Attachment 3 - Drawings Volume II.pdf
PDF 21 MB Posted
- Solicitation number
- 36C77626R0066
About this file
This file contains architectural and engineering drawings for the EHRM Infrastructure Upgrades project at Charles George VA Medical Center in Asheville, NC (Project 637-22-700). The drawing package covers Buildings 3, 4, and 5, with detailed plans for structural, electrical, telecommunications, and physical security systems.
The drawings specify comprehensive infrastructure work including electrical panel upgrades with new 30-ampere L5-30R twist-locking receptacles in wall-mounted telecommunications enclosures on first and second floors; Cat6A cabling replacements throughout all three buildings with new fiber optic backbone infrastructure (144-strand fiber optic patch panels with LC connectors); 12-unit wall-mounted cabinets with UPS and PDU equipment; and bonding and grounding systems compliant with TIA-607 standards. Telecommunications work includes demolition of existing Cat6 and below cabling, wall-mounted fiber boxes, and non-compliant patch panels, with installation of new fiber distribution from Building 47 data center cores to each building's telecommunications enclosures. Electrical scope includes load calculations for new telecommunications equipment (5,760 VA per building), new circuit breakers in existing panels (Panels 3A, 3B, 4A, 4B, 5A, 5B), and coordination with existing 225-ampere disconnects and building transformers. Physical security additions require new camera installations (360-degree ceiling-mounted with supplemental IR), access control card readers, motion detectors, and door position switches coordinated with Johnson Controls base building systems. All work requires field verification of existing conditions, asbestos abatement as necessary per specifications, coordination with VA operations, and compliance with fire/smoke wall ratings.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet List
Sheet Number Sheet Name
BLDG 3
03-GI001 COVER SHEET
03-SF101 STRUCTURAL 1ST & 2ND FLOOR PLAN
03-AE101 1ST & 2ND FLOOR PLANS, ENLARGED PLANS AND ELEVATIONS
03-ED100 ELECTRICAL BASEMENT DEMOLITION
03-ED101 ELECTRICAL 1ST & 2ND FLOOR DEMOLITION
03-EP100 ELECTRICAL BASEMENT PLAN
03-EP101 ELECTRICAL 1ST & 2ND FLOOR PLAN
03-EP601 ONE-LINE DIAGRAM AND SCHEDULES
03-TD100 TELECOMMUNICATIONS BASEMENT DEMOLITION
03-TD101 TELECOMMUNICATIONS 1ST & 2ND FLOOR DEMOLITION
03-TD601 TELECOMMUNICATIONS DEMOLITION RACK ELEVATIONS
03-TN100 TELECOMMUNICATIONS BASEMENT PLAN
03-TN101 TELECOMMUNICATIONS 1ST & 2ND FLOOR PLAN
03-TN601 TELECOMMUNICATIONS DIAGRAMS
03-TY102 1ST & 2ND FLOOR SECURITY PLANS
Grand total: 15
SITE KEY PLAN
TUNNELL ROAD
R
IC
E V
IL
L E
R O
A D
V E
T E
R A
N S
D R
IV
E
ARNOLD ROAD
A R
N O
L D
R O
A D
FINAL BID DOCUMENTS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTS
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
DESIGN TEAM
OWNER
ARCHITECT / CONTRACT PRIME
MECHANICAL / ELECTRICAL /
PLUMBING / FIRE PROTECTION /
STRUCTURAL ENGINEER
Charles George VA Medical Center 1100 Tunnel Road Asheville, NC 28805 Contact: Daniel Chaparro Office: (916) 843-7187 Cell: (916) 542-3038
Awen Solutions Group 215 N. Payne Street, Suite 122 Alexandria, VA 22314 Contact: Amy Carr acarr@awensolutions.com
(720) 703-0640
Coffman Engineers, Inc.
701 Corporate Center Drive, Suite 475 Raleigh, NC 27607 Contact: Lars Iverson lars.iverson@coffman.com
(919) 670-3668
EHRM INFRASTRUCTURE UPGRADES
FINAL BID DOCUMENTS
FOR OFFICIAL USE ONLY
Facilities Management
Services
A u to d e s k D o c s /A s h e v ill e E
H R
M
V
/6
-2
-7
.0
.A .A
S H
E
H R
M .r v t
/1 /2
:4
:0
A
M
03-GI001
COVER SHEET
Awen Solutions Group
215 N. Payne Street, Suite 122
Alexandria, VA 22314
12.19.2025
EHRM INFRASTRUCTURE
UPGRADES 3
1100 TUNNEL ROAD
ASHEVILLE, NC 28805
637-22-700
CHARLES GEORGE VA MEDICAL CENTER
12.19.2025
1100 TUNNEL ROAD ASHEVILLE, NC 28805
BLDG 3
Revisions: Date:
SHEET 65 of 559
UP
OFFICE
OFFICE
OFFICE
HALL
ENTRY
OFFICE
OFFICE
OFFICE
OFFICE TOILET TOILET
CLOSET
OFFICE
OFFICEOFFICE OFFICE OFFICE
HALL
CLOSET
GENERAL NOTES:
(N) WALL MOUNTED TELECOM ENCLOSURE. PROVIDE BACKING PER DETAIL
WALL MOUNT ENCLOSURE TO BACKING PER MANUFACTURER'S
INSTALLATION INSTRUCTIONS.
00-S503
1. FIRE/SMOKE WALL RECORD DRAWINGS WERE NOT PROVIDED BY THE STATION. FIELD-VERIFY
EXISTING PARTITION WALLS TO IDENTIFY FIRE/SMOKE RATING AND PROVIDE ALL REQUIRED
MEASURES AND APPROPRIATE EQUIPMENT IN ACCORDANCE WITH THE VERIFIED PARTITION TYPE.
PLAN
NORTH
N
FINAL BID DOCUMENTS
FOR OFFICIAL USE ONLY
www.coffman.com
701 Corporate Center Drive, Suite 475
Raleigh, NC 27607 ph 919.314.6686
2 2 4 6 8 10
1/4" = 1'-0"
FEETSCALE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTS
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
SHEET NOTES:
03/04/24
Facilities Management
Services
A u to d e s k D o c s /A s h e v ill e E
H R
M
V
/6
-2
-7
.0
.S .A
S H
E
H R
M .r v t
/1 /2
:1
:1
P M
03-SF101
STRUCTURAL 1ST & 2ND FLOOR PLAN
Awen Solutions Group
215 N. Payne Street, Suite 122
Alexandria, VA 22314
12.19.2025
EHRM INFRASTRUCTURE
UPGRADES BLDG 3
1100 TUNNEL ROAD
ASHEVILLE, NC 28805
637-22-700
1/4" = 1'-0"
1 STRUCTURAL 1ST FLOOR PLAN
1/4" = 1'-0"
2 STRUCTURAL 2ND FLOOR PLAN
DU MBHRevisions: Date:
12.12.2025
11 12/19/2025 SHEET 66 of 559
03-AE101
OFFICE
OFFICE
OFFICE
HALL
ENTRY
OFFICE
OFFICE
OFFICE
03-AE101
OFFICE TOILET TOILET
CLOSET
OFFICE
OFFICEOFFICE OFFICE OFFICE
HALL
CLOSET
T01
T02A03
54 TOTAL WAOS/48 (MAX. WAO PER TE)
= 1.125 TE'S REQUIRED IN BLDG 3 (2 TE'S
PROVIDED). (1) HALF-HEIGHT (12 RU) TE
BEING PROVIDED PER FLOOR
03-AE101
OFFICE
D01
T02 A03
T01
54 TOTAL WAOS/48
(MAX. WAO PER TE) =
1.125 TE'S REQUIRED IN
BLDG 3 (2 TE'S
PROVIDED). (1) HALF-
HEIGHT (12 RU) TE
BEING PROVIDED PER
FLOOR
03-AE101
OFFICE
D01
D01
T02
A03
T01
1. COORDINATE WITH FIRE PROTECTION, MECHANICAL, ELECTRICAL, PLUMBING,
TELECOMMUNICATIONS, AND SECURITY PLANS FOR ADDITIONAL
REQUIREMENTS NOT SHOWN ON THIS DRAWING.
2. DIMENSIONS PRECEDED BY A TILDE (~) ARE APPROXIMATE, SUBJECT TO FIELD
VERIFICATION.
3. ASBESTOS-CONTAINING PIPE INSULATION AND FITTINGS MAY BE FOUND IN
PIPE CHASES, WALLS AND OTHER HIDDEN AREAS THROUGHOUT THE
BUILDING. IF THESE MATERIALS HAVE TO BE DISTURBED DURING THE
PROJECT, ABATEMENT MUST BE CONDUCTED PER SPECIFICATION 02 82 11.
4. ASPHALT ROOFING MATERIALS SHOULD BE ASSUMED TO CONTAIN ASBESTOS.
IF THESE MATERIALS HAVE TO BE DISTURBED DURING THE PROJECT,
ABATEMENT MUST BE CONDUCTED PER SPECIFICATION 02 82 13.21.
5. FIRE/SMOKE WALL RECORD DRAWINGS WERE NOT PROVIDED BY THE STATION.
FIELD-VERIFY EXISTING PARTITION WALLS TO IDENTIFY FIRE/SMOKE RATING
AND PROVIDE ALL REQUIRED MEASURES AND APPROPRIATE EQUIPMENT IN
ACCORDANCE WITH THE VERIFIED PARTITION TYPE.
