Attachment 2C BOD Electric Condensate Packages.pdf
PDF 8 MB Posted
- Solicitation number
- 36C24926R0017
About this file
This document is Appendix D—Equipment Cut-Sheets for a federal construction project at Murfreesboro VAMC, Alvin C. York Campus, under AE Works Project No. VMUR-002, VA Contract No. 36C24923C0020, Task Order No. 626A4-22-211. The project involves an upgrade to the steam distribution system (AJP).
The cut-sheets provide detailed technical specifications and ordering information for two primary equipment categories: Armstrong 4700 Series Condensate Units with cast iron tanks and Watson McDaniel W4100, W4200, and W4300 Electric Condensate Pumps. The Armstrong units are available in simplex or duplex configurations with capacities ranging from 2,000 to 50,000 square feet EDR, discharge pressures of 20–50 PSI, pump capacities from 3–75 GPM, and motor horsepower from 0.5–3 HP. Receiver tank sizes range from 6–50 gallons. The units feature heavy-duty cast iron receivers, stainless steel centrifugal pumps, 3450 RPM motors, automatic venting, carbon ceramic pump seals rated to 300°F, and optional accessories including mechanical/electrical alternators, gauge glass, thermometers, isolation valves, and NEMA 12 control panels. The Watson McDaniel electric pumps are available in three tank material options (carbon steel, cast iron, and stainless steel) for both condensate return and boiler feed applications, with discharge pressures up to 50 PSIG and maximum operating temperatures of 190°F. Both product lines include comprehensive ordering guidelines, dimensional diagrams, and accessory options to support the steam system upgrade requirements.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
North America • Latin America • India • Europe / Middle East / Africa • China • Pacific Rim armstronginternational.com/veris
Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit armstronginternational.com/veris for up-to-date information.
4700 SERIES
CONDENSATE UNITS
CAST IRON TANK
Skid Packages are to come with a Bacnet/BAS interface card to retrieve status refer to drawing M801 for points list.
North America • Latin America • India • Europe / Middle East / Africa • China • Pacific Rim armstronginternational.com/veris
Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit armstronginternational.com/veris for up-to-date information.
Technical Specifications
4700 Series Condensate Units set new standards of performance. Reliable and efficient, each unit features heavy-duty cast iron receivers for long operating life.
In addition, 3450 RPM motors assure maximum efficiency while maintaining minimum motor horsepower. Available in a wide range of sizes, these
U.S. made units have just the right accessories and options to meet your unique needs.
Features
• Heavy-duty cast iron receivers
• Simplex or duplex construction
• Stainless steel fitted centrifugal pumps
• Energy efficient 3450 RPM motors
• Automatic venting
• Carbon ceramic pump seal (300°F) with EPDM elastomers
• Heavy-duty float switch
• Wide range of options and accessories
Optional Features
• Mechanical and electric alternators for duplex units
• Gauge glass
• Thermometer
• Isolation valves
• Special motor construction, such as totally enclosed, washdown duty and explosion-proof is available
• 75 & 120 gallon tanks are available
• Elevated tanks are available
• Complete NEMA 12 Control Panel
4700 SERIES Condensate Units - Cast Iron Tank
North America • Latin America • India • Europe / Middle East / Africa • China • Pacific Rim armstronginternational.com/veris
Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit armstronginternational.com/veris for up-to-date information.
Elevated Unit
Control Panel
Complete NEMA 12 Control Panel
(Optional)
• Motor Circuit Protector
• HOA Selector Switch
• External Reset
• Control Circuit Transformer
• Pilot Light (pump running)
• Removable Mounting Plate and Terminal Strip in a
Single NEMA 12 Enclosure
• Mounted and Wired with Single Point Power Connection.
BA
Inside view of control panel
Motors:
Heavy-duty, ball-bearing, close-coupled pump motors with stainless steel shaft. 3450 RPM for greater efficiency and more economical operation.
