SHX Text

O-MA-MV

AutoCAD SHX Text

O-MA-MV

AutoCAD SHX Text

O-MA-MV

AutoCAD SHX Text

O-MA-MV

AutoCAD SHX Text

O-MA-MV

AutoCAD SHX Text

O-MA-MV

AutoCAD SHX Text

O-MA-MV

AutoCAD SHX Text

O-MA-MV

AutoCAD SHX Text

O-MA-MV

AutoCAD SHX Text

O-MA-MV-NO-N

AutoCAD SHX Text

O-MA-NO-MV

AutoCAD SHX Text

AP 8-2

AutoCAD SHX Text

8TH FLOOR

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

6TH FLOOR

AutoCAD SHX Text

6TH FLOOR

AutoCAD SHX Text

6TH FLOOR

AutoCAD SHX Text

6TH FLOOR

AutoCAD SHX Text

6TH FLOOR

AutoCAD SHX Text

O-MA-MV

AutoCAD SHX Text

O-MA-MV

AutoCAD SHX Text

O-MA-MV

AutoCAD SHX Text

O-MA-MV

AutoCAD SHX Text

O-MA-MV

AutoCAD SHX Text

O-MA-MV

AutoCAD SHX Text

O-MA-MV

AutoCAD SHX Text

O-MA-MV

AutoCAD SHX Text O

AutoCAD SHX Text

O-MA-MV

AutoCAD SHX Text NOTES: PLUMBING CONTRACTOR SHALL CONSULT WITH THE GENERAL TRADES CONTRACTOR AND COR FOR ALARM PANEL SIGNAGE. GC TO PROVIDE ALL SIGNAGE. 1. REFER TO DIVISION 22 SPECIFICATIONS REFER TO DIVISION 22 SPECIFICATIONS 2. MODEL AND MANUFACTURER ARE BASIS OF DESIGN MODEL AND MANUFACTURER ARE BASIS OF DESIGN 3. CONTRACTOR TO VERIFY AND CONSULT WITH MANUFACTURE BEFORE PURCHASING CONTRACTOR TO VERIFY AND CONSULT WITH MANUFACTURE BEFORE PURCHASING 4. INSTALL ROUGH IN BOX FOR REMOTE SENSORS ABOVE CEILING. INSTALL ROUGH IN BOX FOR REMOTE SENSORS ABOVE CEILING. 5. ALARM PANEL MONITORS ALL OF THE OPERATING ROOM ZONE VALVE BOXES.ALARM PANEL MONITORS ALL OF THE OPERATING ROOM ZONE VALVE BOXES.

AutoCAD SHX Text

AREA ALARM PANEL SCHEDULE

AutoCAD SHX Text

ZVB G-1

AutoCAD SHX Text

ZVB G-2

AutoCAD SHX Text

ZVB 1-1

AutoCAD SHX Text

ZVB 1-2

AutoCAD SHX Text

ZVB 1-3, 1-4

AutoCAD SHX Text

ZVB 1-5, 1-6

AutoCAD SHX Text

ZVB 1-9

AutoCAD SHX Text

A3AC-U-OAV

AutoCAD SHX Text

A3AC-U-OAV

AutoCAD SHX Text

A3AC-U-OV

AutoCAD SHX Text

ZVB 2-2

AutoCAD SHX Text

ZVB 2-3

AutoCAD SHX Text

ZVB 2-5

AutoCAD SHX Text

ZVB 2-6

AutoCAD SHX Text

ZVB 2-8

AutoCAD SHX Text

ZVB 2-9

AutoCAD SHX Text

ZVB 2-11

AutoCAD SHX Text

A3AC-U-OV

AutoCAD SHX Text

A3AC-U-OV

AutoCAD SHX Text

A3AC-U-OV

AutoCAD SHX Text

A3AC-U-OV

AutoCAD SHX Text

A3AC-U-OAV

AutoCAD SHX Text

A3AC-U-OV

AutoCAD SHX Text

A3AR-U-V

AutoCAD SHX Text

AP 3-1

AutoCAD SHX Text

AP 3-2

AutoCAD SHX Text

AP 3-3

AutoCAD SHX Text

AP 3-4

AutoCAD SHX Text

AP 3-5

AutoCAD SHX Text

AP 3-6

AutoCAD SHX Text

AP 3-7

AutoCAD SHX Text

AP 3-8

AutoCAD SHX Text

AP 3-9

AutoCAD SHX Text

AP 3-10

AutoCAD SHX Text

AP 3-11

AutoCAD SHX Text

A3AC-U-OAV

AutoCAD SHX Text

A3AC-U-OAV

AutoCAD SHX Text

A3AC-U-OAV

AutoCAD SHX Text

A3AC-U-OAV

AutoCAD SHX Text

A3AC-U-OAV

AutoCAD SHX Text

A3AC-U-OAV

AutoCAD SHX Text

A3AC-U-OAV

AutoCAD SHX Text

A3AC-U-OAV

AutoCAD SHX Text

A3AC-U-OAV

AutoCAD SHX Text

EXISTING

AutoCAD SHX Text

ZONE VALVE BOX

AutoCAD SHX Text

ZVB 4-1

AutoCAD SHX Text

ZVB 4-2

AutoCAD SHX Text

ZVB 4-3

AutoCAD SHX Text

OPERATING ROOMS

AutoCAD SHX Text

ZVB 4-8

AutoCAD SHX Text

AP 4-8

AutoCAD SHX Text

O-MA-MV

AutoCAD SHX Text

A3AR-U-OAV2

AutoCAD SHX Text

AP 6-3

AutoCAD SHX Text

AMICO

AutoCAD SHX Text

6TH FLOOR

AutoCAD SHX Text

O-MA-MV

AutoCAD SHX Text

ZVB 5-1

AutoCAD SHX Text

ZVB 5-2

AutoCAD SHX Text

ZVB 5-3

AutoCAD SHX Text

ZVB 6-1A, 6-1B

AutoCAD SHX Text

ZVB 6-2

AutoCAD SHX Text

ZVB 6-4

AutoCAD SHX Text

ZVB 6-5

AutoCAD SHX Text

ZVB 6-6

AutoCAD SHX Text

ZVB 6-7

AutoCAD SHX Text

ZVB 7-1

AutoCAD SHX Text

ZVB 7-2

AutoCAD SHX Text

ZVB 8-1

AutoCAD SHX Text

ZVB 8-2

AutoCAD SHX Text

ZVB 6-3

AutoCAD SHX Text

A3AR-U-OAV

AutoCAD SHX Text

A3AC-U-OAV

AutoCAD SHX Text

A3AC-U-OAV

AutoCAD SHX Text

A3AR-U-OAV

AutoCAD SHX Text

A3AC-U-OAV

AutoCAD SHX Text

A3AR-U-O

AutoCAD SHX Text

A3AR-U-OAV

AutoCAD SHX Text

A3AC-U-OAV

AutoCAD SHX Text

A3AC-U-OAV

AutoCAD SHX Text

A3AR-U-O

AutoCAD SHX Text

EXISTING

AutoCAD SHX Text

A3AR-U-OAV

AutoCAD SHX Text

A3AR-U-OAV

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text

AutoCAD SHX Text 1,2,3,4

AutoCAD SHX Text

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text

A3AC-U-OAV

AutoCAD SHX Text

A3AC-U-OAV

AutoCAD SHX Text

A3AC-U-OAV

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text

AutoCAD SHX Text

SEE PLANS

AutoCAD SHX Text

AMICO

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text

MAP-2

AutoCAD SHX Text

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text 1,2,3,4

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text

A3AC-U-OAV

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text

O-MA-MV-NO-N-WAGD

AutoCAD SHX Text

A3AC-U-OAV

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text

ZVB 1-7

AutoCAD SHX Text

ZVB 2-1

AutoCAD SHX Text

ZVB 2-7

AutoCAD SHX Text

ZVB 3-2

AutoCAD SHX Text

ZVB 3-5

AutoCAD SHX Text

ZVB 3-8

AutoCAD SHX Text

ZVB 3-11

AutoCAD SHX Text NOTES: PLUMBING CONTRACTOR SHALL CONSULT WITH THE GENERAL TRADES CONTRACTOR AND COR FOR ALARM PANEL SIGNAGE. GC TO PROVIDE ALL SIGNAGE. 1. REFER TO DIVISION 22 SPECIFICATIONS REFER TO DIVISION 22 SPECIFICATIONS 2. MODEL AND MANUFACTURER ARE BASIS OF DESIGN MODEL AND MANUFACTURER ARE BASIS OF DESIGN 3. CONTRACTOR TO VERIFY AND CONSULT WITH MANUFACTURE BEFORE PURCHASING CONTRACTOR TO VERIFY AND CONSULT WITH MANUFACTURE BEFORE PURCHASING 4. INSTALL ROUGH IN BOX FOR REMOTE SENSORS ABOVE CEILING. INSTALL ROUGH IN BOX FOR REMOTE SENSORS ABOVE CEILING. 5. ALARM PANEL MONITORS ALL OF THE OPERATING ROOM ZONE VALVE BOXES.ALARM PANEL MONITORS ALL OF THE OPERATING ROOM ZONE VALVE BOXES.

