This document is a technical specification for communications systems (Section 27 05 11) for a Veterans Affairs (VA) project to construct a 12-bed Community Living Center (CLC) at the Trinka Davis Veterans Village in Carrollton, Georgia. The specification provides comprehensive technical requirements for communications infrastructure, including detailed guidelines for installation, testing, equipment standards, submittals, and quality assurance for telecommunications systems.
The specification covers multiple aspects of communications systems, including conduits, cables, grounding, identification, commissioning, and specific requirements for various communication technologies. Key requirements include using UL-listed equipment, providing detailed documentation, ensuring system compatibility, implementing proper grounding and surge protection, and meeting VA and industry standards such as ANSI/TIA and NFPA guidelines. The document outlines specific technical standards for components like cable trays, patch panels, structured cabling, and communication cabinets, with extensive provisions for system testing, maintenance, and warranty.
View the file
Other files
Show all 50
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SPECIFICATIONS
VOLUME 3
DIV. 27 - 34
VA Atlanta TVDD 12 Bed CLC
100% Final Bid Doc Submittal
VA Contract No.: VA36C77622R0059 VA Project No.: 508-349
VA Trinka Davis Veterans Village
Carrollton, GA 30117
August 19, 2024
Project Contacts
OWNER: VA ATLANTA HEALTHCARE SYSTEM
Attn: Darryl Ray, COR
Carrollton, GA 30117
Phone: 404-321-6111 x124275
Email: darryl.ray@va.gov
ARCHITECT, INTERIOR DESIGN, STRUCTURAL & CIVIL ENGINEER: GUIDON DESIGN INC.
Attn: Mark VanderWoude
1221 N. Pennsylvania St.
Indianapolis, IN 46202
Phone: 317-800-6388 x 119
Email: mvanderwoude@guidon.com
M/E/P/FP/T ENGINEER: CHARLOTTE ENGINEERS
Attn: Avery Stanley
5838 Monroe Rd
Charlotte, NC 28212
Phone: 704-531-3000 x106
Email: acallahan@charlotteengineers.com mailto:darryl.ray@va.gov mailto:mvanderwoude@guidon.com mailto:acallahan@charlotteengineers.com
VA Atlanta TVDD 12 Bed CLC Project #508-349
Contract #36C77622R0059
Carrollton GA 30117 06-01-23
00 01 10 - 1
DEPARTMENT OF VETERANS AFFAIRS
VHA MASTER SPECIFICATIONS
TABLE OF CONTENTS
Section 00 01 10
SECTION NO DIVISION AND SECTION TITLES DATE
DIVISION 00 - SPECIAL SECTIONS
00 01 15 List of Drawing Sheets 05-20
DIVISION 01 - GENERAL REQUIREMENTS
01 00 00 General Requirements 11-21
01 32 16.15 Project Schedules (Small Projects – Design/Bid/Build 01-24
01 33 23 Shop Drawings, Product Data, and Samples 11-23
01 35 26 Safety Requirements 05-24
01 42 19 Reference Standards 11-20
01 45 00 Quality Control 02-21
01 45 29 Testing Laboratory Services 11-18
01 45 35 Special Inspections 06-21
01 57 19 Temporary Environmental Controls 01-21
01 58 16 Temporary Interior Signage 07-15
01 74 19 Construction Waste Management 04-22
01 81 13 Sustainable Construction Requirements 10-17
01 91 00 General Commissioning Requirements 04-22
DIVISION 02 – EXISTING CONDITIONS
02 41 00 Demolition 08-17
DIVISION 03 – CONCRETE
03 30 00 Cast-in-Place Concrete 01-21
DIVISION 04 – MASONRY
04 05 13 Masonry Mortaring 10-17
04 05 16 Masonry Grouting 01-21
04 20 00 Unit Masonry 08-17
DIVISION 05 – METALS
05 12 00 Structural Steel Framing 11-18
05 31 00 Steel Decking 01-21
05 36 00 Composite Metal Decking 01-21
05 40 00 Cold-Formed Metal Framing 01-21
05 50 00 Metal Fabrications 08-18
DIVISION 06 – WOOD, PLASTICS AND COMPOSITES
06 10 00 Rough Carpentry 10-17
Carrollton GA 30117 06-01-23
00 01 10 - 2
SECTION NO DIVISION AND SECTION TITLES DATE
06 16 63 Cementitious Sheathing 01-21
06 20 00 Finish Carpentry 01-21
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
07 11 13 Bituminous Dampproofing 01-21
07 13 00 Sheet Waterproofing 01-21
07 21 13 Thermal Insulation 01-21
07 21 29 Spray Applied Insulation
07 22 00 Roof and Deck Insulation 01-21
07 24 00 Exterior Insulation and Finish Systems 01-21
07 27 27 Fluid-Applied Membrane Air Barrier, Vapor Retarding 01-21
07 31 00 Synthetic Roof Tiles
07 54 23 Thermoplastic Polyolefin (TPO) Roofing 01-21
07 60 00 Flashing and Sheet Metal 01-21
07 71 00 Roof Specialties 01-21
07 72 00 Roof Accessories 01-21
07 81 00 Applied Fireproofing 07-23
07 84 00 Firestopping 01-21
07 92 00 Joint Sealants 04-22
DIVISION 08 - OPENINGS
08 11 13 Hollow Metal Doors and Frames 01-21
08 14 00 Interior Wood Doors 01-21
08 31 13 Access Doors and Frames 04-22
08 33 13 Coiling Counter Doors 01-21
08 41 13 Aluminum-Framed Entrances and Storefronts 01-21
08 51 13 Aluminum Windows 01-21
08 71 00 Door Hardware 03-24
08 71 13 Automatic Door Operators 01-21
08 71 13.11 Low Energy Power Assist Door Operators 01-21
08 80 00 Glazing 01-21
08 90 00 Louvers and Vents 01-21
DIVISION 09 – FINISHES
09 05 16 Subsurface Preparation for Floor Finishes 01-21
09 22 16 Non-Structural Metal Framing 06-18
09 29 00 Gypsum Board 04-20
09 30 13 Ceramic/Porcelain Tiling 01-21
09 51 00 Acoustical Ceilings 12-18
09 65 13 Resilient Base and Accessories 01-21
09 65 16 Resilient Sheet Flooring 06-22
09 65 19 Resilient Tile Flooring 05-18
09 67 23.30 Resinous (Epoxy Base) High Performance Decorative
Mortar Flooring (RES-3)
06-24
09 68 00 Carpeting 01-21
09 84 33 Sound-Absorbing Wall Units 01-21
09 91 00 Painting 01-21
Carrollton GA 30117 06-01-23
00 01 10 - 3
SECTION NO DIVISION AND SECTION TITLES DATE
DIVISION 10 – SPECIALTIES
10 14 00 Signage 01-21
10 26 00 Wall and Door Protection 01-21
10 28 00 Toilet, Bath, and Laundry Accessories 01-21
10 44 13 Fire Extinguisher Cabinets 08-18
10 44 16 Fire Extinguishers
DIVISION 11 – EQUIPMENT