Float Switch:
Two-pole, drip proof case, stainless steel float and float rod, double-break silver-to-silver contacts. Float travel adjustment is easy, visible and accessible.
Automatic Venting:
Provides for efficient operation and long life by venting air and flushing seal area.
Large Tanks:
Plenty of capacity for maximum rating of pump. Return inlet is low. Occupies a minimum of floor space.
Impeller:
Made of stainless steel for long life. Efficient design provides maximum capacity, minimum motor load.
Inducer:
Made of stainless steel for long life. Raises the inlet pressure by an amount sufficient to prevent cavitation.
Pump seal (A):
Features the ultimate in ceramic technology for exceptionally long life. Seal is carbon ceramic with
EPDM elastomers. Rated for temperatures up to
300°F.
Isolation Valve (B):
Optional on 4700 Series Condensate Units. Allows removal of pump without draining the tank.
4700 Series Product Features
Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit armstronginternational.com/veris for up-to-date information.
Sample Specification
Furnish and install, where indicated on plans, an Armstrong 4700 Series (simplex or duplex) condensate unit(s), having a capacity of ___________ sq. ft. E.D.R.___________ GPM against a discharge pressure of
___________ PSI. The receiver shall have a capacity of ___________ gallons and be heavy-duty cast iron construction. Pump(s) shall be of the centrifugal type with one-piece enclosed stainless steel impeller, stainless steel inducer, cast iron housing, high temperature (300°F) mechanical seal and stainless steel motor shaft. The float switch shall be two-pole with plastic case, stainless steel float and shaft, and double-break silver contacts. An optional inlet
“Y” or basket strainer is recommended for installation on the tank return inlet for pump protection. The motor(s) shall be vertical, 3450 RPM, ___________ phase, ___________ volt, 60 cycle, _______ H.P. The complete unit is to be factory assembled and tested prior to shipment.
4700 Series Engineering and Capacity Data
Capacity Sq. Ft. EDR
Discharge Pressure PSI
Pump Capacity, GPM
Motor
HP
Rec.
Capacity, Gallons
Unit Model Number Shipping Weight, lbs.
Simplex Duplex Simplex Duplex
2,000
4,000
6,000
8,000
1/2
1/2
1/2
1/2
AFH-4722-K
AFH-4724-K
AFH-4726-K
AFH-4728-K
AFH-4726-KD
AFH-4728-KD
10,000
15,000
20,000
22.5
1/2
1/2
3/4
AFH-47210-K
AFH-47215-K
AFH-47220-K
AFH-47210-KD
AFH-47215-KD
AFH-47220-KD
25,000
30,000
37.5
3/4
AFH-47225-K
AFH-47230-K
AFH-47225-KD
AFH-47230-KD
40,000 20 60 1-1/2 50 AFH-47240-K AFH-47240-KD 420 500
50,000 20 75 1-1/2 50 AFH-47250-K AFH-47250-KD 425 510
2,000
4,000
6,000
8,000
10,000
3/4
3/4
3/4
3/4
AFH-4732-K
AFH-4734-K
AFH-4736-K
AFH-4738-K
AFH-47310-K
AFH-4736-KD
AFH-4738-KD
AFH-47310-KD
15,000
20,000
22.5
AFH-47315-K
AFH-47320-K
AFH-47315-KD
AFH-47320-KD
25,000
30,000
37.5
1-1/2
1-1/2
AFH-47325-K
AFH-47330-K
AFH-47325-KD
AFH-47330-KD
40,000 30 60 2 50 AFH-47340-K AFH-47340-KD 425 510
50,000 30 75 2 50 AFH-47350-K AFH-47350-KD 435 525
2,000
4,000
6,000
8,000
10,000
1-1/2
1-1/2
1-1/2
AFH-4742-K
AFH-4744-K
AFH-4746-K
AFH-4748-K
AFH-47410-K
AFH-4746-KD
AFH-4748-KD
AFH-47410-KD
15,000
20,000
22.5
1-1/2
1-1/2
AFH-47415-K
AFH-47420-K
AFH-47415-KD
AFH-47420-KD
25,000
30,000
37.5
AFH-47425-K
AFH-47430-K
AFH-47425-KD
AFH-47430-KD
40,000 40 60 3 50 AFH-47440-K AFH-47440-KD 425 510
50,000 40 75 3 50 AFH-47450-K AFH-47450-KD 435 525
2,000
4,000
6,000
8,000
10,000
1-1/2
1-1/2
1-1/2
1-1/2
AFH-4752-K
AFH-4754-K
AFH-4756-K
AFH-4758-K
AFH-47510-K
AFH-4756-KD
AFH-4758-KD
AFH-47510-KD
15,000
20,000
22.5
AFH-47515-K
AFH-47520-K
AFH-47515-KD
AFH-47520-KD
25,000
27,000
37.5
AFH-47525-K
AFH-47527-K
AFH-47525-KD
AFH-47527-KD
Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit armstronginternational.com/veris for up-to-date information.