AutoCAD SHX Text

MODEL

AutoCAD SHX Text

ALERT-4 LCD ETHERNET MASTER ALARM

AutoCAD SHX Text

ALERT-4 LCD ETHERNET MASTER ALARM

PG-50

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

BIRMINGHAM

VA MEDICAL

CENTER

U.S. Department of Veterans Affairs

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

PLUMBING: MEDICAL GAS

SCHEDULES

AutoCAD SHX Text

BID DOCUMENTS FOR CONSTRUCTION

AutoCAD SHX Text

FULLY SPRINKLERED

AutoCAD SHX Text

REPLACE/UPGRADE MEDICAL GAS SYSTEM

AutoCAD SHX Text 521-21-106

AutoCAD SHX Text 07-07-2023

AutoCAD SHX Text

700 S. 19TH STREET, BIRMINGHAM, AL. 35233

AutoCAD SHX Text

BIRMINGHAM VA MEDICAL CENTER

AutoCAD SHX Text

AutoCAD SHX Text

TAG

AutoCAD SHX Text

LOCATION

AutoCAD SHX Text

TANK CAPACITY

AutoCAD SHX Text CAPACITY (SCFM) @19" Hg

AutoCAD SHX Text

VACUUM PUMP DATA

AutoCAD SHX Text

WEIGHT

AutoCAD SHX Text

SUCTION CONNECTION

AutoCAD SHX Text

GALLONS

AutoCAD SHX Text

LBS.

AutoCAD SHX Text

MVP-1

AutoCAD SHX Text

1. NFPA 99 AND NEC COMPLIANT NFPA 99 AND NEC COMPLIANT 2. ALL CAPACITIES ARE PER NFPA 99, WITH ONE VACUUM PUMP IN RESERVE ALL CAPACITIES ARE PER NFPA 99, WITH ONE VACUUM PUMP IN RESERVE 3. ALLOW 36" CLEARANCE IN FRONT OF CONTROL PANEL AND 24" FOR ALL OTHER SIDES. ALLOW 36" CLEARANCE IN FRONT OF CONTROL PANEL AND 24" FOR ALL OTHER SIDES. 4. CONTINUOUS DUTY, OIL-LESS, FRICTIONLESS COMPRESSION CLAW TYPE VACUUM PUMPS. CONTINUOUS DUTY, OIL-LESS, FRICTIONLESS COMPRESSION CLAW TYPE VACUUM PUMPS. 5. BACTERIA INTAKE FILTER WITH FLASK. BACTERIA INTAKE FILTER WITH FLASK. 6. EXHAUST MUFFLER EXHAUST MUFFLER 7. INLET CHECK VALVE, INLET ISOLATION VALVE, SAFETY RELIEF VALVE, VACUUM SWITCH, HIGH DISCHARGE TEMPERATURE SWITCH. INLET CHECK VALVE, INLET ISOLATION VALVE, SAFETY RELIEF VALVE, VACUUM SWITCH, HIGH DISCHARGE TEMPERATURE SWITCH. 8. FLEXIBLE CONNECTORS FLEXIBLE CONNECTORS 9. SHUT-OFF COCK FOR GAUGE AND VACUUM SWITCHES. SHUT-OFF COCK FOR GAUGE AND VACUUM SWITCHES. 10. VACUUM RECEIVER OF AMSE CONSTRUCTION RATED FOR 200PSI MWP. VACUUM RECEIVER OF AMSE CONSTRUCTION RATED FOR 200PSI MWP. 11. VACUUM RECEIVER WITH RUST PROTECTION RECEIVER LINING VACUUM RECEIVER WITH RUST PROTECTION RECEIVER LINING 12. RECEIVER GAUGE GLASS RECEIVER GAUGE GLASS 13. RECEIVER TANK TO BE EQUIPPED WITH VACUUM GAUGE, VALVED BY-PASS AND MANUAL TANK DRAIN. RECEIVER TANK TO BE EQUIPPED WITH VACUUM GAUGE, VALVED BY-PASS AND MANUAL TANK DRAIN. 14. LEVEL 2 CONTROL PANEL WITH TOUCH SCREEN HMI LEVEL 2 CONTROL PANEL WITH TOUCH SCREEN HMI 15. VARIABLE FREQUENCY DRIVE FOR SOFT START ONLY (NOT FOR PUMP MODULATION) VARIABLE FREQUENCY DRIVE FOR SOFT START ONLY (NOT FOR PUMP MODULATION) 16. ETHERNET CONNECTIVITY CAPABILITYETHERNET CONNECTIVITY CAPABILITY

AutoCAD SHX Text

SUB-BASEMENT MECHANICAL ROOM

AutoCAD SHX Text

MEDICAL VACUUM AND LABORATORY VACUUM SYSTEM SCHEDULE

AutoCAD SHX Text 4"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

PUMP

AutoCAD SHX Text

AutoCAD SHX Text

SYSTEM

AutoCAD SHX Text

EXHAUST CONNECTION (EACH)

AutoCAD SHX Text 2"

AutoCAD SHX Text

EMSE CORPORATION

AutoCAD SHX Text

1TCB10S200

AutoCAD SHX Text

SYSTEM TYPE

AutoCAD SHX Text

MEDICAL VACUUM

AutoCAD SHX Text

LVP-1

AutoCAD SHX Text

SUB-BASEMENT MECHANICAL ROOM

AutoCAD SHX Text 1 1/4"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 1"

AutoCAD SHX Text

EMSE CORPORATION

AutoCAD SHX Text

1DCB2S120

AutoCAD SHX Text

LABORATORY VACUUM

AutoCAD SHX Text

QUANTITY

AutoCAD SHX Text

HP

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

MANUFACTURER

AutoCAD SHX Text

MODEL

AutoCAD SHX Text

VOLTS/ PHASE

AutoCAD SHX Text 460/3

AutoCAD SHX Text 460/3

AutoCAD SHX Text

SYSTEM FLA

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

TAG

AutoCAD SHX Text

LOCATION

AutoCAD SHX Text

TANK CAPACITY

AutoCAD SHX Text

SYSTEM CAPACITY (SCFM)

AutoCAD SHX Text

COMPRESSOR DATA

AutoCAD SHX Text

WEIGHT

AutoCAD SHX Text

DISCHARGE CONNECTION

AutoCAD SHX Text

ACCESSORIES /NOTES

AutoCAD SHX Text

GALLONS

AutoCAD SHX Text

LBS.

AutoCAD SHX Text

MAC-1

AutoCAD SHX Text

1. NFPA 99 AND NEC COMPLIANT NFPA 99 AND NEC COMPLIANT 2. ALL CAPACITIES ARE PER NFPA 99, WITH RESERVE COMPRESSOR ON STAND-BY ALL CAPACITIES ARE PER NFPA 99, WITH RESERVE COMPRESSOR ON STAND-BY 3. ALLOW 36" CLEARANCE IN FRONT OF CONTROL PANEL AND 24" FOR ALL OTHER SIDES. ALLOW 36" CLEARANCE IN FRONT OF CONTROL PANEL AND 24" FOR ALL OTHER SIDES. 4. ROTARY OIL-LESS, AIR COOLED, V-BELT DRIVEN COMPRESSORS WITH SLIDE BASES FOR BELT TENSION ADJUSTMENT AND TOTALLY ENCLOSED OSHA APPROVED BELT GUARDS ROTARY OIL-LESS, AIR COOLED, V-BELT DRIVEN COMPRESSORS WITH SLIDE BASES FOR BELT TENSION ADJUSTMENT AND TOTALLY ENCLOSED OSHA APPROVED BELT GUARDS 5. GALVANIZED RECEIVER OF ASME CONSTRUCTION RATED FOR 200 PSI MVP GALVANIZED RECEIVER OF ASME CONSTRUCTION RATED FOR 200 PSI MVP 6. RECEIVER TO HAVE PRESSURE GAUGE, SAFETY RELIEF VALVE, 3-WAY BY-PASS, GAUGE GLASS AND AUTOMATIC ELECTRONIC DRAIN WITH MANUAL OVERIDE RECEIVER TO HAVE PRESSURE GAUGE, SAFETY RELIEF VALVE, 3-WAY BY-PASS, GAUGE GLASS AND AUTOMATIC ELECTRONIC DRAIN WITH MANUAL OVERIDE 7. PARALLEL PIPED, DESICCANT DRYER ASSEMBLIES WITH BY-PASS TO EITHER BANK. EACH BANK SIZED FOR 100% SYSTEM CAPACITY PARALLEL PIPED, DESICCANT DRYER ASSEMBLIES WITH BY-PASS TO EITHER BANK. EACH BANK SIZED FOR 100% SYSTEM CAPACITY 8. EACH DRYER TO HAVE 0.5 MICRON PRE-FILTER WITH ELECTRONIC DRAIN AND ELEMENT CHANGE INDICATOR, 0.5 MICRON AFTER-FILTER WITH ELEMENT CHANGE INDICATOR AND PRESSURE REGULATOR EACH DRYER TO HAVE 0.5 MICRON PRE-FILTER WITH ELECTRONIC DRAIN AND ELEMENT CHANGE INDICATOR, 0.5 MICRON AFTER-FILTER WITH ELEMENT CHANGE INDICATOR AND PRESSURE REGULATOR 9. DIGITAL DEW POINT AND CO MONITORS WITH ALARM DIGITAL DEW POINT AND CO MONITORS WITH ALARM 10. FLEXIBLE CONNECTORS. FLEXIBLE CONNECTORS. 11. LEVEL 2 CONTROL PANEL WITH TOUCH SCREEN HMI LEVEL 2 CONTROL PANEL WITH TOUCH SCREEN HMI 12. VARIABLE FREQUENCY DRIVE FOR SOFT START ONLY (NOT FOR PUMP MODULATION) VARIABLE FREQUENCY DRIVE FOR SOFT START ONLY (NOT FOR PUMP MODULATION) 13. ETHERNET CONNECTIVITY CAPABILITYETHERNET CONNECTIVITY CAPABILITY