T02
A03
T01
PLASTIC SHEETING (VISQUEEN)
DEMOLITION LEGEND
WALK-OFF MATS
FINAL BID DOCUMENTS
PLAN
NORTH
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
OVERALL PLAN SHEET NOTES
TR LEGEND
TR TO BE DECOMMISSIONED
EXISTING TR
NEW TR
EXPANDED TR
NEW DATA CENTER
NEW TELECOM ENCLOSURE (TE)
EXISTING DATA CENTER
ENTRANCE ROOM
FINAL BID DOCUMENTS
FOR OFFICIAL USE ONLY
Facilities Management
Services
A u to d e s k D o c s /A s h e v ill e E
H R
M
V
/6
-2
-7
.0
.A .A
S H
E
H R
M .r v t
/1 /2
:4
:1
A
M
03-AE101
1ST & 2ND FLOOR PLANS, ENLARGED
PLANS AND ELEVATIONSAwen Solutions Group
215 N. Payne Street, Suite 122
Alexandria, VA 22314
12.19.2025
EHRM INFRASTRUCTURE
UPGRADES 3
1100 TUNNEL ROAD
ASHEVILLE, NC 28805
637-22-700
1/4" = 1'-0"
1 OVERALL FLOOR PLAN - 1ST FLOOR
1/4" = 1'-0"
2 OVERALL FLOOR PLAN - 2ND FLOOR
KEY TAG DESCRIPTION
A03 4'-0" x 8'-0" AC GRADE 3/4" TRADE SIZE FIRE RATED PLYWOOD BACKBOARD
PAINTED HIGH-GLASS WHITE WITH TWO COATS OF FIRE RESISTANT PAINT
D01 PROVIDE WALK OFF MATS AND PLASTIC SHEETING (VISQUEEN) AT
CONSTRUCTION AREAS.
T01 NEW TELECOMMUNICATIONS ENCLOSURE (TE), SEE
TELECOMMUNICATION DRAWINGS
T02 BONDING BUS BAR (SBB), SEE TELECOMMUNICATIONS DRAWINGS
ENLARGED PLAN KEYNOTES
3/4" = 1'-0"
3 ENLARGED PLAN - 1ST FLOOR (TE)
3/4" = 1'-0"
4 ENLARGED PLAN - 2ND FLOOR (TE)
3/8" = 1'-0"
6 2ND FL TE ELEV.
2 2 4 6 8 10
1/4" = 1'-0"
FEETSCALE
1 1 2 3 4 5 6 7
3/8" = 1'-0"
FEETSCALE
3/8" = 1'-0"
5 1ST FL TE ELEV.
1 1 2 3
3/4" = 1'-0"
FEETSCALE
IF ASBESTO-CONTAINING MATERIAL HAS TO BE DISTURBED DURING THE PROJECT, ABATERMENT MUST BE CONDUCTED PER SPECIFICATION 02 81 11. REFER TO ASBESTOS RE-INSPECTION REPORT FOR MORE DETAILED INFORMATION.
ABATEMENT QUANTITY SCHEDULE - BLDG. 3
LOCATION MATERIAL DISCRIPTION QUANTITY
CRAWLSPACE/
FLOOR/ WALL/
CEILING CHASES
ASBESTOS-CONTAINING PIPE INSULATION AND FITTINGS MAY BE FOUND ON
STEAM LINE INSULATION AND HERD ELBOWS & FITTINGS ON STEAM LINES.
AS REQUIRED BASED ON FIELD
CONDITIONS WITHIN THE WORK
AREA
ROOF
ASBESTOS-CONTAINING ASHPHALT SHINGLES, FELT, AND MASTICS MAY BE
FOUND IN ROOF ASSEMBLY.
AS REQUIRED BASED ON FIELD
CONDITIONS WITHIN THE WORK
AREA
SHEET 67 of 559
J INZ E CHEN
SEAL
040390
N
O
RT
H CAROLIN
A
P R
FO
ESS ON
A L
I
N E
GINEER
(E) 3A
(E) 3B
PLAN
NORTH
N
FOR OFFICIAL USE ONLY
www.coffman.com
701 Corporate Center Drive, Suite 475
Raleigh, NC 27607 ph 919.314.6686
2 2 4 6 8 10
1/4" = 1'-0"
FEETSCALE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTSFacilities Management
Services
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
SHEET NOTES:
12/18/2025
A u to d e s k D o c s /A s h e v ill e E
H R
M
V
/6
-2
-7
.0
.E .A
S H
E
H R
M .r v t
/1 /2
:1
:0
P M
03-ED100
ELECTRICAL BASEMENT DEMOLITION
Awen Solutions Group
215 N. Payne Street, Suite 122
Alexandria, VA 22314
12.19.2025
EHRM INFRASTRUCTURE
UPGRADES BLDG 3
1100 TUNNEL ROAD
ASHEVILLE, NC 28805
637-22-700
1/4" = 1'-0"
1 ELECTRICAL BASEMENT DEMOLITION
GENERAL NOTES:
CONTRACTOR SHALL COORDINATE WITH TELECOM AND FIELD-VERIFY LOCATION OF EXISTING BASEMENT TELECOM ENCLOSURE AND ASSOCIATED ELECTRICAL INFRASTRUCTURE. DEMOLISH EXISTING DUPLEX RECEPTACLE LOCATED NEAR OR INSIDE EXISTING BASEMENT TELECOM ENCLOSURE. DEMOLISH CIRCUIT AND ALL ASSOCIATED HARDWARE BACK TO SOURCE.
1. REFER TO 00-E001 FOR GENERAL NOTES, DEMOLITION NOTES, AND LEGENDS.
2. DEMOLITION PLANS ARE CONCEPTUAL, NOT ALL DEVICES TO BE DEMOLISHED ARE SHOWN. BASEMENT EQUIPMENT LAYOUT IS
SHOWN BASED ON BEST AVAILABLE INFORMATION.
3. ELECTRICAL PANEL LOCATIONS SHOWN FOR REFERENCE ONLY. ALL PANELS ARE EXISTING TO REMAIN.
Revisions: Date: SHEET 68 of 559
040390
N
O
RT
H CAROLIN
A
P R
FO
ESS ON
A L
I
N E
GINEER
OFFICE
OFFICE
OFFICE
HALL ENTRY
OFFICE
OFFICE
OFFICE
OFFICE
CLOSET
TOILET
TOILET
CLOSET
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
HALL
PLAN
NORTH
N
FOR OFFICIAL USE ONLY
www.coffman.com
701 Corporate Center Drive, Suite 475
Raleigh, NC 27607 ph 919.314.6686
2 2 4 6 8 10
1/4" = 1'-0"
FEETSCALE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTSFacilities Management
Services
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
SHEET NOTES:
12/18/2025
A u to d e s k D o c s /A s h e v ill e E
H R
M
V
/6
-2
-7
.0
.E .A
S H
E
H R
M .r v t
/1 /2
:1
:0
P M
03-ED101
ELECTRICAL 1ST & 2ND FLOOR
DEMOLITIONAwen Solutions Group
215 N. Payne Street, Suite 122
Alexandria, VA 22314
12.19.2025
EHRM INFRASTRUCTURE
UPGRADES BLDG 3
1100 TUNNEL ROAD
ASHEVILLE, NC 28805
637-22-700
1/4" = 1'-0"
1 ELECTRICAL 1ST FLOOR DEMOLITION
1/4" = 1'-0"
2 ELECTRICAL 2ND FLOOR DEMOLITION
GENERAL NOTES:
1. REFER TO 00-E001 FOR GENERAL NOTES, DEMOLITION NOTES, AND LEGENDS.
2. ELECTRICAL PANEL LOCATIONS SHOWN FOR REFERENCE ONLY. ALL PANELS ARE EXISTING TO REMAIN.
LOCATION OF NEW TELECOM ENCLOSURE TO BE INSTALLED UNDER THIS PROJECT. ENSURE WALL IS CLEAR OF ANY OBSTRUCTING ELECTRICAL EQUIPMENT, SUCH AS RECEPTACLES, SWITCHES, ETC. COORDINATE WITH VA COR TO REMOVE OR
RELOCATE ANY DEVICES AS NECESSARY.
Revisions: Date: SHEET 69 of 559
040390
N
O
RT
H CAROLIN
A
P R
FO
ESS ON
A L
I
N E
GINEER
(E) 3B
(E) 3A
PLAN
NORTH
N
FOR OFFICIAL USE ONLY
www.coffman.com
701 Corporate Center Drive, Suite 475
Raleigh, NC 27607 ph 919.314.6686
2 2 4 6 8 10
1/4" = 1'-0"
FEETSCALE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTSFacilities Management
Services
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
SHEET NOTES:
12/18/2025
A u to d e s k D o c s /A s h e v ill e E
H R
M
V
/6
-2
-7
.0
.E .A
S H
E
H R
M .r v t
/1 /2
:1
:0
P M
03-EP100
ELECTRICAL BASEMENT PLAN
Awen Solutions Group
215 N. Payne Street, Suite 122
Alexandria, VA 22314
12.19.2025
EHRM INFRASTRUCTURE
UPGRADES BLDG 3
1100 TUNNEL ROAD
ASHEVILLE, NC 28805
637-22-700
1/4" = 1'-0"
1 ELECTRICAL BASEMENT PLAN
GENERAL NOTES:
1. FIRE/SMOKE WALL RECORD DRAWINGS WERE NOT PROVIDED BY THE STATION. FIELD-VERIFY EXISTING PARTITION WALLS TO IDENTIFY FIRE/SMOKE RATING AND PROVIDE ALL REQUIRED MEASURES AND APPROPRIATE EQUIPMENT IN ACCORDANCE WITH
THE VERIFIED PARTITION TYPE.
2. REFER TO 00-E001 FOR GENERAL NOTES AND LEGENDS.
3. NO NEW ELECTRICAL SCOPE IN BASEMENT, PLAN SHOWN FOR REFERENCE ONLY.
4. ELECTRICAL PANEL LOCATIONS SHOWN FOR REFERENCE ONLY. ALL PANELS ARE EXISTING TO REMAIN.
Revisions: Date: SHEET 70 of 559
040390
N
O
RT
H CAROLIN
A
P R
FO
ESS ON
A L
I
N E
GINEER
L5-30R L5-30R
(E) 3A: 39
(E) 3B: 41
(E) 3B: 35
PBB
(E) 3B: 35
OFFICE
OFFICE
OFFICE
HALL ENTRY
OFFICE
OFFICE
OFFICE
1 L5-30R L5-30R
(E) 3A: 41 (E) 3B: 39
(E) 3B: 37
(E) 3B: 37
2SBB
OFFICE
CLOSET
TOILET
TOILET
CLOSET
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
HALL
PLAN
NORTH
N
FOR OFFICIAL USE ONLY
www.coffman.com
701 Corporate Center Drive, Suite 475
Raleigh, NC 27607 ph 919.314.6686
2 2 4 6 8 10
1/4" = 1'-0"
FEETSCALE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTSFacilities Management
Services
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
SHEET NOTES:
12/18/2025
A u to d e s k D o c s /A s h e v ill e E
H R
M
V
/6
-2
-7
.0
.E .A
S H
E
H R
M .r v t
/1 /2
:1
:0
P M
03-EP101
ELECTRICAL 1ST & 2ND FLOOR PLAN
Awen Solutions Group
215 N. Payne Street, Suite 122
Alexandria, VA 22314
12.19.2025
EHRM INFRASTRUCTURE
UPGRADES BLDG 3
1100 TUNNEL ROAD
ASHEVILLE, NC 28805
637-22-700
1/4" = 1'-0"
1 ELECTRICAL 1ST FLOOR PLAN
1/4" = 1'-0"
2 ELECTRICAL 2ND FLOOR PLAN
GENERAL NOTES:
1. FIRE/SMOKE WALL RECORD DRAWINGS WERE NOT PROVIDED BY THE STATION. FIELD-VERIFY EXISTING PARTITION WALLS TO IDENTIFY FIRE/SMOKE RATING AND PROVIDE ALL REQUIRED MEASURES AND APPROPRIATE EQUIPMENT IN ACCORDANCE WITH THE
VERIFIED PARTITION TYPE.
