This document contains details of a federal solicitation opportunity and related electrical drawings attachment. The solicitation seeks a general contractor to construct twenty-four telecommunication rooms at a Veterans Affairs medical center to upgrade electrical infrastructure including panels, power systems, bonding, UPS, building management system interfaces and HVAC assessments. Additional requirements include communication infrastructure installation and upgrades, physical security enhancements, fiber backbone assessment and hazardous material abatement. The opportunity was issued by the Department of Veterans Affairs Technology Acquisition Center Austin. The solicitation number is 36C77623B0034 and is titled "Y1BG--EHRM Infrastructure Upgrades Construction John Cochran."
View the file
Other files for this federal contract opportunity
Show all 32
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL BE INSTALLED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS, THE MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT AND WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE AND VA STANDARDS.
2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT AND FEEDERS WHERE THE BUILDING CONSTRUCTION IS
NOT SUITABLE FOR DIRECT MOUNTING.
3. FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR SPACE AROUND ALL PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILING, AND ROOFS IN ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE, UL LISTING REQUIREMENT AND THE APPLICABLE BUILDING CODES.
4. VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES, TRIMS AND ALL REQUIRED MOUNTING HARDWARE TO SUIT
THE PARTICULAR INSTALLATION.
5. PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES DURING CONSTRUCTION.
6. BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.
7. COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION SO AS TO AVOID CONFLICT DURING
CONSTRUCTION.
8. ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION, OR SPARE, OR SPACE.
9. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO INDICATE A QUALITY STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER. PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE ACCEPTED. ALL PRODUCTS MUST COMPLY WITH "BUY AMERICAN ACT".
10. ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL, BREAKER, AND/OR PARTICULAR EQUIPMENT
MANUFACTURER'S SPECIFICATIONS.
11. CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES SHALL BE TERMINATED ON THE DEVICE'S SCREW
TERMINALS.
12. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET, FIXTURE, OR EQUIPMENT UNLESS NOTED OTHERWISE.
13. ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.
14. ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS OTHERWISE NOTED.
15. ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC CONDUIT SHALL BE USED ON VIBRATING EQUIPMENT (MAXIMUM LENGTH OF 6 FEET). PVC SHALL BE USED FOR UNDERGROUND CONDUIT OR WHERE CONCRETE-ENCASED. WHERE VIBRATING EQUIPMENT IS LOCATED OUTSIDE, LFMC CONDUIT SHALL BE USED (MAXIMUM SIX FEET) FOR FINAL CONNECTIONS.
16. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN APPROVED THIRD PARTY
TESTING AGENCY.
17. FOR ALL LED FIXTURES, THE FIXTURE MUST BE CAPABLE OF SELF-RESETTING TO THE SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC PROTECTIVE MEASURES DISABLE THE LED LAMPS. PROVIDE A LETTER OR STATEMENT FROM THE MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT BROWNOUT PROTECTION, WILL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY. PROVIDE
STATEMENT WITH THE FIXTURE SUBMITTALS.
18. IN CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT DRAWINGS, THE BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER QUANTITY OF WORK , AS DETERMINED BY THE GOVERNMENT, SHALL BE PROVIDED.
19. COMPRESSION COUPLINGS SHALL BE USED. NO SET SCREW FITTINGS ARE ALLOWED.
20. MINIMUM CONDUIT SIZE TO BE USED IS 3/4".
21. FEEDER TAGS APPENDED WITH 'VD' ARE UPSIZED IN AMPACITY DUE TO VOLTAGE DROP.
22. CEILING TILES WHICH ARE REMOVED FOR WORK, SHALL BE REINSTALLED AT THE END OF EACH WORK SHIFT, SO AS TO
MAINTAIN SPRINKLER SYSTEM EFFECTIVENESS.
23. IF FLOOR OR WALL RATED PENETRATIONS CANNOT BE FIRESTOPPED AT THE END OF EACH WORK SHIFT DUE TO THE NEED TO PULL ADDITIONAL CABLES, TEMPORARY FIRESTOPPING COMPOSED OF MINERAL WOOL SHOULD BE INSTALLED IN THE PENETRATION TO PROVIDE PROTECTION AGAINST FIRE/SMOKE SPREAD THROUGH THE UNSEALED PENETRATION.
L L
SPKR SPEAKER
SP SPARE
SR SURFACE RACEWAY
SS STAINLESS STEEL
SSW SELECTOR SWITCH
STD STANDARD
SURF SURFACE MOUNTED
SW SWITCH
SWBD SWITCHBOARD
SYM SYMMETRICAL
SYS SYSTEM
TC TIMECLOCK
TEL TELEPHONE
TEL/DATA TELEPHONE/DATA
TERM TERMINAL
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TR TAMPER RESISTANT
T-STAT THERMOSTAT
TTB TELEPHONE TERMINAL BOARD
TTC TELEPHONE TERMINAL CABINET
TV TELEVISION
TYP TYPICAL
UC UNDER COUNTER
UE UNDERGROUND ELECTRICAL
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITER'S LABORATORY
UT UNDERGROUND TELEPHONE
UTP UNSHIELDED TWISTED PAIR
UTIL UTILITY
UV UNIT VENTILATOR OR
ULTRAVIOLET
V VOLT
VA VOLT-AMPERES
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
W WATT
W/ WITH
WH WATER HEATER
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
XFR TRANSFER
ANGLE
@ AT
DELTA
' FEET
" INCHES
# NUMBER
Φ PHASE
C CENTER LINE
P PLATE
MTR MOTOR, MOTORIZED
MTS MANUAL TRANSFER SWITCH
NA NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION
NFDS NON-FUSED SAFETY DISCONNECT
SWITCH
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
OL OVERLOAD
PA PUBLIC ADDRESS
PB PULL BOX OR PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT
UNIT
PCB POLYCHLORINATED BIPHENYL
PC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PIV POST INDICATING VALVE
PNL PANEL
POE POWER-OVER-ETHERNET
PR PAIR
PRI PRIMARY
PROJ PROJECTION
PRV POWER ROOF VENTILATOR
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (CONDUIT)
PWR POWER
QTY QUANTITY
R RELOCATE/RELOCATED
RCP REFLECTED CEILING PLAN
RCPT RECEPTACLE
REQD REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
RTU ROOF TOP UNIT
SC SURFACE CONDUIT
SEC SECONDARY
SF SQUARE FEET/FOOT
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SIM SIMILAR
S/N SOLID NEUTRAL
SPEC SPECIFICATION
1P 1 POLE (2P, 3P, 4P, ETC.)
1PH 1 PHASE
2/C TWO-CONDUCTOR (3/C, 4/C, ETC.)
2W TWO-WIRE (3W, 4W, ETC.)
3PH 3 PHASE
A AMPERE
AAP ALARM ANNUNCIATOR PANEL
AC ABOVE COUNTER
AIR CONDITIONER
ALTERNATING CURRENT
ACC ACCESSIBLE
ACLG ABOVE CEILING
ADO AUTOMATIC DOOR OPENER
A/E ARCHITECT/ENGINEER
AF AMP FRAME
AFC AVAILABLE FAULT CURRENT (KILOAMPS)
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFI ARC FAULT CIRCUIT INTERRUPTER
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING CAPACITY
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
APPROX APPROXIMATELY
ARCH ARCHITECT, ARCHITECTURAL
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
BAS BUILDING AUTOMATION SYSTEM
BATT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISHED FLOOR
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
BYP BYPASS
C CONDUIT
CAB CABINET
CALC CALCULATED
CAP CAPACITY
CAT CATALOG, CATEGORY
CATV COMMUNITY ANTENNA TELEVISION
CB CIRCUIT BREAKER
CCR CONTROL CONTACTOR
CCT CORRELATED COLOR TEMPERATURE
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR-FURNISHED
CKT CIRCUIT
CLG CEILING
CO CONTRACTING OFFICER
COAX COAXIAL CABLE
COMM COMMUNICATION
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION OR CONTINUOUS
CONTR CONTRACTOR
COORD COORDINATE
COR CONTRACTING OFFICER'S
REPRESENTATIVE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CTR CENTER
CU COPPER
CU FT CUBIC FEET
D DEMOLITION
dB DECIBEL
DB DIRECT BURIAL
DC DIRECT CURRENT
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLISH/DEMOLITION
DEPT DEPARTMENT
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DS SAFETY DISCONNECT SWITCH
DT DOUBLE THROW
DWG DRAWING
EC ELECTRICAL CONTRACTOR
EG EQUIPMENT GROUND
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
EM EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
EPO EMERGENCY POWER OFF
EQUIP EQUIPMENT
ESMT EASEMENT
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WALL HEATER
ELECTRIC WATER HEATER
EX EXISTING
EXP EXPLOSION PROOF
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FCU FAN COIL UNIT
FIXT FIXTURE
FLR FLOOR
FU FUSE
FUDS FUSED SAFETY DISCONNECT
SWITCH
FVR FULL VOLTAGE REVERSING
FVNR FULL VOLTAGE NON-REVERSING
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERATOR
GFI GROUND FAULT CIRCUIT INTERRUPTER
GND GROUND
GRS GALVANIZED RIGID STEEL (CONDUIT)
GYP BD GYPSUM BOARD
HID HIGH-INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HTR HEATER
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING AND AIR
CONDITIONING
IES ILLUMINATION ENGINEERING SOCIETY
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
IR INFRARED
I/W INTERLOCK WITH
IWH INSTANTANEOUS WATER HEATER
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAR KILOVOLT-AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
LED LIGHT-EMITTING DIODE
LF LINEAR FEET/FOOT
LM LUMEN
LRA LOCKED ROTOR AMPS
LT LIGHT
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
METAL-CLAD (CONDUIT)
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MFR MANUFACTURER
MFS MAIN FUSED DISCONNECT SWITCH
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MOA MULTIOUTLET ASSEMBLY
MSBD MAIN SWITCHBOARD
MT MOUNT
SHORT CIRCUIT CURRENT CALCULATIONS SHALL BE PERFORMED ON THE ELECTRICAL SYSTEM USING A BOLTED THREE PHASE FAULT CONDITION FOR CALCULATIONS TO ACHIEVE MAXIMUM THERMAL AND MECHANICAL STRESS TO THE SYSTEM FOR CALCULATIONS PURPOSES. EXISTING SHORT CIRCUIT VALUES WILL BE USED OUTSIDE THE WORK
AREA, FOR THE STARTING POINT OF THE CALCULATIONS.
