ATTACHMENT 7 DRAWINGS 145 AW Repair Maint. Hangar Building 51 dated 20 July 2022 Vol 3.pdf
PDF 17 MB Posted
- Attached to
- Repair Building 51
- Solicitation number
- W50S87-23-B-0001
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT MAP:
PROJECT
LOCATION
BASE
ENTRANCE
CONSTRUCTION
ENTRANCE
BASE
OUTLINE
STATE MAP:
STATE OF NORTH CAROLINA
CITY OF CHARLOTTE,
MECKLENBURG COUNTY
VICINITY MAP:
PROJECT LOCATION
1. ROLLER SHADES IN LEU OF SLAT BLINDS
2. EPOXY FLOOR IN ROOMS:
A. HYDRO SHOP
B. WHEEL/TIRE SHOP
C. SUPPORT EQUIPMENT
D. CTK
3. ADDITIONAL PARKING SPACES
BID OPTIONS:
ANG PROJECT No.:
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
710 Avis Drive, #100 Ann Arbor, MI 48108-9649 phone: 810-956-9300 fax: 810-956-9281
/1
/2
:3 :5
P
M C
R e v it L o c a l\
.0
-A -R c h ri s .d o u g a n
.r v t
FJRP112701
REPAIR MAINTENANCE HANGAR BUILDING 51
CHARLOTTE DOUGLAS IAP
CHARLOTTE, NORTH CAROLINA
NCANG - 145TH AW
COVER SHEET -
VOLUME 3
FJRP112701ANG PRO. NO.:
3258000-181469.01
NJD, KB
DMD
July 20, 2022
ATM
N C
A N
G
T
H A
W
C H
A R
L O
T T
E D
O U
G L A
S I A
P C
H A
R L O
T T
E N
O R
T H
C A
R O
L
IN
A
R E
P A
IR
M
A
IN
T E
N A
N C
E H
A N
G A
R B
U
IL
D
IN
G
G-000C
VOLUME 3
07/20/22 B-3 SUBMITTAL
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
ISSUED
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
710 Avis Drive, #100 Ann Arbor, MI 48108-9649 phone: 810-956-9300 fax: 810-956-9281
/2
/2
:0
:2
A
M C
R e v it L o c a l\
.0
-A -R c h ri s .d o u g a n
.r v t
SHEET INDEX -
VOLUME 3
FJRP112701ANG PRO. NO.:
3258000-181469.01
NJD, KB
DMD
July 20, 2022
ATM
N C
A N
G
T
H A
W
C H
A R
L O
T T
E D
O U
G L A
S I A
P C
H A
R L O
T T
E N
O R
T H
C A
R O
L
IN
A
R E
P A
IR
M
A
IN
T E
N A
N C
E H
A N
G A
R B
U
IL
D
IN
G
G-001C
SHEET INDEX - VOLUME 2
A-515 PLAN DETAILS INTERIOR - MINOR CONSTRUCTION
A-601 DOOR AND FRAME SCHEDULES AND LEGENDS - EXIST & AREA A
A-602 DOOR AND FRAME SCHEDULES AND LEGENDS - AREAS B & C
A-603 WINDOW TYPES & DETAILS
A-605 TRANSLUCENT PANEL DETAILS
A-621 DOOR DETAILS-INTERIOR AND EXTERIOR
A-700 FINISH SCHEDULES
A-701A FINISH PLAN - AREA A
A-701A2 FINISH PLANS - AREA A2
A-701B FINISH PLAN - AREA B
A-701B2 FINISH PLAN - MINOR CONSTRUCTION AREA B2
A-701C FINISH PLAN-AREA C
A-702A HANGAR BAY STRIPING PLAN
A-703 FINISH DETAILS
A-801A SIGNAGE PLAN - AREA A
A-801A2 SIGNAGE PLANS - AREA A2
A-801B SIGNAGE PLAN - AREA B
A-801B2 SIGNAGE PLAN - MINOR CONSTRUCTION AREA B2
A-801C SIGNAGE PLAN - AREA C
A-804 SIGNAGE PLAN - LOWER CATWALK
A-805 SIGNAGE PLAN - UPPER CATWALK
A-851 SIGNAGE DETAILS
A-852 SIGNAGE SCHEDULE
A-901A2 FIXTURES, FURNITURE AND EQUIPMENT PLANS - AREA A2
A-901B FIXTURES, FURNITURE AND EQUIPMENT PLAN - AREA B
A-901C FIXTURES, FURNITURE AND EQUIPMENT PLAN - AREA C
Sheets in Volume: 135
SHEET INDEX - VOLUME 2
GENERAL
G-001B SHEET INDEX - VOLUME 2
ARCHITECTURAL
A-001 NOTES & SYMBOLS
A-002 PARTITION TYPES
A-003 PARTITION DETAILS & TOILET ACCESSORY MOUNTING HEIGHTS
A-004 ASSEMBLIES
A-005 ARCHITECTURAL KEYNOTES
AD100 DEMOLITION OVERALL PLAN
AD101A DEMOLITION FLOOR PLAN - AREA A
AD101B DEMOLITION FLOOR PLAN - AREA B
AD101C DEMOLITION FLOOR PLAN - AREA C
AD101C2 DEMOLITION FLOOR PLAN - MINOR CONSTRUCTION AREA C2
AD102A DEMOLITION MEZZANINE PLAN - AREA A
AD102A2 DEMOLITION MEZZANINE PLANS - AREA A2
AD105A DEMOLITION ROOF PLAN - AREA A
AD105B DEMOLITION ROOF PLAN - AREA B
AD105C DEMOLITION ROOF PLAN - AREA C
AD105C2 DEMOLITION ROOF PLAN - MINOR CONSTRUCTION AREA C2
AD121A DEMOLITION REFLECTED CEILING PLAN - AREA A
AD121B DEMOLITION REFLECTED CEILING PLAN - AREA B
AD121C DEMOLITION REFLECTED CEILING PLAN - AREA C
AD201 DEMOLITION EXTERIOR ELEVATIONS - AREA A
AD202 DEMOLITION EXTERIOR ELEVATIONS - AREA A
AD203 DEMOLITION EXTERIOR ELEVATIONS - AREA B
AD204 DEMOLITION EXTERIOR ELEVATIONS AREA C
AD205 DEMOLITION EXTERIOR ELEVATIONS - MINOR CONSTRUCTION
AD206 DEMOLITION EXTERIOR ELEVATIONS - AREA C2
AD301 DEMOLITION SECTIONS
A-100 OVERALL PLAN
A-101A FIRST FLOOR PLAN - AREA A
A-101A2 FIRST FLOOR PLANS - AREA A2
A-101B FIRST FLOOR PLAN - AREA B
A-101B2 FIRST FLOOR PLAN - MINOR CONSTRUCTION AREA B2
A-101C FIRST FLOOR PLAN - AREA C
A-101C2 FIRST FLOOR PLAN - MINOR CONSTRUCTION AREA C2
A-102 MEZZANINE PLAN - OVERALL
A-102A2 MEZZANINE PLANS - AREA A2
A-102A3 MEZZANINE ISOMETRICS - AREA A2
A-102B2 CLERESTORY FLOOR PLAN - MINOR CONSTRUCTION AREA B2
A-103 LOWER CATWALK PLAN
A-104 UPPER CATWALK PLAN
A-105 ROOF PLAN - OVERALL
A-105A ROOF PLAN - AREA A
A-105B ROOF PLAN - AREA B
A-105B2 ROOF PLAN - MINOR CONSTRUCTION AREA B2
A-105C ROOF PLAN - AREA C
A-105C2 ROOF PLAN - MINOR CONSTRUCTION AREA C2
A-121A REFLECTED CEILING PLAN - AREA A
A-121A2 REFLECTED CEILING PLANS - AREA A2
A-121B REFLECTED CEILING PLAN - AREA B
A-121B2 REFLECTED CEILING PLAN - MINOR CONSTRUCTION AREA B2
A-121C REFLECTED CEILING PLAN - AREA C
A-121C2 REFLECTED CEILING PLAN - MINOR CONSTRUCTION AREA C2
A-122B ENLARGED CEILING PLANS - AREAS B & C
A-151A2 FIRST FLOOR AIR BARRIER PLANS - AREA A2
A-151B FIRST FLOOR AIR BARRIER PLAN - AREA B
A-151B2 FIRST FLOOR AIR BARRIER PLAN - MINOR CONSTRUCTION AREA B2
A-151C FIRST FLOOR AIR BARRIER PLAN - AREA C
A-152B2 CLERESTORY AIR BARRIER PLAN - MINOR CONSTRUCTION AREA B2
A-152C2 CLERESTORY AIR BARRIER PLAN - MINOR CONSTRUCTION AREA C2
A-201 EXTERIOR ELEVATIONS - AREA A
A-202 EXTERIOR ELEVATIONS - AREA A
A-203 EXTERIOR ELEVATIONS - AREA B
A-204 EXTERIOR ELEVATIONS - MINOR CONSTRUCTION AREA B2
A-205 EXTERIOR ELEVATIONS - AREA C
A-206 EXTERIOR ELEVATIONS - MINOR CONSTRUCTION AREA C2
A-207 EXTERIOR FACADE REPAIR ELEVATIONS - AREA A
A-208 EXTERIOR FACADE REPAIR ELEVATIONS - AREAS B & C
A-301 BUILDING SECTIONS - AREA A
A-302 BUILDING SECTIONS - AREA A2
A-303 BUILDING SECTIONS - AREA B
A-304 BUILDING SECTIONS - MINOR CONSTRUCTION AREA B2
A-305 BUILDING SECTIONS - MINOR CONSTRUCTION AREA C2
A-310 WALL SECTIONS - AREA A
A-311 WALL SECTIONS - AREA A2 SOUTH HANGAR SHOP
A-312 WALL SECTIONS - AREA A2 NORTH HANGAR SHOP
A-313 WALL SECTIONS - AREA B
A-314 WALL SECTIONS - AREA B
A-315 WALL SECTIONS - MINOR CONSTRUCTION AREA B2
A-316 WALL SECTIONS - AREAS B & B2
A-317 WALL SECTIONS - MINOR CONSTRUCTION AREA B2
A-318 WALL SECTIONS - AREAS B & C
A-319 WALL SECTIONS - AREA C
A-320 WALL SECTIONS - MINOR CONSTRUCTION AREA C2
A-321 WALL SECTIONS - AREA B & C AIR BARRIER
A-322 WALL SECTIONS - HANGAR SHOP AIR BARRIERS
A-400 ENLARGED PLANS AND INTERIOR ELEVATIONS - AREA A