11 40 00 Food Service 01-21
11 40 11 Custom Fabricated Food Service Equipment 01-21
11 41 00 Food Storage Equipment
11 44 00 Food Cooking Equipment 01-21
11 48 00 Cleaning and Disposal Equipment 01-21
DIVISION 12 – FURNISHINGS
12 24 00 Window Shades 08-17
12 32 00 Manufactured Wood Casework 01-21
12 34 00 Manufactured Plastic Casework 01-21
12 35 70.21 Medication Cabinet 01-21
12 36 00 Countertops 12-23
DIVISION 21- FIRE SUPPRESSION
21 08 00 Commissioning of Fire Suppression System 11-16
21 13 13 Wet-Pipe Sprinkler Systems 06-15
DIVISION 22 – PLUMBING
22 05 11 Common Work Results for Plumbing 01-23
22 05 12 General Motor Requirements for Plumbing Equipment 09-20
22 05 19 Meters and Gages for Plumbing Piping 09-20
22 05 23 General-Duty Valves for Plumbing Piping 09-20
22 07 11 Plumbing Insulation 09-19
22 08 00 Commissioning of Plumbing Systems 11-16
22 11 00 Facility Water Distribution 05-21
22 13 00 Facility Sanitary and Vent Piping 09-20
22 13 23 Sanitary Waste Interceptors 09-20
22 14 00 Facility Storm Drainage 09-15
22 34 00 Fuel-Fired Domestic Water Heaters 09-20
22 40 00 Plumbing Fixtures 05-24
DIVISION 23 – HEATING, VENTILATING, AND AIR
CONDITIONING (HVAC)
23 05 11 Common Work Results for HVAC 03-23
23 05 12 General Motor Requirements for HVAC and Steam
Generation Equipment
03-23
Carrollton GA 30117 06-01-23
00 01 10 - 4
SECTION NO DIVISION AND SECTION TITLES DATE
23 05 41 Noise and Vibration Control for HVAC Piping and
Equipment
03-23
23 05 93 Testing, Adjusting, and Balancing for HVAC 03-23
23 07 11 HVAC and Boiler Plant Insulation 02-20
23 08 00 Commissioning of HVAC Systems 03-23
23 09 23 Direct-Digital Control System for HVAC 03-23
23 11 23 Facility Natural-Gas Piping 04-20
23 23 00 Refrigerant Piping 03-24
23 31 00 HVAC Ducts and Casings 03-23
23 34 00 HVAC Fans 03-23
23 37 00 Air Outlets and Inlets 03-23
23 38 13 Commercial-Kitchen Hoods 03-23
23 40 00 HVAC Air Cleaning Devices 03-23
23 72 00 Air-to-Air Energy Recovery Equipment 03-24
23 73 00 Indoor Central-Station Air-Handling Units 03-23
23 81 00 Decentralized Unitary HVAC Equipment 03-24
23 82 16 Air Coils 03-24
DIVISION 26 – ELECTRICAL
26 05 11 Requirements for Electrical Installations 11-22
26 05 19 Low-Voltage Electrical Power Conductors and Cables 11-22
26 05 26 Grounding and Bonding for Electrical Systems 11-22
26 05 33 Raceway and Boxes for Electrical Systems 11-22
26 05 41 Underground Electrical Construction 11-22
26 05 73 Overcurrent Protective Device Coordination Study 11-22
26 08 00 Commissioning of Electrical Systems 11-22
26 09 23 Lighting Controls 11-22
26 22 00 Low-Voltage Transformers 11-22
26 24 16 Panelboards 11-22
26 27 26 Wiring Devices 11-22
26 29 11 Motor Controllers 11-22
26 29 21 Enclosed Switches and Circuit Breakers 11-22
26 32 13 Engine Generators 11-22
26 36 23 Automatic Transfer Switches 11-22
26 41 00 Facility Lightning Protection 11-22
26 42 00 Cathodic Protection 11-22
26 43 13 Surge Protective Devices 11-22
26 51 00 Interior Lighting 03-24
26 56 00 Exterior Lighting 11-22
DIVISION 27 – COMMUNICATIONS
27 05 11 Requirements for Communications Installations 09-19
27 05 26 Grounding and Bonding for Communications Systems 12-22
27 05 33 Conduits and Backboxes for Communications Systems 12-22
27 05 36 Cable Trays for Communications Systems 12-22
27 05 53 Identification for Communications Systems 12-22
27 08 00 Commissioning of Communication Systems 11-16
27 10 00 Structured Cabling 12-22
27 11 16 Communications Cabinets, Racks, Frames, and Enclosures 12-22
Carrollton GA 30117 06-01-23
00 01 10 - 5
SECTION NO DIVISION AND SECTION TITLES DATE
27 11 19 Communications Termination Blocks and Patch Panels 12-22
27 11 26 Communications Rack Mounted Power Protection and Power
Strips
12-22
27 13 23 Communications Optical Fiber Backbone Cabling 12-22
27 15 13 Communications Copper Horizontal Cabling 12-22
27 16 19 Communications Patch Cords, Station Cords, and Cross-
Connect Wire
12-22
27 51 16 Public Address and Mass Notification Systems 11-22
27 52 23 Nurse Call and Code Blue Systems 12-20
DIVISION 28 – ELECTRONIC SAFETY AND SECURITY
28 05 00 Common Work Results for Electronic Safety and Security 04-18
28 05 13 Conductors and Cables for Electronic Safety and
Security
10-18
28 05 26 Grounding and Bonding for Electronic Safety and
Security
09-11
28 05 28.33 Conduits and Backboxes for Electronic Safety and
Security
09-11
28 08 00 Commissioning of Electronic Safety and Security Systems 11-16
28 13 00 Physical Access Control System 10-11
28 23 00 Video Surveillance 09-11
28 31 00 Fire Detection and Alarm 10-11
DIVISION 31 – EARTHWORK
31 20 00 Earthwork 08-23
DIVISION 32 – EXTERIOR IMPROVEMENTS
32 05 23 Cement and Concrete for Exterior Improvements 08-16
32 17 23 Pavement Markings 08-16
32 31 40 High Security Fences and Gates 08-16
32 90 00 Planting 08-16
DIVISION 33 – UTILITIES
33 10 00 Water Utilities 03-17
33 30 00 Sanitary Sewer Utilities 06-13
33 40 00 Storm Sewer Utilities 12-17
33 51 00 Natural-Gas Distribution 10-11
DIVISION 34 – TRANSPORTATION
34 71 13 Passive Vehicle Barriers 04-18
APPENDIX
Geotech Report
Carrollton GA 30117 06-01-23
00 01 10 - 6
Carrollton GA 30117 09-01-19
27 05 11 - 1
SECTION 27 05 11
REQUIREMENTS FOR COMMUNICATIONS INSTALLATIONS
PART 1 - GENERAL
1.1 DESCRIPTION
A. This section includes common requirements to communications installations and applies to all sections of Division 27.
B. Provide completely functioning communications systems.
C. Comply with VAAR 852.236.91 and FAR clause 52.236-21 in circumstance of a need for additional detail or conflict between drawings, specifications, reference standards or code.