AutoCAD SHX Text

SUB-BASEMENT MECHANICAL ROOM

AutoCAD SHX Text

MEDICAL AIR AND LABORATORY AIR SYSTEM SCHEDULE

AutoCAD SHX Text 1"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 69.6

AutoCAD SHX Text

AutoCAD SHX Text 1 - 13

AutoCAD SHX Text

50 PSIG

AutoCAD SHX Text 64.0

AutoCAD SHX Text

120 PSIG

AutoCAD SHX Text

INTAKE CONNECTION

AutoCAD SHX Text 1"

AutoCAD SHX Text

EMSE CORPORATION

AutoCAD SHX Text

3DOHS20S120D

AutoCAD SHX Text

SYSTEM TYPE

AutoCAD SHX Text

MEDICAL AIR

AutoCAD SHX Text

LAC-1

AutoCAD SHX Text

SUB-BASEMENT MECHANICAL ROOM

AutoCAD SHX Text 3/4"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 25.2

AutoCAD SHX Text

AutoCAD SHX Text 24.0

AutoCAD SHX Text 1 1/2"

AutoCAD SHX Text

EMSE CORPORATION

AutoCAD SHX Text

3DOHS7.5S120D

AutoCAD SHX Text

LABORATORY AIR

AutoCAD SHX Text

QUANTITY

AutoCAD SHX Text

HP

AutoCAD SHX Text

AutoCAD SHX Text 7.5

AutoCAD SHX Text

MANUFACTURER

AutoCAD SHX Text

MODEL

AutoCAD SHX Text

VOLTS/ PHASE

AutoCAD SHX Text 460/3

AutoCAD SHX Text 460/3

AutoCAD SHX Text

SYSTEM FLA

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 1 - 13

AutoCAD SHX Text

ACCESSORIES /NOTES

AutoCAD SHX Text 1 - 16

AutoCAD SHX Text 1 - 16

AutoCAD SHX Text

TAG

AutoCAD SHX Text

LOCATION

AutoCAD SHX Text

TANK CAPACITY

AutoCAD SHX Text CAPACITY (CFM) @8" Hg

AutoCAD SHX Text

VACUUM PUMP DATA

AutoCAD SHX Text

WEIGHT

AutoCAD SHX Text

SUCTION CONNECTION

AutoCAD SHX Text

GALLONS

AutoCAD SHX Text

LBS.

AutoCAD SHX Text

OEP-1

AutoCAD SHX Text

1. THE COMPLETE PACKAGE INCLUDES FOUR REGENERATIVE TYPE VACUUM PUMPS, ONE STAINLESS STEEL SEPARATOR TANK, TWO AMALGAM SEPARATORS AND ONE REMOTE CONTROL PANEL. THE COMPLETE PACKAGE INCLUDES FOUR REGENERATIVE TYPE VACUUM PUMPS, ONE STAINLESS STEEL SEPARATOR TANK, TWO AMALGAM SEPARATORS AND ONE REMOTE CONTROL PANEL. 2. ALL INTERCONNECTING PIPING AND WIRING SHALL BE FIELD SUPPLIED AND INSTALLED. ALL INTERCONNECTING PIPING AND WIRING SHALL BE FIELD SUPPLIED AND INSTALLED. 3. SYSTEM SHALL INCLUDE TWO 30 GALLON, STAINLESS STEEL, FLOAT PROTECTED, CORROSION RESISTANT SEPARATOR WHICH SHALL PREVENT LIQUIDS AND SOLIDS FROM REACHING THE PUMPS. SYSTEM SHALL INCLUDE TWO 30 GALLON, STAINLESS STEEL, FLOAT PROTECTED, CORROSION RESISTANT SEPARATOR WHICH SHALL PREVENT LIQUIDS AND SOLIDS FROM REACHING THE PUMPS. 4. NFPA 99 COMPLIANT NFPA 99 COMPLIANT 5. ALLOW 36" CLEARANCE IN FRONT OF CONTROL PANEL AND 24" FOR ALL OTHER SIDES. ALLOW 36" CLEARANCE IN FRONT OF CONTROL PANEL AND 24" FOR ALL OTHER SIDES. 6. VACUUM PUMPS ARE REGENERATIVE TYPE AIR-COOLED DESIGN. VACUUM PUMPS ARE REGENERATIVE TYPE AIR-COOLED DESIGN. 7. EXHAUST MUFFLER EXHAUST MUFFLER 8. INLET CHECK VALVE INLET CHECK VALVE 9. FLEXIBLE CONNECTORS FLEXIBLE CONNECTORS 10. RECEIVER TANK TO BE EQUIPPED WITH VACUUM GAUGE, VALVED BY-PASS AND MANUAL TANK DRAIN. RECEIVER TANK TO BE EQUIPPED WITH VACUUM GAUGE, VALVED BY-PASS AND MANUAL TANK DRAIN. 11. VARIABLE FREQUENCY DRIVEVARIABLE FREQUENCY DRIVE

AutoCAD SHX Text

SUB-BASEMENT MECHANICAL ROOM

AutoCAD SHX Text

ORAL EVACUATION SYSTEM SCHEDULE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

PUMP

AutoCAD SHX Text

AutoCAD SHX Text

SYSTEM

AutoCAD SHX Text

EXHAUST CONNECTION (EACH)

AutoCAD SHX Text

AutoCAD SHX Text

TECH WEST

AutoCAD SHX Text

ECO DRY-VAC VPD10D2

AutoCAD SHX Text

SYSTEM TYPE

AutoCAD SHX Text

ORAL EVACUATION

AutoCAD SHX Text

OEP-2

AutoCAD SHX Text

SUB-BASEMENT MECHANICAL ROOM

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

ORAL EVACUATION

AutoCAD SHX Text

QUANTITY

AutoCAD SHX Text

HP

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

MANUFACTURER

AutoCAD SHX Text

MODEL

AutoCAD SHX Text

VOLTS/ PHASE

AutoCAD SHX Text 208/3

AutoCAD SHX Text 208/3

AutoCAD SHX Text

PUMP AMPS

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

ACCESSORIES /NOTES

AutoCAD SHX Text 1 - 11

AutoCAD SHX Text 1 - 11

AutoCAD SHX Text

ECO DRY-VAC VPD10D2

TECH WEST

PG-51

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

BIRMINGHAM

VA MEDICAL

CENTER

U.S. Department of Veterans Affairs

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

PLUMBING: MEDICAL GAS

ALARM PANEL DIAGRAM

AutoCAD SHX Text

BID DOCUMENTS FOR CONSTRUCTION

AutoCAD SHX Text

FULLY SPRINKLERED

AutoCAD SHX Text

REPLACE/UPGRADE MEDICAL GAS SYSTEM

AutoCAD SHX Text 521-21-106

AutoCAD SHX Text 07-07-2023

AutoCAD SHX Text

700 S. 19TH STREET, BIRMINGHAM, AL. 35233

AutoCAD SHX Text

BIRMINGHAM VA MEDICAL CENTER

AutoCAD SHX Text

AutoCAD SHX Text

120V EM POWER

AutoCAD SHX Text

120V EM POWER

AutoCAD SHX Text

SUBBASEMENT

AutoCAD SHX Text

4TH FLOOR SURGICAL STORAGE 4419

AutoCAD SHX Text

120V EM POWER

AutoCAD SHX Text

120V EM POWER

AutoCAD SHX Text

120V EM POWER

AutoCAD SHX Text SERVICE INDICATOR LIGHTS OXYGEN LINE PRESSURE LOW OXYGEN PRIMARY LIQUID LEVEL LOW OXYGEN LINE PRESSURE HIGH OXYGEN SECONDARY LIQUID LEVEL LOW OXYGEN SECONDARY LIQUID LOW HEAD PRESSURE OXYGEN SECONDARY LIQUID SUPPLY IN USE NITROUS OXIDE RESERVE CYLINDERS IN USE NITROUS OXIDE LINE PRESSURE HIGH NITROUS OXIDE LINE PRESSURE LOW NITROGEN RESERVE CYLINDERS IN USE NITROGEN LINE PRESSURE LOW NITROGEN LINE PRESSURE HIGH MEDICAL AIR HIGH DEW POINT MEDICAL AIR LINE PRESSURE HIGH MEDICAL AIR LINE PRESSURE LOW MEDICAL AIR LAG COMPRESSOR IN USE MEDICAL AIR COMPRESSOR HIGH TEMP. SHUTDOWN MEDICAL AIR CARBON MONOXIDE LEVEL HIGH MEDICAL AIR LOCAL ALARM LAB AIR HIGH DEW POINT LAB AIR LINE PRESSURE HIGH LAB AIR LINE PRESSURE LOW LAB AIR LAG COMPRESSOR IN USE LAB AIR COMPRESSOR HIGH TEMP. SHUTDOWN LAB AIR CARBON MONOXIDE LEVEL HIGH LAB AIR LOCAL ALARM MEDICAL VACUUM PUMPS MAINTENANCE REQUIRED MEDICAL VACUUM LOW BLANK LAB VACUUM PUMPS MAINTENANCE REQUIRED LAB VACUUM LOW BLANK

