Attachment 8 - 668-16-110_Feasibility Study_Fixture Inventory and Tracking .pdf

PDF 2 MB Posted

Attached to
C1DA--668-22-106 Correct Domestic Water System Deficiencies Buildings 1 and 12
Solicitation number
36C26024R0038
Issued by

About this file

This notice requests Standard Form 330 Architect-Engineer Qualifications packages for a design contract to modify existing hot and cold potable water distribution systems in Buildings 1 and 12 at the Mann-Grandstaff VA Medical Center in Spokane, Washington. The contract is a 100% set-aside for Service-Disabled Veteran-Owned Small Businesses. The design period of performance is 315 calendar days from notice of award. The anticipated construction value is between $1,000,000 and $2,000,000. Submissions are due by April 15, 2024 and shall not exceed 20 pages. The selection will evaluate professional qualifications, specialized experience, capacity, past performance, and knowledge of the project locality. Discussions will be held with the top three firms based on written responses. The highest rated firm after discussions will receive a request for fee proposal.

View the file

Other files

File Type Posted
Attachment 10 - 668-16-110_Cross-Connection Evaluation Plans 1of10 .pdf PDF
Attachment 31 - VHA DIRECTIVE 1061_2021-02-16 .pdf PDF
Attachment 1 - 668-22-106_SOW_Revision 3.pdf PDF
Attachment 25 - 668-16-110_Cross-Connection Inventory Report - APPENDIX D - 1of3 .pdf PDF
Attachment 2 - 668-14-107_Plumbing Survey_FINAL DRAWINGS.pdf PDF
Attachment 3 - 668-14-107_Plumbing Survey_FINAL INVENTORY .pdf PDF
Attachment 35 - Phigenics As-Built Drawings.pdf PDF
Attachment 6 - 668-16-110_Feasibility Study_Project Manual .pdf PDF
Attachment 14 - 668-16-110_Cross-Connection Evaluation Plans 5of10 .pdf PDF
36C26024R0038_1.docx DOCX document
Attachment 28 - 668-16-110_Cross-Connection Inventory Report - APPENDIX E-F .pdf PDF
Attachment 13 - 668-16-110_Cross-Connection Evaluation Plans 4of10 .pdf PDF
Attachment 4 - 668-14-107_Plumbing Survey_Dead Leg Summary Total .pdf PDF
Attachment 24 - 668-16-110_Cross-Connection Inventory Report - APPENDIX C .pdf PDF
Attachment 16 - 668-16-110_Cross-Connection Evaluation Plans 7of10 .pdf PDF
Attachment 18 - 668-16-110_Cross-Connection Evaluation Plans 9of10 .pdf PDF
Attachment 20 - 668-16-110_Cross-Connection Inventory Report .pdf PDF
Attachment 33 - 668-22-106_DESIGN REVIEW COMMENT SHEET.xlsx XLSX spreadsheet
Attachment 29 - 668-16-110_Cross-Connection Corrective Action Report .pdf PDF
Attachment 23 - 668-16-110_Cross-Connection Inventory Report - APPENDIX B2 .pdf PDF
Attachment 5 - 668-16-110_Feasibility Study_Drawings .pdf PDF
Attachment 7 - 668-16-110_Feasibility Study_Report .pdf PDF
Attachment 15 - 668-16-110_Cross-Connection Evaluation Plans 6of10 .pdf PDF
Attachment 19 - 668-16-110_Cross-Connection Evaluation Plans 10of10 .pdf PDF
Attachment 12 - 668-16-110_Cross-Connection Evaluation Plans 3of10 .pdf PDF
Attachment 17 - 668-16-110_Cross-Connection Evaluation Plans 8of10 .pdf PDF
Attachment 9 - 668-16-110_Feasibility Study_Cost Estimate .pdf PDF
Attachment 27 - 668-16-110_Cross-Connection Inventory Report - APPENDIX D - 3of3 .pdf PDF
Attachment 22 - 668-16-110_Cross-Connection Inventory Report - APPENDIX B1 .pdf PDF
Attachment 26 - 668-16-110_Cross-Connection Inventory Report - APPENDIX D - 2of3.pdf PDF
Attachment 11 - 668-16-110_Cross-Connection Evaluation Plans 2of10 .pdf PDF
Attachment 32 - MGVMAC_Design Amendments_May 2021 .pdf PDF
Attachment 36 - PPQ.docx DOCX document
Attachment 34 - 2020 GAO High Quality Project Estimate Characteristics .xlsx XLSX spreadsheet
Attachment 30 - 668-16-110_Cross-Connection Control Plan FINAL .pdf PDF
Attachment 21 - 668-16-110_Cross-Connection Inventory Report - APPENDIX A .pdf PDF
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Clients Name: ___VA Hospital - Spokane, WA________________________________

Project #: ___2021-019_______

WH1-1

WH1-2

Sink No

Sink Yes

Shower

Sink Yes

Sink No

Pipes

Sink Yes

Sink Yes

Sink Yes

CW Main

CW Main

Sinks Yes

Showers No

CW Pipe

Sinks No

No

Sinks No

No

No

Mop Sink No

Sinks Yes

Sink No

Sink Yes

Pipes

Pipes

Pipes

Pipes

B008 142 F, Set Point 143 F, C: 62 F

145 F, Set Point 144 F, C: 62 F

Domestic Water Fixture

Tracking Sheet

Building #: ___1______ Name: ___Hospital_______________ Floor #: ___Basement___

Room #

Mixing

Valve NotesUsage

Fixture

Type

Mechanical

Morg Storage

Morg

Shower Room

Bio Med Shop

Mechanical

Mechanical

B011 H: 109 F (134 F), C: 69 F

B007 H: 100 F, C: 60 F

B016 H: 125 F, C: Not Functioning (N.F.)

B018 H: N.F., C: 68 F

B002 H: 130 F, C: 75 F

A002 Out of Order

B003 H: 139 F, C: 60 F

B004 No Access

Plumb Storage

Dietetic Servic

C008A C: 70 F

C001 C: 61 F

D008G H: 97 F, C: 66 F

D008C M: 97 F, H: 98 F (P), C: 64 F

M&O Shop

Break Rm/Comp Lab

Mechanical

Mechanical

C005D C: 66 F

C002 H: 130 F, C: 62 F (Near Hall)

C003A M: 96 F, H: 105 F, C: 63 F

H: 122 F, C: 62 F

Locker Rm/Restroom

Housekeeping

Dishwashing

H: 129 F, C: 64 F (Rinse near Hall)

H: 135 F, C: 76 F (South West)

H: 125 F, C: 62 F (Center)

A007 H: 111 F, C: 65 F (Hand Sink)Kitchen

A010 No good way to measure.

A006A M: 103 F, H: 119 F, C: 66 F

A007A H: 124 F, C: 74 F

C004A M: 104 F, H: 125 F, C: 61 F

Small Breakroom

Locker/Restroom

Janitorial Closet

Restroom/Kitchen

H: 131 F, HR: 124 F, C: 62 F

End of N Wing H: 127 F, HR: 123 F, C: 65 F

End of S Wing H: 128 F, HR: 115 F, C: 73 F

Mid of S Wing H: 122 F, HR: 115 F, C: 63 F

Corridor

Corridor

Corridor/Plumb Stor

Corridor

Center/B002

= No Mixing Valve Page: _1__ of _1__

Sink Yes

Sink Yes

Wash Sink No

Sink Yes

Sink ?

Sink Above Deck

Sink No

Sink No

Sink No

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Above Deck

Sink Yes

Sink Yes

Sink No

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Above Deck

Sink Above Deck

Sink Above Deck

Sink Above Deck

Sink Above Deck

Sink No

Sink No

Sink No

Sink Yes

Sink Yes

Sink YesB102 M: 110 F *

B106 M: 100 F, H: ?, C: ? *

M: 100 F, H: ?, C: ? *

B117 H: 140 F, C: 60 F

B119 H: 142 F, C: 60 F

D127 M: 114 F, H: 134 F, C: 64 F

A127C H: 135 F, C: 70 F

D128 M: 97 F, H: 136 F, C: 62 F

D129 M: 135 F, H: 135 F, C: 84 F

Exam Room

Exam Room

Exam Room

Director Office

D131 M: 130 F, H: 133 F, C: 69 F

D130 M: 81 F, H: 123 F, C: 64 F

D133 M: 113 F, H: 125 F, C: 66 F

D132 M: 126 F, H: 129 F, C: 83 F

Exam Room

Exam Room

SDS Care Coordinator

Exam Room

D135 M: 109 F, H: 112 F, C: 67 F

D134 M: 101 F, H: 110 F, C: 66 F

D107 M: 131 F, H: 131 F, C: 67 F

D105 H: 94 F, C: 64 F

Office

Conference Room

Exam Room

Exam Room

D108 M: 104 F, H: 131 F, C: 62 F

D106 M: 99 F, H: 135 F, C: 66 F

D110 M: 88 F, H: 110 F, C: 64 F

D109 M: 95 F, H: 137 F, C: 61 F

Womens Locker Rm

Office/Exam Rm

Mens Locker Rm

Exam Room

D113 M: 124 F, H: 127 F, C: 76 F

D111 M: 97 F, H: 134 F, C: 63 F

M: 122 F, H: 130 F, C: 70 F

D124 M: 114 F, H: 132 F, C: 66 FER Check-In

Office

Physician Office

D119 H: 139 F, C: 61 F

D123 M: 115 F, H: 133 F, C: 79 F

D117 H: 139 F, C: 61 F

D118 H: 139 F, C: 61 F

Soiled Utility Rm

Exam/Treatment Rm

Blood Draw Rm

Patient Restroom

Office

Procedure Rm 2

Procedure Rm 1

D115 77 F was only temp

D114 M: 92 F, H: 98 F, C: 67 F

C145D H: 140 F, C: 62 F

M: 77 F, H: 132 F, C: 63 F

C145A M: 110 F, H & C: No Adjustment (NA)

C145B M: 101 F, H & C: NA

Domestic Water Fixture

Tracking Sheet

Building #: ___1______ Name: ___Hospital_______________ Floor #: ___1st_Floor___

Room #

Mixing

Valve NotesUsage

Fixture

Type

Specimen Restroom

Specimen Restroom

Small Breakroom

Restroom

Mens Restroom

Womens Restroom

* No access to separate Hot and Cold, enclosed pipes.