1.2 REFERENCES
A. Abbreviations and Acronyms
1. Refer to http://www.cfm.va.gov/til/sdetail.asp for Division 00, ARCHITECTURAL ABBREVIATIONS.
2. Additional Abbreviations and Acronyms:
A Ampere
AC Alternating Current
AE Architect and Engineer
AFF Above Finished Floor
AHJ Authority Having Jurisdiction
ANSI American National Standards Institute
AWG American Wire Gauge (refer to STP and UTP)
AWS Advanced Wireless Services
BCT Bonding Conductor for Telecommunications (also
Telecommunications Bonding Conductor (TBC))
BDA Bi-Directional Amplifier
BICSI Building Industry Consulting Service International
BIM Building Information Modeling
BOM Bill of Materials
BTU British Thermal Units
BUCR Back-up Computer Room
BTS Base Transceiver Station
CAD AutoCAD
CBOPC Community Based Out Patient Clinic
27 05 11 - 2
CBC Coupled Bonding Conductor
CBOC Community Based Out Patient Clinic (refer to CBOPC, OPC, VAMC)
CCS TIP's Cross Connection System (refer to VCCS and
HCCS)
CFE Contractor Furnished Equipment
CFM US Department of Veterans Affairs Office of
Construction and Facilities Management
CFR Consolidated Federal Regulations
CIO Communication Information Officer (Facility, VISN or
Region) cm Centimeters
CO Central Office
COR Contracting Officer Representative
CPU Central Processing Unit
CSU Customer Service Unit
CUP Conditional Use Permit(s) – Federal/GSA for VA dB Decibel dBm Decibel Measured dBmV Decibel per milli-Volt
DC Direct Current
DEA United States Drug Enforcement Administration
DSU Data Service Unit
EBC Equipment Bonding Conductor
ECC Engineering Control Center (refer to DCR, EMCR)
EDGE Enhanced Data (Rates) for GSM Evolution
EDM Electrical Design Manual
EMCR Emergency Management Control Room (refer to DCR, ECC)
EMI Electromagnetic Interference (refer to RFI)
EMS Emergency Medical Service
EMT Electrical Metallic Tubing or thin wall conduit
ENTR Utilities Entrance Location (refer to DEMARC, POTS, LEC)
27 05 11 - 3
EPBX Electronic Digital Private Branch Exchange
ESR Vendor’s Engineering Service Report
FA Fire Alarm
FAR Federal Acquisition Regulations in Chapter 1 of Title
48 of Code of Federal Regulations
FMS VA’s Headquarters or Medical Center Facility’s
Management Service
FR Frequency (refer to RF)
FTS Federal Telephone Service
GFE Government Furnished Equipment
GPS Global Positioning System
GRC Galvanized Rigid Metal Conduit
GSM Global System (Station) for Mobile
HCCS TIP’s Horizontal Cross Connection System (refer to
CCS & VCCS)
HDPE High Density Polyethylene Conduit
HDTV Advanced Television Standards Committee High-
Definition Digital Television
HEC Head End Cabinets(refer to HEIC, PA)
HEIC Head End Interface Cabinets(refer to HEC, PA)
HF High Frequency (Radio Band; Re FR, RF, VHF & UHF)
HSPA High Speed Packet Access
HZ Hertz
IBT Intersystem Bonding Termination (NEC 250.94)
IC Intercom
ICRA Infectious Control Risk Assessment
IDEN Integrated Digital Enhanced Network
IDC Insulation Displacement Contact
IDF Intermediate Distribution Frame
ILSM Interim Life Safety Measures
IMC Rigid Intermediate Steel Conduit
IRM Department of Veterans Affairs Office of Information
Resources Management
27 05 11 - 4
ISDN Integrated Services Digital Network
ISM Industrial, Scientific, Medical
IWS Intra-Building Wireless System
LAN Local Area Network
LBS Location Based Services, Leased Based Systems
LEC Local Exchange Carrier (refer to DEMARC, PBX & POTS)
LED Light Emitting Diode
LMR Land Mobile Radio
LTE Long Term Evolution, or 4G Standard for Wireless Data
Communications Technology
M Meter
MAS Medical Administration Service
MATV Master Antenna Television
MCR Main Computer Room
MCOR Main Computer Operators Room
MDF Main Distribution Frame
MH Manholes or Maintenance Holes
MHz Megaherts (106 Hz) mm Millimeter
MOU Memorandum of Understanding
MW Microwave (RF Band, Equipment or Services)
NID Network Interface Device (refer to DEMARC)
NEC National Electric Code
NOR Network Operations Room
NRTL OSHA Nationally Recognized Testing Laboratory
NS Nurse Stations
NTIA U.S. Department of Commerce National
Telecommunications and Information Administration
OEM Original Equipment Manufacturer
OI&T Office of Information and Technology
OPC VA’s Outpatient Clinic (refer to CBOC, VAMC)
OSH Department of Veterans Affairs Office of Occupational
Safety and Health
27 05 11 - 5
OSHA United States Department of Labor Occupational Safety and Health Administration
OTDR Optical Time-Domain Reflectometer
PA Public Address System (refer to HE, HEIC, RPEC)
PBX Private Branch Exchange (refer to DEMARC, LEC, POTS)
PCR Police Control Room (refer to SPCC, could be designated SCC)
PCS Personal Communications Service (refer to UPCS)
PE Professional Engineer
PM Project Manager
PoE Power over Ethernet
POTS Plain Old Telephone Service (refer to DEMARC, LEC, PBX)
PSTN Public Switched Telephone Network
PSRAS Public Safety Radio Amplification Systems
PTS Pay Telephone Station
PVC Poly-Vinyl Chloride
PWR Power (in Watts)
RAN Radio Access Network
RBB Rack Bonding Busbar
RE Resident Engineer or Senior Resident Engineer
RF Radio Frequency (refer to FR)
RFI Radio Frequency Interference (refer to EMI)
RFID RF Identification (Equipment, System or Personnel)
RMC Rigid Metal Conduit
RMU Rack Mounting Unit
RPEC Radio Paging Equipment Cabinets(refer to HEC, HEIC, PA)
RTLS Real Time Location Service or System
RUS Rural Utilities Service
SCC Security Control Console (refer to PCR, SPCC)
SMCS Spectrum Management and Communications Security
(COMSEC)
27 05 11 - 6
SFO Solicitation for Offers
SME Subject Matter Experts (refer to AHJ)
SMR Specialized Mobile Radio
SMS Security Management System
SNMP Simple Network Management Protocol
SPCC Security Police Control Center (refer to PCR, SMS)
STP Shielded Balanced Twisted Pair (refer to UTP)
STR Stacked Telecommunications Room
TAC VA’s Technology Acquisition Center, Austin, Texas
TCO Telecommunications Outlet
TER Telephone Equipment Room
TGB Telecommunications Grounding Busbar (also Secondary
Bonding Busbar (SBB))
TIP Telecommunications Infrastructure Plant
TMGB Telecommunications Main Grounding Busbar (also
Primary Bonding Busbar (PBB))
TMS Traffic Management System
TOR Telephone Operators Room
TP Balanced Twisted Pair (refer to STP and UTP)
TR Telecommunications Room (refer to STR)
TWP Twisted Pair
UHF Ultra High Frequency (Radio)
UMTS Universal Mobile Telecommunications System
UPCS Unlicensed Personal Communications Service (refer to
PCS)
UPS Uninterruptible Power Supply
USC United States Code
UTP Unshielded Balanced Twisted Pair (refer to TP and
STP)
UV Ultraviolet
V Volts
VAAR Veterans Affairs Acquisition Regulation
VACO Veterans Affairs Central Office
27 05 11 - 7
VAMC VA Medical Center (refer to CBOC, OPC, VACO)
VCCS TIP’s Vertical Cross Connection System (refer to CCS and HCCS)
VHF Very High Frequency (Radio)
VISN Veterans Integrated Services Network (refers to geographical region)
VSWR Voltage Standing Wave Radio
W Watts
WEB World Electronic Broadcast
WiMAX Worldwide Interoperability (for MW Access)
WI-FI Wireless Fidelity
WMTS Wireless Medical Telemetry Service
WSP Wireless Service Providers
B. Definitions:
1. Access Floor: Pathway system of removable floor panels supported on adjustable pedestals to allow cable placement in area below.
