This document is a detailed installation drawing set for ceiling lifts at the VA Trinka Davis Veteran Village facility. The drawings specify an Arjo ECS (Embedded Ceiling System) track installation for 12 rooms (Rooms 122-139), with each room receiving a ceiling lift system with a safe working load of 600 lbs [272 kg]. The installation involves both embedded and ceiling-mounted track configurations, with specific requirements for track brackets, lateral braces, and structural mounting.
Key technical specifications include a maximum 2½" distance between angle fittings and ceiling, Unistrut P1000T strut bridges with spans ranging from 1'-8" to 10'-4", and a comprehensive hardware kit including threaded rods, nuts, washers, and mounting brackets. The drawings emphasize critical installation notes such as verifying ceiling structural capacity, removing potential obstructions, and ensuring precise track alignment. The installation also includes an X-Y gate system and an ECS-CSTAT charging configuration with contact boxes and wiring kit, with compatibility noted for V5 Duo and MS600 systems.
View the file
Other files
Show all 50
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DISTRIBUTOR :
REPRESENTATIVE :
DATE (DD-MMM-YYYY) :
REFERENCE # : PAGE :
INSTALLATION DRAWING
1. The ceiling minimum structure capacity must be able to support the load specified on the installation drawing.
2. Electrical power source outlet already available by the facility at a maximum distance of 3 meters from charging station.
3. Any obstructions such as vents, pipes, lights and sprinklers that could possibly be in the path of the ceiling lifts to be removed or relocated by the facility prior to installation.
4. Modifications of door headers by the facility.
5. Arjo reserves the right to slightly modify the track layout if necessary.
6. See the "Agreed Conditions for the Installation of Ceiling Lifts" document included with this quote for important installation details.
7. Arjo will not be held responsible for any damages, inconvenience, resulting from hitting any non visible conduits during our installation process.
8. Signed drawings are required prior to ordering and installation of ceiling lifts. This signature of each drawings confirms agreement of all the conditions listed above.
IMPORTANT NOTES
MY SIGNATURE BELOW VERIFIES THAT I HAVE:
Reviewed all ____ pages, with a total quantity of ____ rooms, for the approbation of layout for each room and the approbation of structure for each room. I verify that the answers below are accurate to the best of my knowledge and I understand that the quote produced is dependent upon the conditions below as well as this full drawing set.
· Is a load dock available? YES NO
· Can facility accept shipment and store until install begins? YES NO
· Will a drop trailer be needed? YES NO
· Is parking available on site? Is there a fee involved? YES NO
· Are there any installation time frame limitations?
What are they? YES NO
· Is a level of infectious control required? YES NO
If YES, then what level ___________________________
CUSTOMER
APPROVAL: DATE:
REVISION(S) DATE(S) (D-M-Y)
VA TRINKA DAVIS
VETERAN VILLAGE
QC-11032301
03-NOV-2023
ARJO
TIM MUCHNA
1 / 19
Rev1-un001629 07-NOV-2023
Rev2-un001629 10-NOV-2023
Legend
IV
(*) Symbol may vary depending of equipment type
Track
ServZone
Track with gate
X-Y Trolley (Suspended)
X-Y Trolley (Embedded)
Turntable (Auto/Manual)
Track with gate reverse
Wall post
Wall bracket
Wall post side
Track with service zone
Track with wall fixation
Track with T-junction
Exchanger
Swivel pole
IV track
Curtain track
Sprinkler
Smoke detector
Electrical outlet
Ceiling light
Ceiling vent
Access trap required
Existing access trap
Additional items
Motor/charger location
SPRINKLER SHIM
ECS-CSTAT
X-Y alim. type + options
BATH
122A
BEDROOM
156"h90
156"h90 h
ServZone
ServZone h
79"h90 h
ECS-CSTAT
LISTING OF ROOM NUMBER(S):
- ALL HARDWARE INCLUDED.
