Attachment 11 - Electrical Set Final.pdf

PDF 12 MB Posted

Attached to
Y1DA--689-402 Expand Primary Care - Construction (VA-19-00070477)
Solicitation number
36E77620B0003
Issued by

About this file

This document provides details for a federal contract solicitation to expand primary care facilities at the Newington VA Medical Center in Connecticut. The Department of Veterans Affairs seeks to renovate approximately 20,000 square feet of existing buildings and construct a new 5,000 square foot addition to create 25,000 additional square feet for primary care. The project also involves renovating several other spaces in other buildings to relocate offices and operations. The solicitation will be issued as an Invitation for Bid on March 31, 2020, with a performance period of approximately 600 calendar days. The contract value is estimated between $5-10 million. The solicitation is set aside solely for Service-Disabled Veteran-Owned Small Businesses. Questions must be submitted in writing by the deadline to the identified point of contact.

View the file

Other files

File Type Posted
36E77620B0003 0008.docx DOCX document
36E77620B0003 0007.docx DOCX document
36E77620B0003 0006.docx DOCX document
36E77620B0003 0005.docx DOCX document
Attachment 16 - Steam Coil Piping Connections Detail (SD238216-03).pdf PDF
Attachment 18 - Answers to Technical Questions.pdf PDF
36E77620B0003 0004.docx DOCX document
Attachment 15 - Revised Specifications TOC and Added Specs.pdf PDF
Attachment 17 - Borings Log Pictures from 1995 Project.zip ZIP file
36E77620B0003 0003.docx DOCX document
Attachment 1.pdf PDF
36E77620B0003 0002.docx DOCX document
36E77620B0003 0001.docx DOCX document
Attachment 14 - Wage Determination.pdf PDF
36E77620B0003.docx DOCX document
Attachment 10 - Fire Protection Set Final.pdf PDF
Attachment 2 - Combined Specs Volume 2.pdf PDF
Attachment 4 - General Set Final.pdf PDF
Attachment 9 - Plumbing Set Final.pdf PDF
Attachment 3 - Hazardous Materials Surveys.zip ZIP file
Attachment 13 - CONTRACTOR SAFETY AND ENV RECORD FORM.docx DOCX document
Attachment 12 - Combined Survey Final.pdf PDF
Attachment 5 - Civil Set Final.pdf PDF
Attachment 1 - Combined Specs Volume 1.pdf PDF
Attachment 7 - Structural Set Final.pdf PDF
Attachment 6 - Architectural Set Final.pdf PDF
Attachment 8 - Mechanical Set Final.pdf PDF
Show all 27

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A AMPERE

A/C AIR CONDITIONING

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHU AIR HANDLING UNIT

AWG AMERICAN WIRE GAUGE

BG BELOW GRADE

BLDG BUILDING

BRKR BREAKER

C CONDUIT

C B

CIRCUIT BREAKER

DWG DRAWING

EF EXHAUST FAN

EMT ELECTRICAL METALLIC

TUBING

EQUIP EQUIPMENT

ETR EXISTING TO REMAIN

EXIST EXISTING

FACP FIRE ALARM CONTROL PANEL

FLA FULL LOAD AMPS

GFI GROUND FAULT INTERRUPTER

GN

D

GROUND

HP HORSEPOWER

KAIC THOUSAND AMP INTERRUPTING

CAPACITY, RMS SYMMETRICAL

KCMIL

KILOWATT HOURKWH

THOUSAND CIRCULAR MILS

KVA KILOVOLT AMPERE

MCB MAIN CIRCUIT BREAKER

MLO MAIN LUG ONLY

MT MOUNT

MTD MOUNTED

MTG HT MOUNTING HEIGHT

N/C NORMALLY CLOSED

NF NON-FUSED

N/O NORMALLY OPEN

P POLE

PH PHASE

PNL PANEL

RECE

PT

RECEPTACLE

REQ'D REQUIRED

SF SUPPLY FAN

SW SWITCH

TELECOM TELECOMMUNICATIONS

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

UH UNIT HEATER

UG UNDERGROUND

UON UNLESS OTHERWISE NOTED

V VOLTS OR

VOLTAGEVA

C

VOLTS-AMPERES

VDC VOLTS-DIRECT CURRENT

WP WEATHERPROOF EQUIPMENT

XFMR TRANSFORMER

FC FOOTCANDLE

DT DRY TYPE

MSB MAIN SWITCHBOARD

NEC NATIONAL ELECTRICAL CODE

TGB TELECOMMUNICATIONS GROUND BUS

TMGB TELECOMMUNICATIONS MAIN GROUND

BUS

LAN LOCAL AREA NETWORK

LTG LIGHTING

UP UNDERGROUND POWER

SPD SURGE PROTECTIVE DEVICE

RM ROOM

FO FIBER OPTIC

CCTV CLOSED CIRCUIT TV

CR CARD READER

EIA ELECTRONIC INDUSTRIES

ALLIANCE

EP EMERGENCY POWER CIRCUIT

TIA TELECOMMUNICATIONS INDUSTRY

ASSOCIATION

MSGB MAIN SYSTEM GROUND BUSBAR

WAP WIRELESS ACCESS POINT

BOD BASIS OF DESIGN

DEMARC DEMARCATION POINT

(TELEPHONE/DATA)

F FUSED

FA FIRE ALARM

PA PUBLIC ADDRESS

ACC ACCESS CONTROL

(SECURITY)

FATC FIRE ALARM TERMINATION

CABINET

LED LIGHTING FIXTURE ( INDICATES BRACKET, WALL

MOUNTED FIXTURES).

EXIT LIGHTING FIXTURE. ARROW, WHEN USED, INDICATES DIRECTION.

( INDICATES BRACKET, WALL MOUNTED FIXTURES). FILLED-IN

QUADRANT(S) OF SYMBOL INDICATES NUMBER AND ORIENTATION OF

ILLUMINATED FACES. (SEE LEGEND NOTE 3).

SINGLE POLE SWITCH, 20A, 120/277VAC. MOUNT 48" AFF UON.

DOUBLE POLE SWITCH, 20A, 120/277VAC. MOUNT 48" AFF UON.

DUPLEX CONVENIENCE RECEPTACLE, 20A, 125VAC, MOUNT +

18" AFF UON. "WP" INDICATES WEATHERPROOF OUTLET.

RECEPTACLE AS NOTED ABOVE. MOUNT 48" AFF, OR 6" ABOVE

BACKSPLASH, OR COUNTER-TOP WHERE COUNTER IS INDICATED.

VOICE OUTLET, MOUNT 18"AFF U.O.N. SEE DETAIL 6 ON SHEET

EY501 FOR JACK ASSIGNMENT.

DESCRIPTIONSYMBOL

LIGHTINGPROVIDE

PASSIVE INFRARED DIMMABLE WALL SWITCH. BOD:

WATTSTOPPER PW-311.

POWER DEVICES

TELECOMMUNICATIONS SYSTEMS

EQUIPMENT CONNECTIONS

JUNCTION BOX.

ENCLOSED CIRCUIT BREAKER 480V IN NEMA 1 ENCLOSURE 14

KAIC UON 3P = NO. OF POLES, 100 = FRAME RATING, 40 = TRIP

RATING.

DESCRIPTIONSYMBOL

DISTRIBUTION

PANELBOARD - 208Y/120V.

DRY TYPE TRANSFORMER, SIZE AS NOTED.

PANELBOARD - 480Y/277V.

WIRE, CONDUIT AND RACEWAY

BRANCH CIRCUIT OR FEEDER WIRING IN CONDUIT. CONDUIT

LARGER THAN 1/2" & WIRE LARGER THAN #12 SHALL BE AS

INDICATED. (SEE LEGEND NOTE 1).

INDICATES A CONDUIT RUN CONCEALED IN CEILING, WALL,

FLOOR, OR ABOVE SUSPENDED CEILING UON.

HOMERUNS TO PANEL. PANEL AND CIRCUIT

DESIGNATIONS AS INDICATED.

CONDUIT TURNED DOWN.

CONDUIT TURNED UP.

L2A-1,3

GENERAL

NOTE REFERENCE (DIAMOND IS DEMO NOTE, CIRCLE IS NEW

WORK NOTE) - TYPICALLY LOCATED ON SAME SHEET WHERE

SYMBOL IS USED.

FOUR-WAY SWITCH, 20A, 120/277 VAC. MOUNT 48" AFF UON.

MOTOR CONNECTION AS NOTED.

QUADRUPLEX CONVENIENCE RECEPTACLE MOUNTED IN TWO-

GANG OUTLET BOX - EACH RATED 20A, 125VAC WITH SINGLE

COVER PLATE, MOUNT 18" AFF, UON.

LIGHTING FIXTURE TYPE, SEE LIGHTING FIXTURE SCHEDULE

ON THIS SHEET.

A

LED LIGHTING FIXTURE ON EMERGENCY CIRCUIT ( INDICATES

BRACKET, WALL MOUNTED FIXTURES). (SEE LEGEND NOTE 3).

THREE-WAY SWITCH, 20A, 120/277VAC. MOUNT 48" AFF UON.

DATA OUTLET MOUNT 18" AFF UON. SEE DETAIL 7 ON SHEET

EY501 FOR JACK ASSIGNMENT.

MAGNETIC MOTOR CONTROLLER (CONTROLLER

FURNISHED WITH EQUIPMENT).

MOTOR RATED SWITCH.

MANUAL MOTOR CONTROLLER (CONTROLLER

FURNISHED WITH EQUIPMENT).

DISCONNECT SWITCH. 600 V IN NEMA 1 ENCLOSURE UON 3P =

NO. OF POLES, 60 = SWITCH RATING, 40 = FUSE RATING (NF

INDICATES NON-FUSIBLE).

DISCONNECT SWITCH PROVIDED INTEGRAL WITH EQUIPMENT.

POINT OF CONNECTION NEW-TO-EXISTING (SEE LEGEND

NOTE 2).

POINT OF DEMOLITION.

ROOM NUMBER.

D

J

M

C

M

T

OR

3P 60

3P 60

VARIABLE FREQUENCY DRIVE CONNECTION (DRIVE FURNISHED

WITH EQUIPMENT).

VFD

PROVIDE

CONDUIT SEAL.

DASHED LINE INDICATES REMOVE INDICATED DEVICE OR

CIRCUIT.

EXISTING

D

J

M

C

M

OR

3P 60

3P 60

VFD

L2A-1,3

T

EXISTING

CONVENIENCE RECEPTACLE, 20A, 125VAC, WITH INTERNAL

GROUND FAULT INTERUPTION, MOUNT +18" AFF UON.

OROR

OCCUPANCY SENSOR.OS

DAYLIGHT SENSOR.DL

ROOM CONTROLLER (SINGLE RELAY). BOD: WATTSTOPPER

LMRC-221.

RC

OS

DL

RC RC OS

DLA

DIGITAL DIMMING SWITCH. BOD: WATTSTOPPER LMDM-101.AA

R2

WIRELESS ACCESS POINT (WAP). SURFACE MOUNT ON CEILING

UON.

W

MATV OUTLET, FLUSH-MOUNT ON WALL AT 56" AFF UON.TVTV

W

ROOM CONTROLLER (SINGLE RELAY). BOD: WATTSTOPPER

LMRC-222.

E EQUIPMENT CONNECTION.

TELECOM JUNCTION BOX. FLUSH-MOUNT ON FLOOR UON. (

INDICATES FLUSH-MOUNTED ON WALL). PROVIDE 4-11/16" X 4-

11/16" X 2-1/2" JUNCTION BOX UON.