METHOD OF SHORT CIRCUIT CURRENT CALCULATIONS
USING OHM'S LAW AND THE KNOWN RESISTIVITY CONSTANT OF CONDUCTOR METAL (CIRCULAR MIL-OHM PER FOOT) FOR COPPER CONDUCTORS, CALCULATE THE REQUIRED WIRE SIZE NECESSARY SO AS NOT TO EXCEED THE
RECOMMENDED VOLTAGE DROP OF 3% FOR BRANCH CIRCUIT CONDUCTORS.
METHOD OF VOLTAGE DROP CALCULATIONS
A1 b
E1 c d
T1
'LPN'
THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER OR AN UPPER
CASE LETTER AND NUMBER.
THE SWITCH DESIGNATION (IF NEEDED) IS INDICATED BY A LOWER CASE LETTER.
EXAMPLE: LIGHTING FIXTURE TYPE 'A1' IS CONTROLLED BY SWITCH 'b'.
EXIT SIGNS: STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING
MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES
DIRECTIONAL ARROW ON ILLUMINATED FACE(S).
DEVICES: THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
TRANSFORMERS: THE TRANSFORMER TYPE IS INDICATED BY A NUMBER
FOLLOWING THE UPPER CASE LETTER 'T'. SEE THE TRANSFORMER SCHEDULE OR
THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND
REQUIREMENTS.
PANELBOARDS: PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING
SIDE OF RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR
DESIGNATION CODES.
SHEET KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE NOTE
NUMBER INDICATED IN THE HEXAGON.
HOME RUN TO BRANCH CIRCUIT PANEL: THE PANEL DESIGNATION AND CIRCUIT
DESIGNATION ARE SHOWN ADJACENT TO THE HOME RUN ARROW.
CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANEL
SCHEDULE WITH THE CORRESPONDING PANEL AND CIRCUIT DESIGNATION.
SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE
A UNIT TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.
'LPN'-1,3,5
EXAMPLE 1: WALL MOUNTED EXIT SIGN TYPE 'E1' WITH SINGLE FACE
AND DIRECTIONAL ARROW.
EXAMPLE 2: CEILING MOUNTED EXIT SIGN TYPE 'E2' WITH DOUBLE
FACE AND DIRECTIONAL ARROWS.
E2
EXAMPLE: SPLIT DUPLEX RECEPTACLE; ONE RECEPTACLE OUTLET IS
CONTROLLED BY SWITCH 'c'.
EXAMPLE: SINGLE POLE SWITCH 'd' TO CONTROL LIGHTING FIXTURES INDICATED BY 'd'.
EXAMPLE: TRANSFORMER TYPE 'T1'.
EXAMPLE: HOME RUN TO PANELBOARD 'LPN'; CIRCUITS 1, 3, 5.
# DEMOLITION KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE
NOTE NUMBER INDICATED IN THE SQUARE.
A. RETURN REMOVED MATERIAL DEEMED SALVAGEABLE BY THE COR. MATERIALS DEEMED NOT SALVAGEABLE SHALL BE
REMOVED FROM THE PREMISES.
B. ALL EXISTING CONDITIONS, INCLUDING BUT NOT LIMITED TO EQUIPMENT, DEVICES, FIXTURES, CONDUIT AND CIRCUITS, ARE BASED ON THE BEST AVAILABLE INFORMATION AT THE TIME OF SURVEY AND VISUAL INSPECTION.
C. THE DRAWINGS ARE GENERALLY DIAGRAMMATIC AND THE CONTRACTOR SHALL HARMONIZE HIS WORK SO THAT EACH PIECE OF EQUIPMENT WILL BE INSTALLED AS TO FUNCTION PROPERLY. THE CONTRACTOR SHALL COOPERATE WITH OTHER
TRADES.
D. REMOVE ALL EXISTING WIRING DEVICES, LIGHT FIXTURES, WIRE, CONDUIT, ETC., AS NOTED OR INDICATED WITHIN DEMOLITION AREA. (ALL ITEMS MAY NOT BE SHOWN). REWORK AS NECESSARY CIRCUITING WHICH REQUIRES
CONTINUATION THROUGH THE AREA.
E. ELECTRICAL CONTRACTOR TO PROVIDE ALL NECESSARY LABOR, CONDUIT, WIRE, CONNECTIONS, ETC., FOR DEVICES, FIXTURES, ETC., NOTED AS "EXISTING TO REMAIN" SUCH THAT EXISTING CIRCUIT CONTINUITY IS MAINTAINED.
F. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK REQUIRED TO REMOVE/RELOCATE ANY EXISTING ELECTRICAL EQUIPMENT SUCH THAT ELECTRIC SHOCK HAZARDS TO WORKMEN ARE ELIMINATED DURING DEMOLITION AND
NEW CONSTRUCTION.
G. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK IN REMOVING AND REPLACING "EXISTING TO REMAIN" FIXTURES, DEVICES, ETC., AS REQUIRED SO THAT THESE DEVICES ARE NOT DAMAGED DURING DEMOLITION. RELOCATED TO NEAREST APPROPRIATE LOCATION TO AVOID CONFLICTS WITH OTHER TRADES' WORK. REPLACE WITH NEW ANY "EXISTING
TO REMAIN" FIXTURE, DEVICE, ETC., NOT DEEMED SALVAGEABLE BY THE COR.
H. REMOVED OR DAMAGED CONDUIT, WIRE, AND FITTINGS SHALL NOT BE REUSED FOR RELOCATED OR NEW DEVICES.
I. MAKE AS-BUILTS WITH NEW TYPED DIRECTORIES FOR ALL PANELBOARDS, INDICATING CIRCUIT DESCRIPTION (USED OR
SPARE), CIRCUIT BREAKERS AND CIRCUIT LOAD.
J. WORK REQUIRED FOR EXISTING EQUIPMENT NOTED AS "EXISTING TO BE REMOVED" SHALL INCLUDE:
A. REMOVAL OF FEEDER FROM EQUIPMENT TO POINT OF FEED.
B. REMOVAL OR RE-CIRCUITING OF ALL BRANCH CIRCUITING.
C. REMOVAL OF ALL FITTINGS, SUPPORTS, BRACKETS, ETC.
D. PATCHING OF WALLS, FLOORS AND CEILINGS PER ARCHITECT'S INSTRUCTIONS.
E. CAPPING OF FEEDER CONDUIT AT 6" ABOVE OR BELOW FLOOR/CEILING AS REQUIRED AND MARKING LOCATION OF POINT
OF FEED WITH AN ENGRAVED BRASS TAG.
F. REMOVAL OF FEEDER CONDUIT IF FOUND TO BE UNSALVAGEABLE BY ARCHITECT, ENGINEER OR THE COR.
K. EXISTING EQUIPMENT NOT IMPLICITLY SHOWN ON THE DRAWINGS IS INTENDED TO BE "EXISTING TO REMAIN UNCHANGED", UNLESS NOTED OTHERWISE.
A. PRIOR TO SUBMITTING PROPOSAL, BIDDER SHALL EXAMINE ALL GENERAL CONSTRUCTION DRAWINGS.
B. CERTAIN REMODELING OF ELECTRICAL FACILITIES WILL BE REQUIRED IN THE EXISTING BUILDING. EXISTING CONDUIT RUNS ARE GENERALLY NOT SHOWN. ALTHOUGH A FULL ATTEMPT HAS BEEN MADE TO SHOW SOME EXISTING CONDITIONS, OF WHICH INFORMATION HAS BEEN TAKEN FROM EXISTING RECORD DRAWINGS OF THIS PROJECT. THE DRAWINGS SHOWING LOCATION OF EXISTING EQUIPMENT, OUTLETS, FIXTURES, ETC., IN EXISTING AREAS ARE APPROXIMATE ONLY (FIELD
VERIFY).
C. BRANCH CIRCUITS SHALL BE REUSED WHERE PRACTICAL AND SHALL, IN ADDITION, BE REMODELED AS REQUIRED. THE
CONTRACTOR SHALL CONCEAL ALL WORK WHERE POSSIBLE.
