Amendment 3 Attachment 5 PLUMBING REVISIONS.pdf

PDF 6 MB Posted

Attached to
CNRC Critical Upgrades to Insulation, Piping & HVAC
Solicitation number
12805B24R0012
Issued by

About this file

This document appears to be plumbing drawings and specifications for the CNRC Critical Upgrades to Insulation, Piping & HVAC project in Houston, TX. The key details are:

The project involves removing and replacing existing cast iron storm drain piping as indicated on the drawings. The work must be coordinated with insulation repairs listed on the architectural drawings and will need to be performed in a way that minimizes disruption to the occupied facility. The drawings provide detailed plans for the new storm drain piping layout on each floor, including cleanouts, deck drains, and riser diagrams. All new storm drain piping is required to be insulated.

The related federal contract opportunity is a 100% small business set-aside solicitation with a NAICS code of 236220 - Commercial and Institutional Building Construction. The magnitude of the project is between $1-5 million. Vendors must be in an active status in SAM.gov at the time of proposal submission.

View the file

Other files

Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GENERAL NOTES

1. PLUMBING WORK IN THIS PROJECT CONSISTS OF REMOVING AND REPLACING THE EXISTING CAST IRON

STORM DRAIN PIPING AS INDICATED.

2. NOTE: COORDINATE WITH INSULATION REPAIRS LISTED ON ARCHITECTURAL DRAWINGS. STORM DRAIN PIPING REPLACEMENT MUST BE COMPLETED AFTER INSULATION REPAIRS HAVE BEEN CONSTRUCTED.

3. THIS PROJECT IS A RENOVATION OF AN EXISTING FACILITY. IT IS THE CONTRACTOR'S RESPONSIBILITY TO FIELD VERIFY ALL DIMENSIONS PRIOR TO FABRICATION OR PURCHASE OF EQUIPMENT, MATERIALS, AND ASSEMBLIES. ANY DEVIATIONS SHALL BE BROUGHT TO THE CONTRACTING OFFICERS ATTENTION FOR RESOLUTION BEFORE PROCEEDING WITH ANY CONSTRUCTION, FABRICATION, OR EQUIPMENT PURCHASE.

4. THE FACILITY WILL REMAIN ACTIVE WHILE CONSTRUCTION WORK IS IN PROGRESS. ALL WORK SHALL BE

PERFORMED SO THAT IT MINIMIZES DISRUPTION OF THE OPERATION OF THE FACILITY.

5. WORK SEQUENCING WILL BE REQUIRED TO ALLOW THE FACILITY TO REMAIN OCCUPIED AND OPERATIONAL DURING THE PROJECT. ALL WORK SHALL BE PERFORMED SO THAT IT MINIMIZES DISRUPTION OF THE

OPERATION OF THE FACILITY.

6. PROVIDE SAFETY BARRIERS AND FOLLOW ALL SAFETY REQUIREMENTS OF THE OWNER. TAKE PRECAUTIONS

TO ENSURE THE SAFETY OF ALL PERSONNEL.

7. THESE DRAWINGS ARE SCHEMATIC IN NATURE AND ARE NOT INTENDED TO SHOW ALL POSSIBLE CONDITIONS (DO NOT SCALE FOR LOCATIONS). THE CONTRACTOR SHALL PROVIDE A COMPLETE AND FUNCTIONAL STORM

DRAIN SYSTEM AS INDICATED.

8. CONTRACTOR SHALL EMPLOY WORKMEN WHO ARE TRAINED AND EXPERIENCED IN NECESSARY SKILLS TO

PERFORM DEMOLITION WORK.

9. CONTRACTOR SHALL USE APPROPRIATE TOOLS AND SHALL NOT IMPART EXCESSIVE VIBRATIONS TO THE

EXISTING STRUCTURE OR OTHER BUILDING COMPONENTS.

10. COORDINATE PIPING WITH EXISTING STRUCTURAL, ELECTRICAL, PLUMBING, AND COMMUNICATION. MAKE OFFSETS AND TRANSITIONS TO COORDINATE WITH OTHER TRADES WITHOUT ANY ADDITIONAL EXPENSE TO

THE OWNER. CONTRACTOR SHALL PROVIDE COORDINATION DRAWINGS OF TRADES.

11. ALL STORM DRAIN PIPING SHALL BE INSULATED COMPLETELY. PIPING INSULATION SHALL CONFORM TO

REQUIREMENTS OF NFPA 90A.

12. PROVIDE HANGERS AND SUPPORTS FOR NEW STORM DRAIN PIPING.

ABBREVIATIONS GENERAL DEMOLITION NOTES

1. THE DEMOLITION PLAN AND EXISTING CONDITIONS SHOWN ARE APPROXIMATE AND ARE TO BE FIELD

VERIFIED. ITEMS TO BE REMOVED ARE DENOTED BY HATCHING.

2. DEMOLITION SHALL INCLUDE, BUT IS NOT LIMITED TO, THE ITEMS IDENTIFIED. THE CONTRACTOR SHALL COORDINATE ALL REQUIRED RENOVATION AND NEW CONSTRUCTION WITH THE EXISTING BUILDING TO

IDENTIFY THE TOTAL EXTENT OF THE DEMOLITION WORK REQUIRED.

3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DEMOLITION AND REMOVAL OF ALL EXISTING BUILDING COMPONENTS, MATERIALS, EQUIPMENT, AND APPURTENANCES AS REQUIRED TO BUILD, ERECT, INSTALL, OR

ACCOMMODATE ALL NEW CONSTRUCTION.

4. IN THE EVENT THE CONTRACTOR ENCOUNTERS ON THE SITE MATERIAL BELIEVED TO BE ASBESTOS, LEAD-BASED PAINT, OR ANY OTHER HAZARDOUS MATERIAL WHICH HAS NOT BEEN RENDERED HARMLESS, THE CONTRACTOR SHALL IMMEDIATELY STOP WORK AND REPORT THE CONDITION TO THE CONTRACTING

OFFICER.

5. THE CONTRACTOR IS RESPONSIBLE FOR THE ERECTION, MAINTENANCE, AND REMOVAL OF ALL

CONSTRUCTION ASSISTANCE DEVICES SUCH AS SCAFFOLDING AND BARRIERS.

6. DEMOLISH ALL EXISTING PIPE HANGERS FOR STORM DRAIN PIPING BEING REMOVED.

ACCU AIR COOLED CONDENSING UNIT GAL. GALLONS

AD ACCESS DOOR GALV. GALVANIZED

A.F.F. ABOVE FINISHED FLOOR GEN. GENERAL

A.F.G. ABOVE FINISHED GRADE G.P.H. GALLONS PER HOUR

AHU AIR HANDLING UNIT G.P.M. GALLONS PER MINUTE

AP ACCESS PANEL HR. HOUR

APPROX. APPROXIMATE I.D. INSIDE DIMENSION

ARCH ARCHITECTURAL IN INCHES

CD CEILING DIFFUSER K.W. KILOWATT

CL CENTER LINE L LOUVER

C.O. CLEAN OUT LB POUND

C.V. CHECK VALVE LD LINEAR DIFFUSER

CFM CUBIC FEET PER MINUTE LAT LEAVING AIR TEMPERATURE

CLG CEILING LWT LEAVING WATER TEMPERATURE

CONC. CONCRETE MAU MAKEUP AIR UNIT

CONT. CONTINUATION MAX. MAXIMUM

CP CONDENSER WATER PUMP MFR. MANUFACTURER

CHWR CHILLED WATER RETURN MECH. MECHANICAL

CHWS CHILLED WATER SUPPLY MIN. MINIMUM OR MINUTE

CWP CHILLED WATER PUMP NC NORMALLY CLOSED

CWR CONDENSER WATER RETURN NO NORMALLY OPENED

CWS CONDENSER WATER SUPPLY NPT NATIONAL PIPE THREAD

CT COOLING TOWER Ø DIAMETER

CTE CONNECT TO EXISTING O/A OUTSIDE AIR

CU CONDENSING UNIT O.D. OUTSIDE DIMENSION

dB DECIBELS PH PHASE

DIFF. DIFFUSER PRV PRESSURE REDUCING VALVE

DN. DOWN PSI POUNDS PER SQUARE INCH

DET. DETAIL R/A RETURN AIR

DIA. DIAMETER RAD RADIUS

DIM. DIMENSION RAR RETURN AIR REGISTER

DWG. DRAWING RED. REDUCER

EA. EACH REINF. REINFORCING

E/A EXHAUST AIR REQ'D. REQUIRED

EAG EXHAUST AIR GRILLE RPM REVOLUTIONS PER MINUTE

EAT ENTERING AIR TEMPERATURE RTU ROOF TOP UNIT

EF EXHAUST FAN S/A SUPPLY AIR

EWT ENTERING WATER TEMPERATURE SAG SUPPLY AIR GRILLE

ECC ECCENTRIC SC STEAM CONVERTER

EFF EFFICIENCY SEN SENSIBLE

ELEC. ELECTRICAL SF SQUARE FEET

ELEV. ELEVATION SQ. SQUARE

ET EXPANSION TANK TA TRANSFER AIR

F FAHRENHEIT TEMP TEMPERATURE

FLR FLOOR TH THERMOMETER

FDC FIRE DEPARTMENT CONNECTION TYP. TYPICAL

F/SD FIRE/SMOKE DAMPER U.N.P. UNLESS NOTED OTHERWISE

FPM FEET PER MINUTE UC UNIT COOLER

FCO FLOOR CLEAN OUT UH UNIT HEATER

FCU FAN COIL UNIT VA VALVE

UH UNIT HEATER VAV VARIABLE AIR VOLUME (BOX)

FT. FOOT V VOLTS

FIN. FINISHED V.T.R. VENT THRU ROOF

G NATURAL GAS PIPING W/ WITH

GA. GAUGE WT WEIGHT

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

c P.A.

FIRMTHE

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

USDA AGRICULTURAL RESEARCH SERVICE

CHILDREN'S NUTRITION RESEARCH CENTER

CRITICAL UPGRADES

HOUSTON, TX

PLUMBING ABBREVIATIONS

AND NOTES

P-001 17 911/04/24

SME

SME

DRL

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

2923-E

B. DEAN

XXX

D. CORDRAY

W. ROSS

REVISED PIPE MATERIAL4/23/241 SME

0 16'8'4' 24'

SCALE: 1/8"= 1'-0"

SCALE:

BAEMENT LEVEL 3 STORM

DRAIN PIPING FLOOR PLAN

1/8"=1'-0"

P-101

CO

CO EXIST. 4" UP

6" UP

EXIST.

1-1/2" UP

6" DOWN

TO SUMP

CO

PLUMBING LEGEND:

CO CLEANOUT

DD DECK DRAIN

EXIST. EXISTING

FD FLOOR DRAIN

HD HUB DRAIN

PAD PLANTING AREA DRAIN

TYP. TYPICAL

EXIST. STORM DRAIN

NEW STORM DRAIN PIPING

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

c P.A.

FIRMTHE

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

USDA AGRICULTURAL RESEARCH SERVICE

CHILDREN'S NUTRITION RESEARCH CENTER

CRITICAL UPGRADES

HOUSTON, TX

BASEMENT LEVEL 3 STORM

DRAIN PIPING FLOOR PLAN

P-101 28 911/04/24

SME

SME

DRL

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

2923-E

XXX

XXX

XXX

XXX

PLAN

NORTH

SCALE:

BASEMENT LEVEL 2 STORM

DRAIN PIPING FLOOR PLAN

1/8"=1'-0"

P-102

6"

1-1/2" UP

6" UP

EXIST. 4"

UP

EXIST. 6"

UP TO

TRENCH

CO

EXIST. 4" UP

EXIST. 4"

DOWN

3" UP

PLUMBING LEGEND:

CO CLEANOUT

DD DECK DRAIN

EXIST. EXISTING

FD FLOOR DRAIN

HD HUB DRAIN

PAD PLANTING AREA DRAIN

TYP. TYPICAL

EXIST. STORM DRAIN

NEW STORM DRAIN PIPING

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

c P.A.

FIRMTHE

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

USDA AGRICULTURAL RESEARCH SERVICE

CHILDREN'S NUTRITION RESEARCH CENTER

CRITICAL UPGRADES

HOUSTON, TX

BASEMENT LEVEL 2 STORM

DRAIN PIPING FLOOR PLAN

P-102 29 911/04/24

SME

SME

DRL

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

2923-E

XXX

XXX

XXX

XXX

3" UP

CO

PLAN

NORTH

SCALE:

BASEMENT LEVEL 1 STORM

DRAIN PIPING FLOOR PLAN

1/8"=1'-0"

P-103

10"

EXIST.

12"EXIST. 12"

6"

EXIST. 4" FORCED

WASTE WATER

CO

CO

8" UP

EXIST.

12" UP

EXIST. 4" EXIST. 2"

EXIST. 4"

EXIST.

1-1/2"

12" UP

12" UP EXIST.

4" UP

6" UP

CO

CO

CO

PLUMBING LEGEND:

CO CLEANOUT

DD DECK DRAIN

EXIST. EXISTING

FD FLOOR DRAIN

HD HUB DRAIN

PAD PLANTING AREA DRAIN

TYP. TYPICAL

EXIST. STORM DRAIN

NEW STORM DRAIN PIPING

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

c P.A.

FIRMTHE

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

USDA AGRICULTURAL RESEARCH SERVICE

CHILDREN'S NUTRITION RESEARCH CENTER

CRITICAL UPGRADES

HOUSTON, TX

BASEMENT LEVEL 1 STORM

DRAIN PIPING FLOOR PLAN

P-103 30 911/04/24

SME

SME

DRL

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

2923-E

XXX

XXX

XXX

XXX

PLAN

NORTH

EXIST. 3" PAD

EXIST. 6" FD-4

EXIST. 3" PAD

SCALE:

LEVEL 1 STORM DRAIN

PIPING FLOOR PLAN

1/8"=1'-0"

P-104

4" UP EXIST.

4" UP

EXIST.

4" UP

4" UP

EXIST.

4" UP

EXIST.

4" UP

EXIST. 4"

EXIST. 4" EXIST. 6"

EXIST. 6"

8" DOWN

3" UP EXIST.

3" UP

EXIST.

3" UP

EXIST.

3" UP

EXIST.

3" UP

EXIST.

3" UP

CO CO

PLUMBING LEGEND:

CO CLEANOUT

DD DECK DRAIN

EXIST. EXISTING

FD FLOOR DRAIN

HD HUB DRAIN

PAD PLANTING AREA DRAIN

TYP. TYPICAL

EXIST. STORM DRAIN

NEW STORM DRAIN PIPING

4"

4"

4"

12" UP

4" UP4" UP 4" UP

3" UP3" UP3" UP3" UP3" UP3" UP

4" UP

CO

COCO

12" UP

4" UP

CO

KEYED NOTES

1. PROVIDE PIPING TO EXISTING ROOF DRAIN

ABOVE.

2. PROVIDE VERTICAL STORM DRAIN PIPING TO

FLOORS ABOVE/BELOW.

GENERAL NOTES

1. PIPING SHOWN IS ABOVE CEILING, INDICATING

DRAINS FOR FLOOR ABOVE.

2. REMOVE AND REINSTALL EXISTING CEILINGS,

LIGHTS AND BUILDING SYSTEMS REQUIRED TO

PERFORM THE WORK.

3. PROVIDE INSULATION ON ALL STORM DRAIN

PIPING BEING INSTALLED.

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

c P.A.

FIRMTHE

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

USDA AGRICULTURAL RESEARCH SERVICE

CHILDREN'S NUTRITION RESEARCH CENTER

CRITICAL UPGRADES

HOUSTON, TX

LEVEL 1 STORM DRAIN

PIPING FLOOR PLAN

P-104 31 911/04/24

SME

SME

DRL

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

2923-E

B. DEAN

XXX

D. CORDRAY

W. ROSS

PLAN

NORTH

SCALE:

LEVEL 2 STORM DRAIN

PIPING FLOOR PLAN

1/8"=1'-0"

P-105PLUMBING LEGEND:

CO CLEANOUT

DD DECK DRAIN

EXIST. EXISTING

FD FLOOR DRAIN

HD HUB DRAIN

PAD PLANTING AREA DRAIN

TYP. TYPICAL

EXIST. STORM DRAIN

NEW STORM DRAIN PIPING

8"

8" 10"

12"

CO

EXIST.

3" UP EXIST.

3" UP

EXIST.

3" UP

EXIST.

3" UP

3" UP

CO

3" UP

3" UP3" UP3" UP3" UP3" UP3" UP

CO

4" UP 4" UP

4" DOWN

4" UP

4"4"

4"

EXIST. 4"EXIST. 4"EXIST. 3"

EXIST.

4" UP

EXIST.

4" UP

EXIST.

4" UP

10" UP

CO

CO

CO

12" UP

12" DOWN

CO

EXIST. 4"

DOWN

8" UP

10" UP

EXIST.

3" UP

4" UP 4" UP

1 1

12"

KEYED NOTES

1. PROVIDE PIPING TO EXISTING ROOF DRAIN

ABOVE.

2. PROVIDE VERTICAL STORM DRAIN PIPING UP TO

FLOORS ABOVE.

GENERAL NOTES

1. PIPING SHOWN IS ABOVE CEILING, INDICATING

DRAINS FOR FLOOR ABOVE.

2. REMOVE AND REINSTALL EXISTING CEILINGS,

LIGHTS AND BUILDING SYSTEMS REQUIRED TO

PERFORM THE WORK.

3. PROVIDE INSULATION ON ALL STORM DRAIN

PIPING BEING INSTALLED.

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

c P.A.

FIRMTHE

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

USDA AGRICULTURAL RESEARCH SERVICE

CHILDREN'S NUTRITION RESEARCH CENTER

CRITICAL UPGRADES

HOUSTON, TX

LEVEL 2 STORM DRAIN

PIPING FLOOR PLAN

P-105 32 911/04/24

SME

SME

DRL

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

2923-E

B. DEAN

XXX

D. CORDRAY

W. ROSS

PLAN

NORTH

EXIST.

3" HD

EXIST.

3" HD

EXIST.

3" HD

EXIST.

3" HD

EXIST.

3" HD

EXIST.

3" HD

EXIST.

3" HD

EXIST.

3" HD

EXIST.

3" HD

EXIST.

3" HD

EXIST.

4" DD-1

EXIST.

4" DD-1

EXIST.

4" DD-1

EXIST.

4" DD-1

EXIST.

4" DD-1

EXIST.

4" DD-1EXIST.

4" DD-1

EXIST.

4" DD-1

EXIST.

4" DD-1

EXIST.

3" HD

EXIST.

3" HD

REVISED PIPE MATERIAL4/23/241 SME

SCALE:

LEVEL 3 STORM DRAIN

PIPING FLOOR PLAN

1/8"=1'-0"

P-106PLUMBING LEGEND:

CO CLEANOUT

DD DECK DRAIN

EXIST. EXISTING

FD FLOOR DRAIN

HD HUB DRAIN

PAD PLANTING AREA DRAIN

TYP. TYPICAL

EXIST. STORM DRAIN

NEW STORM DRAIN PIPING

6" UP

8"

6" UP

4" UP

3" UP

4" UP4" UP

ABOVE CEILING

(TYP.)

6"

4" UP

4" UP

6" UP

10"

12"

12" UP

6" UP8"

4" UP

6" UP

6"

6" UP

8"

10"

6" UP

8"

3" UP

6" UP

8"

6" UP 8"

8" DOWN

6" UP

10" DOWN

10"

10" DOWN

6" UP

6" UP

10"

3" UP8"

3" UP

3" UP

3"

3" UP

8"

6" UP

6"

8"

6"

3" UP

3" UP

4" UP

6"

6" UP

6" UP

6" UP

CO

CO

CO

CO

CO

CO

CO

CO

CO

ABOVE CEILING

CO

12" UP

6" UP

1 2

1 1

1 1

8"

KEYED NOTES

1. PROVIDE PIPING TO EXISTING ROOF DRAIN

ABOVE.

2. PROVIDE VERTICAL STORM DRAIN PIPING UP TO

FLOORS ABOVE.

GENERAL NOTES

1. PIPING SHOWN IS ABOVE CEILING, INDICATING

DRAINS FOR FLOOR ABOVE.

2. REMOVE AND REINSTALL EXISTING CEILINGS,

LIGHTS AND BUILDING SYSTEMS REQUIRED TO

PERFORM THE WORK.

3. PROVIDE INSULATION ON ALL STORM DRAIN

PIPING BEING INSTALLED.

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

c P.A.

FIRMTHE

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

USDA AGRICULTURAL RESEARCH SERVICE

CHILDREN'S NUTRITION RESEARCH CENTER

CRITICAL UPGRADES

HOUSTON, TX

LEVEL 3 STORM DRAIN

PIPING FLOOR PLAN

P-106 33 911/04/24

SME

SME

DRL

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

2923-E

B. DEAN

XXX

D. CORDRAY

W. ROSS

PLAN

NORTH

EXIST.

3" HD

EXIST.

4" DD-1

EXIST.

4" DD-1

EXIST.

4" DD-1

EXIST.

4" DD-1

EXIST.

4" DD-1

EXIST.

3" HD

EXIST.

3" HD

EXIST.

3" HD

EXIST.

3" HD

EXIST.

4" DD-1EXIST.

4" DD-1

EXIST.

3" HD

EXIST.

3" HD

EXIST.

3" HD

EXIST.

3" HD

EXIST.

3" HD

EXIST.

3" HD

EXIST.

3" HD

EXIST.

3" HD

REVISED PIPE MATERIAL4/23/241 SME

SCALE:

LEVEL 4 STORM DRAIN

PIPING FLOOR PLAN

1/8"=1'-0"

P-107

12" DOWN8" UP 12"

8" UP

PLUMBING LEGEND:

CO CLEANOUT

DD DECK DRAIN

EXIST. EXISTING

FD FLOOR DRAIN

HD HUB DRAIN

PAD PLANTING AREA DRAIN

TYP. TYPICAL

EXIST. STORM DRAIN

NEW STORM DRAIN PIPING

KEYED NOTES

1. PROVIDE PIPING TO EXISTING ROOF DRAIN

ABOVE.

GENERAL NOTES

1. PIPING SHOWN IS ABOVE CEILING, INDICATING

DRAINS FOR FLOOR ABOVE.

2. REMOVE AND REINSTALL EXISTING CEILINGS,

LIGHTS AND BUILDING SYSTEMS REQUIRED TO

PERFORM THE WORK.

3. PROVIDE INSULATION ON ALL STORM DRAIN

PIPING BEING INSTALLED.

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

c P.A.

FIRMTHE

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

USDA AGRICULTURAL RESEARCH SERVICE

CHILDREN'S NUTRITION RESEARCH CENTER

CRITICAL UPGRADES

HOUSTON, TX

LEVEL 4 STORM DRAIN

PIPING FLOOR PLAN

P-107 34 911/04/24

SME

SME

DRL

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

2923-E

B. DEAN

XXX

D. CORDRAY

W. ROSS

PLAN

NORTH

6" DD-1 4" DD-16" DD-1

6" DD-16" DD-1

6" DD-1

6" DD-1

6" DD-1

6" DD-1

3" PAD-1

6" DD-1

6" DD-1

6" DD-1 6" DD-1

6" DD-1 6" DD-1

6" DD-1

6" DD-1

6" DD-1

6" DD-1

12" DN

4" DD-1

4" DD-1

4" DD-1

4" DD-1

4" DD-1

4" DD-1

3" PAD-1

3" PAD-1

3" PAD-1 3" PAD-1 3" PAD-1

3" PAD-1

3" PAD-1

8" UP 12"

8"

6" DD-1

REVISED PIPE MATERIAL4/23/241 SME

SCALE:

LEVEL 10 STORM DRAIN

PIPING FLOOR PLAN

1/8"=1'-0"

P-113PLUMBING LEGEND:

CO CLEANOUT

DD DECK DRAIN

EXIST. EXISTING

FD FLOOR DRAIN

HD HUB DRAIN

PAD PLANTING AREA DRAIN

TYP. TYPICAL

EXIST. STORM DRAIN

NEW STORM DRAIN PIPING

4" UP

6"

4" UP

8" ABOVE

CEILING

(TYP.)

8"

4" UP

8"

CO

CO

CO

CO

4" UP

8" UP

8" UP

KEYED NOTES

1. PROVIDE PIPING TO EXISTING ROOF DRAIN

ABOVE.

2. PROVIDE VERTICAL STORM DRAIN PIPING UP TO

FLOORS ABOVE.

GENERAL NOTES

1. PIPING SHOWN IS ABOVE CEILING, INDICATING

DRAINS FOR FLOOR ABOVE.

2. REMOVE AND REINSTALL EXISTING CEILINGS,

LIGHTS AND BUILDING SYSTEMS REQUIRED TO

PERFORM THE WORK.

3. PROVIDE INSULATION ON ALL STORM DRAIN

PIPING BEING INSTALLED.

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

c P.A.

FIRMTHE

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

USDA AGRICULTURAL RESEARCH SERVICE

CHILDREN'S NUTRITION RESEARCH CENTER

CRITICAL UPGRADES

HOUSTON, TX

LEVEL 10 STORM DRAIN

PIPING FLOOR PLAN

P-113 35 911/04/24

SME

SME

DRL

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

2923-E

B. DEAN

XXX

D. CORDRAY

W. ROSS

PLAN

NORTH

REVISED PIPE MATERIAL4/23/241 SME

AC PANEL LOCATION:

BREAKER #:

AC PANEL LOCATION:

BREAKER #:

0 16'8'4' 24'

SCALE: 1/8"= 1'-0"

SCALE:

LEVEL 11 STORM DRAIN

PIPING FLOOR PLAN

1/8"=1'-0"

P-114PLUMBING LEGEND:

CO CLEANOUT

DD DECK DRAIN

EXIST. EXISTING

FD FLOOR DRAIN

HD HUB DRAIN

PAD PLANTING AREA DRAIN

TYP. TYPICAL

EXIST. STORM DRAIN

NEW STORM DRAIN PIPING

ROUTE 8" STORM

DRAIN IN CHASE

TO FLOORS

BELOW

4" UP

4" UP3" UP

3" UP 3" UP

4" UP

4" UP

6" UP

4" UP4" UP

4" UP4" UP

4" UP

4" UP

4" UP 4" UP

8"8"6"6"6"6"4"

ABOVE

CEILING

(TYP.)

4" ABOVE CEILING

4"6"6"6"6"

CO

CO

CO

CO

4" UP

3" UP 3" UP 3" UP

3" UP 3" UP 3" UP 3" UP

1 1

11111

1 1

ROUTE 8" STORM

DRAIN IN CHASE

TO FLOORS

BELOW

KEYED NOTES

1. PROVIDE PIPING TO EXISTING ROOF DRAIN

ABOVE.

2. PROVIDE VERTICAL STORM DRAIN PIPING UP TO

FLOORS ABOVE.

GENERAL NOTES

1. PIPING SHOWN IS ABOVE CEILING, INDICATING

DRAINS FOR FLOOR ABOVE.

2. REMOVE AND REINSTALL EXISTING CEILINGS,

LIGHTS AND BUILDING SYSTEMS REQUIRED TO

PERFORM THE WORK.

3. PROVIDE INSULATION ON ALL STORM DRAIN

PIPING BEING INSTALLED.

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

c P.A.

FIRMTHE

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

USDA AGRICULTURAL RESEARCH SERVICE

CHILDREN'S NUTRITION RESEARCH CENTER

CRITICAL UPGRADES

HOUSTON, TX

LEVEL 11 STORM DRAIN

PIPING FLOOR PLAN

P-114 36 911/04/24

SME

SME

DRL

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

2923-E

B. DEAN

XXX

D. CORDRAY

W. ROSS

PLAN

NORTH

EXIST.

4" DD-1

EXIST.

4" DD-1

EXIST.

4" DD-1

EXIST.

4" DD-1

REVISED PIPE MATERIAL4/23/241 SME

https://simplex-fire.com/en/us/DocumentsandMedia/4090-0002.pdf https://simplex-fire.com/en/us/DocumentsandMedia/4090-0002.pdf https://simplex-fire.com/en/us/DocumentsandMedia/4090-0002.pdf https://simplex-fire.com/en/us/DocumentsandMedia/4090-0002.pdf https://simplex-fire.com/en/us/DocumentsandMedia/4090-0002.pdf https://simplex-fire.com/en/us/DocumentsandMedia/4090-0002.pdf https://simplex-fire.com/en/us/DocumentsandMedia/4090-0002.pdf https://simplex-fire.com/en/us/DocumentsandMedia/4090-0002.pdf

SCALE:

LEVEL 12 STORM DRAIN

PIPING FLOOR PLAN

1/8"=1'-0"

P-115

6" DN

4" UP4" BELOW ROOF4" UP TO PENTHOUSE

(SEE P-601)

PLUMBING LEGEND:

CO CLEANOUT

DD DECK DRAIN

EXIST. EXISTING

FD FLOOR DRAIN

HD HUB DRAIN

PAD PLANTING AREA DRAIN

TYP. TYPICAL

EXIST. STORM DRAIN

NEW STORM DRAIN PIPING

KEYED NOTES

1. PROVIDE VERTICAL STORM DRAIN PIPING UP TO

FLOORS ABOVE.

GENERAL NOTES

1. PIPING SHOWN IS ABOVE CEILING, INDICATING

DRAINS FOR FLOOR ABOVE.

2. REMOVE AND REINSTALL EXISTING CEILINGS,

LIGHTS AND BUILDING SYSTEMS REQUIRED TO

PERFORM THE WORK.

3. PROVIDE INSULATION ON ALL STORM DRAIN

PIPING BEING INSTALLED.

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

c P.A.

FIRMTHE

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

USDA AGRICULTURAL RESEARCH SERVICE

CHILDREN'S NUTRITION RESEARCH CENTER

CRITICAL UPGRADES

HOUSTON, TX

LEVEL 12 STORM DRAIN

PIPING FLOOR PLAN

P-115 37 911/04/24

SME

SME

DRL

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

2923-E

B. DEAN

XXX

D. CORDRAY

W. ROSS

PLAN

NORTH

4" RD

4" RD

4" RD4" RD

4" RD 4" RD 4" RD 4" RD

3" RD

3" RD3" RD3" RD3" RD

3" RD3" RD3" RD3" RD

4" RD4" RD4" RD4" RD4" RD

3" RD

REVISED PIPE MATERIAL4/23/241 SME

PENTHOUSE

SCALE: 1/8"= 1'-0"

SCALE:

BUILDING STORM

DRAIN RISER

1/8"=1'-0"

P-601

CHASE ROOF

LEVEL 12

LEVEL 11

LEVEL 10

LEVEL 9

LEVEL 8

LEVEL 7

LEVEL 6

LEVEL 5

LEVEL 4

LEVEL 3

LEVEL 2

LEVEL 1

BASEMENT LEVEL 1

BASEMENT LEVEL 2

4" RD

4" RD4" RD4" RD4" RD4" RD4" RD3" RD

3" RD 3" RD

4" RD4" RD4" RD4" RD 4" RD

3" RD 3" RD 3" RD 4" RD 3" RD 3" RD 3" RD 3" RD 3" RD 3" RD

4" DD-1

3" PAD

CO

CO

CO

CO

CO

CO

CO

CO

CO

CO

CO

CO

COCOCO

CO

CO

CO

CO

CO

CO

CO

CO

CO

CO

3" PAD 3" PAD 3" PAD 3" PAD 3" PAD 3" PAD 3" PAD 6" DD-1

3" HD 3" HD3" HD 3" HD3" HD 3" HD 3" HD 3" HD 3" HD 3" HD

3" HD3" HD 3" HD 3" HD 3" HD 3" HD

CO

6"6"

6" 6"6"6"6"6"

6" 6"6"

6" 6"

6"6"6" 6"4"

6"

4"6"6"6"6"6"

6"

6" 6" 6" 6" 6" 6" 6"

CO

8"

8"

4"4"4" 4"4"

4"4"4"4" 4"

3" 3"

4" 4" 4" 4"

4"

4" 4"

4"

4" 4"

4" 4"4"

4"

4"

4" 3"4"

4"

4"4" 4" 4"

4"

4" 4" 4"

4" 4"

4" 4"

4" 4" 4"

8"

6" 8" 8" 8"

8"

8"

8"

8"

8"

8"

8"8"8"

3" 3" 3" 3" 3"

3" 3"3"3"3"

8"

3"

3" 3" 3" 3"

3" 3" 3" 3" 3" 3"3"3"

3"3"3"3"3"3" 4"

3"3"3"

8"

10" 10"

10"

10"

10" 10"

10" 10"

10"

12"

12"

12"

12"

12" 12"

12"

12"

12"

4" DD-1 4" DD-1 4" DD-1

4" DD-14" DD-14" DD-1 4" DD-14" DD-1

4" DD-1

4" DD-1

4" DD-1 4" DD-1 4" DD-1 4" DD-1

4" DD-1 4" DD-1 4" DD-1

6" DD-1 6" DD-16" DD-16" DD-16" DD-16" DD-16" DD-16" DD-14" DD-14" DD-16" DD-16" DD-16" DD-16" DD-16" DD-1

4"

6"

CO

CO

4"

4" DD-13" HD

3"

3" HD

3"

3" HD

3"

3" HD

3"

3" HD

3" 4" 4"

4" DD-1

4"

4" DD-1

4"

4" DD-1

4"CO4"

4"

4" DD-1 3" HD

3" 4"

3" HD

3"

4" DD-1

4"

4" DD-1

3" HD 3" HD

4" 3" 3"

4" DD-1

CO

CO

6" DD-1 6" DD-1

6"

10"

CO

PLUMBING LEGEND:

CO CLEANOUT

DD DECK DRAIN

EXIST. EXISTING

FD FLOOR DRAIN

HD HUB DRAIN

PAD PLANTING AREA DRAIN

TYP. TYPICAL

STORM DRAIN TO REMAIN

STORM DRAIN PIPING TO

BE REPLACED

CO

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

c P.A.

FIRMTHE

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

USDA AGRICULTURAL RESEARCH SERVICE

CHILDREN'S NUTRITION RESEARCH CENTER

CRITICAL UPGRADES

HOUSTON, TX

STORM DRAIN

RISER DIAGRAM

P-601 38 911/04/24

SME

SME

DRL

2150 CENTRE AVENUE

BLDG D, SUITE 300

FORT COLLINS, CO

XXX

2923-E

B. DEAN

XXX

D. CORDRAY

W. ROSS

BASEMENT LEVEL 3

EXIST. TRENCH

DRAIN COURTYARD

6" TO B1004 TO BE

REMOVED

4" TO B1016

MANIFOLD TO

BE REMOVED3" PAD 3" PAD

3"

CO

6"

6" FD-4

4"

6" TO SUMP

PUMP TO BE

REMOVED

Sheets and Views
P-001
P-101
P-102
P-103
P-104
P-105
P-106
P-107
P-113
P-114
P-115
P-601

File details come from the government source that posted it. Updated .