Attachment 5 - Drawings Volume IV.pdf
PDF 20 MB Posted
- Solicitation number
- 36C77626R0066
About this file
These are the final bid documents for the EHRM (Electronic Health Records Management) Infrastructure Upgrades to Building 47 at the VA Medical Center in Asheville, North Carolina, consisting of mechanical, electrical, and plumbing design plans and specifications. The project is located at 1100 Tunnel Road, Asheville, NC 28805, with Project Number 637-22-700 and Building 47 designated as the subject facility.
The mechanical scope includes installation of ductless split-system HVAC units throughout multiple floors (basement through 5th floor and roof level), with detailed plans showing equipment locations, refrigerant line routing, and condensate management. The project specifies Vertiv WLM series mini-split indoor units and Vertiv CUD series outdoor condensing units for standard areas, plus Liebert CRAC (Computer Room Air Conditioning) units for the new data center, and specialized equipment for telecommunications spaces. Key mechanical components include multiple indoor/outdoor unit pairs (47-IDU and 47-ODU designations), four CRAC units (47-CRAC-1A/1B and 47-CRAC-2A/2B), condensing units (47-CU-1A/1B and 47-CU-2A/2B), and control systems with Vigilent monitoring integration for the data center. The electrical scope encompasses new and modified branch panels, busway systems rated 60-600 amperes distributed across floors, UPS systems (UPS-A and UPS-B), comprehensive building power distribution infrastructure, and emergency power provisions. The plans provide detailed panel schedules, one-line diagrams for critical and equipment branches, and equipment specifications with electrical ratings and circuit assignments throughout the building. Design documents include full-scale mechanical floor plans (basement through roof), enlarged demolition and new construction details, partition legends identifying fire barriers and smoke barriers, and comprehensive equipment and materials schedules prepared by Awen Solutions Group (Architecture/Engineer of Record) under VA Facilities Management Services for final bid distribution.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
47-MP400
47-MP400
47-MP400
47-MP401
47-MD401
47-MD400
47-MD400
47-MD400
PARTITION LEGEND
FIRE BARRIER, 2 HR
FIRE BARRIER, 1 HR
SMOKE BARRIER, 1/2 HR
SMOKE RESISTIVE HAZARDOUS
PATIENT SUIT/ NON SLEEPING
R
OBERT BEL L
SEAL
047145
N
O
RT
H CAROLIN
A
P R
FO
ESS ON
A L
I
N E
GINEER
PLAN
NORTH
N
FINAL BID DOCUMENTS
FOR OFFICIAL USE ONLY
www.coffman.com
701 Corporate Center Drive, Suite 475
Raleigh, NC 27607 ph 919.314.6686
20 20 40
1" = 20'-0"
FEETSCALE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTS
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
SHEET NOTES:
SHEET OF
Facilities Management
Services
12/18/2025
A u to d e s k D o c s /A s h e v ill e E
H R
M
V
/6
-2
-7
.0
.M
.A S
H
E H
R M
.r v t
/1 /2
:3
:4
P M
47-MP100
MECHANICAL BASEMENT PLAN -
OVERALLAwen Solutions Group
215 N. Payne Street, Suite 122
Alexandria, VA 22314
12.19.2025
EHRM INFRASTRUCTURE
UPGRADES BLDG 47
1100 TUNNEL ROAD
ASHEVILLE, NC 28805
637-22-700
D
A B
C
G E
F
KEY PLAN
1" = 20'-0"
1 MECHANICAL BASEMENT PLAN - OVERALL
GENERAL NOTES:
Revisions: Date: SHEET 354 of 559
47-MP402
47-MP402
47-MP402
47-MP402
47-MP402
47-MD402
47-MD402
47-MD402
47-MD402
47-MD402
PARTITION LEGEND
FIRE BARRIER, 2 HR
FIRE BARRIER, 1 HR
SMOKE BARRIER, 1/2 HR
SMOKE RESISTIVE HAZARDOUS
PATIENT SUIT/ NON SLEEPING
R
OBERT BEL L
SEAL
047145
N
O
RT
H CAROLIN
A
P R
FO
ESS ON
A L
I
N E
GINEER
PLAN
NORTH
N
FINAL BID DOCUMENTS
FOR OFFICIAL USE ONLY
www.coffman.com
701 Corporate Center Drive, Suite 475
Raleigh, NC 27607 ph 919.314.6686
20 20 40
1" = 20'-0"
FEETSCALE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTS
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
SHEET NOTES:
SHEET OF
Facilities Management
Services
12/18/2025
A u to d e s k D o c s /A s h e v ill e E
H R
M
V
/6
-2
-7
.0
.M
.A S
H
E H
R M
.r v t
/1 /2
:3
:4
P M
47-MP101
MECHANICAL 1ST FLOOR PLAN -
OVERALLAwen Solutions Group
215 N. Payne Street, Suite 122
Alexandria, VA 22314
12.19.2025
EHRM INFRASTRUCTURE
UPGRADES BLDG 47
1100 TUNNEL ROAD
ASHEVILLE, NC 28805
637-22-700
D
A B
C
G E
F
KEY PLAN
1" = 20'-0"
1 MECHANICAL 1ST FLOOR PLAN - OVERALL
Revisions: Date: SHEET 355 of 559
47-MP403
47-MP403
47-MP403
47-MD403
47-MD403
47-MD403
PARTITION LEGEND
FIRE BARRIER, 2 HR
FIRE BARRIER, 1 HR
SMOKE BARRIER, 1/2 HR
SMOKE RESISTIVE HAZARDOUS
PATIENT SUIT/ NON SLEEPING
R
OBERT BEL L
SEAL
047145
N
O
RT
H CAROLIN
A
P R
FO
ESS ON
A L
I
N E
GINEER
PLAN
NORTH
N
FINAL BID DOCUMENTS
FOR OFFICIAL USE ONLY
www.coffman.com
701 Corporate Center Drive, Suite 475
Raleigh, NC 27607 ph 919.314.6686
20 20 40
1" = 20'-0"
FEETSCALE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTS
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
SHEET NOTES:
SHEET OF
Facilities Management
Services
12/18/2025
A u to d e s k D o c s /A s h e v ill e E
H R
M
V
/6
-2
-7
.0
.M
.A S
H
E H
R M
.r v t
/1 /2
:3
:4
P M
47-MP102
MECHANICAL 2ND FLOOR PLAN -
OVERALLAwen Solutions Group
215 N. Payne Street, Suite 122
Alexandria, VA 22314
12.19.2025
EHRM INFRASTRUCTURE
UPGRADES BLDG 47
1100 TUNNEL ROAD
ASHEVILLE, NC 28805
637-22-700
B
C
E
F
KEY PLAN
1" = 20'-0"
1 MECHANICAL 2ND FLOOR PLAN - OVERALL
Revisions: Date: SHEET 356 of 559
47-MD404
47-MP404
PARTITION LEGEND
FIRE BARRIER, 2 HR
FIRE BARRIER, 1 HR
SMOKE BARRIER, 1/2 HR
SMOKE RESISTIVE HAZARDOUS
PATIENT SUIT/ NON SLEEPING
R
OBERT BEL L
SEAL
047145
N
O
RT
H CAROLIN
A
P R
FO
ESS ON
A L
I
N E
GINEER
PLAN
NORTH
N
FINAL BID DOCUMENTS
FOR OFFICIAL USE ONLY
www.coffman.com
701 Corporate Center Drive, Suite 475
Raleigh, NC 27607 ph 919.314.6686
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTS
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
SHEET NOTES:
SHEET OF
Facilities Management
Services
12/18/2025
A u to d e s k D o c s /A s h e v ill e E
H R
M
V
/6
-2
-7
.0
.M
.A S
H
E H
R M
.r v t
/1 /2
:3
:5
P M
47-MP103
MECHANICAL 3RD FLOOR PLAN -
OVERALLAwen Solutions Group
215 N. Payne Street, Suite 122
Alexandria, VA 22314
12.19.2025
EHRM INFRASTRUCTURE
UPGRADES BLDG 47
1100 TUNNEL ROAD
ASHEVILLE, NC 28805
637-22-700
B
C
KEY PLAN
GENERAL NOTES:
3/32" = 1'-0"
1 MECHANICAL 3RD FLOOR PLAN - OVERALL
Revisions: Date: SHEET 357 of 559
47-MP404
PARTITION LEGEND
FIRE BARRIER, 2 HR
FIRE BARRIER, 1 HR
SMOKE BARRIER, 1/2 HR
SMOKE RESISTIVE HAZARDOUS
PATIENT SUIT/ NON SLEEPING
R
OBERT BEL L
SEAL
047145
N
O
RT
H CAROLIN
A
P R
FO
ESS ON
A L
I
N E
GINEER
PLAN
NORTH
N
FINAL BID DOCUMENTS
FOR OFFICIAL USE ONLY
www.coffman.com
701 Corporate Center Drive, Suite 475
Raleigh, NC 27607 ph 919.314.6686
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTS
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
SHEET NOTES:
SHEET OF
Facilities Management
Services
12/18/2025
A u to d e s k D o c s /A s h e v ill e E
H R
M
V
/6
-2
-7
.0
.M
.A S
H
E H
R M
.r v t
/1 /2
:3
:5
P M
47-MP104
MECHANICAL 4TH FLOOR PLAN -
OVERALLAwen Solutions Group