2. REFER TO 00-E001 FOR GENERAL NOTES, LEGENDS, AND POWER EQUIPMENT SCHEDULE. PROVIDE UPS AND PDU EQUIPMENT IN
EACH TELECOM ENCLOSURE AS SPECIFIED.
3. REFER TO 03-EP601 FOR BUILDING ONE-LINE AND PANEL SCHEDULES.
4. REFER TO TELECOM DRAWINGS FOR EQUIPMENT AND TELECOM ENCLOSURE LAYOUT.
5. ELECTRICAL PANEL LOCATIONS SHOWN FOR REFERENCE ONLY. ALL PANELS ARE EXISTING TO REMAIN.
6. REFER TO 00-E502, DETAILS 1 & 2 FOR TYPICAL EQUIPMENT ELEVATION FOR TELECOM ENCLOSURE INSTALLATIONS. INSTALL, CONNECT, AND ENERGIZE RACK POWER EQUIPMENT AS SPECIFIED.
PROVIDE TWO (2) NEMA L5-30R TWIST LOCKING RECEPTACLES MOUNTED INSIDE WALL MOUNTED TELECOM ENCLOSURE.
COORDINATE FINAL INSTALLATION AND MOUNTING HEIGHT WITH ENCLOSURE INSTALLATION.
BOND RACK BONDING BUSBAR (RBB) TO THE SBB. SBB SHALL BE BONDED BACK TO THE BUILDING PBB. REFER TO GROUNDING
AND BONDING DETAIL(S) ON SHEET 03-TN601 FOR FURTHER DETAILS.
BOND RACK BONDING BUSBAR (RBB) TO THE PBB. CONTRACTOR SHALL LOCATE THE BUILDING MAIN GROUND BAR AND BOND THE PBB BACK TO IT. REFER TO GROUNDING AND BONDING DETAIL(S) ON SHEET 03-TN601 FOR FURTHER DETAILS.
FOR VERTICALLY STACKED QUAD RECEPTACLES, REFER TO DETAIL 1/00-E502 FOR INSTALLATION.
Revisions: Date: SHEET 71 of 559
040390
N
O
RT
H CAROLIN
A
P R
FO
ESS ON
A L
I
N E
GINEER
(E) BLDG 4 XFMR
100KVA
12470V-240V
(E) BLDG 2
DISCONNECT
240V, 225A
(E) BLDG 3
DISCONNECT
240V, 225A
(E) PANEL
3B
200A 120/240V
(E) PANEL
3A
200A 120/240V
(E) BLDG 4
DISCONNECT
240V, 225A
(E) PANEL
4B
150A 120/240V
(E) PANEL
4A
150A 120/240V
(E) BLDG 5
DISCONNECT
240V, 225A
(E) PANEL
5B
150A 120/240V
(E) PANEL
5A
150A 120/240V
TO CAMPUS MV
DISTRIBUTION
(E) PANEL
2A
200A 120/240V
FOR OFFICIAL USE ONLY
www.coffman.com
701 Corporate Center Drive, Suite 475
Raleigh, NC 27607 ph 919.314.6686
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTSFacilities Management
Services
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
SHEET NOTES:
12/18/2025
A u to d e s k D o c s /A s h e v ill e E
H R
M
V
/6
-2
-7
.0
.E .A
S H
E
H R
M .r v t
/1 /2
:1
:0
P M
03-EP601
ONE-LINE DIAGRAM AND SCHEDULES
Awen Solutions Group
215 N. Payne Street, Suite 122
Alexandria, VA 22314
12.19.2025
EHRM INFRASTRUCTURE
UPGRADES BLDG 3
1100 TUNNEL ROAD
ASHEVILLE, NC 28805
637-22-700
N.T.S.
1 BUILDING 3 PARTIAL ONE-LINE DIAGRAM
1. USE EXISTING BLANK PANEL SPACE. PROVIDE NEW BREAKER, WHICH SHALL MATCH THE EXISTING PANEL MANUFACTURER AND AIC RATING, AND MAINTAIN EXISTING PANEL UL RATING.
Notes:
Total Est. Demand Current: 24 A
Total Conn. Current: 24 A
Total Est. Demand: 5760 VA
Total Conn. Load: 5760 VA
Telecommunications Equipment 5760 VA 100.00% 5760 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 24 A 24 A
Total Load: 2880 VA 2880 VA
41 L5-30R, TE 2ND FLR 30 A 1 1 2880 -- 1 -- SPACE 42
39 L5-30R, TE 1ST FLR 30 A 1 1 2880 -- 1 -- SPACE 40
37 SPACE -- 1 -- -- 1 -- SPACE 38
35 SPACE -- 1 -- -- 1 -- SPACE 36
33 SPACE -- 1 -- -- 1 -- SPACE 34
31 SPACE -- 1 -- -- 1 -- SPACE 32
29 SPARE 20 A 1 0 0 1 20 A SPARE 30
27 (E) BSA CON 20 A 1 0 0 1 20 A SPARE 28
25 (E) UNKNOWN LOAD 20 A 1 0 0 1 20 A (E) OUTSIDE A/C 26
23 -- -- -- -- 0 0 1 20 A (E) OUTSIDE A/C 24
21 (E) OUTSIDE A/C 20 A 2 0 0 1 20 A (E) DOWNSTAIRS HEAT 22
19 (E) UPSTAIRS HEAT 20 A 1 0 0 1 20 A (E) WASHER 20
17 (E) SMOKE DETECTOR 20 A 1 0 0 1 20 A (E) KIT. LITE/REC., DIN. REC 18
15 (E) BATH LTG, W.BR REC/LTG 20 A 1 0 0 1 20 A (E) ATTIC FAN & LITE 16
13 (E) STEAM CONTROL 20 A 1 0 0 1 20 A (E) KIT. REC 14
11 SPARE 20 A 1 0 0 1 20 A (E) BASE LTG, DISP., D LTG/REC 12
9 (E) REC, HALL 20 A 1 0 0 1 20 A (E) HALL LTG, BR LTG/REC 10
7 -- -- -- -- 0 0 1 20 A (E) LTG, REFRIG 8
5 SPARE 20 A 2 0 0 1 20 A SPARE 6
3 -- -- -- -- 0 0 -- -- -- -- 4
1 SPARE 20 A 2 0 0 2 20 A SPARE 2
CKT Circuit Description Trip Poles Notes A B Notes Poles Trip Circuit Description CKT
Enclosure: Type 1 MCB Rating: 200 A
Mounting: SURFACE Wires: 3 Mains Rating: 225 A
Supply From: Phases: 1 Mains Type: MCB
Location: Volts: 120/240 Single A.I.C. Rating: UNKNOWN
Branch Panel: (E) 3A
1. USE EXISTING BLANK PANEL SPACE. PROVIDE NEW BREAKER, WHICH SHALL MATCH THE EXISTING PANEL MANUFACTURER AND AIC RATING, AND MAINTAIN EXISTING PANEL UL RATING.
Notes:
Total Est. Demand Current: 30 A
Total Conn. Current: 30 A
Total Est. Demand: 7200 VA
Telecommunications Equipment 5760 VA 100.00% 5760 VA Total Conn. Load: 7200 VA
REC, 1440 VA 100.00% 1440 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 30 A 30 A
Total Load: 3600 VA 3600 VA
41 L5-30R, TE 2ND FLR 30 A 1 1 2880 -- 1 -- SPACE 42
39 L5-30R, TE 1ST FLR 30 A 1 1 2880 -- 1 -- SPACE 40
37 REC, 2ND FLOOR TE 20 A 1 1 720 -- 1 -- SPACE 38
35 REC, 1ST FLOOR TE 20 A 1 1 720 -- 1 -- SPACE 36
33 SPACE -- 1 -- -- 1 -- SPACE 34
31 SPARE 20 A 1 0 0 1 20 A SPARE 32
29 -- -- -- -- 0 0 1 20 A (E) EXISTING LOAD 30
27 (E) OUTSIDE A/C 20 A 2 0 0 1 20 A SPARE 28
25 (E) DOWNSTAIRS HEAT 20 A 1 0 0 1 20 A SPARE 26
23 (E) SMOKE DETECTOR 20 A 1 0 0 -- -- -- -- 24
21 SPARE 20 A 1 0 0 2 20 A (E) OUTSIDE A/C 22
19 (E) WASHER, DISP., REFRIDGE. 20 A 1 0 0 1 20 A (E) UPSTAIRS HEAT 20
17 (E) LR REC LITE, HALL REC. 20 A 1 0 0 1 20 A SPARE 18
15 (E) HALL LITE/REC, BATH LITE 20 A 1 0 0 1 20 A (E) KIT. REC. 16
13 (E) SUN RM. REC/LITE 20 A 1 0 0 1 20 A (E) SO. BR LITE/REC. 14
11 (E) BACK LITE, DIN REC/LITE 20 A 1 0 0 1 20 A (E) BASE LITE/REC, KIT. LITE 12
9 (E) KIT. REC 20 A 1 0 0 1 20 A SPARE 10
7 -- -- -- -- 0 0 1 20 A (E) ATTIC FAN, REC/LITE 8
5 (E) DRYER 60 A 2 0 0 1 20 A (E) STEAM CONTROL 6
3 -- -- -- -- 0 0 -- -- -- -- 4
1 (E) WATER HEATER 60 A 2 0 0 2 20 A (E) RANGE 2
CKT Circuit Description Trip Poles Notes A B Notes Poles Trip Circuit Description CKT
Enclosure: Type 1 MCB Rating: 200 A
Mounting: SURFACE Wires: 3 Mains Rating: 225 A
Supply From: Phases: 1 Mains Type: MCB
Location: Volts: 120/240 Single A.I.C. Rating: UNKNOWN
Branch Panel: (E) 3B
GENERAL NOTES:
1. REFER TO 00-E001 FOR GENERAL NOTES AND LEGENDS.
2. ALL PANELS ARE EXISTING TO REMAIN. PANELS SHOWN IN BOLD INDICATE SCOPE IN THOSE PANELS.
3. ADDITIONAL LOAD TO BE ADDED TO PANELS AS SHOWN. EXISTING LOAD INFORMATION FOR PANELS WAS UNAVAILABLE AT THE
TIME OF DESIGJN. "PANEL TOTALS" REPRESENT LOAD ADDED TO PANEL.
