0001 Attachment 2c Combined Drawings Construct Addition and Renovated Bldg 60.pdf

PDF 10 MB Posted

Attached to
Y1DA--589-703 Construct Addition and Renovate Community Living Center, Building 60 (VA-24-00028736)
Solicitation number
36C77624B0019
Issued by

About this file

This document is a set of combined drawings for Construct Addition and Renovated Building 60, which is part of the federal contract opportunity with Solicitation Number 36C77624B0019. The contract is for the Department of Veterans Affairs Technology Acquisition Center Austin to construct an addition and renovate the Community Living Center, Building 60 (VA-24-00028736). The drawings provide the technical specifications and engineering details for the construction and renovation work required under this contract opportunity. No further details about the required products, services, timeline, or pricing are provided in this specific document.

View the file

Other files

File Type Posted
36C77624B0019 0003.pdf PDF
0002 Attachment 4 Bldg 60 Asbestos Survey.pdf PDF
0002 Attachment 3 DBA Wage Determination Sedgewick 20240906.pdf PDF
0002 Attachment 2 589-703 Bldg. 60 Site Visit Sign-in Sheet.pdf PDF
0002 Attachment 1 Technical Questions Received Responses.docx DOCX document
36C77624B0019 0002.pdf PDF
0001 Attachment 2i Combined Drawings Construct Addition and Renovated Bldg 60.pdf PDF
0001 Attachment 2h Combined Drawings Construct Addition and Renovated Bldg 60.pdf PDF
0001 Attachment 2a Combined Drawings Construct Addition and Renovated Bldg 60.pdf PDF
0001 Attachment 2g Combined Drawings Construct Addition and Renovated Bldg 60.pdf PDF
0001 Attachment 2b Combined Drawings Construct Addition and Renovated Bldg 60.pdf PDF
0001 Attachment 2d Combined Drawings Construct Addition and Renovated Bldg 60.pdf PDF
0001 Attachment 2f Combined Drawings Construct Addition and Renovated Bldg 60.pdf PDF
0001 Attachment 2e Combined Drawings Construct Addition and Renovated Bldg 60.pdf PDF
36C77624B0019 0001.pdf PDF
Attachment 1 FINAL SPECS Construct Addition and Renovate Bldg 60.pdf PDF
Attachment 2e Combined Drawings Construct Addition and Renovated Bldg 60.pdf PDF
Attachment 4 Limitations on Subcontracting - Construction.docx DOCX document
Attachment 2i Combined Drawings Construct Addition and Renovated Bldg 60.pdf PDF
Attachment 2h Combined Drawings Construct Addition and Renovated Bldg 60.pdf PDF
Attachment 2c Combined Drawings Construct Addition and Renovated Bldg 60.pdf PDF
Attachment 2b Combined Drawings Construct Addition and Renovated Bldg 60.pdf PDF
Attachment 2f Combined Drawings Construct Addition and Renovated Bldg 60.pdf PDF
FINAL SPECS Attachment 2 Geotech Report.pdf PDF
Attachment 2g Combined Drawings Construct Addition and Renovated Bldg 60.pdf PDF
Attachment 3 DBA Wage Determination Sedgwick - 20240522.pdf PDF
Attachment 2d Combined Drawings Construct Addition and Renovated Bldg 60.pdf PDF
36C77624B0019_1.docx DOCX document
Attachment 5 Division Cost Breakdown - 5-29-24.xlsx XLSX spreadsheet
Attachment 2a Combined Drawings Construct Addition and Renovated Bldg 60.pdf PDF
FINAL SPECS Attachment 1 Contract Documents Addendum 01.pdf PDF
Show all 31

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A

B B

L4x4x3/8" x (COL WIDTH +2") T&B

TS BEAM

SEE PLAN

STEEL COL

SEE PLAN

NOTE:

WHERE TS BEAM IS NOT CENTERED

ON COLUMN, INCREASE ANGLE

LENGTH AS REQ'D

GRID

1'-4" MAX

4" MIN.

36" MAX

4 1/2" MIN.

COLUMN OR

BEAM

COLUMN OR

BEAM FLANGE

4" M

IN

1' -4

M

A X

M A

X

1/ 2"

M

IN

1" MIN. 1" MIN.

3" MIN.

1" MIN. 1" MIN.

3" MIN. 3" MIN.

3" M

IN

1" MIN.

SINGLE LINE SPACING

MULTIPLE LINE SPACING PLAN

WHERE MULTIPLE LINE

SPCG IS REQ'D AT A BM

w/ A FLANGE WIDTH LESS

THAN 5" SPACE THUS.

NOTES:

1. STUDS SHALL BE TYPE S3L, ¾"Ø AS MANUFACTURED BY NELSON

STUD DIVISION, OR APPROVED EQUAL. STUDS SHALL HAVE PROPER

FERRULES FOR WELD-THRU DECK APPLICATIONS.

2. STUD (AFTER WELDING) SHALL PROJECT A MIN. OF 1 ½" ABOVE TOP

METAL DECK AND THERE SHALL BE A MIN. OF 1" CONCRETE ABOVE

STUDS. STUDS SHALL BE WELDED PER MANUFACTURER'S

RECOMMENDATIONS.

3. STUDS SHALL BE ATTACHED DIRECTLY OVER WEB UNLESS THE BM

FLANGE THICKNESS IS 0.3 OR THICKER FOR ¾"Ø STUDS.

TOWARDS

SUPPORTS

MID-SPAN OF BEAM

PLACE STUD AWAY FROM

MID-SPAN OF BEAM. CLOSER

TOWARDS THE SUPPORTS.

STRONG SIDE OF FLUTES

3/4"Ø x 5-3/16" TALL HEADED

STUDS

COLUMN OR

BEAM CL

TOWARDS

SUPPORTS

SEE PLAN FOR HEADED

STUDS ON BEAMS

< 6"

6" - 12"

PL THICK

3/16"

1/4"

"L" WELD "W"

1/8"

3/16"

NOTES:

1. THIS DETAIL SHALL NOT APPLY

IF BEAM FLANGE IS LESS THAN

5" WIDE AND SLAB EDGE DIST "L"

IS GREATER THAN 10".

2. HOOKED DWLS ARE NOT REQ'D

IF "L" < 6".

3. OUTLOOK L4X4X1/4" WITH

L4X4X1/4" BRACE @ 2'-6" OC

WHEN DECK DIMENSION

EXCEEDS 12". MAX LENGTH 18"

"W" 2-12

BENT PLATE

PER SCHEDULE

W BEAM, SEE PLAN

w/ FLANGES 4" WIDE OR LESS)

2" MIN.; (EXCEPTION: 1" MIN. FOR BEAMS

"L"

DOWEL

#3 @ 18" OC

2"

1" MAX

2' - 0"

1"

DWL w/ 180° STD HOOK.

SEE SCHEDULE FOR SIZE

AND SPACING

1/2"Ø x 5" HEADED STUDS, MATCH REINF DWL

SPACING (24" MAX)

CONC SLAB w/

REINF, SEE PLAN

W BEAM, SEE PLAN

12" - 18" 3/8" 3/16" #3 @ 18" OC

SEE MEP

OPENING DIMENSION

3/16 2@12

T/O STEEL ELEV

SEE PLAN

SEE MEP

OPENING DIMENSION

T/O STEEL ELEV

SEE PLAN

SEE ARCH DWGS FOR

CURB DETAILS, TYP

L3-1/2x3-1/2x1/4" NEAR SIDE

& FAR SIDE OF OPENING

STEEL BEAM, SEE PLAN

L3x3x1/4" CONT CLOSURE ANGLE FRAME w/ POURSTOP

SECTION A-A

SECTION B-B

DECK SPAN

W

ID

TH

(2)-#5 BARS EA SIDE

OF OPENING EXTENDED

2'-0" PAST OPENING

CUT DECK OUT ONLY AFTER

CONCRETE HAS ATTAINED

75% OF ITS DESIGN STRENGTH

(1)-#5 x 4'-0" DIAG

EA CORNER

ADJACENT BEAMS

SUPPORTING DECK

3" TYP

NOTE:

THIS DETAIL APPLIES TO OPENINGS WHERE THE "WIDTH" IS 10" TO 2'-0"

OMIT #5 BARS AT OPENINGS LESS THAN 10" IN WIDTH. OPENINGS

GREATER THAN 2'-0" MUST BE FRAMED WITH STEEL BEAMS.

NOTE:

REINFORCEMENT SHOWN OVER GIRDERS IS IN ADDITION TO THE

TYPICAL SLAB REINFORCEMENT SPECIFIED ON THE DRAWING.

6" MIN. 6" MIN.

ADD'L #4 x 1' - 6" @ 12"

CENTERED OVER GIRDERS

STEEL FLOOR DECK

STEEL GIRDER

C

LR

C O

V E

R

CONTINUOUS HIGH

CHAIRS FOR STEEL

DECK (CRSI TYPE CHCM)

@ 48" MAXIMUM.

W BEAM

FLOOR DECK

ARCH'L FINISH

SEE ARCH

HSS5x5x1/4"

@ 3'-0" OC MAX

AND 6" FROM

EACH END

7' -2

M

A X

CONT L6x4x5/16"

(LLH)

CONT L6x6x1/2" BTWN BEAMS

WELDED TO BOT OF FLANGE

GRID

L6x6x1/2" @

3'-0" OC MAX

SEE FOR

TYPICAL EDGE DETAILS

W BEAM

1/2"

TO DOOR/WINDOW

SEE ARCH

/1 SF501 CONTRACTOR TO ENSURE BRACING

IS ABOVE THE CEILING.

