This document is a detailed specification bulletin for S&C Electric Company's Manual Vista® and Vista® Green Underground Distribution Switchgear, covering outdoor distribution systems rated from 15.5 kV through 38 kV. The switchgear features load-interrupter switches for switching 600- or 900-ampere main feeders, with microprocessor-controlled arc-spinners or vacuum fault interrupters for switching and protection. Key technical specifications include three-position switches with manual operation, visible gap confirmation, internal grounding, and arc resistance certification per IEC 62271-200.
The specification bulletin provides comprehensive technical details on switchgear styles (UnderCover, vault-mounted, pad-mounted), optional features (auxiliary contacts, potential indication, key interlocks), and installation configurations. Standard Vista switchgear uses sulfur hexafluoride (SF6) insulating gas, while the new Vista Green variant uses a dielectric gas mixture of CO2 and C4-FN. The document includes detailed dimensional drawings, rating tables, and a comprehensive catalog numbering system for configuring specific switchgear models with various ratings, ways, and optional features. The technical specifications are intended to provide electrical engineers and procurement professionals with complete information for specifying and ordering these underground distribution switchgear systems.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Questions and Answers - Transformers.pdf | ||
| Concept drawings Rev1.pdf | ||
| Solicitation - FA557525B0002.pdf | ||
| Attachment 1b Specifications (Esp)- Transformers Multi.PDF | ||
| Attachment 2 Photos.pdf | ||
| Attachment 6 QUUG 23-1017 CCE blank.xlsx | XLSX spreadsheet | |
| Attachment 1a Specifications (Eng)- Transformers Multi.PDF | ||
| Attachment 5 Schedule of Material Submittals.xlsx | XLSX spreadsheet | |
| Attachment 8 DataSheets compilation.pdf | ||
| Attachment 3 QUUG 23-1017 Concept drawings.pdf | ||
| Attachment 4 Record Drawings.pdf |
Show all 11
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
January 8, 2024 © S&C Electric Company 1996-2024, all rights reserved Specification Bulletin 681-31
Manual Vista® Underground Distribution Switchgear Vista® Green Underground Distribution Switchgear Outdoor Distribution (15.5 kV through 38 kV)
Conditions of Sale STANDARD: The seller’s standard conditions of sale set forth in Price Sheet 150 apply, except as modified under the “Special Warranty Provisions” section on “Special Warranty Provisions” on page 4.
SPECIAL TO THIS PRODUCT:
INCLUSIONS: Vista Underground Distribution Switchgear features load-interrupter switches for switching 600- or 900-ampere main feeders and microprocessor-controlled arc-spinners or vacuum fault interrupters for switching and protection of 600- or 900-ampere main feeders and 200-, 600-, or 900-ampere taps, laterals, and subloops.
These elbow-connected components are enclosed in a gas-insulated gas-tight (SF6) or hermetically sealed (CO2 mix) welded-steel tank, completely protected from the environ-ment. The switchgear is available with up to six ways (bus terminals, switches and/or fault interrupters) in ratings through 38 kV and 25 kA symmetrical. Standard Vista switchgear products ship with sulfur hexafluoride (SF6) insulating gas. The new optional Vista Green Underground Distribution Switchgear ships with a dielectric gas mixture of CO2 and C4-FN insulating gas instead of SF6. See pages 6 and 7 for details on how to build Vista and Vista Green switchgear catalog numbers.
The three-position (CLOSED-OPEN-GROUNDED) load-interrupter switches are manually operated and provide three-pole live switching of 600- or 900-ampere three-phase circuits. These switches also provide a visible gap when open and internal grounding for all three phases— without exposure to medium voltage or the need to manipulate elbows, arc-spinning contacts (15.5-kV, 12.5-kA symmetrical SF6 gas-insulated models only), or vacuum interrupters in series with manually operated three-position (CLOSED-OPEN-GROUNDED) disconnects (15.5-kV, 25-kA symmetrical, and all 29-kV and 38-kV models) for isolation and internal grounding of each phase. See Table 1 on page 8 for the available Vista and Vista Green switchgear ratings.
Fault interrupters provide three-pole load switching and fault interruption through 25 kA symmetrical or single-pole load switching and fault interruption through
12.5 kA symmetrical. (For other possible ratings, refer to the nearest S&C Sales Office). Fault interruption is initiated by a programmable overcurrent control. The total clearing time (from initiation of the fault to total clearing) can be as fast as 40 milliseconds. For single-pole fault interrupt-ers, the overcurrent control can also be programmed to provide three-pole fault interruption.
Large windows provide a clear view of the open gap, ground position, and ground bus, allowing the operator to easily confirm the positions of the load-interrupter switches and disconnects of the fault interrupters. Trip indicators, which are readily visible through the windows, are provided for the fault interrupters. Each unit of gear is furnished with a manual handle to charge the operating mechanisms and open, close, and ground the load-interrupter switches and fault interrupters. The operating mechanisms operate independently of the speed of the manual handle and are designed to prevent inadvertent operation from the Closed position directly to the Ground position, and vice versa.
Operating shafts are padlockable in any position and can also be padlocked to prevent operation to the Ground position.
Terminals are equipped with 200-ampere rated bushing wells (SF6 models only) or 600- or 900-ampere bushings (as specified). Bushing and bushing-well interfaces are in accordance with IEEE Standard 386 to accept all standard insulated connectors and inserts.
In addition, Vista Underground Distribution Switchgear has been certified as arc resistant per IEC 62271-200 for fault currents up to 12.5 kA symmetrical for 15 cycles (25 kA symmetrical for units rated 25 kA short circuit). Arc resis-tance is standard for the pad-mounted and UnderCover™ styles. For the vault-mounted style, catalog number suffix “-N” must be specified, in which case a flange will be welded to the pressure-relief device for connection of user-supplied piping to vent exhaust gases out of the vault area.
Specifications
2 S&C Specification Bulletin 681-31
Manual Vista® Underground Distribution Switchgear Vista® Green Underground Distribution Switchgear
When optional voltage indication is specified, all routine operating tasks—switching, voltage testing, and ground-ing—can be accomplished by a single person without cable handling or exposure to medium voltage. An optional feature that combines voltage indication with provisions for low-voltage phasing is also available. Cable testing for faults can be performed through the back of a user-supplied elbow or through a user-supplied feedthru insert eliminat-ing the need for difficult cable handling or parking stands.
Vista Overcurrent Control 2.0 Fault interruption is initiated by a programmable over-current control housed in a watertight enclosure. The control is programed using a personal computer connected to the control via a USB cable (Type A to Type A). The control receives both sensing and control inputs from current transformers. No batteries are needed for the Vista overcurrent control 2.0.
Current transformers provide power and input signals.
