The solicitation seeks to award a firm fixed-price construction contract to build consolidated clinic space for social workers at a Veterans Affairs medical center. Offerors must submit proposals by April 4, 2022 addressing the statement of work in Volume III of the combined drawings package. The contract is set aside for service-disabled veteran-owned small businesses. The period of performance is 365 calendar days from the notice to proceed. The place of performance will be the VA medical center in Austin, Texas.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PLUMBING GENERAL NOTES
1. ALL WORK AND MATERIAL SHALL BE PERFORMED AND
INSTALLED IN COMPLIANCE WITH THE LATEST
INTERNATIONAL PLUMBING CODE AND VA DESIGN
GUIDES.
2. CONTRACTOR SHALL BE RESPONSIBLE FOR DOMESTIC
WATER AND, SEWER, SYSTEMS AND ACCESSORIES
NECESSARY FOR THE INSTALLATION OF SUCH SYSTEMS.
3. CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS,
SERVICES, TESTING, TRANSPORTATION AND EQUIPMENT
NECESSARY FOR COMPLETION OF THIS WORK.
4. CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS,
LICENSES AND INSPECTIONS REQUIRED BY THE
AUTHORITIES HAVING JURISDICTION.
5. CONTRACTOR SHALL PROVIDE A COMPLETE DRAWING
RECORD SET SHOWING ANY DEVIATIONS TO THE
ORIGINAL DRAWINGS. CONTRACTOR SHALL GUARANTEE
THE ENTIRE PLUMBING SYSTEM UNCONDITIONALLY FOR
A PERIOD OF ONE YEAR. CONTRACTOR SHALL VERIFY
EXISTING UTILITIES AND METERS ARE SUFFICIENT FOR
DEMAND SHOWN ON DRAWINGS.
6. CONTRACTOR SHALL INSPECT THE SITE PRIOR TO BID.
FAILURE TO INSPECT SITE SHALL NOT RELIEVE THE
CONTRACTOR OF THE RESPONSIBILITY TO PERFORM ANY
WORK REQUIRED DUE TO UNUSUAL SITE CONDITIONS.
SUBMIT ALL FIXTURES, MATERIAL, EQUIPMENT AND
DEVICES.
7. IN SUBMITTALS EACH ITEM SHALL BE INDEXED AND
REFERENCED TO IDENTIFICATION NUMBERS ON
SCHEDULES. ITEMS NOT SUBMITTED SHALL BE
FURNISHED AND INSTALLED PER PLANS.
8. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL COSTS
ASSOCIATED WITH SUBSTITUTIONS NOT APPROVED BY
THE OWNER'S REPRESENTATIVE.
10. COSTS INCURRED DUE TO UNAPPROVED DEVIATIONS
FROM CONSTRUCTION DOCUMENTS SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR. COSTS SHALL
INCLUDE, BUT ARE NOT LIMITED TO MATERIAL, LABOR
AND CHANGES TO DRAWINGS FOR SUBMITTAL TO
AUTHORITIES HAVING JURISDICTION.
11. PIPE SHALL BE ROUND AND STRAIGHT. CUTTING SHALL
BE DONE WITH PROPER TOOLS. PIPE SHALL BE REAMED
TO FULL SIZE AFTER CUTTING.
12. BELOW GRADE, NON-METALLIC PIPE SHALL BE INSTALLED
WITH 14 GAUGE COPPER TRACER WIRE WITH
POLYETHYLENE INSULATION. THIN OR NYLON INSULATED
WIRE SHALL NOT BE PERMITTED.
13. DOMESTIC WATER PIPING SHALL BE INSTALLED AND
SLOPED SO AS TO FACILITATE DRAINING. BRANCHES
SERVING FIXTURES BELOW MAIN SHALL BE CONNECTED
TO BOTTOM OF MAIN. BRANCHES SERVING FIXTURES
ABOVE MAIN SHALL BE CONNECTED AT TOP OF MAIN.
14. SEISMIC SUPPORT OF PIPING SHALL CONFORM TO
SMACNA GUIDELINES FOR SEISMIC RESTRAINT OF PIPING
SYSTEMS.
15. PROTECT ALL MATERIALS AND EQUIPMENT DURING
CONSTRUCTION. COVER, CAP OR PLUG OPENINGS TO
PREVENT INGRESS OF FOREIGN MATTER.
16. THOROUGHLY CLEAN ALL FIXTURES, EQUIPMENT,
MATERIAL AND WORK AREAS PRIOR TO COMPLETION OF
CONSTRUCTION. SURFACES SHALL BE LEFT CLEAN AND
READY TO PAINT.
17. CAULK JOINTS BETWEEN FIXTURE AND FINISHED
SURFACE SO AS TO BE SMOOTH, EVEN AND WATER-
TIGHT.
18. INSTALL EQUIPMENT, FIXTURES, VALVES AND
APPURTENANCES SO AS TO ALLOW FOR NORMAL
MAINTENANCE.
19. CONCEALED VALVES, WATER HAMMER ARRESTORS AND
TRAP PRIMERS SHALL BE INSTALLED BEHIND ACCESS
PANELS SO AS TO BE VISIBLE, ACCESSIBLE AND FULLY
OPERABLE THROUGH THE ACCESS PANEL.
20. COORDINATE INSTALLATION TO AVOID CONFLICT WITH
OTHER TRADES' INSTALLATIONS, TO KEEP OPENINGS,
DOORWAYS, WINDOWS AND PASSAGES CLEAR AND TO
PRESERVE HEADROOM.
21. COORDINATE WITH GENERAL CONTRACTOR ANY
REQUIREMENTS OF INSTALLATIONS NOT ADDRESSED BY
THESE CONSTRUCTION DOCUMENTS.
22. SEE ARCHITECTURAL DRAWINGS FOR MOUNTING
HEIGHTS AND ELEVATIONS OF FIXTURES.
23. CONTRACTOR SHALL NOT CAUSE OR ALLOW ANY OF HIS
WORK TO BE COVERED OR ENCLOSED PRIOR TO
INSPECTION, TESTING OR APPROVAL BY THE OWNER,
ARCHITECT OR INSPECTOR HAVING JURISDICTION.
24. TEST SOIL, WASTE, STORM SEWER AND VENT SYSTEMS
TO 10' HEAD FOR MINIMUM 15 MINUTES.
25. TEST POTABLE WATER SYSTEMS PRIOR TO
CONCEALMENT TO 100 PSI FOR TWO HOURS.
26. TEST ALL OTHER PIPING SYSTEMS TO 150% OF ACTUAL
OPERATING PRESSURE.
27. AFTER TESTING, STERILIZE DOMESTIC WATER PIPING
PER AWWA C651 USING LIQUID CHLORINE OR
HYPOCHLORITE.
28. LABEL PIPING PER ANSI STANDARD 13.1. LABEL VALVES
WITH BRASS TAGS TO INDICATE SERVICE AND AREA
SERVED.
29. PRIOR TO COMPLETION, PROVIDE OWNER WITH
MAINTENANCE AND OPERATION DATA, WARRANTY
INFORMATION, OPERATION INSTRUCTIONS, SPECIAL KEYS
AND/OR TOOLS REQUIRED.
30. FOR ALL EQUIPMENT, VALVES, FIXTURES, ETC. BEFORE
COMMENCEMENT OF WORK, THE CONTRACTOR SHALL
VERIFY THE EXACT LOCATIONS, ELEVATIONS AND
CHARACTERISTICS OF ALL UTILITIES AND PIPING, AND
SHALL IMMEDIATELY NOTIFY THE ARCHITECT OF ANY
DISCREPANCIES.
31. ALL VALVES, UNIONS, ETC. TO BE SAME SIZE AS PIPE
UNLESS OTHERWISE INDICATED ON DRAWINGS.
32. INSULATE ALL EXPOSED HOT WATER AND DRAIN PIPING
BELOW ACCESSIBLE LAVATORIES AND SINKS AND
OFFSET P-TRAP AGAINST WALL.
33. CONNECTION BETWEEN INCOMPATIBLE MATERIALS
ABOVE GRADE AND INSIDE BUILDING SHALL BE MADE
WITH TWO (2) DIELECTRIC UNIONS SEPARATED BY A
TWELVE INCH (12") SECTION OF RED BRASS PIPE.
34. ALL REQUIRED CLEANOUTS SHALL BE INSTALLED AS PER
THE CALIFORNIA PLUMBING CODE.
35. EACH PLUMBING VENT SHALL TERMINATE NOT LESS
THAN TEN (10) FEET FROM OR AT LEAST THREE (3) FEET
ABOVE ANY WINDOW, DOOR, OPENING, AIR INTAKE.
36. NEW OR REPAIRED POTABLE WATER SYSTEMS SHALL BE
DISINFECTED PRIOR TO USE ACCORDING TO THE
METHOD SET IN THE PLUMBING CODE.
37. ALL PLUMBING FIXTURES AND FIXTURE FITTINGS SHALL
MEET THE STANDARDS REFERENCED IN THE CALIFORNIA
GREEN BUILDING CODE.
PLUMBING SYMBOL LIST
SYMBOL: DESCRIPTION:
PIPE SERVING FIXTURE ON FLOOR ABOVE
(EXAMPLE: FD = FLOOR DRAIN)FD
PITCH PIPE IN DIRECTION
RD-1
6"(1000)
ROOF DRAIN PROPERTIES SYMBOL
SIZE (ROOF SQ. FT.)
DIELECTRIC CONNECTION
UNION/FLANGE
BALANCING VALVE (NUMBER INDICATES GPM)
GPM
CHECK VALVE
REDUCER - REFERENCE SPECIFICATION
FOR CONCENTRIC/ECCENTRIC AND FOT/FOB
METERM
ALIGNMENT GUIDE
PIPE ANCHOR
EXPANSION JOINT
PIPE CAP
PIPE DOWN
PIPE UP OR UP/DOWN
DIRECTION OF FLOW IN PIPE
NEW CONNECTION
SHUTOFF VALVE NORMALLY OPEN
SHUTOFF VALVE NORMALLY CLOSED
ACID VENTAV
ACID WASTEAW
COLD WATER - POTABLECW
DT DRAIN TILE
SANITARY DRAINAGE (GREASE SANITARY DRAINAGE)GSAN
HOT WATER - POTABLEHW
HOT WATER CIRCULATING - POTABLEHWC
HOT WATER - POTABLE NUMBER INDICATES TEMPHW140
HOT WATER CIRC. - POTABLE NUMBER INDICATES TEMPHWC140
NON-POTABLE COLD WATERNCW
NON-POTABLE HOT WATERNHW
PUMPED DISCHARGEPD
SANITARY DRAINAGESAN
SOFT COLD WATERSCW
SOFT HOT WATERSHW
STORM DRAINAGE (ROOF SQUARE FOOTAGE)ST(1,000)
STS STORM DRAINAGE (SECONDARY)
VENTV
WASTE ANETHESIA GAS DISPOSALWAGD
GREASE VENTGV
COMPRESSED AIRCA
DEIONIZED WATERDI
PROPANE GASP
REVERSE OSMOSIS WATERRO
STW SOFT TEMPERED WATER
TW TEMPERED WATER
DRAIND
G NATURAL GAS
NOT ALL SYMBOLS MAY APPLY.