DD

DATA OUTLET FLUSH-MOUNT ON FLOOR UON. FOLLOW DETAIL

ON SHEET EY501 ONLY FOR JACK ASSIGNMENT. BOD: LEGRAND

EFB45CTGY.

F F

FF

FIRE ALARM PULL STATION. MOUNT AT 48" AFF WITHIN 6 LINEAR

FEET OF EXITS AND STAIRWELLS AS INDICATED ON PLANS.

FIRE ALARM SPEAKER-STROBE APPLIANCE, WALL-MOUNT 6"

DOWN FROM CEILING IF SHOWN ON WALL, CEILING-MOUNT

WHEN SHOWN SUSPENDED.

FIRE ALARM CEILING-MOUNTED STROBE APPLIANCE.

FIRE ALARM

FIRE ALARM SMOKE DETECTOR, CEILING-MOUNT UON.

FIRE ALARM TERMINATION CABINET.FATCFATC

N NURSE CALL DUTY STATION, MOUNT 48" AFF UON.

NURSE CALL EMERGENCY PULLSTATION, MOUNT 48" AFF UON.

NURSE CALL CEILING MOUNTED CORRIDOR LIGHT.

MOUNT CENTERED 12" ABOVE DOORWAY.

NURSE CALL

D

N E

N

PUBLIC ADDRESS

PUBLIC ADDRESS SPEAKER. CEILING MOUNT UON. SEE RISER

ON SHEET EY701.

S S

SECURITY

INTERIOR CCTV CAMERA, SURFACE-MOUNT ON CEILING UON.

SEE DETAIL 5 ON SHEET EY501.

EXTERIOR CCTV CAMERA WITH PAN AND ZOOM FEATURE.

WALL-MOUNT AT 144" AFF UON. SEE DETAIL 5 ON SHEET EY501.

CR ACCESS CONTROL CARD READER, MOUNT AT 48"AFF UON.CR

KP COMBINATION ACCESS CONTROL CARD READER AND KEYPAD.

MOUNT AT 48"AFF UON.

SS

MS SECURITY CCTV MONITORING STATION OUTLET(S) LOCATION.

COORDINATE FINAL OUTLET(S) LOCATION WITH VA IT

DEPARTMENT PRIOR TO ROUGH-IN.

TV MAIN ANTENNA TELEVISION OUTLET. MOUNT AT 56" AFF UON.

LEGEND NOTES GENERAL NOTES

A. WIRING SHALL BE IN CONDUIT, MINIMUM SIZE ONE-HALF (1/2) INCH WITH

LARGER SIZES AS INDICATED OR REQUIRED BY NEC.

B. WIRE AND CABLE SHALL BE #12 AWG MINIMUM.

C. OPENINGS CREATED IN A FIRE OR SMOKE RATED WALL OR FLOOR BY

PROVISION OF ANY ELECTRICAL DEVICE OR CONDUIT, SHALL BE SEALED

AFTER THE WORK IS COMPLETED WITH A UL APPROVED FIRE/SMOKE

SEALANT APPROPRIATE TO RE-ESTABLISH THE PREVIOUS RATING OF

THE WALL OR FLOOR. SEE ARCHITECTURAL PLANS FOR FIRE RATED

WALLS/FLOORS AND THEIR RATING.

D. COORDINATE EXACT LOCATION OF CEILING MOUNTED LIGHTING

FIXTURES AND SPEAKERS WITH ARCHITECTURAL REFLECTED CEILING

PLANS.

E. CONNECTIONS TO FURNITURE OR EQUIPMENT SHALL BE FIELD-

COORDINATED PRIOR TO ROUGH-IN TO ENSURE PROPER INSTALLATION.

CONTRACTOR SHALL PROVIDE ELECTRICAL AND/OR DATA/TELECOM AS

SHOWN ON PLANS AND INSTALLED FOR FURNITURE OR EQUIPMENT PER

MANUFACTURER'S RECOMMENDATIONS. MAKE ALL CONNECTIONS AS

REQUIRED.

1. WIRE AND CONDUIT FOR MOTOR AND EQUIPMENT LOADS SHALL BE

CONTINUOUS IN SIZE AND COUNT FROM SOURCE TO FINAL CONNECTION.

SIZE AND COUNT SHALL BE AS INDICATED ON THE CIRCUIT HOMERUN

UON.

2. WHERE A NEW-TO-EXISTING CONNECTION IS INDICATED, PROVIDE

MATERIALS AND LABOR REQUIRED TO MAKE THE CONNECTION.

3. BRANCH CIRCUIT WIRING TO EXIT LIGHT FIXTURES SHALL BE

UNSWITCHED, CONNECTED AHEAD OF ANY CONTROL SWITCHES.

4. WHERE EQUIPMENT OR DEVICES ARE NOTED AS "REMOVE", REMOVE

CONDUCTORS ASSOCIATED WITH THESE ITEMS TO THE LAST ACTIVE

ITEM ON THE CIRCUIT, OR TO THE BRANCH CIRCUIT BREAKER IF ALL

ITEMS ON THE CIRCUIT ARE REMOVED. REMOVE CONDUITS FOR THESE

CIRCUITS WHERE THEY RUN EXPOSED OR IN CEILING OR FLOOR

PLENUMS. CONDUITS RUN CONCEALED IN WALLS OR FLOOR SLABS

SHALL BE CUT OFF FLUSH WITH SURFACE AND ABANDONED. VOIDS IN

WALLS OR FLOOR SLABS LEFT BY THE REMOVAL OF ELECTRICAL

EQUIPMENT OR CONDUITS SHALL BE FILLED WITH NON-SHRINK GROUT

AND FINISHED TO MATCH EXISTING ADJACENT SURFACES

ELECTRICAL ABBREVIATIONSELECTRICAL LEGEND

NOTES

1. EXACT NUMBER OF DEVICES SHOWN ON PLANS.

2. 120/277VAC POWER CONNECTION TO LIGHT FIXTURE.

3. 120/277VAC POWER SOURCE.

4. CAT 5E CABLE, NOT SHOWN ON DRAWINGS.

5. CAT 5E CABLE TO NEXT OCCUPANCY SENSOR, NOT SHOWN ON

DRAWINGS.

6. CAT 5E CABLE TO NEXT DAYLIGHT SENSOR, NOT SHOWN ON DRAWINGS.

7. 120/277VAC POWER SOURCE FOR SUBSEQUENT ROOM CONTROLLERS.

(LIGHTING CONTROL DIAGRAM ONLY)

LIGHTING CONTROL DIAGRAM

SCALE: NONE

(TYPICAL FOR ALL CONTROLLED SPACES)

LIGHTING FIXTURE SCHEDULE

TYPE MANUFACTURER MODEL NO.

LAMPS

VOLTAGE MOUNTING Description

Apparent LoadTYPE

A COLUMBIA

LIGHTING

LCAT24-35HLG-EDU LED 277 V LAY IN RECESSED 2X4 LED CENTER

ANGLED PRISMATIC LENS

48 VA

B COLUMBIA

LIGHTING

LCAT24-35MLG-EDU LED LAY IN RECESSED 2X4 LED CENTER

ANGLED PRISMATIC LENS

40 VA

C COLUMBIA

LIGHTING

LCAT22-35LWG-EDU LED LAY IN 2X2 INDIRECT/DIRECT, LED, 2000

LUMEN

23 VA

D HUBBEL

LIGHTING

LF6L-6LFSL-11L-35K-WNCT LED 277 V RECESSED DOWNLIGHT, 8" DIA., 32W TT,

VERTICAL LAMP

14 VA

E LITHONIA

LIGHTING

WL4-40L-LP835 LED SURFACE

MOUNT

1X4 INDIRECT/DIRECT 38 VA

F PEERLESS

LIGHTING

7CRM7L HI I4 120 EZB SCT

LP835

LED 277 V PENDANT LINEAR LED PENDANT, HI

OUTPUT

30 VA

G PEERLESS

LIGHTING

CRW7L-MSL4-80CRF-35K-I90

0LMF-ET-277

LED 277 V WALL MOUNT LINEAR WALL MOUNT LED, CURV,

PERF

30 VA

L LITHONIA

LIGHTING

DSXW1-20C-1000-30K-T2M-M

VOLT

LED 277 V WALL MOUNT LED WALL PACK 70 VA

X LITHONIA

LIGHTING

EDGR-R LED 277 V CEILING CEILING MOUNTED EXIT LIGHT 5 VA

LIGHTING CONTROL DESCRIPTION

LIGHTING CONTROL WILL BE ACHIEVED USING ROOM CONTROLLERS,

DIGITAL DIMMING SWITCHES, OCCUPANCY SENSORS, AND DAYLIGHT

SENSORS TIED TOGETHER TO CREATE A COMPLETE AND OPERABLE

SYSTEM. WHERE INDICATED, DUAL RELAY ROOM CONTROLLERS WILL

BE USED TO CONTROL TWO ROOMS PER ROOM CONTROLLER. IN

ROOMS WITH EMERGENCY LIGHTING, TWO CIRCUITS WILL BE REQUIRED,

ONE FOR NORMAL POWER AND ANOTHER FOR EMERGENCY POWER.

SEE ROOM CONTROLLER MANUFACTURER'S INSTALLATION GUIDE FOR

SPECIFIC WIRING DIRECTIONS AND LIGHTING CONTROL DIAGRAM FOR

GENERAL SYSTEM STRUCTURE.

MVOLT

MVOLT

th re e inc he s = o ne fo ot

6" on e an d on e ha lf i nc he s = o ne fo ot

6" on e inc h on e fo ot th re e qu ar te rs in ch o ne fo ot on e ha lf i nc h on e fo ot th re e eig ht hs in ch o ne fo ot on e qu ar te r i nc h on e fo ot on e eig ht h inc h on e fo ot

6"

6"

VA FORM 08-6231

Revisions:

1 2 3 4 5 6 7 8 9

Date:

Drawing Title:

Approved Project Director:

Project Title:

Location:

Date: Checked: Drawn:

Drawing Number:

Building Numbers:

Project Number:

Dwg. of

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

A R C H I T E C T S , I N C .A R C H I T E C T S , I N C .A R C H I T E C T S , I N C .A R C H I T E C T S , I N C .

TOLAND MIZELL

FINAL SUBMITTAL

ELECTRICAL LEGEND EXPAND PRIMARY CARE -

NEWINGTON VAMC

NEWINGTON, CT

E001

689-402

JUNE 7, 2019 RGB HVB 113

Approver

MVOLT

W W

W

W

W

W

W

W

W F

F F

F

F

W

F F

W

F

F

F

F

F

F

F

FF

F

F

F

F

F

F

M

M

F

F

F

F

F

S

S

S S

S

S

F

F

S

S

S

S

S S

S

S

F

NL

1M

NH

1M

LS

DP

2C

CR

DP

2C

ED

P2 C

EQ

DP

2C

A B C D F

NL

1F

NL

1F

NH1F

E

GENERAL NOTES

(THIS SHEET ONLY)

A. THIS PLAN SHOWS GENERALLY THE EXTENT OF

DEMOLITION TO BE PERFORMED. UNLESS

NOTED OTHERWISE, DISCONNECT, REMOVE,

AND HAUL OFF ALL ELECTRICAL ASSOCIATED

WITH AREAS TO BE RENOVATED. THIS MUST

INCLUDE, BUT NOT BE LIMITED TO: LIGHT

FIXTURES, WIRING DEVICES, PANELS,

DISCONNECTS, ACCESSIBLE BOXES, CONDUIT,

CONDUCTORS, ETC. WHERE BRANCH CIRCUITS

ARE BEING REMOVED, REMOVE BACK TO PANEL

FEEDING OR CLOSEST JUNCTION BOX OF

BRANCH CIRCUIT TO REMAIN. FIELD-VERIFY

AND COORDINATE EXISTING BRANCH CIRCUITS

AND ELECTRICAL TO REMAIN IN ALL AREAS AND

KEEP ACTIVE THROUGHOUT CONSTRUCTION.