4700 Series Product Diagrams – continued
Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit armstronginternational.com/veris for up-to-date information.
Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit armstronginternational.com/veris for up-to-date information.
Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit armstronginternational.com/veris for up-to-date information.
North America • Latin America • India • Europe / Middle East / Africa • China • Pacific Rim armstronginternational.com/veris
Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit armstronginternational.com/veris for up-to-date information.
Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit armstronginternational.com/veris for up-to-date information.
W4100, W4200 & W4300 Electric PumpElectric Condensate Pumps
Model W4100 W4200 W4300 Connections NPT NPT NPT Tank Material Carbon Steel Cast Iron Stainless Steel Max Disch. Press. 50 PSIG 50 PSIG 50 PSIG
TMO/TMA 190˚F 190˚F 190˚F
Options Mechanical & electrical alternators; gauge glass; thermometer; discharge pressure gauges; isolation valves; magnetic starters; 1750 RPM motors; control panels;
oversized or stainless steel receivers; high temperature components
ELEC
TR
IC
P U
M P S
Typical Applications
Used for general condensate return or for boiler feed applications.
Available in Simplex or Duplex configurations with several different receiver sizes available.
How It Works
For Condensate Return Applications:
The float, which is connected to the switch assembly, rises when condensate enters the receiver tank. When the float rises above its set point, it energizes the motor on the pump. Once started, the pump will continue to run until the water level drops below the bottom position of the float switch.There it will de-energize the motor to shut off the pump. This cycle repeats as condensate begins to fill the receiver tank. On duplex systems the float switch is replaced with a Mechanical Alternator-Switch connected to a float. The Mechanical Alternator cycles use between the two pumps, allowing only one pump to run at a time under normal conditions. If the condensate reaches a high water level, both pumps will be activated.
For Boiler Feed Applications:
For Boiler Feed units, the operation of the pump is controlled by the water level control device which is part of the boiler control package. When the boiler requires water, the pump switches on pumping water from the receiver into the boiler.
On Duplex boiler feed units, an Electrical Alternator is used to activate one pump at a time in alternating fashion. The receiver tank also contains an internal make-up water valve actuated by a stainless steel float. This is used if the amount of condensate being returned to the receiver tank is inadequate.
Sample Specifications
Pump(s) shall be of the centrifugal type with 2-piece closed bronze impeller, cast iron housing and stainless steel motor shaft.
A flat perforated brass strainer shall be provided in the inlet of the pump.
Installation
Place on an elevated, level and substantial foundation in a clean, dry and accessible area. Locate receiver tank inlet below lowest point of the condensate return lines.
