This solicitation is for a 100% total small business set-aside project titled "CNRC Critical Upgrades to Insulation, Piping & HVAC - Houston, TX". The project scope involves critical upgrades to insulation, piping, and HVAC systems. The applicable NAICS code is 236220 - Commercial and Institutional Building Construction, and the SBA size standard is $45.0M. Vendors are required to complete blocks 14, 15, 17, 19, and 20 A-C on the solicitation form. Contractors must be registered in active status in SAM.gov at the time of proposal submission according to FAR 52.204-7. The solicitation is issued by the Department of Agriculture Agricultural Research Service Field Research Implementation and Information Delivery Plains Area for a project with a value between $1,000,000 - $5,000,000.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
USDA
INDEX OF DRAWINGS
GENERAL NOTES:
1. BUILDING WILL REMAIN OCCUPIED AND OPERATION BY THE GOVERNMENT DURING THE
WORK. MEANS OF EGRESS SHALL BE MAINTAINED AT ALL TIMES.
2. STORM DRAIN REPLACEMENT AND INSULATION WORK MUST BE COMPLETED OUTSIDE OF
REGULAR HOURS. REFER TO SPECIFICATIONS FOR WORKING HOURS REQUIREMENTS.
3. STORM DRAIN WORK INDICATED ON PLUMBING DRAWINGS MUST BE COMPLETED PRIOR
TO INSULATION WORK BENEATH PATIOS.
4. COORDINATE CONSTRUCTION ACCESS AND STAGING AREA(S) WITH CONTRACTING
OFFICER PRIOR TO COMMENCING WORK.
U.S. DEPARTMENT OF AGRICULTURE
AGRICULTURAL RESEARCH SERVICE
CNRC CRITICAL UPGRADES
TASK ORDER: 12805B23F0146
CHILDREN'S NUTRITIONAL RESEARCH CENTER (CNRC)
HOUSTON, TEXAS
PROJECT LOCATION
LEGEND
ELEVATION CROSS REFERENCEX
XXXXX
ENLARGED PLAN/AREA OF WORK REFERENCEX
XXXXX
NORTH ARROW
VICINITY MAP (1" = 0.4 MILES)
SHEET NO. DRAWING NO. TITLE
T-001 1 OF 91 TITLE SHEET AND INDEX
A1301 2 OF 91 BASEMENT LEVEL 3 - RCP
A1302 3 OF 91 BASEMENT LEVEL 2 - RCP
A1303 4 OF 91 BASEMENT LEVEL 1 - RCP
A1304 5 OF 91 FLOOR LEVEL 1 - RCP
A1305 6 OF 91 FLOOR LEVEL 2 - RCP
A1306 7 OF 91 FLOOR LEVEL 3 - RCP
A1307 8 OF 91 FLOOR LEVEL 4 - RCP
A1308 9 OF 91 FLOOR LEVEL 5 - RCP
A1309 10 OF 91 FLOOR LEVEL 6 - RCP
A1310 11 OF 91 FLOOR LEVEL 7 - RCP
A1311 12 OF 91 FLOOR LEVEL 8 - RCP
A1312 13 OF 91 FLOOR LEVEL 9 - RCP
A1313 14 OF 91 FLOOR LEVEL 10 - RCP
A1314 15 OF 91 FLOOR LEVEL 11 - RCP
A1315 16 OF 91 FLOOR LEVEL 12 - RCP
P-001 17 OF 91 PLUMBING ABBREVIATIONS AND NOTES
PD101 18 OF 91 BASEMENT LEVEL 3 STORM DRAIN PIPING DEMO. PLAN
PD102 19 OF 91 BASEMENT LEVEL 2 STORM DRAIN PIPING DEMO. PLAN
PD103 20 OF 91 BASEMENT LEVEL 1 STORM DRAIN PIPING DEMO. PLAN
PD104 21 OF 91 LEVEL 1 STORM DRAIN PIPING DEMO. PLAN
PD105 22 OF 91 LEVEL 2 STORM DRAIN PIPING DEMO. PLAN
PD106 23 OF 91 LEVEL 3 STORM DRAIN PIPING DEMO. PLAN
PD107 24 OF 91 LEVEL 4 STORM DRAIN PIPING DEMO. PLAN
PD113 25 OF 91 LEVEL 10 STORM DRAIN PIPING DEMO. PLAN
PD114 26 OF 91 LEVEL 11 STORM DRAIN PIPING DEMO. PLAN
PD115 27 OF 91 LEVEL 12 STORM DRAIN PIPING DEMO. PLAN
P-101 28 OF 91 BASEMENT LEVEL 3 STORM DRAIN PIPING FLOOR PLAN
P-102 29 OF 91 BASEMENT LEVEL 2 STORM DRAIN PIPING FLOOR PLAN
P-103 30 OF 91 BASEMENT LEVEL 1 STORM DRAIN PIPING FLOOR PLAN
P-104 31 OF 91 LEVEL 1 STORM DRAIN PIPING FLOOR PLAN
P-105 32 OF 91 LEVEL 2 STORM DRAIN PIPING FLOOR PLAN
SHEET NO. DRAWING NO. TITLE
P-106 33 OF 91 LEVEL 3 STORM DRAIN PIPING FLOOR PLAN
P-107 34 OF 91 LEVEL 4 STORM DRAIN PIPING FLOOR PLAN
P-113 35 OF 91 LEVEL 10 STORM DRAIN PIPING FLOOR PLAN
P-114 36 OF 91 LEVEL 11 STORM DRAIN PIPING FLOOR PLAN
P-115 37 OF 91 LEVEL 12 STORM DRAIN PIPING FLOOR PLAN
P-601 38 OF 91 STORM DRAIN RISER DIAGRAM
M-001 39 OF 91 MECHANICAL ABBREVIATIONS AND NOTES
MD104 40 OF 91 LEVEL 1 MECHANICAL DEMOLITION PLAN
MD105 41 OF 91 LEVEL 2 MECHANICAL DEMOLITION PLAN
MD106 42 OF 91 LEVEL 3 MECHANICAL DEMOLITION PLAN
MD107 43 OF 91 LEVEL 4 MECHANICAL DEMOLITION PLAN
MD108 44 OF 91 LEVEL 5 MECHANICAL DEMOLITION PLAN
MD109 45 OF 91 LEVEL 6 MECHANICAL DEMOLITION PLAN
MD111 46 OF 91 LEVEL 8 MECHANICAL DEMOLITION PLAN
MD112 47 OF 91 LEVEL 9 MECHANICAL DEMOLITION PLAN
MD113 48 OF 91 LEVEL 10 MECHANICAL DEMOLITION PLAN
MD114 49 OF 91 LEVEL 11 MECHANICAL DEMOLITION PLAN
M-103 50 OF 91 BASEMENT LEVEL 1 MECHANICAL FLOOR PLAN
M-104 51 OF 91 LEVEL 1 MECHANICAL FLOOR PLAN
M-105 52 OF 91 LEVEL 2 MECHANICAL FLOOR PLAN
M-106 53 OF 91 LEVEL 3 MECHANICAL FLOOR PLAN
M-107 54 OF 91 LEVEL 4 MECHANICAL FLOOR PLAN
M-108 55 OF 91 LEVEL 5 MECHANICAL FLOOR PLAN
M-109 56 OF 91 LEVEL 6 MECHANICAL FLOOR PLAN
M-111 57 OF 91 LEVEL 8 MECHANICAL FLOOR PLAN
M-112 58 OF 91 LEVEL 9 MECHANICAL FLOOR PLAN
M-113 59 OF 91 LEVEL 10 MECHANICAL FLOOR PLAN
M-114 60 OF 91 LEVEL 11 MECHANICAL FLOOR PLAN
M-601 61 OF 91 MECHANICAL SCHEDULES AND DETAILS
E-001 62 OF 91 ELECTRICAL LEGEND & NOTES
ED103 63 OF 91 BASEMENT LEVEL 1 ELECTRICAL DEMOLITION PLAN
ED104 64 OF 91 LEVEL 1 ELECTRICAL DEMOLITION PLAN
SHEET NO. DRAWING NO. TITLE
ED106 65 OF 91 LEVEL 3 ELECTRICAL DEMOLITION PLAN
ED107 66 OF 91 LEVEL 4 ELECTRICAL DEMOLITION PLAN
ED108 67 OF 91 LEVEL 5 ELECTRICAL DEMOLITION PLAN
ED109 68 OF 91 LEVEL 6 ELECTRICAL DEMOLITION PLAN
ED111 69 OF 91 LEVEL 8 ELECTRICAL DEMOLITION PLAN
ED112 70 OF 91 LEVEL 9 ELECTRICAL DEMOLITION PLAN
ED113 71 OF 91 LEVEL 10 ELECTRICAL DEMOLITION PLAN
ED114 72 OF 91 LEVEL 11 ELECTRICAL DEMOLITION PLAN
ED115 73 OF 91 LEVEL 12 ELECTRICAL DEMOLITION PLAN
ED205 74 OF 91 LEVEL 2 LIGHTING DEMO PLAN
ED206 75 OF 91 LEVEL 3 LIGHTING DEMO PLAN
E-103 76 OF 91 BASEMENT LEVEL 1 ELECTRICAL FLOOR PLAN
E-104 77 OF 91 LEVEL 1 ELECTRICAL FLOOR PLAN
E-106 78 OF 91 LEVEL 3 ELECTRICAL FLOOR PLAN
E-107 79 OF 91 LEVEL 4 ELECTRICAL FLOOR PLAN
E-108 80 OF 91 LEVEL 5 ELECTRICAL FLOOR PLAN
E-109 81 OF 91 LEVEL 6 ELECTRICAL FLOOR PLAN
E-111 82 OF 91 LEVEL 8 ELECTRICAL FLOOR PLAN
E-112 83 OF 91 LEVEL 9 ELECTRICAL FLOOR PLAN
E-113 84 OF 91 LEVEL 10 ELECTRICAL FLOOR PLAN
E-114 85 OF 91 LEVEL 11 ELECTRICAL FLOOR PLAN
E-115 86 OF 91 LEVEL 12 ELECTRICAL FLOOR PLAN
E-205 87 OF 91 LEVEL 2 LIGHTING PLAN
E-206 88 OF 91 LEVEL 3 LIGHTING PLAN
E-500 89 OF 91 TRANSFER SWITCH TYPICAL CONTROLS DIAGRAM
E-600 90 OF 91 ELECTRICAL SCHEDULES
E-601 91 OF 91 ELECTRICAL SCHEDULES
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
CHILDREN'S NUTRITION RESEARCH CENTER
CRITICAL UPGRADES
HOUSTON, TX
TITLE SHEET AND INDEX
T-001 1 911/04/24
SME
BSN
DRL
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
2923-E
B. DEAN
XXX
D. CORDRAY
W. ROSS
PLAN
NORTH
CHILDREN'S NUTRITIONAL RESEARCH CENTER (CNRC),
1100 BATES AVE, HOUSTON, TX 77030
SOUTH STAIR
FOUNDATION
DRAINAGE
EQUIPMENT
ROOM
B3024
ELEV #3
SERVICE
ELEV
MECHANICAL
B3022
CORRIDOR
OPEN
OFFICESTORAGE
B3016
CONTROL
B3012
OPEN OFFICE AREA
B3014 ENTRY LOBBY
ENTRY
ELEV VEST
ELEV #1
ELEV #2
OPEN
OFFICE
SHUTTLE
ELEV
MACHINE
ROOM
B3000
PUMP
ROOM
B3002
CORRIDOR
TOILET
B3004
LUNCHROOM
B3010
CORRIDOR
B3017
HVAC & SEWAGE
EJECTION RM
B3010B
WBC A
B3008
WBC B
B3006
C
LO
SE
T
STAIR
VESTIBULE
WBC HVAC
B3018
TUNNEL TO
TCH
WEST
STAIR
BASEMENT LEVEL 3 - REFLECTED CEILING PLAN
SCALE: 1/8"=1'-0"
A1301
PLAN
NORTH
INSULATION NOTES LEGEND
LINE OF EXTERIOR
WALL ABOVE
EXISTING CONCRETE
FLOOR / ROOF DECK
EXISTING PATIO,
DECK, OR ROOF EXISTING EXTERIOR CLADDING
EXISTING CMU
EXISTING CONCRETE BEAM
EXISTING CMU
LINE OF EXISTING
METAL STUDS
EXISTING FIBERGLASS
INSULATION
EXISTING ACOUSTICAL CEILING
EXISTING DRYWALL
NEW 4" FOAM INSULATION
PER "INSULATION NOTES"
DEMOLITION WORK
A. CONTRACTOR SHALL REMOVE ALL EXISTING SPRAY
INSULATION ON CONCRETE DECK.