PROVIDE ALL APPURTENCANCES NECESSARY

AND MAKE ALL CONNECTIONS AS REQUIRED.

COORDINATE WITH ARCHITECTURAL DRAWINGS

FOR EXACT LIMITS OF CONSTRUCTION.

B. REMOVE TELECOMMUNICATIONS OUTLETS.

REMOVE BOXES, CONDUIT, AND CABLING BACK

TO POINT OF SERVICE. BLDG 2W EXISTING

TELECOM EQUIPMENT IS LOCATED IN TELECOM

ROOM 2W-128. BLDG 2C EXISTING TELECOM

EQUIPMENT IS LOCATED IN TELECOM ROOM 2C-

1156 (BLDG 2C FIRST FLOOR).

C. EXISTING FIRE ALARM SYSTEMS ARE SIMPLEX.

FOR BLDG 2W, THE EXISTING FATC IS A

SIMPLEX 4100ES. REMOVE PANEL AND STORE

FOR INSTALLATION DURING NEW WORK.

PRESERVE NETWORK CONNECTIONS AND

CONNECTIONS TO 2W BASEMENT DEVICES.

COORDINATE FIRE ALARM OUTAGE WITH

OWNER. REMOVE FIRE ALARM DEVICES IN AREA

OF RENOVATION AND TURN OVER TO OWNER.

REMOVE BOXES, CONDUIT, AND CABLING BACK

TO POINT OF SERVICE. AT BLDG 2C, THE

EXISTING FATC IS A 4100ES AND IS LOCATED IN

THE SERVICE LOBBY C1-9. REMOVE FIRE ALARM

DEVICES UNLESS OTHERWISE NOTED AND

TURN OVER TO OWNER. REMOVE BOXES,

CONDUIT, AND CABLING BACK TO POINT OF

SERVICE OR NEAREST REMAINING DEVICE.

SERVICES TO OTHER FLOORS OR AREAS ON

THE SAME FLOOR MUST NOT BE INTERRUPTED.

D. REMOVE WAPS AND TURN OVER TO VA FOR

STORAGE. REINSTALL WAPS DURING NEW

WORK.

E. REMOVE PUBLIC ADDRESS SPEAKERS IN AREAS

OF RENOVATION. REMOVE BOXES, CONDUIT,

AND CABLING BACK TO NEAREST REMAINING

DEVICE OR TERMINAL CABINET. EXISTING

HEAD-END EQUIPMENT IS LOCATED IN ROOM

2E-5151 (BLDG 2E 5TH FLOOR) . EXISTING

TERMINAL CABINETS IN AREAS OF RENOVATION

ARE LOCATED IN ROOMS 2W-128 (BLDG 2W 1ST

FLOOR) AND 2C-147 (BLDG 2C 1ST FLOOR).

SERVICES TO OTHER FLOORS OR OTHER

AREAS ON THE SAME FLOOR MUST NOT BE

INTERRUPTED.

DEMOLITION KEY NOTES

(THIS SHEET ONLY)

1. PANELS IN THIS SPACE ARE EXISTING TO

REMAIN.

2. EXISTING TO REMAIN TELECOMMUNICATIONS

ROOM.

3. LIGHTING IN THIS SPACE IS EXISTING TO

REMAIN.

BLDG

2W BLDG 2C

BLDG 2E

BL

DG

BLDG 3

BLDG

BLDG 34

BLDG 33

BL

DG

2 KEY PLAN

NTS

ADDITION

BLDG

th re e inc he s = o ne fo ot

6" on e an d on e ha lf i nc he s = o ne fo ot

6" on e inc h on e fo ot th re e qu ar te rs in ch o ne fo ot on e ha lf i nc h on e fo ot th re e eig ht hs in ch o ne fo ot on e qu ar te r i nc h on e fo ot on e eig ht h inc h on e fo ot

6"

6"

VA FORM 08-6231

Revisions:

1 2 3 4 5 6 7 8 9

Date:

Drawing Title:

Approved Project Director:

Project Title:

Location:

Date: Checked: Drawn:

Drawing Number:

Building Numbers:

Project Number:

Dwg. of

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

A R C H I T E C T S , I N C .A R C H I T E C T S , I N C .A R C H I T E C T S , I N C .A R C H I T E C T S , I N C .

TOLAND MIZELL

FINAL SUBMITTAL

FIRST FLOOR DEMOLITION PLAN

BUILDINGS 2W & 2C

EXPAND PRIMARY CARE -

NEWINGTON VAMC

NEWINGTON, CT

ED101

689-402

JUNE 7, 2019 RGB TWG 113

Approver

1/8" = 1'-0"

2W/2C - FIRST FLOOR - DEMO

FATC

F

F S

W

W

W

W

W

F

F

F

F

F

F

TV

N

N

S

S

S

S W

W

W F

F

F

F

F

W

J

E

F

F

F

W

W

W

W

EH

BA

CL

BA

NLBA3

NLBA1

NLBA2

CHBA

NHBA

2E-B139

DEMOLITION KEY NOTES

(THIS SHEET ONLY)

1. PANELS IN THIS SPACE (ELEC ROOM 2E-

B139) ARE EXISTING TO REMAIN.

2. REMOVE FIRE ALARM DEVICES IN THIS

AREA.

3. REMOVE EXISTING WIREWAY BACK TO

DISCONNECT SWITCH ON SOUTH WALL ON

FLOOR BELOW IN COMPRESSOR ROOM.

SEE NOTE 4.

4. EXISTING DISCONNECT SWITCH TO BE

REMOVED.

5. EXISTING EXHAUST FAN MONITORING

PANEL TO BE REMOVED.

6. EXISTING SWITCH FOR EXISTING EXAUST

FAN ON ROOF TO BE REMOVED.

7. DEMOLISH CIRCUIT SERVING EXISTING

HVAC EQUIPMENT BACK TO SOURCE.

8. THIS PANEL IS EXISTING TO REMAIN ON

FLOOR ABOVE, ROOM 2E-173.

GENERAL NOTES

(THIS SHEET ONLY)

A. THIS PLAN SHOWS GENERALLY THE EXTENT

OF DEMOLITION TO BE PERFORMED. UNLESS

NOTED OTHERWISE, DISCONNECT, REMOVE,

AND HAUL OFF ALL ELECTRICAL ASSOCIATED

WITH AREAS TO BE RENOVATED. THIS MUST

INCLUDE, BUT NOT BE LIMITED TO: LIGHT

FIXTURES, WIRING DEVICES, PANELS,

DISCONNECTS, ACCESSIBLE BOXES,

CONDUIT, CONDUCTORS, ETC. WHERE

BRANCH CIRCUITS ARE BEING REMOVED,

REMOVE BACK TO PANEL FEEDING OR

CLOSEST JUNCTION BOX OF BRANCH

CIRCUIT TO REMAIN. FIELD-VERIFY AND

COORDINATE EXISTING BRANCH CIRCUITS

AND ELECTRICAL TO REMAIN IN ALL AREAS

AND KEEP ACTIVE THROUGHOUT

CONSTRUCTION. PROVIDE ALL

PURTENCANCES NECESSARY AND MAKE ALL

CONNECTIONS AS REQUIRED. COORDINATE

WITH ARCHITECTURAL RAWINGS FOR EXACT

LIMITS OF CONSTRUCTION.

B. REMOVE TELECOMMUNICATIONS OUTLETS

AS SHOWN. REMOVE BOXES, CONDUIT, AND

CABLING BACK TO POINT OF SERVICE.

C. EXISTING FIRE ALARM SYSTEMS ARE

SIMPLEX. AT BLDG 1, REMOVE FIRE ALARM

DEVICES AS SHOWN AND TURN OVER TO

OWNER. REMOVE BOXES, CONDUIT, AND

CABLING BACK TO POINT OF SERVICE OR

NEAREST REMAINING DEVICE. SERVICES TO

OTHER FLOORS OR AREAS ON THE SAME

FLOOR MUST NOT BE INTERRUPTED. AT

BLDG 2E, REMOVE FIRE ALARM DEVICES AS

SHOWN AND TURN OVER TO OWNER.

REMOVE BOXES, CONDUIT, AND CABLING

BACK TO POINT OF SERVICE OR NEAREST

REMAINING DEVICE. SERVICES TO OTHER

FLOORS OR AREAS ON THE SAME FLOOR

MUST NOT BE INTERRUPTED.

D. REMOVE WAPS AND TURN OVER TO VA FOR

STORAGE. REINSTALL WAPS DURING NEW

WORK.

E. REMOVE PUBLIC ADDRESS SPEAKERS IN

AREAS OF RENOVATION. REMOVE BOXES,

CONDUIT, AND CABLING BACK TO NEAREST

REMAINING DEVICE OR TERMINAL CABINET.

EXISTING HEAD-END EQUIPMENT IS LOCATED

IN ROOM 2E-5151. EXISTING TERMINAL

CABINET IN AREA OF RENOVATION IS

LOCATED IN ROOM 2E-B44. SERVICES TO

OTHER FLOORS OR OTHER AREAS ON THE

SAME FLOOR MUST NOT BE INTERRUPTED.

6110-0278

EM6

6110-0279

BLDG

2W

BUILDING 2C

BUILDING 2E

BL

DG

1BUILDING 3

BLDG

BLDG 34

BLDG 33

BL

DG

2 KEY PLAN

NTS

ADDITION

2E BASEMENT

BLDG

2E-B139 th re e inc he s = o ne fo ot

6" on e an d on e ha lf i nc he s = o ne fo ot

6" on e inc h on e fo ot th re e qu ar te rs in ch o ne fo ot on e ha lf i nc h on e fo ot th re e eig ht hs in ch o ne fo ot on e qu ar te r i nc h on e fo ot on e eig ht h inc h on e fo ot

6"

6"

VA FORM 08-6231

Revisions:

1 2 3 4 5 6 7 8 9

Date:

Drawing Title:

Approved Project Director:

Project Title:

Location:

Date: Checked: Drawn:

Drawing Number:

Building Numbers:

Project Number:

Dwg. of

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

A R C H I T E C T S , I N C .A R C H I T E C T S , I N C .A R C H I T E C T S , I N C .A R C H I T E C T S , I N C .

