Attachment 4 IFC Plans 671A4-22-109 Reconstruct PEMB 115 SEALED.pdf
PDF 26 MB Posted
- Solicitation number
- 36C25725R0051
About this file
This document is a comprehensive set of architectural and engineering design plans for the reconstruction of Building 115 at the Kerrville VA Medical Center in Texas. The project involves constructing a 3,530 square foot, single-story pre-engineered metal building (PEMB) with a mezzanine, classified as a Group U (Utility and Miscellaneous) occupancy with Type II-A construction. The building will have multiple storage areas totaling approximately 3,530 square feet, with an occupant load of 14 people, and will include features such as three 32-inch egress doors, fire protection systems, and accessibility compliant design.
The design documents, dated November 30, 2023, include detailed plans for structural, civil, architectural, mechanical, electrical, and plumbing systems. Key technical specifications include a roof live load of 20 PSF, wind design for 105 mph basic wind speed, and seismic design category A. The project is part of VA South Texas Healthcare System's contract number 36C25720D0060, with the design prepared by OEI-LBL Joint Venture LLC and O'Brien Engineering Inc. The construction will involve site preparation, utility installations, including a new 4-inch water line for fire protection, and adherence to multiple building codes and accessibility standards.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
OWNER
ARCHITECT
STRUCTURAL ENGINEER
O'BRIEN ENGINEERING, INC.
CONTRACT OFFICER REPRESENTATIVE
MECHANICAL, PLUMBING, AND
ELECTRICAL ENGINEER
O'BRIEN ENGINEERING, INC.
R. L. WOODS & ASSOCIATES (RLWA)
VA SOUTH TEXAS HEALTHCARE SYSTEM
MS. MARIA HERNANDEZ
FIRE PROTECTION ENGINEER
SEBENCH ENGINEERING, INC
VICINITY MAP
NOT TO SCALE
N
KERRVILLE VA
MEDICAL CENTER
VETERANS H
W
Y
CANYON D
R
NICHO
LS ST
MEMORIAL BLVD
TUCKER S
T
1594 N
REVIERSIDE DR
SP
U
R
BLDG 115
GUADALUPE REVIER
PROJECT DESCRIPTION
• 3,530 SF, 21'-7" TALL, 1 STORY W/ MEZZANINE, SPRINKLERED
• OCCUPANCY CLASSIFICATIONS:
GROUP U: UTILITY AND MISCELLANEOUS (AGRICULTURAL BUILDING)
• CONSTRUCTION TYPE: II-A
QUALITY CONTROL CERTIFICATION
I HEREBY CERTIFY THAT THE DRAWINGS SHOWN AND MARKED IN THIS
SUBMITTAL, THAT ARE PROPOSED TO BE INCORPORATED INTO CONTRACT
NUMBER 36C25720D0060, ARE IN COMPLIANCE WITH THE CONTRACT
DOCUMENTS, AND ARE SUBMITTED FOR GOVERNMENT APPROVAL.
DESIGNER OF RECORD (DOR):
DESIGN QUALITY CONTROL MANAGER (DQC):
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
APPROVING OFFICIAL:
COR, MS. MARIA HERNANDEZ
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A/E:
OEI-LBL Joint Venture LLC
2340 E. Trinity Mills Rd. Ste 220
Carrollton, TX 75006
O'Brien Engineering Inc., Managing Partner
972-233-2288
115O'Brien Engineering, Inc.
Carrollton, TX 75006
972-233-2288
2340 E. Trinity Mills Rd. Ste 220 www.obrieneng.com
A/E:
www.obrieneng.com
GI001
COVER SHEET RECONSTRUCT BLDG 115
KERRVILLE, TX
671A4-22-109
11/30/2023 JOW CH
ISSUE FOR
CONSTRUCTION
11/30/2023
RECONSTRUCT BLDG 115 : 671A4-22-109
KERRVILLE, TEXAS
VA SOUTH TEXAS HEALTHCARE SYSTEM
SHEET INDEX
SHEET NUMBER SHEET NAME
00_GENERAL
GI001 COVER SHEET
GI002 SYMBOLS AND NOTES
GI101 ACCESSIBILITY STANDARDS
GI102 CODE SUMMARY
GI103 LIFE SAFETY PLAN
GI201 SITE PLAN
05_CIVIL
CU101 UTILITY PLAN
CU501 CIVIL AND UTILITY DETAILS
07_STRUCTURAL
SS001 GENERAL NOTES
SS002 SPECIAL INSPECTIONS NOTES
SS101 FOUNDATION DETAILS
SS201 FOUNDATION & MEZZANINE FRAMING PLANS
SS301 FRAMING DETAILS
08_ARCHITECTURAL
AD101 DEMOLITION PLAN
AS111 FLOOR PLAN / DIMENSIONS
AS121 FINISH PLAN
AS131 EQUIPMENT PLAN
AS141 REFLECTED CEILING PLAN
AS151 ROOF PLAN
AS200 EXTERIOR ELEVATION
AS300 BUILDING SECTIONS
AS301 WALL SECTIONS
AS310 SECTION DETAILS
SHEET INDEX
SHEET NUMBER SHEET NAME
AS410 STANDARD PARTITION TYPES
AS500 STAIR DETAILS
AS600 DOOR & WINDOW SCHEDULES AND DETAILS
AS900 PERSPECTIVE VIEW
10_FIRE PROTECTION
FA100 FIRE ALARM DETAILS
FA101 FIRE ALARM PLAN
FP100 FIRE PROTECTION NOTES AND DETAILS
FP101 FIRE PROTECTION PLAN
11_PLUMBING
P001 COVERSHEET - GENERAL NOTES
P002 COVER SHEET - GENERAL NOTES, SYMBOLS & LEGENDS
PP101 PLUMBING PLAN - LEVEL 1
PP102 PLUMBING PLAN - MEZZANINE
PP501 PLUMBING DETAILS AND SCHEDULES
PP901 PLUMBING ISOMETRICS
13_MECHANICAL
M001 COVER SHEET - GENERAL NOTES
M002 COVER SHEET - GENERAL NOTES, SYMBOLS & LEGENDS
MD101 OVERALL MECHANICAL DEMOLITION PLAN - LEVEL 1
MH101 OVERALL MECHANICAL HVAC PLAN - LEVEL 1
14_ELECTRICAL
E001 COVER SHEET - GENERAL NOTES - SHEET LOG
E002 COVER SHEET - GENERAL NOTES
E003 COVER SHEET - SYMBOLS & ABBREVIATIONS
ED101 ELECTRICAL DEMOLITION PLAN - LEVEL 1
SHEET INDEX
SHEET NUMBER SHEET NAME
ED102 ELECTRICAL DEMOLITION PLAN - MEZZANINE
EL101 ELECTRICAL LIGHTING PLAN - MEZZANINE
EL102 ELECTRICAL LIGHTING PLAN - UNDER MEZZANINE
EP101 ELECTRICAL POWER PLAN - LEVEL 1
EP102 ELECTRICAL POWER PLAN - MEZZANINE
EP501 ELECTRICAL POWER DETAILS
EP601 SCHEDULES & DIAGRAMS
EP701 ELECTRICAL SITE PLAN
EP900 ELECTRICAL ONELINE DIAGRAM
Revisions: Date:
BATT. INSULATION
CAST IN PLACE CONCRETE
CAST STONE
CONCRETE MASONRY/CMU
EARTH IN SECTION
FACE BRICK
GYP./GYPSUM BOARD
MARBLE
PARTICLE BOARD/PLYWOOD
ROOF INSULATION
STUCCO
CONTINUOUS WOOD BLOCKING
DISCONTINUOUS WOOD BLOCKING
FINISHED WOOD
0 COLUMN GRID LINE
DOOR NUMBER
SYMBOL
DETAIL - SECTION
POSITION ON SHEET
SHEET NUMBER
DETAIL - PLAN/ RCP
POSITION ON SHEET
SHEET NUMBER
WALL SECTION
POSITION ON SHEET
SHEET NUMBER
EXTERIOR ELEVATION
POSITION ON SHEET
SHEET NUMBER
INTERIOR ELEVATION
POSITION ON SHEET
SHEET NUMBER
EXTERIOR WALL TYPE TAG
EXTERIOR WINDOW
SIGN TYPE, SEE SIGNAGE
SCHEDULE
DRAWING NUMBER
DRAWING SCALE
VIEW TITLE
NOTES BY NUMBER
DRAWING REVISION
LEVEL DATUM
LEVEL NAME
LEVEL ELEVATION
NORTH ARROW
INTERIOR WINDOW
GRAPHIC SCALE
0 4'-0" 8'-0" 16'-0"
-G D
XX
XX
XXXX
7'-0" R 3'-11"
100°
SIM
X
X-XXX
DIMENSION TO FACE OF FINISH,
FACE OF CONCRETE, COLUMN
CENTERLINE, OR AS NOTED.
