ATTACHMENT 8 DRAWINGS 145 AW Repair Maint. Hangar Building 51 dated 20 July 2022 Vol 4.pdf
PDF 15 MB Posted
- Attached to
- Repair Building 51
- Solicitation number
- W50S87-23-B-0001
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT MAP:
PROJECT
LOCATION
BASE
ENTRANCE
CONSTRUCTION
ENTRANCE
BASE
OUTLINE
STATE MAP:
STATE OF NORTH CAROLINA
CITY OF CHARLOTTE,
MECKLENBURG COUNTY
VICINITY MAP:
PROJECT LOCATION
1. ROLLER SHADES IN LEU OF SLAT BLINDS
2. EPOXY FLOOR IN ROOMS:
A. HYDRO SHOP
B. WHEEL/TIRE SHOP
C. SUPPORT EQUIPMENT
D. CTK
3. ADDITIONAL PARKING SPACES
BID OPTIONS:
ANG PROJECT No.:
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
710 Avis Drive, #100 Ann Arbor, MI 48108-9649 phone: 810-956-9300 fax: 810-956-9281
/1
/2
:3 :0
P
M C
R e v it L o c a l\
.0
-A -R c h ri s .d o u g a n
.r v t
FJRP112701
REPAIR MAINTENANCE HANGAR BUILDING 51
CHARLOTTE DOUGLAS IAP
CHARLOTTE, NORTH CAROLINA
NCANG - 145TH AW
COVER SHEET -
VOLUME 4
FJRP112701ANG PRO. NO.:
3258000-181469.01
NJD, KB
DMD
July 20, 2022
ATM
N C
A N
G
T
H A
W
C H
A R
L O
T T
E D
O U
G L A
S I A
P C
H A
R L O
T T
E N
O R
T H
C A
R O
L
IN
A
R E
P A
IR
M
A
IN
T E
N A
N C
E H
A N
G A
R B
U
IL
D
IN
G
G-000D
VOLUME 4
07/20/22 B-3 SUBMITTAL
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
ISSUED
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
710 Avis Drive, #100 Ann Arbor, MI 48108-9649 phone: 810-956-9300 fax: 810-956-9281
/2
/2
:0
:3
A
M C
R e v it L o c a l\
.0
-A -R c h ri s .d o u g a n
.r v t
SHEET INDEX -
VOLUME 4
FJRP112701ANG PRO. NO.:
3258000-181469.01
NJD, KB
DMD
July 20, 2022
ATM
N C
A N
G
T
H A
W
C H
A R
L O
T T
E D
O U
G L A
S I A
P C
H A
R L O
T T
E N
O R
T H
C A
R O
L
IN
A
R E
P A
IR
M
A
IN
T E
N A
N C
E H
A N
G A
R B
U
IL
D
IN
G
G-001D
SHEET INDEX - VOLUME 2
A-515 PLAN DETAILS INTERIOR - MINOR CONSTRUCTION
A-601 DOOR AND FRAME SCHEDULES AND LEGENDS - EXIST & AREA A
A-602 DOOR AND FRAME SCHEDULES AND LEGENDS - AREAS B & C
A-603 WINDOW TYPES & DETAILS
A-605 TRANSLUCENT PANEL DETAILS
A-621 DOOR DETAILS-INTERIOR AND EXTERIOR
A-700 FINISH SCHEDULES
A-701A FINISH PLAN - AREA A
A-701A2 FINISH PLANS - AREA A2
A-701B FINISH PLAN - AREA B
A-701B2 FINISH PLAN - MINOR CONSTRUCTION AREA B2
A-701C FINISH PLAN-AREA C
A-702A HANGAR BAY STRIPING PLAN
A-703 FINISH DETAILS
A-801A SIGNAGE PLAN - AREA A
A-801A2 SIGNAGE PLANS - AREA A2
A-801B SIGNAGE PLAN - AREA B
A-801B2 SIGNAGE PLAN - MINOR CONSTRUCTION AREA B2
A-801C SIGNAGE PLAN - AREA C
A-804 SIGNAGE PLAN - LOWER CATWALK
A-805 SIGNAGE PLAN - UPPER CATWALK
A-851 SIGNAGE DETAILS
A-852 SIGNAGE SCHEDULE
A-901A2 FIXTURES, FURNITURE AND EQUIPMENT PLANS - AREA A2
A-901B FIXTURES, FURNITURE AND EQUIPMENT PLAN - AREA B
A-901C FIXTURES, FURNITURE AND EQUIPMENT PLAN - AREA C
Sheets in Volume: 135
SHEET INDEX - VOLUME 2
GENERAL
G-001B SHEET INDEX - VOLUME 2
ARCHITECTURAL
A-001 NOTES & SYMBOLS
A-002 PARTITION TYPES
A-003 PARTITION DETAILS & TOILET ACCESSORY MOUNTING HEIGHTS
A-004 ASSEMBLIES
A-005 ARCHITECTURAL KEYNOTES
AD100 DEMOLITION OVERALL PLAN
AD101A DEMOLITION FLOOR PLAN - AREA A
AD101B DEMOLITION FLOOR PLAN - AREA B
AD101C DEMOLITION FLOOR PLAN - AREA C
AD101C2 DEMOLITION FLOOR PLAN - MINOR CONSTRUCTION AREA C2
AD102A DEMOLITION MEZZANINE PLAN - AREA A
AD102A2 DEMOLITION MEZZANINE PLANS - AREA A2
AD105A DEMOLITION ROOF PLAN - AREA A
AD105B DEMOLITION ROOF PLAN - AREA B
AD105C DEMOLITION ROOF PLAN - AREA C
AD105C2 DEMOLITION ROOF PLAN - MINOR CONSTRUCTION AREA C2
AD121A DEMOLITION REFLECTED CEILING PLAN - AREA A
AD121B DEMOLITION REFLECTED CEILING PLAN - AREA B
AD121C DEMOLITION REFLECTED CEILING PLAN - AREA C
AD201 DEMOLITION EXTERIOR ELEVATIONS - AREA A
AD202 DEMOLITION EXTERIOR ELEVATIONS - AREA A
AD203 DEMOLITION EXTERIOR ELEVATIONS - AREA B
AD204 DEMOLITION EXTERIOR ELEVATIONS AREA C
AD205 DEMOLITION EXTERIOR ELEVATIONS - MINOR CONSTRUCTION
AD206 DEMOLITION EXTERIOR ELEVATIONS - AREA C2
AD301 DEMOLITION SECTIONS
A-100 OVERALL PLAN
A-101A FIRST FLOOR PLAN - AREA A
A-101A2 FIRST FLOOR PLANS - AREA A2
A-101B FIRST FLOOR PLAN - AREA B
A-101B2 FIRST FLOOR PLAN - MINOR CONSTRUCTION AREA B2
A-101C FIRST FLOOR PLAN - AREA C
A-101C2 FIRST FLOOR PLAN - MINOR CONSTRUCTION AREA C2
A-102 MEZZANINE PLAN - OVERALL
A-102A2 MEZZANINE PLANS - AREA A2
A-102A3 MEZZANINE ISOMETRICS - AREA A2
A-102B2 CLERESTORY FLOOR PLAN - MINOR CONSTRUCTION AREA B2
A-103 LOWER CATWALK PLAN
A-104 UPPER CATWALK PLAN
A-105 ROOF PLAN - OVERALL
A-105A ROOF PLAN - AREA A
A-105B ROOF PLAN - AREA B
A-105B2 ROOF PLAN - MINOR CONSTRUCTION AREA B2
A-105C ROOF PLAN - AREA C
A-105C2 ROOF PLAN - MINOR CONSTRUCTION AREA C2
A-121A REFLECTED CEILING PLAN - AREA A
A-121A2 REFLECTED CEILING PLANS - AREA A2
A-121B REFLECTED CEILING PLAN - AREA B
A-121B2 REFLECTED CEILING PLAN - MINOR CONSTRUCTION AREA B2
A-121C REFLECTED CEILING PLAN - AREA C
A-121C2 REFLECTED CEILING PLAN - MINOR CONSTRUCTION AREA C2
A-122B ENLARGED CEILING PLANS - AREAS B & C
A-151A2 FIRST FLOOR AIR BARRIER PLANS - AREA A2
A-151B FIRST FLOOR AIR BARRIER PLAN - AREA B
A-151B2 FIRST FLOOR AIR BARRIER PLAN - MINOR CONSTRUCTION AREA B2
A-151C FIRST FLOOR AIR BARRIER PLAN - AREA C
A-152B2 CLERESTORY AIR BARRIER PLAN - MINOR CONSTRUCTION AREA B2
A-152C2 CLERESTORY AIR BARRIER PLAN - MINOR CONSTRUCTION AREA C2
A-201 EXTERIOR ELEVATIONS - AREA A
A-202 EXTERIOR ELEVATIONS - AREA A
A-203 EXTERIOR ELEVATIONS - AREA B
A-204 EXTERIOR ELEVATIONS - MINOR CONSTRUCTION AREA B2
A-205 EXTERIOR ELEVATIONS - AREA C
A-206 EXTERIOR ELEVATIONS - MINOR CONSTRUCTION AREA C2
A-207 EXTERIOR FACADE REPAIR ELEVATIONS - AREA A
A-208 EXTERIOR FACADE REPAIR ELEVATIONS - AREAS B & C
A-301 BUILDING SECTIONS - AREA A
A-302 BUILDING SECTIONS - AREA A2
A-303 BUILDING SECTIONS - AREA B
A-304 BUILDING SECTIONS - MINOR CONSTRUCTION AREA B2
A-305 BUILDING SECTIONS - MINOR CONSTRUCTION AREA C2
A-310 WALL SECTIONS - AREA A
A-311 WALL SECTIONS - AREA A2 SOUTH HANGAR SHOP
A-312 WALL SECTIONS - AREA A2 NORTH HANGAR SHOP
A-313 WALL SECTIONS - AREA B
A-314 WALL SECTIONS - AREA B
A-315 WALL SECTIONS - MINOR CONSTRUCTION AREA B2
A-316 WALL SECTIONS - AREAS B & B2
A-317 WALL SECTIONS - MINOR CONSTRUCTION AREA B2
A-318 WALL SECTIONS - AREAS B & C
A-319 WALL SECTIONS - AREA C
A-320 WALL SECTIONS - MINOR CONSTRUCTION AREA C2
A-321 WALL SECTIONS - AREA B & C AIR BARRIER
A-322 WALL SECTIONS - HANGAR SHOP AIR BARRIERS
A-400 ENLARGED PLANS AND INTERIOR ELEVATIONS - AREA A
A-401 INTERIOR ELEVATIONS - AREA A
A-402 ENLARGED PLANS AND INTERIOR ELEVATIONS - AREA B
A-403 ENLARGED PLANS AND INTERIOR ELEVATIONS - AREA B
A-404 ENLARGED PLANS AND INTERIOR ELEVATIONS - AREA C
