Attachment 2i Combined Drawings Construct Addition and Renovated Bldg 60.pdf
PDF 8 MB Posted
- Attached to
- Y1DA--589-703 Construct Addition and Renovate Community Living Center, Building 60 (VA-24-00028736)
- Solicitation number
- 36C77624B0019
About this file
This document is a construction solicitation issued by the Department of Veterans Affairs (VA) Technology Acquisition Center Austin for the Y1DA--589-703 Construct Addition and Renovate Community Living Center, Building 60 project. The solicitation covers the construction of an addition and renovation of Building 60 at the Robert J. Dole VA Medical Center in Wichita, Kansas. The project involves technology, security, and audiovisual systems work, as detailed in the attached specifications and drawings. The solicitation has a response deadline of September 6, 2023. The contract will be a firm-fixed-price construction contract. No set-asides are specified. The award date is not provided. The attached drawings and specifications provide a detailed overview of the required construction work, technology systems, and other project requirements.
View the file
Other files
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Z
CB
B
DS
E
EP
LS
KS
NA
NM
SS
BC
PS
CATV
FO
T
T/D
D
S
IC
UC
SSTV
IC
WAP
#D/#TV
V
CR
DM
EL
GB
MD
PB
RE
EC
LA
GO
COMMUNICATIONS OUTLET, TYPE AS NOTED
COMMUNICATIONS OUTLET, FLOOR BOX, TYPE AS NOTED
WIRELESS ACCESS POINT, CEILING MOUNTED
COMMUNICATIONS OUTLET, CEILING MTD, TYPE AS NOTED
SPEAKER, CEILING MOUNTED
SERVER RACK, TWO-POST, FLOOR MOUNTED
3/4"x4'x8', FIRE-RATED PLYWOOD BACKBOARD
GROUND BAR, TYPE AS NOTED
SERVER RACK, WALL MOUNTED
CABLE TRAY, TYPE AS NOTED
CABLE TELEVISION LINE
FIBEROPTIC LINE
TELEPHONE LINE
TELEPHONE/DATA LINE
DATA LINE
SPEAKER LINE
INTERCOM LINE
VOLUME CONTROL, WALL MOUNTED
CODE BLUE PUSHBUTTON STATION
DUTY STATION
STAFF EMERGENCY ASSIST STATION
PATIENT EMERGENCY PULL CORD STATION
STAFF LOCATOR SENSOR
NURSE CALL KEY SWITCH
NURSE CALL VISUAL ANNUNCIATOR PANEL
NURSE CALL MASTER STATION
STAFF STATION (NORMAL, EMERGENCY & CODE BLUE)
DOME LIGHT, WALL MOUNTED
DOME LIGHT, CEILING MOUNTED
ZONE DOME LIGHT
MULTI-SERVICE POWER POLE WITH POWER/DATA,
TYPE AS NOTED AND/OR SCHEDULED
UNDERGROUND COMMUNICATIONS LINE,
CABLING TYPE AS NOTED
MULTI-SERVICE FLOOR BOX/POKE-THRU WITH POWER/DATA,
TYPE AS NOTED AND/OR SCHEDULED
SERVER RACK, FOUR-POST, FLOOR MOUNTED
SERVER CABINET, FLOOR MOUNTED
CLOSED CIRCUIT TELEVISION LINE, MIN. 1" RACEWAY
CARD READER, PROXIMITY TYPE W/ KEYPAD
DOOR POSITION MONITOR
ELECTRIFIED LOCKING DEVICE, LATCH BOLT MONITOR,
GLASS BREAK DETECTOR
MOTION DETECTOR
DURESS PUSHBUTTON
REQUEST TO EXIT BUTTON
SINGLE VIEW SECURITY CAMERA
EMERGENCY CALL STATION
LOCAL DOOR POSITION ALARM/ANTI-PROP
GATE OPENER
DUAL VIEW SECURITY CAMERA
180-DEGREE PANORAMIC VIEW SECURITY CAMERA
270-DEGREE PANORAMIC/MULTI-IMAGE VIEW
360-DEGREE PANORAMIC/MULTI-IMAGE VIEW
SECURITY CAMERA
SECURITY CAMERA
PATIENT STATION WITH BED CONNECTOR; MOUNTED AT
42" AFF
PATIENT STATION WITH CODE BLUE
SECURITY SYMBOLS
#D = DATA, # = QUANTITY OF CABLES
#TV = CABLE TELEVISION, # = QUANTITY OF CABLES
#D = DATA, # = QUANTITY OF CABLES
#TV = CABLE TELEVISION, # = QUANTITY OF CABLES
#V = VOICE, # = QUANTITY OF CABLES
#D = DATA, # = QUANTITY OF CABLES
#E = ELEVATOR, # = QUANTITY OF CABLES
#FMS = FACILITY MONITORING SYSTEM,
# = QUANTITY OF CABLES
NURSE CALL SYMBOLS
COMMUNICATION SYMBOLS
#TV = CABLE TELEVISION, # = QUANTITY OF CABLES
#V = VOICE, # = QUANTITY OF CABLES
WP - WEATHERPROOF
ML MAGNETIC LOCK
CU
MECHANICAL OR FIRE SPRINKLER PLAN NOTE CALL OUT
PLUMBING PLAN NOTE CALL OUT
ELECTRICAL, TECHNOLOGY OR FIRE ALARM
PLUMBING EQUIPMENT DESIGNATION
EQUIPMENT DESIGNATION TAG
OWNER FURNISHED, CONTRACTOR INSTALLED
EQUIPMENT DESIGNATION
NEW WORK TO EXISTING WORK CONNECTION POINT
DETAIL REFERENCE
SECTION CUT DESIGNATION
ELECTRICAL: (AFF, AFG UNLESS NOTED OTHERWISE)
PLAN NOTE CALL OUT
EP-101
EP-101
M (CONT'D)
MV MEDIUM VOLTAGE
MVA MEGAVOLT-AMPERE
MW MEGAWATT
AUDIBLE APPLIANCES (CENTERLINE) 84"
ALARMS (TOP) 48"
ANNUNCIATOR PANELS (TOP) 48"
CLOCK OUTLETS (CENTERLINE) 84"
CONTROLS (TOP) 48"
EXIT SIGNS (WALL-MOUNTED, BOTTOM) 80"
FIRE ALARM ANNUNCIATOR PANEL (DISPLAY) 60"
FIRE ALARM BELL (EXTERIOR) 120"
FIRE ALARM CONTROL PANEL/UNIT (DISPLAY) 60"
INTERCOM (AFEA ONLY) 36"
INTERCOMS (TOP) 48"
PANELS & PANELBOARDS (TOP) 72"
PULL STATIONS (TOP) 48"
PHOTOCELLS 144"
RECEPTACLES (BOTTOM) 18"
RECEPTACLES, EXTERIOR (BOTTOM) 24"
RECEPTACLES, GARAGES (BOTTOM) 26"
RECEPTACLES IN EQUIPMENT ROOMS (TOP) 48"
RECEPTACLES ABOVE COUNTERTOPS (TOP) 44"
REMOTE INDICATING LIGHT, EQUIPMENT ROOMS (TOP) 48"
REMOTE INDICATING LIGHT, FINISHED AREAS (TOP) CEILING
SAFETY SWITCHES & STARTERS 48"
SWITCHES (TOP) 48"
TELEPHONE/DATA/TV OUTLETS (BOTTOM) 18"
VISIBLE APPLIANCES (CENTERLINE) 84"
X
W
V
U
T
S
R
ANNOTATION STANDARD MOUNTING HEIGHTS
P
O
N
M
L
K
J
I
H
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FABL FIRE ALARM BELL
FABX FIRE ALARM BOX
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FI FILM ILLUMINATOR
FIXT FIXTURE
FLA FULL LOAD AMPS
FLEX FLEXIBLE METALLIC CONDUIT
FLUOR FLUORESCENT
FO FIBER-OPTIC
FP FIRE PROTECTION
FT FEET OR FOOT
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
G
F
E
D
EC EMPTY CONDUIT
EG EQUIPMENT GROUND
EL ELEVATION
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMCP EMER. MONITORING CONTROL PANEL
EMER EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
ESMT EASEMENT
ETD EXISTING TO BE DEMOLISHED
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXIST EXISTING
DB DECIBEL OR DIRECT BURIAL
DC DIRECT CURRENT
DCP DIMMER CONTROL PANEL
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLITION
DIAG DIAGRAM
DISC DISCONNECT
DISTR DISTRIBUTION
DISTR PNL DISTRIBUTION PANEL
DN DOWN
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
DRSW DOOR SWITCH
DS DISCONNECT SWITCH
DWG DRAWING
C CONDUIT
CAP CAPACITY
CAT CATALOG
CATV COMMUNITY ANTENNA TELEVISION
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED/
CONTRACTOR INSTALLED
CF/OI CONTRACTOR FURNISHED/
OWNER
CFE CONTRACTOR FURNISHED
EQUIPMENT
CHW CHILLED WATER
CHWP CHILLED WATER PUMP
CKT CIRCUIT
CKT BRKR CIRCUIT BREAKER
CLF CURRENT LIMITING FUSE
CLG CEILING
CMU CONCRETE MASONRY UNIT
COAX COAX CABLE
COMM COMMUNICATION
CONC CONCRETE
CONT CONTINUE
CONTR CONTRACTOR
COORD COORDINATE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
CU FT CUBIC FEET
C
B
A
ABBREVIATIONS
UFD UNDERFLOOR DUCT
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UNO UNLESS NOTED OTHERWISE
UPS UNINTERRUPTIBLE POWER SUPPLY