2. BNC Connector (BNC): United States Military Standard MIL-C-39012/21 bayonet-type coaxial connector with quick twist mating/unmating, and two lugs preventing accidental disconnection from pulling forces on cable.
3. Bond: Permanent joining of metallic parts to form an electrically conductive path to ensure electrical continuity and capacity to safely conduct any currents likely to be imposed to earth ground.
4. Bundled Microducts: All forms of jacketed microducts.
5. Conduit: Includes all raceway types specified.
6. Conveniently Accessible: Capable of being reached without use of ladders, or without climbing or crawling under or over obstacles such as, motors, pumps, belt guards, transformers, piping, ductwork, conduit and raceways.
7. Distributed (in house) Antenna System (DAS): An Emergency Radio Communications System installed for Emergency Responder (or first responders and Government personnel) use while inside facility to maintain contact with each respective control point; refer to
Section 27 53 19, DISTRIBUTED RADIO ANTENNA (WITHIN BUILDING)
EQUIPMENT AND SYSTEMS.
27 05 11 - 8
8. DEMARC, Extended DMARC or ENTR: Service provider's main point of demarcation owned by LEC or service provider and establishes a physical point where service provider's responsibilities for service and maintenance end. This point is called NID, in data networks.
9. Effectively Grounded: Intentionally bonded to earth through connections of low impedance having current carrying capacity to prevent buildup of currents and voltages resulting in hazard to equipment or persons.
10. Electrical Supervision: Analyzing a system’s function and components (i.e. cable breaks / shorts, inoperative stations, lights, LEDs and states of change, from primary to backup) on a 24/7/365 basis;
provide aural and visual emergency notification signals to minimum two remote designated or accepted monitoring stations.
11. Electrostatic Interference (ESI) or Electrostatic Discharge Interference: Refer to EMI and RFI.
12. Project 25 (2014) (P25 (TIA-102 Series)): Set of standards for local, state and Federal public safety organizations and agencies digital LMR services. P25 is applicable to LMR equipment authorized or licensed under the US Department of Commerce National
Telecommunications and Information Administration or FCC rules and regulations, and is a required standard capability for all LMR equipment and systems.
13. Grounding Electrode Conductor: (GEC) Conductor connected to earth grounding electrode.
14. Grounding Electrode System: Electrodes through which an effective connection to earth is established, including supplementary, communications system grounding electrodes and GEC.
15. Grounding Equalizer or Backbone Bonding Conductor (BBC): Conductor that interconnects elements of telecommunications grounding infrastructure.
16. Head End (HE): Equipment, hardware and software, or a master facility at originating point in a communications system designed for centralized communications control, signal processing, and distribution that acts as a common point of connection between equipment and devices connected to a network of interconnected equipment, possessing greatest authority for allowing information to be exchanged, with whom other equipment is subordinate.
27 05 11 - 9
17. Microducts: All forms of air blown fiber pathways.
18. Ohm: A unit of restive measurement.
19. Received Signal Strength Indication (RSSI): A measurement of power present in a received RF signal.
20. Service Provider Demarcation Point (SPDP): Not owned by LEC or service provider, but designated by Government as point within facility considered the DEMARC.
21. Sound (SND): Changing air pressure to audible signals over given time span.
22. System: Specific hardware, firmware, and software, functioning together as a unit, performing task for which it was designed.
23. Telecommunications Bonding Backbone (TBB): Conductors of appropriate size (minimum 53.49 mm2 [1/0 AWG]) stranded copper wire, that connect to Grounding Electrode System and route to telecommunications main grounding busbar (TMGB) and circulate to interconnect various TGBs and other locations shown on drawings.
24. Voice over Internet Protocol (VoIP): A telephone system in which voice signals are converted to packets and transmitted over LAN network using Transmission Control Protocol (TCP)/Internet Protocol
(IP). VA’S VoIP is not listed or coded for life and public safety, critical, emergency or other protection functions. When VoIP system or equipment is provided instead of PBX system or equipment, each TR
(STR) and DEMARC requires increased AC power provided to compensate for loss of PBX’s telephone instrument line power; and, to compensate for absence of PBX’s UPS capability.
25. Wide Area Network (WAN): A digital network that transcends localized LANs within a given geographic location. VA’S WAN/LAN is not nationally listed or coded for life and public safety, critical, emergency or other safety functions.
1.3 APPLICABLE PUBLICATIONS
A. Applicability of Standards: Unless documents include more stringent requirements, applicable construction industry standards have same force and effect as if bound or copied directly into the documents to extent referenced. Such standards are made a part of these documents by reference.
1. Each entity engaged in construction must be familiar with industry standards applicable to its construction activity.
27 05 11 - 10
2. Obtain standards directly from publication source, where copies of standards are needed to perform a required construction activity.