The control features a variety of time-current characteristic (TCC) curves—standard “E,” “K,” and “T” speed curves, Vista coordinating-speed tap and main curves, and relay curves per IEEE C37.112-2018.
Coordinating-speed tap curves are used for fault inter-rupters feeding subloop taps and are specificallydesigned to optimize coordination with load-side weak-link/backup current-limiting fuse combinations and source-side relays with low time-dial settings. The coordinating-speed main curves are used for fault interrupters on main feeders and have a longer minimum response time and a different shape to coordinate with tap-interrupter curves. Coordinating-speed curves have phase-overcurrent, ground-protection, negative-sequence fault, and sensitive-earth fault settings.
The coordinating-speed tap and main curves, as well as IEEE and IEC relay TCC curves, can be tailored to the application using a variety of TCC curve based and definite-time settings. Ground-protection, negative-sequence fault, and sensitive-earth fault settings are also available.
Vista Switchgear Styles:
Vista switchgear is considerably smaller than traditional air-insulated gear and is available in several styles so it can be installed exactly where needed. The standard mounting styles of switchgear are as follows:
UnderCover Style When the UnderCover Style is specified, the gear is provided with a stainless steel tank and submersible wiring.
Vault-Mounted Style Two versions of this style are available. The wet-vault mounted style is intended for vaults subject to periodic flooding and includes submersible wiring and electrical components. The dry-vault mounted style is intended for vaults not subject to periodic flooding and does not include submersible wiring and electrical components. A stainless steel tank suitable for mounting on the floor or wall of the vault is furnished with both wet- and dry-vault mounted styles.
Pad-Mounted Style When the pad-mounted style is specified, a mild-steel or, optionally, stainless steel enclosure and tank are provided.
Pad-mounted enclosures meet the requirements of ANSI C57.12.28 (enclosure integrity). The top of the pad-mounted enclosure is hinged on both sides for convenient access to the operating and termination compartments. The roof of the enclosure is sloped outward to ensure water flows away from the switchgear.
A removable panel provides access to the elbows and cables and is secured by the overlapping padlockable top. A resilient closed-cell gasket on the enclosure bottom flange protects the finish from being scratched during installation and isolates it from the alkalinity of a concrete founda-tion. Enclosures are protected from corrosion by S&C’s Ultradur® II Outdoor Finish.
S&C Specification Bulletin 681-31 3
Vista® Green Underground Distribution Switchgear
Application Notes:
Fault Interrupter Vista Underground Distribution Switchgear features either arc-spinning contacts (15.5-kV, 12.5-kA symmetrical SF6 gas-insulated models only) vacuum fault interrupters for three-pole load switching and fault interruption through 25 kA symmetrical, or single-pole load switching and fault interruption through 12.5 kA symmetrical.
Complete ratings for the fault interrupter, as applied in Vista switchgear, are shown in Table 1 on page 8.
In addition to the load-dropping ratings shown, the fault interrupter is capable of interrupting transformer magnetiz-ing currents associated with the applicable loads, as well as line-charging and cable-charging currents typical for distribution systems of these voltage ratings. The duty-cycle fault-closing rating shown for the fault interrupter defines the ability to close the interrupter the designated number of times into the Closed position or Grounded position against a three-phase fault as follows:
• Main Contacts. The fault-interrupter has the ability to close the designated number of times into a three-phase fault equal to rated value and interrupt the resulting short-circuit current. The fault interrupter remains operable and able to carry and interrupt its rated continuous current.
• Ground Contacts. The fault interrupter ground switch has the ability to close the designated number of times against a three-phase fault equal to the rated value with the ground switch remaining operable and able to carry its rated fault-closing current.
A Note on Single-Pole Switching In single-pole switching of ungrounded-primary three-phase transformers or banks (or single-phase transformers connected line to line), circuit connections or parameters may, in some cases, produce excessive overvoltages. In particular, for the following applications above 22 kV, single-pole switching by any means should be performed only under the conditions stated in italics:
• Switching unloaded or lightly loaded delta-connected or ungrounded-primary wye-wye-connected three-phase transformers or banks (or line-to-line connected single-phase transformers), rated 150 kVA or less three-phase, or 50 kVA or less single-phase—or of any kVA rating when combined with unloaded cables or lines—where maximum system operating voltage exceeds 22 kV (Single-pole switching should be performed only if each phase is carrying 5% load or more or if the transformer or bank is temporarily grounded at the primary neutral during switching.)
• Switching loaded or unloaded ungrounded-primary wye-delta connected three-phase transformers or banks—alone or combined with unloaded cables or lines—where maximum system operating voltage exceeds 22 kV (Single-pole switching should be performed only if each phase is carrying 5% load or more and if the lighting-load phase is always switched open first (or switched closed last) or if the trans-former or bank is temporarily grounded at the primary neutral during switching.)
4 S&C Specification Bulletin 681-31
Vista® Green Underground Distribution Switchgear
Load-Interrupter Switch Vista Underground Distribution Switchgear features load-interrupter switches for three-pole live switching of three-phase circuits.
Complete ratings for the load-interrupter switch, as applied in Vista switchgear, are shown in Table 1 on page
8. In addition to the load-dropping ratings shown, the switch is capable of interrupting transformer magnetiz-ing currents associated with the applicable loads as well as line-charging and cable-charging currents typical for distribution systems of these voltage ratings.
For applications involving load current with high harmonic content (such as rectifier load currents), refer to the nearest S&C Sales Office. The duty-cycle fault-closing rating shown for the switch defines the ability to close the switch into the Closed or Grounded position the desig-nated number of times against a three-phase fault equal to the rated value, with the switch remaining operable and able to carry and interrupt rated current.
EXCLUSIONS: Three-phase units listed in Table 2 on pages 9 through 14 do not include the switchgear style, optional features, or accessories listed in Tables 3, 4, and 5 on pages 15 through 21.
Special Warranty Provisions The standard warranty contained in the seller’s standard conditions of sale, as set forth in Price Sheets 150 and 181, applies only to manual Vista Underground Distribution Switchgear and its associated options. The Vista overcur-rent control 2.0 shall have the following warranty provisions:
the first and second paragraphs of Price Sheet 150 warranty are replaced with the following:
(1) General: The seller warrants to the immediate purchaser or end user for a period of 10 years from the date of shipment that the equipment delivered will be of the kind and quality specified in the contract description and will be free of defects of workmanship and material. Should any failure to conform to this warranty appear under proper and normal use within 10 years after the date of shipment, the seller agrees, upon prompt notification thereof and confirmation that the equipment has been stored, installed, operated, and maintained in accordance with recommendations of the seller and standard industry practice, to correct the nonconformity either by repairing any damaged or defective parts of the equipment or (at the seller’s option) by shipment of necessary replacement parts.