A-405 INTERIOR ELEVATIONS - AREA C
A-406 CASEWORK DETAILS
A-410 RAILING TYPES
A-411 ENLARGED STAIR AND SHIPS LADDER PLANS & SECTIONS - AREA B, B2 &
HANGAR SHOP SOUTH
A-412 ENLARGED STAIR AND SHIPS LADDER PLANS & SECTIONS - HANGAR SHOP
NORTH
A-501 ROOF DETAILS
A-502 SECTION DETAILS EXTERIOR
A-503 SECTION DETAILS - AREA A
A-504 SECTION DETAILS EXTERIOR - MINOR CONSTRUCTION AREA B2
A-505 SECTION DETAILS EXTERIOR - MINOR CONSTRUCTION AREA B2
A-506 SECTION DETAILS - MINOR CONSTRUCTION AREA C2
A-507 SECTION DETAILS - MINOR CONSTRUCTION AREA C2
A-508 SECTION DETAILS - INTERIOR
A-509 PLAN DETAILS - AIR BARRIER
A-510 SECTION DETAILS - AIR BARRIER
A-511 PLAN DETAILS EXTERIOR - MINOR CONSTRUCTION AREAS B & B2
A-512 PLAN DETAILS - MINOR CONSTRUCTION AREA B2
A-513 PLAN DETAILS EXTERIOR - MINOR CONSTRUCTION AREA C2
A-514 PLAN DETAILS INTERIOR - AREAS A, B & C
SHEET INDEX - VOLUME 1
GENERAL
G-001A SHEET INDEX - VOLUME 1
G-003 CODE ANALYSIS
G-004A ROOM OCCUPANCY CLASSIFICATIONS
G-004B OCCUPANCY PLANS
G-005A LIFE SAFETY PLAN - AREA A
G-005A2 LIFE SAFETY PLANS - AREA A2
G-005B LIFE SAFETY PLANS - AREA B & C
G-006A LIFE SAFETY PLAN - LOW CATWALK
G-007A LIFE SAFETY PLAN - UPPER CATWALK
CIVIL
C100 CIVIL LEGEND AND ABBREVIATIONS
VF101 EXISTING CONDITIONS
GC121 SURVEY CONTROL PLAN
GC141 CONSTRUCTION ACCESS & LOCATION PLAN
GC145 CONSTRUCTION OPERATION PLAN NOTES
BB101 PLAN & LOG OF SOIL BORINGS
EC101 EROSION CONTROL PLAN
EC501 EROSION CONTROL DETAILS
CD101 DEMOLITION PLAN
CS111 SITE PLAN
CS121 ENLARGED SITE AND PAVING PLAN - AREAS 1 & 2
CS122 ENLARGED SITE AND PAVING PLAN - AREA 3
CS501 SITE DETAILS
CS502 SITE DETAILS
CS503 SITE DETAILS
CS504 SITE DETAILS
CG121 ENLARGED GRADING & DRAINAGE PLAN - AREAS 1 & 2
CG122 ENLARGED GRADING & DRAINAGE PLAN - AREA 3
CU101 ENLARED UTILITY PLAN - AREA 3
CU501 UTILITY DETAILS
CU502 UTILITY DETAILS
STRUCTURAL
S-001 NOTES, SYMBOLS, AND ABBREVIATIONS
S-002 NOTES, SYMBOLS, AND ABBREVIATIONS
S-005 STATEMENT OF SPECIAL INSPECTIONS
S-006 STRUCTURAL STEEL SPECIAL INSPECTIONS
S-007 MASONRY AND STEEL DECK SPECIAL INSPECTIONS
S-008 STRUCTURAL PROJECT KEYNOTES
S-010 ROOF LOADING PLAN
S-052A EXISTING BOTTOM CHORD FRAMING PLAN - AREA A
S-053A EXISTING ROOF FRAMING PLAN - AREA A
SD101A FOUNDATION AND FLATWORK DEMOLITION PLAN - AREA A
SD101B FOUNDATION AND FLATWORK DEMOLITION PLAN - AREA B
SD101C FOUNDATION AND FLATWORK DEMOLITION PLAN - AREA C
SD101C2 FOUNDATION AND FLATWORK DEMOLITION PLAN - MINOR
CONSTRUCTION - AREA C2
SD131B STRUCTURAL DEMOLITION FLOOR PLAN - AREA B
SD131C STRUCTURAL DEMOLITION FLOOR PLAN - AREA C
SD152A BOTTOM CHORD FRAMING DEMOLITION PLAN - AREA A
S-101A FOUNDATION PLAN - AREA A
S-101A2 FOUNDATION PLANS - AREA A2
S-101B FOUNDATION PLAN - AREA B
S-101B2 FOUNDATION PLAN - MINOR CONSTRUCTION - AREA B2
S-101C FOUNDATION PLAN - AREA C
S-101C2 FOUNDATION PLAN - MINOR CONSTRUCTION - AREA C2
S-111A FLATWORK PLAN - AREA A
S-111A2 FLATWORK PLANS - AREA A2
S-111B FLATWORK PLAN - AREA B
S-111B2 FLATWORK PLAN - MINOR CONSTRUCTION - AREA B2
S-111C FLATWORK PLAN - AREA C
S-111C2 FLATWORK PLAN - MINOR CONSTRUCTION - AREA C2
S-131A STRUCTURAL FLOOR PLAN - AREA A
S-131A2 STRUCTURAL FLOOR PLANS - AREA A2
S-131B STRUCTURAL FLOOR PLAN - AREA B
S-131B2 STRUCTURAL FLOOR PLAN - MINOR CONSTRUCTION - AREA
B2
S-131C STRUCTURAL FLOOR PLAN - AREA C
S-142A MEZZANINE FRAMING PLAN - AREA A
S-142A2 MEZZANINE FRAMING PLANS - AREA A2
S-151B ROOF FRAMING PLAN - AREA B
S-151C ROOF FRAMING PLAN - AREA C
S-151C2 ROOF FRAMING PLAN - MINOR CONSTRUCTION - AREA C2
S-152A BOTTOM CHORD FRAMING PLAN - AREA A
S-153A ROOF FRAMING PLAN - AREA A
S-153B2 HIGH ROOF FRAMING PLAN - MINOR CONSTRUCTION - AREA
B2
S-153C2 HIGH ROOF FRAMING PLAN - MINOR CONSTRUCTION - AREA
C2
S-301 SECTIONS
S-411 ENLARGED FLATWORK PLANS
S-431 ENLARGED STRUCTURAL FLOOR PLANS
S-441 ENLARGED FRAMING PLAN AND DETAILS
S-501 FOUNDATION DETAILS
S-502 FOUNDATION DETAILS
S-511 FLATWORK DETAILS
S-512 FLATWORK DETAILS
S-521 WALL DETAILS
S-522 WALL DETAILS
S-541 FRAMING DETAILS
S-542 FRAMING DETAILS
S-543 FRAMING DETAILS
S-544 FRAMING DETAILS
S-545 FRAMING DETAILS
S-551 FRAMING DETAILS
S-552 FRAMING DETAILS
S-601 STRUCTURAL SCHEDULES
Sheets in Volume: 90
SHEET INDEX - VOLUME 3
GENERAL
G-001C SHEET INDEX - VOLUME 3
FIRE ALARM
FA001 NOTES & SYMBOLS
FAD101 FIRE ALARM OVERALL DEMO PLAN
FA102 FIRE ALARM AND MNS FLOOR PLAN HANGAR
FA103 FIRE ALARM AND MNS FLOOR PLAN NORTH WING
FA104 FIRE ALARM AND MNS ENLARGED FLOOR PLAN EAST WING
FA105 FIRE ALARM AND MNS RISER DIAGRAM AND MATRIX
FIRE PROTECTION
FX001 NOTES & SYMBOLS
FXD101 FIRE PROTECTION HANGAR DEMO PLAN
FXD102 FIRE PROTECTION DEMO PLAN NORTH WING
FX101 DESIGN DENSITY PLAN HANGAR
FX102 DESIGN DENSITY NORTH WING
FX102B2 DESIGN DENSITY PLAN - AREA B2 - MINOR CONSTRUCTION
FX103 FIRE PROTECTION HANGAR FLOOR PLAN
FX104 FIRE PROTECTION FIRE PUMP ROOM
FX105 FIRE PROTECTION SPRINKLER ROOM
PLUMBING
P-001 PLUMBING NOTES & SYMBOLS
PD100B UNDERGROUND DRAIN AND VENT DEMO PLUMBING PLAN - AREA B
PD100C UNDERGROUND DRAIN AND VENT DEMO PLUMBING PLAN - AREA C
PD101A ABOVEGROUD DRAIN AND VENT DEMO PLUMBING PLAN - AREA A
PD101B ABOVEGROUND DRAIN AND VENT DEMO PLUMBING PLAN - AREA B
PD101C ABOVEGROUND DRAIN AND VENT DEMO PLUMBING PLAN - AREA C
PD102A ROOF - DRAIN AND VENT DEMO PLUMBING PLAN - AREA A
PD102B ROOF - DRAIN AND VENT DEMO PLUMBING PLAN - AREA B
PD102C ROOF - DRAIN AND VENT DEMO PLUMBING PLAN - AREA C
PD131A SUPPLY DEMO PLUMBING PLAN - AREA A
PD131B SUPPLY DEMO PLUMBING PLAN - AREA B
PD131C SUPPLY DEMO PLUMBING PLAN - AREA C
P-100A2 UNDERGROUND DRAIN AND VENT PLUMBING PLAN - HANGAR SHOPS
P-100B UNDERGROUND DRAIN AND VENT PLUMBING PLAN - AREA B
P-100B2 UNDERGROUND DRAIN AND VENT PLUMBING PLAN - AREA B2
P-100C UNDERGROUND DRAIN AND VENT PLUMBING PLAN - AREA C
P-101A DRAIN AND VENT PLUMBING PLAN - AREA A
P-101A2 DRAIN AND VENT PLUMBING PLAN - HANGAR SHOPS
P-101B DRAIN AND VENT PLUMBING PLAN - AREA B
P-101B2 DRAIN AND VENT PLUMBING PLAN - AREA B2
P-101C DRAIN AND VENT PLUMBING PLAN - AREA C
P-102A ROOF - DRAIN AND VENT PLUMBING PLAN - AREA A
P-102B ROOF - DRAIN AND VENT PLUMBING PLAN - AREA B
P-102B2 ROOF - DRAIN AND VENT PLUMBING PLAN - AREA B2
P-102C ROOF - DRAIN AND VENT PLUMBING PLAN - AREA C
P-131A SUPPLY PLUMBING PLAN - AREA A
P-131A2 SUPPLY PLUMBING PLANS - HANGAR SHOPS
P-131B SUPPLY PLUMBING PLAN - AREA B
P-131C SUPPLY PLUMBING PLAN - AREA C
P-501 PLUMBING DETAILS
P-502 PLUMBING DETAILS
P-601 PLUMBING SCHEDULES
P-602 PLUMBING SCHEDULES
P-901 DRAIN AND VENT ISOMETRIC PLUMBING DIAGRAM
P-931 SUPPLY ISOMETRIC PLUMBING PLAN
MECHANICAL
M-001 MECHANICAL NOTES & SYMBOLS
MD101A HVAC DEMOLITION FLOOR PLAN - AREA A