4. IF SPACE ALLOCATED FOR NEW LOADS IS NOT AVAILABLE DURING CONSTRUCTION, CONTACT THE DOR.
5. DEMAND LOAD CALCULATIONS WERE DONE USING EXISTING INFORMATION FROM PROVIDED AS-BUILTS, SITE OBSERVATIONS, AND PHOTOS. PANELS WITH NEW LOADS ADDED WERE WERE SELECTED USING THE DEMAND LOAD ESTIMATES.
6. PANEL AIC RATINGS SHOWN WERE DONE USING EXISTING INFORMATION FROM PROVIDED AS-BUILTS, SITE OBSERVATIONS, AND
PHOTOS. CONTRACTOR TO VERFIY AIC RATING BEFORE ADDING NEW BREAKERS.
Revisions: Date: SHEET 72 of 559
Expires12-31-28
BICSI ID # 237176
Jinze Chen
PLAN
NORTH
N
FOR OFFICIAL USE ONLY
www.coffman.com
701 Corporate Center Drive, Suite 475
Raleigh, NC 27607 ph 919.314.6686
2 2 4 6 8 10
1/4" = 1'-0"
FEETSCALE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTSFacilities Management
Services
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
SHEET NOTES:
12/18/2025
A u to d e s k D o c s /A s h e v ill e E
H R
M
V
/6
-2
-7
.0
.E .A
S H
E
H R
M .r v t
/1 /2
:5
:4
P M
03-TD100
TELECOMMUNICATIONS BASEMENT
DEMOLITIONAwen Solutions Group
215 N. Payne Street, Suite 122
Alexandria, VA 22314
12.19.2025
EHRM INFRASTRUCTURE
UPGRADES BLDG 3
1100 TUNNEL ROAD
ASHEVILLE, NC 28805
637-22-700
1/4" = 1'-0"
1 TELECOMMUNICATIONS BASEMENT DEMOLITION
GENERAL NOTES:
1. REFER TO 00-T001 FOR GENERAL NOTES AND LEGENDS.
2. ALL EXISTING CABLES AND INFRASTRUCTURE NOT CAT6A RATED TO BE DEMOLISHED.
3. NOT ALL DEVICES ARE SHOWN. CONTRACTOR TO VERIFY ALL DATA OUTLET LOCATIONS IN THE FIELD.
4. THE QUANTITY OF TELECOM DROPS TO BE REMOVED, INSTALLED, AND MAINTAINED IS BASED ON THE INFORMATION KNOWN AT THE TIME OF DESIGN. PRIOR TO CONSTRUCTION, TELECOM DROP LOCATIONS SHALL BE SURVEYED. ANY DISCREPANCIES SHALL
BE PROVIDED TO THE DOR IMMEDIATELY.
5. EXISTING ROUTING FOR TELECOM DROPS TO REMAIN SHALL BE MAINTAINED TO THE FULLEST EXTENT.
6. DEMOLITION DETAILS (IN NO PARTICULAR ORDER):
A. REFER TO ENLARGED PLANS FOR ADDITIONAL REQUIREMENTS.
B. CABLE CAT6 AND BELOW HORIZONTAL CABLE SHALL BE REMOVED FROM EXISTING PATCH PANELS BACK TO FINAL DATA
JACK LOCATIONS. CABLE SHALL BE REMOVED BETWEEN EXISTING SWITCH AND PATCH PANEL.
C. PATCH PANELS CURRENTLY NOT DESIGNED FOR CAT6A CABLE SHALL BE REMOVED.
D. WALL PLATES AND RJ-45 JACKS FOR WALL OUTLET BOXES FOR CAT5E, 6 AND BELOW CABLE SHALL BE REMOVED.
E. DATA RACKS SHALL BE REMOVED.
F. HORIZONTAL AND VERTICAL CABLE MANAGEMENT FOR RACKS SHALL BE REMOVED IF APPLICABLE.
G. WALL MOUNTED FIBER BOXES SHALL BE REMOVED.
H. FIBER CABLE AND ENCLOSURES SHALL BE REMOVED BACK TO SOURCE AFTER ALL NEW FIBER CONNECTIONS IN THIS
BUILDING HAVE BEEN CONNECTED. PRIOR TO DEMOLITION, COORDINATE WITH VA COR TO ENSURE ALL FIBER IS INACTIVE
BEFORE DEMOLITION.
I. EXISTING CABLE TRAY TO REMAIN.
J. COPPER PHONE PUNCH DOWN BLOCKS SHALL REMAIN UNLESS OTHERWISE NOTED.
7. DEMOLISH ALL TELECOMMUNICATIONS CABLE THAT IS NOT TERMINATED AT BOTH ENDS AT A CONNECTOR OR OTHER EQUIPMENT AND NOT IDENTIFIED 'FOR FUTURE USE' WITH A TAG. ENSURE DEMOLITION OF ABANDONED CABLE WILL NOT DISRUPT VA OPERATIONS PRIOR TO REMOVAL. WHERE DISRUPTION OF SERVICE OCCURS DUE TO DEMOLISHED CABLE, NEW
CABLE SHALL BE INSTALLED TO RESTORE THE SYSTEM AT THE CONTRACTOR'S EXPENSE.
8. PRIOR TO DEMOLITION, COORDINATE DISPOSAL WITH VA. ALL VA STANDARDS, EPA STANDARDS AND LOCAL STANDARDS MUST BE
FOLLOWED WHEN DISPOSING OF ASBESTOS EXPOSED ITEMS.
1 EXISTING TO REMAIN 1-4"C FROM EXISTING HANDHOLE TO BE REUSED FOR OSP FIBER.
Revisions: Date: SHEET 73 of 559
Jinze Chen
D1/3
D2/3
D1/3
D2/3
D1/3
D1/3
D2/3
D0/3
D1/3
D2/3 D2/3
D1/3
D1/3
OFFICE
OFFICE
OFFICE
HALL ENTRY
OFFICE
OFFICE
OFFICE
D0/3
D1/3
D0/1
D2/3
D2/3
D1/3D1/3 D1/3
D1/3
D2/3
D2/3
D2/3
D1/3
OFFICE
CLOSET
TOILET
TOILET
CLOSET
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
HALL
PLAN
NORTH
N
FOR OFFICIAL USE ONLY
www.coffman.com
701 Corporate Center Drive, Suite 475
Raleigh, NC 27607 ph 919.314.6686
2 2 4 6 8 10
1/4" = 1'-0"
FEETSCALE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTSFacilities Management
Services
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
SHEET NOTES:
12/18/2025
A u to d e s k D o c s /A s h e v ill e E
H R
M
V
/6
-2
-7
.0
.E .A
S H
E
H R
M .r v t
/1 /2
:5
:4
P M
03-TD101
TELECOMMUNICATIONS 1ST & 2ND
FLOOR DEMOLITIONAwen Solutions Group
215 N. Payne Street, Suite 122
Alexandria, VA 22314
12.19.2025
EHRM INFRASTRUCTURE
UPGRADES BLDG 3
1100 TUNNEL ROAD
ASHEVILLE, NC 28805
637-22-700
1/4" = 1'-0"
1 TELECOMMUNICATIONS 1ST FLOOR DEMOLITION
1/4" = 1'-0"
2 TELECOMMUNICATIONS 2ND FLOOR DEMOLITION
GENERAL NOTES:
1. REFER TO 00-T001 FOR GENERAL NOTES AND LEGENDS.
2. ALL EXISTING CABLES AND INFRASTRUCTURE NOT CAT6A RATED TO BE DEMOLISHED.
3. NOT ALL DEVICES ARE SHOWN. CONTRACTOR TO VERIFY ALL DATA OUTLET LOCATIONS IN THE FIELD.
4. THE QUANTITY OF TELECOM DROPS TO BE REMOVED, INSTALLED, AND MAINTAINED IS BASED ON THE INFORMATION KNOWN AT THE TIME OF DESIGN. PRIOR TO CONSTRUCTION, TELECOM DROP LOCATIONS SHALL BE SURVEYED. ANY DISCREPANCIES SHALL
BE PROVIDED TO THE DOR IMMEDIATELY.
5. EXISTING ROUTING FOR TELECOM DROPS TO REMAIN SHALL BE MAINTAINED TO THE FULLEST EXTENT.
6. DEMOLITION DETAILS (IN NO PARTICULAR ORDER):
A. REFER TO ENLARGED PLANS FOR ADDITIONAL REQUIREMENTS.
B. CABLE CAT6 AND BELOW HORIZONTAL CABLE SHALL BE REMOVED FROM EXISTING PATCH PANELS BACK TO FINAL DATA
JACK LOCATIONS. CABLE SHALL BE REMOVED BETWEEN EXISTING SWITCH AND PATCH PANEL.
C. PATCH PANELS CURRENTLY NOT DESIGNED FOR CAT6A CABLE SHALL BE REMOVED.
D. WALL PLATES AND RJ-45 JACKS FOR WALL OUTLET BOXES FOR CAT5E, 6 AND BELOW CABLE SHALL BE REMOVED.
E. DATA RACKS SHALL BE REMOVED.
F. HORIZONTAL AND VERTICAL CABLE MANAGEMENT FOR RACKS SHALL BE REMOVED IF APPLICABLE.
G. WALL MOUNTED FIBER BOXES SHALL BE REMOVED.
H. FIBER CABLE AND ENCLOSURES SHALL BE REMOVED BACK TO SOURCE AFTER ALL NEW FIBER CONNECTIONS IN THIS
BUILDING HAVE BEEN CONNECTED. PRIOR TO DEMOLITION, COORDINATE WITH VA COR TO ENSURE ALL FIBER IS INACTIVE
BEFORE DEMOLITION.