B. Government Codes, Standards and Executive Orders: Refer to http://www.cfm.va.gov/TIL/cPro.asp:
1. Federal Communications Commission, (FCC) CFR, Title 47:
Part 15 Restrictions of use for Part 15 listed RF
Equipment in Safety of Life Emergency Functions and Equipment Locations
Part 47 Chapter A, Paragraphs 6.1-6.23, Access to
Telecommunications Service, Telecommunications
Equipment and Customer Premises Equipment
Part 58 Television Broadcast Service
Part 73 Radio and Television Broadcast Rules
Part 90 Rules and Regulations, Appendix C
Form 854 Antenna Structure Registration
Chapter XXIII National Telecommunications and Information
Administration (NTIA, P/O Commerce, Chapter
XXIII) the ‘Red Book’– Chapters 7, 8 & 9 compliments CFR, Title 47, FCC Part 15, RF
Restriction of Use and Compliance in “Safety of
Life” Functions & Locations
2. US Department of Agriculture, (Title 7, USC, Chapter 55, Sections 2201, 2202 & 2203:RUS 1755 Telecommunications Standards and
Specifications for Materials, Equipment and Construction:
RUS Bull 1751F-630 Design of Aerial Cable Plants
RUS Bull 1751F-640 Design of Buried Cable Plant, Physical
Considerations
RUS Bull 1751F-643 Underground Plant Design
RUS Bull 1751F-815 Electrical Protection of Outside Plants, RUS Bull 1753F-201 Acceptance Tests of Telecommunications Plants
(PC-4)
RUS Bull 1753F-401 Splicing Copper and Fiber Optic Cables (PC-2)
RUS Bull 345-50 Trunk Carrier Systems (PE-60)
RUS Bull 345-65 Shield Bonding Connectors (PE-65)
RUS Bull 345-72 Filled Splice Closures (PE-74)
RUS Bull 345-83 Gas Tube Surge Arrestors (PE-80)
27 05 11 - 11
3. US Department of Commerce/National Institute of Standards Technology,(NIST):
FIPS PUB 1-1 Telecommunications Information Exchange
FIPS PUB 100/1 Interface between Data Terminal Equipment (DTE)
Circuit Terminating Equipment for operation with Packet Switched Networks, or Between Two
DTEs, by Dedicated Circuit
FIPS PUB 140/2 Telecommunications Information Security
Algorithms
FIPS PUB 143 General Purpose 37 Position Interface between
DTE and Data Circuit Terminating Equipment
FIPS 160/2 Electronic Data Interchange (EDI), FIPS 175 Federal Building Standard for
Telecommunications Pathway and Spaces
FIPS 191 Guideline for the Analysis of Local Area
Network Security
FIPS 197 Advanced Encryption Standard (AES)
FIPS 199 Standards for Security Categorization of
Federal Information and Information Systems
4. US Department of Defense, (DoD):
MIL-STD-188-110 Interoperability and Performance Standards for
Data Modems
MIL-STD-188-114 Electrical Characteristics of Digital Interface
Circuits
MIL-STD-188-115 Communications Timing and Synchronizations
Subsystems
MIL-C-28883 Advanced Narrowband Digital Voice Terminals
MIL-C-39012/21 Connectors, Receptacle, Electrical, Coaxial, Radio Frequency, (Series BNC (Uncabled), Socket
Contact, Jam Nut Mounted, Class 2)
5. US Department of Health and Human Services:
The Health Insurance Portability and Accountability Act of 1996
(HIPAA) Privacy, Security and Breach Notification Rules
6. US Department of Justice:
2010 Americans with Disabilities Act Standards for Accessible Design
(ADAAD).
27 05 11 - 12
7. US Department of Labor, (DoL) - Public Law 426-62 – CFR, Title 29, Part 1910, Chapter XVII - Occupational Safety and Health
Administration (OSHA), Occupational Safety and Health Standards):
Subpart 7 Approved NRTLs; obtain a copy at https://www.osha.gov/dts/otpca/nrtl/nrtllist.ht ml
Subpart 35 Compliance with NFPA 101, Life Safety Code
Subpart 36 Design and Construction Requirements for Exit
Routes
Subpart 268 Telecommunications
Subpart 305 Wiring Methods, Components, and Equipment for
General Use
Subpart 508 Americans with Disabilities Act Accessibility
Guidelines; technical requirement for accessibility to buildings and facilities by individuals with disabilities
8. US Department of Transportation, (DoT):
a. Public Law 85-625, CFR, Title 49, Part 1, Subpart C – Federal
Aviation Administration (FAA):AC 110/460-ID & AC 707 / 460-2E –
Advisory Circulars Standards for Construction of Antenna Towers, and 7450 and 7460-2 – Antenna Construction Registration Forms.
9. US Department of Veterans Affairs (VA): Office of Telecommunications
(OI&T), MP-6, PART VIII, TELECOMMUNICATIONS, CHAPTER 5, AUDIO, RADIO
AND TELEVISION (and COMSEC) COMMUNICATIONS SYSTEMS: Spectrum
Management and COMSEC Service (SMCS), AHJ for:
a. CoG, “Continuance of Government” communications guidelines and compliance.
b. COMSEC,“VA wide coordination and control of security classified communication assets.”
c. COOP, “Continuance of Operations” emergency communications guidelines and compliance.
d. FAA, FCC, and US Department of Commerce National Telecommunications and Information Administration, “VA wide RF
Co-ordination, Compliance and Licensing.”
e. Handbook 6100 – Telecommunications: Cyber and Information Security Office of Cyber and Information Security, and Handbook
6500 – Information Security Program.
27 05 11 - 13
f. Low Voltage Special Communications Systems “Design, Engineering, Construction Contract Specifications and Drawings Conformity, Proof of Performance Testing, VA Compliance and Life Safety
Certifications for CFM and VA Facility Low Voltage Special
Communications Projects (except Fire Alarm, Telephone and Data
Systems).”
g. SATCOM, “Satellite Communications” guidelines and compliance, and Security and Law Enforcement Systems – “Coordinates the Design, Engineering, Construction Contract Specifications and Drawings
Conformity, Proof of Performance Testing, VA Compliance, DEA and
Public Safety Certification(s) for CFM and VA Facility Security
Low Voltage Special Communications and Physical Security
Projects.
h. VHA’s National Center for Patient Safety – Veterans Health Administration (VHA) Warning System, Failure of Medical Alarm
Systems using Paging Technology to Notify Clinical Staff, July
2004.
i. VA’s CEOSH, concurrence with warning identified in VA Directive 7700.
j. Wireless and Handheld Devices, “Guidelines and Compliance,”
k. Office of Security and Law Enforcement: VA Directive 0730 and
Health Special Presidential Directive (HSPD)-12.
