This document is a set of reflected ceiling plan drawings for the Children's Nutrition Research Center (CNRC) in Houston, TX. The drawings depict the existing conditions and required renovations for the insulation, piping, and HVAC systems across multiple floors of the facility.
The key details include:
- Removal of existing spray and fiberglass insulation on concrete decks and exterior walls
- Application of 4-inch closed-cell spray foam insulation on the underside of floors/roofs and exterior walls
- Application of intumescent coating over the new spray foam insulation
- Requirement to provide protective measures to contain demolition debris and filter return air systems
- Responsibility to move and return furniture impacted by the work, and replace any damaged finishes
- Requirement to provide 24x24-inch aluminum access doors in ceilings for pipe cleanout access
This document supports a larger solicitation for the "CNRC Critical Upgrades to Insulation, Piping & HVAC" project. The solicitation is a 100% small business set-aside with an estimated value between $1-5 million.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SOUTH STAIR
FOUNDATION
DRAINAGE
EQUIPMENT
ROOM
B3024
ELEV #3
SERVICE
ELEV
MECHANICAL
B3022
CORRIDOR
OPEN
OFFICESTORAGE
B3016
CONTROL
B3012
OPEN OFFICE AREA
B3014 ENTRY LOBBY
ENTRY
ELEV VEST
ELEV #1
ELEV #2
OPEN
OFFICE
SHUTTLE
ELEV
MACHINE
ROOM
B3000
PUMP
ROOM
B3002
CORRIDOR
TOILET
B3004
LUNCHROOM
B3010
CORRIDOR
B3017
HVAC & SEWAGE
EJECTION RM
B3010B
WBC A
B3008
WBC B
B3006
C L O
S E
T
STAIR
VESTIBULE
WBC HVAC
B3018
TUNNEL TO
TCH
WEST
STAIR
BASEMENT LEVEL 3 - REFLECTED CEILING PLAN
SCALE: 1/8"=1'-0"
A1301
PLAN
NORTH
0' 2' 8' 16'
SCALE: 1/8"=1'-0"
4'
LINE OF EXTERIOR
WALL ABOVE
EXISTING CONCRETE
FLOOR / ROOF DECK
EXISTING PATIO,
DECK, OR ROOF EXISTING EXTERIOR CLADDING
EXISTING CMU
EXISTING CONCRETE BEAM
EXISTING CMU
LINE OF EXISTING
METAL STUDS
EXISTING FIBERGLASS
INSULATION
EXISTING ACOUSTICAL CEILING
EXISTING DRYWALL
NEW 4" FOAM INSULATION
PER "INSULATION NOTES"
NOTE: LIGHT FIXTURE LAYOUTS SHOWN IN
ARCHITECTURAL REFLECTED CEILING PLANS
ARE REPRESENTATIONAL OF EXISTING LIGHT
FIXTURE TYPES AND LAYOUTS.
0' 1' 2' 4' 6'
SCALE: 1/2"=1'-0"
INSULATION DETAILINSULATION NOTES LEGEND
DEMOLITION WORK
A. CONTRACTOR SHALL REMOVE ALL EXISTING SPRAY INSULATION
ON CONCRETE DECK.
B. CONTRACTOR SHALL CLEAN DECK THOROUGHLY AS REQUIRED
BY NEW SPRAY FOAM INSTRUCTIONS WHERE SHOWN ON THE
PLANS PER THE LEGEND AND DETAILS.
C. CONTRACTOR SHALL REMOVE ALL EXISTING FIBERGLASS
INSULATION FROM CEILING LEVEL UP TO DECK ON ALL EXTERIOR
WALLS WHERE SHOWN ON THE PLANS PER THE LEGEND.
D. CONTRACTOR SHALL PROVIDE PROTECTIVE WORK AREAS TO
KEEP DEMOLITION DEBRIS FROM GETTING INTO THE INTERIOR
WORK ENVIRONMENT AND FROM GETTING INTO RETURN AIR
HVAC SYSTEM PER 02 41 00. CONTRACTOR SHALL PROVIDE
FILTERING AT RETURN AIR SYSTEM. CONTRACTOR SHALL
REMOVE ALL LOOSE INSULATION DEBRIS DUE TO DEMOLITION
FROM WORK AREAS AND SPACES ABOVE CEILING.
E. CONTRACTOR SHALL BE RESPONSIBLE FOR MOVING FURNITURE
AS REQUIRED TO PERFORM THE DEMO WORK WHICH INCLUDES
BUT IS NOT LIMITED TO THE REMOVAL OF EXISTING FINISHES
(INCLUDING CEILING TILES).
REMOVE AND APPLY INSULATION ON
CONCRETE DECK PER "INSULATION NOTES"
NEW APPLICATIONS
EXISTING
EXPOSED
NEW WORK
A. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL INSULATION
AS SPECIFIED ON UNDERSIDE OF FLOOR / ROOF DECK AS DESCRIBED
HEREIN AND WHERE SHOWN ON THE PLANS PER THE LEGEND.
B. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL INSULATION
AS SPECIFIED ON EXTERIOR WALLS AS DESCRIBED HEREIN WHERE
SHOWN ON THE PLANS PER THE LEGEND.
C. CONTRACTOR SHALL APPLY INTUMESCENT COATING AS SPECIFIED
OVER ALL OF THE NEW SPRAY-APPLIED INSULATION.
D. CONTRACTOR SHALL BE RESPONSIBLE FOR RETURNING ALL
FURNITURE THAT WAS MOVED IN ORDER TO PERFORM THE SCOPE
OF WORK. ANY FINISHES DAMAGED DURING THE WORK SHALL BE
REPLACED LIKE IN-KIND.
E. PROVIDE 24"x24" ALUMINUM ACCESS DOORS AT GYPSUM BOARD OR
STUCCO CEILINGS FOR ACCESS TO PIPE CLEANOUTS. SEE THE
PLUMBING DRAWINGS FOR LOCATIONS OF EACH CLEANOUT. ACCESS
DOORS SHALL BE PAINTED TO MATCH ADJACENT CEILING COLOR.
REMOVE AND APPLY INSULATION ON
EXTERIOR WALL PER "INSULATION NOTES"
EXISTING
STUCCO / PLASTER
EXISTING CEILING FINISHES
EXISTING
GYP. BD.
EXISTING SACT
NO WORK
THIS FLOOR
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
JOB #
CHECKED BY
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
CHILDREN'S NUTRITION RESEARCH CENTER
HOUSTON, TX
BASEMENT LEVEL 3 - RCP
A1301
2 911/04/24
SME
CLR
DRL
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
2923-E
B. DEAN
XXX
D. CORDRAY
W. ROSS
1 04.04.2024 CLR REVISED HATCH PATTERNS AND
ADDED NOTE FOR ACCESS DOORS
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
HT
XET
TA
FO ET
S
R
EG
IS
SA
TC
E
IT
RERE A
CD
JE
RR
Y G. MARTIN
1 3573
ELEV #3
SERVICE
ELEV
LL2-016
ELEV #1
ELEV #2
WEST STAIR
EAST PARKING
SLOPE UP SLOPE DOWN
SLOPE DOWN
WEST PARKING
LL2-014
TRANSFORMER ROOM
EXHAUST
STORAGE
B-2010TRANSFORMER
ROOM LL2-010
B-2008
SWITCH
ROOM
B-2006
LL2-008
ELECTRICAL
B-2000
FUSE ROOM
B-2002
FUSE ROOM
B-2004
STORAGE
B-2012
0' 2' 8' 16'
SCALE: 1/8"=1'-0"
4'
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
JOB #
CHECKED BY
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
CHILDREN'S NUTRITION RESEARCH CENTER
HOUSTON, TX
BASEMENT LEVEL 2 - RCP
A1302
3 911/04/24
SME
CLR
DRL
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
2923-E
B. DEAN
XXX
D. CORDRAY
W. ROSS
BASEMENT LEVEL 2 - REFLECTED CEILING PLAN
SCALE: 1/8"=1'-0"
A1302
PLAN
NORTH
LINE OF EXTERIOR
WALL ABOVE
EXISTING CONCRETE
FLOOR / ROOF DECK
EXISTING PATIO,
DECK, OR ROOF EXISTING EXTERIOR CLADDING
EXISTING CMU
EXISTING CONCRETE BEAM
EXISTING CMU
LINE OF EXISTING
METAL STUDS
EXISTING FIBERGLASS
INSULATION
EXISTING ACOUSTICAL CEILING
EXISTING DRYWALL
NEW 4" FOAM INSULATION
PER "INSULATION NOTES"
NOTE: LIGHT FIXTURE LAYOUTS SHOWN IN
ARCHITECTURAL REFLECTED CEILING PLANS
ARE REPRESENTATIONAL OF EXISTING LIGHT
FIXTURE TYPES AND LAYOUTS.
0' 1' 2' 4' 6'
SCALE: 1/2"=1'-0"
INSULATION DETAILINSULATION NOTES LEGEND
DEMOLITION WORK
A. CONTRACTOR SHALL REMOVE ALL EXISTING SPRAY INSULATION
ON CONCRETE DECK.
B. CONTRACTOR SHALL CLEAN DECK THOROUGHLY AS REQUIRED
BY NEW SPRAY FOAM INSTRUCTIONS WHERE SHOWN ON THE
PLANS PER THE LEGEND AND DETAILS.
C. CONTRACTOR SHALL REMOVE ALL EXISTING FIBERGLASS
INSULATION FROM CEILING LEVEL UP TO DECK ON ALL EXTERIOR
WALLS WHERE SHOWN ON THE PLANS PER THE LEGEND.
D. CONTRACTOR SHALL PROVIDE PROTECTIVE WORK AREAS TO
KEEP DEMOLITION DEBRIS FROM GETTING INTO THE INTERIOR
WORK ENVIRONMENT AND FROM GETTING INTO RETURN AIR
HVAC SYSTEM PER 02 41 00. CONTRACTOR SHALL PROVIDE
FILTERING AT RETURN AIR SYSTEM. CONTRACTOR SHALL
REMOVE ALL LOOSE INSULATION DEBRIS DUE TO DEMOLITION
FROM WORK AREAS AND SPACES ABOVE CEILING.