A-401 INTERIOR ELEVATIONS - AREA A
A-402 ENLARGED PLANS AND INTERIOR ELEVATIONS - AREA B
A-403 ENLARGED PLANS AND INTERIOR ELEVATIONS - AREA B
A-404 ENLARGED PLANS AND INTERIOR ELEVATIONS - AREA C
A-405 INTERIOR ELEVATIONS - AREA C
A-406 CASEWORK DETAILS
A-410 RAILING TYPES
A-411 ENLARGED STAIR AND SHIPS LADDER PLANS & SECTIONS - AREA B, B2 &
HANGAR SHOP SOUTH
A-412 ENLARGED STAIR AND SHIPS LADDER PLANS & SECTIONS - HANGAR SHOP
NORTH
A-501 ROOF DETAILS
A-502 SECTION DETAILS EXTERIOR
A-503 SECTION DETAILS - AREA A
A-504 SECTION DETAILS EXTERIOR - MINOR CONSTRUCTION AREA B2
A-505 SECTION DETAILS EXTERIOR - MINOR CONSTRUCTION AREA B2
A-506 SECTION DETAILS - MINOR CONSTRUCTION AREA C2
A-507 SECTION DETAILS - MINOR CONSTRUCTION AREA C2
A-508 SECTION DETAILS - INTERIOR
A-509 PLAN DETAILS - AIR BARRIER
A-510 SECTION DETAILS - AIR BARRIER
A-511 PLAN DETAILS EXTERIOR - MINOR CONSTRUCTION AREAS B & B2
A-512 PLAN DETAILS - MINOR CONSTRUCTION AREA B2
A-513 PLAN DETAILS EXTERIOR - MINOR CONSTRUCTION AREA C2
A-514 PLAN DETAILS INTERIOR - AREAS A, B & C
SHEET INDEX - VOLUME 1
GENERAL
G-001A SHEET INDEX - VOLUME 1
G-003 CODE ANALYSIS
G-004A ROOM OCCUPANCY CLASSIFICATIONS
G-004B OCCUPANCY PLANS
G-005A LIFE SAFETY PLAN - AREA A
G-005A2 LIFE SAFETY PLANS - AREA A2
G-005B LIFE SAFETY PLANS - AREA B & C
G-006A LIFE SAFETY PLAN - LOW CATWALK
G-007A LIFE SAFETY PLAN - UPPER CATWALK
CIVIL
C100 CIVIL LEGEND AND ABBREVIATIONS
VF101 EXISTING CONDITIONS
GC121 SURVEY CONTROL PLAN
GC141 CONSTRUCTION ACCESS & LOCATION PLAN
GC145 CONSTRUCTION OPERATION PLAN NOTES
BB101 PLAN & LOG OF SOIL BORINGS
EC101 EROSION CONTROL PLAN
EC501 EROSION CONTROL DETAILS
CD101 DEMOLITION PLAN
CS111 SITE PLAN
CS121 ENLARGED SITE AND PAVING PLAN - AREAS 1 & 2
CS122 ENLARGED SITE AND PAVING PLAN - AREA 3
CS501 SITE DETAILS
CS502 SITE DETAILS
CS503 SITE DETAILS
CS504 SITE DETAILS
CG121 ENLARGED GRADING & DRAINAGE PLAN - AREAS 1 & 2
CG122 ENLARGED GRADING & DRAINAGE PLAN - AREA 3
CU101 ENLARED UTILITY PLAN - AREA 3
CU501 UTILITY DETAILS
CU502 UTILITY DETAILS
STRUCTURAL
S-001 NOTES, SYMBOLS, AND ABBREVIATIONS
S-002 NOTES, SYMBOLS, AND ABBREVIATIONS
S-005 STATEMENT OF SPECIAL INSPECTIONS
S-006 STRUCTURAL STEEL SPECIAL INSPECTIONS
S-007 MASONRY AND STEEL DECK SPECIAL INSPECTIONS
S-008 STRUCTURAL PROJECT KEYNOTES
S-010 ROOF LOADING PLAN
S-052A EXISTING BOTTOM CHORD FRAMING PLAN - AREA A
S-053A EXISTING ROOF FRAMING PLAN - AREA A
SD101A FOUNDATION AND FLATWORK DEMOLITION PLAN - AREA A
SD101B FOUNDATION AND FLATWORK DEMOLITION PLAN - AREA B
SD101C FOUNDATION AND FLATWORK DEMOLITION PLAN - AREA C
SD101C2 FOUNDATION AND FLATWORK DEMOLITION PLAN - MINOR
CONSTRUCTION - AREA C2
SD131B STRUCTURAL DEMOLITION FLOOR PLAN - AREA B
SD131C STRUCTURAL DEMOLITION FLOOR PLAN - AREA C
SD152A BOTTOM CHORD FRAMING DEMOLITION PLAN - AREA A
S-101A FOUNDATION PLAN - AREA A
S-101A2 FOUNDATION PLANS - AREA A2
S-101B FOUNDATION PLAN - AREA B
S-101B2 FOUNDATION PLAN - MINOR CONSTRUCTION - AREA B2
S-101C FOUNDATION PLAN - AREA C
S-101C2 FOUNDATION PLAN - MINOR CONSTRUCTION - AREA C2
S-111A FLATWORK PLAN - AREA A
S-111A2 FLATWORK PLANS - AREA A2
S-111B FLATWORK PLAN - AREA B
S-111B2 FLATWORK PLAN - MINOR CONSTRUCTION - AREA B2
S-111C FLATWORK PLAN - AREA C
S-111C2 FLATWORK PLAN - MINOR CONSTRUCTION - AREA C2
S-131A STRUCTURAL FLOOR PLAN - AREA A
S-131A2 STRUCTURAL FLOOR PLANS - AREA A2
S-131B STRUCTURAL FLOOR PLAN - AREA B
S-131B2 STRUCTURAL FLOOR PLAN - MINOR CONSTRUCTION - AREA
B2
S-131C STRUCTURAL FLOOR PLAN - AREA C
S-142A MEZZANINE FRAMING PLAN - AREA A
S-142A2 MEZZANINE FRAMING PLANS - AREA A2
S-151B ROOF FRAMING PLAN - AREA B
S-151C ROOF FRAMING PLAN - AREA C
S-151C2 ROOF FRAMING PLAN - MINOR CONSTRUCTION - AREA C2
S-152A BOTTOM CHORD FRAMING PLAN - AREA A
S-153A ROOF FRAMING PLAN - AREA A
S-153B2 HIGH ROOF FRAMING PLAN - MINOR CONSTRUCTION - AREA
B2
S-153C2 HIGH ROOF FRAMING PLAN - MINOR CONSTRUCTION - AREA
C2
S-301 SECTIONS
S-411 ENLARGED FLATWORK PLANS
S-431 ENLARGED STRUCTURAL FLOOR PLANS
S-441 ENLARGED FRAMING PLAN AND DETAILS
S-501 FOUNDATION DETAILS
S-502 FOUNDATION DETAILS
S-511 FLATWORK DETAILS
S-512 FLATWORK DETAILS
S-521 WALL DETAILS
S-522 WALL DETAILS
S-541 FRAMING DETAILS
S-542 FRAMING DETAILS
S-543 FRAMING DETAILS
S-544 FRAMING DETAILS
S-545 FRAMING DETAILS
S-551 FRAMING DETAILS
S-552 FRAMING DETAILS
S-601 STRUCTURAL SCHEDULES
Sheets in Volume: 90
SHEET INDEX - VOLUME 3
GENERAL
G-001C SHEET INDEX - VOLUME 3
FIRE ALARM
FA001 NOTES & SYMBOLS
FAD101 FIRE ALARM OVERALL DEMO PLAN
FA102 FIRE ALARM AND MNS FLOOR PLAN HANGAR
FA103 FIRE ALARM AND MNS FLOOR PLAN NORTH WING
FA104 FIRE ALARM AND MNS ENLARGED FLOOR PLAN EAST WING
FA105 FIRE ALARM AND MNS RISER DIAGRAM AND MATRIX
FIRE PROTECTION
FX001 NOTES & SYMBOLS
FXD101 FIRE PROTECTION HANGAR DEMO PLAN
FXD102 FIRE PROTECTION DEMO PLAN NORTH WING
FX101 DESIGN DENSITY PLAN HANGAR
FX102 DESIGN DENSITY NORTH WING
FX102B2 DESIGN DENSITY PLAN - AREA B2 - MINOR CONSTRUCTION
FX103 FIRE PROTECTION HANGAR FLOOR PLAN
FX104 FIRE PROTECTION FIRE PUMP ROOM
FX105 FIRE PROTECTION SPRINKLER ROOM
PLUMBING
P-001 PLUMBING NOTES & SYMBOLS
PD100B UNDERGROUND DRAIN AND VENT DEMO PLUMBING PLAN - AREA B
PD100C UNDERGROUND DRAIN AND VENT DEMO PLUMBING PLAN - AREA C
PD101A ABOVEGROUD DRAIN AND VENT DEMO PLUMBING PLAN - AREA A
PD101B ABOVEGROUND DRAIN AND VENT DEMO PLUMBING PLAN - AREA B
PD101C ABOVEGROUND DRAIN AND VENT DEMO PLUMBING PLAN - AREA C
PD102A ROOF - DRAIN AND VENT DEMO PLUMBING PLAN - AREA A
PD102B ROOF - DRAIN AND VENT DEMO PLUMBING PLAN - AREA B
PD102C ROOF - DRAIN AND VENT DEMO PLUMBING PLAN - AREA C
PD131A SUPPLY DEMO PLUMBING PLAN - AREA A
PD131B SUPPLY DEMO PLUMBING PLAN - AREA B
PD131C SUPPLY DEMO PLUMBING PLAN - AREA C
P-100A2 UNDERGROUND DRAIN AND VENT PLUMBING PLAN - HANGAR SHOPS
P-100B UNDERGROUND DRAIN AND VENT PLUMBING PLAN - AREA B
P-100B2 UNDERGROUND DRAIN AND VENT PLUMBING PLAN - AREA B2
P-100C UNDERGROUND DRAIN AND VENT PLUMBING PLAN - AREA C
P-101A DRAIN AND VENT PLUMBING PLAN - AREA A
P-101A2 DRAIN AND VENT PLUMBING PLAN - HANGAR SHOPS
P-101B DRAIN AND VENT PLUMBING PLAN - AREA B
P-101B2 DRAIN AND VENT PLUMBING PLAN - AREA B2
P-101C DRAIN AND VENT PLUMBING PLAN - AREA C
P-102A ROOF - DRAIN AND VENT PLUMBING PLAN - AREA A
P-102B ROOF - DRAIN AND VENT PLUMBING PLAN - AREA B
P-102B2 ROOF - DRAIN AND VENT PLUMBING PLAN - AREA B2
P-102C ROOF - DRAIN AND VENT PLUMBING PLAN - AREA C