PRESSURE REDUCING VALVE (LIQUID/GAS)
OIL RETURNOR
OIL SUPPLYOS
LAB VACUUMVAC
SOLENOID VALVE
SAFETY/RELIEF VALVE
VACUUM BREAKER
PRESSURE GAUGE (FURNISHED WITH BALL VALVE)P
TEMPERATURE SENSOR WITH WELL
T
THERMOMETER WITH WELL (DIAL TYPE)T
THERMOMETER WITH WELL (FILLED TYPE)
PUMP
GRV GAS REGULATOR VENT
INSTRUMENT AIRIA
MEDICAL AIRMA
MEDICAL VACUUMMV
NITROGENN
NITROUS OXIDENO
OXYGENO
PURE WATERPW
SERVICE WATER - POTABLEW
PIPE CONTINUATION
PRESSURE SENSOR (FURNISHED WITH BALL VALVE)P
ROUTE TO DRAIN
"WYE" - STRAINER
"WYE" - STRAINER W/SHUTOFF VALVE
AND HOSE CONNECTION WITH CAP
FLEXIBLE CONNECTION
MANUAL AIR VENT
DRAIN VALVE WITH HOSE CONNECTION AND CAP
EA MEDICAL EQUIPMENT AIR
VALVE BOX
MEDICAL GAS OUTLET (MGO)
ALARM PANEL
HEADWALL
SINGLE GAS OUTLET (AIR)A
SINGLE GAS OUTLET (OXYGEN)O
SINGLE GAS OUTLET (VACUUM)V
NITROGEN PRESSURE CONTROL CABINET
PRESSURE TRANSDUCER WITH ALARM WIRING
CO2 CARBON DIOXIDE
DRAIN - MEDICAL GASDMG
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
DETAIL REFERRED TO BY SECTION CUT
SHEET DETAIL IS LOCATED ON
NAME
VIEW NAME
1/8" = 1'-0"
M101
T101
SIM
DETAIL REFERRED TO BY ELEVATION
SHEET DETAIL IS LOCATED ON
INDICATES SIMILAR DETAIL
REFERENCED IN MULTIPLE LOCATIONS
SIM
INDICATES SIMILAR DETAIL
REFERENCED IN MULTIPLE LOCATIONS
LEVEL NAME
10' - 0" HEIGHT ABOVE
PROJECT 0' - 0"
1 INDICATES NOTE USED TO DESCRIBE
ADDITIONAL INFORMATION ABOUT
WORK REQUIRED, SPECIFIC TO THE
SHEET AND/OR DETAIL
N
O R HT
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
NEW WORK BY THIS CONTRACTOR
(DARK SOLID LINE)
NEW WORK UNDERFLOOR OR UNDERGROUND BY THIS CONTRACTOR
(DARK LONG DASHED LINE)
NEW WORK BY OTHERS AND/OR EXISTING TO REMAIN
(LIGHT SOLID LINE)
EXISTING TO BE REMOVED BY THIS CONTRACTOR
(DARK SHORT DASHED LINE)
LINE TYPE KEY:
APPLICABLE CODES
• 2016 CALIFORNIA BUILDING STANDARDS ADMINISTRATIVE CODE CALIFORNIA CODE OF
REGULATIONS (CCR) TITLE 24, PART 1
• 2016 CALIFORNIA BUILDING CODE (CBC) CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24, PART 2 (2015 INTERNATIONAL BUILDING CODE (IBC) W/CALIFORNIA AMENDMENTS)
• 2016 CALIFORNIA REFERENCED STANDARDS CODE CALIFORNIA CODE OF REGULATIONS (CCR)
TITLE 24, PART 122016 CALIFORNIA REFERENCED STANDARDS CODE CALIFORNIA CODE OF
REGULATIONS (CCR) TITLE 24, PART 12
• 2016 CALIFORNIA ELECTRICAL CODE (CEC) CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24, PART 3 (2014 NATIONAL ELECTRICAL CODE (NEC) W/CALIFORNIA AMENDMENTS)
• 2016 CALIFORNIA MECHANICAL CODE CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24,
PART 4 (2015 UNIFORM MECHANICAL CODE (UMC) W/CALIFORNIA AMENDMENTS)
• 2016 CALIFORNIA PLUMBING CODE CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24, PART 5
(2015 UNIFORM PLUMBING CODE (UPC) W/CALIFORNIA AMENDMENTS)
• 2016 CALIFORNIA ENERGY EFFICIENCY STANDARDS CODE CALIFORNIA CODE OF REGULATIONS
(CCR) TITLE 24, PART 6
• 2016 CALIFORNIA FIRE CODE (CFC) CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24, PART 9
(2015 INTERNATIONAL FIRE CODE (IFC) W/CALIFORNIA AMENDMENTS)
STANDARDS:
NFPA 13 AUTOMATIC SPRINKLER SYSTEM (2016)
NFPA 24 PRIVATE FIRE MAINS (2016)
TEMPERATURE CONTROLS CONTRACTORT.C.C.
SECURITY CONTRACTORS.C.
AUDIO/VISUAL CONTRACTORA.V.C.
NURSE CALL CONTRACTORN.C.C.
CIVIL CONTRACTORC.C.
ASBESTOS ABATEMENT CONTRACTOR
FIRE PROTECTION CONTRACTORF.P.C.
AUTOMATIC TEMPERATURE CONTROL CONTRACTORA.T.C.
HEATING CONTRACTORH.C.
PLUMBING CONTRACTORP.C.
GENERAL CONTRACTORG.C.
MECHANICAL CONTRACTORM.C.
VENTILATION CONTRACTORV.C.
ELECTRICAL CONTRACTORE.C.
A.C.
CONTRACTOR ABBREVIATION KEY
ABBR: DESCRIPTION:
TECHNOLOGY CONTRACTORT.C.
CONSTRUCTION MANAGERC.M.
FOOD SERVICE CONTRACTORF.S.C.
R
EG
IS
T
ER
ED
PROFESS IONAL
ENG
IN
E E
R
S T
A
TE
OF CA L I FORN
I A
No. M029768
Exp. 06/30/22
M
E C HA N I CA
L
P A
U L
Q I P I NG
DO
N GRomanyk Consulting
Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
SD-1 PACKAGE - ORIGINAL SUBMITTAL 5/24/2017
SD-1 PACKAGE - RESUBMITTAL
SD-1 PACKAGE - RESUBMITTAL
SD-1 PACKAGE - RESUBMITTAL - SITE LOCATIONS
8/15/2017
9/15/2017
12/5/2017
SD-2 PACKAGE 5/15/2018
DD-1 NON REVIEW 8/02/2018
DD-1 SUBMISSION 8/23/2018
DD-2 SUBMISSION 10/27/2018
CD-1 SUBMISSION 02/10/2019
CD-1 RE-SUBMISSION 04/12/2019
CD-1 RE-SUBMISSION 01/31/2020
CD-2 SUBMISSION 04/30/2020
CONSTRUCTION DOCUMENT SUBMISSION 06/29/2020
REVIEW SET FOR CONSTRUCTION DOCUMENT SUBMISSION #2 09/24/2020
CONSTRUCTION DOCUMENT SUBMISSION #2 12/04/2020 C
R e v it L o c a l F ile s \P
M a th e r
S o c ia l S e rv ic e s C e lli e .t ra n .r v t
/4 /2
:4
:5
A
M
PLUMBING SYMBOLS, ABBREVIATIONS AND
GENERAL NOTES
SN LC
CONSTRUCTION DOCUMENT
SUBMISSION
FULLY SPRINKLERED
612-163
P-001
DESIGN SOCIAL WORK AND EXPAND
CLINICAL SPACE
3551 Femoyer Street Mather, CA 95655
12/04/2020
300 N. LAKE AVENUE 14TH FLOOR
PASADENA, CA 91101
626.463.2800 FAX: 626.463.2801
www.imegcorp.com # 02165361.00
HOSE BIBB
RECESSED
WATER CLOSET
DESCRIPTION
LAVATORY
PLUMBING FIXTURE SCHEDULE
WASTE PIPE
[MM]
VENT PIPE
REMARKS
FLOOR SINK
FLOOR DRAIN
ROOF RECEPTOR
ROOF DRAIN
OVERFLOW
DRAIN
FLOOR MOUNTED
WATER HAMMER
ARRESTOR
TRAP PRIMER
WITH
ACCESS PANEL
WITH
ACCESS PANEL
P-114
P-418
MARK
FD-S
FD-C
WB-1
RR-1
RD-1
OD-1
WHA-1
TP-2
AREA
AND/OR
BLDG
SERVED GPM
TYPEMARK LOCATION
RECIRCULATION PUMP SCHEDULE
[1.3]CENTRIFUGALBUILDINGLEVEL 2
HAC #205
CP-1
FLUID
DOMESTIC
COLD
WATER
(L/s)
FLOW
FT (kPa)
HEAD
20 10
FT (kPa)
NPSH
AVAILABLE
NANA
°F (°C)
TEMPERATURE
[60]140
SP. GR.
MIN. %
EFF HP (kW)
NOMINAL
POWER
NA1/12
PHASE
CIRCULATING FLUID ELECTRICAL MOTOR
VOLT
MAX
RPM
SPEED
CONTROL
REMARKS
1 120 2650 CONSTANT70
BELL & GOSSETT MODEL NO. PL-30B OR APPROVED
EQUAL. WALL MOUNTED WITH UNI-STRUT.
AREA
AND/OR
BLDG
SERVED GAL/HR
TYPEMARK LOCATION
GAS FIRED WATER HEATER SCHEDULE
[916]TANKLEVEL 2
HAC #205
WH-1
STORAGE
CAPACITY
[L/HR]
RECOVERY @
70°F
[39°C] RISE TIME TO
RECOVER
CONTENTS,
MINUTES
242 -
PSIG (kPa)
RELIEF VALVE
SETTING
[1034]150
TYPE
NATURAL
GAS
IN WG
[PA] CFH [L/H]
FLOW
[4247]150
PHASE
ELECTRICAL MOTOR
VOLT REMARKS
- [-][2739]
BRADFORD WHITE, MODEL NO. EF-60T-150E-3N(A) OR
APPROVED EQUAL, WITH CONCENTRIC VENT KIT
TERMINATION AND NEUTRALIZATION KIT.
GAL [L]
60 [227]
FUEL
INLET
PRESSURE
NOMINAL POWER
EA.