COORDINATE WITH ARCH.

CONT L6x6x1/2"

CONT L6x4x3/8"

(LLV)

GRID

SLIDING CLIPS

ATTACHED TO CFMF

BENT PLATE

CONCRETE SLAB

ON METAL DECK

PERIMETER BEAM

CFMF - BY CFMF CONTRACTOR

CONT L4x3x¼" (LLH)

OR 1/4" BENT PLATE

TOS

W BEAM

ARCH'L FINISH,

SEE ARCH

L3x3x1/4" @ 3'-0" OC

SEE FOR

TYPICAL EDGE DETAILS

/1 SF501

SEE ARCH

GRID

CFMF - BY CFMF CONTRACTOR BENT PLATE

CONC SLAB ON METAL DECK

W BM

CONT L4x3x¼" (LLH)

OR 1/4" BENT PLATE

TOS

SLIDING CLIPS ATTACHED TO

NON-STRUCTURAL FRAMING

PERIMETER BEAM

ARCH'L FINISH,

SEE ARCH

L3x3x1/4" @ 3'-0" OC

CFMF - BY CFMF CONTRACTOR

SEE FOR

TYPICAL EDGE DETAILS

1/2"

/1 SF501

SEE ARCH

GRID

SLIDING CLIPS ATTACHED TO

NON-STRUCTURAL FRAMING

BENT PLATE,

SEE

ROOF

ROOF SLAB

PERIMETER BEAM

CFMF - BY CFMF

CONTRACTOR

TOS

W BEAM

ARCH'L FINISH,

SEE ARCH

SEE ARCH

CONT L4x3x¼" (LLH) OR 1/4" BENT PLATE L3x3x1/4" @ 3'-0" OC

2'

6"

GALV WT4x33.5 @ 6'-0" OC

1/2" THK 10" SQ GALV CAP

PLATE

6"Ø STD GALV PIPE

COLUMN @ 6'-0" OC

CONT GALV L6x4x5/16" (LLH)

GALV EMBED PLATE,

SEE DETAIL

CFMF PARAPET AND

CONNECTION TO THE

STRUCTURE BY CFMF

CONTRACTOR

3' - 0"

CFMF - BY CFMF

CONTRACTOR

TOP OF PARAPET

SEE ARCH

SEE FOR

TYPICAL EDGE DETAILS

1/2"

/1 SF501

L4x4x1/4" OUTLK

@ 3'-0" OC PROVIDE

L4x4x1/4" BRACE IF EDGE

DIMENSION EXCEEDS 12"

/9 SA051

3" SEISMIC

EXPANSION JOINT

EXISTING BUILDING

WALL VIF

/1 SF501

th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t

00 00

11 11 o n e in c h o n e fo o t o n e in c h o n e fo o t o n e in c h o n e fo o t o n e in c h o n e fo o t

00 00

22 22 th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t

00 00 22 22 o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t

00 00 44 44 th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t

00 00 44 44 o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

00 00 44 44

88 88 o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t

00 00 44 44

88 88

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. A-930 EXP. 12/31/2023

ENGR REG. NO. E-2586 EXP. 12/31/2023

STRUCTURAL/CIVIL

ENGINEER

H2B

1225 N. LOOP W #800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH

ENGINEER

SPUR DESIGN

11020 KING STREET, STE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

LANDSCAPE ARCHITECT

CLS & ASSOCIATES

825 N. BROADWAY AVE, STE 315

OKLAHOMA, OK 73102

(405) 525-2220

HEALTHCARE/MED

EQUIPMENT PLANNER

INNOVA GROUP

3196 N. SWAN ROAD

TUCSON, AZ 85712

(520) 886-8650

PHYSICAL SECURITY

FORCE PROTECT SECURITY

CONSULTANTS,

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

FOOD & BEVERAGE

PLANNER

STURM CONSULTING

5838 S. HUDSON PLACE

TULSA, OK 74135

(918) 260-0667

ENVIRONMENTAL

ENGINEER

RIVERFRONT ENVIRONMENTAL

1139 OLIVE STREET, STE 300

ST. LOUIS, MO 63101

(314) 436-9492

SPUR #: 2015

09/06/23

/3

/2

:3 :3

P

M

FLOOR FRAMING DETAILS

ZAFSJB

BID DOCUMENTS

ADDITION AND RENOVATION

OF CLC

09/06/2023

589-703

ROBERT J. DOLE VA MEDICAL CENTER

5500 EAST KELLOGG, BLDG. 60

WICHITA, KS 67218

SF501

NTS9

TYPICAL TUBE TO COLUMN CONN DETAIL

NTS6

COMPOSITE BEAM SHEAR STUD LAYOUT DETAIL

NTS1

TYPICAL EDGE DETAIL

NTS2

TYPICAL FRAMING AT FLOOR OPENING

NTS4

TYPICAL DETAIL OF OPENINGS IN COMPOSITE SLABS

NTS3

TYP ADD'L REINF AT INTERIOR GIRDERS

NTS5

DETAIL AT DOOR/WINDOW OPENING

NTS8

DETAIL AT PERIMETER

NTS7

DETAIL AT PERIMETER

NTS10

DETAIL AT ROOF PARAPET AT EXISTING

No. REVISION DESCRIPTION DATE

GRID

TOS

FLOOR DECK

BRICK, SEE

ARCH

STEEL BEAM,

SEE PLAN

CFMF, SEE

ARCH

C6x13 WELDED TO AND

SPANNING IN BETWEEN

BEAMS. CHANNEL SHALL

BE PLACED UNDER BRICK.

SEE ARCH

SEE SA051

FOR CONN

STEEL BEAM,

SEE PLAN

GRID

FLOOR DECK CFMF

C4x5.4 @ 4'-0"

OC & @ ENDS

BRICK,

SEE ARCH

SEE ARCH

BM, SEE PLAN

TOS

BM, SEE PLAN

C4x5.4 WELDED TO AND

SPANNING IN BETWEEN

CHANNELS. CHANNEL

SHALL BE PLACED UNDER

BRICK.

GRID

SLIDING CLIPS ATTACHED TO

NON-STRUCTURAL FRAMING

BENT PLATE,

SEE

ROOF

ROOF SLAB

PERIMETER BEAM

CFMF - BY CFMF

CONTRACTOR

TOS

W BEAM

ARCH'L FINISH,

SEE ARCH

SEE ARCH

CONT L4x3x¼" (LLH)

OR 1/4" BENT PLATE

L3x3x1/4" @ 3'-0" OC

2'

6"

GALV LL4x4x5/16", 0" GAP

@ 6'-0" OC

1/2" THK 10" SQ GALV CAP

PLATE

6"Ø STD GALV PIPE

COLUMN @ 6'-0" OC

CONT GALV L6x4x5/16" (LLH)

GALV EMBED PLATE,

SEE DETAIL

CFMF PARAPET AND

CONNECTION TO THE

STRUCTURE BY CFMF

CONTRACTOR

3' - 0"

CFMF - BY CFMF

CONTRACTOR

TOP OF PARAPET

SEE ARCH

SEE FOR

TYPICAL EDGE DETAILS

1/2"

/1 SF501

L4x4x1/4" OUTLK

@ 3'-0" OC PROVIDE

L4x4x1/4" BRACE IF EDGE

DIMENSION EXCEEDS 12"

/9 SA051

/1 SF501

3'

8" 4'

2"

4'

2"

HSS 3 1/2 x 3 1/2 x 1/4" @ 8'-0" OC MAX

TOP OF

ROOFING

W BEAM

HSS 3 1/2 x 3 1/2 x 1/4"

HSS 3 1/2 x 3 1/2 x 1/4"

2'

7"

2'

7"

1/2" THK CAP

PLATE

1/4" THK CAP

PLATE

TYP

7'

RF FRAMING PLAN

14'-6"

TOS

19'-2"

TOS

26'-6"

STIFFENER PLATE EACH

SIDE TO MATCH BEAM

WEB THICKNESS

STIFFENER PLATE EACH

SIDE TO MATCH BEAM

WEB THICKNESS

NOTE:

1. TUBE STEEL TO BE HOT-DIPPED

GALVANIZED

2. ALL FIELD WELDS TO BE GROUND

SMOOTH AND TOUCHED UP WITH

ZINC RICH PAINT

HSS POST - SEE PLAN

TOS

22'-10"

SEE PLAN

GRID

CFMF - BY CFMF CONTRACTOR

BENT PLATE,

SEE

ROOF SLAB

W BM

CONT L4x3x¼" (LLH)

OR 1/4" BENT PLATE

TOS

SLIDING CLIPS ATTACHED TO

NON-STRUCTURAL FRAMING

PERIMETER BEAM

ARCH'L FINISH,

SEE ARCH

SEE ARCH

L3x3x1/4" @ 3'-0" OC

ROOF

ROOF SLAB

GALV LL4x4x5/16", 0" GAP

@ 6'-0" OC

1/2" THK 10" SQ GALV CAP

PLATE

6" Ø STD GALV PIPE

COLUMN @ 6'-0" OC

CONT GALV L6x4x5/16" (LLH)

GALV EMBED PLATE,

SEE DETAIL

CFMF PARAPET AND

CONNECTION TO THE

STRUCTURE BY CFMF

CONTRACTOR

TOP OF PARAPET

SEE ARCH

3' - 0"

2'

6"

SEE FOR

TYPICAL EDGE DETAILS

1/2"

/1 SF501

L4x4x1/4" OUTLK

@ 3'-0" OC PROVIDE

L4x4x1/4" BRACE IF EDGE

DIMENSION EXCEEDS 12"

