ATTACHMENT 4 - Architectural Drawings.pdf
PDF 18 MB Posted
- Attached to
- Y1BG--EHRM Infrastructure Upgrades Construction John Cochran Federal contract opportunity
- Solicitation number
- 36C77623B0034
About this file
This document provides details for a federal contract solicitation to upgrade infrastructure at a Veterans Affairs medical center. The St. Louis John Cochran VAMC is seeking a general contractor to construct twenty-four new telecommunication rooms in Building 1. The scope of work includes electrical panel upgrades and installation of power, bonding, UPS, and a building management system. It also requires assessment and potential upgrades or expansion of HVAC, demolition and new construction of spaces, finishes installation, construction of an exterior telecommunications tower, installation of new and upgraded data outlets and patch panels with Cat 6A cable. Additional requirements encompass physical security upgrades, assessment and upgrade of the fiber infrastructure backbone campus wide within Building 1, and hazardous material abatement as needed. The solicitation number is 36C77623B0034 and was issued by the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas. The response due date and contract award date are not provided in this document.
View the file
Other files for this federal contract opportunity
Show all 32
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AFF ABOVE FINISHED FLOOR
ACP/APC ACOUSTIC CEILING PANEL/
ACOUSTIC PANEL CEILING
ACT ACOUSTIC(AL) TILE
ADJ ADJUSTABLE
ADT'L ADDITIONAL
AGG AGGREGATE
ALT ALTERNATE
AL ALUMINUM
APPROX APPROXIMATE(LY)
ASPH ASPHALT
AUTO AUTOMATIC
B/O BOTTOM OF
BD BOARD
BLDG BUILDING
BLKG BLOCKING
BOT BOTTOM
BRG BEARING
CENTERLINE
C/C CENTER TO CENTER
CJ CONTROL JOINT
CLL CONTRACT LIMIT LINE
CEM CEMENT(ITIOUS)
CMU CONCRETE MASONRY UNIT
CLG CEILING
CLR CLEAR
COL COLUMN
CONC CONCRETE
CONST CONSTRUCTION
CONT CONTINUOUS
CPT CARPET
CT CERAMIC TILE
CTR CENTER(ED)
DF DRINKING FOUNTAIN
DS DOWNSPOUT
DBL DOUBLE
DEG DEGREE
DEMO DEMOLITION
DET/DTL DETAIL
DIA DIAMETER
DIM DIMENSION
DN DOWN
DWG(S) DRAWING(S)
E EAST
EC ELECTRICAL CONTRACTOR
EHO ELECTRICAL HOLD OPEN
EJ EXPANSION JOINT
EW EACH WAY
EA EACH
EIFS EXTERIOR INSULATION
FINISH SYSTEM
EL ELEVATION
ELEC ELECTRIC(AL)
ELEV ELEVATOR
EMER EMERGENCY
EQ EQUAL
EQUIP EQUIPMENT
EXIST EXISTING
EXT EXTERIOR
EWC ELECTRIC WATER COOLER
FD FLOOR DRAIN
FE FIRE EXTINGUISHER
FFE FINISH FLOOR ELEVATION
FV FIELD VERIFY
FEC FIRE EXTINGUISHER CABINET
FDN FOUNDATION
FIN FINISH
FLSHG FLASHING
FLR FLOOR
FRMG FRAMING
FT FOOT/FEET
FTG FOOTING
GC GENERAL CONTRACTOR
GA GAUGE
GALV GALVANIZED
GEN GENERAL
GYP GYPSUM
HM HOLLOW METAL
HDWR HARDWARE
HOL HOLLOW
HOR HORIZONTAL
HT HEIGHT
HVAC HEATING/VENTILATION/AIR
CONDITIONING
ID INSIDE DIAMETER
IN INCH
INCL INCLUDING
INSUL INSULATION
INT INTERIOR
JAN JANITOR
JT JOINT
LAV LAVATORY
LB(S) POUND(S)
L/S LANDSCAPE
LT LIGHT
MO MASONRY OPENING
MAS MASONRY
MAT'L MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MTD MOUNTED
MTL METAL
N NORTH
NIC NOT IN CONTRACT
NTS NOT TO SCALE
NOM NOMINAL
OC ON CENTER
OD OUTSIDE DIAMETER
O TO O OUT TO OUT
OPNG OPENING
OPP OPPOSITE
OVHD OVERHEAD
PEB PRE-ENGINEERED BUILDING
PJF PREFORMED JOINT FILLER
PT PRESSURE TREATED
PERIM PERIMETER
PL PLATE
PLAM PLASTIC LAMINATE
PLBG PLUMBING
PLYWD PLYWOOD
PNT PAINT
PR PAIR
PTD PAINTED
PWR POWER
RB RUBBER BASE
RD ROOF DRAIN
RO ROUGH OPENING
RAD RADIUS
REC RECESSED
REINF REINFORCED
REQ'D REQUIRED
REV REVISED (REVISION)
RM ROOM
S SOUTH
SB SPLASH BLOCK
SF SQUARE FEET
SS STAINLESS STEEL
SIM SIMILAR
SPEC SPECIFICATIONS
SQ SQUARE
STD STANDARD
STL STEEL
STOR STORAGE
STRUCT STRUCTURAL
SUSP SUSPENDED
T&G TONGUE AND GROOVE
T/O TOP OF
TELE TELEPHONE
TRTD TREATED
TS TUBE STEEL
TYP TYPICAL
UNFIN UNFINISHED
UNO UNLESS NOTED OTHERWISE
VCT VINYL COMPOSITION TILE
VIF VERIFY IN FIELD
VERT VERTICAL
W WEST
W/ WITH
W/O WITHOUT
WC WATER CLOSET
WWF WELDED WIRE FABRIC
WD WOOD
WH WATER HEATER
WT WEIGHT
CL
DEMOLITION KEYNOTE
WINDOW TYPE DOOR NUMBERTYPICAL KEYNOTE CEILING/ SOFFIT
HEIGHT
MATL
1'-0"
1#
1. INDICATIONS OF PROJECT LIMITS OR LINES OF DEMARCATION ARE SHOWN FOR GENERAL SCOPE DEFINITION AND REFLECT THE UNDERSTANDING OF THE ARCHITECT AS TO THE LIMITATIONS OF THE WORK AREA IN AN OCCUPIED AREA. ACTUAL CONTRACT LIMITS ARE TO BE DETERMINED BY AGREEMENT BETWEEN THE COR AND
CONTRACTOR BEFORE THE START OF THE WORK.
2. DRAWINGS ARE PREPARED USING PRODUCT DIMENSIONS AND DETAILS FROM BASIS OF DESIGN PRODUCT.
PRODUCTS MAY CHANGE IN DIMENSION AND DETAIL BEFORE THEY ARE INCORPORATED INTO
WORK. PRODUCTS FROM OTHER MANUFACTURER’S ARE ALSO ACCEPTABLE. DIMENSIONS AND DETAILS FOR ALTERNATE PRODUCTS MAY VARY FROM BASIS OF DESIGN. CONTRACTOR SHALL VERIFY INSTALLATION REQUIREMENTS FOR ALL PRODUCTS TO BE INCORPORATED INTO WORK (INCLUDING THICKNESS FOR RECESSED OR SEMI-RECESSED PRODUCTS) AND IS REPONSIBLE FOR ACCOMODATING AND COORDINATING CHANGES TO OTHER MATERIALS OR PRODUCTS THAT ARE NECESSARY BECAUSE OF THESE DIFFERENCES.
3. THE DRAWINGS AND SPECIFICATIONS ARE SEPARATED INTO DISCIPLINES FOR CONVENIENCE. THE SEPARATIONS ARE USED ONLY FOR THE PURPOSES OF CONVENIENCE AND REFERENCE AND IN NO WAY DO THEY DEFINE OR LIMIT THE SCOPE OR INTENT OF ANY PART OF THE DRAWINGS AND SPECIFICATIONS AS A WHOLE. THE FACT THAT THE DRAWINGS ARE SEPARATED IN NO WAY SUGGESTS THAT THE WORK IS NOT TO
BE CONSTRUCTED AS A COMPLETE, INTEGRATED AND UNIFIED WHOLE.
4. THE DRAWINGS AND SPECIFICATIONS, INCLUDING DRAWINGS PREPARED BY SPECIFIC ENGINEERING DISCIPLINES ARE COMPLEMENTARY; ITEMS SHOWN IN ANY ONE LOCATION IN THE DRAWINGS SHALL BE CONSIDERED TO BE REQUIREMENTS OF THE CONTRACT FOR CONSTRUCTION. IN THE EVENT OF AN INCONSISTENCY BETWEEN THE DRAWINGS AND SPECIFICATIONS, OR WITHIN EITHER DOCUMENT, THE CONTRACTOR SHALL SEEK CLARIFICATION OR INTERPRETATION FROM THE COR PRIOR TO BIDDING. WHERE INCONSISTENCIES ARE NOT CLARIFIED PRIOR TO BIDDING, AND WHERE THE ACTUAL SOLUTION OR INTENT CANNOT BE REASONABLY INFERRED, THE CONTRACTOR SHALL PROVIDE THE BETTER QUALITY OR GREATER
QUANTITY OF WORK.
5. THE CONTRACTOR SHALL NOTIFY THE COR IMMEDIATELY SHOULD DISCREPANCIES BE FOUND IN THE
DRAWINGS AND SPECIFICATIONS.
6. THE CONTRACTOR IS RESPONSIBLE FOR CHECKING ALL FIELD CONDITIONS AND DIMENSIONS AS THEY RELATE TO THIS PROJECT, FOR EACH PHASE. SHOULD DISCREPANCIES EXIST BETWEEN THE WORK INDICATED AND
ACTUAL FIELD CONDITIONS, NOTIFY THE COR PRIOR TO PROCEEDING WITH THE WORK.
7. DO NOT SCALE THE DRAWINGS. DRAWING SCALES AS INDICATED ARE FOR REFERENCE ONLY AND ARE NOT INTENDED TO ACCURATELY DEPICT ACTUAL OR DESIGNATED CONDITIONS. WRITTEN DIMENSIONS SHALL
GOVERN.
