0001 Attachment 2i Combined Drawings Construct Addition and Renovated Bldg 60.pdf

PDF 8 MB Posted

Attached to
Y1DA--589-703 Construct Addition and Renovate Community Living Center, Building 60 (VA-24-00028736)
Solicitation number
36C77624B0019
Issued by

About this file

This document is a federal contract opportunity solicitation from the Department of Veterans Affairs Technology Acquisition Center Austin for the construction of an addition and renovation of the Community Living Center, Building 60, at the Robert J. Dole VA Medical Center in Wichita, Kansas. The key details include:

The solicitation number is 36C77624B0019, with an opportunity type of Solicitation and a description of "Y1DA--589-703 Construct Addition and Renovate Community Living Center, Building 60 (VA-24-00028736)". The agency involved is the Department of Veterans Affairs Technology Acquisition Center Austin. The statement of work is provided as an attachment. No additional details on pricing, set-asides, incumbents, or award dates are included in the provided materials.

View the file

Other files

File Type Posted
36C77624B0019 0003.pdf PDF
0002 Attachment 4 Bldg 60 Asbestos Survey.pdf PDF
0002 Attachment 3 DBA Wage Determination Sedgewick 20240906.pdf PDF
0002 Attachment 2 589-703 Bldg. 60 Site Visit Sign-in Sheet.pdf PDF
0002 Attachment 1 Technical Questions Received Responses.docx DOCX document
36C77624B0019 0002.pdf PDF
0001 Attachment 2c Combined Drawings Construct Addition and Renovated Bldg 60.pdf PDF
0001 Attachment 2h Combined Drawings Construct Addition and Renovated Bldg 60.pdf PDF
0001 Attachment 2a Combined Drawings Construct Addition and Renovated Bldg 60.pdf PDF
0001 Attachment 2g Combined Drawings Construct Addition and Renovated Bldg 60.pdf PDF
0001 Attachment 2b Combined Drawings Construct Addition and Renovated Bldg 60.pdf PDF
0001 Attachment 2d Combined Drawings Construct Addition and Renovated Bldg 60.pdf PDF
0001 Attachment 2f Combined Drawings Construct Addition and Renovated Bldg 60.pdf PDF
0001 Attachment 2e Combined Drawings Construct Addition and Renovated Bldg 60.pdf PDF
36C77624B0019 0001.pdf PDF
Attachment 1 FINAL SPECS Construct Addition and Renovate Bldg 60.pdf PDF
Attachment 2e Combined Drawings Construct Addition and Renovated Bldg 60.pdf PDF
Attachment 4 Limitations on Subcontracting - Construction.docx DOCX document
Attachment 2i Combined Drawings Construct Addition and Renovated Bldg 60.pdf PDF
Attachment 2h Combined Drawings Construct Addition and Renovated Bldg 60.pdf PDF
Attachment 2c Combined Drawings Construct Addition and Renovated Bldg 60.pdf PDF
Attachment 2b Combined Drawings Construct Addition and Renovated Bldg 60.pdf PDF
Attachment 2f Combined Drawings Construct Addition and Renovated Bldg 60.pdf PDF
FINAL SPECS Attachment 2 Geotech Report.pdf PDF
Attachment 2g Combined Drawings Construct Addition and Renovated Bldg 60.pdf PDF
Attachment 3 DBA Wage Determination Sedgwick - 20240522.pdf PDF
Attachment 2d Combined Drawings Construct Addition and Renovated Bldg 60.pdf PDF
36C77624B0019_1.docx DOCX document
Attachment 5 Division Cost Breakdown - 5-29-24.xlsx XLSX spreadsheet
Attachment 2a Combined Drawings Construct Addition and Renovated Bldg 60.pdf PDF
FINAL SPECS Attachment 1 Contract Documents Addendum 01.pdf PDF
Show all 31

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Z

CB

B

DS

E

EP

LS

KS

NA

NM

SS

BC

PS

CATV

FO

T

T/D

D

S

IC

UC

SSTV

IC

WAP

#D/#TV

V

CR

DM

EL

GB

MD

PB

RE

EC

LA

GO

COMMUNICATIONS OUTLET, TYPE AS NOTED

COMMUNICATIONS OUTLET, FLOOR BOX, TYPE AS NOTED

WIRELESS ACCESS POINT, CEILING MOUNTED

COMMUNICATIONS OUTLET, CEILING MTD, TYPE AS NOTED

SPEAKER, CEILING MOUNTED

SERVER RACK, TWO-POST, FLOOR MOUNTED

3/4"x4'x8', FIRE-RATED PLYWOOD BACKBOARD

GROUND BAR, TYPE AS NOTED

SERVER RACK, WALL MOUNTED

CABLE TRAY, TYPE AS NOTED

CABLE TELEVISION LINE

FIBEROPTIC LINE

TELEPHONE LINE

TELEPHONE/DATA LINE

DATA LINE

SPEAKER LINE

INTERCOM LINE

VOLUME CONTROL, WALL MOUNTED

CODE BLUE PUSHBUTTON STATION

DUTY STATION

STAFF EMERGENCY ASSIST STATION

PATIENT EMERGENCY PULL CORD STATION

STAFF LOCATOR SENSOR

NURSE CALL KEY SWITCH

NURSE CALL VISUAL ANNUNCIATOR PANEL

NURSE CALL MASTER STATION

STAFF STATION (NORMAL, EMERGENCY & CODE BLUE)

DOME LIGHT, WALL MOUNTED

DOME LIGHT, CEILING MOUNTED

ZONE DOME LIGHT

MULTI-SERVICE POWER POLE WITH POWER/DATA,

TYPE AS NOTED AND/OR SCHEDULED

UNDERGROUND COMMUNICATIONS LINE,

CABLING TYPE AS NOTED

MULTI-SERVICE FLOOR BOX/POKE-THRU WITH POWER/DATA,

TYPE AS NOTED AND/OR SCHEDULED

SERVER RACK, FOUR-POST, FLOOR MOUNTED

SERVER CABINET, FLOOR MOUNTED

CLOSED CIRCUIT TELEVISION LINE, MIN. 1" RACEWAY

CARD READER, PROXIMITY TYPE W/ KEYPAD

DOOR POSITION MONITOR

ELECTRIFIED LOCKING DEVICE, LATCH BOLT MONITOR,

GLASS BREAK DETECTOR

MOTION DETECTOR

DURESS PUSHBUTTON

REQUEST TO EXIT BUTTON

SINGLE VIEW SECURITY CAMERA

EMERGENCY CALL STATION

LOCAL DOOR POSITION ALARM/ANTI-PROP

GATE OPENER

DUAL VIEW SECURITY CAMERA

180-DEGREE PANORAMIC VIEW SECURITY CAMERA

270-DEGREE PANORAMIC/MULTI-IMAGE VIEW

360-DEGREE PANORAMIC/MULTI-IMAGE VIEW

SECURITY CAMERA

SECURITY CAMERA

PATIENT STATION WITH BED CONNECTOR; MOUNTED AT

42" AFF

PATIENT STATION WITH CODE BLUE

SECURITY SYMBOLS

#D = DATA, # = QUANTITY OF CABLES

#TV = CABLE TELEVISION, # = QUANTITY OF CABLES

#D = DATA, # = QUANTITY OF CABLES

#TV = CABLE TELEVISION, # = QUANTITY OF CABLES

#V = VOICE, # = QUANTITY OF CABLES

#D = DATA, # = QUANTITY OF CABLES

#E = ELEVATOR, # = QUANTITY OF CABLES

#FMS = FACILITY MONITORING SYSTEM,

# = QUANTITY OF CABLES

NURSE CALL SYMBOLS

COMMUNICATION SYMBOLS

#TV = CABLE TELEVISION, # = QUANTITY OF CABLES

#V = VOICE, # = QUANTITY OF CABLES

WP - WEATHERPROOF

ML MAGNETIC LOCK

CU

MECHANICAL OR FIRE SPRINKLER PLAN NOTE CALL OUT

PLUMBING PLAN NOTE CALL OUT

ELECTRICAL, TECHNOLOGY OR FIRE ALARM

PLUMBING EQUIPMENT DESIGNATION

EQUIPMENT DESIGNATION TAG

OWNER FURNISHED, CONTRACTOR INSTALLED

EQUIPMENT DESIGNATION

NEW WORK TO EXISTING WORK CONNECTION POINT

DETAIL REFERENCE

SECTION CUT DESIGNATION

ELECTRICAL: (AFF, AFG UNLESS NOTED OTHERWISE)

PLAN NOTE CALL OUT

EP-101

EP-101

M (CONT'D)

MV MEDIUM VOLTAGE

MVA MEGAVOLT-AMPERE

MW MEGAWATT

AUDIBLE APPLIANCES (CENTERLINE) 84"

ALARMS (TOP) 48"

ANNUNCIATOR PANELS (TOP) 48"

CLOCK OUTLETS (CENTERLINE) 84"

CONTROLS (TOP) 48"

EXIT SIGNS (WALL-MOUNTED, BOTTOM) 80"

FIRE ALARM ANNUNCIATOR PANEL (DISPLAY) 60"

FIRE ALARM BELL (EXTERIOR) 120"

FIRE ALARM CONTROL PANEL/UNIT (DISPLAY) 60"

INTERCOM (AFEA ONLY) 36"

INTERCOMS (TOP) 48"

PANELS & PANELBOARDS (TOP) 72"

PULL STATIONS (TOP) 48"

PHOTOCELLS 144"

RECEPTACLES (BOTTOM) 18"

RECEPTACLES, EXTERIOR (BOTTOM) 24"

RECEPTACLES, GARAGES (BOTTOM) 26"

RECEPTACLES IN EQUIPMENT ROOMS (TOP) 48"

RECEPTACLES ABOVE COUNTERTOPS (TOP) 44"

REMOTE INDICATING LIGHT, EQUIPMENT ROOMS (TOP) 48"

REMOTE INDICATING LIGHT, FINISHED AREAS (TOP) CEILING

SAFETY SWITCHES & STARTERS 48"

SWITCHES (TOP) 48"

TELEPHONE/DATA/TV OUTLETS (BOTTOM) 18"

VISIBLE APPLIANCES (CENTERLINE) 84"