/9 SA051

/1 SF501

CFMF - BY CFMF

CONTRACTOR

GRID

EDGE ANGLE,

SEE

ROOFING

ROOF DECK

PERIMETER BEAM

CFMF - BY CFMF

CONTRACTOR

TOS

W BEAM

ARCH'L FINISH,

SEE ARCH

CONNECTION TO THE

STRUCTURE BY CFMF

CONTRACTOR. SLIDING CLIPS

ATTACHED TO EDGE ANGLE

OR DECK

CFMF - BY CFMF

CONTRACTOR

TOP OF PARAPET

SEE ARCH

SEE FOR

TYPICAL EDGE DETAILS

/6 SA050

L4x4x1/4" OUTLK

@ 3'-0" OC PROVIDE

L4x4x1/4" BRACE IF EDGE

DIMENSION EXCEEDS 12"

1/2"

SEE ARCH

/1 SF501

SEE PLAN

GRID

EDGE ANGLE,

SEE

ROOFING

ROOF DECK

PERIMETER BEAM

CFMF - BY CFMF

CONTRACTOR

TOS

ARCH'L FINISH,

SEE ARCH

CONNECTION TO THE

STRUCTURE BY CFMF

CONTRACTOR. SLIDING CLIPS

ATTACHED TO EDGE ANGLE

OR DECK

CFMF - BY CFMF

CONTRACTOR

TOP OF PARAPET

SEE ARCH

SEE FOR

TYPICAL EDGE DETAILS

/6 SA050

JOIST, SEE PLAN

SEE ARCH

L4x4x1/4" OUTLK

@ 3'-0" OC PROVIDE

L4x4x1/4" BRACE IF EDGE

DIMENSION EXCEEDS 12"

/1 SF501

SEE PLAN

th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t

00 00

11 11 o n e in c h o n e fo o t o n e in c h o n e fo o t o n e in c h o n e fo o t o n e in c h o n e fo o t

00 00

22 22 th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t

00 00 22 22 o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t

00 00 44 44 th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t

00 00 44 44 o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

00 00 44 44

88 88 o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t

00 00 44 44

88 88

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. A-930 EXP. 12/31/2023

ENGR REG. NO. E-2586 EXP. 12/31/2023

STRUCTURAL/CIVIL

ENGINEER

H2B

1225 N. LOOP W #800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH

ENGINEER

SPUR DESIGN

11020 KING STREET, STE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

LANDSCAPE ARCHITECT

CLS & ASSOCIATES

825 N. BROADWAY AVE, STE 315

OKLAHOMA, OK 73102

(405) 525-2220

HEALTHCARE/MED

EQUIPMENT PLANNER

INNOVA GROUP

3196 N. SWAN ROAD

TUCSON, AZ 85712

(520) 886-8650

PHYSICAL SECURITY

FORCE PROTECT SECURITY

CONSULTANTS,

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

FOOD & BEVERAGE

PLANNER

STURM CONSULTING

5838 S. HUDSON PLACE

TULSA, OK 74135

(918) 260-0667

ENVIRONMENTAL

ENGINEER

RIVERFRONT ENVIRONMENTAL

1139 OLIVE STREET, STE 300

ST. LOUIS, MO 63101

(314) 436-9492

SPUR #: 2015

09/06/23

/3

/2

:3 :3

P

M

ROOF FRAMING DETAILS

ZAFSJB

BID DOCUMENTS

ADDITION AND RENOVATION

OF CLC

09/06/2023

589-703

ROBERT J. DOLE VA MEDICAL CENTER

5500 EAST KELLOGG, BLDG. 60

WICHITA, KS 67218

SF504

NTS7

DETAIL AT LOW ROOF

NTS

DETAIL AT LOW ROOF

NTS1

DETAIL AT ROOF PARAPET

NTS5

ROOF SCREEN WALL SECTION

NTS2

DETAIL AT ROOF PARAPET

NTS3

DETAIL AT ROOF PARAPET

NTS4

DETAIL AT ROOF PARAPET

A A

A A

A A

ROOF FRAMING

PLAN @ 14'-6" TOS

14' - 6"

E4

ENTRANCE EAVE

16' - 8 3/4"

POST

HSS POST UP

RE:

7' - 6" 7' - 6"

RIDGE ELEV

1.81.2

SEE ARCH

/5 SA051

COPE AS NEEDED

TO A MIN OF 5"

SF505

DECK NOT SHOWN

FOR CLARITY

15' - 0"

7' - 6" 7' - 6" 3' - 3 1/2"

W10 BEAM,

SEE PLAN

W21 BEAM,

SEE PLAN

SF505

SF505

TOS

15' - 11 3/4"

GRID

T/O RIDGE

SEE PLAN

14GA BENT PLATE

TO MATCH ROOF

SLOPE

STEEL BEAM

SEE PLAN

NOTE:

ROOF DECK NOT

SHOWN FOR CLARITY

GRID

CONT 3/16" BENT

PLATE w/ 4" LEGS

SEE ARCH

W BEAM - SEE PLAN

ARCH FINISH,

SEE ARCH

SEE ARCH

W BEAM;

SEE PLAN

TOS ELEV

SEE PLAN

M

IN

5"

L4x4x1/4

EA SIDE

4"

MAX

10 3/4"

HSS 8x6 -

SEE PLAN

CONT L6x4x3/8"

(LLH, GALV)

TOS

SEE PLAN

TO WINDOW

SEE ARCH

BEAM

CEILING

SEE ARCH

M A

X

1/

2"

GRID

CONT 3/16" BENT

PLATE w/ 4" LEGS

SEE ARCH

W BEAM - SEE PLAN

ARCH FINISH,

SEE ARCH

SEE ARCH

W BEAM;

SEE PLAN

TOS ELEV

SEE PLAN

SEE ARCH

PLAN

SEE

GRID

TOS EL

SEE PLAN

TO DOOR

SEE ARCH

M A

X 1/

2"

1/4" CONT PLATE

HSS BM -

SEE PLAN

CFMF BY OTHERS

HSS4x4x1/4" @ EA

CANOPY CONNECTION

ARCH'L FINISH

3/4"x6"x8" PLATE w. HOLES

TO MATCH THOSE REQ'D

BY CANOPY SUPPLIER

BEAM

1/ 2"

C6x8.2 @ 4'-0" OC

CONT 5x5x3/8" (GALV)

EXTERIOR WALL PANEL

RE:ARCH

GC TO PROVIDE SAME 12"x5"x3/8" PLATE WITH HSS4x4 STUB OUT AND CAP PLATE

GC TO VERIFY ALLOWABLE SPAN OF CONT.

ALUMINUM MEMBER WITH CANOPY SUPPLIER AND

PROVIDE PLATE AND STUB OUT AS REQ'D

CONT. ALUMINUM MEMBER CAN BE BOLTED TO

CAP PLATE AS NEEDED.

ALUMINUM CANOPY

MEMBERS BY OTHERS

PROVIDE A 12"x5"x3/8" THICK STEEL PLATE WITH A HSS4x4x5/16" STUB OUT

CENTERED AND WELDED ALL AROUND

ALSO PROVIDE 3/8" CAP PLATE FOR

HSS4x4 STUB OUT

GC TO COORDINATE WITH CANOPY MANUF. FOR

ANTICIPATED CONNECTION TO STRUCTURE. CANOPY

CAN EITHER BE BOLTED TO THE 3/8" THICK STEEL

CAP PLATE OR CAN BE BOLTED TO A 1/2" THICK

KNIFE PLATE (REQUIRED DIMENSIONS BY CANOPY MANUF).

CFMF HEADER, BY

OTHERS

NOTE:

1. CFMF SUPPLIER TO COORD WITH CANOPY

MANUFACTURER EXACT LOADING FROM

CANOPY FOR DESIGN INTO MTL STUD

HEADERS & JAMBS.

2. NEW CFMF HEADER TO BE DESIGNED BY

OTHERS. EXISTING CFMF STUD WALL TO BE

CHECKED FOR ADDITIONAL LOAD FROM

NEW HEADER.

1 1/2" 9" 1 1/2"

5"

SECTION AA

4' - 0" MAX

EXISTING CFMF STUD. CONTRACTOR

TO COORDINATE LOCATIONS OF

EXISTING STUDS IN THE FIELD.

< 6"

6" - 12"

PL THICK

3/16"

1/4"

"L" WELD "W"

1/8"

3/16"

"W" 2-12

BENT PLATE

PER SCHEDULE

W BEAM, SEE PLAN

w/ FLANGES 4" WIDE OR LESS)

2" MIN.; (EXCEPTION: 1" MIN. FOR BEAMS

L

METAL DECK, SEE

PLAN

W BEAM, SEE PLAN

12" - 18" 1/2" 3/16"

18" - 30" 3/8" 1/4"

NOTE:

CONTRACTOR TO

COORDINATE BENT

PLATE SIZE WITH ARCH.