P-131A SUPPLY PLUMBING PLAN - AREA A
P-131A2 SUPPLY PLUMBING PLANS - HANGAR SHOPS
P-131B SUPPLY PLUMBING PLAN - AREA B
P-131C SUPPLY PLUMBING PLAN - AREA C
P-501 PLUMBING DETAILS
P-502 PLUMBING DETAILS
P-601 PLUMBING SCHEDULES
P-602 PLUMBING SCHEDULES
P-901 DRAIN AND VENT ISOMETRIC PLUMBING DIAGRAM
P-931 SUPPLY ISOMETRIC PLUMBING PLAN
MECHANICAL
M-001 MECHANICAL NOTES & SYMBOLS
MD101A HVAC DEMOLITION FLOOR PLAN - AREA A
MD101B HVAC DEMOLITION FLOOR PLAN - AREA B
MD101C HVAC DEMOLITION FLOOR AND ROOF PLAN - AREA C
MD105A HVAC DEMOLITION ROOF PLAN - AREA A
MD105B HVAC DEMOLITION ROOF PLAN - AREA B
MD131A MECHANICAL PIPING DEMOLITION FLOOR PLAN - AREA A
MD131B MECHANICAL PIPING DEMOLITION FLOOR PLAN - AREA B
MD131C MECHANICAL PIPING DEMOLITION FLOOR PLAN - AREA C
MD401 ENLARGED DEMOLITION PLANS - AREA B AND AREA C
M-101A HVAC FLOOR PLAN - AREA A
M-101A2 HVAC FIRST FLOOR PLAN - AREA A2
M-101B HVAC FLOOR PLAN - AREA B
M-101B2 HVAC FLOOR PLAN - MINOR CONSTRUCTION AREA B2
M-101C HVAC FLOOR AND ROOF PLAN - AREA C
M-102A2 HVAC MEZZANINE PLANS - AREA A2
M-105A HVAC ROOF PLAN - AREA A
M-105B HVAC ROOF PLAN - AREA B
M-131A MECHANICAL PIPING FLOOR PLAN - AREA A
M-131A2 MECHANICAL FIRST FLOOR PLAN - AREA A2
M-131B MECHANICAL PIPING FLOOR PLAN - AREA B
M-131B2 MECHANICAL FLOOR PLAN - MINOR CONSTRUCTION AREA B2
M-131C MECHANICAL PIPING FLOOR PLAN - AREA C
M-132A2 MECHANICAL MEZZANINE PLANS - AREA A2
M-401 ENLARGED PLANS - AREA B, AREA C AND AREA D
M-501 MECHANICAL DETAILS
M-502 MECHANICAL DETAILS
M-503 MECHANICAL DETAILS
M-504 MECHANICAL DETAILS
M-601 MECHANICAL SCHEDULES
M-602 MECHANICAL SCHEDULES
M-603 MECHANICAL SCHEDULES
M-604 MECHANICAL SCHEDULES
M-605 MECHANICAL SCHEDULES
M-606 MECHANICAL SCHEDULES
M-607 MECHANICAL SCHEDULES
M-608 MECHANICAL SCHEDULES
M-609 MECHANICAL SCHEDULES
M-711 MECHANICAL SCHEMATICS
M-712 MECHANICAL SCHEMATICS
M-801 MECHANICAL CONTROL SCHEMATICS
M-802 MECHANICAL CONTROL SCHEMATICS
M-803 MECHANICAL CONTROL SCHEMATICS
M-804 MECHANICAL CONTROL SCHEMATICS
M-805 MECHANICAL CONTROL SCHEMATICS
Sheets in Volume: 96
SHEET INDEX - VOLUME 4
GENERAL
G-001D SHEET INDEX - VOLUME 4
ELECTRICAL
E-001 NOTES, SYMBOLS & ABBREVIATIONS
ED101A FIRST FLOOR ELECTRICAL DEMOLITON PLAN - AREA A
ED101B FIRST FLOOR ELECTRICAL DEMOLITON PLAN - AREA B
ED101C FIRST FLOOR & ROOF ELECTRICAL DEMOLITION PLAN - AREA C
ED102A MEZZANINE FLOOR & CATWALK LEVEL ELECTRICAL DEMOLITION PLAN - AREA A
ED102B ROOF ELECTRICAL & LIGHTNING PROTECTION DEMOLITION PLAN - AREA B
ED103A ROOF ELECTRICAL & LIGHTNING PROTECTION DEMOLITION PLAN - AREA A
ED701 DEMOLITION ONE-LINE DIAGRAM
E-100A HAZARDOUS AREA CLASSIFICATION PLAN
E-101A FIRST FLOOR POWER PLAN - AREA A
E-101A2 FIRST FLOOR POWER PLAN - AREA A2
E-101B FIRST FLOOR POWER PLAN - AREA B
E-101B2 FIRST FLOOR POWER PLAN - MINOR CONSTRUCTION - AREA B2
E-101C FIRST FLOOR & ROOF POWER PLAN - AREA C
E-102A MEZZANINE FLOOR & CATWALK LEVEL POWER PLAN - AREA A
E-103A ROOF POWER & LIGHTNING PROTECTION PLAN - AREA A
E-103B ROOF POWER & LIGHTNING PROTECTION PLAN - AREA B
E-103B2 ROOF POWER & LPS PLAN - MINOR CONSTRUCTION - AREA B2
E-121A FIRST FLOOR LIGHTING PLAN - AREA A
E-121A2 FIRST FLOOR LIGHTING PLAN - AREA A2
E-121B FIRST FLOOR LIGHTING PLAN - AREA B
E-121B2 FIRST FLOOR LIGHTING PLAN - MINOR CONSTRUCTION - AREA B2
E-121C FIRST FLOOR LIGHTING PLAN - AREA C
E-122A MEZZANINE FLOOR & CATWALK LEVEL LIGHTING PLAN - AREA A
E-401 ENLARGED POWER & DEMOLITION PLANS
E-402 ENLARGED POWER PLANS
E-403 ENLARGED PLANS
E-404 ENLARGED PHOTOS
E-405 ENLARGED PHOTOS
E-501 ELECTRICAL DETAILS
E-502 ELECTRICAL DETAILS
E-601 LUMINAIRE SCHEDULES
E-602 LIGHTING CONTROL SCHEDULES & CONTROLS NARRATIVE
E-603 EQUIPMENT WIRING SCHEDULES
E-604 EQUIPMENT WIRING SCHEDULES
E-605 PANEL SCHEDULES
E-606 PANEL SCHEDULES
E-607 PANEL SCHEDULES
E-608 PANEL SCHEDULES
E-701 ONE-LINE DIAGRAM
E-702 ONE-LINE DIAGRAM
TECHNOLOGY SYSTEMS
T-001 NOTES, SYMBOLS & ABBREVIATIONS
TD101A FIRST FLOOR TECHNOLOGY DEMOLITION PLAN - AREA A - HANGAR
TD101B FIRST FLOOR TECHNOLOGY DEMOLITION PLAN - AREA B - NORTH WING
TD101C FIRST FLOOR & ROOF TECHNOLOGY DEMOLITION PLAN - AREA C - EAST WING
TD102A MEZZANINE FLOOR & CATWALK LEVEL TECHNOLOGY DEMOLITION PLAN - AREA A - HANGAR
TD103A ROOF TECHNOLOGY DEMOLITION PLAN - AREA A - HANGAR
T-100 TECHNOLOGY SITE PLAN
T-101A FIRST FLOOR - AREA A - TECHNOLOGY SYSTEMS
T-101A2 HANGAR SHOP - AREA A2 - TECHNOLOGY SYSTEMS
T-101B FIRST FLOOR - AREA B - TECHNOLOGY SYSTEMS
T-101B2 FIRST FLOOR - AREA B2 - TECHNOLOGY SYSTEMS
T-101C FIRST FLOOR - AREA C - TECHNOLOGY SYSTEMS
T-102 MEZZANINE PLANS - TECHNOLOGY SYSTEMS
T-103A ROOF TECHNOLOGY PLAN - AREA A
T-121A FIRST FLOOR - AREA A - SECURITY
T-121A2 HANGAR SHOP - AREA A2 - SECURITY SYSTEMS
T-121B FIRST FLOOR - AREA B - SECURITY
T-121B2 FIRST FLOOR - AREA B2 - SECURITY
T-121C FIRST FLOOR - AREA C - SECURITY
T-123A ROOF SECURITY PLAN - AREA A
T-401 ENLARGED PLANS
T-402 ENLARGED PLANS
T-403 ENLARGED PLANS
T-404 ENLARGED PLANS
T-405 ENLARGED PLANS
T-501 DETAILS
T-502 DETAILS
T-503 DETAILS
T-701 ONE-LINE DIAGRAMS
Sheets in Volume: 71
XX
RTS
FAA
FMCP
LOC
WP
XX
AIM
A0M
SPD
XX
GENERAL NOTES:
PROVIDE NEW COMBINATION FIRE ALARM AND MASS NOTIFICATION SYSTEM (MNS) IN
ACCORDANCE WITH UFC 4-021-01, UFC 3-600-01, NFPA 72, OTHER REFERENCED CODES
AND STANDARDS, PROJECT SPECIFICATIONS, AND DESIGN DOCUMENTS. THE SYSTEM
SHALL HAVE THE ABILITY TO BROADCAST BOTH PRE-RECORDED AND LIVE VOICE
MESSAGES. THE FIRE ALARM AND MASS NOTIFICATION SYSTEM SHALL UTILIZE
SHARED SPEAKERS. THE MNS SHALL HAVE THE HIGHEST PRIORITY.
FIRE ALARM AND MASS NOTIFICATION CIRCUITS SHALL BE CLASS "B", SURVIVABILITY
LEVEL 1, IN ACCORDANCE WITH NFPA 72.
PROVIDE A NEW MONACO BT-XM RADIO TRANSCEIVER TO TRANSMIT ALARM,
SUPERVISORY, AND TROUBLE SIGNALS TO THE EXISTING BASE MONITORING STATION.
THE NEW SYSTEM SHALL BE FULLY COMPATIBLE WITH EXISTING MONACO RECEIVING
EQUIPMENT AND SHALL HAVE THE CAPABILITY FOR INTERFACE WITH FUTURE BASE-
WIDE MASS NOTIFICATION FUNCTIONS.
PROVIDE AUDIBLE (SPEAKERS) AND VISUAL NOTIFICATION APPLIANCES THROUGHOUT
ALL SPACES OF THE BUILDING, PROVIDE VISUAL COMBINED FIRE ALARM MASS
NOTIFICATION STROBES (CLEAR, MARKED "ALERT") SPACED IN ACCORDANCE WITH
NFPA 72.
PROVIDE EXTERIOR SPEAKERS ON THE EXTERIOR WALL OF THE BUILDING AT EACH
EXIT DOOR LOCATION PER UFC 4-021-01 TO PROVIDE FIRE ALARM AND MNS
ANNOUNCEMENTS. EXTERIOR SPEAKERS SHALL BE WEATHER RESISTANT TYPE.