215 N. Payne Street, Suite 122
Alexandria, VA 22314
12.19.2025
EHRM INFRASTRUCTURE
UPGRADES BLDG 47
1100 TUNNEL ROAD
ASHEVILLE, NC 28805
637-22-700
B
C
KEY PLAN
GENERAL NOTES:
3/32" = 1'-0"
1 MECHANICAL 4TH FLOOR PLAN - OVERALL
Revisions: Date: SHEET 358 of 559
47-MP404
PARTITION LEGEND
FIRE BARRIER, 2 HR
FIRE BARRIER, 1 HR
SMOKE BARRIER, 1/2 HR
SMOKE RESISTIVE HAZARDOUS
PATIENT SUIT/ NON SLEEPING
R
OBERT BEL L
SEAL
047145
N
O
RT
H CAROLIN
A
P R
FO
ESS ON
A L
I
N E
GINEER
PLAN
NORTH
N
FINAL BID DOCUMENTS
FOR OFFICIAL USE ONLY
www.coffman.com
701 Corporate Center Drive, Suite 475
Raleigh, NC 27607 ph 919.314.6686
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTS
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
SHEET NOTES:
SHEET OF
Facilities Management
Services
12/18/2025
A u to d e s k D o c s /A s h e v ill e E
H R
M
V
/6
-2
-7
.0
.M
.A S
H
E H
R M
.r v t
/1 /2
:3
:5
P M
47-MP105
MECHANICAL 5TH FLOOR PLAN -
OVERALLAwen Solutions Group
215 N. Payne Street, Suite 122
Alexandria, VA 22314
12.19.2025
EHRM INFRASTRUCTURE
UPGRADES BLDG 47
1100 TUNNEL ROAD
ASHEVILLE, NC 28805
637-22-700
B
C
KEY PLAN
GENERAL NOTES:
3/32" = 1'-0"
1 MECHANICAL 5TH FLOOR PLAN - OVERALL
Revisions: Date: SHEET 359 of 559
47-MP405
47-MP405
47-MP405
47-MP405
47-MP405
R
OBERT BEL L
SEAL
047145
N
O
RT
H CAROLIN
A
P R
FO
ESS ON
A L
I
N E
GINEER
PLAN
NORTH
N
FINAL BID DOCUMENTS
FOR OFFICIAL USE ONLY
www.coffman.com
701 Corporate Center Drive, Suite 475
Raleigh, NC 27607 ph 919.314.6686
20 20 40
1" = 20'-0"
FEETSCALE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTS
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
SHEET NOTES:
SHEET OF
Facilities Management
Services
12/18/2025
A u to d e s k D o c s /A s h e v ill e E
H R
M
V
/6
-2
-7
.0
.M
.A S
H
E H
R M
.r v t
/1 /2
:3
:5
P M
47-MP106
MECHANICAL ROOF PLAN - OVERALL
Awen Solutions Group
215 N. Payne Street, Suite 122
Alexandria, VA 22314
12.19.2025
EHRM INFRASTRUCTURE
UPGRADES BLDG 47
1100 TUNNEL ROAD
ASHEVILLE, NC 28805
637-22-700
1" = 20'-0"
1 MECHANICAL ROOF PLAN - OVERALL
D
A B
C
G E
F
KEY PLAN
Revisions: Date: SHEET 360 of 559
TELECOM
BF107
EMS CHIEF
BF108
M-LOUNGE
BF109
SIGNAL FMS
BB018
STAIR
ELECTRICAL
FMS
BC118
R
OBERT BEL L
SEAL
047145
N
O
RT
H CAROLIN
A
P R
FO
ESS ON
A L
I
N E
GINEER
PLAN
NORTH
N
FINAL BID DOCUMENTS
FOR OFFICIAL USE ONLY
www.coffman.com
701 Corporate Center Drive, Suite 475
Raleigh, NC 27607 ph 919.314.6686
2 2 4 6 8 10
1/4" = 1'-0"
FEETSCALE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTS
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
SHEET NOTES:
SHEET OF
Facilities Management
Services
12/18/2025
A u to d e s k D o c s /A s h e v ill e E
H R
M
V
/6
-2
-7
.0
.M
.A S
H
E H
R M
.r v t
/1 /2
:3
:5
P M
47-MD400
ENLARGED MECHANICAL BASEMENT
DEMOLITIONAwen Solutions Group
215 N. Payne Street, Suite 122
Alexandria, VA 22314
12.19.2025
EHRM INFRASTRUCTURE
UPGRADES BLDG 47
1100 TUNNEL ROAD
ASHEVILLE, NC 28805
637-22-700
GENERAL NOTES:
REMOVE ANY EXISTING SUPPLY AND RETURN DUCTWORK BACK TO MAIN IN ADJOINING CORRIDOR. CAP AND SEAL PER SMACNA STANDARDS. REMOVE EXISTING DIFFUSERS AND GRILLES. REMOVE ANY EXISTING TRANSFER DUCTWORK. PATCH ALL OPENINGS LEFT IN WALL FROM DUCT REMOVAL. COORDINATE WITH ARCHITECTURAL DRAWINGS FOR WALL RATINGS. MAINTAIN WALL RATING
IF RATED.
1/4" = 1'-0"
1 BF107 - MECHANICAL DEMOLITION PLAN
1/4" = 1'-0"
3 BB018 - MECHANICAL DEMOLITION PLAN
1/4" = 1'-0"
2 BC118 - MECHANICAL DEMOLITION PLAN
Revisions: Date: SHEET 361 of 559
47-CRAC-3-EX
47-CRAC-4-EX
47-CRAC-2-EX 47-CRAC-1-EX
47-CU-1-EX 47-CU-2-EX 47-CU-3-EX 47-CU-4-EX
1 1
5 6
1 1 4
AREA OF DEMOLITION
TELEHEALTH
BC131
COMPUTER ROOM
BC144
PIPE BASEMENT
2B239
R
OBERT BEL L
SEAL
047145
N
O
RT
H CAROLIN
A
P R
FO
ESS ON
A L
I
N E
GINEER
PLAN
NORTH
N
FINAL BID DOCUMENTS
FOR OFFICIAL USE ONLY
www.coffman.com
701 Corporate Center Drive, Suite 475
Raleigh, NC 27607 ph 919.314.6686
5 5 10 15 20
1/8" = 1'-0"
FEETSCALE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTS
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
SHEET NOTES:
SHEET OF
Facilities Management
Services
12/18/2025
A u to d e s k D o c s /A s h e v ill e E
H R
M
V
/6
-2
-7
.0
.M
.A S
H
E H
R M
.r v t
/1 /2
:3
:5
P M
47-MD401
ENLARGED MECHANICAL DATA
CENTER DEMOLITIONAwen Solutions Group
215 N. Payne Street, Suite 122
Alexandria, VA 22314
12.19.2025
EHRM INFRASTRUCTURE
UPGRADES BLDG 47
1100 TUNNEL ROAD
ASHEVILLE, NC 28805
637-22-700
G
KEY PLAN
GENERAL NOTES:
1/8" = 1'-0"
1 DATA CENTER - MECHANICAL DEMOLITION PLAN
EXISTING EQUIPMENT, CONNECTED PIPING, AND DUCTWORK TO BE REMOVED AFTER NEW EQUIPMENT AND ASSOCIATED PIPING
AND DUCTWORK HAS BEEN INSTALLED AND IN OPERATION. SEE 1/47-MP401.
EXISTING EQUIPMENT, CONNECTED PIPING, AND DUCTWORK TO BE REMOVED.
REMOVE EXISTING SUPPLY DUCTWORK BACK TO CORRESPONDING CRAC UNIT. CAP AND SEAL PER SMACNA STANDARDS. REMOVE EXISTING DIFFUSERS AND GRILLES. REMOVE ANY EXISTING TRANSFER DUCTWORK. PATCH ALL OPENINGS LEFT IN WALL FROM DUCT REMOVAL. COORDINATE WITH ARCHITECTURAL DRAWINGS FOR WALL RATINGS. MAINTAIN WALL RATING IF RATED.
RETAIN AND REUSE EXISTING MOUNTING PADS IF IN GOOD CONDITION.
REMOVE EXISTING SUPPLY AND RETURN DUCTWORK BACK TO MAIN. CAP AND SEAL PER SMACNA STANDARDS. REMOVE EXISTING DIFFUSERS AND GRILLES. REMOVE ANY EXISTING TRANSFER DUCTWORK. PATCH ALL OPENINGS LEFT IN WALL FROM DUCT REMOVAL. COORDINATE WITH ARCHITECTURAL DRAWINGS FOR WALL RATINGS. MAINTAIN WALL RATING IF RATED.
NOTE ANY EXISTING MECHANICAL PIPING RUNNING DIRECTLY OVER THE LOCATION OF THE NEW SERVER RACKS, UPS'S, AND OTHER
ELECTRICAL EQUIPMENT AND INFORM THE EOR OF ANY OCCURANCE. SEE 1/47-MP401.
Revisions: Date: SHEET 362 of 559
SIGNAL
1B134
STAIR
FIRE EQUIP
N/A
OFFICE
1D146
RADIOLOGIST
1D145
COMP ROOM
1D144
EDUC
1W133
OFFICE
1H113
SIGNAL
1A137
R
OBERT BEL L
SEAL
047145
N
O
RT
H CAROLIN
A
P R
FO
ESS ON
A L
I
N E
GINEER
PLAN
NORTH
N
FINAL BID DOCUMENTS
FOR OFFICIAL USE ONLY
www.coffman.com
701 Corporate Center Drive, Suite 475
Raleigh, NC 27607 ph 919.314.6686
2 2 4 6 8 10
1/4" = 1'-0"
FEETSCALE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTS
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
SHEET NOTES:
SHEET OF
Facilities Management
Services
12/18/2025
A u to d e s k D o c s /A s h e v ill e E
H R
M
V
/6
-2
-7
.0
.M
.A S
H
E H
R M
.r v t
/1 /2
:3
:0
P M
47-MD402
ENLARGED MECHANICAL 1ST FLOOR
DEMOLITIONAwen Solutions Group
215 N. Payne Street, Suite 122
Alexandria, VA 22314
12.19.2025
EHRM INFRASTRUCTURE
UPGRADES BLDG 47
1100 TUNNEL ROAD
ASHEVILLE, NC 28805
637-22-700
1/4" = 1'-0"
1 1B134 - MECHANICAL DEMOLITION PLAN
GENERAL NOTES:
1/4" = 1'-0"
4 1A137 - MECHANICAL DEMOLITION PLAN
1/4" = 1'-0"
2 1D144 - MECHANICAL DEMOLITION PLAN
1/4" = 1'-0"
5 1H113 - MECHANICAL DEMOLITION PLAN
REMOVE ANY EXISTING SUPPLY AND RETURN DUCTWORK BACK TO MAIN IN ADJOINING CORRIDOR. CAP AND SEAL PER SMACNA STANDARDS. REMOVE EXISTING DIFFUSERS AND GRILLES. REMOVE ANY EXISTING TRANSFER DUCTWORK. PATCH ALL OPENINGS LEFT IN WALL FROM DUCT REMOVAL. COORDINATE WITH ARCHITECTURAL DRAWINGS FOR WALL RATINGS. MAINTAIN WALL RATING IF
RATED.
