ATTACHMENT 8 DRAWINGS 145 AW Repair Maint. Hangar Building 51 dated 20 July 2022 Vol 4.pdf

PDF 15 MB Posted

Attached to
Repair Building 51
Solicitation number
W50S87-23-B-0001
Issued by

View the file

Other files

File Type Posted
Bid Opening Sign-in Sheet.jpg JPG image
OF 1419 Abstract signed.pdf PDF
Questions and Answers 07102023.pdf PDF
Amendment 0001.pdf PDF
Pre-bid signin sheet.jpg JPG image
PreBidSlides_W50S87-23-B-0001 Repair Building 51.pptx PPTX presentation
Pre Bid Sign in sheet.jpg JPG image
ATTACHMENT 13 BRAND NAME JUSTIFICATION Monaco Fire Alarm Trasceiver redacted.pdf PDF
ATTACHMENT 1 SPECS REPAIR BUILDING 51 FJRP112701 dated 20 July 2022 Vol 1 of 4 502 pages.pdf PDF
ATTACHMENT 7 DRAWINGS 145 AW Repair Maint. Hangar Building 51 dated 20 July 2022 Vol 3.pdf PDF
ATTACHMENT 12 BRAND NAME JUSTIFICATION Interior and Exterior Finishes redacted.pdf PDF
ATTACHMENT 18 145 AW CONTRACTOR SECURITY GUIDE.pdf PDF
ATTACHMENT 5 DRAWINGS 145 AW Repair Maint. Hangar Building 51 dated 20 July 2022 Vol 1.pdf PDF
ATTACHMENT 16 PREBID CONFERENCE SITE VISIT and BID DROP OFF MAP.pdf PDF
W50S87-23-B-0001.pdf PDF
ATTACHMENT 19 145 AW CONTRACTOR ENVIRONMENTAL GUIDE.pdf PDF
ATTACHMENT 17 145 AW CONTRACTOR SAFETY GUIDE.pdf PDF
ATTACHMENT 9 SOW Repair Bldg 51 dated 6 November 2022.pdf PDF
ATTACHMENT 3 SPECS REPAIR BUILDING 51 FJRP112701 dated 20 July 2022 Vol 3 of 4 490 pages.pdf PDF
ATTACHMENT 15 VISITOR REQUEST WORKSHEET.pdf PDF
ATTACHMENT 4 SPECS REPAIR BUILDING 51 FJRP112701 dated 20 July 2022 Vol 4 of 4 444 pages.pdf PDF
ATTACHMENT 11 BRAND NAME JUSTIFICATION Alerton Direct Digital Controls redacted.pdf PDF
ATTACHMENT 6 DRAWINGS 145 AW Repair Maint. Hangar Building 51 dated 20 July 2022 Vol 2.pdf PDF
ATTACHMENT 10 BRAND NAME JUSTIFICATION - Best Door hardware redacted.pdf PDF
ATTACHMENT 14 BRAND NAME JUSTIFICATION- Sika Sarnafil PVC Roof Membrane redacted.pdf PDF
ATTACHMENT 2 SPECS REPAIR BUILDING 51 FJRP112701 dated 20 July 2022 Vol 2 of 4 542 pages.pdf PDF
Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT MAP:

PROJECT

LOCATION

BASE

ENTRANCE

CONSTRUCTION

ENTRANCE

BASE

OUTLINE

STATE MAP:

STATE OF NORTH CAROLINA

CITY OF CHARLOTTE,

MECKLENBURG COUNTY

VICINITY MAP:

PROJECT LOCATION

1. ROLLER SHADES IN LEU OF SLAT BLINDS

2. EPOXY FLOOR IN ROOMS:

A. HYDRO SHOP

B. WHEEL/TIRE SHOP

C. SUPPORT EQUIPMENT

D. CTK

3. ADDITIONAL PARKING SPACES

BID OPTIONS:

ANG PROJECT No.:

SHEET NO.:

SHEET CONTENTS

DO NOT SCALE DRAWINGS

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

ISSUED

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

710 Avis Drive, #100 Ann Arbor, MI 48108-9649 phone: 810-956-9300 fax: 810-956-9281

/1

/2

:3 :0

P

M C

R e v it L o c a l\

.0

-A -R c h ri s .d o u g a n

.r v t

FJRP112701

REPAIR MAINTENANCE HANGAR BUILDING 51

CHARLOTTE DOUGLAS IAP

CHARLOTTE, NORTH CAROLINA

NCANG - 145TH AW

COVER SHEET -

VOLUME 4

FJRP112701ANG PRO. NO.:

3258000-181469.01

NJD, KB

DMD

July 20, 2022

ATM

N C

A N

G

T

H A

W

C H

A R

L O

T T

E D

O U

G L A

S I A

P C

H A

R L O

T T

E N

O R

T H

C A

R O

L

IN

A

R E

P A

IR

M

A

IN

T E

N A

N C

E H

A N

G A

R B

U

IL

D

IN

G

G-000D

VOLUME 4

07/20/22 B-3 SUBMITTAL

SHEET NO.:

SHEET CONTENTS

DO NOT SCALE DRAWINGS

ISSUED

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

710 Avis Drive, #100 Ann Arbor, MI 48108-9649 phone: 810-956-9300 fax: 810-956-9281

/2

/2

:0

:3

A

M C

R e v it L o c a l\

.0

-A -R c h ri s .d o u g a n

.r v t

SHEET INDEX -

VOLUME 4

FJRP112701ANG PRO. NO.:

3258000-181469.01

NJD, KB

DMD

July 20, 2022

ATM

N C

A N

G

T

H A

W

C H

A R

L O

T T

E D

O U

G L A

S I A

P C

H A

R L O

T T

E N

O R

T H

C A

R O

L

IN

A

R E

P A

IR

M

A

IN

T E

N A

N C

E H

A N

G A

R B

U

IL

D

IN

G

G-001D

SHEET INDEX - VOLUME 2

A-515 PLAN DETAILS INTERIOR - MINOR CONSTRUCTION

A-601 DOOR AND FRAME SCHEDULES AND LEGENDS - EXIST & AREA A

A-602 DOOR AND FRAME SCHEDULES AND LEGENDS - AREAS B & C

A-603 WINDOW TYPES & DETAILS

A-605 TRANSLUCENT PANEL DETAILS

A-621 DOOR DETAILS-INTERIOR AND EXTERIOR

A-700 FINISH SCHEDULES

A-701A FINISH PLAN - AREA A

A-701A2 FINISH PLANS - AREA A2

A-701B FINISH PLAN - AREA B

A-701B2 FINISH PLAN - MINOR CONSTRUCTION AREA B2

A-701C FINISH PLAN-AREA C

A-702A HANGAR BAY STRIPING PLAN

A-703 FINISH DETAILS

A-801A SIGNAGE PLAN - AREA A

A-801A2 SIGNAGE PLANS - AREA A2

A-801B SIGNAGE PLAN - AREA B

A-801B2 SIGNAGE PLAN - MINOR CONSTRUCTION AREA B2

A-801C SIGNAGE PLAN - AREA C

A-804 SIGNAGE PLAN - LOWER CATWALK

A-805 SIGNAGE PLAN - UPPER CATWALK

A-851 SIGNAGE DETAILS

A-852 SIGNAGE SCHEDULE

A-901A2 FIXTURES, FURNITURE AND EQUIPMENT PLANS - AREA A2

A-901B FIXTURES, FURNITURE AND EQUIPMENT PLAN - AREA B

A-901C FIXTURES, FURNITURE AND EQUIPMENT PLAN - AREA C

Sheets in Volume: 135

SHEET INDEX - VOLUME 2

GENERAL

G-001B SHEET INDEX - VOLUME 2

ARCHITECTURAL

A-001 NOTES & SYMBOLS

A-002 PARTITION TYPES

A-003 PARTITION DETAILS & TOILET ACCESSORY MOUNTING HEIGHTS

A-004 ASSEMBLIES

A-005 ARCHITECTURAL KEYNOTES

AD100 DEMOLITION OVERALL PLAN

AD101A DEMOLITION FLOOR PLAN - AREA A

AD101B DEMOLITION FLOOR PLAN - AREA B

AD101C DEMOLITION FLOOR PLAN - AREA C

AD101C2 DEMOLITION FLOOR PLAN - MINOR CONSTRUCTION AREA C2

AD102A DEMOLITION MEZZANINE PLAN - AREA A

AD102A2 DEMOLITION MEZZANINE PLANS - AREA A2

AD105A DEMOLITION ROOF PLAN - AREA A

AD105B DEMOLITION ROOF PLAN - AREA B

AD105C DEMOLITION ROOF PLAN - AREA C

AD105C2 DEMOLITION ROOF PLAN - MINOR CONSTRUCTION AREA C2

AD121A DEMOLITION REFLECTED CEILING PLAN - AREA A

AD121B DEMOLITION REFLECTED CEILING PLAN - AREA B

AD121C DEMOLITION REFLECTED CEILING PLAN - AREA C

AD201 DEMOLITION EXTERIOR ELEVATIONS - AREA A

AD202 DEMOLITION EXTERIOR ELEVATIONS - AREA A

AD203 DEMOLITION EXTERIOR ELEVATIONS - AREA B

AD204 DEMOLITION EXTERIOR ELEVATIONS AREA C

AD205 DEMOLITION EXTERIOR ELEVATIONS - MINOR CONSTRUCTION

AD206 DEMOLITION EXTERIOR ELEVATIONS - AREA C2

AD301 DEMOLITION SECTIONS

A-100 OVERALL PLAN

A-101A FIRST FLOOR PLAN - AREA A

A-101A2 FIRST FLOOR PLANS - AREA A2

A-101B FIRST FLOOR PLAN - AREA B

A-101B2 FIRST FLOOR PLAN - MINOR CONSTRUCTION AREA B2

A-101C FIRST FLOOR PLAN - AREA C

A-101C2 FIRST FLOOR PLAN - MINOR CONSTRUCTION AREA C2

A-102 MEZZANINE PLAN - OVERALL

A-102A2 MEZZANINE PLANS - AREA A2

A-102A3 MEZZANINE ISOMETRICS - AREA A2

A-102B2 CLERESTORY FLOOR PLAN - MINOR CONSTRUCTION AREA B2

A-103 LOWER CATWALK PLAN

A-104 UPPER CATWALK PLAN

A-105 ROOF PLAN - OVERALL

A-105A ROOF PLAN - AREA A

A-105B ROOF PLAN - AREA B

A-105B2 ROOF PLAN - MINOR CONSTRUCTION AREA B2

A-105C ROOF PLAN - AREA C

A-105C2 ROOF PLAN - MINOR CONSTRUCTION AREA C2

A-121A REFLECTED CEILING PLAN - AREA A

A-121A2 REFLECTED CEILING PLANS - AREA A2

A-121B REFLECTED CEILING PLAN - AREA B

A-121B2 REFLECTED CEILING PLAN - MINOR CONSTRUCTION AREA B2

A-121C REFLECTED CEILING PLAN - AREA C

A-121C2 REFLECTED CEILING PLAN - MINOR CONSTRUCTION AREA C2

A-122B ENLARGED CEILING PLANS - AREAS B & C

A-151A2 FIRST FLOOR AIR BARRIER PLANS - AREA A2

A-151B FIRST FLOOR AIR BARRIER PLAN - AREA B

A-151B2 FIRST FLOOR AIR BARRIER PLAN - MINOR CONSTRUCTION AREA B2

A-151C FIRST FLOOR AIR BARRIER PLAN - AREA C

A-152B2 CLERESTORY AIR BARRIER PLAN - MINOR CONSTRUCTION AREA B2

A-152C2 CLERESTORY AIR BARRIER PLAN - MINOR CONSTRUCTION AREA C2

A-201 EXTERIOR ELEVATIONS - AREA A

A-202 EXTERIOR ELEVATIONS - AREA A

A-203 EXTERIOR ELEVATIONS - AREA B

A-204 EXTERIOR ELEVATIONS - MINOR CONSTRUCTION AREA B2

A-205 EXTERIOR ELEVATIONS - AREA C

A-206 EXTERIOR ELEVATIONS - MINOR CONSTRUCTION AREA C2

A-207 EXTERIOR FACADE REPAIR ELEVATIONS - AREA A

A-208 EXTERIOR FACADE REPAIR ELEVATIONS - AREAS B & C

A-301 BUILDING SECTIONS - AREA A

A-302 BUILDING SECTIONS - AREA A2

A-303 BUILDING SECTIONS - AREA B

A-304 BUILDING SECTIONS - MINOR CONSTRUCTION AREA B2

A-305 BUILDING SECTIONS - MINOR CONSTRUCTION AREA C2

A-310 WALL SECTIONS - AREA A

A-311 WALL SECTIONS - AREA A2 SOUTH HANGAR SHOP

A-312 WALL SECTIONS - AREA A2 NORTH HANGAR SHOP

A-313 WALL SECTIONS - AREA B

A-314 WALL SECTIONS - AREA B

A-315 WALL SECTIONS - MINOR CONSTRUCTION AREA B2

A-316 WALL SECTIONS - AREAS B & B2

A-317 WALL SECTIONS - MINOR CONSTRUCTION AREA B2

A-318 WALL SECTIONS - AREAS B & C

A-319 WALL SECTIONS - AREA C

A-320 WALL SECTIONS - MINOR CONSTRUCTION AREA C2

A-321 WALL SECTIONS - AREA B & C AIR BARRIER

A-322 WALL SECTIONS - HANGAR SHOP AIR BARRIERS

A-400 ENLARGED PLANS AND INTERIOR ELEVATIONS - AREA A

A-401 INTERIOR ELEVATIONS - AREA A

A-402 ENLARGED PLANS AND INTERIOR ELEVATIONS - AREA B

A-403 ENLARGED PLANS AND INTERIOR ELEVATIONS - AREA B

A-404 ENLARGED PLANS AND INTERIOR ELEVATIONS - AREA C

A-405 INTERIOR ELEVATIONS - AREA C

A-406 CASEWORK DETAILS

A-410 RAILING TYPES

A-411 ENLARGED STAIR AND SHIPS LADDER PLANS & SECTIONS - AREA B, B2 &

HANGAR SHOP SOUTH

A-412 ENLARGED STAIR AND SHIPS LADDER PLANS & SECTIONS - HANGAR SHOP

NORTH

A-501 ROOF DETAILS

A-502 SECTION DETAILS EXTERIOR

A-503 SECTION DETAILS - AREA A

A-504 SECTION DETAILS EXTERIOR - MINOR CONSTRUCTION AREA B2

A-505 SECTION DETAILS EXTERIOR - MINOR CONSTRUCTION AREA B2

A-506 SECTION DETAILS - MINOR CONSTRUCTION AREA C2

A-507 SECTION DETAILS - MINOR CONSTRUCTION AREA C2

A-508 SECTION DETAILS - INTERIOR

A-509 PLAN DETAILS - AIR BARRIER

A-510 SECTION DETAILS - AIR BARRIER

A-511 PLAN DETAILS EXTERIOR - MINOR CONSTRUCTION AREAS B & B2

A-512 PLAN DETAILS - MINOR CONSTRUCTION AREA B2

A-513 PLAN DETAILS EXTERIOR - MINOR CONSTRUCTION AREA C2

A-514 PLAN DETAILS INTERIOR - AREAS A, B & C

SHEET INDEX - VOLUME 1

GENERAL

G-001A SHEET INDEX - VOLUME 1

G-003 CODE ANALYSIS

G-004A ROOM OCCUPANCY CLASSIFICATIONS

G-004B OCCUPANCY PLANS

G-005A LIFE SAFETY PLAN - AREA A

G-005A2 LIFE SAFETY PLANS - AREA A2

G-005B LIFE SAFETY PLANS - AREA B & C

G-006A LIFE SAFETY PLAN - LOW CATWALK

G-007A LIFE SAFETY PLAN - UPPER CATWALK

CIVIL

C100 CIVIL LEGEND AND ABBREVIATIONS

VF101 EXISTING CONDITIONS

GC121 SURVEY CONTROL PLAN

GC141 CONSTRUCTION ACCESS & LOCATION PLAN

GC145 CONSTRUCTION OPERATION PLAN NOTES

BB101 PLAN & LOG OF SOIL BORINGS

EC101 EROSION CONTROL PLAN

EC501 EROSION CONTROL DETAILS

CD101 DEMOLITION PLAN

CS111 SITE PLAN

CS121 ENLARGED SITE AND PAVING PLAN - AREAS 1 & 2

CS122 ENLARGED SITE AND PAVING PLAN - AREA 3

CS501 SITE DETAILS

CS502 SITE DETAILS

CS503 SITE DETAILS

CS504 SITE DETAILS

CG121 ENLARGED GRADING & DRAINAGE PLAN - AREAS 1 & 2

CG122 ENLARGED GRADING & DRAINAGE PLAN - AREA 3

CU101 ENLARED UTILITY PLAN - AREA 3

CU501 UTILITY DETAILS

CU502 UTILITY DETAILS

STRUCTURAL

S-001 NOTES, SYMBOLS, AND ABBREVIATIONS

S-002 NOTES, SYMBOLS, AND ABBREVIATIONS

S-005 STATEMENT OF SPECIAL INSPECTIONS

S-006 STRUCTURAL STEEL SPECIAL INSPECTIONS

S-007 MASONRY AND STEEL DECK SPECIAL INSPECTIONS

S-008 STRUCTURAL PROJECT KEYNOTES

S-010 ROOF LOADING PLAN

S-052A EXISTING BOTTOM CHORD FRAMING PLAN - AREA A

S-053A EXISTING ROOF FRAMING PLAN - AREA A

SD101A FOUNDATION AND FLATWORK DEMOLITION PLAN - AREA A

SD101B FOUNDATION AND FLATWORK DEMOLITION PLAN - AREA B

SD101C FOUNDATION AND FLATWORK DEMOLITION PLAN - AREA C

SD101C2 FOUNDATION AND FLATWORK DEMOLITION PLAN - MINOR

CONSTRUCTION - AREA C2

SD131B STRUCTURAL DEMOLITION FLOOR PLAN - AREA B

SD131C STRUCTURAL DEMOLITION FLOOR PLAN - AREA C

SD152A BOTTOM CHORD FRAMING DEMOLITION PLAN - AREA A

S-101A FOUNDATION PLAN - AREA A

S-101A2 FOUNDATION PLANS - AREA A2

S-101B FOUNDATION PLAN - AREA B

S-101B2 FOUNDATION PLAN - MINOR CONSTRUCTION - AREA B2

S-101C FOUNDATION PLAN - AREA C

S-101C2 FOUNDATION PLAN - MINOR CONSTRUCTION - AREA C2

S-111A FLATWORK PLAN - AREA A

S-111A2 FLATWORK PLANS - AREA A2

S-111B FLATWORK PLAN - AREA B

S-111B2 FLATWORK PLAN - MINOR CONSTRUCTION - AREA B2

S-111C FLATWORK PLAN - AREA C

S-111C2 FLATWORK PLAN - MINOR CONSTRUCTION - AREA C2

S-131A STRUCTURAL FLOOR PLAN - AREA A

S-131A2 STRUCTURAL FLOOR PLANS - AREA A2

S-131B STRUCTURAL FLOOR PLAN - AREA B

S-131B2 STRUCTURAL FLOOR PLAN - MINOR CONSTRUCTION - AREA

B2

S-131C STRUCTURAL FLOOR PLAN - AREA C

S-142A MEZZANINE FRAMING PLAN - AREA A

S-142A2 MEZZANINE FRAMING PLANS - AREA A2

S-151B ROOF FRAMING PLAN - AREA B

S-151C ROOF FRAMING PLAN - AREA C

S-151C2 ROOF FRAMING PLAN - MINOR CONSTRUCTION - AREA C2

S-152A BOTTOM CHORD FRAMING PLAN - AREA A