CENTERLINE
X
X X
X
A1
A101
SIM
A101
SIM
ROOM TAG (FOR SPECIALTY PLANS)
ROOM NAME
ROOM NUMBER
FLOOR FINISH
ROOM NAME
XXXX
FLOR
BASE
WALL
CEIL BASE TYPE
WALL FINISH
CEILING TYPE
A
A101
SIM
Name Elevation
1/8" = 1'-0"
AC1
N
INTERIOR PARTITION TYPE TAGA3
ROOM NAME
150 SF
ROOM NAME
ROOM NUMBER
ROOM AREA
ROOM TAG (FOR STANDARD PLANS)
BUILDING SECTION
POSITION ON SHEET
SHEET NUMBER
A101
SIM
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
APPROVING OFFICIAL:
COR, MS. MARIA HERNANDEZ
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A/E:
OEI-LBL Joint Venture LLC
2340 E. Trinity Mills Rd. Ste 220
Carrollton, TX 75006
O'Brien Engineering Inc., Managing Partner
972-233-2288
115O'Brien Engineering, Inc.
Carrollton, TX 75006
972-233-2288
2340 E. Trinity Mills Rd. Ste 220 www.obrieneng.com
A/E:
www.obrieneng.com
GI002
SYMBOLS AND NOTES RECONSTRUCT BLDG 115
KERRVILLE, TX
671A4-22-109
11/30/2023 JOW CH
ISSUE FOR
CONSTRUCTION
11/30/2023
DRAWING LEGENDABBREVIATIONS
ACT. ACTUAL
ADJ. ADJUSTABLE
A.F.F. ABOVE FINISH FLOOR
A.F.S. ABOVE FINISH SLAB
AGG. AGGREGATE
AHJ AUTHORITY HAVING JURISDICTION
ALUM. ALUMINUM
BLDG. BUILDING
BK. BRICK
BM. BEAM
CAB. CABINET
CPT. CARPET
C.J. CONTROL JOINT
CENTERLINE
CG CORNER GUARD
CLG. CEILING
COL. COLUMN
CONC. CONCRETE
COND. CONDITION
CONT. CONTINUOUS
C.T. COUNTERTOP
DBL. DOUBLE
DEMO. DEMOLITION
DIA. DIAMETER
DIM. DIMENSION
DISP. DISPENSER
DN. DOWN
DWG. DRAWING
E.W.C. ELECTRIC WATER COOLER
EA. EACH
E.J. EXPANSION JOINT
EXP. EXPANSION
E.W. EACH WAY
EXT. EXTERIOR
EXIST. EXISTING
F.E.C. FIRE EXTINGUISHER CABINET
F.D. FINISH DIMENSION
F.D.V.B. FIRE DEPARTMENT VALVE BOX
F.F. FINISH FLOOR
FIN. FINISH(ED)
FRT. FIRE RETARDANT TREATED
G.I. GALVANIZED IRON
G.B./GYP.BD. GYPSUM BOARD
GA. GAUGE
GALV. GALVANIZED
GL. GLASS
H.M. HOLLOW METAL
H.S. HORIZONTAL IN SPLASH
I.C.U. INTENSIVE CARE UNIT
INT. INTERIOR
INSUL. INSULATION
I.T.C. INSTALLED THIS CONTRACT
K.S. KNEE SPACE
LAM. LAMINATED
LAV. LAVATORY
L.L.V. LONG LEG VERTICAL
L.L.H. LONG LEG HORIZONTAL
MANUF. MANUFACTURER
MAX. MAXIMUM
MECH. MECHANICAL
MIN. MINIMUM
M.O. MASONRY OPENING
MTL./MET. METAL
MNT. MOUNTED
N/A NOT APPLICABLE
NOM. NOMINAL
N.T.S. NOT TO SCALE
N.I.C. NOT IN CONTRACT
O.C. ON CENTER
O.D. OVERFLOW DRAIN
O.H/OPP.H. OPPOSITE HAND
P.D. PLAN DIMENSION
PLAS. LAM. PLASTIC LAMINATE
P.T. PORCELAIN TILE
P.T.D. PAPER TOWEL DISPENSER
RB RUBBER BASE
R./REV. REVISED/REVERSE
R./RAD. RADIUS
REINF. REINFORCE
REF. REFERENCE/REFER TO
REQ'D REQUIRED
R.D. ROOF DRAIN
RM. ROOM
R.O. ROUGH OPENING
SCHED. SCHEDULED
SAB. SOUND ATTENUATION BATTS
SHT. SHEET
SIM. SIMILAR
SL. SLOPE
STL. STEEL
S.S. STAINLESS STEEL
S.S.V. SOLID SURFACE VENEER
SUSP. SUSPENDED
S.V. SHEET VINYL
T.A.S. TEXAS ACCESSIBILITY STANDARDS
T.B. TACK BOARD
T.D.H. TEXAS DEPARTMENT OF HEALTH
TEMP. TEMPERED GLASS
THK. THICK
TOIL. TOILET
TYP. TYPICAL
U.C. UNDER COUNTER
UCR UNDER COUNTER REFRIGERATOR
U.L. UNDERWRITERS LABORATORIES
U.N.O. UNLESS NOTED OTHERWISE
UR. NEW URINAL
VCT VINYL COMPOSITION TILE
V.T. VINYL TILE
VERT. VERTICAL
W.C. NEW WATER CLOSET
WDW. WINDOW
WD. WOOD
WH WATER HEATER
W/ WITH
W/O WITHOUT
MATERIALS LEGEND GENERAL NOTES
1. ALL WORK RELATING TO THIS CONSTRUCTION SHALL COMPLY WITH U.S. DEPARTMENT OF
LABOR, THE OCCUPATIONAL SAFETY AND HEALTH STANDARDS AND ALL RELATED LOCAL AND
FEDERAL BUILDING CODES AND ORDINANCES.
2. DO NOT SCALE THE DOCUMENTS.
3. ALL DIMENSIONS ARE TO BE FIELD VERIFIED AND BACK CHECKED FOR CORRECTNESS. IF ANY
DEVIATIONS OR DISCREPANCIES OCCUR, CONTACT CONTRACTING OFFICER REPRESENTATIVE
(COR) FOR VERIFICATION PRIOR TO PROCEEDING WITH THE WORK.
4. THE GENERAL CONTRACTOR IS TO VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS ON THE
SITE PRIOR TO THE BEGINNING OF THE WORK AND ADVISE THE COR OF ANY AND ALL
DISCREPANCIES.
5. ALL DIMESIONS ON PLANS ARE TO FACE OF FINISHED WALL, METAL PANEL OR CENTER LINE OF
STRUCTURAL COLUMNS.
6. THE GENERAL CONTRACTOR AND ALL SUBCONTRACTORS SHALL CAREFULLY REVIEW THE
DRAWINGS, SPECIFICATIONS DETAILS AND NOTES FOR INFORMATION REGARDING THE SCOPE
OF WORK INTENDED PRIOR TO PROCEEDING WITH THE WORK.
7. THE CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE ALL MECHANICAL, ELECTRICAL,
AND PLUMBING PENETRATIONS REQUIRED BY THE WORK WHETHER EXPRESSLY NOTED IN THE
DOCUMENTS OR NOT.
8. FIRE SPRINKLER HEAD LOCATIONS ARE TO BE COORDINATED WITH LIGHTING
9. THE CONTRACTOR SHALL REVIEW THE SOILS REPORT, AND THESE DOCUMENTS (ALL IN THEIR
ENTIRETY) TO INSURE THAT ALL REQUIRED EARTHWORK, PAVING, AND STRUCTURAL SLAB
WORK IS FULLY COVERED IN THE SCOPE OF THE CONTRACTOR'S BID. THE CONTRACTOR SHALL
FULLY COORDINATE ALL OF THE ABOVE REFERENCED WORK WITH THE OWNER'S
REPRESENTATIVE TO INSURE THAT ALL WORK IS FULLLY COORDINATED AND COMPLETED.
10. ALL MATERIALS SHALL BE INSTALLED ACCORDING TO INDUSTRY STANDARDS, ALL AGENCIES OR
"STANDARD" RECOMMENDATIONS REFERENCED IN THE SPECIFICATIONS, OR MANUFACTURER'S
RECOMMENDED INSTALLATION PROCEDURES, WHICHEVER IS THE MOST STRINGENT.
11. THE CONTRACTOR REPRESENTS AND WARRANTS THAT IT HAS EXAMINED THE PLANS,
DRAWINGS, SPECIFICATIONS AND ALL CONSTRUCTION CRITERIA OF THE OWNER AND HAS
SATISFIED ITSELF THAT THE INFORMATION CONTAINED THEREIN IS SUFFICIENT TO FULLY AND
COMPLETELY CONSTRUCT THE PROJECT.
12. IN THE EVENT OF A CONFLICT WITH THE CONSTRUCTION DOCUMENTS, THE MORE EXPENSIVE, GREATER QUALITY, AND LARGER SCOPE SHALL GOVERN.
13. THE CONTRACTOR SHALL PROVIDE ALL NECESSARY BLOCKING IN WALLS / PARTITIONS FOR
THE MOUNTING OF EQUIPMENT, ACCESSORIES, ETC. THAT ARE PROVIDED BY THE
CONTRACTOR OR THE OWNER.