8. PROVIDE SEALANT AT ALL INTERSECTIONS BETWEEN DIFFERENT MATERIALS.
9. COORDINATE WORK OF ALL TRADES PRIOR TO STARTING CONSTRUCTION.
10. REFER TO ALL OTHER TRADE DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION ON THIS
PROJECT.
11. PROVIDE BLOCKING AT PARTITIONS AS REQUIRED FOR MOUNTING OF WALL-MOUNTED ITEMS: PROVIDE SUPPLEMENTAL FRAMING AT WALL OPENINGS INCLUDING KING STUDS, JACK STUDS, AND CRIPPLE STUDS, AS
REQUIRED FOR COMPLETION OF THE WORK.
12. DIMENSIONS SHOWN ARE TO FACE OF STUD FRAMING, FACE OF CONCRETE/MASONRY WALLS, OR FINISHED
FACE OF EXISTING WALL SURFACE.
13. THE CONTRACTOR IS REQUIRED TO SUBMIT A SUBMITTAL PRIOR TO BEGINNING CONSTRUCTION. THE FOLLOWING: A LIST OF ALL MAJOR EQUIPMENT MECHANICAL AND ELECTRICAL EQUIPMENT AND ITEMS WHICH
WILL BE INSTALLED IN THIS PROJECT.
14. ALL TELECOMMUNICATIONS ROOMS WILL HAVE OPEN CEILINGS TO DECK ABOVE AND ALL WALLS TO EXTEND
TO THE DECK.
1. KEY NOTES AND DRAWINGS ARE INTENDED TO GRAPHICALLY REPRESENT GENERAL WORK AND DO NOT
PORTRAY FULL SCOPE OF THE PROJECT. SEE SPECIFICATIONS FOR DETAILED REQUIREMENTS.
2. REMOVE EXISTING CONSTRUCTION AS DESIGNATED HEREIN AND CLEAR AREA OF DEBRIS PRIOR TO
PROCEEDING WITH NEW CONSTRUCTION.
3. EXISTING EQUIPMENT NOTED FOR DEMOLITION SHALL BE PROPERLY DISPOSED OFF PROJECT GROUNDS.
4. FOR RENOVATION PROJECTS AT AREAS INDICATED TO BE PATCHED AND REPAIRED, THE CONSTRUCTION AND ASSEMBLY OF THE PATCH OR REPAIR SHALL MATCH THE ASSEMBLY AND INTEGRITY OF THE ADJACENT EXISTING CONSTRUCTION, FOR FIRE RATING, MATERIALS, FINISH, THICKNESS, AND QUALITY.
5. SCHEDULE WORKING HOURS ALLOWED FOR DEMOLITION AND WASTE REMOVAL WITH COR.
6. NOTIFY COR OF ANY DEMOLITION REQUIRED AND NOT INDICATED FOR INSTALLATION OF ELECTRICAL OR DATA ITEMS. AFTER SUCH DEMOLITION AND INSTALLATION, PATCH OR REPLACE MATERIALS AND FINISHES TO MATCH
EXISTING.
7. CONTRACTOR SHALL PROTECT AREA ADJACENT TO THE DEMOTION AND NEW CONSTRUCTION WORK TO PREVENT DAMAGES, (IF DAMAGED: REPAIR, RE-PATCH, SAND SMOOTH AND REFINISH TO MATCH EXISTING.)
REPAIR OR REPLACE ITEMS DAMAGED DURING CONSTRUCTION ACTIVITIES AT NO ADDITIONAL COST.
8. THE INFORMATION CONTAINED REGARDING DEMOLITION IN THESE DOCUMENTS DEFINES GENERAL SCOPE ONLY AND DOES NOT RELIEVE THE CONTRACTOR OF THE RESPONSIBILITY OF PROVIDING ALL DEMOLITION
REQUIRED FOR THE COMPLETION OF THE PROJECT.
9. DO NOT ENCROACH ON ADJACENT OCCUPIED AREAS NOT IDENTIFIED WITHIN THE SCOPE OF WORK.
10. REFER TO THE ELECTRICAL DRAWINGS FOR FURTHER INFORMATION REGARDING DEMOLITION OF ELECTRICAL
SYSTEMS.
11. BEFORE THE START OF WORK, IDENTIFY ANY REQUIRED DEMOLITION BEYOND THE IDENTIFIED PROJECT SCOPE WHETHER ABOVE, BELOW, OR OUTSIDE THE PROJECT AREA. NOTIFY AND COORDINATE WITH THE COR, PROVIDE DEMOLITION OF THESE AREAS AND PATCH THE SAME AS A PART OF THE SCOPE OF THE PROJECT.
12. ALL DEMOLITION WORK SHALL BE PERFORMED WITH DUE CARE AND DILIGENCE IN ORDER TO PREVENT ARBITRARY DAMAGE OR INTERRUPTION OF SERVICE OR CONCEALED UTILITIES INTENDED TO REMAIN IN SERVICE. DISCOVERY OF UTILITIES OR CONDITIONS LOCATED DIFFERING FROM THOSE INDICATED OR THAT
ARE NOT IDENTIFIED, SHALL BE REPORTED TO THE COR.
13. AFTER REMOVAL OF EXISTING SOLID CONCRETE MASONRY WALL, FILL FLOOR VOIDS UP TO FINISH CONCRETE
LEVEL AND PERFORM FLOOR LEVELING FOR ENTIRE AREA OF RENOVATION.
14. ALL ITEMS BEING SALVAGED SHALL REMAIN THE PROPERTY OF THE VA UNTIL CONFIRMATION HAS BEEN MADE AS TO WHETHER THE VA WILL RETAIN SUCH ITEMS. ALL ITEMS NOT BEING RETAINED BY THE VA ARE TO BE
REMOVED FROM THE SITE BY CONTRACTOR IN APPROVED MANNER.
15. AT THE JOHN COCHRAN CAMPUS THERE IS NO SPACE AVAILABLE FOR DUMPSTER SITES AND STAGING AREAS.
THE LOCATIONS OF DUMPSTER SITES AND STAGING AREAS WILL HAVE TO BE OFF PROPERTY AND DETERMINING, MANAGING, AND PAYING FOR ALL ASSOCIATED COSTS FOR THESE LOCATIONS IS THE
RESPONSIBILITY OF THE CONTRACTOR.
16. THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING THE VA A LIST OF ALL MAJOR EQUIPMENT REMOVED DURING THIS PROJECT. THE CONTRACTOR SHALL INCLUDE WITHIN THE LIST THE EQUIPMENT IDENTIFICATION
NUMBERS(EE NUMBERS) WHICH ARE FOUND AS A TAG ON ALL EQUIPMENT AT THE VA.
17. THE CONTRACTOR SHALL DETERMINE WHETHER THE COURTYARD WALL MUST BE REMOVED IN ORDER TO CONSTRUCT THE TELECOMM. TOWER. THE CONTRACTOR ALSO BECOMES COMPLETELY RESPONSIBLE FOR REBUILDING THE COURTYARD WALL TO NEW CONDITIONS, EQUAL TO EXISTING CONDITIONS OR BETTER, UPON
COMPLETION OF THE TELECOMM TOWER.
WALL SECTION
SYMBOL
INTERIOR ELEVATION
SYMBOL
COLUMN GRID
ELEVATION SYMBOL
REVISION NOTE
ENLARGED DETAIL CALLOUT
ROOM DESIGNATION
SYMBOL
BREAK LINE
ROOF SLOPE
DIRECTION SYMBOL
TYPICAL GRAPHIC SCALE
DETAIL #
PAGE #
DETAIL #
PAGE #
VIEW NORTH ARROW
A8.1
EXTERIOR ELEVATION
SYMBOL
DETAIL #
PAGE #
A8.1
A8.1
A8.1
BUILDING SECTION
SYMBOL
DETAIL #
PAGE #
A8.1
A8.1
DETAIL SECTION
SYMBOL
DETAIL #
PAGE #
A8.1
WALL GRID
(REPRESENTS
FACE OF EXISTING
WALL)
XX.X
XX.X
ELEVATION
0'-0"
ROOM
NAME
101A
NORTHNORTH
0 4 8 16
ANY UTILITY SHUTDOWN REQUIRES 3 WEEK ADVANCE NOTICE.
INTER. TUB SIZE
1'-0"
OVERALL OUTSIDE TRIM
1'-3 3/8"
O V
E R
A L L
O U
T S
ID
E
T R
IM
/8
IN
T
E R
IO
R
D
IM
E N
S
IO
N
WALL
OPENING,
13"W x 31"H x 6-1/4"D
SEMI-RECESSED
FIRE EXTINGUISHER
CABINET, SIZED FOR
20 LB FIRE
EXTINGUISHER, ON
RATED WALL
SEALANT
SEE PLANS
FOR WALL
TYPES
PLAN
EXISTING METAL DECK OR STRUCTURE ABOVE
EXTEND WALL TO DECK, MATCH
EXISTING WALL THICKNESS
EXISTING WALL
EXISTING FLOOR LINE
TR ROOM
REFLECTED CEILING PLAN
LEGEND
DENOTES GWB
SOFFIT/CEILING
CEILING HEIGHT
DESIGNATION
(WHEN HEIGHT
VARIES FROM
TYPICAL)
2'X2' RECESSED
LED FIXTURE
2'x4' RECESSED LED
FIXTURE
EQ. A EQ. A
E Q
B
E Q
B
EXIT SIGN (SHADED
AREA INDICATES
DIRECTION OF
EGRESS)
SUPPLY DIFFUSER
RETURN GRILL
UPRIGHT
SPRINKLER HEAD
CEILING CONTRACTOR TO MEASURE EACH
CEILING AREA AND ESTABLISH A CEILING LAYOUT
TO BALANCE BORDER WIDTHS AT OPPOSITE
EDGES OF EACH ROOM. AVOID USE OF LESS-
THAN 6" TILES.