S-153A ROOF FRAMING PLAN - AREA A

S-153B2 HIGH ROOF FRAMING PLAN - MINOR CONSTRUCTION - AREA

B2

S-153C2 HIGH ROOF FRAMING PLAN - MINOR CONSTRUCTION - AREA

C2

S-301 SECTIONS

S-411 ENLARGED FLATWORK PLANS

S-431 ENLARGED STRUCTURAL FLOOR PLANS

S-441 ENLARGED FRAMING PLAN AND DETAILS

S-501 FOUNDATION DETAILS

S-502 FOUNDATION DETAILS

S-511 FLATWORK DETAILS

S-512 FLATWORK DETAILS

S-521 WALL DETAILS

S-522 WALL DETAILS

S-541 FRAMING DETAILS

S-542 FRAMING DETAILS

S-543 FRAMING DETAILS

S-544 FRAMING DETAILS

S-545 FRAMING DETAILS

S-551 FRAMING DETAILS

S-552 FRAMING DETAILS

S-601 STRUCTURAL SCHEDULES

Sheets in Volume: 90

SHEET INDEX - VOLUME 3

GENERAL

G-001C SHEET INDEX - VOLUME 3

FIRE ALARM

FA001 NOTES & SYMBOLS

FAD101 FIRE ALARM OVERALL DEMO PLAN

FA102 FIRE ALARM AND MNS FLOOR PLAN HANGAR

FA103 FIRE ALARM AND MNS FLOOR PLAN NORTH WING

FA104 FIRE ALARM AND MNS ENLARGED FLOOR PLAN EAST WING

FA105 FIRE ALARM AND MNS RISER DIAGRAM AND MATRIX

FIRE PROTECTION

FX001 NOTES & SYMBOLS

FXD101 FIRE PROTECTION HANGAR DEMO PLAN

FXD102 FIRE PROTECTION DEMO PLAN NORTH WING

FX101 DESIGN DENSITY PLAN HANGAR

FX102 DESIGN DENSITY NORTH WING

FX102B2 DESIGN DENSITY PLAN - AREA B2 - MINOR CONSTRUCTION

FX103 FIRE PROTECTION HANGAR FLOOR PLAN

FX104 FIRE PROTECTION FIRE PUMP ROOM

FX105 FIRE PROTECTION SPRINKLER ROOM

PLUMBING

P-001 PLUMBING NOTES & SYMBOLS

PD100B UNDERGROUND DRAIN AND VENT DEMO PLUMBING PLAN - AREA B

PD100C UNDERGROUND DRAIN AND VENT DEMO PLUMBING PLAN - AREA C

PD101A ABOVEGROUD DRAIN AND VENT DEMO PLUMBING PLAN - AREA A

PD101B ABOVEGROUND DRAIN AND VENT DEMO PLUMBING PLAN - AREA B

PD101C ABOVEGROUND DRAIN AND VENT DEMO PLUMBING PLAN - AREA C

PD102A ROOF - DRAIN AND VENT DEMO PLUMBING PLAN - AREA A

PD102B ROOF - DRAIN AND VENT DEMO PLUMBING PLAN - AREA B

PD102C ROOF - DRAIN AND VENT DEMO PLUMBING PLAN - AREA C

PD131A SUPPLY DEMO PLUMBING PLAN - AREA A

PD131B SUPPLY DEMO PLUMBING PLAN - AREA B

PD131C SUPPLY DEMO PLUMBING PLAN - AREA C

P-100A2 UNDERGROUND DRAIN AND VENT PLUMBING PLAN - HANGAR SHOPS

P-100B UNDERGROUND DRAIN AND VENT PLUMBING PLAN - AREA B

P-100B2 UNDERGROUND DRAIN AND VENT PLUMBING PLAN - AREA B2

P-100C UNDERGROUND DRAIN AND VENT PLUMBING PLAN - AREA C

P-101A DRAIN AND VENT PLUMBING PLAN - AREA A

P-101A2 DRAIN AND VENT PLUMBING PLAN - HANGAR SHOPS

P-101B DRAIN AND VENT PLUMBING PLAN - AREA B

P-101B2 DRAIN AND VENT PLUMBING PLAN - AREA B2

P-101C DRAIN AND VENT PLUMBING PLAN - AREA C

P-102A ROOF - DRAIN AND VENT PLUMBING PLAN - AREA A

P-102B ROOF - DRAIN AND VENT PLUMBING PLAN - AREA B

P-102B2 ROOF - DRAIN AND VENT PLUMBING PLAN - AREA B2

P-102C ROOF - DRAIN AND VENT PLUMBING PLAN - AREA C

P-131A SUPPLY PLUMBING PLAN - AREA A

P-131A2 SUPPLY PLUMBING PLANS - HANGAR SHOPS

P-131B SUPPLY PLUMBING PLAN - AREA B

P-131C SUPPLY PLUMBING PLAN - AREA C

P-501 PLUMBING DETAILS

P-502 PLUMBING DETAILS

P-601 PLUMBING SCHEDULES

P-602 PLUMBING SCHEDULES

P-901 DRAIN AND VENT ISOMETRIC PLUMBING DIAGRAM

P-931 SUPPLY ISOMETRIC PLUMBING PLAN

MECHANICAL

M-001 MECHANICAL NOTES & SYMBOLS

MD101A HVAC DEMOLITION FLOOR PLAN - AREA A

MD101B HVAC DEMOLITION FLOOR PLAN - AREA B

MD101C HVAC DEMOLITION FLOOR AND ROOF PLAN - AREA C

MD105A HVAC DEMOLITION ROOF PLAN - AREA A

MD105B HVAC DEMOLITION ROOF PLAN - AREA B

MD131A MECHANICAL PIPING DEMOLITION FLOOR PLAN - AREA A

MD131B MECHANICAL PIPING DEMOLITION FLOOR PLAN - AREA B

MD131C MECHANICAL PIPING DEMOLITION FLOOR PLAN - AREA C

MD401 ENLARGED DEMOLITION PLANS - AREA B AND AREA C

M-101A HVAC FLOOR PLAN - AREA A

M-101A2 HVAC FIRST FLOOR PLAN - AREA A2

M-101B HVAC FLOOR PLAN - AREA B

M-101B2 HVAC FLOOR PLAN - MINOR CONSTRUCTION AREA B2

M-101C HVAC FLOOR AND ROOF PLAN - AREA C

M-102A2 HVAC MEZZANINE PLANS - AREA A2

M-105A HVAC ROOF PLAN - AREA A

M-105B HVAC ROOF PLAN - AREA B

M-131A MECHANICAL PIPING FLOOR PLAN - AREA A

M-131A2 MECHANICAL FIRST FLOOR PLAN - AREA A2

M-131B MECHANICAL PIPING FLOOR PLAN - AREA B

M-131B2 MECHANICAL FLOOR PLAN - MINOR CONSTRUCTION AREA B2

M-131C MECHANICAL PIPING FLOOR PLAN - AREA C

M-132A2 MECHANICAL MEZZANINE PLANS - AREA A2

M-401 ENLARGED PLANS - AREA B, AREA C AND AREA D

M-501 MECHANICAL DETAILS

M-502 MECHANICAL DETAILS

M-503 MECHANICAL DETAILS

M-504 MECHANICAL DETAILS

M-601 MECHANICAL SCHEDULES

M-602 MECHANICAL SCHEDULES

M-603 MECHANICAL SCHEDULES

M-604 MECHANICAL SCHEDULES

M-605 MECHANICAL SCHEDULES

M-606 MECHANICAL SCHEDULES

M-607 MECHANICAL SCHEDULES

M-608 MECHANICAL SCHEDULES

M-609 MECHANICAL SCHEDULES

M-711 MECHANICAL SCHEMATICS

M-712 MECHANICAL SCHEMATICS

M-801 MECHANICAL CONTROL SCHEMATICS

M-802 MECHANICAL CONTROL SCHEMATICS

M-803 MECHANICAL CONTROL SCHEMATICS

M-804 MECHANICAL CONTROL SCHEMATICS

M-805 MECHANICAL CONTROL SCHEMATICS

Sheets in Volume: 96

SHEET INDEX - VOLUME 4

GENERAL

G-001D SHEET INDEX - VOLUME 4

ELECTRICAL

E-001 NOTES, SYMBOLS & ABBREVIATIONS

ED101A FIRST FLOOR ELECTRICAL DEMOLITON PLAN - AREA A

ED101B FIRST FLOOR ELECTRICAL DEMOLITON PLAN - AREA B

ED101C FIRST FLOOR & ROOF ELECTRICAL DEMOLITION PLAN - AREA C

ED102A MEZZANINE FLOOR & CATWALK LEVEL ELECTRICAL DEMOLITION PLAN - AREA A

ED102B ROOF ELECTRICAL & LIGHTNING PROTECTION DEMOLITION PLAN - AREA B

ED103A ROOF ELECTRICAL & LIGHTNING PROTECTION DEMOLITION PLAN - AREA A

ED701 DEMOLITION ONE-LINE DIAGRAM

E-100A HAZARDOUS AREA CLASSIFICATION PLAN

E-101A FIRST FLOOR POWER PLAN - AREA A

E-101A2 FIRST FLOOR POWER PLAN - AREA A2

E-101B FIRST FLOOR POWER PLAN - AREA B

E-101B2 FIRST FLOOR POWER PLAN - MINOR CONSTRUCTION - AREA B2

E-101C FIRST FLOOR & ROOF POWER PLAN - AREA C

E-102A MEZZANINE FLOOR & CATWALK LEVEL POWER PLAN - AREA A

E-103A ROOF POWER & LIGHTNING PROTECTION PLAN - AREA A

E-103B ROOF POWER & LIGHTNING PROTECTION PLAN - AREA B

E-103B2 ROOF POWER & LPS PLAN - MINOR CONSTRUCTION - AREA B2

E-121A FIRST FLOOR LIGHTING PLAN - AREA A

E-121A2 FIRST FLOOR LIGHTING PLAN - AREA A2

E-121B FIRST FLOOR LIGHTING PLAN - AREA B

E-121B2 FIRST FLOOR LIGHTING PLAN - MINOR CONSTRUCTION - AREA B2

E-121C FIRST FLOOR LIGHTING PLAN - AREA C

E-122A MEZZANINE FLOOR & CATWALK LEVEL LIGHTING PLAN - AREA A

E-401 ENLARGED POWER & DEMOLITION PLANS

E-402 ENLARGED POWER PLANS

E-403 ENLARGED PLANS

E-404 ENLARGED PHOTOS

E-405 ENLARGED PHOTOS

E-501 ELECTRICAL DETAILS

E-502 ELECTRICAL DETAILS

E-601 LUMINAIRE SCHEDULES

E-602 LIGHTING CONTROL SCHEDULES & CONTROLS NARRATIVE

E-603 EQUIPMENT WIRING SCHEDULES

E-604 EQUIPMENT WIRING SCHEDULES

E-605 PANEL SCHEDULES

E-606 PANEL SCHEDULES

E-607 PANEL SCHEDULES

E-608 PANEL SCHEDULES

E-701 ONE-LINE DIAGRAM

E-702 ONE-LINE DIAGRAM

TECHNOLOGY SYSTEMS

T-001 NOTES, SYMBOLS & ABBREVIATIONS

TD101A FIRST FLOOR TECHNOLOGY DEMOLITION PLAN - AREA A - HANGAR

TD101B FIRST FLOOR TECHNOLOGY DEMOLITION PLAN - AREA B - NORTH WING

TD101C FIRST FLOOR & ROOF TECHNOLOGY DEMOLITION PLAN - AREA C - EAST WING

TD102A MEZZANINE FLOOR & CATWALK LEVEL TECHNOLOGY DEMOLITION PLAN - AREA A - HANGAR

TD103A ROOF TECHNOLOGY DEMOLITION PLAN - AREA A - HANGAR

T-100 TECHNOLOGY SITE PLAN

T-101A FIRST FLOOR - AREA A - TECHNOLOGY SYSTEMS

T-101A2 HANGAR SHOP - AREA A2 - TECHNOLOGY SYSTEMS

T-101B FIRST FLOOR - AREA B - TECHNOLOGY SYSTEMS

T-101B2 FIRST FLOOR - AREA B2 - TECHNOLOGY SYSTEMS

T-101C FIRST FLOOR - AREA C - TECHNOLOGY SYSTEMS

T-102 MEZZANINE PLANS - TECHNOLOGY SYSTEMS

T-103A ROOF TECHNOLOGY PLAN - AREA A

T-121A FIRST FLOOR - AREA A - SECURITY

T-121A2 HANGAR SHOP - AREA A2 - SECURITY SYSTEMS

T-121B FIRST FLOOR - AREA B - SECURITY

T-121B2 FIRST FLOOR - AREA B2 - SECURITY

T-121C FIRST FLOOR - AREA C - SECURITY

T-123A ROOF SECURITY PLAN - AREA A

T-401 ENLARGED PLANS

T-402 ENLARGED PLANS

T-403 ENLARGED PLANS

T-404 ENLARGED PLANS

T-405 ENLARGED PLANS

T-501 DETAILS

T-502 DETAILS

T-503 DETAILS

T-701 ONE-LINE DIAGRAMS

Sheets in Volume: 71

M

VFD

RACEWAY SYMBOLS

SURFACE MOUNTED CONDUIT

JUNCTION BOX - CEILING MOUNTED

CONCEALED CONDUIT IN CEILING OR WALL

WIREWAY, SIZE AND TYPE

AS INDICATED ON DRAWINGS

JUNCTION BOX - WALL MOUNTED

J

J

JUNCTION BOX - WALL MOUNTED

SECURITY ACCESS DOOR POWER

JACD

RECEPTACLE SYMBOLS

DUPLEX RECEPTACLE TEXT INDICATES MOUNTING HEIGHT

CEILING MOUNTED DOUBLE DUPLEX RECEPTACLE

SPLIT WIRED DUPLEX RECEPTACLE

SIMPLEX RECEPTACLE

DOUBLE DUPLEX RECEPTACLE

SPECIAL PURPOSE CONNECTION, SEE EQUIPMENT

WIRING SCHEDULE

WELDING RECEPTACLE

DISCONNECT/WELDING RECEPTACLE

DISCONNECT/WELDING RECEPTACLE, NEMA 4X

MULTI-OUTLET SURFACE RACEWAY -

REFER TO KEYED NOTES &

SPECIFICATIONS FOR TYPES

CEILING MOUNTED DUPLEX RECEPTACLE

CEILING MOUNTED SPECIAL PURPOSE

CONNECTION, SEE EQUIPMENT WIRING

SCHEDULE

ABOVE COUNTER DUPLEX RECEPTACLE. MOUNT 6" TO

CENTERLINE ABOVE COUNTER OR BACKSPLASH

EMERGENCY SHADING MODIFIER

C

F FLOOR BOX

P POKE THRU

C

C

60"