A/C AIR CONDITIONING
ACT ACOUSTICAL CEILING TILE
AD AREA DRAIN
ADB AUTOMATIC DOOR BUTTON
ADD ADDENDUM
ADDL ADDITIONAL
ADJ ADJUSTABLE/ ADJACENT
AFF ABOVE FINISH FLOOR
AGGR AGGREGATE
ALT ALTERNATE/ ALTERERATION
ALUM ALUMINUM
AMT AMOUNT
ANCH ANCHOR
ANDD ANODIZED
APPROX APPROXIMITE(LY)
ARCH ARCHITECTURAL
ARF ABOVE REFERENCE FLOOR
ASPH ASPHALT(IC)
ASST ASSISTANT
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AVG AVERAGE
BAL BALANCE
BB BULLETIN BOARD
B/C BOTTOM OF CURB
BD BOARD
BL BUILDING LINE
BLDG BUILDING
BLK BLOCK(ING)
BM BENCH MARK/BEAM
B.O. BOTTOM OF
BOT BOTTOM
BSMT BASEMENT
CAB CABINET
CB CATCH BASIN
C/C CENTER TO CENTER
CCTV CLOSED CIRCUIT TV
CEMPL CEMENT PLASTER
CER CERAMIC
CG CORNER GUARD
CH COAT HOOK
CHAN CHANNEL
CHKBD CHALKBOARD
CIP CAST-IN-PLACE (CONCRETE)
CJ CONTROL JOINT
CL CENTER LINE/ CLEARANCE
CLG CEILING
CLR CLEAR
CMT CERAMIC MOSAIC TILE
CMU CONCRETE MASONRY UNIT
CNTR COUNTER
CO CLEAN OUT
COL COLUMN
COMB COMBINATION/ COMBUSTIBLE
COMP COMPRESS(ED)/ COMPOSITE
CONC CONCRETE
COND CONDUIT/ CONDITION
CONF CONFERENCE
CONN CONNECT(ION)
CONST CONSTRUCTION
CONT CONTINUE/ CONTINUOUS
CONTR CONTRACTOR
COORD COORDINATOR
CORR CORRIDOR
CPT CARPET
CSWK CASEWORK
CT CERAMIC TILE
CTR CENTER
CU CLEAN UTILITY ROOM
D DETENTION
D.A.F.S DIRECT APPLIED FINISH SYSTEM
DBL DOUBLE
DE DETENTION EQUIPMENT
DEG DEGREE(S)
DEMO DEMOLISH/ DEMOLITION
DEPT DEPARTMENT
DET DETAIL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DIV DIVISION/ DIVIDER
DN DOWN
D.D. DOUBLE OCCUPANCY CELL
D.U. DIRTY UTILITY ROOM
DWL DOWEL
DWR DRAWER
EA EACH
EB EXPANSION BOLT
EJ EXPANSION JOINT
ELEC ELECTRIC(AL)
ELEV ELEVATOR/ ELEVATION
ENAM ENAMEL(ED)
EMER EMERGENCY
ENCL ENCLOSURE
ENGR ENGINEER
ENTR ENTRANCE
EPFL EPOXY FLOORING
EPNT EPOXY PAINT
EQ EQUAL
EQUIP EQUIPMENT
ES ELECTRONIC SECURITY
EST ESTIMATE(D)
ETC ET CETERA
EW EACH WAY
EWC ELECTRIC WATER COOLER
EXAM EXAMINATION/ EXAMINING
EXC EXCAVATED/ EXCAVATION
EXH EXHAUST
EXIST(E) EXISTING
EXP EXPOSED/ EXPANSION
EXT EXTERIOR
FA FIRE ALARM
FAB FABRICATE/ FABRICATOR/ FABRIC
FD FLOOR DRAIN
FDC FIRE DEPARTMENT CONNECTION
FDN FOUNDATION
FDPR FIRE DAMPER
FDV FIRE DEPARTMENT VALVE
FDVC FIRE DEPT. VALVE CABINET
FE FIRE EXTINGUISHER
FEB FIRE EXTINGUISHER BRACKET
FEC FIRE EXTINGUISHER CAB.
FH FIRE HYDRANT/ FUME HOOD/ FLAT HEAD
FHC FIRE HOSE CABINET
FHEC FIRE HOSE & EXTINGUISHER CAB.
FIN FINISH(ED)
FL FLOOR LINE/ FLOOR
FLASH FLASHING
FLEX FLEXIBLE
FLR FLOOR(ING)
FLUOR FLUORESCENT
FOS FACE OF STUD
FP FIREPROOF(ING)/ FULL PENETRATION
FRAM(G) FRAMING
FRT FIRE RETARDANT
FS FULL SIZE/ FLOOR SINK
FT FOOT/ FEET
FTG FOOTING
FURR FURRING
FXD FIXED
GA GAUGE/ GAGE
GALV GALVANIZED
GB GRAB BAR
GC GENERAL CONTRACTOR
GEN GENERAL/ GENERATOR
GL GLASS/ GLAZING/ GLAZED
GLAM GLUE LAMINATED
GND GROUND
GWB GYPSUM WALLBOARD
GYP GYPSUM
HA HANDICAPPED ACCESSIBLE
HB HOSE BIBB
HC HOSE CABINET/ HANDICAP/ HOLLOW CORE
H.C.S.D. SINGLE OCCUPANT CELL
HCW HOLLOW CORE WOOD
H/C WTR HOT AND COLD WATER
HDBD HARDBOARD
HDCP HANDICAPPED (ACCESSIBLE)
HDR HEADER
HDWD HEADWOOD
HDWR HARDWARE
HGT(HT) HEIGHT
HM HOLLOW METAL
HR HOUR
HS HOOK STRIP/ HIGH STRENGTH
HSKG HOUSEKEEPING
HTR HEATER
HVAC HEATING/ VENTILATION/ AIR CONDITIONING
HWY HIGHWAY
HYD HYDRANT
ID INSIDE DIAMETER (DIM.)
IE THAT IS
IG INSULATING GLASS
IMP INSULATED METAL PANEL
IN INCH
INCAND INCANDESCENT
INCL INCLUDE(ING)
IND INDUSTRIAL
INFO INFORMATION
ING INSULATING GLASS
INSTIL INSTALLATION/ INSTALL
INSUL INSULATE(D) (ING)
INT INTERIOR
INTER INTERSECTION/ INTERMEDIATE
INV INVERT
ISO ISOLATION CELL
I.T. INMATE TOILET
JAN JANITOR
J.C. JANITOR CLOSET
JST JOIST
JT JOINT
KD KNOCK OUT
KP KICK PLATE
LAB LABORATORY
LAM LAMINATE
LAV LAVATORY
LB(S) LAG BOLT(S)/ POUND(S)
LBL LABEL
LF LINEAL FOOT/ LINEAR FOOT
LH LEFT HAND
LHR LEFT HAND REVERSE
LIN LINEAR
LL LIVE LOAD
L&P LATH & PLASTER
LT(G) LIGHT(ING)
LW LIGHTWEIGHT
MACH MACHINE
MAINT MAINTENANCE
MAS MASONRY
MAT MATERIAL
MAX MAXIMUM
MBR MEMBER
MC MEDICINE CABINET
MCW MINERAL CORE WOOD
MDFB MEDIUM DENSITY FIBER BOARD
MECH MECHANINCAL
MED MEDICAL/ MEDIUM
MED.S. MEDICAL STORAGE
MET METAL
MEZZ MEZZANINE
MFB MINERAL FIBER BOARD
MFR MANUFACTUR(ER) (ING)
MGR MANAGER
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MIR MIRROR
MISC MISCELLANEOUS
ML METAL LATH/ MATCH LINE
MLP METAL LATH AND PLASTER
MMB MEMBRANE
MO MASONRY OPENING
MOD MODULAR/ MODIFIED/ MODICATION
MP MOVABLE PARTITION/ METAL PANEL
MR MET RECESS, MOD RACK
M&S MIRROR & SHELF
MT MOUNT (ED) (ING)
MTR MOTOR
MTL METAL
MUL MULLION
N NORTH
NEG NEGATIVE
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO or # NUMBER
NOM NOMINAL
NONCOM NONCOMBUSTIBLE
NRC NOISE REDUCTION COEFFICIENT
NS NON SLIP
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER (DIM.)