HP [KW]
1 115
AREA
AND/OR
BLDG
SERVED
TYPEMARK LOCATION
DOMESTIC WATER THERMAL EXPANSION TANK SCHEDULE
[49]
THERMAL
EXPANSION
TANK
BUILDINGET-1
°F
MAX
FT (kPa)
INITIAL PRESSURE
IN TANK
120 [419]140
PSIG [kPa]
MAX OPERATING
PRESSURE
[1034]150
RELIEF VALVE
PSIG [KPA]
[1034]150 2
PIPE SIZE TO
TANK
REMARKS
[7.6]
SYSTEM TEMPERATURE RANGE
MIN
[°C]
[13]55
PSIG [kPa]
MIN. TANK
VOLUME
GAL [L] IN [MM]
3/4 [19]
IN
[100] 2 [50]
[MM]IN
COLD WATER
1.5 [38]
[MM]IN
HOT WATER
[MM]IN
WASTE
FIXTURE
UNITS
WRIST
BLADE
HANDLES
ELECTRIC
SENSOR
6 N/A NO
WATER
FIXTURE
UNITS
2 [75] 2 [50] .75 [19] 2 N/A NO2.75 [19]
SINK SERVICEP-501 3 [75] 2 [50] .75 [19] 3 N/A NO4.75 [19]
P-704 2 [50] 1.5 [38] .75 [13] 2 N/A NO2.75 [19]SHOWER
AMERICAN STANDARD MODEL NO. 3461.001, BARIATRIC 1000 LBS CAPACITY, VITREOUS CHINA, FLOOR MOUNTED, ELONGATED BOWL, 1 1/2" TOP SPUD,
1.28 GPF, ADA COMPLIANT; FLUSHOMETER, SLOAN MODEL NO. 111-SMO-1.28, BATTERY SENSOR OPERATED; SEAT, BEMIS MODEL NO. 9400SSCT, PLASTIC OPEN FRONT, SELF-SUSTAINING CHECK HINGES, STAINLESS STEEL POSTS. SUBSTITUTIONS CAN BE MADE FOR THE LISTED MODELS AS LONG
AS THEY ARE APPROVED EQUALS.
AMERICAN STANDARD MODEL NO. 9024.004EC, VITREOUS CHINA, WALL HUNG, CONCEALED ARM SUPPORTS; FAUCET, CHICAGO FAUCETS MODEL NO.
116.203.AB.1, LEAD FREE BRASS CONSTRUCTION, CHROME PLATED, GOOSENECK, 0.5 GPM, LAMINAR FLOW OUTLET, BATTERY OPERATED, DUAL BEAM
INFRARED SENSOR, ADA COMPLIANT; COVER PLATE, CHICAGO FAUCET MODEL NO. 240.627.21.1, P-TRAP, MCGUIRE MODEL NO. 8090CNCSAN, LA-PATTERN; STOPS, CHICAGO FAUCET MODEL NO. STB.21.00.AB; RISERS, BRASS CRAFT S1-12KCF; ADA COVERS, TRUEBRO MODEL NO. 103 E-Z
INSULATING KIT FOR WASTE AND ANGLE STOPS. SUBSTITUTIONS CAN BE MADE FOR THE LISTED MODELS AS LONG AS THEY ARE APPROVED EQUALS.
AMERICAN STANDARD MODEL NO. 7741.000, FLOOR MOUNTED, WHITE EMAMELED CAST IRON, WITH CHROME PLATED FLAT GRID DRAIN, REMOVABLE VINYL RIM GUARD; FAUCET, CHICAGO MODEL NO. 897-CCP, VACUUM BREAKER, PAIL HOOK, INTEGRAL CHECK VALVES, INTEGRAL STOPS, HOSE THREAD OUTLET, WALL BRACE. SUBSTITUTIONS CAN BE MADE FOR THE LISTED MODELS AS LONG AS THEY
ARE APPROVED EQUALS.
EXAM ROOMSP-420 2 [75] 2 [50] .75 [19] 2 N/A NO2.75 [19]
AMERICAN STANDARD MODEL NO. 0483.600, VITREOUS CHINA, UNDERCOUNTER; FAUCET, CHICAGO FAUCETS MODEL NO. 116.203.AB.1, BATTERY
OPERATED, LEAD FREE BRASS CONSTRUCTION, CHROME PLATED, GOOSENECK, 1.5 GPM, LAMINAR FLOW OUTLET, DUAL BEAM INFRARED SENSOR, ADA
COMPLIANT; DRAIN, MCGUIRE MODEL NO. 155WCSAN; COVER PLATE, CHICAGO FAUCET MODEL NO. 240.627.21.1; P-TRAP, MCGUIRE MODEL NO.
8090CNCSAN, LA-PATTERN; STOPS, CHICAGO FAUCET MODEL NO. STB.21.00.AB; RISERS, BRASS CRAFT S1-12KCF; ADA COVERS, TRUEBRO MODEL NO.
103 E-Z INSULATING KIT FOR WASTE AND ANGLE STOPS. SUBSTITUTIONS CAN BE MADE FOR THE LISTED MODELS AS LONG AS THEY ARE APPROVED
EQUALS.
BREAK ROOMSP-528 2 [75] 2 [50] .75 [19] 2 N/A NO2.75 [19]
JUST MODEL NO. SL-ADA-2019-16-GR, SINGLE BOWL, 5 1/2" DEEP, 16 GAUGE, 304 STAINLESS STEEL, SELF-RIMMING, LEDGE BACK; FAUCET, CHICAGO
FAUCETS MODEL NO. 786-E35VPCABCP, 8" CENTERS, LEAD FREE BRASS CONSTRUCTION, CHROME PLATED, GOOSENECK, 1.5 GPM, LAMINAR FLOW
OUTLET, MANUAL OPERATED, WRIST BLADES, ADA COMPLIANT; DRAIN, JUST MODEL NO. J-ADA-35-SSF, STAINLESS STEEL WITH REMOVABLE STRAINER;
P-TRAP, MCGUIRE MODEL NO. 8090CNCSAN, LA-PATTERN; STOPS, CHICAGO FAUCET MODEL NO. STB.21.00.AB; RISERS, BRASS CRAFT S1-12KCF; ADA
COVERS, TRUEBRO MODEL NO. 103 E-Z INSULATING KIT FOR WASTE AND ANGLE STOPS. SUBSTITUTIONS CAN BE MADE FOR THE LISTED MODELS AS
LONG AS THEY ARE APPROVED EQUALS.
J.R. SMITH MODEL NO. 3100-Y-C OR APPROVED EQUAL, MEDIUM CAPACITY, RECTANGULAR, FLASHING CLAMP, CAST IRON WITH ACID RESISTANT
ENAMEL COATED INTERIOR AND ALUMINUM DOME BOTTOM STRAINER, DOUBLE DRAINAGE FLANGE, SEEPAGE HOLES, WITH NICKEL BRONZE 1/2
OR 3/4 TOP AND TRAP PRIMER CONNECTION AS REQUIRED.
JAY R. SMITH MODEL #1015Y-R-C-CID OR APPROVED EQUAL, CAST IRON BODY WITH COMBINED FLASHING CLAMP AND GRAVEL STOP, SUMP
RECEIVER, UNDERDECK CLAMP AND CAST IRON DOME. WITH ADJUSTABLE EXTENSION. OR APPROVED EQUAL.
JAY R. SMITH MODEL #1080Y-R-C-CID OR APPROVED EQUAL, CAST IRON BODY WITH COMBINED FLASHING CLAMP AND GRAVEL STOP, SUMP
RECEIVER, UNDERDECK CLAMP AND CAST IRON DOME. 2" CAST IRON WATER DAM. OR APPROVED EQUAL.
PRECISION PLUMBING PRODUCTS MODEL NO. SC-500A THROUGH SC-2000F OR APPROVED EQUAL, BARREL FABRICATED OF TYPE
K HARD DRAWN COPPER, BRASS PISTON, "O" RING EPDM SEAL, INSTALL AT EACH PLUMBING FIXTURE OR BATTERY OF PLUMBING
FIXTURE. INSTALL ON BOTH HOT AND COLD WATER BRANCH LINES IN AN UP RIGHT POSITION AS CLOSE AS POSSIBLE TO THE
VALVE OR VALVES BEING SERVED. SIZE AND LOCATION PER P.D.I. STANDARD WH-201. PROVIDE DISTRIBUTION UNIT FOR MULTIPLE
DRAINS.
ICE MAKER
BOX
IMB-1
2 [50] 2 [50] N/A N/A 2 N/A N/A2N/A N/A
2 [50] 2 [50] 2 N/A N/A2
N/A N/A N/A N/A N/A N/A N/AN/AN/A N/A
N/A N/A N/A N/A .75 [19] N/A N/A N/AN/AN/A N/A
N/A N/A
N/A N/A N/A N/A N/A N/A N/AN/AN/A N/A
N/A N/A N/A N/A
N/A N/A N/A N/A .75 [19] N/A N/A N/AN/AN/A N/A
N/A N/A N/A N/A .75 [19] N/AN/A N/A N/A
MINIMUM
FLOW RATE
(GPM)
TW
OUT
(°F)
LOCATIONSYMBOL
MIXING VALVE SCHEDULE
FLOW RATE
(GPM) REMARKSMANUFACTURER
AND MODEL
INLET SIZE
(IN)
OUTLET
SIZE (IN)
PRESS.
DROP @
FLOW
RATE (IN)
105-3/8" 3/8"
CHICAGO FAUCET
MODEL NO.
131-ABNF OR
APPROVED EQUAL
MULTIPLE
LOCATIONS
- 0.35
ASSE 1070 COMPLIANT, BRASS BODY CONSTRUCTION, CORROSION RESISTANT INTERNAL COMPONENTS, THERMOSTATIC WATER MIXING VALVE, LEAD FREE, COMPENSATE FOR CHANGES IN WATER TEMPERATURE, ADJUSTMENT CAP WITH LOCKING FEATURE, EQUIPPED WITH INTEGRAL CHECK VALVES AT INLETS. (SET AT
105°F)
105-1/2" 1/2"
CHICAGO FAUCET
MODEL NO.
122-ABNF OR
APPROVED EQUAL
MULTIPLE
LOCATIONS
ASSE 1017 COMPLIANT, BRASS BODY CONSTRUCTION, CORROSION RESISTANT INTERNAL COMPONENTS, THERMOSTATIC WATER MIXING VALVE, LEAD FREE, COMPENSATE FOR CHANGES IN WATER
TEMPERATURE, ADJUSTMENT CAP WITH LOCKING FEATURE, EQUIPPED WITH INTEGRAL CHECK VALVES AT
INLETS. (SET AT 100°F)
TMV-1
TMV-2
SE E
PLANS
SE E
PLANS
SE E
PLANS
SE E
PLANS
J.R. SMITH MODEL NO. 2005-A OR APPROVED EQUAL, DUCO CAST BODY, ROUND NICKEL BRONZE HEEL PROOF ADJUSTABLE 6" STRAINER
GRATE WITH DOUBLE DRAINAGE FLANGE, WEEP HOLES, 2" HUBLESS. PROVIDE WITH TRAP PRIMER CONNECTION AS REQUIRED.
