Amendment 3 Attachment 5 PLUMBING REVISIONS.pdf
PDF 6 MB Posted
- Solicitation number
- 12805B24R0012
About this file
This document appears to be plumbing drawings and specifications for the CNRC Critical Upgrades to Insulation, Piping & HVAC project in Houston, TX. The key details are:
The project involves removing and replacing existing cast iron storm drain piping as indicated on the drawings. The work must be coordinated with insulation repairs listed on the architectural drawings and will need to be performed in a way that minimizes disruption to the occupied facility. The drawings provide detailed plans for the new storm drain piping layout on each floor, including cleanouts, deck drains, and riser diagrams. All new storm drain piping is required to be insulated.
The related federal contract opportunity is a 100% small business set-aside solicitation with a NAICS code of 236220 - Commercial and Institutional Building Construction. The magnitude of the project is between $1-5 million. Vendors must be in an active status in SAM.gov at the time of proposal submission.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL NOTES
1. PLUMBING WORK IN THIS PROJECT CONSISTS OF REMOVING AND REPLACING THE EXISTING CAST IRON
STORM DRAIN PIPING AS INDICATED.
2. NOTE: COORDINATE WITH INSULATION REPAIRS LISTED ON ARCHITECTURAL DRAWINGS. STORM DRAIN PIPING REPLACEMENT MUST BE COMPLETED AFTER INSULATION REPAIRS HAVE BEEN CONSTRUCTED.
3. THIS PROJECT IS A RENOVATION OF AN EXISTING FACILITY. IT IS THE CONTRACTOR'S RESPONSIBILITY TO FIELD VERIFY ALL DIMENSIONS PRIOR TO FABRICATION OR PURCHASE OF EQUIPMENT, MATERIALS, AND ASSEMBLIES. ANY DEVIATIONS SHALL BE BROUGHT TO THE CONTRACTING OFFICERS ATTENTION FOR RESOLUTION BEFORE PROCEEDING WITH ANY CONSTRUCTION, FABRICATION, OR EQUIPMENT PURCHASE.
4. THE FACILITY WILL REMAIN ACTIVE WHILE CONSTRUCTION WORK IS IN PROGRESS. ALL WORK SHALL BE
PERFORMED SO THAT IT MINIMIZES DISRUPTION OF THE OPERATION OF THE FACILITY.
5. WORK SEQUENCING WILL BE REQUIRED TO ALLOW THE FACILITY TO REMAIN OCCUPIED AND OPERATIONAL DURING THE PROJECT. ALL WORK SHALL BE PERFORMED SO THAT IT MINIMIZES DISRUPTION OF THE
OPERATION OF THE FACILITY.
6. PROVIDE SAFETY BARRIERS AND FOLLOW ALL SAFETY REQUIREMENTS OF THE OWNER. TAKE PRECAUTIONS
TO ENSURE THE SAFETY OF ALL PERSONNEL.
7. THESE DRAWINGS ARE SCHEMATIC IN NATURE AND ARE NOT INTENDED TO SHOW ALL POSSIBLE CONDITIONS (DO NOT SCALE FOR LOCATIONS). THE CONTRACTOR SHALL PROVIDE A COMPLETE AND FUNCTIONAL STORM
DRAIN SYSTEM AS INDICATED.
8. CONTRACTOR SHALL EMPLOY WORKMEN WHO ARE TRAINED AND EXPERIENCED IN NECESSARY SKILLS TO
PERFORM DEMOLITION WORK.
9. CONTRACTOR SHALL USE APPROPRIATE TOOLS AND SHALL NOT IMPART EXCESSIVE VIBRATIONS TO THE
EXISTING STRUCTURE OR OTHER BUILDING COMPONENTS.
10. COORDINATE PIPING WITH EXISTING STRUCTURAL, ELECTRICAL, PLUMBING, AND COMMUNICATION. MAKE OFFSETS AND TRANSITIONS TO COORDINATE WITH OTHER TRADES WITHOUT ANY ADDITIONAL EXPENSE TO
THE OWNER. CONTRACTOR SHALL PROVIDE COORDINATION DRAWINGS OF TRADES.
11. ALL STORM DRAIN PIPING SHALL BE INSULATED COMPLETELY. PIPING INSULATION SHALL CONFORM TO
REQUIREMENTS OF NFPA 90A.
12. PROVIDE HANGERS AND SUPPORTS FOR NEW STORM DRAIN PIPING.
ABBREVIATIONS GENERAL DEMOLITION NOTES
1. THE DEMOLITION PLAN AND EXISTING CONDITIONS SHOWN ARE APPROXIMATE AND ARE TO BE FIELD
VERIFIED. ITEMS TO BE REMOVED ARE DENOTED BY HATCHING.
2. DEMOLITION SHALL INCLUDE, BUT IS NOT LIMITED TO, THE ITEMS IDENTIFIED. THE CONTRACTOR SHALL COORDINATE ALL REQUIRED RENOVATION AND NEW CONSTRUCTION WITH THE EXISTING BUILDING TO
IDENTIFY THE TOTAL EXTENT OF THE DEMOLITION WORK REQUIRED.
3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DEMOLITION AND REMOVAL OF ALL EXISTING BUILDING COMPONENTS, MATERIALS, EQUIPMENT, AND APPURTENANCES AS REQUIRED TO BUILD, ERECT, INSTALL, OR
ACCOMMODATE ALL NEW CONSTRUCTION.
4. IN THE EVENT THE CONTRACTOR ENCOUNTERS ON THE SITE MATERIAL BELIEVED TO BE ASBESTOS, LEAD-BASED PAINT, OR ANY OTHER HAZARDOUS MATERIAL WHICH HAS NOT BEEN RENDERED HARMLESS, THE CONTRACTOR SHALL IMMEDIATELY STOP WORK AND REPORT THE CONDITION TO THE CONTRACTING
OFFICER.
5. THE CONTRACTOR IS RESPONSIBLE FOR THE ERECTION, MAINTENANCE, AND REMOVAL OF ALL
CONSTRUCTION ASSISTANCE DEVICES SUCH AS SCAFFOLDING AND BARRIERS.
6. DEMOLISH ALL EXISTING PIPE HANGERS FOR STORM DRAIN PIPING BEING REMOVED.
ACCU AIR COOLED CONDENSING UNIT GAL. GALLONS
AD ACCESS DOOR GALV. GALVANIZED
A.F.F. ABOVE FINISHED FLOOR GEN. GENERAL
A.F.G. ABOVE FINISHED GRADE G.P.H. GALLONS PER HOUR
AHU AIR HANDLING UNIT G.P.M. GALLONS PER MINUTE
AP ACCESS PANEL HR. HOUR
APPROX. APPROXIMATE I.D. INSIDE DIMENSION
ARCH ARCHITECTURAL IN INCHES
CD CEILING DIFFUSER K.W. KILOWATT
CL CENTER LINE L LOUVER
C.O. CLEAN OUT LB POUND
C.V. CHECK VALVE LD LINEAR DIFFUSER
CFM CUBIC FEET PER MINUTE LAT LEAVING AIR TEMPERATURE
CLG CEILING LWT LEAVING WATER TEMPERATURE
CONC. CONCRETE MAU MAKEUP AIR UNIT
CONT. CONTINUATION MAX. MAXIMUM
CP CONDENSER WATER PUMP MFR. MANUFACTURER
CHWR CHILLED WATER RETURN MECH. MECHANICAL
CHWS CHILLED WATER SUPPLY MIN. MINIMUM OR MINUTE
CWP CHILLED WATER PUMP NC NORMALLY CLOSED
CWR CONDENSER WATER RETURN NO NORMALLY OPENED
CWS CONDENSER WATER SUPPLY NPT NATIONAL PIPE THREAD
CT COOLING TOWER Ø DIAMETER
CTE CONNECT TO EXISTING O/A OUTSIDE AIR
CU CONDENSING UNIT O.D. OUTSIDE DIMENSION
dB DECIBELS PH PHASE
DIFF. DIFFUSER PRV PRESSURE REDUCING VALVE
DN. DOWN PSI POUNDS PER SQUARE INCH
DET. DETAIL R/A RETURN AIR
DIA. DIAMETER RAD RADIUS
DIM. DIMENSION RAR RETURN AIR REGISTER
DWG. DRAWING RED. REDUCER
EA. EACH REINF. REINFORCING
E/A EXHAUST AIR REQ'D. REQUIRED
EAG EXHAUST AIR GRILLE RPM REVOLUTIONS PER MINUTE
EAT ENTERING AIR TEMPERATURE RTU ROOF TOP UNIT
EF EXHAUST FAN S/A SUPPLY AIR
EWT ENTERING WATER TEMPERATURE SAG SUPPLY AIR GRILLE
ECC ECCENTRIC SC STEAM CONVERTER
EFF EFFICIENCY SEN SENSIBLE
ELEC. ELECTRICAL SF SQUARE FEET
ELEV. ELEVATION SQ. SQUARE
ET EXPANSION TANK TA TRANSFER AIR
F FAHRENHEIT TEMP TEMPERATURE
FLR FLOOR TH THERMOMETER
FDC FIRE DEPARTMENT CONNECTION TYP. TYPICAL
F/SD FIRE/SMOKE DAMPER U.N.P. UNLESS NOTED OTHERWISE
FPM FEET PER MINUTE UC UNIT COOLER
FCO FLOOR CLEAN OUT UH UNIT HEATER
FCU FAN COIL UNIT VA VALVE
UH UNIT HEATER VAV VARIABLE AIR VOLUME (BOX)
FT. FOOT V VOLTS
FIN. FINISHED V.T.R. VENT THRU ROOF
G NATURAL GAS PIPING W/ WITH
GA. GAUGE WT WEIGHT
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
CHILDREN'S NUTRITION RESEARCH CENTER
CRITICAL UPGRADES
HOUSTON, TX
PLUMBING ABBREVIATIONS
AND NOTES
P-001 17 911/04/24
SME
SME
DRL
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
2923-E
B. DEAN
XXX
D. CORDRAY
W. ROSS
REVISED PIPE MATERIAL4/23/241 SME
0 16'8'4' 24'
SCALE: 1/8"= 1'-0"
SCALE:
BAEMENT LEVEL 3 STORM
DRAIN PIPING FLOOR PLAN
1/8"=1'-0"
P-101
CO
CO EXIST. 4" UP
6" UP
EXIST.
1-1/2" UP
6" DOWN
TO SUMP
CO
PLUMBING LEGEND:
CO CLEANOUT
DD DECK DRAIN
EXIST. EXISTING
FD FLOOR DRAIN
HD HUB DRAIN
PAD PLANTING AREA DRAIN
TYP. TYPICAL
EXIST. STORM DRAIN
NEW STORM DRAIN PIPING
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
CHILDREN'S NUTRITION RESEARCH CENTER
CRITICAL UPGRADES
HOUSTON, TX
BASEMENT LEVEL 3 STORM
DRAIN PIPING FLOOR PLAN
P-101 28 911/04/24
SME
SME
DRL
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
2923-E
XXX
XXX
XXX
XXX
PLAN
NORTH
SCALE:
BASEMENT LEVEL 2 STORM
DRAIN PIPING FLOOR PLAN
1/8"=1'-0"
P-102
6"
1-1/2" UP
6" UP
EXIST. 4"
UP
EXIST. 6"
UP TO
TRENCH
CO
EXIST. 4" UP
EXIST. 4"
DOWN
3" UP
PLUMBING LEGEND:
CO CLEANOUT
DD DECK DRAIN
EXIST. EXISTING
FD FLOOR DRAIN
HD HUB DRAIN
PAD PLANTING AREA DRAIN
TYP. TYPICAL
EXIST. STORM DRAIN
NEW STORM DRAIN PIPING
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
CHILDREN'S NUTRITION RESEARCH CENTER
CRITICAL UPGRADES
HOUSTON, TX
BASEMENT LEVEL 2 STORM
DRAIN PIPING FLOOR PLAN
P-102 29 911/04/24
SME
SME
DRL
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
2923-E
XXX
XXX
XXX
XXX
3" UP
CO
PLAN
NORTH
SCALE:
BASEMENT LEVEL 1 STORM
DRAIN PIPING FLOOR PLAN
1/8"=1'-0"
P-103
10"
EXIST.
12"EXIST. 12"
6"
EXIST. 4" FORCED
WASTE WATER
CO
CO
8" UP
EXIST.
12" UP
EXIST. 4" EXIST. 2"
EXIST. 4"
EXIST.
1-1/2"
12" UP
12" UP EXIST.
4" UP
6" UP
CO
CO
CO
PLUMBING LEGEND:
CO CLEANOUT
DD DECK DRAIN
EXIST. EXISTING
FD FLOOR DRAIN
HD HUB DRAIN
PAD PLANTING AREA DRAIN
TYP. TYPICAL
EXIST. STORM DRAIN
NEW STORM DRAIN PIPING
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
CHILDREN'S NUTRITION RESEARCH CENTER
CRITICAL UPGRADES
HOUSTON, TX
BASEMENT LEVEL 1 STORM
DRAIN PIPING FLOOR PLAN
P-103 30 911/04/24
SME
SME
DRL
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
2923-E
XXX
XXX
XXX
XXX
PLAN
NORTH
EXIST. 3" PAD
EXIST. 6" FD-4
EXIST. 3" PAD
SCALE:
LEVEL 1 STORM DRAIN
PIPING FLOOR PLAN
1/8"=1'-0"
P-104
4" UP EXIST.
4" UP
EXIST.
4" UP
4" UP
EXIST.
4" UP
EXIST.
4" UP
EXIST. 4"
EXIST. 4" EXIST. 6"
EXIST. 6"
8" DOWN
3" UP EXIST.
3" UP
EXIST.
3" UP
EXIST.
3" UP
EXIST.
3" UP
EXIST.
3" UP
CO CO
PLUMBING LEGEND:
CO CLEANOUT
DD DECK DRAIN
EXIST. EXISTING
FD FLOOR DRAIN
HD HUB DRAIN
PAD PLANTING AREA DRAIN
TYP. TYPICAL
EXIST. STORM DRAIN
NEW STORM DRAIN PIPING
4"
4"
4"
12" UP
4" UP4" UP 4" UP
3" UP3" UP3" UP3" UP3" UP3" UP
4" UP
CO
COCO
12" UP
4" UP
CO
KEYED NOTES
1. PROVIDE PIPING TO EXISTING ROOF DRAIN
ABOVE.
2. PROVIDE VERTICAL STORM DRAIN PIPING TO
FLOORS ABOVE/BELOW.
GENERAL NOTES
1. PIPING SHOWN IS ABOVE CEILING, INDICATING
DRAINS FOR FLOOR ABOVE.
2. REMOVE AND REINSTALL EXISTING CEILINGS,
LIGHTS AND BUILDING SYSTEMS REQUIRED TO
PERFORM THE WORK.
3. PROVIDE INSULATION ON ALL STORM DRAIN
PIPING BEING INSTALLED.
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
CHILDREN'S NUTRITION RESEARCH CENTER
CRITICAL UPGRADES
HOUSTON, TX
LEVEL 1 STORM DRAIN
PIPING FLOOR PLAN
P-104 31 911/04/24
SME
SME
DRL
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
2923-E
B. DEAN
XXX
D. CORDRAY
W. ROSS
PLAN
NORTH
SCALE:
LEVEL 2 STORM DRAIN
PIPING FLOOR PLAN
1/8"=1'-0"
P-105PLUMBING LEGEND:
CO CLEANOUT
DD DECK DRAIN
EXIST. EXISTING
FD FLOOR DRAIN
HD HUB DRAIN
PAD PLANTING AREA DRAIN
TYP. TYPICAL
EXIST. STORM DRAIN
NEW STORM DRAIN PIPING
8"
8" 10"
12"
CO
EXIST.
3" UP EXIST.
3" UP
EXIST.
3" UP
EXIST.
3" UP
3" UP
CO
3" UP
3" UP3" UP3" UP3" UP3" UP3" UP
CO
4" UP 4" UP
4" DOWN
4" UP
4"4"
4"
EXIST. 4"EXIST. 4"EXIST. 3"
EXIST.
4" UP
EXIST.
4" UP
EXIST.
4" UP
10" UP
CO
CO
CO
12" UP
12" DOWN
CO
EXIST. 4"
DOWN
8" UP
10" UP
EXIST.
3" UP
4" UP 4" UP
1 1
12"
KEYED NOTES
1. PROVIDE PIPING TO EXISTING ROOF DRAIN
ABOVE.
2. PROVIDE VERTICAL STORM DRAIN PIPING UP TO
FLOORS ABOVE.
GENERAL NOTES
1. PIPING SHOWN IS ABOVE CEILING, INDICATING
DRAINS FOR FLOOR ABOVE.
2. REMOVE AND REINSTALL EXISTING CEILINGS,
LIGHTS AND BUILDING SYSTEMS REQUIRED TO
PERFORM THE WORK.
3. PROVIDE INSULATION ON ALL STORM DRAIN
PIPING BEING INSTALLED.
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
CHILDREN'S NUTRITION RESEARCH CENTER
CRITICAL UPGRADES
HOUSTON, TX
LEVEL 2 STORM DRAIN
PIPING FLOOR PLAN
P-105 32 911/04/24
SME
SME
DRL
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
2923-E
B. DEAN
XXX
D. CORDRAY
W. ROSS
PLAN
NORTH
EXIST.
3" HD
EXIST.
3" HD
EXIST.
3" HD
EXIST.
3" HD
EXIST.
3" HD
EXIST.
3" HD
EXIST.
3" HD
EXIST.
3" HD
EXIST.
3" HD
EXIST.
3" HD
EXIST.
4" DD-1
EXIST.
4" DD-1
EXIST.
4" DD-1
EXIST.
4" DD-1
EXIST.
4" DD-1
EXIST.
4" DD-1EXIST.
4" DD-1
EXIST.
4" DD-1
EXIST.
4" DD-1
EXIST.
3" HD
EXIST.
3" HD
REVISED PIPE MATERIAL4/23/241 SME
SCALE:
LEVEL 3 STORM DRAIN
PIPING FLOOR PLAN
1/8"=1'-0"
P-106PLUMBING LEGEND:
CO CLEANOUT
DD DECK DRAIN
EXIST. EXISTING
FD FLOOR DRAIN
HD HUB DRAIN
PAD PLANTING AREA DRAIN
TYP. TYPICAL
EXIST. STORM DRAIN
NEW STORM DRAIN PIPING
6" UP
8"
6" UP
4" UP
3" UP
4" UP4" UP
ABOVE CEILING
(TYP.)
6"
4" UP
4" UP
6" UP
10"
12"
12" UP
6" UP8"
4" UP
6" UP
6"
6" UP
8"
10"
6" UP
8"
3" UP
6" UP
8"
6" UP 8"
8" DOWN
6" UP
10" DOWN
10"
10" DOWN
6" UP
6" UP
10"
3" UP8"
3" UP
3" UP
3"
3" UP
8"
6" UP
6"
8"
6"
3" UP
3" UP
4" UP
6"
6" UP
6" UP
6" UP
CO
CO
CO
CO
CO
CO
CO
CO
CO
ABOVE CEILING
CO
12" UP
6" UP
1 2
1 1
1 1
8"
KEYED NOTES
1. PROVIDE PIPING TO EXISTING ROOF DRAIN
ABOVE.
2. PROVIDE VERTICAL STORM DRAIN PIPING UP TO
FLOORS ABOVE.
GENERAL NOTES
1. PIPING SHOWN IS ABOVE CEILING, INDICATING
DRAINS FOR FLOOR ABOVE.
2. REMOVE AND REINSTALL EXISTING CEILINGS,
LIGHTS AND BUILDING SYSTEMS REQUIRED TO
PERFORM THE WORK.
3. PROVIDE INSULATION ON ALL STORM DRAIN
PIPING BEING INSTALLED.
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
CHILDREN'S NUTRITION RESEARCH CENTER
CRITICAL UPGRADES
HOUSTON, TX
LEVEL 3 STORM DRAIN
PIPING FLOOR PLAN
P-106 33 911/04/24
SME
SME
DRL
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
2923-E
B. DEAN
XXX
D. CORDRAY
W. ROSS
PLAN
NORTH
EXIST.
3" HD
EXIST.
4" DD-1
EXIST.
4" DD-1
EXIST.
4" DD-1
EXIST.
4" DD-1
EXIST.
4" DD-1
EXIST.
3" HD
EXIST.
3" HD
EXIST.
3" HD
EXIST.
3" HD
EXIST.
4" DD-1EXIST.
4" DD-1
EXIST.
3" HD
EXIST.
3" HD
EXIST.
3" HD
EXIST.
3" HD
EXIST.
3" HD
EXIST.
3" HD
EXIST.
3" HD
EXIST.
3" HD
REVISED PIPE MATERIAL4/23/241 SME
SCALE:
LEVEL 4 STORM DRAIN
PIPING FLOOR PLAN
1/8"=1'-0"
P-107
12" DOWN8" UP 12"
8" UP
PLUMBING LEGEND:
CO CLEANOUT
DD DECK DRAIN
EXIST. EXISTING
FD FLOOR DRAIN
HD HUB DRAIN
PAD PLANTING AREA DRAIN
TYP. TYPICAL
EXIST. STORM DRAIN
NEW STORM DRAIN PIPING
KEYED NOTES
1. PROVIDE PIPING TO EXISTING ROOF DRAIN
ABOVE.
GENERAL NOTES
1. PIPING SHOWN IS ABOVE CEILING, INDICATING
DRAINS FOR FLOOR ABOVE.
2. REMOVE AND REINSTALL EXISTING CEILINGS,
LIGHTS AND BUILDING SYSTEMS REQUIRED TO
PERFORM THE WORK.
3. PROVIDE INSULATION ON ALL STORM DRAIN
PIPING BEING INSTALLED.
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
CHILDREN'S NUTRITION RESEARCH CENTER
CRITICAL UPGRADES
HOUSTON, TX
LEVEL 4 STORM DRAIN
PIPING FLOOR PLAN
P-107 34 911/04/24
SME
SME
DRL
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
2923-E
B. DEAN
XXX
D. CORDRAY
W. ROSS
PLAN
NORTH
6" DD-1 4" DD-16" DD-1
6" DD-16" DD-1
6" DD-1
6" DD-1
6" DD-1
6" DD-1
3" PAD-1
6" DD-1
6" DD-1
6" DD-1 6" DD-1
6" DD-1 6" DD-1
6" DD-1
6" DD-1
6" DD-1
6" DD-1
12" DN
4" DD-1
4" DD-1
4" DD-1
4" DD-1
4" DD-1
4" DD-1
3" PAD-1
3" PAD-1
3" PAD-1 3" PAD-1 3" PAD-1
3" PAD-1
3" PAD-1
8" UP 12"
8"
6" DD-1
REVISED PIPE MATERIAL4/23/241 SME
SCALE:
LEVEL 10 STORM DRAIN
PIPING FLOOR PLAN
1/8"=1'-0"
P-113PLUMBING LEGEND:
CO CLEANOUT
DD DECK DRAIN
EXIST. EXISTING
FD FLOOR DRAIN
HD HUB DRAIN
PAD PLANTING AREA DRAIN
TYP. TYPICAL
EXIST. STORM DRAIN
NEW STORM DRAIN PIPING
4" UP
6"
4" UP
8" ABOVE
CEILING
(TYP.)
8"
4" UP
8"
CO
CO
CO
CO
4" UP
8" UP
8" UP
KEYED NOTES
1. PROVIDE PIPING TO EXISTING ROOF DRAIN
ABOVE.
2. PROVIDE VERTICAL STORM DRAIN PIPING UP TO
FLOORS ABOVE.
GENERAL NOTES
1. PIPING SHOWN IS ABOVE CEILING, INDICATING
DRAINS FOR FLOOR ABOVE.
2. REMOVE AND REINSTALL EXISTING CEILINGS,
LIGHTS AND BUILDING SYSTEMS REQUIRED TO
PERFORM THE WORK.
3. PROVIDE INSULATION ON ALL STORM DRAIN
PIPING BEING INSTALLED.
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
CHILDREN'S NUTRITION RESEARCH CENTER
CRITICAL UPGRADES
HOUSTON, TX
LEVEL 10 STORM DRAIN
PIPING FLOOR PLAN
P-113 35 911/04/24
SME
SME
DRL
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
2923-E
B. DEAN
XXX
D. CORDRAY
W. ROSS
PLAN
NORTH
REVISED PIPE MATERIAL4/23/241 SME
AC PANEL LOCATION:
BREAKER #:
AC PANEL LOCATION:
BREAKER #:
0 16'8'4' 24'
SCALE: 1/8"= 1'-0"
SCALE:
LEVEL 11 STORM DRAIN
PIPING FLOOR PLAN
1/8"=1'-0"
P-114PLUMBING LEGEND:
CO CLEANOUT
DD DECK DRAIN
EXIST. EXISTING
FD FLOOR DRAIN
HD HUB DRAIN
PAD PLANTING AREA DRAIN
TYP. TYPICAL
EXIST. STORM DRAIN
NEW STORM DRAIN PIPING
ROUTE 8" STORM
DRAIN IN CHASE
TO FLOORS
BELOW
4" UP
4" UP3" UP
3" UP 3" UP
4" UP
4" UP
6" UP
4" UP4" UP
4" UP4" UP
4" UP
4" UP
4" UP 4" UP
8"8"6"6"6"6"4"
ABOVE
CEILING
(TYP.)
4" ABOVE CEILING
4"6"6"6"6"
CO
CO
CO
CO
4" UP
3" UP 3" UP 3" UP
3" UP 3" UP 3" UP 3" UP
1 1
11111
1 1
ROUTE 8" STORM
DRAIN IN CHASE
TO FLOORS
BELOW
KEYED NOTES
1. PROVIDE PIPING TO EXISTING ROOF DRAIN
ABOVE.
2. PROVIDE VERTICAL STORM DRAIN PIPING UP TO
FLOORS ABOVE.
GENERAL NOTES
1. PIPING SHOWN IS ABOVE CEILING, INDICATING
DRAINS FOR FLOOR ABOVE.
2. REMOVE AND REINSTALL EXISTING CEILINGS,
LIGHTS AND BUILDING SYSTEMS REQUIRED TO
PERFORM THE WORK.
3. PROVIDE INSULATION ON ALL STORM DRAIN
PIPING BEING INSTALLED.
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
CHILDREN'S NUTRITION RESEARCH CENTER
CRITICAL UPGRADES
HOUSTON, TX
LEVEL 11 STORM DRAIN
PIPING FLOOR PLAN
P-114 36 911/04/24
SME
SME
DRL
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
2923-E
B. DEAN
XXX
D. CORDRAY
W. ROSS
PLAN
NORTH
EXIST.
4" DD-1
EXIST.
4" DD-1
EXIST.
4" DD-1
EXIST.
4" DD-1
REVISED PIPE MATERIAL4/23/241 SME
https://simplex-fire.com/en/us/DocumentsandMedia/4090-0002.pdf https://simplex-fire.com/en/us/DocumentsandMedia/4090-0002.pdf https://simplex-fire.com/en/us/DocumentsandMedia/4090-0002.pdf https://simplex-fire.com/en/us/DocumentsandMedia/4090-0002.pdf https://simplex-fire.com/en/us/DocumentsandMedia/4090-0002.pdf https://simplex-fire.com/en/us/DocumentsandMedia/4090-0002.pdf https://simplex-fire.com/en/us/DocumentsandMedia/4090-0002.pdf https://simplex-fire.com/en/us/DocumentsandMedia/4090-0002.pdf
SCALE:
LEVEL 12 STORM DRAIN
PIPING FLOOR PLAN
1/8"=1'-0"
P-115
6" DN
4" UP4" BELOW ROOF4" UP TO PENTHOUSE
(SEE P-601)
PLUMBING LEGEND:
CO CLEANOUT
DD DECK DRAIN
EXIST. EXISTING
FD FLOOR DRAIN
HD HUB DRAIN
PAD PLANTING AREA DRAIN
TYP. TYPICAL
EXIST. STORM DRAIN
NEW STORM DRAIN PIPING
KEYED NOTES
1. PROVIDE VERTICAL STORM DRAIN PIPING UP TO
FLOORS ABOVE.
GENERAL NOTES
1. PIPING SHOWN IS ABOVE CEILING, INDICATING
DRAINS FOR FLOOR ABOVE.
2. REMOVE AND REINSTALL EXISTING CEILINGS,
LIGHTS AND BUILDING SYSTEMS REQUIRED TO
PERFORM THE WORK.
3. PROVIDE INSULATION ON ALL STORM DRAIN
PIPING BEING INSTALLED.
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
CHILDREN'S NUTRITION RESEARCH CENTER
CRITICAL UPGRADES
HOUSTON, TX
LEVEL 12 STORM DRAIN
PIPING FLOOR PLAN
P-115 37 911/04/24
SME
SME
DRL
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
2923-E
B. DEAN
XXX
D. CORDRAY
W. ROSS
PLAN
NORTH
4" RD
4" RD
4" RD4" RD
4" RD 4" RD 4" RD 4" RD
3" RD
3" RD3" RD3" RD3" RD
3" RD3" RD3" RD3" RD
4" RD4" RD4" RD4" RD4" RD
3" RD
REVISED PIPE MATERIAL4/23/241 SME
PENTHOUSE
SCALE: 1/8"= 1'-0"
SCALE:
BUILDING STORM
DRAIN RISER
1/8"=1'-0"
P-601
CHASE ROOF
LEVEL 12
LEVEL 11
LEVEL 10
LEVEL 9
LEVEL 8
LEVEL 7
LEVEL 6
LEVEL 5
LEVEL 4
LEVEL 3
LEVEL 2
LEVEL 1
BASEMENT LEVEL 1
BASEMENT LEVEL 2
4" RD
4" RD4" RD4" RD4" RD4" RD4" RD3" RD
3" RD 3" RD
4" RD4" RD4" RD4" RD 4" RD
3" RD 3" RD 3" RD 4" RD 3" RD 3" RD 3" RD 3" RD 3" RD 3" RD
4" DD-1
3" PAD
CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
COCOCO
CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
3" PAD 3" PAD 3" PAD 3" PAD 3" PAD 3" PAD 3" PAD 6" DD-1
3" HD 3" HD3" HD 3" HD3" HD 3" HD 3" HD 3" HD 3" HD 3" HD
3" HD3" HD 3" HD 3" HD 3" HD 3" HD
CO
6"6"
6" 6"6"6"6"6"
6" 6"6"
6" 6"
6"6"6" 6"4"
6"
4"6"6"6"6"6"
6"
6" 6" 6" 6" 6" 6" 6"
CO
8"
8"
4"4"4" 4"4"
4"4"4"4" 4"
3" 3"
4" 4" 4" 4"
4"
4" 4"
4"
4" 4"
4" 4"4"
4"
4"
4" 3"4"
4"
4"4" 4" 4"
4"
4" 4" 4"
4" 4"
4" 4"
4" 4" 4"
8"
6" 8" 8" 8"
8"
8"
8"
8"
8"
8"
8"8"8"
3" 3" 3" 3" 3"
3" 3"3"3"3"
8"
3"
3" 3" 3" 3"
3" 3" 3" 3" 3" 3"3"3"
3"3"3"3"3"3" 4"
3"3"3"
8"
10" 10"
10"
10"
10" 10"
10" 10"
10"
12"
12"
12"
12"
12" 12"
12"
12"
12"
4" DD-1 4" DD-1 4" DD-1
4" DD-14" DD-14" DD-1 4" DD-14" DD-1
4" DD-1
4" DD-1
4" DD-1 4" DD-1 4" DD-1 4" DD-1
4" DD-1 4" DD-1 4" DD-1
6" DD-1 6" DD-16" DD-16" DD-16" DD-16" DD-16" DD-16" DD-14" DD-14" DD-16" DD-16" DD-16" DD-16" DD-16" DD-1
4"
6"
CO
CO
4"
4" DD-13" HD
3"
3" HD
3"
3" HD
3"
3" HD
3"
3" HD
3" 4" 4"
4" DD-1
4"
4" DD-1
4"
4" DD-1
4"CO4"
4"
4" DD-1 3" HD
3" 4"
3" HD
3"
4" DD-1
4"
4" DD-1
3" HD 3" HD
4" 3" 3"
4" DD-1
CO
CO
6" DD-1 6" DD-1
6"
10"
CO
PLUMBING LEGEND:
CO CLEANOUT
DD DECK DRAIN
EXIST. EXISTING
FD FLOOR DRAIN
HD HUB DRAIN
PAD PLANTING AREA DRAIN
TYP. TYPICAL
STORM DRAIN TO REMAIN
STORM DRAIN PIPING TO
BE REPLACED
CO
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
CHILDREN'S NUTRITION RESEARCH CENTER
CRITICAL UPGRADES
HOUSTON, TX
STORM DRAIN
RISER DIAGRAM
P-601 38 911/04/24
SME
SME
DRL
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
2923-E
B. DEAN
XXX
D. CORDRAY
W. ROSS
BASEMENT LEVEL 3
EXIST. TRENCH
DRAIN COURTYARD
6" TO B1004 TO BE
REMOVED
4" TO B1016
MANIFOLD TO
BE REMOVED3" PAD 3" PAD
3"
CO
6"
6" FD-4
4"
6" TO SUMP
PUMP TO BE
REMOVED
| Sheets and Views |
| P-001 |
| P-101 |
| P-102 |
| P-103 |
| P-104 |
| P-105 |
| P-106 |
| P-107 |
| P-113 |
| P-114 |
| P-115 |
| P-601 |