Attachment 5 - Drawings Volume IV.pdf

PDF 20 MB Posted

Attached to
Y1DA--637-22-700 | EHRM Infrastructure Upgrades | Asheville, NC |
Solicitation number
36C77626R0066
Issued by

About this file

These are the final bid documents for the EHRM (Electronic Health Records Management) Infrastructure Upgrades to Building 47 at the VA Medical Center in Asheville, North Carolina, consisting of mechanical, electrical, and plumbing design plans and specifications. The project is located at 1100 Tunnel Road, Asheville, NC 28805, with Project Number 637-22-700 and Building 47 designated as the subject facility.

The mechanical scope includes installation of ductless split-system HVAC units throughout multiple floors (basement through 5th floor and roof level), with detailed plans showing equipment locations, refrigerant line routing, and condensate management. The project specifies Vertiv WLM series mini-split indoor units and Vertiv CUD series outdoor condensing units for standard areas, plus Liebert CRAC (Computer Room Air Conditioning) units for the new data center, and specialized equipment for telecommunications spaces. Key mechanical components include multiple indoor/outdoor unit pairs (47-IDU and 47-ODU designations), four CRAC units (47-CRAC-1A/1B and 47-CRAC-2A/2B), condensing units (47-CU-1A/1B and 47-CU-2A/2B), and control systems with Vigilent monitoring integration for the data center. The electrical scope encompasses new and modified branch panels, busway systems rated 60-600 amperes distributed across floors, UPS systems (UPS-A and UPS-B), comprehensive building power distribution infrastructure, and emergency power provisions. The plans provide detailed panel schedules, one-line diagrams for critical and equipment branches, and equipment specifications with electrical ratings and circuit assignments throughout the building. Design documents include full-scale mechanical floor plans (basement through roof), enlarged demolition and new construction details, partition legends identifying fire barriers and smoke barriers, and comprehensive equipment and materials schedules prepared by Awen Solutions Group (Architecture/Engineer of Record) under VA Facilities Management Services for final bid distribution.

View the file

Other files

File Type Posted
Addendum 1 8-6-26.zip ZIP file
Amendment 0007.pdf PDF
RFI Responses.docx DOCX document
Attachment 9 - Key Subcontractor Information.docx DOCX document
Amendment 0006.pdf PDF
Amendment 0005.pdf PDF
Amendment 0004.pdf PDF
Amendment 0003.pdf PDF
Amendment 0002.pdf PDF
Amendment 0001 - Site Visit Sign In.pdf PDF
Amendment 0001.pdf PDF
Amendment 0001 - Site Visit Agenda.pdf PDF
Attachment 8 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 9 - Key Subcontractor Information.docx DOCX document
Attachment 6 - Drawings Volume V.pdf PDF
Attachment 4 - Drawings Volume III.pdf PDF
Attachment 3 - Drawings Volume II.pdf PDF
36C77626R0066.pdf PDF
Attachment 12 - Wage Determination.pdf PDF
Attachment 11 - Division Pricing Template.xlsx XLSX spreadsheet
Attachment 7 - Drawings Volume VI.pdf PDF
Attachment 13 - Site Visit Details.pdf PDF
Attachment 10 - Key Personnel.docx DOCX document
Attachment 2 - Drawings Volume I.pdf PDF
Attachment 1 - Specifications.pdf PDF
Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

47-MP400

47-MP400

47-MP400

47-MP401

47-MD401

47-MD400

47-MD400

47-MD400

PARTITION LEGEND

FIRE BARRIER, 2 HR

FIRE BARRIER, 1 HR

SMOKE BARRIER, 1/2 HR

SMOKE RESISTIVE HAZARDOUS

PATIENT SUIT/ NON SLEEPING

R

OBERT BEL L

SEAL

047145

N

O

RT

H CAROLIN

A

P R

FO

ESS ON

A L

I

N E

GINEER

PLAN

NORTH

N

FINAL BID DOCUMENTS

FOR OFFICIAL USE ONLY

www.coffman.com

701 Corporate Center Drive, Suite 475

Raleigh, NC 27607 ph 919.314.6686

20 20 40

1" = 20'-0"

FEETSCALE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL BID DOCUMENTS

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMP

321 4 5 6 7 8 9 10

SHEET NOTES:

SHEET OF

Facilities Management

Services

12/18/2025

A u to d e s k D o c s /A s h e v ill e E

H R

M

V

/6

-2

-7

.0

.M

.A S

H

E H

R M

.r v t

/1 /2

:3

:4

P M

47-MP100

MECHANICAL BASEMENT PLAN -

OVERALLAwen Solutions Group

215 N. Payne Street, Suite 122

Alexandria, VA 22314

12.19.2025

EHRM INFRASTRUCTURE

UPGRADES BLDG 47

1100 TUNNEL ROAD

ASHEVILLE, NC 28805

637-22-700

D

A B

C

G E

F

KEY PLAN

1" = 20'-0"

1 MECHANICAL BASEMENT PLAN - OVERALL

GENERAL NOTES:

Revisions: Date: SHEET 354 of 559

47-MP402

47-MP402

47-MP402

47-MP402

47-MP402

47-MD402

47-MD402

47-MD402

47-MD402

47-MD402

PARTITION LEGEND

FIRE BARRIER, 2 HR

FIRE BARRIER, 1 HR

SMOKE BARRIER, 1/2 HR

SMOKE RESISTIVE HAZARDOUS

PATIENT SUIT/ NON SLEEPING

R

OBERT BEL L

SEAL

047145

N

O

RT

H CAROLIN

A

P R

FO

ESS ON

A L

I

N E

GINEER

PLAN

NORTH

N

FINAL BID DOCUMENTS

FOR OFFICIAL USE ONLY

www.coffman.com

701 Corporate Center Drive, Suite 475

Raleigh, NC 27607 ph 919.314.6686

20 20 40

1" = 20'-0"

FEETSCALE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL BID DOCUMENTS

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMP

321 4 5 6 7 8 9 10

SHEET NOTES:

SHEET OF

Facilities Management

Services

12/18/2025

A u to d e s k D o c s /A s h e v ill e E

H R

M

V

/6

-2

-7

.0

.M

.A S

H

E H

R M

.r v t

/1 /2

:3

:4

P M

47-MP101

MECHANICAL 1ST FLOOR PLAN -

OVERALLAwen Solutions Group

215 N. Payne Street, Suite 122

Alexandria, VA 22314

12.19.2025

EHRM INFRASTRUCTURE

UPGRADES BLDG 47

1100 TUNNEL ROAD

ASHEVILLE, NC 28805

637-22-700

D

A B

C

G E

F

KEY PLAN

1" = 20'-0"

1 MECHANICAL 1ST FLOOR PLAN - OVERALL

Revisions: Date: SHEET 355 of 559

47-MP403

47-MP403

47-MP403

47-MD403

47-MD403

47-MD403

PARTITION LEGEND

FIRE BARRIER, 2 HR

FIRE BARRIER, 1 HR

SMOKE BARRIER, 1/2 HR

SMOKE RESISTIVE HAZARDOUS

PATIENT SUIT/ NON SLEEPING

R

OBERT BEL L

SEAL

047145

N

O

RT

H CAROLIN

A

P R

FO

ESS ON

A L

I

N E

GINEER

PLAN

NORTH

N

FINAL BID DOCUMENTS

FOR OFFICIAL USE ONLY

www.coffman.com

701 Corporate Center Drive, Suite 475

Raleigh, NC 27607 ph 919.314.6686

20 20 40

1" = 20'-0"

FEETSCALE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL BID DOCUMENTS

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMP

321 4 5 6 7 8 9 10

SHEET NOTES:

SHEET OF

Facilities Management

Services

12/18/2025

A u to d e s k D o c s /A s h e v ill e E

H R

M

V

/6

-2

-7

.0

.M

.A S

H

E H

R M

.r v t

/1 /2

:3

:4

P M

47-MP102

MECHANICAL 2ND FLOOR PLAN -

OVERALLAwen Solutions Group

215 N. Payne Street, Suite 122

Alexandria, VA 22314

12.19.2025

EHRM INFRASTRUCTURE

UPGRADES BLDG 47

1100 TUNNEL ROAD

ASHEVILLE, NC 28805

637-22-700

B

C

E

F

KEY PLAN

1" = 20'-0"

1 MECHANICAL 2ND FLOOR PLAN - OVERALL

Revisions: Date: SHEET 356 of 559

47-MD404

47-MP404

PARTITION LEGEND

FIRE BARRIER, 2 HR

FIRE BARRIER, 1 HR

SMOKE BARRIER, 1/2 HR

SMOKE RESISTIVE HAZARDOUS

PATIENT SUIT/ NON SLEEPING

R

OBERT BEL L

SEAL

047145

N

O

RT

H CAROLIN

A

P R

FO

ESS ON

A L

I

N E

GINEER

PLAN

NORTH

N

FINAL BID DOCUMENTS

FOR OFFICIAL USE ONLY

www.coffman.com

701 Corporate Center Drive, Suite 475

Raleigh, NC 27607 ph 919.314.6686

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL BID DOCUMENTS

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMP

321 4 5 6 7 8 9 10

SHEET NOTES:

SHEET OF

Facilities Management

Services

12/18/2025

A u to d e s k D o c s /A s h e v ill e E

H R

M

V

/6

-2

-7

.0

.M

.A S

H

E H

R M

.r v t

/1 /2

:3

:5

P M

47-MP103

MECHANICAL 3RD FLOOR PLAN -

OVERALLAwen Solutions Group

215 N. Payne Street, Suite 122

Alexandria, VA 22314

12.19.2025

EHRM INFRASTRUCTURE

UPGRADES BLDG 47

1100 TUNNEL ROAD

ASHEVILLE, NC 28805

637-22-700

B

C

KEY PLAN

GENERAL NOTES:

3/32" = 1'-0"

1 MECHANICAL 3RD FLOOR PLAN - OVERALL

Revisions: Date: SHEET 357 of 559

47-MP404

PARTITION LEGEND

FIRE BARRIER, 2 HR

FIRE BARRIER, 1 HR

SMOKE BARRIER, 1/2 HR

SMOKE RESISTIVE HAZARDOUS

PATIENT SUIT/ NON SLEEPING

R

OBERT BEL L

SEAL

047145

N

O

RT

H CAROLIN

A

P R

FO

ESS ON

A L

I

N E

GINEER

PLAN

NORTH

N

FINAL BID DOCUMENTS

FOR OFFICIAL USE ONLY

www.coffman.com

701 Corporate Center Drive, Suite 475

Raleigh, NC 27607 ph 919.314.6686

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL BID DOCUMENTS

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMP

321 4 5 6 7 8 9 10

SHEET NOTES:

SHEET OF

Facilities Management

Services

12/18/2025

A u to d e s k D o c s /A s h e v ill e E

H R

M

V

/6

-2

-7

.0

.M

.A S

H

E H

R M

.r v t

/1 /2

:3

:5

P M

47-MP104

MECHANICAL 4TH FLOOR PLAN -

OVERALLAwen Solutions Group

215 N. Payne Street, Suite 122

Alexandria, VA 22314

12.19.2025

EHRM INFRASTRUCTURE

UPGRADES BLDG 47

1100 TUNNEL ROAD

ASHEVILLE, NC 28805

637-22-700

B

C

KEY PLAN

GENERAL NOTES:

3/32" = 1'-0"

1 MECHANICAL 4TH FLOOR PLAN - OVERALL

Revisions: Date: SHEET 358 of 559

47-MP404

PARTITION LEGEND

FIRE BARRIER, 2 HR

FIRE BARRIER, 1 HR

SMOKE BARRIER, 1/2 HR

SMOKE RESISTIVE HAZARDOUS

PATIENT SUIT/ NON SLEEPING

R

OBERT BEL L

SEAL

047145

N

O

RT

H CAROLIN

A

P R

FO

ESS ON

A L

I

N E

GINEER

PLAN

NORTH

N

FINAL BID DOCUMENTS

FOR OFFICIAL USE ONLY

www.coffman.com

701 Corporate Center Drive, Suite 475

Raleigh, NC 27607 ph 919.314.6686

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL BID DOCUMENTS

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMP

321 4 5 6 7 8 9 10

SHEET NOTES:

SHEET OF

Facilities Management

Services

12/18/2025

A u to d e s k D o c s /A s h e v ill e E

H R

M

V

/6

-2

-7

.0

.M

.A S

H

E H

R M

.r v t

/1 /2

:3

:5

P M

47-MP105

MECHANICAL 5TH FLOOR PLAN -

OVERALLAwen Solutions Group

215 N. Payne Street, Suite 122

Alexandria, VA 22314

12.19.2025

EHRM INFRASTRUCTURE

UPGRADES BLDG 47

1100 TUNNEL ROAD

ASHEVILLE, NC 28805

637-22-700

B

C

KEY PLAN

GENERAL NOTES:

3/32" = 1'-0"

1 MECHANICAL 5TH FLOOR PLAN - OVERALL

Revisions: Date: SHEET 359 of 559

47-MP405

47-MP405

47-MP405

47-MP405

47-MP405

R

OBERT BEL L

SEAL

047145

N

O

RT

H CAROLIN

A

P R

FO

ESS ON

A L

I

N E

GINEER

PLAN

NORTH

N

FINAL BID DOCUMENTS

FOR OFFICIAL USE ONLY

www.coffman.com

701 Corporate Center Drive, Suite 475

Raleigh, NC 27607 ph 919.314.6686

20 20 40

1" = 20'-0"

FEETSCALE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL BID DOCUMENTS

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMP

321 4 5 6 7 8 9 10

SHEET NOTES:

SHEET OF

Facilities Management

Services

12/18/2025

A u to d e s k D o c s /A s h e v ill e E

H R

M

V

/6

-2

-7

.0

.M

.A S

H

E H

R M

.r v t

/1 /2

:3

:5

P M

47-MP106

MECHANICAL ROOF PLAN - OVERALL

Awen Solutions Group

215 N. Payne Street, Suite 122

Alexandria, VA 22314

12.19.2025

EHRM INFRASTRUCTURE

UPGRADES BLDG 47

1100 TUNNEL ROAD

ASHEVILLE, NC 28805

637-22-700

1" = 20'-0"

1 MECHANICAL ROOF PLAN - OVERALL

D

A B

C

G E

F

KEY PLAN

Revisions: Date: SHEET 360 of 559

TELECOM

BF107

EMS CHIEF

BF108

M-LOUNGE

BF109

SIGNAL FMS

BB018

STAIR

ELECTRICAL

FMS

BC118

R

OBERT BEL L

SEAL

047145

N

O

RT

H CAROLIN

A

P R

FO

ESS ON

A L

I

N E

GINEER

PLAN

NORTH

N

FINAL BID DOCUMENTS

FOR OFFICIAL USE ONLY

www.coffman.com

701 Corporate Center Drive, Suite 475

Raleigh, NC 27607 ph 919.314.6686

2 2 4 6 8 10

1/4" = 1'-0"

FEETSCALE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL BID DOCUMENTS

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMP

321 4 5 6 7 8 9 10

SHEET NOTES:

SHEET OF

Facilities Management

Services

12/18/2025

A u to d e s k D o c s /A s h e v ill e E

H R

M

V

/6

-2

-7

.0

.M

.A S

H

E H

R M

.r v t

/1 /2

:3

:5

P M

47-MD400

ENLARGED MECHANICAL BASEMENT

DEMOLITIONAwen Solutions Group

215 N. Payne Street, Suite 122

Alexandria, VA 22314

12.19.2025

EHRM INFRASTRUCTURE

UPGRADES BLDG 47

1100 TUNNEL ROAD

ASHEVILLE, NC 28805

637-22-700

GENERAL NOTES:

REMOVE ANY EXISTING SUPPLY AND RETURN DUCTWORK BACK TO MAIN IN ADJOINING CORRIDOR. CAP AND SEAL PER SMACNA STANDARDS. REMOVE EXISTING DIFFUSERS AND GRILLES. REMOVE ANY EXISTING TRANSFER DUCTWORK. PATCH ALL OPENINGS LEFT IN WALL FROM DUCT REMOVAL. COORDINATE WITH ARCHITECTURAL DRAWINGS FOR WALL RATINGS. MAINTAIN WALL RATING

IF RATED.

1/4" = 1'-0"

1 BF107 - MECHANICAL DEMOLITION PLAN

1/4" = 1'-0"

3 BB018 - MECHANICAL DEMOLITION PLAN

1/4" = 1'-0"

2 BC118 - MECHANICAL DEMOLITION PLAN

Revisions: Date: SHEET 361 of 559

47-CRAC-3-EX

47-CRAC-4-EX

47-CRAC-2-EX 47-CRAC-1-EX

47-CU-1-EX 47-CU-2-EX 47-CU-3-EX 47-CU-4-EX

1 1

5 6

1 1 4

AREA OF DEMOLITION

TELEHEALTH

BC131

COMPUTER ROOM

BC144

PIPE BASEMENT

2B239

R

OBERT BEL L

SEAL

047145

N

O

RT

H CAROLIN

A

P R

FO

ESS ON

A L

I

N E

GINEER

PLAN

NORTH

N

FINAL BID DOCUMENTS

FOR OFFICIAL USE ONLY

www.coffman.com

701 Corporate Center Drive, Suite 475

Raleigh, NC 27607 ph 919.314.6686

5 5 10 15 20

1/8" = 1'-0"

FEETSCALE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL BID DOCUMENTS

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMP

321 4 5 6 7 8 9 10

SHEET NOTES:

SHEET OF

Facilities Management

Services

12/18/2025

A u to d e s k D o c s /A s h e v ill e E

H R

M

V

/6

-2

-7

.0

.M

.A S

H

E H

R M

.r v t

/1 /2

:3

:5

P M

47-MD401

ENLARGED MECHANICAL DATA

CENTER DEMOLITIONAwen Solutions Group

215 N. Payne Street, Suite 122

Alexandria, VA 22314

12.19.2025

EHRM INFRASTRUCTURE

UPGRADES BLDG 47

1100 TUNNEL ROAD

ASHEVILLE, NC 28805

637-22-700

G

KEY PLAN

GENERAL NOTES:

1/8" = 1'-0"

1 DATA CENTER - MECHANICAL DEMOLITION PLAN

EXISTING EQUIPMENT, CONNECTED PIPING, AND DUCTWORK TO BE REMOVED AFTER NEW EQUIPMENT AND ASSOCIATED PIPING

AND DUCTWORK HAS BEEN INSTALLED AND IN OPERATION. SEE 1/47-MP401.

EXISTING EQUIPMENT, CONNECTED PIPING, AND DUCTWORK TO BE REMOVED.

REMOVE EXISTING SUPPLY DUCTWORK BACK TO CORRESPONDING CRAC UNIT. CAP AND SEAL PER SMACNA STANDARDS. REMOVE EXISTING DIFFUSERS AND GRILLES. REMOVE ANY EXISTING TRANSFER DUCTWORK. PATCH ALL OPENINGS LEFT IN WALL FROM DUCT REMOVAL. COORDINATE WITH ARCHITECTURAL DRAWINGS FOR WALL RATINGS. MAINTAIN WALL RATING IF RATED.

RETAIN AND REUSE EXISTING MOUNTING PADS IF IN GOOD CONDITION.

REMOVE EXISTING SUPPLY AND RETURN DUCTWORK BACK TO MAIN. CAP AND SEAL PER SMACNA STANDARDS. REMOVE EXISTING DIFFUSERS AND GRILLES. REMOVE ANY EXISTING TRANSFER DUCTWORK. PATCH ALL OPENINGS LEFT IN WALL FROM DUCT REMOVAL. COORDINATE WITH ARCHITECTURAL DRAWINGS FOR WALL RATINGS. MAINTAIN WALL RATING IF RATED.

NOTE ANY EXISTING MECHANICAL PIPING RUNNING DIRECTLY OVER THE LOCATION OF THE NEW SERVER RACKS, UPS'S, AND OTHER

ELECTRICAL EQUIPMENT AND INFORM THE EOR OF ANY OCCURANCE. SEE 1/47-MP401.