UTIL UTILITY
V VOLT
VA VOLT AMPERE
VAR VOLT AMPERE REACTIVE
VCM VERTICAL CABLE MANAGER
VFD VARIABLE FREQUENCY DRIVE
VOLT VOLTAGE
TC TIME CLOCK
TEL TELEPHONE
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TYP TYPICAL
RCP REFLECTED CEILING PLAN
RCPT RECEPTACLE
REC RECESSED
REQD REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
RU RACK UNIT
N NEUTRAL
NA NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NS NO SCALE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OL OVERLOAD
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC METAL-CLAD
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MG MOTOR GENERATOR
MH MANHOLE
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT PROTECTION
MLO MAIN LUGS ONLY
MT MOUNT
MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
KV KILOVOLT
KVA KILOVOLT AMPERE
KVAH KILOVOLT AMPERE PER HOUR
KVAR KILOVOLT AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
KWHM KILOWATT HOUR METER
JB OR J-BOX JUNCTION BOX
XFER TRANSFER
XFMR TRANSFORMER
XP EXPLOSION PROOF
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LM LUMEN
LP LIGHT POLE
LPS LOW PRESSURE SODIUM
LRA LOCKED ROTOR AMPS
LTCP LOCAL TEMPERATURE CONTROL PANEL
LT LIGHT
LTG LIGHTING
LTG PNL LIGHTING PANEL
LTNG LIGHTNING
LV LOW VOLTAGE
W WATT
WH WATER HEATER
WP WEATHERPROOF
IESNA ILLUMINATION ENGINEERING
SOCIETY OF NORTH AMERICA
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
IWH INSTANTANEOUS WATER HEATER
G OR GND GROUND OR GENERATOR
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GTB GROUND TERMINAL BOX
SCC SHORT CIRCUIT CAPACITY
SES SERVICE ENTRANCE SECTION
SD SMOKE DETECTOR
SF SQUARE FOOT (FEET)
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SPEC SPECIFICATION
SPST SINGLE POLE, SINGLE THROW
SURF SURFACE
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
P POLE
PA PUBLIC ADDRESS
PB PANELBOARD, PULL BOX, OR
PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT UNIT
PCB POLYCHLORINATED BIPHENYL
PEC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PNL PANEL
POD POWER OPERATED DAMPER
POE POWER OVER ETHERNET
PP PATCH PANEL
PT POTENTIAL TRANSFORMER
PTRV POWER TYPE ROOF VENTILATION
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
1P SINGLE POLE
1PH SINGLE-PHASE
3P THREE POLE
3PH THREE-PHASE
3W THREE WIRE
4W FOUR WIRE
A/C AIR CONDITIONING
A/E ARCHITECT/ENGINEER
AAP ALARM ANNUNCIATOR PANEL
AC ALTERNATING CURRENT OR
ARMORED
ACC ACCESSIBLE
ADDL ADDITIONAL
ADJ ADJACENT, ADJOINING
ADO AUTOMATIC DOOR OPENER
AF AMPERE FRAME OR AMP FUSE
AFC ABOVE FINISHED COUNTER,
AUTOMATIC FREQUENCY
CONTROL, OR AVAILABLE FAULT
CURRENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AH AMPERE HOUR
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
ALT ALTERNATE
AMB OR A AMBIENT
AMP AMPERE
ARCH ARCHITECT
ASC AMPS SHORT CIRCUIT
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
HCM HORIZONTAL CABLE MANAGER
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HZ HERTZ
BAT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISH FLOOR
BIL BASIC INSULATION LEVEL
BLDG BUILDING
BLK BLOCK
BPIP BOILER PLANT INSTRUMENTATION
PANEL
BRKR BREAKER
BYP BY PASS
IC INSULATION CONTACT
AD AUTOMATIC DOOR OPENER
IC WALL INTERCOM STATION
DS AIPHONE DOOR/GATE STATION
A. TECHNOLOGY PLANS AND SECTIONS ARE INTENDED TO
ACCURATELY ILLUSTRATE THE SCOPE OF WORK, BUT ARE STILL
DIAGRAMMATIC IN NATURE.
B. TECHNOLOGY DRAWINGS DO NOT SHOW ALL ACCESSORIES
TO BE INSTALLED. THE CONTRACTOR IS RESPONSIBLE FOR
ENSURING THAT ALL SYSTEMS ARE FULLY FUNCTIONAL AND
COMPLIANT WITH APPLICABLE CODES.
C. TECHNOLOGY DRAWINGS REFLECT COORDINATION EFFORTS
WITH BUILDING DISCIPLINES. HOWEVER, COORDINATION WITH
OTHER TRADES IS REQUIRED.
D. REFERENCE ARCHITECTURAL DRAWINGS FOR ADDITIONAL
INFORMATION REGARDING SCHEDULE AND PHASING
REQUIREMENTS. SCHEDULE WORK TO MINIMIZE DISRUPTION OF
SERVICES.
E. COORDINATE WITH SCHEDULE WITH THE CONTRACTING
OFFICER'S REPRESENTATIVE BEFORE THE START OF WORK.
F. NEW SERVER RACKS AND OTHER TECHNOLOGY EQUIPMENT
REQUIRE SHUTDOWN. COORDINATE SERVICE SHUTDOWN FOR
ALL EQUIPMENT WITH THE CONTRACTING OFFICER'S
REPRESENTATIVE.
G. MOUNTING HEIGHTS FOR DEVICES SHALL BE MEASURED FROM
FINAL FINISH FLOOR TO CENTER OF BOX.
GENERAL NOTES
PROJECT CODES AND STANDARDS
A. VA OFFICE OF INFORMATION & TECHNOLOGY (OIT) DESIGN
GUIDE, FEBRUARY 2011
B. VA OFFICE OF INFORMATION & TECHNOLOGY (OIT)
INFRASTRUCTURE STANDARDS FOR TELECOMMUNICATIONS
SPACES, JUNE 1 2023
C. INFRASTRUCTURE STANDARDS FOR TELECOMMUNICATIONS
SPACES, AUGUST 2020
D. VA PG-18-10 TELECOMMUNICATIONS AND SPECIAL
TELECOMMUNICATIONS SYSTEMS DESIGN MANUAL, FEBRUARY
E. BICSI AND EIA/TIA STANDARDS AS DEFINED IN VA-18-10
F. VA-PSRDM - PHYSICAL SECURITY AND RESILIENCY DESIGN
MANUAL 2020, 1 JUNE 2023 REVISION
KS KEY SWITCH
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. A-930 EXP. 12/31/2023
ENGR REG. NO. E-2586 EXP. 12/31/2023
STRUCTURAL/CIVIL
ENGINEER
H2B
1225 N. LOOP W #800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH
ENGINEER
SPUR DESIGN
11020 KING STREET, STE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
LANDSCAPE ARCHITECT
CLS & ASSOCIATES
825 N. BROADWAY AVE, STE 315
OKLAHOMA, OK 73102
(405) 525-2220
HEALTHCARE/MED
EQUIPMENT PLANNER
INNOVA GROUP
3196 N. SWAN ROAD
TUCSON, AZ 85712
(520) 886-8650
PHYSICAL SECURITY
FORCE PROTECT SECURITY
CONSULTANTS,
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
FOOD & BEVERAGE
PLANNER
STURM CONSULTING
5838 S. HUDSON PLACE
TULSA, OK 74135
(918) 260-0667
ENVIRONMENTAL
ENGINEER
RIVERFRONT ENVIRONMENTAL
1139 OLIVE STREET, STE 300
ST. LOUIS, MO 63101
(314) 436-9492
/2
/2
:1 :0
P
M
TECHNOLOGY SYMBOLS &
ABBREVIATIONS
MDT Drawing # 201 OF 222KGH
100% CONSTRUCTION DOCUMENTS
ADDITION AND RENOVATION
OF CLC
09/06/2023
589-703
ROBERT J. DOLE VA MEDICAL CENTER
5500 EAST KELLOGG, BLDG. 60
WICHITA, KS 67218
T-000
SPUR #: 2015
No. REVISION DESCRIPTION DATE
ECEC
T
T
T TT T T T T T
T T
T T
T T
T T
T T
T T
T T
T
TT
T T
T T
T T
T TT T T
T
T
T T
T
T T
DS
CR
DM
DM
T
TT T
DS CR
DMDM
T T
T T
TS101
COMM
MANHOLE
008 TN201
REFER TO DETAIL 2/ES101 FOR
DIRECT BURIAL CONDUIT
DETAIL (IN COORDINATION
WITH ELECTRICAL POWER)
12"x22" (NOMINAL
I.D.) HANDHOLE
TS101
REFER TO DETAIL 2/ES101 FOR
DIRECT BURIAL CONDUIT
DETAIL (IN COORDINATION
WITH ELECTRICAL POWER)
12"x22" (NOMINAL
I.D.) HANDHOLE
A1
CONTINUATION ON
DETAIL 1, SHEET
TS101.
1" CONCRETE-
ENCASED
CONDUIT
1" CONCRETE-
ENCASED
CONDUIT
12"x22" (NOMINAL
I.D.) HANDHOLE
CONTINUATION ON DETAIL 1,
SHEET TS101.
1" CONCRETE-
ENCASED
CONDUIT
1" CONCRETE-
ENCASED
CONDUIT
12"x22"
(NOMINAL I.D.)