The seller’s warranty does not apply to any equipment that has been disassembled, repaired, or altered by anyone other than the seller. This limited warranty is granted only to the immediate purchaser or, if the equipment is purchased by a third party for installation in third-party equipment, the end user of the equipment.
The seller’s duty to perform under any warranty may be delayed, at the seller’s sole option, until the seller has been paid in full for all goods purchased by the immediate purchaser. No such delay shall extend the warranty period.
The seller further warrants to the immediate purchaser or end user that for a period of two years from the date of shipment the software will perform substantially in accordance with the then-current release of specifications if properly used in accor-dance with the procedures described in the seller’s instructions. The seller’s liability regarding any of the software is expressly limited to exercising its reason-able efforts in supplying or replacing any media found to be physically defective or in correcting defects in the software during the warranty period. The seller does not warrant the use of the software will be uninter-rupted or error-free.
S&C Specification Bulletin 681-31 5
Vista® Green Underground Distribution Switchgear
How to Order Complete these steps to identify the base catalog number, the appropriate options, and the product accessories needed for a complete order:
STEP 1. Obtain the catalog number of the desired switchgear unit from Table 2 on pages 9 through 14.
Catalog Number:
STEP 2. Specify the desired switchgear style from Table 3 on page 15 and add the appropriate suffix to the catalog number.
Suf fix:
STEP 3. For 12.5-kA rated models with one or more fault interrupters: Add a suffix designation to the catalog number indicating the desired number of three-pole and single-pole fault inter-rupters, selected from Table 4 on page 16.
Note: This step is not applicable to models rated 25 kA short circuit.
Suf fix:
STEP 4. Add suffix designations to the catalog number indicating the optional features desired, selected from Table 5 on pages 17 through 20. (Add as many suffixes as required.)
Suffixes:
Note: At this point, the catalog number for the Vista switchgear unit is complete. The next steps using Tables 6 and 7 are for product accessories and touch-up kit compo-nents that would be separate line items on the order. Contact S&C for additional available options.
STEP 5. Obtain catalog numbers for any accessories from Table 6 on page 21 and apply as a separate line item on the order.
Catalog Number:
6 S&C Specification Bulletin 681-31
Vista® Green Underground Distribution Switchgear
– P 1 4 C 1 2
Type and Interrupting/ Short-Circuit Level
Vista Model Number
Max Voltage (kV) Any Number of Suffixes
85- Manual Vista switchgear 25 kA 93- Manual Vista switchgear 12.5 kA
2- 15.5 kV 3- 29 kV 4- 38 kV
The catalog number created above represents manual Vista switchgear, 25 kA, with a total of three ways that includes one load-interrupter switch and two fault-interrupter switches for a 29-kV application. The unit will also be pad-mount style with a stainless steel outer enclosure and an olive-green finish, for the auxiliary contacts on the load-interrupter way with wires routed to terminal blocks mounted in an enclosure for customer connection. (The terminal block enclosure is typically mounted on the side of the Vista switchgear tank near the overcurrent relay enclosure.)
No. of ways
No. of load-interrupter switches
No. of fault-interrupter switches
Anatomy of a Vista Switchgear Catalog Number
STEP 6. Include touch-up kit components from Table 7 on page 21.
Catalog Number: –
Example: The catalog number for an UnderCover Style Vista switchgear unit, Model 422, with all single-pole fault inter-rupters, rated 12.5 kA short circuit and 15.5 kV maximum at 60 Hertz, and equipped with voltage indication with provisions for low-voltage phasing is:
9 3 4 2 2 4 R 1 – U T 0 L 2 Note: To select and configure 40-kA Vista loadbreak switches or remote supervisory, source-transfer, or solid dielectric products, see the appropriate specification bulletin for those products.
8 5 3 31 2
S&C Specification Bulletin 681-31 7
Vista® Green Underground Distribution Switchgear
Type and Interrupting/ Short-Circuit Level
Vista Model Number
Max Voltage (kV) Any Number of Suffixes
85- Manual Vista switchgear 25 kA 93- Manual Vista switchgear 12.5 kA
2-15.5 kV 3- 29 kV 4- 38 kV
Add “-GRN-” suffix here
The catalog number created above represents manual Vista Green switchgear (CO2 mix), 25 kA, with a total of three ways that includes one load interrupter switch and two fault-interrupter switches for a 29-kV application. The unit will also be pad-mount style with a stainless steel outer enclosure and an olive-green finish, for the auxiliary contacts on the load-interrupter way with wires routed to terminal blocks mounted in an enclosure for customer connection. (The terminal block enclosure is typically mounted on the side of the Vista switchgear tank near the overcurrent relay enclosure.)
No. of ways
No. of load-interrupter switches
No. of fault-interrupter switches
Anatomy of a Vista Green Switchgear Catalog Number
How to Order Complete these steps to identify the base catalog number, the appropriate options, and the product accessories needed for a complete order:
STEP 1. Obtain the catalog number of the desired switchgear unit from Table 2 on pages 9 through 14.
Catalog Number:
STEP 2. Insulating Gas. To order the new CO2 mix insu-lating gas, add “-GRN-” after the base catalog number. (To order SF6 insulating gas, skip this step and proceed to Step 3.)
Suf fix:– G R N –
STEP 3. Specify the desired switchgear style from Table 3 on page 15 and add the appropriate suffix to the catalog number.
Suf fix:
STEP 4. Add suffix designations to the catalog number indicating the optional features desired, selected from Table 5 on pages 17 through 20. (Add as many suffixes as required.)
Suf fix:
Note: At this point, the catalog number for the Vista Green switchgear unit is complete. The next steps using Tables 6 and 7 are for product accessories and touch-up kit compo-nents that would be separate line items on the order. Contact S&C for additional available options.
STEP 5. Obtain catalog numbers for any accessories from Table 6 on page 21 and apply as a separate line item on the order.
Catalog Number:
STEP 6. Include touch-up kit components from Table 7 on page 21.
Catalog Number: –
Example: The catalog number for an UnderCover Style Vista Green switchgear unit, Model 422, rated 25 kA for a 38-kV system, maximum at 60 Hertz, and equipped with voltage indication with provisions for low-voltage phasing is:
8 5 4 2 2 4 – G R N – U L 2
8 5 – P 1 4 C 1 233 1 2 – G R N
8 S&C Specification Bulletin 681-31
Vista® Green Underground Distribution Switchgear
Table 1. 50/60-Hz ANSI Ratings—IEC Ratings in Parentheses① kV Amperes, RMS
System Class
Max BIL Main Bus
Cont.
Current
Short- Circuit, Sym.
Fault Interrupter Load-Interrupter Switch
Cont., Load
Dropping, and Load
Splitting②
10-Time Duty-Cycle Fault-Closing, Sym.