** Appears no Hot at all. = No Mixing Valve Page: ____ of _3__ andrewp Text Box

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Above Deck

Sink Above Deck

Sink Above Deck

Sink Above Deck

Sink No?

Sink No

Sink No

Sink No

Sink No

Spray Rinse No

Hand Sink No

Sanitizer No

Spray Rinse No

Sink Yes?

Mop Sink No

Sink Above Deck

Sink Above Deck

Sink Above Deck

Sink Above Deck

Utility Sink No

Sink Above Deck

Utility Sink No

Sink Above Deck

Sink Above Deck

Sink Above Deck

Sink Above Deck

Sink Above Deck

Sink Above Deck

Sink Above Deck

Sink Above DeckE136 M: 91 F, H: 116 F, C: 61 F

E135 M: 94 F, H: 117 F, C: 61 F

E134 M: 97 F, H: 129 F, C: 61 F

Exam Room

Exam Room

Exam Room

E132 M: 90 F, H: 121 F, C: 63 F

E133 M: 90 F, H: 113 F, C: 62 F

E129 M: 88 F, H: 120 F, C: 63 F

E130 M: 86 F, H: 130 F, C: 63 F

Patient Restroom

Exam Room

Exam Room

Exam Room

E121 H: 112 F, C: 63 F

M: 82 F, H: 107 F, C: 63 F

H: 126 F, C: 61 F

E128 M: 88 F, H: 109 F, C: 66 FExam Room

Soiled Utility

E120 M: 80 F, H: 115 F, C: 65 F

E126 M: 96 F, H: 116 F, C: 66 F

A107C H: 119 F, C: 71 F

E118 M: 95 F, H: 114 F, C: 67 F

Office/Breakroom

Exam Room

Wound Care

Minor Operatory

H: 117 F, C: 58 F

H: 128 F, C: 58 F

H: 129 F, C: 58 F

A102F M: 101 F, H & C: ? *

A102E H: 110 F, C: 61 F (C delayed)

H: 119 F, Hot Only

B107A H: 58 F, C: 58 F **Pre-Rinse Room

IV Room

Storage Closet

C112B H: 134 F, C: 60 F

B109A H: 128 F, C: 58 F

M: 82 F, H: 130 F, C: 63 F

C112A H: 133 F, C: 61 F *

H: 124 F, C: 58 F

M: 120 F, H: ?, C: 61 F *

M: 108 F, H: 126 F, C: 77 F

C109 M: 92 F, H: 128 F, C: 65 F

M: 124 F *

C113 M: 110 F, H: 127 F, C: 75 F

Domestic Water Fixture

Tracking Sheet

Building #: ___1______ Name: ___Hospital_______________ Floor #: ___1st_Floor___

Room #

Mixing

Valve Notes

Out of Order

D104 M: 104 F *

B102 M: 108 F

D103

Usage

Fixture

Type

Womens Restroom

Mens Restroom

Womens Restroom

Mens Restroom

Family Restroom

Office

Office

Cafeteria Kitchen

* No access to separate Hot and Cold, enclosed pipes.

** Appears no Hot at all. = No Mixing Valve Page: ____ of _3__ andrewp

Sink Above Deck

Sink No

Mop Sink No

Sink Above Deck

Sink Above Deck

Utility Sink No

Sink Above Deck

Sink No

Sink No

Sink No

E140 Conference/Break Rm H: 127 F, C: 60 F

Domestic Water Fixture

Tracking Sheet

Building #: ___1______ Name: ___Hospital_______________ Floor #: ___1st_Floor___

Room # Usage

Fixture

Type

Mixing

Valve Notes

E139 Locker Room M: 92 F, H: 115 F, C: 61 F

E113 Housekeeping H: 120 F, C: 60 F

E110 Staff Restroom M: Lever Adjust, H: 122 F, C: 65 F

E119 Exam Room M: 106 F, H: 117 F, C: 66 F

H: 122 F, C: 61 F

E122 Exam Room M: 80 F, H: 112 F, C: 65 F

By Main Entrance Coffee Shop H: 135 F, C: 59 F

H: 135 F, C: 59 F

H: 135 F, C: 58 F

* No access to separate Hot and Cold, enclosed pipes.

** Appears no Hot at all. = No Mixing Valve Page: ____ of _3__ andrewp

Mop Sink No

Sink Yes

Sink Above Deck

Mop Sink No

Sink Yes

Shower Controls

Sink ?

Sink Yes

Sink No

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Above Deck

Sink Above Deck

Sink Yes

Sink Yes

Sink Yes

Sink Above Deck

Sink Yes

Sink Yes

Utility Sink No

Sink No

Utility Sink No

Sink Yes

Shower Controls

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Above Deck

Sink Yes

Sink Above Deck

Sink Above Deck

Sink Above DeckA240A H: Not Working, C: 72 F ****

B248 H: 134 F, C: 74 F ****

A240B H: Not Working, C: 73 F ****

B253 H: 138 F, C: 85 F ****

B250 M: 106 F, H: 133 F, C: 69 F

B257 M: ?, H: 137 F, C: 74 F ****

B255 M: ?, H: 140 F, C: 78 F ****

B262H M: 101 F, H: 122 F, C: 59 F

B262 M: 88 F, H: 123 F, C: 59 F

Exam Room

Infusion Clinic

Exam Room

Exam Room

B262J M: 83 F, H: 125 F, C: 61 F

H: 128 F, C: Not Working

A200A H: 98F, C: 61 F

H: 139 F, C: 65 F

Lab Room

Patient Bathroom

A200D M: 102 F, H: 102 F, C: 69 F

H: 97 F, C: 61 F

C209 M: 105 F, H: 105 F, C: No Cold Supply

A200E M: 106 F, H: 129 F, C: 66 F

Restroom

Staff Restroom

Microbiology

C208H M: 107 F, H: 128 F, C: 73 F

C211 M: 75 F, H: 75 F, C: 72 F

C208J M: 129 F, H: 129 F, C: No Cold

C208G M: 104 F, H: 129 F, C: 68 F

Restroom

Xray Procedure 3

Xray Procedure 4

CT Room

C215 M: 135 F, H: 135 F, C: No Cold Supply

C208F M: 126 F, H: 126 F, C: NCS, very slow

C219 M: 105 F, H: 125 F, C: 70 F

C217 M: 104 F, H: 129 F, C: 68 F

Exam Room

Exam Room

Bathroom

Restroom

B260 H: 124 F, C: 60 F

C221 M: 116 F, H: 129 F, C: 70 F

E227 H: 115 F, C: 60 F ***

C222A M: 105 F, H: 129 F, C: 68 F

Staff Restroom

Exam Room

Women's Restroom

Housekeeping

Men's Locker

Breakroom

Office

E222 M: 91 F, H: 133 F, C: 62 F

H: 86 F, C: 60 F

A234 M: 110 F, H: 110 F, C: ? **

E202 H: No Access, C: 69 F

A202 H: 139 F, C: 58 F

A232 M: 101 F, H: 101 F, C: 76 F *

Domestic Water Fixture

Tracking Sheet

Building #: ___1______ Name: ___Hospital_______________ Floor #: ___2nd Floor___

Room #

Mixing

Valve NotesUsage

Fixture

Type

Housekeeping

Men's Restroom

Cardiology Office

Breakroom

Nursing ADPAC

Echo Procedure

Echo Procedure

* Not a good Cold reading.

** No access for Cold.

*** Pipes covered, no access.

**** Temp adjust lever.

***** Has Cold supply, but only mix to both

H and C on faucet.

= No Mixing Valve

Page: ____ of _2__ andrewp

Sink Above Deck

Sink Yes

Sink Yes

Shower Controls

Sink No

Sink Yes

Sink Yes

Utility Sink No

Mop Sink No

Hand Sink Yes

Utility Sink No

Utility Sink No

Utility Sink No

Spray Rinse No

Spray Rinse No

Sink Yes

Sink Yes

E229 M: 128 F, H: 128 F, C: ? *****

H: No Hot, C: 78 F

H: 123 F, C: 66 F

E231A M: 105 F, H: 120 F, C: 65 F *****

H: 124 F, C: 65 F

H: 129 F, C: 65 F

H: ?, C: 63 F (H no handle)

E231 M: 95 F, H: 121 F, C: 63 F

H: 124 F, C: 67 F

M: 113 F, H: 133 F, C: 65 F

E235 M: 101 F, H: 121 F, C: 69 F

E228A H: ?, C: 63 F (H no flow)

A237 H: 132 F, C: 67 F

A237A M: 111 F, H: 130 F, C: 71 F

Domestic Water Fixture

Tracking Sheet

Building #: ___1______ Name: ___Hospital_______________ Floor #: ___2nd Floor___

Room #

Mixing

Valve Notes

E219 M: 90 F, H: 131 F, C: 67 F

Fixture disassembled.

A238 H: Not Working, C: 63 F

A236

Usage

Fixture

Type

Office

Cardiac Stress Test

Women's Locker

Nuclear Medicine

Hot Lab

Tool Sterilization

Workroom

Sterilization Room

Workroom

Workroom

* Not a good Cold reading.

** No access for Cold.

*** Pipes covered, no access.

**** Temp adjust lever.

***** Has Cold supply, but only mix to both

H and C on faucet.