GRID

SEE ARCH

DECK NOT SHOWN

FOR CLARITY

SF505

W10, SEE PLAN

W10, SEE PLAN

W18, SEE PLAN

4x4 BENT PLATE

BM SEAT, IF

REQ'D

DOUBLE ANGLE CONNECTION, SEE

STRUCTURAL STEEL NOTE #12 ON

SHEET SA002 FOR DESIGN

CRITIERIA

th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t

00 00

11 11 o n e in c h o n e fo o t o n e in c h o n e fo o t o n e in c h o n e fo o t o n e in c h o n e fo o t

00 00

22 22 th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t

00 00 22 22 o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t

00 00 44 44 th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t

00 00 44 44 o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

00 00 44 44

88 88 o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t

00 00 44 44

88 88

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. A-930 EXP. 12/31/2023

ENGR REG. NO. E-2586 EXP. 12/31/2023

STRUCTURAL/CIVIL

ENGINEER

H2B

1225 N. LOOP W #800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH

ENGINEER

SPUR DESIGN

11020 KING STREET, STE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

LANDSCAPE ARCHITECT

CLS & ASSOCIATES

825 N. BROADWAY AVE, STE 315

OKLAHOMA, OK 73102

(405) 525-2220

HEALTHCARE/MED

EQUIPMENT PLANNER

INNOVA GROUP

3196 N. SWAN ROAD

TUCSON, AZ 85712

(520) 886-8650

PHYSICAL SECURITY

FORCE PROTECT SECURITY

CONSULTANTS,

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

FOOD & BEVERAGE

PLANNER

STURM CONSULTING

5838 S. HUDSON PLACE

TULSA, OK 74135

(918) 260-0667

ENVIRONMENTAL

ENGINEER

RIVERFRONT ENVIRONMENTAL

1139 OLIVE STREET, STE 300

ST. LOUIS, MO 63101

(314) 436-9492

SPUR #: 2015

09/06/23

/3

/2

:3 :4

P

M

STRUCTURAL FRAMING DETAILS

ZAFSJB

BID DOCUMENTS

ADDITION AND RENOVATION

OF CLC

09/06/2023

589-703

ROBERT J. DOLE VA MEDICAL CENTER

5500 EAST KELLOGG, BLDG. 60

WICHITA, KS 67218

SF505

1/2" = 1'-0"

NEW ENTRANCE ELEVATION

NTS2

DETAIL AT RIDGE

NTS3

DETAIL AT ROOF EDGE AT ENTRANCE

NTS4

DETAIL AT WINDOW

NTS6

DETAIL AT ENTRANCE VESTIBULE

NTS7

TYP CANOPY CONNECTION TO STUD WALL

NTS8

TYPICAL EDGE DETAIL

NTS5

DETAIL AT ENTRANCE VESTIBULE

SEE ARCH

SEE PLAN

1/2"

GRID

TO BLKG

SEE ARCH

TOS EL

SEE PLAN

W21 - SEE

PLAN

CEILING - SEE ARCH

ARCH'L FINISH

CONT L6x3 1/2x5/16

(LLH)

CONT L4x4x1/4

SEE DETAIL

FOR INFORMATION NOT

SHOWN /6 SA050

ROOF DECK,

SEE PLAN

L3x3x1/4" OUTLOOK @ 3'-0" OC MAX, PROVIDE L3x3x1/4" BRACE

WITH EDGE DIMENSION

EXCEEDS 12"

SEE ARCH

SEE PLAN

1/2"

GRID

TO BLKG

SEE ARCH

W21 - SEE PLAN

CEILING - SEE ARCH

ARCH'L FINISH

CONT L6x3 1/2x5/16

(LLH)

CONT L4x4x1/4

SEE DETAIL

FOR INFORMATION NOT

SHOWN /6 SA050

ROOF DECK,

SEE PLAN

TOS EL

SEE PLAN

W12 - SEE PLANL3x3x1/4" OUTLOOK @ 3'-0" OC MAX, PROVIDE L3x3x1/4"

BRACE WITH EDGE

DIMENSION EXCEEDS 12"

STL BM

SEE PLAN

CONT L6x3 1/2x5/16

(LLH)

CONT L4x4x3/8

SEE DETAIL FOR

INFORMATION NOT SHOWN

GRID

SEE PLAN

TOS EL

SEE PLAN

TOS EL

SEE PLAN

/2 SF504

ROOF DECK,

SEE PLAN

SEE ARCH

ARCH'L FINISH

SEE DETAIL

FOR EMBED PLATE

/9 SA051

th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t

00 00

11 11 o n e in c h o n e fo o t o n e in c h o n e fo o t o n e in c h o n e fo o t o n e in c h o n e fo o t

00 00

22 22 th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t

00 00 22 22 o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t

00 00 44 44 th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t

00 00 44 44 o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

00 00 44 44

88 88 o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t

00 00 44 44

88 88

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. A-930 EXP. 12/31/2023

ENGR REG. NO. E-2586 EXP. 12/31/2023

STRUCTURAL/CIVIL

ENGINEER

H2B

1225 N. LOOP W #800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH

ENGINEER

SPUR DESIGN

11020 KING STREET, STE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

LANDSCAPE ARCHITECT

CLS & ASSOCIATES

825 N. BROADWAY AVE, STE 315

OKLAHOMA, OK 73102

(405) 525-2220

HEALTHCARE/MED

EQUIPMENT PLANNER

INNOVA GROUP

3196 N. SWAN ROAD

TUCSON, AZ 85712

(520) 886-8650

PHYSICAL SECURITY

FORCE PROTECT SECURITY

CONSULTANTS,

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

FOOD & BEVERAGE

PLANNER

STURM CONSULTING

5838 S. HUDSON PLACE

TULSA, OK 74135

(918) 260-0667

ENVIRONMENTAL

ENGINEER

RIVERFRONT ENVIRONMENTAL

1139 OLIVE STREET, STE 300

ST. LOUIS, MO 63101

(314) 436-9492

SPUR #: 2015

09/06/23

/3

/2

:3 :4

P

M

STRUCTURAL FRAMING DETAILS

ZAFSJB

BID DOCUMENTS

ADDITION AND RENOVATION

OF CLC

09/06/2023

589-703

ROBERT J. DOLE VA MEDICAL CENTER

5500 EAST KELLOGG, BLDG. 60

WICHITA, KS 67218

SF506

NTS1

DETAIL AT MULTIPURPOSE ROOM

NTS3

DETAIL AT MULTIPURPOSE ROOM

NTS2

DETAIL AT MULTIPURPOSE ROOM AND HIGH ROOF

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

6 Veterans

Health Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

VA Health Care System Approval:

ARCHITECT:

U.S. Department of Veteran Affairs

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MO ARCH REG. NO. 2012034754, EXP. 12/31/2020

MO ENGR REG. NO. 2014031351, EXP. 12/31/2020

STRUCTURAL/ CIVIL

ENGINEER

H2B

1225 N LOOP W #800

HOUSTON, TX 77008

713-864-2900

FIRE PROTECTION ENGINEER

SPUR DESIGN

312 SW 25TH STREET

OKLAHOMA CITY, OK 73109

405-842-6100

POOLE FIRE PROTECTION

19910 W. 161ST STREET

OLATHE, KS 66062

913-829-8650

HEALTHCARE/ MEDICAL

EQUIPMENT PLANNER

INNOVA GROUP

3196 N SWAN ROAD

TUCSON, AZ 85712

520-886-8650

LANDSCAPE ARCHITECT

CLS & ASSOCIATES

825 N BROADWAY AVE #315

OKLAHOMA CITY, OK 73102

405-525-2220

FOOD AND BEVERAGE

PLANNER

STURM CONSULTING

5838 S. HUDSON PLACE

TULSA, OK 74135

918-260-0667

ENVIRONMENTAL ENGINEER

RIVERFRONT ENVIRONMENTAL

1139 OLIVE STREET, SUITE 300

ST. LOUIS, MO 63101

314-436-9492

MECHANICAL/ ELECITRICAL

PLUMBING

FU

LL

Y

SP

R

IN

K

LE

R

ED

2/ 3/

:1

3:

A M

ENVIRONMENTAL GENERAL

NOTES

061 220

ADDITION AND RENOVATION OF CLC

09/06/2023

589-703

5500 EAST KELLOGG

WICHITA, KS 67218 HA001

No Revision Description Date

GENERAL NOTES

CONTRACTOR IS TO BE LICENSED TO ENGAGE IN ASBESTOS AND LEAD RELATED PROJECT

WORK AND USE LICENSED/TRAINED PERSONNEL.

ABATEMENT WORK WILL REQUIRE SEVERAL MOBILIZATIONS. FACILITATE WORK FLOW IN

PROJECT PHASES SHOWN BY DRAWING GI011 AND APPROVED PROJECT SCHEDULE.

WITHIN AN NPE, HVAC AIR FLOW SHALL BE SHUTDOWN AND OPENINGS COVERED WITH

CRITICAL BARRIERS THROUGHOUT ABATEMENT. SCHEDULE SHUTDOWNS WITH THE

VACOR TO ACCOMMODATE FACILITY AND CONSTRUCTION REQUIREMENTS.

ALL AUTHORIZED PERSONNEL WITHIN AN NPE SHALL DON, AT MINIMUM, HALF FACE AIR

PURIFYING RESPIRATORS WITH P100 FILTERS, DISPOSABLE DUST SUITS (WITH BOOT AND

HEAD COVERS) AND GLOVES. RESPIRATORY PROTECTION MAY REQUIRE USE OF

POWERED AIR PURIFYING RESPIRATORS.