SYMMONS MODEL NO. 1-117VT-FS. PROVIDE WITH PRESSURE BALANCING VALVE , FIXED SHOWER HEAD, INTEGRAL SERVICE STOPS, 30 INCH SLIDE
BAR, 60 INCH WHITE VINYL HOSE, VANDAL RESISTANT ESCUTCHEON SCREWS; SYMMONS MODEL NO. ADACHS, HAND HELD SHOWER, NON-POSITIVE
SHUT-OFF BUTTON, 1.5 GPM FLOW RATE, ADA COMPLIANT; SYMMONS MODEL NO. 4-451, PUSH-BUTTON DIVERTER VALVE, AND SYMMONS MODLE NO.
VB VACUUM BREAKER. SUBSTITUTIONS CAN BE MADE FOR THE LISTED MODELS AS LONG AS THEY ARE APPROVED EQUALS.
HOSE BIBB
ROOF
HB-1
N/A N/A N/A N/AN/A N/A N/A N/A
N/AN/A N/AN/A N/AN/A N/AN/A N/A N/AN/A N/A.75 [19] 1 N/A N/AN/AN/A
N/AN/A N/AN/A N/AN/A N/AN/A N/A N/AN/A N/A.75 [19] 1 N/A N/AN/AN/A
2 2 [50] 2 [50] 2N/A N/AN/A N/AN/A N/AN/A N/A N/A N/AN/A
AMTROL, MODEL NO. ST-5C OR APPROVED EQUAL, ASME COMPLAINT, POLYPROPYLENE LINER.
BUILDING
DOWNSPOUT
COVER
DSC-1
LEVEL 2
HAC #205
DRINKING
FOUNTAIN
P-608 OASIS MODEL NO. PGFEBFSL OR APPROVED EQUAL, ADA COMPLIANT, WITH BOTTLE FILLER, STAINLESS STEEL CONSTRUCTION, LEAD FREE FILTER, [30]
°F [°C]
N/A N/AN/AN/A N/A N/AN/A N/A N/A N/A N/A N/A J.R. SMITH MODEL NO. 1775 OR APPROVED EQUAL, 304 STAINLESS STEEL CONSTRUCTION, WITH PERFORATED HINGED COVER.
2 [50] 2 [50] 1 N/A N/A1N/A N/AN/A N/A0.75 [19]
LAUNDRY
BOX
LB-1 2 [50] 2 [50] 3 - -40.75 [19] 0.75 [19]
PPP MODEL NO. MM-500MLB OR APPROVED EQUAL, WHITE POWDER COATED STEEL, PROVIDE WITH TWO VALVES, WATER HAMMER ARRESTOR AND
2" DRAIN.
EQUIPMENT SCHEDULE
NSF/ANSI 372 COMPLIANT.
PPP MODEL NO. MM-500MIMB OR APPROVED EQUAL, WHITE POWDER COATED METAL BOX, LEAD FREE, BRASS PLATED QUARTER TURN VALVE.
PLUMBING EQUIPMENT SCHEDULE
DESCRIPTIONSYMBOL REMARKS
BOOSTER
PUMP
BP-1
BFP-1
AREA
AND/OR
BLDG
SERVED
TYPEMARK LOCATION
HYDRO-PNEUMATIC TANK SCHEDULE
HYDRO
-PNEUMATIC
TANK
BUILDINGHNT-1
°F
MAX
FT (kPa)
INITIAL PRESSURE
IN TANK
70 [120]40
PSIG [kPa]
MAX OPERATING
PRESSURE
[523]175
RELIEF VALVE
PSIG [KPA]
-- 68
PIPE SIZE TO
TANK
REMARKS
[258]
SYSTEM TEMPERATURE RANGE
MIN
[°C]
[13]55
PSIG [kPa]
MIN. TANK
VOLUME
GAL [L] IN [MM]
1 1/4 [32]
LEVEL 1
STORAGE 112
°F [°C]
AMTROL, MODEL NO. WX-404C OR APPROVED EQUAL, ASME COMPLAINT,
POLYPROPYLENE LINER.
ELEC REQUIREMENT: 115V
PLUMBING EQUIPMENT SCHEDULE
DESCRIPTIONSYMBOL REMARKS
SEISMIC GAS
VALVE
PACIFIC SEISMIC PRODUCTS, VERTICAL MOUNTED VALVE MODEL NO. VT-315F, 3" SIZE. VALVE IS RATED FOR 60 PSI. INSTALL VALVE SO IT CAN BE PROPERLY MAINTAINED IN THE FIELD.
CALIFORNIA SEISMIC VALVES ARE UL LISTED IN USA AND CANADA, CERTIFIED BY THE CALIFORNIA STATE ARCHITECTS OFFICE. VALVE SHALL MEET CALIFORNIA STANDARDS FOR EARTHQUAKE ACTUATED AUTOMATIC GAS SHUT OFF SYSTEMS STANDARD NUMBER 12-23-1, ANSI Z21.70, 1981 AND ASCE 25-97 STANDARDS.
EQV-1
PRECISION PLUMBING PRODUCTS PRIME-RITE, P-1 OR P-2 SERIES OR APPROVED EQUAL, WITH DISTRIBUTION UNIT FOR
MULTIPLE DRAINS. 3/4" MALE HOSE W/ VACUUM BREAKER. PROVIDE WITH ACCESS PANEL.
ACORN MODEL NO. 8101 OR APPROVED EQUAL, RECESSED HOSE BOX, INTEGRAL VACUUM BREAKER AND LOOSE KEY OPERATION.
ACORN MODEL NO. 8126-LF OR APPROVED EQUAL, BENT NOSE, VERITICAL STANDPIPE VALVE, INTEGRAL VACUUM BREAKER AND
LOOSE KEY OPERATION.
JR SMITH MODEL NO. 3960Y OR APPROVED EQUAL, WITH SOLID WATER DAM AND BOTTOM STRAINER.
EQUIP. TYPE
BACKFLOW
PREVENTER
TAG
REMARKS
DESCRIPTION
3/4", WATTS MODEL NO. LF909, REDUCED PRESSURE TYPE, FDA EPOXY COATED CAST IRON. LEAD FREE ALL HYDRAULIC SENSING PASSAGES SHALL BE INTERNALLY
LOCATED WITHIN THE MAINLINE AND RELIEF VALVE BODIES AND RELIEF VALVE COVER, FDA EPOXY COATED STRAINER, OS&V GATE VALVES, PROVIDE WITH AIR GAP, USC AND ASSE 1013 COMPLIANT.
HYDRO, MODEL NO. MPC-E 2CRE 10-1 3X460V, DUPLEX POTABLE WATER BOOSTER PUMP SYSTEM, PRE-FABRICATED AND TESTED, VARIABLE SPEED DRIVE, HAVING A CONSTANT WATER DELIVER PRESSURE. THE PUMP SYSTEM SHALL INCLUDE PUMPS, PUMP LOGIC CONTROLLER WITH COLOR DISPLAY, ABLE TO COMMUNICATE WITH BACNET, MODBUS, PROFIBUS AND LON, UL CERTIFIED AND LISTED, NSF 61 LISTED, LOW LEAD, ASHRAE 90.1 COMPLIANT WITHOUT THE NEED FOR A REMOTE SENSOR, IN-LINE VERTICAL MULTI-STAGE DESIGN, IMPELLER DIRECTLY CONNECTED TO THE PUMP SHAFT, ANSI CLASS 250 FLANGES FOR WATER CONNECTIONS, IMPELLERS AND SHAFTS SHALL BE STAINLESS STEEL, TOTALLY ENCLOSED FAN COOLED MOTORS WITH NEMA C-FACE, CLASS F INSULATION, ISOLATION VALVES SHALL BE ON THE SUCTION AND DISCHARGE SIDE OF THE PUMPS, A SPRING LOADED NON-SLAM CHECK VALVE SHALL BE ON THE DISCHARGE SIDE THE PUMP, 1 HP, 3 PHASE, 460V EACH OF 2 PUMPS.
R
EG
IS
T
ER
ED
PROFESS IONAL
ENG
IN
E E
R
S T
A
TE
OF CA L I FORN
I A
No. M029768
Exp. 06/30/22
M
E C HA N I CA
L
P A
U L
Q I P I NG
DO
N GRomanyk Consulting
Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
SD-1 PACKAGE - ORIGINAL SUBMITTAL 5/24/2017
SD-1 PACKAGE - RESUBMITTAL
SD-1 PACKAGE - RESUBMITTAL
SD-1 PACKAGE - RESUBMITTAL - SITE LOCATIONS
8/15/2017
9/15/2017
12/5/2017
SD-2 PACKAGE 5/15/2018
DD-1 NON REVIEW 8/02/2018
DD-1 SUBMISSION 8/23/2018
DD-2 SUBMISSION 10/27/2018
CD-1 SUBMISSION 02/10/2019
CD-1 RE-SUBMISSION 04/12/2019
CD-1 RE-SUBMISSION 01/31/2020
CD-2 SUBMISSION 04/30/2020
CONSTRUCTION DOCUMENT SUBMISSION 06/29/2020
REVIEW SET FOR CONSTRUCTION DOCUMENT SUBMISSION #2 09/24/2020
CONSTRUCTION DOCUMENT SUBMISSION #2 12/04/2020 C
R e v it L o c a l F ile s \P
M a th e r
S o c ia l S e rv ic e s C e lli e .t ra n .r v t
/4 /2
:4
:0
A
M
PLUMBING SCHEDULES
SN LC
CONSTRUCTION DOCUMENT
SUBMISSION
FULLY SPRINKLERED
612-163
P-002
DESIGN SOCIAL WORK AND EXPAND
CLINICAL SPACE
3551 Femoyer Street Mather, CA 95655
12/04/2020
300 N. LAKE AVENUE 14TH FLOOR
PASADENA, CA 91101
3.4
20.27
6.9
2.65
40.08
-8.35
19.29
0.87
60.35
3.18
WATER METER BY (LOCAL WATER DISTRICT)
BACKFLOW PREVENTOR (BY CIVIL) = PSI
= PSI
TOTAL SITE LOSSES: (C) + (D) + (F) + (G) = PSI
STATIC LOSSES: BUILDING HEIGHT x .433
= PSI
RESIDUAL PRESSURE = = PSI
= PSI
TOTAL BLDG LOSSES: (I) + (K) + (L) = PSI
WATER PRESSURE:
= PSI
PSI
= PSI
A
B
I
J
L
M
C
D
H
O(A) - (H)MINIMUM PRESSURE BOOST
MINIMUM PUMP HEAD: (Q) X 2.31
SIZE BOOSTER PUMP AT: 20 FT HD @ 74 GPM
HEAD LOSS: 3 PSI/100 FT
LENGTH OF PIPE: 136 FEET
PIPE HEAD LOSS: 3PSI/100 FT X (136 FT X 1.5) / 2.31
16 FT X .433
SITE PIPE FRICTION:
STATIC HEIGHT: SITE HEIGHT CHANGE x .433
= PSIG2 FT X .433
TOTAL SITE LOSSES: (H) + (M) = PSIN
PIPE HEAD LOSS AGE FACTOR: (J) X 1.2 = PSIK
FT
PUMP DESCRIPTION:
PSI
WATER HEATER DEMAND TABLE
GALLONS
DEMAND
QTY TOTAL (GPH)
(PSMD) POSSIBLE MAXIMUM DEMAND
FIXTURE
MOP SINK 40202
SINK (OTHER) 11 6
LAVATORY 7 6 42
SHOWER * 2 30 60
BOILER
EQUIPMENT QTY
INDIVIDUAL
CAPACITY (CFH)
500 500
(CFH)
SUBTOTAL REQUIRED
PRESSURE
8"WC
1030 CFHTOTAL
EXISTING LOAD
EXISTING LOAD TO REMAIN
EXISTING LOAD TO BE REMOVED
NEW LOAD
TOTAL
0 CFH
0 CFH
0 CFH
1030 CFH
1030 CFH
USE 300 FEET ON TABLES 1216.2(1) CPC
TOTAL DEVELOPED PIPE LENGTH = 190 FEET X 1.5 = 285 FEET
MEASURED PIPE LENGTH = 190 FEET
GAS LOAD SUMMARY
INDIVIDUAL EQUIPMENT GAS LOADS
PIPE MATERIAL: TYPE L COPPER
MAXIMUM ACCEPTABLE PRESSURE LOSS: 3.0 PSI/100 FT.
