This solicitation is for a 100% total small business set-aside project titled "CNRC Critical Upgrades to Insulation, Piping & HVAC - Houston, TX". The project scope involves critical upgrades to insulation, piping, and HVAC systems. The applicable NAICS code is 236220 - Commercial and Institutional Building Construction, and the SBA size standard is $45.0M. Vendors are required to complete blocks 14, 15, 17, 19, and 20 A-C on the solicitation form. Contractors must be registered in active status in SAM.gov at the time of proposal submission according to FAR 52.204-7. The solicitation is issued by the Department of Agriculture Agricultural Research Service Field Research Implementation and Information Delivery Plains Area for a project with a value between $1,000,000 - $5,000,000.

View the file

Other files

Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

USDA

INDEX OF DRAWINGS

GENERAL NOTES:

1. BUILDING WILL REMAIN OCCUPIED AND OPERATION BY THE GOVERNMENT DURING THE

WORK. MEANS OF EGRESS SHALL BE MAINTAINED AT ALL TIMES.

2. STORM DRAIN REPLACEMENT AND INSULATION WORK MUST BE COMPLETED OUTSIDE OF

REGULAR HOURS. REFER TO SPECIFICATIONS FOR WORKING HOURS REQUIREMENTS.

3. STORM DRAIN WORK INDICATED ON PLUMBING DRAWINGS MUST BE COMPLETED PRIOR

TO INSULATION WORK BENEATH PATIOS.

4. COORDINATE CONSTRUCTION ACCESS AND STAGING AREA(S) WITH CONTRACTING

OFFICER PRIOR TO COMMENCING WORK.

U.S. DEPARTMENT OF AGRICULTURE

AGRICULTURAL RESEARCH SERVICE

CNRC CRITICAL UPGRADES

TASK ORDER: 12805B23F0146

CHILDREN'S NUTRITIONAL RESEARCH CENTER (CNRC)

HOUSTON, TEXAS

PROJECT LOCATION

LEGEND

ELEVATION CROSS REFERENCEX

XXXXX

ENLARGED PLAN/AREA OF WORK REFERENCEX

XXXXX

NORTH ARROW

VICINITY MAP (1" = 0.4 MILES)

SHEET NO. DRAWING NO. TITLE

T-001 1 OF 91 TITLE SHEET AND INDEX

A1301 2 OF 91 BASEMENT LEVEL 3 - RCP

A1302 3 OF 91 BASEMENT LEVEL 2 - RCP

A1303 4 OF 91 BASEMENT LEVEL 1 - RCP

A1304 5 OF 91 FLOOR LEVEL 1 - RCP

A1305 6 OF 91 FLOOR LEVEL 2 - RCP

A1306 7 OF 91 FLOOR LEVEL 3 - RCP

A1307 8 OF 91 FLOOR LEVEL 4 - RCP

A1308 9 OF 91 FLOOR LEVEL 5 - RCP

A1309 10 OF 91 FLOOR LEVEL 6 - RCP

A1310 11 OF 91 FLOOR LEVEL 7 - RCP

A1311 12 OF 91 FLOOR LEVEL 8 - RCP

A1312 13 OF 91 FLOOR LEVEL 9 - RCP

A1313 14 OF 91 FLOOR LEVEL 10 - RCP

A1314 15 OF 91 FLOOR LEVEL 11 - RCP

A1315 16 OF 91 FLOOR LEVEL 12 - RCP

P-001 17 OF 91 PLUMBING ABBREVIATIONS AND NOTES

PD101 18 OF 91 BASEMENT LEVEL 3 STORM DRAIN PIPING DEMO. PLAN

PD102 19 OF 91 BASEMENT LEVEL 2 STORM DRAIN PIPING DEMO. PLAN

PD103 20 OF 91 BASEMENT LEVEL 1 STORM DRAIN PIPING DEMO. PLAN

PD104 21 OF 91 LEVEL 1 STORM DRAIN PIPING DEMO. PLAN

PD105 22 OF 91 LEVEL 2 STORM DRAIN PIPING DEMO. PLAN

PD106 23 OF 91 LEVEL 3 STORM DRAIN PIPING DEMO. PLAN

PD107 24 OF 91 LEVEL 4 STORM DRAIN PIPING DEMO. PLAN

PD113 25 OF 91 LEVEL 10 STORM DRAIN PIPING DEMO. PLAN

PD114 26 OF 91 LEVEL 11 STORM DRAIN PIPING DEMO. PLAN

PD115 27 OF 91 LEVEL 12 STORM DRAIN PIPING DEMO. PLAN

P-101 28 OF 91 BASEMENT LEVEL 3 STORM DRAIN PIPING FLOOR PLAN

P-102 29 OF 91 BASEMENT LEVEL 2 STORM DRAIN PIPING FLOOR PLAN

P-103 30 OF 91 BASEMENT LEVEL 1 STORM DRAIN PIPING FLOOR PLAN

P-104 31 OF 91 LEVEL 1 STORM DRAIN PIPING FLOOR PLAN

P-105 32 OF 91 LEVEL 2 STORM DRAIN PIPING FLOOR PLAN

SHEET NO. DRAWING NO. TITLE

P-106 33 OF 91 LEVEL 3 STORM DRAIN PIPING FLOOR PLAN

P-107 34 OF 91 LEVEL 4 STORM DRAIN PIPING FLOOR PLAN

P-113 35 OF 91 LEVEL 10 STORM DRAIN PIPING FLOOR PLAN

P-114 36 OF 91 LEVEL 11 STORM DRAIN PIPING FLOOR PLAN

P-115 37 OF 91 LEVEL 12 STORM DRAIN PIPING FLOOR PLAN

P-601 38 OF 91 STORM DRAIN RISER DIAGRAM

M-001 39 OF 91 MECHANICAL ABBREVIATIONS AND NOTES

MD104 40 OF 91 LEVEL 1 MECHANICAL DEMOLITION PLAN

MD105 41 OF 91 LEVEL 2 MECHANICAL DEMOLITION PLAN

MD106 42 OF 91 LEVEL 3 MECHANICAL DEMOLITION PLAN

MD107 43 OF 91 LEVEL 4 MECHANICAL DEMOLITION PLAN

MD108 44 OF 91 LEVEL 5 MECHANICAL DEMOLITION PLAN

MD109 45 OF 91 LEVEL 6 MECHANICAL DEMOLITION PLAN

MD111 46 OF 91 LEVEL 8 MECHANICAL DEMOLITION PLAN

MD112 47 OF 91 LEVEL 9 MECHANICAL DEMOLITION PLAN

MD113 48 OF 91 LEVEL 10 MECHANICAL DEMOLITION PLAN

MD114 49 OF 91 LEVEL 11 MECHANICAL DEMOLITION PLAN

M-103 50 OF 91 BASEMENT LEVEL 1 MECHANICAL FLOOR PLAN

M-104 51 OF 91 LEVEL 1 MECHANICAL FLOOR PLAN

M-105 52 OF 91 LEVEL 2 MECHANICAL FLOOR PLAN

M-106 53 OF 91 LEVEL 3 MECHANICAL FLOOR PLAN

M-107 54 OF 91 LEVEL 4 MECHANICAL FLOOR PLAN

M-108 55 OF 91 LEVEL 5 MECHANICAL FLOOR PLAN

M-109 56 OF 91 LEVEL 6 MECHANICAL FLOOR PLAN

M-111 57 OF 91 LEVEL 8 MECHANICAL FLOOR PLAN

M-112 58 OF 91 LEVEL 9 MECHANICAL FLOOR PLAN

M-113 59 OF 91 LEVEL 10 MECHANICAL FLOOR PLAN

M-114 60 OF 91 LEVEL 11 MECHANICAL FLOOR PLAN

M-601 61 OF 91 MECHANICAL SCHEDULES AND DETAILS

E-001 62 OF 91 ELECTRICAL LEGEND & NOTES

ED103 63 OF 91 BASEMENT LEVEL 1 ELECTRICAL DEMOLITION PLAN

ED104 64 OF 91 LEVEL 1 ELECTRICAL DEMOLITION PLAN

SHEET NO. DRAWING NO. TITLE

ED106 65 OF 91 LEVEL 3 ELECTRICAL DEMOLITION PLAN

ED107 66 OF 91 LEVEL 4 ELECTRICAL DEMOLITION PLAN

ED108 67 OF 91 LEVEL 5 ELECTRICAL DEMOLITION PLAN

ED109 68 OF 91 LEVEL 6 ELECTRICAL DEMOLITION PLAN

ED111 69 OF 91 LEVEL 8 ELECTRICAL DEMOLITION PLAN

ED112 70 OF 91 LEVEL 9 ELECTRICAL DEMOLITION PLAN

ED113 71 OF 91 LEVEL 10 ELECTRICAL DEMOLITION PLAN

ED114 72 OF 91 LEVEL 11 ELECTRICAL DEMOLITION PLAN

ED115 73 OF 91 LEVEL 12 ELECTRICAL DEMOLITION PLAN

ED205 74 OF 91 LEVEL 2 LIGHTING DEMO PLAN

ED206 75 OF 91 LEVEL 3 LIGHTING DEMO PLAN

E-103 76 OF 91 BASEMENT LEVEL 1 ELECTRICAL FLOOR PLAN

E-104 77 OF 91 LEVEL 1 ELECTRICAL FLOOR PLAN

E-106 78 OF 91 LEVEL 3 ELECTRICAL FLOOR PLAN

E-107 79 OF 91 LEVEL 4 ELECTRICAL FLOOR PLAN

E-108 80 OF 91 LEVEL 5 ELECTRICAL FLOOR PLAN

E-109 81 OF 91 LEVEL 6 ELECTRICAL FLOOR PLAN

E-111 82 OF 91 LEVEL 8 ELECTRICAL FLOOR PLAN

E-112 83 OF 91 LEVEL 9 ELECTRICAL FLOOR PLAN

E-113 84 OF 91 LEVEL 10 ELECTRICAL FLOOR PLAN

E-114 85 OF 91 LEVEL 11 ELECTRICAL FLOOR PLAN

E-115 86 OF 91 LEVEL 12 ELECTRICAL FLOOR PLAN

E-205 87 OF 91 LEVEL 2 LIGHTING PLAN

E-206 88 OF 91 LEVEL 3 LIGHTING PLAN

E-500 89 OF 91 TRANSFER SWITCH TYPICAL CONTROLS DIAGRAM

E-600 90 OF 91 ELECTRICAL SCHEDULES

E-601 91 OF 91 ELECTRICAL SCHEDULES

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

c P.A.

FIRMTHE

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

USDA AGRICULTURAL RESEARCH SERVICE

CHILDREN'S NUTRITION RESEARCH CENTER

CRITICAL UPGRADES

HOUSTON, TX

TITLE SHEET AND INDEX

T-001 1 911/04/24

SME

BSN

DRL

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

2923-E

B. DEAN

XXX

D. CORDRAY

W. ROSS

PLAN

NORTH

CHILDREN'S NUTRITIONAL RESEARCH CENTER (CNRC),

1100 BATES AVE, HOUSTON, TX 77030

SOUTH STAIR

FOUNDATION

DRAINAGE

EQUIPMENT

ROOM

B3024

ELEV #3

SERVICE

ELEV

MECHANICAL

B3022

CORRIDOR

OPEN

OFFICESTORAGE

B3016

CONTROL

B3012

OPEN OFFICE AREA

B3014 ENTRY LOBBY

ENTRY

ELEV VEST

ELEV #1

ELEV #2

OPEN

OFFICE

SHUTTLE

ELEV

MACHINE

ROOM

B3000

PUMP

ROOM

B3002

CORRIDOR

TOILET

B3004

LUNCHROOM

B3010

CORRIDOR

B3017

HVAC & SEWAGE

EJECTION RM

B3010B

WBC A

B3008

WBC B

B3006

C

LO

SE

T

STAIR

VESTIBULE

WBC HVAC

B3018

TUNNEL TO

TCH

WEST

STAIR

BASEMENT LEVEL 3 - REFLECTED CEILING PLAN

SCALE: 1/8"=1'-0"

A1301

PLAN

NORTH

INSULATION NOTES LEGEND

LINE OF EXTERIOR

WALL ABOVE

EXISTING CONCRETE

FLOOR / ROOF DECK

EXISTING PATIO,

DECK, OR ROOF EXISTING EXTERIOR CLADDING

EXISTING CMU

EXISTING CONCRETE BEAM

EXISTING CMU

LINE OF EXISTING

METAL STUDS

EXISTING FIBERGLASS

INSULATION

EXISTING ACOUSTICAL CEILING

EXISTING DRYWALL

NEW 4" FOAM INSULATION

PER "INSULATION NOTES"

DEMOLITION WORK

A. CONTRACTOR SHALL REMOVE ALL EXISTING SPRAY

INSULATION ON CONCRETE DECK.

B. CONTRACTOR SHALL CLEAN DECK THOROUGHLY AS

REQUIRED BY NEW SPRAY FOAM INSTRUCTIONS WHERE

SHOWN ON THE PLANS PER THE LEGEND AND DETAILS.

C. CONTRACTOR SHALL REMOVE ALL EXISTING FIBERGLASS

INSULATION FROM CEILING LEVEL UP TO DECK ON ALL

EXTERIOR WALLS WHERE SHOWN ON THE PLANS PER THE

LEGEND.

D. CONTRACTOR SHALL PROVIDE PROTECTIVE WORK AREAS

TO KEEP DEMOLITION DEBRIS FROM GETTING INTO THE

INTERIOR WORK ENVIRONMENT AND FROM GETTING INTO

RETURN AIR HVAC SYSTEM PER 02 41 00. CONTRACTOR

SHALL PROVIDE FILTERING AT RETURN AIR SYSTEM.

CONTRACTOR SHALL REMOVE ALL LOOSE INSULATION

DEBRIS DUE TO DEMOLITION FROM WORK AREAS AND

SPACES ABOVE CEILING.

E. CONTRACTOR SHALL BE RESPONSIBLE FOR MOVING

FURNITURE AS REQUIRED TO PERFORM THE DEMO WORK

WHICH INCLUDES BUT IS NOT LIMITED TO THE REMOVAL OF

EXISTING FINISHES (INCLUDING CEILING TILES).

REMOVE AND APPLY INSULATION ON CONCRETE DECK

PER "INSULATION NOTES"

REMOVE AND APPLY INSULATION ON EXTERIOR WALL

PER "INSULATION NOTES"

NEW APPLICATIONS

EXISTING

STUCCO / PLASTER

EXISTING CEILING FINISHES

EXISTING

GYP. BD.

EXISTING SACT

EXISTING

EXPOSED

NOTE: LIGHT FIXTURE LAYOUTS SHOWN IN

ARCHITECTURAL REFLECTED CEILING PLANS

ARE REPRESENTATIONAL OF EXISTING LIGHT

FIXTURE TYPES AND LAYOUTS.

NEW WORK

A. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL

INSULATION AS SPECIFIED ON UNDERSIDE OF FLOOR / ROOF

DECK AS DESCRIBED HEREIN AND WHERE SHOWN ON THE

PLANS PER THE LEGEND.

B. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL

INSULATION AS SPECIFIED ON EXTERIOR WALLS AS

DESCRIBED HEREIN WHERE SHOWN ON THE PLANS PER THE

LEGEND.

C. CONTRACTOR SHALL APPLY INTUMESCENT COATING AS

SPECIFIED OVER ALL OF THE NEW SPRAY-APPLIED

INSULATION.

D. CONTRACTOR SHALL BE RESPONSIBLE FOR RETURNING

ALL FURNITURE THAT WAS MOVED IN ORDER TO PERFORM

THE SCOPE OF WORK. ANY FINISHES DAMAGED DURING THE

WORK SHALL BE REPLACED LIKE IN-KIND.

INSULATION DETAIL NO WORK

THIS FLOOR

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

c P.A.

FIRMTHE

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

USDA AGRICULTURAL RESEARCH SERVICE

CHILDREN'S NUTRITION RESEARCH CENTER

CRITICAL UPGRADES

HOUSTON, TX

BASEMENT LEVEL 3 - RCP

A1301 2 911/04/24

SME

CLR

DRL

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

2923-E

B. DEAN

XXX

D. CORDRAY

W. ROSS

0 16'8'4' 24'

SCALE: 1/8"= 1'-0"

HT

XET

TA

FO ET

S

R

EG

IS

SA

TC

E

IT

RERE A

CD

JE

RR

Y G. MARTIN

1 3573

ELEV #3

SERVICE

ELEV

LL2-016

ELEV #1

ELEV #2

WEST STAIR

EAST PARKING

SLOPE UP SLOPE DOWN

SLOPE DOWN

WEST PARKING

LL2-014

TRANSFORMER ROOM

EXHAUST

STORAGE

B-2010TRANSFORMER

ROOM LL2-010

B-2008

SWITCH

ROOM

B-2006

LL2-008

ELECTRICAL

B-2000

FUSE ROOM

B-2002

FUSE ROOM

B-2004

STORAGE

B-2012

BASEMENT LEVEL 2 - REFLECTED CEILING PLAN

SCALE: 1/8"=1'-0"

A1302

PLAN

NORTH

INSULATION NOTES LEGEND

LINE OF EXTERIOR

WALL ABOVE

EXISTING CONCRETE

FLOOR / ROOF DECK

EXISTING PATIO,

DECK, OR ROOF EXISTING EXTERIOR CLADDING

EXISTING CMU

EXISTING CONCRETE BEAM

EXISTING CMU

LINE OF EXISTING

METAL STUDS

EXISTING FIBERGLASS

INSULATION

EXISTING ACOUSTICAL CEILING

EXISTING DRYWALL

NEW 4" FOAM INSULATION

PER "INSULATION NOTES"

DEMOLITION WORK

A. CONTRACTOR SHALL REMOVE ALL EXISTING SPRAY

INSULATION ON CONCRETE DECK.

B. CONTRACTOR SHALL CLEAN DECK THOROUGHLY AS

REQUIRED BY NEW SPRAY FOAM INSTRUCTIONS WHERE

SHOWN ON THE PLANS PER THE LEGEND AND DETAILS.

C. CONTRACTOR SHALL REMOVE ALL EXISTING FIBERGLASS

INSULATION FROM CEILING LEVEL UP TO DECK ON ALL

EXTERIOR WALLS WHERE SHOWN ON THE PLANS PER THE

LEGEND.

D. CONTRACTOR SHALL PROVIDE PROTECTIVE WORK AREAS

TO KEEP DEMOLITION DEBRIS FROM GETTING INTO THE

INTERIOR WORK ENVIRONMENT AND FROM GETTING INTO

RETURN AIR HVAC SYSTEM PER 02 41 00. CONTRACTOR

SHALL PROVIDE FILTERING AT RETURN AIR SYSTEM.

CONTRACTOR SHALL REMOVE ALL LOOSE INSULATION

DEBRIS DUE TO DEMOLITION FROM WORK AREAS AND

SPACES ABOVE CEILING.

E. CONTRACTOR SHALL BE RESPONSIBLE FOR MOVING

FURNITURE AS REQUIRED TO PERFORM THE DEMO WORK

WHICH INCLUDES BUT IS NOT LIMITED TO THE REMOVAL OF

EXISTING FINISHES (INCLUDING CEILING TILES).

REMOVE AND APPLY INSULATION ON CONCRETE DECK

PER "INSULATION NOTES"

REMOVE AND APPLY INSULATION ON EXTERIOR WALL

PER "INSULATION NOTES"

NEW APPLICATIONS

EXISTING

STUCCO / PLASTER

EXISTING CEILING FINISHES

EXISTING

GYP. BD.

EXISTING SACT

EXISTING

EXPOSED

NOTE: LIGHT FIXTURE LAYOUTS SHOWN IN

ARCHITECTURAL REFLECTED CEILING PLANS

ARE REPRESENTATIONAL OF EXISTING LIGHT

FIXTURE TYPES AND LAYOUTS.

NEW WORK

A. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL

INSULATION AS SPECIFIED ON UNDERSIDE OF FLOOR / ROOF

DECK AS DESCRIBED HEREIN AND WHERE SHOWN ON THE

PLANS PER THE LEGEND.

B. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL

INSULATION AS SPECIFIED ON EXTERIOR WALLS AS

DESCRIBED HEREIN WHERE SHOWN ON THE PLANS PER THE

LEGEND.

C. CONTRACTOR SHALL APPLY INTUMESCENT COATING AS

SPECIFIED OVER ALL OF THE NEW SPRAY-APPLIED

INSULATION.

D. CONTRACTOR SHALL BE RESPONSIBLE FOR RETURNING

ALL FURNITURE THAT WAS MOVED IN ORDER TO PERFORM

THE SCOPE OF WORK. ANY FINISHES DAMAGED DURING THE

WORK SHALL BE REPLACED LIKE IN-KIND.

INSULATION DETAIL NO WORK

THIS FLOOR

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

c P.A.

FIRMTHE

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

USDA AGRICULTURAL RESEARCH SERVICE

CHILDREN'S NUTRITION RESEARCH CENTER

CRITICAL UPGRADES

HOUSTON, TX

BASEMENT LEVEL 2 - RCP

A1302 3 911/04/24

SME

CLR

DRL

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

2923-E

B. DEAN

XXX

D. CORDRAY

W. ROSS

0 16'8'4' 24'

SCALE: 1/8"= 1'-0"

HT

XET

TA

FO ET

S

R

EG

IS

SA

TC

E

IT

RERE A

CD

JE

RR

ELEV #3

SERVICE

ELEV

ELEV #1

ELEV #2

WEST

STAIR

FAN

ROOM

FAN

ROOM

EAST RAMP

BICYCLE

PARKING

MACHINE SHOP

B-1002

STORAGE

B1004

EQUIPMENT

ROOM

B1010

SWITCHGEAR

B-1012

MECHANICAL

EQUIPMENT

B1006

ENGINEER'S

OFFICE

B-1008

CENTRAL STAIR

ELEV

LOBBY

RAMP UP TO L1

CONTROL BOOTH

WEST RAMP

MOTOR BIKE

PARKING

PUMP ROOM

B-1016

CENTRAL PLANT

B-1014

STORAGE

B-1000

BASEMENT LEVEL 1 - REFLECTED CEILING PLAN

SCALE: 1/8"=1'-0"

A1303

PLAN

NORTH

INSULATION NOTES LEGEND

LINE OF EXTERIOR

WALL ABOVE

EXISTING CONCRETE

FLOOR / ROOF DECK

EXISTING PATIO,

DECK, OR ROOF EXISTING EXTERIOR CLADDING

EXISTING CMU

EXISTING CONCRETE BEAM

EXISTING CMU

LINE OF EXISTING

METAL STUDS

EXISTING FIBERGLASS

INSULATION

EXISTING ACOUSTICAL CEILING

EXISTING DRYWALL

NEW 4" FOAM INSULATION

PER "INSULATION NOTES"

DEMOLITION WORK

A. CONTRACTOR SHALL REMOVE ALL EXISTING SPRAY

INSULATION ON CONCRETE DECK.

B. CONTRACTOR SHALL CLEAN DECK THOROUGHLY AS

REQUIRED BY NEW SPRAY FOAM INSTRUCTIONS WHERE

SHOWN ON THE PLANS PER THE LEGEND AND DETAILS.

C. CONTRACTOR SHALL REMOVE ALL EXISTING FIBERGLASS

INSULATION FROM CEILING LEVEL UP TO DECK ON ALL

EXTERIOR WALLS WHERE SHOWN ON THE PLANS PER THE

LEGEND.

D. CONTRACTOR SHALL PROVIDE PROTECTIVE WORK AREAS

TO KEEP DEMOLITION DEBRIS FROM GETTING INTO THE

INTERIOR WORK ENVIRONMENT AND FROM GETTING INTO

RETURN AIR HVAC SYSTEM PER 02 41 00. CONTRACTOR

SHALL PROVIDE FILTERING AT RETURN AIR SYSTEM.

CONTRACTOR SHALL REMOVE ALL LOOSE INSULATION

DEBRIS DUE TO DEMOLITION FROM WORK AREAS AND

SPACES ABOVE CEILING.

E. CONTRACTOR SHALL BE RESPONSIBLE FOR MOVING

FURNITURE AS REQUIRED TO PERFORM THE DEMO WORK

WHICH INCLUDES BUT IS NOT LIMITED TO THE REMOVAL OF

EXISTING FINISHES (INCLUDING CEILING TILES).

REMOVE AND APPLY INSULATION ON CONCRETE DECK

PER "INSULATION NOTES"

REMOVE AND APPLY INSULATION ON EXTERIOR WALL

PER "INSULATION NOTES"

NEW APPLICATIONS

EXISTING

STUCCO / PLASTER

EXISTING CEILING FINISHES

EXISTING

GYP. BD.

EXISTING SACT

EXISTING

EXPOSED

NOTE: LIGHT FIXTURE LAYOUTS SHOWN IN

ARCHITECTURAL REFLECTED CEILING PLANS

ARE REPRESENTATIONAL OF EXISTING LIGHT

FIXTURE TYPES AND LAYOUTS.

NEW WORK

A. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL

INSULATION AS SPECIFIED ON UNDERSIDE OF FLOOR / ROOF

DECK AS DESCRIBED HEREIN AND WHERE SHOWN ON THE

PLANS PER THE LEGEND.

B. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL

INSULATION AS SPECIFIED ON EXTERIOR WALLS AS

DESCRIBED HEREIN WHERE SHOWN ON THE PLANS PER THE

LEGEND.

C. CONTRACTOR SHALL APPLY INTUMESCENT COATING AS

SPECIFIED OVER ALL OF THE NEW SPRAY-APPLIED

INSULATION.

D. CONTRACTOR SHALL BE RESPONSIBLE FOR RETURNING

ALL FURNITURE THAT WAS MOVED IN ORDER TO PERFORM

THE SCOPE OF WORK. ANY FINISHES DAMAGED DURING THE

WORK SHALL BE REPLACED LIKE IN-KIND.

INSULATION DETAIL NO WORK

THIS FLOOR

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

c P.A.

FIRMTHE

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

USDA AGRICULTURAL RESEARCH SERVICE

CHILDREN'S NUTRITION RESEARCH CENTER

CRITICAL UPGRADES

HOUSTON, TX

BASEMENT LEVEL 1 - RCP

A1303 4 911/04/24

SME

CLR

DRL

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

2923-E

B. DEAN

XXX

D. CORDRAY

W. ROSS

0 16'8'4' 24'

SCALE: 1/8"= 1'-0"

HT

XET

TA

FO ET

S

R

EG

IS

SA

TC

E

IT

RERE A

CD

JE

RR

FARM ANIMAL SUITE

JAN

JAN/STOR

PIGS

ANIMAL/REC DRIVEWAY

DRIVEWAY

SOUTH

STAIR

OFFICE

LOADING DOCK

RECEIVING OFFICE

CLOSET

1HC22

BULK CHENICAL

GENERAL STORAGE

RODENTS

CENTRAL CORRIDOR

GEN PURP STOR

ANIMAL/REC DOCK

FREEZER

1095A

TOILET

SOUTH

HALL

SOUTH

HALL

CAGE WASH/DIRTY

CAGE WASH/CLEAN

STORAGE

MECH

1024A

WEST HALL

HOLDING

TREAT

CHOW

CENTRAL

HALL

STOR

SPECIAL STUDIES

BEDDING

INV RM

HOLDING

WEST

HALL

SCRUB

PANTRY

1022A

FLURO ROOM

TELE

ELECTRICAL

CENTRAL JAN SUPPLY

NORTH

CORRIDOR

SECURITY OFF

DRY FOOD STORAGE

MEN

SWITCH ROOM

ELEV LOBBY

FIRE COMD STN

STAIR #5 ONLY

TO LEV 2

SCIENTIST OFF

GEN STORAGE/

HOUSEKEEPING

ELEV

#3

ELEV LOBBY

SERVICE

AREA

STAIR #2

CENTRAL STAIR

LOUNGE

TOILET

INFO & SECURITY

STORAGE

1101A

LAB

1014ANIMAL HVAC EQUIP ROOM

STAIR #1

LOBBY EXHIBIT

PIGS

PIGS

PIGS

CLOSET

RODENTS

RODENTS

RODENTS

RODENTS

ANIMAL

HOLDING

COOLER

RODENTS

RODENTS

RODENTS

SOWS

SOWS

PIGS

PIGS

PIGS

STORAGE

JAN

1084HOLDING

HOLDING

NORTH

HALL

TOILET

NORTH

HALL

AF1

LAB

LAB

LAB

LAB

ELEV

#4

ELEV

#5

EAST

CORRIDOR

WOMEN

ELEV

#1

ELEV

#2

NORTH

STAIR

FLOOR LEVEL 1 - REFLECTED CEILING PLAN

SCALE: 1/8"=1'-0"

A1304

PLAN

NORTH

INSULATION NOTES LEGEND

LINE OF EXTERIOR

WALL ABOVE

EXISTING CONCRETE

FLOOR / ROOF DECK

EXISTING PATIO,

DECK, OR ROOF EXISTING EXTERIOR CLADDING

EXISTING CMU

EXISTING CONCRETE BEAM

EXISTING CMU

LINE OF EXISTING

METAL STUDS

EXISTING FIBERGLASS

INSULATION

EXISTING ACOUSTICAL CEILING

EXISTING DRYWALL

NEW 4" FOAM INSULATION

PER "INSULATION NOTES"

DEMOLITION WORK

A. CONTRACTOR SHALL REMOVE ALL EXISTING SPRAY

INSULATION ON CONCRETE DECK.

B. CONTRACTOR SHALL CLEAN DECK THOROUGHLY AS

REQUIRED BY NEW SPRAY FOAM INSTRUCTIONS WHERE

SHOWN ON THE PLANS PER THE LEGEND AND DETAILS.

C. CONTRACTOR SHALL REMOVE ALL EXISTING FIBERGLASS

INSULATION FROM CEILING LEVEL UP TO DECK ON ALL

EXTERIOR WALLS WHERE SHOWN ON THE PLANS PER THE

LEGEND.

D. CONTRACTOR SHALL PROVIDE PROTECTIVE WORK AREAS

TO KEEP DEMOLITION DEBRIS FROM GETTING INTO THE

INTERIOR WORK ENVIRONMENT AND FROM GETTING INTO

RETURN AIR HVAC SYSTEM PER 02 41 00. CONTRACTOR

SHALL PROVIDE FILTERING AT RETURN AIR SYSTEM.

CONTRACTOR SHALL REMOVE ALL LOOSE INSULATION

DEBRIS DUE TO DEMOLITION FROM WORK AREAS AND

SPACES ABOVE CEILING.

E. CONTRACTOR SHALL BE RESPONSIBLE FOR MOVING

FURNITURE AS REQUIRED TO PERFORM THE DEMO WORK

WHICH INCLUDES BUT IS NOT LIMITED TO THE REMOVAL OF

EXISTING FINISHES (INCLUDING CEILING TILES).

REMOVE AND APPLY INSULATION ON CONCRETE DECK

PER "INSULATION NOTES"

REMOVE AND APPLY INSULATION ON EXTERIOR WALL

PER "INSULATION NOTES"

NEW APPLICATIONS

EXISTING

STUCCO / PLASTER

EXISTING CEILING FINISHES

EXISTING

GYP. BD.

EXISTING SACT

EXISTING

EXPOSED

NOTE: LIGHT FIXTURE LAYOUTS SHOWN IN

ARCHITECTURAL REFLECTED CEILING PLANS

ARE REPRESENTATIONAL OF EXISTING LIGHT

FIXTURE TYPES AND LAYOUTS.

NEW WORK

A. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL

INSULATION AS SPECIFIED ON UNDERSIDE OF FLOOR / ROOF

DECK AS DESCRIBED HEREIN AND WHERE SHOWN ON THE

PLANS PER THE LEGEND.

B. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL

INSULATION AS SPECIFIED ON EXTERIOR WALLS AS

DESCRIBED HEREIN WHERE SHOWN ON THE PLANS PER THE

LEGEND.

C. CONTRACTOR SHALL APPLY INTUMESCENT COATING AS

SPECIFIED OVER ALL OF THE NEW SPRAY-APPLIED

INSULATION.

D. CONTRACTOR SHALL BE RESPONSIBLE FOR RETURNING

ALL FURNITURE THAT WAS MOVED IN ORDER TO PERFORM

THE SCOPE OF WORK. ANY FINISHES DAMAGED DURING THE

WORK SHALL BE REPLACED LIKE IN-KIND.

INSULATION DETAIL

PROVIDE SPRAY-APPLIED

INSULATION AT EXTERIOR

WALL ABOVE CEILING;

RE: INSULATION NOTES

PROVIDE SPRAY-APPLIED

INSULATION AT EXTERIOR

WALL ABOVE CEILING;

RE: INSULATION NOTES

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

c P.A.

FIRMTHE

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

USDA AGRICULTURAL RESEARCH SERVICE

CHILDREN'S NUTRITION RESEARCH CENTER

CRITICAL UPGRADES

HOUSTON, TX

FLOOR LEVEL 1 - RCP

A1304 5 911/04/24

SME

CLR

DRL

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

2923-E

B. DEAN

XXX

D. CORDRAY

W. ROSS

0 16'8'4' 24'

SCALE: 1/8"= 1'-0"

4'

SCALE: 1/2"=1'-0"

0 1' 2' 8'

HT

XET

TA

FO ET

S

R

EG

IS

SA

TC

E

IT

RERE A

CD

JE

RR

JAN.

STORAGE

OFFICE

OFFICE

OFFICE

EDITOR

ASST.

EDITOR

ASST.

EDITOR

ILLUSTRATOR

DARK

RM.

PHOTO

STUDIO

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

DIRECTOR

CNRC

EMPLOYEE LOUNGE

OPEN

OFFICE

REPRODUCTION

CENTER

WORD PROCESSING

CLOSET

2HC20

SOUTH

CORR.

OPERATOR/TECH.

OFFICE

OFFICE

OFFICE

SECRETARY

CLOSET

2HC21

OFFICE

STORAGE

2060AOFFICE

OFFICE

OFFICE

OFFICE

TERRACE

EAST

CORRIDOR

SERVER

ROOM

TELECOM. ROOM

SVC.

CORR

CENTRAL

CORRIDOR

JANITOR

ELECTRICAL

ADMINISTRATIVE LOBBY

RECP.

COFFEE

2027A

RECEPTION

CONFERENCE ROOM

TERRACE

OFFICE

OFFICE

OFFICE

ELEV #3

SERVICE ELEV

LOBBY 2075

TELE

LIBRARIAN

CLOSET

2HC19

STORAGE

MAIL ROOM

ELEV #5 ELEV #4

ELEV LOBBY

ELEV #6 ELEV #7

AUDITORIUM

LOBBY

VENDING

OFFICE

CLOSET

WOMEN

MEN

CONTROL ROOM

PROJECTION ROOM

KITCHEN

CONFERENCE ROOM

PUBLIC

TEL.

STOR.

STAIR A

PROJ.

BOOTH

AUDITORIUM 2000

(OPEN TO ABOVE)

CORRIDOR

LOBBY

ARCHIVES

CLOSET

2HC18

STAIR #3

COPY RM

WEST

CORRIDOR

LIBRARY

FLOOR LEVEL 2 - REFLECTED CEILING PLAN

SCALE: 1/8"=1'-0"

A1305

PLAN

NORTH

INSULATION NOTES LEGEND

LINE OF EXTERIOR

WALL ABOVE

EXISTING CONCRETE

FLOOR / ROOF DECK

EXISTING PATIO,

DECK, OR ROOF EXISTING EXTERIOR CLADDING

EXISTING CMU

EXISTING CONCRETE BEAM

EXISTING CMU

LINE OF EXISTING

METAL STUDS

EXISTING FIBERGLASS

INSULATION

EXISTING ACOUSTICAL CEILING

EXISTING DRYWALL

NEW 4" FOAM INSULATION

PER "INSULATION NOTES"

DEMOLITION WORK

A. CONTRACTOR SHALL REMOVE ALL EXISTING SPRAY

INSULATION ON CONCRETE DECK.

B. CONTRACTOR SHALL CLEAN DECK THOROUGHLY AS

REQUIRED BY NEW SPRAY FOAM INSTRUCTIONS WHERE

SHOWN ON THE PLANS PER THE LEGEND AND DETAILS.

C. CONTRACTOR SHALL REMOVE ALL EXISTING FIBERGLASS

INSULATION FROM CEILING LEVEL UP TO DECK ON ALL

EXTERIOR WALLS WHERE SHOWN ON THE PLANS PER THE

LEGEND.

D. CONTRACTOR SHALL PROVIDE PROTECTIVE WORK AREAS

TO KEEP DEMOLITION DEBRIS FROM GETTING INTO THE

INTERIOR WORK ENVIRONMENT AND FROM GETTING INTO

RETURN AIR HVAC SYSTEM PER 02 41 00. CONTRACTOR

SHALL PROVIDE FILTERING AT RETURN AIR SYSTEM.

CONTRACTOR SHALL REMOVE ALL LOOSE INSULATION

DEBRIS DUE TO DEMOLITION FROM WORK AREAS AND

SPACES ABOVE CEILING.

E. CONTRACTOR SHALL BE RESPONSIBLE FOR MOVING

FURNITURE AS REQUIRED TO PERFORM THE DEMO WORK

WHICH INCLUDES BUT IS NOT LIMITED TO THE REMOVAL OF

EXISTING FINISHES (INCLUDING CEILING TILES).

REMOVE AND APPLY INSULATION ON CONCRETE DECK

PER "INSULATION NOTES"

REMOVE AND APPLY INSULATION ON EXTERIOR WALL

PER "INSULATION NOTES"

NEW APPLICATIONS

EXISTING

STUCCO / PLASTER

EXISTING CEILING FINISHES

EXISTING

GYP. BD.

EXISTING SACT

EXISTING

EXPOSED

NOTE: LIGHT FIXTURE LAYOUTS SHOWN IN

ARCHITECTURAL REFLECTED CEILING PLANS

ARE REPRESENTATIONAL OF EXISTING LIGHT

FIXTURE TYPES AND LAYOUTS.

NEW WORK

A. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL

INSULATION AS SPECIFIED ON UNDERSIDE OF FLOOR / ROOF

DECK AS DESCRIBED HEREIN AND WHERE SHOWN ON THE

PLANS PER THE LEGEND.

B. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL

INSULATION AS SPECIFIED ON EXTERIOR WALLS AS

DESCRIBED HEREIN WHERE SHOWN ON THE PLANS PER THE

LEGEND.

C. CONTRACTOR SHALL APPLY INTUMESCENT COATING AS

SPECIFIED OVER ALL OF THE NEW SPRAY-APPLIED

INSULATION.

D. CONTRACTOR SHALL BE RESPONSIBLE FOR RETURNING

ALL FURNITURE THAT WAS MOVED IN ORDER TO PERFORM

THE SCOPE OF WORK. ANY FINISHES DAMAGED DURING THE

WORK SHALL BE REPLACED LIKE IN-KIND.

INSULATION DETAIL

PROVIDE SPRAY-APPLIED

INSULATION AT EXTERIOR

WALL ABOVE CEILING;

RE: INSULATION NOTES

PROVIDE SPRAY-APPLIED

INSULATION AT EXTERIOR

WALL ABOVE CEILING;

RE: INSULATION NOTES

PROVIDE SPRAY-APPLIED

INSULATION AT EXTERIOR

WALL ABOVE CEILING;

RE: INSULATION NOTES

PROVIDE SPRAY-APPLIED

INSULATION AT EXTERIOR

WALL ABOVE CEILING;

RE: INSULATION NOTES

PROVIDE SPRAY-APPLIED

INSULATION AT EXTERIOR

WALL ABOVE CEILING;

RE: INSULATION NOTES

PROVIDE SPRAY-APPLIED

INSULATION AT EXTERIOR

WALL ABOVE CEILING;

RE: INSULATION NOTES

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

c P.A.

FIRMTHE

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

USDA AGRICULTURAL RESEARCH SERVICE

CHILDREN'S NUTRITION RESEARCH CENTER

CRITICAL UPGRADES

HOUSTON, TX

FLOOR LEVEL 2 - RCP

A1305 6 911/04/24

SME

CLR

DRL

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

2923-E

B. DEAN

XXX

D. CORDRAY

W. ROSS

0 16'8'4' 24'

SCALE: 1/8"= 1'-0"

4'

SCALE: 1/2"=1'-0"

0 1' 2' 8'

HT

XET

TA

FO ET

S

R

EG

IS

SA

TC

E

IT

RERE A

CD

JE

RR

CLOS.

CLOS.

BATHRM.BATHRM.

CLOS. CLOS.

BATHRM.BATHRM.

DWELLING UNITDWELLING UNIT

KIT EMPLOYEE LOUNGE

PROCEDURES

CENTRAL CORRIDOR

CORRIDOR

TELE.

CLOS.CLOS.

DWELLING UNITDWELLING UNITDWELLING UNITDWELLING UNIT

WEST CORRIDOR

CLOS.

ATTENDANT

STATION

TOILETTOILET

BATHRM.BATHRM.

BATHRM. BATHRM.BATHRM.

STAIR #9

STAIR #2

CALOR. #2

EAST CORRIDOR

3050C

3050J

3050H

3028 3030302630243022

3050B3050A

CALIBRATION LAB

STAIR#6

LEV 3&4 ONLY

TERRACE

WEIGHING

MEN

DWELLING SUITE

BEDROOM

STAIR #3

BATHRM.

DWELLING SUITE

CLOS.

CLOS.

BATHRM.

DWELLING UNIT

CORR.

CLOS.

JAN.

STAIR

VESTIBULE

WAITING &

ADULT DAY RM.

METABOLIC STORAGE

CLOS.

CLOS.

BATHRM.

DWELLING UNIT

DWELLING UNIT

DWELLING UNIT

CLOS.

CLOS.

CALORIMETER SUITE

CALOR. #3

3050E

CALOR. #4

3050D

CALOR. #4

3050F

CALOR. #1

3050G

PHYSICAL

EXERCISE LAB

CLINICAL

ANALYSIS

PHARMACY LAB

ELECTRICAL

LAUNDRY

TERRACE

DINING RM.

DISH RM.

3005B

BOTTLE WASH

3005A

WEIGHT STA.

JAN 3005

ELEV #6 ELEV #7

WOMEN

CART WASH

BREAK ROOM

MECHANICAL

STORAGE

FREEZER

3005J

COOLER

3005H

STAIR

VEST. 3062

STOR.

3005G

GENERAL

KITCHEN AREA

OFFICE

OFFICE

COMP.

3011A1

BAKERY

3005F

POT WASH

FREEZER

3005E

COOLER

3005D

W.S.

3005C

W.S. 4 W.S. 3 W.S. 2 W.S. 1

ELEVATOR

LOBBY

SERVICE

ELEV

ELEV #3ELEV #4ELEV #5

CORR.

KITCHEN

ELEV LOBBY

STAIR #1

AUDITORIUM

(OPEN TO BELOW)

FLOOR LEVEL 3 - REFLECTED CEILING PLAN

SCALE: 1/8"=1'-0"

A1306

PLAN

NORTH

INSULATION NOTES LEGEND INSULATION DETAIL

LINE OF EXTERIOR

WALL ABOVE

EXISTING CONCRETE

FLOOR / ROOF DECK

EXISTING PATIO,

DECK, OR ROOF EXISTING EXTERIOR CLADDING

EXISTING CMU

EXISTING CONCRETE BEAM

EXISTING CMU

LINE OF EXISTING

METAL STUDS

EXISTING FIBERGLASS

INSULATION

EXISTING ACOUSTICAL CEILING

EXISTING DRYWALL

NEW 4" FOAM INSULATION

PER "INSULATION NOTES"

DEMOLITION WORK

A. CONTRACTOR SHALL REMOVE ALL EXISTING SPRAY

INSULATION ON CONCRETE DECK.

B. CONTRACTOR SHALL CLEAN DECK THOROUGHLY AS

REQUIRED BY NEW SPRAY FOAM INSTRUCTIONS WHERE

SHOWN ON THE PLANS PER THE LEGEND AND DETAILS.

C. CONTRACTOR SHALL REMOVE ALL EXISTING FIBERGLASS

INSULATION FROM CEILING LEVEL UP TO DECK ON ALL

EXTERIOR WALLS WHERE SHOWN ON THE PLANS PER THE

LEGEND.

D. CONTRACTOR SHALL PROVIDE PROTECTIVE WORK AREAS

TO KEEP DEMOLITION DEBRIS FROM GETTING INTO THE

INTERIOR WORK ENVIRONMENT AND FROM GETTING INTO

RETURN AIR HVAC SYSTEM PER 02 41 00. CONTRACTOR

SHALL PROVIDE FILTERING AT RETURN AIR SYSTEM.

CONTRACTOR SHALL REMOVE ALL LOOSE INSULATION

DEBRIS DUE TO DEMOLITION FROM WORK AREAS AND

SPACES ABOVE CEILING.

E. CONTRACTOR SHALL BE RESPONSIBLE FOR MOVING

FURNITURE AS REQUIRED TO PERFORM THE DEMO WORK

WHICH INCLUDES BUT IS NOT LIMITED TO THE REMOVAL OF

EXISTING FINISHES (INCLUDING CEILING TILES).

REMOVE AND APPLY INSULATION ON CONCRETE DECK

PER "INSULATION NOTES"

REMOVE AND APPLY INSULATION ON EXTERIOR WALL

PER "INSULATION NOTES"

NEW APPLICATIONS

EXISTING

STUCCO / PLASTER

EXISTING CEILING FINISHES

EXISTING

GYP. BD.

EXISTING

SACT

EXISTING

EXPOSED

NOTE: LIGHT FIXTURE LAYOUTS SHOWN IN

ARCHITECTURAL REFLECTED CEILING PLANS

ARE REPRESENTATIONAL OF EXISTING LIGHT

FIXTURE TYPES AND LAYOUTS.

NEW WORK

A. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL

INSULATION AS SPECIFIED ON UNDERSIDE OF FLOOR / ROOF

DECK AS DESCRIBED HEREIN AND WHERE SHOWN ON THE

PLANS PER THE LEGEND.

B. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL

INSULATION AS SPECIFIED ON EXTERIOR WALLS AS

DESCRIBED HEREIN WHERE SHOWN ON THE PLANS PER THE

LEGEND.

C. CONTRACTOR SHALL APPLY INTUMESCENT COATING AS

SPECIFIED OVER ALL OF THE NEW SPRAY-APPLIED

INSULATION.

D. CONTRACTOR SHALL BE RESPONSIBLE FOR RETURNING

ALL FURNITURE THAT WAS MOVED IN ORDER TO PERFORM

THE SCOPE OF WORK. ANY FINISHES DAMAGED DURING THE

WORK SHALL BE REPLACED LIKE IN-KIND.

REMOVE EXISTING AND INSTALL NEW DRYWALL

CEILING. SEE DRYWALL CEILINGS REPAIR DETAILS

PROVIDE SPRAY-APPLIED

INSULATION AT EXTERIOR

WALL ABOVE CEILING;

RE: INSULATION NOTES

PROVIDE SPRAY-APPLIED

INSULATION AT EXTERIOR

WALL ABOVE CEILING;

RE: INSULATION NOTES

DRYWALL CEILINGS REPAIR DETAILS

SCALE: 6"=1'-0"

A1306

FRAMED CEILING DETAIL

EXISTING HANGER WIRES TO REMAIN

EXISTING FRAMING MEMBERS TO REMAIN;

CONTRACTOR TO REMOVE AND RE-INSTALL

THESE FRAMING MEMBERS AS NECESSARY TO

PERFORM SCOPE OF WORK ABOVE CEILING

DEMOLISH ALL EXISTING DRYWALL CEILING

BOARD ALONG WITH CEILING-MOUNTED

LIGHTS, DIFFUSERS, ALARM, DEVICES, ETC.;

INSTALL NEW 1/2" DRYWALL CEILING BOARD

WITH LEVEL 4 FINISH AFTER ALL REQUIRED

WORK ABOVE CEILING IS COMPLETED.

RE-INSTALL ALL DIFFUSERS, ALARM, DEVICES,

ETC. IN-KIND. INSTALL NEW LIGHTS PER

ELECTRICAL REQUIREMENTS

SUSPENDED CEILING DETAIL

EXISTING FRAMING MEMBERS TO

REMAIN; CONTRACTOR TO

REMOVE AND RE-INSTALL THESE

FRAMING MEMBERS AS

NECESSARY TO PERFORM SCOPE

OF WORK ABOVE CEILING

PROVIDE SPRAY-APPLIED

INSULATION AT EXTERIOR

WALL ABOVE CEILING;

RE: INSULATION NOTES

PROVIDE SPRAY-APPLIED

INSULATION AT EXTERIOR

WALL ABOVE CEILING;

RE: INSULATION NOTES

PROVIDE SPRAY-APPLIED

INSULATION AT EXTERIOR

WALL ABOVE CEILING;

RE: INSULATION NOTES

DEMOLISH ALL EXISTING PLASTER CEILING

ALONG WITH CEILING-MOUNTED LIGHTS,

DIFFUSERS, ALARM, DEVICES, ETC.; INSTALL

NEW ACOUSTICAL PLASTER CEILING AS

SPECIFIED WITH LEVEL 4 FINISH AFTER ALL

REQUIRED WORK ABOVE CEILING IS

COMPLETED. RE-INSTALL ALL DIFFUSERS,

ALARM, DEVICES, ETC. IN-KIND. INSTALL NEW

LIGHTS PER ELECTRICAL REQUIREMENTS

SCALE: 6"=1'-0"

1 1/2" 3" 6"

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

c P.A.

FIRMTHE

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

USDA AGRICULTURAL RESEARCH SERVICE

CHILDREN'S NUTRITION RESEARCH CENTER

CRITICAL UPGRADES

HOUSTON, TX

FLOOR LEVEL 3 - RCP

A1306 7 911/04/24

SME

CLR

DRL

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

2923-E

B. DEAN

XXX

D. CORDRAY

W. ROSS

0 16'8'4' 24'

SCALE: 1/8"= 1'-0"

4'

SCALE: 1/2"=1'-0"

0 1' 2' 8'

HT

XET

TA

FO ET

S

R

EG

IS

SA

TC

E

IT

RERE A

CD

JE

RR

ELECT.

SOUTH

TERRACE

MECHANICAL

ROOM

STAIR VEST.

TERRACE

CORRIDOR

DAY ROOM

DAY ROOM

TOILETSTOR.

OFFICE

4004A

OFFICE

4004B

ADOLESCENT

EXERCISE &

ENTERTAINMENT

OFFICE

4004D

ATTENDANT

STATION

CENTRAL

CORRIDOR

SERVICE

ELEV.

TELE.

SHOWER

SUPPORT

PROCED

ELEV #3

EAST

CORRIDOR

TLT

CHANGE

WAITING

MEN

WOMEN

CHANGE

OFFICE

OFFICE

EAST

TERRACE

ACOUSTICS

4HC17

TOBEC

EXAM

ELEV #4ELEV #5

EXAM

ELEV #7ELEV #6

EMERGENCY

GENERATOR

MECHANICAL

ROOM

CORRIDOR

NORTHEAST

TERRACE

STAIR VEST.

NORTH

TERRACE

WEST

TERRACE

SOUTH STAIR

NORTH

STAIR

STAIR#6

LEV 3&4 ONLYCENTRAL STAIR

FLOOR LEVEL 4 - REFLECTED CEILING PLAN

SCALE: 1/8"=1'-0"

A1307

PLAN

NORTH

AWINDOW TYPE

CURTAIN WALL ELEVATION

SCALE: 1/4"=1'-0"

A1307

FLOOR LEVEL 4

ELEV. 94.00'

±49'-8" (EXISTING - VERIFY)

±1 3'-

0" (E

XI

ST

IN

G

- V

ER

IF

Y)

4'- 0"

5'- 6"

3'- 6"

21 2" 3'-

1" 21 2"

21 2" 3'-

7" 21 2"

24'-41 2" 3'-0"

DOOR

22'-31

2"

9'- 0"

2" 3'-111

4" 21 2" 4'-61

4" 21 2" 4'-61

4" 21 2" 4'-61

4" 21 2" 4'-61

2" 21 2" 1'-11

2" 21 2" 1'-6" 21

2" 4'-11" 21 2" 4'-101

4" 21 2" 4'-101

4" 21 2" 4'-11"

2"

ALIGN TOP OF MULLION

IN-KIND WITH LINE OF

GRANITE TRIM (TYP)

ALIGN TOP OF MULLION

IN-KIND WITH CENTERLINE

OF GRANITE JOINT (TYP)

ALIGN CENTERLINE OF MULLION IN-KIND WITH CENTERLINE

OF VERTICAL GRANITE JOINT WHERE SHOWN (TYP)

GRANITE JOINT 'GJ' (TYP)

'GJ' 'GJ' 'GJ' 'GJ' 'GJ' 'GJ' 'GJ' 'GJ'

EXISTING PATIO / FLOOR / ROOF SLAB (TYP)

PREFINISHED METAL SUBSILL FLASHING;

REPLACE EXISTING AND EXTEND NEW

BELOW TILE LIKE EXISTING FLASHING; SET

IN CONT. BED OF SEALANT (TYP)

CURTAIN WALL SYSTEM

AS SPECIFIED

PROTECT EXISTING WATERPROOF

MEMBRANE DURING CONSTRUCTION (TYP)

BACKER ROD AND

SEALANT (TYP) BACKER ROD AND SEALANT;

DO NOT BLOCK CURTAIN

WALL WEEP DRAIN (TYP)

EXISTING CONCRETE

PAVERS; REMOVE AND

REINSTALL ONLY AS REQ'D

TO INSTALL NEW SUBSILL

FLASHING (TYP)

GLAZING; RE: SECTION 08 81 00

CURTAIN WALL SILL DETAIL

SCALE: 3"=1'-0"

TYPICAL

CURTAIN WALL JAMB DETAIL

SCALE: 3"=1'-0"

TYPICALA1307 A1307

BACKER ROD AND

SEALANT (TYP)

EXISTING GRANITE

PANEL (TYP)

EXISTING JAMB FLASHING

TO REMAIN (TYP)

EXISTING SHEATHING (TYP)

EDGE OF EXISTING INTERIOR

WALL CONSTRUCTION (TYP)

BACKER ROD AND

SEALANT (TYP)

CURTAIN WALL SYSTEM

AS SPECIFIED

GLAZING AS SPECIFIED

CURTAIN WALL HEAD DETAIL

SCALE: 3"=1'-0"

TYPICALA1307

GLAZING AS SPECIFIED

CURTAIN WALL SYSTEM

AS SPECIFIED

PREFINISHED METAL HEAD FLASHING

AS SPECIFIED (TYP)

BACKER ROD AND SEALANT (TYP)

EXISTING GRANITE PANEL (TYP)

EXISTING SHEATHING (TYP)

EXISTING CONT. STEEL ANGLE

FOR ATTACHMENT OF CURTAIN

WALL SYSTEM; SCRAPE CLEAN,

PRIME, AND PAINT (TYP)

EXISTING STEEL ANGLE

BRACING (TYP)

NEW 4" FOAM INSULATION

PER "INSULATION NOTES"

REPLACE EXISTING 2'-8" WIDE DOOR WITH

NEW 36" WIDE DOOR TO MEET EXIT EGRESS;

MODIFY CURTAIN WALL FRAME AS REQ'D TO

ACCOMMODATE NEW DOOR WIDTH (TYP)

GLAZING AS SPECIFIED

A1307

BID OPTION 003 : REPLACE EXISTING CURTAIN

WALL SYSTEM LIKE IN-KIND AS SPECIFIED

±4 9'-

8" (E

XI

ST

IN

G

- V

ER

IF

Y)

SHIM AS REQ'D

SHIM AS REQ'D

BACKER ROD AND

SEALANT (TYP)

SHIM AS REQ'D

EXISTING STEEL LINTEL (TYP)

CONTRACTOR SHALL TO FIELD VERIFY ALL DIMENSIONS AND DEPTHS OF EXISTING CURTAIN

WALL FRAMING AND GLAZING. CONTRACTOR SHALL CONSULT CONTRACTING OFFICER

IMMEDIATELY IF DISCREPANCIES ARE FOUND BETWEEN WHAT IS SHOWN IN THE DRAWINGS

AND SITE CONDITIONS, PRIOR TO SUBMITTAL OF SHOP DRAWINGS.

PROVIDE SPRAY-APPLIED

INSULATION AT EXTERIOR

WALL ABOVE CEILING;

RE: INSULATION NOTES

INSULATION NOTES

DEMOLITION WORK

A. CONTRACTOR SHALL REMOVE ALL EXISTING SPRAY

INSULATION ON CONCRETE DECK.

B. CONTRACTOR SHALL CLEAN DECK THOROUGHLY AS

REQUIRED BY NEW SPRAY FOAM INSTRUCTIONS WHERE

SHOWN ON THE PLANS PER THE LEGEND AND DETAILS.

C. CONTRACTOR SHALL REMOVE ALL EXISTING FIBERGLASS

INSULATION FROM CEILING LEVEL UP TO DECK ON ALL

EXTERIOR WALLS WHERE SHOWN ON THE PLANS PER THE

LEGEND.

D. CONTRACTOR SHALL PROVIDE PROTECTIVE WORK AREAS

TO KEEP DEMOLITION DEBRIS FROM GETTING INTO THE

INTERIOR WORK ENVIRONMENT AND FROM GETTING INTO

RETURN AIR HVAC SYSTEM PER 02 41 00. CONTRACTOR

SHALL PROVIDE FILTERING AT RETURN AIR SYSTEM.

CONTRACTOR SHALL REMOVE ALL LOOSE INSULATION

DEBRIS DUE TO DEMOLITION FROM WORK AREAS AND

SPACES ABOVE CEILING.

E. CONTRACTOR SHALL BE RESPONSIBLE FOR MOVING

FURNITURE AS REQUIRED TO PERFORM THE DEMO WORK

WHICH INCLUDES BUT IS NOT LIMITED TO THE REMOVAL OF

EXISTING FINISHES (INCLUDING CEILING TILES).

NEW WORK

A. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL

INSULATION AS SPECIFIED ON UNDERSIDE OF FLOOR / ROOF

DECK AS DESCRIBED HEREIN AND WHERE SHOWN ON THE

PLANS PER THE LEGEND.

B. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL

INSULATION AS SPECIFIED ON EXTERIOR WALLS AS

DESCRIBED HEREIN WHERE SHOWN ON THE PLANS PER THE

LEGEND.

C. CONTRACTOR SHALL APPLY INTUMESCENT COATING AS

SPECIFIED OVER ALL OF THE NEW SPRAY-APPLIED

INSULATION.

D. CONTRACTOR SHALL BE RESPONSIBLE FOR RETURNING

ALL FURNITURE THAT WAS MOVED IN ORDER TO PERFORM

THE SCOPE OF WORK. ANY FINISHES DAMAGED DURING THE

WORK SHALL BE REPLACED LIKE IN-KIND.

(BID OPTION 003)

(BID OPTION 003)(BID OPTION 003)(BID OPTION 003)

SCALE: 3"=1'-0"

3"0 6" 1'

8'0 2' 4' 12'

SCALE: 1/4"= 1'-0"

0 16'8'4' 24'

SCALE: 1/8"= 1'-0"

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

c P.A.

FIRMTHE

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

USDA AGRICULTURAL RESEARCH SERVICE

CHILDREN'S NUTRITION RESEARCH CENTER

CRITICAL UPGRADES

HOUSTON, TX

FLOOR LEVEL 4 - RCP

A1307 8 911/04/24

SME

CLR

DRL

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

2923-E

B. DEAN

XXX

D. CORDRAY

W. ROSS

HT

XET

TA

FO ET

S

R

EG

IS

SA

TC

E

IT

RERE A

CD

JE

RR

JAN.

NORTH

CORRIDOR

CORRIDOR

EQUIP

OFFICE

5053OFFICE

OFFICE

OFFICE

LAB

EAST CORRIDOR

TELE.

DARK RM.

SO

U

TH

C

O R

R

ID

O R

GLASS

WASH

OFFICE

PROCESS LAB.

VEST.

COLD RM.

COLD RM.

ELECT.

MALE

FEMALE

WEST CORRIDOR

ELEV. #7ELEV. #6

ELEV.

LOBBY

ELEV. #4ELEV. #5 ELEV. #3

SERV.

ELEV.

STORAGE

OFFICE

OFFICE

SECRETARY

& FILES 5082

OFFICE

OFFICE

STOR.

5000A

OFFICE

CONFERENCE

COFFEE

TECHNICIAN LOUNGE

OFFICE

EQUIP. LAB.

CORR.

CLOSET

5HC16

CHEM. LAB.

EXCREMENT

PROCESS'G.

STAIR C

LAB

LAB

LAB

CHEM. LAB.

5004 CHEM. LAB.

CHEM. LAB.

CHEM. LAB.

CHEM. LAB.

STAIR B OFFICE

OFFICE

STAIR A

FLOOR LEVEL 5 - REFLECTED CEILING PLAN

SCALE: 1/8"=1'-0"

A1308

PLAN

NORTH

INSULATION NOTES LEGEND

LINE OF EXTERIOR

WALL ABOVE

EXISTING CONCRETE

FLOOR / ROOF DECK

EXISTING PATIO,

DECK, OR ROOF EXISTING EXTERIOR CLADDING

EXISTING CMU

EXISTING CONCRETE BEAM

EXISTING CMU

LINE OF EXISTING

METAL STUDS

EXISTING FIBERGLASS

INSULATION

EXISTING ACOUSTICAL CEILING

EXISTING DRYWALL

NEW 4" FOAM INSULATION

PER "INSULATION NOTES"

DEMOLITION WORK

A. CONTRACTOR SHALL REMOVE ALL EXISTING SPRAY

INSULATION ON CONCRETE DECK.

B. CONTRACTOR SHALL CLEAN DECK THOROUGHLY AS

REQUIRED BY NEW SPRAY FOAM INSTRUCTIONS WHERE

SHOWN ON THE PLANS PER THE LEGEND AND DETAILS.

C. CONTRACTOR SHALL REMOVE ALL EXISTING FIBERGLASS

INSULATION FROM CEILING LEVEL UP TO DECK ON ALL

EXTERIOR WALLS WHERE SHOWN ON THE PLANS PER THE

LEGEND.

D. CONTRACTOR SHALL PROVIDE PROTECTIVE WORK AREAS

TO KEEP DEMOLITION DEBRIS FROM GETTING INTO THE

INTERIOR WORK ENVIRONMENT AND FROM GETTING INTO

RETURN AIR HVAC SYSTEM PER 02 41 00. CONTRACTOR

SHALL PROVIDE FILTERING AT RETURN AIR SYSTEM.

CONTRACTOR SHALL REMOVE ALL LOOSE INSULATION

DEBRIS DUE TO DEMOLITION FROM WORK AREAS AND

SPACES ABOVE CEILING.

E. CONTRACTOR SHALL BE RESPONSIBLE FOR MOVING

FURNITURE AS REQUIRED TO PERFORM THE DEMO WORK

WHICH INCLUDES BUT IS NOT LIMITED TO THE REMOVAL OF

EXISTING FINISHES (INCLUDING CEILING TILES).

REMOVE AND APPLY INSULATION ON CONCRETE DECK

PER "INSULATION NOTES"

REMOVE AND APPLY INSULATION ON EXTERIOR WALL

PER "INSULATION NOTES"

NEW APPLICATIONS

EXISTING

STUCCO / PLASTER

EXISTING CEILING FINISHES

EXISTING

GYP. BD.

EXISTING SACT

EXISTING

EXPOSED

NOTE: LIGHT FIXTURE LAYOUTS SHOWN IN

ARCHITECTURAL REFLECTED CEILING PLANS

ARE REPRESENTATIONAL OF EXISTING LIGHT

FIXTURE TYPES AND LAYOUTS.

NEW WORK

A. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL

INSULATION AS SPECIFIED ON UNDERSIDE OF FLOOR / ROOF

DECK AS DESCRIBED HEREIN AND WHERE SHOWN ON THE

PLANS PER THE LEGEND.

B. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL

INSULATION AS SPECIFIED ON EXTERIOR WALLS AS

DESCRIBED HEREIN WHERE SHOWN ON THE PLANS PER THE

LEGEND.

C. CONTRACTOR SHALL APPLY INTUMESCENT COATING AS

SPECIFIED OVER ALL OF THE NEW SPRAY-APPLIED

INSULATION.

D. CONTRACTOR SHALL BE RESPONSIBLE FOR RETURNING

ALL FURNITURE THAT WAS MOVED IN ORDER TO PERFORM

THE SCOPE OF WORK. ANY FINISHES DAMAGED DURING THE

WORK SHALL BE REPLACED LIKE IN-KIND.

INSULATION DETAIL

PROVIDE SPRAY-APPLIED

INSULATION AT EXTERIOR

WALL ABOVE CEILING;

RE: INSULATION NOTES

PROVIDE SPRAY-APPLIED

INSULATION AT EXTERIOR

WALL ABOVE CEILING;

RE: INSULATION NOTES

PROVIDE SPRAY-APPLIED

INSULATION AT EXTERIOR

WALL ABOVE CEILING;

RE: INSULATION NOTES

PROVIDE SPRAY-APPLIED

INSULATION AT EXTERIOR

WALL ABOVE CEILING;

RE: INSULATION NOTES

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

c P.A.

FIRMTHE

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

USDA AGRICULTURAL RESEARCH SERVICE

CHILDREN'S NUTRITION RESEARCH CENTER

CRITICAL UPGRADES

HOUSTON, TX

FLOOR LEVEL 5 - RCP

A1308 9 911/04/24

SME

CLR

DRL

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

2923-E

B. DEAN

XXX

D. CORDRAY

W. ROSS

0 16'8'4' 24'

SCALE: 1/8"= 1'-0"

4'

SCALE: 1/2"=1'-0"

0 1' 2' 8'

HT

XET

TA

FO ET

S

R

EG

IS

SA

TC

E

IT

RERE A

CD

JE

RR

ELEV. #6 ELEV. #7

ELECT.

TELE.

SOUTH

COLD RM.

DARK RM.

CORRIDOR

OFFICE

OVEN RM.

LAB

BIO LAB

LAB

LAB

BIO LAB

BIO LAB

BIO LAB

BIO LAB

LAB STORAGE

OFFICE

OFFICE

EQUIP

60636065

LAB

LAB

OFFICE

LAB

SEC'Y &

FILES

CORRIDOR

CLOSET

6HC12

WEST CORRIDOR

CHEM. LAB.

LEUKOCYTE

BIOLOGY

OFFICE

OFFICE

GLASS

WASH

MALE

FEMALE

JAN.

STORAGE

ELEV. #3

SERV. ELEV.

ELEV. #4ELEV. #5

ELEV. LOBBY

NORTH

CORRIDOR

STOR.

6000ACONFERENCE

COFFEE

ANTE RM.

CORRIDOR

TECHNICIAN

LOUNGE

EQUIP. LAB.

EQUIP. LAB.

OFFICE

OFFICE

OFFICE

OFFICE

STAIR C

SOUTH STAIR

CENTRAL STAIR

NORTH STAIR

CHEM. LAB.

EAST CORRIDOR

CHEM. LAB.

CHEM. LAB.

CHEM.

LAB.

FLOOR LEVEL 6 - REFLECTED CEILING PLAN

SCALE: 1/8"=1'-0"

A1309

PLAN

NORTH

INSULATION NOTES LEGEND

LINE OF EXTERIOR

WALL ABOVE

EXISTING CONCRETE

FLOOR / ROOF DECK

EXISTING PATIO,

DECK, OR ROOF EXISTING EXTERIOR CLADDING

EXISTING CMU

EXISTING CONCRETE BEAM

EXISTING CMU

LINE OF EXISTING

METAL STUDS

EXISTING FIBERGLASS

INSULATION

EXISTING ACOUSTICAL CEILING

EXISTING DRYWALL

NEW 4" FOAM INSULATION

PER "INSULATION NOTES"

DEMOLITION WORK

A. CONTRACTOR SHALL REMOVE ALL EXISTING SPRAY

INSULATION ON CONCRETE DECK.

B. CONTRACTOR SHALL CLEAN DECK THOROUGHLY AS

REQUIRED BY NEW SPRAY FOAM INSTRUCTIONS WHERE

SHOWN ON THE PLANS PER THE LEGEND AND DETAILS.

C. CONTRACTOR SHALL REMOVE ALL EXISTING FIBERGLASS

INSULATION FROM CEILING LEVEL UP TO DECK ON ALL

EXTERIOR WALLS WHERE SHOWN ON THE PLANS PER THE

LEGEND.

D. CONTRACTOR SHALL PROVIDE PROTECTIVE WORK AREAS

TO KEEP DEMOLITION DEBRIS FROM GETTING INTO THE

INTERIOR WORK ENVIRONMENT AND FROM GETTING INTO

RETURN AIR HVAC SYSTEM PER 02 41 00. CONTRACTOR

SHALL PROVIDE FILTERING AT RETURN AIR SYSTEM.

CONTRACTOR SHALL REMOVE ALL LOOSE INSULATION

DEBRIS DUE TO DEMOLITION FROM WORK AREAS AND

SPACES ABOVE CEILING.

E. CONTRACTOR SHALL BE RESPONSIBLE FOR MOVING

FURNITURE AS REQUIRED TO PERFORM THE DEMO WORK

WHICH INCLUDES BUT IS NOT LIMITED TO THE REMOVAL OF

EXISTING FINISHES (INCLUDING CEILING TILES).

REMOVE AND APPLY INSULATION ON CONCRETE DECK

PER "INSULATION NOTES"

REMOVE AND APPLY INSULATION ON EXTERIOR WALL

PER "INSULATION NOTES"

NEW APPLICATIONS

EXISTING

STUCCO / PLASTER

EXISTING CEILING FINISHES

EXISTING

GYP. BD.

EXISTING SACT

EXISTING

EXPOSED

NOTE: LIGHT FIXTURE LAYOUTS SHOWN IN

ARCHITECTURAL REFLECTED CEILING PLANS

ARE REPRESENTATIONAL OF EXISTING LIGHT

FIXTURE TYPES AND LAYOUTS.

NEW WORK

A. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL

INSULATION AS SPECIFIED ON UNDERSIDE OF FLOOR / ROOF

DECK AS DESCRIBED HEREIN AND WHERE SHOWN ON THE

PLANS PER THE LEGEND.

B. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL

INSULATION AS SPECIFIED ON EXTERIOR WALLS AS

DESCRIBED HEREIN WHERE SHOWN ON THE PLANS PER THE

LEGEND.

C. CONTRACTOR SHALL APPLY INTUMESCENT COATING AS

SPECIFIED OVER ALL OF THE NEW SPRAY-APPLIED

INSULATION.

D. CONTRACTOR SHALL BE RESPONSIBLE FOR RETURNING

ALL FURNITURE THAT WAS MOVED IN ORDER TO PERFORM

THE SCOPE OF WORK. ANY FINISHES DAMAGED DURING THE

WORK SHALL BE REPLACED LIKE IN-KIND.

INSULATION DETAIL

PROVIDE SPRAY-APPLIED

INSULATION AT EXTERIOR

WALL ABOVE CEILING;

RE: INSULATION NOTES

PROVIDE SPRAY-APPLIED

INSULATION AT EXTERIOR

WALL ABOVE CEILING;

RE: INSULATION NOTES

PROVIDE SPRAY-APPLIED

INSULATION AT EXTERIOR

WALL ABOVE CEILING;

RE: INSULATION NOTES

PROVIDE SPRAY-APPLIED

INSULATION AT EXTERIOR

WALL ABOVE CEILING;

RE: INSULATION NOTES

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

c P.A.

FIRMTHE

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

USDA AGRICULTURAL RESEARCH SERVICE

CHILDREN'S NUTRITION RESEARCH CENTER

CRITICAL UPGRADES

HOUSTON, TX

FLOOR LEVEL 6 - RCP

A1309 10 911/04/24

SME

CLR

DRL

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

2923-E

B. DEAN

XXX

D. CORDRAY

W. ROSS

0 16'8'4' 24'

SCALE: 1/8"= 1'-0"

4'

SCALE: 1/2"=1'-0"

0 1' 2' 8'

HT

XET

TA

FO ET

S

R

EG

IS

SA

TC

E

IT

RERE A

CD

JE

RR

ELEV. #3ELEV. #4ELEV. #5

GAS

ISOTOPE

LAB.

COMBUST

DIGEST

SAMPLE

PURIFICATION RM.

STORAGE

SERV. ELEV.

SEC'Y. & FILES

OFFICE

CORR

CLOSET

7HC11

BIOCHEM. LAB.

CHEM.

LAB.

LAB. STOR.

OFFICE

OFFICE

GAS

ISOTOPE

LAB.

EQUIP

OFFICE

OFFICE

T.I.M.S.

ANTE

ASHING

FILAMENT

CLEAN RM.

SAMPLE ISOL.

DERIVATION GC LAB.

SOUTH

CORRIDOR

REF. STOR.

CLOSET

7HC10

PROTOCOL

KIT. STOR.

REF. STOR.

7019DISP. RET

ELECT.

7063TELE.

JAN.

MALE

FEMALE

WEST CORRIDOR

PROCEDURE

BIO-CHEM. LAB.

G.C.M.S. II

COMPUTER

STORAGE

TECHNICIAN

LOUNGE

COFFEE

EQUIP. LAB.

STORAGE

CONFERENCE

NORTH

CORRIDOR ELEV. LOBBY

STOR.

7000A

OFFICE

CLOSET

7HC9CLOSET

7HC8

OFFICE

OFFICE

PAPER STOR.

E. CORRIDOR

OFFICE

OFFICE

CORR

G.C.M.S. I

FLOOR LEVEL 7 - REFLECTED CEILING PLAN

SCALE: 1/8"=1'-0"

A1310

PLAN

NORTH

INSULATION NOTES LEGEND

LINE OF EXTERIOR

WALL ABOVE

EXISTING CONCRETE

FLOOR / ROOF DECK

EXISTING PATIO,

DECK, OR ROOF EXISTING EXTERIOR CLADDING

EXISTING CMU

EXISTING CONCRETE BEAM

EXISTING CMU

LINE OF EXISTING

METAL STUDS

EXISTING FIBERGLASS

INSULATION

EXISTING ACOUSTICAL CEILING

EXISTING DRYWALL

NEW 4" FOAM INSULATION

PER "INSULATION NOTES"

DEMOLITION WORK

A. CONTRACTOR SHALL REMOVE ALL EXISTING SPRAY

INSULATION ON CONCRETE DECK.

B. CONTRACTOR SHALL CLEAN DECK THOROUGHLY AS

REQUIRED BY NEW SPRAY FOAM INSTRUCTIONS WHERE

SHOWN ON THE PLANS PER THE LEGEND AND DETAILS.

C. CONTRACTOR SHALL REMOVE ALL EXISTING FIBERGLASS

INSULATION FROM CEILING LEVEL UP TO DECK ON ALL

EXTERIOR WALLS WHERE SHOWN ON THE PLANS PER THE

LEGEND.

D. CONTRACTOR SHALL PROVIDE PROTECTIVE WORK AREAS

TO KEEP DEMOLITION DEBRIS FROM GETTING INTO THE

INTERIOR WORK ENVIRONMENT AND FROM GETTING INTO

RETURN AIR HVAC SYSTEM PER 02 41 00. CONTRACTOR

SHALL PROVIDE FILTERING AT RETURN AIR SYSTEM.

CONTRACTOR SHALL REMOVE ALL LOOSE INSULATION

DEBRIS DUE TO DEMOLITION FROM WORK AREAS AND

SPACES ABOVE CEILING.

E. CONTRACTOR SHALL BE RESPONSIBLE FOR MOVING

FURNITURE AS REQUIRED TO PERFORM THE DEMO WORK

WHICH INCLUDES BUT IS NOT LIMITED TO THE REMOVAL OF

EXISTING FINISHES (INCLUDING CEILING TILES).

REMOVE AND APPLY INSULATION ON CONCRETE DECK

PER "INSULATION NOTES"

REMOVE AND APPLY INSULATION ON EXTERIOR WALL

PER "INSULATION NOTES"

NEW APPLICATIONS

EXISTING

STUCCO / PLASTER

EXISTING CEILING FINISHES

EXISTING

GYP. BD.

EXISTING SACT

EXISTING

EXPOSED

NOTE: LIGHT FIXTURE LAYOUTS SHOWN IN

ARCHITECTURAL REFLECTED CEILING PLANS

ARE REPRESENTATIONAL OF EXISTING LIGHT

FIXTURE TYPES AND LAYOUTS.

NEW WORK

A. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL

INSULATION AS SPECIFIED ON UNDERSIDE OF FLOOR / ROOF

DECK AS DESCRIBED HEREIN AND WHERE SHOWN ON THE

PLANS PER THE LEGEND.

B. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL

INSULATION AS SPECIFIED ON EXTERIOR WALLS AS

DESCRIBED HEREIN WHERE SHOWN ON THE PLANS PER THE

LEGEND.

C. CONTRACTOR SHALL APPLY INTUMESCENT COATING AS

SPECIFIED OVER ALL OF THE NEW SPRAY-APPLIED

INSULATION.

D. CONTRACTOR SHALL BE RESPONSIBLE FOR RETURNING

ALL FURNITURE THAT WAS MOVED IN ORDER TO PERFORM

THE SCOPE OF WORK. ANY FINISHES DAMAGED DURING THE

WORK SHALL BE REPLACED LIKE IN-KIND.

INSULATION DETAIL

PROVIDE SPRAY-APPLIED

INSULATION AT EXTERIOR

WALL ABOVE CEILING;

RE: INSULATION NOTES

PROVIDE SPRAY-APPLIED

INSULATION AT EXTERIOR

WALL ABOVE CEILING;

RE: INSULATION NOTES

PROVIDE SPRAY-APPLIED

INSULATION AT EXTERIOR

WALL ABOVE CEILING;

RE: INSULATION NOTES

PROVIDE SPRAY-APPLIED

INSULATION AT EXTERIOR

WALL ABOVE CEILING;

RE: INSULATION NOTES

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

c P.A.

FIRMTHE

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

USDA AGRICULTURAL RESEARCH SERVICE

CHILDREN'S NUTRITION RESEARCH CENTER

CRITICAL UPGRADES

HOUSTON, TX

FLOOR LEVEL 7 - RCP

A1310 11 911/04/24

SME

CLR

DRL

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

2923-E

B. DEAN

XXX

D. CORDRAY

W. ROSS

0 16'8'4' 24'

SCALE: 1/8"= 1'-0"

4'

SCALE: 1/2"=1'-0"

0 1' 2' 8'

HT

XET

TA

FO ET

S

R

EG

IS

SA

TC

E

IT

RERE A

CD

JE

RR

CHEM.

LAB.

CHEM. LAB.

EQUIP. LAB.

TECHNICIAN

LOUNGE

COFFEE

CHEM. LAB.

STOR.

CONFERENCE

STOR.

OFFICE

OFFICE

OFFICE

OFFICE

COMPUTER

CHEM. LAB. CHEM.LAB.

TELE.

SERV.

WOMEN

MEN

ELECT.

CHEM. LAB.CHEM. LAB.CHEM. LAB.

STORAGE

JAN.

CHEM. LAB. CHEM. LAB.

CHEM. LAB.

FREEZERS

SOUTH

STORAGE

DARK RM.

COLD RM.

GLASS

WASH

OFFICE

OFFICE

EQUIP.

LAB.

COLD RM.

LAB.

CHEM.

LAB.

OFFICEGRAD.

STUDENT

& FILES

SECRETARY

ELEV. 6 ELEV. 7 ELEV. 3

ELEV. 6

ELEV 7

EAST CORRIDOR

NORTH

CORRIDOR

CORRIDOR

WEST CORRIDOR

8010 8014

8006 80088004 8012

8000A

8064 8052 8056 80548060 8058

80518024

8017 8022

8074 8009

ELEVATOR LOBBY

CORR

ELEV.

CLOSET

8HC6

OFFICE

SPEC.

PROC. LAB.

CLOSET

8HC7

CORR

FLOOR LEVEL 8 - REFLECTED CEILING PLAN

SCALE: 1/8"=1'-0"

A1311

PLAN

NORTH

INSULATION NOTES LEGEND

LINE OF EXTERIOR

WALL ABOVE

EXISTING CONCRETE

FLOOR / ROOF DECK

EXISTING PATIO,

DECK, OR ROOF EXISTING EXTERIOR CLADDING

EXISTING CMU

EXISTING CONCRETE BEAM

EXISTING CMU

LINE OF EXISTING

METAL STUDS

EXISTING FIBERGLASS

INSULATION

EXISTING ACOUSTICAL CEILING

EXISTING DRYWALL

NEW 4" FOAM INSULATION

PER "INSULATION NOTES"

DEMOLITION WORK

A. CONTRACTOR SHALL REMOVE ALL EXISTING SPRAY

INSULATION ON CONCRETE DECK.

B. CONTRACTOR SHALL CLEAN DECK THOROUGHLY AS

REQUIRED BY NEW SPRAY FOAM INSTRUCTIONS WHERE

SHOWN ON THE PLANS PER THE LEGEND AND DETAILS.

C. CONTRACTOR SHALL REMOVE ALL EXISTING FIBERGLASS

INSULATION FROM CEILING LEVEL UP TO DECK ON ALL

EXTERIOR WALLS WHERE SHOWN ON THE PLANS PER THE

LEGEND.

D. CONTRACTOR SHALL PROVIDE PROTECTIVE WORK AREAS

TO KEEP DEMOLITION DEBRIS FROM GETTING INTO THE

INTERIOR WORK ENVIRONMENT AND FROM GETTING INTO

RETURN AIR HVAC SYSTEM PER 02 41 00. CONTRACTOR

SHALL PROVIDE FILTERING AT RETURN AIR SYSTEM.

CONTRACTOR SHALL REMOVE ALL LOOSE INSULATION

DEBRIS DUE TO DEMOLITION FROM WORK AREAS AND

SPACES ABOVE CEILING.

E. CONTRACTOR SHALL BE RESPONSIBLE FOR MOVING

FURNITURE AS REQUIRED TO PERFORM THE DEMO WORK

WHICH INCLUDES BUT IS NOT LIMITED TO THE REMOVAL OF

EXISTING FINISHES (INCLUDING CEILING TILES).

REMOVE AND APPLY INSULATION ON CONCRETE DECK

PER "INSULATION NOTES"

REMOVE AND APPLY INSULATION ON EXTERIOR WALL

PER "INSULATION NOTES"

NEW APPLICATIONS

EXISTING

STUCCO / PLASTER

EXISTING CEILING FINISHES

EXISTING

GYP. BD.

EXISTING SACT

EXISTING

EXPOSED

NOTE: LIGHT FIXTURE LAYOUTS SHOWN IN

ARCHITECTURAL REFLECTED CEILING PLANS

ARE REPRESENTATIONAL OF EXISTING LIGHT

FIXTURE TYPES AND LAYOUTS.

NEW WORK

A. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL

INSULATION AS SPECIFIED ON UNDERSIDE OF FLOOR / ROOF

DECK AS DESCRIBED HEREIN AND WHERE SHOWN ON THE

PLANS PER THE LEGEND.

B. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL

INSULATION AS SPECIFIED ON EXTERIOR WALLS AS

DESCRIBED HEREIN WHERE SHOWN ON THE PLANS PER THE

LEGEND.

C. CONTRACTOR SHALL APPLY INTUMESCENT COATING AS

SPECIFIED OVER ALL OF THE NEW SPRAY-APPLIED

INSULATION.

D. CONTRACTOR SHALL BE RESPONSIBLE FOR RETURNING

ALL FURNITURE THAT WAS MOVED IN ORDER TO PERFORM

THE SCOPE OF WORK. ANY FINISHES DAMAGED DURING THE

WORK SHALL BE REPLACED LIKE IN-KIND.

INSULATION DETAIL

PROVIDE SPRAY-APPLIED

INSULATION AT EXTERIOR

WALL ABOVE CEILING;

RE: INSULATION NOTES

PROVIDE SPRAY-APPLIED

INSULATION AT EXTERIOR

WALL ABOVE CEILING;

RE: INSULATION NOTES

PROVIDE SPRAY-APPLIED

INSULATION AT EXTERIOR

WALL ABOVE CEILING;

RE: INSULATION NOTES

PROVIDE SPRAY-APPLIED

INSULATION AT EXTERIOR

WALL ABOVE CEILING;

RE: INSULATION NOTES

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

c P.A.

FIRMTHE

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

A…