AutoCAD SHX Text

NITROUS OXIDE RESERVE CYLINDERS IN USE

AutoCAD SHX Text

NITROUS OXIDE LINE PRESSURE HIGH

AutoCAD SHX Text

NITROUS OXIDE LINE PRESSURE LOW

AutoCAD SHX Text

NITROGEN RESERVE CYLINDERS IN USE

AutoCAD SHX Text

NITROGEN LINE PRESSURE HIGH

AutoCAD SHX Text

NITROGEN LINE PRESSURE LOW

AutoCAD SHX Text

MEDICAL AIR HIGH DEW POINT

AutoCAD SHX Text

MEDICAL AIR LINE PRESSURE HIGH

AutoCAD SHX Text

MEDICAL AIR LINE PRESSURE LOW

AutoCAD SHX Text

MEDICAL AIR LAG COMPRESSOR IN USE

AutoCAD SHX Text

MEDICAL AIR COMPRESSOR HIGH TEMP. SHUTDOWN

AutoCAD SHX Text

MEDICAL AIR CARBON MONOXIDE LEVEL HIGH

AutoCAD SHX Text

MEDICAL AIR LOCAL ALARM

AutoCAD SHX Text

LAB AIR HIGH DEW POINT

AutoCAD SHX Text

LAB AIR LINE PRESSURE HIGH

AutoCAD SHX Text

LAB AIR LINE PRESSURE LOW

AutoCAD SHX Text

LAB AIR LAG COMPRESSOR IN USE

AutoCAD SHX Text

LAB AIR COMPRESSOR HIGH TEMP. SHUTDOWN

AutoCAD SHX Text

LAB AIR CARBON MONOXIDE LEVEL HIGH

AutoCAD SHX Text

LAB AIR LOCAL ALARM

AutoCAD SHX Text

MEDICAL VACUUM PUMPS MAINTENANCE REQUIRED

AutoCAD SHX Text

MEDICAL VACUUM LOW

AutoCAD SHX Text

WAGD MAIN LINE VACUUM LOW

AutoCAD SHX Text

LAB VACUUM PUMPS MAINTENANCE REQUIRED

AutoCAD SHX Text

LAB VACUUM LOW

AutoCAD SHX Text

WAGD MAIN LINE VACUUM LOW

AutoCAD SHX Text

OXYGEN LINE PRESSURE LOW

AutoCAD SHX Text

OXYGEN PRIMARY LIQUID LEVEL LOW

AutoCAD SHX Text

OXYGEN LINE PRESSURE HIGH

AutoCAD SHX Text

OXYGEN SECONDARY LIQUID LEVEL LOW

AutoCAD SHX Text

OXYGEN SECONDARY LIQUID LOW HEAD PRESSURE

AutoCAD SHX Text

OXYGEN SECONDARY LIQUID SUPPLY IN USE

AutoCAD SHX Text

120V EM POWER

AutoCAD SHX Text

120V EM POWER

AutoCAD SHX Text

NITROGEN N2

AutoCAD SHX Text

MEDICAL AIR COMPRESSOR

AutoCAD SHX Text

NITROUS OXIDE N2O

AutoCAD SHX Text

LAB AIR

AutoCAD SHX Text

MEDICAL VACUUM

AutoCAD SHX Text

FUTURE

AutoCAD SHX Text

LAB VACUUM

AutoCAD SHX Text

FUTURE

AutoCAD SHX Text

MASTER ALARM PANEL MAP-1 LOCATED IN ENGINEERING OFFICE B103

AutoCAD SHX Text

MASTER ALARM PANEL MAP-2 LOCATED IN SWITCHBOARD OPERATOR RM 3313

AutoCAD SHX Text

OXYGEN PAD

AutoCAD SHX Text

BASEMENT LEVEL

AutoCAD SHX Text

INLINE PRESSURE SENSORS

AutoCAD SHX Text

OXYGEN TANKS

AutoCAD SHX Text

TWISTED SHIELDED PAIR BINARY INPUT TO BAS

AutoCAD SHX Text

TWISTED SHIELDED PAIR WIRING

AutoCAD SHX Text

BUILDING AUTOMATION SYSTEM

AutoCAD SHX Text

TWISTED SHIELDED PAIR WIRING

AutoCAD SHX Text

ETHERNET CABLE

AutoCAD SHX Text

VAMC COMPUTER

AutoCAD SHX Text

(GENERAL ALARM ONLY)

AutoCAD SHX Text

FACILITY'S NETWORK

AutoCAD SHX Text

ALARM PANEL SCHEDULE

AutoCAD SHX Text

FOR CENTRAL MODULE MASTER ALARM PANELS

BY VAMC FACILITIES

E-00

BVG MMF

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

BIRMINGHAM

VA MEDICAL

CENTER

U.S. Department of Veterans Affairs

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

WAP

AutoCAD SHX Text

BID DOCUMENTS FOR CONSTRUCTION

AutoCAD SHX Text

FULLY SPRINKLERED

AutoCAD SHX Text

REPLACE/UPGRADE MEDICAL GAS SYSTEM

AutoCAD SHX Text 521-21-106

AutoCAD SHX Text 07-07-2023

AutoCAD SHX Text

700 S. 19TH STREET, BIRMINGHAM, AL. 35233

AutoCAD SHX Text

BIRMINGHAM VA MEDICAL CENTER

AutoCAD SHX Text

AutoCAD SHX Text

ELECTRICAL LEGEND, GENERAL NOTES AND ABBREVIATIONS

AutoCAD SHX Text LED STRIP / INDUSTRIAL LUMINAIRE (LIGHT FIXTURE) LUMINAIRE SHALL BE ON EMERGENCY POWER AS INDICATED ON DRAWINGS. SEE LUMINAIRE SCHEDULE FOR DETAILS RECESSED DOWNLIGHT LUMINAIRE SEE LUMINAIRE SCHEDULE FOR DETAILS WALL WASH LUMINAIRE ARROW INDICATES DIRECTION SEE LUMINAIRE SCHEDULE FOR DETAILS WALL MOUNTED LUMINAIRE SEE LUMINAIRE SCHEDULE FOR DETAILS EXIT SIGN - DIRECTIONAL ARROWS AS INDICATED. CEILING OR WALL MOUNT AT 7'-6" AFF TO CENTE OR ABOVE DOOR SEE LUMINAIRE SCHEDULE FOR DETAILS PHOTOELECTRIC CELL SWITCH MOUNTED 48" AFF UNLESS NOTED OTHERWISE LOWERCASE LETTER INDICATES SWITCH CONTROL '3' INDICATES THREE-WAY '4' INDICATES FOUR-WAY 'D' INDICATES DIMMER SWITCH 'P' INDICATES PILOT LIGHT SWITCH (PILOT ON) 'WP' INDICATES WEATHERPROOF COVER CEILING MOUNTED OCCUPANCY SENSOR WITH POWER PACK - BASIS OF DESIGN: HUBBELL #OMNIDT2000RP WITH #UVPP OR APPROVED EQUIVALENT CEILING MOUNTED DAYLIGHT SENSOR WALL MOUNTED OCCUPANCY SENSOR. REFER TO SPECIFICATIONS FOR DETAILS.