PROVIDE A LOCAL OPERATING CONSOLE (LOC) AS SHOWN ON THE FLOOR PLAN.
TYPICALLY EACH LOC IS LOCATED WITHIN 200 FEET OF TRAVEL ON EACH LEVEL OF
THE BUILDING;
THE BUILDING PUBLIC ADDRESS SYSTEM SHALL NOT BE COMBINED WITH THE FIRE
ALARM AND MNS SYSTEM. PROVIDE INTERFACE WITH PUBLIC ADDRESS (PA) SYSTEM
THAT WILL SILENCE THE PA SYSTEM UPON ACTIVATION OF A FIRE ALARM OR MNS
ANNOUNCEMENT.
PROVIDE REMOTE POWER SUPPLIES (NAC), IN ADDITION TO THOSE SHOWN ON THE
FLOOR PLAN, AS NEEDED TO SUPPORT THE FIRE ALARM AND MASS NOTIFICATION
SYSTEM. THE REMOTE POWER SUPPLIES ARE REQUIRED TO BE LOCATED WITHIN
ELECTRICAL ROOMS OR OTHER UTILITY SPACES. PROVIDE A SMOKE DETECTOR
ABOVE EACH REMOTE POWER SUPPLY IN ACCORDANCE WITH NFPA 72.
PROVIDE A SMOKE DETECTOR ABOVE THE FIRE ALARM AND MASS NOTIFICATION
CONTROL PANEL (FMCP) OR OTHER PIECE OF FIRE ALARM SYSTEM CONTROL
EQUIPMENT IN ACCORDANCE WITH NFPA 72. NOTE THE NFPA 72 DOES NOT REQUIRE
SMOKE DETECTION ABOVE THE REMOTE ANNUNCIATOR (FAA) OR THE LOCAL
OPERATING CONSOLE (LOC).
EACH ACOUSTICALLY DISTINGUISHABLE SPACE (ADS) SHALL NOT BE REQUIRED TO
COMPLY WITH GENERAL INTELLIGIBILITY REQUIREMENTS FOR THE BUILDING.
INSTEAD, INTELLIGIBILITY WITHIN EACH ADS SHALL COMPLY WITH UFC 4-021-01 WHICH
PERMITS AN OCCUPANT TO TRAVEL NO MORE THAN 30 FEET (NORMALLY OCCUPIED
AREAS) OR 50 FEET ( NORMALLY UNOCCUPIED AREAS) TO A LOCATION WHERE
INTELLIGIBILITY IS ACHIEVED. REFER TO THE "ACOUSTICALLY DISTINGUISHABLE
SPACE (ADS) AND NOTIFICATION LEGEND" AND ASSOCIATED HATCHING ON THE
FLOOR PLAN FOR MORE INFORMATION.
THE GENERAL MINIMUM INTELLIGIBILITY CIS SCORE IS 0.8 FOR THE ARMY AND AIR
FORCE PER UFC 4-021-01, 4-4.1.2. NOTE THAT CIS SCORES OF 0.75 - 0.79 MAY BE
ROUNDED UP THE 0.8.
THE LAYOUT OF DEVICES, APPLIANCES, CONTROL EQUIPMENT, AND OTHER SYSTEM
COMPONENTS ON THESE DRAWINGS SHOWS THE MINIMUM NUMBER OF
COMPONENTS. THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING ADDITIONAL
DEVICES, APPLIANCES, CONTROL EQUIPMENT, AND OTHER SYSTEM COMPONENTS AS
REQUIRED TO COMPLY WITH THE APPLICABLE CODES, STANDARDS, SPECIFICATIONS,
AND DESIGN CRITERIA. THE CONTRACTOR SHALL PROVIDE A SYSTEM THAT MEETS
THE AUDIBILITY AND INTELLIGIBILITY OF UFC 4-021-01 AND AUDIBLE AND VISIBLE
REQUIREMENTS OF NFPA 72. PERFORMANCE RESULTS, INCLUDING THE REQUIRED
SOUND PRESSURE LEVELS AND INTELLIGIBILITY VALUES, SHALL BE DOCUMENTED ON
A FLOOR PLAN AND SUBMITTED TO THE GOVERNMENT.
CONTRACTOR SHALL PROVIDE INTERFACE WITH THE WATERFLOW AND VALVE
TAMPER SWITCHES FOR MONITORING OF THE FIRE SUPPRESSION SYSTEMS. NUMBER
OF DEVICES AND LOCATIONS SHALL BE COORDINATED WITH THE FIRE SUPPRESSION
SYSTEM SUBCONTRACTOR.
PROVIDE HVAC SHUTDOWN SWITCHES CAPABLE OF SHUTTING DOWN ALL HVAC
EQUIPMENT IN THE FACILITY IN ACCORDANCE WITH UFC 4-101-01. PROVIDE HVAC
SHUTDOWN SWITCHES NEAR EACH OF THE LOCAL OPERATING CONSOLES IN
LOCATION APPROVED BY THE CONTRACTING OFFICER. COORDINATE WITH THE
MECHANICAL CONTRACTOR AND REFER TO THE MECHANICAL DRAWINGS.
PROVIDE DUCT SMOKE DETECTION IN HVAC SYSTEM IN ACCORDANCE WITH NFPA 90A
(2015 EDITION). NUMBER OF DEVICES AND LOCATIONS SHALL BE COORDINATED WITH
THE MECHANICAL CONTRACTOR. PROVIDE REMOTE TEST STATIONS WHERE DUCT
DETECTORS ARE INSTALLED IN LOCATIONS OVER 1.8m ABOVE THE FLOOR.
LOCATIONS THAT ARE NOT EASILY ACCESSIBLE, OR WHERE DUCT DETECTORS ARE
LOCATED ABOVE CEILINGS.
PROVIDE MANUAL PULL STATIONS AT EACH OF THE EXTERIOR DOORS AND AT
ENTRANCES TO EXIT STAIRS IN ACCORDANCE WITH NFPA 72 AND UFC 3-600-01.
THE FIRE ALARM AND MASS NOTIFICATION SYSTEM SHALL MONITOR THE FIRE PUMPS
AND FIRE SUPPRESSION SYSTEM EQUIPMENT IN ACCORDANCE WITH NFPA 72, NFPA
20, AND UFC 3-600.01.
PROVIDE NEMA 250 TYPE 4 WALL MOUNTED DEVICES AND APPLIANCES WITHIN THE
HANGAR BAY (INCLUDING BACKBOXES). PROVIDE WATERTIGHT CONDUIT AND
JUNCTION BOXES THROUGHOUT HANGAR BAY.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
FIRE ALARM & MASS NOTIFICATION LEGEND
SMOKE DETECTOR
CLEAR STROBE (XX = CANDELA RATING)
SPEAKER APPLIANCE
DUCT DETECTOR
REMOTE TEST SWITCH FOR DUCT DETECTOR
HORN APPLIANCE (WEATHERPROOF)
ELECTRIC FIRE ALARM BELL
(WEATHERPROOF)
SUPERVISORY (TAMPER) SWITCH
WATER FLOW SWITCH
FIRE ALARM GRAPHIC ANNUNCIATOR
FIRE ALARM / MASS NOTIFICATION CONTROL PANEL
LOCAL OPERATING CONSOLE
FIRE ALARM MANUAL PULL STATION
COMBINATION SPEAKER - STROBE APPLIANCE
AMBER STROBE (XX = CANDELA RATING)
(MAY BE COMBINED WITH SPEAKER APPLIANCES)
MNS
ADDRESSABLE OUTPUT MODULE
ADDRESSABLE INPUT MODULE
VS
WF
SURGE PROTECTIVE DEVICE
DET-TRONICS CONTROL PANELDET
CO CARBON MONOXIDE DETECTOR
DET-TRONICS X3301 OPTICAL FLAME DETECTOR
SYSTEM INPUTS
MANUAL PULL STATION
A U
D
IO
-V
IS
U A
L F
IR
E
A L A
R M
I N
D
IC
A T
IO
N
B Y
D E
V
IC
E
CONTROL UNIT
ANNUNCIATION
A U
D
IO
-V
IS
U A
L S
U P
E R
V
IS
O R
Y I N
D
IC
A T
IO
N
B Y
D E
V
IC
E
A U
D
IO
-V
IS
U A
L T
R O
U B
L E
I D
E N
T
IF
IC
A
T
IO
N
B Y
D E
V
IC
E
A U
D
IO
-V
IS
U A
L S
U P
E R
V
IS
O R
Y I N
D
IC
A T
IO
N F
O R
F A
S O
V E
R R
ID
E
B Y
M N
S
F
IR
E A
L A
R M
S
IG
N A
L
B Y
D E
V
IC
E T
Y P
E
G E
N E
R A
L S
U P
E R
V
IS
O R
Y S
IG
N
A L
G E
N E
R A
L T
R O
U B
L E
S
IG
N A
L
TRANSMIT TO
BASE RECIEVING
STATION
NOTIFICATION
SIGNALS
TAMPER SWITCH
FAS / MNS SYSTEM LOW BATTERY
GROUND FAULT
NOTIFICATION APPLIANCE SHORT CIRCUIT
RADIO SIGNAL - SINGLE FAULT
SYSTEM OUTPUTS
OPEN CIRCUIT
A B C D E F G H I J K M
F
IR
E A
L A
M
S
IG
N A
L S
S U
P E
R V
IS
O
Y
N A
L
FAS / MNS AC POWER FAILURE
T R
O U
B
E
N A
L S
L
WATER FLOW SWITCH - WET-PIPE SPRINKLER SYSTEM
SMOKE DETECTOR - ABOVE FACP
MANUAL MNS ACTIVATION AT FMCP/LOC
MANUAL HVAC SHUTDOWN AT LOC
CONCURRENT FAS & MNS ACTIVATION
RADIO SIGNAL - INTERFERENCE
RADIO SIGNAL - REMOVAL
S U
P E
R V
IS
O
R Y
S
IG
N A
L F
O R
F A
S O
V E
R R
ID
E
B Y
M N
S
A C
T U
A T E
F A
S M
N S
V
IS
U A
L N
O T
IF
IC
A
T
IO
N
P
P L
IA
N C
E S
S
T R
O B
E S
A N
D L
E D
S
IG
N S
A C
T U
A T E
F A
S M
N S
A U
D
IB
L E
N O
T
IF
IC
A
T
P L
IA
N C
E S
S
P E
A K
E R
S
T E
M P
O R
A R
IL
Y
S
IL
E N
C E
F A
S S
Y S
T E
M A
U D
IB
T
IF
IC
A
T
IO
N A
C T U
A T E
E X
T E
R
IO
R F
A S
M
N S
A U
D
IB
T
IF
IC
A
T
IO
N A
P P
L
IA
N C
E S
S
P E
A K
E R
S
A C
T U
A T E
E X
T E
R
IO
R W
A T E
R F L O
W A
L A
R M
B E
L L
AUXILIARY
FUNCTIONS
N O
A C
T
IV
A T E
R E
L A
Y T
O S
H U
T D
O W
N H
V A
C S
Y S
T
Q
U
IP
M E
N T
A C
T
IV
A T E
R E
L A
Y T
O I N
IT
IA
T E
F
IR
E P
U M
P
P
DRY PIPE SPRINKLER SYSTEM - SUPERVISORY PRESSURE SWITCH
FIRE PUMP RUNNING
DUCT SMOKE DETECTOR
(NOT USED)
A C
T U
A T E
E X
T E
R
IO
R D
IV
E
R T E
R V
A L V
E
FIRE PUMP LOSS OF POWER 13
FIRE PUMP PHASE REVERSAL 14
(NOT USED)
DIVERTER VALVE MANUAL PULL STATION
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
ISSUED
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
710 Avis Drive, #100 Ann Arbor, MI 48108-9649 phone: 810-956-9300 fax: 810-956-9281
/1
/2
:0 :0
A
M C
R e v it L o c a l\
.0
-E
-R
D a n .G o ld b e rg G
C S
L
.r v t
NOTES & SYMBOLS
NOT FOR CONSTRUCTION
FJRP112701ANG PRO. NO.:
3258000-131303.01
DEG
MAM
April 25, 2022
DEG
N C
A N
G
T
H A
W
C H
A R
L O
T T
E D
O U
G L A
S I A
P C
H A
R L O
T T
E N
O R
T H
C A
R O
L
IN
A
R E
P A
IR
M
A
IN
T E
N A
N C
E H
A N
G A
R B
U
IL
D
IN
G
FA001
NO SCALE1
Fire Alarm Ops Matrix
C
LO
C
P
P
P
P
P
P
P
P
E5
E4
E3
E2
E1
EC
EB
EA
N9 N8 N7 N6 N5N4 N3 N2 N1
ND
NC
NB
NA
HG
7.7
7.3
E
D
C
B
A
F J
K
5.001
5.001
5.001
DEMO NOTES:
THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND ARE
INTENDED TO INDICATE THE SCOPE OF WORK REQUIRED. THE
CONTRACTOR SHALL VISIT THE SITE PRIOR TO SUBMITTING A BID
AND VERIFY EXISTING CONDITIONS.