MD101B HVAC DEMOLITION FLOOR PLAN - AREA B
MD101C HVAC DEMOLITION FLOOR AND ROOF PLAN - AREA C
MD105A HVAC DEMOLITION ROOF PLAN - AREA A
MD105B HVAC DEMOLITION ROOF PLAN - AREA B
MD131A MECHANICAL PIPING DEMOLITION FLOOR PLAN - AREA A
MD131B MECHANICAL PIPING DEMOLITION FLOOR PLAN - AREA B
MD131C MECHANICAL PIPING DEMOLITION FLOOR PLAN - AREA C
MD401 ENLARGED DEMOLITION PLANS - AREA B AND AREA C
M-101A HVAC FLOOR PLAN - AREA A
M-101A2 HVAC FIRST FLOOR PLAN - AREA A2
M-101B HVAC FLOOR PLAN - AREA B
M-101B2 HVAC FLOOR PLAN - MINOR CONSTRUCTION AREA B2
M-101C HVAC FLOOR AND ROOF PLAN - AREA C
M-102A2 HVAC MEZZANINE PLANS - AREA A2
M-105A HVAC ROOF PLAN - AREA A
M-105B HVAC ROOF PLAN - AREA B
M-131A MECHANICAL PIPING FLOOR PLAN - AREA A
M-131A2 MECHANICAL FIRST FLOOR PLAN - AREA A2
M-131B MECHANICAL PIPING FLOOR PLAN - AREA B
M-131B2 MECHANICAL FLOOR PLAN - MINOR CONSTRUCTION AREA B2
M-131C MECHANICAL PIPING FLOOR PLAN - AREA C
M-132A2 MECHANICAL MEZZANINE PLANS - AREA A2
M-401 ENLARGED PLANS - AREA B, AREA C AND AREA D
M-501 MECHANICAL DETAILS
M-502 MECHANICAL DETAILS
M-503 MECHANICAL DETAILS
M-504 MECHANICAL DETAILS
M-601 MECHANICAL SCHEDULES
M-602 MECHANICAL SCHEDULES
M-603 MECHANICAL SCHEDULES
M-604 MECHANICAL SCHEDULES
M-605 MECHANICAL SCHEDULES
M-606 MECHANICAL SCHEDULES
M-607 MECHANICAL SCHEDULES
M-608 MECHANICAL SCHEDULES
M-609 MECHANICAL SCHEDULES
M-711 MECHANICAL SCHEMATICS
M-712 MECHANICAL SCHEMATICS
M-801 MECHANICAL CONTROL SCHEMATICS
M-802 MECHANICAL CONTROL SCHEMATICS
M-803 MECHANICAL CONTROL SCHEMATICS
M-804 MECHANICAL CONTROL SCHEMATICS
M-805 MECHANICAL CONTROL SCHEMATICS
Sheets in Volume: 96
SHEET INDEX - VOLUME 4
GENERAL
G-001D SHEET INDEX - VOLUME 4
ELECTRICAL
E-001 NOTES, SYMBOLS & ABBREVIATIONS
ED101A FIRST FLOOR ELECTRICAL DEMOLITON PLAN - AREA A
ED101B FIRST FLOOR ELECTRICAL DEMOLITON PLAN - AREA B
ED101C FIRST FLOOR & ROOF ELECTRICAL DEMOLITION PLAN - AREA C
ED102A MEZZANINE FLOOR & CATWALK LEVEL ELECTRICAL DEMOLITION PLAN - AREA A
ED102B ROOF ELECTRICAL & LIGHTNING PROTECTION DEMOLITION PLAN - AREA B
ED103A ROOF ELECTRICAL & LIGHTNING PROTECTION DEMOLITION PLAN - AREA A
ED701 DEMOLITION ONE-LINE DIAGRAM
E-100A HAZARDOUS AREA CLASSIFICATION PLAN
E-101A FIRST FLOOR POWER PLAN - AREA A
E-101A2 FIRST FLOOR POWER PLAN - AREA A2
E-101B FIRST FLOOR POWER PLAN - AREA B
E-101B2 FIRST FLOOR POWER PLAN - MINOR CONSTRUCTION - AREA B2
E-101C FIRST FLOOR & ROOF POWER PLAN - AREA C
E-102A MEZZANINE FLOOR & CATWALK LEVEL POWER PLAN - AREA A
E-103A ROOF POWER & LIGHTNING PROTECTION PLAN - AREA A
E-103B ROOF POWER & LIGHTNING PROTECTION PLAN - AREA B
E-103B2 ROOF POWER & LPS PLAN - MINOR CONSTRUCTION - AREA B2
E-121A FIRST FLOOR LIGHTING PLAN - AREA A
E-121A2 FIRST FLOOR LIGHTING PLAN - AREA A2
E-121B FIRST FLOOR LIGHTING PLAN - AREA B
E-121B2 FIRST FLOOR LIGHTING PLAN - MINOR CONSTRUCTION - AREA B2
E-121C FIRST FLOOR LIGHTING PLAN - AREA C
E-122A MEZZANINE FLOOR & CATWALK LEVEL LIGHTING PLAN - AREA A
E-401 ENLARGED POWER & DEMOLITION PLANS
E-402 ENLARGED POWER PLANS
E-403 ENLARGED PLANS
E-404 ENLARGED PHOTOS
E-405 ENLARGED PHOTOS
E-501 ELECTRICAL DETAILS
E-502 ELECTRICAL DETAILS
E-601 LUMINAIRE SCHEDULES
E-602 LIGHTING CONTROL SCHEDULES & CONTROLS NARRATIVE
E-603 EQUIPMENT WIRING SCHEDULES
E-604 EQUIPMENT WIRING SCHEDULES
E-605 PANEL SCHEDULES
E-606 PANEL SCHEDULES
E-607 PANEL SCHEDULES
E-608 PANEL SCHEDULES
E-701 ONE-LINE DIAGRAM
E-702 ONE-LINE DIAGRAM
TECHNOLOGY SYSTEMS
T-001 NOTES, SYMBOLS & ABBREVIATIONS
TD101A FIRST FLOOR TECHNOLOGY DEMOLITION PLAN - AREA A - HANGAR
TD101B FIRST FLOOR TECHNOLOGY DEMOLITION PLAN - AREA B - NORTH WING
TD101C FIRST FLOOR & ROOF TECHNOLOGY DEMOLITION PLAN - AREA C - EAST WING
TD102A MEZZANINE FLOOR & CATWALK LEVEL TECHNOLOGY DEMOLITION PLAN - AREA A - HANGAR
TD103A ROOF TECHNOLOGY DEMOLITION PLAN - AREA A - HANGAR
T-100 TECHNOLOGY SITE PLAN
T-101A FIRST FLOOR - AREA A - TECHNOLOGY SYSTEMS
T-101A2 HANGAR SHOP - AREA A2 - TECHNOLOGY SYSTEMS
T-101B FIRST FLOOR - AREA B - TECHNOLOGY SYSTEMS
T-101B2 FIRST FLOOR - AREA B2 - TECHNOLOGY SYSTEMS
T-101C FIRST FLOOR - AREA C - TECHNOLOGY SYSTEMS
T-102 MEZZANINE PLANS - TECHNOLOGY SYSTEMS
T-103A ROOF TECHNOLOGY PLAN - AREA A
T-121A FIRST FLOOR - AREA A - SECURITY
T-121A2 HANGAR SHOP - AREA A2 - SECURITY SYSTEMS
T-121B FIRST FLOOR - AREA B - SECURITY
T-121B2 FIRST FLOOR - AREA B2 - SECURITY
T-121C FIRST FLOOR - AREA C - SECURITY
T-123A ROOF SECURITY PLAN - AREA A
T-401 ENLARGED PLANS
T-402 ENLARGED PLANS
T-403 ENLARGED PLANS
T-404 ENLARGED PLANS
T-405 ENLARGED PLANS
T-501 DETAILS
T-502 DETAILS
T-503 DETAILS
T-701 ONE-LINE DIAGRAMS
Sheets in Volume: 71
M
VFD
RACEWAY SYMBOLS
SURFACE MOUNTED CONDUIT
JUNCTION BOX - CEILING MOUNTED
CONCEALED CONDUIT IN CEILING OR WALL
WIREWAY, SIZE AND TYPE
AS INDICATED ON DRAWINGS
JUNCTION BOX - WALL MOUNTED
J
J
JUNCTION BOX - WALL MOUNTED
SECURITY ACCESS DOOR POWER
JACD
RECEPTACLE SYMBOLS
DUPLEX RECEPTACLE TEXT INDICATES MOUNTING HEIGHT
CEILING MOUNTED DOUBLE DUPLEX RECEPTACLE
SPLIT WIRED DUPLEX RECEPTACLE
SIMPLEX RECEPTACLE
DOUBLE DUPLEX RECEPTACLE
SPECIAL PURPOSE CONNECTION, SEE EQUIPMENT
WIRING SCHEDULE
WELDING RECEPTACLE
DISCONNECT/WELDING RECEPTACLE
DISCONNECT/WELDING RECEPTACLE, NEMA 4X
MULTI-OUTLET SURFACE RACEWAY -
REFER TO KEYED NOTES &
SPECIFICATIONS FOR TYPES
CEILING MOUNTED DUPLEX RECEPTACLE
CEILING MOUNTED SPECIAL PURPOSE
CONNECTION, SEE EQUIPMENT WIRING
SCHEDULE
ABOVE COUNTER DUPLEX RECEPTACLE. MOUNT 6" TO
CENTERLINE ABOVE COUNTER OR BACKSPLASH
EMERGENCY SHADING MODIFIER
C
F FLOOR BOX
P POKE THRU
C
C
60"
DENOTES SWITCH LEG FOR SWITCHED OUTLETSa
RECEPTACLE & FLOOR BOX NOTATIONS:
DENOTES HORIZONTALLY MOUNTED OUTLETSH
DENOTES TAMPER RESISTANT SAFETY OUTLETSTR
DENOTES WEATHER PROOF OUTLETSWP
DENOTES EXPLOSION PROOF CLASS 1 DIVISION 2 DEVICEX2
DENOTES EXPLOSION PROOF CLASS 1 DIVISION 1 DEVICEX1
DENOTES GROUND FAULT INTERRUPTER OUTLETSGFCI
DENOTES COMBINATION DUPLEX/USB OUTLETSUSB
DENOTES ISOLATED GROUND OUTLETSIG
DENOTES ELECTRIC WATER COOLER OUTLETSEWC
4X
CORD REELE
CONTACTORC
DENOTES 28VDC, 30A, 2P, 3W (NEMA FSL1-R)28V
DENOTES RECEPTACLE FOR WALL MOUNT TV (96" AFF)TV
DENOTES GROUND JACK, RATED 30A.G
DENOTES 120/208V, 400HZ, 30A, 4P (NEMA FSL4-R)4HZ
DENOTES OCCUPANCY CONTROLLED OUTLETSOC
MOUNT AT 6" TO CENTER ABOVE COUNTER/BACKSPLASHA
DENOTES NEMA 5-15R DUPLEX RECEPTACLED
CR
HOSE REEL FOR AIR OR EXHAUSTE HR
SERVICE & DISTRIBUTION SYMBOLS
GROUND ROD
GROUNDING CONDUCTORG
NEW PANELBOARD
EXISTING PANELBOARD
EMERGENCY POWER OFFEPO
LIGHTNING ROD
STATIC GROUND RECEPTACLE
GR
CONTACTORC
PUSH BUTTON
M2 - MOMENTARY CONTACT, TWO BUTTON SWITCH.