E. CONTRACTOR SHALL BE RESPONSIBLE FOR MOVING FURNITURE
AS REQUIRED TO PERFORM THE DEMO WORK WHICH INCLUDES
BUT IS NOT LIMITED TO THE REMOVAL OF EXISTING FINISHES
(INCLUDING CEILING TILES).
REMOVE AND APPLY INSULATION ON
CONCRETE DECK PER "INSULATION NOTES"
NEW APPLICATIONS
EXISTING
EXPOSED
NEW WORK
A. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL INSULATION
AS SPECIFIED ON UNDERSIDE OF FLOOR / ROOF DECK AS DESCRIBED
HEREIN AND WHERE SHOWN ON THE PLANS PER THE LEGEND.
B. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL INSULATION
AS SPECIFIED ON EXTERIOR WALLS AS DESCRIBED HEREIN WHERE
SHOWN ON THE PLANS PER THE LEGEND.
C. CONTRACTOR SHALL APPLY INTUMESCENT COATING AS SPECIFIED
OVER ALL OF THE NEW SPRAY-APPLIED INSULATION.
D. CONTRACTOR SHALL BE RESPONSIBLE FOR RETURNING ALL
FURNITURE THAT WAS MOVED IN ORDER TO PERFORM THE SCOPE
OF WORK. ANY FINISHES DAMAGED DURING THE WORK SHALL BE
REPLACED LIKE IN-KIND.
E. PROVIDE 24"x24" ALUMINUM ACCESS DOORS AT GYPSUM BOARD OR
STUCCO CEILINGS FOR ACCESS TO PIPE CLEANOUTS. SEE THE
PLUMBING DRAWINGS FOR LOCATIONS OF EACH CLEANOUT. ACCESS
DOORS SHALL BE PAINTED TO MATCH ADJACENT CEILING COLOR.
REMOVE AND APPLY INSULATION ON
EXTERIOR WALL PER "INSULATION NOTES"
EXISTING
STUCCO / PLASTER
EXISTING CEILING FINISHES
EXISTING
GYP. BD.
EXISTING SACT
NO WORK
THIS FLOOR
1 04.04.2024 CLR REVISED HATCH PATTERNS AND
ADDED NOTE FOR ACCESS DOORS
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
HT
XET
TA
FO ET
S
R
EG
IS
SA
TC
E
IT
RERE A
CD
JE
RR
ELEV #3
SERVICE
ELEV
ELEV #1
ELEV #2
WEST
STAIR
FAN
ROOM
FAN
ROOM
EAST RAMP
BICYCLE
PARKING
MACHINE SHOP
B-1002
STORAGE
B1004
EQUIPMENT
ROOM
B1010
SWITCHGEAR
B-1012
MECHANICAL
EQUIPMENT
B1006
ENGINEER'S
OFFICE
B-1008
CENTRAL STAIR
ELEV
LOBBY
RAMP UP TO L1
CONTROL BOOTH
WEST RAMP
MOTOR BIKE
PARKING
PUMP ROOM
B-1016
CENTRAL PLANT
B-1014
STORAGE
B-1000
0' 2' 8' 16'
SCALE: 1/8"=1'-0"
4'
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
JOB #
CHECKED BY
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
CHILDREN'S NUTRITION RESEARCH CENTER
HOUSTON, TX
BASEMENT LEVEL 1 - RCP
A1303
4 911/04/24
SME
CLR
DRL
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
2923-E
B. DEAN
XXX
D. CORDRAY
W. ROSS
BASEMENT LEVEL 1 - REFLECTED CEILING PLAN
SCALE: 1/8"=1'-0"
A1303
PLAN
NORTH
LINE OF EXTERIOR
WALL ABOVE
EXISTING CONCRETE
FLOOR / ROOF DECK
EXISTING PATIO,
DECK, OR ROOF EXISTING EXTERIOR CLADDING
EXISTING CMU
EXISTING CONCRETE BEAM
EXISTING CMU
LINE OF EXISTING
METAL STUDS
EXISTING FIBERGLASS
INSULATION
EXISTING ACOUSTICAL CEILING
EXISTING DRYWALL
NEW 4" FOAM INSULATION
PER "INSULATION NOTES"
NOTE: LIGHT FIXTURE LAYOUTS SHOWN IN
ARCHITECTURAL REFLECTED CEILING PLANS
ARE REPRESENTATIONAL OF EXISTING LIGHT
FIXTURE TYPES AND LAYOUTS.
0' 1' 2' 4' 6'
SCALE: 1/2"=1'-0"
INSULATION DETAILINSULATION NOTES LEGEND
DEMOLITION WORK
A. CONTRACTOR SHALL REMOVE ALL EXISTING SPRAY INSULATION
ON CONCRETE DECK.
B. CONTRACTOR SHALL CLEAN DECK THOROUGHLY AS REQUIRED
BY NEW SPRAY FOAM INSTRUCTIONS WHERE SHOWN ON THE
PLANS PER THE LEGEND AND DETAILS.
C. CONTRACTOR SHALL REMOVE ALL EXISTING FIBERGLASS
INSULATION FROM CEILING LEVEL UP TO DECK ON ALL EXTERIOR
WALLS WHERE SHOWN ON THE PLANS PER THE LEGEND.
D. CONTRACTOR SHALL PROVIDE PROTECTIVE WORK AREAS TO
KEEP DEMOLITION DEBRIS FROM GETTING INTO THE INTERIOR
WORK ENVIRONMENT AND FROM GETTING INTO RETURN AIR
HVAC SYSTEM PER 02 41 00. CONTRACTOR SHALL PROVIDE
FILTERING AT RETURN AIR SYSTEM. CONTRACTOR SHALL
REMOVE ALL LOOSE INSULATION DEBRIS DUE TO DEMOLITION
FROM WORK AREAS AND SPACES ABOVE CEILING.
E. CONTRACTOR SHALL BE RESPONSIBLE FOR MOVING FURNITURE
AS REQUIRED TO PERFORM THE DEMO WORK WHICH INCLUDES
BUT IS NOT LIMITED TO THE REMOVAL OF EXISTING FINISHES
(INCLUDING CEILING TILES).
REMOVE AND APPLY INSULATION ON
CONCRETE DECK PER "INSULATION NOTES"
NEW APPLICATIONS
EXISTING
EXPOSED
NEW WORK
A. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL INSULATION
AS SPECIFIED ON UNDERSIDE OF FLOOR / ROOF DECK AS DESCRIBED
HEREIN AND WHERE SHOWN ON THE PLANS PER THE LEGEND.
B. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL INSULATION
AS SPECIFIED ON EXTERIOR WALLS AS DESCRIBED HEREIN WHERE
SHOWN ON THE PLANS PER THE LEGEND.
C. CONTRACTOR SHALL APPLY INTUMESCENT COATING AS SPECIFIED
OVER ALL OF THE NEW SPRAY-APPLIED INSULATION.
D. CONTRACTOR SHALL BE RESPONSIBLE FOR RETURNING ALL
FURNITURE THAT WAS MOVED IN ORDER TO PERFORM THE SCOPE
OF WORK. ANY FINISHES DAMAGED DURING THE WORK SHALL BE
REPLACED LIKE IN-KIND.
E. PROVIDE 24"x24" ALUMINUM ACCESS DOORS AT GYPSUM BOARD OR
STUCCO CEILINGS FOR ACCESS TO PIPE CLEANOUTS. SEE THE
PLUMBING DRAWINGS FOR LOCATIONS OF EACH CLEANOUT. ACCESS
DOORS SHALL BE PAINTED TO MATCH ADJACENT CEILING COLOR.
REMOVE AND APPLY INSULATION ON
EXTERIOR WALL PER "INSULATION NOTES"
EXISTING
STUCCO / PLASTER
EXISTING CEILING FINISHES
EXISTING
GYP. BD.