D. EXISTING ELECTRICAL WIRING WHICH WILL NOT BE MADE OBSOLETE AND WHICH WILL BE DISTURBED DUE TO CONSTRUCTION CHANGES REQUIRED BY THIS CONTRACT SHALL BE RESTORED TO OPERATING CONDITION, AS REQUIRED AND/OR DIRECTED. WHERE REQUIRED, SHOWN AND/OR DIRECTED, OUTLETS AND CONDUIT RUNS SHALL BE RELOCATED.
IN SOME CASES IT MAY BE NECESSARY TO EXTEND CONDUITS AND PULL IN NEW WIRING OR INSTALL JUNCTION BOXES AND
SPLICE IN NEW WIRING OR REPLACE OLD WIRING WITH NEW.
E. OUTLETS FROM WHICH FIXTURES, SWITCHES, RECEPTACLES, AND/OR OTHER ELECTRICAL DEVICES ARE MOVED AND WHICH ARE NOT REPLACED OR REUSED SHALL BE REMOVED OR, IF IT IS NOT POSSIBLE TO REMOVE, PLACE A BLANK COVER ON THE OUTLET BOX. WHERE OUTLETS, BOXES, ETC., ARE COMPLETELY REMOVED, THE CONTRACTOR SHALL CUT
OFF CONDUITS AND REMOVE WIRING.
F. WHERE EXISTING LIGHT FIXTURES ARE TO BE REUSED, THE ELECTRICAL CONTRACTOR SHALL CLEAN AND REPLACE
LAMPS, REPAIR OR REPLACE DEFECTIVE PARTS, LENS, BALLAST, ETC. AS REQUIRED.
G. WHERE CONDUITS EXTENDING THROUGH FLOORS ARE TO BE ABANDONED, THE CONTRACTOR SHALL CUT AND CAP OR
PLUG CONDUIT, THAT IT WILL NOT PROTRUDE ABOVE THE FLOOR.
H. WHERE EXISTING CONDUIT IS TO BE ABANDONED, THE CONDUIT SHALL BE REMOVED IF IT IS EXPOSED, IN A CRAWL SPACE OR IN AN ACCESSIBLE CEILING. WHERE IT IS IMPOSSIBLE TO REMOVE THE CONDUIT, IT SHALL BE CUT OFF AND CAPPED OR
PLUGGED.
I. THE CONTRACTOR SHALL BE HELD FULLY RESPONSIBLE FOR THE PROPER RESTORATION OF ALL EXISTING SURFACES REQUIRED PATCHING, PLASTERING, PAINTING AND/OR OTHER REPAIR DUE TO THE INSTALLATION OF ELECTRICAL WORK UNDER THE TERMS OF THIS SPECIFICATION. CLOSE ALL OPENINGS, REPAIR ALL SURFACES, ETC., AS REQUIRED. THE CONTRACTOR SHALL EMPLOY QUALIFIED AND EXPERIENCED WORKMEN FOR THIS WORK. ALL RESTORATION WORK SHALL
BE SUBJECT TO THE APPROVAL OF THE ARCHITECT AND/OR THE COR/VA.
J. ALL TEMPORARY AND REMODELING WORK SHALL BE CONSIDERED A PART OF THIS CONTRACT AND NO EXTRA CHARGES WILL BE ALLOWED. THIS SHALL INCLUDE MINOR ITEMS OF MATERIAL OR EQUIPMENT NECESSARY TO MEET THE
REQUIREMENTS AND INTENT OF THE PROJECT.
K. EXAMINE ARCHITECTURAL, STRUCTURAL, AND MECHANICAL DRAWINGS AND SPECIFICATIONS TO DETERMINE THE SEQUENCE OF CONSTRUCTION THROUGHOUT THE PROJECT, INCLUDING EXISTING, TEMPORARY, REMODELED AND NEW
AREAS.
L. ALL ELECTRICAL CONNECTIONS REQUIRING AN OUTAGE SHALL BE MADE DURING AN APPROVED TIME LIMIT.
CHANGEOVERS SHALL BE AS SHORT A DURATION AS POSSIBLE AND SHALL NOT INTERFERE WITH NORMAL OPERATION OF THE COR/VA FACILITIES. NOTIFY COR/VA NO LESS THAN 21 DAYS (TWO WEEKS) IN ADVANCE OF A SHUTDOWN OF ANY ELECTRICAL CIRCUIT FOR CHANGEOVER, AND SUCH A CHANGEOVER SHALL BE DONE DURING HOURS AS DIRECTED BY COR/VA. WORK SHALL BE SCHEDULED SO THAT AT NO TIME WILL ANY EMERGENCY FEEDER, CIRCUIT, OR FIRE ALARM ZONE BE OUT OF SERVICE. PROVIDE NECESSARY TEMPORARY FEEDERS TO ACCOMPLISH THIS REQUIREMENT.
M. EXISTING LOW VOLTAGE WIRING WHICH WILL NOT BE MADE OBSOLETE AND WHICH WILL BE DISTURBED DUE TO CONSTRUCTION CHANGES REQUIRED BY THIS CONTRACT SHALL BE RESTORED TO CONDITION, OR POSITION, AS REQUIRED. PROPERLY RE-SECURE CABLE IN CHASES, CRAWL SPACES, TUNNELS, AND CEILING SPACES AS REQUIRED BY NEC. IN SOME CASES IT MAY BE NECESSARY TO ADD SUPPORTING HARDWARE TO ACCOMPLISH THIS REQUIREMENT.
N. IF POSSIBLE, ALL NEWLY INSTALLED RECEPTACLES SHALL BE INSTALLED IN SEPARATE OR ADJACENT STUD SPACES, TO AVOID SOUND TRANSMISSION AND WALL INTEGRITY ISSUES. ALL NEWLY INSTALLED RECEPTACLES LOCATED IN COMMON STUD SPACES OF FIRE-RESISTANT WALLS SHALL BE EQUIPPED WITH FIRE-RESISTANT PUTTY PADS AT THE BACK OF EACH
BOX IN ACCORDANCE WITH NEC 300.21.
120V DUPLEX RECEPTACLE
RECEPTACLE MODIFIERS:
AC: 3" ABOVE COUNTERTOP/BACKSPLASH
GFI: GROUND FAULT CURRENT INTERRUPTER
WP: WEATHERPROOF ENCLOSURE
DED: DEDICATED CIRCUIT
120V DUPLEX RECEPTACLE EMERGENCY OUTLET
AND COVER PLATE SHALL BE RED IN COLOR
120V QUADRUPLEX RECEPTACLE
120V QUADRUPLEX RECEPTACLE EMERGENCY
OUTLET AND COVER PLATE SHALL BE RED IN COLOR
JUNCTION BOX, WALL MOUNTED, PURPOSE AS NOTED
DISCONNECT SWITCH NON-FUSED
DISCONNECT SWITCH FUSED
SINGLE POLE WALL SWITCH: 48" AFF STANDARD UNO
SYMBOL HEIGHT DESCRIPTION
18"
18"
18"
18"
AS
NOTED
72" TOP
72" TOP
SWITCH MODIFIERS:
M: MOTOR-RATED
48"
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
TOP: HEIGHT TO TOP OF DEVICE
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.
SPECIAL RECEPTACLE
EQUIPMENT CONNECTION
AS
NOTED
E
208V DUPLEX RECEPTACLE18"
18"
120V DUPLEX RECEPTACLE FLOOR BOX
120V DUPLEX RECEPTACLE EMERGENCY FLOOR BOX
OUTLET AND COVER PLATE SHALL BE RED IN COLOR
120V QUADRUPLEX RECEPTACLE FLOOR BOX
120V QUADUPLEX RECEPTACLE EMERGENCY
FLOOR BOX OUTLET AND COVER PLATE SHALL BE
RED IN COLOR
CLNG
J
J
J
JUNCTION BOX, CEILING MOUNTED, PURPOSE AS
NOTED
JUNCTION BOX, FLOOR MOUNTED, PURPOSE AS
NOTED
120V SIMPLEX RECEPTACLE18"
2' X 2' RECESSED ARCHITECTURAL TROFFER
2' X 4' RECESSED ARCHITECTURAL TROFFER
SYMBOL
HEIGHT
AFF * DESCRIPTION
--- 2' X 4' RECESSED FLAT LENS TROFFER
4' LINEAR STRIP - SUSPENDED---
WALL SCONCE
6'-0"
CENTER
EXIT SIGN - WALL MOUNTED
EXIT SIGN - CEILING MOUNTED---
7'-5"
BOTTOM
SINGLE POLE WALL SWITCH
SWITCH MODIFIERS:
OS: OCCUPANCY SENSOR, LOW VOLTAGE,
DUAL TECHNOLOGY
VS: VACANCY SENSOR, LOW VOLTAGE,
DUAL TECHNOLOGY
DR: DUAL RELAY
VSD: VACANCY SENSOR, LINE VOLTAGE, DIMMER
OSD: OCCUPANCY SENSOR, LINE VOLTAGE, DIMMER
LV: LOW VOLTAGE
LVD: LOW VOLTAGE DIMMER
D: LINE VOLTAGE DIMMER
T: DIGITAL TIMER
K: KEYED
3: 3 WAY
4: 4 WAY
48"
CENTER
OCCUPANCY SENSOR - CEILING MOUNTED---
--- LOW VOLTAGE LIGHTING CONTROL DEVICE
OCCUPANCY SENSOR - WALL/CORNER MOUNTED---
EMERGENCY LIGHT BATTERY
OPERATED - WALL MOUNTED
7'-6"
CENTER
RC
* - ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.