(ACCORDING TO STRUCTURE)
QUANTITY OF ROOMS:
DRAWN BY :
REFERENCE # : PAGE :
SCALE :
DATE CREATED (DD-MMM-YYYY) :
SAFE WORKING LOAD BELOW LIFT:
WEIGHT FOR LOAD TEST MAY VARY DEPENDING YOUR REGION
VA TRINKA DAVIS
VETERAN VILLAGE
QC-11032301
03-NOV-2023
un001629 1/4" = 1'
2 / 19
600LB [272KG]
Rev1-un001629 07-NOV-2023
Rev2-un001629 10-NOV-2023
THIS LAYOUT HAS BEEN PREPARED WITH SUPPLIED DATA. NOTE: CUTTING OF RAILS ON SITE ONLY
A=108"
B=52"
F=16"
G=72"
H=6" ECS SYSTEM
EMBEDDED TRACKS
NOTE: ATTENTION INSTALLERS
*****Any deviation/changes from the Arjo specified installation details i.e. hardware, bracing, track layout
MUST be captured, marked on the drawings and returned to Arjo for an as built revision.*****
B
G
A
TILE
NOTE: ATTENTION INSTALLERS
*****XY PORETION OF SYSTEM
WILL BE EMBEDDED
LINEAR PORTION OF SYSTEM
WILL BE CEILING MOUNTED.*****
BEDROOM
BATH
123A
156"h90
156"h90 h
ServZone
ServZone h
79"h90 h
ECS-CSTAT
LISTING OF ROOM NUMBER(S):
- ALL HARDWARE INCLUDED.
(ACCORDING TO STRUCTURE)
QUANTITY OF ROOMS:
DRAWN BY :
REFERENCE # : PAGE :
SCALE :
DATE CREATED (DD-MMM-YYYY) :
SAFE WORKING LOAD BELOW LIFT:
WEIGHT FOR LOAD TEST MAY VARY DEPENDING YOUR REGION
VA TRINKA DAVIS
VETERAN VILLAGE
QC-11032301
03-NOV-2023
un001629 1/4" = 1'
3 / 19
600LB [272KG]
Rev1-un001629 07-NOV-2023
Rev2-un001629 10-NOV-2023
THIS LAYOUT HAS BEEN PREPARED WITH SUPPLIED DATA. NOTE: CUTTING OF RAILS ON SITE ONLY
B
G
A
TILE
A=108"
B=52"
F=16"
G=72"
H=6" ECS SYSTEM
EMBEDDED TRACKS
NOTE: ATTENTION INSTALLERS
*****Any deviation/changes from the Arjo specified installation details i.e. hardware, bracing, track layout
MUST be captured, marked on the drawings and returned to Arjo for an as built revision.*****
B
G
A
TILE
NOTE: ATTENTION INSTALLERS
*****XY PORETION OF SYSTEM
WILL BE EMBEDDED
124A
BEDROOM
156"h90
156"h90 h
ServZone
ServZone h
79"h90 h
ECS-CSTAT
LISTING OF ROOM NUMBER(S):
- ALL HARDWARE INCLUDED.
(ACCORDING TO STRUCTURE)
QUANTITY OF ROOMS:
DRAWN BY :
REFERENCE # : PAGE :
SCALE :
DATE CREATED (DD-MMM-YYYY) :
SAFE WORKING LOAD BELOW LIFT:
WEIGHT FOR LOAD TEST MAY VARY DEPENDING YOUR REGION
VA TRINKA DAVIS
VETERAN VILLAGE
QC-11032301
03-NOV-2023
un001629 1/4" = 1'
4 / 19
600LB [272KG]
Rev1-un001629 07-NOV-2023
Rev2-un001629 10-NOV-2023
THIS LAYOUT HAS BEEN PREPARED WITH SUPPLIED DATA. NOTE: CUTTING OF RAILS ON SITE ONLY
B
G
A
TILE
A=108"
B=52"
F=16"
G=72"
H=6" ECS SYSTEM
EMBEDDED TRACKS
NOTE: ATTENTION INSTALLERS
*****Any deviation/changes from the Arjo specified installation details i.e. hardware, bracing, track layout
MUST be captured, marked on the drawings and returned to Arjo for an as built revision.*****
B
G
A
TILE
NOTE: ATTENTION INSTALLERS
*****XY PORETION OF SYSTEM
WILL BE EMBEDDED
BATH
125A
156"h90
156"h90 h
ServZone
ServZone h
79"h90 h
ECS-CSTAT
LISTING OF ROOM NUMBER(S):
- ALL HARDWARE INCLUDED.
(ACCORDING TO STRUCTURE)
QUANTITY OF ROOMS:
DRAWN BY :
REFERENCE # : PAGE :
SCALE :
DATE CREATED (DD-MMM-YYYY) :
SAFE WORKING LOAD BELOW LIFT:
WEIGHT FOR LOAD TEST MAY VARY DEPENDING YOUR REGION
VA TRINKA DAVIS
VETERAN VILLAGE
QC-11032301
03-NOV-2023
un001629 1/4" = 1'
5 / 19
600LB [272KG]
Rev1-un001629 07-NOV-2023
Rev2-un001629 10-NOV-2023
THIS LAYOUT HAS BEEN PREPARED WITH SUPPLIED DATA. NOTE: CUTTING OF RAILS ON SITE ONLY
B
G
A
TILE
A=108"
B=52"
F=16"
G=72"
H=6" ECS SYSTEM
EMBEDDED TRACKS
NOTE: ATTENTION INSTALLERS
*****Any deviation/changes from the Arjo specified installation details i.e. hardware, bracing, track layout
MUST be captured, marked on the drawings and returned to Arjo for an as built revision.*****
B
G
A
TILE
NOTE: ATTENTION INSTALLERS
*****XY PORETION OF SYSTEM
WILL BE EMBEDDED
126A
BEDROOM
156"h90
156"h90 h
ServZone
ServZone h
79"h90 h
ECS-CSTAT
LISTING OF ROOM NUMBER(S):
- ALL HARDWARE INCLUDED.