HANDHOLE
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. A-930 EXP. 12/31/2023
ENGR REG. NO. E-2586 EXP. 12/31/2023
STRUCTURAL/CIVIL
ENGINEER
H2B
1225 N. LOOP W #800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH
ENGINEER
SPUR DESIGN
11020 KING STREET, STE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
LANDSCAPE ARCHITECT
CLS & ASSOCIATES
825 N. BROADWAY AVE, STE 315
OKLAHOMA, OK 73102
(405) 525-2220
HEALTHCARE/MED
EQUIPMENT PLANNER
INNOVA GROUP
3196 N. SWAN ROAD
TUCSON, AZ 85712
(520) 886-8650
PHYSICAL SECURITY
FORCE PROTECT SECURITY
CONSULTANTS,
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
FOOD & BEVERAGE
PLANNER
STURM CONSULTING
5838 S. HUDSON PLACE
TULSA, OK 74135
(918) 260-0667
ENVIRONMENTAL
ENGINEER
RIVERFRONT ENVIRONMENTAL
1139 OLIVE STREET, STE 300
ST. LOUIS, MO 63101
(314) 436-9492
KEY PLAN
N
/2
/2
:1 :1
P
M
TECHNOLOGY SITE PLAN
MDT Drawing # 202 OF 222KGH
100% CONSTRUCTION DOCUMENTS
ADDITION AND RENOVATION
OF CLC
09/06/2023
589-703
ROBERT J. DOLE VA MEDICAL CENTER
5500 EAST KELLOGG, BLDG. 60
WICHITA, KS 67218
TS101
SPUR #: 2015
N
1/16" = 1'-0"
TECHNOLOGY SITE PLAN - BUILDING 601
ELECTRICAL KEYNOTES
1 PROVIDE UNDERGROUND TELECOMMUNICATION PATHWAY FROM EXISTING COMMUNICATIONS
MANHOLE-8. ROUTE (1) 4" CONCRETE-ENCASED CONDUIT WITH (4) 1" INTERDUCTS AND
CONDUCTORS WITH 12-STRAND, SINGLE-MODE FIBER AND 12-STRAND, MULTI-MODE FIBER
FROM THE DATACENTER IN BUILDING 4 AND (1) 4" CONCRETE-ENCASED CONDUIT WITH (4) 1"
INTERDUCTS AND CONDUCTORS WITH 6-STRAND, MULTI-MODE FIBER FOR SECURITY FROM
BUILDING 1 ROOM 113.
2 PROVIDE EXTERIOR WALL MOUNTED 180-DEGREE MULTISENSOR, ZOOM, NIGHT VISION,
SECURITY CAMERA MOUNTED AT 144" AFF. MAKE CONNECTION TO NEW SSTV SYSTEM.
(TYPICAL)
3 ENSURE SSTV CAMERA IS PROGRAMMED WITH BEHAVIOR ANALYTICS TO COVER THE PARKING
LOTS AND BUILDING ENVELOPE APPROACH.
4 PROVIDE EXTERIOR WALL MOUNTED 90-DEGREE MOTION ACTIVATED, NIGHT VISION, SECURITY
CAMERA MOUNTED AT 144" AFF. MAKE CONNECTION TO NEW SSTV SYSTEM.
5 PROVIDE (1) 6'X3" ROUND POLE FOR THE MOUNTING OF A SSTV FACIAL ANALYTICS CAMERA.
(TYPICAL)
6 PROVIDE GATE ARM OPERATOR WITH GATE POSITION MONITOR TO INDICATE THE POSITION OF
THE GATE ARM. PROVIDE INTEGRATIONS TO ALLOW THE ACCESS CONTROL SYSTEM TO
CONDUCT POSITION MONITORING, REMOTE OPENING, OPEN SCHEDULE, ABILITY TO MAINTAIN
OPEN STATE FOR SCHEDULED PERIOD OF TIME, AND TO OPEN ON AUTHORIZED TRIPLE
AUTHENTICATION. (TYPICAL)
7 PROVIDE SSTV CAMERA TO BE PROGRAMMED WITH FACIAL ANALYTICS AS THE THIRD
AUTHENTICATION IN THE TRIPLE AUTHENTICATION PROCESS. COORDINATE EXACT MOUNTING
HEIGHT AT THE TIME OF INSTALLATION. (TYPICAL)
8 PROVIDE A POLE-MOUNTED LICENSE PLATE RECOGNITION (LPR) STANDARD RANGE CAMERA.
COORDINATE EXACT MOUNTING HEIGHT WITH CAMERA MANUFACTURERS AT THE TIME OF
INSTALLATION. CAMERA SHALL BE PROGRAMMED AS THE FIRST AUTHENTICATION IN THE
TRIPLE AUTHENTICATION PROCESS. (TYPICAL)
9 PROVIDE (1) 6'X3" ROUND POLE FOR THE MOUNTING OF A LICENSE PLATE RECOGNITION (LPR)
CAMERA. (TYPICAL)
10 PROVIDE VEHICLE DETECTION LOOP. COORDINATE CONNECTION INTO GATE OPERATING
SYSTEM CONTROLS. (TYPICAL)
11 PROVIDE ACCESS CONTROL TO THIS LOCATION VIA PIV READER PROGRAMMED AS THE
SECOND AUTHENTICATION IN THE TRIPLE AUTHENTICATION PROCESS. (TYPICAL)
12 PROVIDE AIPHONE (OR EQUIVALENT) TWO-WAY INTERCOM SYSTEM DOOR STATION AND WIRE
TO ACTIVATE WITH VEHICLE DETECTION LOOP. ROUTE 1" CONDUIT AND (1) CATEGORY 6 CABLE
WITH TAMPER PROOF SCREWS TO POLICE STATION. MAKE CONNECTION TO NEWLY INSTALLED
AIPHONE MASTER STATION IN CAMPUS SECURITY CONTROL CENTER. (TYPICAL)
13 INSTALL PRESERVED EMERGENCY CALL STATION AND CONNECT TO CAMPUS SECURITY
CONTROL CENTER.
14 PROVIDE DUAL-HEIGHT GATE ACCESS CONTROL PEDESTAL. (TYPICAL)
GENERAL NOTES:
A. THE AREA OF WORK SHOWN IS ASSOCIATED WITH AN OPERATING FACILITY THAT MUST
REMAIN IN SERVICE 24/7.
B. COORDINATE TECHNOLOGY WORK WITH ALL OTHER TRADES. VERIFY ALL EXISTING
CONDITIONS BEFORE THE START OF WORK.
C. SEE SHEETS GI011 AND GI012 FOR ADDITIONAL INFORMATION REGARDING SCHEDULE AND
PHASING REQUIREMENTS. SCHEDULE WORK TO MINIMIZE DISRUPTION OF SERVICES.
D. ALL CARD READER SYSTEMS WITH AUTOMATIC DOOR CONTROLS SHALL BE WIRED TO
AUTOMATICALLY OPEN DOORS UPON CARD READER AUTHENTICATION.
E. PROVIDE CATEGORY 6A CABLING TO ALL CARD READERS AND SECURITY CAMERAS WITHIN
THE SCOPE OF WORK.
F. ALL TELECOMMUNCATIONS CABLING SHALL BE CATEGORY 6A, PLENUM RATED CABLE WITH
SPLINE/SEPERATOR BETWEEN PAIRS. COORDINATE CABLE COLOR CODE REQUIREMENTS
WITH VA PRIOR TO BID.
N
3/16" = 1'-0" REF: 1/ TS101
TECHNOLOGY SITE PLAN - SOUTH SECURITY GATE3
BID DEDUCT ALTERNATE KEYED NOTES
A1. BID DEDUCT ALTERNATE #14: IF DEDUCT ALTERNATE IS ACCEPTED, OMIT ALL
CONDUCTORS, CONDUIT, TELECOMMUNICATION CABLING, SECURITY CABLING,
TELECOMMUNICATION DEVICES, AND SECURITY DEVICES SERVING THE SECURITY GATE.
N
3/16" = 1'-0" REF: 1/ TS101
TECHNOLOGY SITE PLAN - NORTH SECURITY GATE2
A1
T TT T T T T T
T TT T T T T T T T T T T T T T T T T T T T T T T T
T T
T T
T T
T T
T
T T
T T
T T
T
T TT T T T T T
T T
T
T T
T T
T
T
T
T T
T T
T T
T T
T
T
T
T T T T T T T T T T
T
T
T
T
T T T T T T T
T
T
T TT T
COMM
MANHOLE
COMM
MANHOLE
TELECOM
ROOM A009
BUILDING 4
IT CLOSET
A107
BUILDING 60
IT ROOM 116
BUILDING 60
COMM ROOM
1B126
BUILDING 60
IT ROOM 103
BUILDING 59
TS-102
COMM
MANHOLE
EXISTING
UNDERGOUND
TELECOM
PATHWAY
EXISTING
UNDERGOUND
TELECOM
PATHWAY
EXISTING
UNDERGOUND
TELECOM
PATHWAY
DIRECT-BURIED DUCT LINE
GENERAL NOTES:
1. CONCRETE SHALL BE 2000 P.S.I. @ 28 DAYS, OR AS SPECIFIED.
2. PROVIDE #4 REINFORCING RODS ON TOP AND BOTTOM OF DUCTS
WHEN CROSSING OR PLACED IN ROADWAYS.
3. MINIMUM COVER TO TOP OF ENVELOPE SHALL BE 610mm (24") OR AS
OTHERWISE SPECIFIED IN SECTION 26 05 41.
(24" MIN.)