I. EXISTING CABLE TRAY TO REMAIN.
J. COPPER PHONE PUNCH DOWN BLOCKS SHALL REMAIN UNLESS OTHERWISE NOTED.
7. DEMOLISH ALL TELECOMMUNICATIONS CABLE THAT IS NOT TERMINATED AT BOTH ENDS AT A CONNECTOR OR OTHER EQUIPMENT AND NOT IDENTIFIED 'FOR FUTURE USE' WITH A TAG. ENSURE DEMOLITION OF ABANDONED CABLE WILL NOT DISRUPT VA OPERATIONS PRIOR TO REMOVAL. WHERE DISRUPTION OF SERVICE OCCURS DUE TO DEMOLISHED CABLE, NEW
CABLE SHALL BE INSTALLED TO RESTORE THE SYSTEM AT THE CONTRACTOR'S EXPENSE.
8. PRIOR TO DEMOLITION, COORDINATE DISPOSAL WITH VA. ALL VA STANDARDS, EPA STANDARDS AND LOCAL STANDARDS MUST BE
FOLLOWED WHEN DISPOSING OF ASBESTOS EXPOSED ITEMS.
Revisions: Date: SHEET 74 of 559
Jinze Chen
(E) RACK
FIBER OPTIC
HORIZONTAL CABLES
PATCH CORD
TOTAL PORTS
WALL-MOUNTED ENCLOSURE TO BE DEMOLISHED. ENCLOSURE WAS UNABLE TO BE LOCATED DUE TO CONSTRUCTION IN BUILDING 3 AT TIME OF DESIGN. FIELD VERIFY LOCATION OF THE EXISTING ENCLOSURE AND DEMOLISH.
FIBER OPTIC PATCH PANEL TO BE DEMOLISHED.
DETAIL NOTES:
FOR OFFICIAL USE ONLY
www.coffman.com
701 Corporate Center Drive, Suite 475
Raleigh, NC 27607 ph 919.314.6686
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTSFacilities Management
Services
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
SHEET NOTES:
12/18/2025
A u to d e s k D o c s /A s h e v ill e E
H R
M
V
/6
-2
-7
.0
.E .A
S H
E
H R
M .r v t
/1 /2
:5
:4
P M
03-TD601
TELECOMMUNICATIONS DEMOLITION
RACK ELEVATIONSAwen Solutions Group
215 N. Payne Street, Suite 122
Alexandria, VA 22314
12.19.2025
EHRM INFRASTRUCTURE
UPGRADES BLDG 3
1100 TUNNEL ROAD
ASHEVILLE, NC 28805
637-22-700
GENERAL NOTES:
1. RACK ELEVATION BASED OFF OF BEST AVAILABLE INFORMATION. PRIOR TO CONSTRUCTION, RACK SHALL BE SURVEYED. ANY
DISCREPANCIES SHALL BE PROVIDED TO THE DOR IMMEDIATELY.
N.T.S.
1 (E) RACK ELEVATION
Revisions: Date: SHEET 75 of 559
Jinze Chen
D2 D2
PLAN
NORTH
N
FOR OFFICIAL USE ONLY
www.coffman.com
701 Corporate Center Drive, Suite 475
Raleigh, NC 27607 ph 919.314.6686
2 2 4 6 8 10
1/4" = 1'-0"
FEETSCALE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTSFacilities Management
Services
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
SHEET NOTES:
12/18/2025
A u to d e s k D o c s /A s h e v ill e E
H R
M
V
/6
-2
-7
.0
.E .A
S H
E
H R
M .r v t
/1 /2
:5
:4
P M
03-TN100
TELECOMMUNICATIONS BASEMENT
PLANAwen Solutions Group
215 N. Payne Street, Suite 122
Alexandria, VA 22314
12.19.2025
EHRM INFRASTRUCTURE
UPGRADES BLDG 3
1100 TUNNEL ROAD
ASHEVILLE, NC 28805
637-22-700
1/4" = 1'-0"
1 TELECOMMUNICATIONS BASEMENT PLAN
GENERAL NOTES:
1. FIRE/SMOKE WALL RECORD DRAWINGS WERE NOT PROVIDED BY THE STATION. FIELD-VERIFY EXISTING PARTITION WALLS TO
IDENTIFY FIRE/SMOKE RATING AND PROVIDE ALL REQUIRED MEASURES AND APPROPRIATE EQUIPMENT IN ACCORDANCE WITH
THE VERIFIED PARTITION TYPE.
2. REFER TO 00-T001 FOR GENERAL NOTES AND LEGENDS.
3. ALL EXISTING CABLES AND INFRASTRUCTURE NOT CAT6A RATED TO BE REPLACED WITH CAT6A CABLING.
4. NOT ALL DEVICES ARE SHOWN. CONTRACTOR TO VERIFY ALL DATA OUTLET LOCATIONS IN THE FIELD.
5. THE QUANTITY OF TELECOM DROPS TO BE REMOVED, INSTALLED, AND MAINTAINED IS BASED ON THE INFORMATION KNOWN AT THE TIME OF DESIGN. PRIOR TO CONSTRUCTION, TELECOM DROP LOCATIONS SHALL BE SURVEYED. ANY DISCREPANCIES SHALL
BE PROVIDED TO THE VA COR IMMEDIATELY.
6. WHERE DROP CEILING TILES ARE DISTURBED FOR INSTALLATION OF TELECOMMUNICATIONS CABLE, INNERDUCT, CABLE TRAY, ETC., ENSURE ALL DUST AND PARTICLES ARE CLEANED PRIOR TO LEAVING THE DISTURBED AREA. PROVIDE NEW DROP CEILING
TILES WHERE TILES ARE DAMAGED DURING CONSTRUCTION.
7. ALL ROUTING FOR NEW BACKBONE CABLE SHALL BE ROUTED IN CORRUGATED INNERDUCT.
8. DATA DROPS TO BE FED FROM THE NEW WALL MOUNTED CABINET ON THE CORRESPONDING FLOOR. DATA DROPS IN THE
BASEMENT ARE TO BE FED FROM THE FIRST FLOOR WALL MOUNTED CABINET.
PROVIDE PULL BOX.
1-4"C FROM HANDHOLE TO PULLBOX FOR "A SIDE" FIBER:
PROVIDE 1-4"C CONTAINING ONE (1) 3" CORRUGATED INNERDUCT WITH 2-24ST OS2 FIBER FROM THE "A SIDE" MDA IN THE DATA CENTER OF BUILDING 47 TO FIRST AND SECOND FLOOR TES IN BUILDING 3. CONTRACTOR TO ROUTE CONDUITS THROUGH THE BASEMENT IN FIELD TO AVOID OBSTRUCTIONS AND MINIMIZE DISTURBANCE TO USERS. REFER TO 00-TS100 FOR ADDITIONAL
INFORMATION.
1-4"C FROM EXISTING HANDHOLE TO PULLBOX FOR "B SIDE" FIBER:
IN EXISTING 1-4"C, PROVIDE ONE (1) 3" CORRUGATED INNERDUCT WITH 2-24ST OS2 FIBER FROM THE "B SIDE" MDA IN THE DATA CENTER OF BUILDING 47 TO FIRST AND SECOND FLOOR TES IN BUILDING 3. CONTRACTOR TO ROUTE CONDUITS THROUGH THE BASEMENT IN FIELD TO AVOID OBSTRUCTIONS AND MINIMIZE DISTURBANCE TO USERS. REFER TO 00-TS100 FOR ADDITIONAL
INFORMATION.
1-4"C FROM PULLBOX TO PULLBOX FOR "B SIDE" FIBER:
PROVIDE 1-4"C CONTAINING ONE (1) 3" CORRUGATED INNERDUCT WITH 2-24ST OS2 FIBER FROM THE "B SIDE" MDA IN THE DATA CENTER OF BUILDING 47 TO FIRST AND SECOND FLOOR TES IN BUILDING 3. CONTRACTOR TO ROUTE CONDUITS THROUGH THE BASEMENT IN FIELD TO AVOID OBSTRUCTIONS AND MINIMIZE DISTURBANCE TO USERS. REFER TO 04-TN601 FOR ADDITIONAL
INFORMATION.
2-4"C FROM PULLBOX TO FIRST FLOOR TE:
PROVIDE 1-4"C CONTAINING ONE (1) 3" CORRUGATED INNERDUCT FOR FIBER BACKBONE FROM THE "A SIDE" MDA IN THE DATA CENTER OF BUILDING 47 GOING TO THE FIRST AND SECOND FLOOR TES IN BUILDING 3. ROUTE 1-24ST OS2 FIBER TO EACH TE FROM THE A SIDE MDA. PROVIDE 1-4"C CONTAINING ONE (1) 3" CORRUGATED INNERDUCT WITH 2-24ST OS2 FIBER FROM THE "B SIDE" MDA IN THE DATA CENTER OF BUILDING 47 TO FIRST AND SECOND FLOOR TES IN BUILDING 3. ROUTE 1-24ST OS2 FIBER TO EACH TE FROM
THE B SIDE MDA.
Revisions: Date: SHEET 76 of 559
Jinze Chen
2 5
D2
D2
D2
D2
D2
D2
D2
D2
D2
D2
D2
D2
2' - 0" (TYP.)
(T Y
P
2' - 0" (TYP.)