= No Mixing Valve

Page: ____ of _2__ andrewp

Sink Yes

Sink Yes

Sink No

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Above Deck

Mop Sink No

Sink No

Sink Yes

Sink Yes

Sink Yes

C308 M: 108 F, H: 120 F, C: 73 F *

C312 M: 112 F, H: 125 F, C: 76 F

Domestic Water Fixture

Tracking Sheet

Building #: ___1______ Name: ___Hospital_______________ Floor #: ___3rd Floor___

Room #

Mixing

Valve NotesUsage

Fixture

Type

Procedure Rm

Procedure Rm

Procedure Rm

Procedure Rm

Procedure Rm

Procedure Rm

Procedure Rm

Procedure Rm

C322 M: 105 F, H: 123 F, C: 62 F

C325 M: 106 F, H: 121 F, C: 72 F

C318 H: 132 F, C: 58 F

C320 M: 105 F, H: 130 F, C: 60 F

C315 M: 104 F, H: 126 F, C: 62 F

C313 M: 105 F, H: 126 F, C: 62 F

C321 M: 105 F, H: 127 F, C: 66 F

C319 M: 102 F, H: 124 F, C: 62 F

Neurology Rm

Procedure Rm

A301 H: 135 F, C: 63 F

A300 M: 108 F, H: 133 F, C: 63 F

C307 M: 78 F, H: 87 F, C: 68 F

C303 H: 102 F, C: 63 F

Men's Restroom

Housekeeping

Women's Restroom

Nutrition Clinic

C324 M: 104 F, H: 135 F, C: 65 F

C327 M&H: Hot Water Off, C: 66 F

Exam/Treatment Rm

Cardiology

* Difficult to get good reading. = No Mixing Valve Page: _1__ of _1__

Sink Yes

Shower Controls

Sink Yes

Shower Controls

Sink Yes

Sink Yes

Shower Controls

Sink Yes

Shower Controls

Sink Yes

Shower Controls

Sink Yes

Shower Controls

Sink Yes

Sink Yes

Shower Controls

Sink Above Deck

Sink Yes

Shower Controls

Sink Yes

Sink Yes

Shower Controls

Shower Controls

Sink Yes

Shower Controls

Sink Yes

Shower Controls

Sink Above Deck

Shower Controls

Sink No

Sink Above Deck

Shower Controls

Sink Above Deck

Sink Above Deck

Shower Controls H: 95 F, C: 64 F

Mid S Wing M: ?, H: 125 F, C: 60 F *

B449 M: ?, H: 138 F, C: 71 F *

B452 M: 102 F, H: 105 F, C: 60 F

B452A H: 86 F, C: 59 F

B453A H: 124 F, C: 63 F

H: 138 F, C: 62 F

Inaccessable

B453 M: ?, H: 132 F, C: 76 F *Office

Bathroom

B455A H: 91 F, C: 65 F

B454 M: 136 F, H: 136 F, C: 71 F *

B456A H: 105 F, C: 65 F

B455 M: 133 F, H: 133 F, C: 65 F *

Bathroom

CPAP Clinic

Patient Bathroom

Home O2

B447 M: 89 F, H: 97 F, C: 70 F

Inaccessable

C404A H: 119 F, C: 68 F

B448 M: 96 F, H: 97 F, C: 65 F

Bathroom

Restroom

PFT Clinic

N Wing - Elevators H: 126 F, C: 69 F

C404 M: 132 F, H: 132 F, C: 67 F

C406 M: 108 F, H: 130 F, C: 72 F

C406A H: 126 F, C: 73 F

Patient Room

Bathroom

Corridor

Patient Room

C411A H: 109 F, C: 65 F

Mid N Wing M: 131 F, H: 131 F, C: 75 F

C410A H: 132 F, C: 76 F

C411 M: 118 F, H: 119 F, C: 65 F

Bathroom

Patient Room

Bathroom

Corridor

C413A H: 127 F, C: 66 F

C410 M: 110 F, H: 112 F, C: 75 F

C412A H: 129 F, C: 74 F

C413 M: 105 F, H: 130 F, C: 63 F

Bathroom

Patient Room

Patient Room

Bathroom

Corridor

Patient Room

Bathroom

Patient Room

End N Wing M: 127 F, H: 127 F, C: 72 F

C412 M: 102 F, H: 123 F, C: 74 F

C415 M: 106 F, H: 133 F, C: 69 F

C415A H: 117 F, C: 70 F

C414 M: 102 F, H: 134 F, C: 61 F

C414A H: 116 F, C: 62 F

Domestic Water Fixture

Tracking Sheet

Building #: ___1______ Name: ___Hospital_______________ Floor #: ___4th Floor___

Room #

Mixing

Valve NotesUsage

Fixture

Type

Patient Room

Bathroom

CPAP Clinic A

Bathroom

Corridor

CPAP Clinic C

* Temperature adjust lever.

** Pinkish-orange colored water, first couple seconds.

= No Mixing Valve Page: ____ of _2__ andrewp

Sink Above Deck

Shower Controls

Sink Above Deck

Wash Sink No

Sink Yes

Tub Yes

Sink Yes

Sink Yes

Sink Yes

Mop Sink No

Sink Yes

Sink Yes

Shower Controls

Sink Yes

Sink No

Sink NoA401 Unoperable

H: 128 F, C: 70 F

A420 M: 100 F, H: 131 F, C: 66 F

A426A M: 102 F, H: 134 F, C: 72 F

A420A M: 105 F, H: 123 F, C: 66 F

A430 M: 106 F, H: 133 F, C: 63 F

A428 H: 131 F, C: 73 F

A400H H: 120 F, C: 68 F

H: 97 F, C: 75 F

A436 M: 108 F, H: 134 F, C: 64 F

A440 M: 109 F, H: 130 F, C: 64 F

A433 M: 72 F, H: 72, C: 68 F

Out of Order

Domestic Water Fixture

Tracking Sheet

Building #: ___1______ Name: ___Hospital_______________ Floor #: ___4th Floor___

Room #

Mixing

Valve Notes

N End of S Wing M: ?, H: 139 F, C: 68 F *

A431 H: 140 F, C: 78 F

B448 M: ?, H: 140 F, C: 75 F */**

B448A

Usage

Fixture

Type

Respiratory Therapy

Bathroom

Corridor

Soiled Utility

Hydrotherapy Rm

Staff Restroom

Staff Breakroom

Nutrition

Housekeeping

Restroom

Patient Bathroom

MSA Check-In

Staff Restroom

Office

* Temperature adjust lever.

** Pinkish-orange colored water, first couple seconds.

= No Mixing Valve Page: ____ of _2__ andrewp

Sink Yes

Sink Yes

Shower Controls

Sink Yes

Sink Yes

Sink Yes

Sink ?

Sink Yes

Sink Yes

Mop Sink No

Sink Yes

Sink Yes Bed Pan Washer No

Sink Above Deck

Bed Pan Washer No

Sink Yes

Sink Yes

Tub ?

Sink No

Sink Above Deck

Sink Yes

Shower Controls

Sink Above Deck

Sink Yes

Shower Controls

Sink Yes

Sink Yes

Shower Controls

Sink Yes

Shower Controls

Sink Yes

Shower Controls

Sink Yes

Shower Controls

Sink Yes

Patient Bedroom

Patient/Storage

Patient Room

N Wing (C5-C1) M: 111 F, H: 125 F, C: 77 F

C514 M: 110 F, H: 125 F, C: 67 F

Domestic Water Fixture

Tracking Sheet

Building #: ___1______ Name: ___Hospital_______________ Floor #: ___5th Floor___

Room #

Mixing

Valve NotesUsage

Fixture

Type

Corridor

Patient Room

Corridor

Publice Restroom

Locker Restroom

Soiled Utility

Breakroom

A501 M: 123 F, H: ? F, C: 62 F *

A500H M: 103 F, H: ? F, C: 61 F *

H: 100 F, C: 67 F

Mid N Wing M: 105 F, H: 105 F, C: 64 F *

A526 M: 107 F, H: 119 F, C: 61 F

A531 H: 130 F, C: 63 F

A503 Can't see for Mix, no water flow.

A500E M: 104 F, H: 125 F, C: 60 F

Nutrition Room

Housekeeping Closet

H: 137 F, C: 58 F

A530A M: 106 F, H: 127 F, C: 62 F

A530C M: 106 F, H: 118 F, C: 69 F

A530B M: 108 F, H: 119 F, C: 63 F

ICU Bed Room

ICU Bed Room

ICU Bed Room

A535 M: 105 F, H: ?, C: 61 F *

Out of Order.

H: 137 F, C: 57 F

A530 M: 104 F, H: 134 F, C: 58 FICU

Hydrotherapy

B543 M: 110 F, H: 131 F, C: 67 F

H: 119 F, C: 69 F

A537 H: 136 F, C: 61 F

Mid S Wing M: 102 F, H: 131 F, C: 67 F

Soiled Utility

Corridor

Patient Bedroom

H: 115 F, C: 68 F

B547 M: 110 F, H: 122 F, C: 64 F

End of S Wing M: 101 F, H: 132 F, C: 71 F

B545 M: 104 F, H: 117 F, C: 63 F

Corridor

Patient Room

Staff Restroom

M: 105 F, H: 132 F, C: 60 F

H: 109 F, C: 66 F

B546 M: 117 F, H: 128 F, C: 63 F

H: 104 F, C: 69 F

Patient Bedroom

Patient Bedroom

C517 M: 105 F, H: 120 F, C: 63 F

C518 M: 100 F, H: 122 F, C: 76 F

H: 114 F, C: 61 F

C513 M: 105 F, H: 126 F, C: 61 F

H: 132 F, C: 67 F

B544

* Had difficulty getting a good reading on Hot, could be long line.

= No Mixing Valve Page: ____ of _2__ andrewp

Shower Controls

Sink Yes

Shower Controls

Sink Yes

Shower Controls

Sink Yes

Sink Yes

Shower Controls

Sink Yes

Shower Controls

Sink Yes

Shower Controls

Sink Yes

Shower Controls

Usage

Fixture

Type

Restroom

Patient Room

Patient Room

Restroom

Patient Room

Patient Room

Patient Room

Patient Room

Patient Room

Domestic Water Fixture

Tracking Sheet

Building #: ___1______ Name: ___Hospital_______________ Floor #: ___5th Floor___

Room #

Mixing

Valve Notes

H: 122 F, C: 79 F

B541 M: 111 F, H: 129 F, C: 63 F

C517A H: 120 F, C: 73 F

C516 M: 104 F, H: 122 F, C: 67 F

B539 M: 105 F, H: 123 F, C: 63 F

H: 116 F, C: 63 F

B541A H: 126 F, C: 67 F

A530D M: ?, H: 75 F, C: 71 F *

B542 M: 88 F, H: 127 F, C: 63 F

H: 112 F, C: 70 F

B540 M: 92 F, H: 134 F, C: 62 F

H: 117 F, C: 64 F

C515 M: 100 F, H: 120 F, C: 64 F

H: 101 F, C: 66 F

* Had difficulty getting a good reading on Hot, could be long line.

= No Mixing Valve Page: ____ of _2__ andrewp

Mop Sink No

Sink Yes

Sink Yes

Sink Yes

Sink No

Wash Sink No

Sink Yes

Hand Wash No?