LIGHT LEVEL SENSOR, SINGLE ZONE
DIMMING CLOSED LOOP - CEILING MOUNTED
--- LOW VOLTAGE LIGHTING CONTROL
DEVICE WITH 0-10V DIMMING
RCD
OS
OS
LS
BRANCH PANELS - PNL (FOLLOWED BY FLOOR, CRITICALITY OF PANEL, SECTION OF HOSPITAL, SUB LETTER OF PANEL):
1. PNL 1 LS A (A), 1LSA(B), 1LSA(C)
(FIRST FLOOR, “LIFE SAFETY”, SECTION OF HOSPITAL, SUB LETTER OF PANEL)
2. PNL 1 CR A (A)
(FIRST FLOOR, “CRITICAL” POWER, SECTION OF HOSPITAL, SUB LETTER OF PANEL)
3. PNL 1 EQ A (A)
(FIRST FLOOR, “EQUIPMENT” POWER, SECTION OF HOSPITAL, SUB LETTER OF PANEL)
4. PNL 1 N A (A), 1NA (B), 1NA(C)
(FIRST FLOOR, NORMAL POWER, SECTION OF HOSPITAL, SUB LETTER OF PANEL)
5. PNL 1 E A (A), 1EA(B)
(FIRST FLOOR, EMERGENCY POWER, SECTION OF HOSPITAL, SUB LETTER OF PANEL)
ALL DISTRIBUTION PANELS LISTED ABOVE SHOULD HAVE NAME PLAQUES PLACED ON THE OUTSIDE OF THE PANEL WITH THIS INFORMATION ON THEM. ALSO, THE PLAQUE WILL NEED TO HAVE THE VOLTAGE SIZE AND NUMBER OF PHASES FEEDING THE PANEL AND NUMBER OF FEEDER WIRES (120/208 3PH, 4W) (480V, 3PH, 4W) ALONG WITH THE PANEL'S LINE FEED PANEL NAME (E.G. PNL1EAB FED FROM DP1E). PLAQUES PLACED ON LIFE SAFETY, CRITICAL, EMERGENCY, AND EQUIPMENT PANELS THAT ARE EMERGENCY FED WILL BE SOLID RED WITH WHITE LETTERING AND ALL NORMAL POWER PANELS WILL BE LABELED WITH SOLID BLACK WITH WHITE LETTERING.
VERIFY EXACT NAME OF EACH PANEL WITH THE COR PRIOR TO ENGRAVING OF THE PHENOLIC LABELS.
Engineers Architects th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
VA Health Care System Approval:
Revision: Date:
ARCHITECT/ENGINEER:
JOHN COCHRAN DIVISION
915 NORTH GRAND BLVD - ST. LOUIS, MO 63106
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
FULLY SPRINKLERED
C U s e rs
\a m a s o n \D o c u m e n ts
\A M
E P
F
-J
C
-C
O R
E a m a s o n a c g
-p a
.c o m
.r v t
/2
/2
:2 :1
P
M
21-124 ELECTRICAL SYMBOLS,
ABBREVIATIONS AND NOTES
EHRM INFRASTRUCTURE UPGRADES 657-21-700JC
BID DOCUMENTS
KLCNOVEMBER 28, 2022 JKM
1 34
00-ET001
ELECTRICAL GENERAL NOTESELECTRICAL ABBREVIATIONS LIST
ELECTRICAL SYMBOL NOTES GENERAL ELECTRICAL DEMO NOTES
GENERAL ELECTRICAL REMODELING NOTES
ELECTRICAL SYMBOLS
LIGHTING SYMBOLS
GENERAL NOTES:
A. MANUFACTURER AND CATALOG NUMBERS SHOWN ARE FOR BASIS OF DESIGN, DESCRIPTIVE AND QUALITY STANDARDS ONLY, NOT TO BE USED FOR ORDERING WITHOUT VERIFICATION AND APPROVAL. CONTRACTOR TO PROVIDE PRODUCT OR EQUAL FOR APPROVAL BY COR, ARCHITECT AND ENGINEER. ENGINEER SHALL NOT BE RESPONSIBLE FOR MISMATCHED OR INACCURATE PART NUMBERS.
B. FOR ALL LED FIXTURES, THE FIXTURE SHALL BE CAPABLE OF SELF-RESETTING TO THE SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC PROTECTIVE MEASURES DISABLE THE LED LAMPS. PROVIDE A LETTER OR STATEMENT FROM THE MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT BROWNOUT PROTECTION, SHALL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY. PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.
C. LIGHTING CONTROLS, INCLUDING CONTROL SCHEMATICS, DEVICES, SWITCHES, SENSORS AND GRAPHIC DISPLAYS/CONTROLLERS. THIS INFORMATION MUST BE SUBMITTED WITH THE LIGHT FIXTURE SHOP...
LUMINAIRE SCHEDULE
TYPE DESCRIPTION MOUNTING LAMP DRIVER VOLTAGE WATTS MANUFACTURER MODEL NUMBER
E1 CONTEMPORARY LED SINGLE FACED EXIT SIGN WITH BLACK
POWDER PAINT ALUMINUM HOUSING, BRUSHED ALUMINUM
FACE, RED LETTERS, AND CHEVRON ARROWS AS SHOWN
ON PLANS.
UNIVERSAL LED RED --- MULTI-VOLT 5 W DUAL LITE SE S R BN
L1 48" LINEAR STRIP; STEEL HOUSING WITH WHITE ENAMELED
FINISH, CURVED, FROSTED ACRYLIC LENS, WIDE
DISTRIBUTION, BUY AMERICAN QUALIFIED
CABLE
SUSPEND
LED; 6,000
LUMENS; 80+
CRI; 4000K
FIXED OUTPUT LED
DRIVER, <10% thd, PF>0.95
MULTI-VOLT 50 W COLUMBIA MPS4-40HL-CW-EU
L2 2' X 4' ARCHITECTURAL TROFFER WITH CENTER LENS
DIFFUSER
RECESSED
GRID
LED; 3400
LUMENS; 80 CRI;
3500K
FIXED OUTPUT LED
DRIVER, <10% thd, PF>0.95
MULTI-VOLT 30 W COLUMBIA LCAT24-35 MW G E U
W1 EXTERIOR ARCHITECTURAL WALL PACK; SILVER FINISH;
WITH INTEGRAL PHOTOCELL
SURFACE
WALL
LED; 1800
LUMENS; 80 CRI;
4000K
ELECTRONIC MULTI-VOLT 18 W LITHONIA WDGE2 LED P2 40K 80CRI VF MVOLT SRM PE
CUSTOM SILVER
NEW PANEL NAMING LEGEND
DocuSign Envelope ID: 2F5F2D4F-7BA7-40B1-AEEB-B0D63C70C5C7
11/21/2022
TECHNOLOGY GENERAL NOTES
1. PROVIDE COMMUNICATIONS DEVICES AND EQUIPMENT IN ACCORDANCE WITH THE CONTRACT DOCUMENTS, MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT, LATEST EDITION OF THE NATIONAL ELECTRICAL CODE, BICSI STANDARDS, AND VA OIT
STANDARDS.
2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES AND EQUIPMENT WHERE BUILDING CONSTRUCTION IS NOT
SUITABLE FOR DIRECT MOUNTING.
3. FIRESTOP, DRAFTSTOP, SMOKESTOP OR PROTECT ANNULAR SPACE AROUND PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILINGS, AND ROOF IN ACCORDANCE WITH REQUIREMENTS OF NFPA 70, UL
LISTING REQUIREMENT AND APPLICABLE BUILDING CODES.
4. PROVIDE CABLING THAT COMPLIES WITH THE LATEST EDITION OF TELECOMMUNICATIONS DISTRIBUTION
METHOD MANUAL AND ANSI/TIA/EIA PUBLICATIONS.
5. COMPLY WITH THE LATEST ANSI/TIA/EIA 758 AND 607B OR 607A - GROUNDING AND BONDING REQUIREMENTS
FOR TELECOMMUNICATIONS IN COMMERCIAL BUILDING.
6. COMPLY WITH THE LATEST ANSI/TIA/EIA 568IEB - COMMERCIAL BUILDING TELECOMMUNICATIONS WIRING
STANDARD.
7. COMPLY WITH THE LATEST ANSI/TIA/EIA 569E - TELECOMMUNICATIONS PATHWAYS AND SPACES.
8. COMPLY WITH THE LATEST NFPA 70 NATIONAL ELECTRICAL CODE.
9. COMPLY WITH THE LATEST NFPA 99 HEALTHCARE FACILITIES CODE.
10. COMPLY WITH THE LATEST NFPA 101 LIFE SAFETY CODE.
11. COORDINATE WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION.
12. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES TO INDICATE A QUALITY STANDARD AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER.
PRODUCTS DEEMED EQUAL AND APPROVED BY THE COR WILL BE ACCEPTABLE. COMPLY WITH "BUY AMERICAN
ACT".
13. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, BOXES, OUTLET, OR EQUIPMENT UNLESS NOTED
OTHERWISE.
14. PROVIDE RGS OR EMT CONDUIT UNLESS OTHERWISE NOTED.
15. PROVIDE MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT LABEL LISTED BY APPROVED THIRD PARTY
TESTING AGENCY.
16. NOTIFY COR REGARDING DISCREPANCY BETWEEN PLANS AND SPECIFICATIONS FOR CLARIFICATION. THE
MORE STRINGENT OF THE THEM SHALL TAKE PRECEDENCE.
17. PROVIDE TIA/EIA 4PR UTP COPPER CABLES, JACKS AND CONNECTORS.
18. ALL WORK AREA OUTLETS SHALL BE 8 PIN, 8P8C KEYSTONE JACK WIRED PER T568A OR T568B AS DIRECTED BY
THE VA COR.
19. LABEL DEVICES IN ACCORDANCE WITH LATEST ANSI/TIA 606A OR 606B EDITION AS WELL AS THE STANDARDS
SET FORTH BY THE VA MC OIT.
20. PROVIDE A MINIMUM OF 12" CLEARANCE ABOVE THE CABLE TRAY PER TIA/EIA 569.B PARAGRAPH 4.5.6.2.
21. VA SHALL CONDUCT A WAP SURVEY AND PROVIDE THE SURVEY TO THE CONTRACTOR. CONTRACTOR SHALL INSTALL CABLING AND EQUIPMENT IN ACCORDANCE WITH THE SURVEY. COORDINATE WITH COR/OIT.
22. ALL CABLING INSTALLED ABOVE CEILING SHALL BE PLENUM RATED.
23. MINIMUM CONDUIT SIZE TO BE USED IS 1 1/4" CONDUIT.
24. DEVICES PLACED IN INTERCOMMUNICATION ROOM TO BE MOUNTED ON FIRE RETARDANT PLYWOOD.
25. PROVIDE OUTDOOR AND INDOOR CONDUITS,INNERDUCTS, TELECOM HANDHOLES, TELECOM MANHOLES, HANDHOLE COVERS, CABLING BOTH FIBER AND COPPER, SUPPORTS, TESTING, AND ALL RELATED MATERIALS
FOR A COMPLETE SYSTEM AS SHOWN HEREIN AND DESCRIBED IN THE SPECIFICATIONS.
26. PROVIDE CABLE TRAY, J-HOOKS, CONDUITS, JUNCTION BOXES, SUPPORTS FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, FLOOR SLEEVES, CORE DRILLING, CABLING BOTH FIBER AND COPPER, JACKS, TERMINATIONS, COVER PLATES, LABELING, PATCH PANELS, PATCH CORDS, CHANNEL RACKS,VERTICAL AND HORIZONTAL WIRE MANAGEMENT, GROUNDING BUS BARS, RACK MOUNTED GROUND BUS, GROUND CABLING, BONDING TO THE GROUNDING SYSTEM, GROUND CABLE IN THE CABLE AND LADDER TRAY, POWER STRIPS, PDU'S, UPD’S, UPS’S, TESTING AND RELATED MATERIALS FOR A COMPLETE CABLING SYSTEM AS SHOWN HEREIN AND AS
DESCRIBED IN THE SPECIFICATIONS.
27. PROVIDE J-HOOKS WHERE CABLE TRAY IS NOT SHOWN OR IF THERE IS OBSTRUCTION IN THE PATH OF THE CABLE TRAY, OR USE FLEXIBLE CONDUITS (NOT TO EXCEED 10 FEET), JUNCTION BOXES, FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, COVER PLATES, LABELING, SUPPORT J-HOOKS AND CONDUITS EVERY 4-5 FEET, AS SHOWN HEREIN AND AS DESCRIBED IN THE SPECIFICATIONS.
28. PROVIDE 12 PORT WALL MOUNTED COPPER PATCH PANEL IN THE EXISTING TR/FACILITY ROOM AND ANOTHER 12 PORT IN EACH NEW TR AND RUN 12- 4PR CAT 6A CABLE BETWEEN THESE TR’S TERMINATE AND TEST, LABEL
EACH PORT.
29. PROVIDE MULTI-SENSOR PANORAMIC SECURITY SURVEILLANCE TELEVISION SYSTEM (SSTV) CAMERAS, DVRS/NVRS, STORAGE, SOFTWARE, LICENSES, CONDUITS, JUNCTION BOXES, FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, CABLING ,COVER, JACKS, TERMINATIONS, COVER PLATES, LABELING, PATCH PANELS, PATCH CORDS, TESTING AND RELATED MATERIALS FOR A COMPLETE OPERATIONAL SSTV SYSTEM AS SHOWN HEREIN
AND AS DESCRIBED IN THE SPECIFICATIONS.
30. PROVIDE CARD READERS, DOOR CONTROLLERS, TR KEYPADS FOR PHYSICAL ACCESS AND CONTROL SYSTEM (PACS), SOFTWARE, LICENSES, CONDUITS, JUNCTION BOXES, FIRE AND SMOKE RATED SLEEVE ASSEMBLIES,CABLING ,COVER, JACKS, TERMINATIONS, COVER PLATES, LABELING, TESTING AND RELATED MATERIALS FOR A COMPLETE OPERATIONAL PACS SYSTEM AS SHOWN HEREIN AND AS DESCRIBED IN THE
SPECIFICATIONS.
31. PROVIDE NEW FIRE ALARM SYSTEM DEVICES, FIRE ALARM PANEL, NAC PANEL, POWER SUPPLY, FOR A
COMPLETE FIRE AND DETECTION SYSTEM, RED CONDUIT AND JUNCTION BOXES,COVER PLATES,
LABELING, CABLING BOTH COPPER AND FIBER, PROGRAMMING, SOFTWARE, LICENSES, FIRE AND SMOKE RATED SLEEVE ASSEMBLIES,CABLING ,COVER, JACKS, TERMINATIONS,TESTING AND RELATED MATERIALS FOR
A COMPLETE OPERATIONAL FIRE ALARM SYSTEM AS SHOWN HEREIN AND AS DESCRIBED IN THE
SPECIFICATIONS.
32. CAMERAS SHALL BE PANORAMIC MULTI-SENSOR AND SHALL MEET THE NATIONAL DEFENSE AUTHORIZATION
ACT-NDAA.
ADO AUTOMATIC DOOR OPERATOR
AFF ABOVE FINISH FLOOR
BOD BASIS OF DESIGN
CCTV CLOSED CIRCUIT TELEVISION
COAX COAXIAL CABLE
COMM COMMUNICATION
COR CONTRACTING OFFICER REPRESENTATIVE
DC DOOR CONTACT SWITCH
DN DOWN
DO DOOR OPERATOR
DVC DIGITAL VOICE COMMAND
DVR DIGITAL VIDEO RECORDER
EX EXISTING DEVICES
EEB EMERGENCY EXIT BUTTON
EL ELECTRICAL STRIKE
ETR EXISTING TO REMAIN
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FAAP FIRE ALARM ANNUNCIATOR PANEL
FO FIBER OPTIC
FAGAP FIRE ALARM GRAPHIC ANNUNCIATOR PANEL
IT INTERCOMMUNICATION ROOM
MATV MASTER ANTENNA TELEVISION
MM MULTI MODE FIBER
NAC NETWORK APPLIANCE CIRCUIT PANEL
N NEW DEVICES
NCA NETWORK CONTROL ANNUNCIATOR
NS NO SCALE
NTS NOT TO SCALE
NVR NETWORK VIDEO RECORDER
TECHNOLOGY ABBREVIATIONS LIST
OC ON CENTER
OIT OFFICE OF INFORMATION TECHNOLOGY
PACS PHYSICAL ACCESS CONTROL SYSTEM
PAMN PUBLIC ADDRESS AND MASS NOTIFICATION SYSTEM
PB PUSH BUTTON
PBB PRIMARY BONDING BUSBAR
PDU RACK POWER DISTRIBUTION UNITS
POE POWER OVER ETHERNET
PR PAIR
RBB RACK BONDING BUSBAR
RX REQUEST TO EXIT
SBB SECONDARY BONDING BUSBAR
SEP SERVICE ENTRANCE PROTECTION
SLC SIGNALING LINE CIRCUIT
SM SINGLE MODE FIBER
TBB TELECOM BONDING CONDUCTOR
TELTELEPHONE
TGB TELECOM GROUND BUS BAR
TM TELEMONITORING
TMGB TELECOM MAIN GROUND BUS BAR
TP TWISTED PAIR
TR TELECOM ROOM
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
WMWIRE MANAGEMENT
WAP WIRELESS ACCESS POINT
UL UNDERWRITERS LABORATORY
UPS UNINTERRUPTIBLE POWER SUPPLY
UTP UNSHIELDED TWISTED PAIR