C. NRTL Standards: Refer to https://www.osha.gov/laws-regs/regulations/standardnumber/1926
1. Canadian Standards Association (CSA); same tests as presented by UL
2. Communications Certifications Laboratory (CEL); same tests as presented by UL.
3. Intertek Testing Services NA, Inc., (ITSNA), formerly Edison Testing Laboratory (ETL) same tests as presented by UL).
4. Underwriters Laboratory (UL):
1-2005 Flexible Metal Conduit
5-2011 Surface Metal Raceway and Fittings
6-2007 Rigid Metal Conduit
44-010 Thermoset-Insulated Wires and Cables
50-1995 Enclosures for Electrical Equipment
65-2010 Wired Cabinets
83-2008 Thermoplastic-Insulated Wires and Cables
27 05 11 - 14
96-2005 Lightning Protection Components
96A-2007 Installation Requirements for Lightning
Protection Systems
360-2013 Liquid-Tight Flexible Steel Conduit
444-2008 Communications Cables
467-2013 Grounding and Bonding Equipment
486A-486B-2013 Wire Connectors
486C-2013 Splicing Wire Connectors
486D-2005 Sealed Wire Connector Systems
486E-2009 Standard for Equipment Wiring Terminals for Use with Aluminum and/or Copper Conductors
493-2007 Thermoplastic-Insulated Underground Feeder and
Branch Circuit Cable
497/497A/497B/497C
497D/497E Protectors for Paired Conductors/Communications
Circuits/Data Communications and Fire Alarm
Circuits/coaxial circuits/voltage protections/Antenna Lead In
510-2005 Polyvinyl Chloride, Polyethylene and Rubber
Insulating Tape
514A-2013 Metallic Outlet Boxes
514B-2012 Fittings for Cable and Conduit
514C-1996 Nonmetallic Outlet Boxes, Flush-Device Boxes and Covers
651-2011 Schedule 40 and 80 Rigid PVC Conduit
651A-2011 Type EB and A Rigid PVC Conduit and HDPE
Conduit
797-2007 Electrical Metallic Tubing
884-2011 Underfloor Raceways and Fittings
1069-2007 Hospital Signaling and Nurse Call Equipment
1242-2006 Intermediate Metal Conduit
1449-2006 Standard for Transient Voltage Surge
Suppressors
1479-2003 Fire Tests of Through-Penetration Fire Stops
1480-2003 Speaker Standards for Fire Alarm, Emergency, Commercial and Professional use
27 05 11 - 15
1666-2007 Standard for Wire/Cable Vertical (Riser) Tray
Flame Tests
1685-2007 Vertical Tray Fire Protection and Smoke Release
Test for Electrical and Fiber Optic Cables
1861-2012 Communication Circuit Accessories
1863-2013 Standard for Safety, communications Circuits
Accessories
1865-2007 Standard for Safety for Vertical-Tray Fire
Protection and Smoke-Release Test for
Electrical and Optical-Fiber Cables
2024-2011 Standard for Optical Fiber Raceways
2024-2014 Standard for Cable Routing Assemblies and
Communications Raceways
2196-2001 Standard for Test of Fire Resistive Cable
60950-1 ed. 2-2014 Information Technology Equipment Safety
D. Industry Standards:
1. Advanced Television Systems Committee (ATSC):
A/53 Part 1: 2013 ATSC Digital Television Standard, Part 1, Digital Television System
A/53 Part 2: 2011 ATSC Digital Television Standard, Part 2, RF/Transmission System Characteristics
A/53 Part 3: 2013 ATSC Digital Television Standard, Part 3, Service Multiplex and Transport System
Characteristics
A/53 Part 4: 2009 ATSC Digital Television Standard, Part 4, MPEG-
2 Video System Characteristics
A/53 Part 5: 2014 ATSC Digital Television Standard, Part 5, AC-3
Audio System Characteristics
A/53 Part 6: 2014 ATSC digital Television Standard, Part 6, Enhanced AC-3 Audio System Characteristics
2. American Institute of Architects (AIA): 2006 Guidelines for Design & Construction of Health Care Facilities.
3. American Society of Mechanical Engineers (ASME):
A17.1 (2013) Safety Code for Elevators and Escalators
Includes Requirements for Elevators, Escalators, Dumbwaiters, Moving Walks, Material
27 05 11 - 16
Lifts, and Dumbwaiters with Automatic Transfer
Devices
17.3 (2011) Safety Code for Existing Elevators and
Escalators
17.4 (2009) Guide for Emergency Personnel
17.5 (2011) Elevator and Escalator Electrical Equipment
4. American Society for Testing and Materials (ASTM):
B1 (2001) Standard Specification for Hard-Drawn Copper
Wire
B8 (2004) Standard Specification for Concentric-Lay-
Stranded Copper Conductors, Hard, Medium-Hard, or Soft
D1557 (2012) Standard Test Methods for Laboratory Compaction
Characteristics of Soil Using Modified Effort
56,000 ft-lbf/ft3 (2,700 kN-m/m3)
D2301 (2004) Standard Specification for Vinyl Chloride
Plastic Pressure Sensitive Electrical
Insulating Tape
B258-02 (2008) Standard Specification for Standard Nominal
Diameters and Cross-Sectional Areas of AWG
Sizes of Solid Round Wires Used as Electrical
Conductors
D709-01(2007) Standard Specification for Laminated
Thermosetting Materials
D4566 (2008) Standard Test Methods for Electrical
Performance Properties of Insulations and
Jackets for Telecommunications Wire and Cable
5. American Telephone and Telegraph Corporation (AT&T) - Obtain following AT&T Publications at https://ebiznet.sbc.com/sbcnebs/
ATT-TP-76200 (2013) Network Equipment and Power Grounding, Environmental, and Physical Design Requirements