AutoCAD SHX Text 14-30

AutoCAD SHX Text

NP3A

AutoCAD SHX Text A/P/V/N

AutoCAD SHX Text

AutoCAD SHX Text S

AutoCAD SHX Text

MMSS

AutoCAD SHX Text T1

AutoCAD SHX Text

AutoCAD SHX Text NEW INTERIOR WIRING - ABOVE GRADE - CONCEALED OR EXPOSED HOMERUN - ARROWS INDICATE NUMBER OF CIRCUITS (GND NOT SHOWN) CONDUCTORS ARE #12 UNLESS NOTED OTHERWISE. CIRCUIT NUMBER DESIGNATION PANELBOARD DESIGNATION JUNCTION BOX - SIZE AS INDICATED OR REQUIRED. PANELBOARD, RECESSED OR SURFACE MOUNT AS SPECIFIED. DESIGNATION PER CLIENT STANDARD DRY-TYPE TRANSFORMER - KVA AS INDICATED, 'T1' INDICATES DESIGNATION SAFETY DISCONNECT SWITCH A INDICATES AMPS P INDICATES POLES V INDICATES LINE TO LINE VOLTS N INDICATES NEMA ENCLOSURE DESIGNATION \ (SLASH) INDICATES FUSIBLE INDICATES FUSIBLE MAGNETIC MOTOR STARTER - 'PR' INDICATES PROVIDE PHASE PROTECTION RELAY. NUMBER INDICATES NEMA SIZE COMBINATION TYPE MAGNETIC MOTOR STARTER/DISCONNECT NUMBER INDICATES NEMA SIZE MANUAL MOTOR STARTER SWITCH WITH THERMAL OVERLOAD PROTECTION MOTOR - NUMBER INDICATES HORSEPOWER. WIRE COMPLETE WITH DISCONNECT SWITCH AS INDICATED OR REQUIRED, 'M' INDICATES FRACTIONAL HORSEPOWER INDICATES THREE-PHASE MOTOR DUPLEX RECEPTACLE - 125V, 20A, GROUND TYPE MOUNT 18" AFF UNLESS NOTED OTHERWISE 'S' INDICATES TOP HALF SWITCHED 'IG' INDICATES ISOLATED GROUND 'WP' INDICATES WEATHER-PROOF. PROVIDE WEATHER-RESISTANT PER NEC 406.8. NEC 406.8. 'SS' INDICATES SURGE SUPPRESSION TYPE 'TR' INDICATES TAMPER RESISTANT TYPE DUPLEX RECEPTACLE - GROUND FAULT CIRCUIT INTERRUPTER MOUNT 48" AFF UNLESS NOTED OTHERWISE. DUPLEX RECEPTACLE - ON EMERGENCY POWER QUADRAPLEX RECEPTACLE - 125V, 20A, GROUND TYPE - MOUNT 18" AFF UNLESS NOTED OTHERWISE QUADRAPLEX RECEPTACLE - ON EMERGENCY POWER SINGLE RECEPTACLE - 125V, 20A, GROUND TYPE - MOUNT 18" AFF UNLESS NOTED OTHERWISE SINGLE POWER RECEPTACLE - SPECIAL PURPOSE - NEMA CONFIGURATION AS INDICATED FLOOR BOX WITH POWER, REFER TO PLANS FOR RECEPTACLE TYPE AND CIRCUITING. ELECTRICAL STRIP MOLD RECEPTACLES ON 2'-0" CENTERS UNLESS OTHERWISE NOTED MOUNT 42" AFF UNLESS OTHERWISE NOTED EMERGENCY POWER OFF (ABORT) BUTTON MUSHROOM HEAD STYLE PUSH PLATE (FOR AUTOMATIC DOOR ACTUATION) VARIABLE FREQUENCY DRIVE BUS DUCT SEE PLANS FOR FURTHER INFORMATION.

AutoCAD SHX Text

NP3A-23

AutoCAD SHX Text J

AutoCAD SHX Text

PC

AutoCAD SHX Text %%uLIGHTING

AutoCAD SHX Text %%uPOWER

AutoCAD SHX Text %%uGENERAL NOTES

AutoCAD SHX Text %%uABBREVIATIONS

AutoCAD SHX Text %%uCOMMUNICATIONS

AutoCAD SHX Text A AMP AMP AC ALTERNATING CURRENT ALTERNATING CURRENT ADA AMERICANS WITH DISABILITIES ACT AMERICANS WITH DISABILITIES ACT AF AMP FRAME AMP FRAME AFCI ARC FAULT CIRCUIT INTERRUPTER ARC FAULT CIRCUIT INTERRUPTER AFF ABOVE FINISHED FLOOR ABOVE FINISHED FLOOR AFG ABOVE FINISHED GRADE ABOVE FINISHED GRADE AIC AMPERES INTERRUPTING CAPACITY AMPERES INTERRUPTING CAPACITY AL ALUMINUM ALUMINUM AT AMP TRIP AMP TRIP ATC AUTOMATIC TEMPERATURE CONTROL AUTOMATIC TEMPERATURE CONTROL AWG AMERICAN WIRE GAUGE AMERICAN WIRE GAUGE BLDG BUILDING BUILDING C CONDUIT CONDUIT CB CIRCUIT BREAKER CIRCUIT BREAKER CKT CIRCUIT CIRCUIT CEIL CEILING CEILING CENTERLINE CENTERLINE CMU CONCRETE MASONRY UNIT CONCRETE MASONRY UNIT CONC CONCRETE CONCRETE CONT'D CONTINUED CONTINUED CR CRITICAL CRITICAL CU COPPER COPPER CUH CABINET UNIT HEATER CABINET UNIT HEATER DC DIRECT CURRENT DIRECT CURRENT DW DISH WASHER DISH WASHER EC ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR EF EXHAUST FAN EXHAUST FAN EGC EQUIPMENT GROUNDING CONDUCTOR EQUIPMENT GROUNDING CONDUCTOR EM EMERGENCY EMERGENCY EUH ELECTRIC UNIT HEATER ELECTRIC UNIT HEATER EWC ELECTRIC WATER COOLER ELECTRIC WATER COOLER FACP FIRE ALARM CONTROL PANEL FIRE ALARM CONTROL PANEL GD GARBAGE DISPOSAL GARBAGE DISPOSAL GEC GROUNDING ELECTRODE CONDUCTOR GROUNDING ELECTRODE CONDUCTOR GFI GROUND FAULT INTERRUPTER GROUND FAULT INTERRUPTER GND GROUND GROUND HID HIGH INTENSITY DISCHARGE HIGH INTENSITY DISCHARGE HOA HAND-OFF-AUTOMATIC HAND-OFF-AUTOMATIC HP HORSEPOWER HORSEPOWER HPS HIGH PRESSURE SODIUM HIGH PRESSURE SODIUM HZ HERTZ HERTZ JB JUNCTION BOX JUNCTION BOX KAIC THOUSAND AMP INTERRUPTING THOUSAND AMP INTERRUPTING CAPACITY KCMIL THOUSAND CIRCULAR MIL THOUSAND CIRCULAR MIL KV THOUSAND VOLTS (KILOVOLT) THOUSAND VOLTS (KILOVOLT) KVA THOUSAND VOLT-AMPS THOUSAND VOLT-AMPS KW THOUSAND WATTS (KILOWATT) THOUSAND WATTS (KILOWATT) LC LIGHTING CONTACTORS LIGHTING CONTACTORS LCP LATERAL CONTROL PIT LATERAL CONTROL PIT LED LIGHT EMITTING DIODE LIGHT EMITTING DIODE LP LIGHTING PANELBOARD LIGHTING PANELBOARD LTG LIGHTING LIGHTING MCC MOTOR CONTROL CENTER MOTOR CONTROL CENTER MCCB MOLDED CASE CIRCUIT BREAKER MOLDED CASE CIRCUIT BREAKER MCB MAIN CIRCUIT BREAKER MAIN CIRCUIT BREAKER MH MANHOLE OR METAL HALIDE MANHOLE OR METAL HALIDE MIC MICROWAVE OR MICROPHONE MICROWAVE OR MICROPHONE MLO MAIN LUGS ONLY MAIN LUGS ONLY MTS MANUAL TRANSFER SWITCHMANUAL TRANSFER SWITCH