MAXIMUM ACCEPTABLE VELOCITY: 4 FT./SEC.
PIPE MATERIAL: TYPE L COPPER
MAXIMUM ACCEPTABLE PRESSURE LOSS: 3.0 PSI/100 FT.
MAXIMUM ACCEPTABLE VELOCITY: 6 FT./SEC.
DOMESTIC HOT WATER SIZING
1/2"
3/4"
1"
1 1/4"
1 1/2"
2"
2 1/2"
1.82
4.75
9.58
15.67
22.18
38.59
59.50
2.50
3.15
3.72
4.0
4.0
4.0
4.0
3" 84.93 299 -4.0
DOMESTIC COLD WATER SIZING
1/2"
3/4"
1"
1 1/4"
1 1/2"
2"
2 1/2"
1.82
4.75
9.58
16.66
26.31
54.48
89.25
2.50
3.15
3.72
4.25
4.74
5.65
6.0
3" 127.40 518 4126.0
4" 223.99 1123 11236.0
5" 349.09 1500 15006.0
FIXTURE UNITS
PIPE
SIZE
(GPM) FLUSH
TANK
FLUSH
VALVE
FLOW
RATE VELOCITY
(FT/SEC.)
FIXTURE UNITS
PIPE SIZE
(GPM) FLUSH
TANK
FLUSH
VALVE
FLOW
RATE VELOCITY
(FT/SEC.)
6" 501.83 1500 15006.0
3 1/2" 172.31 761 7186.0
3 1/2" 114.87 454 -4.0
4" 149.33 634 -4.0
5" 232.73 1194 -4.0
(FLUSH VALVE FIXTURE UNITS)
FIXTURE UNIT TOTAL
FIXTURE QUANTITY
TOTAL 115.5
FIXTURE UNITS REQUIRED EA.
CW HW CW HW
DOMESTIC WATER FIXTURE UNIT LOADS
DRINKING FOUNTAIN
2 .25 .5-
WATER CLOSET
7 10 70- -
(PUBLIC)
LAVATORY
7 1.5 10.51.5 10.5
(PUBLIC)
SINK
13 1.5 19.51.5 19.5
(PUBLIC)
SHOWER
2 3 63 6
(PUBLIC)
MOP/ SERVICE SINK
2 3 63 6(PUBLIC)
(PUBLIC)
CLOTHES WASHER
1 3 33(PUBLIC)
MAXIMUM LENGTH OF RUNOUTS
PIPE SIZE
(IN)
3/8
1/2
3/4
CAPACITY PER FOOT
(GAL/FT)
0.00753
0.01210
0.02510
0.04290
PUBLIC LAVATORIES,
SINK, LOW FLOW
FIXTURES (.5 GPM)
12 OZ
NON-PUBLIC
LAVATORIES AND
SINKS (PATIENT AND
EXAM ROOMS)
24 OZ
ICE MACHINES
12 OZ
SHOWERS
24 OZ
LOW FLOW URINAL
.125 GAL
URINAL
0.5
PUBLIC LAVATORIES,
SINK, LOW FLOW
FIXTURES
24 OZ
NON-PUBLIC
LAVATORIES AND
SINKS (PATIENT AND
EXAM ROOMS)
24 OZ
WATER CLOSET
1.28 GAL
TRAP PRIMER
4 OZ
12.45020
7.74793
NA
NA
24.90040
15.49587
NA
NA
12.45020
7.74793
NA
NA
24.90040
15.49587
NA
NA
24.90040
15.49587
NA
NA
NA
15.49587
NA
NA
NA
NA
4.98008
NA
NA
NA
19.92032
NA
NA
NA
NA
29.83683
4.15007
2.58264
NA
NA
CLOTHES WASHER 1 15 15
PANTRY SINK 20102
WH-1 150 150 8"WC1
MINIMUM STREET PRESSURE @ BLDG:
MAXIMUM STREET PRESSURE @ BLDG:
DOMESTIC BOOSTER PUMP CALCULATION
H-1 215 215 8"WC1
H-2 165 165 8"WC1
(PRMD) PROBABLE MAXIMUM DEMAND:
(SDF) STORAGE DEMAND FACTOR:
(PSMD) POSSIBLE MAXIMUM DEMAND
(DF) DEMAND FACTOR:
(SCF) STORAGE CAPACITY FACTOR:
(RRPH) RECOVERY RATE PER HOUR: (PRMD)+(SDF)=(RRPH)
(ST) SPACE TYPE:
(PSMD)x(DF)=(PRMD)
2.00
(PRMD)x(SCF)=(SDF)
.3
OFFICE BUILDING
(34.65)+(69.3)=(103.95)
(115.5)x(.3)=(34.65)
(34.65)x(2.00)=(69.3)
115.5
TOTAL NEEDED FOR RECOVERY 103.95
R
EG
IS
T
ER
ED
PROFESS IONAL
ENG
IN
E E
R
S T
A
TE
OF CA L I FORN
I A
No. M029768
Exp. 06/30/22
M
E C HA N I CA
L
P A
U L
Q I P I NG
DO
N GRomanyk Consulting
Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
SD-1 PACKAGE - ORIGINAL SUBMITTAL 5/24/2017
SD-1 PACKAGE - RESUBMITTAL
SD-1 PACKAGE - RESUBMITTAL
SD-1 PACKAGE - RESUBMITTAL - SITE LOCATIONS
8/15/2017
9/15/2017
12/5/2017
SD-2 PACKAGE 5/15/2018
DD-1 NON REVIEW 8/02/2018
DD-1 SUBMISSION 8/23/2018
DD-2 SUBMISSION 10/27/2018
CD-1 SUBMISSION 02/10/2019
CD-1 RE-SUBMISSION 04/12/2019
CD-1 RE-SUBMISSION 01/31/2020
CD-2 SUBMISSION 04/30/2020
CONSTRUCTION DOCUMENT SUBMISSION 06/29/2020
REVIEW SET FOR CONSTRUCTION DOCUMENT SUBMISSION #2 09/24/2020
CONSTRUCTION DOCUMENT SUBMISSION #2 12/04/2020 C
R e v it L o c a l F ile s \P
M a th e r
S o c ia l S e rv ic e s C e lli e .t ra n .r v t
/4 /2
:4
:0
A
M
PLUMBING CALCULATIONS
SN LC
CONSTRUCTION DOCUMENT
SUBMISSION
FULLY SPRINKLERED
612-163
P-003
DESIGN SOCIAL WORK AND EXPAND
CLINICAL SPACE
3551 Femoyer Street Mather, CA 95655
12/04/2020
300 N. LAKE AVENUE 14TH FLOOR
PASADENA, CA 91101
626.463.2800 FAX: 626.463.2801
(LOW PRESSURE GAS SYSTEM - LESS THAN 2 PSI)
FEMOYER STREETFEMOYER STREET
P E
T E
R A
. M cC
U E
N B
LV
D
F
U T
U R
E E
X T
E N
S
IO
N O
F P
E T
E R
A . M cC U
E N
B
LV
D
(N .I.
C
EXISTING SIDEWALK
E N
T R
Y /E
G R
E S
S
N .I
.C
LANDSCAPE
P A
R K
IN
G
N
.I .C
SIDEWALK
S
ID
E W
A L K
F U
T U
R E
S
ID
E W
A L K
N
.I .C
PARKING (N.I.C.) ENTRY/EGRESS
(N.I.C.)
HANDICAP
PARKING
CONCRETE & PAVEMENT AREA
PROPOSED IN CONTRACT
L A
N D
S C
A P
E
EN
TR
Y
S
ID
E W
A L K
SIDEWALK
4" SAN (102 FU)
I.E.= -5'-10"
FOR CONT.
REFER TO
CIVIL DWGS
2 1/2" CW(138.5 FU)
DEPTH OF COVER = 3'-0"
FOR CONT., SEE CIVIL DWGS. 3" G (1030 CFH)
DEPTH OF COVER = 3'-0"
FOR CONT., SEE CIVIL
DWGS.
LANDSCAPE W/ BERM
AND BOULDERS
ALONG SIDEWALK
F
6" FW
DEPTH OF COVER = 4'-0"
FOR CONT., SEE CIVIL DWGS.
METER &
REGULATOR BY
GAS CO.
EQV-1
4"C.O.