X

W

V

U

T

S

R

ANNOTATION STANDARD MOUNTING HEIGHTS

P

O

N

M

L

K

J

I

H

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FABL FIRE ALARM BELL

FABX FIRE ALARM BOX

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FI FILM ILLUMINATOR

FIXT FIXTURE

FLA FULL LOAD AMPS

FLEX FLEXIBLE METALLIC CONDUIT

FLUOR FLUORESCENT

FO FIBER-OPTIC

FP FIRE PROTECTION

FT FEET OR FOOT

FVNR FULL VOLTAGE NON-REVERSING

FVR FULL VOLTAGE REVERSING

G

F

E

D

EC EMPTY CONDUIT

EG EQUIPMENT GROUND

EL ELEVATION

ELEC ELECTRIC OR ELECTRICAL

ELEV ELEVATOR

EMCP EMER. MONITORING CONTROL PANEL

EMER EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

EPO EMERGENCY POWER OFF

ESMT EASEMENT

ETD EXISTING TO BE DEMOLISHED

ETR EXISTING TO REMAIN

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EXIST EXISTING

DB DECIBEL OR DIRECT BURIAL

DC DIRECT CURRENT

DCP DIMMER CONTROL PANEL

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLITION

DIAG DIAGRAM

DISC DISCONNECT

DISTR DISTRIBUTION

DISTR PNL DISTRIBUTION PANEL

DN DOWN

DPDT DOUBLE POLE, DOUBLE THROW

DPST DOUBLE POLE, SINGLE THROW

DRSW DOOR SWITCH

DS DISCONNECT SWITCH

DWG DRAWING

C CONDUIT

CAP CAPACITY

CAT CATALOG

CATV COMMUNITY ANTENNA TELEVISION

CCR CONTROL CONTACTOR

CCTV CLOSED CIRCUIT TELEVISION

cd CANDELA

CD CONSTRUCTION DOCUMENTS

CF CONTRACTOR FURNISHED

CF/CI CONTRACTOR FURNISHED/

CONTRACTOR INSTALLED

CF/OI CONTRACTOR FURNISHED/

OWNER

CFE CONTRACTOR FURNISHED

EQUIPMENT

CHW CHILLED WATER

CHWP CHILLED WATER PUMP

CKT CIRCUIT

CKT BRKR CIRCUIT BREAKER

CLF CURRENT LIMITING FUSE

CLG CEILING

CMU CONCRETE MASONRY UNIT

COAX COAX CABLE

COMM COMMUNICATION

CONC CONCRETE

CONT CONTINUE

CONTR CONTRACTOR

COORD COORDINATE

CPT CONTROL POWER TRANSFORMER

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CTV CABLE TELEVISION

CU COPPER

CU FT CUBIC FEET

C

B

A

ABBREVIATIONS

UFD UNDERFLOOR DUCT

UGND UNDERGROUND

UL UNDERWRITERS LABORATORY

UNO UNLESS NOTED OTHERWISE

UPS UNINTERRUPTIBLE POWER SUPPLY

UTIL UTILITY

V VOLT

VA VOLT AMPERE

VAR VOLT AMPERE REACTIVE

VCM VERTICAL CABLE MANAGER

VFD VARIABLE FREQUENCY DRIVE

VOLT VOLTAGE

TC TIME CLOCK

TEL TELEPHONE

TP TWISTED PAIR

TPS TWISTED PAIR SHIELDED

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

TYP TYPICAL

RCP REFLECTED CEILING PLAN

RCPT RECEPTACLE

REC RECESSED

REQD REQUIRED

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT MEAN SQUARE

RU RACK UNIT

N NEUTRAL

NA NOT APPLICABLE

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURERS ASSOCIATION

NFPA NATIONAL FIRE PROTECTION

ASSOCIATION

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NS NO SCALE

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OL OVERLOAD

MATV MASTER ANTENNA TELEVISION SYSTEM

MAX MAXIMUM

MC METAL-CLAD

MCA MINIMUM CIRCUIT AMPS

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MG MOTOR GENERATOR

MH MANHOLE

MIN MINIMUM

MOCP MAXIMUM OVERCURRENT PROTECTION

MLO MAIN LUGS ONLY

MT MOUNT

MTD MOUNTED

MTG MOUNTING

MTS MANUAL TRANSFER SWITCH

KV KILOVOLT

KVA KILOVOLT AMPERE

KVAH KILOVOLT AMPERE PER HOUR

KVAR KILOVOLT AMPERE REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

KWHM KILOWATT HOUR METER

JB OR J-BOX JUNCTION BOX

XFER TRANSFER

XFMR TRANSFORMER

XP EXPLOSION PROOF

LED LIGHT EMITTING DIODE

LF LINEAR FEET (FOOT)

LM LUMEN

LP LIGHT POLE

LPS LOW PRESSURE SODIUM

LRA LOCKED ROTOR AMPS

LTCP LOCAL TEMPERATURE CONTROL PANEL

LT LIGHT

LTG LIGHTING

LTG PNL LIGHTING PANEL

LTNG LIGHTNING

LV LOW VOLTAGE

W WATT

WH WATER HEATER

WP WEATHERPROOF

IESNA ILLUMINATION ENGINEERING

SOCIETY OF NORTH AMERICA

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

INCAND INCANDESCENT

IR INFRARED

IWH INSTANTANEOUS WATER HEATER

G OR GND GROUND OR GENERATOR

GEN GENERATOR

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GTB GROUND TERMINAL BOX

SCC SHORT CIRCUIT CAPACITY

SES SERVICE ENTRANCE SECTION

SD SMOKE DETECTOR

SF SQUARE FOOT (FEET)

SHT SHEET

SI INTERNATIONAL SYSTEM OF UNITS

SPEC SPECIFICATION

SPST SINGLE POLE, SINGLE THROW

SURF SURFACE

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

P POLE

PA PUBLIC ADDRESS

PB PANELBOARD, PULL BOX, OR

PUSHBUTTON

PBPU PREFABRICATED BEDSIDE PATIENT UNIT

PCB POLYCHLORINATED BIPHENYL

PEC PHOTOELECTRIC CELL

PED PEDESTAL

PEND PENDANT

PF POWER FACTOR

PH PHASE

PNL PANEL

POD POWER OPERATED DAMPER

POE POWER OVER ETHERNET

PP PATCH PANEL

PT POTENTIAL TRANSFORMER

PTRV POWER TYPE ROOF VENTILATION

PVC POLYVINYL CHLORIDE (PLASTIC)

PWR POWER

1P SINGLE POLE

1PH SINGLE-PHASE

3P THREE POLE

3PH THREE-PHASE

3W THREE WIRE

4W FOUR WIRE

A/C AIR CONDITIONING

A/E ARCHITECT/ENGINEER

AAP ALARM ANNUNCIATOR PANEL

AC ALTERNATING CURRENT OR

ARMORED

ACC ACCESSIBLE

ADDL ADDITIONAL

ADJ ADJACENT, ADJOINING

ADO AUTOMATIC DOOR OPENER

AF AMPERE FRAME OR AMP FUSE

AFC ABOVE FINISHED COUNTER,

AUTOMATIC FREQUENCY

CONTROL, OR AVAILABLE FAULT

CURRENT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AH AMPERE HOUR

AHJ AUTHORITY HAVING JURISDICTION

AIC AMPERE INTERRUPTING CAPACITY

ALT ALTERNATE

AMB OR A AMBIENT

AMP AMPERE

ARCH ARCHITECT

ASC AMPS SHORT CIRCUIT

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AV AUDIO VISUAL

HCM HORIZONTAL CABLE MANAGER

HID HIGH INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HT HEIGHT

HZ HERTZ

BAT BATTERY

BC BARE COPPER

BD BOARD

BFF BELOW FINISH FLOOR

BIL BASIC INSULATION LEVEL

BLDG BUILDING

BLK BLOCK

BPIP BOILER PLANT INSTRUMENTATION

PANEL

BRKR BREAKER

BYP BY PASS

IC INSULATION CONTACT

AD AUTOMATIC DOOR OPENER

IC WALL INTERCOM STATION

DS AIPHONE DOOR/GATE STATION

A. TECHNOLOGY PLANS AND SECTIONS ARE INTENDED TO

ACCURATELY ILLUSTRATE THE SCOPE OF WORK, BUT ARE STILL

DIAGRAMMATIC IN NATURE.

B. TECHNOLOGY DRAWINGS DO NOT SHOW ALL ACCESSORIES

TO BE INSTALLED. THE CONTRACTOR IS RESPONSIBLE FOR

ENSURING THAT ALL SYSTEMS ARE FULLY FUNCTIONAL AND

COMPLIANT WITH APPLICABLE CODES.

C. TECHNOLOGY DRAWINGS REFLECT COORDINATION EFFORTS

WITH BUILDING DISCIPLINES. HOWEVER, COORDINATION WITH

OTHER TRADES IS REQUIRED.

D. REFERENCE ARCHITECTURAL DRAWINGS FOR ADDITIONAL

INFORMATION REGARDING SCHEDULE AND PHASING

REQUIREMENTS. SCHEDULE WORK TO MINIMIZE DISRUPTION OF

SERVICES.

E. COORDINATE WITH SCHEDULE WITH THE CONTRACTING

OFFICER'S REPRESENTATIVE BEFORE THE START OF WORK.

F. NEW SERVER RACKS AND OTHER TECHNOLOGY EQUIPMENT

REQUIRE SHUTDOWN. COORDINATE SERVICE SHUTDOWN FOR

ALL EQUIPMENT WITH THE CONTRACTING OFFICER'S

REPRESENTATIVE.

G. MOUNTING HEIGHTS FOR DEVICES SHALL BE MEASURED FROM

FINAL FINISH FLOOR TO CENTER OF BOX.