Sink Yes

Sink Yes

Sink No

Wash Sink No

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Above Deck

Sink Yes

Sink No

Sink No

Wash Sink No

Sink Yes

Sink Yes

Sink Yes

Sink Yes Auto Hand Wash Yes

Sink Yes

Sink Yes

Sink Yes

Wash Sink No

C624 M: 128 F, H: 131 F, C: 66 F

H: 133 F, C: 60 F

C620 M: 128 F, H: 125 F, C: 76 F

C622 M: 72 F, H: 110 F, C: 72 F *

C616 M: 120 F, H: 125 F, C: 74 F

Mid N Wing M: 105 F

C612 M: 121 F, H: 123 F, C: 73 F

C614 M: 130 F, H: 129 F, C: 74 F

Exam Room

Exam Room

Exam Room

Corridor

H: 140 F, C: 66 F

C610 M: 118 F, H: 120 F, C: 74 F

H: 138 F, C: 69 F

C608 H: 140 F, C: 67 FSoiled

Patient Check-In

A630 M: 93 F, H: 122 F, C: 67 F

C605 M: 114 F, H: 133 F, C: 73 F

A632 M: 106 F, H: 132 F, C: 66 F

A632A M: 98 F, H: 111 F, C: 69 F

Break Room

Restroom

Restroom

PAT Anesthesia Exam

B654 M: 66 F, H: ? Not getting H, C: 66 F

B650 M: 100 F, H: 112 F, C: 70 F

B655 M: 119 F, H: 123 F, C: 69 F

B656 M: 136 F, H: 135 F, C: 71 F

Procedure Room

Staff Restroom

Procedure Room

Procedure Room

B647 M: 113 F, H: 135 F, C: 65 F

B649 M: 129 F, H: 135 F, C: 71 F

B645 H: 139 F, C: 65 F

H: 138 F, C: 65 F

Soiled Room

Procedure Room

Procedure Room

B646 M: 68 F, H: Not On, C: 65 F

B648 M: 115 F, H: 119 F, C: 71 F

B643 M: 105 F, H: 130 F, C: 65 F

H: 139 F

Procedure Room

Procedure Room

PACU 2

Restroom

Soiled

Pre-Op

A638 H: 140 F, C: 62 F

H: 139 F, C: 59 F

A637 M: 108 F, H: 124 F, C: 72 F

A637C M: 125 F, H: 133 F, C: 75 F

A633 H: 138 F, C: 76 F

A636 M: 109 F, H: 134 F, C: 66 F

Domestic Water Fixture

Tracking Sheet

Building #: ___1______ Name: ___Hospital_______________ Floor #: ___6th Floor___

Room #

Mixing

Valve NotesUsage

Fixture

Type

Housekeeping

PACU 1

Exam Room

Exam Room

Exam Room

* Mixing Valve hooked up in reverse.

** Difficulty getting a good reading on Hot.

= No Mixing Valve Page: ____ of _2__ andrewp

Sink Yes

Wash Sink No

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink No

H: 136 F, C: 59 F

C617A M: 104 F, H: 107 F, C: 68 F **

C615 H: 130 F, C: 65 F

C619 M: 113 F, H: 130 F, C: 65 F

C617 M: 127 F, H: 127 F, C: 71 F **

Domestic Water Fixture

Tracking Sheet

Building #: ___1______ Name: ___Hospital_______________ Floor #: ___6th Floor___

Room #

Mixing

Valve Notes

C623 M: 120 F, H: 125 F, C: 67 F

C621 M: 115 F, H: 126 F, C: 65 F

C625 M: 116 F, H: 131 F, C: 63 F

Usage

Fixture

Type

Exam Room

Exam Room

Exam Room

Exam Room

Exam Room

Restroom

Restroom

* Mixing Valve hooked up in reverse.

** Difficulty getting a good reading on Hot.

= No Mixing Valve Page: ____ of _2__ andrewp

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Mop Sink No

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink No

Sink Yes

C722 H: 138 F, C: 59 F

C721 M: 105 F, H: 131 F, C: 71 F

B733A M: 107 F, H: 126 F, C: 59 F

B755 M: 83 F, H: 85 F, C: 70 F

Staff Breakroom

Staff Restroom

Office

Office

B737 M: 104 F, H: 113 F, C: 60 F

M: 104 F, H: 125 F, C: 60 F

C717 M: 106 F, H: 122 F, C: 67 F

A731 H: 137 F, C: 73 F

Men's Restroom

Staff Restroom

Office

Office

Staff Restroom

Housekeeping

C708 M: 105 F, H: 133 F, C: 76 F

C713 M: 96 F, H: 101 F, C: 66 F

M: 104 F, H: 130 F, C: 76 F

A706 M: 105 F, H: 134 F, C: 76 F

A702 M: 102 F, H: 126 F, C: 71 F

A704 M: 105 F, H: 127 F, C: 75 F

Domestic Water Fixture

Tracking Sheet

Building #: ___1______ Name: ___Hospital_______________ Floor #: ___7th Floor___

Room #

Mixing

Valve NotesUsage

Fixture

Type

Men's Restroom

Women's Restroom

= No Mixing Valve Page: _1__ of _1__

Sink Yes Drinking Fountain No

Shower No

Sink Yes

Shower No

Sink Yes

Shower No

Sink No

Mop Sink No

Sink No

Mop Sink No

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink No Drinking Fountain No

B818 M: 112 F, H: 138 F, C: 59 F

End of S Wing C: 59 F

Domestic Water Fixture

Tracking Sheet

Building #: ___1______ Name: ___Hospital_______________ Floor #: ___8th Floor___

Room #

Mixing

Valve NotesUsage

Fixture

Type

Breakroom

Corridor

Janitor Closet

Locker Room (M)

Locker Room (W)

Bio Med

H: 137 F, C: 61 F

B806 M: 103 F, H: 125 F, C: 63 F

B810 H: 137 F, C: Removed Handle

B808 M: 102 F, H: 132 F, C: 61 F

H: 140 F, C: 65 F

B800A H: 138 F, C: 64 F

H: 134 F, C: 64 F

B803 H: 140 F, C: 67 F

Wash Closet

M: 93 F *

M: 121 F *

A806 H: 123 F, C: 63 F

A809 M: 101 F *

Janitor Closet

Surgery Wash

Mid N Wing No Pressure.

M: 105 F, C: 77 F *

A805 H: 130 F, C: 64 FSurgery/Storage Rm

Corridor

* No good way to measure Hot. Cold is same.

Sink No9th Floor H: 134 F, C: 66 F *

Domestic Water Fixture

Tracking Sheet

Building #: ___1______ Name: ___Hospital_______________ Floor #: ___9th Floor___

Room #

Mixing

Valve NotesUsage

Fixture

Type

Mechanical

* Cold had reached as high as 90 F when running.

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink No

Sink Yes

Sink Above Deck

Wash Sink No

Sink No

Shower Controls

Sink No

Shower Controls

Sink Yes

Sink Yes

Sink Yes

Tub/Shower Controls

Sink No

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink No

Sink Yes

Womens Restroom

Exam/Treatment

156 M: 106 F, H: 126 F, C: 72 F

156A M: 106 F, H: 119 F, C: 71 F

Domestic Water Fixture

Tracking Sheet

Building #: ___12_____ Name: ___CLC_________________ Floor #: ___1st_Floor___

Room #

Mixing

Valve NotesUsage

Fixture

Type

Patient Room

Restroom

Patient Room

Patient Room

Restroom

Patient Room

Restroom

Patient Room

160A M: 110 F, H: 135 F, C: 60 F

155 M: 108 F, H: 125 F, C: 72 F

157 M: 104 F, H: 121 F, C: 72 F

160 M: 105 F, H: 125 F, C: 60 F

151 M: 100 F, H: 121 F, C: 63 F

151A M: 108 F, H: 126 F, C: 60 F

154A M: 112 F, H: 122 F, C: 71 F

154 M: 103 F, H: 120 F, C: 68 F

Patient Room

Restroom

163A M: 105 F, H: 123 F, C: 60 F

164 M: 91 F, H: 121 F, C: 58 F

150 M: 101 F, H: 132 F, C: 58 F

163 M: 111 F, H: 124 F, C: 60 F

Office

Breakroom

Restroom

Patient Room

119 M: 107 F, H: 116 F, C: 59 F

167 M: 100 F, H: 122 F, C: 63 F

164A M: 100 F, H: 121 F, C: 59 F

168 C: 60 F, H & M: ?, Cold Only *

Restroom

Staff Office

Hair Cut Closet

Staff Restroom

H: 117 F, C: 69 F

109D H: 125 F, C: 66 F

106 H: 125 F, C: 69 F

109C H: 127 F, C: 69 F

Janitorial

Female Locker/Rest.

Male Locker/Rest.

115B M: 104 F, H: 121 F, C: 60 F

115D M: 106 F, H: 123 F, C: 59 F

H: 120 F, C: 67 F

114 M: 107 F, H: 122 F, C: 59 FStaff Lounge

Breakroom/Office

Restroom

M: 86 F, H: 100 F (Point of Use), C: 61 F

117 M: 108 F, H: 129 F, C: 59 F

H: 107 F (M), C: 59 F

116 H: 64 F, C: 59 F **Community Center

Mens Restroom

M: 103 F, H: 132 F, C: 59 F

M: 106 F, H: 130 F, C: 59 F

122 H: 134 F, C: 60 F

M: 107 F, H: 127 F, C: 59 F

118 M: 103 F, H: 119 F, C: 61 F

* Difficult to tell, foot pedal controls.

** Point of use Hot Water Tank, not on unplugged.

*** Assuming built in mixer. = No Mixing Valve

Page: ____ of _3__ andrewp

Wash Sink No

Sink No

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Mop Sink No?

Mop Sink No

Shower Controls

Shower Controls

Shower Controls

Sink Yes

Tub ?

Tub ?

Wash Sink ?

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Tub/Shower Controls

Sink Yes

Sink Yes

Sink Yes

Tub/Shower Controls

Sink Yes

Sink Yes

Tub/Shower Controls

Sink Yes

Sink Yes

Usage

Fixture

Type

Soiled Utility

Patient Room

Restroom

Medication Room

Nourishment Kitchen

Housekeeping Closet

Housekeeping

Shower/Bath Room

Patient Room

Restroom

Domestic Water Fixture

Tracking Sheet

Building #: ___12_____ Name: ___CLC_________________ Floor #: ___1st_Floor___

Room #

Mixing

Valve Notes

126 M: 106 F, H: 130 F, C: 59 F

M: 107 F, H: 131 F, C: 59 F

124 C: 59 F, Cold Only

No Water, Foot Controls.