EXISTING SACT
NO WORK
THIS FLOOR
1 04.04.2024 CLR REVISED HATCH PATTERNS AND
ADDED NOTE FOR ACCESS DOORS
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
HT
XET
TA
FO ET
S
R
EG
IS
SA
TC
E
IT
RERE A
CD
JE
RR
FARM ANIMAL SUITE
JAN
JAN/STOR
PIGS
ANIMAL/REC DRIVEWAY
DRIVEWAY
SOUTH
STAIR
OFFICE
LOADING DOCK
RECEIVING OFFICE
CLOSET
1HC22
BULK CHENICAL
GENERAL STORAGE
RODENTS
CENTRAL CORRIDOR
GEN PURP STOR
ANIMAL/REC DOCK
FREEZER
1095A
TOILET
SOUTH
HALL
SOUTH
HALL
CAGE WASH/DIRTY
CAGE WASH/CLEAN
STORAGE
MECH
1024A
WEST HALL
HOLDING
TREAT
CHOW
CENTRAL
HALL
STOR
SPECIAL STUDIES
BEDDING
INV RM
HOLDING
WEST
HALL
SCRUB
PANTRY
1022A
FLURO ROOM
TELE
ELECTRICAL
CENTRAL JAN SUPPLY
NORTH
CORRIDOR
SECURITY OFF
DRY FOOD STORAGE
MEN
SWITCH ROOM
ELEV LOBBY
FIRE COMD STN
STAIR #5 ONLY
TO LEV 2
SCIENTIST OFF
GEN STORAGE/
HOUSEKEEPING
ELEV
#3
ELEV LOBBY
SERVICE
AREA
STAIR #2
CENTRAL STAIR
LOUNGE
TOILET
INFO & SECURITY
STORAGE
1101A
LAB
ANIMAL HVAC EQUIP ROOM
STAIR #1
LOBBY EXHIBIT
PIGS
PIGS
PIGS
CLOSET
RODENTS
RODENTS
RODENTS
RODENTS
ANIMAL
HOLDING
COOLER
RODENTS
RODENTS
RODENTS
SOWS
SOWS
PIGS
PIGS
PIGS
STORAGE
JAN
1084HOLDING
HOLDING
NORTH
HALL
TOILET
NORTH
HALL
AF1
LAB
LAB
LAB
LAB
ELEV
#4
ELEV
#5
EAST
CORRIDOR
WOMEN
ELEV
#1
ELEV
#2
NORTH
STAIR
0' 2' 8' 16'
SCALE: 1/8"=1'-0"
4'
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
JOB #
CHECKED BY
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
CHILDREN'S NUTRITION RESEARCH CENTER
HOUSTON, TX
FLOOR LEVEL 1 - RCP
A1304
5 911/04/24
SME
CLR
DRL
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
2923-E
B. DEAN
XXX
D. CORDRAY
W. ROSS
FLOOR LEVEL 1 - REFLECTED CEILING PLAN
SCALE: 1/8"=1'-0"
A1304
PLAN
NORTH
LINE OF EXTERIOR
WALL ABOVE
EXISTING CONCRETE
FLOOR / ROOF DECK
EXISTING PATIO,
DECK, OR ROOF EXISTING EXTERIOR CLADDING
EXISTING CMU
EXISTING CONCRETE BEAM
EXISTING CMU
LINE OF EXISTING
METAL STUDS
EXISTING FIBERGLASS
INSULATION
EXISTING ACOUSTICAL CEILING
EXISTING DRYWALL
NEW 4" FOAM INSULATION
PER "INSULATION NOTES"
NOTE: LIGHT FIXTURE LAYOUTS SHOWN IN
ARCHITECTURAL REFLECTED CEILING PLANS
ARE REPRESENTATIONAL OF EXISTING LIGHT
FIXTURE TYPES AND LAYOUTS.
0' 1' 2' 4' 6'
SCALE: 1/2"=1'-0"
INSULATION DETAILINSULATION NOTES LEGEND
DEMOLITION WORK
A. CONTRACTOR SHALL REMOVE ALL EXISTING SPRAY INSULATION
ON CONCRETE DECK.
B. CONTRACTOR SHALL CLEAN DECK THOROUGHLY AS REQUIRED
BY NEW SPRAY FOAM INSTRUCTIONS WHERE SHOWN ON THE
PLANS PER THE LEGEND AND DETAILS.
C. CONTRACTOR SHALL REMOVE ALL EXISTING FIBERGLASS
INSULATION FROM CEILING LEVEL UP TO DECK ON ALL EXTERIOR
WALLS WHERE SHOWN ON THE PLANS PER THE LEGEND.
D. CONTRACTOR SHALL PROVIDE PROTECTIVE WORK AREAS TO
KEEP DEMOLITION DEBRIS FROM GETTING INTO THE INTERIOR
WORK ENVIRONMENT AND FROM GETTING INTO RETURN AIR
HVAC SYSTEM PER 02 41 00. CONTRACTOR SHALL PROVIDE
FILTERING AT RETURN AIR SYSTEM. CONTRACTOR SHALL
REMOVE ALL LOOSE INSULATION DEBRIS DUE TO DEMOLITION
FROM WORK AREAS AND SPACES ABOVE CEILING.
E. CONTRACTOR SHALL BE RESPONSIBLE FOR MOVING FURNITURE
AS REQUIRED TO PERFORM THE DEMO WORK WHICH INCLUDES
BUT IS NOT LIMITED TO THE REMOVAL OF EXISTING FINISHES
(INCLUDING CEILING TILES).
REMOVE AND APPLY INSULATION ON
CONCRETE DECK PER "INSULATION NOTES"
NEW APPLICATIONS
EXISTING
EXPOSED
NEW WORK
A. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL INSULATION
AS SPECIFIED ON UNDERSIDE OF FLOOR / ROOF DECK AS DESCRIBED
HEREIN AND WHERE SHOWN ON THE PLANS PER THE LEGEND.
B. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL INSULATION
AS SPECIFIED ON EXTERIOR WALLS AS DESCRIBED HEREIN WHERE
SHOWN ON THE PLANS PER THE LEGEND.
C. CONTRACTOR SHALL APPLY INTUMESCENT COATING AS SPECIFIED
OVER ALL OF THE NEW SPRAY-APPLIED INSULATION.
D. CONTRACTOR SHALL BE RESPONSIBLE FOR RETURNING ALL
FURNITURE THAT WAS MOVED IN ORDER TO PERFORM THE SCOPE
OF WORK. ANY FINISHES DAMAGED DURING THE WORK SHALL BE
REPLACED LIKE IN-KIND.
E. PROVIDE 24"x24" ALUMINUM ACCESS DOORS AT GYPSUM BOARD OR
STUCCO CEILINGS FOR ACCESS TO PIPE CLEANOUTS. SEE THE
PLUMBING DRAWINGS FOR LOCATIONS OF EACH CLEANOUT. ACCESS
DOORS SHALL BE PAINTED TO MATCH ADJACENT CEILING COLOR.
REMOVE AND APPLY INSULATION ON
EXTERIOR WALL PER "INSULATION NOTES"
EXISTING
STUCCO / PLASTER
EXISTING CEILING FINISHES
EXISTING
GYP. BD.
EXISTING SACT
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
1 04.04.2024 CLR REVISED HATCH PATTERNS AND
ADDED NOTE FOR ACCESS DOORS
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
HT
XET
TA
FO ET
S
R
EG
IS
SA
TC
E
IT
RERE A
CD
JE
RR
JAN.
STORAGE
OFFICE
OFFICE
OFFICE
EDITOR
ASST.
EDITOR
ASST.
EDITOR
ILLUSTRATOR
DARK
RM.
PHOTO
STUDIO
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
DIRECTOR
CNRC
EMPLOYEE LOUNGE
OPEN
OFFICE
REPRODUCTION
CENTER
WORD PROCESSING
CLOSET
2HC20
SOUTH
CORR.
OPERATOR/TECH.
OFFICE
OFFICE
OFFICE
SECRETARY
CLOSET
2HC21
OFFICE
STORAGE
2060AOFFICE
OFFICE
OFFICE
OFFICE
EAST
CORRIDOR
SERVER
ROOM
TELECOM. ROOM
SVC.
CORR
CENTRAL
CORRIDOR
JANITOR
ELECTRICAL
ADMINISTRATIVE LOBBY
RECP.
COFFEE
2027A
RECEPTION
CONFERENCE ROOM
TERRACE
OFFICE
OFFICE
OFFICE
ELEV #3
SERVICE ELEV
LOBBY 2075
TELE
LIBRARIAN
CLOSET
2HC19
STORAGE
MAIL ROOM
ELEV #5 ELEV #4
ELEV LOBBY
ELEV #6 ELEV #7
AUDITORIUM
LOBBY
VENDING
OFFICE
CLOSET
WOMEN
MEN
CONTROL ROOM
PROJECTION ROOM
KITCHEN
CONFERENCE ROOM
PUBLIC
TEL.
STOR.
STAIR A
PROJ.
BOOTH
AUDITORIUM 2000
(OPEN TO ABOVE)
CORRIDOR
ARCHIVES
CLOSET
2HC18
STAIR #3
COPY RM
WEST
CORRIDOR
LIBRARY
0' 2' 8' 16'
SCALE: 1/8"=1'-0"
4'
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
JOB #
CHECKED BY
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
CHILDREN'S NUTRITION RESEARCH CENTER
HOUSTON, TX
FLOOR LEVEL 2 - RCP
A1305
6 911/04/24
SME
CLR
DRL
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
2923-E
B. DEAN
XXX
D. CORDRAY
W. ROSS
FLOOR LEVEL 2 - REFLECTED CEILING PLAN
SCALE: 1/8"=1'-0"
A1305
PLAN
NORTH
LINE OF EXTERIOR
WALL ABOVE
EXISTING CONCRETE
FLOOR / ROOF DECK
EXISTING PATIO,
DECK, OR ROOF EXISTING EXTERIOR CLADDING
EXISTING CMU
EXISTING CONCRETE BEAM
EXISTING CMU
LINE OF EXISTING
METAL STUDS
EXISTING FIBERGLASS
INSULATION
EXISTING ACOUSTICAL CEILING
EXISTING DRYWALL
NEW 4" FOAM INSULATION
PER "INSULATION NOTES"
NOTE: LIGHT FIXTURE LAYOUTS SHOWN IN
ARCHITECTURAL REFLECTED CEILING PLANS
ARE REPRESENTATIONAL OF EXISTING LIGHT
FIXTURE TYPES AND LAYOUTS.
0' 1' 2' 4' 6'
SCALE: 1/2"=1'-0"
INSULATION DETAILINSULATION NOTES LEGEND
DEMOLITION WORK
A. CONTRACTOR SHALL REMOVE ALL EXISTING SPRAY INSULATION
ON CONCRETE DECK.
B. CONTRACTOR SHALL CLEAN DECK THOROUGHLY AS REQUIRED
BY NEW SPRAY FOAM INSTRUCTIONS WHERE SHOWN ON THE
PLANS PER THE LEGEND AND DETAILS.
C. CONTRACTOR SHALL REMOVE ALL EXISTING FIBERGLASS
INSULATION FROM CEILING LEVEL UP TO DECK ON ALL EXTERIOR
WALLS WHERE SHOWN ON THE PLANS PER THE LEGEND.
D. CONTRACTOR SHALL PROVIDE PROTECTIVE WORK AREAS TO
KEEP DEMOLITION DEBRIS FROM GETTING INTO THE INTERIOR
WORK ENVIRONMENT AND FROM GETTING INTO RETURN AIR
HVAC SYSTEM PER 02 41 00. CONTRACTOR SHALL PROVIDE
FILTERING AT RETURN AIR SYSTEM. CONTRACTOR SHALL
REMOVE ALL LOOSE INSULATION DEBRIS DUE TO DEMOLITION
FROM WORK AREAS AND SPACES ABOVE CEILING.