REGULATED AREA NEGATIVE PRESSURE ENCLOSURES SHALL BE PREPARED IN

ACCORDANCE WITH THE FOLLOWING:A) ALL FLOORS, CEILINGS AND WALLS SHALL BE

ISOLATED USING 2-LAYERS OF 6-MIL POLY SHEETING; B) OSHA ASBESTOS SIGNAGE AT

ENTRANCE TO REGULATED AREAS; C)SINGLE-POINT OF ENTRY WITH 3-STAGE WET

DECONTAMINATION STATION TO ALLOW WORKERS TO REMOVE PPE, WASH AND VACUUM

THEMSELVES OFF PRIOR TO EXITING THE REGULATED WORK AREA; D) MAINTAINED UNDER

NEGATIVE PRESSURE (-0.02 IN WG OR BETTER) USING HEPA FILTERED AIR MACHINES WITH

EXHAUST ROUTED TO OUTDOORS; E) MINIMUM OF 4 AIR CHANGES PER HOUR; F)

CLEAN/CHANGE ROOM SUFFICIENT FOR WORKERS TO CHANGE INTO STREET CLOTHES

(OPAQUE POLY REQUIRED AS NEEDED FOR PRIVACY); G) RENEWABLE ADHESIVE MATS

IMMEDIATELY OUTSIDE OF REGULATED WORK AREA TO ENSURE FOOT TRAFFIC DOES NOT

SPREAD DUST/DEBRIS TO OTHER AREAS OF FACILITY.

PERFORM ABATEMENT USING THE FOLLOWING CONTROLS: A) HEPA FILTERED VACUUM

FOR CONTINUOUS AND FINAL CLEANUP; B) USE MANUAL REMOVAL MEANS/TOOLS WHERE

ACM IS DISTURBED.

CLEANING OF REGULATED WORK AREAS IS TO INCLUDE HEPA VACUUMING & WET WIPING

METHODS. REGULATED AREAS ARE TO PASS A SUCCESSFUL VISUAL INSPECTION BY THE

VPIH PRIOR TO COLLECTION OF CLEARANCE SAMPLES.

VPIH WILL PERFORM PERIMETER AIR MONITORING, VISUAL INSPECTIONS AND FINAL AIR

CLEARANCE SAMPLING.

CONTRACTOR TO PERFORM OSHA EMPLOYEE EXPOSURE MONITORING.

WASTE PRODUCED DURING REMEDIATION SHALL BE COLLECTED, CONTAINERIZED,

LABELED, CHARACTERIZED AND DISPOSED IN ACCORDANCE WITH SPECIFICATION 02.82.11

10. WASTE CONTAINERS, TOOLS, EQUIPMENT, ETC. SHALL BE WET WIPED PRIOR TO

LEAVING REGULATED WORK AREA.

WHERE THE COMBINED AREA OF THE NPE INCLUDING , DECONTAMINATION, LOADOUT,

AND WORK CHAMBERS DOES NOT FIT WITHIN A ROOM, THE DECON/LOADOUT

CONFIGURATION MAY EXTEND INTO 1/2 WIDTH OF THE HALLWAY AS REQUIRED TO ALLOW

PASSAGE IN CORRIDOR.

ASBESTOS BLACK MASTIC IS PRESENT UNDERLYING VANITY COUNTERS AND ROOM

LOCKERS.

BID DOCUMENTS

e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

6 Veterans

Health Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

VA Health Care System Approval:

ARCHITECT:

U.S. Department of Veteran Affairs

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MO ARCH REG. NO. 2012034754, EXP. 12/31/2020

MO ENGR REG. NO. 2014031351, EXP. 12/31/2020

STRUCTURAL/ CIVIL

ENGINEER

H2B

1225 N LOOP W #800

HOUSTON, TX 77008

713-864-2900

FIRE PROTECTION ENGINEER

FU

LL

Y

SP

R

IN

K

LE

R

ED

SPUR DESIGN

312 SW 25TH STREET

OKLAHOMA CITY, OK 73109

405-842-6100

POOLE FIRE PROTECTION

19910 W. 161ST STREET

OLATHE, KS 66062

913-829-8650

HEALTHCARE/ MEDICAL

EQUIPMENT PLANNER

INNOVA GROUP

3196 N SWAN ROAD

TUCSON, AZ 85712

520-886-8650

LANDSCAPE ARCHITECT

CLS & ASSOCIATES

825 N BROADWAY AVE #315

OKLAHOMA CITY, OK 73102

405-525-2220

FOOD AND BEVERAGE

PLANNER

STURM CONSULTING

5838 S. HUDSON PLACE

TULSA, OK 74135

918-260-0667

ENVIRONMENTAL ENGINEER

RIVERFRONT ENVIRONMENTAL

1139 OLIVE STREET, SUITE 300

ST. LOUIS, MO 63101

314-436-9492

MECHANICAL/ ELECITRICAL

PLUMBING

2/ 3/

:1

3:

A M

ENVIRONMENTAL HAZARDS -

GROUND FLOOR

062 220

ADDITION AND RENOVATION OF CLC

09/06/2023

589-703

5500 EAST KELLOGG

WICHITA, KS 67218 HA100

No Revision Description Date

VISUAL KEY

AREA OF ASBESTOS BLACK MASTIC UNDERLYING

FLOORING TO BE REMOVED

LIMITS OF NEGATIVE PRESSURE CONTAINMENT

3-STAGE WET DECONTAMINATION CHAMBERS

2,000 CFM HEPA FILTERED AIR MACHINE

D

AM

A1 A3

A1A1A1A1A1 A1 A1 A1

L1 L1 L1

L1 L1 L1

L1 L1 L1

L1

A2

A2

A2

A2

A2

L3 L3 L3 L3

A2

A2

A2

A2 A2 A2 A2 A2

L3

L3

L3

L3 L3

L3

L2

A2

A5

A2

A2

A2 A2

A2

A2

A2

A2

A2

A1

A1

A2

A2

A2

A3

A3

A2

L3

L3

A2

L3

L1

L1

L1

L3

A2 A2

D

A5

A5

A1

A5

A5

A5

A5

D

AM

A1A3

A1

AM AM AM

AM

A6

A1

A1 A1 A1 A1 A1

A4A4A4A4A4A4A4A4A4

A4

A4

A4

A4

A4

A4

A4

A4

ENVIRONMENTAL HAZARDS KEY NOTES - PHASE 1

REMOVE WINDOW ASSEMBLY WITH ASBESTOS

GLAZING AND ASSOCIATED UNDERLYING CAULK

ON ADJACENT SURFACES USING MANUAL MEANS

WITHIN A NEGATIVE PRESSURE ENCLOSURE, 9

WINDOW GROUPS.

REMOVE ASBESTOS FIRE DOOR GROUPS AND

FRAMES AND ASSOCIATED CAULKS USING

MANUAL MEANS WITHIN A NEGATIVE PRESSURE

ENCLOSURE, 1 FIRE DOOR GROUP AND FRAME.

KEYNOTE REMOVED FOLLOWING ACCEPTANCE

OF BID DEDUCT

A5

A6

A7

ENVIRONMENTAL HAZARDS KEY NOTES - PHASE 3

REMOVE WINDOW ASSEMBLY WITH ASBESTOS

GLAZING AND ASSOCIATED UNDERLYING CAULK

ON ADJACENT SURFACES USING MANUAL MEANS

WITHIN A NEGATIVE PRESSURE ENCLOSURE, 19

WINDOW GROUPS.

REMOVE ASBESTOS BLACK MASTIC UNDERLYING

NON-ASBESTOS SHEET FLOORING OR FLOOR

TILES USING MANUAL MEANS WITHIN A NEGATIVE

PRESSURE ENCLOSURE, 8,850 SF.

REMOVE ASBESTOS FIRE DOOR GROUPS,

FRAMES, AND ASSOCIATED CAULKS USING

MANUAL MEANS WITHIN A NEGATIVE PRESSURE

ENCLOSURE, 7 FIRE DOOR GROUPS AND FRAMES.

WINDOWS TO REMAIN FOLLOWING THE

ACCEPTANCE OF BID DEDUCT. DO NOT DISTURB

WINDOW ASSEMBLIES

REMOVE LEAD CONTAINING PORCELAIN WALL

MOUNTED HAND SINKS WITHIN WHOLE WITHIN A

NEGATIVE PRESSURE ENCLOSURE, 14 SINKS

REMOVE LEAD CONTAINING PORCELAIN BATH

TUB IN WHOLE WITHIN A NEGATIVE PRESSURE

ENCLOSURE, 1 TUB

REMOVE LBP METAL CLOTHING LOCKER UNITS IN

WHOLE WITHIN A NEGATIVE PRESSURE

ENCLOSURE, 17 LOCKERS

A1

A2

A3

A4

L1

L2

L3

A5

A5 e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

6 Veterans

Health Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

VA Health Care System Approval:

ARCHITECT:

U.S. Department of Veteran Affairs

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MO ARCH REG. NO. 2012034754, EXP. 12/31/2020

MO ENGR REG. NO. 2014031351, EXP. 12/31/2020

STRUCTURAL/ CIVIL

ENGINEER

H2B

1225 N LOOP W #800

HOUSTON, TX 77008

713-864-2900

FIRE PROTECTION ENGINEER

FU

LL

Y

SP

R

IN

K

LE

R

ED

SPUR DESIGN

312 SW 25TH STREET

OKLAHOMA CITY, OK 73109

405-842-6100

POOLE FIRE PROTECTION

19910 W. 161ST STREET

OLATHE, KS 66062

913-829-8650

HEALTHCARE/ MEDICAL

EQUIPMENT PLANNER

INNOVA GROUP

3196 N SWAN ROAD

TUCSON, AZ 85712

520-886-8650

LANDSCAPE ARCHITECT

CLS & ASSOCIATES

825 N BROADWAY AVE #315

OKLAHOMA CITY, OK 73102

405-525-2220

FOOD AND BEVERAGE

PLANNER

STURM CONSULTING

5838 S. HUDSON PLACE

TULSA, OK 74135

918-260-0667

ENVIRONMENTAL ENGINEER

RIVERFRONT ENVIRONMENTAL

1139 OLIVE STREET, SUITE 300

ST. LOUIS, MO 63101

314-436-9492

MECHANICAL/ ELECITRICAL

PLUMBING

2/ 3/

:1

3:

A M

ENVIRONMENTAL HAZARDS -

ROOF

063 219

ADDITION AND RENOVATION OF CLC

09/06/2023

589-703

5500 EAST KELLOGG

WICHITA, KS 67218 HA200

No Revision Description Date

ENVIRONMENTAL HAZARDS KEY NOTES

REMOVE NEWER MEMBRANE ROOF AND

UNDERLYING ASBESTOS BUILT-UP ROOF,

FLASHING, SEALANTS AND ASSOCIATED GUTTER

SYSTEM TO GROUND HUB USING MANUAL MEANS

IN A REGULATED AREA, 800 SF.