Features
• Fabricated steel receivers (W4100), Cast Iron (W4200), Stainless Steel (W4300)
• Simplex and duplex packages
• Bronze-fitted centrifugal pumps
• Energy-efficient 3450 RPM motors
• Automatic venting of mechanical seal
• Ceramic pump seal with carbon face
• Heavy-duty float switch
• All steel and iron receivers over 24 gallons include a threaded NPT overflow port
Options
• Mechanical and Electrical Alternators
• Gauge Glass
• Thermometers
• Discharge Pressure Gauges
• Isolation valves
• Magnetic Starters with HOA Selector Switch
• 1750 RPM Motors
• Larger pumping capacities & higher discharge pressures
• Wide variety of control panels
• Oversized Receivers (45, 60 & 95 gallons)
• Stainless Steel Receivers
• High Temperature (250˚F) Components
Tel: 610-495-5131 • Pottstown PA • USA •• www.watsonmcdaniel.com
60 Hz Motor 50 Hz MotorMotor Phase & Voltage Code Code
115 VAC 1P115 1P115E
208 VAC 1P208 1P208E
230 VAC 1P230 1P230E
208 VAC 3P208 3P208E
230 VAC 3P230 3P230E
460 VAC 3P460 3P460E
575 VAC 3P575 3P575E
Single Phase
Three Phase
Phase & Voltage Codes for Standard 60/50 Hz Motors
Option Suffix Code
Totally Enclosed Fan Cooled (1/2 to 3 hp) TEFC Explosion Proof – 1/2, 3/4, 1 hp EP1 Explosion Proof – 11/2 & 2 hp EP2 Explosion Proof – 3 hp EP3
Gate Valve, Check Valve &
Pressure Gauge (optional)
Gauge Glass (optional on condensate return units)
NEMA-12
Control Panel
(optional)
Thermometer (optional)
Isolation Valve (optional)
Mechanical Alternator (must be ordered separately with Duplex units)
Float Switch (standard with Simplex units)
Codes for Specialty Motors (add as a Suffix)
W4100, W4200 & W4300 Electric Condensate Pumps Electric Pump
Ordering Guidelines:
1) Decide on appropriate Receiver tank material for the application; W4100-Series with Steel Receiver tanks, W4200-Series with Cast Iron Receiver tanks or W4300 with Stainless Steel Receiver tanks.
2) Based on the particular application the model selection charts are separated on adjoining pages into either Boiler Feed or Condensate Return units. The proper pump model/size in GPM (gallons per minute) to suit the application and recommended receiver size for a Boiler Feed application is based on boiler size measured in Boiler Horsepower. The proper pump model size in GPM and recommended receiver size for a Condensate Return application is based on the Effective Direct Radiation (EDR) in square feet of the heating surfaces throughout the facility that the pump is expected to handle.
3) Select a pump discharge pressure that will exceed system back pressure, friction loss in piping and pressure in the boiler (in the case of a boiler feed pump). Selecting a pump with a significantly higher discharge pressure than required can cause pump to cavitate.
4) Decide if a Simplex (Single pump) unit is adequate or a Duplex (two pump) unit would be more appropriate in terms of system reliability and redundancy in the event of a pump failure.
5) Select Motor Phase and Voltage (reference chart). For smaller units under 11/2 hp Single phase motors may be desirable because of ease of installation. For units in excess of 11/2 hp, the more efficient and robust 3-phase motors are recommended.
Example Model Code: W4142JD-3P230 Duplex Condensate Return Pump, 3 GPM flow rate & 40 PSI discharge (Pump Unit) pressure & 15 gallon receiver, 1hp, 230 VAC, 60Hz, 3-Phase motor.
Example Model Code: MECH-ALT-N1 Note: Since a Duplex pump was chosen, a Mechanical Alternator must be purchased (Mechanical Alternator) separately to replace the standard Float Switch.
How to Order an Electric Condensate Return or Boiler Feed Pump
Condensate Return Boiler Feed
Water Make-Up Valve
Gauge Glass (standard on
Boiler Feed Pumps)
NEMA-12
Control Panel
(optional)
EL
EC
TR
IC
P U
M P S www.watsonmcdaniel.com •• Pottstown PA • USA • Tel: 610-495-5131
Allows pump and motor to be removed without draining condensate.