A.F.F.10' 6"
SPRINKLER HEAD
RETURN GRILL
CEILING HATCH
SIDEWALL SUPPLY
DIFFUSER
EXHAUST GRILL
STRIP LIGHT
Engineers Architects th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
VA Health Care System Approval:
Revision: Date:
ARCHITECT/ENGINEER:
JOHN COCHRAN DIVISION
915 NORTH GRAND BLVD - ST. LOUIS, MO 63106
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
FULLY SPRINKLERED
C U s e rs \l b y rd
\D o c u m e n ts
\A M
E P
F
-J C
-C O
R E lb y rd
V D
E K
F .r v t
/1
/2
:5
:0
A
M
21-124 ARCHITECTURAL SYMBOLS,
ABBREVIATIONS AND NOTES
EHRM INFRASTRUCTURE UPGRADES 657-21-700JC
BID DOCUMENTS
LBNOVEMBER 21, 2022 WVS
1 37
00-A-001
ABBREVIATIONS
ARCHITECTURAL SYMBOL LEGEND GENERAL NOTES
DEMOLITION NOTES
GENERAL SYMBOL LEGEND
UTILITY SHUTDOWN
FIRE EXTINGUISHER CABINET
Scale: 1" = 1'-0"
SCHEMATIC DETAIL - EXTEND WALLS TO DECK
DocuSign Envelope ID: 8DECC0E5-72B5-415E-9515-D9B367F0B4D4
11/22/2022
Engineers Architects th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
VA Health Care System Approval:
Revision: Date:
ARCHITECT/ENGINEER:
JOHN COCHRAN DIVISION
915 NORTH GRAND BLVD - ST. LOUIS, MO 63106
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
FULLY SPRINKLERED
C U s e rs \l b y rd
\D o c u m e n ts
\A M
E P
F
-J C
-C O
R E lb y rd
V D
E K
F .r v t
/1
/2
:4
:3
A
M
21-124 UL DETAILS EHRM INFRASTRUCTURE UPGRADES 657-21-700JC
BID DOCUMENTS
LBNOVEMBER 21, 2022 WVS
2 37
00-A-002
Engineers Architects th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
VA Health Care System Approval:
Revision: Date:
ARCHITECT/ENGINEER:
JOHN COCHRAN DIVISION
915 NORTH GRAND BLVD - ST. LOUIS, MO 63106
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
FULLY SPRINKLERED
C U s e rs \l b y rd
\D o c u m e n ts
\A M
E P
F
-J C
-C O
R E lb y rd
V D
E K
F .r v t
/1
/2
:4
:3
A
M
21-124 UL DETAILS EHRM INFRASTRUCTURE UPGRADES 657-21-700JC
BID DOCUMENTS
LBNOVEMBER 21, 2022 WVS
3 37
00-A-003
1-HX-1
01-A-101
01-A-101
3RD FLOOR ROOF
9TH FLOOR ROOF
PENTHOUSE LOW ROOF
PENTHOUSE ROOF
ROOF AREA ACCESS
POINT
01-A-101
01-A-201
01-A-301
01-A-301 _______4
01-A-301
SLOPE: 1/4"
19'-10"
NEW EXISTING
ROOFINGROOFING
PHOTO KEY
AREA OF WORK
1 1
01-A-1015
JC01 572.4 FLOOR 03
22' - 11"
2'-0"
# KEY NOTES:
# KEY NOTES:
Engineers Architects th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
VA Health Care System Approval:
Revision: Date:
ARCHITECT/ENGINEER:
JOHN COCHRAN DIVISION
915 NORTH GRAND BLVD - ST. LOUIS, MO 63106
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
FULLY SPRINKLERED
SHEET NOTES:
C
U s e rs \l b y rd
\D o c u m e n ts
\A M
E P
F
-J C
-C O
R E lb y rd
V D
E K
F .r v t
/1
/2
:4
:3
A
M
21-124 BUILDING 1, PARTIAL ROOF PLAN EHRM INFRASTRUCTURE UPGRADES 657-21-700JC
BID DOCUMENTS
LBNOVEMBER 21, 2022 WVS
4 37
01-A-101
Scale: 1/8" = 1'-0"
BUILDING 1, PARTIAL ROOF PLAN
1. THIS SHEET IS INTENDED TO PROVIDE GENERAL
SCOPE OVERVIEW FOR ROOF-TOP MECHANICAL
EQUIPMENT.
1 NEW HVAC EQUIPMENT
2 EXISTING TPO ROOF
3 NEW ROOF
4 NEW PARAPET WALL
5 APPROXIMATE EXISTING DRAIN LOCATION
6 NEW ALUMINUM COPING, .063, CONTINUOUS CLEAT
TYPE, COLOR TO MATCH COMPOSITE METAL
PANEL COLOR
7 MITERED CORNER
8 NEW TPO MEMBRANE, SEE SECTION
9 EXTEND MEMBRANE 8" UP WALL MIN AND SECURE
WITH TERMINATION BAR
10 TIE NEW METAL COPING TO EXISTING COPING FOR
WATER TIGHT, FLEXIBLE CONNECTION
11 INSTALL RECLAIMED BRICK AT THIS FACE. NEW
MEMBRANE ROOFING TO RUN UP PARAPET WALL
AND UNDER NEW METAL COPING
12 INSTALL NEW ROOFING SYSTEM FLUSH WITH
EXISTING (DRAIN TO INTERIOR OF 3RD FLOOR
ROOF) INCLUDING INSULATION, COVER BOARD
AND ROOFING MEMBRANE
13 SPLICE IN NEW METAL COPING END CAP
MIN LENGTH 4'. COLOR TO MATCH EXISTING METAL
COPING
14 EXISTING BRICK
15 LINE OF NEW TELECOM TOWER
16 INSTALL PERIMETER F.R. WOOD BLOCKING AND
ROOF EDGE, 24 GAUGE STEEL, KYNAR PAINTED -
MATCH COLOR OF PARAPET COPING. DEPTH AS
REQUIRED TO MAINTAIN INTERIOR DRAINAGE AT
3RD FLOOR ROOF
Scale: 1/4" = 1'-0"
9TH FLOOR ROOF TELECOM TOWER ENLARGED PLAN
NORTH
0 8 16 32
1 DEMOLISH EXISTING PARAPET DOWN TO
CONCRETE ROOF STRUCTURE.
N
KEY PLAN
SCALE: NO SCALE
Scale: No Scale
REFERENCE PHOTO KEY 1
Scale: No Scale
REFERENCE PHOTO KEY 2
Scale: No Scale
REFERENCE PHOTO KEY 3
LEGEND
Scale: 1/4" = 1'-0"
9TH FLOOR ROOF TELECOM TOWER ENLARGED
DEMOLITION PLAN
Scale: 1/4" = 1'-0"
3RD FLOOR ROOF TELECOM
TOWER ENLARGED PLAN
Scale: 1/4" = 1'-0"
PARTIAL ELEVATION
NORTH
0 8 16 32
NORTH
0 8 16 32
NORTH
0 8 16 32
JC01 549.5 FLOOR 01
0"
JC01 561.4 FLOOR 02
11' - 11"
JC01 572.4 FLOOR 03
22' - 11"
JC01 583.4 FLOOR 04
33' - 11"
JC01 596.0 FLOOR 05
46' - 6 1/4"
JC01 607.9 FLOOR 06
58' - 5 1/4"
JC01 618.9 FLOOR 07
69' - 5 1/4"
JC01 630.8 FLOOR 08
81' - 4 1/4"
JC01 642.3 FLOOR 09
92' - 9 3/4"
JC01 653.3 FLOOR PENTHOUSE
103' - 9 3/4"
REFLECTED CEILING PLAN AT
AREA WAY
-11' - 0"
JC01 531.0 FLOOR SUB BASEMENT
-18' - 6"
JC01 656.7 PENTHOUSE L.P. ROOF
107' - 2 9/16"
111' - 3 1/2"
AREAWAY ELEVATION
-16' - 6"
ELECTRICAL ROOM FLOOR
-16' - 0"
S101A
F.V.
19'-10"
EQ. EQ. EQ. 3'-8" F.V.
6"
F
.V
3'-10"
EQ.
JC01 549.5 FLOOR 01
0"
JC01 561.4 FLOOR 02
11' - 11"
JC01 572.4 FLOOR 03
22' - 11"
JC01 583.4 FLOOR 04
33' - 11"
JC01 596.0 FLOOR 05
46' - 6 1/4"
JC01 607.9 FLOOR 06
58' - 5 1/4"
JC01 618.9 FLOOR 07
69' - 5 1/4"
JC01 630.8 FLOOR 08
81' - 4 1/4"
JC01 642.3 FLOOR 09
92' - 9 3/4"
JC01 653.3 FLOOR PENTHOUSE
103' - 9 3/4"
JC01 667.7 FLOOR MACHINE RM
118' - 2"
REFLECTED CEILING PLAN AT
AREA WAY
-11' - 0"
JC01 531.0 FLOOR SUB BASEMENT
-18' - 6"
G.9H.5
AREAWAY ELEVATION
-16' - 6"
ELECTRICAL ROOM FLOOR
-16' - 0"
F .V
EQ. EQ. EQ. 10"
NOTE: DIMENSIONS ARE FROM REVEAL CENTERLINES
NEW ALUMINUM COPING
EXIST. CONCRETE
ROOF DECK
THICKNESS OF
EXIST. INSULATION
(ASSUMED)
PANELS TO 8"
ABOVE EXIST.