5 1
D2
D2
D2
D2 D2
D2
D2
D2
D2
D2
D2
D0
D0
PLAN
NORTH
N
FOR OFFICIAL USE ONLY
www.coffman.com
701 Corporate Center Drive, Suite 475
Raleigh, NC 27607 ph 919.314.6686
2 2 4 6 8 10
1/4" = 1'-0"
FEETSCALE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTSFacilities Management
Services
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
SHEET NOTES:
12/18/2025
A u to d e s k D o c s /A s h e v ill e E
H R
M
V
/6
-2
-7
.0
.E .A
S H
E
H R
M .r v t
/1 /2
:5
:4
P M
03-TN101
TELECOMMUNICATIONS 1ST & 2ND
FLOOR PLANAwen Solutions Group
215 N. Payne Street, Suite 122
Alexandria, VA 22314
12.19.2025
EHRM INFRASTRUCTURE
UPGRADES BLDG 3
1100 TUNNEL ROAD
ASHEVILLE, NC 28805
637-22-700
1/4" = 1'-0"
1 TELECOMMUNICATIONS 1ST FLOOR PLAN
1/4" = 1'-0"
2 TELECOMMUNICATIONS 2ND FLOOR PLAN
GENERAL NOTES:
1. FIRE/SMOKE WALL RECORD DRAWINGS WERE NOT PROVIDED BY THE STATION. FIELD-VERIFY EXISTING PARTITION WALLS TO
IDENTIFY FIRE/SMOKE RATING AND PROVIDE ALL REQUIRED MEASURES AND APPROPRIATE EQUIPMENT IN ACCORDANCE WITH THE
VERIFIED PARTITION TYPE.
2. REFER TO 00-T001 FOR GENERAL NOTES AND LEGENDS.
3. ALL EXISTING CABLES AND INFRASTRUCTURE NOT CAT6A RATED TO BE REPLACED WITH CAT6A CABLING.
4. CONTRACTOR TO VERIFY ALL DATA OUTLET LOCATIONS IN THE FIELD.
5. THE QUANTITY OF TELECOM DROPS TO BE REMOVED, INSTALLED, AND MAINTAINED IS BASED ON THE INFORMATION KNOWN AT THE TIME OF DESIGN. PRIOR TO CONSTRUCTION, TELECOM DROP LOCATIONS SHALL BE SURVEYED. ANY DISCREPANCIES SHALL
BE PROVIDED TO THE VA COR IMMEDIATELY.
6. WHERE DROP CEILING TILES ARE DISTURBED FOR INSTALLATION OF TELECOMMUNICATIONS CABLE, INNERDUCT, CABLE TRAY, ETC., ENSURE ALL DUST AND PARTICLES ARE CLEANED PRIOR TO LEAVING THE DISTURBED AREA. PROVIDE NEW DROP CEILING
TILES WHERE TILES ARE DAMAGED DURING CONSTRUCTION.
7. ALL ROUTING FOR NEW BACKBONE CABLE SHALL BE ROUTED IN CORRUGATED INNERDUCT.
8. ALL EXISTING DATA DROPS TO BE REFED FROM THE NEW WALL MOUNTED CABINET ON THE CORRESPONDING FLOOR. IF THERE ARE EXISTING DATA DROPS IN THE BASEMENT, THEN THEY ARE TO BE FED FROM THE FIRST FLOOR WALL MOUNTED CABINET.
PROVIDE 4' BY 8' AC GRADE 3/4" TRADE SIZE PLYWOOD BACKBOARD PAINTED HIGH-GLOSS WHITE WITH TWO COATS OF FIRE
RESISTANT PAINT.
PROVIDE NEW PRIMARY BONDING BUS BAR (PBB) ON PLYWOOD BACKBOARD. REFER TO SHEET 00-T501 FOR GROUNDING AND
BONDING DETAILS.
PROVIDE NEW WALL-MOUNTED 12U CABINET ON PLYWOOD BACKBOARD.
PROVIDE NEW SECONDARY BONDING BUS BAR (SBB) ON PLYWOOD BACKBOARD. REFER TO SHEET 00-T501 FOR GROUNDING AND
BONDING DETAILS.
2-4"C FROM PULLBOX TO TE:
PROVIDE 1-4"C CONTAINING ONE (1) 3" CORRUGATED INNERDUCT FOR FIBER BACKBONE FROM THE "A SIDE" MDA IN THE DATA CENTER OF BUILDING 47 GOING TO THE FIRST AND SECOND FLOOR TES IN BUILDING 3. ROUTE 1-24ST OS2 FIBER TO EACH TE FROM THE A SIDE MDA. PROVIDE 1-4"C CONTAINING ONE (1) 3" CORRUGATED INNERDUCT WITH 2-24ST OS2 FIBER FROM THE "B SIDE" MDA IN THE DATA CENTER OF BUILDING 47 TO FIRST AND SECOND FLOOR TES IN BUILDING 3. ROUTE 1-24ST OS2 FIBER TO EACH TE
FROM THE B SIDE MDA.
1-4"C FROM FIRST FLOOR TE TO FIRST FLOOR CEILING FOR HORIZONTAL DISTRIBUTION.
1-4"C FROM SECOND FLOOR TE TO SECOND FLOOR CEILING FOR HORIZONTAL DISTRIBUTION.
Revisions: Date: SHEET 77 of 559
Jinze Chen
CABLE MANAGER
FIRST FLOOR CABINET
FIBER OPTIC
PATCH PANEL
CABLE MANAGER
SWITCH
CABLE MANAGER
PDU
OUTLETS
PDU
UPS
CABLE MANAGER
SECOND FLOOR CABINET
FIBER OPTIC
PATCH PANEL
CABLE MANAGER
SWITCH
CABLE MANAGER
PDU
OUTLETS
PDU
UPS
1 12U WALL-MOUNTED 2-POST CABINET WITH LOCKABLE FRONT DOOR AND
SWING-OUT REAR ACCESS TO EQUIPMENT.
144-STRAND FIBER OPTIC PATCH PANEL WITH SPLICE KIT, LC CONNECTORS,
1U.
1U WIRE MANAGEMENT.
48-PORT UTP CAT6A PATCH PANEL, 1U.
VA LAN SWITCH PROVIDED BY OTHERS.
LOCKING 120V 30A OUTLETS.
RACK MOUNTED PDU. L5-30P INPUT POWER CORD PLUG TYPE AND NEMA
5-20 OUTPUT, 1RU.
RACK MOUNTED UPS. L5-30 INPUT AND L5-30 OUTPUT, CAPACITY NTE 2880
VA, 2U.
DETAIL NOTES:
HORIZONTAL CABLES
HORIZONTAL CABLES + 10% OVERAGE
TOTAL SPARE HORIZONTAL CABLES
(48 x 1) - 27 = 21
HORIZONTAL CABLES
HORIZONTAL CABLES + 10% OVERAGE
TOTAL SPARE HORIZONTAL CABLES
(48 x 1) - 25 = 23
FIBER PP
1 3
LEVEL 1
FIBER PP
1 3
LEVEL 2
FIBER FROM CORE 1 IN BUILDING 47 LANDING ON FIBER OPTIC PATCH PANEL IN TR:
(1) 24ST OS2 SINGLE MODE FIBER
FIBER ORIGINATING FROM CORE 1 IN BUILDING 47:
(2) 24ST OS2 SINGLE MODE FIBER
FIBER FROM CORE 2 IN BUILDING 47 LANDING ON FIBER OPTIC PATCH PANEL IN TR:
(1) 24ST OS2 SINGLE MODE FIBER
FIBER ORIGINATING FROM CORE 2 IN BUILDING 47:
(2) 24ST OS2 SINGLE MODE FIBER
DETAIL NOTES:
BASEMENT
FIRST FLOOR
ELECTRICAL PANEL
GROUND BUS
TO BUILDING
STEEL
TELECOM CABINET BOND
#6 AWG TEBC
#1/0 TBC
CONDUITS ENTERING COMM ROOM
TO GROUNDING BUS (MGB)
#6 AWG TEBC
SECOND FLOOR
ELECTRICAL PANEL
GROUND BUS
SBB
ROOM 2F
#6 AWG ACEG
TO BUILDING
STEEL
TELECOM CABINET BOND
#6 AWG BSB
#6 AWG BSB
#6 AWG ACEG
#1/0 AWG TBB
#6 AWG TEBC
CONDUITS ENTERING COMM ROOM
#6 AWG TEBC
METALLIC TELECOM RACEWAY AND EQUIPMENT SHALL BE GROUNDED. BOND
RACEWAY TO NEAREST TELECOM GROUND BUS USING A TEBC, #6 AWG MINIMUM.
TELECOM GROUNDING SYSTEM MUST BE IN ACCORDANCE WITH TIA-607 AND THE
VA DESIGN STANDARDS.
COAXIAL METAL SHEATH MUST BE GROUNDED AND BONDED PER NEC
REQUIREMENTS.
TBB CONDUCTOR MUST BE SIZED BASED ON THE TABLE BELOW, SIZING OF
TELECOM BONDING BACKBONE.
ACRONYMS
ACEG ALTERNATING CURRENT EQUIPMENT GROUND
BBC BACKBONE BONDING CONDUCTOR
BSB BUILDING STRUCTURE BONDING
MGB MAIN GROUNDING BUS
PBB PRIMARY BONDING BUSBAR
SBB SECONDARY BONDING BUSBAR
TBB TELECOMMUNICATIONS BACKBONE BONDING CONDUCTOR
TBC TELECOMMUNICATIONS BONDING CONDUCTOR
TEBC TELECOMMUNICATIONS EQUIPMENT BONDING CONDUCTOR
GROUNDING NOTES:
1.
2.
3.
4.
#1/0 AWG TBB
SIZING OF TELECOM BONDING BACKBONE
<13
14-20
21-26
27-33
34-41
42-52
53-66
67-84
85-105
106-125
126-150
176-250
151-175
251-300
>301
TBB LINEAR FT
1/0
2/0
3/0
4/0
250KCMIL
300KCMIL
500KCMIL
350KCMIL
600KCMIL
750KCMIL
TBB SIZE (AWG)
FOR OFFICIAL USE ONLY
www.coffman.com
701 Corporate Center Drive, Suite 475
Raleigh, NC 27607 ph 919.314.6686
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTSFacilities Management
Services
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
12/18/2025
A u to d e s k D o c s /A s h e v ill e E
H R
M
V
/6
-2
-7
.0
.E .A
S H
E
H R
M .r v t
/1 /2
:5
:4
P M
03-TN601
TELECOMMUNICATIONS DIAGRAMS
Awen Solutions Group
215 N. Payne Street, Suite 122
Alexandria, VA 22314
12.19.2025
EHRM INFRASTRUCTURE
UPGRADES BLDG 3
1100 TUNNEL ROAD
ASHEVILLE, NC 28805
637-22-700
N.T.S.