P
EQUIPMENT GROUND BUSEGB
CONNECTION TO GROUNDING
ELECTRODE
PANEL DESIGNATION KEY
FLOOR
2 L N L 1
TYPE
SYSTEM/SOURCE
VOLTAGE
SEQUENCE NUMBER OR LETTER
NUMBER OR LETTER IN SEQUENCE
I.E. 1,2,3 OR A,B,C
L - 208Y/120V H - 480Y/277V
N - NORMAL BRANCH
U - UNINTERRUPTIBLE SOURCE
E - EMERGENCY BRANCH (NEC 700)
L - LIGHTING PANELBOARD
D - DISTRIBUTION PANELBOARD
P - POWER/EQUIPMENT PANELBOARD
R - RECEPTACLE PANELBOARD
MSB - MAIN SWITCHBOARD
1 - FIRST FLOOR
M - MEZZANINE
MOTOR & EQUIPMENT CONNECTION SYMBOLS
1 PHASE MOTOR CONNECTION
EQUIPMENT CONNECTION
3 PHASE MOTOR CONNECTION
COMBINATION MAGNETIC MOTOR CONTROLLER
MANUAL MOTOR CONTROLLER (3 PHASE)
MAGNETIC MOTOR CONTROLLER
NON-FUSED DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
MOTOR RATED SWITCH WITH OVERLOADS
VARIABLE FREQUENCY MOTOR CONTROLLER
GENERAL SYMBOLS
KEYED NOTE, USED TO DESCRIBE ADDITIONAL
INFORMATION OF WORK REQUIRED, SPECIFIC TO
THE SHEET AND/OR DETAIL IT IS SHOWN WITH.
DETAIL NUMBER / SHEET NUMBER#/E-###
9.###
# KITCHEN EQUIPMENT TAG. # REFERS TO
CORRESPONDING NUMBER IN KITCHEN
EQUIPMENT SCHEDULE.
LINE TYPE KEY
EXISTING TO BE REMOVED BY THIS
CONTRACTOR (DARK DASHED LINE)
EXISTING TO REMAIN WORK
(THIN SOLID LINE)
NEW WORK BY THIS CONTRACTOR
(DARK SOLID LINE)
NEW WORK UNDER FLOOR BY
THIS CONTRACTOR
ONE-LINE EQUIPMENT ENCLOSURE
PANEL DIVISION LINES
SITE UNDERGROUND ELECTRICE
SITE REMOVED UNDERGROUND
ELECTRIC
//E//
SINGLE POLE SWITCH
LUMINAIRE CONTROL SYMBOLS
PHOTO ELECTRIC CONTROL
OCCUPANCY SENSOR CEILING MOUNT
DAYLIGHT SENSOR
LIGHTING CONTROL PANEL
(x REPRESENTS PANEL DESIGNATION)
LUMINAIRE SYMBOLS
RECESSED LUMINAIRE
RECESSED TROFFER
RECESSED LINEAR
WALL MOUNTED EXIT SIGN
CEILING MOUNTED EXIT SIGN
UL 924 LISTED EMERGENCY LIGHTING BYPASS
CONTROL UNIT
OS X
DS
PE
LCP X
PT
ARROW DENOTES EXIT SIGN CHEVRON
EMERGENCY BATTERY UNIT
REMOTE POWER SUPPLY OR DRIVERPS
LOW VOLTAGE SWITCH
* DENOTES SWITCH NAME, SEE LIGHTING
CONTROL PANEL & SWITCH SCHEDULE.
L
SWITCH NOTATIONS:
3 DENOTES 3-WAY SWITCH
4 DENOTES 4-WAY SWITCH
WL DENOTES WET LOCATION SWITCH
D DENOTES WALL BOX DIMMER SWITCH
T DENOTES TIMER SWITCH
K DENOTES KEY SWITCH
P DENOTES PILOT SWITCH
OS DENOTES OCCUPANCY SENSOR
X1 DENOTES EXPLOSION PROOF CLASS 1 DIVISION 1 SWITCH
X2 DENOTES EXPLOSION PROOF CLASS 1 DIVISION 2 SWITCH
M MOMENTARY CONTACT SWITCH
C MAINTAINED CONTACT, THREE POSITION, CENTER OFF
F FAN SPEED CONTROL SWITCH
WALL WASH MODIFIER
EMERGENCY SHADING MODIFIER
PENDANT INDUSTRIAL
WALL BRACKET
WALL SURFACE LINEAR
RECESSED EMERGENCY BATTERY UNIT
SURFACE LINEAR/INDUSTRIAL LUMINAIRE
A1
1R#a
LUMINAIRE TYPE
LUMINAIRE CIRCUITRY & CONTROL KEY:
LOWER CASE LETTER INDICATES SWITCHLEG CONTROL
(R#) INDICATES CENTRALIZED LOW VOLTAGE RELAY NUMBER
(Z#) INDICATES DISTRIBUTED LOW VOLTAGE RELAY NUMBER
REFER TO LIGHTING CONTROL PANEL SCHEDULES
NUMBER INDICATES BRANCH PANEL CIRCUIT NUMBER
SE
SE: DENOTES LUMINAIRE IS SWITCHED/CONTROLLED DURING
NORMAL OPERATION AND OPERATES FROM EMERGENCY
BATTERY AND/OR EMERGENCY CIRCUIT UPON LOSS OF POWER.
NL: DENOTES LUMINAIRE IS UNSWITCHED FOR NIGHT LIGHT.
SURFACE ROUND LUMINAIRE
PENDANT ROUND LUMINAIRE
SITE SYMBOLS
ELECTRIC HANDHOLE
HH HANDHOLE, GENERIC
E
E ELECTRIC MANHOLE
TRANS
ELECTRIC TRANSFORMER
DEMOLITION GENERAL NOTES:
1. THE INFORMATION SHOWN IS BASED ON EXISTING DRAWINGS
AND SITE OBSERVATIONS TO ASSIST CONTRACTOR IN BIDDING.
THE ELECTRICAL DRAWINGS INDICATE EXISTING ELECTRICAL
ITEMS TO BE REMOVED. THE DRAWINGS ARE INTENDED TO
INDICATE THE SCOPE OF WORK REQUIRED AND DO NOT INDICATE
EVERY BOX, CONDUIT, OR WIRE THAT MUST BE REMOVED. THE
CONTRACTOR SHALL VISIT THE SITE PRIOR TO SUBMITTING A BID
AND VERIFY EXISTING CONDITIONS. REFER TO SPECIFICATIONS
FOR ADDITIONAL REQUIREMENTS.
2. DASHED WALLS ON THE FLOOR PLANS INDICATE EXISTING WALLS
BEING DEMOLISHED. REFER TO THE ARCHITECTURAL
DEMOLITION PLANS FOR THE EXACT EXTENT OF WORK REQUIRED
BY THIS PROJECT. REMOVE ALL DEVICES ON DASHED WALLS NOT
SHOWN ON THE CONTRACT DRAWINGS. REFER TO DEMOLITION
DRAWINGS OF OTHER TRADES. WHERE MOTORS CONTROL
PANELS, AND OTHER LOADS OR APPARATUS THAT HAVE
ELECTRICAL CONNECTION ARE BEING REMOVED, INCLUDE
DISCONNECTION AND REMOVAL OF ALL ASSOCIATED CONDUIT,
WIRING, ETC.
3. ELECTRICAL ITEMS (i.e., LIGHTING FIXTURES, PANELBOARDS, DISCONNECTS, MOTOR CONTROLLERS , ETC.) REMOVED AND
NOT RELOCATED REMAIN THE PROPERTY OF THE OWNER AND
SHALL BE TURNED OVER TO THE OWNER, IN A STORAGE AREA TO
BE DESIGNATED BY THE OWNER. EQUIPMENT BEING REMOVED
SHALL BE HANDLED SO AS NOT TO FURTHER REDUCE ITS VALUE
TO THE OWNER. THE CONTRACTOR SHALL DISPOSE OF
MATERIAL THE OWNER DOES NOT WANT TO REUSE OR RETAIN
FOR MAINTENANCE PURPOSES.
4. WHERE LIGHTS, SWITCHES, RECEPTACLES, ETC., ARE BEING
REMOVED ALL ASSOCIATED CONDUIT AND WIRE BACK TO THE
PANELBOARD OR FEEDER JUNCTION BOX SERVING THE DEVICE
SHALL ALSO BE REMOVED, UNLESS THE CONDUIT CAN BE
REUSED FOR NEW CONDUCTORS. THE CONTRACTOR SHALL
DISPOSE OF MATERIAL THE OWNER DOES NOT WANT TO REUSE
OR RETAIN FOR MAINTENANCE PURPOSES.
5. ALL BOXES THAT REMAIN IN PLACE IN EXISTING MASONRY WALLS
THAT ARE TO REMAIN SHALL BE PROVIDED WITH A BLANK
COVERPLATE. REFER TO SPECIFICATIONS FOR ADDITIONAL
REQUIREMENTS ASSOCIATED WITH TYPE AND ATTACHMENT.
6. ALL CONDUIT SHALL BE REMOVED WHERE WALLS ARE BEING
REMOVED. WHERE CONDUIT IS IN THE CONCRETE SLAB, CUT OFF
FLUSH, PULL OUT WIRE, AND PLUG. WHERE CONDUIT IS RUN
EXPOSED, ALL ASSOCIATED CLAMPS, SUPPORTS, HANGERS,
ETC., SHALL ALSO BE REMOVED. CONDUIT CONCEALED IN WALL
CONSTRUCTION MAY BE ABANDONED IN PLACE IF NOT AFFECTED
BY OTHER CONSTRUCTION.