10-Time Duty-Cycle
Fault- Interr., Sym.
Cont., Load
Dropping, and Load
Splitting②
10-Time Duty-Cycle
Fault- Closing, Sym.③
Mom.
and One- Second, Sym.
Into Closed
Position
Into Grounded Position
15.5 (12)
15.5 (15.5)
(95)
(630)
12 500 (12 500)
(200)●
12 500 (12 500)
12 500 (12 500)
12 500 (12 500)
(630)■
12 500 (12 500)
12 500 (12 500)
(630)▲
25 000 (25 000)
(630)◆
25 000 (25 000) ▼
25 000 (25 000)
(630)□ ▼
25 000 (25 000)
(24)
(29)
(125)
(630)▲
12 500 (12 500)
(200)●
12 500 (12 500)
12 500 (12 500)
12 500 (12 500)
(630)■
16 000 (16 000)
12 500 (12 500)
25 000 (25 000)
(630)◆
25 000 (25 000) ▼
25 000 (25 000)
(630)□ ▼
25 000 (25 000)
(36)
(38)
(150)
(630)▲
12 500 (12 500)
(200)●
12 500 (12 500)
12 500 (12 500)
12 500 (12 500)
(630)■
16 000 (16 000)
12 500 (12 500)
25 000 (25 000)
(630)◆
25 000 (25 000) ▼
25 000 (25 000)
(630)□ ▼
25 000 (25 000)
① Refer to the nearest S&C Sales Office for other possible ratings.
② Parallel or loop switching. Fault interrupters and load-interrupter switches can switch the magnetizing current of transformers associ-ated with the load-dropping rating. Unloaded cable switching rating:
10 amperes at 15.5 kV; 20 amperes at 29 kV and 38 kV.
③ Applicable to fault closing into closed or grounded position.
● 600 (630) amperes when switchgear is furnished with optional 600-ampere bushings at fault interrupter terminals, catalog number suf-fix “-M2” or “-M3.” Note: 600-ampere bushings are supplied as stan-dard for Vista Green switchgear.
■ 200 (200) amperes when switchgear is furnished with optional 200-ampere bushing wells at load-interrupter switch terminals, catalog number suffix “-M4.” Note: SF6 models only.
▲ 1200 (1200) amperes when switchgear is furnished with optional copper bus, catalog number suffix “-Z5.”
◆ 900 (900) amperes when switchgear is furnished with optional 900-ampere fault interrupters, catalog number suffix “-Q1” through “-Q6,” plus an optional copper bus, catalog number suffix “-Z5.” (SF6 and 15.5-kV, 25-kA Vista Green switchgear models only).
▼ 25 000 (25 000) amperes symmetrical three-time duty-cycle fault-closing rating; 16 000 (16 000) amperes symmetrical 10-time duty-cycle fault-closing rating.
□ 900 (900) amperes when switchgear is furnished with optional 900-ampere load-interrupter switches, catalog number suffix “-K1” through “-K6,” plus an optional copper bus, catalog number suffix “-Z5.”
(SF6 and 15.5-kV, 25-kA Vista Green switchgear models only).
1635521917E Highlight
1635521917E Highlight
1635521917E Highlight
1635521917E Highlight
1635521917E Highlight
S&C Specification Bulletin 681-31 9
Vista® Green Underground Distribution Switchgear
① The model number defines the total number of ways, the number of load-interrupter switch ways, and the number of fault-interrupter ways.
For example, a Model 431 has “4” ways in total of which “3” are load-interrupter switch ways and “1” is a fault-interrupter way.
② Refer to the nearest S&C Sales Office for other possible configurations.
③ Refer to Table 1 on page 8 for continuous, load-dropping, interrupt-ing, and momentary ratings.
④ Welded-steel tank including components and insulating gas.
● These models have not been certified as arc resistant for unre-stricted access. Refer to the nearest S&C Sales Office.
TABLE CONTINUED ▶
Table 2. Three-Phase Units
Model① One-Line Diagram②
Ratings③
Catalog Number
Net Wt., Lbs. (kg)④
Page Reference for Dimensional
Information kV Short-Circuit
Amperes, RMS, Sym.Max BIL
15.5 95 12 500 25 000
932012R1 852012
550 (249) 550 (249)
22 through 29
29 125 12 500 25 000
932013 852013
550 (249) 800 (363)
38 150 12 500 25 000
932014● 852014
800 (363) 800 (363)
15.5 95 12 500 25 000
932102R1 852102
550 (249) 550 (249)
29 125 12 500 25 000
932103 852103
550 (249) 800 (363)
38 150 12 500 25 000
932104● 852104
800 (363) 800 (363)
15.5 95 12 500 25 000
932112R1 852112
550 (249) 550 (249)
29 125 12 500 25 000
932113 852113
550 (249) 800 (363)
38 150 12 500 25 000
932114● 852114
800 (363) 800 (363)
15.5 95 12 500 25 000
932202R1 852202
550 (249) 550 (249)
29 125 12 500 25 000
932203 852203
550 (249) 800 (363)
38 150 12 500 25 000
932204 852204
800 (363) 800 (363)
10 S&C Specification Bulletin 681-31
Vista® Green Underground Distribution Switchgear
① The model number defines the total number of ways, the number of load-interrupter switch ways, and the number of fault-interrupter ways.
For example, a Model 431 has “4” ways in total of which “3” are load-interrupter switch ways and “1” is a fault-interrupter way.
② Refer to the nearest S&C Sales Office for other possible configurations.
③ Refer to Table 1 on page 8 for continuous, load-dropping, interrupt-ing, and momentary ratings.
④ Welded-steel tank including components and insulating gas.
■ Auxiliary contacts unavailable as standard. Refer to the nearest S&C Sales Office.
TABLE CONTINUED ▶
Table 2. Three-Phase Units–Continued
Model① One-Line Diagram②
Ratings③
Catalog Number
Net Wt., Lbs. (kg)④
Page Reference for Dimensional
Information kV Short-Circuit
Amperes, RMS, Sym.Max BIL
15.5 95 12 500 25 000
933022R1 853022
825 (374) 825 (374)
22 through 29
29 125 12 500 25 000
933023 853023
825 (374) 1075 (488)
38 150 12 500 25 000
933024 853024
1075 (488) 1075 (488)
303■
15.5 95 12 500 25 000
933032R1 853032
825 (374) 825 (374)
29 125 12 500 25 000
933033 853033
825 (374) 1075 (488)
38 150 12 500 25 000
933034 853034
1075 (488) 1075 (488)
15.5 95 12 500 25 000
933122R1 853122
825 (374) 825 (374)
29 125 12 500 25 000
933123 853123
825 (374) 1075 (488)
38 150 12 500 25 000
933124 853124
1075 (488) 1075 (488)
15.5 95 12 500 25 000
933202R1 853202
825 (374) 825 (374)
29 125 12 500 25 000
933203 853203
825 (374) 1075 (488)
38 150 12 500 25 000
933204 853204
1075 (488) 1075 (488)
S&C Specification Bulletin 681-31 11
Vista® Green Underground Distribution Switchgear
① The model number defines the total number of ways, the number of load-interrupter switch ways, and the number of fault-interrupter ways.