DEMO EXISTING IDU AND CORRESPONDING ODU. ALL EXISTING REFRIGERANT PIPING TO BE REMOVED AND DISPOSED.
REMOVE EXISTING THERMOSTATS.
1/4" = 1'-0"
3 1W133 - MECHANICAL FIRST FLOOR DEMOLITION PLAN
Revisions: Date: SHEET 363 of 559
STAIR
2B251
SIGNAL
2B212
SIGNAL
2A246
STAIR #1
2A240
HSKG
2E204
EQUIP'T STORAGE
2E206
STAFF CONF
ROOM
2E205
R
OBERT BEL L
SEAL
047145
N
O
RT
H CAROLIN
A
P R
FO
ESS ON
A L
I
N E
GINEER
PLAN
NORTH
N
FINAL BID DOCUMENTS
FOR OFFICIAL USE ONLY
www.coffman.com
701 Corporate Center Drive, Suite 475
Raleigh, NC 27607 ph 919.314.6686
2 2 4 6 8 10
1/4" = 1'-0"
FEETSCALE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTS
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
SHEET NOTES:
SHEET OF
Facilities Management
Services
12/18/2025
A u to d e s k D o c s /A s h e v ill e E
H R
M
V
/6
-2
-7
.0
.M
.A S
H
E H
R M
.r v t
/1 /2
:3
:0
P M
47-MD403
ENLARGED MECHANICAL 2ND FLOOR
DEMOLITIONAwen Solutions Group
215 N. Payne Street, Suite 122
Alexandria, VA 22314
12.19.2025
EHRM INFRASTRUCTURE
UPGRADES BLDG 47
1100 TUNNEL ROAD
ASHEVILLE, NC 28805
637-22-700
GENERAL NOTES:
REMOVE ANY EXISTING SUPPLY AND RETURN DUCTWORK BACK TO MAIN IN ADJOINING CORRIDOR. CAP AND SEAL PER SMACNA STANDARDS. REMOVE EXISTING DIFFUSERS AND GRILLES. REMOVE ANY EXISTING TRANSFER DUCTWORK. PATCH ALL OPENINGS LEFT IN WALL FROM DUCT REMOVAL. COORDINATE WITH ARCHITECTURAL DRAWINGS FOR WALL RATINGS. MAINTAIN WALL RATING
IF RATED.
1/4" = 1'-0"
2 2A246 - MECHANICAL DEMOLITION PLAN
1/4" = 1'-0"
3 2E205 - MECHANICAL DEMOLITION PLAN
1/4" = 1'-0"
1 2B212 - MECHANICAL DEMOLITION PLAN
Revisions: Date: SHEET 364 of 559
EXAM
A302
FC&NC
A301A
DATA IRM
A301
PHONE FMS
TA300B
47-FCU-A301B-EX
47-FCU-A301A-EX
47-FCU-A401B-EX
47-FCU-A401A-EX
EC FMS
TA401D
FC FMS
TA401C
STORAGE FMS
A401A
BEDROOM #1
NURSING
4W401
PHONE IRM
A401
47-FCU-A501B-EX
47-FCU-A501A-EX
EC FMS
TA501A
FA FMS
A501A
FA
TA501B
PHONE IRM
A501 BEDROOM #1
5W501
R
OBERT BEL L
SEAL
047145
N
O
RT
H CAROLIN
A
P R
FO
ESS ON
A L
I
N E
GINEER
PLAN
NORTH
N
FINAL BID DOCUMENTS
FOR OFFICIAL USE ONLY
www.coffman.com
701 Corporate Center Drive, Suite 475
Raleigh, NC 27607 ph 919.314.6686
2 2 4 6 8 10
1/4" = 1'-0"
FEETSCALE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTS
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
SHEET NOTES:
SHEET OF
Facilities Management
Services
12/18/2025
A u to d e s k D o c s /A s h e v ill e E
H R
M
V
/6
-2
-7
.0
.M
.A S
H
E H
R M
.r v t
/1 /2
:3
:1
P M
47-MD404
ENLARGED MECHANICAL 3RD, 4TH,
AND 5TH FLOOR DEMOLITIONAwen Solutions Group
215 N. Payne Street, Suite 122
Alexandria, VA 22314
12.19.2025
EHRM INFRASTRUCTURE
UPGRADES BLDG 47
1100 TUNNEL ROAD
ASHEVILLE, NC 28805
637-22-700
GENERAL NOTES:
1/4" = 1'-0"
1 A301 - MECHANICAL DEMOLITION PLAN
1/4" = 1'-0"
2 A401 - MECHANICAL DEMOLITION PLAN
1/4" = 1'-0"
3 A501 - MECHANICAL DEMOLITION PLAN
REMOVE ANY EXISTING SUPPLY AND RETURN DUCTWORK BACK TO MAIN IN ADJOINING CORRIDOR. CAP AND SEAL PER SMACNA STANDARDS. REMOVE EXISTING DIFFUSERS AND GRILLES. REMOVE ANY EXISTING TRANSFER DUCTWORK. PATCH ALL OPENINGS LEFT IN WALL FROM DUCT REMOVAL. COORDINATE WITH ARCHITECTURAL DRAWINGS FOR WALL RATINGS. MAINTAIN WALL RATING
IF RATED.
REMOVE EXISTING WALL-MOUNTED AND SUSPENDED FAN COIL UNITS. REMOVE CONNECTED WATER PIPING BACK TO MAINS IN
ADJACENT CORRIDOR. CAP AND SEAL.
Revisions: Date: SHEET 365 of 559
TR (EXPANDED)
BF107
OFFICE
BF108
LOUNGE
BF109
T
S
47-IDU-BF107
TR (EXISTING)
BB018ELEC.
BB019
STAIR #2
T
S
47-IDU-BB018
TR (EXPANDED)
BC118
247-IDU-BC118A
47-IDU-BC118B
S
T
PARTITION LEGEND
FIRE BARRIER, 2 HR
FIRE BARRIER, 1 HR
SMOKE BARRIER, 1/2 HR
SMOKE RESISTIVE HAZARDOUS
PATIENT SUIT/ NON SLEEPING
R
OBERT BEL L
SEAL
047145
N
O
RT
H CAROLIN
A
P R
FO
ESS ON
A L
I
N E
GINEER
PLAN
NORTH
N
FINAL BID DOCUMENTS
FOR OFFICIAL USE ONLY
www.coffman.com
701 Corporate Center Drive, Suite 475
Raleigh, NC 27607 ph 919.314.6686
2 2 4 6 8 10
1/4" = 1'-0"
FEETSCALE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTS
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
SHEET NOTES:
SHEET OF
Facilities Management
Services
12/18/2025
A u to d e s k D o c s /A s h e v ill e E
H R
M
V
/6
-2
-7
.0
.M
.A S
H
E H
R M
.r v t
/1 /2
:3
:1
P M
47-MP400
ENLARGED MECHANICAL BASEMENT
PLANSAwen Solutions Group
215 N. Payne Street, Suite 122
Alexandria, VA 22314
12.19.2025
EHRM INFRASTRUCTURE
UPGRADES BLDG 47
1100 TUNNEL ROAD
ASHEVILLE, NC 28805
637-22-700
1/4" = 1'-0"
1 BF107 - MECHANICAL PLAN
GENERAL NOTES:
1. ROUTE REFRIGERANT LINES TIGHT TO UNDERSIDE OF FLOOR ABOVE.
2. SIZE REFRIGERANT LINES PER MANUFACTURER'S RECOMMENDATIONS.
3. PROVIDE FIRE-STOPPING WHERE PIPING PENETRATES FIRE-RATED WALLS. RATED WALLS ARE INDICATED ON
PLANS.
4. IT RACKS SHOWN FOR REFERENCE ONLY. DASHED LINES INDICATE PLACEHOLDER FOR FUTURE RACK, NOT IN
CONTRACT. SEE TELECOM DRAWINGS FOR MORE INFORMATION.
1/4" = 1'-0"
3 BB018 - MECHANICAL PLAN
1/4" = 1'-0"
2 BC118 - MECHANICAL PLAN
MOUNT UNIT ON WALL ABOVE DOOR. SEE DETAIL 7/00-M501. MAINTAIN MANUFACTURER'S MINIMUM CLEARANCES.
RS/RL UP TO CORRESPONDING ODU ON ROOF.
LOCATE TEMPTRAK TEMPERATURE/HUMIDITY SENSOR ON WALL WITHIN 6 FT OF TELECOM RACK. TEMPTRAK SENSOR SHALL INTEGRATE WITH VA'S CENTRAL MONITORING SYSTEM TO ALERT WHEN ENVIRONMENTAL CONDITION REQUIREMENTS ARE NOT MET.
SEE DESIGN CONDITIONS TABLE ON SHEET 00-M0
MOUNT UNIT ON WALL 10'-0" AFF IN LOCATION SHOWN. SEE DETAIL 7/00-M501.
TWO (2) INDOOR UNITS ARE PROVIDED DUE TO REFRIGERANT CHARGE LIMITATIONS PER ASHRAE STANDARD 15. PROVIDE ONE (1) CONTROLLER TO CONTROL BOTH INDOOR UNITS SERVING THE TELECOM ROOM. CONTROLLER SHALL BE PROGRAMMED FOR LEAD/LAG OPERATION. THE LEAD UNIT SHALL OPERATE TO MAINTAIN THE ROOM TEMPERATURE SETPOINT. THE LAG UNIT SHALL START AUTOMATICALLY ON THE ROOM TEMPERATURE EXCEEDING THE SETPOINT BY 2°F (ADJ). THE UNITS SHALL SWAP LEAD AND LAG ROLES
ON A WEEKLY BASIS TO ENSURE EQUAL AVAILABLE OPERATION TIME.
Revisions: Date: SHEET 366 of 559
STAIR
CORRIDOR
DATA CENTER
(NEW)
BC131B
24"x14" RA
50"x28" RA
50"x28" RA
47-CU-2A
47-CU-1A47-CU-1B
47-CU-2B
47-CRAC-1A
47-CRAC-2A
47-CRAC-2B
47-CRAC-1B
PIPE BASEMENT
ENTRANCE ROOM
01 (NEW)
BC131A
ENTRANCE ROOM
02 (NEW)
BC143A
TR
(DECOMMISSIONED)
BC143
OFFICE
BC141
OFFICE
BC142
CORRIDOR
ELEC
BC140
STOR.