DASHED WALLS ON THE FLOOR PLANS INDICATE EXISTING WALLS
BEING DEMOLISHED. REFER TO THE ARCHITECTURAL DEMOLITION
PLANS FOR THE EXACT EXTENT OF WORK REQUIRED BY THIS
PROJECT.
THE EXISTING FIRE ALARM SYSTEM SHALL REMAIN IN OPERATION
THROUGHOUT AREAS OUTSIDE OF ARCHITECTURAL SCOPE OF
CONSTRUCTION PRIOR TO DEMOLITION OF THE FIRE ALARM SYSTEM
COMPONENTS IN THOSE SPACES. DURING THE DEMOLITION OF THE
FIRE ALARM SYSTEM TEMPORARY HEAT DETECTORS SHALL BE
CONNECTED TO A SPARE CIRCUIT OF THE FIRE ALARM SYSTEM
WHEN THE SPACE IS OCCUPIED BY THE CONTRACTOR. WHERE
TEMPORARY HEAT DETECTORS ARE NOT FEASIBLE, THE
CONTRACTOR SHALL PROVIDE TRAINED ROAMING FIRE WATCH
DURING SYSTEM OUTAGES.
WHERE FIRE ALARM DEVICES ARE BEING REMOVED, ALL
ASSOCIATED CONDUIT AND WIRE BACK TO THE ASSOCIATED FIRE
ALARM PANEL OR JUNCTION BOX SERVING THE DEVICE SHALL ALSO
BE REMOVED. THE CONTRACTOR SHALL DISPOSE OF MATERIAL THE
OWNER DOES NOT WANT TO REUSE OR RETAIN FOR MAINTENANCE
PURPOSES.
ALL BOXES THAT REMAIN IN PLACE IN EXISTING MASORY WALLS
THAT ARE TO REMAIN SHALL BE PROVIDED WITH A BLANK
COVERPLATE.
ALL CONDUIT SHALL BE REMOVED WHERE WALLS ARE BEING
REMOVED. WHERE CONDUT IS IN THE CONCRETE SLAB, CUT OFF
FLUSH, PULL OUT WIRE, AND PLUG. WHERE CONDUIT IS RUN
EXPOSED, ALL ASSOCIATED CLAMPS, SUPORTS, HANGERS, ETC.,
SHALL ALSO BE REMOVED. CONDUIT CONCEALED IN WALL
CONSTRUCTION MAY BE ABANDONED IN PLACE IF NOT AFFECTED BY
OTHER CONSTRUCTION.
THE CONTRACTOR SHALL COORDINATE ALL WORK, INCLUDING
PHASING, WITH OTHER CONTRACTORS AT THE JOB SITE BEFORE
REMOVING EXISTING FIRE ALARM DEVICES AND INSTALLING NEW
ITEMS.
EXISTING CONDUIT IN GOOD CONDITION MAY BE REUSED IN PLACE.
RELOCATION OF EXISTING CONDUIT SHALL NOT BE PERMITTED.
1.
2.
3.
4.
5.
6.
7.
8.
KEY PLAN
A
B
C
SHOP
SOUTH
SHOP
NORTH
B2
A2
A2
C2
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
ISSUED
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
710 Avis Drive, #100 Ann Arbor, MI 48108-9649 phone: 810-956-9300 fax: 810-956-9281
/1
/2
:0 :4
A
M C
R e v it L o c a l\
.0
-E
-R
D a n .G o ld b e rg G
C S
L
.r v t
FIRE ALARM
OVERALL DEMO
PLAN
NOT FOR CONSTRUCTION
FJRP112701ANG PRO. NO.:
3258000-131303.01
DEG
MAM
April 25, 2022
DEG
N C
A N
G
T
H A
W
C H
A R
L O
T T
E D
O U
G L A
S I A
P C
H A
R L O
T T
E N
O R
T H
C A
R O
L
IN
A
R E
P A
IR
M
A
IN
T E
N A
N C
E H
A N
G A
R B
U
IL
D
IN
G
FAD101
3/64" = 1'-0"1
FIRE ALARM OVERALL DEMO PLAN
KEYED NOTES
5.001 REMOVE ALL FIRE ALARM DEVICES, CONDUCTORS, CONNECTORS, AND
CONDUIT IN HATCHED AREA.
EF.
R E
F
R E F.
DN
DN
FACP
M M
M
M
M
M
M
M
M M
M M
M
M
M
M
MM
M
M
M
M
M
M
M
M
M
MM
M M
M
LOC
LO
C
M
M
DET
CO
CO
CM
E5
E4
E3
E2
E1
EC
EB
EA
N7
N6
N5N4
N3
N2 N1
ND
NC
NB
NA
H
G
10 9 8
7.7 7.3
E
D
C
B
A
11 7 6 5 4 3 2 1
F
J
K
HANGAR
H100
HYDRO
WORK
AREA
H145
BATTERY
ROOM
H135
ELEC
WORK
AREA
H134
HYDRO
ADMIN
H144
ELEC
ADMIN
H142
LOX
CART
ROOM
H132
OPEN
OFFICE
H112
ELEC./MECH.
RM.
H118
SPRINKLER
ROOM
H115
FA103
FA104
5.105
5.103
5.103
5.103
5.103
5.103
5.103
5.102
5.102
5.104 5.101
5.101
5.106
KEY PLAN
A
B
C
SHOP
SOUTH
SHOP
NORTH
B2
A2
A2
C2
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
ISSUED
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
710 Avis Drive, #100 Ann Arbor, MI 48108-9649 phone: 810-956-9300 fax: 810-956-9281
/1
/2
:0 :1
A
M C
R e v it L o c a l\
.0
-E
-R
D a n .G o ld b e rg G
C S
L
.r v t
FIRE ALARM AND
MNS FLOOR PLAN
HANGAR
NOT FOR CONSTRUCTION
FJRP112701ANG PRO. NO.:
3258000-131303.01
DEG
MAM
April 25, 2022
DEG
N C
A N
G
T
H A
W
C H
A R
L O
T T
E D
O U
G L A
S I A
P C
H A
R L O
T T
E N
O R
T H
C A
R O
L
IN
A
R E
P A
IR
M
A
IN
T E
N A
N C
E H
A N
G A
R B
U
IL
D
IN
G
FA102
1/16" = 1'-0"1
FIRE ALARM AND MNS FLOOR PLAN HANGAR
KEYED NOTES
5.101 PROVIDE CARBON MONOXIDE DETECTOR FOR ERV UNIT ON MEZZANINE
LEVEL. SEE MECHANICAL DRAWINGS FOR EXACT LOCATION.
5.102 MANUAL DIVERTER VALVE PULL STATION
5.103 DET-TRONICS X3301 OPTICAL FLAME DETECTOR.
5.104 DET-TRONICS CONTROL PANEL
5.105 CLASS I DIV 2 BATTERY STORAGE AREA.
5.106 PROVIDE WEATHERPROOF CONTROL MODULE FOR DIVERTER VALVE
ACTUATION IN DIVERTED VALVE VAULT. SEE CIVIL DRAWINGS FOR EXACT
LOCATION.
DN
MM
M
M
M
M M
M
M
M
M
M
M
MM
M
M
M
M
MM
M
M
M
MM
MM
M
M
M
M
M
MM
M
M
M M
M
M
MMM
M
M
MM
M
MM
M
L O
C
N9 N8 N7 N6 N5N4 N3 N2 N1
ND
NC
NB
NA
H G
10 9 8 7.7
E
D
F J
K
AMXS
CHIEF
N153B
AMXS
FLIGHT
CHIEF
N153A
AMXS
FLIGHT
CHIEF
N153C
AMXS
FLIGHT
CHIEF
N153F
CORRIDOR
N153
AMXS
FLIGHT
CHIEF
N153E
COPY/PRINT
N153D
FOYER
N160
CORRIDOR
N150
SUPPORT
EQUIPMENT
N152
MECHANICAL
ROOM
N161
STORAGE
N113B
READY/BREAK
ROOM
N151
SHIRT
OFFICE
N143
COMMANDER
N141
CTK
N131
CTK
CHECKOUT
N131A
VESTIBULE
N132
CORRIDOR
N130
BOEING
REP
N125A
WOMEN
N124
MENS
N123
OPEN
OFFICE
N125
MENS
LOCKER
N121A
MENS
N121
CORRIDOR
N120
MOO
N142
PRO
SUP
N144
STORAGE
N145
JANITOR/LAUNDRY
N146
BREAK
ROOM
N122
ENGINE
WORKROOM
N113
PW
OFFICE
N111
PMEL
STORAGE
N112
ENG
ELEMENT
CHIEF
N113A VESTIBULE
N109
AVIONICS
ELEMENT
CHIEF
N116
CMF
CHIEF
N117
CONFERENCE
N118
CORRIDOR
N107
PASSAGE
N115
AVIONICS
N110
SIPR
N110A
AVIONICS
STORAGE
N110B
COMSEC
N110AA
CORRIDOR
N101
VESTIBULE
N100
ELEC.