AutoCAD SHX Text A. NOT ALL SYMBOLS INDICATED IN THE LEGEND, OR NOT ALL SYMBOLS INDICATED IN THE LEGEND, OR LISTED ABBREVIATIONS, APPEAR ON THE DRAWINGS. COORDINATE WORK ACCORDINGLY. COMPLY WITH SPECIFICATIONS AND NOTES BELOW AS APPLICABLE. B. ALL RECEPTACLES SHALL BE INSTALLED 18" AFF ALL RECEPTACLES SHALL BE INSTALLED 18" AFF UNLESS NOTED OTHERWISE. C. ALL CONDUIT SHALL BE CONCEALED WITHIN WALLS ALL CONDUIT SHALL BE CONCEALED WITHIN WALLS UNLESS OTHERWISE NOTED. D. ALL WIRING SHALL BE COPPER. ALUMINUM WIRING ALL WIRING SHALL BE COPPER. ALUMINUM WIRING SHALL NOT BE PERMITTED. UNLESS OTHERWISE NOTED, ALL WIRING SHALL BE 2#12 AWG AND 1#12 AWG EQUIPMENT GROUNDING CONDUCTOR IN EMT. HOMERUNS FED FROM A 20A-1P, 120V CIRCUIT IN EXCESS OF 70' SHALL BE #10 AWG. E. SEE MECHANICAL PLANS FOR HVAC UNITS, PUMPS SEE MECHANICAL PLANS FOR HVAC UNITS, PUMPS AND FANS CONTROLLED BY THERMOSTATS AND OVERRIDE SWITCHES (PROVIDED BY ATC CONTRACTOR). F. FUSES AND OVERLOAD UNITS FOR MOTORS SHALL BE FUSES AND OVERLOAD UNITS FOR MOTORS SHALL BE SIZED BASED ON ACTUAL MOTOR NAMEPLATE DATA AND IN ACCORDANCE WITH NEC. G. ALL WORK SHALL COMPLY WITH LATEST EDITION OF ALL WORK SHALL COMPLY WITH LATEST EDITION OF NFPA70, NFPA72, NFPA99, NFPA101, NEC & ALL FEDERAL, STATE & LOCAL REGULATIONS. H. ALL PENETRATIONS THROUGH FLOORS, RATED WALLS ALL PENETRATIONS THROUGH FLOORS, RATED WALLS AND PARTITIONS SHALL BE SEALED WITH UL APPROVED FIRE SEALANT MATERIAL TO MAINTAIN FIRE RATING FOR THE SEPARATION. I. ALL ENCLOSURES, CONDUIT BODIES AND THEIR ALL ENCLOSURES, CONDUIT BODIES AND THEIR COVERS CONTAINING FIRE ALARM SYSTEM CONDUCTORS SHALL BE PAINTED RED. J. AN EQUIPMENT GROUNDING CONDUCTOR SHALL BE AN EQUIPMENT GROUNDING CONDUCTOR SHALL BE INSTALLED WITH ALL FEEDER AND BRANCH CIRCUITS. SIZE IN ACCORDANCE WITH NFPA 70 ARTICLE 250. K. FLEXIBLE CONNECTIONS TO MOTORS SHALL BE LIQUID FLEXIBLE CONNECTIONS TO MOTORS SHALL BE LIQUID TIGHT FLEXIBLE METAL CONDUIT IN A 360° LOOP EXCEPT AS NOTED OTHERWISE. L. LOCATE DISCONNECTS AT EQUIPMENT AS REQUIRED LOCATE DISCONNECTS AT EQUIPMENT AS REQUIRED BY MANUFACTURER. LOCATIONS ON DRAWINGS ARE APPROXIMATE. M. IDENTIFICATION: IDENTIFICATION: RECEPTACLES CONNECTED TO THE ESSENTIAL ELECTRICAL SYSTEM SHALL BE RED WITH A WHITE LABEL CONTAINING THE WORD "EMERGENCY" IN BLACK ON THE TOP OF THE PLATE AND A WHITE LABEL WITH THE CIRCUIT NUMBER IN BLACK ON THE BOTTOM. "NORMAL" RECEPTACLES SHALL HAVE A WHITE LABEL WITH THE CIRCUIT NUMBER IN BLACK AT THE BOTTOM OF THE PLATE. N. PROVIDE WIRE MARKERS TO IDENTIFY CABLES FOR PROVIDE WIRE MARKERS TO IDENTIFY CABLES FOR ALL SYSTEMS AT THE ORIGIN, PULL BOXES, AND TERMINATION POINTS. LABELS SHALL BE SELF ADHESIVE OR HEAT SHRINK TYPE. O. NO LIVE WORK SHALL BE PERMITTED. EVERY CIRCUIT NO LIVE WORK SHALL BE PERMITTED. EVERY CIRCUIT SHALL BE LOCKED-OUT AND TAGGED-OUT BEFORE COMMENCING WORK. P. ALL WIRING SHALL BE IN CONDUIT. ALL WIRING SHALL BE IN CONDUIT. -INSTALL CABLE TRAY FOR COMM / DATA WIRING. -CONTROL SYSTEMS SHALL BE IN BLUE EMT. -FIRE ALARM SYSTEMS SHALL BE IN RED EMT. -NO "J" HOOKS Q. ELECTRICAL CONTRACTOR SHALL RE-PRINT ALL PANEL ELECTRICAL CONTRACTOR SHALL RE-PRINT ALL PANEL CIRCUIT DIRECTORIES TO REFLECT CIRCUITS REMOVED AND ADDED. R. ELECTRICAL CONTRACTOR SHALL PROVIDE LABELS ON ELECTRICAL CONTRACTOR SHALL PROVIDE LABELS ON ALL SERVICE DISCONNECTS (LOCATED AT EQUIPMENT) INDICATING BRANCH CIRCUIT AND PANEL THE EQUIPMENT IS FED FROM.

AutoCAD SHX Text DATA/VOIP OUTLET MOUNTED AS NOTED. INDICATES FOUR DATA PORTS. PIPE TO CABLE TRAY. 'W' INDICATES WALL MOUNTED VOIP DATA OUTLET AT 54" ABOVE FINISHED FLOOR. CATV OUTLET MOUNTED AS NOTED. HOMERUN COAX CABLE TO VA SELECTED SOURCE. SYSTEM SHALL BE IN EMT. WIRELESS ACCESS POINT. PROVIDE (1) DATA OUTLET FOR ANTENNA AT ACCESSIBLE LOCATION ABOVE CEILING. PROVIDE (1) LEVEL 6 CABLE BACK TO RACK MOUNTED PATCH PANEL. PROVIDE DUPLEX RECEPTACLE AND CONNECT TO BRANCH CIRCUIT AS INDICATED ON FLOOR PLANS. ALL IN CABLE TRAY. CEILING MOUNTED PA SPEAKER

AutoCAD SHX Text NC NORMALLY CLOSED OR NURSE CALL NORMALLY CLOSED OR NURSE CALL NEC NATIONAL ELECTRICAL CODE NATIONAL ELECTRICAL CODE NFPA NATIONAL FIRE PROTECTION ASSOCIATION NATIONAL FIRE PROTECTION ASSOCIATION NO NORMALLY OPEN NORMALLY OPEN NO. NUMBER NUMBER OL OVERLOAD OVERLOAD P POLE POLE PA PUBLIC ADDRESS PUBLIC ADDRESS PB PUSH BUTTON PUSH BUTTON PF POWER FACTOR POWER FACTOR PH PHASE PHASE PNL PANEL PANEL PT POTENTIAL TRANSFORMER POTENTIAL TRANSFORMER PVC POLYVINYL CHLORIDE POLYVINYL CHLORIDE REF REFRIGERATOR REFRIGERATOR RSC RIGID STEEL CONDUIT RIGID STEEL CONDUIT RTU ROOF TOP UNIT ROOF TOP UNIT SCCR SHORT CIRCUIT CURRENT RATING SHORT CIRCUIT CURRENT RATING SF SUPPLY FAN SUPPLY FAN SLD SINGLE LINE DIAGRAM SINGLE LINE DIAGRAM SS SOLID STATE SOLID STATE SWBD1 SWITCHBOARD, NUMBER AS INDICATED SWITCHBOARD, NUMBER AS INDICATED TC TIME CLOCK TIME CLOCK TELCOM TELECOMMUNICATIONS TELECOMMUNICATIONS TS TRANSFER SWITCH TRANSFER SWITCH T&B TOP AND BOTTOM TOP AND BOTTOM TYP TYPICAL TYPICAL TV TELEVISION TELEVISION UC UNDER COUNTER UNDER COUNTER UG UNDERGROUND UNDERGROUND V VOLT VOLT VA DEPARTMENT OF VETERAN AFFAIRS DEPARTMENT OF VETERAN AFFAIRS VA VOLT-AMPERE VOLT-AMPERE VAMC VA MEDICAL CENTER VA MEDICAL CENTER VFD VARIABLE FREQUENCY DRIVE VARIABLE FREQUENCY DRIVE VOIP VOICE OVER INTERNET PROTOCOL (PHONE) VOICE OVER INTERNET PROTOCOL (PHONE) W WATT WATT W/ WITH WITH WP WEATHERPROOF WEATHERPROOF WRG WIRING WIRING XFMR TRANSFORMER TRANSFORMER XP EXPLOSION-PROOF EXPLOSION-PROOF 3PH THREE PHASE (Ø) THREE PHASE (Ø) Ø) ) 3W THREE WIRE THREE WIRE 4W FOUR WIRE FOUR WIRE (R) LOCATION OF RELOCATED DEVICE OR LOCATION OF RELOCATED DEVICE OR EQUIPMENT (RR) REMOVE AND RELOCATE EXISTING DEVICE OR REMOVE AND RELOCATE EXISTING DEVICE OR EQUIPMENT (RX) REMOVE EXISTING DEVICE OR EQUIPMENT REMOVE EXISTING DEVICE OR EQUIPMENT (X) EXISTING DEVICE OR EQUIPMENT TO REMAIN EXISTING DEVICE OR EQUIPMENT TO REMAIN (XR) EXISTING DEVICE OR EQUIPMENT TO BE EXISTING DEVICE OR EQUIPMENT TO BE REMOVED AND REPLACED AT SAME LOCATION

AutoCAD SHX Text

TV

AutoCAD SHX Text NURSE CALL STATION 'HW' INDICATES PATIENT HEADWALL NURSE CALL 'D' INDICATES DUTY STATION 'R' INDICATES RESTROOM PULL STATION: MOUNT 72" AFF FOR SHOWER LOCATION MOUNT 54" AFF FOR TUB LOCATION MOUNT 36" AFF FOR TOILET LOCATION CEILING MOUNTED NURSE CALL LIGHT '2' INDICATES 2-LAMP DOME LIGHT 'C' INDICATES CORRIDOR DOME LIGHT 'I' INDICATES AUXILIARY INTERSECTIONAL DOME LIGHT NURSE'S CALL MASTER STATION MOUNTED ON NURSE'S COUNTER TOP UNLESS OTHERWISE NOTED. NOTE: WIRING SHALL BE IN EMT WITH TAMPER RESISTANT SCREWS.

