Attachment 7-648-20-116 Drawings 134-169.pdf

PDF 3 MB Posted

Attached to
Z2DA--CON 648-20-116 Correct Electrical FCA Deficiencies Bldgs. /Site (Vancouver)
Solicitation number
36C26026R0040
Issued by

About this file

These are electrical one-line diagrams and related construction drawings for Building 011, Building 012, Building 013, Building 015, Building 018, Building 019, Building 020, Building 021, Building 022, Building 023, Building 025, Building T819, Building TR3, and associated site electrical infrastructure for a Department of Veterans Affairs facility located in Vancouver, Washington. The drawings are prepared by SpeedSpec Design Build as the Architect/Engineer of Record and represent design-build electrical work for the Pacific Highway Suite project.

The documents depict comprehensive electrical systems including low-voltage and medium-voltage distribution, panel boards, switchboards, motor control centers, transformers, capacitor banks, protective devices, lighting circuits, emergency systems, site utility connections, and grounding schemes. Key components shown include multiple distribution panels (ranging from 200-400 amperes at various voltages), square-D and Cutler-Hammer circuit breakers and disconnects in various configurations, diesel generators with automatic transfer switches, active harmonic filters, power factor correction capacitors, and extensive branch circuits serving building loads for HVAC, lighting, emergency systems, well pumps, and specialized medical or administrative equipment. The drawings indicate coordination with Clark Public Utilities for utility service connections and reference compliance with NEC and local code requirements. Medium-voltage transformer stations rated at multiple kVA levels with primary selectivity and disconnect provisions are shown serving multiple buildings. The documents are marked as revised and contain cross-references to related sheets, suggesting this is part of a larger electrical design and construction package for a multi-building federal facility renovation or expansion project.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

(013EP101)

7 MV TRANSFORMER SHALL HAVE THE FOLLOWING

CHARACTERISTICS:

- PRIMARY SELECTIVITY AND DISCONNECT.

- PRIMARY FUSES PER MANUFACTURER.

- PROVIDE GROUND ROD AND GROUNDING CONDUCTOR

BONDING WITHIN XFMR FOOTPRINT PER NEC.

3 MV TRANSFORMER SHALL HAVE THE FOLLOWING

CHARACTERISTICS:

- PRIMARY SELECTIVITY AND DISCONNECT.

- PRIMARY FUSES PER MANUFACTURER.

- PROVIDE GROUND ROD AND GROUNDING CONDUCTOR

BONDING WITHIN XFMR FOOTPRINT PER NEC.

012-P-01

DPMSPD

90A 3P

SPD

60A 3P

WEATHERPROOF SOUND

PROVIDE GENERATOR AS INDICATED TO REPLACE EXISTING

GENERATOR SERVING BUILDINGS 01 AND 11. ALL

ASSOCIATED POWER FEEDERS AND CONTROLS SHALL BE

REPLACED AS REQUIRED. REFERENCE ONE-LINE DIAGRAM

ON SHEET 001ED603 AND ENLARGED PLAN ON SHEET

001EP401d FOR ADDITIONAL INFORMATION. REFERENCE

SPECIFICATION 26 32 13 ENGINE GENERATORS FOR

ADDITIONAL INFORMATION.