ROOM
N102
WOMEN
N104
REF.
PLAN OF THIS AREA
FOR2/ FA104
FA104
KEY PLAN
A
B
C
SHOP
SOUTH
SHOP
NORTH
B2
A2
A2
C2
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
ISSUED
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
710 Avis Drive, #100 Ann Arbor, MI 48108-9649 phone: 810-956-9300 fax: 810-956-9281
/1
/2
:0 :2
A
M C
R e v it L o c a l\
.0
-E
-R
D a n .G o ld b e rg G
C S
L
.r v t
FIRE ALARM AND
MNS FLOOR PLAN
NORTH WING
NOT FOR CONSTRUCTION
FJRP112701ANG PRO. NO.:
3258000-131303.01
DEG
MAM
April 25, 2022
DEG
N C
A N
G
T
H A
W
C H
A R
L O
T T
E D
O U
G L A
S I A
P C
H A
R L O
T T
E N
O R
T H
C A
R O
L
IN
A
R E
P A
IR
M
A
IN
T E
N A
N C
E H
A N
G A
R B
U
IL
D
IN
G
FA103
1/8" = 1'-0"1
FIRE ALARM AND MNS FLOOR PLAN NORTH WING
REF.
M
M
M
M
M M
M
M M
M M
M
M
M
MM
M
M
M
M M
M
M
M
M
LOC
M
M
DN
M
M
M
MM
E5
E4
E3
E2
E1
EC
EBEA
H
G
F
J
K
VESTIBULE
E125
MEN
E122
OPEN
OFFICE
E123
CHIEF
INSPECTOR
E123A
QA
SUPER
E123B
STORAGE
E123D
TESTING
E107A
COMM
E119
ELEC
E116
WOMEN
E120
CORRIDOR
E115
BREAK
E117
CLASSROOM
E108
UTM
OFFICE
E107
CONF
ROOM
E123C
FOYER
E101
VESTIBULE
E100
DCM.
E104
MXG/CC
E105
MXG/ADM
E103
CCC
E106
OPEN
OFFICE
E102MECH.
E126
STORAGE
E108A
N9 N8 N7 N6 N5N4
NB
NA
E12
D
F
CTK
N131
CTK
CHECKOUT
N131A
BATTERY
STORAGE
H135A
CORRIDOR
N130
VESTIBULE
N132
KEY PLAN
A
B
C
SHOP
SOUTH
SHOP
NORTH
B2
A2
A2
C2
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
ISSUED
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
710 Avis Drive, #100 Ann Arbor, MI 48108-9649 phone: 810-956-9300 fax: 810-956-9281
/1
/2
:0 :2
A
M C
R e v it L o c a l\
.0
-E
-R
D a n .G o ld b e rg G
C S
L
.r v t
FIRE ALARM AND
MNS ENLARGED
FLOOR PLAN EAST
WING
NOT FOR CONSTRUCTION
FJRP112701ANG PRO. NO.:
3258000-131303.01
DEG
MAM
April 25, 2022
DEG
N C
A N
G
T
H A
W
C H
A R
L O
T T
E D
O U
G L A
S I A
P C
H A
R L O
T T
E N
O R
T H
C A
R O
L
IN
A
R E
P A
IR
M
A
IN
T E
N A
N C
E H
A N
G A
R B
U
IL
D
IN
G
FA104
1/8" = 1'-0"1
FIRE ALARM AND MNS ENLARGED FLOOR PLAN EAST WING
1/8" = 1'-0"2
FIRE ALARM AND MNS ENLARGED FLOOR PLAN AREA B2 - MINOR CONSTRUCTION
FIRE ALARM & MASS NOTIFICATION SYSTEM NOTES:
1. FIRE ALARM CONTROL UNIT AND MASS NOTIFICATION AUTONOMOUS CONTROL UNIT (FMCP) IS A COMBINED UNIT OF THE FIRE ALARM CONTROL PANEL (FACP) AND THE MNS AUTONOMOUS CONTROL UNIT (ACU). THE UNIT COULD USE
ONE OR MORE ENCLOSURES.
2. MASS NOTIFICATION ACU SHALL BE INTERFACED WITH THE TELEPHONE SYSTEM, SO THAT ANNOUNCEMENTS MAY BE
MADE OVER THE FA / MNS SPEAKERS VIA THE TELEPHONE SYSTEM.
3. ALL DETECTION AND ALARM CIRCUITS SHALL BE OF THE SUPERVISED CLASS A, STYLE D FOR INITIATING CIRCUITS AND A SUPERVISED CLASS A, STYLE Z FOR NOTIFICATION APPLIANCE CIRCUITS. SIGNALING LINE CIRCUITS (SLC) SHALL BE CLASS A, STYLE 2α.
4. MONITORED DEVICES INCLUDE FLOW AND TAMPER SWITCHES.
5. IF NOTIFICATION APPLIANCE CIRCUIT (NAC) POWER SUPPLIES OR AMPLIFIERS ARE REQUIRED, LOCATIONS SHALL BE APPROVED BY THE OWNER AND SHALL BE ACCESSIBLE TO THE FIRE DEPARTMENT. PROVIDE SMOKE DETECTOR (NOT SHOWN ON FLOOR PLANS) AT EACH NAC POWER SUPPLY/AMPLIFIER LOCATION UNLESS THE ROOM IS COVERED BY AREA SMOKE DETECTION. PROVIDE 120V POWER TO EACH LOCATION. NOTE THE SPEAKERS IN THE SECURE AREA
SHALL HAVE THEIR OWN HIGH GAIN POWER AMPLIFIER.
6. SEE PLANS FOR SPECIFIC CANDELA (CD) RATINGS ON NOTIFICATION APPLIANCES
7. ALL JUNCTION, TERMINAL, AND PULLING BOXES AND COVERS SHALL BE PAINTED RED AND SHALL BE IDENTIFIED WITH ENGRAVED LABELS BY CIRCUIT THAT IT CONTAINS. ALL CONDULETS AND SIMILAR UNITS SHALL BE PAINTED RED. ALL DETECTION AND TERMINAL DEVICES SHALL HAVE ENGRAVED PLASTIC OR METALLIC ALPHANUMERIC IDENTIFICATION, WHICH SHALL BE KEYED TO THE POSTED AND OPERATIONS AND MAINTENANCE INSTRUCTIONS.
8. ALL WIRING SHALL BE PER MANUFACTURER'S RECOMMENDATIONS.
9. WHEN THE MNS IS ANNOUNCING, AUDIBLE AND VISUAL FIRE ALARMS SHALL BE DE-ENERGIZED. CONTRACTOR SHALL
SUPPLY ALL NECESSARY EQUIPMENT TO ACCOMPLISH THIS PROCEDURE.
10. ALL SPEAKER AND STROBE CIRCUITS SHALL BE SUPERVISED.
11. STROBES SHALL BE DUAL AMBER/CLEAR TYPE WITH SEPARATE CABLING TO EACH STROBE.
12. SEE DRAWING FOR EXACT LOCATION OF REMOTE LOCAL OPERATION CONSOLE (LOC).
13. EMERGENCY EYEWASH STATIONS SHALL EACH HAVE A HORN/STROBE NOTIFICATIONS APPLIANCE AND A FLOW SWITCH. IF THE STATION IS USED THE FLOW SWITCH SHALL PROVIDE A TROUBLE ALARM AT THE FACP, AND THE HORN/STROBE LOCATED AT THE SPECIFIC EYEWASH STATION THAT HAS BEEN USED SHALL BE ENERGIZED.
CDCD CD
CDCDCDCD
CD
24V POWER
SLC CIRCUIT
ANTENNA CABLING
FIRE ALARM
CONTROL PANEL
(FACP)
MNS
AUTONOMOUS
CONTROL UNIT
(ACU)
ROOM H115
120 VAC
LOC CORRIDOR H116
TO OTHER DUAL AMBER/CLEAR STROBES
AND THEN BACK TO FACP/ACU
TO OTHER SPEAKERS
AND THEN BACK TO FACP/ACU
TO OTHER DUAL AMBER/CLEAR STROBES
AND THEN BACK TO FACP/ACU
TO OTHER SPEAKERS
AND THEN BACK TO AMPLIFIER
TO OTHER EQUIPMENT
AND THEN BACK TO FACP/ACU
MONITORED
DEVICE
CONTROLLED
DEVICE
S SSS
S S S S
MM CMDS
RTS/I
SPD
FIRE ALARM / MNS
CONTROL PANEL
(FMCP)
DET-TRONICS
CONTROL PANEL
(DET)
120 VAC
SPD
TO OTHER FLAME DETECTION
DEVICES AND THEN BACK TO DET
LOC CORRIDOR N153
LOC OPEN OFFICE E102
CONTROL UNIT
ANNUNCIATION
A U
D
IO
-V
IS
U A
L F
IR
E A
LA
R
M
IN
D
IC
A T
IO
N
B Y D
E V
IC
E
A U
D
IO
-V
IS
U A
L S
U P
E R
V
IS
O R
Y
IN
D
IC
A T
IO
N
B Y D
E V
IC
E
A U
D
IO
-V
IS
U A
L T R
O U
B
LE
ID
E
N T
IF
IC
A
T
IO
N
B Y
D E
V
IC
E
A U
D
IO
-V
IS
U A
L S
U P
E R
V
IS
O R
Y
IN
D
IC
A T
IO
N F
O R
F
V
E R
R
ID
E B
Y M
N S
F
IR
E A
LA
R
M S
IG
N
A L
B
Y D
E V
IC
E
T Y P
E
A B C D E F G
F
IR
E A
L A
N
A L S
MANUAL PULL STATION
WATER FLOW SWITCH - FLOOR SPRINKLER SYSTEM ZONE
SMOKE DETECTOR - ABOVE FMCU
G E
N E
R A
L S
U P
E R
V
IS
O R
Y S
IG
N
A L
G E
N E
R A
L T R
O U
B
LE
S
IG
N A
L
S U
P E
R V
IS
O
R Y S
IG
N
A L
F O
R F
A S
O V
E R
R
ID
E B
Y M
N S
TX TO BASE
REC. STATION
H
S U
P E
R V
IS
O
R Y
S
IG
N A
L S
TAMPER SWITCH
DRY PIPE SPRINKLER SYSTEM - SUPERVISORY PRESSURE SWITCH
MANUAL MNS ACTIVATION AT FMCU / LOC
CONCURRENT FAS & MNS ACTIVATION
DUCT SMOKE DETECTOR FOR HVAC SHUTDOWN
FAS / MNS AC POWER FAILURE
MANUAL HVAC SHUTDOWN AT LOC
FAS / MNS SYSTEM LOW BATTERY
OPEN CIRCUIT, SHORT CIRCUIT
GROUND FAULT
NOTIFICATION APPLIANCE SHORT CIRCUIT
RADIO SIGNAL - SINGLE FAULT
RADIO SIGNAL - INTERFERENCE
RADIO SIGNAL - REMOVAL
T R
O U
B L E
S
IG
N A
L S
A C
T U
A T E
F A
S /M
N S
V
IS
U A
L N
O T
IF
IC
A
T
P
LI
A N
C E
S S
T R
O B
E S
A N
D L
E D
S
IG
N S
A
C T U
A T E
E X T E
R
IO
R W
A T E
R F
LO
W A
LA
R
M B
E
LL
A C
T U
A T E
F A
S /M
N S
A U
D
IB
LE
N
O T
IF
IC
A
T
P
LI
A N
C E
S H
O R
N S
S
P E
A K
E R
S
T E
M P
O R
A R
IL
Y
S
IL
E N
C E
F A
S S
Y S
T E
M A
U D
IB
LE
T
IF
IC
A
T
IO
N
A C
T U
A T E
E X
T E
R
IO
R F
A S
/M N
S A
U D
IB
LE
T
IF
IC
A
T
IO
N A
P P
LI
A
N C
E S
S
P E
A K
E R
S
I J K L M
NOTIFICATION
SIGNALS
N O P
AUXILIARY
FUNCTIONS
A C
T
IV
A T E
R E
LA
Y T
O S
H U
T D
O W
N H
V A
C S
Y S
T
Q
U
IP
M E
N T
SYSTEM INPUTS
S Y
S T E
M O
U T P
U T S
S
E Q
U E
N C
E O
F O
P E
R A
T
IO
N S
NOTES:
1. TWO SEPARATE AND DISTINCT SIGNALS MUST BE INITIATED: ONE INDICATING MOVEMENT OF A
VALVE FROM ITS NORMAL POSITION (OFF-NORMAL), AND THE OTHER INDICATING RESTORATION
OF THE VALVE TO ITS NORMAL POSITION. (NFPA 72 SECTION 17.17.1.1)
2. SIMULTANEOUS FIRE ALARM AND MASS NOTIFICATION EVENTS MUST TRANSMIT A UNIQUE AND
DISTINCT SUPERVISORY SIGNAL.
ABBREVIATIONS:
FAS: FIRE ALARM SYSTEM
FMCU: FIRE ALARM AND MASS NOTIFICATION CONTROL UNIT
FSCS: FIRE FIGHTERS' SMOKE CONTROL STATION
LOC: LOCAL OPERATING CONSOLE
MNS: MASS NOTIFICATION SYSTEM
REC: RECEIVING
TX: TRANSMIT
FIRE PUMP - PHASE REVERSAL
FIRE PUMP - POWER FAILURE
FIRE PUMP - RUN
A C
T
IV
A T E
R E
LA
Y
T O
IN
IT
IA
T E
F
IR
E P
U M
P
A C
T
IV
A T E
R E
LA
Y
T O
IN
IT
IA
T E
D
IV
E R
T E
R V
A
LV
E
(NOT USED)
(NOT USED)
DIVERTER VALVE MANUAL PULL STATION
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
ISSUED
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
710 Avis Drive, #100 Ann Arbor, MI 48108-9649 phone: 810-956-9300 fax: 810-956-9281
/2
/2
:1 :4
A
M C
R e v it L o c a l\
.0
-E -R c h ri s .d o u g a n
.r v t
FIRE ALARM AND
MNS RISER
DIAGRAM AND
MATRIX
FJRP112701ANG PRO. NO.:
3258000-131303.01
Author
Checker
July 20, 2022
Designer
N C
A N
G
T
H A
W
C H
A R
L O
T T
E D
O U
G L A
S I A
P C
H A
R L O
T T
E N
O R
T H
C A
R O
L
IN
A
R E
P A
IR
M
A
IN
T E
N A
N C
E H
A N
G A
R B
U
IL
D
IN
G
FA105
07/20/22 B-3 SUBMITTAL
NO SCALE1
FIRE ALARM RISER DIAGRAM
NO SCALE2
FIRE ALARM MATRIX
FIRE PROTECTION GENERAL NOTES:
1. ABBREVIATIONS INDICATED HERE AND NOT USED IN THE CONTRACT
DOCUMENTS DO NOT APPLY TO THIS PROJECT. ADDITIONAL ABBREVIATIONS
MAY BE INDICATED IN THE CONTRACT DOCUMENTS.
2. THESE DRAWINGS ARE DESIGN DRAWINGS AND ARE DIAGRAMMATIC. THEY
MAY NOT SHOW ALL PHYSICAL ARRANGEMENTS, OFFSETS, BENDS, OR
ELBOWS WHICH MAY BE REQUIRED FOR INSTALLATION OF VARIOUS
MATERIALS, EQUIPMENT AND PIPING IN ALLOTTED SPACES. EXAMINE THESE
AND OTHER AVAILABLE DRAWINGS TO DETERMINE SPACE LIMITATIONS AND
INTERFERENCES. MAKE ANY MINOR CHANGES IN LOCATIONS OF EQUIPMENT
AND PIPING FROM THAT SHOWN ON DRAWINGS AND FOR ALL PHYSICAL
DETAILS REQUIRED FOR INSTALLATION. COST FOR ADAPTING WORK TO JOB
SITE CONDITIONS SHALL NOT BE CONSIDERED AS BASIS OF AN EXTRA COST
TO CONTRACT.
3. ELEVATION OF PIPING INDICATED ON THESE DRAWINGS ARE TO BE USED AS
GUIDELINES TO ASSIST WITH INSTALLATIONS. MINOR CHANGES TO THESE
ELEVATIONS MAY BE NECESSARY TO ELIMINATE UNFORESEEN
INTERFERENCES. ANY CHANGE IN ELEVATION SHALL BE APPROVED PRIOR TO
CHANGE.
4. ANY AND ALL INFORMATION SHOWN ON THESE DRAWINGS WITH RESPECT TO
EXISTING STRUCTURES, UTILITIES, AND MECHANICAL SYSTEMS IS AS EXACT
AS COULD BE SECURED. THE INFORMATION IS NOT WARRANTED NOR
GUARANTEED ACCURATE. FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO
PROCEEDING WITH WORK.
5. ACCURATE AND LEGIBLE RECORD DRAWINGS SHALL BE MAINTAINED AT THE
JOB SITE AND BE SUBMITTED PRIOR TO FINAL PAYMENT.
6. ROOFING SYSTEMS SHALL BE PROTECTED FROM DAMAGE DURING
CONSTRUCTION ACTIVITIES.
7. TEMPORARILY PATCH ALL ROOF OPENINGS WATERTIGHT UNTIL FINAL
CLOSURE CAN BE MADE.
8. VERIFY ALL EQUIPMENT LOCATIONS AND PIPE ROUTING WITH OWNER PRIOR
TO INSTALLATION.
9. SEQUENCE OF WORK AND/OR PLACE OF COMMENCEMENT OF WORK SHALL
BE APPROVED PRIOR TO WORK BEING STARTED. SCHEDULED SHUTDOWNS
SHALL BE CLOSELY COORDINATED WITH EXISTING OPERATIONS.
FIRE PROTECTION HATCH PATTERN LEGEND:
LIGHT HAZARD: 0.10 GPM/FT^2 OVER 1,500 FT^2
ORDINARY HAZARD: 0.20 GPM/FT^2 OVER 2,500 FT^2
EXTRA HAZARD: 0.30 GPM/FT^2 OVER 2,500 FT^2
AIRCRAFT HANGAR: 12 K-25.2 HEADS @ 7 PSI
FLANGE
MAINTAIN 1' ANNULAR GAP
BETWEEN PIPE AND SLAB.
SEAL GAP
EXTERIOR WALL
FINISHED FLOOR LEVEL
GRADE
/3
78" MINIMUM
LOCATE JOINT 24" OUTSIDE OF
FOOTING PRESSURE LINE
45.00°
FOOTING PRESSURE LINE
EXTEND CASING 2" PAST
FOOTING PRESSURE LINE
(TYP)
END SEAL (TYP)
CASING
THRUST
BLOCK
SERVICE
ENTRANCE
PIPE
/3
X
/1
12"
IF DIMENSION "X" IS LESS THAN 12", INSTALL DI OR RCP CASING.
MAINTAIN AT LEAST 2" ANNULAR GAP BETWEEN PIPE AND CASING.
APPLY CASING END SEALS.
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
ISSUED
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
710 Avis Drive, #100 Ann Arbor, MI 48108-9649 phone: 810-956-9300 fax: 810-956-9281
/1
/2
:1 :1
A
M C
R e v it L o c a l\
.0
-P
-R
D a n .G o ld b e rg G
C S
L
.r v t
NOTES & SYMBOLS
NOT FOR CONSTRUCTION
FJRP112701ANG PRO. NO.:
3258000-131303.01
DEG
RMM
April 25, 2022
DEG
N C
A N
G
T
H A
W
C H
A R
L O
T T
E D
O U
G L A
S I A
P C
H A
R L O
T T
E N
O R
T H
C A
R O
L
IN
A
R E
P A
IR
M
A
IN
T E
N A
N C
E H
A N
G A
R B
U
IL
D
IN
G
FX001
04/25/22 B-2 RESUBMITTAL
NO SCALE1
FIRE WATER SERVICE ENTRANCE
F.E
F.E.
F.E.
F.E. F.E.
F .E
F
.E
N1N2N3N4N5N6N7N8N9
D
C
B
A
EBEA
E1
E2
E3
E4
E5
FX105
5.002
5.002
5.002
5.002
5.002
5.002
5.001
KEY PLAN
A
B
C
SHOP
SOUTH
SHOP
NORTH
B2
A2
A2
C2
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
ISSUED
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
710 Avis Drive, #100 Ann Arbor, MI 48108-9649 phone: 810-956-9300 fax: 810-956-9281
/1
/2
:1 :2
A
M C
R e v it L o c a l\
.0
-P
-R
D a n .G o ld b e rg G
C S
L
.r v t
FIRE PROTECTION
HANGAR DEMO PLAN
NOT FOR CONSTRUCTION
FJRP112701ANG PRO. NO.:
3258000-131303.01
DEG
RMM
April 25, 2022
DEG
N C
A N
G
T
H A
W
C H
A R
L O
T T
E D
O U
G L A
S I A
P C
H A
R L O
T T
E N
O R
T H
C A
R O
L
IN
A
R E
P A
IR
M
A
IN
T E
N A
N C
E H
A N
G A
R B
U
IL
D
IN
G
FXD101
1/16" = 1'-0"1
FIRE PROTECTION HANGER DEMO PLAN
KEYED NOTES
5.001 REMOVE ENTIRETY OF FIRE SUPPRESSION SYSTEM INCLUDING ALL
SPRINKLER HEADS, PIPING, FITTINGS, HANGERS AND APPURTENANCES.