BC139
Room
2B272
6"ø OA
47-IDU-BC143C
6"ø OA
36"x14" RA
36"x14" RA
T
T
H14x14
H14x14
H14x14
H14x14
R S
/R L
R S
/R L
R S
/R L
R S
/R L
S
S
S
R S
/R L
"ø
O A
H18x12
TRANSFORMER
R S
/R L
R S
/R L
47-ODU-BC143A
47-ODU-BC143B
T 6
47-IDU-BC143A
47-ODU-BC131A
47-IDU-BC131A
47-IDU-BC131B
47-IDU-BC143B
47-ODU-BC131B
/4
R
S /R
L
47-ODU-BC143C
13IF-1
1415EMERGENCY SHUTOFF FOR
CRAC UNITS
S
30"x28" RA
30"x28" RA
275 CFM
275 CFM
700 CFM
275 CFM
700 CFM
700 CFM
275 CFM
700 CFM
700 CFM
700 CFM
700 CFM
700 CFM
700 CFM
700 CFM
700 CFM
700 CFM
700 CFM
700 CFM
700 CFM
700 CFM
700 CFM
700 CFM
0 CFM
300 CFM
300 CFM
0 CFM
300 CFM
300 CFM
PARTITION LEGEND
FIRE BARRIER, 2 HR
FIRE BARRIER, 1 HR
SMOKE BARRIER, 1/2 HR
SMOKE RESISTIVE HAZARDOUS
PATIENT SUIT/ NON SLEEPING
R
OBERT BEL L
SEAL
047145
N
O
RT
H CAROLIN
A
P R
FO
ESS ON
A L
I
N E
GINEER
PLAN
NORTH
N
FINAL BID DOCUMENTS
FOR OFFICIAL USE ONLY
www.coffman.com
701 Corporate Center Drive, Suite 475
Raleigh, NC 27607 ph 919.314.6686
5 5 10 15 20
1/8" = 1'-0"
FEETSCALE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTS
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
SHEET NOTES:
SHEET OF
Facilities Management
Services
12/18/2025
A u to d e s k D o c s /A s h e v ill e E
H R
M
V
/6
-2
-7
.0
.M
.A S
H
E H
R M
.r v t
/1 /2
:3
:1
P M
47-MP401
ENLARGED MECHANICAL DATA
CENTER PLANAwen Solutions Group
215 N. Payne Street, Suite 122
Alexandria, VA 22314
12.19.2025
EHRM INFRASTRUCTURE
UPGRADES BLDG 47
1100 TUNNEL ROAD
ASHEVILLE, NC 28805
637-22-700
G
KEY PLAN
GENERAL NOTES:
1. CRAC UNITS TO BE DOWNFLOW UNITS. SUPPLY AIR FROM CRAC UNITS TO BLOW FROM BOTTOM OF UNIT, ACROSS THE FLOOR, AND
TO THE FRONT SIDE OF CABINETS. DATA, NETWORK, AND POWER CABINETS TO HAVE CHIMNEY STACKS ON TOP OF CABINETS.
CHIMNEY STACKS TO CONNECT DIRECTLY TO UNDERSIDE OF RETURN AIR DUCTWORK. RETURN DUCTWORK TO ROUTE DIRECTLY BACK TO TOP SIDE OF CRAC UNITS. HOT AIR FROM CABINETS TO FLOW THROUGH DUCTWORK AND TO TOP SIDE OF CRAC UNITS.
2. ROUTE REFRIGERANT LINES AND DUCTWORK TIGHT TO UNDERSIDE OF FLOOR ABOVE.
3. EMERGENCY SHUT OFF SWITCHES FOR CRAC UNITS LOCATED AT NEW DATA CENTER EXITS, PER LIFE SAFETY COMMENTS.
4. DATA CENTER CRAC UNITS AND CONDITIONS TO BE CONTROLLED AND MONITORED BY THE VIGILENT CONTROL SYSTEM AS PER VA
RECOMMENDATIONS.
5. SIZE REFRIGERANT LINES PER MANUFACTURER'S RECOMMENDATIONS.
6. PROVIDE FIRE-STOPPING WHERE PIPING PENETRATES FIRE-RATED WALLS. RATED WALLS ARE INDICATED ON PLANS.
1/8" = 1'-0"
1 DATA CENTER - MECHANICAL PLAN
MOUNT CRAC UNIT DIRECTLY ON 4" CONCRETE EQUIPMENT PAD. SEE DETAIL 1/00-M501. ROUTE REFRIGERANT PIPING TO OUTDOOR UNIT. COORDINATE WITH PLUMBING CONTRACTOR FOR DOMESTIC COLD WATER PIPING TO HUMIDIFIER. (SEE 1/47-PP401). CONNECT CRAC UNIT TO WIRELESS VIGILENT CONTROL MODULE TO BE CONTROLLED BY VIGILENT SYSTEM.
LOCATE CONDENSING UNIT WHERE EXISTING UNIT WAS LOCATED. MOUNT ON CONCRETE PAD. SEE DETAIL 7/00-M501. REUSE
EXISTING PAD WHERE POSSIBLE.
TEMPERATURE AND HUMIDITY ENTERING AND LEAVING SERVER CABINETS MONITORED BY VIGILENT WIRELESS SENSOR MODULES LOCATED AS NOTED ON THE DRAWINGS AND BY THE FOLLOWING CRITERIA FROM THE ISTS STANDARDS: ONE TEMPERATURE SENSOR AND ONE HUMIDITY SENSOR CENTERED HORIZONTALLY, INSIDE THE FRONT DOOR, 4-FT +/-6IN. FROM THE FINISHED FLOOR SURFACE;
ONE TEMPERATURE SENSOR CENTER HORIZONTALLY, INSIDE THE REAR DOOR, NO MORE THAN 1-FT FROM THE TOP OF THE CABINET.
THIS CONFIGURATION OF SENSORS LOCATED IN CABINETS AT THE ENDS OF EACH CONTIGUOUS ROW AND IN EVERY THIRD CABINET
IN THE MIDDLE OF EACH CONTIGUOUS ROW.
MOUNT CONDENSING UNIT ON NEW MOUNTING PAD IN MECHANICAL YARD. SEE DETAIL 5/00-M501. EXTEND MOUNTING PAD MINIMUM 6" FROM EACH FACE OF EQUIPMENT. PROVIDE MINIMUM 6" CLEARANCE BETWEEN WALL AND EQUIPMENT PAD.
LOCAL ECC TO SERVE DATA CENTER ONLY. SET UP ECC TO SUPPORT SYSTEM CONSOLE AND WIRLESS NETWORK MANAGER FOR THE VIGILENT SYSTEM. VA PREFERS VIGILENT MONITORING SYSTEM AS BASIS OF DESIGN. COORDINATE WITH COR AND OIT FOR EXACT LOCATION OF SYSTEM CONSOLE, WIRELESS NETWORK MANAGER FOR SENSOR MODULES, ARTIFICIAL INTELLIGENCE ENGINE, AND OTHER CONTROL EQUIPMENT. CONTROL SYSTEM TO BE MONITORED BUT NOT CONTROLLED BY THE BUILDING BMS.
PROVIDE ONE (1) CONTROLLER TO CONTROL BOTH INDOOR UNITS SERVING ENTRANCE ROOM. CONTROLLER SHALL BE PROGRAMMED FOR PRIMARY/BACKUP OPERATION. THE PRIMARY UNIT SHALL OPERATE TO MAINTAIN THE ROOM TEMPERATURE SETPOINT. THE BACKUP UNIT SHALL START AUTOMATICALLY ON A FAILURE IN THE PRIMARY UNIT. THE UNITS SHALL SWAP PRIMARY AND BACKUP
ROLES ON A WEEKLY BASIS TO ENSURE EQUAL AVAILABLE OPERATION TIME.
LOCATE TEMPTRAK TEMPERATURE/HUMIDITY SENSOR ON WALL WITHIN 6 FT OF TELECOM EQUIPMENT. TEMPTRAK SENSOR SHALL INTEGRATE WITH VA'S CENTRAL MONITORING SYSTEM TO ALERT WHEN ENVIRONMENTAL CONDITION REQUIREMENTS ARE NOT MET.
SEE DESIGN CONDITIONS TABLE ON SHEET 00-M001.
MOUNT CONDENSING UNIT ON NEW MOUNTING PAD IN MECHANICAL YARD. SEE DETAIL 5/00-M501. EXTEND MOUNTING PAD MINIMUM 6" FROM FACE OF EQUIPMENT. PROVIDE MINIMUM 36" CLEARANCE BETWEEN WALL AND EQUIPMENT PAD.
ROUTE OUTSIDE AIR DUCT UP TO EXISTING LOUVER. PROVIDE BACKDRAFT DAMPER AND BIRD/INSECT SCREEN.
INSTALL ZETAFRAME VERTICAL EXHAUST DUCT AND ATTACH TO UNDERSIDE OF OVERHEAD RETURN DUCT. INSTALL GREENHECK MBD-15 BALANCING DAMPER FOR EACH VERTICAL EXAUST DUCT. BALANCE TO TO THE CFMS SHOWN ON THE PLANS. TYPICAL ALL IT
CABINETS IN THE SAME ROW. SEE DETAIL 9/00-M-501.
RETURN AIR GRILLE TO PULL HEAT FROM TRANSFORMER NEXT TO CRAC UNIT. ANGLE BLADES TOWARD TRANSFORMER.
PROVIDE GREENHECK GM-30 BACKDRAFT DAMPER TO PREVENT AIRFLOW THROUGH UNIT WHEN OFFLINE. ORIENT DAMPER IN
DIRECTION OF AIRFLOW.
IN-LINE FAN TO PULL OUTSIDE AIR TO CEILING CASSETTE. INTERLOCK FAN WITH CEILING CASSETTE TO RUN WHEN CEILING CASSETTE
FAN RUNS AND TO SHUT OFF WHEN CEILING CASSETTE FANS SHUTS OFF.