E. CONTRACTOR SHALL BE RESPONSIBLE FOR MOVING FURNITURE
AS REQUIRED TO PERFORM THE DEMO WORK WHICH INCLUDES
BUT IS NOT LIMITED TO THE REMOVAL OF EXISTING FINISHES
(INCLUDING CEILING TILES).
REMOVE AND APPLY INSULATION ON
CONCRETE DECK PER "INSULATION NOTES"
NEW APPLICATIONS
EXISTING
EXPOSED
NEW WORK
A. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL INSULATION
AS SPECIFIED ON UNDERSIDE OF FLOOR / ROOF DECK AS DESCRIBED
HEREIN AND WHERE SHOWN ON THE PLANS PER THE LEGEND.
B. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL INSULATION
AS SPECIFIED ON EXTERIOR WALLS AS DESCRIBED HEREIN WHERE
SHOWN ON THE PLANS PER THE LEGEND.
C. CONTRACTOR SHALL APPLY INTUMESCENT COATING AS SPECIFIED
OVER ALL OF THE NEW SPRAY-APPLIED INSULATION.
D. CONTRACTOR SHALL BE RESPONSIBLE FOR RETURNING ALL
FURNITURE THAT WAS MOVED IN ORDER TO PERFORM THE SCOPE
OF WORK. ANY FINISHES DAMAGED DURING THE WORK SHALL BE
REPLACED LIKE IN-KIND.
E. PROVIDE 24"x24" ALUMINUM ACCESS DOORS AT GYPSUM BOARD OR
STUCCO CEILINGS FOR ACCESS TO PIPE CLEANOUTS. SEE THE
PLUMBING DRAWINGS FOR LOCATIONS OF EACH CLEANOUT. ACCESS
DOORS SHALL BE PAINTED TO MATCH ADJACENT CEILING COLOR.
REMOVE AND APPLY INSULATION ON
EXTERIOR WALL PER "INSULATION NOTES"
EXISTING
STUCCO / PLASTER
EXISTING CEILING FINISHES
EXISTING
GYP. BD.
EXISTING SACT
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
1 04.04.2024 CLR REVISED HATCH PATTERNS AND
ADDED NOTE FOR ACCESS DOORS
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
HT
XET
TA
FO ET
S
R
EG
IS
SA
TC
E
IT
RERE A
CD
JE
RR
BATHRM.BATHRM.BATHRM.BATHRM.
DWELLING UNITDWELLING UNIT
KIT EMPLOYEE LOUNGE
PROCEDURES
CENTRAL CORRIDOR
CORRIDOR
TELE.
DWELLING UNITDWELLING UNITDWELLING UNITDWELLING UNIT
WEST CORRIDOR
ATTENDANT
STATION
TOILETTOILET
BATHRM.BATHRM.
BATHRM. BATHRM.BATHRM.
STAIR #9
EAST CORRIDOR
3050C
3050J
3050H
3028 3030302630243022
3050B 3050A
CALIBRATION LAB
STAIR#6
LEV 3&4 ONLY
TERRACE
WEIGHING
MEN
DWELLING SUITE
BEDROOM
BATHRM.
DWELLING SUITE
BATHRM.
DWELLING UNIT
CORR.
JAN.
STAIR
VESTIBULE
WAITING &
ADULT DAY RM.
METABOLIC STORAGE
BATHRM.
DWELLING UNIT
DWELLING UNIT
DWELLING UNIT
CALORIMETER SUITE
3050E
3050D
3050F
3050G
PHYSICAL
EXERCISE LAB
CLINICAL
ANALYSIS
PHARMACY LAB
ELECTRICAL
LAUNDRY
TERRACE
DINING RM.
DISH RM.
3005B
BOTTLE WASH
3005A
WEIGHT STA.
JAN 3005
ELEV #6 ELEV #7
WOMEN
BREAK ROOM
MECHANICAL
STORAGE
FREEZER
3005J
COOLER
3005H
STAIR
VEST. 3062
STOR.
3005G
GENERAL
KITCHEN AREA
OFFICE
OFFICE
COMP.
3011A1
BAKERY
3005F
POT WASH
FREEZER
3005E
COOLER
3005D
W.S.
3005C
W.S. 4 W.S. 3 W.S. 2 W.S. 1
ELEVATOR
LOBBY
SERVICE
ELEV
ELEV #3ELEV #4ELEV #5
CORR.
KITCHEN
ELEV LOBBY
STAIR #1
AUDITORIUM
(OPEN TO BELOW)
0' 2' 8' 16'
SCALE: 1/8"=1'-0"
4'
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
JOB #
CHECKED BY
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
CHILDREN'S NUTRITION RESEARCH CENTER
HOUSTON, TX
FLOOR LEVEL 3 - RCP
A1306
7 911/04/24
SME
CLR
DRL
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
2923-E
B. DEAN
XXX
D. CORDRAY
W. ROSS
FLOOR LEVEL 3 - REFLECTED CEILING PLAN
SCALE: 1/8"=1'-0"
A1306
PLAN
NORTH
0' 1' 2' 4' 6'
SCALE: 1/2"=1'-0"
INSULATION NOTES LEGEND INSULATION DETAIL
LINE OF EXTERIOR
WALL ABOVE
EXISTING CONCRETE
FLOOR / ROOF DECK
EXISTING PATIO,
DECK, OR ROOF EXISTING EXTERIOR CLADDING
EXISTING CMU
EXISTING CONCRETE BEAM
EXISTING CMU
LINE OF EXISTING
METAL STUDS
EXISTING FIBERGLASS
INSULATION
EXISTING ACOUSTICAL CEILING
EXISTING DRYWALL
NEW 4" FOAM INSULATION
PER "INSULATION NOTES"
DEMOLITION WORK
A. CONTRACTOR SHALL REMOVE ALL EXISTING SPRAY INSULATION
ON CONCRETE DECK.
B. CONTRACTOR SHALL CLEAN DECK THOROUGHLY AS REQUIRED
BY NEW SPRAY FOAM INSTRUCTIONS WHERE SHOWN ON THE
PLANS PER THE LEGEND AND DETAILS.
C. CONTRACTOR SHALL REMOVE ALL EXISTING FIBERGLASS
INSULATION FROM CEILING LEVEL UP TO DECK ON ALL EXTERIOR
WALLS WHERE SHOWN ON THE PLANS PER THE LEGEND.
D. CONTRACTOR SHALL PROVIDE PROTECTIVE WORK AREAS TO
KEEP DEMOLITION DEBRIS FROM GETTING INTO THE INTERIOR
WORK ENVIRONMENT AND FROM GETTING INTO RETURN AIR
HVAC SYSTEM PER 02 41 00. CONTRACTOR SHALL PROVIDE
FILTERING AT RETURN AIR SYSTEM. CONTRACTOR SHALL
REMOVE ALL LOOSE INSULATION DEBRIS DUE TO DEMOLITION
FROM WORK AREAS AND SPACES ABOVE CEILING.
E. CONTRACTOR SHALL BE RESPONSIBLE FOR MOVING FURNITURE
AS REQUIRED TO PERFORM THE DEMO WORK WHICH INCLUDES
BUT IS NOT LIMITED TO THE REMOVAL OF EXISTING FINISHES
(INCLUDING CEILING TILES).
REMOVE AND APPLY INSULATION ON
CONCRETE DECK PER "INSULATION NOTES"
REMOVE AND APPLY INSULATION ON
EXTERIOR WALL PER "INSULATION NOTES"
NEW APPLICATIONS
EXISTING
STUCCO / PLASTER
EXISTING CEILING FINISHES
EXISTING
GYP. BD.
EXISTING
SACT
EXISTING
EXPOSED
NOTE: LIGHT FIXTURE LAYOUTS SHOWN IN
ARCHITECTURAL REFLECTED CEILING PLANS
ARE REPRESENTATIONAL OF EXISTING LIGHT
FIXTURE TYPES AND LAYOUTS.
NEW WORK
A. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL INSULATION
AS SPECIFIED ON UNDERSIDE OF FLOOR / ROOF DECK AS DESCRIBED
HEREIN AND WHERE SHOWN ON THE PLANS PER THE LEGEND.
B. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL INSULATION
AS SPECIFIED ON EXTERIOR WALLS AS DESCRIBED HEREIN WHERE
SHOWN ON THE PLANS PER THE LEGEND.
C. CONTRACTOR SHALL APPLY INTUMESCENT COATING AS SPECIFIED
OVER ALL OF THE NEW SPRAY-APPLIED INSULATION.
D. CONTRACTOR SHALL BE RESPONSIBLE FOR RETURNING ALL
FURNITURE THAT WAS MOVED IN ORDER TO PERFORM THE SCOPE
OF WORK. ANY FINISHES DAMAGED DURING THE WORK SHALL BE
REPLACED LIKE IN-KIND.
E. PROVIDE 24"x24" ALUMINUM ACCESS DOORS AT GYPSUM BOARD OR
STUCCO CEILINGS FOR ACCESS TO PIPE CLEANOUTS. SEE THE
PLUMBING DRAWINGS FOR LOCATIONS OF EACH CLEANOUT. ACCESS
DOORS SHALL BE PAINTED TO MATCH ADJACENT CEILING COLOR.
REMOVE EXISTING DRYWALL CEILING AND
APPLY INSULATION ON CONCRETE DECK
PER "INSULATION NOTES." INSTALL NEW
DRYWALL CEILING. SEE DRYWALL CEILINGS
REPAIR DETAILS.