DENOTES SWITCH LEG FOR SWITCHED OUTLETSa

RECEPTACLE & FLOOR BOX NOTATIONS:

DENOTES HORIZONTALLY MOUNTED OUTLETSH

DENOTES TAMPER RESISTANT SAFETY OUTLETSTR

DENOTES WEATHER PROOF OUTLETSWP

DENOTES EXPLOSION PROOF CLASS 1 DIVISION 2 DEVICEX2

DENOTES EXPLOSION PROOF CLASS 1 DIVISION 1 DEVICEX1

DENOTES GROUND FAULT INTERRUPTER OUTLETSGFCI

DENOTES COMBINATION DUPLEX/USB OUTLETSUSB

DENOTES ISOLATED GROUND OUTLETSIG

DENOTES ELECTRIC WATER COOLER OUTLETSEWC

4X

CORD REELE

CONTACTORC

DENOTES 28VDC, 30A, 2P, 3W (NEMA FSL1-R)28V

DENOTES RECEPTACLE FOR WALL MOUNT TV (96" AFF)TV

DENOTES GROUND JACK, RATED 30A.G

DENOTES 120/208V, 400HZ, 30A, 4P (NEMA FSL4-R)4HZ

DENOTES OCCUPANCY CONTROLLED OUTLETSOC

MOUNT AT 6" TO CENTER ABOVE COUNTER/BACKSPLASHA

DENOTES NEMA 5-15R DUPLEX RECEPTACLED

CR

HOSE REEL FOR AIR OR EXHAUSTE HR

SERVICE & DISTRIBUTION SYMBOLS

GROUND ROD

GROUNDING CONDUCTORG

NEW PANELBOARD

EXISTING PANELBOARD

EMERGENCY POWER OFFEPO

LIGHTNING ROD

STATIC GROUND RECEPTACLE

GR

CONTACTORC

PUSH BUTTON

M2 - MOMENTARY CONTACT, TWO BUTTON SWITCH.

P

EQUIPMENT GROUND BUSEGB

CONNECTION TO GROUNDING

ELECTRODE

PANEL DESIGNATION KEY

FLOOR

2 L N L 1

TYPE

SYSTEM/SOURCE

VOLTAGE

SEQUENCE NUMBER OR LETTER

NUMBER OR LETTER IN SEQUENCE

I.E. 1,2,3 OR A,B,C

L - 208Y/120V H - 480Y/277V

N - NORMAL BRANCH

U - UNINTERRUPTIBLE SOURCE

E - EMERGENCY BRANCH (NEC 700)

L - LIGHTING PANELBOARD

D - DISTRIBUTION PANELBOARD

P - POWER/EQUIPMENT PANELBOARD

R - RECEPTACLE PANELBOARD

MSB - MAIN SWITCHBOARD

1 - FIRST FLOOR

M - MEZZANINE

MOTOR & EQUIPMENT CONNECTION SYMBOLS

1 PHASE MOTOR CONNECTION

EQUIPMENT CONNECTION

3 PHASE MOTOR CONNECTION

COMBINATION MAGNETIC MOTOR CONTROLLER

MANUAL MOTOR CONTROLLER (3 PHASE)

MAGNETIC MOTOR CONTROLLER

NON-FUSED DISCONNECT SWITCH

FUSED DISCONNECT SWITCH

MOTOR RATED SWITCH WITH OVERLOADS

VARIABLE FREQUENCY MOTOR CONTROLLER

GENERAL SYMBOLS

KEYED NOTE, USED TO DESCRIBE ADDITIONAL

INFORMATION OF WORK REQUIRED, SPECIFIC TO

THE SHEET AND/OR DETAIL IT IS SHOWN WITH.

DETAIL NUMBER / SHEET NUMBER#/E-###

9.###

# KITCHEN EQUIPMENT TAG. # REFERS TO

CORRESPONDING NUMBER IN KITCHEN

EQUIPMENT SCHEDULE.

LINE TYPE KEY

EXISTING TO BE REMOVED BY THIS

CONTRACTOR (DARK DASHED LINE)

EXISTING TO REMAIN WORK

(THIN SOLID LINE)

NEW WORK BY THIS CONTRACTOR

(DARK SOLID LINE)

NEW WORK UNDER FLOOR BY

THIS CONTRACTOR

ONE-LINE EQUIPMENT ENCLOSURE

PANEL DIVISION LINES

SITE UNDERGROUND ELECTRICE

SITE REMOVED UNDERGROUND

ELECTRIC

//E//

SINGLE POLE SWITCH

LUMINAIRE CONTROL SYMBOLS

PHOTO ELECTRIC CONTROL

OCCUPANCY SENSOR CEILING MOUNT

DAYLIGHT SENSOR

LIGHTING CONTROL PANEL

(x REPRESENTS PANEL DESIGNATION)

LUMINAIRE SYMBOLS

RECESSED LUMINAIRE

RECESSED TROFFER

RECESSED LINEAR

WALL MOUNTED EXIT SIGN

CEILING MOUNTED EXIT SIGN

UL 924 LISTED EMERGENCY LIGHTING BYPASS

CONTROL UNIT

OS X

DS

PE

LCP X

PT

ARROW DENOTES EXIT SIGN CHEVRON

EMERGENCY BATTERY UNIT

REMOTE POWER SUPPLY OR DRIVERPS

LOW VOLTAGE SWITCH

* DENOTES SWITCH NAME, SEE LIGHTING

CONTROL PANEL & SWITCH SCHEDULE.

L

SWITCH NOTATIONS:

3 DENOTES 3-WAY SWITCH

4 DENOTES 4-WAY SWITCH

WL DENOTES WET LOCATION SWITCH

D DENOTES WALL BOX DIMMER SWITCH

T DENOTES TIMER SWITCH

K DENOTES KEY SWITCH

P DENOTES PILOT SWITCH

OS DENOTES OCCUPANCY SENSOR

X1 DENOTES EXPLOSION PROOF CLASS 1 DIVISION 1 SWITCH

X2 DENOTES EXPLOSION PROOF CLASS 1 DIVISION 2 SWITCH

M MOMENTARY CONTACT SWITCH

C MAINTAINED CONTACT, THREE POSITION, CENTER OFF

F FAN SPEED CONTROL SWITCH

WALL WASH MODIFIER

EMERGENCY SHADING MODIFIER

PENDANT INDUSTRIAL

WALL BRACKET

WALL SURFACE LINEAR

RECESSED EMERGENCY BATTERY UNIT

SURFACE LINEAR/INDUSTRIAL LUMINAIRE

A1

1R#a

LUMINAIRE TYPE

LUMINAIRE CIRCUITRY & CONTROL KEY:

LOWER CASE LETTER INDICATES SWITCHLEG CONTROL

(R#) INDICATES CENTRALIZED LOW VOLTAGE RELAY NUMBER

(Z#) INDICATES DISTRIBUTED LOW VOLTAGE RELAY NUMBER

REFER TO LIGHTING CONTROL PANEL SCHEDULES

NUMBER INDICATES BRANCH PANEL CIRCUIT NUMBER

SE

SE: DENOTES LUMINAIRE IS SWITCHED/CONTROLLED DURING

NORMAL OPERATION AND OPERATES FROM EMERGENCY

BATTERY AND/OR EMERGENCY CIRCUIT UPON LOSS OF POWER.

NL: DENOTES LUMINAIRE IS UNSWITCHED FOR NIGHT LIGHT.

SURFACE ROUND LUMINAIRE

PENDANT ROUND LUMINAIRE

SITE SYMBOLS

ELECTRIC HANDHOLE

HH HANDHOLE, GENERIC

E

E ELECTRIC MANHOLE

TRANS

ELECTRIC TRANSFORMER

DEMOLITION GENERAL NOTES:

1. THE INFORMATION SHOWN IS BASED ON EXISTING DRAWINGS

AND SITE OBSERVATIONS TO ASSIST CONTRACTOR IN BIDDING.

THE ELECTRICAL DRAWINGS INDICATE EXISTING ELECTRICAL

ITEMS TO BE REMOVED. THE DRAWINGS ARE INTENDED TO

INDICATE THE SCOPE OF WORK REQUIRED AND DO NOT INDICATE

EVERY BOX, CONDUIT, OR WIRE THAT MUST BE REMOVED. THE

CONTRACTOR SHALL VISIT THE SITE PRIOR TO SUBMITTING A BID

AND VERIFY EXISTING CONDITIONS. REFER TO SPECIFICATIONS

FOR ADDITIONAL REQUIREMENTS.

2. DASHED WALLS ON THE FLOOR PLANS INDICATE EXISTING WALLS

BEING DEMOLISHED. REFER TO THE ARCHITECTURAL

DEMOLITION PLANS FOR THE EXACT EXTENT OF WORK REQUIRED

BY THIS PROJECT. REMOVE ALL DEVICES ON DASHED WALLS NOT

SHOWN ON THE CONTRACT DRAWINGS. REFER TO DEMOLITION

DRAWINGS OF OTHER TRADES. WHERE MOTORS CONTROL

PANELS, AND OTHER LOADS OR APPARATUS THAT HAVE

ELECTRICAL CONNECTION ARE BEING REMOVED, INCLUDE

DISCONNECTION AND REMOVAL OF ALL ASSOCIATED CONDUIT,

WIRING, ETC.

3. ELECTRICAL ITEMS (i.e., LIGHTING FIXTURES, PANELBOARDS, DISCONNECTS, MOTOR CONTROLLERS , ETC.) REMOVED AND

NOT RELOCATED REMAIN THE PROPERTY OF THE OWNER AND

SHALL BE TURNED OVER TO THE OWNER, IN A STORAGE AREA TO

BE DESIGNATED BY THE OWNER. EQUIPMENT BEING REMOVED

SHALL BE HANDLED SO AS NOT TO FURTHER REDUCE ITS VALUE

TO THE OWNER. THE CONTRACTOR SHALL DISPOSE OF

MATERIAL THE OWNER DOES NOT WANT TO REUSE OR RETAIN

FOR MAINTENANCE PURPOSES.

4. WHERE LIGHTS, SWITCHES, RECEPTACLES, ETC., ARE BEING

REMOVED ALL ASSOCIATED CONDUIT AND WIRE BACK TO THE

PANELBOARD OR FEEDER JUNCTION BOX SERVING THE DEVICE

SHALL ALSO BE REMOVED, UNLESS THE CONDUIT CAN BE

REUSED FOR NEW CONDUCTORS. THE CONTRACTOR SHALL

DISPOSE OF MATERIAL THE OWNER DOES NOT WANT TO REUSE

OR RETAIN FOR MAINTENANCE PURPOSES.