7. THIS CONTRACTOR SHALL COORDINATE ALL HIS WORK,
INCLUDING PHASING WITH OTHER CONTRACTORS AT THE JOB
SITE BEFORE REMOVING EXISTING ELECTRICAL AND INSTALLING
NEW ITEMS.
8. EXISTING CONDUIT IN GOOD CONDITION, MAY BE REUSED IN
PLACE. RELOCATED EXISTING CONDUIT SHALL NOT BE ALLOWED.
BONDING CONDUCTORS SHALL BE INSTALLED IN ALL REUSED
CONDUIT TO ASSURE PROPER GROUND PATH.
9. MAINTAIN CIRCUIT CONTINUITY OF DEVICES LOCATED OUTSIDE
OF CONSTRUCTION AREA. DEVICE AND EQUIPMENT REMOVAL IN
CERTAIN LOCATIONS MAY REQUIRE THE INSTALLATION OF A
JUNCTION BOX TO RECONNECT CIRCUITS THAT REMAIN IN
OPERATION. EXTEND CONDUIT AND WIRING AS REQUIRED TO
MAINTAIN POWER TO REMAINING EQUIPMENT.
10. BALLASTS MANUFACTURED PRIOR TO 1980 CONTAIN PCBs AND
SHALL BE DISPOSED OF IN ACCORDANCE WITH SPECIFICATIONS.
11. HID AND FLUORESCENT LAMPS CONTAIN MERCURY AND SHALL
BE DISPOSED OF IN ACCORDANCE WITH SPECIFICATIONS.
12. CONTRACTOR SHALL REMOVE AND INSTALL ALL CEILING TILES
AS REQUIRED FOR THE EXECUTION OF ELECTRICAL WORK THAT
IS OUTSIDE THE CONTRACT LIMITS OF CONSTRUCTION.
CONTRACTOR SHALL REPLACE CEILING TILES WITH IDENTICAL
MATERIAL WHERE DAMAGED BY THIS CONTRACTOR.
13. PROVIDE REVISED TYPED CIRCUIT DIRECTORY IN
PANELBOARDS THAT HAVE CIRCUITS REMOVED OR ADDED
CIRCUITS.
14. REMOVE EXPOSED ABANDONED CONDUIT, INCLUDING
ABANDONED CONDUIT ABOVE ACCESSIBLE CEILING FINISHES.
CUT RACEWAY FLUSH WITH WALLS AND FLOORS, PATCH
SURFACES TO MATCH EXISTING. REMOVE ALL ASSOCIATED
CLAMPS, HANGERS, SUPPORTS, ETC. ASSOCIATED WITH
RACEWAY REMOVAL.
15. DISCONNECT AND REMOVE ABANDONED LUMINAIRES,
INCLUDING BRACKETS, STEMS, HANGERS, AND OTHER
ACCESSORIES.
16. DISCONNECT AND REMOVED ELECTRICAL DEVICES AND
EQUIPMENT SERVING UTILIZATION EQUIPMENT THAT HAS BEEN
REMOVED.
GENERAL NOTES:
1. REFER TO THE G SERIES DRAWINGS FOR CODE ANALYSIS PLANS,
INFORMATION AND NOTES.
2. THE CONTRACTOR SHALL BECOME FAMILIAR WITH THE DETAILS OF
WORK, VERIFY DIMENSIONSIN THE FIELD, AND ADVISE THE
CONTRACTING OFFICER OF ANY DISCREPANCY BEFORE PERFORMING
ANY WORK.
3. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE ABA
(ARCHITECTURAL BARRIERS ACT).
4. REFER TO ARCHITECTUAL DRAWINGS FOR FIRE RATED WALLS AND
FLOORS. MAKE RATED PENETRATIONS AS REQUIRED.SEAL ALL RATED
PENETRATIONS AS IDENTIFIED IN DIVISION 1 REQUIREMENTS.
5. FLUSH MOUNT ALL TOGGLE SWITCHES AND RECEPTACLES AT HEIGHTS
ABOVE FINISHED FLOOR AS SHOWN IN THE DEVICE MOUNTING HEIGHT
DETAIL ON SHEET E-501, EXCEPT WHERE OTHERWISE NOTED. DEVICES
MAY BE SURFACE MOUNTED WHEN CONDUIT IS SPECIFIED EXPOSED.
6. CIRCUIT NUMBERS ARE SHOWN FOR CIRCUIT IDENTIFICATION.
CIRCUITING SHALL AGREE WITH NUMBERING ON THE PANEL SCHEDULES
PROVIDED. BALANCE THE LOAD ON PANELS AS EVENLY AS POSSIBLE
BETWEEN EACH PHASE.
7. CIRCUITS SERVING EMERGENCY AND EXIT LUMINAIRES WILL BE RUN IN
SEPARATE RACEWAY FROM ALL OTHER CIRCUITS.
8. A #12 GREEN INSULATED GROUND CONDUCTOR SHALL BE INSTALLED
WITH CIRCUIT CONDUCTORS TO ALL RECEPTACLES.
9. CONCEAL ALL CONDUIT IN WALLS, PARTITIONS, ABOVE CEILING, ETC.
UNLESS OTHERWISE INDICATED ON THE PLANS OR IN THE
SPECIFICATIONS. CONDUIT IN MECHANICAL ROOMS, AND STORAGE
ROOMS WITHOUT CEILINGS MAY BE EXPOSED ON BUILDING STRUCTURE.
WHERE RACEWAY IS REQUIRED ON EXISTING CONCRETE AND MASONY
WALLS, SURFACE RACEWAY MAY BE USED IN LIEU OF CHANNELING
WALLS TO ALLOW CONCEALED ROUTING. THE RACEWAY SHALL BE
SINGLE CHANNEL STYLE TYPE WITH IVORY FINISH. THIS APPLIES FOR
BRANCH CIRCUIT CONDUITS UP TO 3/4" SIZE. CONDUITS LARGER THAN
3/4" MAY BE ROUTED EXPOSED, BUT INSTALLED PARALLEL AND/OR
PERPENDICULAR TO BUIDLING LINES AND RUN AS UNOBTRUSIVLY AS
POSSIBLE.
10. BOXES LOCATED ON OPPOSITE SIDES OF NON-RATED WALLS SHALL BE
OFFSET A MINIMUM OF 6" HORIZONTALLY. "THRU-THE-WALL" BOXES
SHALL NOT BE ALLOWED WITHOUT PRIOR WRITTEN APPROVAL OF THE
ARCHITECT/ENGINEER.
11. COORDINATE AND CO-LOCATE WALL MOUNTED RECEPTACLE
LOCATIONS WITH TECHNOLOGY (VOICE/DATA,CATV,FIDS, ETC) OUTLETS
SHOWN ON THE T-SERIES DRAWINGS.UNLESS OTHERWISE NOTED, EACH
TECHNOLOGY OUTLET SHALL BE LOCATED WITHIN 6"OF ITS ASSOCIATED
RECEPTACLE. ASSOCIATED RECEPTACLE SHALL BE DEFINED AS THE
RECEPTACLE NEAREST THE LOCATION OF, AND AT THE SAME HEIGHT
AS,THE TECHNOLOGY OUTLET WHEN MULTIPLE RECEPTACLES ARE
SHOWN ON A WALL.
12. DUPLEX RECEPTACLES FOR ELECTRIC WATER COOLERS (EWC) SHALL
BE CONCEALED BEHIND WATER COOLER ACCESS PLATE OR BE
DIRECTLY BELOW AND CENTERED ON EWC. CONTRACTOR SHALL VERIFY
TYPE OF EWC TO BE INSTALLED.
13. CONTRACTOR SHALL VERIFY ALL FURNITURE, MODULAR FURNITURE
AND EQUIPMENT LOCATIONS WITH ARCHITECTURAL PLANS, ELEVATIONS
AND REVIEWED SHOP DRAWINGS. PRIOR TO MAKING THE ACTUAL
ELECTRICAL INSTALLATION THIS CONTRACTOR SHALL ADJUST
RECEPTACLES, OUTLETS OR CONNECTION LOCATIONS TO
ACCOMMODATE FURNITURE AND/OR EQUIPMENT.
14. ELECTRICAL AND TELECOMMUNICATIONS EQUIPMENT SHALL BE
MOUNTED TO AVOID IMPEDANCE OF, OPERATION OF, AND/OR ACCESS TO
ELECTRICAL AND MECHANICAL EQUIPMENT. ALL MOUNTING OF
ELECTRICAL AND TELECOMMUNICATIONS EQUIPMENT, ON EQUIPMENT
SUPPLIED BY ANOTHER CONTRACTOR, SHALL BE APPROVED IN ADVANCE
BY THE OTHER CONTRACTOR.
15. CONTRACTOR TO PROVIDE SUITABLE MECHANICAL PROTECTION
AROUND ALL CONDUITS STUBBED OUT FROM FLOORS, WALLS OR
CEILINGS DURING CONSTRUCTION TO PREVENT BENDING OR DAMAGING
OF STUB OUTS DUE TO CARELESSNESS WITH CONSTRUCTION
EQUIPMENT.
16. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OPENINGS REQUIRED
IN WALLS. ALL OPENINGS SHALL BE REPAIRED TO MATCH EXISTING BY A
QUALIFIED CONTRACTOR AT THE EXPENSE OF THIS CONTRACTOR. ALL
CONDUITS THROUGH WALLS SHALL BE GROUTED OR SEALED INTO
OPENINGS.
17. DRAWINGS INDICATE THE EXTENT OF HAZARDOUS OR WET LOCATIONS.
INSTALLATION MEANS AND METHODS SHALL BE SUITABLY RATED FOR
THE ENVIRONMENT INDICATED ON THE DRAWINGS.
18. CONTRACTOR SHALL REMOVE AND REINSTALL ALL CEILING TILES AS
REQUIRED FOR THE EXECUTION OF ELECTRICAL WORK THAT IS OUTSIDE
THE CONTRACT LIMITS OF CONSTRUCTION. CONTRACTOR SHALL
REPLACE CEILING TILES WITH IDENTICAL MATERIAL WHERE DAMAGED BY
THIS CONTRACTOR.
19. ALL INTERLOCKING REQUIRED BY THE DRIVE MANUFACTURER
BETWEEN THE VARIABLE FREQUENCY DRIVE AND THE DISCONNECT
SWITCHES SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL
CONTRACTOR.
20. SCCR RATINGS LISTED FOR EQUIPMENT ARE MINIMUM REQUIREMENTS
FOR BUS BRACING AND DEVICE RATING. ALL EQUIPMENT SHALL BE FULLY
RATED UNLESS SPECIFICALLY NOTED AS SERIES RATED.
21. SHADED LUMINAIRE OR DEVICE INDICATES LUMINIARE OR DEVICE IS
CONNECTED TO AN EMERGENCY CIRCUIT AND/OR OPERATES FROM
EMERGENCY BATTERY PACK INTERGAL TO FIXTURE OR LIGHTING
INVERTER.