ATT-TP-76300(2012) Merged AT&T Affiliate Companies Installation
Requirements
ATT-TP-76305 (2013) Common Systems Cable and Wire Installation and
Removal Requirements - Cable Racks and Raceways
ATT-TP-76306 (2009) Electrostatic Discharge Control
ATT-TP-76400 (2012) Detail Engineering Requirements
27 05 11 - 17
ATT-TP-76402 (2013) AT&T Raised Access Floor Engineering and
Installation Requirements
ATT-TP-76405 (2011) Technical Requirements for Supplemental Cooling
Systems in Network Equipment Environments
ATT-TP-76416 (2011) Grounding and Bonding Requirements for Network
Facilities
ATT-TP-76440 (2005) Ethernet Specification
ATT-TP-76450 (2013) Common Systems Equipment Interconnection
Standards for AT&T Network Equipment Spaces
ATT-TP-76461 (2008) Fiber Optic Cleaning
ATT-TP-76900 (2010) AT&T Installation Testing Requirement
ATT-TP-76911 (1999) AT&T LEC Technical Publication Notice
6. British Standards Institution (BSI):
BS EN 50109-2 Hand Crimping Tools - Tools for The Crimp
Termination of Electric Cables and Wires for
Low Frequency and Radio Frequency Applications
– All Parts & Sections. October 1997
7. Building Industry Consulting Service International(BICSI):
ANSI/BICSI 002-2011 Data Center Design and Implementation Best
Practices
ANSI/BICSI 004-2012 Information Technology Systems Design and
Implementation Best Practices for Healthcare
Institutions and Facilities
ANSI/NECA/BICSI
568-2006 Standard for Installing Commercial Building
Telecommunications Cabling
NECA/BICSI 607-2011 Standard for Telecommunications Bonding and
Grounding Planning and Installation Methods for
Commercial Buildings
ANSI/BICSI 005-2013 Electronic Safety and Security (ESS) System
Design and Implementation Best Practices
8. Electronic Components Assemblies and Materials Association,(ECA).
ECA EIA/RS-270 (1973)Tools, Crimping, Solderless Wiring Devices –
Recommended Procedures for User Certification
EIA/ECA 310-E (2005) Cabinets, and Associated Equipment
9. Facility Guidelines Institute: 2010 Guidelines for Design and Construction of Health Care Facilities.
27 05 11 - 18
10. Insulated Cable Engineers Association (ICEA):
ANSI/ICEA
S-80-576-2002 Category 1 & 2 Individually Unshielded Twisted-
Pair Indoor Cables for Use in Communications
Wiring Systems
ANSI/ICEA
S-84-608-2010 Telecommunications Cable, Filled Polyolefin
Insulated Copper Conductor, S-87-640(2011)
Optical Fiber Outside Plant Communications
Cable
ANSI/ICEA
S-90-661-2012 Category 3, 5, & 5e Individually Unshielded
Twisted-Pair Indoor Cable for Use in General
Purpose and LAN Communication Wiring Systems
S-98-688 (2012) Broadband Twisted Pair Cable Aircore, Polyolefin Insulated, Copper Conductors
S-99-689 (2012) Broadband Twisted Pair Cable Filled, Polyolefin
Insulated, Copper Conductors
ICEA S-102-700
(2004) Category 6 Individually Unshielded Twisted Pair
Indoor Cables (With or Without an Overall
Shield) for use in Communications Wiring
Systems Technical Requirements
11. Institute of Electrical and Electronics Engineers (IEEE):
ISSN 0739-5175 March-April 2008 Engineering in Medicine and
Biology Magazine, IEEE (Volume: 27, Issue:2)
Medical Grade-Mission Critical-Wireless
Networks
IEEE C2-2012 National Electrical Safety Code (NESC)
C62.41.2-2002/
Cor 1-2012 IEEE Recommended Practice on Characterization of
Surges in Low-Voltage (1000 V and Less) AC
Power Circuits 4)
C62.45-2002 IEEE Recommended Practice on Surge Testing for
Equipment Connected to Low-Voltage (1000 V and
Less) AC Power Circuits
27 05 11 - 19
81-2012 IEEE Guide for Measuring Earth Resistivity, Ground
Impedance, and Earth Surface Potentials of a
Grounding System
100-1992 IEEE the New IEEE Standards Dictionary of
Electrical and Electronics Terms
602-2007 IEEE Recommended Practice for Electric Systems in Health Care Facilities
1100-2005 IEEE Recommended Practice for Powering and
Grounding Electronic Equipment
12. International Code Council:
AC193 (2014) Mechanical Anchors in Concrete Elements
13. International Organization for Standardization (ISO):
ISO/TR 21730 (2007) Use of Mobile Wireless Communication and
Computing Technology in Healthcare Facilities -
Recommendations for Electromagnetic
Compatibility (Management of Unintentional
Electromagnetic Interference) with Medical
Devices
14. National Electrical Manufacturers Association (NEMA):
NEMA 250 (2008) Enclosures for Electrical Equipment (1,000V
Maximum)
ANSI C62.61 (1993) American National Standard for Gas Tube Surge
Arresters on Wire Line Telephone Circuits
ANSI/NEMA FB 1 (2012)Fittings, Cast Metal Boxes and Conduit Bodies for Conduit, Electrical Metallic Tubing EMT) and Cable
ANSI/NEMA OS 1 (2009)Sheet-Steel Outlet Boxes, Device Boxes, Covers, and Box Supports
NEMA SB 19 (R2007) NEMA Installation Guide for Nurse Call Systems
TC 3 (2004) Polyvinyl Chloride (PVC) Fittings for Use with
Rigid PVC Conduit and Tubing
NEMA VE 2 (2006) Cable Tray Installation Guidelines
15. National Fire Protection Association (NFPA):
70E-2015 Standard for Electrical Safety in the Workplace
70-2014 National Electrical Code (NEC)
72-2013 National Fire Alarm Code
27 05 11 - 20
75-2013 Standard for the Fire Protection of Information
Technological Equipment
76-2012 Recommended Practice for the Fire Protection of
Telecommunications Facilities
77-2014 Recommended Practice on Static Electricity
90A-2015 Standard for the Installation of Air
Conditioning and Ventilating Systems
99-2015 Health Care Facilities Code
101-2015 Life Safety Code
241 Safeguarding construction, alternation and
Demolition Operations
255-2006 Standard Method of Test of Surface Burning
Characteristics of Building Materials
262 - 2011 Standard Method of Test for Flame Travel and
Smoke of Wires and Cables for Use in Air-
Handling Spaces
780-2014 Standard for the Installation of Lightning
Protection Systems
1221-2013 Standard for the Installation, Maintenance, and
Use of Emergency Services Communications
Systems
5000-2015 Building Construction and Safety Code
16. Society for Protective Coatings (SSPC):
SSPC SP 6/NACE No.3 (2007) Commercial Blast Cleaning
17. Society of Cable Telecommunications Engineers (SCTE):
ANSI/SCTE 15 2006 Specification for Trunk, Feeder and
Distribution Coaxial Cable
18. Telecommunications Industry Association (TIA):
TIA-120 Series Telecommunications Land Mobile communications
(APCO/Project 25) (January 2014)
TIA TSB-140 Additional Guidelines for Field-Testing Length, Loss and Polarity of Optical Fiber Cabling
Systems (2004)
TIA-155 Guidelines for the Assessment and Mitigation of
Installed Category 6 Cabling to Support
10GBASE-T (2010)
27 05 11 - 21
TIA TSB-162-A Telecommunications Cabling Guidelines for
Wireless Access Points (2013)
TIA-222-G Structural Standard for Antenna Supporting
Structures and Antennas (2014)
TIA/EIA-423-B Electrical Characteristics of Unbalanced
Voltage Digital Interface Circuits (2012)
TIA-455-C General Requirements for Standard Test
Procedures for Optical Fibers, Cables, Transducers, Sensors, Connecting and
Terminating Devices, and other Fiber Optic
Components (August 2014)
TIA-455-53-A FOTP-53 Attenuation by Substitution
Measurements for Multimode Graded-Index Optical
Fibers in Fiber Assemblies (Long Length)
(September 2001)
TIA-455-61-A FOTP-61 Measurement of Fiber of Cable
Attenuation Using an OTDR (July 2003)
TIA-472D000-B Fiber Optic Communications Cable for Outside
Plant Use (July 2007)
ANSI/TIA-492-B 62.5-µ Core Diameter/125-um Cladding Diameter
Class 1a Graded-Index Multimode Optical Fibers
(November 2009)
ANSI/TIA-492AAAB-A 50-um Core Diameter/125-um Cladding Diameter
Class IA Graded-Index Multimode Optically
Optimized American Standard Fibers (November
TIA-492CAAA Detail Specification for Class IVa Dispersion-
Unshifted Single-Mode Optical Fibers (September
2002)
TIA-492E000 Sectional Specification for Class IVd Nonzero-
Dispersion Single-Mode Optical Fibers for the
1,550 nm Window (September 2002)
TIA-526-7-B Measurement of Optical Power Loss of Installed
Single-Mode Fiber Cable Plant – OFSTP-7
(December 2008)
27 05 11 - 22
TIA-526.14-A Optical Power Loss Measurements of Installed
Multimode Fiber Cable Plant – SFSTP-14 (August
1998)
TIA-568 Revision/Edition: C Commercial Building
Telecommunications Cabling Standard Set: (TIA-
568-C.0-2 Generic Telecommunications Cabling for Customer Premises (2012), TIA-568-C.1-1
Commercial Building Telecommunications Cabling
Standard Part 1: General Requirements (2012), TIA-568-C.2 Commercial Building
Telecommunications Cabling Standard—Part 2:
Balanced Twisted Pair Cabling Components
(2009), TIA-568-C.3-1 Optical Fiber Cabling
Components Standard, (2011) AND TIA-568-C.4
Broadband Coaxial Cabling and Components
Standard (2011) with addendums and erratas
TIA-569 Revision/Edition C Telecommunications Pathways and Spaces (March 2013)
TIA-574 Position Non-Synchronous Interface between Data
Terminal equipment and Data Circuit Terminating
Equipment Employing Serial Binary Interchange
(May 2003)
TIA/EIA-590-A Standard for Physical Location and Protection of Below Ground Fiber Optic Cable Plant (July
2001)
TIA-598-D Optical Fiber Cable Color Coding (January 2005)
TIA-604-10-B Fiber Optic Connector Intermateablility
Standard (August 2008)
ANSI/TIA-606-B Administration Standard for Telecommunications
Infrastructure (2012)
TIA-607-B Generic Telecommunications Bonding and
Grounding (Earthing) For Customer Premises
(January 2013)
TIA-613 High Speed Serial Interface for Data Terminal
Equipment and Data Circuit Terminal Equipment
(September 2005)
27 05 11 - 23
ANSI/TIA-758-B Customer-owned Outside Plant Telecommunications
Infrastructure Standard (April 2012)
ANSI/TIA-854 A Full Duplex Ethernet Specification for 1000
Mb/s (1000BASE-TX) Operating over Category 6
Balanced Twisted-Pair Cabling (2001)
ANSI/TIA-862-A Building Automation Systems Cabling Standard
(April 2011)
TIA-942-A Telecommunications Infrastructure Standard for
Data Centers (March 2014)
TIA-1152 Requirements for Field Testing Instruments and
Measurements for Balanced Twisted Pair Cabling
(September 2009)
TIA-1179 Healthcare Facility Telecommunications
Infrastructure Standard (July 2010)
1.4 SINGULAR NUMBER
A. Where any device or part of equipment is referred in singular number (such as " rack"), reference applies to as many such devices as are required to complete installation.