GENERAL NOTES

PROJECT CODES AND STANDARDS

A. VA OFFICE OF INFORMATION & TECHNOLOGY (OIT) DESIGN

GUIDE, FEBRUARY 2011

B. VA OFFICE OF INFORMATION & TECHNOLOGY (OIT)

INFRASTRUCTURE STANDARDS FOR TELECOMMUNICATIONS

SPACES, JUNE 1 2023

C. INFRASTRUCTURE STANDARDS FOR TELECOMMUNICATIONS

SPACES, AUGUST 2020

D. VA PG-18-10 TELECOMMUNICATIONS AND SPECIAL

TELECOMMUNICATIONS SYSTEMS DESIGN MANUAL, FEBRUARY

E. BICSI AND EIA/TIA STANDARDS AS DEFINED IN VA-18-10

F. VA-PSRDM - PHYSICAL SECURITY AND RESILIENCY DESIGN

MANUAL 2020, 1 JUNE 2023 REVISION

KS KEY SWITCH

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. A-930 EXP. 12/31/2023

ENGR REG. NO. E-2586 EXP. 12/31/2023

STRUCTURAL/CIVIL

ENGINEER

H2B

1225 N. LOOP W #800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH

ENGINEER

SPUR DESIGN

11020 KING STREET, STE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

LANDSCAPE ARCHITECT

CLS & ASSOCIATES

825 N. BROADWAY AVE, STE 315

OKLAHOMA, OK 73102

(405) 525-2220

HEALTHCARE/MED

EQUIPMENT PLANNER

INNOVA GROUP

3196 N. SWAN ROAD

TUCSON, AZ 85712

(520) 886-8650

PHYSICAL SECURITY

FORCE PROTECT SECURITY

CONSULTANTS,

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

FOOD & BEVERAGE

PLANNER

STURM CONSULTING

5838 S. HUDSON PLACE

TULSA, OK 74135

(918) 260-0667

ENVIRONMENTAL

ENGINEER

RIVERFRONT ENVIRONMENTAL

1139 OLIVE STREET, STE 300

ST. LOUIS, MO 63101

(314) 436-9492

/2

/2

:1 :0

P

M

TECHNOLOGY SYMBOLS &

ABBREVIATIONS

MDT Drawing # 201 OF 222KGH

100% CONSTRUCTION DOCUMENTS

ADDITION AND RENOVATION

OF CLC

09/06/2023

589-703

ROBERT J. DOLE VA MEDICAL CENTER

5500 EAST KELLOGG, BLDG. 60

WICHITA, KS 67218

T-000

SPUR #: 2015

No. REVISION DESCRIPTION DATE

ECEC

T

T

T TT T T T T T

T T

T T

T T

T T

T T

T T

T T

T

TT

T T

T T

T T

T TT T T

T

T

T T

T

T T

DS

CR

DM

DM

T

TT T

DS CR

DMDM

T T

T T

TS101

COMM

MANHOLE

008 TN201

REFER TO DETAIL 2/ES101 FOR

DIRECT BURIAL CONDUIT

DETAIL (IN COORDINATION

WITH ELECTRICAL POWER)

12"x22" (NOMINAL

I.D.) HANDHOLE

TS101

REFER TO DETAIL 2/ES101 FOR

DIRECT BURIAL CONDUIT

DETAIL (IN COORDINATION

WITH ELECTRICAL POWER)

12"x22" (NOMINAL

I.D.) HANDHOLE

A1

CONTINUATION ON

DETAIL 1, SHEET

TS101.

1" CONCRETE-

ENCASED

CONDUIT

1" CONCRETE-

ENCASED

CONDUIT

12"x22" (NOMINAL

I.D.) HANDHOLE

CONTINUATION ON DETAIL 1,

SHEET TS101.

1" CONCRETE-

ENCASED

CONDUIT

1" CONCRETE-

ENCASED

CONDUIT

12"x22"

(NOMINAL I.D.)

HANDHOLE

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. A-930 EXP. 12/31/2023

ENGR REG. NO. E-2586 EXP. 12/31/2023

STRUCTURAL/CIVIL

ENGINEER

H2B

1225 N. LOOP W #800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH

ENGINEER

SPUR DESIGN

11020 KING STREET, STE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

LANDSCAPE ARCHITECT

CLS & ASSOCIATES

825 N. BROADWAY AVE, STE 315

OKLAHOMA, OK 73102

(405) 525-2220

HEALTHCARE/MED

EQUIPMENT PLANNER

INNOVA GROUP

3196 N. SWAN ROAD

TUCSON, AZ 85712

(520) 886-8650

PHYSICAL SECURITY

FORCE PROTECT SECURITY

CONSULTANTS,

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

FOOD & BEVERAGE

PLANNER

STURM CONSULTING

5838 S. HUDSON PLACE

TULSA, OK 74135

(918) 260-0667

ENVIRONMENTAL

ENGINEER

RIVERFRONT ENVIRONMENTAL

1139 OLIVE STREET, STE 300

ST. LOUIS, MO 63101

(314) 436-9492

KEY PLAN

N

/2

/2

:1 :1

P

M

TECHNOLOGY SITE PLAN

MDT Drawing # 202 OF 222KGH

100% CONSTRUCTION DOCUMENTS

ADDITION AND RENOVATION

OF CLC

09/06/2023

589-703

ROBERT J. DOLE VA MEDICAL CENTER

5500 EAST KELLOGG, BLDG. 60

WICHITA, KS 67218

TS101

SPUR #: 2015

N

1/16" = 1'-0"

TECHNOLOGY SITE PLAN - BUILDING 601

ELECTRICAL KEYNOTES

1 PROVIDE UNDERGROUND TELECOMMUNICATION PATHWAY FROM EXISTING COMMUNICATIONS

MANHOLE-8. ROUTE (1) 4" CONCRETE-ENCASED CONDUIT WITH (4) 1" INTERDUCTS AND

CONDUCTORS WITH 12-STRAND, SINGLE-MODE FIBER AND 12-STRAND, MULTI-MODE FIBER

FROM THE DATACENTER IN BUILDING 4 AND (1) 4" CONCRETE-ENCASED CONDUIT WITH (4) 1"

INTERDUCTS AND CONDUCTORS WITH 6-STRAND, MULTI-MODE FIBER FOR SECURITY FROM

BUILDING 1 ROOM 113.

2 PROVIDE EXTERIOR WALL MOUNTED 180-DEGREE MULTISENSOR, ZOOM, NIGHT VISION,

SECURITY CAMERA MOUNTED AT 144" AFF. MAKE CONNECTION TO NEW SSTV SYSTEM.

(TYPICAL)

3 ENSURE SSTV CAMERA IS PROGRAMMED WITH BEHAVIOR ANALYTICS TO COVER THE PARKING

LOTS AND BUILDING ENVELOPE APPROACH.

4 PROVIDE EXTERIOR WALL MOUNTED 90-DEGREE MOTION ACTIVATED, NIGHT VISION, SECURITY

CAMERA MOUNTED AT 144" AFF. MAKE CONNECTION TO NEW SSTV SYSTEM.

5 PROVIDE (1) 6'X3" ROUND POLE FOR THE MOUNTING OF A SSTV FACIAL ANALYTICS CAMERA.

(TYPICAL)

6 PROVIDE GATE ARM OPERATOR WITH GATE POSITION MONITOR TO INDICATE THE POSITION OF

THE GATE ARM. PROVIDE INTEGRATIONS TO ALLOW THE ACCESS CONTROL SYSTEM TO

CONDUCT POSITION MONITORING, REMOTE OPENING, OPEN SCHEDULE, ABILITY TO MAINTAIN

OPEN STATE FOR SCHEDULED PERIOD OF TIME, AND TO OPEN ON AUTHORIZED TRIPLE

AUTHENTICATION. (TYPICAL)

7 PROVIDE SSTV CAMERA TO BE PROGRAMMED WITH FACIAL ANALYTICS AS THE THIRD

AUTHENTICATION IN THE TRIPLE AUTHENTICATION PROCESS. COORDINATE EXACT MOUNTING

HEIGHT AT THE TIME OF INSTALLATION. (TYPICAL)

8 PROVIDE A POLE-MOUNTED LICENSE PLATE RECOGNITION (LPR) STANDARD RANGE CAMERA.

COORDINATE EXACT MOUNTING HEIGHT WITH CAMERA MANUFACTURERS AT THE TIME OF

INSTALLATION. CAMERA SHALL BE PROGRAMMED AS THE FIRST AUTHENTICATION IN THE

TRIPLE AUTHENTICATION PROCESS. (TYPICAL)

9 PROVIDE (1) 6'X3" ROUND POLE FOR THE MOUNTING OF A LICENSE PLATE RECOGNITION (LPR)

CAMERA. (TYPICAL)

10 PROVIDE VEHICLE DETECTION LOOP. COORDINATE CONNECTION INTO GATE OPERATING

SYSTEM CONTROLS. (TYPICAL)

11 PROVIDE ACCESS CONTROL TO THIS LOCATION VIA PIV READER PROGRAMMED AS THE

SECOND AUTHENTICATION IN THE TRIPLE AUTHENTICATION PROCESS. (TYPICAL)

12 PROVIDE AIPHONE (OR EQUIVALENT) TWO-WAY INTERCOM SYSTEM DOOR STATION AND WIRE

TO ACTIVATE WITH VEHICLE DETECTION LOOP. ROUTE 1" CONDUIT AND (1) CATEGORY 6 CABLE

WITH TAMPER PROOF SCREWS TO POLICE STATION. MAKE CONNECTION TO NEWLY INSTALLED

AIPHONE MASTER STATION IN CAMPUS SECURITY CONTROL CENTER. (TYPICAL)

13 INSTALL PRESERVED EMERGENCY CALL STATION AND CONNECT TO CAMPUS SECURITY

CONTROL CENTER.

14 PROVIDE DUAL-HEIGHT GATE ACCESS CONTROL PEDESTAL. (TYPICAL)

GENERAL NOTES:

A. THE AREA OF WORK SHOWN IS ASSOCIATED WITH AN OPERATING FACILITY THAT MUST

REMAIN IN SERVICE 24/7.

B. COORDINATE TECHNOLOGY WORK WITH ALL OTHER TRADES. VERIFY ALL EXISTING

CONDITIONS BEFORE THE START OF WORK.

C. SEE SHEETS GI011 AND GI012 FOR ADDITIONAL INFORMATION REGARDING SCHEDULE AND

PHASING REQUIREMENTS. SCHEDULE WORK TO MINIMIZE DISRUPTION OF SERVICES.

D. ALL CARD READER SYSTEMS WITH AUTOMATIC DOOR CONTROLS SHALL BE WIRED TO

AUTOMATICALLY OPEN DOORS UPON CARD READER AUTHENTICATION.

E. PROVIDE CATEGORY 6A CABLING TO ALL CARD READERS AND SECURITY CAMERAS WITHIN

THE SCOPE OF WORK.

F. ALL TELECOMMUNCATIONS CABLING SHALL BE CATEGORY 6A, PLENUM RATED CABLE WITH

SPLINE/SEPERATOR BETWEEN PAIRS. COORDINATE CABLE COLOR CODE REQUIREMENTS

WITH VA PRIOR TO BID.