1 CABINET ELEVATIONS
N.T.S.
2 TELECOMMUNICATIONS RISER DIAGRAM
N.T.S.
3 TELECOMMUNICATIONS GROUNDING RISER DIAGRAM
Revisions: Date: SHEET 78 of 559
NEW TE
360°
DPS
W
XT
OFFICE
ENTRY
HALL
OFFICE
OFFICE OFFICE OFFICE
OFFICE
NEW TE
360°
DPS
OFFICE
HALL
TOILET TOILET
CLOSET CLOSET
HALL
OFFICE
OFFICEOFFICEOFFICEOFFICE
X
T
VENDOR CONTACT INFORMATION:
BRIAN SHALLENBERGER
JOHNSON CONTROLS
GREENVILLE-SPARTANBURG, SC
BRIAN.SHALLENBERGER@JCI.COM
SYMBOLS LEGEND:
COORDINATE MOUNTING HEIGHTS AND INSTALLATION DETAILS WITH ARCHITECTURAL
DRAWINGS.
BASE BUILDING SECURITY SYSTEM IS JOHNSON CONTROLS (JCI). COORDINATE SECURITY
SYSTEM CABINETS, HEAD-ENDS, AND ASSOCIATED INFRASTRUCTURE TO FEED NEW
CAMERA AND ACCESS CONTROL DEVICES WITH BASE BUILDING SECURITY VENDOR.
CONTRACTOR TO SUBMIT SHOP DRAWINGS FOR REVIEW AND APPROVAL BY AE WHICH ARE
PREPARED BY BASE BUILDING SECURITY SYSTEM VENDOR. DRAWINGS TO INCLUDE ALL
NECESSARY COMPONENTS AND BACK-END EQUIPMENT LOCATIONS FOR A COMPLETE AND
FULLY FUNCTIONAL SYSTEM.
CONTRACTOR SHALL VERIFY IN FIELD EXISTING AVAILABLE NETWORK SWITCHES. NEW
CAMERAS SHALL BE CONNECTED TO NEAREST AVAILABLE NETWORK SWITCH. FOR BID
PURPOSES, ASSUME 300FT CABLE LENGTH FROM CAMERA TO SECURITY SWITCH.
ACCESS CONTROL SYSTEM: NEW ACCESS CONTROL PROVISIONS TO BE INSTALLED FOR
ALL NEW, RELOCATED, OR EXPANDED TELECOM ROOMS. CONTRACTOR TO COORDINATE
ALL HARDWARE AND LOCATIONS WITH BASE BUILDING SECURITY SYSTEM VENDOR AND VA
STAFF.
SSTV SYSTEM: NEW SECURITY CAMERAS TO BE INSTALLED FOR ALL NEW, RELOCATED, OR
EXPANDED TELECOM ROOMS. CONTRACTOR TO COORDINATE ALL HARDWARE AND
LOCATIONS WITH BASE BUILDING SECURITY SYSTEM VENDOR AND VA STAFF.
ALL CONDUIT AND BACK BOXES REQUIRED FOR THE INSTALLATION OF SECURITY DEVICES
AND EQUIPMENT TO BE PROVIDED BY DIV. 26 CONTRACTOR. COORDINATE WITH THE VA
FACILITIES DEPARTMENT FOR EXACT LOCATION OF DEVICES.
REFERENCE ARCHITECTURAL SHEETS FOR ALL DOOR TYPES, ENCLOSURES, FRAME
DETAILS AND PATHWAYS.
ALL TELECOM RACKS TO BE PROVIDED BY DIV. 27 CONTRACTOR.
ALL SECURITY HEAD-END EQUIPMENT IS EXISTING TO REMAIN. EXISTING CAMERAS BEING
FED FROM DECOMMISSIONED TELECOM RACKS, PER TELECOM DRAWINGS AND SCOPE,
SHALL BE RE-FED FROM NEW/REPLACEMENT RACKS IN NEW TELECOM ROOM LOCATION.
COORDINATE WITH TELECOM DRAWINGS FOR MORE INFORMATION.
COORDINATE WITH DOOR HARDWARE SCHEDULE IN ARCHITECTURAL DRAWING SET FOR
LOCKING MECHANISM TYPE FOR SECURITY INTEGRATION (ELECTRIC LATCH, ELECTRIC
STRIKE, MAGNETIC LOCK). PROVIDE ALL HARDWARE AND ACCESSORIES NECESSARY.
MOTION DETECTOR REX TO BE PROGRAMMED AND INTEGRATED WITH DOOR HARDWARE
TO PREVENT LOCKING OF DOOR IF ROOM IS OCCUPIED. INSTALL REX MOTION SENSOR
ABOVE DOOR FRAME.
PROVIDE TRI-TECH MOTION SENSOR IN TR'S (SEPARATE FROM REX) FOR ROOM
OCCUPANCY MONITORING TIED TO PACS SYSTEM.
SUBMIT COMPLETE ACCESS CONTROL AND VIDEO SURVEILLANCE SUBMITTAL PACKAGE
PER SPECIFICATION SECTIONS 282300-1.5D AND 281300-1.4D.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
CARD READER WITH KEYPAD (W - WALL MTD)
CEILING MTD. CAMERA, 360 DEGREE, W/ SUPPLEMENTAL IR RING.360°
W
ELECTRONIC LOCK
SECURITY ACCESS, SWITCH, BALANCED MAGNETIC CONTROL
MOTION DETECTOR
T-ROOM OCCUPANCY MOTION SENSOR (TRI-TECH- PIR, MICROWAVE, DOPPLER)
X-REQUEST-TO-EXIT MOTION SENSOR (DUAL TECH- PIR, MICROWAVE)
DPS ACCESS CONTROL DOOR POSITION SWITCH
FINAL BID DOCUMENTS
PLAN
NORTH
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTS
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
SHEET NOTES:
FOR OFFICIAL USE ONLY
Facilities Management
Services
A u to d e s k D o c s /A s h e v ill e E
H R
M
V
/6
-2
-7
.0
.A .A
S H
E
H R
M .r v t
/1 /2
:4
:1
A
M
03-TY102
1ST & 2ND FLOOR SECURITY PLANS
Awen Solutions Group
215 N. Payne Street, Suite 122
Alexandria, VA 22314
12.19.2025
EHRM INFRASTRUCTURE
UPGRADES 3
1100 TUNNEL ROAD
ASHEVILLE, NC 28805
637-22-700
1/4" = 1'-0"
1 1ST FLOOR SECURITY PLAN
1/4" = 1'-0"
2 2ND FLOOR SECURITY PLAN
2 2 4 6 8 10
1/4" = 1'-0"
FEETSCALE
SHEET 79 of 559
Sheet List
BLDG 4
01-GENERAL
04-GI001 COVER SHEET
7-STRUCTURAL
04-SF101 STRUCTURAL 1ST & 2ND FLOOR PLAN
08-ARCHITECTURE
04-AE101 BASEMENT, 1ST & 2ND FLOOR PLANS, ENLARGED PLANS, ELEVATION
15-ELECTRICAL
04-ED100 ELECTRICAL BASEMENT DEMOLITION
04-ED101 ELECTRICAL 1ST & 2ND FLOOR DEMOLITION
04-EP100 ELECTRICAL BASEMENT PLAN
04-EP101 ELECTRICAL 1ST & 2ND FLOOR PLAN
04-EP601 ONE-LINE DIAGRAM AND SCHEDULES
16-TELECOMMUNICATION
04-TD100 TELECOMMUNICATIONS BASEMENT DEMOLITION
04-TD101 TELECOMMUNICATIONS 1ST & 2ND FLOOR DEMOLITION
04-TD601 TELECOMMUNICATIONS DEMOLITION RACK ELEVATIONS
04-TN100 TELECOMMUNICATIONS BASEMENT PLAN
04-TN101 TELECOMMUNICATIONS 1ST & 2ND FLOOR PLAN
04-TN601 TELECOMMUNICATIONS DIAGRAMS
16.4 - PHYSICAL SECURITY
04-TY101 1ST & 2ND FLOOR SECURITY PLANS
Grand total: 15
SITE KEY PLAN
TUNNELL ROAD
R
IC
E V
IL
L E
R O
A D
V E
T E
R A
N S
D R
IV
E
ARNOLD ROAD
A R
N O
L D
R O
A D
FINAL BID DOCUMENTS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTS
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
DESIGN TEAM
OWNER
ARCHITECT / CONTRACT PRIME
MECHANICAL / ELECTRICAL /
PLUMBING / FIRE PROTECTION /
STRUCTURAL ENGINEER
Charles George VA Medical Center 1100 Tunnel Road Asheville, NC 28805 Contact: Daniel Chaparro Office: (916) 843-7187 Cell: (916) 542-3038
Awen Solutions Group 215 N. Payne Street, Suite 122 Alexandria, VA 22314 Contact: Amy Carr acarr@awensolutions.com
(720) 703-0640
Coffman Engineers, Inc.
701 Corporate Center Drive, Suite 475 Raleigh, NC 27607 Contact: Lars Iverson lars.iverson@coffman.com
(919) 670-3668
EHRM INFRASTRUCTURE UPGRADES
FINAL BID DOCUMENTS
FOR OFFICIAL USE ONLY
Facilities Management
Services
A u to d e s k D o c s /A s h e v ill e E
H R
M
V
/6
-2
-7
.0
.A .A
S H
E
H R
M .r v t
/1 /2
:4
:3
A
M
04-GI001
COVER SHEET
Awen Solutions Group
215 N. Payne Street, Suite 122
Alexandria, VA 22314
12.19.2025
EHRM INFRASTRUCTURE
UPGRADES 4
1100 TUNNEL ROAD
ASHEVILLE, NC 28805
637-22-700
CHARLES GEORGE VA MEDICAL CENTER
12.19.2025
1100 TUNNEL ROAD ASHEVILLE, NC 28805
BLDG 4
SHEET 80 of 559
CONSULT
MALE TLT.
HAC
FEMALE TLT.
BREAKROOM
OFFICE
CONFERENCE
ROOM
VETERAN GROUP
RM
OFFICE
ENTRY
ENTRY
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
TLT.
TLT.