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
DRYWALL CEILINGS REPAIR DETAILS
SCALE: 6"=1'-0"
A1306
FRAMED CEILING DETAIL
EXISTING HANGER WIRES TO REMAIN
EXISTING FRAMING MEMBERS TO REMAIN;
CONTRACTOR TO REMOVE AND RE-INSTALL
THESE FRAMING MEMBERS AS NECESSARY TO
PERFORM SCOPE OF WORK ABOVE CEILING
DEMOLISH ALL EXISTING DRYWALL CEILING
BOARD ALONG WITH CEILING-MOUNTED
LIGHTS, DIFFUSERS, ALARM, DEVICES, ETC.;
INSTALL NEW 1/2" DRYWALL CEILING BOARD
WITH LEVEL 4 FINISH AFTER ALL REQUIRED
WORK ABOVE CEILING IS COMPLETED.
RE-INSTALL ALL DIFFUSERS, ALARM, DEVICES,
ETC. IN-KIND. INSTALL NEW LIGHTS PER
ELECTRICAL REQUIREMENTS
SUSPENDED CEILING DETAIL
EXISTING FRAMING MEMBERS TO
REMAIN; CONTRACTOR TO
REMOVE AND RE-INSTALL THESE
FRAMING MEMBERS AS
NECESSARY TO PERFORM SCOPE
OF WORK ABOVE CEILING
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
DEMOLISH ALL EXISTING PLASTER CEILING
ALONG WITH CEILING-MOUNTED LIGHTS,
DIFFUSERS, ALARM, DEVICES, ETC.; INSTALL
NEW ACOUSTICAL PLASTER CEILING AS
SPECIFIED WITH LEVEL 4 FINISH AFTER ALL
REQUIRED WORK ABOVE CEILING IS
COMPLETED. RE-INSTALL ALL DIFFUSERS,
ALARM, DEVICES, ETC. IN-KIND. INSTALL NEW
LIGHTS PER ELECTRICAL REQUIREMENTS
0 1 1/2" 3" 6"
SCALE: 6"=1'-0"
1 04.04.2024 CLR REVISED HATCH PATTERNS AND
ADDED NOTE FOR ACCESS DOORS
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
HT
XET
TA
FO ET
S
R
EG
IS
SA
TC
E
IT
RERE A
CD
JE
RR
ELECT.
SOUTH
TERRACE
MECHANICAL
ROOM
STAIR VEST.
TERRACE
CORRIDOR
DAY ROOM
DAY ROOM
TOILETSTOR.
OFFICE
4004A
OFFICE
4004B
ADOLESCENT
EXERCISE &
ENTERTAINMENT
OFFICE
4004D
ATTENDANT
STATION
CENTRAL
CORRIDOR
SERVICE
ELEV.
TELE.
SHOWER
SUPPORT
PROCED
ELEV #3
EAST
CORRIDOR
TLT
CHANGE
WAITING
MEN
WOMEN
CHANGE
OFFICE
OFFICE
EAST
TERRACE
ACOUSTICS
4HC17
TOBEC
EXAM
ELEV #4ELEV #5
EXAM
ELEV #7ELEV #6
EMERGENCY
GENERATOR
MECHANICAL
ROOM
CORRIDOR
NORTHEAST
TERRACE
STAIR VEST.
NORTH
TERRACE
WEST
TERRACE
SOUTH STAIR
NORTH
STAIR
STAIR#6
LEV 3&4 ONLYCENTRAL STAIR
0' 2' 8' 16'
SCALE: 1/8"=1'-0"
4'
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
JOB #
CHECKED BY
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
CHILDREN'S NUTRITION RESEARCH CENTER
HOUSTON, TX
FLOOR LEVEL 4 - RCP
A1307
8 911/04/24
SME
CLR
DRL
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
2923-E
B. DEAN
XXX
D. CORDRAY
W. ROSS
FLOOR LEVEL 4 - REFLECTED CEILING PLAN
SCALE: 1/8"=1'-0"
A1307
PLAN
NORTH
WINDOW TYPE
CURTAIN WALL ELEVATION
SCALE: 1/4"=1'-0"
A1307
FLOOR LEVEL 4
ELEV. 94.00'
±49'-8" (EXISTING - VERIFY)
'-0
(E X
IS
T
IN
G
V
E R
IF
Y
4' -0
5'
-6
3' -6
2"
3' -1
2"
2" 3'
-7
2"
24'-41 2" 3'-0"
DOOR
22'-31 2"
9' -0
2" 3'-111
4" 21 2" 4'-61
4" 21 2" 4'-61
4" 21 2" 4'-61
4" 21 2" 4'-61
2" 21 2" 1'-11
2" 21 2" 1'-6" 21
2" 4'-11" 21 2" 4'-101
4" 21 2" 4'-101
4" 21 2" 4'-11"
2"
ALIGN TOP OF MULLION
IN-KIND WITH LINE OF
GRANITE TRIM (TYP)
ALIGN TOP OF MULLION
IN-KIND WITH CENTERLINE
OF GRANITE JOINT (TYP)
ALIGN CENTERLINE OF MULLION IN-KIND WITH CENTERLINE
OF VERTICAL GRANITE JOINT WHERE SHOWN (TYP)
GRANITE JOINT 'GJ' (TYP)
'GJ' 'GJ' 'GJ' 'GJ' 'GJ' 'GJ' 'GJ' 'GJ'
0' 2' 4' 8' 12'
SCALE: 1/4"=1'-0"
0' 1" 2" 3" 1'
SCALE: 3"=1'-0"
6"
EXISTING PATIO / FLOOR / ROOF SLAB (TYP)
PREFINISHED METAL SUBSILL FLASHING;
REPLACE EXISTING AND EXTEND NEW
BELOW TILE LIKE EXISTING FLASHING; SET
IN CONT. BED OF SEALANT (TYP)
CURTAIN WALL SYSTEM
AS SPECIFIED
PROTECT EXISTING WATERPROOF
MEMBRANE DURING CONSTRUCTION (TYP)
BACKER ROD AND
SEALANT (TYP) BACKER ROD AND SEALANT;
DO NOT BLOCK CURTAIN
WALL WEEP DRAIN (TYP)
EXISTING CONCRETE
PAVERS; REMOVE AND
REINSTALL ONLY AS REQ'D
TO INSTALL NEW SUBSILL
FLASHING (TYP)
GLAZING; RE: SECTION 08 81 00
CURTAIN WALL SILL DETAIL
SCALE: 3"=1'-0"
TYPICAL
CURTAIN WALL JAMB DETAIL
SCALE: 3"=1'-0"
TYPICALA1307 A1307
BACKER ROD AND
SEALANT (TYP)
EXISTING GRANITE
PANEL (TYP)
EXISTING JAMB FLASHING
TO REMAIN (TYP)
EXISTING SHEATHING (TYP)
EDGE OF EXISTING INTERIOR
WALL CONSTRUCTION (TYP)
BACKER ROD AND
SEALANT (TYP)
CURTAIN WALL SYSTEM
AS SPECIFIED
GLAZING AS SPECIFIED
CURTAIN WALL HEAD DETAIL
SCALE: 3"=1'-0"
TYPICALA1307
GLAZING AS SPECIFIED
CURTAIN WALL SYSTEM
AS SPECIFIED
PREFINISHED METAL HEAD FLASHING
AS SPECIFIED (TYP)
BACKER ROD AND SEALANT (TYP)
EXISTING GRANITE PANEL (TYP)
EXISTING SHEATHING (TYP)
EXISTING CONT. STEEL ANGLE
FOR ATTACHMENT OF CURTAIN
WALL SYSTEM; SCRAPE CLEAN,
PRIME, AND PAINT (TYP)
EXISTING STEEL ANGLE
BRACING (TYP)
NEW 4" FOAM INSULATION
PER "INSULATION NOTES"
REPLACE EXISTING 2'-8" WIDE DOOR WITH
NEW 36" WIDE DOOR TO MEET EXIT EGRESS;
MODIFY CURTAIN WALL FRAME AS REQ'D TO
ACCOMMODATE NEW DOOR WIDTH (TYP)
GLAZING AS SPECIFIED
BID OPTION 003 : REPLACE EXISTING CURTAIN
WALL SYSTEM LIKE IN-KIND AS SPECIFIED
'-8
(E X
IS
T
IN
G
V
E R
IF
Y
SHIM AS REQ'D
SHIM AS REQ'D
BACKER ROD AND
SEALANT (TYP)
SHIM AS REQ'D
EXISTING STEEL LINTEL (TYP)
CONTRACTOR SHALL TO FIELD VERIFY ALL DIMENSIONS AND DEPTHS OF EXISTING CURTAIN
WALL FRAMING AND GLAZING. CONTRACTOR SHALL CONSULT CONTRACTING OFFICER
IMMEDIATELY IF DISCREPANCIES ARE FOUND BETWEEN WHAT IS SHOWN IN THE DRAWINGS
AND SITE CONDITIONS, PRIOR TO SUBMITTAL OF SHOP DRAWINGS.
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
INSULATION NOTES
DEMOLITION WORK
A. CONTRACTOR SHALL REMOVE ALL EXISTING SPRAY
INSULATION ON CONCRETE DECK.
B. CONTRACTOR SHALL CLEAN DECK THOROUGHLY AS
REQUIRED BY NEW SPRAY FOAM INSTRUCTIONS WHERE
SHOWN ON THE PLANS PER THE LEGEND AND DETAILS.
C. CONTRACTOR SHALL REMOVE ALL EXISTING FIBERGLASS
INSULATION FROM CEILING LEVEL UP TO DECK ON ALL
EXTERIOR WALLS WHERE SHOWN ON THE PLANS PER THE
LEGEND.
D. CONTRACTOR SHALL PROVIDE PROTECTIVE WORK AREAS
TO KEEP DEMOLITION DEBRIS FROM GETTING INTO THE
INTERIOR WORK ENVIRONMENT AND FROM GETTING INTO
RETURN AIR HVAC SYSTEM PER 02 41 00. CONTRACTOR
SHALL PROVIDE FILTERING AT RETURN AIR SYSTEM.
CONTRACTOR SHALL REMOVE ALL LOOSE INSULATION
DEBRIS DUE TO DEMOLITION FROM WORK AREAS AND
SPACES ABOVE CEILING.