5. ALL BOXES THAT REMAIN IN PLACE IN EXISTING MASONRY WALLS

THAT ARE TO REMAIN SHALL BE PROVIDED WITH A BLANK

COVERPLATE. REFER TO SPECIFICATIONS FOR ADDITIONAL

REQUIREMENTS ASSOCIATED WITH TYPE AND ATTACHMENT.

6. ALL CONDUIT SHALL BE REMOVED WHERE WALLS ARE BEING

REMOVED. WHERE CONDUIT IS IN THE CONCRETE SLAB, CUT OFF

FLUSH, PULL OUT WIRE, AND PLUG. WHERE CONDUIT IS RUN

EXPOSED, ALL ASSOCIATED CLAMPS, SUPPORTS, HANGERS,

ETC., SHALL ALSO BE REMOVED. CONDUIT CONCEALED IN WALL

CONSTRUCTION MAY BE ABANDONED IN PLACE IF NOT AFFECTED

BY OTHER CONSTRUCTION.

7. THIS CONTRACTOR SHALL COORDINATE ALL HIS WORK,

INCLUDING PHASING WITH OTHER CONTRACTORS AT THE JOB

SITE BEFORE REMOVING EXISTING ELECTRICAL AND INSTALLING

NEW ITEMS.

8. EXISTING CONDUIT IN GOOD CONDITION, MAY BE REUSED IN

PLACE. RELOCATED EXISTING CONDUIT SHALL NOT BE ALLOWED.

BONDING CONDUCTORS SHALL BE INSTALLED IN ALL REUSED

CONDUIT TO ASSURE PROPER GROUND PATH.

9. MAINTAIN CIRCUIT CONTINUITY OF DEVICES LOCATED OUTSIDE

OF CONSTRUCTION AREA. DEVICE AND EQUIPMENT REMOVAL IN

CERTAIN LOCATIONS MAY REQUIRE THE INSTALLATION OF A

JUNCTION BOX TO RECONNECT CIRCUITS THAT REMAIN IN

OPERATION. EXTEND CONDUIT AND WIRING AS REQUIRED TO

MAINTAIN POWER TO REMAINING EQUIPMENT.

10. BALLASTS MANUFACTURED PRIOR TO 1980 CONTAIN PCBs AND

SHALL BE DISPOSED OF IN ACCORDANCE WITH SPECIFICATIONS.

11. HID AND FLUORESCENT LAMPS CONTAIN MERCURY AND SHALL

BE DISPOSED OF IN ACCORDANCE WITH SPECIFICATIONS.

12. CONTRACTOR SHALL REMOVE AND INSTALL ALL CEILING TILES

AS REQUIRED FOR THE EXECUTION OF ELECTRICAL WORK THAT

IS OUTSIDE THE CONTRACT LIMITS OF CONSTRUCTION.

CONTRACTOR SHALL REPLACE CEILING TILES WITH IDENTICAL

MATERIAL WHERE DAMAGED BY THIS CONTRACTOR.

13. PROVIDE REVISED TYPED CIRCUIT DIRECTORY IN

PANELBOARDS THAT HAVE CIRCUITS REMOVED OR ADDED

CIRCUITS.

14. REMOVE EXPOSED ABANDONED CONDUIT, INCLUDING

ABANDONED CONDUIT ABOVE ACCESSIBLE CEILING FINISHES.

CUT RACEWAY FLUSH WITH WALLS AND FLOORS, PATCH

SURFACES TO MATCH EXISTING. REMOVE ALL ASSOCIATED

CLAMPS, HANGERS, SUPPORTS, ETC. ASSOCIATED WITH

RACEWAY REMOVAL.

15. DISCONNECT AND REMOVE ABANDONED LUMINAIRES,

INCLUDING BRACKETS, STEMS, HANGERS, AND OTHER

ACCESSORIES.

16. DISCONNECT AND REMOVED ELECTRICAL DEVICES AND

EQUIPMENT SERVING UTILIZATION EQUIPMENT THAT HAS BEEN

REMOVED.

GENERAL NOTES:

1. REFER TO THE G SERIES DRAWINGS FOR CODE ANALYSIS PLANS,

INFORMATION AND NOTES.

2. THE CONTRACTOR SHALL BECOME FAMILIAR WITH THE DETAILS OF

WORK, VERIFY DIMENSIONSIN THE FIELD, AND ADVISE THE

CONTRACTING OFFICER OF ANY DISCREPANCY BEFORE PERFORMING

ANY WORK.

3. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE ABA

(ARCHITECTURAL BARRIERS ACT).

4. REFER TO ARCHITECTUAL DRAWINGS FOR FIRE RATED WALLS AND

FLOORS. MAKE RATED PENETRATIONS AS REQUIRED.SEAL ALL RATED

PENETRATIONS AS IDENTIFIED IN DIVISION 1 REQUIREMENTS.

5. FLUSH MOUNT ALL TOGGLE SWITCHES AND RECEPTACLES AT HEIGHTS

ABOVE FINISHED FLOOR AS SHOWN IN THE DEVICE MOUNTING HEIGHT

DETAIL ON SHEET E-501, EXCEPT WHERE OTHERWISE NOTED. DEVICES

MAY BE SURFACE MOUNTED WHEN CONDUIT IS SPECIFIED EXPOSED.

6. CIRCUIT NUMBERS ARE SHOWN FOR CIRCUIT IDENTIFICATION.

CIRCUITING SHALL AGREE WITH NUMBERING ON THE PANEL SCHEDULES

PROVIDED. BALANCE THE LOAD ON PANELS AS EVENLY AS POSSIBLE

BETWEEN EACH PHASE.

7. CIRCUITS SERVING EMERGENCY AND EXIT LUMINAIRES WILL BE RUN IN

SEPARATE RACEWAY FROM ALL OTHER CIRCUITS.

8. A #12 GREEN INSULATED GROUND CONDUCTOR SHALL BE INSTALLED

WITH CIRCUIT CONDUCTORS TO ALL RECEPTACLES.

9. CONCEAL ALL CONDUIT IN WALLS, PARTITIONS, ABOVE CEILING, ETC.

UNLESS OTHERWISE INDICATED ON THE PLANS OR IN THE

SPECIFICATIONS. CONDUIT IN MECHANICAL ROOMS, AND STORAGE

ROOMS WITHOUT CEILINGS MAY BE EXPOSED ON BUILDING STRUCTURE.

WHERE RACEWAY IS REQUIRED ON EXISTING CONCRETE AND MASONY

WALLS, SURFACE RACEWAY MAY BE USED IN LIEU OF CHANNELING

WALLS TO ALLOW CONCEALED ROUTING. THE RACEWAY SHALL BE

SINGLE CHANNEL STYLE TYPE WITH IVORY FINISH. THIS APPLIES FOR

BRANCH CIRCUIT CONDUITS UP TO 3/4" SIZE. CONDUITS LARGER THAN

3/4" MAY BE ROUTED EXPOSED, BUT INSTALLED PARALLEL AND/OR

PERPENDICULAR TO BUIDLING LINES AND RUN AS UNOBTRUSIVLY AS

POSSIBLE.

10. BOXES LOCATED ON OPPOSITE SIDES OF NON-RATED WALLS SHALL BE

OFFSET A MINIMUM OF 6" HORIZONTALLY. "THRU-THE-WALL" BOXES

SHALL NOT BE ALLOWED WITHOUT PRIOR WRITTEN APPROVAL OF THE

ARCHITECT/ENGINEER.

11. COORDINATE AND CO-LOCATE WALL MOUNTED RECEPTACLE

LOCATIONS WITH TECHNOLOGY (VOICE/DATA,CATV,FIDS, ETC) OUTLETS

SHOWN ON THE T-SERIES DRAWINGS.UNLESS OTHERWISE NOTED, EACH

TECHNOLOGY OUTLET SHALL BE LOCATED WITHIN 6"OF ITS ASSOCIATED

RECEPTACLE. ASSOCIATED RECEPTACLE SHALL BE DEFINED AS THE

RECEPTACLE NEAREST THE LOCATION OF, AND AT THE SAME HEIGHT

AS,THE TECHNOLOGY OUTLET WHEN MULTIPLE RECEPTACLES ARE

SHOWN ON A WALL.

12. DUPLEX RECEPTACLES FOR ELECTRIC WATER COOLERS (EWC) SHALL

BE CONCEALED BEHIND WATER COOLER ACCESS PLATE OR BE

DIRECTLY BELOW AND CENTERED ON EWC. CONTRACTOR SHALL VERIFY

TYPE OF EWC TO BE INSTALLED.

13. CONTRACTOR SHALL VERIFY ALL FURNITURE, MODULAR FURNITURE

AND EQUIPMENT LOCATIONS WITH ARCHITECTURAL PLANS, ELEVATIONS

AND REVIEWED SHOP DRAWINGS. PRIOR TO MAKING THE ACTUAL

ELECTRICAL INSTALLATION THIS CONTRACTOR SHALL ADJUST

RECEPTACLES, OUTLETS OR CONNECTION LOCATIONS TO

ACCOMMODATE FURNITURE AND/OR EQUIPMENT.

14. ELECTRICAL AND TELECOMMUNICATIONS EQUIPMENT SHALL BE

MOUNTED TO AVOID IMPEDANCE OF, OPERATION OF, AND/OR ACCESS TO

ELECTRICAL AND MECHANICAL EQUIPMENT. ALL MOUNTING OF

ELECTRICAL AND TELECOMMUNICATIONS EQUIPMENT, ON EQUIPMENT

SUPPLIED BY ANOTHER CONTRACTOR, SHALL BE APPROVED IN ADVANCE

BY THE OTHER CONTRACTOR.

15. CONTRACTOR TO PROVIDE SUITABLE MECHANICAL PROTECTION

AROUND ALL CONDUITS STUBBED OUT FROM FLOORS, WALLS OR

CEILINGS DURING CONSTRUCTION TO PREVENT BENDING OR DAMAGING

OF STUB OUTS DUE TO CARELESSNESS WITH CONSTRUCTION

EQUIPMENT.

16. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OPENINGS REQUIRED

IN WALLS. ALL OPENINGS SHALL BE REPAIRED TO MATCH EXISTING BY A

QUALIFIED CONTRACTOR AT THE EXPENSE OF THIS CONTRACTOR. ALL

CONDUITS THROUGH WALLS SHALL BE GROUTED OR SEALED INTO

OPENINGS.

17. DRAWINGS INDICATE THE EXTENT OF HAZARDOUS OR WET LOCATIONS.

INSTALLATION MEANS AND METHODS SHALL BE SUITABLY RATED FOR

THE ENVIRONMENT INDICATED ON THE DRAWINGS.

18. CONTRACTOR SHALL REMOVE AND REINSTALL ALL CEILING TILES AS

REQUIRED FOR THE EXECUTION OF ELECTRICAL WORK THAT IS OUTSIDE

THE CONTRACT LIMITS OF CONSTRUCTION. CONTRACTOR SHALL

REPLACE CEILING TILES WITH IDENTICAL MATERIAL WHERE DAMAGED BY

THIS CONTRACTOR.