MOUNT UNIT ON WALL ABOVE DOOR. SEE DETAIL 7/00-M501. MAINTAIN MANUFACTURER'S MINIMUM CLEARANCES.
MOUNT UNIT ON WALL 9'-6" AFF IN LOCATION SHOWN. SEE DETAIL 7/00-M501.
PASSIVE MDA CABINET.
Revisions: Date: SHEET 367 of 559
ELEC
1B135
TR (EXISTING)
1B134
STAIR
T
S47-IDU-1B134
ELEC
1A136
TR (EXISTING)
1A137
STAIR
T
S
47-IDU-1A137
TR (NEW)
1H113
T
S
47-IDU-1H113
TR (NEW)
1W133
T
S
47-IDU-1W133
TR (NEW)
1D144
T
S7
47-IDU-1D144A
47-ODU-1D144
PARTITION LEGEND
FIRE BARRIER, 2 HR
FIRE BARRIER, 1 HR
SMOKE BARRIER, 1/2 HR
SMOKE RESISTIVE HAZARDOUS
PATIENT SUIT/ NON SLEEPING
R
OBERT BEL L
SEAL
047145
N
O
RT
H CAROLIN
A
P R
FO
ESS ON
A L
I
N E
GINEER
PLAN
NORTH
N
FINAL BID DOCUMENTS
FOR OFFICIAL USE ONLY
www.coffman.com
701 Corporate Center Drive, Suite 475
Raleigh, NC 27607 ph 919.314.6686
2 2 4 6 8 10
1/4" = 1'-0"
FEETSCALE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTS
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
SHEET NOTES:
SHEET OF
Facilities Management
Services
12/18/2025
A u to d e s k D o c s /A s h e v ill e E
H R
M
V
/6
-2
-7
.0
.M
.A S
H
E H
R M
.r v t
/1 /2
:3
:2
P M
47-MP402
ENLARGED MECHANICAL 1ST FLOOR
PLANSAwen Solutions Group
215 N. Payne Street, Suite 122
Alexandria, VA 22314
12.19.2025
EHRM INFRASTRUCTURE
UPGRADES BLDG 47
1100 TUNNEL ROAD
ASHEVILLE, NC 28805
637-22-700
1/4" = 1'-0"
1 1B134 - MECHANICAL PLAN
GENERAL NOTES:
1. ROUTE REFRIGERANT LINES TIGHT TO UNDERSIDE OF FLOOR ABOVE.
2. SIZE REFRIGERANT LINES PER MANUFACTURER'S RECOMMENDATIONS.
3. PROVIDE FIRE-STOPPING WHERE PIPING PENETRATES FIRE-RATED RATES. RATED WALLS ARE INDICATED ON
PLANS.
4. IT RACKS SHOWN FOR REFERENCE ONLY. DASHED LINES INDICATE PLACEHOLDER FOR FUTURE RACK, NOT IN
CONTRACT. SEE TELECOM DRAWINGS FOR MORE INFORMATION.
1/4" = 1'-0"
4 1A137 - MECHANICAL PLAN
1/4" = 1'-0"
5 1H113 - MECHANICAL PLAN
1/4" = 1'-0"
3 1W133 - MECHANICAL PLAN
1/4" = 1'-0"
2 1D144 - MECHANICAL PLAN
MOUNT UNIT ON WALL ABOVE DOOR. SEE DETAIL 7/00-M501. MAINTAIN MANUFACTURER'S MINIMUM CLEARANCES.
REFRIGERANT LINE SET UP TO CORRESPONDING ODU ON ROOF.
MOUNT CONDENSING UNIT ON MOUNTING PAD IN MECHANICAL YARD. SEE DETAIL 5/00-M501. PROVIDE MINIMUM 6" CLEARANCE BETWEEN WALL AND EQUIPMENT PAD. PROVIDE MINIMUM 12" CLEARANCE FROM WALL TO ODU ITSELF. FOR SPACING BETWEEN THE
ODU'S PROVIDE THE GREATER OF: 24", AND THE MANUFACTURER'S RECOMMENDED CLEARANCE.
REFRIGERANT LINE SET FROM IDU-BB018 BELOW UP TO CORRESPONDING ODU ON ROOF.
REFRIGERANT LINE SET FROM IDU-BF107 BELOW UP TO CORRESPONDING ODU ON ROOF.
MOUNT UNIT ON WALL 9'-6" AFF IN LOCATION SHOWN. SEE DETAIL 7/00-M501.
LOCATE TEMPTRAK TEMPERATURE/HUMIDITY SENSOR ON WALL WITHIN 6 FT OF TELECOM RACK. TEMPTRAK SENSOR SHALL INTEGRATE WITH VA'S CENTRAL MONITORING SYSTEM TO ALERT WHEN ENVIRONMENTAL CONDITION REQUIREMENTS ARE NOT MET.
SEE DESIGN CONDITIONS TABLE ON SHEET 00-M001.
Revisions: Date: SHEET 368 of 559
TR (NEW)
2E202ACONF
2E205
T
S
47-IDU-2E202A
ELEC
2A245
TR (EXISTING)
2A246
STAIR #1
T
S
47-IDU-2A246
ELEC
2B213
TR (EXISTING)
2B212
STAIR #2
T
S
47-IDU-2B212
PARTITION LEGEND
FIRE BARRIER, 2 HR
FIRE BARRIER, 1 HR
SMOKE BARRIER, 1/2 HR
SMOKE RESISTIVE HAZARDOUS
PATIENT SUIT/ NON SLEEPING
R
OBERT BEL L
SEAL
047145
N
O
RT
H CAROLIN
A
P R
FO
ESS ON
A L
I
N E
GINEER
PLAN
NORTH
N
FINAL BID DOCUMENTS
FOR OFFICIAL USE ONLY
www.coffman.com
701 Corporate Center Drive, Suite 475
Raleigh, NC 27607 ph 919.314.6686
2 2 4 6 8 10
1/4" = 1'-0"
FEETSCALE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTS
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
SHEET NOTES:
SHEET OF
Facilities Management
Services
12/18/2025
A u to d e s k D o c s /A s h e v ill e E
H R
M
V
/6
-2
-7
.0
.M
.A S
H
E H
R M
.r v t
/1 /2
:3
:2
P M
47-MP403
ENLARGED MECHANICAL 2ND FLOOR
PLANSAwen Solutions Group
215 N. Payne Street, Suite 122
Alexandria, VA 22314
12.19.2025
EHRM INFRASTRUCTURE
UPGRADES BLDG 47
1100 TUNNEL ROAD
ASHEVILLE, NC 28805
637-22-700
GENERAL NOTES:
1/4" = 1'-0"
2 2E202A - MECHANICAL PLAN
1/4" = 1'-0"
3 2A246 - MECHANICAL PLAN
MOUNT UNIT ON WALL ABOVE DOOR. SEE DETAIL 7/00-M501. MAINTAIN MANUFACTURER'S MINIMUM CLEARANCES.
REFRIGERANT LINE SET UP TO CORRESPONDING ODU ON ROOF.
REFRIGERANT LINE SET FROM IDU-1B134 BELOW UP TO CORRESPONDING ODU ON ROOF.
REFRIGERANT LINE SET FROM IDU-BB018 BELOW UP TO CORRESPONDING ODU ON ROOF.
REFRIGERANT LINE SET FROM IDU-1A137 BELOW UP TO CORRESPONDING ODU ON ROOF.
REFRIGERANT LINE SET FROM IDU-1W133 BELOW UP TO CORRESPONDING ODU ON ROOF.
REFRIGERANT LINE SET FROM IDU-BC118 BELOW UP TO CORRESPONDING ODU ON ROOF.
LOCATE TEMPTRAK TEMPERATURE/HUMIDITY SENSOR ON WALL WITHIN 6 FT OF TELECOM RACK. TEMPTRAK SENSOR SHALL INTEGRATE WITH VA'S CENTRAL MONITORING SYSTEM TO ALERT WHEN ENVIRONMENTAL CONDITION REQUIREMENTS ARE NOT MET.
SEE DESIGN CONDITIONS TABLE ON SHEET 00-M001.
MOUNT UNIT ON WALL 9'-6" AFF IN LOCATION SHOWN. SEE DETAIL 7/00-M501.
1/4" = 1'-0"
1 2B212 - MECHANICAL PLAN
1. ROUTE REFRIGERANT LINES TIGHT TO UNDERSIDE OF FLOOR ABOVE.
2. SIZE REFRIGERANT LINES PER MANUFACTURER'S RECOMMENDATIONS.
3. PROVIDE FIRE-STOPPING WHERE PIPING PENETRATES FIRE-RATED WALLS. RATED WALLS ARE INDICATED ON
PLANS.
4. IT RACKS SHOWN FOR REFERENCE ONLY. DASHED LINES INDICATE PLACEHOLDER FOR FUTURE RACK, NOT IN
CONTRACT. SEE TELECOM DRAWINGS FOR MORE INFORMATION.
Revisions: Date: SHEET 369 of 559
TR (EXPANDED)
A301
T 2
S5
47-IDU-A301
TR (EXPANDED)
A401
T
S5
47-IDU-A401
TR (EXPANDED)
A501
T
S5
47-IDU-A501
PARTITION LEGEND
FIRE BARRIER, 2 HR
FIRE BARRIER, 1 HR
SMOKE BARRIER, 1/2 HR
SMOKE RESISTIVE HAZARDOUS
PATIENT SUIT/ NON SLEEPING
R
OBERT BEL L
SEAL
047145
N
O
RT
H CAROLIN
A
P R
FO
ESS ON
A L
I
N E
GINEER
PLAN
NORTH
N
FINAL BID DOCUMENTS
FOR OFFICIAL USE ONLY
www.coffman.com
701 Corporate Center Drive, Suite 475
Raleigh, NC 27607 ph 919.314.6686
2 2 4 6 8 10
1/4" = 1'-0"
FEETSCALE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTS
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
SHEET NOTES:
SHEET OF
Facilities Management
Services
12/18/2025
A u to d e s k D o c s /A s h e v ill e E
H R
M
V
/6
-2
-7
.0
.M
.A S
H
E H
R M
.r v t
/1 /2
:3
:2
P M
47-MP404
ENLARGED MECHANICAL 3RD, 4TH,
AND 5TH FLOOR PLANSAwen Solutions Group
215 N. Payne Street, Suite 122
Alexandria, VA 22314
12.19.2025
EHRM INFRASTRUCTURE
UPGRADES BLDG 47
1100 TUNNEL ROAD
ASHEVILLE, NC 28805
637-22-700
1/4" = 1'-0"
1 A301 - MECHANICAL PLAN
1/4" = 1'-0"
2 A401 - MECHANICAL PLAN
1/4" = 1'-0"
3 A501 - MECHANICAL PLAN
GENERAL NOTES:
MOUNT UNIT ON WALL ABOVE DOOR. SEE DETAIL 7/00-M501. MAINTAIN MANUFACTURER'S MINIMUM CLEARANCES.