For example, a Model 431 has “4” ways in total of which “3” are load-interrupter switch ways and “1” is a fault-interrupter way.
② Refer to the nearest S&C Sales Office for other configurations.
③ Refer to Table 1 on page 8 for continuous, load-dropping, interrupt-ing, and momentary ratings.
④ Welded-steel tank including components and insulating gas.
TABLE CONTINUED ▶
Table 2. Three-Phase Units—Continued
Model① One-Line Diagram②
Ratings③
Catalog Number
Net Wt., Lbs. (kg)④
Page Reference for Dimensional
Information kV Short-Circuit
Amperes, RMS, Sym.Max BIL
15.5 95 12 500 25 000
933212R1 853212
825 (374) 825 (374)
22 through 29
29 125 12 500 25 000
933213 853213
825 (374) 1075 (488)
38 150 12 500 25 000
933214 853214
1075 (488) 1075 (488)
15.5 95 12 500 25 000
933302R1 853302
825 (374) 825 (374)
29 125 12 500 25 000
933303 853303
825 (374) 1075 (488)
38 150 12 500 25 000
933304 853304
1075 (488) 1075 (488)
15.5 95 12 500 25 000
934042R1 854042
1100 (499) 1100 (499)
29 125 12 500 25 000
934043 854043
1100 (499) 1350 (612)
38 150 12 500 25 000
934044 854044
1350 (612) 1350 (612)
15.5 95 12 500 25 000
934132R1 854132
1100 (499) 1100 (499)
29 125 12 500 25 000
934133 854133
1100 (499) 1350 (612)
38 150 12 500 25 000
934134 854134
1350 (612) 1350 (612)
12 S&C Specification Bulletin 681-31
Vista® Green Underground Distribution Switchgear
TABLE CONTINUED ▶
① The model number defines the total number of ways, the number of load-interrupter switch ways, and the number of fault-interrupter ways.
For example, a Model 431 has “4” ways in total of which “3” are load-interrupter switch ways and “1” is a fault-interrupter way.
② Refer to the nearest S&C Sales Office for other configurations.
③ Refer to Table 1 on page 8 for continuous, load-dropping, interrupt-ing, and momentary ratings.
④ Welded-steel tank including components and insulating gas.
■ Auxiliary contacts unavailable as standard. Contact the nearest S&C Sales Office.
Table 2. Three-Phase Units—Continued
Model① One-Line Diagram②
Ratings③
Catalog Number
Net Wt., Lbs. (kg)④
Page Reference for Dimensional
Information kV Short-Circuit
Amperes, RMS, Sym.Max BIL
15.5 95 12 500 25 000
934222R1 854222
1100 (499) 1100 (499)
22 through 29
29 125 12 500 25 000
934223 854223
1100 (499) 1350 (612)
38 150 12 500 25 000
934224 854224
1350 (612) 1350 (612)
15.5 95 12 500 25 000
934312R1 854312
1100 (499) 1100 (499)
29 125 12 500 25 000
934313 854313
1100 (499) 1350 (612)
38 150 12 500 25 000
934314 854314
1350 (612) 1350 (612)
15.5 95 12 500 25 000
934402R1 854402
1100 (499) 1100 (499)
29 125 12 500 25 000
934403 854403
1100 (499) 1350 (612)
38 150 12 500 25 000
934404 854404
1350 (612) 1350 (612)
505■
15.5 95 12 500 25 000
935052R1 855052
1375 (624) 1375 (624)
29 125 12 500 25 000
935053 855053
1375 (624) 1625 (737)
38 150 12 500 25 000
935054 855054
1625 (737) 1625 (737)
1635521917E Highlight
1635521917E Highlight
1635521917E Highlight
1635521917E Highlight
S&C Specification Bulletin 681-31 13
Vista® Green Underground Distribution Switchgear
① The model number defines the total number of ways, the number of load-interrupter switch ways, and the number of fault-interrupter ways.
For example, a Model 431 has “4” ways in total of which “3” are load-interrupter switch ways and “1” is a fault-interrupter way.
② Refer to the nearest S&C Sales Office for other configurations.
③ Refer to Table 1 on page 8 for continuous, load-dropping, interrupt-ing, and momentary ratings.
④ Welded-steel tank including components and insulating gas.
Table 2. Three-Phase Units—Continued
Model① One-Line Diagram②
Ratings③
Catalog Number
Net Wt., Lbs. (kg)④
Page Reference for Dimensional
Information kV Short-Circuit
Amperes, RMS, Sym.Max BIL
15.5 95 12 500 25 000
935142R1 855142
1375 (624) 1375 (624)
22 through 29
29 125 12 500 25 000
935143 855143
1375 (624) 1625 (737)
38 150 12 500 25 000
935144 855144
1625 (737) 1625 (737)
15.5 95 12 500 25 000
935232R1 855232
1375 (624) 1625 (737)
29 125 12 500 25 000
935233 855233
1625 (737) 1625 (737)
38 150 12 500 25 000
935234 855234
1625 (737) 1625 (737)
15.5 95 12 500 25 000
935322R1 855322
1375 (624) 1375 (624)
29 125 12 500 25 000
935323 855323
1375 (624) 1625 (737)
38 150 12 500 25 000
935324 855324
1625 (737) 1625 (737)
15.5 95 12 500 25 000
935412R1 855412
1375 (624) 1375 (624)
29 125 12 500 25 000
935413 855413
1375 (624) 1625 (737)
38 150 12 500 25 000
935414 855414
1625 (737) 1625 (737)
15.5 95 12 500 25 000
935502R1 855502
1375 (624) 1375 (624)
29 125 12 500 25 000
935503 855503
1375 (624) 1625 (737)
38 150 12 500 25 000
935504 855504
1625 (737) 1625 (737)
TABLE CONTINUED ▶
14 S&C Specification Bulletin 681-31
Vista® Green Underground Distribution Switchgear
① The model number defines the total number of ways, the number of load-interrupter switch ways, and the number of fault-interrupter ways.
For example, a Model 431 has “4” ways in total of which “3” are load-interrupter switch ways and “1” is a fault-interrupter way.
② Refer to the nearest S&C Sales Office for other configurations.
③ Refer to Table 1 on page 8 for continuous, load-dropping, interrupt-ing, and momentary ratings.