(ACCORDING TO STRUCTURE)
QUANTITY OF ROOMS:
DRAWN BY :
REFERENCE # : PAGE :
SCALE :
DATE CREATED (DD-MMM-YYYY) :
SAFE WORKING LOAD BELOW LIFT:
WEIGHT FOR LOAD TEST MAY VARY DEPENDING YOUR REGION
VA TRINKA DAVIS
VETERAN VILLAGE
QC-11032301
03-NOV-2023
un001629 1/4" = 1'
6 / 19
600LB [272KG]
Rev1-un001629 07-NOV-2023
Rev2-un001629 10-NOV-2023
THIS LAYOUT HAS BEEN PREPARED WITH SUPPLIED DATA. NOTE: CUTTING OF RAILS ON SITE ONLY
B
G
A
TILE
A=108"
B=52"
F=16"
G=72"
H=6" ECS SYSTEM
EMBEDDED TRACKS
NOTE: ATTENTION INSTALLERS
*****Any deviation/changes from the Arjo specified installation details i.e. hardware, bracing, track layout
MUST be captured, marked on the drawings and returned to Arjo for an as built revision.*****
B
G
A
TILE
NOTE: ATTENTION INSTALLERS
*****XY PORETION OF SYSTEM
WILL BE EMBEDDED
BATH
130A
156"H90
156"H90
H
E C
S E
C S
156"H90
ServZone
ServZone
LISTING OF ROOM NUMBER(S):
- ALL HARDWARE INCLUDED.
(ACCORDING TO STRUCTURE)
QUANTITY OF ROOMS:
DRAWN BY :
REFERENCE # : PAGE :
SCALE :
DATE CREATED (DD-MMM-YYYY) :
SAFE WORKING LOAD BELOW LIFT:
WEIGHT FOR LOAD TEST MAY VARY DEPENDING YOUR REGION
VA TRINKA DAVIS
VETERAN VILLAGE
QC-11032301
03-NOV-2023
un001629 1/4" = 1'
7 / 19
600LB [272KG]
Rev1-un001629 07-NOV-2023
Rev2-un001629 10-NOV-2023
THIS LAYOUT HAS BEEN PREPARED WITH SUPPLIED DATA. NOTE: CUTTING OF RAILS ON SITE ONLY
B
G
A
TILE
A=108"
B=52"
F=16"
G=72"
H=6" ECS SYSTEM
EMBEDDED TRACKS
NOTE: ATTENTION INSTALLERS
*****Any deviation/changes from the Arjo specified installation details i.e. hardware, bracing, track layout
MUST be captured, marked on the drawings and returned to Arjo for an as built revision.*****
B
G
A
TILE
A=108"
B=52"
F=16"
G=72" ECS SYSTEM
EMBEDDED TRACKS
131A
BEDROOM
156"H90
156"H90
H
E C
S E
C S
ServZone
ServZone
LISTING OF ROOM NUMBER(S):
- ALL HARDWARE INCLUDED.
(ACCORDING TO STRUCTURE)
QUANTITY OF ROOMS:
DRAWN BY :
REFERENCE # : PAGE :
SCALE :
DATE CREATED (DD-MMM-YYYY) :
SAFE WORKING LOAD BELOW LIFT:
WEIGHT FOR LOAD TEST MAY VARY DEPENDING YOUR REGION
VA TRINKA DAVIS
VETERAN VILLAGE
QC-11032301
03-NOV-2023
un001629 1/4" = 1'
8 / 19
600LB [272KG]
Rev1-un001629 07-NOV-2023
Rev2-un001629 10-NOV-2023
THIS LAYOUT HAS BEEN PREPARED WITH SUPPLIED DATA. NOTE: CUTTING OF RAILS ON SITE ONLY
B
G
A
TILE
A=108"
B=52"
F=16"
G=72"
H=6" ECS SYSTEM
EMBEDDED TRACKS
NOTE: ATTENTION INSTALLERS
*****Any deviation/changes from the Arjo specified installation details i.e. hardware, bracing, track layout
MUST be captured, marked on the drawings and returned to Arjo for an as built revision.*****
B
G
A
TILE
GAS CYLINDER
STORAGE
BATH
135A
BEDROOM
156"h90
156"h90 h
ServZone
ServZone h
79"h90 h
ECS-CSTAT
LISTING OF ROOM NUMBER(S):
- ALL HARDWARE INCLUDED.