TOLAND MIZELL

FINAL SUBMITTAL

DEMOLITION PLANS BULDINGS 1 &

2E

EXPAND PRIMARY CARE -

NEWINGTON VAMC

NEWINGTON, CT

ED102

689-402

JUNE 7, 2019 RGB TWG 113

Approver

1/8" = 1'-0"

2E - BASEMENT - DEMO

1/8" = 1'-0"

42 - SECOND FLOOR - DEMO

1/8" = 1'-0"

3 - SECOND FLOOR - DEMO

1/8" = 1'-0"

1 - FOURTH FLOOR - DEMO

A

D

A

DD

A A

A A

D D

D D

A

A

A

A

AA

D

D D

D

A D

DD

D

R2

RC

RCRC

RC

RC

RCRC

RC

RC

OS OS

DL

D

DD

D D

OS

DL

OS

DL

OS OS

OS

OS

A

RC

RC

R2

D DL

R2

OS DL

R2

OS DL OS DL

OSDL

OSDL

OSDL

OSDL

RC

RC

RC

RC

RC

RC

R2

R2

R2

R2

R2R2

RCRC

R2 R2

A A A

D

OS OS

DL DL

D

OS DL

DL

OS DL

A

OS

OS

C

B B B B

B B B B

B B

B BA

C

C

C

C

C

C

C

C

B

B

B B

B

B

C

C C C C C C C

AB

B

B

B

B

B B

B

C

C

C C

C

B B

C

C A A

C

C C

C

C C

C C

B

B

A

A

B

G G

L L

EDP2C

CRDP2C

LSDP2C

EQDP2C

F

F F

F

F F

C

C

C

C

C

C

C

C

C

C

NL1F2

G

G

NL1M

NH1M

A

X

X

X

X

X

X

X

X

X X

E E E E

E E

G

G

A

A

E E E

B

C

C

C

C

C

C

C C

C

F

F

B

B

A

A

A

A

G

G

B

C

C

A

C

A

C

A

C

B

C

C

C

C

A

A

A

C

C

C

B

C

A

C

A

C A

C A

C

A

A

C

A

C

A

C

A

C

A

C

C

A

C

A

C

C

A

A

C

A

B B

C C

C B

C A

C A

C B

B

B B

B B

X

B

NH1F

1C4

2W-118 2W-119 2W-120 2W-122 2W-124

2W-125

2W-126 1C5

2W-1232W-121

1C3

2W-115

2W-116 2W-117

2W-114

2W-112

2W-109A

2W-131C

2W-131B

2W-130B

2W-127

2W-130A

2C-1178

2C-1182

2C-1180

2C-1179

2W-215

2W-132B

2W-100

2W-101

2W-102

2W-106 2W-104

1C2

2W-103A

2W-103B

2W-108B

1C3

2W-107B

2W-107A

2W-105A2W-105B

2W-108A

2W-113

2W-110

2W-131A

2C-1146

2C-1141

2C-S8

2C-1145 2C-1144 2C-1143

42-248

42-247

42-246

C1-1041

2C-1166

2C-1164

2C-1165

2C-1167

2C-11682C-1173

2C-1172

2C-1171

2C-1170 2C-1169

C2-1

C2-2

2C-1176

2C-1175

2C-1174

2C-1177

X

B

2W-109B

A B C D F

NH1M - 12

NH1M - 8

NH1M - 13

NH1M - 9

LSDP2C - 15

NH1F - 22

LSDP2C - 13

NH1F - 25

EHBM - 13

EHBM - 12

EHBM - 10

1 1

11 1

A

C

NH1M - 10

NH1M - 15

EHBM - 17

NH1M - 11

LSDP2C - 17

NH1F - 23

NL1F1

EHBM - 15

D

D

D

L

L

E

LIGHTING KEY NOTES

(THIS SHEET ONLY)

1. PROVIDE WITH UL LIGHTING RELAY

CONTROL DEVICE. UPON LOSS OF "NORMAL"

POWER, LUMENAIRES ON GENERATOR

BACKUP SHALL COME ON TO FULL LUMENS.

QHBM QLBM ELBM EHBM

A

2W-B00A

BLDG

2W

BLDG 2C

BLDG 2E

BL

DG

BLDG 3

BLDG

BLDG 34

BLDG 33

BL

DG

2 KEY PLAN

NTS

ADDITION

BASEMENT ELEC RM

BLDG

th re e inc he s = o ne fo ot

6" on e an d on e ha lf i nc he s = o ne fo ot

6" on e inc h on e fo ot th re e qu ar te rs in ch o ne fo ot on e ha lf i nc h on e fo ot th re e eig ht hs in ch o ne fo ot on e qu ar te r i nc h on e fo ot on e eig ht h inc h on e fo ot

6"

6"

VA FORM 08-6231

Revisions:

1 2 3 4 5 6 7 8 9

Date:

Drawing Title:

Approved Project Director:

Project Title:

Location:

Date: Checked: Drawn:

Drawing Number:

Building Numbers:

Project Number:

Dwg. of

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

A R C H I T E C T S , I N C .A R C H I T E C T S , I N C .A R C H I T E C T S , I N C .A R C H I T E C T S , I N C .

TOLAND MIZELL

FINAL SUBMITTAL

FIRST FLOOR LIGHTING PLAN

BUILDINGS 2W & 2C

EXPAND PRIMARY CARE -

NEWINGTON VAMC

NEWINGTON, CT

EL101

689-402

JUNE 7, 2019 RGB PEW 113

Approver

1/8" = 1'-0"

2W/2C - FIRST FLOOR - LIGHTING

2W - BASEMENT ELEC RM - LIGHTING

RC

RCRC

RC

RC

RC

3 3

A

A

D D D D

D D

D D D

D D

D D

DDD

D

RC RC

DL

OS

OS

A

A A

RC

RC

OS

OS

OS

DL

OS

RC

D D

D

A

A A

A

RC

RC

RC

A

OS

DL

DL

NLBA2

NLBA1

NLBA3

EHBA CLBA

CHBA

NHBA

B

B

B

B

B

B

B

B

B

B

B B B B B

B B

B B B

B B B B B

B B B B B

B

B

B

B

B

B

B B

B B

B

B

B

B

B

B

C

C

CC

CB

B

C C C

CC

C

BBB B

BB BB

B

B

B

B

B

B D

2E-B140C

2E-B140D 2E-B140E 2E-B140F

2E-B140G 2E-B140H

2E-B137C

2E-B137A

2E-B137B

2E-B137

2E-B042

2E-B140B

2E-B140A 2E-B40

2E-B127E2E-B127C

2E-B127B

2E-B127A

2E-B127D 2E-B46

1 1

EHBA - 11

NHBA - 1NHBA - 18

NHBA - 17

D D D

2E-B140H

CB-11

LIGHTING KEY NOTES

(THIS SHEET ONLY)

1. PROVIDE WITH UL LIGHTING RELAY CONTROL

DEVICE. UPON LOSS OF "NORMAL" POWER,

LUMINAIRES ON GENERATOR BACKUP SHALL

COME ON TO FULL LUMENS.

2. CONNECT TO EXISTING EMERGENCY POWER

LIGHTING CIRCUIT IN THIS SPACE.

3. CONNECT TO EXISTING NORMAL POWER

LIGHTING CIRCUIT IN THIS SPACE.

B B B B B B

B

B

B

B

B

B

B

B B B

B

B

B

B

B B B

C C

C C

C C C C

B

C C C

C

C

C

C C C

B

ROOF

ROOF

42-216 42-217 42-218

42-209 42-215

42-207

42-209

42-211

42-208

42-202

42-203

42-206

42-205 42-204

42-201A

42-201

42-213 42-219

42-A - 27

42-A - 25

42-A - 23

B B B B

B B B

B

B B B B

3-201

C2-2

C2-1

1-445

B B B

B

B

B BB

B B BB

B

B B

BB

B B

B B

NL4Q

EL

4Q

E

B

EL4Q - 9

NL4Q - 41

1-434A

1-434B

1-434C

1-434

Unoccupied

1-445

1-445A

1-434D

1-446

C4-12A

1-428

1-428

1-430

1-444

BLDG

2W

BUILDING 2C

BUILDING 2E

BL

DG

1BUILDING 3

BLDG

BLDG 34

BLDG 33

BL

DG

2 KEY PLAN

NTS

ADDITION

2E BASEMENT

BLDG

th re e inc he s = o ne fo ot

6" on e an d on e ha lf i nc he s = o ne fo ot

6" on e inc h on e fo ot th re e qu ar te rs in ch o ne fo ot on e ha lf i nc h on e fo ot th re e eig ht hs in ch o ne fo ot on e qu ar te r i nc h on e fo ot on e eig ht h inc h on e fo ot

6"

6"

VA FORM 08-6231

Revisions:

1 2 3 4 5 6 7 8 9

Date:

Drawing Title:

Approved Project Director:

Project Title:

Location:

Date: Checked: Drawn:

Drawing Number:

Building Numbers:

Project Number:

Dwg. of

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

A R C H I T E C T S , I N C .A R C H I T E C T S , I N C .A R C H I T E C T S , I N C .A R C H I T E C T S , I N C .

TOLAND MIZELL

FINAL SUBMITTAL

LIGHTING PLANS BUILDINGS 2E, 3,

AND 42

EXPAND PRIMARY CARE -

NEWINGTON VAMC

NEWINGTON, CT

EL102

689-402

JUNE 7, 2019 RGB PEW 113

Approver

1/8" = 1'-0"

2E- BASEMENT - LIGHTING

42 - SECOND FLOOR - LIGHTING

3 - SECOND FLOOR - LIGHTING

1 - FOURTH FLOOR - LIGHTING

E M

E M

E M

E M E M

E M

E M

E M

E M

E M

E M

E M E M

E M

E M

E M

E M

E M

E M

E M

E M

E M

E M

E M

E M

E M

E M 5

A B C ED F

2W-115

2W-116

2W-129

2W-113

2W-106 2W-104

2W-117

2W-131B

2W-101

2W-100

1C1-02W

2W-114

2W-112

2W-109A

2W-108A

2W-131A

2W-1232W-121

2W-108B

2W-131C

2W-109B

2W-103B

2W-110

C2-2

2C-1177 2C-1173

2C-1172

2C-1171

2C-1176

2C-1174

2C-1175

2W-120

2W-124

2W-103A

2W-126

2W-107B

2W-107A 2W-102

2W-105A

2C-1180 2C-1179

2C-1167

2C-1166

2C-1145 2C-1143

2C-1144

C2-1

2W-215 C1-1041

2W-127

2W-132B 2C-1181

2C-1178

2W-130B

2W-130A

1C2

1C4

1C3

1C5 2C-1164

2C-1141

2C-1146

2C-1168

2W-105B

2W-125

NH

1M

NL

1M

LS

DP

2C

ED

P2 C

EQ

DP

2C CR

DP

2C

NL1M - 2 NL1M - 3

NL1M - 1

NL1M - 4

NL1M - 5

NL1M - 6

NL1M - 14

NL1M - 15

NL1M - 16

NL1M - 22

NL1M - 18

NL1M - 19

NL1M - 21

NL1M - 29

NL1M - 28

NL1M - 31

NL1M - 30 NL1M - 32

NL1M - 33

NL1M - 24

NL1M - 26

NL1M - 11

NL1M - 13

NL1M - 35

NL1M - 8

NL1M - 10

NL1M - 12

NL1M - 9

NH1F

NL1M - 20

NL1M - 23 NL1M - 25

NL1M - 37

NL1M - 36

NL1M - 38

NL1M - 39

NL

1F

NL

1F

NL1F2 - 27

NL1F2 - 22

NL1F2 - 19

NL1F2 - 21

NL1F2 - 4

NL1F2 - 36 NL1F2 - 35

NL1F2 - 24

NL1F2 - 25

NL1F2 - 23

NL1F2 - 26

NL1F2 - 1 NL1F2 - 7

NL1F2 - 8

NL1F2 - 5

NL1F2 - 6

NL1F2 - 14

NL1F2 - 9

NL1F2 - 10

NL1F2 - 33

NL1F2 - 11

NL1F2 - 30

NL1F2 - 29

NL1F2 - 28

NL1F2 - 31

NL1F2 - 31

NL1F2 - 20

NL1F2 - 12

NL1F2 - 18

NL1F2 - 13

NL1F2 - 34

NL1F2 - 3

NL1F2 - 17

NL1F2 - 16

NL1F2 - 2

NL1M - 17

NL1F2 - 32

1111 11

11 11

11 11

11 1111

NL1F2 - 15

2C-13

2C-08

2C-05

2C-09

2W-15

2W-14

2C-11

2W-12

2C-13 2W-08

2W-09

2W-02

2W-07

2C-01

2C-02 2C-04

2C-10

2C-03

2C-11

2C-06

2C-07

2W-03

2W-01

2W-04

AC

-1

AC

-2

2W-13

2W-05

2C-12

A B C ED F12

12 12

12 12

NL1F1 - 1,3

NL1M - 40,42

E.01

E

NL1M - 7

NL1M - 41

POWER KEY NOTES

(THIS SHEET ONLY)

1. EXISTING PANEL NL1F2 IS A WESTINGHOUSE

PRL1, 208Y/120V, 150A MAIN BREAKER

PANELBOARD.