R
EG
IS
T
ER
ED
PROFESS IONAL
ENG
IN
E E
R
S T
A
TE
OF CA L I FORN
I A
No. M029768
Exp. 06/30/22
M
E C HA N I CA
L
P A
U L
Q I P I NG
DO
N GRomanyk Consulting
Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
SD-1 PACKAGE - ORIGINAL SUBMITTAL 5/24/2017
SD-1 PACKAGE - RESUBMITTAL
SD-1 PACKAGE - RESUBMITTAL
SD-1 PACKAGE - RESUBMITTAL - SITE LOCATIONS
8/15/2017
9/15/2017
12/5/2017
SD-2 PACKAGE 5/15/2018
DD-1 NON REVIEW 8/02/2018
DD-1 SUBMISSION 8/23/2018
DD-2 SUBMISSION 10/27/2018
CD-1 SUBMISSION 02/10/2019
CD-1 RE-SUBMISSION 04/12/2019
CD-1 RE-SUBMISSION 01/31/2020
CD-2 SUBMISSION 04/30/2020
CONSTRUCTION DOCUMENT SUBMISSION 06/29/2020
REVIEW SET FOR CONSTRUCTION DOCUMENT SUBMISSION #2 09/24/2020
CONSTRUCTION DOCUMENT SUBMISSION #2 12/04/2020 C
R e v it L o c a l F ile s \P
M a th e r
S o c ia l S e rv ic e s C e lli e .t ra n .r v t
/4 /2
:4
:2
A
M
PLUMBING SITE PLAN
SN LC
CONSTRUCTION DOCUMENT
SUBMISSION
FULLY SPRINKLERED
612-163
PS101
DESIGN SOCIAL WORK AND EXPAND
CLINICAL SPACE
3551 Femoyer Street Mather, CA 95655
12/04/2020
300 N. LAKE AVENUE 14TH FLOOR
PASADENA, CA 91101
626.463.2800 FAX: 626.463.2801
www.imegcorp.com # 02165361.00
1" = 20'-0"1
PLUMBING SITE PLAN
B1 B2 B3 B4 B4.5 B4.9 B5 B6
0.1
1.0
1.1
2.0
3.0
4.0
4.3
B1.4
B3.3
0.9
3.4
Y
0.05
0.06
2.6
B4.1
B4.3
0.08
0.09
B1.8
1/4" / 12"
3"
2" 2" 2"
2"2"3"
2"
2" 4"
4" 3"
4"W FR.
FCO ABV
2"W FR.
P-528 ABV.
2"W FR.
P-420 ABV.
2"W FR.
P-420 ABV.
2"W FR.
P-420 ABV.
2"W FR.
P-420 ABV.
2"W FR.
P-420 ABV.
2"W FR.
P-420 ABV.
2"W FR.
P-420 ABV.
2"W FR.
P-420 ABV.
2"W FR.
P-420 ABV.
2"W FR.
P-418 ABV.
4"W FR.
P-114 ABV.
4"W FR.
P-114 ABV.
2"W FR.
P-418 ABV.
2"W FR.
P-420 ABV.
3"W FR. ABV.
2"W FR.
FCO ABV
4"W FR.
FCO ABV
3"W FR.
P-501 ABV.
PL301
4"
4"
2"
2"
2"
3" 3"
3"
3"
3"
2"
4"
4"
4"FW RISER
4"FW
DEPTH OF COVER = 3'-0"
FOR CONT., SEE CIVIL DWGS.
2"
1/2"TP
3/4"CW FR. ABV.
1/2"TP
1/2"TP
DF-C
DF-C
DF-C
3"W FR. ABV.
2 1/2"DW (138.5FU)
DEPTH OF COVER = 3'-7 1/2"
FOR CONT., SEE CIVIL DWGS.
GAS LINE BY UTILITY COMPANY.
R
EG
IS
T
ER
ED
PROFESS IONAL
ENG
IN
E E
R
S T
A
TE
OF CA L I FORN
I A
No. M029768
Exp. 06/30/22
M
E C HA N I CA
L
P A
U L
Q I P I NG
DO
N GRomanyk Consulting
Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
SD-1 PACKAGE - ORIGINAL SUBMITTAL 5/24/2017
SD-1 PACKAGE - RESUBMITTAL
SD-1 PACKAGE - RESUBMITTAL
SD-1 PACKAGE - RESUBMITTAL - SITE LOCATIONS
8/15/2017
9/15/2017
12/5/2017
SD-2 PACKAGE 5/15/2018
DD-1 NON REVIEW 8/02/2018
DD-1 SUBMISSION 8/23/2018
DD-2 SUBMISSION 10/27/2018
CD-1 SUBMISSION 02/10/2019
CD-1 RE-SUBMISSION 04/12/2019
CD-1 RE-SUBMISSION 01/31/2020
CD-2 SUBMISSION 04/30/2020
CONSTRUCTION DOCUMENT SUBMISSION 06/29/2020
REVIEW SET FOR CONSTRUCTION DOCUMENT SUBMISSION #2 09/24/2020
CONSTRUCTION DOCUMENT SUBMISSION #2 12/04/2020 C
R e v it L o c a l F ile s \P
M a th e r
S o c ia l S e rv ic e s C e lli e .t ra n .r v t
/4 /2
:4
:0
A
M
PLUMBING FIRST FLOOR PLAN - UNDERGROUND
SN LC
CONSTRUCTION DOCUMENT
SUBMISSION
FULLY SPRINKLERED
612-163
PL101.2
DESIGN SOCIAL WORK AND EXPAND
CLINICAL SPACE
3551 Femoyer Street Mather, CA 95655
12/04/2020
300 N. LAKE AVENUE 14TH FLOOR
PASADENA, CA 91101
626.463.2800 FAX: 626.463.2801
www.imegcorp.com # 02165361.00
1/8" = 1'-0"1
PLUMBING FIRST FLOOR PLAN - UNDERGROUND
GROUP RM.
EXAM
EXAM
EXAM
EXAM
ISO. EXAM
CLEAN
111D
CORRIDOR
BREAK RM.
CONSULT RM.
EXAM
EXAM
EXAM
EXAM
PROCEDURE
TLT.
10A
SOILED
111B
STAFF AREA
ELECT.
111C
HAC
RECEPTION
VESTIBULE
135STORAGE
LOCKERS
CORRIDOR
STAFF TLT
111A
CONSULT RM.
B1 B2 B3 B4 B4.5 B4.9 B5 B6
0.1
1.0
1.1
2.0
3.0
4.0
4.3
B1.4
B3.3
0.9
3.4
Y
0.05
0.06
2.6
B4.1
B4.3
0.08 0.09
B1.8
G
G
G
P-528
W/ TMV-3
P-420
W/ TMV-3
P-420
W/ TMV-3
P-420
W/ TMV-3
P-420
W/ TMV-3
P-418
W/ TMV-2
P-501
W/ TMV-2
P-114
P-418
W/ TMV-2
P-114
P-420
W/ TMV-3
P-420
W/ TMV-3
P-420
W/ TMV-3
P-420
W/ TMV-3
P-420
W/ TMV-3
P-420
W/ TMV-3
C W
PL301
WB-1
WB-1
WB-1
WB-1
3/4"
3/4"
3/4"
3/4"
G 3" G (1030
CFH)
FR. BEL.
3/4"
2 1/2" 2 1/2"
3/4" 3/4"
3"
2 1/2"
1 1/2"
1 1/2"
1 1/4" 1 1/4"
3/4" 3/4"
1 1/4" 1"
1 1/4"1 1/2" 3/4"
3/4" 3/4"
1 1/2"
1 1/2"
1 1/2"G UP
(TYP.)
(TYP.) WHA-1
WHA-1
TP-2
W/ AP
TP-2
W/ AP
BP-1
6" HOUSEKEEPING
PAD
6" HOUSE-
KEEPING
PAD
BOOSTER PUMP
CONTROLER
PANEL
HNT-1
1 1/4"
2 1/2"
S.O.V.
EQV-1
METER & REGULATOR
PROVIDED BY GAS CO.
R
EG
IS
T
ER
ED
PROFESS IONAL
ENG
IN
E E
R
S T
A
TE
OF CA L I FORN
I A
No. M029768
Exp. 06/30/22
M
E C HA N I CA
L
P A
U L
Q I P I NG
DO
N GRomanyk Consulting
Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
SD-1 PACKAGE - ORIGINAL SUBMITTAL 5/24/2017
SD-1 PACKAGE - RESUBMITTAL
SD-1 PACKAGE - RESUBMITTAL
SD-1 PACKAGE - RESUBMITTAL - SITE LOCATIONS
8/15/2017
9/15/2017
12/5/2017
SD-2 PACKAGE 5/15/2018
DD-1 NON REVIEW 8/02/2018
DD-1 SUBMISSION 8/23/2018
DD-2 SUBMISSION 10/27/2018
CD-1 SUBMISSION 02/10/2019
CD-1 RE-SUBMISSION 04/12/2019
CD-1 RE-SUBMISSION 01/31/2020
CD-2 SUBMISSION 04/30/2020
CONSTRUCTION DOCUMENT SUBMISSION 06/29/2020
REVIEW SET FOR CONSTRUCTION DOCUMENT SUBMISSION #2 09/24/2020
CONSTRUCTION DOCUMENT SUBMISSION #2 12/04/2020 C
R e v it L o c a l F ile s \P
M a th e r
S o c ia l S e rv ic e s C e lli e .t ra n .r v t
/4 /2
:4
:0
A
M
PLUMBING FIRST FLOOR PLAN - WATER
SN LC
CONSTRUCTION DOCUMENT
SUBMISSION
FULLY SPRINKLERED
612-163
PL101A
DESIGN SOCIAL WORK AND EXPAND
CLINICAL SPACE
3551 Femoyer Street Mather, CA 95655
12/04/2020
300 N. LAKE AVENUE 14TH FLOOR
PASADENA, CA 91101
626.463.2800 FAX: 626.463.2801
www.imegcorp.com # 02165361.00
1/8" = 1'-0"1
PLUMBING FIRST FLOOR PLAN - WATER
KEYNOTES:
HEAT TRACING AND INSULATION WITH A WEATHER JACKET SHALL BE PROVIDED ON THE HYDROPNEUMATIC TANK (HNT-1), DOMESTIC BOOSTER PUMP (BP-1) AND THE ASSOCIATED EXPOSED PIPING TO THE PUMP, FROM THE PUMP TO THE HYDROPNEUMATIC TANK. THE HEAT TRACING SYSTEM SHALL INCLUDE, BUT NO LIMITED TO, RYCHEM, MODEL 5XL1 CABLE, PAYCLIC-PC POWER CONNECTION, RAYCLIC-T TEE CONNECTION, AMC-F5 - THERMOSTAT/CONTROLLER, GT-66 - ATTACHMENT TAPE FOR PLUMBING, AND AT-180 - ATTACHMENT TAPE FOR HYDROPNEUMATIC TANK.
0.1
1.0
1.1
2.0
4.0
4.3
B1.4
B3.3
0.9
3.4
Y
0.05
0.06
2.6
B4.1
B4.3
0.08
0.09
B1.8
P-528
W/ TMV-3
P-420
W/ TMV-3
P-420
W/ TMV-3
P-420
W/ TMV-3
P-420
W/ TMV-3
P-418
W/ TMV-2
4" OD UP
(2,400 SQ. FT.)
O D
4" SD UP
(2,175 SQ. FT.)
S D
4" SD UP
(2,400 SQ. FT.)
3" OD UP
(190 SQ. FT.)
3" SD UP
(190 SQ. FT.)
4" OD UP
(2,175 SQ. FT.)
P-501
W/ TMV-2
P-114
P-418
W/ TMV-2
P-114
3"V UP.