④ Welded-steel tank including components and insulating gas.
Table 2. Three-Phase Units—Continued
Model① One-Line Diagram②
Ratings③
Catalog Number
Net Wt., Lbs. (kg)④
Page Reference for Dimensional
Information kV Short-Circuit
Amperes, RMS, Sym.Max BIL
15.5 95 12 500 25 000
936062R1 856062
1650 (748) 1650 (748)
22 through 29
29 125 12 500 25 000
936063 856063
1650 (748) 1900 (862)
38 150 12 500 25 000
936064 856064
1900 (862) 1900 (862)
15.5 95 12 500 25 000
936152R1 856152
1650 (748) 1650 (748)
29 125 12 500 25 000
936153 856153
1650 (748) 1900 (862)
38 150 12 500 25 000
936154 856154
1900 (862) 1900 (862)
15.5 95 12 500 25 000
936242R1 856242
1650 (748) 1650 (748)
29 125 12 500 25 000
936243 856243
1650 (748) 1900 (862)
38 150 12 500 25 000
936244 856244
1900 (862) 1900 (862)
15.5 95 12 500 25 000
936332R1 856332
1650 (748) 1650 (748)
29 125 12 500 25 000
936333 856333
1650 (748) 1900 (862)
38 150 12 500 25 000
936334 856334
1900 (862) 1900 (862)
15.5 95 12 500 25 000
936422R1 856422
1650 (748) 1650 (748)
29 125 12 500 25 000
936423 856423
1650 (748) 1900 (862)
38 150 12 500 25 000
936424 856424
1900 (862) 1900 (862)
15.5 95 12 500 25 000
936512R1 856512
1650 (748) 1650 (748)
29 125 12 500 25 000
936513 856513
1650 (748) 1900 (862)
38 150 12 500 25 000
936514 856514
1900 (862) 1900 (862)
15.5 95 12 500 25 000
936602R1 856602
1650 (748) 1650 (748)
29 125 12 500 25 000
936603 856603
1650 (748) 1900 (862)
38 150 12 500 25 000
936604 856604
1900 (862) 1900 (862)
S&C Specification Bulletin 681-31 15
Vista® Green Underground Distribution Switchgear
Table 3. Switchgear Styles
Item
Suffix to be Added to Switchgear Catalog Number
Applicable to Models
Net Weight, Lbs. (Kg)
UnderCover Style. Includes stainless steel tank and submersible wiring and control housings -U All models
Dry-vault floor-mounted style. Includes mild-steel tank. Does not include submersible wiring and control housings -V3 All models
Wet-vault floor-mounted style. Includes stainless steel tank and submersible wiring and control housings -V4 All models
Dry-vault wall-mounted style. Includes a mild-steel tank. Does not include submersible wiring and control housings. Labels are placed to be read while the tank feet are secured to a vertical wall and the operating shafts are below the terminations
-V5 All models
Wet-vault wall-mounted style. Includes a stainless steel tank, submersible wiring, and control housings. Labels are placed to be read while the tank feet are secured to a vertical wall and the operating shafts are below the termination
-V6 All models
Pad-mounted style.
Includes mild-steel tank and mild-steel or stainless steel pad-mounted enclosure for mounting switchgear on a pad. Does not include submersible wiring and control housings
Two-way unit
Mild-steel outer enclosure
Olive-green finish -P2 201, 210, 211, 220
360 (163)● Light gray finish -P7 201, 210, 211, 220
Stainless steel outer enclosure
Olive-green finish -P12 201, 210, 211, 220
Light gray finish -P17 201, 210, 211, 220
Three- or four-way unit
Mild-steel outer enclosure
Olive-green finish -P4 302, 303, 312, 320, 321, 330, 404, 413, 422, 431, 440
519 (235)●
Light gray finish -P9 302, 303, 312, 320, 321, 330, 404, 413, 422, 431, 440
Stainless steel outer enclosure
Olive-green finish -P14 302, 303, 312, 320, 321, 330, 404, 413, 422, 431, 440
Light gray finish -P19 302, 303, 312, 320, 321, 330, 404, 413, 422, 431, 440
Five- or six-way unit
Mild-steel outer enclosure
Olive-green finish -P6
505, 514, 523, 532, 541, 550, 606, 615, 624, 633, 642, 651, 812 (368)●
Light gray finish -P11
505, 514, 523, 532, 541, 550, 606, 615, 624, 633, 642, 651, Stainless steel outer enclosure
Olive-green finish -P16
505, 514, 523, 532, 541, 550, 606, 615, 624, 633, 642, 651, Light gray finish -P21
505, 514, 523, 532, 541, 550, 606, 615, 624, 633, 642, 651,
● Weight includes outer enclosure and base spacer.
1635521917E Highlight
1635521917E Highlight
16 S&C Specification Bulletin 681-31
Vista® Green Underground Distribution Switchgear
Table 4. Single-Pole or Three-Pole Fault Interrupting①②③
Item Suffix to be Added to Switchgear Catalog Number
Applicable to Models
Single-pole manual fault interrupter on all fault-interrupting ways -T0
12.5 kA-rated models with 1 or more fault interrupters
Three-pole manual fault interrupter on one fault-interrupting way (single-pole manual fault interrupter on all other fault-interrupting ways) -T1
12.5 kA-rated models with 1 or more fault interrupters
Three-pole manual fault interrupter on two fault-interrupting ways (single-pole manual fault interrupter on all other fault-interrupting ways) -T2
12.5 kA-rated models with 2 or more fault interrupters
Three-pole manual fault interrupter on three fault-interrupting ways (single-pole manual fault interrupter on all other fault-interrupting ways) -T3
12.5 kA-rated models with 3 or more fault interrupters
Three-pole manual fault interrupter on four fault-interrupting ways (single-pole manual fault interrupter on all other fault-interrupting ways) -T4
12.5 kA-rated models with 4 or more fault interrupters
Three-pole manual fault interrupter on five fault-interrupting ways (single-pole manual fault interrupter on all other fault-interrupting ways) -T5
12.5 kA-rated models with 5 or more fault interrupters
Three-pole manual fault interrupter on six fault-interrupting ways -T6
12.5 kA-rated models with 6 or more fault interrupters
① Not applicable to models rated 25 kA short circuit. All 25 kA-rated models include three-pole manual fault interrupters.
② Refer to the nearest S&C Sales Office for other possible configurations.
③ For standard models, components are in the following order (from left to right) when facing the operating side of the gear: load switches, bus taps, three-pole fault interrupters, single-pole fault interrupters.
S&C Specification Bulletin 681-31 17
Vista® Green Underground Distribution Switchgear
Table 5. Optional Features
Item Suffix to be Added to Switchgear Catalog Number
Applicable to Models
Stainless steel tank for dry-vault mounted style, wet-vault mounted style, or pad-mounted style switchgear -S All models
Auxiliary contacts.