2. EXISTING PANEL NH1M IS A WESTINGHOUSE

PRL3A, 480Y/277V, 150A MAIN LUGS ONLY

PANELBOARD.

3. EXISTING PANEL NL1M IS A WESTINGHOUSE

PRL1 208Y/120V, 150A MAIN BREAKER

PANELBOARD.

4. EXISTING PANEL LSDP2C IS A

WESTINGHOUSE, 480Y/277V, 100A MAIN

BREAKER, 14KAIC PANELBOARD.

5. EXISTING PANEL CRDP2C IS

WESTINGHOUSE, 480Y/277V, 100A MAIN

BREAKER, 14KAIC PANELBOARD.

6. EXISTING PANEL EDP2C IS A SIEMENS, 200A

MAINS PANELBOARD.

7. EXISTING PANEL EQDP2C IS

WESTINGHOUSE, 480Y/277V, 225A MAIN

BREAKER, 22KAIC PANELBOARD.

8. PROVIDE 20A/1P BREAKER IN AVAILABLE

SPACE IN PANEL ELBM. ROUTE 2#12,#

12G;1/2"C.

9. EXISTING PANEL NL1F1 IS A WESTINGHOUSE

PRL1, 208Y/120V, 150A MAIN BREAKER

PANELBOARD.

10. EXISTING PANEL NH1F IS A WESTINGHOUSE

PRL1, 480Y/277V, 225A MAIN BREAKER

PANELBOARD.

11. PROVIDE RECEPTACLE UNDER SINK FOR

AUTOMATIC FAUCET.

QH

BM

QL

BM

EL

BM

EH

BM

2W-B00A

A

WH-1 WH-2RP-3RP-1

RP-4RP-2

MECHANICAL

F

18 J

WH-3 WH-4RP-7RP-5

RP-8RP-6

2W-B02

A

J J

E.01

BLDG

2W BLDG 2C

BLDG 2E

BLDG 1BLDG 3

BLDG

BLDG 34

BLDG 33

BL

DG

2 KEY PLAN

NTS

ADDITION

BASEMENT ELEC RM

BLDG

BASEMEN

T MECH

RM

BASEMEN

T MECH

RM

th re e inc he s = o ne fo ot

6" on e an d on e ha lf i nc he s = o ne fo ot

6" on e inc h on e fo ot th re e qu ar te rs in ch o ne fo ot on e ha lf i nc h on e fo ot th re e eig ht hs in ch o ne fo ot on e qu ar te r i nc h on e fo ot on e eig ht h inc h on e fo ot

6"

6"

VA FORM 08-6231

Revisions:

1 2 3 4 5 6 7 8 9

Date:

Drawing Title:

Approved Project Director:

Project Title:

Location:

Date: Checked: Drawn:

Drawing Number:

Building Numbers:

Project Number:

Dwg. of

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

A R C H I T E C T S , I N C .A R C H I T E C T S , I N C .A R C H I T E C T S , I N C .A R C H I T E C T S , I N C .

TOLAND MIZELL

FINAL SUBMITTAL

FIRST FLOOR POWER PLANS

BUILDINGS 2W & 2C

EXPAND PRIMARY CARE -

NEWINGTON VAMC

NEWINGTON, CT

EP101

689-402

JUNE 7, 2019 RGB PEW 113

Approver

1/8" = 1'-0"

2W/2C - FIRST FLOOR - POWER

1/8" = 1'-0"

2W - BASEMENT ELEC RM - POWER

1/8" = 1'-0"

2C - BASEMENT MECHANICAL RM - ENLARGEMENT

1/8" = 1'-0"

2W - BASEMENT MECHANICAL RM - ENLARGEMENT

12 PROVIDE MOTOR RATED SWITCH IN NEMA 1

ENCLOSURE ABOVE CEILING FOR

TERMINAL UNIT.

13 PROVIDE ELECTRICAL INTERCONNECTION

BETWEEN THIS UNIT AND ROOF-TOP

OUTDOOR UNIT PER MANUFACTURER'S

RECOMMENDATON. PROVIDE NEC

COMPLIANT CIRCUIT IN RACEWAY FOR

INTERCONNECTION.

14 DEDICATED RECEPTACLE FOR RP-2 AND

RP-4. COORDINATE EXACT MOUNTING

LOCATION PRIOR TO ROUGH-IN.

15 POWER CONNECTION TO WATER HEATER

POWER BURNER. COORDINATE EXACT

LOCATION AND CONNECTION PRIOR TO

ROUGH-IN.

16 ROUTE 2#12, #12G IN 3/4"C AND MAKE ALL

CONNECTIONS TO EXISTING 120V/20AMP

CONVENIENCE RECEPTACLE CIRCUIT IN

THIS SPACE.

17 DEDICATED RECEPTACLE FOR RP-5 AND

RP-7. COORDINATE EXACT MOUNTING

LOCATION PRIOR TO ROUGH-IN.

18 ROUTE 2#12, #12G IN 3/4"C TO EXISTING

ELECTRICAL PANEL "EHBM" IN BASEMENT.

PROVIDE 20A/1P BREAKER IN SPACE

AVAILABLE AND MAKE ALL CONNECTIONS.

ASSUME 75' CIRCUIT LENGTH.

19 DEDICATED RECEPTACLE FOR RP-6 AND

RP-8. COORDINATE EXACT MOUNTING

LOCATION PRIOR TO ROUGH-IN.

20 DEDICATED RECEPTACLE FOR RP-1 AND

RP-3. COORDINATE EXACT MOUNTING

LOCATION PRIOR TO ROUGH-IN.

21 ABANDONED UNDERGROUND ELECTRICAL

LINE SHALL BE DEMOLISHED TO EXTENTS

OF PROJECT AREA. CONTRACTOR SHALL

VERIFY ELECTRICAL LINE IS ABANDONED

PRIOR TO BEGINNING WORK.

E M

E M

E M

E M

E M

E M

E M E M E M

E M

E

E

E M E M

E M

E M

E M

E M

E M

E M E M

E M

E M

E M

E M

E M

NLBA2

NLBA1

NLBA3

EH

BA

CL

BA

CHBA

NHBA

NL

BA

T-

NL

BA

4 1314NLBA4 - 1

NLBA4 - 3

NLBA4 - 4

NLBA4 - 5

NLBA4 - 6

NLBA4 - 7

NLBA4 - 8 NLBA4 - 9

NLBA4 - 10

NLBA4 - 11

NLBA4 - 12

NLBA4 - 13

NLBA4 - 14

NLBA4 - 15

NLBA4 - 16

NLBA4 - 17

NLBA4 - 18

NLBA4 - 19

NLBA4 - 20

NLBA4 - 21

NLBA4 - 24 NLBA4 - 25

NLBA4 - 26

NLBA4 - 27 NLBA4 - 28

NLBA4 - 31

NLBA4 - 32

NLBA4 - 34

NLBA4 - 35

NLBA4 - 36

NLBA4 - 2

NLBA4 - 37

NLBA4 - 40

NLBA4 - 41

NLBA4 - 42

2E1-03

2E1-022E1-04

2E1-01

2E1-01

2E2-03

2E2-07

2E2-06

2E2-08

2E2-05

2E2-04

2E2-02

NLBA4 - 38

NLBA4 - 30

NLBA4 - 23

NLBA4 - 22

NLBA4 - 29

NLBA4 - 33

2E-B140C

2E-B127B 2E-B127C

2E-B127E

2E-B462E-B127D

2E-B127A

CB-13

2E-B140A

2E-B140F 2E-B140G2E-B140E

2E-B140D

2E-B140B

CB-11

2E-B140H

2E-B137A

2E-B137B

2E-B137C

2E-B135A 2E-B137

2E-B042

2E-B139

2E-B140H

2E-B133

NLBA4 - 39

80" FOR TV

6110-0278

EM6

6110-0279

HP-1

AHU-1

3-201

42-210

42-228

C2-1

42-227

42-212

C2-2

42-A

42-A - 2 42-A - 3

42-A - 4

42-A - 6

42-A - 8

42-A - 9

42-A - 19

42-A - 13

42-A - 10

42-A - 12

B42-8B42-1

B42-2

B42-3

B42-4

B42-9

B42-5

B42-7

B42-6

42-A - 15,17

42-A - 16

42-A - 1

42-A - 11

42-A - 7

42-A - 14

42-A - 18

42-219

42-213

42-209

42-218

42-21742-216

42-207

42-215

42-211

42-203

42-201 42-201A42-20442-204

42-206

ROOF

ROOF

42-A - 21

42-A - 5

POWER KEY NOTES

(THIS SHEET ONLY)

1. ROUTE 4#4/0,#4G;2-1/2"C.

2. ROUTE 3#2,#6G;1-1/4"C.

3. SEE BUILDING 2E PARTIAL RISER DIAGRAM

THIS SHEET.

4. CONNECT TO EXISTING RECEPTACLE

CIRCUIT IN THIS SPACE.

5. EXISTING PANEL NHBA IS A WESTINGHOUSE,

480Y/208V, 225A MAIN LUGS ONLY, 14KAIC

PANELBOARD.

6. EXISTING PANEL NLBA2 IS A

WESTINGHOUSE, 208Y/120V, 150A MAIN

BREAKER PANELBOARD.

7. EXISTING PANEL NLBA1 IS A WESTINGHOUSE

208Y/120V, 150A MAIN BREAKER

PANELBOARD.

8. EXISTING PANEL NLBA3 IS A SQUARE D,

208Y/120V, 100A MAIN LUGS ONLY

PANELBOARD.

9. EXISTING PANEL EHBA IS A WESTINGHOUSE,

480Y/277V, 100A MAIN LUGS ONLY, 14KAIC

PANELBOARD.

10. EXISTING PANEL CLBA IS A WESTINGHOUSE,

208Y/120V, 60A MAIN BREAKER, 10KAIC

PANELBOARD.

11. EXISTING PANEL CHBA IS A WESTINGHOUSE,

480Y/277V, 125A MAIN LUGS ONLY, 14KAIC

PANELBOARD.

12. 480V PANEL ON THIS WALL ON FIRST FLOOR,

ROOM 2E-173. PROVIDE 110A/3P BREAKER

FOR NEW TRANSFORMER T-NLBA4. SEE

NOTE 14.

13. PROVIDE 225A, 208Y/120V MCB PANELBOARD

HAVING MINIMUM 10,000 AMP WITHSTAND

CAPACITY.

14. PROVIDE 75KVA, 480-208Y/120V DRY TYPE

TRANSFORMER FED FROM PANEL NH1A ON

FLOOR ABOVE. SEE NOTE 12.

15. PROVIDE 110A/3P BREAKER TO FEED NEW

75KVA TRANSFORMER. SEE NOTE 14.