E. CONTRACTOR SHALL BE RESPONSIBLE FOR MOVING
FURNITURE AS REQUIRED TO PERFORM THE DEMO WORK
WHICH INCLUDES BUT IS NOT LIMITED TO THE REMOVAL OF
EXISTING FINISHES (INCLUDING CEILING TILES).
NEW WORK
A. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL
INSULATION AS SPECIFIED ON UNDERSIDE OF FLOOR / ROOF
DECK AS DESCRIBED HEREIN AND WHERE SHOWN ON THE
PLANS PER THE LEGEND.
B. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL
INSULATION AS SPECIFIED ON EXTERIOR WALLS AS
DESCRIBED HEREIN WHERE SHOWN ON THE PLANS PER THE
LEGEND.
C. CONTRACTOR SHALL APPLY INTUMESCENT COATING AS
SPECIFIED OVER ALL OF THE NEW SPRAY-APPLIED
INSULATION.
D. CONTRACTOR SHALL BE RESPONSIBLE FOR RETURNING
ALL FURNITURE THAT WAS MOVED IN ORDER TO PERFORM
THE SCOPE OF WORK. ANY FINISHES DAMAGED DURING THE
WORK SHALL BE REPLACED LIKE IN-KIND.
(BID OPTION 003)
(BID OPTION 003)(BID OPTION 003)(BID OPTION 003)
1 04.04.2024 CLR REVISED HATCH PATTERNS AND
ADDED NOTE FOR ACCESS DOORS
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
HT
XET
TA
FO ET
S
R
EG
IS
SA
TC
E
IT
RERE A
CD
JE
RR
JAN.
NORTH
CORRIDOR
CORRIDOR
EQUIP
OFFICE
OFFICE
OFFICE
OFFICE
LAB
EAST CORRIDOR
TELE.
DARK RM.
S O
U T
H C
O R
R
ID
O R
GLASS
WASH
OFFICE
PROCESS LAB.
VEST.
COLD RM.
COLD RM.
ELECT.
MALE
FEMALE
WEST CORRIDOR
ELEV. #7ELEV. #6
ELEV.
LOBBY
ELEV. #4ELEV. #5 ELEV. #3
SERV.
ELEV.
STORAGE
OFFICE
OFFICE
SECRETARY
& FILES 5082
OFFICE
OFFICE
STOR.
5000A
OFFICE
CONFERENCE
COFFEE
TECHNICIAN LOUNGE
OFFICE
EQUIP. LAB.
CORR.
CLOSET
5HC16
CHEM. LAB.
EXCREMENT
PROCESS'G.
STAIR C
LAB
LAB
LAB
CHEM. LAB.
CHEM. LAB.
CHEM. LAB.
CHEM. LAB.
CHEM. LAB.
STAIR B OFFICE
OFFICE
STAIR A
0' 2' 8' 16'
SCALE: 1/8"=1'-0"
4'
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
JOB #
CHECKED BY
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
CHILDREN'S NUTRITION RESEARCH CENTER
HOUSTON, TX
FLOOR LEVEL 5 - RCP
A1308
9 911/04/24
SME
CLR
DRL
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
2923-E
B. DEAN
XXX
D. CORDRAY
W. ROSS
FLOOR LEVEL 5 - REFLECTED CEILING PLAN
SCALE: 1/8"=1'-0"
A1308
PLAN
NORTH
LINE OF EXTERIOR
WALL ABOVE
EXISTING CONCRETE
FLOOR / ROOF DECK
EXISTING PATIO,
DECK, OR ROOF EXISTING EXTERIOR CLADDING
EXISTING CMU
EXISTING CONCRETE BEAM
EXISTING CMU
LINE OF EXISTING
METAL STUDS
EXISTING FIBERGLASS
INSULATION
EXISTING ACOUSTICAL CEILING
EXISTING DRYWALL
NEW 4" FOAM INSULATION
PER "INSULATION NOTES"
NOTE: LIGHT FIXTURE LAYOUTS SHOWN IN
ARCHITECTURAL REFLECTED CEILING PLANS
ARE REPRESENTATIONAL OF EXISTING LIGHT
FIXTURE TYPES AND LAYOUTS.
0' 1' 2' 4' 6'
SCALE: 1/2"=1'-0"
INSULATION DETAILINSULATION NOTES LEGEND
DEMOLITION WORK
A. CONTRACTOR SHALL REMOVE ALL EXISTING SPRAY INSULATION
ON CONCRETE DECK.
B. CONTRACTOR SHALL CLEAN DECK THOROUGHLY AS REQUIRED
BY NEW SPRAY FOAM INSTRUCTIONS WHERE SHOWN ON THE
PLANS PER THE LEGEND AND DETAILS.
C. CONTRACTOR SHALL REMOVE ALL EXISTING FIBERGLASS
INSULATION FROM CEILING LEVEL UP TO DECK ON ALL EXTERIOR
WALLS WHERE SHOWN ON THE PLANS PER THE LEGEND.
D. CONTRACTOR SHALL PROVIDE PROTECTIVE WORK AREAS TO
KEEP DEMOLITION DEBRIS FROM GETTING INTO THE INTERIOR
WORK ENVIRONMENT AND FROM GETTING INTO RETURN AIR
HVAC SYSTEM PER 02 41 00. CONTRACTOR SHALL PROVIDE
FILTERING AT RETURN AIR SYSTEM. CONTRACTOR SHALL
REMOVE ALL LOOSE INSULATION DEBRIS DUE TO DEMOLITION
FROM WORK AREAS AND SPACES ABOVE CEILING.
E. CONTRACTOR SHALL BE RESPONSIBLE FOR MOVING FURNITURE
AS REQUIRED TO PERFORM THE DEMO WORK WHICH INCLUDES
BUT IS NOT LIMITED TO THE REMOVAL OF EXISTING FINISHES
(INCLUDING CEILING TILES).
REMOVE AND APPLY INSULATION ON
CONCRETE DECK PER "INSULATION NOTES"
NEW APPLICATIONS
EXISTING
EXPOSED
NEW WORK
A. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL INSULATION
AS SPECIFIED ON UNDERSIDE OF FLOOR / ROOF DECK AS DESCRIBED
HEREIN AND WHERE SHOWN ON THE PLANS PER THE LEGEND.
B. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL INSULATION
AS SPECIFIED ON EXTERIOR WALLS AS DESCRIBED HEREIN WHERE
SHOWN ON THE PLANS PER THE LEGEND.
C. CONTRACTOR SHALL APPLY INTUMESCENT COATING AS SPECIFIED
OVER ALL OF THE NEW SPRAY-APPLIED INSULATION.
D. CONTRACTOR SHALL BE RESPONSIBLE FOR RETURNING ALL
FURNITURE THAT WAS MOVED IN ORDER TO PERFORM THE SCOPE
OF WORK. ANY FINISHES DAMAGED DURING THE WORK SHALL BE
REPLACED LIKE IN-KIND.
E. PROVIDE 24"x24" ALUMINUM ACCESS DOORS AT GYPSUM BOARD OR
STUCCO CEILINGS FOR ACCESS TO PIPE CLEANOUTS. SEE THE
PLUMBING DRAWINGS FOR LOCATIONS OF EACH CLEANOUT. ACCESS
DOORS SHALL BE PAINTED TO MATCH ADJACENT CEILING COLOR.
REMOVE AND APPLY INSULATION ON
EXTERIOR WALL PER "INSULATION NOTES"
EXISTING
STUCCO / PLASTER
EXISTING CEILING FINISHES
EXISTING
GYP. BD.
EXISTING SACT
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
1 04.04.2024 CLR REVISED HATCH PATTERNS AND
ADDED NOTE FOR ACCESS DOORS
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
HT
XET
TA
FO ET
S
R
EG
IS
SA
TC
E
IT
RERE A
CD
JE
RR
ELEV. #6 ELEV. #7
ELECT.
TELE.
SOUTH
COLD RM.
DARK RM.
CORRIDOR
OFFICE
OVEN RM.
LAB
BIO LAB
LAB
LAB
BIO LAB
BIO LAB
BIO LAB
BIO LAB
LAB STORAGE
OFFICE
OFFICE
EQUIP
LAB
LAB
OFFICE
LAB
SEC'Y &
FILES
CORRIDOR
CLOSET
6HC12
WEST CORRIDOR
CHEM. LAB.
LEUKOCYTE
BIOLOGY
OFFICE
OFFICE
GLASS
WASH
MALE
FEMALE
JAN.
STORAGE
ELEV. #3
SERV. ELEV.
ELEV. #4ELEV. #5
ELEV. LOBBY
NORTH
CORRIDOR
STOR.
6000A
CONFERENCE
COFFEE
ANTE RM.
CORRIDOR
TECHNICIAN
LOUNGE
EQUIP. LAB.
EQUIP. LAB.
OFFICE
OFFICE
OFFICE
OFFICE
STAIR C
SOUTH STAIR
CENTRAL STAIR
NORTH STAIR
CHEM. LAB.
EAST CORRIDOR
CHEM. LAB.
CHEM. LAB.
CHEM.
LAB.
0' 2' 8' 16'
SCALE: 1/8"=1'-0"
4'
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
JOB #
CHECKED BY
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
CHILDREN'S NUTRITION RESEARCH CENTER
HOUSTON, TX
FLOOR LEVEL 6 - RCP
A1309
10 911/04/24
SME
CLR
DRL
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
2923-E
B. DEAN
XXX
D. CORDRAY
W. ROSS
FLOOR LEVEL 6 - REFLECTED CEILING PLAN
SCALE: 1/8"=1'-0"
A1309
PLAN
NORTH
LINE OF EXTERIOR
WALL ABOVE
EXISTING CONCRETE
FLOOR / ROOF DECK
EXISTING PATIO,
DECK, OR ROOF EXISTING EXTERIOR CLADDING
EXISTING CMU
EXISTING CONCRETE BEAM
EXISTING CMU
LINE OF EXISTING
METAL STUDS
EXISTING FIBERGLASS
INSULATION
EXISTING ACOUSTICAL CEILING
EXISTING DRYWALL
NEW 4" FOAM INSULATION
PER "INSULATION NOTES"
NOTE: LIGHT FIXTURE LAYOUTS SHOWN IN
ARCHITECTURAL REFLECTED CEILING PLANS
ARE REPRESENTATIONAL OF EXISTING LIGHT
FIXTURE TYPES AND LAYOUTS.
0' 1' 2' 4' 6'
SCALE: 1/2"=1'-0"
INSULATION DETAILINSULATION NOTES LEGEND
DEMOLITION WORK
A. CONTRACTOR SHALL REMOVE ALL EXISTING SPRAY INSULATION
ON CONCRETE DECK.
B. CONTRACTOR SHALL CLEAN DECK THOROUGHLY AS REQUIRED
BY NEW SPRAY FOAM INSTRUCTIONS WHERE SHOWN ON THE
PLANS PER THE LEGEND AND DETAILS.
C. CONTRACTOR SHALL REMOVE ALL EXISTING FIBERGLASS
INSULATION FROM CEILING LEVEL UP TO DECK ON ALL EXTERIOR
WALLS WHERE SHOWN ON THE PLANS PER THE LEGEND.
D. CONTRACTOR SHALL PROVIDE PROTECTIVE WORK AREAS TO
KEEP DEMOLITION DEBRIS FROM GETTING INTO THE INTERIOR
WORK ENVIRONMENT AND FROM GETTING INTO RETURN AIR
HVAC SYSTEM PER 02 41 00. CONTRACTOR SHALL PROVIDE
FILTERING AT RETURN AIR SYSTEM. CONTRACTOR SHALL
REMOVE ALL LOOSE INSULATION DEBRIS DUE TO DEMOLITION
FROM WORK AREAS AND SPACES ABOVE CEILING.
E. CONTRACTOR SHALL BE RESPONSIBLE FOR MOVING FURNITURE
AS REQUIRED TO PERFORM THE DEMO WORK WHICH INCLUDES
BUT IS NOT LIMITED TO THE REMOVAL OF EXISTING FINISHES
(INCLUDING CEILING TILES).
REMOVE AND APPLY INSULATION ON
CONCRETE DECK PER "INSULATION NOTES"
NEW APPLICATIONS
EXISTING
EXPOSED
NEW WORK
A. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL INSULATION
AS SPECIFIED ON UNDERSIDE OF FLOOR / ROOF DECK AS DESCRIBED
HEREIN AND WHERE SHOWN ON THE PLANS PER THE LEGEND.
B. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL INSULATION
AS SPECIFIED ON EXTERIOR WALLS AS DESCRIBED HEREIN WHERE
SHOWN ON THE PLANS PER THE LEGEND.
C. CONTRACTOR SHALL APPLY INTUMESCENT COATING AS SPECIFIED
OVER ALL OF THE NEW SPRAY-APPLIED INSULATION.
D. CONTRACTOR SHALL BE RESPONSIBLE FOR RETURNING ALL
FURNITURE THAT WAS MOVED IN ORDER TO PERFORM THE SCOPE
OF WORK. ANY FINISHES DAMAGED DURING THE WORK SHALL BE
REPLACED LIKE IN-KIND.
E. PROVIDE 24"x24" ALUMINUM ACCESS DOORS AT GYPSUM BOARD OR
STUCCO CEILINGS FOR ACCESS TO PIPE CLEANOUTS. SEE THE
PLUMBING DRAWINGS FOR LOCATIONS OF EACH CLEANOUT. ACCESS
DOORS SHALL BE PAINTED TO MATCH ADJACENT CEILING COLOR.
REMOVE AND APPLY INSULATION ON
EXTERIOR WALL PER "INSULATION NOTES"
EXISTING
STUCCO / PLASTER
EXISTING CEILING FINISHES
EXISTING
GYP. BD.
EXISTING SACT
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
1 04.04.2024 CLR REVISED HATCH PATTERNS AND
ADDED NOTE FOR ACCESS DOORS
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
HT
XET
TA
FO ET
S
R
EG
IS
SA
TC
E
IT
RERE A
CD
JE
RR
ELEV. #3
ELEV. #4ELEV. #5
ELEV. #6 ELEV. #7
GAS
ISOTOPE
LAB.
COMBUST
DIGEST
SAMPLE
PURIFICATION RM.
STORAGE
SERV. ELEV.
SEC'Y. & FILES
OFFICE
CORR
CLOSET
7HC11
BIOCHEM. LAB.
CHEM.
LAB.
LAB. STOR.
OFFICE
OFFICE
GAS
ISOTOPE
LAB.
EQUIP
OFFICE
OFFICE
T.I.M.S.
ANTE
ASHING
FILAMENT
CLEAN RM.
SAMPLE ISOL.
DERIVATION GC LAB.
SOUTH
CORRIDOR
REF. STOR.
CLOSET
7HC10
PROTOCOL
KIT. STOR.
REF. STOR.
7019DISP. RET
ELECT.
7063TELE.
JAN.
MALE
FEMALE
WEST CORRIDOR
PROCEDURE
BIO-CHEM. LAB.
G.C.M.S. II
COMPUTER
STORAGE
TECHNICIAN
LOUNGE
COFFEE
EQUIP. LAB.
STORAGE
CONFERENCE
NORTH
CORRIDOR ELEV. LOBBY
STOR.
7000A
OFFICE
CLOSET
7HC9
CLOSET
7HC8
OFFICE
OFFICE
PAPER STOR.
E. CORRIDOR
OFFICE
OFFICE
CORR
G.C.M.S. I
0' 2' 8' 16'
SCALE: 1/8"=1'-0"
4'
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
JOB #
CHECKED BY
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
CHILDREN'S NUTRITION RESEARCH CENTER
HOUSTON, TX
FLOOR LEVEL 7 - RCP
A1310
11 911/04/24
SME
CLR
DRL
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
2923-E
B. DEAN
XXX
D. CORDRAY
W. ROSS
FLOOR LEVEL 7 - REFLECTED CEILING PLAN
SCALE: 1/8"=1'-0"
A1310
PLAN
NORTH
LINE OF EXTERIOR
WALL ABOVE
EXISTING CONCRETE
FLOOR / ROOF DECK
EXISTING PATIO,
DECK, OR ROOF EXISTING EXTERIOR CLADDING
EXISTING CMU
EXISTING CONCRETE BEAM
EXISTING CMU
LINE OF EXISTING
METAL STUDS
EXISTING FIBERGLASS
INSULATION
EXISTING ACOUSTICAL CEILING
EXISTING DRYWALL
NEW 4" FOAM INSULATION
PER "INSULATION NOTES"
NOTE: LIGHT FIXTURE LAYOUTS SHOWN IN
ARCHITECTURAL REFLECTED CEILING PLANS
ARE REPRESENTATIONAL OF EXISTING LIGHT
FIXTURE TYPES AND LAYOUTS.
0' 1' 2' 4' 6'
SCALE: 1/2"=1'-0"
INSULATION DETAILINSULATION NOTES LEGEND
DEMOLITION WORK
A. CONTRACTOR SHALL REMOVE ALL EXISTING SPRAY INSULATION
ON CONCRETE DECK.
B. CONTRACTOR SHALL CLEAN DECK THOROUGHLY AS REQUIRED
BY NEW SPRAY FOAM INSTRUCTIONS WHERE SHOWN ON THE
PLANS PER THE LEGEND AND DETAILS.
C. CONTRACTOR SHALL REMOVE ALL EXISTING FIBERGLASS
INSULATION FROM CEILING LEVEL UP TO DECK ON ALL EXTERIOR
WALLS WHERE SHOWN ON THE PLANS PER THE LEGEND.
D. CONTRACTOR SHALL PROVIDE PROTECTIVE WORK AREAS TO
KEEP DEMOLITION DEBRIS FROM GETTING INTO THE INTERIOR
WORK ENVIRONMENT AND FROM GETTING INTO RETURN AIR
HVAC SYSTEM PER 02 41 00. CONTRACTOR SHALL PROVIDE
FILTERING AT RETURN AIR SYSTEM. CONTRACTOR SHALL
REMOVE ALL LOOSE INSULATION DEBRIS DUE TO DEMOLITION
FROM WORK AREAS AND SPACES ABOVE CEILING.
E. CONTRACTOR SHALL BE RESPONSIBLE FOR MOVING FURNITURE
AS REQUIRED TO PERFORM THE DEMO WORK WHICH INCLUDES
BUT IS NOT LIMITED TO THE REMOVAL OF EXISTING FINISHES
(INCLUDING CEILING TILES).
REMOVE AND APPLY INSULATION ON
CONCRETE DECK PER "INSULATION NOTES"
NEW APPLICATIONS
EXISTING
EXPOSED
NEW WORK
A. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL INSULATION
AS SPECIFIED ON UNDERSIDE OF FLOOR / ROOF DECK AS DESCRIBED
HEREIN AND WHERE SHOWN ON THE PLANS PER THE LEGEND.
B. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL INSULATION
AS SPECIFIED ON EXTERIOR WALLS AS DESCRIBED HEREIN WHERE
SHOWN ON THE PLANS PER THE LEGEND.
C. CONTRACTOR SHALL APPLY INTUMESCENT COATING AS SPECIFIED
OVER ALL OF THE NEW SPRAY-APPLIED INSULATION.
D. CONTRACTOR SHALL BE RESPONSIBLE FOR RETURNING ALL
FURNITURE THAT WAS MOVED IN ORDER TO PERFORM THE SCOPE
OF WORK. ANY FINISHES DAMAGED DURING THE WORK SHALL BE
REPLACED LIKE IN-KIND.
E. PROVIDE 24"x24" ALUMINUM ACCESS DOORS AT GYPSUM BOARD OR
STUCCO CEILINGS FOR ACCESS TO PIPE CLEANOUTS. SEE THE
PLUMBING DRAWINGS FOR LOCATIONS OF EACH CLEANOUT. ACCESS
DOORS SHALL BE PAINTED TO MATCH ADJACENT CEILING COLOR.
REMOVE AND APPLY INSULATION ON
EXTERIOR WALL PER "INSULATION NOTES"
EXISTING
STUCCO / PLASTER
EXISTING CEILING FINISHES
EXISTING
GYP. BD.
EXISTING SACT
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
1 04.04.2024 CLR REVISED HATCH PATTERNS AND
ADDED NOTE FOR ACCESS DOORS
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
HT
XET
TA
FO ET
S
R
EG
IS
SA
TC
E
IT
RERE A
CD
JE
RR
CHEM.
LAB.
CHEM. LAB.
EQUIP. LAB.
TECHNICIAN
LOUNGE
COFFEE
CHEM. LAB.
STOR.
CONFERENCE
STOR.
OFFICE
OFFICE
OFFICE
OFFICE
COMPUTER
CHEM. LAB. CHEM.LAB.
TELE.
SERV.
WOMEN
MEN
ELECT.
CHEM. LAB.
CHEM. LAB.CHEM. LAB.
STORAGE
JAN.
CHEM. LAB. CHEM. LAB.
CHEM. LAB.
FREEZERS
SOUTH
STORAGE
DARK RM.
COLD RM.
GLASS
WASH
OFFICE
OFFICE
EQUIP.
LAB.
COLD RM.
LAB.
CHEM.
LAB.
OFFICEGRAD.
STUDENT
& FILES
SECRETARY
ELEV. 6 ELEV. 7 ELEV. 3
ELEV. 6
ELEV 7
EAST CORRIDOR
NORTH
CORRIDOR
CORRIDOR
WEST CORRIDOR
8010 8014
8006 80088004 8012
8000A
8056 80548060 8058
80518024
ELEVATOR LOBBY
CORR
ELEV.
OFFICE
SPEC.
PROC. LAB.
CLOSET
8HC7
CORR
0' 2' 8' 16'
SCALE: 1/8"=1'-0"
4'
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
JOB #
CHECKED BY
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
CHILDREN'S NUTRITION RESEARCH CENTER
HOUSTON, TX
FLOOR LEVEL 8 - RCP
A1311
12 911/04/24
SME
CLR
DRL
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
2923-E
B. DEAN
XXX
D. CORDRAY
W. ROSS
FLOOR LEVEL 8 - REFLECTED CEILING PLAN
SCALE: 1/8"=1'-0"
A1311
PLAN
NORTH
LINE OF EXTERIOR
WALL ABOVE
EXISTING CONCRETE
FLOOR / ROOF DECK
EXISTING PATIO,
DECK, OR ROOF EXISTING EXTERIOR CLADDING
EXISTING CMU
EXISTING CONCRETE BEAM
EXISTING CMU
LINE OF EXISTING
METAL STUDS
EXISTING FIBERGLASS
INSULATION
EXISTING ACOUSTICAL CEILING
EXISTING DRYWALL
NEW 4" FOAM INSULATION
PER "INSULATION NOTES"
NOTE: LIGHT FIXTURE LAYOUTS SHOWN IN
ARCHITECTURAL REFLECTED CEILING PLANS
ARE REPRESENTATIONAL OF EXISTING LIGHT
FIXTURE TYPES AND LAYOUTS.
0' 1' 2' 4' 6'
SCALE: 1/2"=1'-0"
INSULATION DETAILINSULATION NOTES LEGEND
DEMOLITION WORK
A. CONTRACTOR SHALL REMOVE ALL EXISTING SPRAY INSULATION
ON CONCRETE DECK.
B. CONTRACTOR SHALL CLEAN DECK THOROUGHLY AS REQUIRED
BY NEW SPRAY FOAM INSTRUCTIONS WHERE SHOWN ON THE
PLANS PER THE LEGEND AND DETAILS.
C. CONTRACTOR SHALL REMOVE ALL EXISTING FIBERGLASS
INSULATION FROM CEILING LEVEL UP TO DECK ON ALL EXTERIOR
WALLS WHERE SHOWN ON THE PLANS PER THE LEGEND.
D. CONTRACTOR SHALL PROVIDE PROTECTIVE WORK AREAS TO
KEEP DEMOLITION DEBRIS FROM GETTING INTO THE INTERIOR
WORK ENVIRONMENT AND FROM GETTING INTO RETURN AIR
HVAC SYSTEM PER 02 41 00. CONTRACTOR SHALL PROVIDE
FILTERING AT RETURN AIR SYSTEM. CONTRACTOR SHALL
REMOVE ALL LOOSE INSULATION DEBRIS DUE TO DEMOLITION
FROM WORK AREAS AND SPACES ABOVE CEILING.
E. CONTRACTOR SHALL BE RESPONSIBLE FOR MOVING FURNITURE
AS REQUIRED TO PERFORM THE DEMO WORK WHICH INCLUDES
BUT IS NOT LIMITED TO THE REMOVAL OF EXISTING FINISHES
(INCLUDING CEILING TILES).
REMOVE AND APPLY INSULATION ON
CONCRETE DECK PER "INSULATION NOTES"
NEW APPLICATIONS
EXISTING
EXPOSED
NEW WORK
A. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL INSULATION
AS SPECIFIED ON UNDERSIDE OF FLOOR / ROOF DECK AS DESCRIBED
HEREIN AND WHERE SHOWN ON THE PLANS PER THE LEGEND.
B. CONTRACTOR SHALL SPRAY-APPLY 4" OF CLOSED-CELL INSULATION
AS SPECIFIED ON EXTERIOR WALLS AS DESCRIBED HEREIN WHERE
SHOWN ON THE PLANS PER THE LEGEND.
C. CONTRACTOR SHALL APPLY INTUMESCENT COATING AS SPECIFIED
OVER ALL OF THE NEW SPRAY-APPLIED INSULATION.
D. CONTRACTOR SHALL BE RESPONSIBLE FOR RETURNING ALL
FURNITURE THAT WAS MOVED IN ORDER TO PERFORM THE SCOPE
OF WORK. ANY FINISHES DAMAGED DURING THE WORK SHALL BE
REPLACED LIKE IN-KIND.
E. PROVIDE 24"x24" ALUMINUM ACCESS DOORS AT GYPSUM BOARD OR
STUCCO CEILINGS FOR ACCESS TO PIPE CLEANOUTS. SEE THE
PLUMBING DRAWINGS FOR LOCATIONS OF EACH CLEANOUT. ACCESS
DOORS SHALL BE PAINTED TO MATCH ADJACENT CEILING COLOR.
REMOVE AND APPLY INSULATION ON
EXTERIOR WALL PER "INSULATION NOTES"
EXISTING
STUCCO / PLASTER
EXISTING CEILING FINISHES
EXISTING
GYP. BD.
EXISTING SACT
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
PROVIDE SPRAY-APPLIED
INSULATION AT EXTERIOR
WALL ABOVE CEILING;
RE: INSULATION NOTES
1 04.04.2024 CLR REVISED HATCH PATTERNS AND
ADDED NOTE FOR ACCESS DOORS
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
HT
XET
TA
FO ET
S
R
EG
IS
SA
TC
E
IT
RERE A
CD
JE
RR
ELEV. #6 ELEV. #7
JAN.
STORAGE
ELECT.
TELE.
MALE
FEMALE
OFFICE
COLD RM.
COLD RM.
STOR.
CORR
EQUIP. LAB.
CORR
OFFICE
DARK RM.
TECHNICIAN
EQUIP. LAB.
EAST CORRIDOR
NORTH
CORRIDOR
WEST CORRIDOR
OFFICE
GLASS
WASH
LOUNGE
COFFEE
CONFERENCE
STOR.
OFFICE
ELEV. LOBBY
OFFICE
OFFICE SECRETARY
& FILES
OFFICE
CHEM. LAB.
TERM'. RM.
CHEM. LAB.
CHEM. LAB.
CHEM.
LAB.
HOT RM.
LAB. STOR.
CHEM. LAB.
LAB.
CHEM. LAB.CHEM. LAB.CHEM. LAB.CHEM. LAB.CHEM. LAB.
CHEM. LAB.
CHEM.
LAB.
90529054
9015 9019
9004 9008 90109006
9000A
CLOSET
CLOSET
SERV ELEV.
OFFICE
BOILER
0' 2' 8' 16'
SCALE: 1/8"=1'-0"
4'
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
JOB #
CHECKED BY
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
CHILDREN'S NUTRITION RESEARCH CENTER
HOUSTON, TX
FLOOR LEVEL 9 - RCP
A1312
13 911/04/24
SME
CLR
DRL
2150 CENTRE AVENUE
BLDG D, SUITE 300
FORT COLLINS, CO
XXX
2923-E
B. DEAN
XXX
D. CORDRAY
W. ROSS
FLOOR LEVEL 9 - REFLECTED CEILING PLAN
SCALE: 1/8"=1'-0"
A1312
PLAN
NORTH
LINE OF EXTERIOR
WALL ABOVE
EXISTING CONCRETE
FLOOR / ROOF DECK
EXISTING PATIO,
DECK, OR ROOF EXISTING EXTERIOR CLADDING
EXISTING CMU
EXISTING CONCRETE BEAM
EXISTING CMU
LINE OF EXISTING
METAL STUDS
EXISTING FIBERGLASS
INSULATION
EXISTING ACOUSTICAL CEILING
EXISTING DRYWALL
NEW 4" FOAM INSULATION
PER "INSULATION NOTES"
NOTE: LIGHT FIXTURE LAYOUTS SHOWN IN
ARCHITECTURAL REFLECTED CEILING PLANS
ARE REPRESENTATIONAL OF EXISTING LIGHT
FIXTURE TYPES AND…