19. ALL INTERLOCKING REQUIRED BY THE DRIVE MANUFACTURER

BETWEEN THE VARIABLE FREQUENCY DRIVE AND THE DISCONNECT

SWITCHES SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL

CONTRACTOR.

20. SCCR RATINGS LISTED FOR EQUIPMENT ARE MINIMUM REQUIREMENTS

FOR BUS BRACING AND DEVICE RATING. ALL EQUIPMENT SHALL BE FULLY

RATED UNLESS SPECIFICALLY NOTED AS SERIES RATED.

21. SHADED LUMINAIRE OR DEVICE INDICATES LUMINIARE OR DEVICE IS

CONNECTED TO AN EMERGENCY CIRCUIT AND/OR OPERATES FROM

EMERGENCY BATTERY PACK INTERGAL TO FIXTURE OR LIGHTING

INVERTER.

22. ALL EMERGENCY BATTERY UNITS SHALL BE SERVED FROM AN

UNSWITCHED LEG OF THE LIGHTING BRANCH CIRCUIT SERVING THE

SPACE OR AREA.

23. MOUNT ALL OVERHEAD UTILITIES AND OTHER FIXTURES WEIGHING 31

POUNDS OR MORE (EXCLUDING DISTRIBUTED SYSTEMS SUCH AS PIPING

NETWORKS THAT COLLECTIVELY EXCEED THAT WEIGHT) USING EITHER

RIGID OR FLEXIBLE SYSTEMS TO MINIMIZE THE LIKELIHOOD THAT THEY

WILL FALL AND INJURE BUILDING OCCUPANTS. DESIGN ALL EQUIPMENT

MOUNTINGD TO RESIST FORCES OF 0.5 TIMES THE EQUIPMENT WEIGHT

IN ANY HORIZONTL DIRECTION AND 1.5 TIMES THE EQUIPMENT WEIGHT IN

THE DOWNWARD DIRECTION.

TEMPORARY FACILITIES WORK SCOPE:

REFER TO THE CIVIL DRAWINGS FOR THE LOCATION OF THE TEMPORARY

FACILITIES PORTABLE BUILDINGS. THE CONTRACTOR SHALL PROVIDE

TEMPORARY SERVICE FOR A MINIMUM OF 4 PORTABLE BUILDINGS. FOR

THE PURPOSES OF BIDDING ASSUME A 200A, 120/208V, 3-PHASE SERVICE

TO EACH BUILDING. COORDINATE WITH CONTRACT OFFICER FOR ROUTING

AND SOURCE OF SERVICE FEEDS.

SHEET NO.:

SHEET CONTENTS

DO NOT SCALE DRAWINGS

ISSUED

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

710 Avis Drive, #100 Ann Arbor, MI 48108-9649 phone: 810-956-9300 fax: 810-956-9281

/1

/2

:1 :3

P

M C

R e v it L o c a l\

.0

-E -R k e ff .k u re lla Y

A

.r v t

NOTES, SYMBOLS &

ABBREVIATIONS

FJRP112701ANG PRO. NO.:

3258000-131303.01

KAF

MAM

July 20, 2022

KSK

N C

A N

G

T

H A

W

C H

A R

L O

T T

E D

O U

G L A

S I A

P C

H A

R L O

T T

E N

O R

T H

C A

R O

L

IN

A

R E

P A

IR

M

A

IN

T E

N A

N C

E H

A N

G A

R B

U

IL

D

IN

G

E-001

ELECTRICAL ABBREVIATIONS

SS STAINLESS STEEL

SW SWITCH

SWBK SWITCH BANK

TBR TO BE REMOVED

TCP TEMPERATURE CONTROL PANEL

TFA TO FLOOR ABOVE

TFB TO FLOOR BELOW

TYP TYPICAL

UC UNIT COOLER

UG UNDERGROUND

UH UNIT HEATER

UNO UNLESS NOTED OTHERWISE

UV UNIT VENTILATER

V VOLTS

VER VEHICLE EXHAUST REEL

VFD VARIABLE FREQUENCY DRIVE

VS VERSUS

W WATTS

WCC WATER COOLED CONDENSER

WFE WELDING FUME EXTRACTOR

WH WATER HEATER

WL WET LOCATION LISTED

WP WEATHERPROOF

XFMR TRANSFORMER

XP EXPLOSION PROOF

ELECTRICAL ABBREVIATIONS

3R NEMA 3R RATING

4X NEMA 4X RATING

A AMPERES

A/E ARCHITECT / ENGINEER

AAC ABOVE ACCESSIBLE CEILING

ACCU AIR COOLED CONDENSING UNIT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHU AIR HANDLING UNIT

ALT ALTERNATE

APE AIRCRAFT PROCESS EQUIPMENT

ATS AUTOMATIC TRANSFER SWITCH

BLDG BUILDING

BRKR BREAKER

C CONDUIT

CB CIRCUIT BREAKER

CF CIRCULATION FAN

CH CHILLER

CHWP CHILLED WATER PUMP

CKT CIRCUIT

CP CIRCULATION PUMP

CRAC COMPUTER ROOM AIR CONDITIONER

CRP CONDENSATION RETURN

CT COOLING TOWER

CUH CABINET UNIT HEATER

DC DROP CORD

DDC DIGITAL CONTROL PANEL

DH DUCT HEATER

DISC DISCONNECT

DN DOWN

DO DOOR OPERATOR

DWG DRAWING

E/O ELECTRICAL-TO-OPTICAL CONVERTER

EC ELECTRICAL CONTRACTOR

ECB ENCLOSED CIRCUIT BREAKER

EF EXHAUST FAN

EM EMERGENCY

EMT ELECTRICAL METALLIC TUBING

ES EQUIPMENT SUPPLIER

ETR EXISTING TO REMAIN

EWC ELECTRICAL WATER COOLER

EWH ELECTRICAL WATER HEATER

F FUSED

FA FIRE ALARM

FAF FORCED AIR FURNACE

FCU FAN COIL UNIT

GC GENERAL CONTRACTOR

GFI GROUND FAULT INTERRUPTER

GND GROUND

GWH GAS WATER HEATER

HD HAND DRYER

HEF HEATER EXHAUST FAN (EXHAUSTER)

HP HORSEPOWER

HVAC HEATING, VENTILATION, AIR CONDITIONING

HWB HOT WATER BOILER

HWP HOT WATER PUMP

IEWH INSTANTANEOUS ELECTRIC WATER HEATER

IH INFRARED HEATER

IMC INTERMEDIATE METALLIC CONDUIT

IWH INSTANTANEOUS WATER HEATER

J-BOX JUNCTION BOX

LFS LIGHTING FIXTURE SCHEDULE

LPS LIGHTNING PROTECTION SYSTEM

MAU MAKE-UP AIR UNIT

MAX MAXIMUM

MC MECHANICAL CONTRACTOR

MCC MOTOR CONTROL CENTER

MDF MAIN DISTRIBUTION FRAME

MDP MAIN DISTRIBUTION PANEL

MIN. MINIMUM

MNS MASS NOTIFICATION SYSTEM

MOD MOTOR OPERATED DOOR

MTD MOUNTED

MTG MOUNTING

MTS MANUAL TRANSFER SWITCH

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NL/EL NIGHT LIGHT AND EMERGENCY LIGHT

NTS NOT TO SCALE

OC ON CENTER

OFCI OWNER FURNISHED, CONTRACTOR INSTALLED

OFOI OWNER FURNISHED, OWNER INSTALLED

PH PHASE

PNL PANEL

PS PROJECTION SCREEN

PVC POLYVINYL CHLORIDE

RCP RADIANT CEILING PANEL

RECPT RECEPTACLE

REF REFRIGERATOR

REQ'D REQUIRED

RF RETURN FAN

RGS RIGID GALVANIZED STEEL CONDUIT

MAY ALSO BE REFERENCED AS RMC OR GRC

RMC RIGID METAL CONDUIT

RTU ROOF TOP UNIT

S/N SOLID NEUTRAL

SE SERVICE ENTRANCE

SEC-P SECURITY PANEL

SF SUPPLY FAN

SP SUMP PUMP

F

F

GR

GR

GR GR

GR

GR

GR

GR

GR

GR

GR

GRGR

GR

GR

GR

GR

GR

GR GR

PP

P P

GR

P P

P P

P P

EB

EA

NA

H

G

10 9 8

E

D

C

B

A

11 7 6 5 4 3 2 1

F

J

K

E-401

HFF

UH-7

UH-8

EF-11

EF-10

UH-4

EF-4

EF-5

EF-6

EF-4

MDO

MDO

EF-7

EF-8

EF-9

UH-6

EF-12

UH-5

E-403

E-403

9.019

HEF 9.019

9.015

TYP. 9.019

9.014

9.012

TYP.

9.0199.019

C

C

C

C

C

9.022

TYP.

M2

M2 M2

M2

9.021 9.021

M A

T C

H L

IN

E

S E

E

E

D

B

M A

T C

H L

IN

E

S E

E

E

D C

MATCHLINE

SEE 1 / ED101B

M

ATC

H

LIN

E

SEE 1 / ED

101C

9.020

D

M2 M2

M2M2 M2

M2

9.021

9.021 9.021

9.021 9.021

9.021

DEMOLITION GENERAL NOTES:

1. REFER TO DRAWING E-001 FOR DEMOLITION GENERAL NOTES, SYMBOLS &

ABBREVIATIONS.

KEY PLAN

A

B

C

SHOP

SOUTH

SHOP

NORTH

B2

A2

A2

C2

SHEET NO.:

SHEET CONTENTS

DO NOT SCALE DRAWINGS

ISSUED

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

710 Avis Drive, #100 Ann Arbor, MI 48108-9649 phone: 810-956-9300 fax: 810-956-9281

/1

/2

:1 :4

P

M C

R e v it L o c a l\

.0

-E -R k e ff .k u re lla Y

A

.r v t

FIRST FLOOR

ELECTRICAL

DEMOLITON PLAN -

AREA A

FJRP112701ANG PRO. NO.:

3258000-131303.01

KAF

MAM

July 20, 2022

KSK

N C

A N

G

T

H A

W

C H

A R

L O

T T

E D

O U

G L A

S I A

P C

H A

R L O

T T

E N

O R

T H

C A

R O

L

IN

A

R E

P A

IR

M

A

IN

T E

N A

N C

E H

A N

G A

R B

U

IL

D

IN

G

ED101A

1/16" = 1'-0"1

FIRST FLOOR ELECTRICAL DEMOLITON PLAN - AREA A

KEYED NOTES

9.012 DISCONNECT AND REMOVE FLOODLIGHT, SUPPORTS AND MOUNTING

BRACKETS. LIGHT SWITCH AND WIRING TO BE REMOVED BUT BACKBOX AND

CONDUIT TO REMAIN IN PLACE FOR NEW SWITCH AND WIRING AS SHOWN

ON DRAWING 1/E-121A. EXISTING LIGHTING BRANCH CIRCUIT WIRING TO BE

REMOVED BACK TO SOURCE. RACEWAY TO REMAIN IN PLACE FOR NEW

LIGHTING BRANCH WIRING TO NEW LIGHTING FIXTURE AS NOTED ON

DRAWING 1/E-121A.

9.014 DIVISION 26 CONTRACTOR TO DISCONNECT AND REMOVE POWER BACK TO

SOURCE. EQUIPMENT TO BE REMOVED BY DIVISION 23 CONTRACTOR.