N

3/16" = 1'-0" REF: 1/ TS101

TECHNOLOGY SITE PLAN - SOUTH SECURITY GATE3

BID DEDUCT ALTERNATE KEYED NOTES

A1. BID DEDUCT ALTERNATE #14: IF DEDUCT ALTERNATE IS ACCEPTED, OMIT ALL

CONDUCTORS, CONDUIT, TELECOMMUNICATION CABLING, SECURITY CABLING,

TELECOMMUNICATION DEVICES, AND SECURITY DEVICES SERVING THE SECURITY GATE.

N

3/16" = 1'-0" REF: 1/ TS101

TECHNOLOGY SITE PLAN - NORTH SECURITY GATE2

A1

T TT T T T T T

T TT T T T T T T T T T T T T T T T T T T T T T T T

T T

T T

T T

T T

T

T T

T T

T T

T

T TT T T T T T

T T

T

T T

T T

T

T

T

T T

T T

T T

T T

T

T

T

T T T T T T T T T T

T

T

T

T

T T T T T T T

T

T

T TT T

COMM

MANHOLE

COMM

MANHOLE

TELECOM

ROOM A009

BUILDING 4

IT CLOSET

A107

BUILDING 60

IT ROOM 116

BUILDING 60

COMM ROOM

1B126

BUILDING 60

IT ROOM 103

BUILDING 59

TS-102

COMM

MANHOLE

EXISTING

UNDERGOUND

TELECOM

PATHWAY

EXISTING

UNDERGOUND

TELECOM

PATHWAY

EXISTING

UNDERGOUND

TELECOM

PATHWAY

DIRECT-BURIED DUCT LINE

GENERAL NOTES:

1. CONCRETE SHALL BE 2000 P.S.I. @ 28 DAYS, OR AS SPECIFIED.

2. PROVIDE #4 REINFORCING RODS ON TOP AND BOTTOM OF DUCTS

WHEN CROSSING OR PLACED IN ROADWAYS.

3. MINIMUM COVER TO TOP OF ENVELOPE SHALL BE 610mm (24") OR AS

OTHERWISE SPECIFIED IN SECTION 26 05 41.

(24" MIN.)

76mm

3"

76mm

3"

76mm

3" m m m m

EXISTING SUBSTRATE

GRADE

4" CONDUITS WITH 4-1"

INTERDUCTS FOR

TELECOMMUNICATION

AND SECURITY FIBER

OPTICS

12-STRAND OS1 AND 12-

STRAND OM3 LOOSE TUBE

CABLES FROM COMM

MANHOLE 008 TO

BUILDING 60

6-STRAND OM3 LOOSE

TUBE CABLES FROM

COMM MANHOLE 008 TO

BUILDING 60

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. A-930 EXP. 12/31/2023

ENGR REG. NO. E-2586 EXP. 12/31/2023

STRUCTURAL/CIVIL

ENGINEER

H2B

1225 N. LOOP W #800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH

ENGINEER

SPUR DESIGN

11020 KING STREET, STE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

LANDSCAPE ARCHITECT

CLS & ASSOCIATES

825 N. BROADWAY AVE, STE 315

OKLAHOMA, OK 73102

(405) 525-2220

HEALTHCARE/MED

EQUIPMENT PLANNER

INNOVA GROUP

3196 N. SWAN ROAD

TUCSON, AZ 85712

(520) 886-8650

PHYSICAL SECURITY

FORCE PROTECT SECURITY

CONSULTANTS,

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

FOOD & BEVERAGE

PLANNER

STURM CONSULTING

5838 S. HUDSON PLACE

TULSA, OK 74135

(918) 260-0667

ENVIRONMENTAL

ENGINEER

RIVERFRONT ENVIRONMENTAL

1139 OLIVE STREET, STE 300

ST. LOUIS, MO 63101

(314) 436-9492

/2

/2

:1 :1

P

M

TECHNOLOGY SITE FIBER ROUTING

PLAN

MDT Drawing # 203 OF 222KGH

100% CONSTRUCTION DOCUMENTS

ADDITION AND RENOVATION

OF CLC

09/06/2023

589-703

ROBERT J. DOLE VA MEDICAL CENTER

5500 EAST KELLOGG, BLDG. 60

WICHITA, KS 67218

TS102

SPUR #: 2015

N

3/32" = 1'-0"

TECHNOLOGY SITE FIBER ROUTING PLAN1

ELECTRICAL KEYNOTES

1 PROVIDE ABOVE-CEILING TELECOMMUNICATION PATHWAY AND CABLES WITH 12-STRAND,

SINGLE-MODE FIBER AND 12-STRAND, MULTI-MODE FIBER AND (2) SPARE 4" CONDUIT RUNS

FROM TELECOMMUNICATION ROOM 009A IN BUILDING 4.

2 EXISTING FIBER PATHWAY AND CABLE TO REMAIN FROM IT CLOSET A107 ROUTED TO COMM

ROOM 1B126. ACTUAL PATH IS UNKNOWN.

3 PROVIDE UNDERGROUND TELECOMMUNICATION PATHWAY FROM EXISTING COMMUNICATIONS

MANHOLE-8. ROUTE (1) 4" CONCRETE-ENCASED CONDUIT WITH (4) 1" INTERDUCTS AND

CONDUCTORS WITH 12-STRAND, SINGLE-MODE FIBER AND 12-STRAND, MULTI-MODE FIBER

FROM THE DATACENTER IN BUILDING 4 AND (1) 4" CONCRETE-ENCASED CONDUIT WITH (4) 1"

INTERDUCTS AND CONDUCTORS WITH 6-STRAND, MULTI-MODE FIBER FOR SECURITY FROM

BUILDING 1 ROOM 113.

4 AFTER BACK-FEEDING EXISTING IT CLOSET A107 FROM THE NEW IT ROOM 116, DEMOLISH

EXISTING FIBER AND PATHWAY ROUTED FROM TR 009A IN BUILDING 4 TO IT CLOSET A107 IN

BUILDING 60. COORDINATE DATA OUTAGE DURING CUTOVER WITH VA PRIOR TO ROUGH-IN OF

NEW LINE.

5 UTILIZE EXISTING UNDERGROUND DUCT BANK PATHWAY TO ROUTE NEW FIBER FOR BUILDING

60. ROUTE 12-STRAND, SINGLE-MODE FIBER AND 12-STRAND, MULTI-MODE FIBER FROM THE

DATACENTER IN BUILDING 4 AND 6-STRAND, MULTI-MODE FIBER FOR SECURITY FROM

BUILDING 1 ROOM 113. (TYPICAL)

GENERAL NOTES:

A. THE AREA OF WORK SHOWN IS ASSOCIATED WITH AN OPERATING FACILITY THAT MUST

REMAIN IN SERVICE 24/7.

B. COORDINATE TECHNOLOGY WORK WITH ALL OTHER TRADES. VERIFY ALL EXISTING

CONDITIONS BEFORE THE START OF WORK.

C. SEE SHEETS GI011 AND GI012 FOR ADDITIONAL INFORMATION REGARDING SCHEDULE AND

PHASING REQUIREMENTS. SCHEDULE WORK TO MINIMIZE DISRUPTION OF SERVICES.

NOT TO SCALE

CONCRETE ENCASED CONDUIT DETAIL TECHNOLOGY2

ETD

ETD

E T

D

E T

D

E T

D

PS

P S

C B

P S

E T

D E

T D

E T

D

ETD

ETD

PS

E T

D

CBPS

E T

D

P S

PS

P S

PS

PS

ETD

PS PS PS

PS PS

ETD

E T

D

PS PS

PS

E T

D

E T

D

ETD

ETD

ETD

ETD

E T

D

KP

ML

IC

E T

D

PS

ETD

ETD

ETD

ETD

ETD

ETD

ETD

ETD

ETD

ETD

ETD

ETD

ETD ETD

ETD

ETD ETD

ETD

ETD

ETD

ETD

ETDETD

ETD

ETDETD

ETD

ETD ETD

ETD

ETD

ETD

ETD

ETD

P S

P S

P S

P S

P S

P S

P S

P S

P S

P S

P S

P S

E T

D

E T

D

PS

E T

D

E T

D

E T

D

E T

D

ETD

PS

IC

IC

IC

ICIC

LS

LSLS

LS

LS

LS

LS

LS

LS

LS

LS

LS

LS

LS

LS

LS

LS

LS

LS

LS

LS

NM

E T

D

E T

D

E T

D

PS

NM

PS

ETD

ETD

IC

E12E10

ED

E13

E7

EC

E4

EE

EG

EH

EI

OFFICE

101B

2 BED

TLC ROOM

1B116

2 BED

TLC ROOM

1B114

2 BED

TLC ROOM

1B112

2 BED

TLC ROOM

1B110

2 BED

TLC ROOM

1B108

2 BED

TLC ROOM

1B106

2 BED

TLC ROOM

1B115

2 BED

TLC ROOM

1B113

2 BED

TLC ROOM

1B111

2 BED

TLC ROOM

1B109

2 BED

TLC ROOM

1B107

2 BED

TLC ROOM

1B105

OPEN

OFFICE

1B103

OFFICE

1B103A

COPY

1B103B

TOILET

1B105A

TOILET

1B109A

TOILET

1B113A

CONFERENCE

ROOM

1B101

ACTIVITIES

ROOM

1B100

TOILET

1B101A

DOCTORS

OFFICE

1B119

2 BED

TLC ROOM

1B121

BREAK

ROOM

1B122

CONGREGATE

BATH

1B120

TLC

KITCHENETTE

1B146

2 BED

TLC ROOM

1B144

2 BED

TLC ROOM

1B145

2 BED

TLC ROOM

1B147

PSCHOLOGIST

1B123

SOCIAL

WORKER

1B143

TOILET

1B144A

TOILET

1B121A

LAUNDRY

1B151

TOILET

1B147A

MED

SUPPLY

1B152

COMPUTER

CHARGING

1B153

TOILET

1B114A

TOILET

1B110A

TOILET

1B108A

TOILET

1B106A

SOILED

UTILITY

1B104

CLEAN

LINEN

1B117

CLOSET

1B102

BARBER

1B118

TLC

MEDICATION

1B149

STAFF

TOILET

1B150

TOILET

1B120A

TLC NURSE

0-STATION

CORRIDOR

0-CORR-B1

OFFICE

1B100B

OXYGEN

OPEN

OFFICE

TOILET

1B100A

ELEC.

1B129

NURSE CALL

1B126

COMM.