B. CONTRACTOR SHALL CLEAN DECK THOROUGHLY AS
REQUIRED BY NEW SPRAY FOAM INSTRUCTIONS WHERE
SHOWN ON THE PLANS PER THE LEGEND AND DETAILS.
C. CONTRACTOR SHALL REMOVE ALL EXISTING FIBERGLASS
INSULATION FROM CEILING LEVEL UP TO DECK ON ALL
EXTERIOR WALLS WHERE SHOWN ON THE PLANS PER THE
LEGEND.
D. CONTRACTOR SHALL PROVIDE PROTECTIVE WORK AREAS
TO KEEP DEMOLITION DEBRIS FROM GETTING INTO THE
INTERIOR WORK ENVIRONMENT AND FROM GETTING INTO
RETURN AIR HVAC SYSTEM PER 02 41 00. CONTRACTOR
SHALL PROVIDE FILTERING AT RETURN AIR SYSTEM.
CONTRACTOR SHALL REMOVE ALL LOOSE INSULATION
DEBRIS DUE TO DEMOLITION FROM WORK AREAS AND
SPACES ABOVE CEILING.
E. CONTRACTOR SHALL BE RESPONSIBLE FOR MOVING
FURNITURE AS REQUIRED TO PERFORM THE DEMO WORK
WHICH INCLUDES BUT IS NOT LIMITED TO THE REMOVAL OF
EXISTING FINISHES (INCLUDING CEILING TILES).
REMOVE AND APPLY INSULATION ON CONCRETE DECK
PER "INSULATION NOTES"
REMOVE AND APPLY INSULATION ON EXTERIOR WALL
PER "INSULATION NOTES"
NEW APPLICATIONS
EXISTING
STUCCO / PLASTER
EXISTING CEILING FINISHES
EXISTING
GYP. BD.
EXISTING SACT
EXISTING
EXPOSED
NOTE: LIGHT FIXTURE LAYOUTS SHOWN IN
ARCHITECTURAL REFLECTED CEILING PLANS
ARE REPRESENTATIONAL OF EXISTING LIGHT
FIXTURE TYPES AND LAYOUTS.
NEW WORK
A. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL
INSULATION AS SPECIFIED ON UNDERSIDE OF FLOOR / ROOF
DECK AS DESCRIBED HEREIN AND WHERE SHOWN ON THE
PLANS PER THE LEGEND.
B. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL
INSULATION AS SPECIFIED ON EXTERIOR WALLS AS
DESCRIBED HEREIN WHERE SHOWN ON THE PLANS PER THE
LEGEND.
C. CONTRACTOR SHALL APPLY INTUMESCENT COATING AS
SPECIFIED OVER ALL OF THE NEW SPRAY-APPLIED
INSULATION.
D. CONTRACTOR SHALL BE RESPONSIBLE FOR RETURNING
ALL FURNITURE THAT WAS MOVED IN ORDER TO PERFORM
THE SCOPE OF WORK. ANY FINISHES DAMAGED DURING THE
WORK SHALL BE REPLACED LIKE IN-KIND.
INSULATION DETAIL NO WORK
THIS FLOOR
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
CHILDREN'S NUTRITION RESEARCH CENTER
CRITICAL UPGRADES
HOUSTON, TX
BASEMENT LEVEL 3 - RCP
A1301 2 911/04/24
SME
CLR
DRL
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
2923-E
B. DEAN
XXX
D. CORDRAY
W. ROSS
0 16'8'4' 24'
SCALE: 1/8"= 1'-0"
HT
XET
TA
FO ET
S
R
EG
IS
SA
TC
E
IT
RERE A
CD
JE
RR
Y G. MARTIN
1 3573
ELEV #3
SERVICE
ELEV
LL2-016
ELEV #1
ELEV #2
WEST STAIR
EAST PARKING
SLOPE UP SLOPE DOWN
SLOPE DOWN
WEST PARKING
LL2-014
TRANSFORMER ROOM
EXHAUST
STORAGE
B-2010TRANSFORMER
ROOM LL2-010
B-2008
SWITCH
ROOM
B-2006
LL2-008
ELECTRICAL
B-2000
FUSE ROOM
B-2002
FUSE ROOM
B-2004
STORAGE
B-2012
BASEMENT LEVEL 2 - REFLECTED CEILING PLAN
SCALE: 1/8"=1'-0"
A1302
PLAN
NORTH
INSULATION NOTES LEGEND
LINE OF EXTERIOR
WALL ABOVE
EXISTING CONCRETE
FLOOR / ROOF DECK
EXISTING PATIO,
DECK, OR ROOF EXISTING EXTERIOR CLADDING
EXISTING CMU
EXISTING CONCRETE BEAM
EXISTING CMU
LINE OF EXISTING
METAL STUDS
EXISTING FIBERGLASS
INSULATION
EXISTING ACOUSTICAL CEILING
EXISTING DRYWALL
NEW 4" FOAM INSULATION
PER "INSULATION NOTES"
DEMOLITION WORK
A. CONTRACTOR SHALL REMOVE ALL EXISTING SPRAY
INSULATION ON CONCRETE DECK.
B. CONTRACTOR SHALL CLEAN DECK THOROUGHLY AS
REQUIRED BY NEW SPRAY FOAM INSTRUCTIONS WHERE
SHOWN ON THE PLANS PER THE LEGEND AND DETAILS.
C. CONTRACTOR SHALL REMOVE ALL EXISTING FIBERGLASS
INSULATION FROM CEILING LEVEL UP TO DECK ON ALL
EXTERIOR WALLS WHERE SHOWN ON THE PLANS PER THE
LEGEND.
D. CONTRACTOR SHALL PROVIDE PROTECTIVE WORK AREAS
TO KEEP DEMOLITION DEBRIS FROM GETTING INTO THE
INTERIOR WORK ENVIRONMENT AND FROM GETTING INTO
RETURN AIR HVAC SYSTEM PER 02 41 00. CONTRACTOR
SHALL PROVIDE FILTERING AT RETURN AIR SYSTEM.
CONTRACTOR SHALL REMOVE ALL LOOSE INSULATION
DEBRIS DUE TO DEMOLITION FROM WORK AREAS AND
SPACES ABOVE CEILING.
E. CONTRACTOR SHALL BE RESPONSIBLE FOR MOVING
FURNITURE AS REQUIRED TO PERFORM THE DEMO WORK
WHICH INCLUDES BUT IS NOT LIMITED TO THE REMOVAL OF
EXISTING FINISHES (INCLUDING CEILING TILES).
REMOVE AND APPLY INSULATION ON CONCRETE DECK
PER "INSULATION NOTES"
REMOVE AND APPLY INSULATION ON EXTERIOR WALL
PER "INSULATION NOTES"
NEW APPLICATIONS
EXISTING
STUCCO / PLASTER
EXISTING CEILING FINISHES
EXISTING
GYP. BD.
EXISTING SACT
EXISTING
EXPOSED
NOTE: LIGHT FIXTURE LAYOUTS SHOWN IN
ARCHITECTURAL REFLECTED CEILING PLANS
ARE REPRESENTATIONAL OF EXISTING LIGHT
FIXTURE TYPES AND LAYOUTS.
NEW WORK
A. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL
INSULATION AS SPECIFIED ON UNDERSIDE OF FLOOR / ROOF
DECK AS DESCRIBED HEREIN AND WHERE SHOWN ON THE
PLANS PER THE LEGEND.
B. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL
INSULATION AS SPECIFIED ON EXTERIOR WALLS AS
DESCRIBED HEREIN WHERE SHOWN ON THE PLANS PER THE
LEGEND.
C. CONTRACTOR SHALL APPLY INTUMESCENT COATING AS
SPECIFIED OVER ALL OF THE NEW SPRAY-APPLIED
INSULATION.
D. CONTRACTOR SHALL BE RESPONSIBLE FOR RETURNING
ALL FURNITURE THAT WAS MOVED IN ORDER TO PERFORM
THE SCOPE OF WORK. ANY FINISHES DAMAGED DURING THE
WORK SHALL BE REPLACED LIKE IN-KIND.
INSULATION DETAIL NO WORK
THIS FLOOR
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
CHILDREN'S NUTRITION RESEARCH CENTER
CRITICAL UPGRADES
HOUSTON, TX
BASEMENT LEVEL 2 - RCP
A1302 3 911/04/24
SME
CLR
DRL
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
2923-E
B. DEAN
XXX
D. CORDRAY
W. ROSS
0 16'8'4' 24'
SCALE: 1/8"= 1'-0"
HT
XET
TA
FO ET
S
R
EG
IS
SA
TC
E
IT
RERE A
CD
JE
RR
ELEV #3
SERVICE
ELEV
ELEV #1
ELEV #2
WEST
STAIR
FAN
ROOM
FAN
ROOM
EAST RAMP
BICYCLE
PARKING
MACHINE SHOP
B-1002
STORAGE
B1004
EQUIPMENT
ROOM
B1010
SWITCHGEAR
B-1012
MECHANICAL
EQUIPMENT
B1006
ENGINEER'S
OFFICE
B-1008
CENTRAL STAIR
ELEV
LOBBY
RAMP UP TO L1
CONTROL BOOTH
WEST RAMP
MOTOR BIKE
PARKING
PUMP ROOM
B-1016
CENTRAL PLANT
B-1014
STORAGE
B-1000
BASEMENT LEVEL 1 - REFLECTED CEILING PLAN
SCALE: 1/8"=1'-0"
A1303
PLAN
NORTH
INSULATION NOTES LEGEND
LINE OF EXTERIOR
WALL ABOVE
EXISTING CONCRETE
FLOOR / ROOF DECK
EXISTING PATIO,
DECK, OR ROOF EXISTING EXTERIOR CLADDING
EXISTING CMU
EXISTING CONCRETE BEAM
EXISTING CMU
LINE OF EXISTING
METAL STUDS
EXISTING FIBERGLASS
INSULATION
EXISTING ACOUSTICAL CEILING
EXISTING DRYWALL
NEW 4" FOAM INSULATION
PER "INSULATION NOTES"
DEMOLITION WORK
A. CONTRACTOR SHALL REMOVE ALL EXISTING SPRAY
INSULATION ON CONCRETE DECK.
B. CONTRACTOR SHALL CLEAN DECK THOROUGHLY AS
REQUIRED BY NEW SPRAY FOAM INSTRUCTIONS WHERE
SHOWN ON THE PLANS PER THE LEGEND AND DETAILS.
C. CONTRACTOR SHALL REMOVE ALL EXISTING FIBERGLASS
INSULATION FROM CEILING LEVEL UP TO DECK ON ALL
EXTERIOR WALLS WHERE SHOWN ON THE PLANS PER THE
LEGEND.
D. CONTRACTOR SHALL PROVIDE PROTECTIVE WORK AREAS
TO KEEP DEMOLITION DEBRIS FROM GETTING INTO THE
INTERIOR WORK ENVIRONMENT AND FROM GETTING INTO
RETURN AIR HVAC SYSTEM PER 02 41 00. CONTRACTOR
SHALL PROVIDE FILTERING AT RETURN AIR SYSTEM.
CONTRACTOR SHALL REMOVE ALL LOOSE INSULATION
DEBRIS DUE TO DEMOLITION FROM WORK AREAS AND
SPACES ABOVE CEILING.
E. CONTRACTOR SHALL BE RESPONSIBLE FOR MOVING
FURNITURE AS REQUIRED TO PERFORM THE DEMO WORK
WHICH INCLUDES BUT IS NOT LIMITED TO THE REMOVAL OF
EXISTING FINISHES (INCLUDING CEILING TILES).
REMOVE AND APPLY INSULATION ON CONCRETE DECK
PER "INSULATION NOTES"
REMOVE AND APPLY INSULATION ON EXTERIOR WALL
PER "INSULATION NOTES"
NEW APPLICATIONS
EXISTING
STUCCO / PLASTER
EXISTING CEILING FINISHES
EXISTING
GYP. BD.
EXISTING SACT
EXISTING
EXPOSED
NOTE: LIGHT FIXTURE LAYOUTS SHOWN IN
ARCHITECTURAL REFLECTED CEILING PLANS
ARE REPRESENTATIONAL OF EXISTING LIGHT
FIXTURE TYPES AND LAYOUTS.
NEW WORK
A. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL
INSULATION AS SPECIFIED ON UNDERSIDE OF FLOOR / ROOF
DECK AS DESCRIBED HEREIN AND WHERE SHOWN ON THE
PLANS PER THE LEGEND.
B. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL
INSULATION AS SPECIFIED ON EXTERIOR WALLS AS
DESCRIBED HEREIN WHERE SHOWN ON THE PLANS PER THE
LEGEND.
C. CONTRACTOR SHALL APPLY INTUMESCENT COATING AS
SPECIFIED OVER ALL OF THE NEW SPRAY-APPLIED
INSULATION.
D. CONTRACTOR SHALL BE RESPONSIBLE FOR RETURNING
ALL FURNITURE THAT WAS MOVED IN ORDER TO PERFORM
THE SCOPE OF WORK. ANY FINISHES DAMAGED DURING THE
WORK SHALL BE REPLACED LIKE IN-KIND.
INSULATION DETAIL NO WORK
THIS FLOOR
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
CHILDREN'S NUTRITION RESEARCH CENTER
CRITICAL UPGRADES
HOUSTON, TX
BASEMENT LEVEL 1 - RCP
A1303 4 911/04/24
SME
CLR
DRL
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
2923-E
B. DEAN
XXX
D. CORDRAY
W. ROSS
0 16'8'4' 24'
SCALE: 1/8"= 1'-0"
HT
XET
TA
FO ET
S
R
EG
IS
SA
TC
E
IT
RERE A
CD
JE
RR
FARM ANIMAL SUITE
JAN
JAN/STOR
PIGS
ANIMAL/REC DRIVEWAY
DRIVEWAY
SOUTH
STAIR
OFFICE
LOADING DOCK
RECEIVING OFFICE
CLOSET
1HC22
BULK CHENICAL
GENERAL STORAGE
RODENTS
CENTRAL CORRIDOR
GEN PURP STOR
ANIMAL/REC DOCK
FREEZER
1095A
TOILET
SOUTH
HALL
SOUTH
HALL
CAGE WASH/DIRTY
CAGE WASH/CLEAN
STORAGE
MECH
1024A
WEST HALL
HOLDING
TREAT
CHOW
CENTRAL
HALL
STOR
SPECIAL STUDIES
BEDDING
INV RM
HOLDING
WEST
HALL
SCRUB
PANTRY
1022A
FLURO ROOM
TELE
ELECTRICAL
CENTRAL JAN SUPPLY
NORTH
CORRIDOR
SECURITY OFF
DRY FOOD STORAGE
MEN
SWITCH ROOM
ELEV LOBBY
FIRE COMD STN
STAIR #5 ONLY
TO LEV 2
SCIENTIST OFF
GEN STORAGE/
HOUSEKEEPING
ELEV
#3
ELEV LOBBY
SERVICE
AREA
STAIR #2
CENTRAL STAIR
LOUNGE
TOILET
INFO & SECURITY
STORAGE
1101A
LAB
1014ANIMAL HVAC EQUIP ROOM
STAIR #1
LOBBY EXHIBIT
PIGS
PIGS
PIGS
CLOSET
RODENTS
RODENTS
RODENTS
RODENTS
ANIMAL
HOLDING
COOLER
RODENTS
RODENTS
RODENTS
SOWS
SOWS
PIGS
PIGS
PIGS
STORAGE
JAN
1084HOLDING
HOLDING
NORTH
HALL
TOILET
NORTH
HALL
AF1
LAB
LAB
LAB
LAB
ELEV
#4
ELEV
#5
EAST
CORRIDOR
WOMEN
ELEV
#1
ELEV
#2
NORTH
STAIR
FLOOR LEVEL 1 - REFLECTED CEILING PLAN
SCALE: 1/8"=1'-0"
A1304
PLAN
NORTH
INSULATION NOTES LEGEND
LINE OF EXTERIOR
WALL ABOVE
EXISTING CONCRETE
FLOOR / ROOF DECK
EXISTING PATIO,
DECK, OR ROOF EXISTING EXTERIOR CLADDING
EXISTING CMU
EXISTING CONCRETE BEAM
EXISTING CMU
LINE OF EXISTING
METAL STUDS
EXISTING FIBERGLASS
INSULATION
EXISTING ACOUSTICAL CEILING
EXISTING DRYWALL
NEW 4" FOAM INSULATION
PER "INSULATION NOTES"
DEMOLITION WORK
A. CONTRACTOR SHALL REMOVE ALL EXISTING SPRAY
INSULATION ON CONCRETE DECK.
B. CONTRACTOR SHALL CLEAN DECK THOROUGHLY AS
REQUIRED BY NEW SPRAY FOAM INSTRUCTIONS WHERE
SHOWN ON THE PLANS PER THE LEGEND AND DETAILS.
C. CONTRACTOR SHALL REMOVE ALL EXISTING FIBERGLASS
INSULATION FROM CEILING LEVEL UP TO DECK ON ALL
EXTERIOR WALLS WHERE SHOWN ON THE PLANS PER THE
LEGEND.
D. CONTRACTOR SHALL PROVIDE PROTECTIVE WORK AREAS
TO KEEP DEMOLITION DEBRIS FROM GETTING INTO THE
INTERIOR WORK ENVIRONMENT AND FROM GETTING INTO
RETURN AIR HVAC SYSTEM PER 02 41 00. CONTRACTOR
SHALL PROVIDE FILTERING AT RETURN AIR SYSTEM.
CONTRACTOR SHALL REMOVE ALL LOOSE INSULATION
DEBRIS DUE TO DEMOLITION FROM WORK AREAS AND
SPACES ABOVE CEILING.
E. CONTRACTOR SHALL BE RESPONSIBLE FOR MOVING
FURNITURE AS REQUIRED TO PERFORM THE DEMO WORK
WHICH INCLUDES BUT IS NOT LIMITED TO THE REMOVAL OF
EXISTING FINISHES (INCLUDING CEILING TILES).
REMOVE AND APPLY INSULATION ON CONCRETE DECK
PER "INSULATION NOTES"
REMOVE AND APPLY INSULATION ON EXTERIOR WALL
PER "INSULATION NOTES"
NEW APPLICATIONS
EXISTING
STUCCO / PLASTER
EXISTING CEILING FINISHES
EXISTING
GYP. BD.
EXISTING SACT
EXISTING
EXPOSED
NOTE: LIGHT FIXTURE LAYOUTS SHOWN IN
ARCHITECTURAL REFLECTED CEILING PLANS
ARE REPRESENTATIONAL OF EXISTING LIGHT
FIXTURE TYPES AND LAYOUTS.
NEW WORK
A. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL
INSULATION AS SPECIFIED ON UNDERSIDE OF FLOOR / ROOF
DECK AS DESCRIBED HEREIN AND WHERE SHOWN ON THE
PLANS PER THE LEGEND.
B. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL
INSULATION AS SPECIFIED ON EXTERIOR WALLS AS
DESCRIBED HEREIN WHERE SHOWN ON THE PLANS PER THE
LEGEND.
C. CONTRACTOR SHALL APPLY INTUMESCENT COATING AS
SPECIFIED OVER ALL OF THE NEW SPRAY-APPLIED
INSULATION.
D. CONTRACTOR SHALL BE RESPONSIBLE FOR RETURNING
ALL FURNITURE THAT WAS MOVED IN ORDER TO PERFORM
THE SCOPE OF WORK. ANY FINISHES DAMAGED DURING THE
WORK SHALL BE REPLACED LIKE IN-KIND.
INSULATION DETAIL
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
CHILDREN'S NUTRITION RESEARCH CENTER
CRITICAL UPGRADES
HOUSTON, TX
FLOOR LEVEL 1 - RCP
A1304 5 911/04/24
SME
CLR
DRL
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
2923-E
B. DEAN
XXX
D. CORDRAY
W. ROSS
0 16'8'4' 24'
SCALE: 1/8"= 1'-0"
4'
SCALE: 1/2"=1'-0"
0 1' 2' 8'
HT
XET
TA
FO ET
S
R
EG
IS
SA
TC
E
IT
RERE A
CD
JE
RR
JAN.
STORAGE
OFFICE
OFFICE
OFFICE
EDITOR
ASST.
EDITOR
ASST.
EDITOR
ILLUSTRATOR
DARK
RM.
PHOTO
STUDIO
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
DIRECTOR
CNRC
EMPLOYEE LOUNGE
OPEN
OFFICE
REPRODUCTION
CENTER
WORD PROCESSING
CLOSET
2HC20
SOUTH
CORR.
OPERATOR/TECH.
OFFICE
OFFICE
OFFICE
SECRETARY
CLOSET
2HC21
OFFICE
STORAGE
2060AOFFICE
OFFICE
OFFICE
OFFICE
TERRACE
EAST
CORRIDOR
SERVER
ROOM
TELECOM. ROOM
SVC.
CORR
CENTRAL
CORRIDOR
JANITOR
ELECTRICAL
ADMINISTRATIVE LOBBY
RECP.
COFFEE
2027A
RECEPTION
CONFERENCE ROOM
TERRACE
OFFICE
OFFICE
OFFICE
ELEV #3
SERVICE ELEV
LOBBY 2075
TELE
LIBRARIAN
CLOSET
2HC19
STORAGE
MAIL ROOM
ELEV #5 ELEV #4
ELEV LOBBY
ELEV #6 ELEV #7
AUDITORIUM
LOBBY
VENDING
OFFICE
CLOSET
WOMEN
MEN
CONTROL ROOM
PROJECTION ROOM
KITCHEN
CONFERENCE ROOM
PUBLIC
TEL.
STOR.
STAIR A
PROJ.
BOOTH
AUDITORIUM 2000
(OPEN TO ABOVE)
CORRIDOR
LOBBY
ARCHIVES
CLOSET
2HC18
STAIR #3
COPY RM
WEST
CORRIDOR
LIBRARY
FLOOR LEVEL 2 - REFLECTED CEILING PLAN
SCALE: 1/8"=1'-0"
A1305
PLAN
NORTH
INSULATION NOTES LEGEND
LINE OF EXTERIOR
WALL ABOVE
EXISTING CONCRETE
FLOOR / ROOF DECK
EXISTING PATIO,
DECK, OR ROOF EXISTING EXTERIOR CLADDING
EXISTING CMU
EXISTING CONCRETE BEAM
EXISTING CMU
LINE OF EXISTING
METAL STUDS
EXISTING FIBERGLASS
INSULATION
EXISTING ACOUSTICAL CEILING
EXISTING DRYWALL
NEW 4" FOAM INSULATION
PER "INSULATION NOTES"
DEMOLITION WORK
A. CONTRACTOR SHALL REMOVE ALL EXISTING SPRAY
INSULATION ON CONCRETE DECK.
B. CONTRACTOR SHALL CLEAN DECK THOROUGHLY AS
REQUIRED BY NEW SPRAY FOAM INSTRUCTIONS WHERE
SHOWN ON THE PLANS PER THE LEGEND AND DETAILS.
C. CONTRACTOR SHALL REMOVE ALL EXISTING FIBERGLASS
INSULATION FROM CEILING LEVEL UP TO DECK ON ALL
EXTERIOR WALLS WHERE SHOWN ON THE PLANS PER THE
LEGEND.
D. CONTRACTOR SHALL PROVIDE PROTECTIVE WORK AREAS
TO KEEP DEMOLITION DEBRIS FROM GETTING INTO THE
INTERIOR WORK ENVIRONMENT AND FROM GETTING INTO
RETURN AIR HVAC SYSTEM PER 02 41 00. CONTRACTOR
SHALL PROVIDE FILTERING AT RETURN AIR SYSTEM.
CONTRACTOR SHALL REMOVE ALL LOOSE INSULATION
DEBRIS DUE TO DEMOLITION FROM WORK AREAS AND
SPACES ABOVE CEILING.
E. CONTRACTOR SHALL BE RESPONSIBLE FOR MOVING
FURNITURE AS REQUIRED TO PERFORM THE DEMO WORK
WHICH INCLUDES BUT IS NOT LIMITED TO THE REMOVAL OF
EXISTING FINISHES (INCLUDING CEILING TILES).
REMOVE AND APPLY INSULATION ON CONCRETE DECK
PER "INSULATION NOTES"
REMOVE AND APPLY INSULATION ON EXTERIOR WALL
PER "INSULATION NOTES"
NEW APPLICATIONS
EXISTING
STUCCO / PLASTER
EXISTING CEILING FINISHES
EXISTING
GYP. BD.
EXISTING SACT
EXISTING
EXPOSED
NOTE: LIGHT FIXTURE LAYOUTS SHOWN IN
ARCHITECTURAL REFLECTED CEILING PLANS
ARE REPRESENTATIONAL OF EXISTING LIGHT
FIXTURE TYPES AND LAYOUTS.
NEW WORK
A. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL
INSULATION AS SPECIFIED ON UNDERSIDE OF FLOOR / ROOF
DECK AS DESCRIBED HEREIN AND WHERE SHOWN ON THE
PLANS PER THE LEGEND.
B. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL
INSULATION AS SPECIFIED ON EXTERIOR WALLS AS
DESCRIBED HEREIN WHERE SHOWN ON THE PLANS PER THE
LEGEND.
C. CONTRACTOR SHALL APPLY INTUMESCENT COATING AS
SPECIFIED OVER ALL OF THE NEW SPRAY-APPLIED
INSULATION.
D. CONTRACTOR SHALL BE RESPONSIBLE FOR RETURNING
ALL FURNITURE THAT WAS MOVED IN ORDER TO PERFORM
THE SCOPE OF WORK. ANY FINISHES DAMAGED DURING THE
WORK SHALL BE REPLACED LIKE IN-KIND.
INSULATION DETAIL
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
CHILDREN'S NUTRITION RESEARCH CENTER
CRITICAL UPGRADES
HOUSTON, TX
FLOOR LEVEL 2 - RCP
A1305 6 911/04/24
SME
CLR
DRL
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
2923-E
B. DEAN
XXX
D. CORDRAY
W. ROSS
0 16'8'4' 24'
SCALE: 1/8"= 1'-0"
4'
SCALE: 1/2"=1'-0"
0 1' 2' 8'
HT
XET
TA
FO ET
S
R
EG
IS
SA
TC
E
IT
RERE A
CD
JE
RR
CLOS.
CLOS.
BATHRM.BATHRM.
CLOS. CLOS.
BATHRM.BATHRM.
DWELLING UNITDWELLING UNIT
KIT EMPLOYEE LOUNGE
PROCEDURES
CENTRAL CORRIDOR
CORRIDOR
TELE.
CLOS.CLOS.
DWELLING UNITDWELLING UNITDWELLING UNITDWELLING UNIT
WEST CORRIDOR
CLOS.
ATTENDANT
STATION
TOILETTOILET
BATHRM.BATHRM.
BATHRM. BATHRM.BATHRM.
STAIR #9
STAIR #2
CALOR. #2
EAST CORRIDOR
3050C
3050J
3050H
3028 3030302630243022
3050B3050A
CALIBRATION LAB
STAIR#6
LEV 3&4 ONLY
TERRACE
WEIGHING
MEN
DWELLING SUITE
BEDROOM
STAIR #3
BATHRM.
DWELLING SUITE
CLOS.
CLOS.
BATHRM.
DWELLING UNIT
CORR.
CLOS.
JAN.
STAIR
VESTIBULE
WAITING &
ADULT DAY RM.
METABOLIC STORAGE
CLOS.
CLOS.
BATHRM.
DWELLING UNIT
DWELLING UNIT
DWELLING UNIT
CLOS.
CLOS.
CALORIMETER SUITE
CALOR. #3
3050E
CALOR. #4
3050D
CALOR. #4
3050F
CALOR. #1
3050G
PHYSICAL
EXERCISE LAB
CLINICAL
ANALYSIS
PHARMACY LAB
ELECTRICAL
LAUNDRY
TERRACE
DINING RM.
DISH RM.
3005B
BOTTLE WASH
3005A
WEIGHT STA.
JAN 3005
ELEV #6 ELEV #7
WOMEN
CART WASH
BREAK ROOM
MECHANICAL
STORAGE
FREEZER
3005J
COOLER
3005H
STAIR
VEST. 3062
STOR.
3005G
GENERAL
KITCHEN AREA
OFFICE
OFFICE
COMP.
3011A1
BAKERY
3005F
POT WASH
FREEZER
3005E
COOLER
3005D
W.S.
3005C
W.S. 4 W.S. 3 W.S. 2 W.S. 1
ELEVATOR
LOBBY
SERVICE
ELEV
ELEV #3ELEV #4ELEV #5
CORR.
KITCHEN
ELEV LOBBY
STAIR #1
AUDITORIUM
(OPEN TO BELOW)
FLOOR LEVEL 3 - REFLECTED CEILING PLAN
SCALE: 1/8"=1'-0"
A1306
PLAN
NORTH
INSULATION NOTES LEGEND INSULATION DETAIL
LINE OF EXTERIOR
WALL ABOVE
EXISTING CONCRETE
FLOOR / ROOF DECK
EXISTING PATIO,
DECK, OR ROOF EXISTING EXTERIOR CLADDING
EXISTING CMU
EXISTING CONCRETE BEAM
EXISTING CMU
LINE OF EXISTING
METAL STUDS
EXISTING FIBERGLASS
INSULATION
EXISTING ACOUSTICAL CEILING
EXISTING DRYWALL
NEW 4" FOAM INSULATION
PER "INSULATION NOTES"
DEMOLITION WORK
A. CONTRACTOR SHALL REMOVE ALL EXISTING SPRAY
INSULATION ON CONCRETE DECK.
B. CONTRACTOR SHALL CLEAN DECK THOROUGHLY AS
REQUIRED BY NEW SPRAY FOAM INSTRUCTIONS WHERE
SHOWN ON THE PLANS PER THE LEGEND AND DETAILS.
C. CONTRACTOR SHALL REMOVE ALL EXISTING FIBERGLASS
INSULATION FROM CEILING LEVEL UP TO DECK ON ALL
EXTERIOR WALLS WHERE SHOWN ON THE PLANS PER THE
LEGEND.
D. CONTRACTOR SHALL PROVIDE PROTECTIVE WORK AREAS
TO KEEP DEMOLITION DEBRIS FROM GETTING INTO THE
INTERIOR WORK ENVIRONMENT AND FROM GETTING INTO
RETURN AIR HVAC SYSTEM PER 02 41 00. CONTRACTOR
SHALL PROVIDE FILTERING AT RETURN AIR SYSTEM.
CONTRACTOR SHALL REMOVE ALL LOOSE INSULATION
DEBRIS DUE TO DEMOLITION FROM WORK AREAS AND
SPACES ABOVE CEILING.
E. CONTRACTOR SHALL BE RESPONSIBLE FOR MOVING
FURNITURE AS REQUIRED TO PERFORM THE DEMO WORK
WHICH INCLUDES BUT IS NOT LIMITED TO THE REMOVAL OF
EXISTING FINISHES (INCLUDING CEILING TILES).
REMOVE AND APPLY INSULATION ON CONCRETE DECK
PER "INSULATION NOTES"
REMOVE AND APPLY INSULATION ON EXTERIOR WALL
PER "INSULATION NOTES"
NEW APPLICATIONS
EXISTING
STUCCO / PLASTER
EXISTING CEILING FINISHES
EXISTING
GYP. BD.
EXISTING
SACT
EXISTING
EXPOSED
NOTE: LIGHT FIXTURE LAYOUTS SHOWN IN
ARCHITECTURAL REFLECTED CEILING PLANS
ARE REPRESENTATIONAL OF EXISTING LIGHT
FIXTURE TYPES AND LAYOUTS.
NEW WORK
A. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL
INSULATION AS SPECIFIED ON UNDERSIDE OF FLOOR / ROOF
DECK AS DESCRIBED HEREIN AND WHERE SHOWN ON THE
PLANS PER THE LEGEND.
B. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL
INSULATION AS SPECIFIED ON EXTERIOR WALLS AS
DESCRIBED HEREIN WHERE SHOWN ON THE PLANS PER THE
LEGEND.
C. CONTRACTOR SHALL APPLY INTUMESCENT COATING AS
SPECIFIED OVER ALL OF THE NEW SPRAY-APPLIED
INSULATION.
D. CONTRACTOR SHALL BE RESPONSIBLE FOR RETURNING
ALL FURNITURE THAT WAS MOVED IN ORDER TO PERFORM
THE SCOPE OF WORK. ANY FINISHES DAMAGED DURING THE
WORK SHALL BE REPLACED LIKE IN-KIND.
REMOVE EXISTING AND INSTALL NEW DRYWALL
CEILING. SEE DRYWALL CEILINGS REPAIR DETAILS
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
DRYWALL CEILINGS REPAIR DETAILS
SCALE: 6"=1'-0"
A1306
FRAMED CEILING DETAIL
EXISTING HANGER WIRES TO REMAIN
EXISTING FRAMING MEMBERS TO REMAIN;
CONTRACTOR TO REMOVE AND RE-INSTALL
THESE FRAMING MEMBERS AS NECESSARY TO
PERFORM SCOPE OF WORK ABOVE CEILING
DEMOLISH ALL EXISTING DRYWALL CEILING
BOARD ALONG WITH CEILING-MOUNTED
LIGHTS, DIFFUSERS, ALARM, DEVICES, ETC.;
INSTALL NEW 1/2" DRYWALL CEILING BOARD
WITH LEVEL 4 FINISH AFTER ALL REQUIRED
WORK ABOVE CEILING IS COMPLETED.
RE-INSTALL ALL DIFFUSERS, ALARM, DEVICES,
ETC. IN-KIND. INSTALL NEW LIGHTS PER
ELECTRICAL REQUIREMENTS
SUSPENDED CEILING DETAIL
EXISTING FRAMING MEMBERS TO
REMAIN; CONTRACTOR TO
REMOVE AND RE-INSTALL THESE
FRAMING MEMBERS AS
NECESSARY TO PERFORM SCOPE
OF WORK ABOVE CEILING
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
DEMOLISH ALL EXISTING PLASTER CEILING
ALONG WITH CEILING-MOUNTED LIGHTS,
DIFFUSERS, ALARM, DEVICES, ETC.; INSTALL
NEW ACOUSTICAL PLASTER CEILING AS
SPECIFIED WITH LEVEL 4 FINISH AFTER ALL
REQUIRED WORK ABOVE CEILING IS
COMPLETED. RE-INSTALL ALL DIFFUSERS,
ALARM, DEVICES, ETC. IN-KIND. INSTALL NEW
LIGHTS PER ELECTRICAL REQUIREMENTS
SCALE: 6"=1'-0"
1 1/2" 3" 6"
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
CHILDREN'S NUTRITION RESEARCH CENTER
CRITICAL UPGRADES
HOUSTON, TX
FLOOR LEVEL 3 - RCP
A1306 7 911/04/24
SME
CLR
DRL
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
2923-E
B. DEAN
XXX
D. CORDRAY
W. ROSS
0 16'8'4' 24'
SCALE: 1/8"= 1'-0"
4'
SCALE: 1/2"=1'-0"
0 1' 2' 8'
HT
XET
TA
FO ET
S
R
EG
IS
SA
TC
E
IT
RERE A
CD
JE
RR
ELECT.
SOUTH
TERRACE
MECHANICAL
ROOM
STAIR VEST.
TERRACE
CORRIDOR
DAY ROOM
DAY ROOM
TOILETSTOR.
OFFICE
4004A
OFFICE
4004B
ADOLESCENT
EXERCISE &
ENTERTAINMENT
OFFICE
4004D
ATTENDANT
STATION
CENTRAL
CORRIDOR
SERVICE
ELEV.
TELE.
SHOWER
SUPPORT
PROCED
ELEV #3
EAST
CORRIDOR
TLT
CHANGE
WAITING
MEN
WOMEN
CHANGE
OFFICE
OFFICE
EAST
TERRACE
ACOUSTICS
4HC17
TOBEC
EXAM
ELEV #4ELEV #5
EXAM
ELEV #7ELEV #6
EMERGENCY
GENERATOR
MECHANICAL
ROOM
CORRIDOR
NORTHEAST
TERRACE
STAIR VEST.
NORTH
TERRACE
WEST
TERRACE
SOUTH STAIR
NORTH
STAIR
STAIR#6
LEV 3&4 ONLYCENTRAL STAIR
FLOOR LEVEL 4 - REFLECTED CEILING PLAN
SCALE: 1/8"=1'-0"
A1307
PLAN
NORTH
AWINDOW TYPE
CURTAIN WALL ELEVATION
SCALE: 1/4"=1'-0"
A1307
FLOOR LEVEL 4
ELEV. 94.00'
±49'-8" (EXISTING - VERIFY)
±1 3'-
0" (E
XI
ST
IN
G
- V
ER
IF
Y)
4'- 0"
5'- 6"
3'- 6"
21 2" 3'-
1" 21 2"
21 2" 3'-
7" 21 2"
24'-41 2" 3'-0"
DOOR
22'-31
2"
9'- 0"
2" 3'-111
4" 21 2" 4'-61
4" 21 2" 4'-61
4" 21 2" 4'-61
4" 21 2" 4'-61
2" 21 2" 1'-11
2" 21 2" 1'-6" 21
2" 4'-11" 21 2" 4'-101
4" 21 2" 4'-101
4" 21 2" 4'-11"
2"
ALIGN TOP OF MULLION
IN-KIND WITH LINE OF
GRANITE TRIM (TYP)
ALIGN TOP OF MULLION
IN-KIND WITH CENTERLINE
OF GRANITE JOINT (TYP)
ALIGN CENTERLINE OF MULLION IN-KIND WITH CENTERLINE
OF VERTICAL GRANITE JOINT WHERE SHOWN (TYP)
GRANITE JOINT 'GJ' (TYP)
'GJ' 'GJ' 'GJ' 'GJ' 'GJ' 'GJ' 'GJ' 'GJ'
EXISTING PATIO / FLOOR / ROOF SLAB (TYP)
PREFINISHED METAL SUBSILL FLASHING;
REPLACE EXISTING AND EXTEND NEW
BELOW TILE LIKE EXISTING FLASHING; SET
IN CONT. BED OF SEALANT (TYP)
CURTAIN WALL SYSTEM
AS SPECIFIED
PROTECT EXISTING WATERPROOF
MEMBRANE DURING CONSTRUCTION (TYP)
BACKER ROD AND
SEALANT (TYP) BACKER ROD AND SEALANT;
DO NOT BLOCK CURTAIN
WALL WEEP DRAIN (TYP)
EXISTING CONCRETE
PAVERS; REMOVE AND
REINSTALL ONLY AS REQ'D
TO INSTALL NEW SUBSILL
FLASHING (TYP)
GLAZING; RE: SECTION 08 81 00
CURTAIN WALL SILL DETAIL
SCALE: 3"=1'-0"
TYPICAL
CURTAIN WALL JAMB DETAIL
SCALE: 3"=1'-0"
TYPICALA1307 A1307
BACKER ROD AND
SEALANT (TYP)
EXISTING GRANITE
PANEL (TYP)
EXISTING JAMB FLASHING
TO REMAIN (TYP)
EXISTING SHEATHING (TYP)
EDGE OF EXISTING INTERIOR
WALL CONSTRUCTION (TYP)
BACKER ROD AND
SEALANT (TYP)
CURTAIN WALL SYSTEM
AS SPECIFIED
GLAZING AS SPECIFIED
CURTAIN WALL HEAD DETAIL
SCALE: 3"=1'-0"
TYPICALA1307
GLAZING AS SPECIFIED
CURTAIN WALL SYSTEM
AS SPECIFIED
PREFINISHED METAL HEAD FLASHING
AS SPECIFIED (TYP)
BACKER ROD AND SEALANT (TYP)
EXISTING GRANITE PANEL (TYP)
EXISTING SHEATHING (TYP)
EXISTING CONT. STEEL ANGLE
FOR ATTACHMENT OF CURTAIN
WALL SYSTEM; SCRAPE CLEAN,
PRIME, AND PAINT (TYP)
EXISTING STEEL ANGLE
BRACING (TYP)
NEW 4" FOAM INSULATION
PER "INSULATION NOTES"
REPLACE EXISTING 2'-8" WIDE DOOR WITH
NEW 36" WIDE DOOR TO MEET EXIT EGRESS;
MODIFY CURTAIN WALL FRAME AS REQ'D TO
ACCOMMODATE NEW DOOR WIDTH (TYP)
GLAZING AS SPECIFIED
A1307
BID OPTION 003 : REPLACE EXISTING CURTAIN
WALL SYSTEM LIKE IN-KIND AS SPECIFIED
±4 9'-
8" (E
XI
ST
IN
G
- V
ER
IF
Y)
SHIM AS REQ'D
SHIM AS REQ'D
BACKER ROD AND
SEALANT (TYP)
SHIM AS REQ'D
EXISTING STEEL LINTEL (TYP)
CONTRACTOR SHALL TO FIELD VERIFY ALL DIMENSIONS AND DEPTHS OF EXISTING CURTAIN
WALL FRAMING AND GLAZING. CONTRACTOR SHALL CONSULT CONTRACTING OFFICER
IMMEDIATELY IF DISCREPANCIES ARE FOUND BETWEEN WHAT IS SHOWN IN THE DRAWINGS
AND SITE CONDITIONS, PRIOR TO SUBMITTAL OF SHOP DRAWINGS.
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
INSULATION NOTES
DEMOLITION WORK
A. CONTRACTOR SHALL REMOVE ALL EXISTING SPRAY
INSULATION ON CONCRETE DECK.
B. CONTRACTOR SHALL CLEAN DECK THOROUGHLY AS
REQUIRED BY NEW SPRAY FOAM INSTRUCTIONS WHERE
SHOWN ON THE PLANS PER THE LEGEND AND DETAILS.
C. CONTRACTOR SHALL REMOVE ALL EXISTING FIBERGLASS
INSULATION FROM CEILING LEVEL UP TO DECK ON ALL
EXTERIOR WALLS WHERE SHOWN ON THE PLANS PER THE
LEGEND.
D. CONTRACTOR SHALL PROVIDE PROTECTIVE WORK AREAS
TO KEEP DEMOLITION DEBRIS FROM GETTING INTO THE
INTERIOR WORK ENVIRONMENT AND FROM GETTING INTO
RETURN AIR HVAC SYSTEM PER 02 41 00. CONTRACTOR
SHALL PROVIDE FILTERING AT RETURN AIR SYSTEM.
CONTRACTOR SHALL REMOVE ALL LOOSE INSULATION
DEBRIS DUE TO DEMOLITION FROM WORK AREAS AND
SPACES ABOVE CEILING.
E. CONTRACTOR SHALL BE RESPONSIBLE FOR MOVING
FURNITURE AS REQUIRED TO PERFORM THE DEMO WORK
WHICH INCLUDES BUT IS NOT LIMITED TO THE REMOVAL OF
EXISTING FINISHES (INCLUDING CEILING TILES).
NEW WORK
A. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL
INSULATION AS SPECIFIED ON UNDERSIDE OF FLOOR / ROOF
DECK AS DESCRIBED HEREIN AND WHERE SHOWN ON THE
PLANS PER THE LEGEND.
B. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL
INSULATION AS SPECIFIED ON EXTERIOR WALLS AS
DESCRIBED HEREIN WHERE SHOWN ON THE PLANS PER THE
LEGEND.
C. CONTRACTOR SHALL APPLY INTUMESCENT COATING AS
SPECIFIED OVER ALL OF THE NEW SPRAY-APPLIED
INSULATION.
D. CONTRACTOR SHALL BE RESPONSIBLE FOR RETURNING
ALL FURNITURE THAT WAS MOVED IN ORDER TO PERFORM
THE SCOPE OF WORK. ANY FINISHES DAMAGED DURING THE
WORK SHALL BE REPLACED LIKE IN-KIND.
(BID OPTION 003)
(BID OPTION 003)(BID OPTION 003)(BID OPTION 003)
SCALE: 3"=1'-0"
3"0 6" 1'
8'0 2' 4' 12'
SCALE: 1/4"= 1'-0"
0 16'8'4' 24'
SCALE: 1/8"= 1'-0"
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
CHILDREN'S NUTRITION RESEARCH CENTER
CRITICAL UPGRADES
HOUSTON, TX
FLOOR LEVEL 4 - RCP
A1307 8 911/04/24
SME
CLR
DRL
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
2923-E
B. DEAN
XXX
D. CORDRAY
W. ROSS
HT
XET
TA
FO ET
S
R
EG
IS
SA
TC
E
IT
RERE A
CD
JE
RR
JAN.
NORTH
CORRIDOR
CORRIDOR
EQUIP
OFFICE
5053OFFICE
OFFICE
OFFICE
LAB
EAST CORRIDOR
TELE.
DARK RM.
SO
U
TH
C
O R
R
ID
O R
GLASS
WASH
OFFICE
PROCESS LAB.
VEST.
COLD RM.
COLD RM.
ELECT.
MALE
FEMALE
WEST CORRIDOR
ELEV. #7ELEV. #6
ELEV.
LOBBY
ELEV. #4ELEV. #5 ELEV. #3
SERV.
ELEV.
STORAGE
OFFICE
OFFICE
SECRETARY
& FILES 5082
OFFICE
OFFICE
STOR.
5000A
OFFICE
CONFERENCE
COFFEE
TECHNICIAN LOUNGE
OFFICE
EQUIP. LAB.
CORR.
CLOSET
5HC16
CHEM. LAB.
EXCREMENT
PROCESS'G.
STAIR C
LAB
LAB
LAB
CHEM. LAB.
5004 CHEM. LAB.
CHEM. LAB.
CHEM. LAB.
CHEM. LAB.
STAIR B OFFICE
OFFICE
STAIR A
FLOOR LEVEL 5 - REFLECTED CEILING PLAN
SCALE: 1/8"=1'-0"
A1308
PLAN
NORTH
INSULATION NOTES LEGEND
LINE OF EXTERIOR
WALL ABOVE
EXISTING CONCRETE
FLOOR / ROOF DECK
EXISTING PATIO,
DECK, OR ROOF EXISTING EXTERIOR CLADDING
EXISTING CMU
EXISTING CONCRETE BEAM
EXISTING CMU
LINE OF EXISTING
METAL STUDS
EXISTING FIBERGLASS
INSULATION
EXISTING ACOUSTICAL CEILING
EXISTING DRYWALL
NEW 4" FOAM INSULATION
PER "INSULATION NOTES"
DEMOLITION WORK
A. CONTRACTOR SHALL REMOVE ALL EXISTING SPRAY
INSULATION ON CONCRETE DECK.
B. CONTRACTOR SHALL CLEAN DECK THOROUGHLY AS
REQUIRED BY NEW SPRAY FOAM INSTRUCTIONS WHERE
SHOWN ON THE PLANS PER THE LEGEND AND DETAILS.
C. CONTRACTOR SHALL REMOVE ALL EXISTING FIBERGLASS
INSULATION FROM CEILING LEVEL UP TO DECK ON ALL
EXTERIOR WALLS WHERE SHOWN ON THE PLANS PER THE
LEGEND.
D. CONTRACTOR SHALL PROVIDE PROTECTIVE WORK AREAS
TO KEEP DEMOLITION DEBRIS FROM GETTING INTO THE
INTERIOR WORK ENVIRONMENT AND FROM GETTING INTO
RETURN AIR HVAC SYSTEM PER 02 41 00. CONTRACTOR
SHALL PROVIDE FILTERING AT RETURN AIR SYSTEM.
CONTRACTOR SHALL REMOVE ALL LOOSE INSULATION
DEBRIS DUE TO DEMOLITION FROM WORK AREAS AND
SPACES ABOVE CEILING.
E. CONTRACTOR SHALL BE RESPONSIBLE FOR MOVING
FURNITURE AS REQUIRED TO PERFORM THE DEMO WORK
WHICH INCLUDES BUT IS NOT LIMITED TO THE REMOVAL OF
EXISTING FINISHES (INCLUDING CEILING TILES).
REMOVE AND APPLY INSULATION ON CONCRETE DECK
PER "INSULATION NOTES"
REMOVE AND APPLY INSULATION ON EXTERIOR WALL
PER "INSULATION NOTES"
NEW APPLICATIONS
EXISTING
STUCCO / PLASTER
EXISTING CEILING FINISHES
EXISTING
GYP. BD.
EXISTING SACT
EXISTING
EXPOSED
NOTE: LIGHT FIXTURE LAYOUTS SHOWN IN
ARCHITECTURAL REFLECTED CEILING PLANS
ARE REPRESENTATIONAL OF EXISTING LIGHT
FIXTURE TYPES AND LAYOUTS.
NEW WORK
A. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL
INSULATION AS SPECIFIED ON UNDERSIDE OF FLOOR / ROOF
DECK AS DESCRIBED HEREIN AND WHERE SHOWN ON THE
PLANS PER THE LEGEND.
B. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL
INSULATION AS SPECIFIED ON EXTERIOR WALLS AS
DESCRIBED HEREIN WHERE SHOWN ON THE PLANS PER THE
LEGEND.
C. CONTRACTOR SHALL APPLY INTUMESCENT COATING AS
SPECIFIED OVER ALL OF THE NEW SPRAY-APPLIED
INSULATION.
D. CONTRACTOR SHALL BE RESPONSIBLE FOR RETURNING
ALL FURNITURE THAT WAS MOVED IN ORDER TO PERFORM
THE SCOPE OF WORK. ANY FINISHES DAMAGED DURING THE
WORK SHALL BE REPLACED LIKE IN-KIND.
INSULATION DETAIL
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
CHILDREN'S NUTRITION RESEARCH CENTER
CRITICAL UPGRADES
HOUSTON, TX
FLOOR LEVEL 5 - RCP
A1308 9 911/04/24
SME
CLR
DRL
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
2923-E
B. DEAN
XXX
D. CORDRAY
W. ROSS
0 16'8'4' 24'
SCALE: 1/8"= 1'-0"
4'
SCALE: 1/2"=1'-0"
0 1' 2' 8'
HT
XET
TA
FO ET
S
R
EG
IS
SA
TC
E
IT
RERE A
CD
JE
RR
ELEV. #6 ELEV. #7
ELECT.
TELE.
SOUTH
COLD RM.
DARK RM.
CORRIDOR
OFFICE
OVEN RM.
LAB
BIO LAB
LAB
LAB
BIO LAB
BIO LAB
BIO LAB
BIO LAB
LAB STORAGE
OFFICE
OFFICE
EQUIP
60636065
LAB
LAB
OFFICE
LAB
SEC'Y &
FILES
CORRIDOR
CLOSET
6HC12
WEST CORRIDOR
CHEM. LAB.
LEUKOCYTE
BIOLOGY
OFFICE
OFFICE
GLASS
WASH
MALE
FEMALE
JAN.
STORAGE
ELEV. #3
SERV. ELEV.
ELEV. #4ELEV. #5
ELEV. LOBBY
NORTH
CORRIDOR
STOR.
6000ACONFERENCE
COFFEE
ANTE RM.
CORRIDOR
TECHNICIAN
LOUNGE
EQUIP. LAB.
EQUIP. LAB.
OFFICE
OFFICE
OFFICE
OFFICE
STAIR C
SOUTH STAIR
CENTRAL STAIR
NORTH STAIR
CHEM. LAB.
EAST CORRIDOR
CHEM. LAB.
CHEM. LAB.
CHEM.
LAB.
FLOOR LEVEL 6 - REFLECTED CEILING PLAN
SCALE: 1/8"=1'-0"
A1309
PLAN
NORTH
INSULATION NOTES LEGEND
LINE OF EXTERIOR
WALL ABOVE
EXISTING CONCRETE
FLOOR / ROOF DECK
EXISTING PATIO,
DECK, OR ROOF EXISTING EXTERIOR CLADDING
EXISTING CMU
EXISTING CONCRETE BEAM
EXISTING CMU
LINE OF EXISTING
METAL STUDS
EXISTING FIBERGLASS
INSULATION
EXISTING ACOUSTICAL CEILING
EXISTING DRYWALL
NEW 4" FOAM INSULATION
PER "INSULATION NOTES"
DEMOLITION WORK
A. CONTRACTOR SHALL REMOVE ALL EXISTING SPRAY
INSULATION ON CONCRETE DECK.
B. CONTRACTOR SHALL CLEAN DECK THOROUGHLY AS
REQUIRED BY NEW SPRAY FOAM INSTRUCTIONS WHERE
SHOWN ON THE PLANS PER THE LEGEND AND DETAILS.
C. CONTRACTOR SHALL REMOVE ALL EXISTING FIBERGLASS
INSULATION FROM CEILING LEVEL UP TO DECK ON ALL
EXTERIOR WALLS WHERE SHOWN ON THE PLANS PER THE
LEGEND.
D. CONTRACTOR SHALL PROVIDE PROTECTIVE WORK AREAS
TO KEEP DEMOLITION DEBRIS FROM GETTING INTO THE
INTERIOR WORK ENVIRONMENT AND FROM GETTING INTO
RETURN AIR HVAC SYSTEM PER 02 41 00. CONTRACTOR
SHALL PROVIDE FILTERING AT RETURN AIR SYSTEM.
CONTRACTOR SHALL REMOVE ALL LOOSE INSULATION
DEBRIS DUE TO DEMOLITION FROM WORK AREAS AND
SPACES ABOVE CEILING.
E. CONTRACTOR SHALL BE RESPONSIBLE FOR MOVING
FURNITURE AS REQUIRED TO PERFORM THE DEMO WORK
WHICH INCLUDES BUT IS NOT LIMITED TO THE REMOVAL OF
EXISTING FINISHES (INCLUDING CEILING TILES).
REMOVE AND APPLY INSULATION ON CONCRETE DECK
PER "INSULATION NOTES"
REMOVE AND APPLY INSULATION ON EXTERIOR WALL
PER "INSULATION NOTES"
NEW APPLICATIONS
EXISTING
STUCCO / PLASTER
EXISTING CEILING FINISHES
EXISTING
GYP. BD.
EXISTING SACT
EXISTING
EXPOSED
NOTE: LIGHT FIXTURE LAYOUTS SHOWN IN
ARCHITECTURAL REFLECTED CEILING PLANS
ARE REPRESENTATIONAL OF EXISTING LIGHT
FIXTURE TYPES AND LAYOUTS.
NEW WORK
A. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL
INSULATION AS SPECIFIED ON UNDERSIDE OF FLOOR / ROOF
DECK AS DESCRIBED HEREIN AND WHERE SHOWN ON THE
PLANS PER THE LEGEND.
B. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL
INSULATION AS SPECIFIED ON EXTERIOR WALLS AS
DESCRIBED HEREIN WHERE SHOWN ON THE PLANS PER THE
LEGEND.
C. CONTRACTOR SHALL APPLY INTUMESCENT COATING AS
SPECIFIED OVER ALL OF THE NEW SPRAY-APPLIED
INSULATION.
D. CONTRACTOR SHALL BE RESPONSIBLE FOR RETURNING
ALL FURNITURE THAT WAS MOVED IN ORDER TO PERFORM
THE SCOPE OF WORK. ANY FINISHES DAMAGED DURING THE
WORK SHALL BE REPLACED LIKE IN-KIND.
INSULATION DETAIL
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
CHILDREN'S NUTRITION RESEARCH CENTER
CRITICAL UPGRADES
HOUSTON, TX
FLOOR LEVEL 6 - RCP
A1309 10 911/04/24
SME
CLR
DRL
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
2923-E
B. DEAN
XXX
D. CORDRAY
W. ROSS
0 16'8'4' 24'
SCALE: 1/8"= 1'-0"
4'
SCALE: 1/2"=1'-0"
0 1' 2' 8'
HT
XET
TA
FO ET
S
R
EG
IS
SA
TC
E
IT
RERE A
CD
JE
RR
ELEV. #3ELEV. #4ELEV. #5
GAS
ISOTOPE
LAB.
COMBUST
DIGEST
SAMPLE
PURIFICATION RM.
STORAGE
SERV. ELEV.
SEC'Y. & FILES
OFFICE
CORR
CLOSET
7HC11
BIOCHEM. LAB.
CHEM.
LAB.
LAB. STOR.
OFFICE
OFFICE
GAS
ISOTOPE
LAB.
EQUIP
OFFICE
OFFICE
T.I.M.S.
ANTE
ASHING
FILAMENT
CLEAN RM.
SAMPLE ISOL.
DERIVATION GC LAB.
SOUTH
CORRIDOR
REF. STOR.
CLOSET
7HC10
PROTOCOL
KIT. STOR.
REF. STOR.
7019DISP. RET
ELECT.
7063TELE.
JAN.
MALE
FEMALE
WEST CORRIDOR
PROCEDURE
BIO-CHEM. LAB.
G.C.M.S. II
COMPUTER
STORAGE
TECHNICIAN
LOUNGE
COFFEE
EQUIP. LAB.
STORAGE
CONFERENCE
NORTH
CORRIDOR ELEV. LOBBY
STOR.
7000A
OFFICE
CLOSET
7HC9CLOSET
7HC8
OFFICE
OFFICE
PAPER STOR.
E. CORRIDOR
OFFICE
OFFICE
CORR
G.C.M.S. I
FLOOR LEVEL 7 - REFLECTED CEILING PLAN
SCALE: 1/8"=1'-0"
A1310
PLAN
NORTH
INSULATION NOTES LEGEND
LINE OF EXTERIOR
WALL ABOVE
EXISTING CONCRETE
FLOOR / ROOF DECK
EXISTING PATIO,
DECK, OR ROOF EXISTING EXTERIOR CLADDING
EXISTING CMU
EXISTING CONCRETE BEAM
EXISTING CMU
LINE OF EXISTING
METAL STUDS
EXISTING FIBERGLASS
INSULATION
EXISTING ACOUSTICAL CEILING
EXISTING DRYWALL
NEW 4" FOAM INSULATION
PER "INSULATION NOTES"
DEMOLITION WORK
A. CONTRACTOR SHALL REMOVE ALL EXISTING SPRAY
INSULATION ON CONCRETE DECK.
B. CONTRACTOR SHALL CLEAN DECK THOROUGHLY AS
REQUIRED BY NEW SPRAY FOAM INSTRUCTIONS WHERE
SHOWN ON THE PLANS PER THE LEGEND AND DETAILS.
C. CONTRACTOR SHALL REMOVE ALL EXISTING FIBERGLASS
INSULATION FROM CEILING LEVEL UP TO DECK ON ALL
EXTERIOR WALLS WHERE SHOWN ON THE PLANS PER THE
LEGEND.
D. CONTRACTOR SHALL PROVIDE PROTECTIVE WORK AREAS
TO KEEP DEMOLITION DEBRIS FROM GETTING INTO THE
INTERIOR WORK ENVIRONMENT AND FROM GETTING INTO
RETURN AIR HVAC SYSTEM PER 02 41 00. CONTRACTOR
SHALL PROVIDE FILTERING AT RETURN AIR SYSTEM.
CONTRACTOR SHALL REMOVE ALL LOOSE INSULATION
DEBRIS DUE TO DEMOLITION FROM WORK AREAS AND
SPACES ABOVE CEILING.
E. CONTRACTOR SHALL BE RESPONSIBLE FOR MOVING
FURNITURE AS REQUIRED TO PERFORM THE DEMO WORK
WHICH INCLUDES BUT IS NOT LIMITED TO THE REMOVAL OF
EXISTING FINISHES (INCLUDING CEILING TILES).
REMOVE AND APPLY INSULATION ON CONCRETE DECK
PER "INSULATION NOTES"
REMOVE AND APPLY INSULATION ON EXTERIOR WALL
PER "INSULATION NOTES"
NEW APPLICATIONS
EXISTING
STUCCO / PLASTER
EXISTING CEILING FINISHES
EXISTING
GYP. BD.
EXISTING SACT
EXISTING
EXPOSED
NOTE: LIGHT FIXTURE LAYOUTS SHOWN IN
ARCHITECTURAL REFLECTED CEILING PLANS
ARE REPRESENTATIONAL OF EXISTING LIGHT
FIXTURE TYPES AND LAYOUTS.
NEW WORK
A. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL
INSULATION AS SPECIFIED ON UNDERSIDE OF FLOOR / ROOF
DECK AS DESCRIBED HEREIN AND WHERE SHOWN ON THE
PLANS PER THE LEGEND.
B. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL
INSULATION AS SPECIFIED ON EXTERIOR WALLS AS
DESCRIBED HEREIN WHERE SHOWN ON THE PLANS PER THE
LEGEND.
C. CONTRACTOR SHALL APPLY INTUMESCENT COATING AS
SPECIFIED OVER ALL OF THE NEW SPRAY-APPLIED
INSULATION.
D. CONTRACTOR SHALL BE RESPONSIBLE FOR RETURNING
ALL FURNITURE THAT WAS MOVED IN ORDER TO PERFORM
THE SCOPE OF WORK. ANY FINISHES DAMAGED DURING THE
WORK SHALL BE REPLACED LIKE IN-KIND.
INSULATION DETAIL
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
CHILDREN'S NUTRITION RESEARCH CENTER
CRITICAL UPGRADES
HOUSTON, TX
FLOOR LEVEL 7 - RCP
A1310 11 911/04/24
SME
CLR
DRL
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
2923-E
B. DEAN
XXX
D. CORDRAY
W. ROSS
0 16'8'4' 24'
SCALE: 1/8"= 1'-0"
4'
SCALE: 1/2"=1'-0"
0 1' 2' 8'
HT
XET
TA
FO ET
S
R
EG
IS
SA
TC
E
IT
RERE A
CD
JE
RR
CHEM.
LAB.
CHEM. LAB.
EQUIP. LAB.
TECHNICIAN
LOUNGE
COFFEE
CHEM. LAB.
STOR.
CONFERENCE
STOR.
OFFICE
OFFICE
OFFICE
OFFICE
COMPUTER
CHEM. LAB. CHEM.LAB.
TELE.
SERV.
WOMEN
MEN
ELECT.
CHEM. LAB.CHEM. LAB.CHEM. LAB.
STORAGE
JAN.
CHEM. LAB. CHEM. LAB.
CHEM. LAB.
FREEZERS
SOUTH
STORAGE
DARK RM.
COLD RM.
GLASS
WASH
OFFICE
OFFICE
EQUIP.
LAB.
COLD RM.
LAB.
CHEM.
LAB.
OFFICEGRAD.
STUDENT
& FILES
SECRETARY
ELEV. 6 ELEV. 7 ELEV. 3
ELEV. 6
ELEV 7
EAST CORRIDOR
NORTH
CORRIDOR
CORRIDOR
WEST CORRIDOR
8010 8014
8006 80088004 8012
8000A
8064 8052 8056 80548060 8058
80518024
8017 8022
8074 8009
ELEVATOR LOBBY
CORR
ELEV.
CLOSET
8HC6
OFFICE
SPEC.
PROC. LAB.
CLOSET
8HC7
CORR
FLOOR LEVEL 8 - REFLECTED CEILING PLAN
SCALE: 1/8"=1'-0"
A1311
PLAN
NORTH
INSULATION NOTES LEGEND
LINE OF EXTERIOR
WALL ABOVE
EXISTING CONCRETE
FLOOR / ROOF DECK
EXISTING PATIO,
DECK, OR ROOF EXISTING EXTERIOR CLADDING
EXISTING CMU
EXISTING CONCRETE BEAM
EXISTING CMU
LINE OF EXISTING
METAL STUDS
EXISTING FIBERGLASS
INSULATION
EXISTING ACOUSTICAL CEILING
EXISTING DRYWALL
NEW 4" FOAM INSULATION
PER "INSULATION NOTES"
DEMOLITION WORK
A. CONTRACTOR SHALL REMOVE ALL EXISTING SPRAY
INSULATION ON CONCRETE DECK.
B. CONTRACTOR SHALL CLEAN DECK THOROUGHLY AS
REQUIRED BY NEW SPRAY FOAM INSTRUCTIONS WHERE
SHOWN ON THE PLANS PER THE LEGEND AND DETAILS.
C. CONTRACTOR SHALL REMOVE ALL EXISTING FIBERGLASS
INSULATION FROM CEILING LEVEL UP TO DECK ON ALL
EXTERIOR WALLS WHERE SHOWN ON THE PLANS PER THE
LEGEND.
D. CONTRACTOR SHALL PROVIDE PROTECTIVE WORK AREAS
TO KEEP DEMOLITION DEBRIS FROM GETTING INTO THE
INTERIOR WORK ENVIRONMENT AND FROM GETTING INTO
RETURN AIR HVAC SYSTEM PER 02 41 00. CONTRACTOR
SHALL PROVIDE FILTERING AT RETURN AIR SYSTEM.
CONTRACTOR SHALL REMOVE ALL LOOSE INSULATION
DEBRIS DUE TO DEMOLITION FROM WORK AREAS AND
SPACES ABOVE CEILING.
E. CONTRACTOR SHALL BE RESPONSIBLE FOR MOVING
FURNITURE AS REQUIRED TO PERFORM THE DEMO WORK
WHICH INCLUDES BUT IS NOT LIMITED TO THE REMOVAL OF
EXISTING FINISHES (INCLUDING CEILING TILES).
REMOVE AND APPLY INSULATION ON CONCRETE DECK
PER "INSULATION NOTES"
REMOVE AND APPLY INSULATION ON EXTERIOR WALL
PER "INSULATION NOTES"
NEW APPLICATIONS
EXISTING
STUCCO / PLASTER
EXISTING CEILING FINISHES
EXISTING
GYP. BD.
EXISTING SACT
EXISTING
EXPOSED
NOTE: LIGHT FIXTURE LAYOUTS SHOWN IN
ARCHITECTURAL REFLECTED CEILING PLANS
ARE REPRESENTATIONAL OF EXISTING LIGHT
FIXTURE TYPES AND LAYOUTS.
NEW WORK
A. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL
INSULATION AS SPECIFIED ON UNDERSIDE OF FLOOR / ROOF
DECK AS DESCRIBED HEREIN AND WHERE SHOWN ON THE
PLANS PER THE LEGEND.
B. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL
INSULATION AS SPECIFIED ON EXTERIOR WALLS AS
DESCRIBED HEREIN WHERE SHOWN ON THE PLANS PER THE
LEGEND.
C. CONTRACTOR SHALL APPLY INTUMESCENT COATING AS
SPECIFIED OVER ALL OF THE NEW SPRAY-APPLIED
INSULATION.
D. CONTRACTOR SHALL BE RESPONSIBLE FOR RETURNING
ALL FURNITURE THAT WAS MOVED IN ORDER TO PERFORM
THE SCOPE OF WORK. ANY FINISHES DAMAGED DURING THE
WORK SHALL BE REPLACED LIKE IN-KIND.
INSULATION DETAIL
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.