76mm
3"
76mm
3"
76mm
3" m m m m
EXISTING SUBSTRATE
GRADE
4" CONDUITS WITH 4-1"
INTERDUCTS FOR
TELECOMMUNICATION
AND SECURITY FIBER
OPTICS
12-STRAND OS1 AND 12-
STRAND OM3 LOOSE TUBE
CABLES FROM COMM
MANHOLE 008 TO
BUILDING 60
6-STRAND OM3 LOOSE
TUBE CABLES FROM
COMM MANHOLE 008 TO
BUILDING 60
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. A-930 EXP. 12/31/2023
ENGR REG. NO. E-2586 EXP. 12/31/2023
STRUCTURAL/CIVIL
ENGINEER
H2B
1225 N. LOOP W #800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH
ENGINEER
SPUR DESIGN
11020 KING STREET, STE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
LANDSCAPE ARCHITECT
CLS & ASSOCIATES
825 N. BROADWAY AVE, STE 315
OKLAHOMA, OK 73102
(405) 525-2220
HEALTHCARE/MED
EQUIPMENT PLANNER
INNOVA GROUP
3196 N. SWAN ROAD
TUCSON, AZ 85712
(520) 886-8650
PHYSICAL SECURITY
FORCE PROTECT SECURITY
CONSULTANTS,
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
FOOD & BEVERAGE
PLANNER
STURM CONSULTING
5838 S. HUDSON PLACE
TULSA, OK 74135
(918) 260-0667
ENVIRONMENTAL
ENGINEER
RIVERFRONT ENVIRONMENTAL
1139 OLIVE STREET, STE 300
ST. LOUIS, MO 63101
(314) 436-9492
/2
/2
:1 :1
P
M
TECHNOLOGY SITE FIBER ROUTING
PLAN
MDT Drawing # 203 OF 222KGH
100% CONSTRUCTION DOCUMENTS
ADDITION AND RENOVATION
OF CLC
09/06/2023
589-703
ROBERT J. DOLE VA MEDICAL CENTER
5500 EAST KELLOGG, BLDG. 60
WICHITA, KS 67218
TS102
SPUR #: 2015
N
3/32" = 1'-0"
TECHNOLOGY SITE FIBER ROUTING PLAN1
ELECTRICAL KEYNOTES
1 PROVIDE ABOVE-CEILING TELECOMMUNICATION PATHWAY AND CABLES WITH 12-STRAND,
SINGLE-MODE FIBER AND 12-STRAND, MULTI-MODE FIBER AND (2) SPARE 4" CONDUIT RUNS
FROM TELECOMMUNICATION ROOM 009A IN BUILDING 4.
2 EXISTING FIBER PATHWAY AND CABLE TO REMAIN FROM IT CLOSET A107 ROUTED TO COMM
ROOM 1B126. ACTUAL PATH IS UNKNOWN.
3 PROVIDE UNDERGROUND TELECOMMUNICATION PATHWAY FROM EXISTING COMMUNICATIONS
MANHOLE-8. ROUTE (1) 4" CONCRETE-ENCASED CONDUIT WITH (4) 1" INTERDUCTS AND
CONDUCTORS WITH 12-STRAND, SINGLE-MODE FIBER AND 12-STRAND, MULTI-MODE FIBER
FROM THE DATACENTER IN BUILDING 4 AND (1) 4" CONCRETE-ENCASED CONDUIT WITH (4) 1"
INTERDUCTS AND CONDUCTORS WITH 6-STRAND, MULTI-MODE FIBER FOR SECURITY FROM
BUILDING 1 ROOM 113.
4 AFTER BACK-FEEDING EXISTING IT CLOSET A107 FROM THE NEW IT ROOM 116, DEMOLISH
EXISTING FIBER AND PATHWAY ROUTED FROM TR 009A IN BUILDING 4 TO IT CLOSET A107 IN
BUILDING 60. COORDINATE DATA OUTAGE DURING CUTOVER WITH VA PRIOR TO ROUGH-IN OF
NEW LINE.
5 UTILIZE EXISTING UNDERGROUND DUCT BANK PATHWAY TO ROUTE NEW FIBER FOR BUILDING
60. ROUTE 12-STRAND, SINGLE-MODE FIBER AND 12-STRAND, MULTI-MODE FIBER FROM THE
DATACENTER IN BUILDING 4 AND 6-STRAND, MULTI-MODE FIBER FOR SECURITY FROM
BUILDING 1 ROOM 113. (TYPICAL)
GENERAL NOTES:
A. THE AREA OF WORK SHOWN IS ASSOCIATED WITH AN OPERATING FACILITY THAT MUST
REMAIN IN SERVICE 24/7.
B. COORDINATE TECHNOLOGY WORK WITH ALL OTHER TRADES. VERIFY ALL EXISTING
CONDITIONS BEFORE THE START OF WORK.
C. SEE SHEETS GI011 AND GI012 FOR ADDITIONAL INFORMATION REGARDING SCHEDULE AND
PHASING REQUIREMENTS. SCHEDULE WORK TO MINIMIZE DISRUPTION OF SERVICES.
NOT TO SCALE
CONCRETE ENCASED CONDUIT DETAIL TECHNOLOGY2
ETD
ETD
E T
D
E T
D
E T
D
PS
P S
C B
P S
E T
D E
T D
E T
D
ETD
ETD
PS
E T
D
CBPS
E T
D
P S
PS
P S
PS
PS
ETD
PS PS PS
PS PS
ETD
E T
D
PS PS
PS
E T
D
E T
D
ETD
ETD
ETD
ETD
E T
D
KP
ML
IC
E T
D
PS
ETD
ETD
ETD
ETD
ETD
ETD
ETD
ETD
ETD
ETD
ETD
ETD
ETD ETD
ETD
ETD ETD
ETD
ETD
ETD
ETD
ETDETD
ETD
ETDETD
ETD
ETD ETD
ETD
ETD
ETD
ETD
ETD
P S
P S
P S
P S
P S
P S
P S
P S
P S
P S
P S
P S
E T
D
E T
D
PS
E T
D
E T
D
E T
D
E T
D
ETD
PS
IC
IC
IC
ICIC
LS
LSLS
LS
LS
LS
LS
LS
LS
LS
LS
LS
LS
LS
LS
LS
LS
LS
LS
LS
LS
NM
E T
D
E T
D
E T
D
PS
NM
PS
ETD
ETD
IC
E12E10
ED
E13
E7
EC
E4
EE
EG
EH
EI
OFFICE
101B
2 BED
TLC ROOM
1B116
2 BED
TLC ROOM
1B114
2 BED
TLC ROOM
1B112
2 BED
TLC ROOM
1B110
2 BED
TLC ROOM
1B108
2 BED
TLC ROOM
1B106
2 BED
TLC ROOM
1B115
2 BED
TLC ROOM
1B113
2 BED
TLC ROOM
1B111
2 BED
TLC ROOM
1B109
2 BED
TLC ROOM
1B107
2 BED
TLC ROOM
1B105
OPEN
OFFICE
1B103
OFFICE
1B103A
COPY
1B103B
TOILET
1B105A
TOILET
1B109A
TOILET
1B113A
CONFERENCE
ROOM
1B101
ACTIVITIES
ROOM
1B100
TOILET
1B101A
DOCTORS
OFFICE
1B119
2 BED
TLC ROOM
1B121
BREAK
ROOM
1B122
CONGREGATE
BATH
1B120
TLC
KITCHENETTE
1B146
2 BED
TLC ROOM
1B144
2 BED
TLC ROOM
1B145
2 BED
TLC ROOM
1B147
PSCHOLOGIST
1B123
SOCIAL
WORKER
1B143
TOILET
1B144A
TOILET
1B121A
LAUNDRY
1B151
TOILET
1B147A
MED
SUPPLY
1B152
COMPUTER
CHARGING
1B153
TOILET
1B114A
TOILET
1B110A
TOILET
1B108A
TOILET
1B106A
SOILED
UTILITY
1B104
CLEAN
LINEN
1B117
CLOSET
1B102
BARBER
1B118
TLC
MEDICATION
1B149
STAFF
TOILET
1B150
TOILET
1B120A
TLC NURSE
0-STATION
CORRIDOR
0-CORR-B1
OFFICE
1B100B
OXYGEN
OPEN
OFFICE
TOILET
1B100A
ELEC.
1B129
NURSE CALL
1B126
COMM.
1B128
JANITOR
1B124
OFFICE
1A100
ENTRY
OFFICE
LOBBY
RECEPTION
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. A-930 EXP. 12/31/2023
ENGR REG. NO. E-2586 EXP. 12/31/2023
STRUCTURAL/CIVIL
ENGINEER
H2B
1225 N. LOOP W #800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH
ENGINEER
SPUR DESIGN
11020 KING STREET, STE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
LANDSCAPE ARCHITECT
CLS & ASSOCIATES
825 N. BROADWAY AVE, STE 315
OKLAHOMA, OK 73102
(405) 525-2220
HEALTHCARE/MED
EQUIPMENT PLANNER
INNOVA GROUP
3196 N. SWAN ROAD
TUCSON, AZ 85712
(520) 886-8650
PHYSICAL SECURITY
FORCE PROTECT SECURITY
CONSULTANTS,
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
FOOD & BEVERAGE
PLANNER
STURM CONSULTING
5838 S. HUDSON PLACE
TULSA, OK 74135
(918) 260-0667
ENVIRONMENTAL
ENGINEER
RIVERFRONT ENVIRONMENTAL
1139 OLIVE STREET, STE 300
ST. LOUIS, MO 63101
(314) 436-9492
KEY PLAN
B
N
PHASING AND PROJECT SCOPE LEGEND
AREAS OF WORK OUTSIDE OF CURRENT PHASE OR OUTSIDE OF
PROJECT SCOPE SHOWN. REFERENCE GI011 & GI012 - PHASING PLANS
FOR MORE INFORMATION
/2
/2
:1 :0
P
M
TECHNOLOGY DEMOLITION PLAN
MDT Drawing # 204 OF 222KGH
100% CONSTRUCTION DOCUMENTS
ADDITION AND RENOVATION
OF CLC
09/06/2023
589-703
ROBERT J. DOLE VA MEDICAL CENTER
5500 EAST KELLOGG, BLDG. 60
WICHITA, KS 67218
TD101
SPUR #: 2015
N
1/8" = 1'-0"
TECHNOLOGY DEMOLITION PLAN1
GENERAL NOTES:
A. DISCONNECT AND REMOVE ALL CEILING MOUNTED FIRE ALARM DEVICES AND SECURITY DOOR HARDWARE
WITHIN THE AREA OF WORK.
B. DISCONNNECT AND REMOVE ALL DATA OUTLETS, ASSOCIATED CONDUITS, CABLES AND CABLE TRAYS, WITHIN
THE AREA OF WORK, BACK TO SERVER RACK IN COMM. ROOM 1B126.