REFRIGERANT LINE SET UP TO CORRESPONDING ODU ON ROOF.
REFRIGERANT LINE SET FROM IDU-A301 BELOW UP TO CORRESPONDING ODU ON ROOF.
REFRIGERANT LINE SET FROM IDU-A401 BELOW UP TO CORRESPONDING ODU ON ROOF.
LOCATE TEMPTRAK TEMPERATURE/HUMIDITY SENSOR ON WALL WITHIN 6 FT OF TELECOM RACK. TEMPTRAK SENSOR SHALL INTEGRATE WITH VA'S CENTRAL MONITORING SYSTEM TO ALERT WHEN ENVIRONMENTAL CONDITION REQUIREMENTS ARE NOT
MET. SEE DESIGN CONDITIONS TABLE ON SHEET 00-M0
1. ROUTE REFRIGERANT LINES TIGHT TO UNDERSIDE OF FLOOR ABOVE.
2. SIZE REFRIGERANT LINES PER MANUFACTURER'S RECOMMENDATIONS.
3. PROVIDE FIRE-STOPPING WHERE PIPING PENETRATES FIRE-RATED WALLS. RATED WALLS ARE INDICATED ON
PLANS.
4. IT RACKS SHOWN FOR REFERENCE ONLY. DASHED LINES INDICATE PLACEHOLDER FOR FUTURE RACK, NOT IN
CONTRACT. SEE TELECOM DRAWINGS FOR MORE INFORMATION.
Revisions: Date: SHEET 370 of 559
47-ODU-1B134 47-ODU-BB018 47-ODU-2B212
47-ODU-BF10747-ODU-1H113
47-ODU-2A246 47-ODU-1A137
47-ODU-2E202A 47-ODU-1W13347-ODU-BC118A
47-ODU-BC118B
47-ODU-A301 47-ODU-A401 47-ODU-A501
PARTITION LEGEND
FIRE BARRIER, 2 HR
FIRE BARRIER, 1 HR
SMOKE BARRIER, 1/2 HR
SMOKE RESISTIVE HAZARDOUS
PATIENT SUIT/ NON SLEEPING
R
OBERT BEL L
SEAL
047145
N
O
RT
H CAROLIN
A
P R
FO
ESS ON
A L
I
N E
GINEER
PLAN
NORTH
N
FINAL BID DOCUMENTS
FOR OFFICIAL USE ONLY
www.coffman.com
701 Corporate Center Drive, Suite 475
Raleigh, NC 27607 ph 919.314.6686
2 2 4 6 8 10
1/4" = 1'-0"
FEETSCALE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTS
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
SHEET NOTES:
SHEET OF
Facilities Management
Services
12/18/2025
A u to d e s k D o c s /A s h e v ill e E
H R
M
V
/6
-2
-7
.0
.M
.A S
H
E H
R M
.r v t
/1 /2
:3
:2
P M
47-MP405
ENLARGED MECHANICAL ROOF PLANS
Awen Solutions Group
215 N. Payne Street, Suite 122
Alexandria, VA 22314
12.19.2025
EHRM INFRASTRUCTURE
UPGRADES BLDG 47
1100 TUNNEL ROAD
ASHEVILLE, NC 28805
637-22-700
1/4" = 1'-0"
3 BB018, 1B134, 2B212 - MECHANICAL ROOF PLAN
GENERAL NOTES:
1/4" = 1'-0"
4 BF107, 1H113 - MECHANICAL ROOF PLAN
1/4" = 1'-0"
2 1A137, 2A246 - MECHANICAL ROOF PLAN
1/4" = 1'-0"
1 BC118, 1W133, 2E202A - MECHANICAL ROOF PLAN
1 REFRIGERANT LINE SET(S) DOWN TO CORRESPONDING IDU. UTILIZE PIPE PORTAL. SEE DETAIL 3/00-M501.
1. MOUNT CONDENSING UNITS ON ROOF CURB OR ROOF RAILS. SEE DETAIL 5/00-M501. LOCATE CONDENSING UNITS AS NEAR AS PRACTICAL TO REFRIGERANT PIPE PORTALS. MAINTAIN MANUFACTURER'S MINIMUM RECOMMENDED CLEARANCES BETWEEN CONDENSING UNITS AND BETWEEN OTHER OBSTRUCTIONS. CONDENSING UNITS SHALL NOT ADVERSELY AFFECT THE PERFORMANCE OR SERVICABILITY OF EXISTING NEARBY EQUIPMENT.
2. SIZE REFRIGERANT LINES PER MANUFACTURER'S RECOMMENDATIONS.
1/4" = 1'-0"
5 A301, A401, A501 - MECHANICAL ROOF PLAN
Revisions: Date: SHEET 371 of 559
1 2 34 5
9 10
S H T
RA
H L T
M
H T H L
SA
STARTER
M
Run Conditions - Continuous (Normal):
The unit shall run continuously at partload capacity in conjunction with the partner unit serving the same row to maintain:
• An average rack face temperature of 75°F (adj.) or below
• A maximum rack face temperature of 80°F or below
Run Conditions - Continuous (Partner Unit Failure):
The unit shall run continuously at full load capacity to compensate for partner unit failure to maintain:
• An average rack face temperature of 75°F (adj.) or below
• A maximum rack face temperature of 80°F or below
Emergency Shutdown:
The unit shall shut down and generate an alarm upon receiving an emergency shutdown signal.
Freeze Protection:
The unit shall shut down and generate an alarm upon receiving a freezestat status.
High Static Shutdown:
The unit shall shut down and generate an alarm upon receiving a high static shutdown signal.
Return Air Smoke Detection:
The unit shall shut down and generate an alarm upon receiving a return air smoke detector status.
Supply Fan:
The supply fan shall run anytime the unit is commanded to run and modulate fan speed based on necessity determined by the Vigilent control system, unless shutdown on safeties. To prevent short cycling, the supply fan shall have a user definable (adj.) minimum runtime.
Alarms shall be provided as follows:
• Supply Fan Failure: Commanded on, but the status is off.
• Supply Fan in Hand: Commanded off, but the status is on.
• Supply Fan Runtime Exceeded: Status runtime exceeds a user definable limit (adj.).
Rack Face Temperature Control:
The wireless sensors shall measure the rack face temperatures at specified points and shall use Artificial Interligence to determine what racks need cooling. The controller shall modulate the supply fan speed to maintain temperature setpoints.
The supply fan ECM shall not drop below 30% (adj.).
Compressor:
The control system shall measure the supply air temperature and modulate the compressor and supply fan to maintain its cooling setpoint.
The cooling shall be enabled whenever:
• The average or maximum rack face temperature is above the cooling setpoint.
• AND the supply fan status is on.
Dehumidification:
The wireless humidity sensors shall measure the humidity levels at various specified points and override the cooling sequence to maintain return air humidity at or below 60% rh (adj.).
Dehumidification shall be enabled whenever the supply fan status is on.
Humidifier Control:
The wireless humidity sensors shall measure the humidity levels at various specified points and modulate the humidifier to maintain a setpoint of 30% rh (adj.) or higher. The humidifier shall be enabled whenever the supply fan status is on.
The humidifier shall turn off whenever:
• Average humidity levels rise above 40% (adj.).
• OR on loss of supply fan status.
Alarms shall be provided as follows:
• High Humidity: If the average humidity levels are greater than 60% rh (adj.).
• Low Humidity: If the average humidity levels are less than 30% rh (adj.).
Prefilter Differential Pressure Monitor:
The control system shall monitor the differential pressure across the prefilter.
Alarms shall be provided as follows:
• Prefilter Change Required: Prefilter differential pressure exceeds a user definable limit (adj.).
Return Air Temperature:
The control system shall monitor the return air temperature and use as required for setpoint control or economizer control (if present).
Alarms shall be provided as follows:
• High Return Air Temp: If the return air temperature is greater than 100°F (adj.).
• Low Return Air Temp: If the return air temperature is less than 45°F (adj.).
Supply Air Temperature:
The control system shall monitor the supply air temperature.
Alarms shall be provided as follows:
• High Supply Air Temp: If the supply air temperature is greater than 80°F (adj.).
• Low Supply Air Temp: If the supply air temperature is less than 45°F (adj.).