16. PROVIDE MOTOR RATED SWITCH IN NEMA 1

ENCLOSURE ABOVE-CEILING FOR TERMINAL

UNIT.

17. PROVIDE 60A/3P FUSED DISCONNECT IN

NEMA 3R ENCLOSURE. PROVIDE 40A/2P

CIRCUIT BREAKER IN EXISTING PANEL 6110-

0279 MATCHING EXISTING BREAKERS IN

TYPE AND AIC RATING. ROUTE 2#8,#

10G;3/4"C.

18. PROVIDE 60A/3P FUSED DISCONNECT IN

NEMA 1 ENCLOSURE. PROVIDE 50A/2P

CIRCUIT BREAKER IN EXISTING PANEL 6110-

0279 MATCHING EXISTING BREAKERS IN

TYPE AND AIC RATING. ROUTE 2#6,#

10G;3/4"C.

19. DISCONNECT ALL CIRCUITS AND CONDUITS

FROM THIS PANEL. MAKE DISCONNECTED

CIRCUITS-TO-REMAIN SAFE FOR

RECONNECTION TO NEW PANEL. MAKE TO-

REMAIN-CONDUITS SAFE FOR

RECONNECTION TO NEW PANEL. PROVIDE

NEW PANEL PER PANEL SCHEDULE "42A" ON

SHEET EP601.

NL4Q

EL4Q

NL4Q - 37

NL4Q - 38

NL4Q - 40

NL4Q - 39

1A42-01

1A42-02 1A42-05

1A42-03

1A42-04

NL4Q - 33

NL4Q - 30,32

1-445A

1-445

1-434 1-434C

1-434B

1-434A

1-434D

Unoccupied

NL4Q - 34

NL4Q - 36

NL4Q - 28

NL4Q - 35

NL4Q - 42

NL4Q - 31

RM 2E-1166

NH1A

NLBA4

FIRST FLOOR

BASEMENT

BASEMENT

MECH RM.

T-NLBA4

BLDG

2W

BUILDING 2C

BUILDING 2E

BL

DG

1BUILDING 3

BLDG

BLDG 34

BLDG 33

BL

DG

2 KEY PLAN

NTS

ADDITION

2E BASEMENT

BLDG

th re e inc he s = o ne fo ot

6" on e an d on e ha lf i nc he s = o ne fo ot

6" on e inc h on e fo ot th re e qu ar te rs in ch o ne fo ot on e ha lf i nc h on e fo ot th re e eig ht hs in ch o ne fo ot on e qu ar te r i nc h on e fo ot on e eig ht h inc h on e fo ot

6"

6"

VA FORM 08-6231

Revisions:

1 2 3 4 5 6 7 8 9

Date:

Drawing Title:

Approved Project Director:

Project Title:

Location:

Date: Checked: Drawn:

Drawing Number:

Building Numbers:

Project Number:

Dwg. of

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

A R C H I T E C T S , I N C .A R C H I T E C T S , I N C .A R C H I T E C T S , I N C .A R C H I T E C T S , I N C .

TOLAND MIZELL

FINAL SUBMITTAL

POWER PLANS BUILDINGS 2E, 3, &

EXPAND PRIMARY CARE -

NEWINGTON VAMC

NEWINGTON, CT

EP102

689-402

JUNE 7, 2019 RGB HVB 113

Approver

1/8" = 1'-0"

2E - BASEMENT - POWER

1/8" = 1'-0"

3 - SECOND FLOOR - POWER

1/8" = 1'-0"

42 - SECOND FLOOR - POWER

1/8" = 1'-0"

1 - FOURTH FLOOR - POWER

NO SCALE

2E - PARTIAL RISER DIAGRAM

EF-4

RTU-42-SF

VFDE

VFDE

E M

RTU-42-RF

7PNL 42A

42A-37,39,41

42A-38,40,42

E

E

E

E

EF-3

E M

XF

M R X M R2 W

M R2 W

A B C D E F

MR2W-1,3

MR2W-2,4

MR2W-5,7

MR2W - 6,8

MR2W - 9,11,13

MR2W-10,12

E M

EF-1

CU-1

CU-2

CU-3

EF-2

SWBD 2W

PROVIDE MINIMUM OF 2

STAINLESS STEEL CHANNEL

SUPPORT COLUMNS

TYPICAL ELECTRICAL PANEL /

DISCONNECT. BOLT-FASTEN

PANEL / DISCONNECT TO

CROSS SUPPORT CHANNELS.

PROVIDE MINIMUM OF 2 STAINLESS

STEEL CHANNEL COLUMN CROSS

SUPPORTS

PROVIDE MINIMUM 2 CHANNEL

BASES THAT SECURELY

SUPPORT COLUMNS

CHANNEL BASE TO BE SECURELY

FASTENED TO ROOF STRUCTURAL

MEMBER OR CONCRETE SLAB

(TYPICAL)

WELD OR BOLT-FASTEN

CHANNEL CROSS SUPPORTS

WELD- OR BOLT-

FASTEN CHANNEL

SUPPORTS

PANEL MR2W SCHEDULE

100 AMP BUS 100 AMP MCB 208Y/120 VOLTS 3PH, 4W, SN, 60HZ MIN. 10 KAIC SURFACE NEMA 3R

CKT

NO.

LOAD DESCRIPTION

COND

SIZE AWIRE

SIZE

BKR

TRIP AMPS B C A B C COND

SIZE

WIRE

SIZE

BKR

TRIP

AMPS LOAD DESCRIPTION

CKT

NO.

EF-1 CU-1 2

3/4 12

2.6

9.8

9.0

9.0

9.0

9.0

9.0

1.0

2.6

9.8

9.0

9.0

9.0

9.0

9.0 9.0

1.0

A: 26.1 B: 18.7 C:15.7 TOTAL AMPS:

NOTES:

EF-2

CU-2

CU-1

CU-3

EF-3

SPARE

BUSSED SPACE

BUSSED SPACE

BUSSED SPACE

LOAD CLASSIFICATION

MECHANICAL

CONNECTED LOAD

7.3 KVA

DEMAND

FACTOR

120%

ESTIMATED

DEMAND

8.7 KVA

PANEL TOTALS

TOTAL CONN. LOAD:

TOTAL EST. DEMAND:

TOTAL CONN:

TOTAL EST. DEMAND: 24.1 A

20.1 A

8.7 KVA

7.3 KVA

BUSSED SPACE

BUSSED SPACE

BUSSED SPACE

BUSSED SPACE

BUSSED SPACE

3/4 3/4

9.0

3/4

3/4

15 12 3/4

SWBD

2W

XFMR

XMR2W

PNL

MR2W

ROOF-TOP

SECOND

FLOOR

MECH / ELEC ROOM 42-219

BUILDING 42

3#10,#10G;3/4"C

3#10,#10G;3/4"C

30A/3P

BLDG

2W

ROOF BLDG 2C ROOF

BLDG 2E

BLDG 1BLDG 3

BLDG

42 ROOF

BLDG 34

BLDG 33

BL

DG

2 KEY PLAN

NTS

ADDITION

BLDG

th re e inc he s = o ne fo ot

6" on e an d on e ha lf i nc he s = o ne fo ot

6" on e inc h on e fo ot th re e qu ar te rs in ch o ne fo ot on e ha lf i nc h on e fo ot th re e eig ht hs in ch o ne fo ot on e qu ar te r i nc h on e fo ot on e eig ht h inc h on e fo ot

6"

6"

VA FORM 08-6231

Revisions:

1 2 3 4 5 6 7 8 9

Date:

Drawing Title:

Approved Project Director:

Project Title:

Location:

Date: Checked: Drawn:

Drawing Number:

Building Numbers:

Project Number:

Dwg. of

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

A R C H I T E C T S , I N C .A R C H I T E C T S , I N C .A R C H I T E C T S , I N C .A R C H I T E C T S , I N C .

TOLAND MIZELL

FINAL SUBMITTAL

POWER PLANS ROOF OF

BUILDINGS 2W, 2C, & 42

EXPAND PRIMARY CARE -

NEWINGTON VAMC

NEWINGTON, CT

EP103

689-402

JUNE 7, 2019 RGB HVB 113

JC

1/8" = 1'-0"4 42 - ROOF-TOP - POWER

POWER KEY NOTES

(THIS SHEET ONLY)

1 PROVIDE COMBINATION 30A DISCONNECT /

SIZE 0 MOTOR STARTER IN NEMA 3R

ENCLOSURE.

2 PROVIDE 30A DISCONNECT IN 3R

ENCLOSURE.

3 PROVIDE MOTOR RATED SWITCH IN NEMA 3R

ENCLOSURE.

4 PROVIDE SINGLE POINT CONNECTIONS TO

VFD/DISCONNECTS IN ELECTRICAL CABINETS

OF SUPPLY AND RETURN FAN SECTIONS OF

AHU. VFD/DISCONNECTS ARE INTEGRAL TO

UNIT.

5 PROVIDE 30KVA 480V-208Y/120V

TRANSFORMER IN VENTILATED NEMA 3R

ENCLOSURE. PROVIDE 3#8, #10G; 3/4"C FROM

THIS TRANSFORMER TO SWITCHBOARD 2W IN

BUILDING 2W. PROVIDE NEW 40A/3P

BREAKER AT 480V SWITCHBOARD IN VACANT

SPACE AND PERMANENTLY LABEL "XFMR

XMR2W ROOF-TOP BLDG 42".SEE PARTIAL

RISER DETAL 3 ON THIS SHEET.

6 PROVIDE CONNECTION TO RTU-42-SF

VFD/DISCONNECT. PROVIDE 3#10,#10G; 3/4"C

TO NEW PANEL "42A" (LOCATED IN SECOND

FLOOR ROOM 42-219). PROVIDE NEW 30A/3P

COMPATIBLE BREAKER IN SPACE # (SEE

PANEL SCHEDULE 42-A ON SHEET EP601).

7 PROVIDE CIRCUIT AND CONNECTION TO

PANEL42A IN ELECTRICAL ROOM ON SECOND

FLOOR OF BUILDING 42, SEE SHEET EP102.

PROVIDE NEW 15A/2P BREAKER IN 208V

PANEL. PROVIDE 2#12, #12G; 1/2"C.

8 PROVIDE NEW PANEL "MR2W" PER PANEL

"MR2W" SCHEDULE ON THIS SHEET. PROVIDE

SUPPORT FOR PANEL PER DETAIL 2 ON THIS

SHEET. PROVIDE 3-#1, #8G; 1-1/4"C TO

SECONDARY OUTPUT OF TRANSFORMER

"XMR2W". SEE PARTIAL RISER DETAL 3 ON

THIS SHEET.

9 PROVIDE CONNECTION TO RTU-42-RF

VFD/DISCONNECT. PROVIDE 3#10,#10G; 3/4"C

TO NEW PANEL "42A" (LOCATED IN SECOND

FLOOR ROOM 42-219). PROVIDE NEW 30A/3P

COMPATIBLE BREAKER IN SPACE # (SEE

PANEL SCHEDULE 42-A ON SHEET EP601).

1/8" = 1'-0"1 2W /2C - ROOF-TOP - POWER PLAN

NO SCALE2

ROOF-TOP PANEL /

DISCONNECT MOUNTING DETAIL

NO SCALE3 42 - ROOF-TOP CONNECTIONS PARTIAL RISER

EXISTING PANEL EHBA SCHEDULE

CKT.

NO.