INSULATION
11'-8"
JC01 549.5 FLOOR 01
0"
JC01 561.4 FLOOR 02
11' - 11"
JC01 572.4 FLOOR 03
22' - 11"
JC01 583.4 FLOOR 04
33' - 11"
JC01 596.0 FLOOR 05
46' - 6 1/4"
JC01 607.9 FLOOR 06
58' - 5 1/4"
JC01 618.9 FLOOR 07
69' - 5 1/4"
JC01 630.8 FLOOR 08
81' - 4 1/4"
JC01 642.3 FLOOR 09
92' - 9 3/4"
JC01 653.3 FLOOR PENTHOUSE
103' - 9 3/4"
JC01 667.7 FLOOR MACHINE RM
118' - 2"
REFLECTED CEILING PLAN AT
AREA WAY
-11' - 0"
JC01 531.0 FLOOR SUB BASEMENT
-18' - 6"
G.9H.5
3 1
AREAWAY ELEVATION
-16' - 6"
ELECTRICAL ROOM FLOOR
-16' - 0"
JC01 549.5 FLOOR 01
0"
JC01 561.4 FLOOR 02
11' - 11"
JC01 572.4 FLOOR 03
22' - 11"
JC01 583.4 FLOOR 04
33' - 11"
9 810
JC01 596.0 FLOOR 05
46' - 6 1/4"
JC01 607.9 FLOOR 06
58' - 5 1/4"
JC01 618.9 FLOOR 07
69' - 5 1/4"
JC01 630.8 FLOOR 08
81' - 4 1/4"
JC01 642.3 FLOOR 09
92' - 9 3/4"
JC01 653.3 FLOOR PENTHOUSE
103' - 9 3/4"
REFLECTED CEILING PLAN AT
AREA WAY
-11' - 0"
JC01 531.0 FLOOR SUB BASEMENT
-18' - 6"
JC01 656.7 PENTHOUSE L.P. ROOF
107' - 2 9/16"
AREAWAY ELEVATION
-16' - 6"
ELECTRICAL ROOM FLOOR
-16' - 0"
# KEY NOTES:
# KEY NOTES:
Engineers Architects th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
VA Health Care System Approval:
Revision: Date:
ARCHITECT/ENGINEER:
JOHN COCHRAN DIVISION
915 NORTH GRAND BLVD - ST. LOUIS, MO 63106
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
FULLY SPRINKLERED
SHEET NOTES:
C
U s e rs \l b y rd
\D o c u m e n ts
\A M
E P
F
-J C
-C O
R E lb y rd
V D
E K
F .r v t
/1
/2
:4
:5
A
M
21-124 EXTERIOR ELEVATIONS EHRM INFRASTRUCTURE UPGRADES 657-21-700JC
BID DOCUMENTS
EJDNOVEMBER 21, 2022 WVS
5 37
01-A-201
Scale: 1/8" = 1'-0"
NORTH EXTERIOR ELEVATION AT TOWER
Scale: 1/8" = 1'-0"
EAST EXTERIOR ELEVATION AT TOWER
Scale: 1/8" = 1'-0"
EAST EXTERIOR DEMOLITION ELEVATION AT TOWER
Scale: 1/8" = 1'-0"
NORTH EXTERIOR DEMOLITION ELEVATION AT TOWER
A. EXISTING WINDOWS TO BE DEMOLISHED KNOWN TO
HAVE ASBESTOS CONTAINING MATERIAL. WINDOWS
MUST BE REMOVED FROM EXTERIOR. BARRIERS TO
BE IN PLACE ON BOTH THE INTERIOR AND EXTERIOR
PRIOR TO WINDOW DEMOLITION. COORDINATE
SEQUENCE OF DEMO WITH COR.
1 DEMOLISH EXISTING FACE BRICK
2 SAW CUT FACE BRICK AT THIS LINE
3 DEMOLISH EXISTING WINDOW, TRIM, AND STEEL
BRICK LINTEL
4 NOTE THAT ALL WORK INVOLVING WINDOW
REMOVAL WITHIN SCOPE OF THIS PROJECT IS
AFFECTED BY THE PRESENCE OF ASBESTOS AND
LEAD. THESE HAZARDOUS WASTE MATERIALS ARE
FOUND ON AND WITHIN THE WINDOW FRAME, ALL
CAULKING ON WINDOWS IS CONSIDERED
HAZARDOUS WASTE, INCLUDING THAT FOUND
BETWEEN WINDOW FRAME AND BRICK
STRUCTURE. ALL REMOVAL OF WINDOWS AND
ABATEMENT OF HAZARDOUS MATERIALS WILL
TAKE PLACE FROM THE OUTSIDE OF THE BUILDING.
5 WALL BEYOND
6 DEMOLISH EXISTING DOOR AND FRAME AND FACE
BRICK STEEL LINTEL
7 TOP OF EXISTING WALL BEYOND
1 COMPOSITE METAL PANELS. BASIS OF DESIGN:
ALPOLIC
2 PROVIDE LOUVER, SEE MECHANICAL
JC01 549.5 FLOOR 01
0"
JC01 561.4 FLOOR 02
11' - 11"
JC01 572.4 FLOOR 03
22' - 11"
JC01 583.4 FLOOR 04
33' - 11"
9 810
JC01 596.0 FLOOR 05
46' - 6 1/4"
JC01 607.9 FLOOR 06
58' - 5 1/4"
JC01 618.9 FLOOR 07
69' - 5 1/4"
JC01 630.8 FLOOR 08
81' - 4 1/4"
JC01 642.3 FLOOR 09
92' - 9 3/4"
JC01 653.3 FLOOR PENTHOUSE
103' - 9 3/4"
JC01 667.7 FLOOR MACHINE RM
118' - 2"
REFLECTED CEILING PLAN AT
AREA WAY
-11' - 0"
JC01 531.0 FLOOR SUB BASEMENT
-18' - 6"
JC01 656.7 PENTHOUSE L.P. ROOF
107' - 2 9/16"
CHASE
CH-A-1
TELECOM
T101 STAIR 01
S101A
TELECOM
T001
TELECOM
T201
TELECOM
T301
TELECOM
T401
TELECOM
T501
TELECOM
T601
TELECOM
T701
TELECOM
T801
TELECOM
T901
01-A-312
AREAWAY ELEVATION
-16' - 6"
JC01 549.5 FLOOR 01
0"
JC01 561.4 FLOOR 02
11' - 11"
JC01 572.4 FLOOR 03
22' - 11"
JC01 583.4 FLOOR 04
33' - 11"
JC01 596.0 FLOOR 05
46' - 6 1/4"
JC01 607.9 FLOOR 06
58' - 5 1/4"
JC01 618.9 FLOOR 07
69' - 5 1/4"
JC01 630.8 FLOOR 08
81' - 4 1/4"
JC01 642.3 FLOOR 09
92' - 9 3/4"
JC01 653.3 FLOOR PENTHOUSE
103' - 9 3/4"
JC01 667.7 FLOOR MACHINE RM
118' - 2"
REFLECTED CEILING PLAN AT
AREA WAY
-11' - 0"
JC01 531.0 FLOOR SUB BASEMENT
-18' - 6"
G.9
JC01 656.7 PENTHOUSE L.P. ROOF
107' - 2 9/16"
01-A-301
TELECOM
T001
STAIR 01
S101A
TELECOM
T201
TELECOM
T301
TELECOM
T401
TELECOM
T501
TELECOM
T601
TELECOM
T701
TELECOM
T801
TELECOM
T901
01-A-312
01-A-312
01-A-312
01-A-312
H.5
01-A-311
01-A-311
2 3
AREAWAY ELEVATION
-16' - 6"
JC01 549.5 FLOOR 01
0"
JC01 561.4 FLOOR 02
11' - 11"
JC01 572.4 FLOOR 03
22' - 11"
JC01 583.4 FLOOR 04
33' - 11"
JC01 596.0 FLOOR 05
46' - 6 1/4"
JC01 607.9 FLOOR 06
58' - 5 1/4"
JC01 618.9 FLOOR 07
69' - 5 1/4"
JC01 630.8 FLOOR 08
81' - 4 1/4"
JC01 642.3 FLOOR 09
92' - 9 3/4"
JC01 653.3 FLOOR PENTHOUSE
103' - 9 3/4"
JC01 667.7 FLOOR MACHINE RM
118' - 2"
REFLECTED CEILING PLAN AT
AREA WAY
-11' - 0"
JC01 531.0 FLOOR SUB BASEMENT
-18' - 6"
G.9
JC01 656.7 PENTHOUSE L.P. ROOF
107' - 2 9/16"
01-A-301
CHASE
CH-A-1
TELECOM
T101
TELECOM
T201
TELECOM
T301
TELECOM
T401
TELECOM
T501
TELECOM
T601
TELECOM
T701
TELECOM
T801
TELECOM
T901
01-A-311
01-A-311
01-A-311
01-A-312
01-A-311
H.5
01-A-311
AREAWAY ELEVATION
-16' - 6"
JC01 549.5 FLOOR 01
0"
JC01 561.4 FLOOR 02
11' - 11"
JC01 572.4 FLOOR 03
22' - 11"
JC01 583.4 FLOOR 04
33' - 11"
JC01 596.0 FLOOR 05
46' - 6 1/4"
JC01 607.9 FLOOR 06
58' - 5 1/4"
JC01 618.9 FLOOR 07
69' - 5 1/4"
JC01 630.8 FLOOR 08
81' - 4 1/4"
JC01 642.3 FLOOR 09
92' - 9 3/4"
JC01 653.3 FLOOR PENTHOUSE
103' - 9 3/4"
JC01 667.7 FLOOR MACHINE RM
118' - 2"
REFLECTED CEILING PLAN AT
AREA WAY
-11' - 0"
JC01 531.0 FLOOR SUB BASEMENT
-18' - 6"
JC01 656.7 PENTHOUSE L.P. ROOF
107' - 2 9/16"
H.5
01-A-311
TELECOM
T001
STAIR 01
S101A
TELECOM
T201
TELECOM
T301
TELECOM
T401
TELECOM
T501
TELECOM
T601
TELECOM
T701
TELECOM
T801
TELECOM
T901
01-A-311
AREAWAY ELEVATION
-16' - 6"
# KEY NOTES:
# KEY NOTES:
Engineers Architects th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
VA Health Care System Approval:
Revision: Date:
ARCHITECT/ENGINEER:
JOHN COCHRAN DIVISION
915 NORTH GRAND BLVD - ST. LOUIS, MO 63106
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
FULLY SPRINKLERED
SHEET NOTES:
C
U s e rs \l b y rd
\D o c u m e n ts
\A M
E P
F
-J C
-C O
R E lb y rd
V D
E K
F .r v t
/1
/2
:4
:1
A
M
21-124 BUILDING SECTIONS EHRM INFRASTRUCTURE UPGRADES 657-21-700JC
BID DOCUMENTS
EJDNOVEMBER 21, 2022 WVS
6 37
01-A-301
Scale: 1/8" = 1'-0"
WALL SECTION
Scale: 1/8" = 1'-0"
WALL SECTION THROUGH NEW DOOR
Scale: 1/8" = 1'-0"
WALL SECTION THROUGH INFILL
1 COMPOSITE METAL PANELS ASSEMBLY
2 ALUM COPING
3 ROOFING SYSTEM
4 CONC COMPOSITE SLAB OVER STEEL FRAMING
5 NEW DOOR AND FRAME
6 METAL PANEL RAINSCREEN CEILING ASSEMBLY
7 FOLLOW ROOFING MANUFACTURER'S STANDARD
DETAIL FOR SPLICING NEW ROOFING TO EXISTING
Scale: 1/8" = 1'-0"
DEMO SECTION AT NEW DOOR
1 REMOVE EXISTING WINDOW, FLASHINGS, AND
ASSOCIATED ELEMENTS
2 REMOVE PORTION OF WALL BELOW WINDOW
3 REMOVE EXISTING DOOR, FRAME, FLASHINGS, AND
ASSOCIATED ELEMENTS
4 REMOVE EXISTING CONC SIDEWALK
5 REMOVE EXISTING SOIL AS REQUIRED FOR NEW
WORK
6 REMOVE PORTION OF WALL FOR NEW DOOR AND
FRAME
7 REMOVE BRICK VENEER WHERE NEW WORK
OCCURS
8 COORDINATE BRICK REMOVAL W/ NEW SHELF
ANGLE AND FLASHING ABOVE NEW ROOF
9 DEMOLISH MASONRY PARAPET DOWN TO EXISTING
CONCRETE ROOF DECK
A. EXISTING WINDOWS TO BE DEMOLISHED KNOWN TO
HAVE ASBESTOS CONTAINING MATERIAL. WINDOWS
MUST BE REMOVED FROM EXTERIOR. BARRIERS TO
BE IN PLACE ON BOTH THE INTERIOR AND EXTERIOR
PRIOR TO WINDOW DEMOLITION. COORDINATE
SEQUENCE OF DEMO WITH COR.