CT
SF
DX
COMPRESSOR
VIGILENT TEMPERATURE/HUMIDITY
SENSOR NETWORK
(SEE 47-MP401 FOR LOCATIONS)
BI
LIEBERT INTERFACE CONTROL PANEL EI
AI AI AI BI AI AI AO AO BO AO AI AI BI
AI
EI
VIGILENT DDC SYSTEM CONTROL MODULE
R
OBERT BEL L
SEAL
047145
N
O
RT
H CAROLIN
A
P R
FO
ESS ON
A L
I
N E
GINEER
FINAL BID DOCUMENTS
FOR OFFICIAL USE ONLY
www.coffman.com
701 Corporate Center Drive, Suite 475
Raleigh, NC 27607 ph 919.314.6686
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTS
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
SHEET OF
Facilities Management
Services
12/18/2025
A u to d e s k D o c s /A s h e v ill e E
H R
M
V
/6
-2
-7
.0
.M
.A S
H
E H
R M
.r v t
/1 /2
:3
:3
P M
47-MG501
MECHANICAL CONTROLS DETAILS
Awen Solutions Group
215 N. Payne Street, Suite 122
Alexandria, VA 22314
12.19.2025
EHRM INFRASTRUCTURE
UPGRADES BLDG 47
1100 TUNNEL ROAD
ASHEVILLE, NC 28805
637-22-700
CRAC POINTS LIST SCHEDULE
POINT ID BMS POINT DESCRIPTION BAS TYPE
1 PREFILTER DIFFERENTIAL PRESSURE AI
2 SUPPLY AIR HUMIDITY AI
3 SUPPLY AIR TEMP AI
4 RETURN AIR HUMIDITY AI
5 RETURN AIR TEMP AI
6 HUMIDIFIER OUTPUT AO
7 SUPPLY FAN SPEED AO
8 COMPRESSOR AO
9 FREEZESTAT BI
10 HIGH STATIC SHUTDOWN BI
11 SUPPLY FAN STATUS BI
12 RETURN AIR SMOKE DETECTOR BI
13 HUMIDIFIER ENABLE BO
14 SUPPLY FAN START/STOP BO
15 RACK TEMP/HUMIDITY SENSORS AI
NTS
1 CRAC CONTROL POINT SCHEMATIC AND SEQUENCE OF OPERATIONS
Revisions: Date: SHEET 372 of 559
R
OBERT BEL L
SEAL
047145
N
O
RT
H CAROLIN
A
P R
FO
ESS ON
A L
I
N E
GINEER
FINAL BID DOCUMENTS
FOR OFFICIAL USE ONLY
www.coffman.com
701 Corporate Center Drive, Suite 475
Raleigh, NC 27607 ph 919.314.6686
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTS
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
SHEET OF
Facilities Management
Services
12/18/2025
A u to d e s k D o c s /A s h e v ill e E
H R
M
V
/6
-2
-7
.0
.M
.A S
H
E H
R M
.r v t
/1 /2
:3
:3
P M
47-MG601
MECHANICAL SCHEDULES
Awen Solutions Group
215 N. Payne Street, Suite 122
Alexandria, VA 22314
12.19.2025
EHRM INFRASTRUCTURE
UPGRADES BLDG 47
1100 TUNNEL ROAD
ASHEVILLE, NC 28805
637-22-700
DC CRAC UNIT SCHEDULE
MARK CORRESPONDING CU LOCATION
FAN COOLING ELECTRICAL BASIS OF DESIGN
REMARKSAIR FLOW ESP HP NOMINAL TONS TOTAL COOLING SENSIBLE COOLING EDB EWB LDB VOLTAGE PHASE FREQUENCY FLA MCA MOCP MAKE MODEL WEIGHT
47-CRAC-1A 47-CU-1A DATA CENTER 3500 CFM 0.2 in-wg 4.2 hp 7.1 ton 85,400 Btu/h 85,400 Btu/h 85 °F 64 °F 55 °F 460 V 3 60 Hz 32.5 A 39.6 A 50 A LIEBERT PX023 670 lb ALL
47-CRAC-1B 47-CU-1B DATA CENTER 3500 CFM 0.2 in-wg 4.2 hp 7.1 ton 85,400 Btu/h 85,400 Btu/h 85 °F 64 °F 55 °F 460 V 3 60 Hz 32.5 A 39.6 A 50 A LIEBERT PX023 670 lb ALL
47-CRAC-2A 47-CU-2A DATA CENTER 13700 CFM 0.2 in-wg 3.6 hp 30.0 ton 360,000 Btu/h 344,000 Btu/h 85 °F 64 °F 55 °F 460 V 3 60 Hz 83.7 A 97.4 A 110 A LIEBERT DS105 2780 lb ALL
47-CRAC-2B 47-CU-2B DATA CENTER 13700 CFM 0.2 in-wg 3.6 hp 30.0 ton 360,000 Btu/h 344,000 Btu/h 85 °F 64 °F 55 °F 460 V 3 60 Hz 83.7 A 97.4 A 110 A LIEBERT DS105 2780 lb ALL
MINI-SPLIT INDOOR UNIT SCHEDULE
MARK CORRESPONDING ODU LOCATION
MAX SUPPLY AIR
FLOW
OUTSIDE AIR
FLOW
COOLING HEATING ELECTRICAL BASIS OF DESIGN
REMARKSEDB EWB LDB EDB LDB VOLTAGE PHASE FREQUENCY FLA MCA MAKE MODEL WEIGHT
47-IDU-A301 47-ODU-A301 BLDG 47 A301 1000 CFM 0 CFM 80 °F 62.5 °F 56 °F - - 208 V 1 60 Hz 3.00 A 4.0 A VERTIV WLM070A 120 lb 4-6,11
47-IDU-A401 47-ODU-A401 BLDG 47 A401 1000 CFM 0 CFM 80 °F 62.5 °F 56 °F - - 208 V 1 60 Hz 3.00 A 4.0 A VERTIV WLM070A 120 lb 1,4-6,11
47-IDU-A501 47-ODU-A501 BLDG 47 A501 1000 CFM 0 CFM 80 °F 62.5 °F 56 °F - - 208 V 1 60 Hz 3.00 A 4.0 A VERTIV WLM070A 120 lb 1,4-6,11
47-IDU-BB018 47-ODU-BB018 BLDG 47 BB018 1000 CFM 0 CFM 80 °F 62.5 °F 56 °F - - 208 V 1 60 Hz 3.00 A 4.0 A VERTIV WLM070A 120 lb 1,4-6,11
47-IDU-BC118A 47-ODU-BC118-A BLDG 47 BC118 616 CFM 0 CFM 80 °F 62.5 °F 58 °F - - 208 V 1 60 Hz 2.00 A 3.0 A VERTIV WLM030A 92 lb 1,5-7,11
47-IDU-BC118B 47-ODU-BC118-B BLDG 47 BC118 616 CFM 0 CFM 80 °F 62.5 °F 58 °F - - 208 V 1 60 Hz 2.00 A 3.0 A VERTIV WLM030A 92 lb 1,5-7,11
47-IDU-BC131A 47-ODU-BC131A BLDG 47 BC131 616 CFM 0 CFM 80 °F 62.5 °F 58 °F - - 208 V 1 60 Hz 2.00 A 3.0 A VERTIV WLM030A 92 lb 1,5-7,11
47-IDU-BC131B 47-ODU-BC131B BLDG 47 BC131 616 CFM 0 CFM 80 °F 62.5 °F 58 °F - - 208 V 1 60 Hz 2.00 A 3.0 A VERTIV WLM030A 92 lb 1,5-7,11
47-IDU-BC143A 47-ODU-BC143A BLDG 47 BC143 616 CFM 0 CFM 80 °F 62.5 °F 58 °F - - 208 V 1 60 Hz 2.00 A 3.0 A VERTIV WLM030A 92 lb 1,5-7,11
47-IDU-BC143B 47-ODU-BC143B BLDG 47 BC143 616 CFM 0 CFM 80 °F 62.5 °F 58 °F - - 208 V 1 60 Hz 2.00 A 3.0 A VERTIV WLM030A 92 lb 1,5-7,11
47-IDU-BC143C 47-ODU-BC143C BLDG 47 BC143 1253 CFM 55 CFM 80 °F 67.0 °F 55 °F 70 °F 90 °F 208 V 1 60 Hz 0.56 A 1.6 A DAIKIN FCA36AAVJU 58 lb 2-4,8-9
47-IDU-BF107 47-ODU-BF107 BLDG 47 BF107 1000 CFM 0 CFM 80 °F 62.5 °F 56 °F - - 208 V 1 60 Hz 3.00 A 4.0 A VERTIV WLM070A 120 lb 1,4-6,11
47-IDU-1A137 47-ODU-1A137 BLDG 47 1A137 1000 CFM 0 CFM 80 °F 62.5 °F 56 °F - - 208 V 1 60 Hz 3.00 A 4.0 A VERTIV WLM070A 120 lb 1,4-6,11
47-IDU-1B134 47-ODU-1B134 BLDG 47 1B134 1000 CFM 0 CFM 80 °F 62.5 °F 56 °F - - 208 V 1 60 Hz 3.00 A 4.0 A VERTIV WLM070A 120 lb 4-6,11
47-IDU-1D144A 47-ODU-1D144 BLDG 47 1D144 1000 CFM 0 CFM 80 °F 62.5 °F 56 °F - - 208 V 1 60 Hz 3.00 A 4.0 A VERTIV WLM070A 120 lb 1,4-6,11
47-IDU-1H113 47-ODU-1H113 BLDG 47 1H113 1000 CFM 0 CFM 80 °F 62.5 °F 56 °F - - 208 V 1 60 Hz 3.00 A 4.0 A VERTIV WLM070A 120 lb 1,4-6,11
47-IDU-1W133 47-ODU-1W133 BLDG 47 1W133 1000 CFM 0 CFM 80 °F 62.5 °F 56 °F - - 208 V 1 60 Hz 3.00 A 4.0 A VERTIV WLM070A 120 lb 1,4-6,11
47-IDU-2A246 47-ODU-2A246 BLDG 47 2A246 1000 CFM 0 CFM 80 °F 62.5 °F 56 °F - - 208 V 1 60 Hz 3.00 A 4.0 A VERTIV WLM070A 120 lb 4-6,10-11
47-IDU-2B212 47-ODU-2B212 BLDG 47 2B212 1000 CFM 0 CFM 80 °F 62.5 °F 56 °F - - 208 V 1 60 Hz 3.00 A 4.0 A VERTIV WLM070A 120 lb 1,4-6,11