1B128

JANITOR

1B124

OFFICE

1A100

ENTRY

OFFICE

LOBBY

RECEPTION

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. A-930 EXP. 12/31/2023

ENGR REG. NO. E-2586 EXP. 12/31/2023

STRUCTURAL/CIVIL

ENGINEER

H2B

1225 N. LOOP W #800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH

ENGINEER

SPUR DESIGN

11020 KING STREET, STE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

LANDSCAPE ARCHITECT

CLS & ASSOCIATES

825 N. BROADWAY AVE, STE 315

OKLAHOMA, OK 73102

(405) 525-2220

HEALTHCARE/MED

EQUIPMENT PLANNER

INNOVA GROUP

3196 N. SWAN ROAD

TUCSON, AZ 85712

(520) 886-8650

PHYSICAL SECURITY

FORCE PROTECT SECURITY

CONSULTANTS,

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

FOOD & BEVERAGE

PLANNER

STURM CONSULTING

5838 S. HUDSON PLACE

TULSA, OK 74135

(918) 260-0667

ENVIRONMENTAL

ENGINEER

RIVERFRONT ENVIRONMENTAL

1139 OLIVE STREET, STE 300

ST. LOUIS, MO 63101

(314) 436-9492

KEY PLAN

B

N

PHASING AND PROJECT SCOPE LEGEND

AREAS OF WORK OUTSIDE OF CURRENT PHASE OR OUTSIDE OF

PROJECT SCOPE SHOWN. REFERENCE GI011 & GI012 - PHASING PLANS

FOR MORE INFORMATION

/2

/2

:1 :0

P

M

TECHNOLOGY DEMOLITION PLAN

MDT Drawing # 204 OF 222KGH

100% CONSTRUCTION DOCUMENTS

ADDITION AND RENOVATION

OF CLC

09/06/2023

589-703

ROBERT J. DOLE VA MEDICAL CENTER

5500 EAST KELLOGG, BLDG. 60

WICHITA, KS 67218

TD101

SPUR #: 2015

N

1/8" = 1'-0"

TECHNOLOGY DEMOLITION PLAN1

GENERAL NOTES:

A. DISCONNECT AND REMOVE ALL CEILING MOUNTED FIRE ALARM DEVICES AND SECURITY DOOR HARDWARE

WITHIN THE AREA OF WORK.

B. DISCONNNECT AND REMOVE ALL DATA OUTLETS, ASSOCIATED CONDUITS, CABLES AND CABLE TRAYS, WITHIN

THE AREA OF WORK, BACK TO SERVER RACK IN COMM. ROOM 1B126.

C. ALL LOCATIONS ARE APPROXIMATE FIELD VERIFY EXACT COUNTS AND LOCATIONS PRIOR TO DEMOLITION.

D. DISCONNECT AND REMOVE ALL POWER, LIGHTING, DATA, AND LOW VOLTAGE CONDUIT, CABLING, DEVICES, AND

RACEWAYS ABOVE CEILING NO LONGER IN USE.

E. DISCONNECT AND REMOVE ALL POWER, DATA DEVICES, AND CABLING IN WALLS OR RAISED FLOORING NO LONGER IN USE. REMOVE ALL ASSOCIATED CONDUIT, JUNCTION BOXES, AND CONDUCTORS BACK TO FEEDER

BRANCH PANEL OR NETWORK SWITCH.

F. SHADED AREAS ARE OUT OF PROJECT SCOPE.

ELECTRICAL KEYNOTES

1 UNABLE TO ACCESS THIS ROOM DURING SITE INVESTIGATION. FIELD VERIFY NECESSARY DEMOLITION IN THIS ROOM

DURING DEMOLITION PHASE FOR VESTIBULE.

FD

FD

FD

FD

FD

FD

BC

PS

PSPS

BC BC BC BC

PS PS PS PS

BC BC

PS PS

BC BC

BC

PS

PS

BC

PS

BC

PS

BC

PS

PS

PS

PS

PS

LS

LS

LS

LS

LS

LS

LS

IC

IC

IC

IC

IC

IC

LS

LS

NM

BC

PS

PS

BC BCBC

PS

IC

DS

DS

DS

IC IC IC IC IC IC IC

IC

IC

IC

IC

IC

IC

IC

IC

PS PSPS

PS

ED

EB1

EC

E4

F

A

64321

C

G

7 85

RESIDENT

RESIDENT

RESIDENT

BATH

122A

BATH

134A

PANTRY

133C

HSKPG

133D

MULTIPURPOSE/

ACTIVITY ROOM

MP STOR

132A

CONF. / PRIVATE DINING

TLT

ART ROOM

BATH

145A

RESIDENT

BATH

146A

RESIDENT

KITCHEN

DINING

133B

LIVING ROOM

133A

STAFF LOUNGE

149TLT

CLEAN SUPPLY

HOUSE OFC

SOILED UTL

TOILET

117A

BATHING RM

IT ROOM

ELECTRICAL

HOUSE LNDRY

HOUSE STOR.

MED

BATH

136A

BATH

139A

RESIDENT

RESIDENT

RESIDENT

BATH

135A

RESIDENT

BATH

140A

BATH

142A

RESIDENT

DEN

RESIDENT, BARIATRIC

BATH

119A

RESIDENT

BATH

143A

FIRE RISER RM

115A

BATH

137A

RESIDENT

RESIDENT

BATH

138A

BATH

141A

RESIDENT

RESIDENT

RESIDENT

HAC

EQ. STOR

BATH

151A

RT OFC

BATH

152A

ALCOVE

008B

LIVING ROOM

1B101D

CHARTING ALCOVE

006B

1D/1TV

66"

EA

INDOOR COURTYARD SPACE INDOOR COURTYARD SPACE

1TV

1TV

66"

66"

1TV

1TV

66"

66"

VESTIBULE

008A

VESTIBULE

006A

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

TN201

66"

1TV

REFER TO

SHEET TN202 FOR

CONTINUATION

REFER TO

SHEET TN202 FOR

CONTINUATION

TN201

REFER TO

SHEET TN202 FOR

CONTINUATION

REFER TO

SHEET ES101 FOR

CONTINUATION

4 5

BATH

121A

66"

1TV

66"

1TV

1D

1D 36"

36"

1D

1TV

66" 1D 36"

1TV

66" 1D 36"

1TV

1D 66"

36"

1TV

1D 66"

36"

1TV

66" 1D 36"

1TV

1D 66"

36"

1TV

66" 1D 36"

1TV

1D 66"

36"

1TV

66" 1D 36"

1TV

1D 66"

36"

1D 36"

1D 36"

1D 36"

1D 36"

1D 36"

1TV

60"

1V

1V

1V 48"

48"

48"

2D/1V

2D/1V 2D/1V 4D

1D

1D

14 15

WAP WAP

WAP

WAP

WAP

WAP

WAP

WAP

W X

D

W X

D

4" W X 4" D 6" W X 4" D 16" W X 4" D

W X

D

2D

2D

2D 1D

1D

1D

42"

42"42" 42" 42" 42" 42" 42" 42"

42"

42"

42"

42"

42"

42"42"42"

E

4 5

N

1/8" = 1'-0"

TECHNOLOGY TELECOMMUNICATIONS PLAN - AREA A1

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. A-930 EXP. 12/31/2023

ENGR REG. NO. E-2586 EXP. 12/31/2023

STRUCTURAL/CIVIL

ENGINEER

H2B

1225 N. LOOP W #800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH

ENGINEER

SPUR DESIGN

11020 KING STREET, STE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

LANDSCAPE ARCHITECT

CLS & ASSOCIATES

825 N. BROADWAY AVE, STE 315

OKLAHOMA, OK 73102

(405) 525-2220

HEALTHCARE/MED

EQUIPMENT PLANNER

INNOVA GROUP

3196 N. SWAN ROAD

TUCSON, AZ 85712

(520) 886-8650

PHYSICAL SECURITY

FORCE PROTECT SECURITY

CONSULTANTS,

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

FOOD & BEVERAGE

PLANNER

STURM CONSULTING

5838 S. HUDSON PLACE

TULSA, OK 74135

(918) 260-0667

ENVIRONMENTAL

ENGINEER

RIVERFRONT ENVIRONMENTAL

1139 OLIVE STREET, STE 300

ST. LOUIS, MO 63101

(314) 436-9492

KEY PLAN

A

N

PHASING AND PROJECT SCOPE LEGEND

AREAS OF WORK OUTSIDE OF CURRENT PHASE OR OUTSIDE OF

PROJECT SCOPE SHOWN. REFERENCE GI011 & GI012 - PHASING PLANS

FOR MORE INFORMATION

/2

/2

:1 :0

P

M

TECHNOLOGY TELECOMMUNICATIONS

PLAN - AREA A

MDT Drawing # 205 OF 222KGH

100% CONSTRUCTION DOCUMENTS

ADDITION AND RENOVATION

OF CLC

09/06/2023

589-703

ROBERT J. DOLE VA MEDICAL CENTER

5500 EAST KELLOGG, BLDG. 60

WICHITA, KS 67218

TN201

SPUR #: 2015

N

1/4" = 1'-0" REF: 1/ TN201

IT ROOM 116 - ENLARGED PATHWAY PLAN2

N

1/4" = 1'-0" REF: 1/ TN201

IT ROOM 116 - ENLARGED PLAN3

GENERAL NOTES:

A. FOR THE TR ROOM, ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE.

TWO SCREW BONDING LUGS NEED TO BE INSTALLED TO BOND ALL METAL

ELEMENTS OF THE RACK AND RUNWAY SYSTEM TO THE TELECOMMUNICATIONS

SECONDARY BONDING BUSBAR.

B. THE AREA OF WORK SHOWN IS ASSOCIATED WITH AN OPERATING FACILITY THAT

MUST REMAIN IN SERVICE 24/7.

C. COORDINATE TECHNOLOGY WORK WITH ALL OTHER TRADES. VERIFY ALL

EXISTING CONDITIONS BEFORE THE START OF WORK.

D. SEE SHEETS GI011 AND GI012 FOR ADDITIONAL INFORMATION REGARDING

SCHEDULE AND PHASING REQUIREMENTS. SCHEDULE WORK TO MINIMIZE

DISRUPTION OF SERVICES.

E. ALL TELECOMMUNCATIONS CABLING SHALL BE CATEGORY 6A, PLENUM RATED

CABLE WITH SPLINE/SEPERATOR BETWEEN PAIRS. COORDINATE CABLE COLOR

CODE REQUIREMENTS WITH VA PRIOR TO BID.