OFD OVERFLOW DRAIN
OFF OFFICE
OH OVERHEAD/ OVERHANG
OPER OPERATING
OPH OPPOSITE HAND
OPN(G) OPEN (ING)
OPP OPPOSITE
PA PUBLIC ADDRESS
PAR PARAGRAPH/ PARAPET
PTN PARTITION (S)
PB PANIC BOLT/ PUSH BUTTON
PBD PARTICLEBOARD
PC PRE-CAST
PED PEDESTAL
PERF PERFORATE (D)
PERIM PERIMETER
PERP PERPENDICULAR
PFB PREFABRICATE (D)
PG PLATE GLASS
PGBD PEGBOARD
PH PHASE/ PAN HEAD
PL PLATE/ PROPERTY LINE
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLBG PLUMBING
PLYWD PLYWOOD
PNEU PNEUMATIC
PNL PANEL
PNT PAINT(ED)
POL POLISH(ED)
PORT PORTABLE
PP PUSH PLATE
PR PAIR, PRINTER, COMPUTER PRINTER
PREFAB PREFABRICATE(D)
PRELIM PRELIMARY
PRESS PRESSURE
PROJ PROJECT(ION)
PROP PROPERTY
PROT PROTECT (IVE) (ION)
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PORCELIN TILE
PTD/R COMBINATRION PAPER TOWEL
DISPENSER & RECEPTACLE
PTR PAPER TOWL RECEPTACLE
PVC POLYVINYL CHLORIDE
PVMT PAVEMENT
QT QUARRY TILE
QTR QUARTER
QUAN QUANITITY
R RADIUS/ RISER/ RESILIENT
RAD RADIATOR/ RADIUS
RB RESILIENT BASE
RCWY RACEWAY
RD ROOF DRAIN/ ROAD
RE: REFER/ REFERENCE
RECEP RECEPTACLE/ RECEPTION
RECIRC RECIRCULATION
RECT RECTANGULAR
RECVD RECIEVED (ING)
REF REFERENCE
REFR REFRIGERATOR
REG REGULATOR/ REGLET/ REGISTER
REINF REINFORCE (D) (ING) (MENT)
REQ(D) REQUIRE (D)
RESIL RESILIENT
RET RETURN
REV REVERSE/ REVISED/ REVISION
RFG ROOFING
RH RIGHT HAND
RHR RIGHT HAND REVERSE
RM ROOM
RND ROUND
RO ROUGH OPENING
ROW RIGHT OF WAY
RS RESILIENT SHEET
R&S ROD AND SHELF
RT RESIDENT TILE
RTN RETURN
SAB SOUND ABSORPTION BATT
SAN SANITARY
SC SOLID CORE
SCHED SCHEDULE
SCN SCREEN
SCW SOLID CORE WOOD
SD SOAP DISPENSER/ SOAP DISH
SECT SECTION
SET SETTING
SF SQUARE FEET
SFC SPECIAL FLOOR COATING
SFP SPRAYED ON FIREPROOFING
SHR SHOWER
SHT SHEET
SK SINK/ SKETCH
SIM SIMILAR
SLR SEALER
SM SHEET METAL
SND SANITARY NAPKIN DISPENSER
SNT SEALANT
SNR SANITARY NAPKIN RECEPTACLE
S.O. SINGLE OCCUPANCY CELL
SP STANDPIPE/ SHEAR PLATE
SPEC SPECIFICATION/ SPECIFIED
SPK SPEAKER
SPL SPECIAL
SPR SPRINKLER
SPNT SPECIAL PAINT
SSK SERVICE SINK
S.T. STAFF TOILET
ST STREET/ STREAM
SST STAINLESS STEEL
STA STATION
STC SOUND TRANSMISSION COEFFICIENT
(CLASS)
STD STANDARD
STL STEEL
STOR STORAGE
STRUC STRUCTURAL
SUBFL SUBFLOOR(ING)
SUP SUPPLY
SUPP SUPPORT/ SUPPLEMENT(AL)
SURF SURFACE
SUSP SUSPEND(ED)
S.V. SAFETY VESTIBULE
S&V STAIN & VARNISH
SWCG SPECIAL WALL COATING
SYM SYMMETRICAL
SYN SYNTHETIC
SYS SYSTEM
T TOP/ TREAD/ TOILET
T&B TOP & BOTTOM
TB TOWEL BAR
TBD TO BE DETERMINED
T/C TOP OF CURB/ TOP OF CONCRETE
TD TOWEL DISPENSER
TEL TELEPHONE
TEMP TEMPERATURE/ TEMPERED/
TEMPORARY
TERR TERRAZZO
TG TEMPERED GLASS
T&G TONGUE AND GROOVE
THB TEMPERED HARDBOARD
THERMO THERMOSTAT(IC)
THK THICK(NESS)
THRES THRESHOLD
THRU THROUGH
TJ TELEPHONE JACK
TKBD TACKBOARD
TOIL TOILET
T.O.M. TOP OF MASONRY
TOP TOPPING
TOS TOP OF STEEL
TPD TOILET PAPER DISPENSER
TR TREAD
TRK TRACK
T/S TOP OF SLAB
TV TELEVISION
T/W TOP OF WALL
TYP TYPICAL
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITERS LABORATORIES, INC.
UNFIN UNFINISHED
UNO UNLESS NOTED OTHERWISE
UR URINAL
UTIL UTILITY
UV UNIT VENTILATOR
VAP VAPOR
VAR VARIABLE/ VARNISH/ VARIES
VB VAPOR BARRIER
V.C. VIOLENT CELL
VEH VEHICLE
VENT VENTILATION/ VENTILATE, VENTILATOR
VEN VENEER
VERT VERTICAL
VEST VESTIBULE
VG VERTICAL GRAIN
VOL VOLUME
VP VENEER PLASTER
W/ WITH
WAIN WAINSCOT
WB WHITE BOARD/ WOOD BASE
WC WATER CLOSET
WCG WALL COVERING
WD WOOD
WDW WINDOW
WF WIDE FLANGE (STEEL)
WG WIRE GLASS/ WALL GRILL
WL WATER LINE
W/O WITHOUT
WP WATERPROOF (ING)/ WORK POINT/ WEATHER
PROOF
WR WATER RESISTANT/ WASTE RECEPTACLE
WT WEIGHT
YD YARD DRAIN
ABBREVIATONS (ARCHITECTURAL ONLY)
HDCP ACCESSIBILITY GENERAL NOTES
1. NOTIFY THE ARCHITECT OF ANY DISCREPANCIES BETWEEN THE ARCHITECTURAL DRAWINGS AND THE INFORMATION
GIVEN ON THIS SHEET.
2. DO NOT SCALE THESE DRAWINGS.
3. DIMENSIONS INDICATED ARE THE MINIMUM CLEAR DIMENSIONS REQUIRED BY THE UNIFORM FEDERAL ACCESSIBILITY STANDARDS (UFAS) AND THE BARRIER FREE DESIGN GUIDE SUPPLEMENT BY THE DEPARTMENT OF THE VA. THE CONTRACTOR IS RESPONSIBLE FOR LAYOUT OF BUILDING ELEMENTS TO ASSURE THAT DIMENSIONS SHOWN ARE
PROVIDED.
4. NOT ALL CONDITIONS SHOWN ON THIS SHEET MAY BE REQUIRED BY THIS PROJECT. COMPARE THE REQUIREMENTS OF
THE ARCHITECTURAL DRAWINGS WITH THIS SHEET FOR RELEVANCE OF INFORMATION.
5. REFERENCE ACCESSIBLE DIMENSIONS LEGEND FOR ACCESIBLE MOUNTING HEIGHTS OF ALL FIXTURES &
ACCESSORIES LOCATED THROUGHOUT CONTRACT DOCUMENTS.
6. DIMENSIONS SHOWN ON INTERIOR ELEVATIONS AT WALLS ARE TO THE FINISHED SURFACE.
7. HANDICAP ACCESSIBLE SHOWERS ARE TO BE RECESSED INTO CONCRETE AT TRANSFER SHOWERS, WRAP AS REQUIRED TO HAVE NO MORE THAN 1/2" LIP AT EDGE OF SHOWER ENTRY (NO LIP AT ROLL-IN SHOWERS)
8. ALL EXPOSED PIPE UNDER SINKS ARE TO BE WRAPPED OR PROTECTED
1/ 2"
M A
X
NOTE: ALL DOORS IN ALCOVES
MUST COMPLY WITH THE
CLEARANCE NOTED FOR FRONT
APPROACHES.
DOOR
THRESHOLD
DETAIL
1' -3
3' -9
ELEC. / COMM
OUTLET
WALL SWITCH
HANDRAIL EXTENTIONS
AT TOP RUN
HANDRAIL EXTENTIONS
AT BOTTOM RUN
ONE TREAD
11" MIN. 1 1/2" MAX.
R 1 1/2"
MINIMUM USABLE AND
MAXIMUM NOSING
DIMENSIONS
(V A
R E
Q 'D
M
IN
. L A
N D
IN
G
'-0
A
T D
O O
R
S (VA REQ'D)
5'-0" MIN.
6'-0" MIN. AT DOORS
MAX. LENGTH= 40' FOR SLOPE LESS THAN 1:25 (VA REQ'D)
MAX. LENGTH= 35' FOR SLOPE OF 1:20 TO 1:25 (VA REQ'D)
(V A
R E
Q 'D
4' -0
M
IN
(V A
R E
Q 'T
HANDLE EXTENTION
1'-0" MIN.
(VA REQ'D)
5'-0" MIN.
6'-0" MIN. AT DOORS
(VA REQ'D)
SLOPE: 1:20 (5%) TO 1:33 (3%)
RAMP DETAIL
1 1/2".
1 1/4" - 1 1/2"
S T
A
IR
N O
S
IN
G A
N D
/O R
R A
M P
S U
R F
A C
E
(V A
R E
Q 'D
T
O P
O F
H A
N D
R A
IL
: 3
4" A
B O
V E
HANDRAIL DETAIL
1 1/4" - 1 1/2"
GRAB BAR DETAIL CHANGES IN LEVEL
1/ 2"
M A
X
1/ 4"
M A
X
HDCP ACCESSIBLE AND STANDARD DIMENSIONS
CLEAR FLOOR
SPACE FOR
WHEELCHAIR
TURNING SPACE
REQUIREMENT
2'-6"
4' -0
(VA REQ'D)
5'-6" MIN.