C. ALL LOCATIONS ARE APPROXIMATE FIELD VERIFY EXACT COUNTS AND LOCATIONS PRIOR TO DEMOLITION.
D. DISCONNECT AND REMOVE ALL POWER, LIGHTING, DATA, AND LOW VOLTAGE CONDUIT, CABLING, DEVICES, AND
RACEWAYS ABOVE CEILING NO LONGER IN USE.
E. DISCONNECT AND REMOVE ALL POWER, DATA DEVICES, AND CABLING IN WALLS OR RAISED FLOORING NO LONGER IN USE. REMOVE ALL ASSOCIATED CONDUIT, JUNCTION BOXES, AND CONDUCTORS BACK TO FEEDER
BRANCH PANEL OR NETWORK SWITCH.
F. SHADED AREAS ARE OUT OF PROJECT SCOPE.
ELECTRICAL KEYNOTES
1 UNABLE TO ACCESS THIS ROOM DURING SITE INVESTIGATION. FIELD VERIFY NECESSARY DEMOLITION IN THIS ROOM
DURING DEMOLITION PHASE FOR VESTIBULE.
FD
FD
FD
FD
FD
FD
BC
PS
PSPS
BC BC BC BC
PS PS PS PS
BC BC
PS PS
BC BC
BC
PS
PS
BC
PS
BC
PS
BC
PS
PS
PS
PS
PS
LS
LS
LS
LS
LS
LS
LS
IC
IC
IC
IC
IC
IC
LS
LS
NM
BC
PS
PS
BC BCBC
PS
IC
DS
DS
DS
IC IC IC IC IC IC IC
IC
IC
IC
IC
IC
IC
IC
IC
PS PSPS
PS
ED
EB1
EC
E4
F
A
64321
C
G
7 85
RESIDENT
RESIDENT
RESIDENT
BATH
122A
BATH
134A
PANTRY
133C
HSKPG
133D
MULTIPURPOSE/
ACTIVITY ROOM
MP STOR
132A
CONF. / PRIVATE DINING
TLT
ART ROOM
BATH
145A
RESIDENT
BATH
146A
RESIDENT
KITCHEN
DINING
133B
LIVING ROOM
133A
STAFF LOUNGE
149TLT
CLEAN SUPPLY
HOUSE OFC
SOILED UTL
TOILET
117A
BATHING RM
IT ROOM
ELECTRICAL
HOUSE LNDRY
HOUSE STOR.
MED
BATH
136A
BATH
139A
RESIDENT
RESIDENT
RESIDENT
BATH
135A
RESIDENT
BATH
140A
BATH
142A
RESIDENT
DEN
RESIDENT, BARIATRIC
BATH
119A
RESIDENT
BATH
143A
FIRE RISER RM
115A
BATH
137A
RESIDENT
RESIDENT
BATH
138A
BATH
141A
RESIDENT
RESIDENT
RESIDENT
HAC
EQ. STOR
BATH
151A
RT OFC
BATH
152A
ALCOVE
008B
LIVING ROOM
1B101D
CHARTING ALCOVE
006B
1D/1TV
66"
EA
INDOOR COURTYARD SPACE INDOOR COURTYARD SPACE
1TV
1TV
66"
66"
1TV
1TV
66"
66"
VESTIBULE
008A
VESTIBULE
006A
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
TN201
66"
1TV
REFER TO
SHEET TN202 FOR
CONTINUATION
REFER TO
SHEET TN202 FOR
CONTINUATION
TN201
REFER TO
SHEET TN202 FOR
CONTINUATION
REFER TO
SHEET ES101 FOR
CONTINUATION
4 5
BATH
121A
66"
1TV
66"
1TV
1D
1D 36"
36"
1D
1TV
66" 1D 36"
1TV
66" 1D 36"
1TV
1D 66"
36"
1TV
1D 66"
36"
1TV
66" 1D 36"
1TV
1D 66"
36"
1TV
66" 1D 36"
1TV
1D 66"
36"
1TV
66" 1D 36"
1TV
1D 66"
36"
1D 36"
1D 36"
1D 36"
1D 36"
1D 36"
1TV
60"
1V
1V
1V 48"
48"
48"
2D/1V
2D/1V 2D/1V 4D
1D
1D
14 15
WAP WAP
WAP
WAP
WAP
WAP
WAP
WAP
W X
D
W X
D
4" W X 4" D 6" W X 4" D 16" W X 4" D
W X
D
2D
2D
2D 1D
1D
1D
42"
42"42" 42" 42" 42" 42" 42" 42"
42"
42"
42"
42"
42"
42"42"42"
E
4 5
N
1/8" = 1'-0"
TECHNOLOGY TELECOMMUNICATIONS PLAN - AREA A1
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. A-930 EXP. 12/31/2023
ENGR REG. NO. E-2586 EXP. 12/31/2023
STRUCTURAL/CIVIL
ENGINEER
H2B
1225 N. LOOP W #800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH
ENGINEER
SPUR DESIGN
11020 KING STREET, STE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
LANDSCAPE ARCHITECT
CLS & ASSOCIATES
825 N. BROADWAY AVE, STE 315
OKLAHOMA, OK 73102
(405) 525-2220
HEALTHCARE/MED
EQUIPMENT PLANNER
INNOVA GROUP
3196 N. SWAN ROAD
TUCSON, AZ 85712
(520) 886-8650
PHYSICAL SECURITY
FORCE PROTECT SECURITY
CONSULTANTS,
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
FOOD & BEVERAGE
PLANNER
STURM CONSULTING
5838 S. HUDSON PLACE
TULSA, OK 74135
(918) 260-0667
ENVIRONMENTAL
ENGINEER
RIVERFRONT ENVIRONMENTAL
1139 OLIVE STREET, STE 300
ST. LOUIS, MO 63101
(314) 436-9492
KEY PLAN
A
N
PHASING AND PROJECT SCOPE LEGEND
AREAS OF WORK OUTSIDE OF CURRENT PHASE OR OUTSIDE OF
PROJECT SCOPE SHOWN. REFERENCE GI011 & GI012 - PHASING PLANS
FOR MORE INFORMATION
/2
/2
:1 :0
P
M
TECHNOLOGY TELECOMMUNICATIONS
PLAN - AREA A
MDT Drawing # 205 OF 222KGH
100% CONSTRUCTION DOCUMENTS
ADDITION AND RENOVATION
OF CLC
09/06/2023
589-703
ROBERT J. DOLE VA MEDICAL CENTER
5500 EAST KELLOGG, BLDG. 60
WICHITA, KS 67218
TN201
SPUR #: 2015
N
1/4" = 1'-0" REF: 1/ TN201
IT ROOM 116 - ENLARGED PATHWAY PLAN2
N
1/4" = 1'-0" REF: 1/ TN201
IT ROOM 116 - ENLARGED PLAN3
GENERAL NOTES:
A. FOR THE TR ROOM, ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE.
TWO SCREW BONDING LUGS NEED TO BE INSTALLED TO BOND ALL METAL
ELEMENTS OF THE RACK AND RUNWAY SYSTEM TO THE TELECOMMUNICATIONS
SECONDARY BONDING BUSBAR.
B. THE AREA OF WORK SHOWN IS ASSOCIATED WITH AN OPERATING FACILITY THAT
MUST REMAIN IN SERVICE 24/7.
C. COORDINATE TECHNOLOGY WORK WITH ALL OTHER TRADES. VERIFY ALL
EXISTING CONDITIONS BEFORE THE START OF WORK.
D. SEE SHEETS GI011 AND GI012 FOR ADDITIONAL INFORMATION REGARDING
SCHEDULE AND PHASING REQUIREMENTS. SCHEDULE WORK TO MINIMIZE
DISRUPTION OF SERVICES.
E. ALL TELECOMMUNCATIONS CABLING SHALL BE CATEGORY 6A, PLENUM RATED
CABLE WITH SPLINE/SEPERATOR BETWEEN PAIRS. COORDINATE CABLE COLOR
CODE REQUIREMENTS WITH VA PRIOR TO BID.
F. INSTALL ALL SIGNAL PULL-BOXES WITH LOCKABLE COVERS.
ELECTRICAL KEYNOTES
1 INSTALL A NEW 4-POST DATA RACK AND 6" WIDE VERTICAL WIRE MANAGERS AS
SHOWN. (TYPICAL)
2 INSTALL A RACK MOUNTED HORIZONTAL BUS BAR AT THE TOP OF EACH RACK ON THE
BACK RAIL. (TYPICAL)
3 NEW SECONDARY UNDERGROUND TELECOMMUNICATION PATHWAY FROM
COMMUNICATIONS MANHOLE-8. (2) 2" CONCRETE ENCASED CONDUITS WITH
12-STRAND, SINGLE-MODE FIBER AND 12-STRAND, MULTI-MODE FIBER FROM THE
DATACENTER IN BUILDING 4. (TYPICAL)
4 NEW PRIMARY TELECOMMUNICATION PATHWAY THROUGH CORRIDOR FROM BUILDING
4. 2" CONDUIT WITH 12-STRAND, SINGLE-MODE FIBER AND 12-STRAND, MULTI-MODE
FIBER FROM THE DATACENTER IN BUILDING 4. (TYPICAL)
5 NEW PRIMARY BACK-FEED TELECOMMUNICATION PATHWAY TO EXISTING TR ROOM. 2"
CONDUIT WITH 12-STRAND, SINGLE-MODE FIBER AND 12-STRAND, MULTI-MODE FIBER
ROUTED ABOVE CEILING. (TYPICAL)
6 NEW SECONDARY BACK-FEED TELECOMMUNICATION PATHWAY TO EXISTING TR
ROOM. 2" CONDUIT WITH 12-STRAND, SINGLE-MODE FIBER AND 12-STRAND,
MULTI-MODE FIBER ROUTED ABOVE CEILING. (TYPICAL)
7 PROVIDE SEISMIC BRACING FOR ALL RACKS PER STRUCTURAL ENGINEER. (TYPICAL)
8 PROVIDE 18" CABLE TRAY. SUPPORT TRAY USING VERTICAL THREADED ROD AND
APPROPRIATE HARDWARE. REFER TO SPECIFICATIONS. (TYPICAL)
9 MOUNT ALL NEW CABLE TRAYS APPROXIMATELY 6" ABOVE RACK HEIGHT. USE
VERTICAL THREADED ROD FOR CABLE TRAY SUPPORT. USE CABLE TRAY EXITS AND
DROP OUTS FOR SMOOTH TRANSITION OF CABLES OUT OF THE CABLE TRAYS AND
INTO THE RACKS. (TYPICAL)
10 PROVIDE VERTICAL SUPPORT FOR CABLES ENTERING HERE. (TYPICAL)
11 INSTALL NEW FIRE RATED SLEEVE FOR CABLING THROUGH THE TR WALL TO THE
CORRIDOR. DO NOT EXCEED 40% FILL RATIO. (TYPICAL)
12 ROUTE 1" CONDUIT TO IRRIGATION CONTROLS, APPROXIMATE LOCATION INDICATED
ON SHEET TS101. COORDINATE EXACT LOCATION AND REQUIREMENTS WITH
LANDSCAPE DRAWINGS PRIOR TO ROUGH-IN.