F. INSTALL ALL SIGNAL PULL-BOXES WITH LOCKABLE COVERS.

ELECTRICAL KEYNOTES

1 INSTALL A NEW 4-POST DATA RACK AND 6" WIDE VERTICAL WIRE MANAGERS AS

SHOWN. (TYPICAL)

2 INSTALL A RACK MOUNTED HORIZONTAL BUS BAR AT THE TOP OF EACH RACK ON THE

BACK RAIL. (TYPICAL)

3 NEW SECONDARY UNDERGROUND TELECOMMUNICATION PATHWAY FROM

COMMUNICATIONS MANHOLE-8. (2) 2" CONCRETE ENCASED CONDUITS WITH

12-STRAND, SINGLE-MODE FIBER AND 12-STRAND, MULTI-MODE FIBER FROM THE

DATACENTER IN BUILDING 4. (TYPICAL)

4 NEW PRIMARY TELECOMMUNICATION PATHWAY THROUGH CORRIDOR FROM BUILDING

4. 2" CONDUIT WITH 12-STRAND, SINGLE-MODE FIBER AND 12-STRAND, MULTI-MODE

FIBER FROM THE DATACENTER IN BUILDING 4. (TYPICAL)

5 NEW PRIMARY BACK-FEED TELECOMMUNICATION PATHWAY TO EXISTING TR ROOM. 2"

CONDUIT WITH 12-STRAND, SINGLE-MODE FIBER AND 12-STRAND, MULTI-MODE FIBER

ROUTED ABOVE CEILING. (TYPICAL)

6 NEW SECONDARY BACK-FEED TELECOMMUNICATION PATHWAY TO EXISTING TR

ROOM. 2" CONDUIT WITH 12-STRAND, SINGLE-MODE FIBER AND 12-STRAND,

MULTI-MODE FIBER ROUTED ABOVE CEILING. (TYPICAL)

7 PROVIDE SEISMIC BRACING FOR ALL RACKS PER STRUCTURAL ENGINEER. (TYPICAL)

8 PROVIDE 18" CABLE TRAY. SUPPORT TRAY USING VERTICAL THREADED ROD AND

APPROPRIATE HARDWARE. REFER TO SPECIFICATIONS. (TYPICAL)

9 MOUNT ALL NEW CABLE TRAYS APPROXIMATELY 6" ABOVE RACK HEIGHT. USE

VERTICAL THREADED ROD FOR CABLE TRAY SUPPORT. USE CABLE TRAY EXITS AND

DROP OUTS FOR SMOOTH TRANSITION OF CABLES OUT OF THE CABLE TRAYS AND

INTO THE RACKS. (TYPICAL)

10 PROVIDE VERTICAL SUPPORT FOR CABLES ENTERING HERE. (TYPICAL)

11 INSTALL NEW FIRE RATED SLEEVE FOR CABLING THROUGH THE TR WALL TO THE

CORRIDOR. DO NOT EXCEED 40% FILL RATIO. (TYPICAL)

12 ROUTE 1" CONDUIT TO IRRIGATION CONTROLS, APPROXIMATE LOCATION INDICATED

ON SHEET TS101. COORDINATE EXACT LOCATION AND REQUIREMENTS WITH

LANDSCAPE DRAWINGS PRIOR TO ROUGH-IN.

13 PROVIDE (4) DATA DROPS, (1) PHONE DROP, (2) USB CONNECTION, AND (3) HDMI

CONNECTIONS WITHIN FLOOR BOX UNDER CONFERENCE TABLE. RUN USB AND HDMI

CABLE CONNECTIONS TO TV LOCATION WITHIN ROOM FOR CONNECTION TO TV

DISPLAY. MAKE CONNECTION TO INTEGRATED DATA OUTLETS WITHIN NEW

CONFERENCE ROOM TABLE. COORDINATE EXACT REQUIREMENTS WITH FINAL

FURNITURE SELECTIONS PRIOR TO ROUGH-IN.

14 ADD ONE DATA DROP, (2) USB CONNECTIONS, AND (3) HDMI CONNECTIONS. RUN USB

AND HDMI CONNECTION TO THE FLOOR BOX UNDER CONFERENCE TABLE. (TYPICAL)

15 MAKE CONNECTION TO VIDEO TELECONFERENCING SYSTEM. VERIFY REQUIREMENTS

WITH SUPPLIER PRIOR TO ROUGH-IN.

FD

FD

BC

BCBCBCBC

PSPSPSPSPSPS

BC

PS

BC

PS

PS

BC

BC

BCBC

PSPSPS

PS

PS

BC

LS LS

LS

LS

LS

LS

LS

LS

LS

IC

IC IC

IC

IC

IC

IC

IC

IC

IC

IC

NM

LS

SS

PS

BC

PS

NM

DS

DSDS

PS

J

IC

IC

IC

IC

IC IC IC

IC

IC

IC

IC IC IC IC IC IC ICICIC

IC IC

IC

IC

IC

IC

IC

IC

IC

IC

IC

IC

PS

E12E10

ED

E13 E7

E3

EC

E4 6

EE

EG

EH

EI

EF1

66"66"

66"

66"

66" 66"66"66" 66"

1D/1TV

66"

TN202

TN202

66"

REFER TO

SHEET TN201 FOR

CONTINUATION

REFER TO

SHEET TN201 FOR

CONTINUATION

REFER TO

SHEET TN201 FOR

CONTINUATION

66"

1D 1D 36"36"

1TV 1TV

1TV

1TV

1TV1TV

1D1D 1D1D

1TV 1TV

66"

1TV1TV

1D1D

36"36" 36"36" 36"36"

1TV

1D

66"

36"

1D 36"

1D

1D

1TV

66"

36"

1D

1TV

36"

1TV

1D1D/1V

1D/1V

1D/1V

1D/1V 1D

1D/1V

1D

1D/1V

1D/1V

1D/1V 1D/1V

1D

1D/1V

1D/1V

1D/1V

4D

1D

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V 4D

1D

42"

RESIDENT - B2

RESIDENT - B2

RESIDENT - B2

RESIDENT - B2

BATH

158A

BATH

157A

BATH

156A

BATH

155A

RESIDENT - B1

RESIDENT - B1

BATH

153A

HAC

RESIDENT - B1

RESIDENT - B1

BATH

162A

BATH

160A

RESIDENT - B1

BATH

164A

BATH

161A

BATH

159A

BATH

163A

MEDS

BATH

173A

RESIDENT - B2

02 FULL

167A

02 USED

167B

CLEAN SUPPLY

SOILED UTL

EQUIP STOR

SW OFC

NRS LDR OFC

MED DIR OFC

CLEAN LINEN

SOILED UTL

GENERAL STOR

TEAM WORKRM

DEN

BATHING RM

TLT

176A

RESIDENT - B2

BATH

175A

ELEC

H. LAUNDRY

DIR OFC

TLT

184A

RESIDENT - B2

RESIDENT - B2

H. STOR

HOUSE OFC

CLC RECEP

100A

KITCHEN

166 DINING

166B

LIVING ROOM

166A

RESIDENT DINING

MOP

131B

HAC

166D

PANTRY

166C

CRASH CART

013A

N&FS KITCHEN/

SERVERY

131A

ELEC

017A

COMM

017B

STOR

017C

HAC

017D

HOSPICE ROOM

HOSPICE ROOM

CORRIDOR

CHARTING ALCOVE

013C

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

STORAGE

110C

EXAM

110B

EXAM

110A

MENS

WOMENS

PHYSICAL THERAPY

EXAM

CORRIDOR

VESTIBULE

001A

WAITING

PT/OT RECEP

100B

HAC

SSTV

131C

TEAM WORKRM

1V

1V 48"

48"

1D/1V

1D/1V

1D

1D

36"

1D

1D/1V

1D/1V

1D

WAP

WAP

WAP WAP

WAP

WAP

WAP

WAP

WAP

W X

D

W X

D

VESTIBULE

014A

2D

42"

42"

42" 42" 42" 42"42" 42"

42"

42"

42"42"42"

EIIT ROOM

B126

IT RACK

(ETR)

TTB

(ETR)

E3

STAIRWELL

#1

IT CLOSET

A107

'MATV'

PACS

'TTB'

N

1/8" = 1'-0"

TECHNOLOGY TELECOMMUNICATIONS PLAN - AREA B1

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. A-930 EXP. 12/31/2023

ENGR REG. NO. E-2586 EXP. 12/31/2023

STRUCTURAL/CIVIL

ENGINEER

H2B

1225 N. LOOP W #800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH

ENGINEER

SPUR DESIGN

11020 KING STREET, STE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

LANDSCAPE ARCHITECT

CLS & ASSOCIATES

825 N. BROADWAY AVE, STE 315

OKLAHOMA, OK 73102

(405) 525-2220

HEALTHCARE/MED

EQUIPMENT PLANNER

INNOVA GROUP

3196 N. SWAN ROAD

TUCSON, AZ 85712

(520) 886-8650

PHYSICAL SECURITY

FORCE PROTECT SECURITY

CONSULTANTS,

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

FOOD & BEVERAGE

PLANNER

STURM CONSULTING

5838 S. HUDSON PLACE

TULSA, OK 74135

(918) 260-0667

ENVIRONMENTAL

ENGINEER

RIVERFRONT ENVIRONMENTAL

1139 OLIVE STREET, STE 300

ST. LOUIS, MO 63101

(314) 436-9492

KEY PLAN

B

N

PHASING AND PROJECT SCOPE LEGEND

AREAS OF WORK OUTSIDE OF CURRENT PHASE OR OUTSIDE OF

PROJECT SCOPE SHOWN. REFERENCE GI011 & GI012 - PHASING PLANS

FOR MORE INFORMATION

/2

/2

:1 :0

P

M

TECHNOLOGY TELECOMMUNICATIONS

PLAN - AREA B

MDT Drawing # 206 OF 222KGH

100% CONSTRUCTION DOCUMENTS

ADDITION AND RENOVATION

OF CLC

09/06/2023

589-703

ROBERT J. DOLE VA MEDICAL CENTER

5500 EAST KELLOGG, BLDG. 60

WICHITA, KS 67218

TN202

SPUR #: 2015

N

3/8" = 1'-0" REF: 1/ TN202

IT ROOM B126 ENLARGED LOW VOLTAGE PLAN2

N

3/8" = 1'-0" REF: 1/ TN202

IT CLOSET A107 ENLARGED LOW VOLTAGE PLAN3

ELECTRICAL KEYNOTES

1 NEW PRIMARY TELECOMMUNICATION PATHWAY THROUGH CORRIDOR FROM BUILDING 4. 2"

CONDUIT WITH 12-STRAND, SINGLE-MODE FIBER AND 12-STRAND, MULTI-MODE FIBER FROM

THE DATACENTER IN BUILDING 4. (TYPICAL)