REMOVE SPOT LOCATIONS OF NEWER

MEMBRANE ROOF AND UNDERLYING ASBESTOS

BUILT-UP ROOF USING MANUAL MEANS IN A

REGULATED AREA. SPOT LOCATIONS FOR

PENETRATIONS, SIZE AND LOCATIONS TO BE

COORDINATED WITH GENERAL CONTRACTOR, 6

LOCATIONS AND 45 SF TOTAL.

UNDERLYING ASBESTOS ROOF AND FLASHING

SYSTEM, PROTECT AS NECESSARY.

A1

VISUAL KEY

AREA OF ROOF AND GUTTER SYSTEM REMOVAL

2-STAGE WET HYGIENE STATION

A2

HS

A3

A1

HS

A2

A3

A2

MECHANICAL PENTHOUSE A2

A2 A2

A2

A3

A3

EXISTING BLDG #60

OMAR BRADLEY DR.

EXISTING PARKING LOT

AS001

20'-0"

'-0

2.20

2.20

25'-0"

2.48 2.47

2.47

2.53

2.512.51

2.522.52

2.53

2.47

2.47

2.54

2.562.56

2.572.57

1. ALL DOOR FRAMES TO BE LOCATED 4" FROM OUTSIDE OF FRAME TO FINISH FACE OF ADJACENT

WALL UNLESS NOTED OTHERWISE.

2. ALL WALLS ARE TYPE C3 PARTITIONS UNLESS OTHERWISE NOTED. REFER TO PARTITION TYPE

SHEET FOR WALL TYPES.

3. REFER TO DOOR SCHEDULE & DETAILS SHEET FOR DOOR INFORMATION.

4. REFER TO GLAZING ELEVATIONS & DETAILS SHEET FOR WINDOW INFORMATION.

5. ALL WALLS ARE DIMENSIONED TO CENTERLINE OF METAL STUD, UNLESS NOTED OTHERWISE.

6. BLOCK OUT SLAB FOR PENETRATIONS SHALL BE 2" LARGER THAN DUCT SIZE TO ALLOW

TOLERANCE FOR DUCT PASSAGE AND PENETRATION FIRESTOPPING. COORDINATE WITH MEP FOR

DUCT SIZES.

7. FURR AROUND ALL COLUMN PROTRUSIONS AS NEEDED UNLESS NOTED OTHERWISE.

8. PATCH AND REPAIR EXISTING INTERIOR FACE OF EXTERIOR WALL AS NECESSARY FOR

INSTALLATION OF NEW FRAMING AND FINISHES.

9. RESIDENT ROOMS B1 TO RECIEVE CEILING MOUNTED PATIENT LIFTS. RESIDENT ROOMS B2 TO

RECIEVE WALL MOUNTED PATIENT LIFTS.

GENERAL PLAN NOTES

SCOPE BOUNDARY

MONITORING WELL & 20'-0" ACCESS CLEARANCE

BUILDING FOOTPRINT

LANDSCAPED AREA

HARDSCAPED AREA

MW

SECURITY BOLLARD - LIGHTED

STORMWATER DRAIN

SECURITY BOLLARD - REMOVABLE

ACCESSIBLE RAMP

LOADING ZONE / FIRE LANE

STABILIZED DECORATIVE ROCK

CONCRETE PAVERS

SITE PLAN - LEGEND

EXISTING TREE TO REMAIN

EXISTING TREE TO BE REMOVED

2.18

3.16

2.232.23

26.10

26.0926.09 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. A-930 EXP. 12/31/2023

ENGR REG. NO. E-2586 EXP. 12/31/2023

STRUCTURAL/CIVIL

ENGINEER

H2B

1225 N. LOOP W #800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH

ENGINEER

SPUR DESIGN

11020 KING STREET, STE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

LANDSCAPE ARCHITECT

CLS & ASSOCIATES

825 N. BROADWAY AVE, STE 315

OKLAHOMA, OK 73102

(405) 525-2220

HEALTHCARE/MED

EQUIPMENT PLANNER

INNOVA GROUP

3196 N. SWAN ROAD

TUCSON, AZ 85712

(520) 886-8650

PHYSICAL SECURITY

FORCE PROTECT SECURITY

CONSULTANTS,

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

FOOD & BEVERAGE

PLANNER

STURM CONSULTING

5838 S. HUDSON PLACE

TULSA, OK 74135

(918) 260-0667

ENVIRONMENTAL

ENGINEER

RIVERFRONT ENVIRONMENTAL

1139 OLIVE STREET, STE 300

ST. LOUIS, MO 63101

(314) 436-9492

SPUR #: 2015

/5

/2

:3

:5

P

M

ARCHITECTURAL DEMOLITION SITE

PLAN

NR 063 OF 221DLK

BID DOCUMENTS

ADDITION AND RENOVATION

OF CLC

09/06/2023

589-703

ROBERT J. DOLE VA MEDICAL CENTER

5500 EAST KELLOGG, BLDG. 60

WICHITA, KS 67218

AS001

N

1" = 20'-0"

DEMOLITION SITE PLAN1

KEYNOTE LEGEND

2.18 EXISTING CHAIN LINK FENCE TO BE DEMOLISHED.

2.20 EXISTING PORTION OF CONCRETE DRIVE TO BE REMOVED FOR NEW SECURITY GATE.

2.23 REMOVE EXISTING TREE IN ITS ENTIRETY. TREE STUMP WILL BE REMOVED FOR NEW

CONSTRUCTION. PROTECT ADJACENT EXISTING EQUIPMENT AND CONSTRUCTION AS

NEEDED DURING DEMO WORK. PREP AREA FOR NEW CONSTRUCTION. REFERENCE

LANDSCAPE AND CIVIL DOCUMENTS FOR ADDITIONAL INFORMATION.

2.47 EXISTING WOOD FENCE TO BE REMOVED AND GIVEN TO THE VA.

2.48 EXISTING STRUCTURE TO BE REMOVED AND COORDINATED WITH THE VA FOR POSSIBLE

NEW LOCATION ON CAMPUS.

2.51 DEMO EXISTING BRICK PAVERS

2.52 DEMO RAISED GARDEN BEDS

2.53 DEMO CONCRETE PAD

2.54 PREPARE SITE FOR TEMPORARY BOILER AND AHU, REFER TO MECHANICAL.

2.56 EXISTING SIGNAGE

2.57 DEMO EXISTING LIGHT POLE

3.16 EXISTING CONCRETE SIDEWALK TO REMAIN

26.09 EXISTING TRANSFORMER, REFER TO ELECTRIAL

26.10 EXISTING SWITCHGEAR, REFER TO ELECTRICAL

1" = 10'-0" 1/ AS001

ARCHITECTURAL DEMO SITE PLAN2

FD

FD

FD

FD

FD

FD

FD

FD

FD

FD

FD

FD

FD

FD

FD

NEW OUTDOOR GARDEN, REF:

LANDSCAPE

NEW ADDITION

OMAR BRADLEY DR.

EXISTING PARING LOT

COURT-

YARD

SPACE

COURTYARD

SPACE

150'-0"

194'-4"

12'-0" 20'-0"

'-0

'-0

'-6

5'

-6

CONTRACTOR

STAGING

AREA

3.14

NEW ENTRY

VESTIBULE

AS010

EXISTING BLDG #60

3.15

32.0132.01

26.0426.04 26.0426.04

26.04

26.04

26.04

26.04

26.05

26.05

26.05

26.0526.05

26.05

26.05

26.05

11.04

26.0426.04

26.0426.04

26.04

26.04

26.05

10.3110.31

32.01

32.01

3.15

3.14

3.173.173.173.173.173.17

26.0426.0426.0426.0426.0426.04

3.17

3.17

3.17

CORRIDOR

BULDING #59

32.0232.03

32.03

32.02

32.04

32.05

22.10

22.10

FFE = 1348.37'

FFE =

1348.37'

SCOPE BOUNDARY

25'-0" SAFETY SETBACK

MONITORING WELL & 20'-0" ACCESS CLEARANCE

BUILDING FOOTPRINT

LANDSCAPED AREA

RAISED PLANTER BOX (BOLLARD ALTERNATIVE)

HARDSCAPED AREA

MW

SECURITY BOLLARD - LIGHTED

STORMWATER DRAIN

SECURITY BOLLARD - REMOVABLE

ACCESSIBLE RAMP

LOADING ZONE / FIRE LANE

STABILIZED DECORATIVE ROCK

CONCRETE PAVERS

SITE PLAN - LEGEND

NEW ANTI-RAM BOULDER, REFER TO LANDSCAPE

AS010

26.07

4.30 26'-0"

3.16

26.10

3' -0

26.0926.09

26.08

BUILDING #60

'-0

26.07

5.34 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. A-930 EXP. 12/31/2023