GENERAL NOTES:
1. FIRE/SMOKE WALL RECORD DRAWINGS WERE NOT PROVIDED BY THE STATION. FIELD-VERIFY EXISTING PARTITION WALLS TO IDENTIFY FIRE/SMOKE RATING AND PROVIDE ALL REQUIRED MEASURES AND APPROPRIATE EQUIPMENT IN ACCORDANCE WITH
THE VERIFIED PARTITION TYPE.
2. FIELD VERIFY EXISTING CONDITIONS.
(N) WALL MOUNTED TELECOM ENCLOSURE. PROVIDE BACKING PER DETAIL
WALL MOUNT ENCLOSURE TO BACKING PER MANUFACTURER'S
INSTALLATION INSTRUCTIONS.
00-S503
PLAN
NORTH
N
FINAL BID DOCUMENTS
FOR OFFICIAL USE ONLY
www.coffman.com
701 Corporate Center Drive, Suite 475
Raleigh, NC 27607 ph 919.314.6686
2 2 4 6 8 10
1/4" = 1'-0"
FEETSCALE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTS
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
SHEET NOTES:
03/04/24
Facilities Management
Services
A u to d e s k D o c s /A s h e v ill e E
H R
M
V
/6
-2
-7
.0
.S .A
S H
E
H R
M .r v t
/1 /2
:2
:3
P M
04-SF101
STRUCTURAL 1ST & 2ND FLOOR PLAN
Awen Solutions Group
215 N. Payne Street, Suite 122
Alexandria, VA 22314
12.19.2025
EHRM INFRASTRUCTURE
UPGRADES BLDG 4
1100 TUNNEL ROAD
ASHEVILLE, NC 28805
637-22-700
1/4" = 1'-0"
1 STRUCTURAL 1ST FLOOR PLAN
1/4" = 1'-0"
2 STRUCTURAL 2ND FLOOR PLAN
DU MBHRevisions: Date:
11 12/19/2025 SHEET 81 of 559
CONSULT
MALE TLT.
HAC
FEMALE TLT.
BREAKROOM
OFFICE
CONFERENCE
ROOM
VETERAN GROUP
RM
OFFICE
04-AE101
ENTRY
ENTRY
BASEMENT
B002
BASEMENT
B001
D09
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
TLT.
TLT.
04-AE101
T01
A03
T02
46 TOTAL WAOS/48 (MAX. WAO
PER TE) = 0.96 TE'S REQUIRED IN
BLDG 4 (2 TE'S PROVIDED). (1)
HALF-HEIGHT (12 RU) TE BEING
PROVIDED PER FLOOR
04-AE101
BREAKROOM
D01
T01
A03
T02
46 TOTAL WAOS/48 (MAX.
WAO PER TE) = 0.96 TE'S
REQUIRED IN BLDG 4 (2 TE'S
PROVIDED). (1) HALF-HEIGHT
(12 RU) TE BEING PROVIDED
PER FLOOR
04-AE1017
OFFICE
D01
T01
A03
T02
1. COORDINATE WITH FIRE PROTECTION, MECHANICAL, ELECTRICAL, PLUMBING,
TELECOMMUNICATIONS, AND SECURITY PLANS FOR ADDITIONAL
REQUIREMENTS NOT SHOWN ON THIS DRAWING.
2. DIMENSIONS PRECEDED BY A TILDE (~) ARE APPROXIMATE, SUBJECT TO FIELD
VERIFICATION.
3. ASBESTOS-CONTAINING PIPE INSULATION AND FITTINGS MAY BE FOUND IN
PIPE CHASES, WALLS AND OTHER HIDDEN AREAS THROUGHOUT THE
BUILDING. IF THESE MATERIALS HAVE TO BE DISTURBED DURING THE
PROJECT, ABATEMENT MUST BE CONDUCTED PER SPECIFICATION 02 82 11.
4. ASPHALT ROOFING MATERIALS SHOULD BE ASSUMED TO CONTAIN
ASBESTOS. IF THESE MATERIALS HAVE TO BE DISTURBED DURING THE
PROJECT, ABATEMENT MUST BE CONDUCTED PER SPECIFICATION 02 82 13.21.
5. FIRE/SMOKE WALL RECORD DRAWINGS WERE NOT PROVIDED BY THE
STATION. FIELD-VERIFY EXISTING PARTITION WALLS TO IDENTIFY FIRE/SMOKE
RATING AND PROVIDE ALL REQUIRED MEASURES AND APPROPRIATE
EQUIPMENT IN ACCORDANCE WITH THE VERIFIED PARTITION TYPE.
T01
A03
T02
PLASTIC SHEETING (VISQUEEN)
DEMOLITION LEGEND
WALK-OFF MATS
FINAL BID DOCUMENTS
PLAN
NORTH
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
OVERALL PLAN SHEET NOTES
TR LEGEND
TR TO BE DECOMMISSIONED
EXISTING TR
NEW TR
EXPANDED TR
NEW DATA CENTER
NEW TELECOM ENCLOSURE (TE)
EXISTING DATA CENTER
ENTRANCE ROOM
FINAL BID DOCUMETNS
FOR OFFICIAL USE ONLY
Facilities Management
Services
A u to d e s k D o c s /A s h e v ill e E
H R
M
V
/6
-2
-7
.0
.A .A
S H
E
H R
M .r v t
/1 /2
:4
:3
A
M
04-AE101
BASEMENT, 1ST & 2ND FLOOR PLANS,
ENLARGED PLANS, ELEVATIONAwen Solutions Group
215 N. Payne Street, Suite 122
Alexandria, VA 22314
12.19.2025
EHRM INFRASTRUCTURE
UPGRADES 4
1100 TUNNEL ROAD
ASHEVILLE, NC 28805
637-22-700
1/4" = 1'-0"
2 OVERALL FLOOR PLAN - 1ST FLOOR
1/4" = 1'-0"
1 OVERALL FLOOR PLAN - BASEMENT
1/4" = 1'-0"
3 OVERALL FLOOR PLAN - 2ND FLOOR
3/8" = 1'-0"
4 ENLARGED PLAN - 1ST FLOOR (TE)
3/8" = 1'-0"
5 ENLARGED PLAN - 2ND FLOOR (TE)
KEY TAG DESCRIPTION
A03 4'-0" x 8'-0" AC GRADE 3/4" TRADE SIZE FIRE RATED PLYWOOD
BACKBOARD PAINTED HIGH-GLOSS WHITE WITH TWO COATS OF FIRE
RESISTANT PAINT
D01 PROVIDE WALK OFF MATS AND PLASTIC SHEETING (VISQUEEN) AT
CONSTRUCTION AREAS.
D02 REMOVE EXISTING CEILING, CEILING SUPPORT, ALL FASTENERS,
LIGHTING FIXTURES, VENTS, AND MEANS OF ATTACHMENT BACK TO
STRUCTURE
D09 REMOVE ALL TELECOMMUNICATIONS EQUIPMENT, SEE
TELECOMMUNICATION DRAWINGS
T01 NEW TELECOMMUNICATIONS ENCLOSURE (TE), SEE
TELECOMMUNICATIONS DRAWINGS
T02 BONDING BUS BAR (SBB), SEE TELECOMMUNICATIONS DRAWINGS
ENLARGED PLAN KEYNOTES
1 1 2 3 4 5 6 7
3/8" = 1'-0"
FEETSCALE
2 2 4 6 8 10
1/4" = 1'-0"
FEETSCALE
3/8" = 1'-0"
7 ELEVATION AT 2ND FL TE
3/8" = 1'-0"
6 ELEVATION AT 1ST FL TE
IF ASBESTO-CONTAINING MATERIAL HAS TO BE DISTURBED DURING THE PROJECT, ABATERMENT MUST BE CONDUCTED PER SPECIFICATION 02 81 11. REFER TO ASBESTOS RE-INSPECTION REPORT FOR MORE...
ABATEMENT QUANTITY SCHEDULE - BLDG. 4
LOCATION MATERIAL DISCRIPTION QUANTITY
FLOOR/ WALL/
CEILING CHASES
ASBESTOS-CONTAINING PIPE INSULATION AND FITTINGS MAY BE
FOUND ON AIR-CELL STEAM LINE INSULATION AND HARD ELBOWS &
FITTINGS ON STEAM LINES.
AS REQUIRED
BASED ON FIELD
CONDITIONS WITHIN
THE WORK AREA
ROOF
ASBESTOS-CONTAINING ASHPHALT SHINGLES, FLET, AND MASTICS
MAY BE FOUND IN ROOF ASSEMBLY.
AS REQUIRED
BASED ON FIELD
CONDITIONS WITHIN
THE WORK AREA
SHEET 82 of 559
040390
N
O
RT
H CAROLIN
A
P R
FO
ESS ON
A L
I
N E
GINEER
(E) 4B
(E) 4A
BASEMENT
B002
BASEMENT
B001
PLAN
NORTH
N
FOR OFFICIAL USE ONLY
www.coffman.com
701 Corporate Center Drive, Suite 475
Raleigh, NC 27607 ph 919.314.6686
2 2 4 6 8 10
1/4" = 1'-0"
FEETSCALE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTSFacilities Management
Services
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
SHEET NOTES:
SHEET OF12/18/2025
A u to d e s k D o c s /A s h e v ill e E
H R
M
V
/6
-2
-7
.0
.E .A
S H
E
H R
M .r v t
/1 /2
:1
:2
P M
04-ED100
ELECTRICAL BASEMENT DEMOLITION
Awen Solutions Group
215 N. Payne Street, Suite 122
Alexandria, VA 22314
12.19.2025
EHRM INFRASTRUCTURE
UPGRADES BLDG 4
1100 TUNNEL ROAD
ASHEVILLE, NC 28805
637-22-700
GENERAL NOTES:
1. REFER TO 00-E001 FOR GENERAL NOTES, DEMOLITION NOTES, AND LEGENDS.
2. DEMOLITION PLANS ARE CONCEPTUAL, NOT ALL DEVICES TO BE DEMOLISHED ARE SHOWN. BASEMENT EQUIPMENT LAYOUT IS
SHOWN BASED ON BEST AVAILABLE INFORMATION.
3. ELECTRICAL PANEL LOCATIONS SHOWN FOR REFERENCE ONLY. ALL PANELS ARE EXISTING TO REMAIN.
1/4" = 1'-0"
1 ELECTRICAL BASEMENT DEMOLITION
DEMOLISH…