Standard form open/ close contact switches①②
All load-interrupter switches③
With wires routed in a bundle on tank for future customer connections -C11● All models
With wires routed to terminal blocks mounted in an enclosure for customer connection (Terminal block enclosure is typically mounted on the side of the Vista switchgear tank near the overcurrent relay enclosure)
-C12■ Pad-mounted and dry-vault style models
All fault interrupters④⑤⑥
With wires routed in a bundle on the tank for future customer connections -C21● All models
With wires routed to terminal blocks mounted in an enclosure for customer connection (Terminal block enclosure is typically mounted on the side of the Vista switchgear tank near the overcurrent relay enclosure)
-C22■ Pad-mounted and dry-vault style models
Mounting provisions for fault indicators for each load- Interrupter switch, fault interrupter switch, or both. Accommodates three-phase indicator with single-phase sensors⑦
For each load-interrupter switch
Without viewing window in pad-mounted enclosure
-F1 All models except 201, 302, 303, 404, 505, and 606With viewing window in pad-mounted enclosure -F2
For each fault-interrupter switch
Without viewing window in pad-mounted enclosure
-F3 All models except 210, 220, 320, 330, 440, 530, 540, 550, 660With viewing window in pad-mounted enclosure -F4
Potential indication with test feature. Includes LCD display to indicate presence of voltage on each phase, and solar panel to supply power for testing of complete voltage-indication circuit and phasing circuit (if furnished). One potential indicator is provided for each bus-terminal, load-interrupter switch, and fault-interrupter way
Without provisions for low-voltage phasing -L1
All models With provisions for low-voltage phasing -L2
Spanish labels -L51 All models
International crating⑧ -L71 All models
① Order auxiliary contacts for planned future manual to remote super-visory conversions. Field retrofit of the auxiliary contacts is not possible.
See similar recommendation for the Remote Low-Pressure Alarm feature for suffix options “-R11”, “-R12,” and “-R2.” For Models 303 and 505, contact the nearest S&C Sales Office.
② If auxiliary contacts are specified for both load-interrupter switches and fault interrupters, both options must have the same termination style.
③ Provides verification of Closed/Open/Grounded blade position.
④ On three-pole fault interrupters, auxiliary contacts provide indication of Closed/Open/Grounded blade position, as well as trip indication.
⑤ Not available with single-pole fault interrupters (catalog option “-T0”) for models with catalog numbers ending in “R1.”
⑥ For single pole fault interrupters, on Vista switchgear models rated 29 kV and 38 kV, auxiliary contacts only provide trip indication.
⑦ Catalog number suffix “-F1” and “-F3” may be selected together or separately; “-F2” and “-F4” may also be selected in the same manner.
No mixed combination of “-F1” or “-F3” with “-F2” or “-F4” is permitted.
⑧ Wood products used in packaging are either hardwood or certified by the wood supplier as being “heat treated” (kiln dried) to a core tempera-ture of 133°F (56°C) for a minimum of 30 minutes.
● Not available with option “-R2,” “-C12,” or “-C22.”
■ Not available with option “-R11,” “-C11,” or “-C21.”
TABLE CONTINUED ▶
1635521917E Highlight
1635521917E Highlight
1635521917E Highlight
1635521917E Highlight
18 S&C Specification Bulletin 681-31
Vista® Green Underground Distribution Switchgear
Table 5. Optional Features—Continued
Item
Suffix to be Added to Switchgear Catalog Number
Applicable to Models
900-ampere load-interrupter switch⑨⑩⑪⑫ on
Way 1 -K1
All models rated 25 kA (SF6 models and 15.5-kV Vista Green models only)
Way 2 -K2
Way 3 -K3
Way 4 -K4
Way 5 -K5
Way 6 -K6
900-ampere fault interrupter⑨⑩⑪⑫ on
Way 1 -Q1
Way 2 -Q2
Way 3 -Q3
Way 4 -Q4
Way 5 -Q5
Way 6 -Q6
600-A bushings without studs, at load-interrupter switch and bus terminals (in lieu of standard 600-A bushings with studs) -M1 All models rated 12.5 kA
600-A⑬ bushings without studs, at load-interrupter switch, fault interrupter, and bus terminals (in lieu of standard 600-A bushings with studs) -M1 All models (both SF6 and
Vista Green) rated 25 kA
600-A bushings at fault-interrupter terminals (in lieu of 200-A bushing wells)
Without studs -M2 All SF6 models rated 12.5 kA except Models 210, 220, 320, 330, 440, 550, and 660.With studs -M3
200-A bushing wells at load-interrupter switch and bus terminals (in lieu of 600-A bushings with studs) -M4 All SF6 models rated 12.5 kA except Model 201⑭
Arc resistance for vault-mounted style (arc resistance is standard for pad-mounted and UnderCover styles), per IEC 298 Appendix AA, for arcs occurring internal to the tank (15 cycles, 12 kA symmetrical for 12.5-kA rated models and 15 cycles, 25 kA symmetrical for 25-kA-rated models)
-N All models with catalog number suffix “-V3,” “-V4,” “V5,” or “-V6”
Two-hole ground pad, one per way, located below bushings or bushing wells (in lieu of standard one ground pad per tank) -O All models
⑨ 900-ampere cable connectors must be used.
⑩ If piggybacked cable connectors are desired, refer to the nearest S&C Sales Office.
⑪ Copper bus, catalog number suffix “-Z5,” must be specified if 900-ampere load-interrupter switches and/or 900-ampere fault inter-rupters are specified.
⑫ If any “-K” or “-Q” suffix options are selected, any bus tap ways and terminals are also rated 900 amperes.
⑬ Bushings are rated 900 amperes on ways furnished with 900-ampere load-interrupter switches (catalog number suffix “-K1” through “-K6”) and/or 900-ampere fault interrupters (catalog number suffix “-Q1” through “-Q6”).
⑭ Model 201 is furnished with 200-ampere bushing wells at bus termi-nals as standard.