2 NEW PRIMARY BACK-FEED TELECOMMUNICATION PATHWAY FROM NEW TR ROOM 116 IN

ADDITION. 2" CONDUIT WITH 12-STRAND, SINGLE-MODE FIBER AND 12-STRAND, MULTI-MODE

FIBER ROUTED ABOVE CEILING. (TYPICAL)

3 NEW SECONDARY BACK-FEED TELECOMMUNICATION PATHWAY FROM NEW TR ROOM 116 IN

ADDITION. PROVIDE ABOVE CEILING TELECOMMUNICATION PATHWAY AND CABLES WITH 2"

CONDUIT WITH 12-STRAND, SINGLE-MODE FIBER AND 12-STRAND, MULTI-MODE FIBER ROUTED

ABOVE CEILING FROM NEW IT ROOM 116 TO EXISTING IT CLOSET A107. DEMOLISH EXISTING

FIBER AND PATHWAY ROUTED FROM TR 009A IN BUILDING 4 TO IT CLOSET A107 IN BUILDING 60

AFTER BACK-FEEDING IT CLOSET A107 FROM NEW IT ROOM 116. COORDINATE DATA OUTAGE

DURING CUTOVER WITH VA PRIOR TO ROUGH-IN OF NEW LINE. (TYPICAL)

4 APPROXIMATE LOCATION OF IRRIGATION CONTROLS. TERMINATE 1" CONDUIT RUN INDICATED

ON SHEET TN301. COORDINATE EXACT LOCATION AND REQUIREMENTS WITH LANDSCAPE

DRAWINGS PRIOR TO ROUGH-IN.

5 APPROXIMATE LOCATION OF 125A LOAD CENTER FOR SERVING COUNTER INSTALLED BY

OTHERS. MAKE NECESSARY CONNECTIONS AT 18" AFF AND COORDINATE EXACT

REQUIREMENTS WITH FOODSERVICE DRAWINGS.

6 PROVIDE JUNCTION BOX AND BLANK FACEPLATE TO ROUGH-IN DATA FOR FUTURE USE.

CONNECT AND STUB 3/4" CONDUIT ABOVE ACCESSIBLE CEILING.

GENERAL NOTES:

A. FOR THE TR ROOM, ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO

SCREW BONDING LUGS NEED TO BE INSTALLED TO BOND ALL METAL ELEMENTS OF THE

RACK AND RUNWAY SYSTEM TO THE TELECOMMUNICATIONS SECONDARY BONDING

BUSBAR.

B. THE AREA OF WORK SHOWN IS ASSOCIATED WITH AN OPERATING FACILITY THAT MUST

REMAIN IN SERVICE 24/7.

C. COORDINATE TECHNOLOGY WORK WITH ALL OTHER TRADES. VERIFY ALL EXISTING

CONDITIONS BEFORE THE START OF WORK.

D. SEE SHEETS GI011 GI012 FOR ADDITIONAL INFORMATION REGARDING SCHEDULE AND

PHASING REQUIREMENTS. SCHEDULE WORK TO MINIMIZE DISRUPTION OF SERVICES.

E. ALL TELECOMMUNCATIONS CABLING SHALL BE CATEGORY 6A, PLENUM RATED CABLE

WITH SPLINE/SEPERATOR BETWEEN PAIRS. COORDINATE CABLE COLOR CODE

REQUIREMENTS WITH VA PRIOR TO BID.

F. INSTALL ALL SIGNAL PULL-BOXES WITH LOCKABLE COVERS.

6" W X 4" D

4" W X 4" D

W X

D

4" W X 4" D 10" W X 4" D

DM LAML

CR

DM

LAML

CR

DM LAML

CR

DM

DM

LAML

CR

DM

ML

CR

DM

EL

LACR

DM

EL

LA

CR

PB

PB

PB

PB

PB

ELDMLA

CR

ELDMLA

CR

DM

DM

LAML

CR

MD

DM

EL

LA

CR

DM

EL

LA

CR

DMDM

DMDM

CR

ML

ML DM

DMLA

MD

CR

LA DM

CR

EL DMLA

DMDM

CR

ML

EL DM LA

CR

CR

EL

KS

KS

MD

MD

MD

DS

MD

LA

MD MD MD

MD

MD

MD

MD

MD

MD

EL

IC

ED

E1 E2 E3

EB1

EC

E4

F

A

64321

C

G

7 85

EA

RESIDENT

RESIDENT

RESIDENT

BATH

122A

BATH

134A

PANTRY

133C

HSKPG

133D

MULTIPURPOSE/

ACTIVITY ROOM

MP STOR

132A

CONF. / PRIVATE DINING

TLT

ART ROOM

BATH

145A

RESIDENT

BATH

146A

RESIDENT

KITCHEN

DINING

133B

LIVING ROOM

133A

STAFF LOUNGE

TLT

CLEAN SUPPLY

HOUSE OFC

SOILED UTL

TOILET

117A

BATHING RM

IT ROOM

ELECTRICAL

HOUSE LNDRY

HOUSE STOR.

MED

BATH

136A

BATH

139A

RESIDENT

RESIDENT

RESIDENT

BATH

135A

RESIDENT

BATH

140A

BATH

142A

RESIDENT

DEN

RESIDENT, BARIATRIC

BATH

119A

RESIDENT

BATH

143A

FIRE RISER RM

115A

BATH

137A

RESIDENT

RESIDENT

BATH

138A

BATH

141A

RESIDENT

RESIDENT

RESIDENT

HAC

EQ. STOR

BATH

151A

RT OFC

BATH

152A

ALCOVE

008B

CHARTING ALCOVE

006B

INDOOR COURTYARD SPACE INDOOR COURTYARD SPACE

VESTIBULE

008A

VESTIBULE

006A

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

BATH

121A

CR-01

CR-01

CR-01

CR-01

CR-02

CR-01

CR-01

CR-01

CR-01

CR-01 CR-01

CR-01

CR-01

CR-01

CR-01

CR-01

CR-01

115A

006A

008C

008A

T-402

T-402

T-402

T-402

T-402

T-402

T-402

T-402

T-402

T-402

T-402

T-402

T-402

T-402

T-402

T-402

T-402

T-402 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. A-930 EXP. 12/31/2023

ENGR REG. NO. E-2586 EXP. 12/31/2023

STRUCTURAL/CIVIL

ENGINEER

H2B

1225 N. LOOP W #800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH

ENGINEER

SPUR DESIGN

11020 KING STREET, STE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

LANDSCAPE ARCHITECT

CLS & ASSOCIATES

825 N. BROADWAY AVE, STE 315

OKLAHOMA, OK 73102

(405) 525-2220

HEALTHCARE/MED

EQUIPMENT PLANNER

INNOVA GROUP

3196 N. SWAN ROAD

TUCSON, AZ 85712

(520) 886-8650

PHYSICAL SECURITY

FORCE PROTECT SECURITY

CONSULTANTS,

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

FOOD & BEVERAGE

PLANNER

STURM CONSULTING

5838 S. HUDSON PLACE

TULSA, OK 74135

(918) 260-0667

ENVIRONMENTAL

ENGINEER

RIVERFRONT ENVIRONMENTAL

1139 OLIVE STREET, STE 300

ST. LOUIS, MO 63101

(314) 436-9492

KEY PLAN

A

N

PHASING AND PROJECT SCOPE LEGEND

AREAS OF WORK OUTSIDE OF CURRENT PHASE OR OUTSIDE OF

PROJECT SCOPE SHOWN. REFERENCE GI011 & GI012 - PHASING PLANS

FOR MORE INFORMATION

/2

/2

:1 :1

P

M

TECHNOLOGY SECURITY PLAN - AREA A

MDT Drawing # 207 OF 222KGH

100% CONSTRUCTION DOCUMENTS

ADDITION AND RENOVATION

OF CLC

09/06/2023

589-703

ROBERT J. DOLE VA MEDICAL CENTER

5500 EAST KELLOGG, BLDG. 60

WICHITA, KS 67218

TY301

SPUR #: 2015

N

1/8" = 1'-0"

TECHNOLOGY SECURITY PLAN - AREA A1

ELECTRICAL KEYNOTES

1 PROVIDE AN INTERIOR CEILING MOUNTED 180-DEGREE MULTISENSOR,

MOTION ACTIVATED SSTV CAMERA. MAKE CONNECTION TO NEW SSTV

SYSTEM. (TYPICAL)

2 PROVIDE AN INTERIOR CEILING MOUNTED 360-DEGREE MULTISENSOR,

MOTION ACTIVATED SSTV CAMERA. MAKE CONNECTION TO NEW SSTV

SYSTEM. (TYPICAL)

3 PROVIDE AN INTERIOR CEILING MOUNTED 360-DEGREE FISHEYE,

MULTISENSOR, MOTION ACTIVATED SSTV CAMERA. MAKE CONNECTION

TO NEW SSTV SYSTEM.

4 PROVIDE AN INTERIOR CEILING MOUNTED SINGLE VIEW MULTISENSOR,

MOTION ACTIVATED SSTV CAMERA. MAKE CONNECTION TO NEW SSTV

SYSTEM. (TYPICAL)

5 PROVIDE SECURITY DEVICES SHOWN ON THE EXISTING GATE TO THE

FENCED EXTERIOR UTILITY YARD.

6 PROVIDE INTERCOM CALL STATION CONNECTED TO CLC RECEPTION

DESK AND CAMPUS SECURITY CONTROL CENTER. (TYPICAL)

GENERAL NOTES:

A. THE AREA OF WORK SHOWN IS ASSOCIATED WITH AN OPERATING FACILITY

THAT MUST REMAIN IN SERVICE 24/7.

B. COORDINATE TECHNOLOGY WORK WITH ALL OTHER TRADES. VERIFY ALL

EXISTING CONDITIONS BEFORE THE START OF WORK.

C. SEE SHEETS GI011 AND GI012 FOR ADDITIONAL INFORMATION REGARDING

SCHEDULE AND PHASING REQUIREMENTS. SCHEDULE WORK TO MINIMIZE

DISRUPTION OF SERVICES.

D. ALL CARD READER SYSTEMS WITH AUTOMATIC DOOR CONTROLS SHALL BE

WIRED TO AUTOMATICALLY OPEN DOORS UPON CARD READER

AUTHENTICATION.