CABLES AND CONNECTORS COLOR LEGEND
TELEPHONE
DESCRIPTION
ITEM JACK CABLE PATCH CABLES I.D. NOTES
DATA/COMPUTER
DATA/COMPUTER
WIRELESS
ACCESS POINT
FIBER - MULTI-MODE
FIBER - SINGLE-MODE
SOUND SYSTEM
NURSE CALL
MATV
CCTV - IP
IVORY
BLUE
YELLOW
GREEN
BLACK
IVORY
N/A
WHITE
N/A
N/A
IVORY
BLUE
YELLOW
GREEN
AQUA
YELLOW
GREEN
WHITE
YELLOW
BLACK
IVORY
BLUE
YELLOW
GREEN
AQUA
YELLOW
WHITE
N/A
N/A
N/A
T
C
C
WAP
FO
FO
SS
CCTV
4 PAIR CABLE
CCTV
4 PAIR CABLE
4 PAIR CABLE
4 PAIR CABLE
6/12/24/36
6/12
MULTI COLOR
CONDUCTORS
NC 4 PAIR UTP
MATV COAX RG6
PACS N/A GRAY N/A PACS
MULTI COLOR
CONDUCTORS
ACC ACCESSIBLE
ACLG ABOVE CEILING
A/E ARCHITECT/ENGINEER
AFF ABOVE FINISHED FLOOR
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
AL ALUMINUM
ALTALTERNATE
AMP AMPERE
APPRX APPROXIMATELY
ARCH ARCHITECT, ARCHITECTURAL
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
BOD BASIS OF DESIGN
C CONDUIT
CAB CABINET
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR-FURNISHED
CKT CIRCUIT
CLG CEILING
CO CONTRACTING OFFICE
COR CONTRACTING OFFICER
REPRESENTATIVE
dB DECIBEL
DN DOWN
DVC DIGITAL VOICE COMMAND
E EXISTING DEVICES
ELEV ELEVATOR
ETR EXISTING TO REMAIN
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FAAP FIRE ALARM ANNUNCIATOR PANEL
FAGAP FIRE ALARM GRAPHIC
ANNUNCIATOR PANEL
FO FIBER OPTIC
J-BOX JUNCTION BOX
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
METAL-CLAD (CONDUIT)
MECH MECHANICAL
MFR MANUFACTURER
MINMINIMUM
MISC MISCELLANEOUS
MT MOUNT
N NEW DEVICES
NAC NETWORK APPLIANCE CIRCUIT
PANEL
NCA NETWORK CONTROL ANNUNCIATOR
NS NO SCALE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
PA PUBLIC ADDRESS
PB PULL BOX OR PUSHBUTTON
PIV POST INDICATING VALVE
PVC POLYVINYL CHLORIDE (CONDUIT)
QTY QUANTITY
R REMOVE AND REPLACE IN NEW
LOCATION
RCP REFLECTED CEILING PLAN
REQD REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
SC SURFACE CONDUIT
SF SQUARE FEET/FOOT
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SIMSIMILAR
SPEC SPECIFICATION
SPKR SPEAKER
SR SURFACE RACEWAY
SS STAINLESS STEEL
STD STANDARD
SURF SURFACE MOUNTED
SYM SYMMETRICAL
SYS SYSTEM
TC TIMECLOCK
TELTELEPHONE
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TR TAMPER RESISTANT
TYP TYPICAL
UL UNDERWRITER'S LABORATORY
UTP UNSHIELDED TWISTED PAIR
1. PROVIDE FIRE ALARM SYSTEM AND COMPONENTS COMPLYING WITH THE LATEST:
A. NFPA 13- STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS.
B. NFPA 14- STANDARD FOR THE INSTALLATION OF STANDPIPE AND HOSE SYSTEM.
C. NFPA 20- STANDARD FOR THE INSTALLATION OF STATIONARY PUMPS FOR FIRE PROTECTION.
D. NFPA 70 NATIONAL ELECTRICAL CODE.
E. NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE.
F. NFPA 90A STANDARD FOR THE INSTALLATION OF AIR CONDITIONING AND VENTILATING SYSTEMS.
G. NFPA 101 LIFE SAFETY CODE.
H. VA FIRE PROTECTION DESIGN MANUAL.
I. ANSI S3.41 AUDIBLE EMERGENCY EVACUATION SIGNAL.
2. FIRE ALARM SYSTEM SHALL COMPLY WITH FACTORY MUTUAL RESEARCH CORPORATION (FM).
3. PROVIDE FIRE ALARM WIRING IN CONDUIT, FACTORY PAINTED RED.
4. BEFORE STARTING WORK, TEST EXISTING FIRE ALARM SYSTEM IN WORK AREA AND ADJACENT AREAS.
5. NOTIFY COR REGARDING DEFICIENCIES AND NON-OPERATING COMPONENTS. VA WILL MAKE REPAIRS.
6. CONTRACTOR TO ENSURE THAT ALL NEW FIRE ALARM SPEAKERS, TONES, AND STROBES ARE IN-SYNC WITH ALL ADJACENT AREAS BEYOND THE AREA OF WORK. WHEN WORK IS COMPLETE, TEST EXISTING FIRE ALARM SYSTEM IN WORK
AREA AND ADJACENT AREAS.
7. MAKE REPAIRS TO RESOLVE INCORRECT SYSTEM OPERATIONS AT NO ADDITIONAL COST.
8. THE FIRE ALARM SYSTEM VENDOR/CONTRACTOR SHALL TERMINATE, TEST AND PROGRAM ALL NEW FIRE ALARM DEVICES.
COORDINATE WITH COR.
9. CONNECT SPRINKLER SYSTEM SUPERVISORY DEVICES TO THE FIRE ALARM SYSTEM. COORDINATE LOCATION WITH THE
SPRINKLER CONTRACTOR.
10. CONNECT ALL ELECTROMAGNETIC DOOR HOLD OPEN DEVICES TO THE FIRE ALARM SYSTEM. COORDINATE WITH THE
DOOR HARDWARE CONTRACTOR.
11. PROVIDE RELAY CONTROL MODULES FOR PACS, COORDINATE WITH PHYSICAL ACCESS CONTROL SYSTEM (PACS), CONTRACTOR AND COR.
12. PROVIDE RELAY CONTROL MODULES FOR COOKING POWER SUPPLY SHUT OFF.
13. PROVIDE RELAY CONTROL MODULES FOR KITCHEN HOOD FIRE SUPPRESSION SYSTEM.
14. THE OPERABLE PART OF A MANUAL ACTUATED ALARM INITIATING DEVICE SHALL BE NOT LESS THAN 42" (1.07M) AND NOT
MORE THAN 48" (1.22M) FROM FINISH FLOOR.
15. FOR LOCATION (CORRIDOR, ROOM OR ADJACENT SPACE) WITH TWO OR MORE VISIBLE FIRE ALARM NOTIFICATION APPLIANCES WITHIN THE FIELD OF VIEW, PROGRAM VISIBLE TO FLASH IN SYNCHRONIZATION.
FIRE ALARM PULL STATION
SYMBOL HEIGHT DESCRIPTION
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
TOP: HEIGHT TO TOP OF DEVICE
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.
F
F
S
FIRE ALARM SPEAKER
FIRE ALARM STROBE
FIRE ALARM SPEAKER AND STROBE
FIRE ALARM DOOR OPEN HOLDER
FIRE ALARM PHOTOELECTRIC SMOKE DETECTOR
FIRE ALARM CEILING MOUNTED SPEAKER
DD FIRE ALARM DUCT SMOKE DETECTOR
FIRE ALARM HEAT DETECTOR
42"-48"
90"
90"
90"
FIRE ALARM CONTROL PANEL
FIRE ALARM NAC PANEL
FIRE ALARM ANNUNCIATOR PANEL
FLOW SWITCH
FACP
NAC
FAAP
TAMPER SWITCH
POST INDICATOR VALVEPIV
REMOTE LIGHT/TEST SWITCH FOR DUCT DETECTORS
F FIRE ALARM BELL90"
XX - CANDELA
XX - CANDELA
XX - WATTAGEF
S
F
S
HD
SD
WALL
CEILING
CEILING
CEILING
6'
6'
6'
6'
FIRE ALARM GRAPHIC ANNUNCIATOR PANELFAGAP 6'
TECHNOLOGY SYMBOL LEGEND
DATA OUTLET - N-4 PR UTP
TELCO OUTLET - N-4 PR UTP
SYMBOL HEIGHT DESCRIPTION
18"
48"
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.
SEE DRAWINGS FOR MORE INFORMATION.
NOTE: NOT ALL SYMBOLS ARE USED.