127 H: 111 F, C: 60 F

111 H: 130 F, C: 60 F

125 M: 103 F, H: 119 F, C: 60 F

147 M: 109 F, H: 123 F, C: 60 F

H: 122 F, C: 66 F

M: 109 F, H: 125 F, C: 64 F

146 H: 119 F, C: 66 F

H: 97 F, C: 65 F

H: 116 F, C: 92 F ***

139 M: 104 F, H: 124 F, C: 66 F

H: 104 F, C: 79 F ***

H: 107 F, C: 77 F ***

136A M: 108 F, H: 123 F, C: 68 F

135 M: 107 F, H: 119 F, C: 69 F

138A M: 115 F, H: 127 F, C: 65 F

137 M: 110 F, H: 121 F, C: 65 FPatient Room

Restroom

Patient Room

133A M: 101 F, H: 123 F, C: 63 F

H: 115 F, C: 63 F

134A M: 113 F, H: 116 F, C: 63 F

133 M: 108 F, H: 121 F, C: 69 F

Restroom

Patient Room

Bath Room

129A M: 105 F, H: 123 F, C: 65 F

H: 113 F, C: 66 F

132 M: 91 F, H: 122 F, C: 64 F

129 M: 96 F, H: 122 F, C: 63 F

Patient Room

Therapy Room

Bath Room

H: 115 F, C: 65 F

158 M: 110 F, H: 124 F, C: 67 F

162 M: 105 F, H: 125 F, C: 65 F

M: 106 F, H: 129 F, C: 66 F

Patient Room

Patient Room

M: 111 F, H: 125 F, C: 67 F

* Difficult to tell, foot pedal controls.

** Point of use Hot Water Tank, not on unplugged.

*** Assuming built in mixer. = No Mixing Valve

Page: ____ of _3__ andrewp

Sink Yes

Sink Yes

Tub/Shower Controls

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Sink Yes

Tub/Shower Controls H: 109 F, C: 71 F

144 Patient Room M: 111 F, H: 124 F, C: 73 F

142 Patient Room M: 111 F, H: 123 F, C: 77 F

142A Restroom M: 103 F, H: 123 F, C: 73 F

141 Patient Room M: 118 F, H: 121 F, C: 72 F

145 Patient Room M: 108 F, H: 124 F, C: 72 F

144A Restroom M: 106 F, H: 128 F, C: 71 F

138 Patient Room M: 101 F, H: 122 F, C: 71 F

140 Patient Room M: 105 F, H: 125 F, C: 73 F

140A Restroom M: 106 F, H: 125 F, C: 71 F

H: 121 F, C: 71 F

134 Patient Room M: 92 F, H: 125 F, C: 71 F

136 Patient Room M: 109 F, H: 125 F, C: 71 F

M: 110 F, H: 126 F, C: 70 F

Domestic Water Fixture

Tracking Sheet

Building #: ___12_____ Name: ___CLC_________________ Floor #: ___1st_Floor___

Room # Usage

Fixture

Type

Mixing

Valve Notes

153 Patient Room M: 105 F, H: 124 F, C: 70 F

* Difficult to tell, foot pedal controls.

** Point of use Hot Water Tank, not on unplugged.

*** Assuming built in mixer. = No Mixing Valve

Page: ____ of _3__ andrewp

VA Project Number 668-14-107 VA Project Number 668-14-107 VA Project Number 668-14-107 Spokane Legionella Water System Diagrams Spokane Legionella Water System Diagrams Spokane Legionella Water System Diagrams Plumbing Fixture, Dead Leg and Critical Control Point Inventory Plumbing Fixture, Dead Leg and Critical Control Point Inventory Plumbing Fixture, Dead Leg and Critical Control Point Inventory Building 1 - Main Hospital - Basement Building 1 - Main Hospital - Basement Building 1 - Main Hospital - Basement

Plumbing Fixture Schedule Data from Plumbing Fixture Frequency of

Use Survey Form Notes (related to Task 1 and Subtasks 1A, 1B and 1C) Dead Leg Log

Notes (related to Task 2 and Subtasks 2A, 2B and 2C) Critical Control Point

Hot Water (check box that applies)

Cold Water (check box that applies)

Area Order

Bldg. No. / Area No.

Building Number / Building Name Area Name

Room Numbe r

Room Name

Stack Number

Fixture Number

Fixture Type

Faucet Type

Add Mixing Valve

Used MORE than once each day

Used LESS than once each day

Used MORE than once each day

Used LESS than once each day

Dead Leg # [DL-Bldg-Floor-Area-#-Length (ft, H or C)-Insp Date

Location in Room Accessible (Y/N)

Length of Pipe

Type Inspection Date

Drawing Number

Length Location

Uninsulated Use of Critical Control Section to be determned

1-1 Building 1 - Main Hospital - Basement - Area 1 DL-01-B-01-01-36'H&C-11/24/15 C005 Above Ceiling Y 36' 5 ####### P-113

1/1 1/Main/1 A007 Kitchen 2 1-25 SS K Yes X X DL-01-B-01-02-36'H-11/24/15 C005D Above Ceiling Y 36' 5 ####### P-113 1/1 1/Main/1 A007 Kitchen 2 1-24 SS K Yes X X DL-01-B-01-03-57'H&C-11/24/15 C005 Above Ceiling Y 57' 1 ####### P-113 1/1 1/Main/1 A010 Housekeeping 1 1-23 SS K Yes X X DL-01-B-01-04-75'H&C-11/24/15 Near Ceiling Y 75' 5 ####### P-113 1/1 1/Main/1 CB-C1 Hall 1 1-22 DF X DL-01-B-01-05-37'H&C-11/24/15 ####### Could not find on drawing 1/1 1/Main/1 C002 Dishwashing 4 1-18 SS K Yes X X DL-01-B-01-06-29'C-02/05/16 C005 Above Ceiling Y 29' 3 2/5/2016 P-113 1/1 1/Main/1 C002 Dishwashing 4 1-19 SS K Yes X X DL-01-B-01-07-27'H&C-02/05/16 A007 Above Ceiling Y 27' 5 2/5/2016 P-113 1/1 1/Main/1 C002 Dishwashing 4 1-20 SS K Yes X X DL-01-B-01-08-25'H&C-02/05/16 Above Ceiling Y 25' 1 2/5/2016 P-113 1/1 1/Main/1 C002 Dishwashing 4 1-21 HB X DL-01-B-01-09-29'HWR-02/05/16 C002 Above Ceiling Y 29' 1 2/5/2016 P-113 1/1 1/Main/1 C003A Mens 23 1-4 LAV WB X X Wall Mounted Ball Valve for sanitizer mixing DL-01-B-01-10-30'H&C-02/05/16 C002 Above Ceiling Y 30' 5 2/5/2016 P-113 1/1 1/Main/1 C003A Mens 23 1-5 LAV WB X X DL-01-B-01-15-24'H&C-03/30/16 A007 Above Ceiling Y 24' 1 3/30/2016 P-113 1/1 1/Main/1 C003A Mens 23 1-6 LAV K X X 1/1 1/Main/1 C003A Mens 23 1-7 LAV K X X 1/1 1/Main/1 C003A Mens 22 1-8 UR X 1/1 1/Main/1 C003A Mens 22 1-9 UR X 1/1 1/Main/1 C003A Mens 22 1-10 WC X 1/1 1/Main/1 C003A Mens 22 1-11 WC X 1/1 1/Main/1 C003A Mens 22 1-12 WC X 1/1 1/Main/1 C003A Mens 22 1-13 SH K Yes 1/1 1/Main/1 C003A Mens 22 1-14 SH K Yes Inoperable, repair required 1/1 1/Main/1 C003A Mens 22 1-15 SH K Yes 1/1 1/Main/1 C004A Womens 7 1-1 LAV WB X X 1/1 1/Main/1 C004A Womens 7 1-2 LAV K X X 1/1 1/Main/1 C004A Womens 7 1-3 WC X 1/1 1/Main/1 D008C Library 25 1-16 LAV WB X X 1/1 1/Main/1 D008G Maintenance 25 1-17 SS K X X Integral Eyewash

1L ICE MACH.

1M RINSE STA.

1N DISHWASH

1P RINSE STA.

1Q SPRAY NOZZ.

1/1 1/MAIN/1 OUTSIDE 4 1-26 HB

1/1 1/MAIN/1 D008A 23 1-27 HB

1-2 Building 1 - Main Hospital - Basement - Area 2

DL-01-B-02-01-36'C-11/24/15 B010 Above Ceiling Y 36' 3 ####### P-114 1/2 1/Main/2 A002 Breakroom 28 1-27 LAV WB X X DL-01-B-02-02-12'C-11/24/15 Y 12' ####### P-114 Looks like this is just a cut off copper pipe and bibb 1/2 1/Main/2 A006A RR 46 1-28 LAV WB X X DL-01-B-02-03-30'C-11/24/15 A007 Above Ceiling Y 30' 1 ####### P-114 1/2 1/Main/2 A006A RR 46 1-29 WC X DL-01-B-02-04-15'C-11/24/15 Above Ceiling Y 15' 3 ####### P-114 1/2 1/Main/2 A007E Kitchen 28 1-26 HB Yes X +72"AFF DL-01-B-02-05-10'C-02/05/16 1/2 1/Main/2 B003 Maintenance 42 1-31 SS K Yes X X DL-01-B-02-06-60'C-02/05/16 B012 Above Ceiling Y 60' 5 2/5/2016 P-114 1/2 1/Main/2 B003 Maintenance 42 1-32 HB K X X +60"AFF DL-01-B-02-07-25'H&C-02/05/16 B014 Above Ceiling Y 25' 1 2/5/2016 P-114 1/2 1/Main/2 B003 Maintenance 42 1-33 HB K X Steamwand DL-01-B-02-08-13'H&C-02/05/16 Above Ceiling Y 13' 4 2/5/2016 P-114 1/2 1/Main/2 B007 IT/Data Services 39 1-34 LAV K X X DL-01-B-02-09-20'H-02/05/16 Above Ceiling Y 20' 4 2/5/2016 P-114 1/2 1/Main/2 B011 Shower 38 1-37 SH K X X 1/2 1/Main/2 B016 Pathology 37 1-35 SS K Yes X X 1/2 1/Main/2 B018 Pathology 38 1-36 LAV FP X X 1/2 1/Main/2 CB-A1 Hall 43 1-30 DF X 1/2 1/Main/2 B010 Exterior 33 1-43 HB X 2/10/2016

1-3 Building 1 - Main Hospital - Basement - Area 3 DL-01-B-03-01-54'C-11/24/15 A007 Above Ceiling N 54' 5 ####### P-115

1/3 1/Main/3 A007 Kitchen 2 1-38 LAV WB Yes X X DL-01-B-03-02-27'C-11/24/15 Y 27' ####### P-115 Perhaps hot into A007A 1/3 1/Main/3 A007 Kitchen 2 1-39 DF X Integral fill station DL-01-B-03-03-98'C-03/21/16 Unfinished Mech Rm at Ceiling Y 98' 3 3/21/2016 P-115

A007 Kitchen 1-40 SS K Yes X X A007 Kitchen 1-41 SS K Yes X X A007A Storage 1-42 SS K Yes X X A007 Exterior 50 1-43 HB - X Adjacent to elevator tower – East Side A007 Exterior 1-44 HB - Adjacent to elevator tower – West Side A007 Exterior 1-45 HB - East Façade adjacent to mech. louvers

1A COFFEE STA.

1B SPRAY NOZZ.

1C ST. COOKER

1D ST. COOKER

1E ST. POT

1F HOLD STA.

1G ST. OVEN

1H ST. OVEN

1J ST. OVEN

1K PREP. STA.

1/3 1/Main/3 Exterior 1-46

Dead Leg Summary

Faucet Type Abbreviations Plumbing Fixture Legend Type Description Quantity

FP - Foot Pedal K - Knob L - Lever S - Sensor WB - Wrist Blade Other - Specify in comments.

DF - Drinking Fountain DHWT - Domestic Hot Water Tank DW - Dishwasher EWC - Electric Water Cooler EWS - Eye Wash Station FCT - Faucet HB - Hose Bibb ICE - Ice Machine LAV - Lavatory LT - Laundry Tray NFWH - Non-Freeze Wall Hydrant SH - Shower SK - Sink SP TUB - Special Tub SS - Service Sink TUB - Bathtub TUB/SH - Bathtub/Shower UR - Urinal WC - Water Closet WM - Washing Machine

1 Pipe lengths greater than 10 feet terminating at a cap. 6

2 Pipe lengths greater than 10 feet terminating at a closed valve. 0

3 Pipe lengths greater than 10 feet terminating at a fitting. 4

Pipe lengths greater than 10 feet terminating at an infrequently used plumbing fixture. An infrequently used plumbing fixture is a fixture where the hot water line or cold water line is run less than once each day.

Pipe lengths greater than 25 feet terminating at a frequently used plumbing fixture. A frequently used plumbing fixture is a fixture where both the hot water line and cold water line are run at least once each day.

Spokane Legionella Water System Diagrams Spokane Legionella Water System Diagrams Spokane Legionella Water System Diagrams Plumbing Fixture, Dead Leg and Critical Control Point Inventory Plumbing Fixture, Dead Leg and Critical Control Point Inventory Plumbing Fixture, Dead Leg and Critical Control Point Inventory Building 1 - Main Hospital - Floor 1 (Areas 1, 2 and 3) Building 1 - Main Hospital - Floor 1 (Areas 1, 2 and 3) Building 1 - Main Hospital - Floor 1 (Areas 1, 2 and 3)

Plumbing Fixture Schedule Data from Plumbing Fixture Frequency of

Use Survey Form Notes (related to Task 1 and Subtasks 1A, 1B and 1C) Dead Leg Log

Notes (related to Task 2 and Subtasks 2A, 2B and 2C) Critical Control Point

Hot Water (check box that applies)

Cold Water (check box that applies)

Area Order

Bldg. No. / Area No.

Building Number / Building Name

Numb er

Room Name

Stack Number

Fixture Number

Fixture Type

Faucet Type

Add Mixing Valve

Used MORE than once each day

Used LESS than once each day

Used MORE than once each day

Used LESS than once each day

Dead Leg # [DL-Bldg-Floor-Area-#-Length(ft, H or C)-Insp Date] Location in Room Accessible

(Y/N) Length of Pipe Type

Inspectio n

Date

Drawing Number

Length Location

Uninsulated Use of Critical Control Section to be determned

13 1-4 Building 1 - Main Hospital - Floor 1 North - Area 1 DL-01-01-01-01-30'H&C-02/29/16 C113 Above Ceiling Y 30' 5 2/29/2016 P-116

DL-01-02-01-02-14'C-02/29/16 C109 Above Ceiling Y 14' 1 2/29/2016 P-116 1 /1 1/Main/1 D103 MENS (PUBLIC RESTROOM) 7 1-1 WC X DL-01-02-01-03-12'H-02/29/16 C109 Above Ceiling Y 12' 1 2/29/2016 P-116 1/1 1/Main/1 D103 MENS (PUBLIC RESTROOM) 7 1-2 UR X DL-01-02-01-04-11'C-02/29/16 D123 Above Ceiling Y 11' 1 2/29/2016 P-116 1/1 1/Main/1 D103 MENS (PUBLIC RESTROOM) 7 1-3 UR X 1/1 1/Main/1 D103 MENS (PUBLIC RESTROOM) 23 1-4 LAV S X X 1/1 1/Main/1 D103 MENS (PUBLIC RESTROOM) 23 1-5 LAV S X X 1/1 1/Main/1 D104 WOMENS (PUBLIC RESTROOM) 23 1-6 LAV S X X 1/1 1/Main/1 D104 WOMENS (PUBLIC RESTROOM) 23 1-7 LAV S X X 1/1 1/Main/1 D104 WOMENS (PUBLIC RESTROOM) 22 1-8 WC X 1/1 1/Main/1 D104 WOMENS (PUBLIC RESTROOM) 22 1-9 WC X 1/1 1/Main/1 D104 WOMENS (PUBLIC RESTROOM) 22 1-10 WC X 1/1 1/Main/1 C1-D6 CORRIDOR 22 1-11 DF X 1/1 1/Main/1 D124 GENERAL USE 22 1-12 SK S X X 1/1 1/Main/1 D123 ICU 22 1-13 SK S X X 1/1 1/Main/1 D123 ICU 22 1-14 SK S X X 1/1 1/Main/1 D119 LAB 22 1-15 SK WB Yes X X (survey form) SS SINK W/DRAINBOARD 1/1 1/Main/1 D119 LAB 25 1-16 SK - (survey form) GRINDERPUMP 1/1 1/Main/1 D117 EXAM 25 1-17 SK FP Yes X X 1/1 1/Main/1 D115 RR 4 1-18 WC X 1/1 1/Main/1 D115 RR 4 1-19 LAV OTHER X X (survey form) VANDALPROOF PUSHBUTTON SPIGOT W/TIMER

1/1 1/Main/1 C144 HOUSEKEEPING 4 1-20 SS K X X 1/1 1/Main/1 D114 EXAM 4 1-21 SK S X X 1/1 1/Main/1 D113 EXAM 1 1-22 SK S X X 1/1 1/Main/1 D111 EXAM 1 1-23 SK S X X 1/1 1/Main/1 D109 EXAM 2 1-24 SK S X X 1/1 1/Main/1 D107 EXAM 48 1-25 SK S X X 1/1 1/Main/1 D105 BREAKROOM 28 1-26 SK WB Yes X X 1/1 1/Main/1 D135 EXAM 28 1-27 SK S X X 1/1 1/Main/1 D134 EXAM 46 1-28 SK S X X 1/1 1/Main/1 D133 EXAM 46 1-29 SK S X X 1/1 1/Main/1 D132 EXAM 42 1-30 SK S X X 1/1 1/Main/1 D131 EXAM 42 1-31 SK S X X 1/1 1/Main/1 D129 EXAM 42 1-32 SK S X X 1/1 1/Main/1 D127 EXAM 42 1-33 SK S X X 1/1 1/Main/1 D128 EXAM 39 1-34 SK S X X 1/1 1/Main/1 D130 EXAM 37 1-35 SK S X X 1/1 1/Main/1 D106 EXAM 38 1-36 SK S X X 1/1 1/Main/1 D108 MENS 38 1-37 UR X 1/1 1/Main/1 D108 MENS 2 1-38 WC X 1/1 1/Main/1 D108 MENS 2 1-39 LAV S X X 1/1 1/Main/1 D110 WOMENS 2 1-40 WC X 1/1 1/Main/1 D110 WOMENS 46 1-41 LAV S X X 1/1 1/Main/1 D118 EXAM 46 1-42 SK FP Yes X X 1/1 1/Main/1 A141 VACANT 3 1-43 - - (survey form) CAPPED HW/CW 1/1 1/Main/1 C145C RR 7 1-44 LAV S X X 1/1 1/Main/1 C145C RR 7 1-45 WC X 1/1 1/Main/1 C145B RR 7 1-46 LAV S X X 1/1 1/Main/1 C145B RR 7 1-47 WC X 1/1 1/Main/1 C145E LAB 7 1-48 SK S X X 1/1 1/Main/1 C145E LAB 7 1-49 SK WB Yes X X (survey form) ADDITIONAL INLINE WALL MOUNTED FLUSHVALVE

1/1 1/Main/1 C112B OFFICE 1-50 SK WB Yes X X 1/1 1/Main/1 C112A OFFICE 1-51 SK L Yes X X 1/1 1/Main/1 C113 MENS (PUBLIC RESTROOM) 15 1-52 LAV S X X 1/1 1/Main/1 C113 MENS (PUBLIC RESTROOM) 15 1-53 LAV S X X 1/1 1/Main/1 C113 MENS (PUBLIC RESTROOM) 15 1-54 UR X 1/1 1/Main/1 C113 MENS (PUBLIC RESTROOM) 15 1-55 UR X 1/1 1/Main/1 C113 MENS (PUBLIC RESTROOM) 15 1-56 WC X 1/1 1/Main/1 C109 WOMENS (PUBLIC RESTROOM) 15 1-57 WC X 1/1 1/Main/1 C109 WOMENS (PUBLIC RESTROOM) 15 1-58 LAV S X X 1/1 1/Main/1 C109 WOMENS (PUBLIC RESTROOM) 15 1-59 LAV S X X 1/1 1/Main/1 EXTERIOR EXTERIOR 7 1-60 NFWH X (survey form) OUTSIDE ROOM C145E BACKFLOW 1/1 1/Main/1 EXTERIOR EXTERIOR 7 1-61 NFWH X (survey form) OUTSIDE ROOM C145E 1/1 1/Main/1 EXTERIOR EXTERIOR 4 1-62 NFWH X (survey form) OUTSIDE ROOM D123 1/1 1/Main/1 EXTERIOR EXTERIOR 1-63 NFWH X (survey form) OUTSIDE ROOM D103/ESPRESSO 1/1 1/Main/1 C106B LAB 7 1A ICE MA. (survey form) SEE EQUIPMENT SCHEDULE SHEET P-116 1/1 1/Main/1 LOBBY LOBBY 1B 3-COMP SK Yes SEE EQUIPMENT SCHEDULE SHEET P-116 1/1 1/Main/1 LOBBY LOBBY 1C SK Yes SEE EQUIPMENT SCHEDULE SHEET P-116 1/1 1/Main/1 LOBBY LOBBY 1D ICE SEE EQUIPMENT SCHEDULE SHEET P-116 1/1 1/Main/1 LOBBY LOBBY 1E COFFEE SEE EQUIPMENT SCHEDULE SHEET P-116 1/1 1/Main/1 LOBBY LOBBY 1F ESPRESSO SEE EQUIPMENT SCHEDULE SHEET P-116

14 1-5 Building 1 - Main Hospital - Floor 1 Center - Area 2 DL-01-01-02-01-28'H-02/29/16 B109A Above Ceiling Y 28' 5 2/29/2016 P-117

1/2 1/Main/2 A127D RR 31 1-1 LAV L Yes X X DL-01-01-02-02-27'C-02/29/16 B109A Above Ceiling Y 27' 5 2/29/2016 P-117 1/2 1/Main/2 A127D RR 31 1-2 WC X 1/2 1/Main/2 B117 HALL 31 1-3 LAV WB Yes X X 1/2 1/Main/2 B119 RR 31 1-4 LAV L Yes X X 1/2 1/Main/2 B119 RR 31 1-5 WC X 1/2 1/Main/2 B119 RR 31 1-6 WC X 1/2 1/Main/2 C1-B1 CORRIDOR 1-7 DF X 1/2 1/Main/2 B102 WOMENS 35 1-8 LAV S X X (survey form) GANGSTYLE FIBERGLASS SINK 1/2 1/Main/2 B102 WOMENS 35 1-9 WC X 1/2 1/Main/2 B103 WOMENS 35 1-10 WC X 1/2 1/Main/2 B106 MENS 35 1-11 LAV S X X (survey form) GANGSTYLE FIBERGLASS SINK 1/2 1/Main/2 B106 MENS 35 1-12 WC X 1/2 1/Main/2 B106 MENS 35 1-13 UR X 1/2 1/Main/2 B106 MENS 35 1-14 UR X 1/2 1/Main/2 B109A KITCHEN 1-15 SK WB, EW Yes X X 1/2 1/Main/2 B109A KITCHEN 1-16 HB K Yes X (survey form) WALL MOUNTED BALL VALVE FOR SANITIZER MIXING

1/2 1/Main/2 B107 SERVING 1G COFFEE (survey form) SEE EQUIPMENT SHEET P-118 1/2 1/Main/2 B107 SERVING 1H COFFEE SEE EQUIPMENT SCHEDULE SHEET P-118 1/2 1/Main/2 B107 SERVING 1J ICE TEA SEE EQUIPMENT SCHEDULE SHEET P-118 1/2 1/Main/2 B107 SERVING 1K FOUNTAIN SEE EQUIPMENT SCHEDULE SHEET P-118 1/2 1/Main/2 B107 SERVING 1L ST. TRAY SEE EQUIPMENT SCHEDULE SHEET P-118 1/2 1/Main/2 B107A KITCHEN 1M RINSE STA. Yes SEE EQUIPMENT SCHEDULE SHEET P-118 1/2 1/Main/2 B107A KITCHEN 1N DISHWASHER SEE EQUIPMENT SCHEDULE SHEET P-118 1/2 1/Main/2 B109A KITCHEN 1P ST. OVEN SEE EQUIPMENT SCHEDULE SHEET P-118 1/2 1/Main/2 B109A KITCHEN 1Q ST. OVEN SEE EQUIPMENT SCHEDULE SHEET P-118 1/2 1/Main/2 B109A KITCHEN 1R ICE MA. SEE EQUIPMENT SCHEDULE SHEET P-118 1/2 1/Main/2 B109A KITCHEN 1S RINSE STA. Yes SEE EQUIPMENT SCHEDULE SHEET P-118 1/2 1/Main/2 B109A KITCHEN 1T RINSE STA. Yes SEE EQUIPMENT SCHEDULE SHEET P-118 1/2 1/Main/2 B109A KITCHEN 1U VEG. PREP SEE EQUIPMENT SCHEDULE SHEET P-118 1/2 1/Main/2 B109A KITCHEN 1V VEG. PREP SEE EQUIPMENT SCHEDULE SHEET P-118

15 1-6 Building 1 - Main Hospital - Floor 1 South - Area 3

1/3 1/Main/3 C1-E1 LOBBY 1-1 DF X 1/3 1/Main/3 A102F CHEMO LAB 1-2 SK S X X 1/3 1/Main/3 A102E CHEMO LAB 1-3 EW,SH X X (survey form) EMERGENCY USE ONLY 1/3 1/Main/3 A102E CHEMO LAB 1-4 SS K Yes X X 1/3 1/Main/3 E107 WORKROOM 1-5 SK WB X X 1/3 1/Main/3 E138 HOUSEKEEPING 1-6 SS K X X 1/3 1/Main/3 E110 RR 1-7 WC X 1/3 1/Main/3 E110 RR 35 1-8 LAV S X X 1/3 1/Main/3 E119 LAB 35 1-9 SP TUB FP Yes X X (survey form) LARGE SS UTILITY 1/3 1/Main/3 E119 LAB 35 1-10 SK S X X 1/3 1/Main/3 E117 BREAKROOM 35 1-11 LAV WB X X 1/3 1/Main/3 E139 RR 35 1-12 WC X 1/3 1/Main/3 E139 RR 35 1-13 LAV S X X 1/3 1/Main/3 E140 BREAKROOM 35 1-14 SK WB Yes X X 1/3 1/Main/3 E135 EXAM 1-15 SK S X X 1/3 1/Main/3 E133 EXAM 1-16 SK S X X 1/3 1/Main/3 E129 RR 1-17 WC X 1/3 1/Main/3 E129 RR 1-18 LAV S X X 1/3 1/Main/3 E121 WORKROOM 1-19 SS WB Yes X X 1/3 1/Main/3 E121 WORKROOM 1-20 SK S X X 1/3 1/Main/3 E136 EXAM 1-21 SK S X X 1/3 1/Main/3 E134 EXAM 1-22 SK S X X 1/3 1/Main/3 E130 EXAM 1-23 SK S X X 1/3 1/Main/3 E130 EXAM 1-24 SK S X X 1/3 1/Main/3 E128 EXAM 1-25 SK S X X 1/3 1/Main/3 E126 EXAM 1-26 SP TUB FP Yes X X (survey form) LARGE SS UTILITY 1/3 1/Main/3 E126 EXAM 1-27 SK S X X 1/3 1/Main/3 E122 EXAM 1-28 SK S X X 1/3 1/Main/3 E120 EXAM 1-29 SK S X X 1/3 1/Main/3 E118 EXAM 1-30 SK NEED SURVEY INFO 1/3 1/Main/3 E113 HOUSEKEEPING 1-6 SS K Yes X X

Dead Leg Summary

Faucet Type Abbreviations Plumbing Fixture Legend Type Description Quantity

FP Foot Pedal K Knob L Lever S Sensor WB Wrist Blade Other Specify in comments.

DF - Drinking Fountain DHWT - Domestic Hot Water Tank DW - Dishwasher EWC - Electric Water Cooler EWS - Eye Wash Station FCT - Faucet HB - Hose Bibb ICE - Ice Machine LAV - Lavatory LT - Laundry Tray NFWH - Non-Freeze Wall Hydrant SH - Shower SK - Sink SP TUB - Special Tub SS - Service Sink TUB - Bathtub TUB/SH - Bathtub/Shower UR - Urinal WC - Water Closet WM - Washing Machine

1 Pipe lengths greater than 10 feet terminating at a cap. 3

2 Pipe lengths greater than 10 feet terminating at a closed valve. 0

3 Pipe lengths greater than 10 feet terminating at a fitting. 0

Pipe lengths greater than 10 feet terminating at an infrequently used plumbing fixture. An infrequently used plumbing fixture is a fixture where the hot water line or cold water line is run less than once each day.

Pipe lengths greater than 25 feet terminating at a frequently used plumbing fixture. A frequently used plumbing fixture is a fixture where both the hot water line and cold water line are run at least once each day.

Spokane Legionella Water System Diagrams Spokane Legionella Water System Diagrams Spokane Legionella Water System Diagrams Plumbing Fixture, Dead Leg and Critical Control Point Inventory Plumbing Fixture, Dead Leg and Critical Control Point Inventory Plumbing Fixture, Dead Leg and Critical Control Point Inventory Building 1 - Main Hospital - Floor 2 (Areas 1 and 2) Building 1 - Main Hospital - Floor 2 (Areas 1 and 2) Building 1 - Main Hospital - Floor 2 (Areas 1 and 2)

Plumbing Fixture Schedule Data from Plumbing Fixture Frequency of

Use Survey Form Notes (related to Task 1 and Subtasks 1A, 1B and 1C) Dead Leg Log

Notes (related to Task 2 and Subtasks 2A, 2B and 2C) Critical Control Point

Hot Water (check box that applies)

Cold Water (check box that applies)

Area Order

Bldg. No. / Area No.