TOTAL AMPS (CONN. LOAD)

TOTAL AMPS (FEEDTHRU)

TOTAL AMPS (CONN. LOAD + FEED-THRU)

PANELBOARD OPTIONS:

LOAD DESCRIPTION

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING SPARE

EXISTING SPARE

LIGHTING

SPARE

SPARE

SPARE

COND

SIZE

EX

EX

EX

1/2

WIRE

SIZE

EX

EX

EX

BKR

TRIP

A:

A:

A:

AMPS

5.0 5.0 5.0

3.0

5.0

5.0

KVA

1.4 1.4 1.4

0.8

100 AMP BUS 100 AMP MCB 480Y/277 VOLTS 3PH, 4W, SN MIN. 10 KAIC SURFACE MOUNTED

PH

A

B C

A B

C A

B C

B:

B:

B:

PANELBOARD NOTES:

KVA

1.4 1.4

10.0

10.0

AMPS

5.0 5.0

BKR

TRIP

C:

C:

C:

WIRE

SIZE

EX

EX

13.0

13.0

COND

SIZE

EX

EX

LOAD DESCRIPTION

EXISTING SPARE

EXISTING LOAD

EXISTING LOAD

EXISTING SPARE

EXISTING SPARE

EXISTING SPARE

EXISTING SPARE

EXISTING SPARE

EXISTING SPARE

CKT.

NO.

EXISTING PANEL EHBM SCHEDULE

CKT.

NO.

TOTAL AMPS (CONN. LOAD)

TOTAL AMPS (FEEDTHRU)

TOTAL AMPS (CONN. LOAD + FEED-THRU)

PANELBOARD OPTIONS:

LOAD DESCRIPTION

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

LIGHTING

LIGHTING

LIGHTING

SPARE

SPARE

SPARE

COND

SIZE

EX

EX

EX

EX

EX

EX

1/2 1/2 1/2

WIRE

SIZE

EX

EX

EX

EX

EX

EX

BKR

TRIP

A:

A:

A:

AMPS

5.0 5.0 5.0 5.0 5.0 5.0 1.0 1.0 1.0

20.9

20.9

KVA

1.4 1.4 1.4 1.4 1.4 1.4 0.3 0.3 0.3

100 AMP BUS 100 AMP MCB 480Y/277 VOLTS 3PH, 4W, SN MIN. 10 KAIC SURFACE MOUNTED

PH

A

B C

A B

C A

B C

A B

C B:

B:

B:

PANELBOARD NOTES:

KVA

1.4 1.4 1.4 1.4 0.3 0.3

17.0

17.0

AMPS

5.0 5.0 5.0 5.0 1.0 1.0

BKR

TRIP

EX

C:

C:

C:

WIRE

SIZE

EX

EX

EX

EX

17.0

17.0

COND

SIZE

EX

EX

EX

EX

1/2 1/2

LOAD DESCRIPTION

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

LIGHTING

LIGHTING

SPARE

SPARE

SPARE

MAIN

CKT.

NO.

EXISTING PANEL ELBM SCHEDULE

CKT.

NO.

TOTAL AMPS (CONN. LOAD)

TOTAL AMPS (FEEDTHRU)

TOTAL AMPS (CONN. LOAD + FEED-THRU)

PANELBOARD OPTIONS:

LOAD DESCRIPTION

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING SPARE

EXISTING SPARE

EXISTING SPARE

RECEPTACLE

RECEPTACLE

RECEPTACLE

SPARE

SPARE

COND

SIZE

EX

EX

EX

EX

1/2 1/2 1/2

WIRE

SIZE

EX

EX

EX

EX

BKR

TRIP

A:

A:

A:

AMPS

5.0 5.0 5.0 5.0

3.0 6.0 6.0

26.0

26.0

KVA

0.6 0.6 0.6 0.6

0.4 0.7 0.7

100 AMP BUS 100 AMP MCB 208Y/120 VOLTS 3PH, 4W, SN MIN. 10 KAIC SURFACE MOUNTED

PH

A

B C

A B

C A

B C

A B

C B:

B:

B:

PANELBOARD NOTES:

KVA

0.6 0.6 0.6 0.6 0.7 0.7

19.0

19.0

AMPS

5.0 5.0 5.0 5.0 6.0 6.0

BKR

TRIP

EX

C:

C:

C:

WIRE

SIZE

EX

EX

EX

EX

22.0

22.0

COND

SIZE

EX

EX

EX

EX

1/2 1/2

LOAD DESCRIPTION

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

RECEPTACLE

RECEPTACLE

SPARE

SPARE

SPARE

MAIN

CKT.

NO.

EXISTING PANEL LSDP2C SCHEDULE

CKT.

NO.

TOTAL AMPS (CONN. LOAD)

TOTAL AMPS (FEEDTHRU)

TOTAL AMPS (CONN. LOAD + FEED-THRU)

PANELBOARD OPTIONS:

LOAD DESCRIPTION

EXISTING LOAD

EXISTING LOAD

LIGHTING

LIGHTING

LIGHTING

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

COND

SIZE

EX

EX

1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2

WIRE

SIZE

EX

EX

BKR

TRIP

A:

A:

A:

AMPS

22.0 22.0 22.0 34.0 34.0 34.0 1.0 1.0 1.0

67.0

67.0

KVA

6.1 6.1 6.1 9.4 9.4 9.4 0.3 0.3 0.3

100 AMP BUS 100 AMP MCB 480Y/277 VOLTS 3PH, 4W, SN MIN. 10 KAIC SURFACE MOUNTED

PH

A

B C

A B

C A

B C

A B

C A

B C

A B

C A

B C

A B

C B:

B:

B:

PANELBOARD NOTES:

KVA

1.4 1.4 1.4

1.4 1.4 1.4

67.0

67.0

AMPS

5.0 5.0 5.0

5.0 5.0 5.0

BKR

TRIP

C:

C:

C:

WIRE

SIZE

EX

EX

EX

67.0

67.0

COND

SIZE

EX

EX

EX

LOAD DESCRIPTION

EXISTING LOAD

EXISTING SPARE

EXISTING SPARE

EXISTING SPARE

EXISTING SPARE

EXISTING SPARE

EXISTING SPARE

EXISTING SPARE

EXISTING SPARE

EXISTING SPARE

EXISTING SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

EXISTING LOAD

MAIN

CKT.

NO.

EXISTING PANEL NH1F SCHEDULE

CKT.

NO.

TOTAL AMPS (CONN. LOAD)

TOTAL AMPS (FEEDTHRU)

TOTAL AMPS (CONN. LOAD + FEED-THRU)

PANELBOARD OPTIONS:

LOAD DESCRIPTION

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING SPARE

EXISTING SPARE

EXISTING SPARE

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

LIGHTING

LIGHTING

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

COND

SIZE

EX

EX

EX

EX

EX

EX

EX

EX

1/2 1/2

WIRE

SIZE

EX

EX

EX

EX

EX

EX

EX

EX

BKR

TRIP

EX

EX

EX

EX

EX

EX

EX

EX

A:

A:

A:

AMPS

5.0 5.0 5.0 5.0 5.0

5.0 5.0 5.0 3.0 2.0

41.8

41.8

KVA

1.4 1.4 1.4 1.4 1.4

1.4 1.4 1.4 0.8 0.6

225 AMP BUS 225 AMP MCB 480Y/277 VOLTS 3PH, 4W, SN MIN. 10 KAIC SURFACE MOUNTED

PH

A

B C

A B

C A

B C

A B

C A

B C

A B

C A

B C

B:

B:

B:

PANELBOARD NOTES:

KVA

1.4 1.4 1.4 1.4 1.4

1.4 1.4 1.4 0.6

1.4 1.4 1.4 1.4 1.4 1.4 41.8

41.8

AMPS

5.0 5.0 5.0 5.0 5.0

5.0 5.0 5.0 2.0

5.0 5.0 5.0 5.0 5.0 5.0

BKR

TRIP

EX

EX

EX

EX

EX

EX

EX

EX

C:

C:

C:

WIRE

SIZE

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

32.9

32.9

COND

SIZE

EX

EX

EX

EX

EX

EX

EX

EX

1/2

EX

EX

LOAD DESCRIPTION

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING SPARE

EXISTING SPARE

EXISTING LOAD

EXISTING SPARE

EXISTING SPARE

LIGHTING

SPARE

SPARE

SPARE

SPARE

EXISTING LOAD

EXISTING LOAD

CKT.

NO.

EXISTING PANEL NH1M SCHEDULE

CKT.

NO.

TOTAL AMPS (CONN. LOAD)

TOTAL AMPS (FEEDTHRU)

TOTAL AMPS (CONN. LOAD + FEED-THRU)

PANELBOARD OPTIONS:

LOAD DESCRIPTION

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

LIGHTING

LIGHTING

LIGHTING

LIGHTING

EXISTING SPARE

EXISTING SPARE

SPARE

COND

SIZE

EX

EX

EX

EX

1/2 1/2 1/2 1/2

WIRE

SIZE

EX

EX

EX

EX

BKR

TRIP

A:

A:

A:

AMPS

5.0 5.0 5.0 5.0 1.0 1.0 1.0 2.0

17.0

17.0

KVA

1.4 1.4 1.4 1.4 0.3 0.3 0.3 0.6

150 AMP BUS 150 AMP MLO 480Y/277 VOLTS 3PH, 4W, SN MIN. 10 KAIC SURFACE MOUNTED

PH

A

B C

A B

C A

B C

A B B:

B:

B:

PANELBOARD NOTES:

KVA

1.4 1.4 1.4 0.3 0.3 0.6

14.0

14.0

AMPS

5.0 5.0 5.0 1.0 1.0 2.0

BKR

TRIP

C:

C:

C:

WIRE

SIZE

EX

EX

EX

13.0

13.0

COND

SIZE

EX

EX

EX

1/2 1/2 1/2

LOAD DESCRIPTION

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

LIGHTING

LIGHTING

LIGHTING

EXISTING SPARE

EXISTING SPARE

MAIN

CKT.

NO.

EXISTING PANEL NHBA SCHEDULE

CKT.

NO.

TOTAL AMPS (CONN. LOAD)

TOTAL AMPS (FEEDTHRU)

TOTAL AMPS (CONN. LOAD + FEED-THRU)

PANELBOARD OPTIONS:

LOAD DESCRIPTION

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING SPARE

EXISTING SPARE

LIGHTING

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

COND

SIZE

EX

EX

EX

EX

EX

EX

1/2

WIRE

SIZE

EX

EX

EX

EX

EX

EX

BKR

TRIP

A:

A:

A:

AMPS

5.0 5.0 5.0 5.0 5.0 5.0

2.0

19.9

19.9

KVA

1.4 1.4 1.4 1.4 1.4 1.4

0.6

100 AMP BUS 100 AMP MCB 480Y/277 VOLTS 3PH, 4W, SN MIN. 10 KAIC SURFACE MOUNTED

PH

A

B C

A B

C A

B C

A B

C A

B C

B:

B:

B:

PANELBOARD NOTES:

KVA

1.4 1.4 1.4 1.4 1.4

0.6

19.9

19.9

AMPS

5.0 5.0 5.0 5.0 5.0

2.0

BKR

TRIP

C:

C:

C:

WIRE

SIZE

EX

EX

EX

EX

EX

18.9

18.9

COND

SIZE

EX

EX

EX

EX

EX

1/2

LOAD DESCRIPTION

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING SPARE

EXISTING SPARE

EXISTING SPARE

LIGHTING

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

CKT.

NO.

EXISTING PANEL NL1F2 SCHEDULE

CKT.

NO.