H.5
MIN R-38 TAPERED ROOF
INSUL
PREFORMED CANT
ROOFING MEMBRANE
5/8" EXTERIOR GRADE GYP
SHEATHING
ROOFING SYSTEM - LAP AND
FASTEN OVER PARAPET BLOCKING
COMPOSITE METAL
PANEL SYSTEM
ALUM COPING
5PLY 3/4" FIRE RESISTANT PLYWOOD
PANEL BRACKET
FIRESTOP TOP TRACK
BASIS OF DESIGN:
HILTI CFS-TTS OR
EQUAL
WEATHER RESISTANT
BARRIER
ANCHOR PLATE
" 4
6" METAL STUDS
R-19 BATT INSUL
ROOFING SYSTEM
ROOFING SYSTEM
TERMINATION BAR
CONTINUOUS 24 GA
FLASHING W/ DRIP EDGE
COLOR TO MATCH
EXISTING BRICK
EXISTING WALL SYSTEM
PREFORMED CANT
ROOFING SYSTEM
STEEL BEAM
REFER TO ELEVATIONS
FOR JOINT LOCATIONS
VENTED CHANNEL
5/8" EXTERIOR GRADE
GYP SHEATHING
ROOF INSULATION
SEALANT
CUT REGLET IN
EXISTING BRICK
SEALANT
GALVANIZED SHELF ANGLE
SEE STRUCTURAL
LINE OF DEMOLISHED
BRICK VENEER
EXISTING STRUCTURE
1'-3"
SPRAY-ON
FIREPROOFING
1'-3"
2'' CONTINUOUS RIGID
INSULATION
5 PLY 3/4" FIRE RESISTANT
PLYWOOD - SECURE TO CMU
JC01 549.5 FLOOR 01
0"
H.5
WEATHER RESISTANT
BARRIER
R-19 BATT INSUL
5/8" GYP SHEATHING
6" METAL STUDS
CONC COMPOSITE SLAB8
STEEL BEAM
REFER TO ELEVATIONS
FOR JOINT LOCATIONS
SEE STRUCTURAL
EXISTING WALL SYSTEM
LINE OF DEMOLISHED
BRICK VENEER
EXISTING FOUNDATION
WALL
1'-3"
LT GA FRAMING
R-19 BATT INSUL
5/8" GYP SHEATHING
VENTED CHANNEL
WOOD BLOCKING
SEALANT
VENTED CLOSURE
3/4" FIRE RESISTANT
PLYWOOD
3"
REFER TO ELEVATIONS
FOR JOINT LOCATIONS
SEALANT
1/2" BITUMINOUS
EXP MATERIAL
JC01 549.5 FLOOR 01
0"
G.9
CONC WALL
1" CHAMFER, ALL EXPOSED EDGES
HINGED STEEL GRATE ASSEMBLY
STEEL ANGLE SUPPORT
1/2" FIBER REINFORCED
EXPANSION JOINT FILLER
CONC SLAB ON GRADE W/ TURN-
DOWN, SEE CIVIL DWGS
EXCAVATE AND BACKFILL AS REQUIRED
FOR FOUNDATION INSTALL
CONC FOUNDATION
EXCAVATE AND BACKFILL AS REQUIRED
FOR FOUNDATION INSTALL
NEW SLAB ON GRADE SLOPE TO
EXISTING DRAIN
STEEL LADDER, SEE DETAIL A-401
AREAWAY ELEVATION
-16' - 6"
ELECTRICAL ROOM FLOOR
-16' - 0"
NEW .063 ALUMINUM COPING. BASIS OF
DESIGN: PETERSON PAC CLAD, PAC TITE OR
EQUAL. COLOR TO BE SELECTED FROM
MANUFACTURER'S STANDARD RANGE
SEALANT
EXPANSION JOINT AND SEALANT
JC01 583.4 FLOOR 04
33' - 11"
H.5
WEATHER RESISTANT
BARRIER
R-19 BATT INSUL
5/8" GYP SHEATHING
6" METAL STUDS
CONC SLAB. SEE
STRUCTURAL
STEEL BEAM
EXISTING WALL SYSTEM
LINE OF DEMOLISHED
BRICK VENEER
EXISTING STRUCTURE
1'-3"
SPRAY-ON
FIREPROOFING
JC01 549.5 FLOOR 01
0"
REFLECTED CEILING PLAN AT
AREA WAY
-11' - 0"
4" CONC TOPPING SLAB
BASIS OF DESIGN: R-38 RIGID INSULATION
CONCRETE SLAB
SEE STRUCTURAL
STEEL BEAM
CONC WALL
CONC FOUNDATION
SLOPE: 1/8" per 1'-0"
1/2" FIBER REINFORCED
EXPANSION JOINT FILLER
CONC SLAB ON GRADE W/ TURN-
DOWN, SEE CIVIL
SHEET MEMBRANE
WATERPROOFING
SPRAY-ON FIREPROOFING
SEALANT
JC01 549.5 FLOOR 01
0"
9 810
REFLECTED CEILING PLAN AT
AREA WAY
-11' - 0"
JC01 531.0 FLOOR SUB BASEMENT
-18' - 6"
TERMINATION BAR
REGLET FLASHING
CUT REGLET INTO
EXISTING MASONRY JOINT
SEALANT
16 GAUGE SS BREAK METAL
TO PROTECT
WATERPROOFING
WATERPROOFING SYSTEM
4" CONC TOPPING SLAB
4" HIGH PSI RIGID INSULATION
CONC COMPOSITE SLAB
STEEL BEAM
SEALANT
16 GAUGE SS REGLET FLASHING &
BREAK METAL TO PROTECT
WATERPROOFING
WATERPROOFING SYSTEM
CAST REGLET INTO CONC WALL
HINGED STEEL GRATE ASSEMBLY
COORDINATE FABRICATION SUCH
THAT WHEN GRATE IS OPENED IT
DOES NOT DAMAGE COPING
STEEL ANGLE SUPPORT
HINGE LOCATION
CONC FOUNDATIONS
SEE STRUCTURAL
EXIST CONC WALL
COMPOSITE METAL PANEL SYSTEM
CONC SLAB ON GRADE
SPRAY-ON FIREPROOFING
AREAWAY ELEVATION
-16' - 6"
ELECTRICAL ROOM FLOOR
-16' - 0"
1" CHAMFER, ALL EXPOSED EDGES
NEW .063 ALUMINUM COPING. BASIS OF
DESIGN: PETERSON PAC CLAD, PAC TITE OR
EQUAL. COLOR TO BE SELECTED FROM
MANUFACTURER'S STANDARD RANGE
1/2" BITUMINOUS EXP
MATERIAL
1/2" BITUMINOUS EXP
MATERIAL
1/2" BITUMINOUS EXP
MATERIAL
1/2" BITUMINOUS EXP
MATERIAL
SEALANT
Engineers Architects th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
VA Health Care System Approval:
Revision: Date:
ARCHITECT/ENGINEER:
JOHN COCHRAN DIVISION
915 NORTH GRAND BLVD - ST. LOUIS, MO 63106
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
FULLY SPRINKLERED
C U s e rs \l b y rd
\D o c u m e n ts
\A M
E P
F
-J C
-C O
R E lb y rd
V D
E K
F .r v t
/1
/2
:4
:3
A
M
21-124 SECTION DETAILS EHRM INFRASTRUCTURE UPGRADES 657-21-700JC
BID DOCUMENTS
EJDNOVEMBER 21, 2022 WVS
7 37
01-A-311
Scale: 1 1/2" = 1'-0"
SECTION DETAIL - ROOF STRUCTURE
Scale: 1 1/2" = 1'-0"
SECTION DETAIL - FIRST FLOOR STRUCTURE
Scale: 3/4" = 1'-0"
SECTION DETAIL - FOUNDATION WALL
Scale: 1 1/2" = 1'-0"
SECTION DETAIL - TYPICAL FLOOR STRUCTURE
Scale: 3/4" = 1'-0"
SECTION DETAIL FOUNDATION WALL AND EXTERIOR WALKWAY
Scale: 3/4" = 1'-0"
SECTION DETAIL AT FOUNDATION WALL AND TR
EXISTING LINTEL TO
REMAIN
LINE OF DEMOLISHED
BRICK VENEER
5/8" GYP BD
2 1/2" METAL STUDS
EXISTING PLASTER
TO REMAIN
ALIGN GYP BD W/
EXISTING PLASTER AND
FINISH TO MATCH
5/8" GYP BD
3 5/8" METAL STUDS
ALIGN GYP BD W/
EXISTING CMU
SEALANT
EXISTING CMU
LINE OF DEMOLISHED
BRICK VENEER
EXISTING PLASTER
CONDITION - NO INTERIOR FURRING
JC01 583.4 FLOOR 04
33' - 11"
CONC COMPOSITE SLAB
STEEL BEAM
LINE OF DEMOLISHED
BRICK VENEER
EXISTING STRUCTURE
LINE OF DEMOLISHED
BRICK VENEER
NEW DOOR AND FRAME
SEALANT
1/2" EXPANSION
MATERIAL
EXISTING CMU LINTEL
LINE OF DEMOLISHED
BRICK VENEER
NEW DOOR AND FRAME
BOX HEADER
5/8" GYP BD
SEALANT
3 5/8" METAL STUDS
SEALANT
8'-0" VIF
EXIST WINDOW HEAD
EXISTING PLASTER
SEALANT
PATCH AND PAINT EDGE
OF PLASTER AND CMU
H.5
PANEL BRACKET
VENTED CLOSURE
VENTED HAT CHANNEL
SS FLASHING
LOUVER ASSEMBLY
SS FLASHING
ALUM RAINSCREEN
SYSTEM
WEATHER RESISTANT
BARRIER
ALUM RAINSCREEN
SYSTEM
1'-3"
SHEET METAL DUCT, SEE
MECHANICAL DRAWINGS
S E
E E
L E
V A
T
IO
N S
REFLECTED CEILING PLAN AT
AREA WAY
-11' - 0"
NEW CONC SLAB ON GRADE
EXISTING CONC WALL
NEW DOOR AND FRAME
1/2" EXPANSION JOINT
GRAVEL, SEE CIVIL
COMPOSITE METAL PANEL
(BEYOND)
SEALANT
WATER PROOFING
SYSTEM: BASIS OF
DESIGN: CARLISLE
MIRADRI, SHEET
MEMBRANE AND
DRAINAGE MAT,
VERTICAL SURFACES
LEVEL 06
EL (24'-11")
WEATHER RESISTANT
BARRIER
R-19 BATT INSUL
5/8" GYP BD.