47-IDU-2E202A 47-ODU-2E202A BLDG 47 2E202A 1000 CFM 0 CFM 80 °F 62.5 °F 56 °F - - 208 V 1 60 Hz 3.00 A 4.0 A VERTIV WLM070A 120 lb 1,4-6,11
MINI-SPLIT OUTDOOR UNIT SCHEDULE
MARK CORRESPONDING IDU LOCATION REFRIGERANT
COOLING HEATING ELECTRICAL BASIS OF DESIGN
REMARKS
NOMINAL
CAPACITY TOTAL COOLING SENSIBLE COOLING NSCOP EER2 SEER2 TOTAL HEATING HSPF2 VOLTAGE PHASE FREQUENCY FLA MCA MAKE MODEL WEIGHT
47-ODU-A301 47-IDU-A301 ROOF R32 7.0 kW 25,468 Btu/h 25,468 Btu/h 4.08 - - 0 Btu/h - 208 V 1 60 Hz 26 A 32.0 A VERTIV CUD070 118 lb 1-2,4-8
47-ODU-A401 47-IDU-A401 ROOF R32 7.0 kW 25,468 Btu/h 25,468 Btu/h 4.08 - - 0 Btu/h - 208 V 1 60 Hz 26 A 32.0 A VERTIV CUD070 118 lb 1-2,4-8
47-ODU-A501 47-IDU-A501 ROOF R32 7.0 kW 25,468 Btu/h 25,468 Btu/h 4.08 - - 0 Btu/h - 208 V 1 60 Hz 26 A 32.0 A VERTIV CUD070 118 lb 1-2,4-8
47-ODU-BB018 47-IDU-BB018 ROOF R32 7.0 kW 25,468 Btu/h 25,468 Btu/h 4.08 - - 0 Btu/h - 208 V 1 60 Hz 26 A 32.0 A VERTIV CUD070 118 lb 1-2,4-8
47-ODU-BC118A 47-IDU-BC118A ROOF R32 7.0 kW 25,468 Btu/h 25,468 Btu/h 4.08 - - 0 Btu/h - 2080 V 1 60 Hz 26 A 32.0 A VERTIV CUD070 118 lb 1-2,4-8
47-ODU-BC118B 47-IDU-BC118B ROOF R32 7.0 kW 25,468 Btu/h 25,468 Btu/h 4.08 - - 0 Btu/h - 2080 V 1 60 Hz 26 A 32.0 A VERTIV CUD070 118 lb 1-2,4-8
47-ODU-BC131A 47-IDU-BC131A BLDG 47 OUTSIDE R32 3.7 kW 14,202 Btu/h 14,202 Btu/h 3.63 - - 0 Btu/h - 208 V 1 60 Hz 19 A 24.0 A VERTIV CUD030 110 lb 1,3-8
47-ODU-BC131B 47-IDU-BC131B BLDG 47 OUTSIDE R32 3.7 kW 14,202 Btu/h 14,202 Btu/h 3.63 - - 0 Btu/h - 208 V 1 60 Hz 19 A 24.0 A VERTIV CUD030 110 lb 1,3-8
47-ODU-BC143A 47-IDU-BC143A BLDG 47 OUTSIDE R32 7.0 kW 25,468 Btu/h 25,468 Btu/h 4.08 - - 0 Btu/h - 208 V 1 60 Hz 26 A 32.0 A VERTIV CUD070 118 lb 1,3-8
47-ODU-BC143B 47-IDU-BC143B BLDG 47 OUTSIDE R32 7.0 kW 25,468 Btu/h 25,468 Btu/h 4.08 - - 0 Btu/h - 208 V 1 60 Hz 26 A 32.0 A VERTIV CUD070 118 lb 1,3-8
47-ODU-BC143C 47-IDU-BC143C SITE R32 10.6 kW 36,000 Btu/h 28,300 Btu/h - 12.2 20 40,000 Btu/h 10 208 V 1 60 Hz 26 A 34.6 A DAIKIN RZA36AAVJU 234 lb 1,3
47-ODU-BF107 47-IDU-BF107 ROOF R32 7.0 kW 25,468 Btu/h 25,468 Btu/h 4.08 - - 0 Btu/h - 208 V 1 60 Hz 26 A 32.0 A VERTIV CUD070 118 lb 1-2,4-8
47-ODU-1A137 47-IDU-1A37 ROOF R32 7.0 kW 25,468 Btu/h 25,468 Btu/h 4.08 - - 0 Btu/h - 208 V 1 60 Hz 26 A 32.0 A VERTIV CUD070 118 lb 1-2,4-8
47-ODU-1B134 47-1DU-1B134 ROOF R32 7.0 kW 25,468 Btu/h 25,468 Btu/h 4.08 - - 0 Btu/h - 208 V 1 60 Hz 26 A 32.0 A VERTIV CUD070 118 lb 1-2,4-8
47-ODU-1D144 47-IDU-1D144A SITE - PLAN NORTH R32 7.0 kW 25,468 Btu/h 25,468 Btu/h 4.08 - - 0 Btu/h - 208 V 1 60 Hz 26 A 32.0 A VERTIV CUD070 118 lb 1,3-8
47-ODU-1H113 47-IDU-1H113 ROOF R32 7.0 kW 25,468 Btu/h 25,468 Btu/h 4.08 - - 0 Btu/h - 208 V 1 60 Hz 26 A 32.0 A VERTIV CUD070 118 lb 1-2,4-8
47-ODU-1W133 47-IDU-1W133 ROOF R32 7.0 kW 25,468 Btu/h 25,468 Btu/h 4.08 - - 0 Btu/h - 208 V 1 60 Hz 26 A 32.0 A VERTIV CUD070 118 lb 1-2,4-8
47-ODU-2A246 47-IDU-2A246 ROOF R32 7.0 kW 25,468 Btu/h 25,468 Btu/h 4.08 - - 0 Btu/h - 208 V 1 60 Hz 26 A 32.0 A VERTIV CUD070 118 lb 1-2,4-8
47-ODU-2B212 47-IDU-2B212 ROOF R32 7.0 kW 25,468 Btu/h 25,468 Btu/h 4.08 - - 0 Btu/h - 208 V 1 60 Hz 26 A 32.0 A VERTIV CUD070 118 lb 1-2,4-8
47-ODU-2E202A 47-IDU-2E202A ROOF R32 7.0 kW 25,468 Btu/h 25,468 Btu/h 4.08 - - 0 Btu/h - 208 V 1 60 Hz 26 A 32.0 A VERTIV CUD070 118 lb 1-2,4-8
NOTES:
1. PROVIDE WITH BLUE DIAMOND MAXIBLUE (X87-721) OR EQUAL CONDENSATE PUMP. COORDINATE WITH ELECTRICAL CONTRACTOR FOR POWER. PROVIDE DRIP PAN WITH MOISTURE SENSOR TO GENERATE AN ALARM TO THE BAS IN THE EVENT OF PRIMARY DRAIN
OVERFLOW.
2. MOUNT IN LAY-IN CEILING AND SUSPEND FROM STRUCTURE ABOVE.
3. PROVIDE WITH MANUFACTURER'S INTEGRAL AIR FILTER.
4. PROVIDE WITH MANUFACTURER'S THERMOSTAT. UNIT TO RUN ON INTERNAL CONTROL LOGIC.
5. INDOOR UNIT POWERED BY OUTDOOR UNIT. ROUTE CONTROL AND POWER WIRING WITH REFRIGERANT LINESET.
6. PROVIDE ONE (1) TEMPTRAK TEMPERATURE/HUMIDITY SENSOR PER TELECOM ROOM TO INTEGRATE WITH VA'S CENTRAL MONITORING SYSTEM TO ALERT WHEN ENVIRONMENTAL CONDITION REQUIREMENTS ARE NOT MET. SEE DESIGN CONDITIONS TABLE ON SHEET 00-
M001.
7. PROVIDE ONE (1) CONTROLLER PER TELECOM ROOM TO CONTROL BOTH INDOOR UNITS.
8. WITH INTEGRAL CONDENSATE LIFT KIT (POWERED BY UNIT). PROVIDE AUXILIARY CONDENSATE PAN WITH FLOAT SWITCH TO SHUT DOWN UNIT AND MOISTURE SENSOR TO GENERATE AN ALARM TO THE BAS IN THE EVENT OF PRIMARY DRAIN PAN OVERFLOW.
9. INDOOR UNIT POWERED FROM ELECTRICAL PANEL. COORDINATE WITH ELECTRICAL CONTRACTOR.
10. PROVIDE WITH BLUE DIAMOND MEGABLUE (X87-835) OR EQUAL CONDENSATE PUMP. COORDINATE WITH ELECTRICAL CONTRACTOR FOR POWER. PROVIDE DRIP PAN WITH MOISTURE SENSOR TO GENERATE AN ALARM TO THE BAS IN THE EVENT OF PRIMARY DRAIN
OVERFLOW
11. ECM FAN.
NOTES:
1. PROVIDE WITH MANUFACTURER'S WIND BAFFLES.
2. PROVIDE WITH MANUFACTURER'S ROOF CURB.
3. PROVIDE WITH MANUFACTURER'S MOUNTING PAD IF EXISTING MOUNTING PAD CANNOT BE REUSED.
4. INDOOR UNIT POWERED BY OUTDOOR UNIT, ROUTE CONTROL AND POWER WIRING WITH REFRIGERANT LINESET.
5. SHALL BE CAPABLE OF OPERATING DOWN TO 0°F OUTDOOR AMBIENT TEMPERATURE.
6. VARIABLE SPEED COMPRESSOR.
7. REFRIGERNAT LINE LENGTH UP TO 197 FT.
8. ECM FAN.
DC CONDENSING UNIT SCHEDULE
MARK CORRESPONDING CRAC LOCATION
ELECTRICAL BASIS OF DESIGN
REMARKSVOLTAGE PHASE FREQUENCY FLA MCA MOCP MAKE MODEL WEIGHT
47-CU-1A 47-CRAC-1A BLDG 47 OUTSIDE 460 V 3 60 Hz 1.40 A 1.80 A 15 A LIEBERT MCM040E1 468 lb 1
47-CU-1B 47-CRAC-1B BLDG 47 OUTSIDE 460 V 3 60 Hz 1.40 A 1.80 A 15 A LIEBERT MCM040E1 468 lb 1
47-CU-2A 47-CRAC-2A BLDG 47 OUTSIDE 460 V 3 60 Hz 5.60 A 6.30 A 15 A LIEBERT MCL110E8 631 lb 1
47-CU-2B 47-CRAC-2B BLDG 47 OUTSIDE 460 V 3 60 Hz 5.60 A 6.30 A 15 A LIEBERT MCL110E8 631 lb 1
NOTES:
1. PROVIDE WITH MANUFACTURER'S INTEGRAL CONDENSATE PUMP.
2. PROVIDE WITH ETHERNET CONNECTION TO TIE INTO VIGILENT SYSTEM.
3. MOUNT ON HOUSEKEEPING PAD. ENSURE HOUSEKEEPING PAD IS 6" LONGER THAN THE UNIT ON ALL SIDES.
4…
This is the start of the file's text. The full file is on GovTribe.