MANEUVERING CLEARANCES AT ALCOVES
2' -6
4'-0" 1'-0"
2' -6
4'-0"
1' -3
M
A X
4' -0
2'-6"
2' -0
M
A X
4' -0
2'-6" 1'-0"
(VA REQ'D)
5'-0" MIN.
(VA REQ'D)
2'-10" MIN.
2' -0
MAX. DOORWAY DEPTH
(VA REQ'D)
2'-10"
CLEAR
1'-6" MIN.
5' -0
M
IN
2' -0
M
IN
1'-0"
IF CLOSER
AND
LATCH
Y
X
NOTE:
X = 36" MIN.
IF Y = 60";
X = 42" MIN.
IF Y = 54"
5'-6"
3' -6
NOTE: 48" IF
DOOR HAS
BOTH LATCH
AND CLOSER
X: 24" MIN.Y
: 4
8" M
IN
. NOTE:
Y = 54" MIN.
IF DOOR
HAS CLOSER
M
IN
2'-0"
NOTE: Y = 48" MIN.
IF DOOR HAS A
CLOSER
MIN. OPENING WIDTH
4'-0"
4'-0"
MINIMUM PASSAGE
WIDTH
(VA REQ'D)
5'-0" MIN.
3' -9
M
A X
9" M
IN
1'-9" MAX.
HIGH AND LOW REACH
(ADJUSTABLE SHELVES)
MAXIMUM SIDE REACH
OVER AN OBSTRUCTION
2'-6" MIN. 2'-0" MAX.
2' -1
0" M
IN
T O
P O
F R
E A
C H
3' -1
0" M
A X
ADJUSTABLE
SHELVES
X: 4'-0" MAX.
Y : 4
'-0
M A
X
1' -3
M
IN
FORWARD REACH
2'-1" MAX.
R E
A C
H
'-8
3' -8
4'
-0
F O
R H
O R
IZ
O
N T
A L
MAXIMUM FRONT
REACH OVER AN
OBSTRUCTION
DOORWAY CLEARANCES: NOTE: PATIENT BEDROOM DOORS AT LEAST 44" WIDE ARE EXEMPT
FROM THE REQUIREMENTS FOR SPACE OF THE LATCH SIDE OF THE DOOR
1 1/2".
(V A
R E
Q 'T
1'-0" MIN.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
APPROVING OFFICIAL:
COR, MS. MARIA HERNANDEZ
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A/E:
OEI-LBL Joint Venture LLC
2340 E. Trinity Mills Rd. Ste 220
Carrollton, TX 75006
O'Brien Engineering Inc., Managing Partner
972-233-2288
115O'Brien Engineering, Inc.
Carrollton, TX 75006
972-233-2288
2340 E. Trinity Mills Rd. Ste 220 www.obrieneng.com
A/E:
www.obrieneng.com
GI101
ACCESSIBILITY STANDARDS RECONSTRUCT BLDG 115
KERRVILLE, TX
671A4-22-109
11/30/2023 JOW CH
ISSUE FOR
CONSTRUCTION
11/30/2023Revisions: Date:
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
APPROVING OFFICIAL:
COR, MS. MARIA HERNANDEZ
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A/E:
OEI-LBL Joint Venture LLC
2340 E. Trinity Mills Rd. Ste 220
Carrollton, TX 75006
O'Brien Engineering Inc., Managing Partner
972-233-2288
115O'Brien Engineering, Inc.
Carrollton, TX 75006
972-233-2288
2340 E. Trinity Mills Rd. Ste 220 www.obrieneng.com
A/E:
www.obrieneng.com
GI102
CODE SUMMARY RECONSTRUCT BLDG 115
KERRVILLE, TX
671A4-22-109
11/30/2023 JOW CH
ISSUE FOR
CONSTRUCTION
11/30/2023
CODE SUMMARY
REFERENCES
1. International Code Council (ICC)
a. International Building Code (IBC), 2021
b. International Mechanical Code (IMC), 2018
c. International Plumbing Code (IPC), 2021
d. International Energy Conservation Code, 2021
2. National Fire Protection Agency (NFPA)
a. NFPA 101 Life Safety Code, 2018
b. NFPA National Fire Codes (except NFPA 900 & 5000)
c. National Electrical Code (NEC), 2020
3. American Society of Mechanical Engineers (ASME)
a. Safety Code for Elevators and Escalators (ASME A17.1)
b. Boiler and Pressure Vessel Code (BVPC), 2021
c. Code for Pressure Piping
4. American Society of Heating, Refrigeration, and Air-Conditioning Engineers
(ASHRAE)
a. Safety Standard for Refrigeration Systems - ASHRAE Standard 15, 2007
b. Ventilation for Acceptable Indoor Quality - ASHRAE Standard 62.1, 2007
5. Architectural Barriers Act Accessibility Standards (ABAAS)
a. including VA supplement, Barrier Free Design Guide (PG-18-13)
6. Building Code Requirements for Reinforced Concrete, American Concrete Institute and Commentary (ACI 318)
7. Manual of Steel Construction, Load and Resistance Factor Design Specifications for Structural Steel Buildings, American Institute of Steel Construction (AISC)
8. VA Seismic Design Requirements, H-18-8
9. VA Physical Security and Resiliency Requirements, LSP w/ MC Utilities / Systems
Redundancies (Warehouse). Exampt from Section 3.3 Standoff Distance, Chapter 6 Building Envelope, Chapter 7 Structural System (Maintenance Storage (Non-biomedical equipment and Non-Mission Critical equipment support)
10. Other Standards;
a. VA Directives, Design Manuals, Master Specifications, Technical
Information Library
b. Occupational Safety and Health Administration (OSHA) Standards
c. Energy Policy Act of 2005 (EPAct)
d. Executive Order 13423: Strengthening Federal Environmental, Energy, and
Transportation Management
e. Federal Leadership in High Performance and Sustainable Buildings:
Memorandum of Understanding (MOU)
f. DOE Interim Final Rule: Energy Conservation Standards for New Federal, Commercial, and Multi-Family High-Rise Residential Buildings and New Low-Rise Residential Buildings, 10 CRT Parts 433, 434, and 435
g. The Provisions for Construction and Safety Signs. Stated in the General Requirements Section 01010 of the VA Master Construction Specification
APPLICATION OF CODES
In accordance with the Department of Veterans Affairs Sixth Edition Fire Protection Design manual dated September 2011, the project is subject to the current edition of the International Building Code (IBC) and the National Fire Protection Agency (NFPA) 101 Life Safety Code. It is assumed that since the IBC has just recently released the 2021 IBC and that the current edition of the Life Safety Code is the 2018, the project will subject to the 2021 edition of IBC and the 2018 edition of the NFPA 101. The NFPA 101 controls over the IBC when regulations are covered in both. However, for Group U or Utility and Miscellaneous (Agricultural Building), the IBC controls for type of construction and location of building on site and the relationship to existing buildings. NFPA does not provide Type of Construction requirements for Utility and Miscellaneous (Group U) occupancies.
ASSUMPTIONS
Per record drawings information provided by the VA, Building 115 is assumed to be Type
II-A
OCCUPANCIES
Group U - Utility and Miscellaneous (Agricultural Building)
Chapter 6 - Classification of Occupancy and Hazard of Contents
Utility and Miscellaneous - Group U (Section 312)
Chapter 7 - Means of Egress
7.1.3 Separation of Means of Egress
7.1.3.1 Exit Access Corridors - Corridors serving an occupant load of 30 or more must be 1-hour rated. Does not apply to existing Business Occupancies or within Business Occupancies where the entire building is sprinklered.
7.1.3.2 Exits
7.1.3.2.1 Where egress is required to be seperated from other parts of the building, it must comply with this Section and Section 8.2
a. Vertical exit enclosures: 1-hour up to three stories (levels) 2 hours thereafter.
b. Rated exit enclosures must be supported by equivalent rated construction.
c. One hour enclosure walls must be supported by equivalent construction.
d. Openings into enclosure are limited to those necessary such as from normally occupied spaces or corridors
e. Penetrations into enclosures are limited to the following:
• Door Assemblies permitted by 7.1.3.2.1 (9)
• Electrical conduit serving the exit enclosure
• Required exit door openings
• Ductwork and equipment necessary for independent stair pressurization
• Water or steam piping necessary for the heating or cooling of the exit enclosure
• Sprinkler piping
• Standpipes
• Existing penetrations protected in accodrance with 8.3.5
• Penetrations for fire alarm ciccuits, where the circuits are installed in metal conduit and the penetrations are protected in accordance with 8.3.5
f. Membrane penetrations are permitted on the exit acces side of the exit enclosure
7.1.3.2.2 An exit enclosure is required to have a continuous protected path of travel to an exit discharge.
7.1.3.2.3 Exit enclosures may not be used for any other purpose except for compliant areas of refuge.
7.1.4 Interior Finish in Exit Enclosures
7.1.4.1 Interior Wall and Ceiling Finish - Class A or B
7.1.4.2 Interior Floor Finish and Exit Enclosures - Class II per Section 10.2
7.1.5 Headroom
7.1.5.1 Minimum headroom in Means of Egress:
New Construction: 7 ' 6" Existing Construction 6' 6"
7.2 Means of Egress Components
7.2.1 Door Openings
7.2.1.2.3.2 Minimum Door Leaf Width - 32"
7.2.1.3 Floor Level: Except for maximum 1/2" thresholds, provide level landings on each side of doors.
7.2.1.4.2 Door Leaf Swing Direction: Doors shall swing in the direction of travel where serving an occupant load of 50 or more. See 7.2.4.3.8.1 or 7.2.4.3.8.2 for exceptions for horizontal exits.