6" METAL STUDS
CONC COMPOSITE SLAB
5/8" EXTERIOR GRADE
GYP SHEATHING
NEW ROOFING SYSTEM, COMPLETE,
TO MATCH EXISTING FROM 2'-0" MIN
AWAY FROM NEW TOWER WALL
PANEL BRACKET
VENTED CLOSURE
VENTED HAT CHANNEL
SS FLASHING
COMPOSITE METAL PANEL
SYSTEM
NEW INSULATION
2" RIGID INSUL
EXISTING STRUCTURE
SEALANT
TERMINATION BAR
OUTLINE OF DEMOLISHED PARAPET WALL
1'-3"
3/4" FIRE RESISTANT PLYWOOD -
PAINT WITH FIRE RESISTANT PAINT
LEAVE ONE LABEL PER SHEET
UNPAINTED
TROWEL AREA SMOOTH WITH
READY MIX CONCRETE PATCH
1/2" EXPANSION
MATERIAL
THIRD FLOOR PLAN
EL (22'-11")2'-0"
M
IN
REMOVE EXISITNG WINDOW ASSEMBLY
REMOVE EXISTING EXTERIOR BRICK
CMU
EXISTING GYPSUM BOARD
EXISTING METAL STUD
REMOVE EXISTING SILL
REMOVE BLOCKING
REMOVE GYPSUM BOARD AT HEAD
AND JAMBS
REMOVE BLOCKING
EXISTING METAL STUD TO REMAIN
REMOVE CONCRETE SILL
REMOVE EXISTING EXTERIOR BRICK
CMU TO REMAIN
REMOVE STEEL ANGLES
EXISITNG GYPSUM BOARD TO REMAIN
EXISITNG CMU
5/8" GYPSUM BOARD ON
3 5/8" METAL STUD INFILL
FLUSH WITH EXISTING
WALL
EXISTING CMU
SEALANT
1/4" SEALANT
5/8" GYPSUM BOARD ON 3 5/8"
METAL STUD INFILL FLUSH
WITH INTERIOR WALL
SURFACE
REMOVE EXISTING EXTERIOR BRICK
CMU
EXISTING GYPSUM BOARD
EXISITNG METAL STUD
REMOVE BLOCKING
REMOVE GYPSUM BOARD AT JAMBS
REMOVE STEEL ANGLES
REMOVE EXISITNG WINDOW JAMB
EXISTING CMU
5/8" GYPSUM BOARD ON 3 5/8" METAL
STUD INFILL FLUSH WITH EXISTING WALL
SEALANT
5/8" GYPSUM BOARD ON 3 5/8" METAL STUD
PAINT TO MATCH ADJACENT COLOR
PAINT 3'-0" OF SURROUNDING SURFACES
TAPE AND FINISH DRYWALL
Engineers Architects th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
VA Health Care System Approval:
Revision: Date:
ARCHITECT/ENGINEER:
JOHN COCHRAN DIVISION
915 NORTH GRAND BLVD - ST. LOUIS, MO 63106
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
FULLY SPRINKLERED
C U s e rs \l b y rd
\D o c u m e n ts
\A M
E P
F
-J C
-C O
R E lb y rd
V D
E K
F .r v t
/1
/2
:4
:5
A
M
21-124 SECTION DETAILS EHRM INFRASTRUCTURE UPGRADES 657-21-700JC
BID DOCUMENTS
LBNOVEMBER 21, 2022 WVS
8 37
01-A-312
Scale: 1 1/2" = 1'-0"
WALL SECTION THRU WINDOW INFILL
Scale: 1 1/2" = 1'-0"
WALL SECTION THROUGH NEW DOOR - SILL
Scale: 1 1/2" = 1'-0"
WALL SECTION THROUGH NEW DOOR - HEAD
Scale: 1 1/2" = 1'-0"
SECTION DETAIL - TYPICAL LOUVER
Scale: 1 1/2" = 1'-0"
SECTION DETAIL AT FIRST AND BASEMENT CONNECTION
Scale: 1 1/2" = 1'-0"
SECTION DETAIL AT ROOF AND EXISTING STRUCTURE CONNECTION
Scale: 1 1/2" = 1'-0"
TOWER WINDOW SECTION DETAIL - DEMO
Scale: 1 1/2" = 1'-0"
TOWER WINDOW SECTION DETAIL - STUD INFILL
Scale: 1 1/2" = 1'-0"
TOWER WINDOW JAMB DETAIL - DEMO
Scale: 1 1/2" = 1'-0"
TOWER WINDOW JAMB DETAIL - STUD INFILL
OS
ELEC
A016A
OI&T
A017A
HAC
A017
F.E.
CLOSET
B682
STAIR 01
S001OFFICE
A019
OFFICE /
STORAGE
A016
CHASE
CH-A-1
G.9 G.9
HH
II
V
IF
VIF
3'-4"
VIF
7'-3"
4" 3'-4" 11"
H008
MAIN ELEVATOR
LOBBY
6 6
TELECOM
T001
OFFICE /
STORAGE
A016
OFFICE
A019
CHASE
CH-A-1
STAIR 01
S001
HAC
A017
OI&T
A017A
F.E.
CLOSET
B682
ELEC
A016A
G.9 G.9
HH
II
H008
MAIN ELEVATOR
LOBBY
CHASE
CH-A-1
OFFICE
A019
STAIR 01
S001
OFFICE /
STORAGE
A016
A015
TOILET, MALE
G.9 G.9
HH
II
F.E.
CLOSET
B682
HAC
A017
OI&T
A017A
ELEC
A016A
H008
MAIN ELEVATOR
LOBBY
ELEC
A016A
OI&T
A017A
HAC
A017
F.E.
CLOSET
B682
STAIR 01
S001
OFFICE
A019
OFFICE /
STORAGE
A016
CHASE
CH-A-1
TELECOM
T001
9'-0"
2'-10" 6'-3"
1 2 3
T
G.9 G.9
HH
II
AREA
WELL
AW001
Maa3
A B
Room
A016B
12 12
1'-6"
1/2" x 2 1/2" STEEL RAILS
3/4" ROUND NON-SLIP
STEEL BAR RUNGS
WELD ALL AROUND TO
VERTICAL STEEL BARS
1/2" x 3" BENT PLATE, WELD
TO VERT. RAILS. SECURE
WITH 1/2" DIAMETER
EXPANSION BOLT THRU
BRICK,
AIR SPACE AND INSULATION
INTO
CMU BACKUP.
AREA WAY
FLOOR
EQ EQ
PIP CONCRETE WALL
A R
E A
W A
Y
H T
V
.I .F
AREA WAY FLOOR
GRIND SMOOTH
NEW CONC WALL
A. ALL EXISTING CONDITIONS ARE BASED ON THE BEST
AVAILABLE INFORMATION AT THE TIME OF THE
SURVEY AND VISUAL INSPECTION. CONTRACTOR
SHALL FIELD VERIFY EXISTING CONDITIONS.
B. ELEMENTS SHOWN WITH LIGHT, GRAY LINES ARE
EXISTING TO REMAIN. ELEMENTS SHOWN WITH DARK,
DASHED LINES ARE EXISTING TO BE DEMOLISHED.
DEMOLITION SHALL INCLUDE, BUT NOT BE LIMITED TO
THOSE ELEMENTS SHOWN.
C. ALL WORK SHALL BE COORDINATED BETWEEN
TRADES.