(ACCORDING TO STRUCTURE)
QUANTITY OF ROOMS:
DRAWN BY :
REFERENCE # : PAGE :
SCALE :
DATE CREATED (DD-MMM-YYYY) :
SAFE WORKING LOAD BELOW LIFT:
WEIGHT FOR LOAD TEST MAY VARY DEPENDING YOUR REGION
VA TRINKA DAVIS
VETERAN VILLAGE
QC-11032301
03-NOV-2023
un001629 1/4" = 1'
9 / 19
600LB [272KG]
Rev1-un001629 07-NOV-2023
Rev2-un001629 10-NOV-2023
THIS LAYOUT HAS BEEN PREPARED WITH SUPPLIED DATA. NOTE: CUTTING OF RAILS ON SITE ONLY
B
G
A
TILE
A=108"
B=52"
F=16"
G=72"
H=6" ECS SYSTEM
EMBEDDED TRACKS
NOTE: ATTENTION INSTALLERS
*****Any deviation/changes from the Arjo specified installation details i.e. hardware, bracing, track layout
MUST be captured, marked on the drawings and returned to Arjo for an as built revision.*****
B
G
A
TILE
NOTE: ATTENTION INSTALLERS
*****XY PORETION OF SYSTEM
WILL BE EMBEDDED
BATH
136A
6"
156"h90
156"h90 h
ServZone
ServZone h
79"h90 h
ECS-CSTAT
LISTING OF ROOM NUMBER(S):
- ALL HARDWARE INCLUDED.
(ACCORDING TO STRUCTURE)
QUANTITY OF ROOMS:
DRAWN BY :
REFERENCE # : PAGE :
SCALE :
DATE CREATED (DD-MMM-YYYY) :
SAFE WORKING LOAD BELOW LIFT:
WEIGHT FOR LOAD TEST MAY VARY DEPENDING YOUR REGION
VA TRINKA DAVIS
VETERAN VILLAGE
QC-11032301
03-NOV-2023
un001629 1/4" = 1'
10 / 19
600LB [272KG]
Rev1-un001629 07-NOV-2023
Rev2-un001629 10-NOV-2023
THIS LAYOUT HAS BEEN PREPARED WITH SUPPLIED DATA. NOTE: CUTTING OF RAILS ON SITE ONLY
B
G
A
TILE
A=108"
B=52"
F=16"
G=72"
H=6" ECS SYSTEM
EMBEDDED TRACKS
NOTE: ATTENTION INSTALLERS
*****Any deviation/changes from the Arjo specified installation details i.e. hardware, bracing, track layout
MUST be captured, marked on the drawings and returned to Arjo for an as built revision.*****
B
G
A
TILE
A=108"
B=52"
F=16"
G=72" ECS SYSTEM
EMBEDDED TRACKS
NOTE: ATTENTION INSTALLERS
*****XY PORETION OF SYSTEM
WILL BE EMBEDDED
137A
BEDROOM
6"
156"h90
156"h90 h
ServZone
ServZone h
79"h90 h
ECS-CSTAT
LISTING OF ROOM NUMBER(S):
- ALL HARDWARE INCLUDED.
(ACCORDING TO STRUCTURE)
QUANTITY OF ROOMS:
DRAWN BY :
REFERENCE # : PAGE :
SCALE :
DATE CREATED (DD-MMM-YYYY) :
SAFE WORKING LOAD BELOW LIFT:
WEIGHT FOR LOAD TEST MAY VARY DEPENDING YOUR REGION
VA TRINKA DAVIS
VETERAN VILLAGE
QC-11032301
03-NOV-2023
un001629 1/4" = 1'
11 / 19
600LB [272KG]
Rev1-un001629 07-NOV-2023
Rev2-un001629 10-NOV-2023
THIS LAYOUT HAS BEEN PREPARED WITH SUPPLIED DATA. NOTE: CUTTING OF RAILS ON SITE ONLY
B
G
A
TILE
A=108"
B=52"
F=16"
G=72"
H=6" ECS SYSTEM
EMBEDDED TRACKS
NOTE: ATTENTION INSTALLERS
*****Any deviation/changes from the Arjo specified installation details i.e. hardware, bracing, track layout
MUST be captured, marked on the drawings and returned to Arjo for an as built revision.*****
B
G
A
TILE
A=108"
B=52"
F=16"
G=72" ECS SYSTEM
EMBEDDED TRACKS
NOTE: ATTENTION INSTALLERS
*****XY PORETION OF SYSTEM
WILL BE EMBEDDED
BATH
138A
156"h90
156"h90 h
ServZone
ServZone h
79"h90 h
ECS-CSTAT
LISTING OF ROOM NUMBER(S):
- ALL HARDWARE INCLUDED.