TOTAL AMPS (CONN. LOAD)

TOTAL AMPS (FEEDTHRU)

TOTAL AMPS (CONN. LOAD + FEED-THRU)

PANELBOARD OPTIONS:

LOAD DESCRIPTION

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

COND

SIZE

1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2

EX

EX

EX

WIRE

SIZE

EX

EX

EX

BKR

TRIP

A:

A:

A:

AMPS

9.0 9.0 11.0 11.0 11.0 11.0 8.0 11.0 9.0 8.0 9.0 9.0 6.0 9.0 6.0 9.0 11.0 6.0 5.0 5.0 5.0 116.0

116.0

KVA

1.1 1.1 1.3 1.3 1.3 1.3 1.0 1.3 1.1 1.0 1.1 1.1 0.7 1.1 0.7 1.1 1.3 0.7 0.6 0.6 0.6

150 AMP BUS 150 AMP MCB 208Y/120 VOLTS 3PH, 4W, SN MIN. 10 KAIC FLUSH MOUNTED

PH

A

B C

A B

C A

B C

A B

C A

B C

A B

C A

B C

B:

B:

B:

PANELBOARD NOTES:

KVA

1.1 1.1 1.3 1.3 1.3 1.3 1.3 1.0 1.3 1.1 1.1 1.1 0.7 1.1 1.0 1.1 0.4 0.4 0.6 0.6 0.6 119.0

119.0

AMPS

9.0 9.0 11.0 11.0 11.0 11.0 11.0 8.0 11.0 9.0 9.0 9.0 6.0 9.0 8.0 9.0 3.0 3.0 5.0 5.0 5.0

BKR

TRIP

C:

C:

C:

WIRE

SIZE

EX

EX

EX

115.0

115.0

COND

SIZE

1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2

EX

EX

EX

LOAD DESCRIPTION

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

CKT.

NO.

EXISTING PANEL NL1M SCHEDULE

CKT.

NO.

TOTAL AMPS (CONN. LOAD)

TOTAL AMPS (FEEDTHRU)

TOTAL AMPS (CONN. LOAD + FEED-THRU)

PANELBOARD OPTIONS:

LOAD DESCRIPTION

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

SPARE

COND

SIZE

1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2

WIRE

SIZE

BKR

TRIP

A:

A:

A:

AMPS

9.0 9.0 9.0 12.0 9.0 9.0 9.0 9.0 15.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 3.0 3.0

109.0

109.0

KVA

1.1 1.1 1.1 1.4 1.1 1.1 1.1 1.1 1.8 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 0.4 0.4

150 AMP BUS 150 AMP MCB 208Y/120 VOLTS 3PH, 4W, SN MIN. 10 KAIC SURFACE MOUNTED

PH

A

B C

A B

C A

B C

A B

C A

B C

A B

C A

B C

B:

B:

B:

PANELBOARD NOTES:

KVA

1.1 1.3 1.1 1.1 1.1 1.1 1.1 1.1 1.1 0.2 1.1 1.1 1.1 1.1 1.1 1.1 1.4 1.3 0.2 1.0 1.0 124.7

124.7

AMPS

9.0 11.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 2.0 9.0 9.0 9.0 9.0 9.0 9.0 12.0 11.0 2.0 10.0 10.0

BKR

TRIP

C:

C:

C:

WIRE

SIZE

124.7

124.7

COND

SIZE

1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2

LOAD DESCRIPTION

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

HVAC

CKT.

NO.

EXISTING PANEL NL4Q SCHEDULE

CKT.

NO.

TOTAL AMPS (CONN. LOAD)

TOTAL AMPS (FEEDTHRU)

TOTAL AMPS (CONN. LOAD + FEED-THRU)

PANELBOARD OPTIONS:

LOAD DESCRIPTION

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

LIGHTING

COND

SIZE

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

1/2 1/2 1/2 1/2 1/2 1/2

WIRE

SIZE

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

BKR

TRIP

A:

A:

A:

AMPS

5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 6.0 9.0 6.0 9.0 9.0 3.0 6.0 86.0

86.0

KVA

0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.7 1.1 0.7 1.1 1.1 0.4 0.7

100 AMP BUS 100 AMP MCB 208Y/120 VOLTS 3PH, 4W, SN MIN. 10 KAIC FLUSH MOUNTED

PH

A

B C

A B

C A

B C

A B

C A

B C

A B

C A

B C

B:

B:

B:

PANELBOARD NOTES:

KVA

0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 1.0 1.0 1.1 0.7 1.3 1.1 0.7 0.6 74.7

74.7

AMPS

5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 10.0 10.0 9.0 6.0 11.0 9.0 6.0 5.0

BKR

TRIP

C:

C:

C:

WIRE

SIZE

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

85.7

85.7

COND

SIZE

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

1/2

1/2 1/2 1/2 1/2 1/2 1/2

LOAD DESCRIPTION

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

HVAC

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

CKT.

NO.

EXISTING PANEL NL1F1 SCHEDULE

CKT.

NO.

TOTAL AMPS (CONN. LOAD)

TOTAL AMPS (FEEDTHRU)

TOTAL AMPS (CONN. LOAD + FEED-THRU)

PANELBOARD OPTIONS:

LOAD DESCRIPTION

SPARE

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

COND

SIZE

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

WIRE

SIZE

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

BKR

TRIP

A:

A:

A:

AMPS

5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 65.0

65.0

KVA

0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6

100 AMP BUS 100 AMP MCB 208Y/120 VOLTS 3PH, 4W, SN MIN. 10 KAIC SURFACE MOUNTED

PH

A

B C

A B

C A

B C

A B

C A

B C

A B

C A

B C

B:

B:

B:

PANELBOARD NOTES:

KVA

0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6

0.6 65.0

65.0

AMPS

5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0

5.0

BKR

TRIP

C:

C:

C:

WIRE

SIZE

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

70.0

70.0

COND

SIZE

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

LOAD DESCRIPTION

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

SPARE

EXISTING LOAD

CKT.

NO.

EXISTING PANEL EL4Q SCHEDULE

CKT.

NO.

TOTAL AMPS (CONN. LOAD)

TOTAL AMPS (FEEDTHRU)

TOTAL AMPS (CONN. LOAD + FEED-THRU)

PANELBOARD OPTIONS:

LOAD DESCRIPTION

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

LIGHTING

EXISTING SPARE

EXISTING SPARE

EXISTING SPARE

EXISTING SPARE

COND

SIZE

EX

EX

EX

EX

1/2

WIRE

SIZE

EX

EX

EX

EX

BKR

TRIP

EX

EX

EX

EX

A:

A:

A:

AMPS

5.0 5.0 5.0 5.0 2.0

15.0

15.0

KVA

0.6 0.6 0.6 0.6 0.2

100 AMP BUS 100 AMP MCB 208Y/120 VOLTS 3PH, 4W, SN MIN. 10 KAIC SURFACE MOUNTED

PH

A

B C

A B

C A

B C

B:

B:

B:

PANELBOARD NOTES:

KVA

0.6 0.6

12.0

12.0

AMPS

5.0 5.0

BKR

TRIP

EX

EX

C:

C:

C:

WIRE

SIZE

EX

EX

5.0

5.0

COND

SIZE

EX

EX

LOAD DESCRIPTION

EXISTING LOAD

EXISTING LOAD

EXISTING SPARE

EXISTING SPARE

EXISTING SPARE

EXISTING SPARE

EXISTING SPARE

EXISTING SPARE

EXISTING SPARE

CKT.

NO.

NEW PANEL 42-A SCHEDULE

NEW PANEL NLBA4 SCHEDULE

CKT.

NO.

TOTAL AMPS (CONN. LOAD)

TOTAL AMPS (FEEDTHRU)

TOTAL AMPS (CONN. LOAD + FEED-THRU)

PANELBOARD OPTIONS:

LOAD DESCRIPTION

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

VAV TERMINAL UNITS

EXISTING LOAD

RECEPTACLE

RECEPTACLE

LIGHTING 216,217,218,216,213,211

LIGHTING 201,204,205,206

LIGHTING CORR. 215,207,203, WAIT. 202

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

RTU-BLDG 42-SUPPLY FAN

COND

SIZE

1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2

EX

1/2 1/2 1/2 1/2 1/2

EX

EX

EX

EX

3/4

WIRE

SIZE

EX

EX

EX

EX

EX

BKR

TRIP

A:

A:

A:

AMPS

9.0 9.0 9.0 9.0 9.0 8.0 8.0 9.0 5.0 8.0 5.0 5.3 3.3 3.3 5.0 5.0 5.0 5.0 16.7 16.7 16.7 115.2

115.2

KVA

1.1 1.1 1.1 1.1 1.1 1.0 1.0 0.9 0.6 1.0 0.6 0.6 0.4 0.4 0.6 0.6 0.6 0.6 1.8 1.8 1.8

225 AMP BUS 225 AMP MCB 208Y/120 VOLTS 3PH, 4W, SN MIN. 10 KAIC SURFACE MOUNTED

PH

A

B C

A B

C A

B C

A B

C A

B C

A B

C A

B C

B:

B:

B:

PANELBOARD NOTES:

KVA

1.1 1.1 1.1 1.1 0.4 0.2 1.0 1.1 0.7 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 1.8 1.8 1.8 107.0

107.0

AMPS

9.0 9.0 9.0 9.0 3.0 2.0 8.0 9.0 6.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 16.7 16.7 16.7

BKR

TRIP

C:

C:

C:

WIRE

SIZE

EX

EX

EX

EX

EX

EX

EX

EX

EX

101.2

101.2

COND

SIZE

1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2

EX

EX

EX

EX

EX

EX

EX

EX

EX

3/4

LOAD DESCRIPTION

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

EXISTING LOAD

RTU-BLDG 42-RETURN FAN

CKT.

NO.

CKT.

NO.

TOTAL AMPS (CONN. LOAD)

TOTAL AMPS (FEEDTHRU)

TOTAL AMPS (CONN. LOAD + FEED-THRU)

PANELBOARD OPTIONS:

LOAD DESCRIPTION

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

COND

SIZE

1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2

WIRE

SIZE

BKR

TRIP

A:

A:

A:

AMPS

8.0 8.0 8.0 8.0 6.0 3.0 9.0 6.0 6.0 9.0 9.0 9.0 6.0 9.0 9.0 6.0 9.0 9.0 8.0 9.0 9.0 110.0

110.0

KVA

1.0 1.0 1.0 1.0 0.7 0.4 1.1 0.7 0.7 1.1 1.1 1.1 0.7 1.1 1.1 0.7 1.1 1.1 1.0 1.1 1.1

225 AMP BUS 225 AMP MCB 208Y/120 VOLTS 3PH, 4W, SN MIN. 10 KAIC SURFACE MOUNTED

PH

A

B C

A B

C A

B C

A B

C A

B C

A B

C A

B C

B:

B:

B:

PANELBOARD NOTES:

KVA

1.1 1.1 1.0 1.0 1.1 1.1 1.1 1.1 0.4 1.1 1.1 1.1 0.7 1.1 1.1 0.7 1.1 1.1 1.1 1.1 1.1 119.0

119.0

AMPS

9.0 9.0 8.0 8.0 9.0 9.0 9.0 9.0 3.0 9.0 9.0 9.0 6.0 9.0 9.0 6.0 9.0 9.0 9.0 9.0 9.0

BKR

TRIP

C:

C:

C:

WIRE

SIZE

109.0

109.0

COND

SIZE

1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2

LOAD DESCRIPTION

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

RECEPTACLE

CKT.

NO.

PANELBOARD OPTIONS: COORDINATE WITH BLDG 2E PARTIAL RISER DIAGRAM ON SHEET EP102.

th re e…

This is the start of the file's text. The full file is on GovTribe.