ENGR REG. NO. E-2586 EXP. 12/31/2023

STRUCTURAL/CIVIL

ENGINEER

H2B

1225 N. LOOP W #800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH

ENGINEER

SPUR DESIGN

11020 KING STREET, STE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

LANDSCAPE ARCHITECT

CLS & ASSOCIATES

825 N. BROADWAY AVE, STE 315

OKLAHOMA, OK 73102

(405) 525-2220

HEALTHCARE/MED

EQUIPMENT PLANNER

INNOVA GROUP

3196 N. SWAN ROAD

TUCSON, AZ 85712

(520) 886-8650

PHYSICAL SECURITY

FORCE PROTECT SECURITY

CONSULTANTS,

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

FOOD & BEVERAGE

PLANNER

STURM CONSULTING

5838 S. HUDSON PLACE

TULSA, OK 74135

(918) 260-0667

ENVIRONMENTAL

ENGINEER

RIVERFRONT ENVIRONMENTAL

1139 OLIVE STREET, STE 300

ST. LOUIS, MO 63101

(314) 436-9492

SPUR #: 2015

/5

/2

:3

:0

P

M

ARCHITECTURAL NEW SITE PLAN

NR 064 OF 221DLK

BID DOCUMENTS

ADDITION AND RENOVATION

OF CLC

09/06/2023

589-703

ROBERT J. DOLE VA MEDICAL CENTER

5500 EAST KELLOGG, BLDG. 60

WICHITA, KS 67218

AS010

N

1" = 20'-0"

OVERALL ARCHITECTURAL SITE PLAN1

KEYNOTE LEGEND

3.14 NEW ASPHALT PAVING, REFER TO CIVIL

3.15 NEW 6" CONCRETE CURB MEDIAN, REFER TO CIVIL

3.16 EXISTING CONCRETE SIDEWALK TO REMAIN

3.17 EXISTING IN GROUND FLAG POLE BASE TO REMAIN

4.30 NEW CMU TRANSFORMER EXPLOSION MITIGATION WALL

5.34 METAL CAP FLASHING

10.31 EXISTING EXTERIOR SIGNAGE TO REMAIN

11.04 NEW BASKETBALL GOAL AND POLE SET IN PLACE, REFER TO LANDSCAPE

22.10 INSTALL EXTERIOR DRAIN, REFER PLUMBING

26.04 EXTERIOR NEW WALL MOUNTED LIGHT FIXTURE, REFER TO ELECTRICAL

26.05 EXTERIOR LIGHT POLE, REFER TO ELECTRICAL

26.07 NEW EMERGENCY GENERATOR, REFER TO ELECTRICAL

26.08 NEW TRANSFORMER, REFER TO ELECTRICAL

26.09 EXISTING TRANSFORMER, REFER TO ELECTRIAL

26.10 EXISTING SWITCHGEAR, REFER TO ELECTRICAL

32.01 NEW SECURITY GATE WITH TRIPLE AUTHENTICATION

32.02 NEW 6' TALL METAL FENCE, REFER TO LANDSCAPE

32.03 NEW 6' TALL AND 4' WIDE METAL GATE WITH SECURITY CARD ACCESS READER, REFER TO

LANDSCAPE AND LOW VOLTAGE

32.04 NEW LICENSE PLATE RECOGNITION (ALPR) STANDARD RANGE CAMERA MOUNTED ON POLE

32.05 NEW VEHILE DETECTION LOOP

N

1" = 10'-0" 1/ AS010

ENLARGED PLAN - NEW GENERATOR2

1/8" = 1'-0" 2/ AS010

CMU WALL AT EMERGENCY GENERATOR3

CONTROLLED UNCLASSIFIED INFORMATION - CUI

2.102.102.10

1B122

1B121A

1B121

1B119

B5

1B120

1B120A

1B146

1B1231B143

B4

1B144

1B144A

1B145

1B147

1B147A

1B151

1B152

1B153

1B149

1B150

1B118

1B106A

1B117

1B104

1B108A 1B110A

1B106 1B108 1B110

1B114A

1B102

1B112 1B114 1B116

1B1151B113

1B113A1B109A1B105A

1B1001B1091B1071B105

1B103A

1B103B1B103

TOILET

1B101A

1B100

TOILET

1B100A

1B100

1B100B

0-STATION

101B101A

B1

104 103

108C

114A

108B

108A

103A

109A

113A

8'-0"

2.10

2.10 2.10

2.10

2.10

2.10

2.10

2.04

110E

110F

110D 110C

110B 110A

1B130

1B131A 1B1251B127

1B141

1B142

1B1241B1261B1281B129

1B140A

2.03

2.03

2.03

2.03

2.39

2.40

2.03

2.39

2.03

4'-5 3/8"

33'-4 3/4" 30'-0 3/8"

6'-2 3/8"

27'-10 1/2"

AE203

EXISTING WALL CONSTRUCTION TO BE DEMOLISHED IN ITS ENTIRETY

EXISTING DOOR AND FRAME TO BE

DEMOLISHED IN THEIR ENTIRETY

DEMOLITION LEGEND

EXISTING WALLS TO REMAIN

EXISTING AREA TO REMAIN

1. ALL EXISTING WALL DIMENSIONS ARE TO FINISH FACE, UNLESS OTHERWISE NOTED.

2. THE CONTRACTOR SHALL VERIFY DIMENSIONS OF AS-BUILT CONDITIONS, AND NOTIFY THE

ARCHITECT IN WRITING OF ANY DISCREPANCIES. ALL INFORMATION SHOWN ON THE

CONSTRUCTION DOCUMENTS IS BASED ON FIELD OBSERVATIONS AND/OR THE ORIGINAL

CONSTRUCTION DOCUMENTS OF THE FACILITY.

3. DEMOLITION AND CONSTRUCTION WORK MUST BE DONE UNDER NEGATIVE PRESSURE UTILIZING

HEPA FILTRATION UNITS.

4. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT OR AREA HAS BEEN

INSPECTED BY THE VA SAFETY OFFICER AND INFECTION CONTROL COORDINATOR AND

THOROUGHLY CLEANED BY ENVIRONMENTAL MANAGEMENT SERVICES.

5. THE CONTRACTOR SHALL PROVIDE PROTECTIVE COVERING FOR EXISTING FLOOR, WALL AND

CEILING FINISHES IN EXISTING AREAS NOT DESIGNATED FOR DEMOLITION OR NEW

CONSTRUCTION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REPAIR OF ANY DAMAGE

CAUSED BY HIS WORK OR ANY SUBCONTRACTOR.

6. THE CONTRACTOR SHALL VERIFY THAT NEW MECHANICAL SYSTEMS CAN BE INSTALLED IN

EXISTING SPACES TO CLEAR EXISTING CEILING AND OTHER CONSTRUCTED ITEMS AND MAINTAIN

FLOOR TO CEILING HEIGHTS INDICATED ON DRAWINGS. IF DISCREPANCIES OCCUR DUE TO

EXISTING CONDITIONS, CONSULT WITH THE ARCHITECT BEFORE PROCEEDING.

7. THE FINISH FACE OF MATERIAL OF NEW PARTITIONS SHALL ALIGN ON BOTH SIDES OF THE

PARTITION WITH THE FACE OF THE MATERIALS ON EXISTING COLUMNS, WALLS, OR PARTITIONS, UNLESS NOTED OTHERWISE.

8. NO WORK TO BE DONE IN HATCHED AREAS ON PLANS, HOWEVER WORK MIGHT NEED TO BE

PERFORMED IN CEILING OR EXISTING CHASES THROUGHOUT BUILDING. REFERENCE

MECHANICAL AND ELECTRICAL DRAWINGS FOR EXTENT OF WORK. COORDINATE ACCESS TO

ROOMS OUTSIDE OF SCOPE WITH OWNER.

GENERAL DEMOLITION NOTES

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. A-930 EXP. 12/31/2023

ENGR REG. NO. E-2586 EXP. 12/31/2023

STRUCTURAL/CIVIL

ENGINEER

H2B

1225 N. LOOP W #800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH

ENGINEER

SPUR DESIGN

11020 KING STREET, STE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

LANDSCAPE ARCHITECT

CLS & ASSOCIATES

825 N. BROADWAY AVE, STE 315

OKLAHOMA, OK 73102

(405) 525-2220

HEALTHCARE/MED

EQUIPMENT PLANNER

INNOVA GROUP

3196 N. SWAN ROAD

TUCSON, AZ 85712

(520) 886-8650

PHYSICAL SECURITY

FORCE PROTECT SECURITY

CONSULTANTS,

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

FOOD & BEVERAGE

PLANNER

STURM CONSULTING

5838 S. HUDSON PLACE

TULSA, OK 74135

(918) 260-0667

ENVIRONMENTAL

ENGINEER

RIVERFRONT ENVIRONMENTAL

1139 OLIVE STREET, STE 300

ST. LOUIS, MO 63101

(314) 436-9492

KEY PLAN

B

A

N

SPUR #: 2015

PHASING AND PROJECT SCOPE LEGEND

AREAS OF WORK OUTSIDE OF CURRENT PHASE OR OUTSIDE OF

PROJECT SCOPE SHOWN. REFERENCE GI011 & GI012 - PHASING PLANS

FOR MORE INFORMATION

/5

/2

:3

:2

P

M

DEMOLITION PLAN

NR 065 OF 221Checker

BID DOCUMENTS

ADDITION AND RENOVATION

OF CLC

09/06/2023

589-703

ROBERT J. DOLE VA MEDICAL CENTER

5500 EAST KELLOGG, BLDG. 60

WICHITA, KS 67218

AD010

N

1/8" = 1'-0"

LEVEL 1 - DEMOLITION PLAN AREA A1

KEYNOTE LEGEND

2.03 REMOVE PLUMBING FIXTURES IN ITS ENTIRETY. PREP AREA FOR NEW CONSTRUCTION.

REFERENCE PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION.

