FROM TO QTY SIZE (QTY) & SIZE GROUND

SIZE

013-P-01 SITE LIGHTING CONTACTOR PANELBOARD "PMP-4/1" SITE LIGHTING CONTACTOR 1 1" (2) 10 AWG (1) 10 AWG - 013-P-02 SURGE PROTECTION DEVICE PANELBOARD "MDS-4" SURGE PROTECTION DEVICE 1 1" (4) 6 AWG (1) 10 AWG -

013-G-01 WATER PIPE BOND MAIN FIRE RISER WATER PIPE BONDING BUSBAR 1 - - 2 AWG -

013-G-02 SERVICE EQUIPMENT BOND BONDING BUSBAR PANEL "MDS-4" 1 - - 2 AWG -

013-G-03 GROUNDING ARRAY GROUND ROD GROUND ROD 1 - - 3/0 AWG 1

013-G-04 AIR TERMINAL BOND ESE AIR TERMINAL GROUND ROD 1 - - 2 AWG -

NOTES

BLDG 013 - CONDUIT AND WIRE SCHEDULE

CONDUIT

TAG SERVICE

ROUTING CONDUIT CONDUCTORS

NOTE(S):

1. GROUNDING ELECTRODE SYSTEM BONDING CONDUCTORS SHALL BE ROUTED IN CONDUIT WHERE EXPOSED AND SHALL BE BARE WHEN UNDERGROUND.

FROM TO QTY SIZE (QTY) & SIZE GROUND

SIZE

013-P-01 SITE LIGHTING CONTACTOR PANELBOARD "PMP-4/1" SITE LIGHTING CONTACTOR 1 1" (2) 10 AWG (1) 10 AWG - 013-P-02 SURGE PROTECTION DEVICE PANELBOARD "MDS-4" SURGE PROTECTION DEVICE 1 1" (4) 6 AWG (1) 10 AWG -

13-C-01 PHOTOCELL SITE LIGHTING CONTACTOR PHOTOCELL 1 1" (2) 12 AWG (1) 12 AWG

013-G-01 WATER PIPE BOND MAIN FIRE RISER WATER PIPE BONDING BUSBAR 1 - - 2 AWG -

013-G-02 SERVICE EQUIPMENT BOND BONDING BUSBAR PANEL "MDS-4" 1 - - 2 AWG -

013-G-03 GROUNDING ARRAY GROUND ROD GROUND ROD 1 - - 3/0 AWG 1

013-G-04 AIR TERMINAL BOND ESE AIR TERMINAL GROUND ROD 1 - - 2 AWG -

NOTES

BLDG 013 - CONDUIT AND WIRE SCHEDULE

CONDUIT

TAG SERVICE

ROUTING CONDUIT CONDUCTORS

NOTE(S):

1. GROUNDING ELECTRODE SYSTEM BONDING CONDUCTORS SHALL BE ROUTED IN CONDUIT WHERE EXPOSED AND SHALL BE BARE WHEN UNDERGROUND.

Location: BLDG 14, RM 112 Volts: 208/120 Wye A.I.C Rating: 22k Supply From: "DP-7/1" Phases: 3 Bus Rating: 225A

Mounting: Surface Wires 4 Main Circuit Breaker: 200A Enclosure: Type 1

CKT Trip Poles Poles Trip 1 20 A 1 0 0 1 20 A 2 3 20 A 1 0 0 1 20 A 4 5 20 A 1 0 0 2 15A 6 7 20 A 1 0 0 '' '' 8 9 20 A 1 0 0 2 20 A 10

11 20 A 2 0 0 " " 12 13 " " 0 0 2 20 A 14 15 20 A 1 0 0 " " 16 17 20 A 1 0 0 1 20 A 18 19 20 A 1 0 0 1 20 A 20 21 20 A 1 0 0 1 20 A 22 23 20 A 1 0 0 1 20 A 24 25 20 A 1 0 0 1 20 A 26 27 20 A 1 0 0 2 20 A 28 29 20 A 1 0 0 " " 30 31 20 A 1 0 0 2 30 A 32 33 20 A 1 0 0 " " 34 35 20 A 1 0 0 1 20 A 36 37 20 A 1 0 0 1 20 A 38 39 20 A 1 0 0 2 30 A 40 41 20 A 1 0 0 " " 42 43 20 A 1 0 0 1 20 A 44 45 20 A 1 0 0 1 20 A 46 47 20 A 1 0 0 1 20 A 48 49 20 A 1 0 100 3 30 A 50 51 20 A 1 0 100 " " 52 53 20 A 1 0 100 " " 54

SPARE SURGE PROTECTION DEVICE

SPARE "

SPARE "

SPARE SPARE

SPARE SPARE

SPARE SPARE

RECEPT RM 108 CONDENSATE PUMP

LIGHTS MEZZAINE RTU HEAT

GYM EXHAUST FANS (OFF) "

LIGHTS UPPER LEVEL SPARE

RECEPT UPPER LEVEL "

RECEPT LOWER LEVEL RM 108 AC / RECEPT

SCOREBOARD LOCKER AREA EXHAUST FANS

LIGHTS MAIN LEVEL EAST WALL HEATER SOUTH STORAGE

LIGHTS MAIN LEVEL NORTH "

EXIT LIGHTS HEAT DOWNSTAIRS WEST (OFF)

GYM RECEPT HEAT DOWNSTAIRS EAST

GYM RECEPT FIRE ALARM PANEL

" GYM LIGHTS

EXHAUST FAN - MECHANICAL RM "

RECEPT MEACHNICAL RM HEAT UPSTAIRS

WALL HEATER NORTH STORAGE RM "

CIRCUIT DESCRIPTION

WATER COOLER - WATER HEATER GYM LIGHTS

GYM CEILING FANS STORAGE RM LIGHTS AND NORTH RECEPT

EXTERIOR LIGHTS - STAIR LIGHTS HEATER ENTRY WAY

PANELBOARD: 14-D6A (REPLACEMENT)

VA PER PHASE

CIRCUIT DESCRIPTION A B C

MECHANICAL RM LIGHTS ''

PUMP - MECHANICAL RM RECEPT GYM LIGHTS