7.2.1.4.3 Door Leaf Encroachment: Shall not reduce the required width of a corridor or landing witch means of egress in any position and may not reduce the required width by more than 7 inches when fully open.
7.2.1.5 Locks, Latches, and Alarm Devices (this section also contains provisions for special locking)
7.2.1.5.1 Must be readily operable from the egress side.
7.2.1.5.3 Locks shall not require any special knowledge or equipment to open.
7.2.1.7 Panic Hardware: Required from training room and all doors in path of travel until egress from the buidling is accomplished.
7.2.2 Stairs
7.2.2. Standard Stairs
New stairs shall comply with [Table 7.2.2.2.1.1 {a}]
• Minimun width See 7.2.2.2.1.2.
• Maximum height of risers 7 "
• Minimum height of risers 4"
• Minimum tread depth 11"
• Minimum headroom 6' 8"
• Maximum height between landings 12'
• Landings 7.2.1.3, 7.2.1.4.3.1, 7.2.2.3.2
Existing stairs shall comply with [Table 7.2.2.2.1.1 {b}]
• Minimum widthclear of all obstructions, except projects not more than 4 1/2 in. at or below handrail height on each side 36"
• Maximum height of risers 7"
• Minimum height of risers 4"
• Minimum tread depth 11"
• Minimum headroom 6' 8"
• Maximum height between landings 12'
• Landings 7.2.1.3, 7.2.1.4.3.1, 7.2.2.3.2
7.2.2.2.1.2 Minimum New Stair Width
a. 44" where serving an occupant load of 50 to 1,999
b. Handrails may project into the required width 4 1/2"
7.2.2.3 Stair Details
7.2.2.3.1 Construction: Must be noncombustible except for handrails and existing stairs.
7.2.2.3.2 Landings
Width must be equal to width of stair and the length must be equal to the width of the stair (may be 4' in width on straight stairs)
7.2.2.4 Guards and Handrails
7.2.2.4.1 Handrails
a. Height 34" (VA REQ'T) above nosing of stair
b. Must be continuously graspable
c. Clearance between handrails and adjacent wall: 1 1/2"
d. Must return to the wall or a newel post
e. Must extend 12" (in the same direction of the handrail) beyond the top riser and the depth of the tread at the bottom riser
7.2.2.4.5 Guards
a. Height 42" minimum
b. Maximum spacing of intermediate rails may not allow passage of a sphere 4" in diameter (6" sphere permitted at the triangular space created by a stair or riser)
7.3 Capacity of Means of Egress
7.3.1 Occupant Load
7.3.1.2 Occupant Load (Table 7.3.1.2)
Conference and waiting areas: 1:15 net Lobbies: 1:5 net Office areas: 1:100 gross Storage areas: 1:500 gross
7.3.3 Egress Capacity (Factors)
a. Stairways: .3 times occupant load served equal width in inches, but not less than minimums
b. Other: .2 times occupant load served equal width in inches, but not less than minimums
Refer to sheet GI103 for occupant load
7.4 Number of Means of Egress
Generally: 1 - 500 occupants requires 2 exits 501 - 1000 occupants requires 3 exits 1001 and greater occupants requires 4 exits
Note: See electrical code for electrical rooms. Section 110.26 (C) and Section 110.33 (A)
7.5 Arrangement of Means of Egress
7.5.1.1.2 Exit access corridors must provide access to at least two approved exits -see exceptions
7.5.1.3.2 Exit separation must be equal to 1/2 the overall diagonal of the building or area served in non-sprinklered buildings
7.5.1.3.3 Exitt separation must be equal to 1/3 the overall diagonal of the building or area served in sprinklered buildings
7.6 Measurement of Travel Distance to Exits
1. Along the centerline of the natural path of travel, starting from the most remote point subject to occupancy.
2. Curving around any corners or obstructions, with a 12" (305 mm) clearance therefrom
3. Terminating at one of the following:
a. Center of the doorway
b. Other point at which the exit begins
7.7 Illumination of the Means of Egress
10 footcandles at stairs 1 footcandle at other locations
7.9 Emergency Lighting
Provide as required by Chapter 38 and Chapter 39
7.10 Marking of Means of Egress
7.10.1.2 Provide exit signs as required by Chapter 38 and 39
7.10.1.3 Provide tactile exit signs at each exit door requiring a sign
Egress (Based on NFPA 101) Chapter 38
New Buildings: Egress for new buildings shal comply with Section 38.2
38.2.1 In general, the means of egress shall comply with Chapter 7.
38.2.2 Means of Egress Components
38.2.2.2.1 Doors: Doors shall comply with 7.2.1
38.2.2.2.2 Locks comply with 7.2.1.2.5 are permitted on the main entrance door
38.2.2.3 Stairs: Stairs shall comply with Section 7.2.2
a. Quantity per Section 7.3
b. A minimum of two exits per story
c. A minimum of two exits shall be accessible from every part of every story
38.2.4.2 A single exit is permitted when the common path of travel per
38.2.5.3 (100ft in sprinklered building) is not exceeded
38.2.5 Arrangement of Means of Egress
38.2.5.1 Arrangement must be in accordance with Section 7.5
38.2.5.2 Dean end corridors must comply with this Section:
38.2.5.2.1 Maximum dead-end corridor in fully sprinklered buildings is 50'
38.2.5.2.2 Maximum dead-end corridor in non-sprinklered buildings is 20'
38.2.5.3 Common path of travel limitations must comply with the following:
38.2.5.3.1 Fully sprinklered building: 100'
38.2.5.3.2 Tenant space with an occupant load of 30 or less: 100'
38.2.5.3.3 Other: 75'
38.2.6 Travel Distance to Exits - Measurement to be in accordance with 706
Sprinklered building: 300' Non-sprinklered building: 200'
38.2.7 Discharge from Exits: per section 7.8
38.2.8 Illumination of Egress: per section 7.8
38.2.9 Emergency Lighting of Mans of Egress: provide egress signs in accordance with 7.9 when any of the following conditions exists
a. The building is three or more stories in height
b. There are 50 or more occupants above or below the level of exit discharge
c. The building occupant is 300 or more
38.2.10 Marking of Means of Egress: provide egress signs in accordance with 7.10
8.2.2.3.2.5 Horizontal Exits: horizontal exits compling with 7.2.4 may be used as part of the Means of Egress
38.2.3 Capacity of Means of Egress
38.2.3.1 Must comply with Section 7.3
38.2.3.2 The clear width of corridors complying with an occupant load served of 50 or more must be at least 44" in width
38.2.3.3 Grade level (street) exits shall be of suffificent width to accommodate the grade level plus any floor level served by an open stair.
38.2.4 Number of Means of Egress: the number of Means of Egress shall comply with the following except as permitted by 38.2.4.2 - 38.2.4.4
Chapter 39
Existing Buildings: In general, existing business occupancy buildings are permitted to comply with Chapter 39 and specificially 39.2
39.2.1.3.2 An inside open stairway is permitted to serve as a required egress facility from not more than one floor level below the street.
39.2.2 Means of Egress Components
39.2.2.5 Horizontal exits complying with 7.2.4 shall be permitted
39.2.3 Capacity of Means of Egress
39.2.3.1 The capacity of the means of egress shall comply with 7.3
39.2.3.2 The clear wideth of any corridor or passageway serving an occupant load of 50 or more shall be not less than 44"
39.2.3.3 Street floor exits must also unclude the capacity of open stairs
39.2.4 Number of Means of Egress
39.2.4.1 The number of exits is required to comply with the following:
a. 7.4.1.1 & 7.4.1.3 - 7.4.1.6
b. A minimum of two exits shall be provided on every story
c. A minimum of two exits shall be accessible from every part of every story
39.2.4.2 Exit access required by 39.2.4.2 shall be permitted to include a single exit access path based on common path of travel requirement of 39.2.5.3
39.2.4.3 Single Exits are permitted from rooms or areas with a total occupant load of less than 100 provided the criteria below are met.