9.015 EXHAUST FAN PILOT LIGHT CONTROL SWITCH. EC TO DISCONNECT AND

REMOVE BACK TO SOURCE.

9.019 OVERHEAD HANGER LIGHTING CONTROL. REMOVE SWITCHES AND WIRING

BACK TO LIGHTING CONTACTOR(S) LOCATED ABOVE PANELBOARD 'EH' IN

ELECTRICAL/MECHANICAL ROOM H103. BACKBOX AND CONDUIT TO REMAIN

IN PLACE AND UTILIZED FOR NEW OVERHEAD HANGER LIGHTING CONTROL.

REFER TO DRAWING 1/E-101A.

9.020 SURFACE MOUNTED CLASS 1, DIV. 2, 200A, 3 POLE, 4 WIRE, 600V

RECEPTACLE. DISCONNECT AND RELOCATE RECEPTACLE. EXTEND

EXISTING FEEDER AND CONDUIT (3#4/0 &1#6 GND. IN 2"C) TO NEW LOCATION

AS SHOWN ON DRAWING 1/E101A.

9.021 EXISTING TWO BUTTON DOOR CONTROL STATION TO BE DISCONNECTED

AND REMOVED INCLUDING WIRING. EXISTING FLUSH MOUNTED BACKBOX

AND CONDUIT TO MAIN CONTROL PANEL TO REMAIN IN PLACE FOR

INSTALLATION OF NEW DOOR KEY SWITCH, PUSHBUTTON CONTROL AS

SHOWN ON DRAWING 1/E-101A.

9.022 SURFACE MOUNTED RECEPTACLE, CLASS 1, DIVISION 2, RATED 200 A, 3

POLE, 4 WIRE, 460 V, 3 PHASE WITH GROUND.

3 3

OS

OS

OS

O S

3 3

OS

F

FF F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

J J J

J

F

F

P

P

M

P

P

E P

O

E P

O

EPO

E P

O

EPO

N9 N8 N7 N6 N5N4 N3 N2 N1

ND

NC

NB

NA

E-401

PANEL AC

PANEL NWLA

E P

O

BRIDGE

CRANE

48"

48"

48"

96"

CTV

96" 96"

96"

TV

96"

TV

96"

TV

96"

TV

PROJECTION

SCREEN

CTV

TV

TV CTV

96"

96"

96"96"

9.001

9.001

9.001

9.001

9.001

9.001

9.001

9.001

9.001

EH-3

EH-4

UH-4A

UH-3A

DODODO

UH-1AUH-2A

EH-2

HWP-1

CPH-2

BOILER

MZ-2

AIR DRYER

AIR COMPRESSORS

CHILLER-2

CHILLER-1

G

WP/GFCI

9.036

TCPHUMIDIFIER

DUPLEX

PANEL T2

48"

48"

UH-6A

CIRC PUMP

WTR HTR

9.031

9.029

28VDC

G

4HZ

D

9.030 9.030

9.030

TV

TV

9.035

WP/GFCI

9.029 9.032

4HZ

28DVC

D G D G

28VDC4HZ

28VDC 4HZ

GD

28VDC 4HZ

GD

4HZ28VDC

D G

9.030 9.030

9.029

FIRE SUPRESSION

COMPRESSOR

HEAT TRACE

HEAT TRACE

9.033

NWL-31,33

9.035

9.035

9.035

9.029

9.029

9.029

9.029EF-8A

EWC

EWC

GFCI

WP/GFCI

GFCI

UH-5A

CTV

(CLG MTD)

9.001

9.001

EF-7A

9.001

9.037

MATCHLINE

SEE 1 / ED101A

M

ATC

H

LI

N E

SEE 1

ED

1A

9.030

DEMOLITION GENERAL NOTES:

1. REFER TO DRAWING E-001 FOR DEMOLITION GENERAL NOTES, SYMBOLS &

ABBREVIATIONS.

KEY PLAN

A

B

C

SHOP

SOUTH

SHOP

NORTH

B2

A2

A2

C2

SHEET NO.:

SHEET CONTENTS

DO NOT SCALE DRAWINGS

ISSUED

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

710 Avis Drive, #100 Ann Arbor, MI 48108-9649 phone: 810-956-9300 fax: 810-956-9281

/1

/2

:1 :5

P

M C

R e v it L o c a l\

.0

-E -R k e ff .k u re lla Y

A

.r v t

FIRST FLOOR

ELECTRICAL

DEMOLITON PLAN -

AREA B

FJRP112701ANG PRO. NO.:

3258000-131303.01

KAF

MAM

July 20, 2022

KSK

N C

A N

G

T

H A

W

C H

A R

L O

T T

E D

O U

G L A

S I A

P C

H A

R L O

T T

E N

O R

T H

C A

R O

L

IN

A

R E

P A

IR

M

A

IN

T E

N A

N C

E H

A N

G A

R B

U

IL

D

IN

G

ED101B1/8" = 1'-0"1

FIRST FLOOR ELECTRICAL DEMOLITON PLAN - AREA B

KEYED NOTES

9.001 REMOVE EXISTING SWITCH. UTILIZE EXISTING BACKBOX FOR NEW LIGHTING

CONTROL IN THIS AREA. REFER TO E-121B & E-121C FOR NEW LIGHTING

CONTROLS.

9.029 SURFACE MOUNTED RACEWAY CONSISTING OF THREE (3) SEPARATE

RACEWAYS ONE (1) FOR 120 VAC., 60HZ, ONE (1) FOR 28 VDC., ONE (1) FOR

120/208 VAC., 400 HZ POWER AND #2 GROUNDING CONDUCTOR.

DISCONNECT AND REMOVE COMPLETELY INCLUDING BRANCH CIRCUIT

WIRING BACK TO SOURCE AND GROUNDING CONDUCTOR.

9.030 SURFACE MOUNTED RACEWAY CONSISTING OF THREE (3) SEPARATE

RACEWAYS ONE (1) FOR 120 VAC., 60HZ, ONE (1) FOR 28 VDC., ONE (1) FOR

120/208 VAC., 400 HZ POWER AND #2 GROUNDING CONDUCTOR.

DISCONNECT AND REMOVE FOR RELOCATION AS SHOWN ON DRAWING

1/E-101B. REWORK AND EXTEND EXISTING BRANCH CIRCUIT WIRING AS

NECESSARY TO NEW LOCATION . CUT RACEWAY AS NECESSARY TO ALLOW

INSTALLATION AT RELOCATED WALLS AT INDICATED LENGTHS .

9.031 COMBINATION FLUSH MOUNTED FLOOR BOX WITH 15 AMP 125 VAC., DUPLEX

RECEPTACLE AND VOICE/DATA OUTLET TO REMAIN.

9.032 TYPICAL: FLOOR BOXES LABELED AS 4HZ ARE CURRENTLY NOT SET TIGHT

IN CONCRETE FLOOR. EC SHALL INVESTIGATE AND REPAIR AS NECESSARY

SO THAT FLOOR BOX SETS FLUSH AND TIGHT IN CONCRETE SLAB. IF

NECESSARY SAW CUT FLOOR AROUND BOX AND RESET IN NEW CONCRETE.

9.033 EXISTING ELECTRICAL EQUIPMENT. REFER TO DRAWING 1/E-405, PHOTO

NO. 1 FOR WORK ASSOCIATED WITH EQUIPMENT.

9.035 DISCONNECT AND REMOVE 'EPO' THREE POSITION SWITCH AND EXTEND

EXISTING WIRING TO NEW LOCATIONS AS SHOWN ON DRAWING 1/E-101B

9.036 TYPICAL FOR ALL UON. REPLACE ALL EXISTING DUPLEX RECEPTACLES

WITH A NEW NEMA 5-20R RECEPTACLE. EXISTING OUTLET BOX AND WIRING

MAY BE REUSED.

9.037 DUE TO DEMOLITION OF EXISTING DEVICES CIRCUIT CONTINUITY TO THIS

DEVICE MAY NOT EXIST. EXTEND EXISTING WIRING AND CONDUIT AS

NECESSARY TO EXISTING 120 V BRANCH CIRCUIT SERVING THIS AREA.

OS

OS

O S

D D

D

3 3

3 3

J

J

F

J J

J

F

F

E5

E4

E3

E2

E1

ECEBEA

E-401

96"

TV

96"

96"

CTV

CTV

EH-1

EDH-1

EDH-2

9.0269.026

9.027

WP/GFCI

EWH

EWC

CTV

GFCI

TV

WP/GFCI

WP/GFIC

9.026

9.026

CHP-1

9.001

PS

96"

PS

9.0399.039

96" 96"

GFCI

GFCI

GFCI

M A

T C

H L

IN

E

S E

E

E

D A

M A

T C

H L

IN

E

S E

E

E

D A

9.036

9.039

9.039

TYP

E5

E4

E3

E2

E1

EC

EB

EA

DN FROM HIGH ROOF

DN FROM HIGH ROOF

EF-1A

G

G

G G G G

G

G

G

G

G

G

G

G G G G G

G

G

G

G

G

G

G

G

G

G

TR

RD

THROUGH ROOF

CONNECTOR TYP.

G

G

G G

G

G

TR

RD

RD

TR

9.025

9.025

TR

M A

T C

H L

IN

E

S E

E

T

D A

M A

T C

H L

IN

E

S E

E

E

D A

DEMOLITION GENERAL NOTES:

1. REFER TO DRAWING E-001 FOR DEMOLITION GENERAL NOTES, SYMBOLS &

ABBREVIATIONS.

KEY PLAN

A

B

C

SHOP

SOUTH

SHOP

NORTH

B2

A2

A2

C2

SHEET NO.:

SHEET CONTENTS

DO NOT SCALE DRAWINGS

ISSUED

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

710 Avis Drive, #100 Ann Arbor, MI 48108-9649 phone: 810-956-9300 fax: 810-956-9281

/1

/2

:2 :0

P

M C

R e v it L o c a l\

.0

-E -R k e ff .k u re lla Y

A

.r v t

FIRST FLOOR &

ROOF ELECTRICAL

DEMOLITION PLAN -

AREA C

FJRP112701ANG PRO. NO.:

3258000-131303.01

KAF

MAM

July 20, 2022

KSK

N C

A N

G

T

H A

W

C H

A R

L O

T T

E D

O U

G L A

S I A

P C

H A

R L O

T T

E N

O R

T H

C A

R O

L

IN

A

R E

P A

IR

M

A

IN

T E

N A

N C

E H

A N

G A

R B

U

IL

D

IN

G

ED101C1/8" = 1'-0"1

FIRST FLOOR ELECTRICAL DEMOLITON PLAN - AREA C

KEYED NOTES

9.001 REMOVE EXISTING SWITCH. UTILIZE EXISTING BACKBOX FOR NEW LIGHTING

CONTROL IN THIS AREA. REFER TO E-121B & E-121C FOR NEW LIGHTING

CONTROLS.

9.025 ALL LIGHTNING PROTECTION SYSTEM THROUGH THE ROOF AND MAIN

DOWN CONDUCTORS TO GROUND RODS ARE TO REMAIN IN PLACE FOR

REUSE WITH NEW LIGHTNING PROTECTION SYSTEM.

9.026 SYSTEM FURNITURE POWER CONNECTION WITH 3/4" FLEXIBLE CONDUIT

CONNECTION.

