ATTACHMENT 12 Dehumidification.docx

DOCX document 666 KB Posted

Attached to
Operation and Maintenance of Pearl Harbor Inactive Vessels
Solicitation number
N00024-21-R-4204
Issued by

About this file

This document contains inspection guidelines and templates for the operation and maintenance of dehumidification systems aboard inactive vessels in Pearl Harbor. The templates provide guidance for inspecting elapsed run times, zone humidity levels, filter changes, and documenting any discrepancies. The related federal contract opportunity is solicitation number N00024-21-R-4204, issued by the Department of the Navy Naval Sea Systems Command, to provide operation and maintenance services for inactive vessels, with proposals due by April 7, 2022. The templates include details on inspection procedures for dehumidification machines and systems, while the solicitation provides an opportunity for contractors to bid on operating and maintaining these inactive vessels in Pearl Harbor.

View the file

Other files

File Type Posted
Attachment J-1 Pre-Proposal Information Form 4.21.22.pdf PDF
Exhbt C - Past Performance Questionnaire Rev 1.docx DOCX document
Attachment J-1 Rev 1 19Apr22.pdf PDF
ATTACHMENT J-4 - Tank Soundings Template.xls XLS spreadsheet
N00024-21-R-4204 Amendment 4.pdf PDF
N00024-21-R-4204 RFP Amendment 3.pdf PDF
ATTACHMENT J15 Arrival Inspection.docx DOCX document
Pearl_RFP_3.4.2022_Solicitation_Amendment_1.pdf PDF
ATTACHMENT J14 Integrity Inspection (1).docx DOCX document
Pearl_RFP_3.7.2022_Solicitation_Amendment_2.pdf PDF
Exhbt C - Past Performance Questionnaire.docx DOCX document
Attachment J-1 Pre-Proposal Information Form.xlsx XLSX spreadsheet
ATTACHMENT J20 QUALITY ASSURANCE PLAN.pdf PDF
Attachment J-2 Cost Element Summary Spreadsheets Pearl Harbor.xlsx XLSX spreadsheet
CDRL53-54 Pearl Harbor.pdf PDF
ATTACHMENT J21 DD254 (PEARL HARBOR).pdf PDF
CDRL05_08.pdf PDF
Pearl_Harbor_RFP_3.4.2022_Base_Solicitation.pdf PDF
CDRL37_40 Pearl Harbor.pdf PDF
ATTACHMENT J17 Fire Extinguisher Log.docx DOCX document
ATTACHMENT J9 VEHICLES.xls.xlsx XLSX spreadsheet
CDRL13-16 Pearl Harbor.pdf PDF
CDRL25-28 Pearl Harbor.pdf PDF
ATTACHMENT J16 Security Report.doc DOC document
ATTACHMENT J4 SAFE STOWAGE CHECK OFF LISTS.doc DOC document
ATTACHMENT 10 Tools and Materials Pearl Harbor (1).xlsx XLSX spreadsheet
ATTACHMENT J8 GFE from Navy ERP.xls.xlsx XLSX spreadsheet
CDRL09_12 Pearl Harbor.pdf PDF
CDRL41_44 Pearl Harbor.pdf PDF
ATTACHMENT J6 History Folder Index (1).docx DOCX document
ATTACHMENT J11 Cathodic Protection.docx DOCX document
CDRL45-48 Pearl Harbor.pdf PDF
ATTACHMENT J7 Janitorial Task and Frequency Chart.xlsx.xlsx XLSX spreadsheet
ATTACHMENT J22 INACTSHIPMAINTO Pearl Harbor Organizational Chart.docx DOCX document
CDRL33_36 Pearl Harbor.pdf PDF
CDRL01_04 Pearl Harbor.pdf PDF
ATTACHMENT J5 RRWO.docx DOCX document
CDRL21-24 Pearl Harbor.pdf PDF
CDRL49-52 Pearl Harbor.pdf PDF
ATTACHMENT J19 PCB Inventory.doc DOC document
Exhbt B - Past Performance Data.docx DOCX document
ATTACHMENT J3 VESSELS.xls.xls XLS spreadsheet
CDRL29-32 Pearl Harbor.pdf PDF
ATTACHMENT J18 Mooring_Security.xlsx XLSX spreadsheet
CDRL17-20 Pearl Harbor.pdf PDF
ATTACHMENT J13 FIRE FLOOD INS.docx DOCX document
ATTACHMENT J-23 List of Key Personnel.docx DOCX document
Show all 47

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Periodicity:

Spec Code:

Berthed At:

Quarter:

NSTM 50 INSPECTION GUIDELINES

DH1

Insp Date:

TDL

Remarks N/A

NO

YES

Description Item Record elapsed time meter readings and date. Are machines operating less than 50% of the time?

Is machine operable ? (Start idle machine manually to ensure operability.)

Have all other discrepancies been reported? If not report them here.

D/H Elapsed Time FWD Draft:

AFT Draft:

List:

Comments:

Inspector Inspector Inspection Manager Elapsed Time Data Table Machine Date E.T.I.

Date Hours Run Elapsed Time Operation

Attachment 11 NSTM 50 INSPECTION GUIDELINES - Descrepancy Listing Spec Code:

Line Item # Location Discrepancy Discovery Dt Correction Dt

Berthed At:

Quarter:

NSTM 50 INSPECTION GUIDELINES

DH2

Insp Date:

TDL

Remarks N/A

NO

YES

Description Item Are average zone readings 40% RH (+ or - 5%)?

Are individual relative humidity (RH) readings 45% or less?

Are air zones in balance? (High or low zone readings within plus or minus 5% RH of the zone average.)

Are permanent zone closures and blanks properly sealed, painted and stenciled?

Access closures operate and seal properly?

Are all exterior hatches, vent openings and huts properly sealed?

Are individual humidistats locations properly identified and labled?

Have all other discrepancies been reported? If not report them here.

D/H Inspection

FWD Draft:

AFT Draft:

List:

Comments:

Inspector Inspector Inspection Manager Elapsed Time Data Table Zone H1 H2 H3 H4 H5 Avg.

Zone H1 H2 H3 H4 H5 Avg.

Topside Hut R.H. and Test Specimen Data Table Zone H1 H2 H3 H4 H5 Avg.

Zone H1 H2 H3 H4 H5 Avg.

Line Item # Location Discrepancy

Berthed At:

Quarter:

NSTM 50 INSPECTION GUIDELINES

DH3

Insp Date:

TDL

Remarks N/A

NO

YES

Description Item Are filters on DH machines located on the interior of the vessel being changed Annually?

Have all other discrepancies been reported? If not report them here.

D/H Filters (Inspection) FWD Draft:

AFT Draft:

List:

Comments:

Inspector Inspector Inspection Manager

Line Item # Location Discrepancy

Berthed At:

Quarter:

NSTM 50 INSPECTION GUIDELINES

DH4

Insp Date:

TDL

Remarks N/A

NO

YES

Description Item Are filters on DH machines located on the weather decks of the vessel being changed Annually?

Have all other discrepancies been reported? If not report them here.

D/H Filters (Topside) FWD Draft:

AFT Draft:

List:

Comments:

Inspector Inspector Inspection Manager

Line Item # Location Discrepancy