13 PROVIDE (4) DATA DROPS, (1) PHONE DROP, (2) USB CONNECTION, AND (3) HDMI
CONNECTIONS WITHIN FLOOR BOX UNDER CONFERENCE TABLE. RUN USB AND HDMI
CABLE CONNECTIONS TO TV LOCATION WITHIN ROOM FOR CONNECTION TO TV
DISPLAY. MAKE CONNECTION TO INTEGRATED DATA OUTLETS WITHIN NEW
CONFERENCE ROOM TABLE. COORDINATE EXACT REQUIREMENTS WITH FINAL
FURNITURE SELECTIONS PRIOR TO ROUGH-IN.
14 ADD ONE DATA DROP, (2) USB CONNECTIONS, AND (3) HDMI CONNECTIONS. RUN USB
AND HDMI CONNECTION TO THE FLOOR BOX UNDER CONFERENCE TABLE. (TYPICAL)
15 MAKE CONNECTION TO VIDEO TELECONFERENCING SYSTEM. VERIFY REQUIREMENTS
WITH SUPPLIER PRIOR TO ROUGH-IN.
FD
FD
BC
BCBCBCBC
PSPSPSPSPSPS
BC
PS
BC
PS
PS
BC
BC
BCBC
PSPSPS
PS
PS
BC
LS LS
LS
LS
LS
LS
LS
LS
LS
IC
IC IC
IC
IC
IC
IC
IC
IC
IC
IC
NM
LS
SS
PS
BC
PS
NM
DS
DSDS
PS
J
IC
IC
IC
IC
IC IC IC
IC
IC
IC
IC IC IC IC IC IC ICICIC
IC IC
IC
IC
IC
IC
IC
IC
IC
IC
IC
IC
PS
E12E10
ED
E13 E7
E3
EC
E4 6
EE
EG
EH
EI
EF1
66"66"
66"
66"
66" 66"66"66" 66"
1D/1TV
66"
TN202
TN202
66"
REFER TO
SHEET TN201 FOR
CONTINUATION
REFER TO
SHEET TN201 FOR
CONTINUATION
REFER TO
SHEET TN201 FOR
CONTINUATION
66"
1D 1D 36"36"
1TV 1TV
1TV
1TV
1TV1TV
1D1D 1D1D
1TV 1TV
66"
1TV1TV
1D1D
36"36" 36"36" 36"36"
1TV
1D
66"
36"
1D 36"
1D
1D
1TV
66"
36"
1D
1TV
36"
1TV
1D1D/1V
1D/1V
1D/1V
1D/1V 1D
1D/1V
1D
1D/1V
1D/1V
1D/1V 1D/1V
1D
1D/1V
1D/1V
1D/1V
4D
1D
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V 4D
1D
42"
RESIDENT - B2
RESIDENT - B2
RESIDENT - B2
RESIDENT - B2
BATH
158A
BATH
157A
BATH
156A
BATH
155A
RESIDENT - B1
RESIDENT - B1
BATH
153A
HAC
RESIDENT - B1
RESIDENT - B1
BATH
162A
BATH
160A
RESIDENT - B1
BATH
164A
BATH
161A
BATH
159A
BATH
163A
MEDS
BATH
173A
RESIDENT - B2
02 FULL
167A
02 USED
167B
CLEAN SUPPLY
SOILED UTL
EQUIP STOR
SW OFC
NRS LDR OFC
MED DIR OFC
CLEAN LINEN
SOILED UTL
GENERAL STOR
TEAM WORKRM
DEN
BATHING RM
TLT
176A
RESIDENT - B2
BATH
175A
ELEC
H. LAUNDRY
DIR OFC
TLT
184A
RESIDENT - B2
RESIDENT - B2
H. STOR
HOUSE OFC
CLC RECEP
100A
KITCHEN
166 DINING
166B
LIVING ROOM
166A
RESIDENT DINING
MOP
131B
HAC
166D
PANTRY
166C
CRASH CART
013A
N&FS KITCHEN/
SERVERY
131A
ELEC
017A
COMM
017B
STOR
017C
HAC
017D
HOSPICE ROOM
HOSPICE ROOM
CORRIDOR
CHARTING ALCOVE
013C
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
STORAGE
110C
EXAM
110B
EXAM
110A
MENS
WOMENS
PHYSICAL THERAPY
EXAM
CORRIDOR
VESTIBULE
001A
WAITING
PT/OT RECEP
100B
HAC
SSTV
131C
TEAM WORKRM
1V
1V 48"
48"
1D/1V
1D/1V
1D
1D
36"
1D
1D/1V
1D/1V
1D
WAP
WAP
WAP WAP
WAP
WAP
WAP
WAP
WAP
W X
D
W X
D
VESTIBULE
014A
2D
42"
42"
42" 42" 42" 42"42" 42"
42"
42"
42"42"42"
EIIT ROOM
B126
IT RACK
(ETR)
TTB
(ETR)
E3
STAIRWELL
#1
IT CLOSET
A107
'MATV'
PACS
'TTB'
N
1/8" = 1'-0"
TECHNOLOGY TELECOMMUNICATIONS PLAN - AREA B1
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. A-930 EXP. 12/31/2023
ENGR REG. NO. E-2586 EXP. 12/31/2023
STRUCTURAL/CIVIL
ENGINEER
H2B
1225 N. LOOP W #800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH
ENGINEER
SPUR DESIGN
11020 KING STREET, STE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
LANDSCAPE ARCHITECT
CLS & ASSOCIATES
825 N. BROADWAY AVE, STE 315
OKLAHOMA, OK 73102
(405) 525-2220
HEALTHCARE/MED
EQUIPMENT PLANNER
INNOVA GROUP
3196 N. SWAN ROAD
TUCSON, AZ 85712
(520) 886-8650
PHYSICAL SECURITY
FORCE PROTECT SECURITY
CONSULTANTS,
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
FOOD & BEVERAGE
PLANNER
STURM CONSULTING
5838 S. HUDSON PLACE
TULSA, OK 74135
(918) 260-0667
ENVIRONMENTAL
ENGINEER
RIVERFRONT ENVIRONMENTAL
1139 OLIVE STREET, STE 300
ST. LOUIS, MO 63101
(314) 436-9492
KEY PLAN
B
N
PHASING AND PROJECT SCOPE LEGEND
AREAS OF WORK OUTSIDE OF CURRENT PHASE OR OUTSIDE OF
PROJECT SCOPE SHOWN. REFERENCE GI011 & GI012 - PHASING PLANS
FOR MORE INFORMATION
/2
/2
:1 :0
P
M
TECHNOLOGY TELECOMMUNICATIONS
PLAN - AREA B
MDT Drawing # 206 OF 222KGH
100% CONSTRUCTION DOCUMENTS
ADDITION AND RENOVATION
OF CLC
09/06/2023
589-703
ROBERT J. DOLE VA MEDICAL CENTER
5500 EAST KELLOGG, BLDG. 60
WICHITA, KS 67218
TN202
SPUR #: 2015
N
3/8" = 1'-0" REF: 1/ TN202
IT ROOM B126 ENLARGED LOW VOLTAGE PLAN2
N
3/8" = 1'-0" REF: 1/ TN202
IT CLOSET A107 ENLARGED LOW VOLTAGE PLAN3
ELECTRICAL KEYNOTES
1 NEW PRIMARY TELECOMMUNICATION PATHWAY THROUGH CORRIDOR FROM BUILDING 4. 2"
CONDUIT WITH 12-STRAND, SINGLE-MODE FIBER AND 12-STRAND, MULTI-MODE FIBER FROM
THE DATACENTER IN BUILDING 4. (TYPICAL)
2 NEW PRIMARY BACK-FEED TELECOMMUNICATION PATHWAY FROM NEW TR ROOM 116 IN
ADDITION. 2" CONDUIT WITH 12-STRAND, SINGLE-MODE FIBER AND 12-STRAND, MULTI-MODE
FIBER ROUTED ABOVE CEILING. (TYPICAL)
3 NEW SECONDARY BACK-FEED TELECOMMUNICATION PATHWAY FROM NEW TR ROOM 116 IN
ADDITION. PROVIDE ABOVE CEILING TELECOMMUNICATION PATHWAY AND CABLES WITH 2"
CONDUIT WITH 12-STRAND, SINGLE-MODE FIBER AND 12-STRAND, MULTI-MODE FIBER ROUTED
ABOVE CEILING FROM NEW IT ROOM 116 TO EXISTING IT CLOSET A107. DEMOLISH EXISTING
FIBER AND PATHWAY ROUTED FROM TR 009A IN BUILDING 4 TO IT CLOSET A107 IN BUILDING 60
AFTER BACK-FEEDING IT CLOSET A107 FROM NEW IT ROOM 116. COORDINATE DATA OUTAGE
DURING CUTOVER WITH VA PRIOR TO ROUGH-IN OF NEW LINE. (TYPICAL)
4 APPROXIMATE LOCATION OF IRRIGATION CONTROLS. TERMINATE 1" CONDUIT RUN INDICATED
ON SHEET TN301. COORDINATE EXACT LOCATION AND REQUIREMENTS WITH LANDSCAPE
DRAWINGS PRIOR TO ROUGH-IN.