ELECTRONIC LOCKING MECHANISM
DOOR CONTACT
REQUEST FOR EXIT SENSOR
CARD READER
(K - KEYPAD)
48"CR
ES
DC
RX
48" EMERGENCY EXIT BUTTON TO RELEASE DOOR (EEB)
WIRELESS ACCESS POINT - N-4 PR UTP
WALL PHONEW
N
S
NURSE CALL PATIENT STATION WITH PILLOW SPEAKER
2 ADDITIONAL PUSHBUTTONS, 1/4 RECEPTACLE AND COVER
(1 - SINGLE, 2 - DUAL, V - VANDAL RESISTANT)
P NURSE CALL PATIENT BED INTERFACE RECEPTACLE
B NURSE CALL CODE BLUE STATION WITH COVER
E NURSE CALL EMERGENCY STATION WITH PULL CORD AND AUDIO +40" AFF IN
RESTROOM, +72" AFF IN SHOWER (V - VANDAL RESISTANT, PB - PUSH BUTTON)
D NURSE CALL DUTY STATION
M NURSE CALL MASTER STATION/CONSOLE
NURSE CALL DOME LIGHT
(Z - ZONE LIGHT, V - VANDAL RESISTANT)
IC
INTERCOM WITH CAMERA
IC
INTERCOM MASTER WITH PUSH TO RELEASE DOORM
NURSE CALL WIRELESS ANTENNASNW
N
TV OUTLET WALL MOUNTED
48"
54"
DESK
CCTV DOME CAMERA FIXED
CCTV DOME CAMERA PAN/TILT/ZOOM
FOUR POST OIT EQUIPMENT RACK
OIT EQUIPMENT CABINET
NURSE CALL EQUIPMENT CABINET
MATV EQUIPMENT CABINET
CCTV EQUIPMENT CABINET
NCE
MATV
CCTV
LADDER CABLE TARY
N
N
FLOOR BOX FOR DATA
AS NOTED
DOOR
DOOR
ABOVE
DOOR
HEADWALL
18"
HEADWALL
/40"
40", 72"
18"
60"
CEILING
CEILING
6' TO TOP
6' TO TOP
FLOOR
PHYSICAL ACCESS CONTROL SYSTEMPACS 6' TO TOP
ELECTRONIC PANIC HARDWAREEP
DO DOOR OPERATOR
HANDWAVE
T
C
NURSE CALL STAFF TERMINAL
NURSE CALL PATIENT STATION WITH CALL CORD.
(1 - SINGLE, 2 - DUAL, V - VANDAL RESISTANT)
60"
HEADWALL
W WIRELESS PENDANT
L
KP PATIENT ROAM ALERT ACCESS CONTROL KEYPAD48"
PATIENT ROAM ALERT ANTENNACEILING
GROUND BUS
CEILING
DOOR
DOOR
48"
ABOVE
DOOR
NURSE CALL DOME LIGHT
FLOOR
FLOOR
FLOOR
ABOVE
CEILING
18"
4'x8'x3/4" FIRE RATED TTB8"
N
M
PATIENT STATION (PB - PUSH BUTTON, M - MICROPHONE, K -KEYED)
88" MOTION DETECTOR
MD
FLOOR TWO POST OIT EQUIPMENT RACK
CEILING MOUNTED SPEAKERSCEILING
WALL MOUNTED SPEAKERS96"
S
S
AREA OF REFUGE PANEL6' TO TOP
AREA OF REFUGE ANNUNCIATION PANEL6' TO TOP
AOF
AOFA
IC AREA OF REFUGE INTERCOM48"
AREA OF REFUGE STROBE LIGHTCEILINGSL
DP
DPP
DURESS PANIC ALARM PUSH BUTTON48"
DURESS PANIC ALARM PANEL6' TO TOP
N
SECURE WIRELESS ACCESS POINT - N-4 PR UTP
N
CEILING
S
(N - QUANTITY)
(N - QUANTITY)
(N - QUANTITY)
(N - QUANTITY)
CEILING
48"
CEILING
CEILING
TELEMETRY ANTENNA - 2-4 PRCEILING
ROBOT PHARMACY ANTENNA - 1-4 PRCEILINGR
Engineers Architects th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
VA Health Care System Approval:
Revision: Date:
ARCHITECT/ENGINEER:
JOHN COCHRAN DIVISION
915 NORTH GRAND BLVD - ST. LOUIS, MO 63106
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
FULLY SPRINKLERED
C U s e rs
\a m a s o n \D o c u m e n ts
\A M
E P
F
-J
C
-C
O R
E a m a s o n a c g
-p a
.c o m
.r v t
/2
/2
:2 :1
P
M
21-124 TECHNOLOGY SYMBOLS,
ABBREVIATIONS AND NOTES
EHRM INFRASTRUCTURE UPGRADES 657-21-700JC
BID DOCUMENTS
KLCNOVEMBER 28, 2022 JKM
2 34
00-ET002
FIRE ALARM ABBREVIATIONS LIST
FIRE ALARM GENERAL NOTES
FIRE ALARM SYMBOLS
OS
M
M
E
E
J
M
C R
DC ES RX
SD
FS
ELEC
A016A
OI&T
A017A
HAC
A017
F.E.
CLOSET
B682
STAIR 01
S001OFFICE
A019
OFFICE /
STORAGE
A016
CHASE
CH-A-1
6810 7
G.9
H
I
6810 7
G.9
H
I
ELEC
A016A
OI&T
A017A
HAC
A017
F.E.
CLOSET
B682
STAIR 01
S001OFFICE
A019
OFFICE /
STORAGE
A016
CHASE
CH-A-1
TELECOM
T001
L1L1
L1
CHASE
CH-A-1
OFFICE
A019
STAIR 01
S001
OFFICE /
STORAGE
A016
TOILET,
MALE
A015
6810 7
G.9
H
I
ELEC
A016A
OI&T
A017A
HAC
A017
F.E.
CLOSET
B682
STAIR 01
S001
OFFICE
A019
OFFICE /
STORAGE
A016
CHASE
CH-A-1
TELECOM
T001
6810 7
G.9
H
I
PANEL 'A'
PANEL 'B'
A B
A
B
B
A
A B
N
A
B
1-FCU-T001
1-FCU-A016
1-FCU-A019
ELEC
A016A
OI&T
A017A
HAC
A017
F.E.
CLOSET
B682
STAIR 01
S001OFFICE
A019
OFFICE /
STORAGE
A016
CHASE
CH-A-1
6810 7
G.9
H
I
ELEC
A016A
OI&T
A017A
HAC
A017
F.E.
CLOSET
B682
STAIR 01
S001OFFICE
A019
OFFICE /
STORAGE
A016
CHASE
CH-A-1
TELECOM
T001
6810 7
G.9
H
I
K
15cd
# KEY NOTES:
# KEY NOTES:
Engineers Architects th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
VA Health Care System Approval:
Revision: Date:
ARCHITECT/ENGINEER:
JOHN COCHRAN DIVISION
915 NORTH GRAND BLVD - ST. LOUIS, MO 63106
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
FULLY SPRINKLERED
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREAS S S S
C U s e rs
\a m a s o n
\D o c u m e n ts \A
M E
P F
-J
C
-0 a m a s o n a c g
-p a
.c o m
.r v t
/2
/2
:0
:0
P
M
21-124 BUILDING 1, GROUND, TELECOM
ROOM T001 PLANS
EHRM INFRASTRUCTURE UPGRADES 657-21-700JC
BID DOCUMENTS
KLCNOVEMBER 28, 2022 JKM
3 34
01-ET401
NORTH
0 2 4 8
Scale: 1/4" = 1'-0"
TELECOM ROOM T001, POWER DEMOLITION PLAN
NORTH
0 2 4 8
Scale: 1/4" = 1'-0"
TELECOM ROOM T001, CEILING PLAN
NORTH
0 2 4 8
Scale: 1/4" = 1'-0"
TELECOM ROOM T001, CEILING DEMOLITION PLAN
NORTH
0 2 4 8
Scale: 1/4" = 1'-0"
TELECOM ROOM T001, POWER PLAN
Scale: 1/4" = 1'-0"
TELECOM ROOM T001, SYSTEMS DEMOLITION PLAN
Scale: 1/4" = 1'-0"
TELECOM ROOM T001, SYSTEMS PLAN
NORTH
0 2 4 8
NORTH
0 2 4 8
A. ALL EXISTING CONDITIONS, CONDUITS AND
DEVICES ARE BASED ON THE BEST AVAILABLE
INFORMATION AT THE TIME OF SURVEY AND
VISUAL INSPECTION. VERIFY EXISTING
CONDITIONS.
B. DEVICES SHOWN WITH LIGHT, GRAY LINES ARE
EXISTING TO REMAIN. DEVICES SHOWN WITH
DARK, DASHED LINES ARE EXISTING TO BE
DEMOLISHED. DEMOLITION SHALL INCLUDE, BUT
NOT BE LIMITED TO, THOSE DEVICES AND
SYSTEMS SHOWN. COORDINATE WITH ALL
OTHER DISCIPLINES.
C. AT ALL TIMES, FIRE SERVICES ARE TO REMAIN
ACTIVE OUTSIDE THE DESIGNATED DEMOLITION
AREA NOTED ON THE PLANS.
D. REMOVE ALL UNUSED CONDUIT AND CABLING.
E. WHERE CONDUIT IS REMOVED FROM AN
EXISTING RATED ASSEMBLY NOT SUBJECT TO
DEMOLITION, THE REMAINING PENETRATION
SHALL BE PATCHED AND REPAIRED TO MAINTAIN
THE RATING OF THE ASSEMBLY.
F. COORDINATE ALL WORK BETWEEN TRADES AND
DISCIPLINES.
G. SEE SHEET 01-ET501 FOR ALL TYPICAL DETAILS
AND NOTES FOR ALL TELECOM ROOMS.
1 NO POWER DEMOLITION WORK IN THIS AREA.
2 EXISTING WINDOW MOUNTED AIR
CONDITIONING UNIT T0 BE REMOVED.
MAINTAIN EXISTING CIRCUIT FOR REUSE.
3 NO SYSTEMS DEMOLITION WORK IN THIS
AREA.
4 NO CEILING DEMOLITION WORK IN THIS
AREA.