D. ALL WORK SHALL BE PERFORMED TO MINIMIZE
DISRUPTION OF AREAS OUTSIDE OF THE PROJECT
LIMITS OF WORK.
E. ALL CEILING DEMOLITION WORK TO BE COORDINATED
WITH CHANGE OF EXISTING PENDANT SPRINKLER
HEADS WITH NEW UPRIGHT SPRINKLERS SUCH THAT
THERE IS NO EXTENDED LOSS OF SPRINKLER
PROTECTION IN THE CONSTRUCTION AREA.
F. FOR FINISHES IN ALL NEW TR ROOMS - SEE ROOM
FINISH SCHEDULE SHEET A-602.
G. ALL NEW TR ROOMS TO HAVE CARBON DIOXIDE
EXTINGUISHER WITHIN 75' OF ROOM. SEE OVERALL
OR ENLARGED PLANS FOR LOCATIONS.
AREA KNOWN TO HAVE ASBESTOS
CONTAINING MATERIAL. REFERENCE
ASBESTOS INSPECTION REPORT BY
RSH FROM JANUARY 28, 2019.
TYPE:
PIPE INSULATION: YES. IN ADJACENT
AREAS
BLACK MASTIC: YES. APPROX. 370 SQ
FT
LEAD: NO
ASBESTOS LEGEND
# KEY NOTES:
# KEY NOTES:
Engineers Architects th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
VA Health Care System Approval:
Revision: Date:
ARCHITECT/ENGINEER:
JOHN COCHRAN DIVISION
915 NORTH GRAND BLVD - ST. LOUIS, MO 63106
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
FULLY SPRINKLERED
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREAS S S S
C U s e rs \l b y rd
\D o c u m e n ts \A
M E
P F
-J
C
-0 lb y rd
V D
E K
F .r v t
/1
/2
:3 :5
P
M
21-124 BUILDING 1, GROUND FLOOR,
TELECOM ROOM T001 PLANS
EHRM INFRASTRUCTURE UPGRADES 657-21-700JC
BID DOCUMENTS
LBNOVEMBER 21, 2022 WVS
9 37
01-A-401
NORTH
0 2 4 8
1 NEW DOOR AND FRAME, SEE SCHEDULE ON SHEET
A-601
2 NEW CARD READER
3 NEW ROOM SIGN, REF A-602 FOR REQUIREMENTS
4 NEW CONC SLAB ON GRADE
5 NEW FLOORING, SEE SCHEDULE ON SHEET A-602
6 NEW CONC FOUNDATION WALL, SEE STRUCTURAL
DRAWINGS
7 INFILL EXISTING OPENING W/ DOUBLE STUD WALL.
SEE DETAILS SHEET A-312.
8 EXPOSED STRUCTURE
9 OPEN TO ABOVE
10 NEW STEEL PIT LADDER, SEE DETAIL ON THIS
SHEET
11 EXISTING FIRE EXTINGUISHER CLOSET. LOCATION
FOR NEW CARBON DIOXIDE EXTINGUISHER WITH
ACCOMPANYING WARNING SIGN, FURNISHED AND
INSTALLED BY CONTRACTOR
12 EXPOSED EXISTING CONCRETE WALL
13 SEAL ALL PERIMETER AND PENETRATIONS FOR A
1-HOUR FIRE BARRIER ENCLOSURE
14 PAINT AND BASE AT INFILL
15 3/4" FIRE RETARDANT PLYWOOD APPLIED OVER
GYP BD FOR MOUNTING OF TELECOMMUNICATIONS
EQUIPMENT, 8” AFF TO 8’-8” AFF, PAINT W/ (2) COATS
OF FIRE RETARDANT PAINT
16 MOVE EXISTING LIGHT, REPLACE CEILING TILE WITH
SALVAGED TILE FROM A016B CEILING DEMO
17 2" CLOSED CELL POLYSTYRENE INSULATION FROM
GRADE TO TOP OF FOUNDATION OVER
WATERPROOFING MEMBRANE
Scale: 1/4" = 1'-0"
TELECOM ROOM T001
DEMOLITION PLAN
NORTH
0 2 4 8
Scale: 1/4" = 1'-0"
TELECOM ROOM T001
REFLECTED CEILING PLAN
NORTH
0 2 4 8
Scale: 1/4" = 1'-0"
TELECOM ROOM T001 DEMOLITION REFLECTED CEILING
PLAN
NORTH
0 2 4 8
Scale: 1/4" = 1'-0"
TELECOM ROOM T001
FLOOR PLAN
1 CREATE ROUGH OPENING FOR NEW DOOR
2 REMOVE PORTION OF FOUNDATION WALL
3 REMOVE EXISTING WINDOW ASSEMBLY
4 REMOVE EXISTING GRATING ABOVE
5 REMOVE EXISTING STEEL PIT LADDER.
6 EXTERIOR FACE BRICK, LINTELS, AND SILLS TO BE
REMOVED
7 REMOVE EXISTING ACT CEILING
8 REMOVE LIGHT, TO BE REUSED IN SAME ROOM
9 AREA KNOWN TO HAVE ASBESTOS CONTAINING
PIPE INSULATION AND OR HVAC DUCT
10 AREA KNOWN TO HAVE ASBESTOS CONTAINING
FLOORING.
Scale: 1/2" = 1'-0"
STEEL PIT LADDER FRONT ELEVATION
Scale: 1/2" = 1'-0"
LADDER ELEVATION
N
KEY PLAN
SCALE: NO SCALE
S S
S
S S
S
S S
S
S S
S
J
L
K
TR
B009
OFFICE
B008
BREAK
ROOM
B006
CONFERENCE
RM.
B007
CORRIDOR
H011
OFFICE
B010
B
9'-6"
Maa3
STORAGE
1'-0"
01-A-603
CORRIDOR
H011
J
L
K
TR
B009
OFFICE
B008
BREAK
ROOM
B006
CONFERENCE
RM.
B007
OFFICE
B010
9'-10"
J
L
K
TR
B009
OFFICE
B008
CORRIDOR
H011
OFFICE
B010
CORRIDOR
H011
BREAK
ROOM
B006
J
L
K
TR
B009
OFFICE
B008
CORRIDOR
H011
OFFICE
B010
CONFERENCE
RM.
B007
BREAK
ROOM
B006
A. ALL EXISTING CONDITIONS ARE BASED ON THE BEST
AVAILABLE INFORMATION AT THE TIME OF THE
SURVEY AND VISUAL INSPECTION. CONTRACTOR
SHALL FIELD VERIFY EXISTING CONDITIONS.
B. ELEMENTS SHOWN WITH LIGHT, GRAY LINES ARE
EXISTING TO REMAIN. ELEMENTS SHOWN WITH DARK,
DASHED LINES ARE EXISTING TO BE DEMOLISHED.
DEMOLITION SHALL INCLUDE, BUT NOT BE LIMITED TO
THOSE ELEMENTS SHOWN.
C. ALL WORK SHALL BE COORDINATED BETWEEN
TRADES.
D. ALL WORK SHALL BE PERFORMED TO MINIMIZE
DISRUPTION OF AREAS OUTSIDE OF THE PROJECT
LIMITS OF WORK.
E. ALL CEILING DEMOLITION WORK TO BE COORDINATED
WITH CHANGE OF EXISTING PENDANT SPRINKLER
HEADS WITH NEW UPRIGHT SPRINKLERS SUCH THAT
THERE IS NO EXTENDED LOSS OF SPRINKLER
PROTECTION IN THE CONSTRUCTION AREA.
F. FOR FINISHES IN ALL NEW TR ROOMS - SEE ROOM
FINISH SCHEDULE SHEET A-602.
G. ALL NEW TR ROOMS TO HAVE CARBON DIOXIDE
EXTINGUISHER WITHIN 75' OF ROOM. SEE OVERALL
OR ENLARGED PLANS FOR LOCATIONS.
AREA KNOWN TO HAVE ASBESTOS
CONTAINING MATERIAL. REFERENCE
ASBESTOS INSPECTION REPORT
DONE BY TERRACON DATED
NOVEMBER 7, 2022. LOCATED IN
SPEC. SECTION 02 82 11.
TYPE:
PIPE INSULATION: YES, IN AREA OF
WORK AND ADJACENT AREAS
BLACK MASTIC: APPROX 390 SQ FT
LEAD: NO
ASBESTOS LEGEND
# KEY NOTES:
# KEY NOTES:
Engineers Architects th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
VA Health Care System Approval:
Revision: Date:
ARCHITECT/ENGINEER:
JOHN COCHRAN DIVISION
915 NORTH GRAND BLVD - ST. LOUIS, MO 63106
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
FULLY SPRINKLERED
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREAS S S S
C U s e rs \l b y rd
\D o c u m e n ts \A
M E
P F
-J
C
-0 lb y rd
V D
E K
F .r v t
/1
/2
:3 :0
P
M
21-124 BUILDING 1, GROUND FLOOR,
TELECOM B009 PLAN
EHRM INFRASTRUCTURE UPGRADES 657-21-700JC
BID DOCUMENTS
LBNOVEMBER 21, 2022 WVS
10 37
01-A-402
Scale: 1/4" = 1'-0"
TELECOM ROOM B009
FLOOR PLAN
Scale: 1/4" = 1'-0"
TELECOM ROOM B009
DEMOLITION FLOOR PLAN
Scale: 1/4" = 1'-0"
TELECOM ROOM B009
REFLECTED CEILING PLAN
Scale: 1/4" = 1'-0"
TELECOM ROOM B009 DEMOLITION REFLECTED CEILING
PLAN
NORTH
0 2 4 8
NORTH
0 2 4 8
NORTH
0 2 4 8
NORTH
0 2 4 8
1 NEW DOOR AND FRAME, SEE SCHEDULE ON
SHEET A-601
2 NEW CARD READER
3 PATCH ALL HOLES AND DIVOTS IN SUBFLOOR
4 NEW FLOORING, SEE SCHEDULE SHEET A-602
5 EXPOSED STRUCTURE
6 NEW ROOM SIGN, REF A-602 FOR
REQUIREMENTS
7 INFILL OPENING W/ NEW 1-HOUR FIRE BARRIER.
PAINT TO MATCH ADJACENT.