P-420
W/ TMV-3
P-420
W/ TMV-3
P-420
W/ TMV-3
4"FCO
P-420
W/ TMV-3
P-420
W/ TMV-3
P-420
W/ TMV-3
4"FCO
3"W FROM
ABV.
3"W DN.
PL301
22"
2" 2"
3"
2" 2"
3"
2"
3"
2"
3"
2"
GROUP RM.
EXAM
EXAM
EXAM
EXAM
CORRIDOR
BREAK RM.
EXAM
EXAM
EXAM
EXAM
PROCEDURE
SOILED
111B
TLT.
10A
CLEAN
111D
STAFF AREA
CONSULT RM.
CONSULT RM.
STORAGE
LOCKERS
CORRIDOR
WHEEL CHAIRS
100A
HAC
STAFF TLT
111A
ELECT.
111C
STAIR
S1
VESTIBULE
ISO. EXAM
3" SD/OD DN.
(305 SQ. FT.)
(TYP.)
3"
2" 2"
2"V
2"V
2"V
3"W DN.
2"
2"W FRM
ABV
2"W FRM
ABV
3"
4" SD
TERMINATE SD & OD
6" AFG
4" SD/OD DN.
(2,590 SQ. FT.)
TERMINATE SD & OD
6" AFG
4" SD/OD DN.
(2,175 SQ. FT.)
TERMINATE SD & OD
6" AFG
WCO
WCO WCO
WCO
WCO
WCOWCOWCO WCO
WCO
MOUNT ON
WALL
R
EG
IS
T
ER
ED
PROFESS IONAL
ENG
IN
E E
R
S T
A
TE
OF CA L I FORN
I A
No. M029768
Exp. 06/30/22
M
E C HA N I CA
L
P A
U L
Q I P I NG
DO
N GRomanyk Consulting
Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
SD-1 PACKAGE - ORIGINAL SUBMITTAL 5/24/2017
SD-1 PACKAGE - RESUBMITTAL
SD-1 PACKAGE - RESUBMITTAL
SD-1 PACKAGE - RESUBMITTAL - SITE LOCATIONS
8/15/2017
9/15/2017
12/5/2017
SD-2 PACKAGE 5/15/2018
DD-1 NON REVIEW 8/02/2018
DD-1 SUBMISSION 8/23/2018
DD-2 SUBMISSION 10/27/2018
CD-1 SUBMISSION 02/10/2019
CD-1 RE-SUBMISSION 04/12/2019
CD-1 RE-SUBMISSION 01/31/2020
CD-2 SUBMISSION 04/30/2020
CONSTRUCTION DOCUMENT SUBMISSION 06/29/2020
REVIEW SET FOR CONSTRUCTION DOCUMENT SUBMISSION #2 09/24/2020
CONSTRUCTION DOCUMENT SUBMISSION #2 12/04/2020 C
R e v it L o c a l F ile s \P
M a th e r
S o c ia l S e rv ic e s C e lli e .t ra n .r v t
/4 /2
:4
:0
A
M
PLUMBING FIRST FLOOR PLAN - WASTE
SN LC
CONSTRUCTION DOCUMENT
SUBMISSION
FULLY SPRINKLERED
612-163
PL101B
DESIGN SOCIAL WORK AND EXPAND
CLINICAL SPACE
3551 Femoyer Street Mather, CA 95655
12/04/2020
300 N. LAKE AVENUE 14TH FLOOR
PASADENA, CA 91101
626.463.2800 FAX: 626.463.2801
www.imegcorp.com # 02165361.00
PLUMBING FIRST FLOOR PLAN - WASTE
DN
OFFICE
OFFICE
211 OFFICE
IT
TOILET
TOILET
HAC
STORAGE
ELEV.
BREAK ROOM
STOR./PRINT
OPEN OFFICE
OFFICE
CONF.
ELECT
B1 B2 B3 B4 B4.5 B4.9 B5 B6
0.1
1.0
1.1
2.0
3.0
4.0
4.3
B1.4
B3.3
0.9
3.4
2.6
B4.1 B4.3
0.08 0.09
B1.8
PL301
3/4" CW
UP
1-1/4" G
(165 CFH)
UP TO
HUMIDIFIER
1-1/2" G
(215CFH)
UP TO
HUMIDIFIER
3/4"
3/4" CW
UP
2" 1 1/2"
CW
G
R
EG
IS
T
ER
ED
PROFESS IONAL
ENG
IN
E E
R
S T
A
TE
OF CA L I FORN
I A
No. M029768
Exp. 06/30/22
M
E C HA N I CA
L
P A
U L
Q I P I NG
DO
N GRomanyk Consulting
Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
SD-1 PACKAGE - ORIGINAL SUBMITTAL 5/24/2017
SD-1 PACKAGE - RESUBMITTAL
SD-1 PACKAGE - RESUBMITTAL
SD-1 PACKAGE - RESUBMITTAL - SITE LOCATIONS
8/15/2017
9/15/2017
12/5/2017
SD-2 PACKAGE 5/15/2018
DD-1 NON REVIEW 8/02/2018
DD-1 SUBMISSION 8/23/2018
DD-2 SUBMISSION 10/27/2018
CD-1 SUBMISSION 02/10/2019
CD-1 RE-SUBMISSION 04/12/2019
CD-1 RE-SUBMISSION 01/31/2020
CD-2 SUBMISSION 04/30/2020
CONSTRUCTION DOCUMENT SUBMISSION 06/29/2020
REVIEW SET FOR CONSTRUCTION DOCUMENT SUBMISSION #2 09/24/2020
CONSTRUCTION DOCUMENT SUBMISSION #2 12/04/2020 C
R e v it L o c a l F ile s \P
M a th e r
S o c ia l S e rv ic e s C e lli e .t ra n .r v t
/4 /2
:4
:1
A
M
PLUMBING SECOND FLOOR PLAN - WATER
SN LC
CONSTRUCTION DOCUMENT
SUBMISSION
FULLY SPRINKLERED
612-163
PL102A
DESIGN SOCIAL WORK AND EXPAND
CLINICAL SPACE
3551 Femoyer Street Mather, CA 95655
12/04/2020
300 N. LAKE AVENUE 14TH FLOOR
PASADENA, CA 91101
626.463.2800 FAX: 626.463.2801
www.imegcorp.com # 02165361.00
PLUMBING SECOND FLOOR PLAN - WATER
DN
0.1
1.0
1.1
2.0
3.0
4.0
4.3
B1.4
B3.3
0.9
3.4
2.6
B4.1
B4.3
0.08
0.09
B1.8
4"SD UP
(2,400 SQ. FT.)
3" SD UP
(305 SQ. FT.)
4" SD DN
(2,175 SQ. FT.)
3"V UP
4"OD UP
(2,400 SQ. FT.)
4"OD DN
(2,400 SQ. FT.)
4"SD DN
(2,400 SQ. FT.)
O D
S D
O
DS
D
4"OD DN
(2,175 SQ. FT.)
4"SD UP
(2,175 SQ. FT.)
4"OD UP
(2,175 SQ. FT.)
SD
OD
3" OD UP
(305 SQ. FT.)
SD
OD
3" SD DN
(305 SQ. FT.)
3" OD DN
(305 SQ. FT.)
3"V UP
3"W FROM
3"RR ABV.
3"W DN.
2"V UP
3"W FR.
3"RR ABV.
2"V UP
3" OD-1
(190 SQ. FT.)
3" RD-1
(190 SQ. FT.)
3/4"CD(1.75 TONS)
P-4.01
AC UNIT,
SEE MECH
DWGS
MAKE POC
TO UNIT
3"W DN.
3"W FROM
3"RR ABV.
2"W FROM
2"RR ABV.
2"W FROM
2"RR ABV.
2"V UP
2"V UP
2"V UP
2"W DN
2"W DN
3/4"CW UP
3/4"CW UP
R
EG
IS
T
ER
ED
PROFESS IONAL
ENG
IN
E E
R
S T
A
TE
OF CA L I FORN
I A
No. M029768
Exp. 06/30/22
M
E C HA N I CA
L
P A
U L
Q I P I NG
DO
N GRomanyk Consulting
Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
SD-1 PACKAGE - ORIGINAL SUBMITTAL 5/24/2017
SD-1 PACKAGE - RESUBMITTAL
SD-1 PACKAGE - RESUBMITTAL
SD-1 PACKAGE - RESUBMITTAL - SITE LOCATIONS
8/15/2017
9/15/2017
12/5/2017
SD-2 PACKAGE 5/15/2018
DD-1 NON REVIEW 8/02/2018
DD-1 SUBMISSION 8/23/2018
DD-2 SUBMISSION 10/27/2018
CD-1 SUBMISSION 02/10/2019
CD-1 RE-SUBMISSION 04/12/2019
CD-1 RE-SUBMISSION 01/31/2020
CD-2 SUBMISSION 04/30/2020
CONSTRUCTION DOCUMENT SUBMISSION 06/29/2020
REVIEW SET FOR CONSTRUCTION DOCUMENT SUBMISSION #2 09/24/2020
CONSTRUCTION DOCUMENT SUBMISSION #2 12/04/2020 C
R e v it L o c a l F ile s \P
M a th e r
S o c ia l S e rv ic e s C e lli e .t ra n .r v t
/4 /2
:4
:1
A
M
PLUMBING SECOND FLOOR PLAN - WASTE
SN LC
CONSTRUCTION DOCUMENT
SUBMISSION
FULLY SPRINKLERED
612-163
PL102B
DESIGN SOCIAL WORK AND EXPAND
CLINICAL SPACE
3551 Femoyer Street Mather, CA 95655
12/04/2020
300 N. LAKE AVENUE 14TH FLOOR
PASADENA, CA 91101
626.463.2800 FAX: 626.463.2801
www.imegcorp.com # 02165361.00
1/8" = 1'-0"1
PLUMBING SECOND FLOOR PLAN - WASTE
KEY NOTES
3/4"(1.75 TONS) CONDENSATE DRAIN DOWN
IN WALL & DISCHARGE INTO LAVATORY TAIL
PIECE.
(2,400 SQ. FT.)
(2,400 SQ. FT.)
4" RD-1
(2,175 SQ. FT.)
4" OD-1
(2,175 SQ. FT.)
4" RD-1
(2,020 SQ. FT.)
4" OD-1
(2,020 SQ. FT.)
3" RD-1
(305 SQ. FT.)
3" OD-1
(305 SQ. FT.)
4" RD-1
4"OD-1
B1 B2 B3 B4 B4.5 B4.9 B5 B6
0.1
1.0
1.1
2.0
3.0
4.0
4.3
B1.4
3.4
2.6
B4.1
0.08
0.09
B1.8
3" RR
3" RR
3" OD-1
(155 SQ. FT.)
3" RD-1
(155 SQ. FT.)
2" VTR
4" VTR
2" VTR
2" VTR
2" VTR
2 1/2" G
(500 CFH)
FROM BELOW
BFP-1
3/4"CW
FRM. BEL.