a. The exit discharges directly to the exterior at the level of exit discharge for the building
b. The maximum travel distance including within the area does not exced 100'
c. The total travel distance of 100' must be within the same story or it may include a stair of not more than 15' in height provided the following are met:
• Interior stairs are completely enclosed
• A single exterior stair in accordance with 7.2.2 is utilized
39.2.5 Arrangement of Means of Egress
39.2.5.1 Arrangement of Means of Egress shall be in accordance with 7.2.5
39.2.5.2 Dead end corridors shall not exceed 50'
39.2.5.3 Limitations on Common Path of Travel
a. 100' in a fully sprinklered building
b. Not liited in a single tenant space with an occupant load of 30 or less
c. In other buildings not complying with a. or b. above, the maximum common path of travel is 75'
39.2.5.4 Travel distance to exits: travel distance to exits shall comply with the following:
a. Shall comply with 7.6
b. Maximum travel distance to an exit shall not exceed 300' except in fully sprinklered buildings where it may be 300'
39.2.7 Discharge from Exits: Discharge from Exits shall comply with 39.2.7
39.2.8 Illumination of Means of Egress: Means of Egress Illumination shall comply with 7.8
39.2.9 Emergency Lighting: Emergency Lighting shall be provided in accordance with 7.9 and the following:
a. The building height is three or more stories
b. There are 100 or more occupants on a level above or below grade
c. The occupant load is 1,000 or more
39.2.9 Marking of Means of Egress: provide exit signage in accordance with 7.10
Chapter 29 - Plumbing Systems
2901 General: refer to the National Standard Plumbing Code
2901.1 Unisex toilet rooms are permitted to be used for the required count in assembly and mercantile occupancies
2902.2 Where fixtures are required, separate facilities must be provided for each sex
Exception 1: not required for dwelling and sleeping units Exception 2: not required in buildings or tenant spaces with a total occupant load, including employees, of 15 or less
2902.3 The occupant load for determining the number or required fixtures shall be based on a load composed of 50% of each sex
2902.4.1 Facilities shall not be located more than 1 story above or below the space required and not more than 500' in travel distance
Exception: In factory occupancies, can exceed limites if approved by code official
Classification U - - - - - -
USE
GROUP
WATER
CLOSETS
(MALE)
WATER
CLOSETS
(FEMALE)
LAVATORIES
(MALE)
LAVATORIES
(FEMALE)
DRINKING
FOUNTAINS
OTHER
Table 2902.1 Minimum Number of Required Plumbing Fixtures
Chapter 30 - Elevators and Conveying Systems
3002.1 Hoistway Enclosure Protection: refer to 707
3002.8 Glass in elevator enclosures: comply with 2409.1
3003.1 Buildings where standby power is required or furnished to operate an elevator:
a. Standby power shall be manually transferable to all elevators in each bank
b. Where only 1 elevator is installed, it shall automatically transfer power within 60 seconds after power failure
c. Where 2 or more elvators are controlled by a common operating system, all shall transfer to standby within 60 seconds where standby is sufficient to operate all elevators at the same time. Otherwise, each shall transfer in sequence. After all have returned to designated level, at least one shall remain operable from standby
3004.1 Hoistways penetrating more than 3 stories: shall be provided with means for venting, smoke, and hot gases
3004.3 Area of vents: at least 3 1.2% of the hoistway area or less than 3 SF for each elevator car
a. Vent area shall not be required to be permanently open where the vent openings automatically open upon detection of smoke in the elvator lobbies or hoistway, upon power failure, and upon activation of a manual override control
b. Reduced vent area allowed with mechanical ventilation (reduction not allowed for overnight sleeping quarters)
3006.2 Machine Room Venting: Machine Rooms that contain solid state equipment shall be provided with independent ventilation or air-conditioning.
3006.4 Machine rooms shall have a fire-resistance rating not les than the reuired rating of the hoistway enclosure and openign shall be protected with assemblies of the same rating as the hoistway doors.
S S S S S
UP
DN
LIFE SAFETY SYMBOLS
XX
PATH OF TRAVEL
(FOR CUMULATIVE DISTANCES REFER TO SCHEDULE)
REFER TO ELECTRICAL DRAWINGS FOR EXIT
LIGHTING, ILLUMINATION OF EXIT LIGHTING
INDICATED FOR REFERENCE
EXIT DISCHARGE
FE
LIFE SAFETY PLANS GENERAL NOTES
A. ALL PENETRATIONS MADE THROUGH RATED WALLS SHALL BE CONSTRUCTED AND
SEALED AS REQUIRED TO MAINTAIN THE REQUIRED WALL RATING.
B. REFER TO PROJECT SPECIFICATION SHEETS FOR ADDITIONAL REQUIREMENTS.
ONE HOUR FIRE RATED PARTITION
TWO HOUR FIRE RATED PARTITION
ONE HOUR FIRE/SMOKE RATED PARTITION
HANGING FIRE EXTINGUISHERS
CODE INFORMATION
BUILDING: 2021 INTERNATIONAL BUILDING CODE
ACCESSIBILITY: ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS
BARRIER FREE DESIGN GUIDE (PG-18-13)
FIRE: 2021 INTERNATIONAL FIRE CODE
2021 NFPA 101
2021 NFPA 80
PLUMBING: 2018 INTERNATIONAL PLUMBING CODE
MECHANICAL: 2018 INTERNATIONAL MECHANICAL CODE
ELECTRICAL: 2017 NATIONAL ELECTRICAL CODE
ENERGY: 2018 INTERNATIONAL ENERGY CODE
2019 ASHRAE 90.1
OCCUPANCY CLASSIFICATIONS
GROUP U: UTILITY AND MISCELLANEOUS (AGRICULTURAL BUILDING)
CONSTRUCTION TYPE
TYPE II-A CONSTRUCTION (IBC 602.2) - PRE-ENGINEERED METAL BUILDING WITH FIRE
RESISTANCE
PROJECT AREA
2,577 SF
953 SF
LEVEL 1
MEZZANINE
3,530 SFTOTAL
1,520 SF/
OCC LOAD:6
GENERAL STORAGE A
300 411 SF/
OCC LOAD:2
TOOL STORAGE CAGE
300 585 SF/
OCC LOAD:2
GENERAL STORAGE B
EXIT #3EXIT #1
1A
1C
1B
EXIT #2
DASHED LINE AT
MEZZANINE ABOVE
FE
FE
FE
957 SF/
OCC LOAD:4
MEZZANINE
OPEN TO BELOW OPEN TO BELOW
2A
2B
FE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
APPROVING OFFICIAL:
COR, MS. MARIA HERNANDEZ
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A/E:
OEI-LBL Joint Venture LLC
2340 E. Trinity Mills Rd. Ste 220
Carrollton, TX 75006
O'Brien Engineering Inc., Managing Partner
972-233-2288
115O'Brien Engineering, Inc.
Carrollton, TX 75006
972-233-2288
2340 E. Trinity Mills Rd. Ste 220 www.obrieneng.com
A/E:
www.obrieneng.com
GI103
LIFE SAFETY PLAN RECONSTRUCT BLDG 115
KERRVILLE, TX
671A4-22-109
11/30/2023 JOW CH
ISSUE FOR
CONSTRUCTION
11/30/2023
TRAVEL DISTANCE SCHEDULE - LEVEL 2
PATH NAME DISTANCE
2A 51'
2B 53'
N
ACTUAL NORTHPLAN NORTH
N
N
ACTUAL NORTHPLAN NORTH
N
1/4" = 1'-0"
LIFE SAFETY PLAN - GROUND FLOOR
1/4" = 1'-0"
LIFE SAFETY PLAN - MEZZANINE
TRAVEL DISTANCE SCHEDULE - LEVEL 1
PATH NAME DISTANCE
1A 80'
1B 68'
1C 42'
OCCUPANT LOAD
Number Occupancy Area Occupant Load Factor Max Room Capacity
101 STORAGE 1,520 SF 300 6
102 STORAGE 411 SF 300 2
103 STORAGE 585 SF 300 2
201 STORAGE 957 SF 300 4
Total Capacity 14
BUILDING EGRESS DOORS
EXIT DOOR TYPE Egress Width Provided
EXIT #1 32"
EXIT #2 32"
EXIT #3 32"
TOTAL 96"
14 OCCUPANTS X 0.2" PER OCCUPANT = 2.8" REQUIRED
(4) 32" DOOR = 128" PROVIDED
EXIST. BLDG 46 NEW BLDG 115
EXIST. PECAN RD.
EXIST. PARKING LOT
COVERED
OUTDOOR
STORAGE
AREA
EXIST. PAVED AREA
PEDESTRIAN
ENTRANCE
4'-0"7'-0"74'-8 1/2"9'-0 3/4" PEDESTRIAN
ENTRANCE
(HC ACCESSIBLE)
VEHICLE
ENTRANCE
VEHICLE
ENTRANCE
VEHICLE
ENTRANCE
VEHICLE
ENTRANCE
PEDESTRIAN
ENTRANCE
(HC ACCESSIBLE)6'-1"15'-1 1/2"9'-1"
RAMP
RAMP
FACE OF MTL. PANEL FACE OF MTL. PANEL
AND EDGE OF STEP
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
APPROVING OFFICIAL:
COR, MS. MARIA HERNANDEZ
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A/E:
OEI-LBL Joint Venture LLC
2340 E. Trinity Mills Rd. Ste 220
Carrollton, TX 75006
O'Brien Engineering Inc., Managing Partner
972-233-2288
115O'Brien Engineering, Inc.
Carrollton, TX 75006
972-233-2288
2340 E. Trinity Mills Rd. Ste 220 www.obrieneng.com
A/E:
www.obrieneng.com
GI201
SITE PLAN RECONSTRUCT BLDG 115
KERRVILLE, TX
671A4-22-109
11/30/2023 JOW CH
ISSUE FOR
CONSTRUCTION
11/30/2023
3/32" = 1'-0"
SITE PLAN
N
ACTUAL NORTHPLAN NORTH
N
EXIST. BLDG 46 NEW BLDG 115
EXIST. PECAN RD.