22. ALL EMERGENCY BATTERY UNITS SHALL BE SERVED FROM AN
UNSWITCHED LEG OF THE LIGHTING BRANCH CIRCUIT SERVING THE
SPACE OR AREA.
23. MOUNT ALL OVERHEAD UTILITIES AND OTHER FIXTURES WEIGHING 31
POUNDS OR MORE (EXCLUDING DISTRIBUTED SYSTEMS SUCH AS PIPING
NETWORKS THAT COLLECTIVELY EXCEED THAT WEIGHT) USING EITHER
RIGID OR FLEXIBLE SYSTEMS TO MINIMIZE THE LIKELIHOOD THAT THEY
WILL FALL AND INJURE BUILDING OCCUPANTS. DESIGN ALL EQUIPMENT
MOUNTINGD TO RESIST FORCES OF 0.5 TIMES THE EQUIPMENT WEIGHT
IN ANY HORIZONTL DIRECTION AND 1.5 TIMES THE EQUIPMENT WEIGHT IN
THE DOWNWARD DIRECTION.
TEMPORARY FACILITIES WORK SCOPE:
REFER TO THE CIVIL DRAWINGS FOR THE LOCATION OF THE TEMPORARY
FACILITIES PORTABLE BUILDINGS. THE CONTRACTOR SHALL PROVIDE
TEMPORARY SERVICE FOR A MINIMUM OF 4 PORTABLE BUILDINGS. FOR
THE PURPOSES OF BIDDING ASSUME A 200A, 120/208V, 3-PHASE SERVICE
TO EACH BUILDING. COORDINATE WITH CONTRACT OFFICER FOR ROUTING
AND SOURCE OF SERVICE FEEDS.
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
ISSUED
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
710 Avis Drive, #100 Ann Arbor, MI 48108-9649 phone: 810-956-9300 fax: 810-956-9281
/1
/2
:1 :3
P
M C
R e v it L o c a l\
.0
-E -R k e ff .k u re lla Y
A
.r v t
NOTES, SYMBOLS &
ABBREVIATIONS
FJRP112701ANG PRO. NO.:
3258000-131303.01
KAF
MAM
July 20, 2022
KSK
N C
A N
G
T
H A
W
C H
A R
L O
T T
E D
O U
G L A
S I A
P C
H A
R L O
T T
E N
O R
T H
C A
R O
L
IN
A
R E
P A
IR
M
A
IN
T E
N A
N C
E H
A N
G A
R B
U
IL
D
IN
G
E-001
ELECTRICAL ABBREVIATIONS
SS STAINLESS STEEL
SW SWITCH
SWBK SWITCH BANK
TBR TO BE REMOVED
TCP TEMPERATURE CONTROL PANEL
TFA TO FLOOR ABOVE
TFB TO FLOOR BELOW
TYP TYPICAL
UC UNIT COOLER
UG UNDERGROUND
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
UV UNIT VENTILATER
V VOLTS
VER VEHICLE EXHAUST REEL
VFD VARIABLE FREQUENCY DRIVE
VS VERSUS
W WATTS
WCC WATER COOLED CONDENSER
WFE WELDING FUME EXTRACTOR
WH WATER HEATER
WL WET LOCATION LISTED
WP WEATHERPROOF
XFMR TRANSFORMER
XP EXPLOSION PROOF
ELECTRICAL ABBREVIATIONS
3R NEMA 3R RATING
4X NEMA 4X RATING
A AMPERES
A/E ARCHITECT / ENGINEER
AAC ABOVE ACCESSIBLE CEILING
ACCU AIR COOLED CONDENSING UNIT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
ALT ALTERNATE
APE AIRCRAFT PROCESS EQUIPMENT
ATS AUTOMATIC TRANSFER SWITCH
BLDG BUILDING
BRKR BREAKER
C CONDUIT
CB CIRCUIT BREAKER
CF CIRCULATION FAN
CH CHILLER
CHWP CHILLED WATER PUMP
CKT CIRCUIT
CP CIRCULATION PUMP
CRAC COMPUTER ROOM AIR CONDITIONER
CRP CONDENSATION RETURN
CT COOLING TOWER
CUH CABINET UNIT HEATER
DC DROP CORD
DDC DIGITAL CONTROL PANEL
DH DUCT HEATER
DISC DISCONNECT
DN DOWN
DO DOOR OPERATOR
DWG DRAWING
E/O ELECTRICAL-TO-OPTICAL CONVERTER
EC ELECTRICAL CONTRACTOR
ECB ENCLOSED CIRCUIT BREAKER
EF EXHAUST FAN
EM EMERGENCY
EMT ELECTRICAL METALLIC TUBING
ES EQUIPMENT SUPPLIER
ETR EXISTING TO REMAIN
EWC ELECTRICAL WATER COOLER
EWH ELECTRICAL WATER HEATER
F FUSED
FA FIRE ALARM
FAF FORCED AIR FURNACE
FCU FAN COIL UNIT
GC GENERAL CONTRACTOR
GFI GROUND FAULT INTERRUPTER
GND GROUND
GWH GAS WATER HEATER
HD HAND DRYER
HEF HEATER EXHAUST FAN (EXHAUSTER)
HP HORSEPOWER
HVAC HEATING, VENTILATION, AIR CONDITIONING
HWB HOT WATER BOILER
HWP HOT WATER PUMP
IEWH INSTANTANEOUS ELECTRIC WATER HEATER
IH INFRARED HEATER
IMC INTERMEDIATE METALLIC CONDUIT
IWH INSTANTANEOUS WATER HEATER
J-BOX JUNCTION BOX
LFS LIGHTING FIXTURE SCHEDULE
LPS LIGHTNING PROTECTION SYSTEM
MAU MAKE-UP AIR UNIT
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
MCC MOTOR CONTROL CENTER
MDF MAIN DISTRIBUTION FRAME
MDP MAIN DISTRIBUTION PANEL
MIN. MINIMUM
MNS MASS NOTIFICATION SYSTEM
MOD MOTOR OPERATED DOOR
MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NL/EL NIGHT LIGHT AND EMERGENCY LIGHT
NTS NOT TO SCALE
OC ON CENTER
OFCI OWNER FURNISHED, CONTRACTOR INSTALLED
OFOI OWNER FURNISHED, OWNER INSTALLED
PH PHASE
PNL PANEL
PS PROJECTION SCREEN
PVC POLYVINYL CHLORIDE
RCP RADIANT CEILING PANEL
RECPT RECEPTACLE
REF REFRIGERATOR
REQ'D REQUIRED
RF RETURN FAN
RGS RIGID GALVANIZED STEEL CONDUIT
MAY ALSO BE REFERENCED AS RMC OR GRC
RMC RIGID METAL CONDUIT
RTU ROOF TOP UNIT
S/N SOLID NEUTRAL
SE SERVICE ENTRANCE
SEC-P SECURITY PANEL
SF SUPPLY FAN
SP SUMP PUMP
F
F
GR
GR
GR GR
GR
GR
GR
GR
GR
GR
GR
GRGR
GR
GR
GR
GR
GR
GR GR
PP
P P
GR
P P
P P
P P
EB
EA
NA
H
G
10 9 8
E
D
C
B
A
11 7 6 5 4 3 2 1
F
J
K
E-401
HFF
UH-7
UH-8
EF-11
EF-10
UH-4
EF-4
EF-5
EF-6
EF-4
MDO
MDO
EF-7
EF-8
EF-9
UH-6
EF-12
UH-5
E-403
E-403
9.019
HEF 9.019
9.015
TYP. 9.019
9.014
9.012
TYP.
9.0199.019
C
C
C
C
C
9.022
TYP.
M2
M2 M2
M2
9.021 9.021
M A
T C
H L
IN
E
S E
E
E
D
B
M A
T C
H L
IN
E
S E
E
E
D C
MATCHLINE
SEE 1 / ED101B
M
ATC
H
LIN
E
SEE 1 / ED
101C
9.020
D
M2 M2
M2M2 M2
M2
9.021
9.021 9.021
9.021 9.021
9.021
DEMOLITION GENERAL NOTES:
1. REFER TO DRAWING E-001 FOR DEMOLITION GENERAL NOTES, SYMBOLS &
ABBREVIATIONS.
KEY PLAN
A
B
C
SHOP
SOUTH
SHOP
NORTH
B2
A2
A2
C2
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
ISSUED
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
710 Avis Drive, #100 Ann Arbor, MI 48108-9649 phone: 810-956-9300 fax: 810-956-9281
/1
/2
:1 :4
P
M C
R e v it L o c a l\
.0
-E -R k e ff .k u re lla Y
A
.r v t
FIRST FLOOR
ELECTRICAL
DEMOLITON PLAN -
AREA A
FJRP112701ANG PRO. NO.:
3258000-131303.01
KAF
MAM
July 20, 2022
KSK
N C
A N
G
T
H A
W
C H
A R
L O
T T
E D
O U
G L A
S I A
P C
H A
R L O
T T
E N
O R
T H
C A
R O
L
IN
A
R E
P A
IR
M
A
IN
T E
N A
N C
E H
A N
G A
R B
U
IL
D
IN
G
ED101A
1/16" = 1'-0"1
FIRST FLOOR ELECTRICAL DEMOLITON PLAN - AREA A
KEYED NOTES
9.012 DISCONNECT AND REMOVE FLOODLIGHT, SUPPORTS AND MOUNTING
BRACKETS. LIGHT SWITCH AND WIRING TO BE REMOVED BUT BACKBOX AND
CONDUIT TO REMAIN IN PLACE FOR NEW SWITCH AND WIRING AS SHOWN
ON DRAWING 1/E-121A. EXISTING LIGHTING BRANCH CIRCUIT WIRING TO BE
REMOVED BACK TO SOURCE. RACEWAY TO REMAIN IN PLACE FOR NEW
LIGHTING BRANCH WIRING TO NEW LIGHTING FIXTURE AS NOTED ON
DRAWING 1/E-121A.
9.014 DIVISION 26 CONTRACTOR TO DISCONNECT AND REMOVE POWER BACK TO
SOURCE. EQUIPMENT TO BE REMOVED BY DIVISION 23 CONTRACTOR.
9.015 EXHAUST FAN PILOT LIGHT CONTROL SWITCH. EC TO DISCONNECT AND
REMOVE BACK TO SOURCE.
9.019 OVERHEAD HANGER LIGHTING CONTROL. REMOVE SWITCHES AND WIRING
BACK TO LIGHTING CONTACTOR(S) LOCATED ABOVE PANELBOARD 'EH' IN
ELECTRICAL/MECHANICAL ROOM H103. BACKBOX AND CONDUIT TO REMAIN
IN PLACE AND UTILIZED FOR NEW OVERHEAD HANGER LIGHTING CONTROL.