9.027 SYSTEM FURNITURE POWER CONNECTION WITH 3/4" FLEXIBLE CONDUIT

CONNECTION. REMOVE BRANCH CIRCUIT WIRING ONLY BACK TO SOURCE.

9.036 TYPICAL FOR ALL UON. REPLACE ALL EXISTING DUPLEX RECEPTACLES

WITH A NEW NEMA 5-20R RECEPTACLE. EXISTING OUTLET BOX AND WIRING

MAY BE REUSED.

9.039 DISCONNECT AND REMOVE DEVICE AND WIRING. BACKBOX AND CONDUIT

TO REMAIN FOR INSTALLATION OF NEW DEVICE AND WIRING SHOWN ON

DRAWING 1/E-101C.

1/8" = 1'-0"2

ROOF ELECTRICAL & LIGHTNING PROTECTION DEMOLITION PLAN - AREA C

EA

NA

H

G

10 9 8

E

D

C

B

A

11 7 6 5 4 3 2 1

F

J

K

IFCP IFCP IFCP

HEF HEF

MDO

IFCP

IFCP

IFCP

UH-9 UH-10

HEF

IFCP

IFCP HEF

HEFHEF

IFCP

IFCP

HEF

HEFHEF

IFCP

IFCP

HEF

IFCP

IFCP

HEF

MDO

HEF

IFCP

HEF HEF

IFCP

HEF

MDO

E-403

LOCATED AT CATWALK LOCATED AT CATWALK

TYP.

TYP.

TYP.

HANGAR DOOR

WIREWAY & DOOR(S)

DISCONNECT

9.011

9.018 9.017

9.017

9.014

M A

T C

H L

IN

E

S E

E

E

D B

M A

T C

H L

IN

E

S E

E

E

D C

MATCHLINE

SEE 1 / ED102B

M

ATC

H

LIN

E

SEE 2 / ED

101C

TYP.

TYP.

9.018

9.018

MDO

MDO

DEMOLITION GENERAL NOTES:

1. REFER TO DRAWING E-001 FOR DEMOLITION GENERAL NOTES, SYMBOLS &

ABBREVIATIONS.

KEY PLAN

A

B

C

SHOP

SOUTH

SHOP

NORTH

B2

A2

A2

C2

SHEET NO.:

SHEET CONTENTS

DO NOT SCALE DRAWINGS

ISSUED

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

710 Avis Drive, #100 Ann Arbor, MI 48108-9649 phone: 810-956-9300 fax: 810-956-9281

/1

/2

:2 :0

P

M C

R e v it L o c a l\

.0

-E -R k e ff .k u re lla Y

A

.r v t

MEZZANINE FLOOR &

CATWALK LEVEL

ELECTRICAL

DEMOLITION PLAN -

AREA A

FJRP112701ANG PRO. NO.:

3258000-131303.01

KAF

MAM

July 20, 2022

KSK

N C

A N

G

T

H A

W

C H

A R

L O

T T

E D

O U

G L A

S I A

P C

H A

R L O

T T

E N

O R

T H

C A

R O

L

IN

A

R E

P A

IR

M

A

IN

T E

N A

N C

E H

A N

G A

R B

U

IL

D

IN

G

ED102A

1/16" = 1'-0"1

MEZZANINE FLOOR & CATWALK LEVEL ELECTRICAL DEMOLITON PLAN - AREA A

KEYED NOTES

9.011 INFRARED CONTROL PANEL LOCATED ON HANDRAIL OF CATWALK.

DISCONNECT AND REMOVE BRANCH CIRCUIT CONDUIT AND WIRING BACK

TO SOURCE. CONTROL PANEL REMOVED BY DIVISION 23 CONTRACTOR.

9.014 DIVISION 26 CONTRACTOR TO DISCONNECT AND REMOVE POWER BACK TO

SOURCE. EQUIPMENT TO BE REMOVED BY DIVISION 23 CONTRACTOR.

9.017 JUNCTION BOX LOCATED ON CATWALK AND CONNECTED TO BRIDGE CRANE

CONTROLLER. EC TO DISCONNECT COMPLETELY INCLUDING ALL

CONTROLS, CONTROL WIRING AND FEEDER BACK TO SOURCE.

9.018 MOTOR OPERATED OVERHEAD DOOR. DISCONNECT AND REMOVE POWER

BACK TO SOURCE, REMOVE DOOR OPERATOR CONTROL STATIONS AND

ASSOCIATED CONDUIT AND WIRING. DOOR OPERATOR AND CONTROLS

REMOVED BY OTHERS.

N9 N8 N7 N6 N5N4 N3 N2 N1

ND

NC

NB

NA

GFCI/WP

DN

DN

SEE SHEET ED103A

FOR CONTINUATION

EF-3A

SF-4SF-2

EF-6A

EF-2A

SF-1 SF-3

G G

G G G

G G G G

G

G

G

G

G

G G

G

G

G

GG

G

G

G

G

G

GGG

G

G

G

G

G

G G G G

G

G

G

G

9.025

G

G

GG

G

GG

G

G

GFCI/WP

TYP. ROOF DRAIN

ROOF HATCH

MATCHLINE

SEE 1 / ED102A

M

ATC

H

LI

N E

SEE 1

ED

2A

DEMOLITION GENERAL NOTES:

1. REFER TO DRAWING E-001 FOR DEMOLITION GENERAL NOTES, SYMBOLS &

ABBREVIATIONS.

KEY PLAN

A

B

C

SHOP

SOUTH

SHOP

NORTH

B2

A2

A2

C2

SHEET NO.:

SHEET CONTENTS

DO NOT SCALE DRAWINGS

ISSUED

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

710 Avis Drive, #100 Ann Arbor, MI 48108-9649 phone: 810-956-9300 fax: 810-956-9281

/1

/2

:2 :1

P

M C

R e v it L o c a l\

.0

-E -R k e ff .k u re lla Y

A

.r v t

ROOF ELECTRICAL &

LIGHTNING

PROTECTION

DEMOLITION PLAN -

AREA B

FJRP112701ANG PRO. NO.:

3258000-131303.01

KAF

MAM

July 20, 2022

KSK

N C

A N

G

T

H A

W

C H

A R

L O

T T

E D

O U

G L A

S I A

P C

H A

R L O

T T

E N

O R

T H

C A

R O

L

IN

A

R E

P A

IR

M

A

IN

T E

N A

N C

E H

A N

G A

R B

U

IL

D

IN

G

ED102B1/8" = 1'-0"1

ROOF ELECTRICAL & LIGHTNING PROTECTION DEMOLITION PLAN - AREA B

KEYED NOTES

9.025 ALL LIGHTNING PROTECTION SYSTEM THROUGH THE ROOF AND MAIN

DOWN CONDUCTORS TO GROUND RODS ARE TO REMAIN IN PLACE FOR

REUSE WITH NEW LIGHTNING PROTECTION SYSTEM.

N1

H

G

10 9 8

E

D

C

B

A

11 7 6 5 4 3 2 1

F

J

K

DN DN

SEE SHEET ED102B FOR

CONTINUATION

DN

DN

DN

EF-5 EF-6 EF-7 EF-8

EF-9

EF-10

EF-11 EF-12

G G

G

G

G G

G

G

G G

G G G

G

G

GGGGGG

G

G

G G

G

G

G

G

GG

GG

GG

GG

G G

G

G

GGG

G G

G G

G

G

G G G

G

G

G

G

G

G

G

G

G

G

G

G G G

G

G G

G

G

G

G G

G

G G

G

G G G G

G

G G G

G

G G G G

G

G

G

G G

G

G

G

G

G

G

G G

G G

G

G G

G

G

HEF HEF

HEF

HEF

HEF

G G G

G

WP/GFCI(E)

WP/GFCI(E)

G

9.025

M A

T C

H L

IN

E

S E

E

E

D B

M A

T C

H L

IN

E

S E

E

E

D C

MATCHLINE

SEE 1 / ED102B

M

ATC

H

LIN

E

SEE 2 / ED

101C

DEMOLITION GENERAL NOTES:

1. REFER TO DRAWING E-001 FOR DEMOLITION GENERAL NOTES, SYMBOLS &

ABBREVIATIONS.

KEY PLAN

A

B

C

SHOP

SOUTH

SHOP

NORTH

B2

A2

A2

C2

SHEET NO.:

SHEET CONTENTS

DO NOT SCALE DRAWINGS

ISSUED

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

710 Avis Drive, #100 Ann Arbor, MI 48108-9649 phone: 810-956-9300 fax: 810-956-9281

/1

/2

:2 :2

P

M C

R e v it L o c a l\

.0

-E -R k e ff .k u re lla Y

A

.r v t

ROOF ELECTRICAL &

LIGHTNING

PROTECTION

DEMOLITION PLAN -

AREA A

FJRP112701ANG PRO. NO.:

3258000-131303.01

KAF

MAM

July 20, 2022

KSK

N C

A N

G

T

H A

W

C H

A R

L O

T T

E D

O U

G L A

S I A

P C

H A

R L O

T T

E N

O R

T H

C A

R O

L

IN

A

R E

P A

IR

M

A

IN

T E

N A

N C

E H

A N

G A

R B

U

IL

D

IN

G

ED103A

KEYED NOTES

9.025 ALL LIGHTNING PROTECTION SYSTEM THROUGH THE ROOF AND MAIN

DOWN CONDUCTORS TO GROUND RODS ARE TO REMAIN IN PLACE FOR

REUSE WITH NEW LIGHTNING PROTECTION SYSTEM.

1/16" = 1'-0"1

ROOF ELECTRICAL & LIGHTNING PROTECTION DEMOLITION PLAN - AREA A

CT'S

EXISTING TRANSFORMER - UT

12470/7200V:480/277V, 3PH, 4W

1000KVA, 5.75%

EXISTING 4 SETS OF 3#600 KCMIL, #3/0G (1600A)

EACH IN 3-1/2"C (BELOW GRADE)

100A, 3P

SPARE

100A, 3P

SPARE

400A, 3P 600A, 3P

18" SPACE

200A, 3P 200A, 3P 200A, 3P 200A, 3P

SPARE

400A, 3P

CAPLA

3-225A 3-600A 3-200A 3-200A 3-200A 3-200A 3-400A

18" SPACE

200A, 3P

3-200A

EXISTING SECONDARY LIGHTING ARRESTOR

EXISTING SURGE CAPACITOR

EXISTING SWBD HSP

480/277V, 3PH, 4W

1600A BUS

50,000 AMP, RMS

1600A

BOLTED PRESSURE

SWITCH - GFI

3-1600A

EXISTING

4#4/0, #3G, 2-1/2"C (200A)

EXISTING

4#4/0, #3G 2-1/2"C (200A)

EXISTING

4#1/0, #6G, 2"C (125A)

DF

EXISTING

4#3, #8G

1-1/4"C (80A)

60A/3P 3-80A

(DEMO)

200A/3P 3-125A

(DEMO)

EXISTING

4#4/0, #4G, 2-1/2"C (225A)

EXISTING

4#4/0, #4G, 2-1/2"C

EXISTING

4#3/0, #6G, 2"C (200A)

EXISTING

3#4/0, #6G, 2"C (200A)

4#500 KCMIL, #3G, 3-1/2"C

1 2 3 4 9 11 12

125A/3P 50A/3P 90A/3P

J J

DUPLEX AIR

COMPRES…