(ACCORDING TO STRUCTURE)
QUANTITY OF ROOMS:
DRAWN BY :
REFERENCE # : PAGE :
SCALE :
DATE CREATED (DD-MMM-YYYY) :
SAFE WORKING LOAD BELOW LIFT:
WEIGHT FOR LOAD TEST MAY VARY DEPENDING YOUR REGION
VA TRINKA DAVIS
VETERAN VILLAGE
QC-11032301
03-NOV-2023
un001629 1/4" = 1'
12 / 19
600LB [272KG]
Rev1-un001629 07-NOV-2023
Rev2-un001629 10-NOV-2023
THIS LAYOUT HAS BEEN PREPARED WITH SUPPLIED DATA. NOTE: CUTTING OF RAILS ON SITE ONLY
B
G
A
TILE
A=108"
B=52"
F=16"
G=72"
H=6" ECS SYSTEM
EMBEDDED TRACKS
NOTE: ATTENTION INSTALLERS
*****Any deviation/changes from the Arjo specified installation details i.e. hardware, bracing, track layout
MUST be captured, marked on the drawings and returned to Arjo for an as built revision.*****
B
G
A
TILE
NOTE: ATTENTION INSTALLERS
*****XY PORETION OF SYSTEM
WILL BE EMBEDDED
BATH
139A
156"h90
156"h90 h
ServZone
ServZone h
79"h90 h
ECS-CSTAT
LISTING OF ROOM NUMBER(S):
- ALL HARDWARE INCLUDED.
(ACCORDING TO STRUCTURE)
QUANTITY OF ROOMS:
DRAWN BY :
REFERENCE # : PAGE :
SCALE :
DATE CREATED (DD-MMM-YYYY) :
SAFE WORKING LOAD BELOW LIFT:
WEIGHT FOR LOAD TEST MAY VARY DEPENDING YOUR REGION
VA TRINKA DAVIS
VETERAN VILLAGE
QC-11032301
03-NOV-2023
un001629 1/4" = 1'
13 / 19
600LB [272KG]
Rev1-un001629 07-NOV-2023
Rev2-un001629 10-NOV-2023
THIS LAYOUT HAS BEEN PREPARED WITH SUPPLIED DATA. NOTE: CUTTING OF RAILS ON SITE ONLY
B
G
A
TILE
A=108"
B=52"
F=16"
G=72"
H=6" ECS SYSTEM
EMBEDDED TRACKS
NOTE: ATTENTION INSTALLERS
*****Any deviation/changes from the Arjo specified installation details i.e. hardware, bracing, track layout
MUST be captured, marked on the drawings and returned to Arjo for an as built revision.*****
B
G
A
TILE
NOTE: ATTENTION INSTALLERS
*****XY PORETION OF SYSTEM
WILL BE EMBEDDED
STRUT BRIDGE (SLOT FACE DOWN)
FOR "G" UP TO
USE UNISTRUT
1'-8"
2'-0"
3'-3"
4'-0"
5'-4"
6'-4"
8'-6"
10'-4"
P1000T
P1000
P5500T
P5500
P1001
P5000
P5501
P5001
BRACE
"NOTE: ARJO GUARANTEES THE STRUCTURAL INTEGRITY OF THE TOTAL LIFT SYSTEM DESIGN, INCLUDING TRACK, BRACING, HANGERS, AND ALL CONNECTIONS TO THE BUILDING STRUCTURE. OUR DESIGN IS BASED ON THE REQUIREMENTS OF THE
CURRENT INTERNATIONAL BUILDING CODE (IBC) AND THE SESMIC LOADS OF THE REGION. THE FACILITY MUST VERIFY THE
ADEQUACY OF THE BUILDING STRUCTURE TO SUPPORT THE LOADS IMPOSED BY THE LIFT SYSTEM."
LIFT CAPACITY= 600 LBS
LIFT RAIL BY
ARJO
" MAX. DISTANCE
BETWEEN ANGLE
FITTING AND CEILING
1 6 8 10
BRACE
(X2) UPPER AND LOWER
CONNECTION FOR LATERAL
OWJ STRUCTURE BY OTHERS
***NOTE
EVERYTHING HIGHLIGHTED IN
BLUE IS PROVIDED BY ARJO AND
INSTALLED BY ARJO.****
FINISHED TILE CEILING
BY OTHERS
STANDARD TRACK INSTALLATION MS2
U
N
I
S
T
R
U
T
P
M
A
X
U
N
I
S
T
R
X
LINEAR PORTION
Item # Part # Description Qty
2 000.00394 THREADED ROD 3/8-16 X 10' ZINC 1
3 000.00402 LOCKNUT STOVER 3/8-16 ZINC 1
4 000.00405 NUT 3/8-16 ZINC 4
8 000.04430 FLAT WASHER M10 ZINC 6
200.11140 CEILING PLATE ø100MM 2
000.00375 BOLT 3/8" - 16 X 1 1/4" 3
700.11100 TRACK BRACKET KWIKTRAK 1
LUS-P27XX UNISTRUT BEAM CLAMP
LUS-P1068 UNISTRUT ANGLE 2
000.04875 FLAT WASHER M12 5
000.00425 LOCKWASHER 3/8" 5
(PENDING ON STRUT USAGE)
000.04435 TAB WASHER M10 1
5 000.00424 1
200.11170 BRACKET SHIM 12mm 1
200.11160
200.11150
BRACKET SHIM 3mm
BRACKET SHIM 1.5mm
16 000.00426
SADDLE NUT 3/8"-16
3CHANNEL NUT 3/8-16
- ALL HARDWARE INCLUDED.
(ACCORDING TO STRUCTURE)
QUANTITY OF ROOMS:
DRAWN BY :
REFERENCE # : PAGE :
SCALE :
DATE CREATED (DD-MMM-YYYY) :
SAFE WORKING LOAD BELOW LIFT:
WEIGHT FOR LOAD TEST MAY VARY DEPENDING YOUR REGION
VA TRINKA DAVIS
VETERAN VILLAGE
QC-11032301
03-NOV-2023
un001629 N/A
14 / 19
600LB [272KG]
750LB [340KG]
Rev1-un001629 07-NOV-2023
Rev2-un001629 10-NOV-2023
AutoCAD SHX Text
STRUT (SEE CHART)
STRUT BRIDGE (SLOT FACE DOWN)
FOR "G" UP TO
USE UNISTRUT
1'-8"
2'-0"
3'-3"
4'-0"
5'-4"
6'-4"
8'-6"
10'-4"
P1000T
P1000
P5500T
P5500
P1001
P5000
P5501
P5001
BRACE
"NOTE: ARJO GUARANTEES THE STRUCTURAL INTEGRITY OF THE TOTAL LIFT SYSTEM DESIGN, INCLUDING TRACK, BRACING, HANGERS, AND ALL CONNECTIONS TO THE BUILDING STRUCTURE. OUR DESIGN IS BASED ON THE REQUIREMENTS OF THE
CURRENT INTERNATIONAL BUILDING CODE (IBC) AND THE SESMIC LOADS OF THE REGION. THE FACILITY MUST VERIFY THE
ADEQUACY OF THE BUILDING STRUCTURE TO SUPPORT THE LOADS IMPOSED BY THE LIFT SYSTEM."
LIFT RAIL BY
ARJO EMBEDDED
" MAX. DISTANCE
BETWEEN ANGLE
FITTING AND TOP
OF ARJO LIFT RAIL
1 6 8 10
BRACE
(X2) UPPER AND LOWER
CONNECTION FOR LATERAL
***NOTE
EVERYTHING HIGHLIGHTED IN
BLUE IS PROVIDED BY ARJO AND
INSTALLED BY ARJO.****
FINISHED TILE CEILING
BY OTHERS
EMBEDDED TRACK INSTALLATION MS2
U
N
I
S
T
R
X
U
N
I
S
T
R
X
OWJ STRUCTURE BY OTHERS
LIFT CAPACITY= 600 LBS
XY PORTION
Item # Part # Description Qty
2 000.00394 THREADED ROD 3/8-16 X 10' ZINC 1
3 000.00402 LOCKNUT STOVER 3/8-16 ZINC 1
4 000.00405 NUT 3/8-16 ZINC 4
8 000.04430 FLAT WASHER M10 ZINC 6
200.11140 CEILING PLATE ø100MM 1
000.00375 BOLT 3/8" - 16 X 1 1/4" 3
700.11100 TRACK BRACKET KWIKTRAK 1
LUS-P27XX UNISTRUT BEAM CLAMP
LUS-P1068 UNISTRUT ANGLE 2
000.04875 FLAT WASHER M12 5
000.00425 LOCKWASHER 3/8" 5
(PENDING ON STRUT USAGE)
000.04435 TAB WASHER M10 1
5 000.00424 1
200.11170 BRACKET SHIM 12mm 1
200.11160
200.11150
BRACKET SHIM 3mm
BRACKET SHIM 1.5mm
16 000.00426
SADDLE NUT 3/8"-16
3CHANNEL NUT 3/8-16
- ALL HARDWARE INCLUDED.
(ACCORDING TO STRUCTURE)
QUANTITY OF ROOMS:
DRAWN BY :
REFERENCE # : PAGE :
SCALE :
DATE CREATED (DD-MMM-YYYY) :
SAFE WORKING LOAD BELOW LIFT:
WEIGHT FOR LOAD TEST MAY VARY DEPENDING YOUR REGION
VA TRINKA DAVIS
VETERAN VILLAGE
QC-11032301
03-NOV-2023
un001629 N/A
15 / 19
600LB [272KG]
750LB [340KG]
Rev1-un001629 07-NOV-2023
Rev2-un001629 10-NOV-2023
STRUT (SEE CHART)
- ALL HARDWARE INCLUDED.
(ACCORDING TO STRUCTURE)
QUANTITY OF ROOMS:
DRAWN BY :
REFERENCE # : PAGE :
SCALE :
DATE CREATED (DD-MMM-YYYY) :
SAFE WORKING LOAD BELOW LIFT:
WEIGHT FOR LOAD TEST MAY VARY DEPENDING YOUR REGION
VA TRINKA DAVIS
VETERAN VILLAGE
QC-11032301
03-NOV-2023
un001629 N/A
16 / 19
600LB [272KG]
750LB [340KG]
Rev1-un001629 07-NOV-2023
Rev2-un001629 10-NOV-2023
LATERAL BRACE REQUIREMENTS REV-3
LEGEND
LATERAL
BRACE
TRACK
BRACKET
TRACK
BRACKET JOINT
4 TRACKS SECTION
3 TRACK BRACKETS JOINT
9 LATERAL BRACES
1 TRACK SECTION
0 TRACK BRACKET JOINT
3 LATERAL BRACES
2 TRACKS SECTION
1 TRACK BRACKET JOINT
4 LATERAL BRACES
3 TRACKS SECTION
2 TRACK BRACKETS JOINT
6 LATERAL BRACES
- MINIMUM 3 LATERAL BRACES.
- NUMBER OF LATERAL BRACE = (NUMBER OF TRACK BRACKET JOINT X 2) + 2.
POSSIBLE ANCHOR LATERAL TO THE CEILING OR TO THE WALL
ACCEPTABLE ANGLE
LATERAL BRACE
LUS-P1000T
UNISTRUT
000.0XXXX
SADDLE NUT
000.00424
FLAT WASHER M10
000.04430
LOCK WASHER 3/8
000.00425
BOLT 3/8-16 X 1"
000.00357
STEEL
ACCEPTABLE ANGLE
EMBEDDED TRACK
BELOW CEILING TRACK
QUANTITY OF ROOMS:
DRAWN BY :
REFERENCE # : PAGE :
SCALE :
DATE CREATED (DD-MMM-YYYY) :
SAFE WORKING LOAD BELOW LIFT:
WEIGHT FOR LOAD TEST MAY VARY DEPENDING YOUR REGION
VA TRINKA DAVIS
VETERAN VILLAGE
QC-11032301
03-NOV-2023
un001629 N/A
17 / 19
600LB [272KG]
750LB [340KG]
Rev1-un001629 07-NOV-2023
Rev2-un001629 10-NOV-2023
MAX. STRUT BRIDGE "SPAN"
STRUT
LIFT CAPACITY
P1000T
P1000
P5500T
P5500
P5501
P5001
P1001
P5000
600#
1'-8"
2'-0"
3'-3"
4'-0"
5'-4"
6'-4"
8'-6"
10'-4"
STRUT BRIDGE PER TABLE
BELOW (SLOT- FACE DOWN)
"SPAN"
REF. TABLE BELOW
DUCT, PIPE
OR OTHER
OBSTRUCTION
AS OCCURS
STRUT TO BUILDING STRUCTURE
REF. PLANS AND DETAILS
B
R
A
C
E
O
S
R
U
C
T
U
R
E
R
E
F
L
A
N
S
N
D
D
E
T
A
I
L
S
BRIDGE DETAIL
Item # Part # Description Qty
000.00394 THREADED ROD 3/8-16 X 10' ZINC 21
000.00405 NUT 3/8-16 ZINC 6
TYP. ROD
HANGER PER
PLANS AND
DETAILS
SQUARE PLATE 3/8"
"NOTE: ARJO GUARANTEES THE STRUCTURAL INTEGRITY OF THE TOTAL LIFT SYSTEM DESIGN, INCLUDING TRACK, BRACING, HANGERS, AND ALL CONNECTIONS TO THE BUILDING STRUCTURE. OUR DESIGN IS BASED ON THE REQUIREMENTS OF THE
CURRENT INTERNATIONAL BUILDING CODE (IBC) AND THE SESMIC LOADS OF THE REGION. THE FACILITY MUST VERIFY THE
ADEQUACY OF THE BUILDING STRUCTURE TO SUPPORT THE LOADS IMPOSED BY THE LIFT SYSTEM."