REFER TO DRAWING 1/E-101A.
9.020 SURFACE MOUNTED CLASS 1, DIV. 2, 200A, 3 POLE, 4 WIRE, 600V
RECEPTACLE. DISCONNECT AND RELOCATE RECEPTACLE. EXTEND
EXISTING FEEDER AND CONDUIT (3#4/0 &1#6 GND. IN 2"C) TO NEW LOCATION
AS SHOWN ON DRAWING 1/E101A.
9.021 EXISTING TWO BUTTON DOOR CONTROL STATION TO BE DISCONNECTED
AND REMOVED INCLUDING WIRING. EXISTING FLUSH MOUNTED BACKBOX
AND CONDUIT TO MAIN CONTROL PANEL TO REMAIN IN PLACE FOR
INSTALLATION OF NEW DOOR KEY SWITCH, PUSHBUTTON CONTROL AS
SHOWN ON DRAWING 1/E-101A.
9.022 SURFACE MOUNTED RECEPTACLE, CLASS 1, DIVISION 2, RATED 200 A, 3
POLE, 4 WIRE, 460 V, 3 PHASE WITH GROUND.
3 3
OS
OS
OS
O S
3 3
OS
F
FF F F
F F
F F
F F
F F
F F
F F
F F
F F
F F
F F
J J J
J
F
F
P
P
M
P
P
E P
O
E P
O
EPO
E P
O
EPO
N9 N8 N7 N6 N5N4 N3 N2 N1
ND
NC
NB
NA
E-401
PANEL AC
PANEL NWLA
E P
O
BRIDGE
CRANE
48"
48"
48"
96"
CTV
96" 96"
96"
TV
96"
TV
96"
TV
96"
TV
PROJECTION
SCREEN
CTV
TV
TV CTV
96"
96"
96"96"
9.001
9.001
9.001
9.001
9.001
9.001
9.001
9.001
9.001
EH-3
EH-4
UH-4A
UH-3A
DODODO
UH-1AUH-2A
EH-2
HWP-1
CPH-2
BOILER
MZ-2
AIR DRYER
AIR COMPRESSORS
CHILLER-2
CHILLER-1
G
WP/GFCI
9.036
TCPHUMIDIFIER
DUPLEX
PANEL T2
48"
48"
UH-6A
CIRC PUMP
WTR HTR
9.031
9.029
28VDC
G
4HZ
D
9.030 9.030
9.030
TV
TV
9.035
WP/GFCI
9.029 9.032
4HZ
28DVC
D G D G
28VDC4HZ
28VDC 4HZ
GD
28VDC 4HZ
GD
4HZ28VDC
D G
9.030 9.030
9.029
FIRE SUPRESSION
COMPRESSOR
HEAT TRACE
HEAT TRACE
9.033
NWL-31,33
9.035
9.035
9.035
9.029
9.029
9.029
9.029EF-8A
EWC
EWC
GFCI
WP/GFCI
GFCI
UH-5A
CTV
(CLG MTD)
9.001
9.001
EF-7A
9.001
9.037
MATCHLINE
SEE 1 / ED101A
M
ATC
H
LI
N E
SEE 1
ED
1A
9.030
DEMOLITION GENERAL NOTES:
1. REFER TO DRAWING E-001 FOR DEMOLITION GENERAL NOTES, SYMBOLS &
ABBREVIATIONS.
KEY PLAN
A
B
C
SHOP
SOUTH
SHOP
NORTH
B2
A2
A2
C2
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
ISSUED
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
710 Avis Drive, #100 Ann Arbor, MI 48108-9649 phone: 810-956-9300 fax: 810-956-9281
/1
/2
:1 :5
P
M C
R e v it L o c a l\
.0
-E -R k e ff .k u re lla Y
A
.r v t
FIRST FLOOR
ELECTRICAL
DEMOLITON PLAN -
AREA B
FJRP112701ANG PRO. NO.:
3258000-131303.01
KAF
MAM
July 20, 2022
KSK
N C
A N
G
T
H A
W
C H
A R
L O
T T
E D
O U
G L A
S I A
P C
H A
R L O
T T
E N
O R
T H
C A
R O
L
IN
A
R E
P A
IR
M
A
IN
T E
N A
N C
E H
A N
G A
R B
U
IL
D
IN
G
ED101B1/8" = 1'-0"1
FIRST FLOOR ELECTRICAL DEMOLITON PLAN - AREA B
KEYED NOTES
9.001 REMOVE EXISTING SWITCH. UTILIZE EXISTING BACKBOX FOR NEW LIGHTING
CONTROL IN THIS AREA. REFER TO E-121B & E-121C FOR NEW LIGHTING
CONTROLS.
9.029 SURFACE MOUNTED RACEWAY CONSISTING OF THREE (3) SEPARATE
RACEWAYS ONE (1) FOR 120 VAC., 60HZ, ONE (1) FOR 28 VDC., ONE (1) FOR
120/208 VAC., 400 HZ POWER AND #2 GROUNDING CONDUCTOR.
DISCONNECT AND REMOVE COMPLETELY INCLUDING BRANCH CIRCUIT
WIRING BACK TO SOURCE AND GROUNDING CONDUCTOR.
9.030 SURFACE MOUNTED RACEWAY CONSISTING OF THREE (3) SEPARATE
RACEWAYS ONE (1) FOR 120 VAC., 60HZ, ONE (1) FOR 28 VDC., ONE (1) FOR
120/208 VAC., 400 HZ POWER AND #2 GROUNDING CONDUCTOR.
DISCONNECT AND REMOVE FOR RELOCATION AS SHOWN ON DRAWING
1/E-101B. REWORK AND EXTEND EXISTING BRANCH CIRCUIT WIRING AS
NECESSARY TO NEW LOCATION . CUT RACEWAY AS NECESSARY TO ALLOW
INSTALLATION AT RELOCATED WALLS AT INDICATED LENGTHS .
9.031 COMBINATION FLUSH MOUNTED FLOOR BOX WITH 15 AMP 125 VAC., DUPLEX
RECEPTACLE AND VOICE/DATA OUTLET TO REMAIN.
9.032 TYPICAL: FLOOR BOXES LABELED AS 4HZ ARE CURRENTLY NOT SET TIGHT
IN CONCRETE FLOOR. EC SHALL INVESTIGATE AND REPAIR AS NECESSARY
SO THAT FLOOR BOX SETS FLUSH AND TIGHT IN CONCRETE SLAB. IF
NECESSARY SAW CUT FLOOR AROUND BOX AND RESET IN NEW CONCRETE.
9.033 EXISTING ELECTRICAL EQUIPMENT. REFER TO DRAWING 1/E-405, PHOTO
NO. 1 FOR WORK ASSOCIATED WITH EQUIPMENT.
9.035 DISCONNECT AND REMOVE 'EPO' THREE POSITION SWITCH AND EXTEND
EXISTING WIRING TO NEW LOCATIONS AS SHOWN ON DRAWING 1/E-101B
9.036 TYPICAL FOR ALL UON. REPLACE ALL EXISTING DUPLEX RECEPTACLES
WITH A NEW NEMA 5-20R RECEPTACLE. EXISTING OUTLET BOX AND WIRING
MAY BE REUSED.
9.037 DUE TO DEMOLITION OF EXISTING DEVICES CIRCUIT CONTINUITY TO THIS
DEVICE MAY NOT EXIST. EXTEND EXISTING WIRING AND CONDUIT AS
NECESSARY TO EXISTING 120 V BRANCH CIRCUIT SERVING THIS AREA.
OS
OS
O S
D D
D
3 3
3 3
J
J
F
J J
J
F
F
E5
E4
E3
E2
E1
ECEBEA
E-401
96"
TV
96"
96"
CTV
CTV
EH-1
EDH-1
EDH-2
9.0269.026
9.027
WP/GFCI
EWH
EWC
CTV
GFCI
TV
WP/GFCI
WP/GFIC
9.026
9.026
CHP-1
9.001
PS
96"
PS
9.0399.039
96" 96"
GFCI
GFCI
GFCI
M A
T C
H L
IN
E
S E
E
E
D A
M A
T C
H L
IN
E
S E
E
E
D A
9.036
9.039
9.039
TYP
E5
E4
E3
E2
E1
EC
EB
EA
DN FROM HIGH ROOF
DN FROM HIGH ROOF
EF-1A
G
G
G G G G
G
G
G
G
G
G
G
G G G G G
G
G
G
G
G
G
G
G
G
G
TR
RD
THROUGH ROOF
CONNECTOR TYP.
G
G
G G
G
G
TR
RD
RD
TR
9.025
9.025
TR
M A
T C
H L
IN
E
S E
E
T
D A
M A
T C
H L
IN
E
S E
E
E
D A
DEMOLITION GENERAL NOTES:
1. REFER TO DRAWING E-001 FOR DEMOLITION GENERAL NOTES, SYMBOLS &
ABBREVIATIONS.
KEY PLAN
A
B
C
SHOP
SOUTH
SHOP
NORTH
B2
A2
A2
C2
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
ISSUED
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
710 Avis Drive, #100 Ann Arbor, MI 48108-9649 phone: 810-956-9300 fax: 810-956-9281
/1
/2
:2 :0
P
M C
R e v it L o c a l\
.0
-E -R k e ff .k u re lla Y
A
.r v t
FIRST FLOOR &
ROOF ELECTRICAL
DEMOLITION PLAN -
AREA C
FJRP112701ANG PRO. NO.:
3258000-131303.01
KAF
MAM
July 20, 2022
KSK
N C
A N
G
T
H A
W
C H
A R
L O
T T
E D
O U
G L A
S I A
P C
H A
R L O
T T
E N
O R
T H
C A
R O
L
IN
A
R E
P A
IR
M
A
IN
T E
N A
N C
E H
A N
G A
R B
U
IL
D
IN
G
ED101C1/8" = 1'-0"1
FIRST FLOOR ELECTRICAL DEMOLITON PLAN - AREA C
KEYED NOTES
9.001 REMOVE EXISTING SWITCH. UTILIZE EXISTING BACKBOX FOR NEW LIGHTING
CONTROL IN THIS AREA. REFER TO E-121B & E-121C FOR NEW LIGHTING
CONTROLS.
9.025 ALL LIGHTNING PROTECTION SYSTEM THROUGH THE ROOF AND MAIN
DOWN CONDUCTORS TO GROUND RODS ARE TO REMAIN IN PLACE FOR
REUSE WITH NEW LIGHTNING PROTECTION SYSTEM.
9.026 SYSTEM FURNITURE POWER CONNECTION WITH 3/4" FLEXIBLE CONDUIT
CONNECTION.
9.027 SYSTEM FURNITURE POWER CONNECTION WITH 3/4" FLEXIBLE CONDUIT
CONNECTION. REMOVE BRANCH CIRCUIT WIRING ONLY BACK TO SOURCE.