1"CD (30 TONS)
1"CD (30 TONS)
HB-1
3/4"CW TO
MECHANICAL
EQUIPMENT
P-4.01
PL401
PL401
3" RR
2" VTR
PL401
2 1-1/4"G
FRM BEL.
2" RR
2" RRBFP-1
3/4"CW
FRM. BEL.
1-1/2"G FRM. BEL.
2" VTR
BFP-1
3/4"CW
FRM. BEL.
3" VTR
3" OD-1
(190 SQ. FT.)
3" RD-1
(190 SQ. FT.)
R
EG
IS
T
ER
ED
PROFESS IONAL
ENG
IN
E E
R
S T
A
TE
OF CA L I FORN
I A
No. M029768
Exp. 06/30/22
M
E C HA N I CA
L
P A
U L
Q I P I NG
DO
N GRomanyk Consulting
Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
SD-1 PACKAGE - ORIGINAL SUBMITTAL 5/24/2017
SD-1 PACKAGE - RESUBMITTAL
SD-1 PACKAGE - RESUBMITTAL
SD-1 PACKAGE - RESUBMITTAL - SITE LOCATIONS
8/15/2017
9/15/2017
12/5/2017
SD-2 PACKAGE 5/15/2018
DD-1 NON REVIEW 8/02/2018
DD-1 SUBMISSION 8/23/2018
DD-2 SUBMISSION 10/27/2018
CD-1 SUBMISSION 02/10/2019
CD-1 RE-SUBMISSION 04/12/2019
CD-1 RE-SUBMISSION 01/31/2020
CD-2 SUBMISSION 04/30/2020
CONSTRUCTION DOCUMENT SUBMISSION 06/29/2020
REVIEW SET FOR CONSTRUCTION DOCUMENT SUBMISSION #2 09/24/2020
CONSTRUCTION DOCUMENT SUBMISSION #2 12/04/2020 C
R e v it L o c a l F ile s \P
M a th e r
S o c ia l S e rv ic e s C e lli e .t ra n .r v t
/4 /2
:4
:1
A
M
PLUMBING ROOF PLAN
SN LC
CONSTRUCTION DOCUMENT
SUBMISSION
FULLY SPRINKLERED
612-163
PL103
DESIGN SOCIAL WORK AND EXPAND
CLINICAL SPACE
3551 Femoyer Street Mather, CA 95655
12/04/2020
300 N. LAKE AVENUE 14TH FLOOR
PASADENA, CA 91101
626.463.2800 FAX: 626.463.2801
www.imegcorp.com # 02165361.00
PLUMBING ROOF PLAN
TOILET
TOILET
EXAM
EXAM
EXAM
EXAM
PROCE
DURE
TLT.
10A
TLT.
10A
HAC
STAFF
TLT.
111A
STAFF
TLT.
111A
TOILET
HAC
SHWR ROOM
102A
STORAGE
STAFF
TLT.
111A
TLT.
10A
ROOF
LEVEL
ROOF
LEVEL
LEVEL 2
LEVEL 1
0'-0"
LEVEL 1
0'-0"
LEVEL 2
WATER PIPE SIZE
1 0 2 1
13 0 10 13
840298
16681668
NOTE:
NOMINAL
PIPE SIZE
COLD WATER
(FLUSH TANK)
COLD WATER
(FLUSH VALVE)
HOT WATERGPM
1. PIPE SIZING IS BASED ON 5 FPS MAXIMUM VELOCITY @
A PRESSURE DROP OF 3.4 PSI/100 FT.
2. NUMBER OF BEDROOM =7
3. NUMBER OF BATHROOMS WITH SHOWER OR TUBS =10
1/2"
3/4"
1"
1 1/4"
1 1/2"
2"
2 1/2"
3"
4"
NOTE:
P-114 P-114
2"(20)
P-418
W/TMV-2
P-501
W/TMV-2
3/4"(2) 3/4"(2) 3/4"(2) 3/4"(2) 3/4"(2) 3/4"(2) 3/4"(4) 3/4"(2)1 1/2"(10) 1 1/2"(10)
3/4"(2) 3/4" (4)
3/4"(2) 2 1/2" (138.5)
FOR CONT.
REFER SHEET
NO. PL202
2 1/2" (89.5)
2 1/2" (137.5)
1 1/2"(34) 3/4"(2)
2"(58)
CW
2 1/2"(138.5 FU)
1 1/2"(10)
WB-1
3/4"(1) 3/4"(1) 3/4"(1)
3/4"(2)
1 1/2"(10) 1 1/2"(10)
WH-1
ET-1
CP-1
1 2
FOR CONT.
REFER SHEET
NO. PL202
2" (69.5)
3/4"(1)
1 1/2"(10)
1 1/2"(12)
PROVIDE EXPANSION LOOPS AND ANCHORAGE WITH PIPE
GUIDES ON STRAIGHT LINE AS PER MFG RECOMMENDATION
BUT NOT GREATER THAN 60 FT LONG.
TP-2TP-2
TP-2
BP-1
HNT-1
1 1/4"
P-420
W/TMV-3
P-420
W/TMV-3
P-420
W/TMV-3
P-420
W/TMV-3
P-420
W/TMV-3
P-418
W/TMV-2
P-114 WB-1 WB-1
P-501
W/TMV-2
P-114
P-418
W/TMV-2 P-704
R
EG
IS
T
ER
ED
PROFESS IONAL
ENG
IN
E E
R
S T
A
TE
OF CA L I FORN
I A
No. M029768
Exp. 06/30/22
M
E C HA N I CA
L
P A
U L
Q I P I NG
DO
N GRomanyk Consulting
Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
SD-1 PACKAGE - ORIGINAL SUBMITTAL 5/24/2017
SD-1 PACKAGE - RESUBMITTAL
SD-1 PACKAGE - RESUBMITTAL
SD-1 PACKAGE - RESUBMITTAL - SITE LOCATIONS
8/15/2017
9/15/2017
12/5/2017
SD-2 PACKAGE 5/15/2018
DD-1 NON REVIEW 8/02/2018
DD-1 SUBMISSION 8/23/2018
DD-2 SUBMISSION 10/27/2018
CD-1 SUBMISSION 02/10/2019
CD-1 RE-SUBMISSION 04/12/2019
CD-1 RE-SUBMISSION 01/31/2020
CD-2 SUBMISSION 04/30/2020
CONSTRUCTION DOCUMENT SUBMISSION 06/29/2020
REVIEW SET FOR CONSTRUCTION DOCUMENT SUBMISSION #2 09/24/2020
CONSTRUCTION DOCUMENT SUBMISSION #2 12/04/2020 C
R e v it L o c a l F ile s \P
M a th e r
S o c ia l S e rv ic e s C e lli e .t ra n .r v t
/4 /2
:4
:1
A
M
PLUMBING DOMESTIC WATER RISER DIAGRAMS
SN LC
CONSTRUCTION DOCUMENT
SUBMISSION
FULLY SPRINKLERED
612-163
PL201
DESIGN SOCIAL WORK AND EXPAND
CLINICAL SPACE
3551 Femoyer Street Mather, CA 95655
12/04/2020
300 N. LAKE AVENUE 14TH FLOOR
PASADENA, CA 91101
626.463.2800 FAX: 626.463.2801
www.imegcorp.com # 02165361.00
NO SCALE1
DOMESTIC COLD AND HOT WATER RISER DIAGRAM AREA "A"
BREAK
RM
BREAK ROOM
TOILET
TOILET
105A
TOILET
105A
TOILET
CLEAN
111D
ISO
EXAM
EXAM
EXAM
EXAM
EXAM
SHWR
ROOM
104A
LAUNDRY
TOILET
105A
LEVEL 2
LEVEL 1
0'-0"
ROOF LEVELROOF LEVEL
LEVEL 2
LEVEL 1
0'-0"
NOMINAL
PIPE SIZE
COLD WATER
(FLUSH TANK)
COLD WATER
(FLUSH VALVE)
HOT WATERGPM
WATER PIPE SIZE
1 0 2 1
13 0 10 13
840298
16681668
NOTE:
1. PIPE SIZING IS BASED ON 5 FPS MAXIMUM VELOCITY @
A PRESSURE DROP OF 3.4 PSI/100 FT.
2. NUMBER OF BEDROOM =7
3. NUMBER OF BATHROOMS WITH SHOWER OR TUBS =10
1/2"
3/4"
1"
1 1/4"
1 1/2"
2"
2 1/2"
3"
4"
BFP
3/4"CW FOR
MAKE UP WATER
FOR MECHANICAL EQP.
BFP
3/4"CW FOR
MAKE UP WATER
FOR MECHANICAL EQP.
(HUMIDIFIER)
BFP
3/4"CW FOR
MAKE UP WATER
FOR MECHANICAL EQP.
(HUMIDIFIER)
P-528
W/TMV-3
3/4"(2)
P-528
W/TMV-2
3/4"(2)
NOTE:
P-114P-114
2"(20)
P-418
W/TMV-2
3/4"(2)
P-420
W/TMV-3
P-420
W/TMV-3
P-420
W/TMV-3
P-420
W/TMV-3
P-420
W/TMV-3
3/4"(4) 3/4"(4)
3/4"(2) 3/4"(2) 3/4"(2) 3/4"(2) 3/4"(2) 3/4"(2) 3/4"(2) 1 1/2" (10)
P-418
W/TMV-2
P-418
W/TMV-2
P-114 P-418
W/TMV-2
P-704
3/4"(2)
3/4"(5)1"(7)1"(13)
2"(25)
2"(44.5)2" (69.5)
1 1/2"(34) 3/4"(4)
1"(10)
1 1/4"(20)
P-420
W/TMV-3
1 1/2"(10)
WB-1
3/4"(1)
WB-1
3/4"(1)
3/4"(2.5)
3/4"(2.5)
2"(25)
1 1/2"(10)
HB-1
BFP-1
P-608
3/4"(1)
P-608
3/4"(1)
FOR CONT.
REFER SHEET
NO. PL201
FOR CONT.
REFER SHEET
NO. PL201
1 1/4" (15.5)
3/4"(4)
1"(8)
1"(8)
3/4"(4)
3/4"(8)
1 1/4"(18)
1 1/4" (19.5)
FOR CONT.
REFER SHEET
NO. PL201
1 1/4"(30) 1 1/2"(32)
PROVIDE EXPANSION LOOPS AND ANCHORAGE WITH PIPE
GUIDES ON STRAIGHT LINE AS PER MFG RECOMMENDATION
BUT NOT GREATER THAN 60 FT LONG.
TP-2 TP-2
BFP-1BFP-1
3/4"3/4"
R
EG
IS
T
ER
ED
PROFESS IONAL
ENG
IN
E E
R
S T
A
TE
OF CA L I FORN
I A
No. M029768
Exp. 06/30/22
M
E C HA N I CA
L
P A
U L
Q I P I NG
DO
N GRomanyk Consulting
Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite…