ATTACHMENT 12 Dehumidification.docx
DOCX document 666 KB Posted
- Solicitation number
- N00024-21-R-4204
About this file
This document contains inspection guidelines and templates for the operation and maintenance of dehumidification systems aboard inactive vessels in Pearl Harbor. The templates provide guidance for inspecting elapsed run times, zone humidity levels, filter changes, and documenting any discrepancies. The related federal contract opportunity is solicitation number N00024-21-R-4204, issued by the Department of the Navy Naval Sea Systems Command, to provide operation and maintenance services for inactive vessels, with proposals due by April 7, 2022. The templates include details on inspection procedures for dehumidification machines and systems, while the solicitation provides an opportunity for contractors to bid on operating and maintaining these inactive vessels in Pearl Harbor.
View the file
Other files
Show all 47
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Periodicity:
Spec Code:
Berthed At:
Quarter:
NSTM 50 INSPECTION GUIDELINES
DH1
Insp Date:
TDL
Remarks N/A
NO
YES
Description Item Record elapsed time meter readings and date. Are machines operating less than 50% of the time?
Is machine operable ? (Start idle machine manually to ensure operability.)
Have all other discrepancies been reported? If not report them here.
D/H Elapsed Time FWD Draft:
AFT Draft:
List:
Comments:
Inspector Inspector Inspection Manager Elapsed Time Data Table Machine Date E.T.I.
Date Hours Run Elapsed Time Operation
Attachment 11 NSTM 50 INSPECTION GUIDELINES - Descrepancy Listing Spec Code:
Line Item # Location Discrepancy Discovery Dt Correction Dt
Berthed At:
Quarter:
NSTM 50 INSPECTION GUIDELINES
DH2
Insp Date:
TDL
Remarks N/A
NO
YES
Description Item Are average zone readings 40% RH (+ or - 5%)?
Are individual relative humidity (RH) readings 45% or less?
Are air zones in balance? (High or low zone readings within plus or minus 5% RH of the zone average.)
Are permanent zone closures and blanks properly sealed, painted and stenciled?
Access closures operate and seal properly?
Are all exterior hatches, vent openings and huts properly sealed?
Are individual humidistats locations properly identified and labled?
Have all other discrepancies been reported? If not report them here.
D/H Inspection
FWD Draft:
AFT Draft:
List:
Comments:
Inspector Inspector Inspection Manager Elapsed Time Data Table Zone H1 H2 H3 H4 H5 Avg.
Zone H1 H2 H3 H4 H5 Avg.
Topside Hut R.H. and Test Specimen Data Table Zone H1 H2 H3 H4 H5 Avg.
Zone H1 H2 H3 H4 H5 Avg.
Line Item # Location Discrepancy
Berthed At:
Quarter:
NSTM 50 INSPECTION GUIDELINES
DH3
Insp Date:
TDL
Remarks N/A
NO
YES
Description Item Are filters on DH machines located on the interior of the vessel being changed Annually?
Have all other discrepancies been reported? If not report them here.
D/H Filters (Inspection) FWD Draft:
AFT Draft:
List:
Comments:
Inspector Inspector Inspection Manager
Line Item # Location Discrepancy
Berthed At:
Quarter:
NSTM 50 INSPECTION GUIDELINES
DH4
Insp Date:
TDL
Remarks N/A
NO
YES
Description Item Are filters on DH machines located on the weather decks of the vessel being changed Annually?
Have all other discrepancies been reported? If not report them here.
D/H Filters (Topside) FWD Draft:
AFT Draft:
List:
Comments:
Inspector Inspector Inspection Manager
Line Item # Location Discrepancy