9.036 TYPICAL FOR ALL UON. REPLACE ALL EXISTING DUPLEX RECEPTACLES
WITH A NEW NEMA 5-20R RECEPTACLE. EXISTING OUTLET BOX AND WIRING
MAY BE REUSED.
9.039 DISCONNECT AND REMOVE DEVICE AND WIRING. BACKBOX AND CONDUIT
TO REMAIN FOR INSTALLATION OF NEW DEVICE AND WIRING SHOWN ON
DRAWING 1/E-101C.
1/8" = 1'-0"2
ROOF ELECTRICAL & LIGHTNING PROTECTION DEMOLITION PLAN - AREA C
EA
NA
H
G
10 9 8
E
D
C
B
A
11 7 6 5 4 3 2 1
F
J
K
IFCP IFCP IFCP
HEF HEF
MDO
IFCP
IFCP
IFCP
UH-9 UH-10
HEF
IFCP
IFCP HEF
HEFHEF
IFCP
IFCP
HEF
HEFHEF
IFCP
IFCP
HEF
IFCP
IFCP
HEF
MDO
HEF
IFCP
HEF HEF
IFCP
HEF
MDO
E-403
LOCATED AT CATWALK LOCATED AT CATWALK
TYP.
TYP.
TYP.
HANGAR DOOR
WIREWAY & DOOR(S)
DISCONNECT
9.011
9.018 9.017
9.017
9.014
M A
T C
H L
IN
E
S E
E
E
D B
M A
T C
H L
IN
E
S E
E
E
D C
MATCHLINE
SEE 1 / ED102B
M
ATC
H
LIN
E
SEE 2 / ED
101C
TYP.
TYP.
9.018
9.018
MDO
MDO
DEMOLITION GENERAL NOTES:
1. REFER TO DRAWING E-001 FOR DEMOLITION GENERAL NOTES, SYMBOLS &
ABBREVIATIONS.
KEY PLAN
A
B
C
SHOP
SOUTH
SHOP
NORTH
B2
A2
A2
C2
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
ISSUED
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
710 Avis Drive, #100 Ann Arbor, MI 48108-9649 phone: 810-956-9300 fax: 810-956-9281
/1
/2
:2 :0
P
M C
R e v it L o c a l\
.0
-E -R k e ff .k u re lla Y
A
.r v t
MEZZANINE FLOOR &
CATWALK LEVEL
ELECTRICAL
DEMOLITION PLAN -
AREA A
FJRP112701ANG PRO. NO.:
3258000-131303.01
KAF
MAM
July 20, 2022
KSK
N C
A N
G
T
H A
W
C H
A R
L O
T T
E D
O U
G L A
S I A
P C
H A
R L O
T T
E N
O R
T H
C A
R O
L
IN
A
R E
P A
IR
M
A
IN
T E
N A
N C
E H
A N
G A
R B
U
IL
D
IN
G
ED102A
1/16" = 1'-0"1
MEZZANINE FLOOR & CATWALK LEVEL ELECTRICAL DEMOLITON PLAN - AREA A
KEYED NOTES
9.011 INFRARED CONTROL PANEL LOCATED ON HANDRAIL OF CATWALK.
DISCONNECT AND REMOVE BRANCH CIRCUIT CONDUIT AND WIRING BACK
TO SOURCE. CONTROL PANEL REMOVED BY DIVISION 23 CONTRACTOR.
9.014 DIVISION 26 CONTRACTOR TO DISCONNECT AND REMOVE POWER BACK TO
SOURCE. EQUIPMENT TO BE REMOVED BY DIVISION 23 CONTRACTOR.
9.017 JUNCTION BOX LOCATED ON CATWALK AND CONNECTED TO BRIDGE CRANE
CONTROLLER. EC TO DISCONNECT COMPLETELY INCLUDING ALL
CONTROLS, CONTROL WIRING AND FEEDER BACK TO SOURCE.
9.018 MOTOR OPERATED OVERHEAD DOOR. DISCONNECT AND REMOVE POWER
BACK TO SOURCE, REMOVE DOOR OPERATOR CONTROL STATIONS AND
ASSOCIATED CONDUIT AND WIRING. DOOR OPERATOR AND CONTROLS
REMOVED BY OTHERS.
N9 N8 N7 N6 N5N4 N3 N2 N1
ND
NC
NB
NA
GFCI/WP
DN
DN
SEE SHEET ED103A
FOR CONTINUATION
EF-3A
SF-4SF-2
EF-6A
EF-2A
SF-1 SF-3
G G
G G G
G G G G
G
G
G
G
G
G G
G
G
G
GG
G
G
G
G
G
GGG
G
G
G
G
G
G G G G
G
G
G
G
9.025
G
G
GG
G
GG
G
G
GFCI/WP
TYP. ROOF DRAIN
ROOF HATCH
MATCHLINE
SEE 1 / ED102A
M
ATC
H
LI
N E
SEE 1
ED
2A
DEMOLITION GENERAL NOTES:
1. REFER TO DRAWING E-001 FOR DEMOLITION GENERAL NOTES, SYMBOLS &
ABBREVIATIONS.
KEY PLAN
A
B
C
SHOP
SOUTH
SHOP
NORTH
B2
A2
A2
C2
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
ISSUED
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
710 Avis Drive, #100 Ann Arbor, MI 48108-9649 phone: 810-956-9300 fax: 810-956-9281
/1
/2
:2 :1
P
M C
R e v it L o c a l\
.0
-E -R k e ff .k u re lla Y
A
.r v t
ROOF ELECTRICAL &
LIGHTNING
PROTECTION
DEMOLITION PLAN -
AREA B
FJRP112701ANG PRO. NO.:
3258000-131303.01
KAF
MAM
July 20, 2022
KSK
N C
A N
G
T
H A
W
C H
A R
L O
T T
E D
O U
G L A
S I A
P C
H A
R L O
T T
E N
O R
T H
C A
R O
L
IN
A
R E
P A
IR
M
A
IN
T E
N A
N C
E H
A N
G A
R B
U
IL
D
IN
G
ED102B1/8" = 1'-0"1
ROOF ELECTRICAL & LIGHTNING PROTECTION DEMOLITION PLAN - AREA B
KEYED NOTES
9.025 ALL LIGHTNING PROTECTION SYSTEM THROUGH THE ROOF AND MAIN
DOWN CONDUCTORS TO GROUND RODS ARE TO REMAIN IN PLACE FOR
REUSE WITH NEW LIGHTNING PROTECTION SYSTEM.
N1
H
G
10 9 8
E
D
C
B
A
11 7 6 5 4 3 2 1
F
J
K
DN DN
SEE SHEET ED102B FOR
CONTINUATION
DN
DN
DN
EF-5 EF-6 EF-7 EF-8
EF-9
EF-10
EF-11 EF-12
G G
G
G
G G
G
G
G G
G G G
G
G
GGGGGG
G
G
G G
G
G
G
G
GG
GG
GG
GG
G G
G
G
GGG
G G
G G
G
G
G G G
G
G
G
G
G
G
G
G
G
G
G
G G G
G
G G
G
G
G
G G
G
G G
G
G G G G
G
G G G
G
G G G G
G
G
G
G G
G
G
G
G
G
G
G G
G G
G
G G
G
G
HEF HEF
HEF
HEF
HEF
G G G
G
WP/GFCI(E)
WP/GFCI(E)
G
9.025
M A
T C
H L
IN
E
S E
E
E
D B
M A
T C
H L
IN
E
S E
E
E
D C
MATCHLINE
SEE 1 / ED102B
M
ATC
H
LIN
E
SEE 2 / ED
101C
DEMOLITION GENERAL NOTES:
1. REFER TO DRAWING E-001 FOR DEMOLITION GENERAL NOTES, SYMBOLS &
ABBREVIATIONS.
KEY PLAN
A
B
C
SHOP
SOUTH
SHOP
NORTH
B2
A2
A2
C2
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
ISSUED
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
710 Avis Drive, #100 Ann Arbor, MI 48108-9649 phone: 810-956-9300 fax: 810-956-9281
/1
/2
:2 :2
P
M C
R e v it L o c a l\
.0
-E -R k e ff .k u re lla Y
A
.r v t
ROOF ELECTRICAL &
LIGHTNING
PROTECTION
DEMOLITION PLAN -
AREA A
FJRP112701ANG PRO. NO.:
3258000-131303.01
KAF
MAM
July 20, 2022
KSK
N C
A N
G
T
H A
W
C H
A R
L O
T T
E D
O U
G L A
S I A
P C
H A
R L O
T T
E N
O R
T H
C A
R O
L
IN
A
R E
P A
IR
M
A
IN
T E
N A
N C
E H
A N
G A
R B
U
IL
D
IN
G
ED103A
KEYED NOTES
9.025 ALL LIGHTNING PROTECTION SYSTEM THROUGH THE ROOF AND MAIN
DOWN CONDUCTORS TO GROUND RODS ARE TO REMAIN IN PLACE FOR
REUSE WITH NEW LIGHTNING PROTECTION SYSTEM.
1/16" = 1'-0"1
ROOF ELECTRICAL & LIGHTNING PROTECTION DEMOLITION PLAN - AREA A
CT'S
EXISTING TRANSFORMER - UT
12470/7200V:480/277V, 3PH, 4W
1000KVA, 5.75%
EXISTING 4 SETS OF 3#600 KCMIL, #3/0G (1600A)
EACH IN 3-1/2"C (BELOW GRADE)
100A, 3P
SPARE
100A, 3P
SPARE
400A, 3P 600A, 3P
18" SPACE
200A, 3P 200A, 3P 200A, 3P 200A, 3P
SPARE
400A, 3P
CAPLA
3-225A 3-600A 3-200A 3-200A 3-200A 3-200A 3-400A
18" SPACE
200A, 3P
3-200A
EXISTING SECONDARY LIGHTING ARRESTOR
EXISTING SURGE CAPACITOR
EXISTING SWBD HSP
480/277V, 3PH, 4W
1600A BUS
50,000 AMP, RMS
1600A
BOLTED PRESSURE
SWITCH - GFI
3-1600A
EXISTING
4#4/0, #3G, 2-1/2"C (200A)
EXISTING
4#4/0, #3G 2-1/2"C (200A)
EXISTING
4#1/0, #6G, 2"C (125A)
DF
EXISTING
4#3, #8G
1-1/4"C (80A)
60A/3P 3-80A
(DEMO)
200A/3P 3-125A
(DEMO)
EXISTING
4#4/0, #4G, 2-1/2"C (225A)
EXISTING
4#4/0, #4G, 2-1/2"C
EXISTING
4#3/0, #6G, 2"C (200A)
EXISTING
3#4/0, #6G, 2"C (200A)
4#500 KCMIL, #3G, 3-1/2"C
1 2 3 4 9 11 12
125A/3P 50A/3P 90A/3P
J J
DUPLEX AIR
COMPRES…