8 APPLY WINDOW FILM WF-1 TO INTERIOR FACE OF
GLAZING, SEE 01-A-602 FOR DETAILS. APPROX.
WINDOW SIZE 3'-0''W X 5'-0"H
9 REPAIR APPROX. 2'x2' HOLE IN WALL ABOVE
CEILING WITH 1 HR RATED CONSTRUCTION
10 3/4" FIRE RETARDANT PLYWOOD APPLIED OVER
GYP BD FOR MOUNTING OF
TELECOMMUNICATIONS EQUIPMENT, 8” AFF TO
8’-8” AFF, PAINT W/ (2) COATS OF FIRE
RETARDANT PAINT
11 EXISTING WALL TO UNDERSIDE OF STRUCTURE
ABOVE
12 12X12 ACT TILES TO MATCH EXISTING, ADHERED
TO 5/8" GYP. BD. ON GYP. BD. CEILING
SUSPENSION SYSTEM.
13 MODIFY HAND AND BUMPER RAIL FOR NEW
DOOR
14 EXTEND EXISTING HANDRAIL AND BUMPER RAIL
15 SEAL ALL PERIMETER AND PENETRATIONS FOR A
1-HOUR FIRE BARRIER ENCLOSURE
16 RELOCATED SECURITY MIRROR.
1 REMOVE EXISTING FLOOR FINISH AND BASE
2 REMOVE EXISTING ACT CEILING, INCLUDING ELEC
AND MECH FIXTURES
3 REMOVE EXISTING DOOR, FRAME AND HARDWARE.
4 PATCH AND REPAINT WALL WHERE DIRECTION
SIGNAGE HAS BEEN REMOVED
5 REMOVE EXISTING FAN COIL UNIT. DEMOLISH
CHILLED WATER SUPPLY AND RETURN PIPING
BACK TO MAINS.
6 EXISTING CEILING TO REMAIN
7 PORTION OF EXISTING ROOM TO REMAIN. PROTECT
FINISHES AND FURNITURE.
8 REMOVE EXISTING BUMPER AND HANDRAIL
9 REMOVE EXISTING DIRECTIONAL SIGNAGE, VA TO
GIVE DIRECTION ON NEW LOCATION INSTALLATION
10 CLEAN AND PREP WINDOWS FOR FILM
INSTALLATION
11 REMOVE EXISTING SECURITY MIRROR, SALVAGE
AND STORE FOR RELOCATION.
12 AREA KNOWN TO HAVE ASBESTOS CONTAINING
PIPE INSULATION AND OR HVAC DUCT
13 AREA KNOWN TO HAVE ASBESTOS CONTAINING
FLOORING. SEE LEGEND FOR SQUARE FOR SQ. FT.
N
KEY PLAN
SCALE: NO SCALE
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
STORAGE
DB16
WORK
RM.
DB10
OFFICE
DB15A
TR
DB15B
OI&T
DB14A
TOILET
DB12
TOILET
DB11
CORRIDOR
H027
TOILET,
MALE
DB17
CORRIDOR
H024
10-A
10-A
11-A
11-A
12-A
12-A
A.1-AA.1-A
8.9-A
8.9-A
8.7-A
S-AS-A
R-AR-A
8'-5''
STORAGE
DB16
WORK
RM.
DB10
OFFICE
DB15A
OI&T
DB14A
TOILET
DB12
TOILET
DB11
CORRIDOR
H027
TOILET,
MALE
DB17
CORRIDOR
H024
OFFICE
DB15B
10-A
10-A
11-A
11-A
12-A
12-A
A.1-AA.1-A
8.9-A8.7-A
8.7-A
S-AS-A
R-AR-A
CORRIDOR
H024
8' - 0"
STORAGE
DB16
WORK
RM.
DB10
OFFICE
DB15A
OI&T
DB14A
CORRIDOR
H027
TOILET,
MALE
DB17
TOILET
DB12
TOILET
DB11
OFFICE
DB15B
10-A
10-A
11-A
11-A
12-A
12-A
A.1-AA.1-A
8.9-A8.7-A
8.7-A
S-AS-A
R-AR-A
CORRIDOR
H024
STORAGE
DB16
WORK
RM.
DB10
OFFICE
DB15A
TR
DB15B
OI&T
DB14A
CORRIDOR
H027
TOILET,
MALE
DB17
TOILET
DB12
TOILET
DB11
D B
B
8'-5"
CORRIDOR
H024
10-A
10-A
11-A
11-A
12-A
12-A
A.1-AA.1-A
8.9-A8.7-A
8.7-A
S-AS-A
R-AR-A
Maa3
01-A-6032
A. ALL EXISTING CONDITIONS ARE BASED ON THE BEST
AVAILABLE INFORMATION AT THE TIME OF THE
SURVEY AND VISUAL INSPECTION. CONTRACTOR
SHALL FIELD VERIFY EXISTING CONDITIONS.
B. ELEMENTS SHOWN WITH LIGHT, GRAY LINES ARE
EXISTING TO REMAIN. ELEMENTS SHOWN WITH DARK,
DASHED LINES ARE EXISTING TO BE DEMOLISHED.
DEMOLITION SHALL INCLUDE, BUT NOT BE LIMITED TO
THOSE ELEMENTS SHOWN.
C. ALL WORK SHALL BE COORDINATED BETWEEN
TRADES.
D. ALL WORK SHALL BE PERFORMED TO MINIMIZE
DISRUPTION OF AREAS OUTSIDE OF THE PROJECT
LIMITS OF WORK.
E. ALL CEILING DEMOLITION WORK TO BE COORDINATED
WITH CHANGE OF EXISTING PENDANT SPRINKLER
HEADS WITH NEW UPRIGHT SPRINKLERS SUCH THAT
THERE IS NO EXTENDED LOSS OF SPRINKLER
PROTECTION IN THE CONSTRUCTION AREA.
F. FOR FINISHES IN ALL NEW TR ROOMS - SEE ROOM
FINISH SCHEDULE SHEET A-602.
G. ALL NEW TR ROOMS TO HAVE CARBON DIOXIDE
EXTINGUISHER WITHIN 75' OF ROOM. SEE OVERALL
OR ENLARGED PLANS FOR LOCATIONS.
AREA KNOWN TO HAVE ASBESTOS
CONTAINING MATERIAL. REFERENCE
ASBESTOS INSPECTION REPORT BY
RSH FROM JANUARY 28, 2019.
TYPE:
PIPE INSULATION: NO
BLACK MASTIC: YES IN ADJACENT
AREAS. APPROX 50 SQ FT
LEAD: NO
ASBESTOS LEGEND
# KEY NOTES:
# KEY NOTES:
Engineers Architects th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
VA Health Care System Approval:
Revision: Date:
ARCHITECT/ENGINEER:
JOHN COCHRAN DIVISION
915 NORTH GRAND BLVD - ST. LOUIS, MO 63106
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.
FULLY SPRINKLERED
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREAS S S S
C U s e rs \l b y rd
\D o c u m e n ts \A
M E
P F
-J
C
-0 lb y rd
V D
E K
F .r v t
/1
/2
:3 :1
P
M
21-124 BUILDING 1, GROUND FLOOR,
TELECOM DB15B PLAN
EHRM INFRASTRUCTURE UPGRADES 657-21-700JC
BID DOCUMENTS
LBNOVEMBER 21, 2022 WVS
11 37
01-A-403
Scale: 1/4" = 1'-0"
TELECOM ROOM DB15B
REFLECTED CEILING PLAN
Scale: 1/4" = 1'-0"
TELECOM ROOM DB15B DEMOLITION REFLECTED CEILING
PLAN
Scale: 1/4" = 1'-0"
TELECOM ROOM DB15B
DEMOLITION FLOOR PLAN
Scale: 1/4" = 1'-0"
TELECOM ROOM DB15B
FLOOR PLAN
NORTH
0 2 4 8
NORTH
0 2 4 8
NORTH
0 2 4 8
NORTH
0 2 4 8
1 CREATE ROUGH OPENING FOR NEW DOOR
2 REMOVE EXISTING DOOR HARDWARE AS
REQUIRED FOR NEW WORK
3 REMOVE EXISTING ACT CEILING, INCLUDING ELEC
AND MECH FIXTURES
4 EXISTING ROOM SIGN TO BE RELOCATED.
5 REMOVE EXISTING WALL SIGNAGE AND TURN OVER
TO VA FOR RELOCATION
6 REMOVE EXISTING FLOOR FINISH AND BASE
7 AREA KNOWN TO HAVE ASBESTOS CONTAINING
FLOORING.
1 NEW DOOR AND FRAME, SEE SCHEDULE ON
SHEET A-601
2 LOCATION OF RELOCATED ROOM SIGN
3 NEW CARD READER
4 NEW FLOORING, BASE AND FINISHES, SEE
SCHEDULE ON SHEET A-602
5 INFILL EXISTING OPENING W/ NEW 1-HOUR FIRE
BARRIER. PAINT, RUBBER BASE ON BOTH SIDES
6 NEW HARD CEILING AT 8'-5" +/- SUSPENDED
DRYWALL GRID SYSTEM WITH (2) LAYERS OF 5/8"
TYPE X GYPSUM BD. BASIS OF DESIGN: USG
DRYWALL SUSPENSION SYSTEMS OR EQUAL.
KEEP AS TIGHT AS POSSIBLE TO DUCT SUPPORT.
7 MODIFY HAND AND BUMPER RAIL FOR NEW DOOR
8 EXISTING SEMI RECESSED FIRE EXTINGUISHER
CABINET. LOCATION FOR NEW CARBON DIOXIDE
EXTINGUISHER WITH ACCOMPANYING WARNING
SIGN, FURNISHED AND INSTALLED BY
CONTRACTOR
9 EXISTING WALL TO UNDERSIDE OF STRUCTURE
ABOVE
10 WALL DOES NOT GO TO…
This is the start of the file's text. The full file is on GovTribe.