E. PROVIDE CATEGORY 6A CABLING TO ALL CARD READERS AND SECURITY

CAMERAS WITHIN THE SCOPE OF WORK.

F. ENSURE LYNX PANIC/DURESS IS INSTALLED ON EVERY PC KEYBOARD

WITHIN AREA OF SCOPE AND TIED TO THE CAMPUS SECURITY CONTROL

CENTER.

DM

EL

LA

CR

ELDMLA

CR

ELDMLA

CR

ML

DM

LA

DM

CR

DM

DM

ML

CR

LA

DM

DM

ML

CR

KS

EL

CR

EL

CR

EL

CR

EL

CR

PB

PB

PB

IC

IC

ML

DM

AD

DM

CR

EL

CR

EL

CR

DM

EL

LA

CR

ELDMLA

CR

CR

CR

CR

CR

EL

EL

EL

EL

LA

LA

LA

LA

DM

DM

DM

DM

DM DM

KS

DM DM

ML KS

DM

DM

ML

KS

ELDMLA

CR

ELDMLA

CR

CR

EL

LA

DM

CR CR

CR

ML

LA MD DM

MD

MD

DM MD

DM MD

DM MD

MD

MD

MD

MD

MD

MD

MD

MD

MD

DM MD

DM

MD

LA

MD

LA

ML

MD

E12E10

ED

E13E7E2 E3

EC

E4 6421

EE

EG

EH

EI

EF1

4 5

CR-01

CR-01

CR-01

CR-01

CR-01

CR-01

CR-01

CR-01

CR-01

CR-01

CR-01

CR-01

CR-02

CR-01

RESIDENT - B2

RESIDENT - B2

RESIDENT - B2

RESIDENT - B2

BATH

158A

BATH

157A

BATH

156A

BATH

155A

RESIDENT - B1

RESIDENT - B1

BATH

153A

HAC

RESIDENT - B1

RESIDENT - B1

BATH

162A

BATH

160A

RESIDENT - B1

BATH

164A

BATH

161A

BATH

159A

BATH

163A

MEDS

BATH

173A

RESIDENT - B2

02 FULL

167A

02 USED

167B

CLEAN SUPPLY

SOILED UTL

EQUIP STOR

SW OFC

NRS LDR OFC

MED DIR OFC

CLEAN LINEN

SOILED UTL

GENERAL STOR

TEAM WORKRM

TEAM WORKRM

DEN

BATHING RM

TLT

176A

RESIDENT - B2

BATH

175A

ELEC

H. LAUNDRY

DIR OFC

TLT

184A

RESIDENT - B2

RESIDENT - B2

H. STOR

HOUSE OFC

CLC RECEP

100A

KITCHEN

DINING

166B

LIVING ROOM

166A

RESIDENT DINING

MOP

131B

HAC

166D

PANTRY

166C

CRASH CART

013A

N&FS KITCHEN/

SERVERY

131A

ELEC

017A

COMM

017B

STOR

017C

HAC

017D

HOSPICE ROOM

HOSPICE ROOM

CORRIDOR

VESTIBULE

014A

CHARTING ALCOVE

013C

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

STORAGE

110C

EXAM

110B

EXAM

110A

MENS

WOMENS

PHYSICAL THERAPY

ROOM

103A

EXAM

CORRIDOR

CORRIDOR

VESTIBULE

001A

WAITING

PT/OT RECEP

100B

HAC

SSTV

131C

CR-01

CR-01

CR-01

CR-01

CR-01

CR-01

CR-01

CR-01CR-01

166D

182181

D

C

A

M

100B

A

014B

T-402

T-402

T-402

T-402

T-402

T-402

T-402

T-402

T-402

T-402

T-402

T-402

T-402

T-402

T-402

T-402

T-402

CR-01

T-402

T-402

T-402

T-402

T-402

CR-01

T-402

T-402

T-402 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. A-930 EXP. 12/31/2023

ENGR REG. NO. E-2586 EXP. 12/31/2023

STRUCTURAL/CIVIL

ENGINEER

H2B

1225 N. LOOP W #800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH

ENGINEER

SPUR DESIGN

11020 KING STREET, STE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

LANDSCAPE ARCHITECT

CLS & ASSOCIATES

825 N. BROADWAY AVE, STE 315

OKLAHOMA, OK 73102

(405) 525-2220

HEALTHCARE/MED

EQUIPMENT PLANNER

INNOVA GROUP

3196 N. SWAN ROAD

TUCSON, AZ 85712

(520) 886-8650

PHYSICAL SECURITY

FORCE PROTECT SECURITY

CONSULTANTS,

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

FOOD & BEVERAGE

PLANNER

STURM CONSULTING

5838 S. HUDSON PLACE

TULSA, OK 74135

(918) 260-0667

ENVIRONMENTAL

ENGINEER

RIVERFRONT ENVIRONMENTAL

1139 OLIVE STREET, STE 300

ST. LOUIS, MO 63101

(314) 436-9492

KEY PLAN

B

N

PHASING AND PROJECT SCOPE LEGEND

AREAS OF WORK OUTSIDE OF CURRENT PHASE OR OUTSIDE OF

PROJECT SCOPE SHOWN. REFERENCE GI011 & GI012 - PHASING PLANS

FOR MORE INFORMATION

/2

/2

:1 :1

P

M

TECHNOLOGY SECURITY PLAN - AREA B

MDT Drawing # 208 OF 222KGH

100% CONSTRUCTION DOCUMENTS

ADDITION AND RENOVATION

OF CLC

09/06/2023

589-703

ROBERT J. DOLE VA MEDICAL CENTER

5500 EAST KELLOGG, BLDG. 60

WICHITA, KS 67218

TY302

SPUR #: 2015

N

1/8" = 1'-0"

TECHNOLOGY SECURITY PLAN - AREA B1

ELECTRICAL KEYNOTES

1 PROVIDE NEW SSTV SWITCH WITHIN A WALL MOUNTED LOCKABLE CABINET

(BASIS OF DESIGN: STARTECH #CAB1019WALL) AND CONNECT TO CAMPUS

SECURITY CONTROL CENTER. SEE SSTV RISER DIAGRAM FOR MORE DETAIL

AND CAMERA CONNECTIONS.

2 PROVIDE AN INTERIOR CEILING MOUNTED 360-DEGREE MULTISENSOR,

MOTION ACTIVATED SSTV CAMERA. MAKE CONNECTION TO NEW SSTV

SYSTEM. (TYPICAL)

3 PROVIDE AN INTERIOR CEILING MOUNTED 180-DEGREE MULTISENSOR,

MOTION ACTIVATED SSTV CAMERA. MAKE CONNECTION TO NEW SSTV

SYSTEM. (TYPICAL)

4 PROVIDE SSTV CAMERA TO BE PROGRAMMED WITH FACIAL ANALYTICS.

5 PROVIDE INTERCOM CALL STATION CONNECTED TO CLC RECEPTION DESK

AND CAMPUS SECURITY CONTROL CENTER. (TYPICAL)

6 PROVIDE GOVERNMENT-SUPPLIED FULLTIME PASSIVE SCREENING SYSTEM

(BASIS OF DESIGN METRASENS PROSCREEN 200) INTERLOCKED WITH THE

INTERIOR SET OF SLIDING DOORS TO CLOSE & LOCK UPON POSITIVE

DETECTION AND NOTIFY CAMPUS SECURITY CONTROL CENTER.

7 PROVIDE PACS TERMINATION PANEL WITHIN A WALL MOUNTED LOCKABLE

CABINET (BASIS OF DESIGN: STARTECH #CAB1019WALL) AS AN EXTENSION OF

THE EXISTING ADVANTOR SYSTEM IN IT CLOSET A107. SYSTEM MUST BE

CCURE 9000 COMPATIBLE AND ABLE TO TIE BACK INTO THE EXISTING CAMPUS

WIDE PACS SYSTEM. SYSTEM HEAD END IS LOCATED IN BUILDING 62 ROOM 41.

GENERAL NOTES:

A. THE AREA OF WORK SHOWN IS ASSOCIATED WITH AN OPERATING FACILITY

THAT MUST REMAIN IN SERVICE 24/7.

B. COORDINATE TECHNOLOGY WORK WITH ALL OTHER TRADES. VERIFY ALL

EXISTING CONDITIONS BEFORE THE START OF WORK.

C. SEE SHEETS GI011 AND GI012 FOR ADDITIONAL INFORMATION REGARDING

SCHEDULE AND PHASING REQUIREMENTS. SCHEDULE WORK TO MINIMIZE

DISRUPTION OF SERVICES.

D. ALL CARD READER SYSTEMS WITH AUTOMATIC DOOR CONTROLS SHALL BE

WIRED TO AUTOMATICALLY OPEN DOORS UPON CARD READER

AUTHENTICATION.

E. PROVIDE CATEGORY 6A CABLING TO ALL CARD READERS AND SECURITY

CAMERAS WITHIN THE SCOPE OF WORK.

GATE

OPERATOR

CONTROL

CABINET

AUXILIARY

CABINET

GRADE

PROVIDE REQUIRED

CONNECTIONS TO VEHICLE

DETECTION LOOPS

GROUND ROD

PROVIDE CONCRETE EQUIPMENT PAD

FOR CONTROL CABINET AND AUXILIARY

CABINET PER MANUFACTURER'S

SPECIFICATIONS

MOUNT CABINETS TO CONCRETE

PAD PER MANUFACTURER'S

INSTRUCTIONS TO ENSURE RAM

PROOF INSTALLATION

LAY-IN CEILING

PROVIDE 4-11/16" X 4-11/16" X

2-1/8" DOUBLE-GANG

BACKBOX WITH

SINGLE-GANG PLASTER

RING.

CEILING TILE ADJUSTABLE

BOX HANGER

ROUTE MINIMUM 1"

RACEWAY AND CABLING

BACK TO SECURITY

SYSTEM HEAD-END

EQUIPMENT IN

COMMUNICATIONS ROOM.

PROVIDE MINIMUM 18" OF

SECURITY CAMERA CABLING

INSIDE BOX WITH DIRECT

CONNECTION TO SECURITY

CAMERA.

DOME CAMERA

CAT 6A

CAT 6ACAT 6A

NOTE:

PERMANENTLY LABEL ALL WALL JACKS IN THE FOLLOWING MANNER: BUILDING-FLOOR-JACK NUMBER-ROOM

NUMBER OF CLOSET. EXAMPLE: 1-1-33-148B (BUILDING 1, FLOOR 1, JACK 33, CLOSET ROOM NUMBER 148B). JACK