2.04 REMOVE CONCRETE TIERED FLOOR COMPLETE AND EXCAVATE.

2.10 REMOVE EXISITNG EXTERIOR WINDOWS

2.39 DEMO EXISTING INTERIOR DOOR AND FRAME SYSTEMS IN ITS ENTIRETY. PREP AREA FOR NEW

CONSTRUCTION.

2.40 COMPLETELY DEMOLISH INTERIOR STUD WALL PARTITION SYSTEM AS INDICATED. PROTECT

ADJACENT AREAS AND SURFACES AS NEEDED DURING DEMOLITION. PREP AREA FOR NEW

CONSTRUCTION. COORDINATE WITH OTHER DISCIPLINES ON MEP ITEMS ASSOCIATED WITH THE

PARTITION SYSTEM.

No. REVISION DESCRIPTION DATE

Checked

DLK

FD

FD

FD

1. ALL EXISTING WALL DIMENSIONS ARE TO FINISH FACE, UNLESS OTHERWISE NOTED.

2. THE CONTRACTOR SHALL VERIFY DIMENSIONS OF AS-BUILT CONDITIONS, AND NOTIFY THE

ARCHITECT IN WRITING OF ANY DISCREPANCIES. ALL INFORMATION SHOWN ON THE

CONSTRUCTION DOCUMENTS IS BASED ON FIELD OBSERVATIONS AND/OR THE ORIGINAL

CONSTRUCTION DOCUMENTS OF THE FACILITY.

3. DEMOLITION AND CONSTRUCTION WORK MUST BE DONE UNDER NEGATIVE PRESSURE UTILIZING

HEPA FILTRATION UNITS.

4. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT OR AREA HAS BEEN

INSPECTED BY THE VA SAFETY OFFICER AND INFECTION CONTROL COORDINATOR AND

THOROUGHLY CLEANED BY ENVIRONMENTAL MANAGEMENT SERVICES.

5. THE CONTRACTOR SHALL PROVIDE PROTECTIVE COVERING FOR EXISTING FLOOR, WALL AND

CEILING FINISHES IN EXISTING AREAS NOT DESIGNATED FOR DEMOLITION OR NEW

CONSTRUCTION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REPAIR OF ANY DAMAGE

CAUSED BY HIS WORK OR ANY SUBCONTRACTOR.

6. THE CONTRACTOR SHALL VERIFY THAT NEW MECHANICAL SYSTEMS CAN BE INSTALLED IN

EXISTING SPACES TO CLEAR EXISTING CEILING AND OTHER CONSTRUCTED ITEMS AND MAINTAIN

FLOOR TO CEILING HEIGHTS INDICATED ON DRAWINGS. IF DISCREPANCIES OCCUR DUE TO

EXISTING CONDITIONS, CONSULT WITH THE ARCHITECT BEFORE PROCEEDING.

7. THE FINISH FACE OF MATERIAL OF NEW PARTITIONS SHALL ALIGN ON BOTH SIDES OF THE

PARTITION WITH THE FACE OF THE MATERIALS ON EXISTING COLUMNS, WALLS, OR PARTITIONS, UNLESS NOTED OTHERWISE.

8. NO WORK TO BE DONE IN HATCHED AREAS ON PLANS, HOWEVER WORK MIGHT NEED TO BE

PERFORMED IN CEILING OR EXISTING CHASES THROUGHOUT BUILDING. REFERENCE

MECHANICAL AND ELECTRICAL DRAWINGS FOR EXTENT OF WORK. COORDINATE ACCESS TO

ROOMS OUTSIDE OF SCOPE WITH OWNER.

GENERAL DEMOLITION NOTES

2 BED

TLC ROOM

1B111

E12E11E10E9AE8A

ED

EE

EF

EG

E13E7

EF1

EH

P

E6 E8 E9

EB

E2 E3

EB1

EC

E4 E5 8543

K

I

H

J

5.5 6.52.5 3.5

N

G

2.40

2.03

2.032.03 2.03

2.03

2.03

2.03

2.03

2.03

2.03

2.03 2.03

2.03

2.03

2.03

2.03

2.03

2.03

2.03 2.03

2.03

2.032.03

2.03

2.03

2.39

2.03

1B122

1B121A

1B121

1B119

B5

1B120

1B120A

1B146

1B1231B143

B4

1B144

1B144A

1B145

1B147

1B147A

1B151

1B152

1B153

1B149

1B150

1B118

1B106A

1B117 1B104

1B108A 1B110A

1B106 1B108 1B110

1B114A

1B102

1B112 1B114 1B116

1B1151B113

1B113A1B109A1B105A

1B1111B1091B1071B105

1B100B

0-STATION

101B101A

B1

L

2.03

RESIDENT

RM

RESIDENT

RM

STAFF

LOUNGE

MULTIPURPOSE

/ ACTIVITY

ROOM

MP STOR

132A

ART ROOM

TOILET

CONF /

PRIVATE

DINING

RT OFC

MEDS

H.STOR

H. LAUNDRY

CORRIDOR

22.0622.06

2.03

22.06

22.06

22.06

22.06

2.03

22.06

2.03

2.03

2.03

22.06

2.392.392.392.392.392.392.392.39

2.392.392.392.392.392.392.392.392.392.392.39

2.392.39

2.39

2.39

2.39

2.39

2.39

2.39

2.39

2.39

2.39

2.39

2.39

2.39

2.39

2.39 2.39

2.39

2.39

2.39 2.39

2.39

2.39

2.39

2.39

2.39

2.39

2.39

2.392.39 2.39

2.39

2.39

2.392.39 2.39 2.39 2.39 2.39

2.39

2.39

2.40

2.40

2.40

2.402.40

2.40 2.402.40

2.40

2.402.402.402.402.40

2.402.40

2.40

2.402.402.40

2.402.40

2.402.402.40

2.40

2.402.402.40 2.402.40

2.40

2.402.40

2.402.402.402.40

2.402.40

2.402.40

2.40

2.40

103A

109A

113A

BATH

152A

BATH

151A

TOILET

EXAM

110B

EXAM

110A

OCCUPATIONAL

THERAPY

STORAGE

110C

OFFICE

110D

1.8

'-0

'-1

/2

'-0

'-3

2.34

2.34

2.45 2.45

2.03

2.39

2.03

2.55

1B130

1B131A 1B1251B127

1B141

1B142

1B1241B1261B1281B129

1B140A

CORRIDOR

EXISTING WALL CONSTRUCTION TO BE DEMOLISHED IN ITS ENTIRETY

EXISTING DOOR AND FRAME TO BE

DEMOLISHED IN THEIR ENTIRETY

DEMOLITION LEGEND

EXISTING WALLS TO REMAIN

EXISTING AREA TO REMAIN

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. A-930 EXP. 12/31/2023

ENGR REG. NO. E-2586 EXP. 12/31/2023

STRUCTURAL/CIVIL

ENGINEER

H2B

1225 N. LOOP W #800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH

ENGINEER

SPUR DESIGN

11020 KING STREET, STE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

LANDSCAPE ARCHITECT

CLS & ASSOCIATES

825 N. BROADWAY AVE, STE 315

OKLAHOMA, OK 73102

(405) 525-2220

HEALTHCARE/MED

EQUIPMENT PLANNER

INNOVA GROUP

3196 N. SWAN ROAD

TUCSON, AZ 85712

(520) 886-8650

PHYSICAL SECURITY

FORCE PROTECT SECURITY

CONSULTANTS,

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

FOOD & BEVERAGE

PLANNER

STURM CONSULTING

5838 S. HUDSON PLACE

TULSA, OK 74135

(918) 260-0667

ENVIRONMENTAL

ENGINEER

RIVERFRONT ENVIRONMENTAL

1139 OLIVE STREET, STE 300

ST. LOUIS, MO 63101

(314) 436-9492

KEY PLAN

B

N

SPUR #: 2015

PHASING AND PROJECT SCOPE LEGEND

AREAS OF WORK OUTSIDE OF CURRENT PHASE OR OUTSIDE OF

PROJECT SCOPE SHOWN. REFERENCE GI011 & GI012 - PHASING PLANS

FOR MORE INFORMATION

/5

/2

:3

:2

P

M

DEMOLITION PLAN

NR 066 OF 221DLK

BID DOCUMENTS

ADDITION AND RENOVATION

OF CLC

09/06/2023

589-703

ROBERT J. DOLE VA MEDICAL CENTER

5500 EAST KELLOGG, BLDG. 60

WICHITA, KS 67218

AD011

N

1/8" = 1'-0"

LEVEL 1 - DEMOLITION PLAN AREA B1

BUILDING 60

KEYNOTE LEGEND

2.03 REMOVE PLUMBING FIXTURES IN ITS ENTIRETY. PREP AREA FOR NEW CONSTRUCTION.

REFERENCE PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION.

2.34 DEMO EXISTING EXTERIOR BRICK VENEER WALL SYSTEM IN ITS ENTIRETY OR AS SHOWN ON

THE PLAN. THIS INCLUDES, BUT IS NOT LIMITED TO BRICK, STUDS, INSULATION, CONCRETE, BLOCKING, FLASHING AND ANY MATERIAL AS PART OF THE…