5 APPROXIMATE LOCATION OF 125A LOAD CENTER FOR SERVING COUNTER INSTALLED BY
OTHERS. MAKE NECESSARY CONNECTIONS AT 18" AFF AND COORDINATE EXACT
REQUIREMENTS WITH FOODSERVICE DRAWINGS.
6 PROVIDE JUNCTION BOX AND BLANK FACEPLATE TO ROUGH-IN DATA FOR FUTURE USE.
CONNECT AND STUB 3/4" CONDUIT ABOVE ACCESSIBLE CEILING.
GENERAL NOTES:
A. FOR THE TR ROOM, ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO
SCREW BONDING LUGS NEED TO BE INSTALLED TO BOND ALL METAL ELEMENTS OF THE
RACK AND RUNWAY SYSTEM TO THE TELECOMMUNICATIONS SECONDARY BONDING
BUSBAR.
B. THE AREA OF WORK SHOWN IS ASSOCIATED WITH AN OPERATING FACILITY THAT MUST
REMAIN IN SERVICE 24/7.
C. COORDINATE TECHNOLOGY WORK WITH ALL OTHER TRADES. VERIFY ALL EXISTING
CONDITIONS BEFORE THE START OF WORK.
D. SEE SHEETS GI011 GI012 FOR ADDITIONAL INFORMATION REGARDING SCHEDULE AND
PHASING REQUIREMENTS. SCHEDULE WORK TO MINIMIZE DISRUPTION OF SERVICES.
E. ALL TELECOMMUNCATIONS CABLING SHALL BE CATEGORY 6A, PLENUM RATED CABLE
WITH SPLINE/SEPERATOR BETWEEN PAIRS. COORDINATE CABLE COLOR CODE
REQUIREMENTS WITH VA PRIOR TO BID.
F. INSTALL ALL SIGNAL PULL-BOXES WITH LOCKABLE COVERS.
6" W X 4" D
4" W X 4" D
W X
D
4" W X 4" D 10" W X 4" D
DM LAML
CR
DM
LAML
CR
DM LAML
CR
DM
DM
LAML
CR
DM
ML
CR
DM
EL
LACR
DM
EL
LA
CR
PB
PB
PB
PB
PB
ELDMLA
CR
ELDMLA
CR
DM
DM
LAML
CR
MD
DM
EL
LA
CR
DM
EL
LA
CR
DMDM
DMDM
CR
ML
ML DM
DMLA
MD
CR
LA DM
CR
EL DMLA
DMDM
CR
ML
EL DM LA
CR
CR
EL
KS
KS
MD
MD
MD
DS
MD
LA
MD MD MD
MD
MD
MD
MD
MD
MD
EL
IC
ED
E1 E2 E3
EB1
EC
E4
F
A
64321
C
G
7 85
EA
RESIDENT
RESIDENT
RESIDENT
BATH
122A
BATH
134A
PANTRY
133C
HSKPG
133D
MULTIPURPOSE/
ACTIVITY ROOM
MP STOR
132A
CONF. / PRIVATE DINING
TLT
ART ROOM
BATH
145A
RESIDENT
BATH
146A
RESIDENT
KITCHEN
DINING
133B
LIVING ROOM
133A
STAFF LOUNGE
TLT
CLEAN SUPPLY
HOUSE OFC
SOILED UTL
TOILET
117A
BATHING RM
IT ROOM
ELECTRICAL
HOUSE LNDRY
HOUSE STOR.
MED
BATH
136A
BATH
139A
RESIDENT
RESIDENT
RESIDENT
BATH
135A
RESIDENT
BATH
140A
BATH
142A
RESIDENT
DEN
RESIDENT, BARIATRIC
BATH
119A
RESIDENT
BATH
143A
FIRE RISER RM
115A
BATH
137A
RESIDENT
RESIDENT
BATH
138A
BATH
141A
RESIDENT
RESIDENT
RESIDENT
HAC
EQ. STOR
BATH
151A
RT OFC
BATH
152A
ALCOVE
008B
CHARTING ALCOVE
006B
INDOOR COURTYARD SPACE INDOOR COURTYARD SPACE
VESTIBULE
008A
VESTIBULE
006A
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
BATH
121A
CR-01
CR-01
CR-01
CR-01
CR-02
CR-01
CR-01
CR-01
CR-01
CR-01 CR-01
CR-01
CR-01
CR-01
CR-01
CR-01
CR-01
115A
006A
008C
008A
T-402
T-402
T-402
T-402
T-402
T-402
T-402
T-402
T-402
T-402
T-402
T-402
T-402
T-402
T-402
T-402
T-402
T-402 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. A-930 EXP. 12/31/2023
ENGR REG. NO. E-2586 EXP. 12/31/2023
STRUCTURAL/CIVIL
ENGINEER
H2B
1225 N. LOOP W #800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH
ENGINEER
SPUR DESIGN
11020 KING STREET, STE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
LANDSCAPE ARCHITECT
CLS & ASSOCIATES
825 N. BROADWAY AVE, STE 315
OKLAHOMA, OK 73102
(405) 525-2220
HEALTHCARE/MED
EQUIPMENT PLANNER
INNOVA GROUP
3196 N. SWAN ROAD
TUCSON, AZ 85712
(520) 886-8650
PHYSICAL SECURITY
FORCE PROTECT SECURITY
CONSULTANTS,
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
FOOD & BEVERAGE
PLANNER
STURM CONSULTING
5838 S. HUDSON PLACE
TULSA, OK 74135
(918) 260-0667
ENVIRONMENTAL
ENGINEER
RIVERFRONT ENVIRONMENTAL
1139 OLIVE STREET, STE 300
ST. LOUIS, MO 63101
(314) 436-9492
KEY PLAN
A
N
PHASING AND PROJECT SCOPE LEGEND
AREAS OF WORK OUTSIDE OF CURRENT PHASE OR OUTSIDE OF
PROJECT SCOPE SHOWN. REFERENCE GI011 & GI012 - PHASING PLANS
FOR MORE INFORMATION
/2
/2
:1 :1
P
M
TECHNOLOGY SECURITY PLAN - AREA A
MDT Drawing # 207 OF 222KGH
100% CONSTRUCTION DOCUMENTS
ADDITION AND RENOVATION
OF CLC
09/06/2023
589-703
ROBERT J. DOLE VA MEDICAL CENTER
5500 EAST KELLOGG, BLDG. 60
WICHITA, KS 67218
TY301
SPUR #: 2015
N
1/8" = 1'-0"
TECHNOLOGY SECURITY PLAN - AREA A1
ELECTRICAL KEYNOTES
1 PROVIDE AN INTERIOR CEILING MOUNTED 180-DEGREE MULTISENSOR,
MOTION ACTIVATED SSTV CAMERA. MAKE CONNECTION TO NEW SSTV
SYSTEM. (TYPICAL)
2 PROVIDE AN INTERIOR CEILING MOUNTED 360-DEGREE MULTISENSOR,
MOTION ACTIVATED SSTV CAMERA. MAKE CONNECTION TO NEW SSTV
SYSTEM. (TYPICAL)
3 PROVIDE AN INTERIOR CEILING MOUNTED 360-DEGREE FISHEYE,
MULTISENSOR, MOTION ACTIVATED SSTV CAMERA. MAKE CONNECTION
TO NEW SSTV SYSTEM.
4 PROVIDE AN INTERIOR CEILING MOUNTED SINGLE VIEW MULTISENSOR,
MOTION ACTIVATED SSTV CAMERA. MAKE CONNECTION TO NEW SSTV
SYSTEM. (TYPICAL)
5 PROVIDE SECURITY DEVICES SHOWN ON THE EXISTING GATE TO THE
FENCED EXTERIOR UTILITY YARD.
6 PROVIDE INTERCOM CALL STATION CONNECTED TO CLC RECEPTION
DESK AND CAMPUS SECURITY CONTROL CENTER. (TYPICAL)
GENERAL NOTES:
A. THE AREA OF WORK SHOWN IS ASSOCIATED WITH AN OPERATING FACILITY
THAT MUST REMAIN IN SERVICE 24/7.
B. COORDINATE TECHNOLOGY WORK WITH ALL OTHER TRADES. VERIFY ALL
EXISTING CONDITIONS BEFORE THE START OF WORK.
C. SEE SHEETS GI011 AND GI012 FOR ADDITIONAL INFORMATION REGARDING
SCHEDULE AND PHASING REQUIREMENTS. SCHEDULE WORK TO MINIMIZE
DISRUPTION OF SERVICES.
D. ALL CARD READER SYSTEMS WITH AUTOMATIC DOOR CONTROLS SHALL BE
WIRED TO AUTOMATICALLY OPEN DOORS UPON CARD READER
AUTHENTICATION.
E. PROVIDE CATEGORY 6A CABLING TO ALL CARD READERS AND SECURITY
CAMERAS WITHIN THE SCOPE OF WORK.
F. ENSURE LYNX PANIC/DURESS IS INSTALLED ON EVERY PC KEYBOARD
WITHIN AREA OF SCOPE AND TIED TO THE CAMPUS SECURITY CONTROL
CENTER.