AutoCAD SHX Text

%%UNURSE CALL

AutoCAD SHX Text F

AutoCAD SHX Text

AutoCAD SHX Text F

AutoCAD SHX Text

AutoCAD SHX Text FIRE ALARM PULL STATION. MOUNTED 48" AFF TO CENTERLINE OF STATION. AUDIO/VISUAL ALARM. COMBINATION SPEAKER WITH ADJUSTABLE CANDELA STROBE LIGHT. WALL MOUNTED 90" AFF TO TOP. CEILING MOUNT WHERE INDICATED. NUMBER INDICATES CANDELA RATING OF STROBE. 'WP' INDICATES WEATHERPROOF UNIT. VISUAL ALARM. ADJUSTABLE CANDELA STROBE LIGHT. WALL MOUNTED 90" AFF TO TOP. CEILING MOUNT WHERE INDICATED. NUMBER INDICATES CANDELA RATING OF STROBE. REFER TO SPECIAL REQUIREMENTS IN SLEEPING AREAS. NS INDICATES NON-SUPERVISED 120 VOLT REMOTE VISUAL SIGNAL, 177 CANDELA, CONNECTED TO NON-SUPERVISED SMOKE DETECTOR. DETECTOR; LETTER INDICATES AS FOLLOWS: BLANK = PHOTOELECTRIC SMOKE DETECTOR H = HEAT SMOKE I = IONIZATION SMOKE IH = IONIZATION AND HEAT SMOKE IP = IONIZATION AND PHOTOELECTRIC SMOKE PH = PHOTOELECTRIC AND HEAT SMOKE IPH = IONIZATION, PHOTOELECTRIC, AND HEAT DUCT MOUNTED SMOKE DETECTOR WITH REMOTE TEST AND RESET STATION. FURNISHED AND WIRED BY ELECTRICAL CONTRACTOR, INSTALLED BY MECHANICAL CONTRACTOR. 'S' INDICATES LOCATED IN SUPPLY AIR DUCT INDICATES LOCATED IN SUPPLY AIR DUCT 'R' INDICATES LOCATED IN RETURN AIR DUCT INDICATES LOCATED IN RETURN AIR DUCT REMOTE TEST STATION WITH RESET FOR DUCT SMOKE DETECTOR ELECTROMAGNETIC TYPE DOOR HOLDER OUTLET

AutoCAD SHX Text

%%UFIRE ALARM

AutoCAD SHX Text

TS

AutoCAD SHX Text

AutoCAD SHX Text F

AutoCAD SHX Text B

AutoCAD SHX Text b

AutoCAD SHX Text D

AutoCAD SHX Text b

AutoCAD SHX Text W

AutoCAD SHX Text b

AutoCAD SHX Text C

AutoCAD SHX Text b

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text b

AutoCAD SHX Text S

AutoCAD SHX Text Mo

AutoCAD SHX Text S

AutoCAD SHX Text H

AutoCAD SHX Text

DH

AutoCAD SHX Text

GFI 48"

AutoCAD SHX Text

EPO

AutoCAD SHX Text N

AutoCAD SHX Text

AutoCAD SHX Text N

AutoCAD SHX Text

HW

AutoCAD SHX Text

NCS

AutoCAD SHX Text

VFD

AutoCAD SHX Text

%%USECURITY

AutoCAD SHX Text CARD ACCESS READER; LETTER INDICATES AS FOLLOWS: M=MOUNT C-CEILING D-DESK F-FLUSH H-HIDDEN D-DESK F-FLUSH H-HIDDEN F-FLUSH H-HIDDEN H-HIDDEN M-MULLION P-PEDESTAL R-RACK P-PEDESTAL R-RACK R-RACK S-SURFACE W-WALL W-WALL T=TECHNOLOGY/TYPE B-BARCODE F-ELEVATOR FLOOR CALL H-ELEVATOR HALL CALL M-MAG STRIP P-PROXIMITY S-SMART CARD T-TOKEN ELECTRONIC LOCK; LETTER INDICATES AS FOLLOWS: M=MOUNT C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLIOND-DESK F-FLUSH H-HIDDEN M-MULLIONF-FLUSH H-HIDDEN M-MULLIONH-HIDDEN M-MULLIONP-PEDESTAL R-RACK S-SURFACE W-WALL S-SURFACE W-WALL T=TECHNOLOGY/TYPE D-DEADBOLT H-HYBRID L-LATCH SET H-HYBRID L-LATCH SET L-LATCH SET M-MAGNETIC S-STRIKE S-STRIKE SECURITY ACCESS, VIDEO CAMERA WITH LENS M = MOTION DETECTOR PZ = MOTION DETECTOR WITH PAN AND ZOOM PTZ= MOTION DETECTOR WITH PAN, TILT, AND ZOOM KEYPAD; LETTER INDICATES AS FOLLOWS: M=MOUNT C-CEILING D-DESK F-FLUSH H-HIDDEN D-DESK F-FLUSH H-HIDDEN F-FLUSH H-HIDDEN H-HIDDEN M-MULLION P-PEDESTAL R-RACK P-PEDESTAL R-RACK R-RACK S-SURFACE W-WALL W-WALL NOTE: WIRING SHALL BE IN EMT WITH TAMPER RESISTANT SCREWS.

AutoCAD SHX Text M

AutoCAD SHX Text T

AutoCAD SHX Text M

AutoCAD SHX Text T

AutoCAD SHX Text M

AutoCAD SHX Text

PTZ

AutoCAD SHX Text M

AutoCAD SHX Text

OS

AutoCAD SHX Text

DS

AutoCAD SHX Text

E-02

BVG

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

BIRMINGHAM

VA MEDICAL

CENTER

U.S. Department of Veterans Affairs

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

ELECTRICAL

SUB BASEMENT: AREA D

MMF

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text

BID DOCUMENTS FOR CONSTRUCTION

AutoCAD SHX Text

FULLY SPRINKLERED

AutoCAD SHX Text

REPLACE/UPGRADE MEDICAL GAS SYSTEM

AutoCAD SHX Text 521-21-106

AutoCAD SHX Text 07-07-2023

AutoCAD SHX Text

700 S. 19TH STREET, BIRMINGHAM, AL. 35233

AutoCAD SHX Text

BIRMINGHAM VA MEDICAL CENTER

AutoCAD SHX Text

AutoCAD SHX Text

DRAWING SCALE: X/X" = 1' - 0"

AutoCAD SHX Text

KEY PLAN: SUB-BASEMENT

AutoCAD SHX Text N

AutoCAD SHX Text

AutoCAD SHX Text 9.5

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text I

AutoCAD SHX Text J

AutoCAD SHX Text H

AutoCAD SHX Text K

AutoCAD SHX Text L'

AutoCAD SHX Text L

AutoCAD SHX Text M

AutoCAD SHX Text N

AutoCAD SHX Text O

AutoCAD SHX Text P

AutoCAD SHX Text KEY NOTES (NEW WORK) 1. CONTINUED FROM SHEET E-01. CONTINUED FROM SHEET E-01. E.C. SHALL PROVIDE NEW 1" EMT CONDUIT, WITH PULL STRING, FROM THE LOCAL ALARM PANELS (NEW EQUIPMENT CONTROL PANELS) UP TO BASEMENT LEVEL CORRIDOR AS SHOWN ON SHEET E-03. ROUTING SHALL FOLLOW THE SAME PATH AS THE NEW MED GAS PIPES SHOWN ON "PG" DRAWINGS. PROVIDE A PULL-BOX FOR EVERY 270º OF BENDS PER VA SPEC. COORDINATE WORK WITH PLUMBING CONTRACTOR. SEE SHEETS E-01 AND E-03 FOR CONTINUATION. WIRING WITHIN THE NEW CONDUIT IS PROVIDED AND PULLED BY THE PLUMBING CONTRACTOR. 2. ROUTE CONDUIT UP TO BASEMENT LEVEL WITHIN OPEN ROUTE CONDUIT UP TO BASEMENT LEVEL WITHIN OPEN VERTICAL SPACE AT THIS LOCATION. REFER TO SHEET E-03 FOR CONTINUATION AT BASEMENT LEVEL.