Building Number / r

Room Name

Stack Number

Fixture Numbe r

Fixture Type

Faucet Type

Add Mixing Valve

Used MORE than once each day

Used LESS than once each day

Used MORE than once each day

Used LESS than once each day

Dead Leg # [DL-Bldg-Floor-Area-#-Length (ft, H or C)-Insp Date

Location in Room Accessible (Y/N)

Length of Pipe

Type Inspection Date

Drawing Number

Length Location

Uninsulated Use of Critical Control Section to be determned

16 1-7 Building 1 - Main Hospital - Floor 2 North - Area 1 DL-01-02-01-01-25'H&C-02/05/16 C221 Above Ceiling Y 25' 4 2/5/2016 P-119

1/MAIN/1 C208H PROCEDURE 20 1-1 SK WB X X DL-01-02-01-02-20'H-02/05/16 C206 Above Ceiling Y 20' 1 2/5/2016 P-119 1/MAIN/1 C208G PROCEDURE 20 1-2 SK WB X X DL-01-02-01-03-34'H&C-02/05/16 C208H/G Above Ceiling Y 34' 5 2/5/2016 P-119

1/MAIN/1 C208J RR 20 1-3 LAV S X X

1/MAIN/1 C208J RR 20 1-4 WC X

1/MAIN/1 C208F RR 20 1-5 LAV S X X

1/MAIN/1 C208F RR 20 1-6 WC X

1/MAIN/1 C208D XRAY 20 1-7 SK WB X X

1/MAIN/1 C222A STORAGE 22 1-8 SK WB X X

1/MAIN/1 C221 CONSULT 22 1-9 SK WB X X

1/MAIN/1 C219 CONSULT 22 1-10 SK WB X X

1/MAIN/1 C217 CONSULT 22 1-11 SK WB X X

1/MAIN/1 C215 RR 20 1-12 LAV S X X

1/MAIN/1 C215 RR 20 1-13 WC X

1/MAIN/1 C211 CT SCAN 20 1-14 SK WB X X

1/MAIN/1 C209 RR 22 1-15 WC X

1/MAIN/1 C209 RR 1-16 LAV S X X

1/MAIN/1 C207A VACANT 1-17 SK L X X

1/MAIN/1 C2-C1 CORRIDOR 1-18 DF X

17 1-8 Building 1 - Main Hospital - Floor 2 South - Area 2 DL-01-02-02-01-35'C-02/05/16 A200D Above Ceiling Y 35' 3 2/5/2016 P-120

1/MAIN/2 A232 MENS PUBLIC RESTROOMS 27 1-1 LAV S X X DL-01-02-02-02-30'C-02/05/16 A200A Above Ceiling Y 30' 5 2/5/2016 P-120 1/MAIN/2 A232 MENS PUBLIC RESTROOMS 27 1-2 UR X DL-01-02-02-03-13'H&HWR-02/05/16 A200A Above Ceiling Y 13' 1 2/5/2016 P-120 1/MAIN/2 A232 MENS PUBLIC RESTROOMS 27 1-3 WC X DL-01-02-02-05-11'H&C-02/05/16 A237 Above Ceiling Y 11' 1 2/5/2016 P-120 1/MAIN/2 A234 WOMENS PUBLIC RESTROOMS 27 1-4 LAV S X X DL-01-02-02-06-19'C-02/05/16 A236 Above Ceiling Y 19' 1 2/5/2016 P-120 1/MAIN/2 A234 WOMENS PUBLIC RESTROOMS 27 1-5 WC X DL-01-02-02-07-42'C-02/05/16 A238 Above Ceiling Y 42' 5 2/5/2016 P-120 1/MAIN/2 A234 WOMENS PUBLIC RESTROOMS 27 1-6 WC X DL-01-02-02-08-25'H-02/05/16 B247 Above Ceiling Y 25' 1 2/5/2016 P-120 1/MAIN/2 A236 LAB 27 1-7 SK S X X DL-01-02-02-09-23'C-02/05/16 B247 Above Ceiling Y 23' 1 2/5/2016 P-120 1/MAIN/2 A238 LAB 30 1-8 SK S X X (survey form) EXTERNAL MIXER DL-01-02-02-10-13'C-02/05/16 B250 Above Ceiling Y 13' 1 2/5/2016 P-120 1/MAIN/2 A240A EXAM 30 1-9 SK S X X (survey form) EXTERNAL MIXER DL-01-02-02-11-54'H&C-02/05/16 B250 Above Ceiling Y 54' 5 2/5/2016 P-120 1/MAIN/2 A240B EXAM 30 1-10 SK S X X (survey form) EXTERNAL MIXER DL-01-02-02-12-28'H&C-02/05/16 B255 Above Ceiling Y 28' 5 2/5/2016 P-120 1/MAIN/2 B248 IT/DATA 32 1-11 SK S X X (survey form) EXTERNAL MIXER DL-01-02-02-13-46'HWR-02/05/16 B257 Above Ceiling Y 46' 1 2/5/2016 P-120 1/MAIN/2 B250 BREAKROOM 30 1-12 SK L X X (survey form) HAND SPRAYER DL-01-02-02-14-21'H&C-02/05/16 A200 Above Ceiling Y 21' 1 2/5/2016 P-120 1/MAIN/2 B260 RR 35 1-13 LAV S Yes X X (survey form) EXTERNAL MIXER

1/MAIN/2 B260 RR 35 1-14 WC X

1/MAIN/2 B256 LAB 39 1-15 SK L X X

1/MAIN/2 B262H LAB 39 1-16 SK FP X X

1/MAIN/2 B262J RR 39 1-17 LAV S X X

1/MAIN/2 B262J RR 39 1-18 SHOWER K X X

1/MAIN/2 B262J RR 39 1-19 WC X

1/MAIN/2 B257 EXAM 30 1-20 SK S X X (survey form) EXTERNAL MIXER 1/MAIN/2 B255 EXAM 30 1-21 SK S X X (survey form) EXTERNAL MIXER 1/MAIN/2 B253 EXAM 30 1-22 SK S X X (survey form) EXTERNAL MIXER 1/MAIN/2 A237 NUCLEAR MEDICINE 48 1-23 SK FP Yes X X 1/MAIN/2 A202 HOUSEKEEPING 1-24 SS K Yes X X

1/MAIN/2 A200E RR 1 1-25 WC X

1/MAIN/2 A200E RR 1 1-26 LAV WB X X

1/MAIN/2 A200E RR 1 1-27 UR X

1/MAIN/2 A200D LAB 2 1-28 SK FP Yes X X

1/MAIN/2 A200D LAB 49 1-29 SK K X X

1/MAIN/2 A200A LAB 50 1-30 SK K Yes X X 1/MAIN/2 A200A LAB 1-31 SS K Yes X X (survey form) EXPOSED COPPER PIPING 1/MAIN/2 A200A LAB 50 1-32 EW X X (survey form) INTEGRAL OVHD SHWR

1/MAIN/2 A237A LAB 48 1-33 SK WB X X

1/MAIN/2 B250 BREAKROOM 30 1-34 ICE

Building 1 - Main Hospital - Floor 2 West - Area 3 1/MAIN/3 E202 HOUSEKEEPING SS K Yes X X

1/MAIN/3 E219 WOMENS LOCKER LAV K X X

1/MAIN/3 E219 WOMENS LOCKER SH K X X

1/MAIN/3 E235 TOOL STERILIZATION SS K X X

1/MAIN/3 E228A WORKROOM SS WB Yes X X 1/MAIN/3 E228A WORKROOM SS K Yes X X

1/MAIN/3 E231 STERILIZATION ROOM SK WB X X

1/MAIN/3 E231 STERILIZATION ROOM SS WB Yes X X 1/MAIN/3 E231 STERILIZATION ROOM SS WB Yes X X 1/MAIN/3 E231 STERILIZATION ROOM SS WB Yes X X 1/MAIN/3 E231 STERILIZATION ROOM RINSE STA. Yes X X 1/MAIN/3 E231 STERILIZATION ROOM RINSE STA. Yes X X

1/MAIN/3 E229 WORKROOM SS WB X X

1/MAIN/3 E231A WORKROOM SS WB X X

1/MAIN/3 E222 MENS LOCKER LAV K X X

1/MAIN/3 E222 MENS LOCKER SH K X X

1/MAIN/3 E227 BREAKROOM SS WB X X

Dead Leg Summary

Faucet Type Abbreviations Plumbing Fixture Legend Type Description Quantity

FP - Foot Pedal K - Knob L - Lever S - Sensor WB - Wrist Blade Other - Specify in comments.

DF - Drinking Fountain DHWT - Domestic Hot Water Tank DW - Dishwasher EWC - Electric Water Cooler EWS - Eye Wash Station FCT - Faucet HB - Hose Bibb ICE - Ice Machine LAV - Lavatory LT - Laundry Tray NFWH - Non-Freeze Wall Hydrant SH - Shower SK - Sink SP TUB - Special Tub SS - Service Sink TUB - Bathtub TUB/SH - Bathtub/Shower UR - Urinal WC - Water Closet WM - Washing Machine

1 Pipe lengths greater than 10 feet terminating at a cap. 9

2 Pipe lengths greater than 10 feet terminating at a closed valve. 0

3 Pipe lengths greater than 10 feet terminating at a fitting. 1

Pipe lengths greater than 10 feet terminating at an infrequently used plumbing fixture. An infrequently used plumbing fixture is a fixture where the hot water line or cold water line is run less than once each day.

Pipe lengths greater than 25 feet terminating at a frequently used plumbing fixture. A frequently used plumbing fixture is a fixture where both the hot water line and cold water line are run at least once each day.

Spokane Legionella Water System Diagrams Spokane Legionella Water System Diagrams Spokane Legionella Water System Diagrams Plumbing Fixture, Dead Leg and Critical Control Point Inventory Plumbing Fixture, Dead Leg and Critical Control Point Inventory Plumbing Fixture, Dead Leg and Critical Control Point Inventory Building 1 - Main Hospital - Floor 3 (Areas 1 and 2) Building 1 - Main Hospital - Floor 3 (Areas 1 and 2) Building 1 - Main Hospital - Floor 3 (Areas 1 and 2)

Plumbing Fixture Schedule Data from Plumbing Fixture Frequency of

Use Survey Form Notes (related to Task 1 and Subtasks 1A, 1B and 1C) Dead Leg Log

Notes (related to Task 2 and Subtasks 2A, 2B and 2C) Critical Control Point

Hot Water (check box that applies)

Cold Water (check box that applies)

Area Order

Bldg. No. / Area No.

Building Number / r

Room Name

Stack Number

Fixture Number

Fixture Type

Faucet Type

Add Mixing Valve

Used MORE than once each day

Used LESS than once each day

Used MORE than once each day

Used LESS than once each day

Dead Leg # [DL-Bldg-Floor-Area-#-Length (ft, H or C)-Insp Date

Location in Room Accessible (Y/N)

Length of Pipe

Type Inspection Date

Drawing Number

Length Location

Uninsulated Use of Critical Control Section to be determned

18 1-9 Building 1 - Main Hospital - Floor 3 North - Area 1 DL-01-03-01-01-28'H&C-02/10/16 C325 Above Ceiling Y 28' 5 2/10/2016 P-121

1 1/MAIN/1 C308…