1.5 RELATED WORK
A. Specification Order of Precedence: FAR Clause 52.236-21, VAAR Clause 852.236-71.
1. Field Cutting and Patching: Section 09 91 00, PAINTING.
2. Additional submittal requirements: Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA AND SAMPLES.
3. Availability and source of references and standards specified in applicable publications: Section 01 42 19, REFERENCE STANDARDS.
4. Control of environmental pollution and damage for air, water, and land resources: Section 01 57 19, TEMPORARY ENVIRONMENTAL CONTROLS.
5. Requirements for non-hazardous building construction and demolition waste: Section 01 74 19, CONSTRUCTION WASTE MANAGEMENT.
6. General requirements and procedures to comply with various federal mandates and U.S. Department of Veterans Affairs (VA) policies for sustainable design: Section 01 81 13,SUSTAINABLE DESIGN
REQUIREMENTS.
7. Closures of openings in walls, floors, and roof decks against penetration of flame, heat, and smoke or gases in fire resistant rated construction: Section 07 84 00, FIRESTOPPING.
27 05 11 - 24
8. Sealant and caulking materials and their application: Section 07 92
00, JOINT SEALANTS.
9. General electrical requirements that are common to more than one section of Division 26: Section 26 05 11, REQUIREMENTS FOR
ELECTRICAL INSTALLATIONS.
10. Electrical conductors and cables in electrical systems rated 600 V and below: Section 26 05 21, LOW VOLTAGE ELECTRICAL POWER CONDUCTORS
AND CABLES (600 VOLTS AND BELOW).
11. Requirements for personnel safety and to provide a low impedance path to ground for possible ground fault currents: Section 26 05 26, GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS.
12. Conduit and boxes: Section 26 05 33, RACEWAYS AND BOXES FOR
ELECTRICAL SYSTEMS.
13. Wiring devices: Section 26 27 26, WIRING DEVICES.
14. Underground ducts, raceways, precast manholes and pull boxes:
Section 26 05 41, UNDERGROUND ELECTRICAL CONSTRUCTION.
15. Lightning protection: Section 26 41 00, FACILITY LIGHTNING
PROTECTION.
16. General requirements common to more than one section in Division 28:
Section 28 05 00, COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND
SECURITY.
17. Conductors and cables for electronic safety and security systems:
Section 28 05 13, CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND
SECURITY.
18. Low impedance path to ground for electronic safety and security system ground fault currents: Section 28 05 26, GROUNDING AND
BONDING FOR SECURITY SYSTEMS.
19. Conduits and partitioned telecommunications raceways for Electronic Safety and Security systems: Section 28 05 28.33, CONDUITS AND BACK
BOXES FOR ELECTRONIC SAFETY AND SECURITY.
20. Physical Access Control System field-installed controllers connected by data transmission network: Section 28 13 00, PHYSICAL ACCESS
DETECTION.
21. Detection and screening systems: Section 28 13 53, SECURITY ACCESS
DETECTION.
27 05 11 - 25
22. Intrusion sensors and detection devices, and communication links to perform monitoring, alarm, and control functions: Section 28 16 11, INTRUSION DETECTION EQUIPMENT AND SYSTEMS.
23. Video surveillance system cameras, data transmission wiring, and control stations with associated equipment: Section 28 23 00, VIDEO
SURVEILLANCE EQUIPMENT AND SYSTEMS.
24. Duress-panic alarms, emergency phones or call boxes, intercom systems, data transmission wiring and associated equipment: Section
28 26 00, ELECTRONIC PERSONAL PROTECTION EQUIPMENT AND SYSTEMS.
25. Alarm initiating devices, alarm notification appliances, control units, fire safety control devices, annunciators, power supplies, and wiring: Section 28 31 00, FIRE DETECTION AND ALARM.
26. Emergency Call telephones, intercom systems, with blue strobe light and equipment: Section 28 52 31, SECURITY EMERGENCY CALL/DURESS
ALARM/COMMUNICATIONS SYSTEM AND EQUIPMENT.
1.6 ADMINISTRATIVE REQUIREMENTS
A. Assign a single communications project manager to serve as point of contact for Government, contractor, and design professional.
B. Be proactive in scheduling work.
1. Use of premises is restricted at times directed by COR.
2. Movement of materials: Unload materials and equipment delivered to site. Pay costs for rigging, hoisting, lowering and moving equipment on and around site, in building or on roof.
3. Coordinate installation of required supporting devices and sleeves to be set in poured-in-place concrete and other structural components, as they are constructed.
4. Sequence, coordinate, and integrate installations of materials and equipment for efficient flow of Work. Plan for large equipment requiring positioning prior to closing in building.
5. Coordinate connection of materials, equipment, and systems with exterior underground and overhead utilities and services. Comply with requirements of governing regulations, franchised service companies, and controlling agencies; provide required connection for each service.
6. Initiate and maintain discussion regarding schedule for ceiling construction and install cables to meet that schedule.
27 05 11 - 26
C. Contact the Office of Telecommunications, Special Communications Team (005OP2H3) (202)461-5310 to have a Government-accepted
Telecommunications COR assigned to project for telecommunications review, equipment and system approval and coordination with other VA personnel.
D. Communications Project Manager Responsibilities:
1. Assume responsibility for overall telecommunications system integration and coordination of work among trades, subcontractors, and authorized system installers.
2. Coordinate with related work indicated on drawings or specified.
3. Manage work related to telecommunications system installation in a manner approved by manufacturer.
1.7 SUBMITTALS
A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT
DATA, AND SAMPLES.
B. Provide parts list including quantity of spare parts.
C. Provide manufacturer product information. Government reserves the right to require a list of installations where products have been in operation.
D. All connections to existing facility shall be approved by COR and coordinated with equipment vendor prior to purchase. Existing system to connect to the facility are as follow:
1. GetWell system
2. Tek-tone 120 (nurse call system)
3. AVS-PL(Overhead paging system)
4. Paitient WIFI
5. Roam Alert
6. B.M.S
E. Provide Source Quality Control Submittal:
1. Submit written certification from OEM indicating that proposed supervisor of installation and proposed provider of warranty maintenance are authorized representatives of OEM. Include individual's legal name, contact information and OEM credentials in certification.
2. Submit written certification from OEM that wiring and connection diagrams meet Government Life Safety Guidelines, NFPA, NEC, NRTL, 27 05 11 - 27 these specifications, and Joint Commission requirements and…