Revisions: Date: SHEET 362 of 559

SIGNAL

1B134

STAIR

FIRE EQUIP

N/A

OFFICE

1D146

RADIOLOGIST

1D145

COMP ROOM

1D144

EDUC

1W133

OFFICE

1H113

SIGNAL

1A137

R

OBERT BEL L

SEAL

047145

N

O

RT

H CAROLIN

A

P R

FO

ESS ON

A L

I

N E

GINEER

PLAN

NORTH

N

FINAL BID DOCUMENTS

FOR OFFICIAL USE ONLY

www.coffman.com

701 Corporate Center Drive, Suite 475

Raleigh, NC 27607 ph 919.314.6686

2 2 4 6 8 10

1/4" = 1'-0"

FEETSCALE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL BID DOCUMENTS

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMP

321 4 5 6 7 8 9 10

SHEET NOTES:

SHEET OF

Facilities Management

Services

12/18/2025

A u to d e s k D o c s /A s h e v ill e E

H R

M

V

/6

-2

-7

.0

.M

.A S

H

E H

R M

.r v t

/1 /2

:3

:0

P M

47-MD402

ENLARGED MECHANICAL 1ST FLOOR

DEMOLITIONAwen Solutions Group

215 N. Payne Street, Suite 122

Alexandria, VA 22314

12.19.2025

EHRM INFRASTRUCTURE

UPGRADES BLDG 47

1100 TUNNEL ROAD

ASHEVILLE, NC 28805

637-22-700

1/4" = 1'-0"

1 1B134 - MECHANICAL DEMOLITION PLAN

GENERAL NOTES:

1/4" = 1'-0"

4 1A137 - MECHANICAL DEMOLITION PLAN

1/4" = 1'-0"

2 1D144 - MECHANICAL DEMOLITION PLAN

1/4" = 1'-0"

5 1H113 - MECHANICAL DEMOLITION PLAN

REMOVE ANY EXISTING SUPPLY AND RETURN DUCTWORK BACK TO MAIN IN ADJOINING CORRIDOR. CAP AND SEAL PER SMACNA STANDARDS. REMOVE EXISTING DIFFUSERS AND GRILLES. REMOVE ANY EXISTING TRANSFER DUCTWORK. PATCH ALL OPENINGS LEFT IN WALL FROM DUCT REMOVAL. COORDINATE WITH ARCHITECTURAL DRAWINGS FOR WALL RATINGS. MAINTAIN WALL RATING IF

RATED.

DEMO EXISTING IDU AND CORRESPONDING ODU. ALL EXISTING REFRIGERANT PIPING TO BE REMOVED AND DISPOSED.

REMOVE EXISTING THERMOSTATS.

1/4" = 1'-0"

3 1W133 - MECHANICAL FIRST FLOOR DEMOLITION PLAN

Revisions: Date: SHEET 363 of 559

STAIR

2B251

SIGNAL

2B212

SIGNAL

2A246

STAIR #1

2A240

HSKG

2E204

EQUIP'T STORAGE

2E206

STAFF CONF

ROOM

2E205

R

OBERT BEL L

SEAL

047145

N

O

RT

H CAROLIN

A

P R

FO

ESS ON

A L

I

N E

GINEER

PLAN

NORTH

N

FINAL BID DOCUMENTS

FOR OFFICIAL USE ONLY

www.coffman.com

701 Corporate Center Drive, Suite 475

Raleigh, NC 27607 ph 919.314.6686

2 2 4 6 8 10

1/4" = 1'-0"

FEETSCALE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL BID DOCUMENTS

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMP

321 4 5 6 7 8 9 10

SHEET NOTES:

SHEET OF

Facilities Management

Services

12/18/2025

A u to d e s k D o c s /A s h e v ill e E

H R

M

V

/6

-2

-7

.0

.M

.A S

H

E H

R M

.r v t

/1 /2

:3

:0

P M

47-MD403

ENLARGED MECHANICAL 2ND FLOOR

DEMOLITIONAwen Solutions Group

215 N. Payne Street, Suite 122

Alexandria, VA 22314

12.19.2025

EHRM INFRASTRUCTURE

UPGRADES BLDG 47

1100 TUNNEL ROAD

ASHEVILLE, NC 28805

637-22-700

GENERAL NOTES:

REMOVE ANY EXISTING SUPPLY AND RETURN DUCTWORK BACK TO MAIN IN ADJOINING CORRIDOR. CAP AND SEAL PER SMACNA STANDARDS. REMOVE EXISTING DIFFUSERS AND GRILLES. REMOVE ANY EXISTING TRANSFER DUCTWORK. PATCH ALL OPENINGS LEFT IN WALL FROM DUCT REMOVAL. COORDINATE WITH ARCHITECTURAL DRAWINGS FOR WALL RATINGS. MAINTAIN WALL RATING

IF RATED.

1/4" = 1'-0"

2 2A246 - MECHANICAL DEMOLITION PLAN

1/4" = 1'-0"

3 2E205 - MECHANICAL DEMOLITION PLAN

1/4" = 1'-0"

1 2B212 - MECHANICAL DEMOLITION PLAN

Revisions: Date: SHEET 364 of 559

EXAM

A302

FC&NC

A301A

DATA IRM

A301

PHONE FMS

TA300B

47-FCU-A301B-EX

47-FCU-A301A-EX

47-FCU-A401B-EX

47-FCU-A401A-EX

EC FMS

TA401D

FC FMS

TA401C

STORAGE FMS

A401A

BEDROOM #1

NURSING

4W401

PHONE IRM

A401

47-FCU-A501B-EX

47-FCU-A501A-EX

EC FMS

TA501A

FA FMS

A501A

FA

TA501B

PHONE IRM

A501 BEDROOM #1

5W501

R

OBERT BEL L

SEAL

047145

N

O

RT

H CAROLIN

A

P R

FO

ESS ON

A L

I

N E

GINEER

PLAN

NORTH

N

FINAL BID DOCUMENTS

FOR OFFICIAL USE ONLY

www.coffman.com

701 Corporate Center Drive, Suite 475

Raleigh, NC 27607 ph 919.314.6686

2 2 4 6 8 10

1/4" = 1'-0"

FEETSCALE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL BID DOCUMENTS

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMP

321 4 5 6 7 8 9 10

SHEET NOTES:

SHEET OF

Facilities Management

Services

12/18/2025

A u to d e s k D o c s /A s h e v ill e E

H R

M

V

/6

-2

-7

.0

.M

.A S

H

E H

R M

.r v t

/1 /2

:3

:1

P M

47-MD404

ENLARGED MECHANICAL 3RD, 4TH,

AND 5TH FLOOR DEMOLITIONAwen Solutions Group

215 N. Payne Street, Suite 122

Alexandria, VA 22314

12.19.2025

EHRM INFRASTRUCTURE

UPGRADES BLDG 47

1100 TUNNEL ROAD

ASHEVILLE, NC 28805

637-22-700

GENERAL NOTES:

1/4" = 1'-0"

1 A301 - MECHANICAL DEMOLITION PLAN

1/4" = 1'-0"

2 A401 - MECHANICAL DEMOLITION PLAN

1/4" = 1'-0"

3 A501 - MECHANICAL DEMOLITION PLAN

REMOVE ANY EXISTING SUPPLY AND RETURN DUCTWORK BACK TO MAIN IN ADJOINING CORRIDOR. CAP AND SEAL PER SMACNA STANDARDS. REMOVE EXISTING DIFFUSERS AND GRILLES. REMOVE ANY EXISTING TRANSFER DUCTWORK. PATCH ALL OPENINGS LEFT IN WALL FROM DUCT REMOVAL. COORDINATE WITH ARCHITECTURAL DRAWINGS FOR WALL RATINGS. MAINTAIN WALL RATING

IF RATED.

REMOVE EXISTING WALL-MOUNTED AND SUSPENDED FAN COIL UNITS. REMOVE CONNECTED WATER PIPING BACK TO MAINS IN

ADJACENT CORRIDOR. CAP AND SEAL.

Revisions: Date: SHEET 365 of 559

TR (EXPANDED)

BF107

OFFICE

BF108

LOUNGE

BF109

T

S

47-IDU-BF107

TR (EXISTING)

BB018ELEC.

BB019

STAIR #2

T

S

47-IDU-BB018

TR (EXPANDED)

BC118

247-IDU-BC118A

47-IDU-BC118B

S

T

PARTITION LEGEND

FIRE BARRIER, 2 HR

FIRE BARRIER, 1 HR

SMOKE BARRIER, 1/2 HR

SMOKE RESISTIVE HAZARDOUS

PATIENT SUIT/ NON SLEEPING

R

OBERT BEL L

SEAL

047145

N

O

RT

H CAROLIN

A

P R

FO

ESS ON

A L

I

N E

GINEER

PLAN

NORTH

N

FINAL BID DOCUMENTS

FOR OFFICIAL USE ONLY

www.coffman.com

701 Corporate Center Drive, Suite 475

Raleigh, NC 27607 ph 919.314.6686

2 2 4 6 8 10

1/4" = 1'-0"

FEETSCALE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL BID DOCUMENTS

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMP

321 4 5 6 7 8 9 10

SHEET NOTES:

SHEET OF

Facilities Management

Services

12/18/2025

A u to d e s k D o c s /A s h e v ill e E

H R

M

V

/6

-2

-7

.0

.M

.A S

H

E H

R M

.r v t

/1 /2

:3

:1

P M

47-MP400

ENLARGED MECHANICAL BASEMENT

PLANSAwen Solutions Group

215 N. Payne Street, Suite 122

Alexandria, VA 22314

12.19.2025

EHRM INFRASTRUCTURE

UPGRADES BLDG 47

1100 TUNNEL ROAD

ASHEVILLE, NC 28805

637-22-700

1/4" = 1'-0"

1 BF107 - MECHANICAL PLAN

GENERAL NOTES:

1. ROUTE REFRIGERANT LINES TIGHT TO UNDERSIDE OF FLOOR ABOVE.

2. SIZE REFRIGERANT LINES PER MANUFACTURER'S RECOMMENDATIONS.

3. PROVIDE FIRE-STOPPING WHERE PIPING PENETRATES FIRE-RATED WALLS. RATED WALLS ARE INDICATED ON

PLANS.

4. IT RACKS SHOWN FOR REFERENCE ONLY. DASHED LINES INDICATE PLACEHOLDER FOR FUTURE RACK, NOT IN

CONTRACT. SEE TELECOM DRAWINGS FOR MORE INFORMATION.

1/4" = 1'-0"

3 BB018 - MECHANICAL PLAN

1/4" = 1'-0"

2 BC118 - MECHANICAL PLAN

MOUNT UNIT ON WALL ABOVE DOOR. SEE DETAIL 7/00-M501. MAINTAIN MANUFACTURER'S MINIMUM CLEARANCES.

RS/RL UP TO CORRESPONDING ODU ON ROOF.

LOCATE TEMPTRAK TEMPERATURE/HUMIDITY SENSOR ON WALL WITHIN 6 FT OF TELECOM RACK. TEMPTRAK SENSOR SHALL INTEGRATE WITH VA'S CENTRAL MONITORING SYSTEM TO ALERT WHEN ENVIRONMENTAL CONDITION REQUIREMENTS ARE NOT MET.

SEE DESIGN CONDITIONS TABLE ON SHEET 00-M0

MOUNT UNIT ON WALL 10'-0" AFF IN LOCATION SHOWN. SEE DETAIL 7/00-M501.

TWO (2) INDOOR UNITS ARE PROVIDED DUE TO REFRIGERANT CHARGE LIMITATIONS PER ASHRAE STANDARD 15. PROVIDE ONE (1) CONTROLLER TO CONTROL BOTH INDOOR UNITS SERVING THE TELECOM ROOM. CONTROLLER SHALL BE PROGRAMMED FOR LEAD/LAG OPERATION. THE LEAD UNIT SHALL OPERATE TO MAINTAIN THE ROOM TEMPERATURE SETPOINT. THE LAG UNIT SHALL START AUTOMATICALLY ON THE ROOM TEMPERATURE EXCEEDING THE SETPOINT BY 2°F (ADJ). THE UNITS SHALL SWAP LEAD AND LAG ROLES

ON A WEEKLY BASIS TO ENSURE EQUAL AVAILABLE OPERATION TIME.

Revisions: Date: SHEET 366 of 559

STAIR

CORRIDOR

DATA CENTER

(NEW)

BC131B

24"x14" RA

50"x28" RA

50"x28" RA

47-CU-2A

47-CU-1A47-CU-1B

47-CU-2B

47-CRAC-1A

47-CRAC-2A

47-CRAC-2B

47-CRAC-1B

PIPE BASEMENT

ENTRANCE ROOM

01 (NEW)

BC131A

ENTRANCE ROOM

02 (NEW)

BC143A

TR

(DECOMMISSIONED)

BC143

OFFICE

BC141

OFFICE

BC142

CORRIDOR

ELEC

BC140

STOR.

BC139

Room

2B272

6"ø OA

47-IDU-BC143C

6"ø OA

36"x14" RA

36"x14" RA

T

T

H14x14

H14x14

H14x14

H14x14

R S

/R L

R S

/R L

R S

/R L

R S

/R L

S

S

S

R S

/R L

"ø

O A

H18x12

TRANSFORMER

R S

/R L

R S

/R L

47-ODU-BC143A

47-ODU-BC143B

T 6

47-IDU-BC143A

47-ODU-BC131A

47-IDU-BC131A

47-IDU-BC131B

47-IDU-BC143B

47-ODU-BC131B

/4

R

S /R

L

47-ODU-BC143C

13IF-1

1415EMERGENCY SHUTOFF FOR

CRAC UNITS

S

30"x28" RA

30"x28" RA

275 CFM

275 CFM

700 CFM

275 CFM

700 CFM

700 CFM

275 CFM

700 CFM

700 CFM

700 CFM

700 CFM

700 CFM

700 CFM

700 CFM

700 CFM

700 CFM

700 CFM

700 CFM

700 CFM

700 CFM

700 CFM

700 CFM

0 CFM

300 CFM

300 CFM

0 CFM

300 CFM

300 CFM

PARTITION LEGEND

FIRE BARRIER, 2 HR

FIRE BARRIER, 1 HR

SMOKE BARRIER, 1/2 HR

SMOKE RESISTIVE HAZARDOUS

PATIENT SUIT/ NON SLEEPING

R

OBERT BEL L

SEAL

047145

N

O

RT

H CAROLIN

A

P R

FO

ESS ON

A L

I

N E

GINEER

PLAN

NORTH

N

FINAL BID DOCUMENTS

FOR OFFICIAL USE ONLY

www.coffman.com

701 Corporate Center Drive, Suite 475

Raleigh, NC 27607 ph 919.314.6686

5 5 10 15 20

1/8" = 1'-0"

FEETSCALE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL BID DOCUMENTS

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMP

321 4 5 6 7 8 9 10

SHEET NOTES:

SHEET OF

Facilities Management

Services

12/18/2025

A u to d e s k D o c s /A s h e v ill e E

H R

M

V

/6

-2

-7

.0

.M

.A S

H

E H

R M

.r v t

/1 /2

:3

:1

P M

47-MP401

ENLARGED MECHANICAL DATA

CENTER PLANAwen Solutions Group

215 N. Payne Street, Suite 122

Alexandria, VA 22314

12.19.2025

EHRM INFRASTRUCTURE

UPGRADES BLDG 47

1100 TUNNEL ROAD

ASHEVILLE, NC 28805

637-22-700

G

KEY PLAN

GENERAL NOTES:

1. CRAC UNITS TO BE DOWNFLOW UNITS. SUPPLY AIR FROM CRAC UNITS TO BLOW FROM BOTTOM OF UNIT, ACROSS THE FLOOR, AND

TO THE FRONT SIDE OF CABINETS. DATA, NETWORK, AND POWER CABINETS TO HAVE CHIMNEY STACKS ON TOP OF CABINETS.

CHIMNEY STACKS TO CONNECT DIRECTLY TO UNDERSIDE OF RETURN AIR DUCTWORK. RETURN DUCTWORK TO ROUTE DIRECTLY BACK TO TOP SIDE OF CRAC UNITS. HOT AIR FROM CABINETS TO FLOW THROUGH DUCTWORK AND TO TOP SIDE OF CRAC UNITS.

2. ROUTE REFRIGERANT LINES AND DUCTWORK TIGHT TO UNDERSIDE OF FLOOR ABOVE.

3. EMERGENCY SHUT OFF SWITCHES FOR CRAC UNITS LOCATED AT NEW DATA CENTER EXITS, PER LIFE SAFETY COMMENTS.

4. DATA CENTER CRAC UNITS AND CONDITIONS TO BE CONTROLLED AND MONITORED BY THE VIGILENT CONTROL SYSTEM AS PER VA

RECOMMENDATIONS.

5. SIZE REFRIGERANT LINES PER MANUFACTURER'S RECOMMENDATIONS.

6. PROVIDE FIRE-STOPPING WHERE PIPING PENETRATES FIRE-RATED WALLS. RATED WALLS ARE INDICATED ON PLANS.

1/8" = 1'-0"

1 DATA CENTER - MECHANICAL PLAN

MOUNT CRAC UNIT DIRECTLY ON 4" CONCRETE EQUIPMENT PAD. SEE DETAIL 1/00-M501. ROUTE REFRIGERANT PIPING TO OUTDOOR UNIT. COORDINATE WITH PLUMBING CONTRACTOR FOR DOMESTIC COLD WATER PIPING TO HUMIDIFIER. (SEE 1/47-PP401). CONNECT CRAC UNIT TO WIRELESS VIGILENT CONTROL MODULE TO BE CONTROLLED BY VIGILENT SYSTEM.

LOCATE CONDENSING UNIT WHERE EXISTING UNIT WAS LOCATED. MOUNT ON CONCRETE PAD. SEE DETAIL 7/00-M501. REUSE

EXISTING PAD WHERE POSSIBLE.

TEMPERATURE AND HUMIDITY ENTERING AND LEAVING SERVER CABINETS MONITORED BY VIGILENT WIRELESS SENSOR MODULES LOCATED AS NOTED ON THE DRAWINGS AND BY THE FOLLOWING CRITERIA FROM THE ISTS STANDARDS: ONE TEMPERATURE SENSOR AND ONE HUMIDITY SENSOR CENTERED HORIZONTALLY, INSIDE THE FRONT DOOR, 4-FT +/-6IN. FROM THE FINISHED FLOOR SURFACE;

ONE TEMPERATURE SENSOR CENTER HORIZONTALLY, INSIDE THE REAR DOOR, NO MORE THAN 1-FT FROM THE TOP OF THE CABINET.

THIS CONFIGURATION OF SENSORS LOCATED IN CABINETS AT THE ENDS OF EACH CONTIGUOUS ROW AND IN EVERY THIRD CABINET

IN THE MIDDLE OF EACH CONTIGUOUS ROW.

MOUNT CONDENSING UNIT ON NEW MOUNTING PAD IN MECHANICAL YARD. SEE DETAIL 5/00-M501. EXTEND MOUNTING PAD MINIMUM 6" FROM EACH FACE OF EQUIPMENT. PROVIDE MINIMUM 6" CLEARANCE BETWEEN WALL AND EQUIPMENT PAD.

LOCAL ECC TO SERVE DATA CENTER ONLY. SET UP ECC TO SUPPORT SYSTEM CONSOLE AND WIRLESS NETWORK MANAGER FOR THE VIGILENT SYSTEM. VA PREFERS VIGILENT MONITORING SYSTEM AS BASIS OF DESIGN. COORDINATE WITH COR AND OIT FOR EXACT LOCATION OF SYSTEM CONSOLE, WIRELESS NETWORK MANAGER FOR SENSOR MODULES, ARTIFICIAL INTELLIGENCE ENGINE, AND OTHER CONTROL EQUIPMENT. CONTROL SYSTEM TO BE MONITORED BUT NOT CONTROLLED BY THE BUILDING BMS.

PROVIDE ONE (1) CONTROLLER TO CONTROL BOTH INDOOR UNITS SERVING ENTRANCE ROOM. CONTROLLER SHALL BE PROGRAMMED FOR PRIMARY/BACKUP OPERATION. THE PRIMARY UNIT SHALL OPERATE TO MAINTAIN THE ROOM TEMPERATURE SETPOINT. THE BACKUP UNIT SHALL START AUTOMATICALLY ON A FAILURE IN THE PRIMARY UNIT. THE UNITS SHALL SWAP PRIMARY AND BACKUP

ROLES ON A WEEKLY BASIS TO ENSURE EQUAL AVAILABLE OPERATION TIME.

LOCATE TEMPTRAK TEMPERATURE/HUMIDITY SENSOR ON WALL WITHIN 6 FT OF TELECOM EQUIPMENT. TEMPTRAK SENSOR SHALL INTEGRATE WITH VA'S CENTRAL MONITORING SYSTEM TO ALERT WHEN ENVIRONMENTAL CONDITION REQUIREMENTS ARE NOT MET.

SEE DESIGN CONDITIONS TABLE ON SHEET 00-M001.

MOUNT CONDENSING UNIT ON NEW MOUNTING PAD IN MECHANICAL YARD. SEE DETAIL 5/00-M501. EXTEND MOUNTING PAD MINIMUM 6" FROM FACE OF EQUIPMENT. PROVIDE MINIMUM 36" CLEARANCE BETWEEN WALL AND EQUIPMENT PAD.

ROUTE OUTSIDE AIR DUCT UP TO EXISTING LOUVER. PROVIDE BACKDRAFT DAMPER AND BIRD/INSECT SCREEN.

INSTALL ZETAFRAME VERTICAL EXHAUST DUCT AND ATTACH TO UNDERSIDE OF OVERHEAD RETURN DUCT. INSTALL GREENHECK MBD-15 BALANCING DAMPER FOR EACH VERTICAL EXAUST DUCT. BALANCE TO TO THE CFMS SHOWN ON THE PLANS. TYPICAL ALL IT

CABINETS IN THE SAME ROW. SEE DETAIL 9/00-M-501.

RETURN AIR GRILLE TO PULL HEAT FROM TRANSFORMER NEXT TO CRAC UNIT. ANGLE BLADES TOWARD TRANSFORMER.

PROVIDE GREENHECK GM-30 BACKDRAFT DAMPER TO PREVENT AIRFLOW THROUGH UNIT WHEN OFFLINE. ORIENT DAMPER IN

DIRECTION OF AIRFLOW.

IN-LINE FAN TO PULL OUTSIDE AIR TO CEILING CASSETTE. INTERLOCK FAN WITH CEILING CASSETTE TO RUN WHEN CEILING CASSETTE

FAN RUNS AND TO SHUT OFF WHEN CEILING CASSETTE FANS SHUTS OFF.

MOUNT UNIT ON WALL ABOVE DOOR. SEE DETAIL 7/00-M501. MAINTAIN MANUFACTURER'S MINIMUM CLEARANCES.

MOUNT UNIT ON WALL 9'-6" AFF IN LOCATION SHOWN. SEE DETAIL 7/00-M501.

PASSIVE MDA CABINET.

Revisions: Date: SHEET 367 of 559

ELEC

1B135

TR (EXISTING)

1B134

STAIR

T

S47-IDU-1B134

ELEC

1A136

TR (EXISTING)

1A137

STAIR

T

S

47-IDU-1A137

TR (NEW)

1H113

T

S

47-IDU-1H113

TR (NEW)

1W133

T

S

47-IDU-1W133

TR (NEW)

1D144

T

S7

47-IDU-1D144A

47-ODU-1D144

PARTITION LEGEND

FIRE BARRIER, 2 HR

FIRE BARRIER, 1 HR

SMOKE BARRIER, 1/2 HR

SMOKE RESISTIVE HAZARDOUS

PATIENT SUIT/ NON SLEEPING

R

OBERT BEL L

SEAL

047145

N

O

RT

H CAROLIN

A

P R

FO

ESS ON

A L

I

N E

GINEER

PLAN

NORTH

N

FINAL BID DOCUMENTS

FOR OFFICIAL USE ONLY

www.coffman.com

701 Corporate Center Drive, Suite 475

Raleigh, NC 27607 ph 919.314.6686

2 2 4 6 8 10

1/4" = 1'-0"

FEETSCALE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL BID DOCUMENTS

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMP

321 4 5 6 7 8 9 10

SHEET NOTES:

SHEET OF

Facilities Management

Services

12/18/2025

A u to d e s k D o c s /A s h e v ill e E

H R

M

V

/6

-2

-7

.0

.M

.A S

H

E H

R M

.r v t

/1 /2

:3

:2

P M

47-MP402

ENLARGED MECHANICAL 1ST FLOOR

PLANSAwen Solutions Group

215 N. Payne Street, Suite 122

Alexandria, VA 22314

12.19.2025

EHRM INFRASTRUCTURE

UPGRADES BLDG 47

1100 TUNNEL ROAD

ASHEVILLE, NC 28805

637-22-700

1/4" = 1'-0"

1 1B134 - MECHANICAL PLAN

GENERAL NOTES:

1. ROUTE REFRIGERANT LINES TIGHT TO UNDERSIDE OF FLOOR ABOVE.

2. SIZE REFRIGERANT LINES PER MANUFACTURER'S RECOMMENDATIONS.

3. PROVIDE FIRE-STOPPING WHERE PIPING PENETRATES FIRE-RATED RATES. RATED WALLS ARE INDICATED ON

PLANS.

4. IT RACKS SHOWN FOR REFERENCE ONLY. DASHED LINES INDICATE PLACEHOLDER FOR FUTURE RACK, NOT IN

CONTRACT. SEE TELECOM DRAWINGS FOR MORE INFORMATION.

1/4" = 1'-0"

4 1A137 - MECHANICAL PLAN

1/4" = 1'-0"

5 1H113 - MECHANICAL PLAN

1/4" = 1'-0"

3 1W133 - MECHANICAL PLAN

1/4" = 1'-0"

2 1D144 - MECHANICAL PLAN

MOUNT UNIT ON WALL ABOVE DOOR. SEE DETAIL 7/00-M501. MAINTAIN MANUFACTURER'S MINIMUM CLEARANCES.

REFRIGERANT LINE SET UP TO CORRESPONDING ODU ON ROOF.

MOUNT CONDENSING UNIT ON MOUNTING PAD IN MECHANICAL YARD. SEE DETAIL 5/00-M501. PROVIDE MINIMUM 6" CLEARANCE BETWEEN WALL AND EQUIPMENT PAD. PROVIDE MINIMUM 12" CLEARANCE FROM WALL TO ODU ITSELF. FOR SPACING BETWEEN THE

ODU'S PROVIDE THE GREATER OF: 24", AND THE MANUFACTURER'S RECOMMENDED CLEARANCE.

REFRIGERANT LINE SET FROM IDU-BB018 BELOW UP TO CORRESPONDING ODU ON ROOF.

REFRIGERANT LINE SET FROM IDU-BF107 BELOW UP TO CORRESPONDING ODU ON ROOF.

MOUNT UNIT ON WALL 9'-6" AFF IN LOCATION SHOWN. SEE DETAIL 7/00-M501.

LOCATE TEMPTRAK TEMPERATURE/HUMIDITY SENSOR ON WALL WITHIN 6 FT OF TELECOM RACK. TEMPTRAK SENSOR SHALL INTEGRATE WITH VA'S CENTRAL MONITORING SYSTEM TO ALERT WHEN ENVIRONMENTAL CONDITION REQUIREMENTS ARE NOT MET.

SEE DESIGN CONDITIONS TABLE ON SHEET 00-M001.

Revisions: Date: SHEET 368 of 559

TR (NEW)

2E202ACONF

2E205

T

S

47-IDU-2E202A

ELEC

2A245

TR (EXISTING)

2A246

STAIR #1

T

S

47-IDU-2A246

ELEC

2B213

TR (EXISTING)

2B212

STAIR #2

T

S

47-IDU-2B212

PARTITION LEGEND

FIRE BARRIER, 2 HR

FIRE BARRIER, 1 HR

SMOKE BARRIER, 1/2 HR

SMOKE RESISTIVE HAZARDOUS

PATIENT SUIT/ NON SLEEPING

R

OBERT BEL L

SEAL

047145

N

O

RT

H CAROLIN

A

P R

FO

ESS ON

A L

I

N E

GINEER

PLAN

NORTH

N

FINAL BID DOCUMENTS

FOR OFFICIAL USE ONLY

www.coffman.com

701 Corporate Center Drive, Suite 475

Raleigh, NC 27607 ph 919.314.6686

2 2 4 6 8 10

1/4" = 1'-0"

FEETSCALE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL BID DOCUMENTS

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMP

321 4 5 6 7 8 9 10

SHEET NOTES:

SHEET OF

Facilities Management

Services

12/18/2025

A u to d e s k D o c s /A s h e v ill e E

H R

M

V

/6

-2

-7

.0

.M

.A S

H

E H

R M

.r v t

/1 /2

:3

:2

P M

47-MP403

ENLARGED MECHANICAL 2ND FLOOR

PLANSAwen Solutions Group

215 N. Payne Street, Suite 122

Alexandria, VA 22314

12.19.2025

EHRM INFRASTRUCTURE

UPGRADES BLDG 47

1100 TUNNEL ROAD

ASHEVILLE, NC 28805

637-22-700

GENERAL NOTES:

1/4" = 1'-0"

2 2E202A - MECHANICAL PLAN

1/4" = 1'-0"

3 2A246 - MECHANICAL PLAN

MOUNT UNIT ON WALL ABOVE DOOR. SEE DETAIL 7/00-M501. MAINTAIN MANUFACTURER'S MINIMUM CLEARANCES.

REFRIGERANT LINE SET UP TO CORRESPONDING ODU ON ROOF.

REFRIGERANT LINE SET FROM IDU-1B134 BELOW UP TO CORRESPONDING ODU ON ROOF.

REFRIGERANT LINE SET FROM IDU-BB018 BELOW UP TO CORRESPONDING ODU ON ROOF.

REFRIGERANT LINE SET FROM IDU-1A137 BELOW UP TO CORRESPONDING ODU ON ROOF.

REFRIGERANT LINE SET FROM IDU-1W133 BELOW UP TO CORRESPONDING ODU ON ROOF.

REFRIGERANT LINE SET FROM IDU-BC118 BELOW UP TO CORRESPONDING ODU ON ROOF.

LOCATE TEMPTRAK TEMPERATURE/HUMIDITY SENSOR ON WALL WITHIN 6 FT OF TELECOM RACK. TEMPTRAK SENSOR SHALL INTEGRATE WITH VA'S CENTRAL MONITORING SYSTEM TO ALERT WHEN ENVIRONMENTAL CONDITION REQUIREMENTS ARE NOT MET.

SEE DESIGN CONDITIONS TABLE ON SHEET 00-M001.

MOUNT UNIT ON WALL 9'-6" AFF IN LOCATION SHOWN. SEE DETAIL 7/00-M501.

1/4" = 1'-0"

1 2B212 - MECHANICAL PLAN

1. ROUTE REFRIGERANT LINES TIGHT TO UNDERSIDE OF FLOOR ABOVE.

2. SIZE REFRIGERANT LINES PER MANUFACTURER'S RECOMMENDATIONS.

3. PROVIDE FIRE-STOPPING WHERE PIPING PENETRATES FIRE-RATED WALLS. RATED WALLS ARE INDICATED ON

PLANS.

4. IT RACKS SHOWN FOR REFERENCE ONLY. DASHED LINES INDICATE PLACEHOLDER FOR FUTURE RACK, NOT IN

CONTRACT. SEE TELECOM DRAWINGS FOR MORE INFORMATION.

Revisions: Date: SHEET 369 of 559

TR (EXPANDED)

A301

T 2

S5

47-IDU-A301

TR (EXPANDED)

A401

T

S5

47-IDU-A401

TR (EXPANDED)

A501

T

S5

47-IDU-A501

PARTITION LEGEND

FIRE BARRIER, 2 HR

FIRE BARRIER, 1 HR

SMOKE BARRIER, 1/2 HR

SMOKE RESISTIVE HAZARDOUS

PATIENT SUIT/ NON SLEEPING

R

OBERT BEL L

SEAL

047145

N

O

RT

H CAROLIN

A

P R

FO

ESS ON

A L

I

N E

GINEER

PLAN

NORTH

N

FINAL BID DOCUMENTS

FOR OFFICIAL USE ONLY

www.coffman.com

701 Corporate Center Drive, Suite 475

Raleigh, NC 27607 ph 919.314.6686

2 2 4 6 8 10

1/4" = 1'-0"

FEETSCALE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL BID DOCUMENTS

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMP

321 4 5 6 7 8 9 10

SHEET NOTES:

SHEET OF

Facilities Management

Services

12/18/2025

A u to d e s k D o c s /A s h e v ill e E

H R

M

V

/6

-2

-7

.0

.M

.A S

H

E H

R M

.r v t

/1 /2

:3

:2

P M

47-MP404

ENLARGED MECHANICAL 3RD, 4TH,

AND 5TH FLOOR PLANSAwen Solutions Group

215 N. Payne Street, Suite 122

Alexandria, VA 22314

12.19.2025

EHRM INFRASTRUCTURE

UPGRADES BLDG 47

1100 TUNNEL ROAD

ASHEVILLE, NC 28805

637-22-700

1/4" = 1'-0"

1 A301 - MECHANICAL PLAN

1/4" = 1'-0"

2 A401 - MECHANICAL PLAN

1/4" = 1'-0"

3 A501 - MECHANICAL PLAN

GENERAL NOTES:

MOUNT UNIT ON WALL ABOVE DOOR. SEE DETAIL 7/00-M501. MAINTAIN MANUFACTURER'S MINIMUM CLEARANCES.

REFRIGERANT LINE SET UP TO CORRESPONDING ODU ON ROOF.

REFRIGERANT LINE SET FROM IDU-A301 BELOW UP TO CORRESPONDING ODU ON ROOF.

REFRIGERANT LINE SET FROM IDU-A401 BELOW UP TO CORRESPONDING ODU ON ROOF.

LOCATE TEMPTRAK TEMPERATURE/HUMIDITY SENSOR ON WALL WITHIN 6 FT OF TELECOM RACK. TEMPTRAK SENSOR SHALL INTEGRATE WITH VA'S CENTRAL MONITORING SYSTEM TO ALERT WHEN ENVIRONMENTAL CONDITION REQUIREMENTS ARE NOT

MET. SEE DESIGN CONDITIONS TABLE ON SHEET 00-M0

1. ROUTE REFRIGERANT LINES TIGHT TO UNDERSIDE OF FLOOR ABOVE.

2. SIZE REFRIGERANT LINES PER MANUFACTURER'S RECOMMENDATIONS.

3. PROVIDE FIRE-STOPPING WHERE PIPING PENETRATES FIRE-RATED WALLS. RATED WALLS ARE INDICATED ON

PLANS.

4. IT RACKS SHOWN FOR REFERENCE ONLY. DASHED LINES INDICATE PLACEHOLDER FOR FUTURE RACK, NOT IN

CONTRACT. SEE TELECOM DRAWINGS FOR MORE INFORMATION.

Revisions: Date: SHEET 370 of 559

47-ODU-1B134 47-ODU-BB018 47-ODU-2B212

47-ODU-BF10747-ODU-1H113

47-ODU-2A246 47-ODU-1A137

47-ODU-2E202A 47-ODU-1W13347-ODU-BC118A

47-ODU-BC118B

47-ODU-A301 47-ODU-A401 47-ODU-A501

PARTITION LEGEND

FIRE BARRIER, 2 HR

FIRE BARRIER, 1 HR

SMOKE BARRIER, 1/2 HR

SMOKE RESISTIVE HAZARDOUS

PATIENT SUIT/ NON SLEEPING

R

OBERT BEL L

SEAL

047145

N

O

RT

H CAROLIN

A

P R

FO

ESS ON

A L

I

N E

GINEER

PLAN

NORTH

N

FINAL BID DOCUMENTS

FOR OFFICIAL USE ONLY

www.coffman.com

701 Corporate Center Drive, Suite 475

Raleigh, NC 27607 ph 919.314.6686

2 2 4 6 8 10

1/4" = 1'-0"

FEETSCALE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL BID DOCUMENTS

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMP

321 4 5 6 7 8 9 10

SHEET NOTES:

SHEET OF

Facilities Management

Services

12/18/2025

A u to d e s k D o c s /A s h e v ill e E

H R

M

V

/6

-2

-7

.0

.M

.A S

H

E H

R M

.r v t

/1 /2

:3

:2

P M

47-MP405

ENLARGED MECHANICAL ROOF PLANS

Awen Solutions Group

215 N. Payne Street, Suite 122

Alexandria, VA 22314

12.19.2025

EHRM INFRASTRUCTURE

UPGRADES BLDG 47

1100 TUNNEL ROAD

ASHEVILLE, NC 28805

637-22-700

1/4" = 1'-0"

3 BB018, 1B134, 2B212 - MECHANICAL ROOF PLAN

GENERAL NOTES:

1/4" = 1'-0"

4 BF107, 1H113 - MECHANICAL ROOF PLAN

1/4" = 1'-0"

2 1A137, 2A246 - MECHANICAL ROOF PLAN

1/4" = 1'-0"

1 BC118, 1W133, 2E202A - MECHANICAL ROOF PLAN

1 REFRIGERANT LINE SET(S) DOWN TO CORRESPONDING IDU. UTILIZE PIPE PORTAL. SEE DETAIL 3/00-M501.

1. MOUNT CONDENSING UNITS ON ROOF CURB OR ROOF RAILS. SEE DETAIL 5/00-M501. LOCATE CONDENSING UNITS AS NEAR AS PRACTICAL TO REFRIGERANT PIPE PORTALS. MAINTAIN MANUFACTURER'S MINIMUM RECOMMENDED CLEARANCES BETWEEN CONDENSING UNITS AND BETWEEN OTHER OBSTRUCTIONS. CONDENSING UNITS SHALL NOT ADVERSELY AFFECT THE PERFORMANCE OR SERVICABILITY OF EXISTING NEARBY EQUIPMENT.

2. SIZE REFRIGERANT LINES PER MANUFACTURER'S RECOMMENDATIONS.

1/4" = 1'-0"

5 A301, A401, A501 - MECHANICAL ROOF PLAN

Revisions: Date: SHEET 371 of 559

1 2 34 5

9 10

S H T

RA

H L T

M

H T H L

SA

STARTER

M

Run Conditions - Continuous (Normal):

The unit shall run continuously at partload capacity in conjunction with the partner unit serving the same row to maintain:

• An average rack face temperature of 75°F (adj.) or below

• A maximum rack face temperature of 80°F or below

Run Conditions - Continuous (Partner Unit Failure):

The unit shall run continuously at full load capacity to compensate for partner unit failure to maintain:

• An average rack face temperature of 75°F (adj.) or below

• A maximum rack face temperature of 80°F or below

Emergency Shutdown:

The unit shall shut down and generate an alarm upon receiving an emergency shutdown signal.

Freeze Protection:

The unit shall shut down and generate an alarm upon receiving a freezestat status.

High Static Shutdown:

The unit shall shut down and generate an alarm upon receiving a high static shutdown signal.

Return Air Smoke Detection:

The unit shall shut down and generate an alarm upon receiving a return air smoke detector status.

Supply Fan:

The supply fan shall run anytime the unit is commanded to run and modulate fan speed based on necessity determined by the Vigilent control system, unless shutdown on safeties. To prevent short cycling, the supply fan shall have a user definable (adj.) minimum runtime.

Alarms shall be provided as follows:

• Supply Fan Failure: Commanded on, but the status is off.

• Supply Fan in Hand: Commanded off, but the status is on.

• Supply Fan Runtime Exceeded: Status runtime exceeds a user definable limit (adj.).

Rack Face Temperature Control:

The wireless sensors shall measure the rack face temperatures at specified points and shall use Artificial Interligence to determine what racks need cooling. The controller shall modulate the supply fan speed to maintain temperature setpoints.

The supply fan ECM shall not drop below 30% (adj.).

Compressor:

The control system shall measure the supply air temperature and modulate the compressor and supply fan to maintain its cooling setpoint.

The cooling shall be enabled whenever:

• The average or maximum rack face temperature is above the cooling setpoint.

• AND the supply fan status is on.

Dehumidification:

The wireless humidity sensors shall measure the humidity levels at various specified points and override the cooling sequence to maintain return air humidity at or below 60% rh (adj.).

Dehumidification shall be enabled whenever the supply fan status is on.

Humidifier Control:

The wireless humidity sensors shall measure the humidity levels at various specified points and modulate the humidifier to maintain a setpoint of 30% rh (adj.) or higher. The humidifier shall be enabled whenever the supply fan status is on.

The humidifier shall turn off whenever:

• Average humidity levels rise above 40% (adj.).

• OR on loss of supply fan status.

Alarms shall be provided as follows:

• High Humidity: If the average humidity levels are greater than 60% rh (adj.).

• Low Humidity: If the average humidity levels are less than 30% rh (adj.).

Prefilter Differential Pressure Monitor:

The control system shall monitor the differential pressure across the prefilter.

Alarms shall be provided as follows:

• Prefilter Change Required: Prefilter differential pressure exceeds a user definable limit (adj.).

Return Air Temperature:

The control system shall monitor the return air temperature and use as required for setpoint control or economizer control (if present).

Alarms shall be provided as follows:

• High Return Air Temp: If the return air temperature is greater than 100°F (adj.).

• Low Return Air Temp: If the return air temperature is less than 45°F (adj.).

Supply Air Temperature:

The control system shall monitor the supply air temperature.

Alarms shall be provided as follows:

• High Supply Air Temp: If the supply air temperature is greater than 80°F (adj.).

• Low Supply Air Temp: If the supply air temperature is less than 45°F (adj.).

CT

SF

DX

COMPRESSOR

VIGILENT TEMPERATURE/HUMIDITY

SENSOR NETWORK

(SEE 47-MP401 FOR LOCATIONS)

BI

LIEBERT INTERFACE CONTROL PANEL EI

AI AI AI BI AI AI AO AO BO AO AI AI BI

AI

EI

VIGILENT DDC SYSTEM CONTROL MODULE

R

OBERT BEL L

SEAL

047145

N

O

RT

H CAROLIN

A

P R

FO

ESS ON

A L

I

N E

GINEER

FINAL BID DOCUMENTS

FOR OFFICIAL USE ONLY

www.coffman.com

701 Corporate Center Drive, Suite 475

Raleigh, NC 27607 ph 919.314.6686

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL BID DOCUMENTS

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMP

321 4 5 6 7 8 9 10

SHEET OF

Facilities Management

Services

12/18/2025

A u to d e s k D o c s /A s h e v ill e E

H R

M

V

/6

-2

-7

.0

.M

.A S

H

E H

R M

.r v t

/1 /2

:3

:3

P M

47-MG501

MECHANICAL CONTROLS DETAILS

Awen Solutions Group

215 N. Payne Street, Suite 122

Alexandria, VA 22314

12.19.2025

EHRM INFRASTRUCTURE

UPGRADES BLDG 47

1100 TUNNEL ROAD

ASHEVILLE, NC 28805

637-22-700

CRAC POINTS LIST SCHEDULE

POINT ID BMS POINT DESCRIPTION BAS TYPE

1 PREFILTER DIFFERENTIAL PRESSURE AI

2 SUPPLY AIR HUMIDITY AI

3 SUPPLY AIR TEMP AI

4 RETURN AIR HUMIDITY AI

5 RETURN AIR TEMP AI

6 HUMIDIFIER OUTPUT AO

7 SUPPLY FAN SPEED AO

8 COMPRESSOR AO

9 FREEZESTAT BI

10 HIGH STATIC SHUTDOWN BI

11 SUPPLY FAN STATUS BI

12 RETURN AIR SMOKE DETECTOR BI

13 HUMIDIFIER ENABLE BO

14 SUPPLY FAN START/STOP BO

15 RACK TEMP/HUMIDITY SENSORS AI

NTS

1 CRAC CONTROL POINT SCHEMATIC AND SEQUENCE OF OPERATIONS

Revisions: Date: SHEET 372 of 559

R

OBERT BEL L

SEAL

047145

N

O

RT

H CAROLIN

A

P R

FO

ESS ON

A L

I

N E

GINEER

FINAL BID DOCUMENTS

FOR OFFICIAL USE ONLY

www.coffman.com

701 Corporate Center Drive, Suite 475

Raleigh, NC 27607 ph 919.314.6686

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL BID DOCUMENTS

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMP

321 4 5 6 7 8 9 10

SHEET OF

Facilities Management

Services

12/18/2025

A u to d e s k D o c s /A s h e v ill e E

H R

M

V

/6

-2

-7

.0

.M

.A S

H

E H

R M

.r v t

/1 /2

:3

:3

P M

47-MG601

MECHANICAL SCHEDULES

Awen Solutions Group

215 N. Payne Street, Suite 122

Alexandria, VA 22314

12.19.2025

EHRM INFRASTRUCTURE

UPGRADES BLDG 47

1100 TUNNEL ROAD

ASHEVILLE, NC 28805

637-22-700

DC CRAC UNIT SCHEDULE

MARK CORRESPONDING CU LOCATION

FAN COOLING ELECTRICAL BASIS OF DESIGN

REMARKSAIR FLOW ESP HP NOMINAL TONS TOTAL COOLING SENSIBLE COOLING EDB EWB LDB VOLTAGE PHASE FREQUENCY FLA MCA MOCP MAKE MODEL WEIGHT

47-CRAC-1A 47-CU-1A DATA CENTER 3500 CFM 0.2 in-wg 4.2 hp 7.1 ton 85,400 Btu/h 85,400 Btu/h 85 °F 64 °F 55 °F 460 V 3 60 Hz 32.5 A 39.6 A 50 A LIEBERT PX023 670 lb ALL

47-CRAC-1B 47-CU-1B DATA CENTER 3500 CFM 0.2 in-wg 4.2 hp 7.1 ton 85,400 Btu/h 85,400 Btu/h 85 °F 64 °F 55 °F 460 V 3 60 Hz 32.5 A 39.6 A 50 A LIEBERT PX023 670 lb ALL

47-CRAC-2A 47-CU-2A DATA CENTER 13700 CFM 0.2 in-wg 3.6 hp 30.0 ton 360,000 Btu/h 344,000 Btu/h 85 °F 64 °F 55 °F 460 V 3 60 Hz 83.7 A 97.4 A 110 A LIEBERT DS105 2780 lb ALL

47-CRAC-2B 47-CU-2B DATA CENTER 13700 CFM 0.2 in-wg 3.6 hp 30.0 ton 360,000 Btu/h 344,000 Btu/h 85 °F 64 °F 55 °F 460 V 3 60 Hz 83.7 A 97.4 A 110 A LIEBERT DS105 2780 lb ALL

MINI-SPLIT INDOOR UNIT SCHEDULE

MARK CORRESPONDING ODU LOCATION

MAX SUPPLY AIR

FLOW

OUTSIDE AIR

FLOW

COOLING HEATING ELECTRICAL BASIS OF DESIGN

REMARKSEDB EWB LDB EDB LDB VOLTAGE PHASE FREQUENCY FLA MCA MAKE MODEL WEIGHT

47-IDU-A301 47-ODU-A301 BLDG 47 A301 1000 CFM 0 CFM 80 °F 62.5 °F 56 °F - - 208 V 1 60 Hz 3.00 A 4.0 A VERTIV WLM070A 120 lb 4-6,11

47-IDU-A401 47-ODU-A401 BLDG 47 A401 1000 CFM 0 CFM 80 °F 62.5 °F 56 °F - - 208 V 1 60 Hz 3.00 A 4.0 A VERTIV WLM070A 120 lb 1,4-6,11

47-IDU-A501 47-ODU-A501 BLDG 47 A501 1000 CFM 0 CFM 80 °F 62.5 °F 56 °F - - 208 V 1 60 Hz 3.00 A 4.0 A VERTIV WLM070A 120 lb 1,4-6,11

47-IDU-BB018 47-ODU-BB018 BLDG 47 BB018 1000 CFM 0 CFM 80 °F 62.5 °F 56 °F - - 208 V 1 60 Hz 3.00 A 4.0 A VERTIV WLM070A 120 lb 1,4-6,11

47-IDU-BC118A 47-ODU-BC118-A BLDG 47 BC118 616 CFM 0 CFM 80 °F 62.5 °F 58 °F - - 208 V 1 60 Hz 2.00 A 3.0 A VERTIV WLM030A 92 lb 1,5-7,11

47-IDU-BC118B 47-ODU-BC118-B BLDG 47 BC118 616 CFM 0 CFM 80 °F 62.5 °F 58 °F - - 208 V 1 60 Hz 2.00 A 3.0 A VERTIV WLM030A 92 lb 1,5-7,11

47-IDU-BC131A 47-ODU-BC131A BLDG 47 BC131 616 CFM 0 CFM 80 °F 62.5 °F 58 °F - - 208 V 1 60 Hz 2.00 A 3.0 A VERTIV WLM030A 92 lb 1,5-7,11

47-IDU-BC131B 47-ODU-BC131B BLDG 47 BC131 616 CFM 0 CFM 80 °F 62.5 °F 58 °F - - 208 V 1 60 Hz 2.00 A 3.0 A VERTIV WLM030A 92 lb 1,5-7,11

47-IDU-BC143A 47-ODU-BC143A BLDG 47 BC143 616 CFM 0 CFM 80 °F 62.5 °F 58 °F - - 208 V 1 60 Hz 2.00 A 3.0 A VERTIV WLM030A 92 lb 1,5-7,11

47-IDU-BC143B 47-ODU-BC143B BLDG 47 BC143 616 CFM 0 CFM 80 °F 62.5 °F 58 °F - - 208 V 1 60 Hz 2.00 A 3.0 A VERTIV WLM030A 92 lb 1,5-7,11

47-IDU-BC143C 47-ODU-BC143C BLDG 47 BC143 1253 CFM 55 CFM 80 °F 67.0 °F 55 °F 70 °F 90 °F 208 V 1 60 Hz 0.56 A 1.6 A DAIKIN FCA36AAVJU 58 lb 2-4,8-9

47-IDU-BF107 47-ODU-BF107 BLDG 47 BF107 1000 CFM 0 CFM 80 °F 62.5 °F 56 °F - - 208 V 1 60 Hz 3.00 A 4.0 A VERTIV WLM070A 120 lb 1,4-6,11

47-IDU-1A137 47-ODU-1A137 BLDG 47 1A137 1000 CFM 0 CFM 80 °F 62.5 °F 56 °F - - 208 V 1 60 Hz 3.00 A 4.0 A VERTIV WLM070A 120 lb 1,4-6,11

47-IDU-1B134 47-ODU-1B134 BLDG 47 1B134 1000 CFM 0 CFM 80 °F 62.5 °F 56 °F - - 208 V 1 60 Hz 3.00 A 4.0 A VERTIV WLM070A 120 lb 4-6,11

47-IDU-1D144A 47-ODU-1D144 BLDG 47 1D144 1000 CFM 0 CFM 80 °F 62.5 °F 56 °F - - 208 V 1 60 Hz 3.00 A 4.0 A VERTIV WLM070A 120 lb 1,4-6,11

47-IDU-1H113 47-ODU-1H113 BLDG 47 1H113 1000 CFM 0 CFM 80 °F 62.5 °F 56 °F - - 208 V 1 60 Hz 3.00 A 4.0 A VERTIV WLM070A 120 lb 1,4-6,11

47-IDU-1W133 47-ODU-1W133 BLDG 47 1W133 1000 CFM 0 CFM 80 °F 62.5 °F 56 °F - - 208 V 1 60 Hz 3.00 A 4.0 A VERTIV WLM070A 120 lb 1,4-6,11

47-IDU-2A246 47-ODU-2A246 BLDG 47 2A246 1000 CFM 0 CFM 80 °F 62.5 °F 56 °F - - 208 V 1 60 Hz 3.00 A 4.0 A VERTIV WLM070A 120 lb 4-6,10-11

47-IDU-2B212 47-ODU-2B212 BLDG 47 2B212 1000 CFM 0 CFM 80 °F 62.5 °F 56 °F - - 208 V 1 60 Hz 3.00 A 4.0 A VERTIV WLM070A 120 lb 1,4-6,11

47-IDU-2E202A 47-ODU-2E202A BLDG 47 2E202A 1000 CFM 0 CFM 80 °F 62.5 °F 56 °F - - 208 V 1 60 Hz 3.00 A 4.0 A VERTIV WLM070A 120 lb 1,4-6,11

MINI-SPLIT OUTDOOR UNIT SCHEDULE

MARK CORRESPONDING IDU LOCATION REFRIGERANT

COOLING HEATING ELECTRICAL BASIS OF DESIGN

REMARKS

NOMINAL

CAPACITY TOTAL COOLING SENSIBLE COOLING NSCOP EER2 SEER2 TOTAL HEATING HSPF2 VOLTAGE PHASE FREQUENCY FLA MCA MAKE MODEL WEIGHT