000.00424 SADDLE NUT 3/8 23
VERIFY IN FIELD
LUS-P1063
QUANTITY OF ROOMS:
DRAWN BY :
REFERENCE # : PAGE :
SCALE :
DATE CREATED (DD-MMM-YYYY) :
SAFE WORKING LOAD BELOW LIFT:
WEIGHT FOR LOAD TEST MAY VARY DEPENDING YOUR REGION
VA TRINKA DAVIS
VETERAN VILLAGE
QC-11032301
03-NOV-2023
un001629 N/A
18 / 19
Z
600LB [272KG]
750LB [340KG]
Rev1-un001629 07-NOV-2023
Rev2-un001629 10-NOV-2023
X-Y GATE SYSTEM
AutoCAD SHX Text
SUPPORT
AutoCAD SHX Text
FIXED BOX
MOBILE BOX
QUANTITY OF ROOMS:
DRAWN BY :
REFERENCE # : PAGE :
SCALE :
DATE CREATED (DD-MMM-YYYY) :
SAFE WORKING LOAD BELOW LIFT:
WEIGHT FOR LOAD TEST MAY VARY DEPENDING YOUR REGION
VA TRINKA DAVIS
VETERAN VILLAGE
QC-11032301
03-NOV-2023
un001629 N/A
19 / 19
Z
600LB [272KG]
750LB [340KG]
Rev1-un001629 07-NOV-2023
Rev2-un001629 10-NOV-2023
ECS - CSTAT CHARGING
STANDARD X-Y CONFIG.
EMBEDDED X-Y CONFIG.
700-11227 - ECS to CSTAT wiring kit
CONTACT BOX (2X)
ECS ON FIXED RAIL
CSTAT ON MOVING RAIL
V5 Duo
MS600
MS2
MS440
V5 Duo
MS600 ecs
MS2 ecs
MS440
| Sheets and Views |
| QC-11032301 Va Trinka Davis Veteran Village -Rev 2-Title |
| QC-11032301 Va Trinka Davis Veteran Village -Rev 2-02 |
| QC-11032301 Va Trinka Davis Veteran Village -Rev 2-03 |
| QC-11032301 Va Trinka Davis Veteran Village -Rev 2-04 |
| QC-11032301 Va Trinka Davis Veteran Village -Rev 2-05 |
| QC-11032301 Va Trinka Davis Veteran Village -Rev 2-06 |
| QC-11032301 Va Trinka Davis Veteran Village -Rev 2-07 |
| QC-11032301 Va Trinka Davis Veteran Village -Rev 2-08 |
| QC-11032301 Va Trinka Davis Veteran Village -Rev 2-09 |
| QC-11032301 Va Trinka Davis Veteran Village -Rev 2-10 |
| QC-11032301 Va Trinka Davis Veteran Village -Rev 2-11 |
| QC-11032301 Va Trinka Davis Veteran Village -Rev 2-12 |
| QC-11032301 Va Trinka Davis Veteran Village -Rev 2-13 |
| QC-11032301 Va Trinka Davis Veteran Village -Rev 2-X-21210.01-S6 |
| QC-11032301 Va Trinka Davis Veteran Village -Rev 2-X-21210.01-S6 (2) |
| QC-11032301 Va Trinka Davis Veteran Village -Rev 2-X-21210.01-LateralUS |
| QC-11032301 Va Trinka Davis Veteran Village -Rev 2-X-21210.01-LateralUS (2) |
| QC-11032301 Va Trinka Davis Veteran Village -Rev 2-X-BB-GATE-01 |
| QC-11032301 Va Trinka Davis Veteran Village -Rev 2-X-BB-BD-ECS.CSTAT-X-ECS-CSTAT |