EXIST. PARKING LOT
COVERED
OUTDOOR
STORAGE
AREA
EXIST. ASPHALT PAVED AREA
RAMP
RAMP
1 - 8" X 6" TEE (E)
1 - 6" X 4" REDUCER (E)
1 - 4" GATE VALVE (E)
EXISTING WATER
LINE SERVICE
PROPOSED 4-INCH
WATER LINE
SERVICE FOR FIRE
PROTECTION
WWWWWWWWWWWW
W W
W
W
W
W
W
W
W
W
W
W
APPROX. 10'
EXIST. ASPHALT PAVED AREA
REMOVE ASPHALT PAVEMENT
AND/OR CONCRETE AS
REQUIRED TO INSTALL FIRE
PROTECTION SERVICE LINE.
REPAIR PAVEMENT PER
ASPHALT REPAIR DETAIL ON
SHEET CU501
GENERAL SITE PLAN NOTE:
A. UNDERGROUND FIRE SERVICE LINE SHALL BE DUCTILE IRON OR PVC C900 PIPE
B. ANY DISTURBED ASPHALT PAVING FOR UTILITY INSTALLATION SHALL BE
REPLACED TO MATCH EXISTING TO THE FULLEST EXTENT POSSIBLE.
C. UTLITY LINE LOCATIONS ARE BASED ON RECORD DRAWINGS AND NOT
IDENTIFIED USING SURVEY OR SUBSURFACE UTILITY ENGINEERING.
CONTRACTOR SHALL VERIFY EXACT UTILITY LOCATIONS AND ADJUST
INSTALLATION ACCORDINGLY.
PROPOSED 4-INCH WATER LINE
SERVICE FOR FIRE PROTECTION
SITE PLAN LEGEND:
EXISTING WATER LINE SERVICEW
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
APPROVING OFFICIAL:
COR, MS. MARIA HERNANDEZ
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A/E:
OEI-LBL Joint Venture LLC
2340 E. Trinity Mills Rd. Ste 220
Carrollton, TX 75006
O'Brien Engineering Inc., Managing Partner
972-233-2288
115O'Brien Engineering, Inc.
Carrollton, TX 75006
972-233-2288
2340 E. Trinity Mills Rd. Ste 220 www.obrieneng.com
A/E:
www.obrieneng.com
CU101
UTILITY PLAN RECONSTRUCT BLDG 115
KERRVILLE, TX
671A4-22-109
11/30/2023 JOW CH
ISSUE FOR
CONSTRUCTION
3/32" = 1'-0"
UTILITY PLAN
N
ACTUAL NORTHPLAN NORTH
N
FINISHED GRADE
2" TYPE "D" H.M.A.C.
12" 2 SACK CONCRETE
OR
8" TYPE "B" H.M.A.C.
PLACED IN TWO LIFTS
OR
8" LIMESTONE ROCK
ASPHALT PLACED IN
TWO LIFTS
*SELECT FILL OR
SATISFACTORY NATIVE
MATERIAL COMPACTED
TO 95% STANDARD
PROCTOR (ASTM D-698)
6"
2' -6
6"
6" 6"
3' M
IN
4'
M A
X
**SELECT FILL TO 95%
STANDARD PROCTOR
OR
SATISFACTORY NATIVE
MATERIAL TO 9%
STANDARD PROCTOR
OR
MATERIAL WITHIN 3%
(+/-) OF OPTIMUM
MOISTURE CONTENT,
COMPACTED TO 95%
STANDARD PROCTOR.
PEA GRAVEL OR 3/4"
WASHED SAND
6" MIN - 12" MAX
SAWCUT FULL DEPTH
FIELD DENSITY TEST
(ASTM D-698) EVERY 100
LINEAR FEET AT DEPTHS
OF 2', 5', 7.5', 10', AND 12'
DEPENDING ON DEPTH
OF SEWER
NOTES:
* MOISTURE SENSITIVE MATERIAL COMPACED TO 95% STANDARD
PROCTOR AND WITHIN 4% (+/-) OF OPTIMUM MOISTURE CONTENT MAY
BE USED WHERE WATER LINE IS NOT UNDERNEATH PAVEMENT.
** MODIFIED PROCTOR (ASTM D-1557) MUST ME USED AT DEPTHS
GREATER THAN 10 FEET.
REPRESENTS FIELD DENSITY TEST LOCATION
INSTALLATION OF PIPE TO FOLLOW CONTRACT SPECIFICATIONS
FINISHED GRADE
*SELECT FILL OR
SATISFACTORY NATIVE
MATERIAL COMPACTED
TO 95% STANDARD
PROCTOR (ASTM D-698)
6" M
IN
6" M
IN
PEA GRAVEL OR 3/4"
WASHED SAND
6" MIN - 12" MAX
LOCATING
TAPE
NOTES:
* MOISTURE SENSITIVE MATERIAL COMPACED TO 95% STANDARD
PROCTOR AND WITHIN 4% (+/-) OF OPTIMUM MOISTURE CONTENT MAY
BE USED WHERE WATER LINE IS NOT UNDERNEATH PAVEMENT.
REPRESENTS FIELD DENSITY TEST LOCATION
INSTALLATION OF PIPE TO FOLLOW CONTRACT SPECIFICATIONS
M
IN
0" M
A X
2' -0
FIELD DENSITY TEST (ASTM
D-698) EVERY 100 LINEAR
FEET AT 18" DEPTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
APPROVING OFFICIAL:
COR, MS. MARIA HERNANDEZ
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A/E:
OEI-LBL Joint Venture LLC
2340 E. Trinity Mills Rd. Ste 220
Carrollton, TX 75006
O'Brien Engineering Inc., Managing Partner
972-233-2288
115O'Brien Engineering, Inc.
Carrollton, TX 75006
972-233-2288
2340 E. Trinity Mills Rd. Ste 220 www.obrieneng.com
A/E:
www.obrieneng.com
CU501
CIVIL AND UTILITY DETAILS RECONSTRUCT BLDG 115
KERRVILLE, TX
671A4-22-109
11/30/2023 JOW CH
ISSUE FOR
CONSTRUCTION
1" = 1'-0"
PAVEMENT REPAIR DETAIL
1" = 1'-0"
WATER LINE EMBEDMENT & FIELD DENSITY TESTING
Revisions: Date:
VHASTXHernaM4 Snapshot
VHASTXHernaM4 Snapshot
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
APPROVING OFFICIAL:
COR, MS. MARIA HERNANDEZ
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
RECONSTRUCT BLDG 115
KERRVILLE, TX
671A4-22-109
11/30/23 RLW BWTRevisions: Date:
1151 W. PIONEER PKWY. (817) 277-6686
ARLINGTON, TX 76013
Texas Registered Engineering Firm F-8284 C 2022 Copyright R. L. Woods & Associates, LLC
Structural and Forensic Engineering R. L. Woods & Associates, LLC
11-30-23
ISSUE FOR
CONSTRUCTION
OEI-LBL Joint Venture LLC
2340 E. Trinity Mills Rd. Ste 220 Carrollton, TX 75006
O'Brend Engineering Inc., Managing Partner
972-233-2288
A/E:
www.obrieneng.com
SS001
GENERAL NOTES
1. Design loads are as follows:
A. Roof live loads 20 PSF B. Roof dead loads (PEMB system) 10 PSF (assumed) C. Rood dead collateral loads 10 PSF D. Floor live loads:
i. Mezzanine light storage 125 PSF
ii. Warehouse - storage 250 PSF
E. Equipment loads:
i. Roof and floor supported HVAC equipment as noted on plan
F. Ground snow loads: 5 PSF G. Wind pressure: unless noted otherwise, per ASCE 7-16 for:
i. Basic wind speed = 105 mph (Risk Category II).
ii. Exposure B.
iii. Component and cladding wind pressure, PSF, for Wind Area = 10 SF:
a. Roof Zone 1: +10.0; -31.6
b. Roof Zone 2: +10.0; -41.7
c. Roof Zone 3: +10.0; -56.8
d. Roof Overhang Zone 1: -28.6
e. Roof Overhang Zone 2: -38.7
f. Roof Overhang Zone 3: -53.8
g. Wall Zone 4: +19.8; -21.5
h. Wall zone 5: +19.8; -26.6
H.Seismic design (per ASCE 7):
a. Seismic Risk Category: II.
b. Seismic Importance Factor: 1.0
c. Mapped Spectral Response Acceleration Parameters:
Ss =.0473g S1 =.0231g
d. Spectral Response Coefficients: Sds = 0.028; Sd1 = 0.012
e. Site Class: A
f. Seismic Design Category: A
g. Seismic Force Resisting System: Ordinary moment resistant frames
h. Design Base Shear: n/a
i. Seismic Response Coefficient (CS) = 0.01
j. Analysis procedure: Equivalent Frame Method
2. Structure was designed in accordance with the IBC 2021 edition.
3. Consult structural engineer if locations or design weights of roof, floor, and mezzanine supported
Mech'l units differ from those indicated on structural plans.
4. All existing conditions shall be field verified.
5. Contractor shall verify all…