AutoCAD SHX Text

MATCH LINE AREA "C" - SEE E-01

AutoCAD SHX Text GENERAL NOTES A. KEY PLAN AREA NAMING DOES NOT CORRESPOND TO HOSPITAL KEY PLAN AREA NAMING DOES NOT CORRESPOND TO HOSPITAL AREA NAMING. B. REFER TO SHEET E-00 FOR ELECTRICAL LEGEND, GENERAL NOTES, REFER TO SHEET E-00 FOR ELECTRICAL LEGEND, GENERAL NOTES, AND ABBREVIATIONS. C. MEDICAL GAS SERVICES TO THE HOSPITAL MUST BE MAINTAINED MEDICAL GAS SERVICES TO THE HOSPITAL MUST BE MAINTAINED THROUGHOUT THE CONSTRUCTION PERIOD. D. BEFORE BEGINNING WORK, THE CONTRACTOR SHALL REFER TO THE BEFORE BEGINNING WORK, THE CONTRACTOR SHALL REFER TO THE ARCHITECTURAL DRAWINGS FOR THE PHASING PLAN. ALSO, SEE THE LIFE SAFETY AND INFECTION CONTROL (ICRA) PLANS. E. COORDINATE DIVISIONS 26 & 27 WORK WITH OTHER TRADES AS COORDINATE DIVISIONS 26 & 27 WORK WITH OTHER TRADES AS INDICATED OR REQUIRED. F. ALL WORK SHALL COMPLY WITH LATEST EDITION OF NFPA70, ALL WORK SHALL COMPLY WITH LATEST EDITION OF NFPA70, NFPA72, NFPA99, NFPA101, NEC & ALL FEDERAL, STATE & LOCAL REGULATIONS. G. ALL PENETRATIONS THROUGH FLOORS, RATED WALLS AND ALL PENETRATIONS THROUGH FLOORS, RATED WALLS AND PARTITIONS SHALL BE SEALED WITH UL APPROVED FIRE SEALANT MATERIAL TO MAINTAIN FIRE RATING FOR THE SEPARATION. H. SOME CIRCUITS AFFECTED BY THE WORK INDICATED ON THIS SHEET SOME CIRCUITS AFFECTED BY THE WORK INDICATED ON THIS SHEET MAY FEED OTHER AREAS OUTSIDE THE SCOPE OF THIS PROJECT. THE CONTRACTOR SHALL MAINTAIN CIRCUIT CONTINUITY AT ALL TIMES TO AREAS OUTSIDE THE SCOPE OF WORK. ANY POWER OUTAGES MUST BE COORDINATED IN ADVANCE WITH THE COR.

AutoCAD SHX Text

E-03

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

BIRMINGHAM

VA MEDICAL

CENTER

U.S. Department of Veterans Affairs

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

ELECTRICAL

BASEMENT: AREA D&F

MMF

AutoCAD SHX Text

BID DOCUMENTS FOR CONSTRUCTION

AutoCAD SHX Text

FULLY SPRINKLERED

AutoCAD SHX Text

REPLACE/UPGRADE MEDICAL GAS SYSTEM

AutoCAD SHX Text 521-21-106

AutoCAD SHX Text 07-07-2023

AutoCAD SHX Text

700 S. 19TH STREET, BIRMINGHAM, AL. 35233

AutoCAD SHX Text

BIRMINGHAM VA MEDICAL CENTER

AutoCAD SHX Text

AutoCAD SHX Text

KEY PLAN: BASEMENT

AutoCAD SHX Text N

AutoCAD SHX Text

DRAWING SCALE: 1/8" = 1' - 0"

AutoCAD SHX Text B

AutoCAD SHX Text D

AutoCAD SHX Text F

AutoCAD SHX Text

AutoCAD SHX Text Q

AutoCAD SHX Text P

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text P

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text R

AutoCAD SHX Text O´

AutoCAD SHX Text GENERAL NOTES A. KEY PLAN AREA NAMING DOES NOT CORRESPOND TO HOSPITAL KEY PLAN AREA NAMING DOES NOT CORRESPOND TO HOSPITAL AREA NAMING. B. REFER TO SHEET E-00 FOR ELECTRICAL LEGEND, GENERAL NOTES, REFER TO SHEET E-00 FOR ELECTRICAL LEGEND, GENERAL NOTES, AND ABBREVIATIONS. C. MEDICAL GAS SERVICES TO THE HOSPITAL MUST BE MAINTAINED MEDICAL GAS SERVICES TO THE HOSPITAL MUST BE MAINTAINED THROUGHOUT THE CONSTRUCTION PERIOD. D. BEFORE BEGINNING WORK, THE CONTRACTOR SHALL REFER TO THE BEFORE BEGINNING WORK, THE CONTRACTOR SHALL REFER TO THE ARCHITECTURAL DRAWINGS FOR THE PHASING PLAN. ALSO, SEE THE LIFE SAFETY AND INFECTION CONTROL (ICRA) PLANS. E. COORDINATE DIVISIONS 26 & 27 WORK WITH OTHER TRADES AS COORDINATE DIVISIONS 26 & 27 WORK WITH OTHER TRADES AS INDICATED OR REQUIRED. F. ALL WORK SHALL COMPLY WITH LATEST EDITION OF NFPA70, ALL WORK SHALL COMPLY WITH LATEST EDITION OF NFPA70, NFPA72, NFPA99, NFPA101, NEC & ALL FEDERAL, STATE & LOCAL REGULATIONS. G. ALL PENETRATIONS THROUGH FLOORS, RATED WALLS AND ALL PENETRATIONS THROUGH FLOORS, RATED WALLS AND PARTITIONS SHALL BE SEALED WITH UL APPROVED FIRE SEALANT MATERIAL TO MAINTAIN FIRE RATING FOR THE SEPARATION. H. SOME CIRCUITS AFFECTED BY THE WORK INDICATED ON THIS SHEET SOME CIRCUITS AFFECTED BY THE WORK INDICATED ON THIS SHEET MAY FEED OTHER AREAS OUTSIDE THE SCOPE OF THIS PROJECT. THE CONTRACTOR SHALL MAINTAIN CIRCUIT CONTINUITY AT ALL TIMES TO AREAS OUTSIDE THE SCOPE OF WORK. ANY POWER OUTAGES MUST BE COORDINATED IN ADVANCE WITH THE COR.

AutoCAD SHX Text

MAP-1

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

LS2BB-5

AutoCAD SHX Text

LS2BB

AutoCAD SHX Text KEY NOTES (NEW WORK) 1. NEW MASTER ALARM PANEL #1. NEW MASTER ALARM PANEL #1. PROVIDE 120V LIFE-SAFETY POWER FROM PANEL "LS2BB." 20A BRANCH CIRCUIT, (2)#12 & (1)#12 G. IN 3/4" C. REFER TO PANEL SCHEDULE ON THIS SHEET. COORDINATE WORK WITH OTHER TRADES. 2. EXISTING ELECTRICAL PANEL "LS2BB." REFER TO PANEL EXISTING ELECTRICAL PANEL "LS2BB." REFER TO PANEL SCHEDULE ON THIS SHEET. 3. CONTINUED FROM SHEET E-02 CONTINUED FROM SHEET E-02 E.C. SHALL PROVIDE NEW 1" EMT CONDUIT, WITH PULL STRING, FROM THE LOCAL ALARM PANELS (NEW EQUIPMENT CONTROL PANELS) IN THE SUB-BASEMENT, UP TO BASEMENT LEVEL CORRIDOR. ROUTING SHALL FOLLOW THE SAME PATH AS THE NEW MED GAS PIPES SHOWN ON "PG" DRAWINGS. PROVIDE A PULL-BOX FOR EVERY 270º OF BENDS PER VA SPEC. COORDINATE WORK WITH PLUMBING CONTRACTOR. SEE SHEETS E-01 AND E-02 FOR CONTINUATION. WIRING WITHIN THE NEW CONDUIT IS PROVIDED AND PULLED BY THE PLUMBING CONTRACTOR. 4. PENETRATE THE WALL SEPARATING THE OPEN-CEILING PENETRATE THE WALL SEPARATING THE OPEN-CEILING CORRIDOR AND THE ACT-CEILING CORRIDOR. TERMINATE CONDUIT WITH A BUSHING-END ABOVE THE ACT CEILING. WIRING SHALL BE PULLED AND CONTINUED WITHIN THE PLENUM BY THE PLUMBING CONTRACTOR.

AutoCAD SHX Text

E-04

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

BIRMINGHAM

VA MEDICAL

CENTER

U.S. Department of Veterans Affairs

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

ELECTRICAL

GROUND FLOOR: AREA A

MMF

AutoCAD SHX Text I

AutoCAD SHX Text H1

AutoCAD SHX Text H

AutoCAD SHX Text J

AutoCAD SHX Text K

AutoCAD SHX Text K1

AutoCAD SHX Text M

AutoCAD SHX Text M1

AutoCAD SHX Text N

AutoCAD SHX Text 21a

AutoCAD SHX Text

AutoCAD SHX Text 22a

AutoCAD SHX Text

AutoCAD SHX Text 23a

AutoCAD SHX Text 23b

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text O

AutoCAD SHX Text

AutoCAD SHX Text

BID DOCUMENTS FOR CONSTRUCTION

AutoCAD SHX Text

FULLY SPRINKLERED

AutoCAD SHX Text

REPLACE/UPGRADE MEDICAL GAS SYSTEM

AutoCAD SHX Text 521-21-106

AutoCAD SHX Text…