5 EXISTING LIGHT FIXTURE TO BE RELOCATED,
PROTECT DURING CONSTRUCTION, CLEAN
AND RELAMP AS NEEDED BEFORE
RE-INSTALLATION. MAINTAIN EXISTING
LIGHTING CIRCUIT AND CONTROLS FOR
REUSE.
1 CIRCUIT FROM DEMOLISHED WINDOW
MOUNTED AIR CONDITIONING UNIT CIRCUIT
MAINTAINED DURING DEMOLITION.
2 RELOCATED LIGHT FIXTURE. RE-CONNECT
TO EXISTING LIGHTING CIRCUIT AND
CONTROLS MAINTAINED DURING
DEMOLITION.
N
KEY PLAN
SCALE: NO SCALE
M
J
S S
S
S S
S
OS
S S
S
S S
S
S S
S
CR
DC RXES
S S
S
J
L
K
B
A
B A
B
A
B
A
N
PANEL 'A'
PANEL 'B'
BA
OFFICE
B008
TR
B009
CORRIDOR
H011
STORAGE
J
L
K
1 2
OFFICE
B008
TR
B009
J
L
K
L1
L1
OFFICE
B008
TR
B009
J
L
K
OFFICE
B008
TR
B009
J
L
K
OFFICE
B008
TR
B009
J
L
K
K
OFFICE
B008
TR
B009
# KEY NOTES:
# KEY NOTES:
Engineers Architects th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
VA Health Care System Approval:
Revision: Date:
ARCHITECT/ENGINEER:
JOHN COCHRAN DIVISION
915 NORTH GRAND BLVD - ST. LOUIS, MO 63106
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
FULLY SPRINKLERED
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREAS S S S
C U s e rs
\a m a s o n
\D o c u m e n ts \A
M E
P F
-J
C
-0 a m a s o n a c g
-p a
.c o m
.r v t
/2
/2
:0
:1
P
M
21-124 BUILDING 1, GROUND, TELECOM
ROOM B009 PLANS
EHRM INFRASTRUCTURE UPGRADES 657-21-700JC
BID DOCUMENTS
KLCNOVEMBER 28, 2022 JKM
4 34
01-ET402
Scale: 1/4" = 1'-0"
TELECOM ROOM B009,
POWER PLAN
Scale: 1/4" = 1'-0"
TELECOM ROOM B009,
POWER DEMOLITION PLAN
Scale: 1/4" = 1'-0"
TELECOM ROOM B009,
CEILING PLAN
Scale: 1/4" = 1'-0"
TELECOM ROOM B009,
CEILING DEMOLITION PLAN
NORTH
0 2 4 8
NORTH
0 2 4 8
NORTH
0 2 4 8
NORTH
0 2 4 8
Scale: 1/4" = 1'-0"
TELECOM ROOM B009,
SYSTEMS DEMOLITION
PLAN
Scale: 1/4" = 1'-0"
TELECOM ROOM B009,
SYSTEMS PLAN
NORTH
0 2 4 8
NORTH
0 2 4 8
A. ALL EXISTING CONDITIONS, CONDUITS AND
DEVICES ARE BASED ON THE BEST AVAILABLE
INFORMATION AT THE TIME OF SURVEY AND
VISUAL INSPECTION. VERIFY EXISTING
CONDITIONS.
B. DEVICES SHOWN WITH LIGHT, GRAY LINES ARE
EXISTING TO REMAIN. DEVICES SHOWN WITH
DARK, DASHED LINES ARE EXISTING TO BE
DEMOLISHED. DEMOLITION SHALL INCLUDE, BUT
NOT BE LIMITED TO, THOSE DEVICES AND
SYSTEMS SHOWN. COORDINATE WITH ALL
OTHER DISCIPLINES.
C. AT ALL TIMES, FIRE SERVICES ARE TO REMAIN
ACTIVE OUTSIDE THE DESIGNATED DEMOLITION
AREA NOTED ON THE PLANS.
D. REMOVE ALL UNUSED CONDUIT AND CABLING.
E. WHERE CONDUIT IS REMOVED FROM AN
EXISTING RATED ASSEMBLY NOT SUBJECT TO
DEMOLITION, THE REMAINING PENETRATION
SHALL BE PATCHED AND REPAIRED TO MAINTAIN
THE RATING OF THE ASSEMBLY.
F. COORDINATE ALL WORK BETWEEN TRADES AND
DISCIPLINES.
G. SEE SHEET 01-ET501 FOR ALL TYPICAL DETAILS
AND NOTES FOR ALL TELECOM ROOMS.
1 DISCONNECT MECHANICAL EQUIPMENT.
REMOVE WIRING AND CONDUIT BACK TO LAST
OPERABLE DEVICE OR PANELBOARD.
2 DISCONNECT AND REMOVE RECEPTACLE.
REMOVE WIRING AND CONDUIT BACK TO LAST
OPERABLE DEVICE OR PANELBOARD.
3 DISCONNECT AND REMOVE LIGHT SWITCH.
REMOVE WIRING AND CONDUIT BACK TO LAST
OPERABLE DEVICE OR PANELBOARD.
4 DISCONNECT AND REMOVE LIGHTING FIXTURE.
REMOVE WIRING AND CONDUIT BACK TO LAST
OPERABLE DEVICE OR PANELBOARD.
5 DISCONNECT AND REMOVE EXISTING
EQUIPMENT RACK.
6 DISCONNECT AND REMOVE CAMERA. RETAIN
CONDUIT AND CABLING FOR NEW WORK.
N
KEY PLAN
SCALE: NO SCALE
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
S
E
M
J
S S
S S
S S
S
S S
S S
S S
S
RX
ES
DC
C R
S S
S S
S S
S
STORAGE
DB16
WORK
RM.
DB10
OFFICE
DB15A
TR
DB15B
OI&T
DB14A
TOILET
DB12
TOILET
DB11
CORRIDOR
H027
TOILET,
MALE
DB17
10-A11-A12-A
A.1-A
8.7-A
S-A
R-A
L1 L1
STORAGE
DB16
WORK
RM.
DB10
OFFICE
DB15A
OI&T
DB14A
TOILET
DB12
TOILET
DB11
CORRIDOR
H027
TOILET,
MALE
DB17
CORRIDOR
H024
10-A11-A12-A
A.1-A
8.7-A
S-A
R-A
OFFICE
DB15B
STORAGE
DB16
WORK
RM.
DB10
OFFICE
DB15A
OI&T
DB14ATOILET
DB12
TOILET
DB11
CORRIDOR
H027
TOILET,
MALE
DB17
TOILET
DB12
TOILET
DB11
10-A11-A12-A
A.1-A
8.7-A
S-A
R-A
1 2
OFFICE
DB15B
STORAGE
DB16
WORK
RM.
DB10
OFFICE
DB15A
TR
DB15B
OI&T
DB14ATOILET
DB12
TOILET
DB11
CORRIDOR
H027
TOILET,
MALE
DB17
TOILET
DB12
TOILET
DB11
10-A11-A12-A
A.1-A
8.9-A
S-A
R-A
N
PANEL 'B'
BA
PANEL 'A'
B
A
A B
B A
A
B
1-FCU-DB15B
STORAGE
DB16
WORK
RM.
DB10
OFFICE
DB15A
OI&T
DB14ATOILET
DB12
TOILET
DB11
CORRIDOR
H027
TOILET,
MALE
DB17
TOILET
DB12
TOILET
DB11
10-A11-A12-A
A.1-A
8.7-A
S-A
R-A
OFFICE
DB15B
STORAGE
DB16
WORK
RM.
DB10
OFFICE
DB15A
TR
DB15B
OI&T
DB14ATOILET
DB12
TOILET
DB11
CORRIDOR
H027
TOILET,
MALE
DB17
TOILET
DB12
TOILET
DB11
10-A11-A12-A
A.1-A
8.9-A
S-A
R-A
K
# KEY NOTES:
Engineers Architects th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
VA Health Care System Approval:
Revision: Date:
ARCHITECT/ENGINEER:
JOHN COCHRAN DIVISION
915 NORTH GRAND BLVD - ST. LOUIS, MO 63106
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
FULLY SPRINKLERED
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREAS S S S
C U s e rs
\a m a s o n
\D o c u m e n ts \A
M E
P F
-J
C
-0 a m a s o n a c g
-p a
.c o m
.r v t
/2
/2
:0
:2
P
M
21-124 BUILDING 1, GROUND, TELECOM
ROOM DB15B PLANS
EHRM INFRASTRUCTURE UPGRADES 657-21-700JC
BID DOCUMENTS
KLCNOVEMBER 28, 2022 JKM
5 34
01-ET403
Scale: 1/4" = 1'-0"
TELECOM ROOM DB15B
CEILING PLAN
Scale: 1/4" = 1'-0"
TELECOM ROOM DB15B
CEILING DEMOLITION PLAN
Scale: 1/4" = 1'-0"
TELECOM ROOM DB15B
POWER DEMOLITION PLAN
Scale: 1/4" = 1'-0"
TELECOM ROOM DB15B
POWER PLAN
NORTH
0 2 4 8
NORTH
0 2 4 8
NORTH
0 2 4 8
NORTH
0 2 4 8
Scale: 1/4" = 1'-0"
TELECOM ROOM DB15B
SYSTEMS DEMOLITION
PLAN
Scale:…