47-ODU-A301 47-IDU-A301 ROOF R32 7.0 kW 25,468 Btu/h 25,468 Btu/h 4.08 - - 0 Btu/h - 208 V 1 60 Hz 26 A 32.0 A VERTIV CUD070 118 lb 1-2,4-8

47-ODU-A401 47-IDU-A401 ROOF R32 7.0 kW 25,468 Btu/h 25,468 Btu/h 4.08 - - 0 Btu/h - 208 V 1 60 Hz 26 A 32.0 A VERTIV CUD070 118 lb 1-2,4-8

47-ODU-A501 47-IDU-A501 ROOF R32 7.0 kW 25,468 Btu/h 25,468 Btu/h 4.08 - - 0 Btu/h - 208 V 1 60 Hz 26 A 32.0 A VERTIV CUD070 118 lb 1-2,4-8

47-ODU-BB018 47-IDU-BB018 ROOF R32 7.0 kW 25,468 Btu/h 25,468 Btu/h 4.08 - - 0 Btu/h - 208 V 1 60 Hz 26 A 32.0 A VERTIV CUD070 118 lb 1-2,4-8

47-ODU-BC118A 47-IDU-BC118A ROOF R32 7.0 kW 25,468 Btu/h 25,468 Btu/h 4.08 - - 0 Btu/h - 2080 V 1 60 Hz 26 A 32.0 A VERTIV CUD070 118 lb 1-2,4-8

47-ODU-BC118B 47-IDU-BC118B ROOF R32 7.0 kW 25,468 Btu/h 25,468 Btu/h 4.08 - - 0 Btu/h - 2080 V 1 60 Hz 26 A 32.0 A VERTIV CUD070 118 lb 1-2,4-8

47-ODU-BC131A 47-IDU-BC131A BLDG 47 OUTSIDE R32 3.7 kW 14,202 Btu/h 14,202 Btu/h 3.63 - - 0 Btu/h - 208 V 1 60 Hz 19 A 24.0 A VERTIV CUD030 110 lb 1,3-8

47-ODU-BC131B 47-IDU-BC131B BLDG 47 OUTSIDE R32 3.7 kW 14,202 Btu/h 14,202 Btu/h 3.63 - - 0 Btu/h - 208 V 1 60 Hz 19 A 24.0 A VERTIV CUD030 110 lb 1,3-8

47-ODU-BC143A 47-IDU-BC143A BLDG 47 OUTSIDE R32 7.0 kW 25,468 Btu/h 25,468 Btu/h 4.08 - - 0 Btu/h - 208 V 1 60 Hz 26 A 32.0 A VERTIV CUD070 118 lb 1,3-8

47-ODU-BC143B 47-IDU-BC143B BLDG 47 OUTSIDE R32 7.0 kW 25,468 Btu/h 25,468 Btu/h 4.08 - - 0 Btu/h - 208 V 1 60 Hz 26 A 32.0 A VERTIV CUD070 118 lb 1,3-8

47-ODU-BC143C 47-IDU-BC143C SITE R32 10.6 kW 36,000 Btu/h 28,300 Btu/h - 12.2 20 40,000 Btu/h 10 208 V 1 60 Hz 26 A 34.6 A DAIKIN RZA36AAVJU 234 lb 1,3

47-ODU-BF107 47-IDU-BF107 ROOF R32 7.0 kW 25,468 Btu/h 25,468 Btu/h 4.08 - - 0 Btu/h - 208 V 1 60 Hz 26 A 32.0 A VERTIV CUD070 118 lb 1-2,4-8

47-ODU-1A137 47-IDU-1A37 ROOF R32 7.0 kW 25,468 Btu/h 25,468 Btu/h 4.08 - - 0 Btu/h - 208 V 1 60 Hz 26 A 32.0 A VERTIV CUD070 118 lb 1-2,4-8

47-ODU-1B134 47-1DU-1B134 ROOF R32 7.0 kW 25,468 Btu/h 25,468 Btu/h 4.08 - - 0 Btu/h - 208 V 1 60 Hz 26 A 32.0 A VERTIV CUD070 118 lb 1-2,4-8

47-ODU-1D144 47-IDU-1D144A SITE - PLAN NORTH R32 7.0 kW 25,468 Btu/h 25,468 Btu/h 4.08 - - 0 Btu/h - 208 V 1 60 Hz 26 A 32.0 A VERTIV CUD070 118 lb 1,3-8

47-ODU-1H113 47-IDU-1H113 ROOF R32 7.0 kW 25,468 Btu/h 25,468 Btu/h 4.08 - - 0 Btu/h - 208 V 1 60 Hz 26 A 32.0 A VERTIV CUD070 118 lb 1-2,4-8

47-ODU-1W133 47-IDU-1W133 ROOF R32 7.0 kW 25,468 Btu/h 25,468 Btu/h 4.08 - - 0 Btu/h - 208 V 1 60 Hz 26 A 32.0 A VERTIV CUD070 118 lb 1-2,4-8

47-ODU-2A246 47-IDU-2A246 ROOF R32 7.0 kW 25,468 Btu/h 25,468 Btu/h 4.08 - - 0 Btu/h - 208 V 1 60 Hz 26 A 32.0 A VERTIV CUD070 118 lb 1-2,4-8

47-ODU-2B212 47-IDU-2B212 ROOF R32 7.0 kW 25,468 Btu/h 25,468 Btu/h 4.08 - - 0 Btu/h - 208 V 1 60 Hz 26 A 32.0 A VERTIV CUD070 118 lb 1-2,4-8

47-ODU-2E202A 47-IDU-2E202A ROOF R32 7.0 kW 25,468 Btu/h 25,468 Btu/h 4.08 - - 0 Btu/h - 208 V 1 60 Hz 26 A 32.0 A VERTIV CUD070 118 lb 1-2,4-8

NOTES:

1. PROVIDE WITH BLUE DIAMOND MAXIBLUE (X87-721) OR EQUAL CONDENSATE PUMP. COORDINATE WITH ELECTRICAL CONTRACTOR FOR POWER. PROVIDE DRIP PAN WITH MOISTURE SENSOR TO GENERATE AN ALARM TO THE BAS IN THE EVENT OF PRIMARY DRAIN

OVERFLOW.

2. MOUNT IN LAY-IN CEILING AND SUSPEND FROM STRUCTURE ABOVE.

3. PROVIDE WITH MANUFACTURER'S INTEGRAL AIR FILTER.

4. PROVIDE WITH MANUFACTURER'S THERMOSTAT. UNIT TO RUN ON INTERNAL CONTROL LOGIC.

5. INDOOR UNIT POWERED BY OUTDOOR UNIT. ROUTE CONTROL AND POWER WIRING WITH REFRIGERANT LINESET.

6. PROVIDE ONE (1) TEMPTRAK TEMPERATURE/HUMIDITY SENSOR PER TELECOM ROOM TO INTEGRATE WITH VA'S CENTRAL MONITORING SYSTEM TO ALERT WHEN ENVIRONMENTAL CONDITION REQUIREMENTS ARE NOT MET. SEE DESIGN CONDITIONS TABLE ON SHEET 00-

M001.

7. PROVIDE ONE (1) CONTROLLER PER TELECOM ROOM TO CONTROL BOTH INDOOR UNITS.

8. WITH INTEGRAL CONDENSATE LIFT KIT (POWERED BY UNIT). PROVIDE AUXILIARY CONDENSATE PAN WITH FLOAT SWITCH TO SHUT DOWN UNIT AND MOISTURE SENSOR TO GENERATE AN ALARM TO THE BAS IN THE EVENT OF PRIMARY DRAIN PAN OVERFLOW.

9. INDOOR UNIT POWERED FROM ELECTRICAL PANEL. COORDINATE WITH ELECTRICAL CONTRACTOR.

10. PROVIDE WITH BLUE DIAMOND MEGABLUE (X87-835) OR EQUAL CONDENSATE PUMP. COORDINATE WITH ELECTRICAL CONTRACTOR FOR POWER. PROVIDE DRIP PAN WITH MOISTURE SENSOR TO GENERATE AN ALARM TO THE BAS IN THE EVENT OF PRIMARY DRAIN

OVERFLOW

11. ECM FAN.

NOTES:

1. PROVIDE WITH MANUFACTURER'S WIND BAFFLES.

2. PROVIDE WITH MANUFACTURER'S ROOF CURB.

3. PROVIDE WITH MANUFACTURER'S MOUNTING PAD IF EXISTING MOUNTING PAD CANNOT BE REUSED.

4. INDOOR UNIT POWERED BY OUTDOOR UNIT, ROUTE CONTROL AND POWER WIRING WITH REFRIGERANT LINESET.

5. SHALL BE CAPABLE OF OPERATING DOWN TO 0°F OUTDOOR AMBIENT TEMPERATURE.

6. VARIABLE SPEED COMPRESSOR.

7. REFRIGERNAT LINE LENGTH UP TO 197 FT.

8. ECM FAN.

DC CONDENSING UNIT SCHEDULE

MARK CORRESPONDING CRAC LOCATION

ELECTRICAL BASIS OF DESIGN

REMARKSVOLTAGE PHASE FREQUENCY FLA MCA MOCP MAKE MODEL WEIGHT

47-CU-1A 47-CRAC-1A BLDG 47 OUTSIDE 460 V 3 60 Hz 1.40 A 1.80 A 15 A LIEBERT MCM040E1 468 lb 1

47-CU-1B 47-CRAC-1B BLDG 47 OUTSIDE 460 V 3 60 Hz 1.40 A 1.80 A 15 A LIEBERT MCM040E1 468 lb 1

47-CU-2A 47-CRAC-2A BLDG 47 OUTSIDE 460 V 3 60 Hz 5.60 A 6.30 A 15 A LIEBERT MCL110E8 631 lb 1

47-CU-2B 47-CRAC-2B BLDG 47 OUTSIDE 460 V 3 60 Hz 5.60 A 6.30 A 15 A LIEBERT MCL110E8 631 lb 1

NOTES:

1. PROVIDE WITH MANUFACTURER'S INTEGRAL CONDENSATE PUMP.

2. PROVIDE WITH ETHERNET CONNECTION TO TIE INTO VIGILENT SYSTEM.

3. MOUNT ON HOUSEKEEPING PAD. ENSURE HOUSEKEEPING PAD IS 6" LONGER THAN THE UNIT ON ALL SIDES.

4…

This is the start of the file's text. The full file is on GovTribe.