ELEC
TR
IC
P U
M P S
For SIMPLEX and DUPLEX pumps Model Code
Gauge Glass for Steel Tank GAUGE-GLASS-ST Gauge Glass for Cast Iron Tank GAUGE-GLASS-CI Isolation Valve ISO-VALVE Dial Thermometer DIAL-THERM Discharge Pressure Gauge PRESS-GAUGE-D Discharge Check Valve CHECK VALVE-D Float Switch - NEMA 4 (for Simplex Unit) FLOAT-SWITCH-N4 Float Switch - Explosion Proof (for Simplex Unit) FLOAT-SWITCH-EP
Electrical Connections
Replaces the standard float switch on Duplex Condensate Return Units. Must be ordered separately.
On Duplex units, the standard float switch is replaced with a Mechanical Alternator float switch to alternate operation between the two pumps. Must be ordered separately.
An Electric Alternator is also an option.
For Duplex Pumps must choose either:
A Mechanical Alternator or 2-Level Float Switch with the Electric Alternator Option on NEMA-12 Control Panel
Mechanical Alternator & Float Switches Model Code
Mechanical Alternator - NEMA 1 (replaces Float Switch on Duplex pumps) MECH-ALT-N1 Mechanical Alternator - NEMA 4 (replaces Float Switch on Duplex) MECH-ALT-N4 Mechanical Alternator - Explosion Proof (replaces Float Switch on Duplex) MECH-ALT-EP 2-Level Float Switch – (required when using an Electrical Alternator - Reference NEMA-12 Control Panel)* FLOAT-SWITCH-2L (Option) High-Level Auxiliary Contacts for Mechanical Alternator CONTACTS-HLA
* 2-level float switch not required with Duplex Boiler Feed Units
Condensate Return Pumps (ordered separately)
W4100, W4200 & W4300 Electric PumpElectric Condensate Pumps
Simplex Duplex Duplex Duplex Cast Iron Tank Cast Iron Tank Stainless Steel Tank Cast Iron Tank
Condensate Return Boiler Feed
For SIMPLEX and DUPLEX pumps Model Code
Isolation Valve ISO-VALVE Dial Thermometer DIAL-THERM Discharge Pressure Gauge PRESS-GAUGE-D Discharge Check Valve CHECK VALVE-D
Gauge glass is standard on boiler feed pumps.
Boiler Feel Pumps (ordered separately)
Isolation Valve
How to Order an Electric Condensate Return or Boiler Feed Pump
Mechanical Alternator For Duplex Condensate Return Pump Only
Accessory Items
NEMA 12 - Control Panel (for Duplex & Simplex Pumps)
Standard Control Panel Includes:
• Motor Circuit Protector(s)
• HOA Selector Switch(s)
• External Reset(s)
Standard Simplex Duplex CONTROL PANEL Model Code Model Code
1/3 thru 5 Horsepower CPN12-P1-S CPN12-P1-D Over 5 Horsepower CPN12-P2-S CPN12-P2-D
Purchasing the optional motor control panel is a convenient and simple method of hooking up your pump.
Example Model Codes: 1) CPN12-P1-S (Control Panel, NEMA 12, 1/3 thru 5 hp, Simplex, no options)
2) CPN12-P1-S-UL (Control Panel, NEMA 12, 1/3 thru 5 hp, Simplex with UL Certification)
3) CPN12-P2-D-E (Control Panel, NEMA 12, over 5 Hp, Duplex, with Electric Alternator)
For Simplex units, the control panel would include a single motor starter with a single HOA (HAND-OFF-AUTOMATIC) selector switch to turn the pump on manually to verify functionality; or, to set in automatic mode along with a single Motor Circuit Protector switch to shut power off to the pump.
For Duplex systems, the control panel would include two motor starters with two HOA (HAND-OFF-AUTOMATIC) selector switches to turn either of the two pumps on manually to verify functionality, or to set in automatic mode along with two separate Motor Circuit Protector switches to shut power off to either of the two pumps.
An Electric Alternator option can be used to replace the standard Mechanical Alternator; this option uses electronic logic as opposed to a mechanical device to cycle operation between the two pumps. If an Electrical Alternator is chosen, the Mechanical Alternator is replaced with a 2-level float switch (suffix code E).
Other Options, such as Pilot Light indicating when the pump is running or High Level Alarm Horn & Light indicating a flood system condition, can be added.
Control Panel Options Pilot Light Indicates when a pump is running;
Simplex - One light; Duplex - Two Lights.
Test Push Button Used to test if pilot light is functional. Press to test.
Electric Alternator Uses electronic logic to alternate operation between two pumps.
This option is required for Duplex Boiler Feed systems.
For Condensate Return Systems: if an Electric Alternator is chosen instead of the Mechanical Alternator, a 2-Level Float Switch is required.
(See Accessories - Electric Alternator Option. Model: FLOAT-SWITCH-2L)
High-Level Alarm Alarm to indicate if maximum water level is exceeded.
W4100, W4200 & W4300 Electric Condensate Pumps Electric Pump
Motor Control Panel
Options Suffix Code UL Certification UL Pilot Light (Power On) (1 required per pump) P Test Push Button (1 required per pump) T Electric Alternator (for Duplex)* E
(2-Level Float Switch is required with Electric Alternator)
High-Level Alarm Horn & Light with Silencing Switch HA All of the Above Options AO
Note: Standard Voltages are: 1-phase/60 Hz/115, 208, 230 VAC and 3-phase/60Hz/208, 230, 460, 575 VAC.
For non-standard voltages; consult factory.
* 2-Level Float Switch is required with Electric Alternator for Condensate Pumps Only; Not required for Boiler Feed Units.
EL
EC
TR
IC
P U
M P S
Control Panel Model Codes www.watsonmcdaniel.com •• Pottstown PA • USA • Tel: 610-495-5131
ELEC
TR
IC
P U
M P S
Motor Control Panel
W4100, W4200 & W4300 Electric PumpElectric Condensate Pumps
Phase Power Voltage Model Code
Up to 1 HP 115 VAC MSN1-1P-1-115 Up to 2 HP 230 VAC MSN1-1P-2-230 Up to 2 HP 115 VAC MSN1-1P-2-115 Up to 3 HP 230 VAC MSN1-1P-3-230 Up to 3 HP 230 VAC MSN1-3P-3-230 Up to 2 HP 460 VAC MSN1-3P-2-460 Up to 7.5 HP 230 VAC MSN1-3P-7-230 Up to 5 HP 460 VAC MSN1-3P-5-460
Option Pilot Light (Suffix Code) P
Example Model Codes:
1) MSN1-1P-1-115 (Motor Starter, NEMA 1, single-phase, 1 HP, 115 VAC)
2) MSN1-3P-3-230-P (Motor Starter, NEMA 1, three-phase, 3 HP, 230 VAC with Pilot light)
Single Phase
Three Phase
NEMA 1 - Control Panel (for Simplex Pumps Only)
• Magnetic across-the-line motor starter *
• Thermal overload and Hand-Off-Automatic (HOA) selector switch
• Optional Pilot Light
* Allows for remote start-up with full line voltage across the motor terminals.
For Simplex units, the NEMA 1 Control Panel will include a single motor starter with a HOA (HAND-OFF-AUTOMATIC) selector switch to turn the pump on manually, or to set in automatic mode. A single Motor Circuit Protector switch shuts the power off to the pump when an overload (OL) condition is detected.
NEMA 12 - Control Panel (for Duplex & Simplex Pumps)
16”6”
5”
16”
5”
Disconnect Switches
Alarm Silence Switch
High-Level Alarm Horn
Alarm Pilot Light
Pump Run Pilot Lights
HAND-OFF-AUTO Selector Switches
Elapsed Time Meters
TEST-PUSH BUTTONS
Mounting Bracket
Untitled