DM
EL
LA
CR
ELDMLA
CR
ELDMLA
CR
ML
DM
LA
DM
CR
DM
DM
ML
CR
LA
DM
DM
ML
CR
KS
EL
CR
EL
CR
EL
CR
EL
CR
PB
PB
PB
IC
IC
ML
DM
AD
DM
CR
EL
CR
EL
CR
DM
EL
LA
CR
ELDMLA
CR
CR
CR
CR
CR
EL
EL
EL
EL
LA
LA
LA
LA
DM
DM
DM
DM
DM DM
KS
DM DM
ML KS
DM
DM
ML
KS
ELDMLA
CR
ELDMLA
CR
CR
EL
LA
DM
CR CR
CR
ML
LA MD DM
MD
MD
DM MD
DM MD
DM MD
MD
MD
MD
MD
MD
MD
MD
MD
MD
DM MD
DM
MD
LA
MD
LA
ML
MD
E12E10
ED
E13E7E2 E3
EC
E4 6421
EE
EG
EH
EI
EF1
4 5
CR-01
CR-01
CR-01
CR-01
CR-01
CR-01
CR-01
CR-01
CR-01
CR-01
CR-01
CR-01
CR-02
CR-01
RESIDENT - B2
RESIDENT - B2
RESIDENT - B2
RESIDENT - B2
BATH
158A
BATH
157A
BATH
156A
BATH
155A
RESIDENT - B1
RESIDENT - B1
BATH
153A
HAC
RESIDENT - B1
RESIDENT - B1
BATH
162A
BATH
160A
RESIDENT - B1
BATH
164A
BATH
161A
BATH
159A
BATH
163A
MEDS
BATH
173A
RESIDENT - B2
02 FULL
167A
02 USED
167B
CLEAN SUPPLY
SOILED UTL
EQUIP STOR
SW OFC
NRS LDR OFC
MED DIR OFC
CLEAN LINEN
SOILED UTL
GENERAL STOR
TEAM WORKRM
TEAM WORKRM
DEN
BATHING RM
TLT
176A
RESIDENT - B2
BATH
175A
ELEC
H. LAUNDRY
DIR OFC
TLT
184A
RESIDENT - B2
RESIDENT - B2
H. STOR
HOUSE OFC
CLC RECEP
100A
KITCHEN
DINING
166B
LIVING ROOM
166A
RESIDENT DINING
MOP
131B
HAC
166D
PANTRY
166C
CRASH CART
013A
N&FS KITCHEN/
SERVERY
131A
ELEC
017A
COMM
017B
STOR
017C
HAC
017D
HOSPICE ROOM
HOSPICE ROOM
CORRIDOR
VESTIBULE
014A
CHARTING ALCOVE
013C
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
STORAGE
110C
EXAM
110B
EXAM
110A
MENS
WOMENS
PHYSICAL THERAPY
ROOM
103A
EXAM
CORRIDOR
CORRIDOR
VESTIBULE
001A
WAITING
PT/OT RECEP
100B
HAC
SSTV
131C
CR-01
CR-01
CR-01
CR-01
CR-01
CR-01
CR-01
CR-01CR-01
166D
182181
D
C
A
M
100B
A
014B
T-402
T-402
T-402
T-402
T-402
T-402
T-402
T-402
T-402
T-402
T-402
T-402
T-402
T-402
T-402
T-402
T-402
CR-01
T-402
T-402
T-402
T-402
T-402
CR-01
T-402
T-402
T-402 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. A-930 EXP. 12/31/2023
ENGR REG. NO. E-2586 EXP. 12/31/2023
STRUCTURAL/CIVIL
ENGINEER
H2B
1225 N. LOOP W #800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH
ENGINEER
SPUR DESIGN
11020 KING STREET, STE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
LANDSCAPE ARCHITECT
CLS & ASSOCIATES
825 N. BROADWAY AVE, STE 315
OKLAHOMA, OK 73102
(405) 525-2220
HEALTHCARE/MED
EQUIPMENT PLANNER
INNOVA GROUP
3196 N. SWAN ROAD
TUCSON, AZ 85712
(520) 886-8650
PHYSICAL SECURITY
FORCE PROTECT SECURITY
CONSULTANTS,
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
FOOD & BEVERAGE
PLANNER
STURM CONSULTING
5838 S. HUDSON PLACE
TULSA, OK 74135
(918) 260-0667
ENVIRONMENTAL
ENGINEER
RIVERFRONT ENVIRONMENTAL
1139 OLIVE STREET, STE 300
ST. LOUIS, MO 63101
(314) 436-9492
KEY PLAN
B
N
PHASING AND PROJECT SCOPE LEGEND
AREAS OF WORK OUTSIDE OF CURRENT PHASE OR OUTSIDE OF
PROJECT SCOPE SHOWN. REFERENCE GI011 & GI012 - PHASING PLANS
FOR MORE INFORMATION
/2
/2
:1 :1
P
M
TECHNOLOGY SECURITY PLAN - AREA B
MDT Drawing # 208 OF 222KGH
100% CONSTRUCTION DOCUMENTS
ADDITION AND RENOVATION
OF CLC
09/06/2023
589-703
ROBERT J. DOLE VA MEDICAL CENTER
5500 EAST KELLOGG, BLDG. 60
WICHITA, KS 67218
TY302
SPUR #: 2015
N
1/8" = 1'-0"
TECHNOLOGY SECURITY PLAN - AREA B1
ELECTRICAL KEYNOTES
1 PROVIDE NEW SSTV SWITCH WITHIN A WALL MOUNTED LOCKABLE CABINET
(BASIS OF DESIGN: STARTECH #CAB1019WALL) AND CONNECT TO CAMPUS
SECURITY CONTROL CENTER. SEE SSTV RISER DIAGRAM FOR MORE DETAIL
AND CAMERA CONNECTIONS.
2 PROVIDE AN INTERIOR CEILING MOUNTED 360-DEGREE MULTISENSOR,
MOTION ACTIVATED SSTV CAMERA. MAKE CONNECTION TO NEW SSTV
SYSTEM. (TYPICAL)
3 PROVIDE AN INTERIOR CEILING MOUNTED 180-DEGREE MULTISENSOR,
MOTION ACTIVATED SSTV CAMERA. MAKE CONNECTION TO NEW SSTV
SYSTEM. (TYPICAL)
4 PROVIDE SSTV CAMERA TO BE PROGRAMMED WITH FACIAL ANALYTICS.
5 PROVIDE INTERCOM CALL STATION CONNECTED TO CLC RECEPTION DESK
AND CAMPUS SECURITY CONTROL CENTER. (TYPICAL)
6 PROVIDE GOVERNMENT-SUPPLIED FULLTIME PASSIVE SCREENING SYSTEM
(BASIS OF DESIGN METRASENS PROSCREEN 200) INTERLOCKED WITH THE
INTERIOR SET OF SLIDING DOORS TO CLOSE & LOCK UPON POSITIVE
DETECTION AND NOTIFY CAMPUS SECURITY CONTROL CENTER.
7 PROVIDE PACS TERMINATION PANEL WITHIN A WALL MOUNTED LOCKABLE
CABINET (BASIS OF DESIGN: STARTECH #CAB1019WALL) AS AN EXTENSION OF
THE EXISTING ADVANTOR SYSTEM IN IT CLOSET A107. SYSTEM MUST BE
CCURE 9000 COMPATIBLE AND ABLE TO TIE BACK INTO THE EXISTING CAMPUS
WIDE PACS SYSTEM. SYSTEM HEAD END IS LOCATED IN BUILDING 62 ROOM 41.
GENERAL NOTES:
A. THE AREA OF WORK SHOWN IS ASSOCIATED WITH AN OPERATING FACILITY
THAT MUST REMAIN IN SERVICE 24/7.
B. COORDINATE TECHNOLOGY WORK WITH ALL OTHER TRADES. VERIFY ALL
EXISTING CONDITIONS BEFORE THE START OF WORK.
C. SEE SHEETS GI011 AND GI012 FOR ADDITIONAL INFORMATION REGARDING
SCHEDULE AND PHASING REQUIREMENTS. SCHEDULE WORK TO MINIMIZE
DISRUPTION OF SERVICES.
D. ALL CARD READER SYSTEMS WITH AUTOMATIC DOOR CONTROLS SHALL BE
WIRED TO AUTOMATICALLY OPEN DOORS UPON CARD READER
AUTHENTICATION.
E. PROVIDE CATEGORY 6A CABLING TO ALL CARD READERS AND SECURITY
CAMERAS WITHIN THE SCOPE OF WORK.
GATE
OPERATOR
CONTROL
CABINET
AUXILIARY
CABINET
GRADE
PROVIDE REQUIRED
CONNECTIONS TO VEHICLE
DETECTION LOOPS
GROUND ROD
PROVIDE CONCRETE EQUIPMENT PAD
FOR CONTROL CABINET AND AUXILIARY
CABINET PER MANUFACTURER'S
SPECIFICATIONS
MOUNT CABINETS TO CONCRETE
PAD PER MANUFACTURER'S
INSTRUCTIONS TO ENSURE RAM
PROOF INSTALLATION
LAY-IN CEILING
PROVIDE 4-11/16" X 4-11/16" X
2-1/8" DOUBLE-GANG
BACKBOX WITH
SINGLE-GANG PLASTER
RING.
CEILING TILE ADJUSTABLE
BOX HANGER
ROUTE MINIMUM 1"
RACEWAY AND CABLING
BACK TO SECURITY
SYSTEM HEAD-END
EQUIPMENT IN
COMMUNICATIONS ROOM.
PROVIDE MINIMUM 18" OF
SECURITY CAMERA CABLING
INSIDE BOX WITH DIRECT
CONNECTION TO SECURITY
CAMERA.
DOME CAMERA
CAT 6A
CAT 6ACAT 6A
NOTE:
PERMANENTLY LABEL ALL WALL JACKS IN THE FOLLOWING MANNER: BUILDING-FLOOR-JACK NUMBER-ROOM
NUMBER OF CLOSET. EXAMPLE: 1-1-33-148B (BUILDING 1, FLOOR 1, JACK 33, CLOSET ROOM NUMBER 148B). JACK