5.002 EXISTING FOAM MONITOR NOZZLE TO BE REMOVED.
04/25/22 B-2 RESUBMITTAL
F.E.
F.E. F.E.
N1N2N3N4N5N6N7N8N9
ND
NC
NB
D
13 12 11 10 9 8
5.001 5.001
KEY PLAN
A
B
C
SHOP
SOUTH
SHOP
NORTH
B2
A2
A2
C2
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
ISSUED
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
710 Avis Drive, #100 Ann Arbor, MI 48108-9649 phone: 810-956-9300 fax: 810-956-9281
/1
/2
:1 :3
A
M C
R e v it L o c a l\
.0
-P
-R
D a n .G o ld b e rg G
C S
L
.r v t
FIRE PROTECTION
DEMO PLAN NORTH
WING
NOT FOR CONSTRUCTION
FJRP112701ANG PRO. NO.:
3258000-131303.01
DEG
RMM
April 25, 2022
DEG
N C
A N
G
T
H A
W
C H
A R
L O
T T
E D
O U
G L A
S I A
P C
H A
R L O
T T
E N
O R
T H
C A
R O
L
IN
A
R E
P A
IR
M
A
IN
T E
N A
N C
E H
A N
G A
R B
U
IL
D
IN
G
FXD102
1/16" = 1'-0"1
DESIGN DENSITY PLAN NORTH WING
KEYED NOTES
5.001 REMOVE ENTIRETY OF FIRE SUPPRESSION SYSTEM INCLUDING ALL
SPRINKLER HEADS, PIPING, FITTINGS, HANGERS AND APPURTENANCES.
F.E.
F.E.
F.E. F.E.
F .E
F
.E
REF.
R
EF.
R E
F
DN
DN
STAIR
STA
IR
STAIR
STAIR
N1N2N3N4N5N6N7N8N9
D
C
B
A
EBEA
E1
E2
E3
E4
E5
FX105
LOX CART
ROOM
H132
ELEC
WORK
AREA
H134
EXIT
PASSAGE
H133
ACCESSORIES
ELEMENT
CHIEF
H141
ELEC
ADMIN
H142
HYDRO
ADMIN
H144
BATTERY
ROOM
H135
BATTERY
STORAGE
H135A
HYDRO
WORK
AREA
H145
IT
H146A
HYDRO
VESTIBULE
H146
ELEC
SECTION
OFFICE
H142A
HYDRO
SECTION
CHIEF
H144A
HANGAR
H100
SPRINKLER
ROOM
H115
VESTIBULE
H113
CORRIDOR
H116
HSC
SECTION
CHIEF
H112C
OPEN
OFFICE
H112
INSPECTION
ELEMENT
CHIEF
H112B
FIRE PROTECTION GENERAL NOTES:
1. ABBREVIATIONS INDICATED HERE AND NOT USED IN THE CONTRACT
DOCUMENTS DO NOT APPLY TO THIS PROJECT. ADDITIONAL ABBREVIATIONS
MAY BE INDICATED IN THE CONTRACT DOCUMENTS.
2. THESE DRAWINGS ARE DESIGN DRAWINGS AND ARE DIAGRAMMATIC. THEY
MAY NOT SHOW ALL PHYSICAL ARRANGEMENTS, OFFSETS, BENDS, OR
ELBOWS WHICH MAY BE REQUIRED FOR INSTALLATION OF VARIOUS
MATERIALS, EQUIPMENT AND PIPING IN ALLOTTED SPACES. EXAMINE THESE
AND OTHER AVAILABLE DRAWINGS TO DETERMINE SPACE LIMITATIONS AND
INTERFERENCES. MAKE ANY MINOR CHANGES IN LOCATIONS OF EQUIPMENT
AND PIPING FROM THAT SHOWN ON DRAWINGS AND FOR ALL PHYSICAL
DETAILS REQUIRED FOR INSTALLATION. COST FOR ADAPTING WORK TO JOB
SITE CONDITIONS SHALL NOT BE CONSIDERED AS BASIS OF AN EXTRA COST
TO CONTRACT.
3. ELEVATION OF PIPING INDICATED ON THESE DRAWINGS ARE TO BE USED AS
GUIDELINES TO ASSIST WITH INSTALLATIONS. MINOR CHANGES TO THESE
ELEVATIONS MAY BE NECESSARY TO ELIMINATE UNFORESEEN
INTERFERENCES. ANY CHANGE IN ELEVATION SHALL BE APPROVED PRIOR TO
CHANGE.
4. ANY AND ALL INFORMATION SHOWN ON THESE DRAWINGS WITH RESPECT TO
EXISTING STRUCTURES, UTILITIES, AND MECHANICAL SYSTEMS IS AS EXACT
AS COULD BE SECURED. THE INFORMATION IS NOT WARRANTED NOR
GUARANTEED ACCURATE. FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO
PROCEEDING WITH WORK.
5. ACCURATE AND LEGIBLE RECORD DRAWINGS SHALL BE MAINTAINED AT THE
JOB SITE AND BE SUBMITTED PRIOR TO FINAL PAYMENT.
6. ROOFING SYSTEMS SHALL BE PROTECTED FROM DAMAGE DURING
CONSTRUCTION ACTIVITIES.
7. TEMPORARILY PATCH ALL ROOF OPENINGS WATERTIGHT UNTIL FINAL
CLOSURE CAN BE MADE.
8. VERIFY ALL EQUIPMENT LOCATIONS AND PIPE ROUTING WITH OWNER PRIOR
TO INSTALLATION.
9. SEQUENCE OF WORK AND/OR PLACE OF COMMENCEMENT OF WORK SHALL
BE APPROVED PRIOR TO WORK BEING STARTED. SCHEDULED SHUTDOWNS
SHALL BE CLOSELY COORDINATED WITH EXISTING OPERATIONS.
FIRE PROTECTION HATCH PATTERN LEGEND:
LIGHT HAZARD: 0.10 GPM/FT^2 OVER 1,500 FT^2
ORDINARY HAZARD: 0.20 GPM/FT^2 OVER 2,500 FT^2
EXTRA HAZARD: 0.30 GPM/FT^2 OVER 2,500 FT^2
AIRCRAFT HANGAR: 12 K-25.2 HEADS @ 7 PSI
KEY PLAN
A
B
C
SHOP
SOUTH
SHOP
NORTH
B2
A2
A2
C2
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
ISSUED
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
710 Avis Drive, #100 Ann Arbor, MI 48108-9649 phone: 810-956-9300 fax: 810-956-9281
/1
/2
:1 :2
A
M C
R e v it L o c a l\
.0
-P
-R
D a n .G o ld b e rg G
C S
L
.r v t
DESIGN DENSITY
PLAN HANGAR
NOT FOR CONSTRUCTION
FJRP112701ANG PRO. NO.:
3258000-131303.01
DEG
RMM
April 25, 2022
DEG
N C
A N
G
T
H A
W
C H
A R
L O
T T
E D
O U
G L A
S I A
P C
H A
R L O
T T
E N
O R
T H
C A
R O
L
IN
A
R E
P A
IR
M
A
IN
T E
N A
N C
E H
A N
G A
R B
U
IL
D
IN
G
FX101
1/16" = 1'-0"1
DESIGN DENSITY PLAN HANGAR
F.E. F.E.
DN
N1N2N3N4N5N6N7N8N9
ND
NC
NB
D
13 12 11 10 9 8
AMXS
CHIEF
N153B
AMXS
FLIGHT
CHIEF
N153C
AMXS
FLIGHT
CHIEF
N153A
CORRIDOR
N153
COPY/PRINT
N153D
AMXS
FLIGHT
CHIEF
N153E
AMXS
FLIGHT
CHIEF
N153F
SUPPORT
EQUIPMENT
N152
FOYER
N160
CORRIDOR
N150
READY/BREAK
ROOM
N151
CTK
N131
CTK
CHECKOUT
N131A
VESTIBULE
N132
CORRIDOR
N130
COMMANDER
N141
SHIRT
OFFICE
N143
MECHANICAL
ROOM
N161
CORRIDOR
N140
JANITOR/LAUNDRY
N146
STORAGE
N145
PRO SUP
N144
MOO
N142
ENGINE
WORKROOM
N113
STORAGE
N113B
ENG
ELEMENT
CHIEF
N113A
VESTIBULE
N109
AVIONICS
ELEMENT
CHIEF
N116
CMF
CHIEF
N117
CONFERENCE
N118
PASSAGE
N115
CORRIDOR
N107
PMEL
STORAGE
N112
AVIONICS
N110
PW
OFFICE
N111
BREAK
ROOM
N122
CORRIDOR
N120
BOEING
REP
N125A
OPEN
OFFICE
N125
WOMEN
N124
MENS
N123
MENS
VESTIBULE
N121B
MENS
N121
MENS
LOCKER
N121A
MENS
SHOWER
N121C
VESTIBULE
N108
SIPR
N110A
COMSEC
N110AA
AVIONICS
STORAGE
N110B
COMM.
N103
ELEC.
ROOM
N102
VESTIBULE
N100
CORRIDOR
N101
WOMEN
N104
WOMEN
SHOWER
N104B
/1 FX102B2 FOR
PLAN OF THIS AREA
FIRE PROTECTION HATCH PATTERN LEGEND:
LIGHT HAZARD: 0.10 GPM/FT^2 OVER 1,500 FT^2
ORDINARY HAZARD: 0.20 GPM/FT^2 OVER 2,500 FT^2
EXTRA HAZARD: 0.30 GPM/FT^2 OVER 2,500 FT^2
AIRCRAFT HANGAR: 12 K-25.2 HEADS @ 7 PSI
KEY PLAN
A
B
C
SHOP
SOUTH
SHOP
NORTH
B2
A2
A2
C2
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
ISSUED
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
710 Avis Drive, #100 Ann Arbor, MI 48108-9649 phone: 810-956-9300 fax: 810-956-9281
/1
/2
:1 :3
A
M C
R e v it L o c a l\
.0
-P
-R
D a n .G o ld b e rg G
C S
L
.r v t
DESIGN DENSITY
NORTH WING
NOT FOR CONSTRUCTION
FJRP112701ANG PRO. NO.:
3258000-131303.01
DEG
RMM
April 25, 2022
DEG
N C
A N
G
T
H A
W
C H
A R
L O
T T
E D
O U
G…