1635521917E Highlight
S&C Specification Bulletin 681-31 19
Vista® Green Underground Distribution Switchgear
Table 5. Optional Features—Continued
Item
Suffix to be Added to
Switchgear Catalog Number
Applicable to Models
Remote low-pressure alarm⑮—includes internal contact for remote low-pressure indication, with wiring to outside of tank
With wires routed in a bundle on the tank for future customer connections
-R11▲ All pad-mounted and dry-vault mounted styles
With wires routed to terminal blocks mounted in an enclosure for customer connection (Terminal block enclosure is typically mounted on the side of the Vista switchgear tank near the overcurrent relay enclosure)
-R12 All UnderCover and wet-vault mounted styles
-R2 ◆ All pad-mounted and dry-vault mounted styles
External trip provisions. Allows three-pole tripping of single-pole or three-pole fault interrupters via a trip signal from a remote location or an external relay. Requires a 110/120-Vac 50/60-Hz control power source⑯
In addition to standard overcurrent control for all fault interrupters
-R31 All pad-mounted and dry-vault mounted styles
-R32 All UnderCover and wet-vault mounted styles
In lieu of standard overcurrent control and current transformers for all fault interrupters
-R41 All pad-mounted and dry-vault mounted styles
-R42 All UnderCover and wet-vault mounted styles
External trip provisions. Allows three-pole tripping of single-pole or three-pole fault interrupters via a trip signal from a remote location or an external relay. Requires a 220/240-Vac 50/60-Hz control power source⑯
In addition to standard overcurrent control for all fault interrupters
-R33 All pad-mounted and dry-vault mounted styles
-R34 All UnderCover and wet-vault mounted styles
In lieu of standard overcurrent control and current transformers for all fault interrupters
-R43 All pad-mounted and dry-vault mounted styles
-R44 All UnderCover and wet-vault mounted styles
Base spacers, Includes a mild-steel or stainless steel base spacer color-matched to enclosure with integral tank supports ▼
15.5 kV 29 kV 38 kV
6-inch (152-mm) base spacer for enclosure and tank
Mild steel -W1 Pad-mounted style enclosures (mild steel) “-P2”, “-P4”, “-P6”, “-P7”, “-P9”, “-P11”
Stainless steel -W11 Pad-mounted style enclosures (mild and stainless steel) “-P2”, “-P4”, “-P6”, “-P7”, “-P9”, “-P11” “-P12”, “-P14”, “-P16”, “-P17”, “-P19”, “-P21”
15.5 kV 29 kV 38 kV
12-inch (305-mm) base spacer for enclosure and tank
Mild steel -W3 Pad-mounted style enclosures (mild steel) “-P2”, “-P4”, “-P6”, “-P7”, “-P9”, “-P11”
Stainless steel -W13 Pad-mounted style enclosures (mild and stainless steel) “-P2”, “-P4”, “-P6”, “-P7”, “-P9”, “-P11” “-P12”, “-P14”, “-P16”, “-P17”, “-P19”, “-P21”
15.5 kV 29 kV 38 kV
18-inch (457-mm) base spacer for enclosure and tank
Mild steel -W5 Pad-mounted style enclosures (mild steel) “-P2”, “-P4”, “-P6”, “-P7”, “-P9”, “-P11”
Stainless steel -W15 Pad-mounted style enclosures (mild and stainless steel) “-P2”, “-P4”, “-P6”, “-P7”, “-P9”, “-P11”, “-P12”, “-P14”, “-P16”, “-P17”, “-P19”, “-P21”
⑮ Must be specified if remote supervisory features such as remote low-pressure indication are planned.
⑯ The user-supplied trip-initiating signal must be a momentary contact. Refer to the nearest S&C Sales Office if an application requires the use of a latching contact.
▲ Not available with option “-C12” or “C22.”
◆ Not available with option “-C11” or “-C21.”
▼ When using a portable motor operator (PMO) on a manual Vista unit, order a 6-inch (152-mm) base spacer for the pad-mount enclosure without tank support rails to allow room for the PMO to be installed.
TABLE CONTINUED ▶
20 S&C Specification Bulletin 681-31
Vista® Green Underground Distribution Switchgear
Table 5. Optional Features—Continued
Item
Suffix to be Added to
Switchgear Catalog Number
Applicable to Models
Key interlocks. Locks load-interrupter switch or three-pole fault interrupter (catalog number suffix “-T1” through “-T6”) in the Open position⑰⑱
Way 1 -X1 Any in which Way 1 is a load-interrupter switch or three-pole fault interrupter
Way 2 -X2 Any in which Way 2 is a load-interrupter switch or three-pole fault interrupter
Way 3 -X3 Any in which Way 3 is a load-interrupter switch or three-pole fault interrupter
Way 4 -X4 Any in which Way 4 is a load-interrupter switch or three-pole fault interrupter
Way 5 -X5 Any in which Way 5 is a load-interrupter switch or three-pole fault interrupter
Way 6 -X6 Any in which Way 6 is a load-interrupter switch or three-pole fault interrupter
Provisions for future key interlocks. Includes welded mounting blocks and locking shaft position indicators for future installation of key interlocks on load-interrupter switches or three-pole fault interrupters⑰⑱⑲
Way 1 -X19 Any in which Way 1 is a load-interrupter switch or three-pole fault interrupter
Way 2 -X29 Any in which Way 2 is a load-interrupter switch or three-pole fault interrupter
Way 3 -X39 Any in which Way 3 is a load-interrupter switch or three-pole fault interrupter
Way 4 -X49 Any in which Way 4 is a load-interrupter switch or three-pole fault interrupter
Way 5 -X59 Any in which Way 5 is a load-interrupter switch or three-pole fault interrupter
Way 6 -X69 Any in which Way 6 is a load-interrupter switch or three-pole fault interrupter
Copper bus⑳ -Z5 All models
⑰ Motor operators can not be retrofitted onto ways with key interlocks.
⑱ The portable motor operator accessory cannot be used on ways with key interlock mounting provisions or key interlocks. Permanent-style motor operators for remote supervisory Vista switchgear cannot be retrofitted onto ways with key interlocks or key interlock mounting provisions.
⑲ Key interlock mounting provisions cannot be added after shipment.
Only switchgear with ordered key interlock mounting provisions can be field equipped with key interlocks.
⑳ Main bus can be rated up to 1200 amperes when catalog number suffix “-Z5” is specified.
S&C Specification Bulletin 681-31 21
Vista® Green Underground Distribution Switchgear
Table 6. Accessories
Item Catalog Number
Shotgun clamp sticks for use with separable connectors 6-foot–5½-inch (197-cm) length 9933-150
8-foot–5½-inch (258-cm) length 9933-151
Storage bag for shotgun clamp sticks, heavy canvas 6-foot-6-inch (198-cm) length 9933-152
8-foot-6-inch (259-cm) length 9933-153
Portable motor operator① for operation of load-interrupter switches and single- or three-pole fault interrupters from a remote location. Includes carrying case, and 50-foot (1524-cm) cable with remote controls. Power supplied by:②
User-furnished 24-Volt battery and battery charger 38320R1
S&C-furnished 24-Volt battery and battery charger 38322R1
S&C-furnished ac input power supply 38323R1
Pentahead socket, for ½-inch drive 9931-074
Vista overcurrent control 2.0 connection cable. (For connecting control to user PC for programming and status information.