This document provides details for a federal contract opportunity to construct a parking garage at the Oklahoma City VA Medical Center. The solicitation number is 36C77623B0046 and seeks bids for the construction of Parking Garage 2 under opportunity Y1DA--635-414. The Department of Veterans Affairs Technology Acquisition Center in Austin is the contracting agency. The scope of work involves all aspects of new construction for the parking garage, with responses due by the date specified in the full solicitation. Pricing will be fixed-price bids with construction to be completed within the timeframe outlined. This opportunity is set aside for verified service-disabled veteran-owned small businesses.
View the file
Other files
Show all 28
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A/E ARCHITECT / ENGINEER
AAHX AIR TO AIR HEAT EXCHANGER
AB AIR BLENDER
AAV AUTOMATIC AIR VENT
ACC AIR-COOLED CONDENSER
ACCH AIR-COOLED CHILLER
ACCU AIR-COOLED CONDENSING UNIT
ACU AIR CONDITIONING UNIT
ACD AUTOMATIC CONTROL DAMPER,
MODULATING
ACD-TP AUTOMATIC CONTROL DAMPER,TWO
POSITION
AD ACCESS DOOR
AF AFTER FILTER
AFCV AIR FLOW CONTROL VALVE
AFF ABOVE FINISHED FLOOR
AFMD AIR FLOW MEASURING DEVICE
AFW AIR FOIL WHEEL (FAN)
AHU AIR-HANDLING UNIT
AMP AMPERAGE
AP ACCESS PANEL
APD AIR PRESSURE DROP
ARI AIR CONDITIONING AND
REFRIGERATION INSTITUTE
AS AIR SEPARATOR
ASME AMERICAN SOCIETY OF MECHANICAL
ENGINEERS
AW AIR WASHER
AXF AXIAL FLOW
B BOILER
BD BUTTERFLY DAMPER
BDD BACKDRAFT DAMPER
BDR BASE BOARD RADIATOR
BFP BACKFLOW PREVENTER
BFT BOILER PLANT FIRE TUBE
BHP BRAKE HORSEPOWER
BHW HOT WATER HEATING BOILER
BHX BOILER BLOWDOWN HEAT
EXCHANGER
BIW BACKWARD INCLINED WHEEL (FAN)
BSC BIOLOGICAL SAFETY CABINETS
BT BUFFER TANK
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
C CENTIGRADE (CELSIUS)
CC COOLING COIL
CCD COOLING COIL CONDENSATE DRAIN
CENT CENTRIFUGAL
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CFT CUBIC FEET
CFP CHEMICAL FEED PUMP
CH CHILLER
CHWP CHILLED WATER PUMP
CHW CHILLER WATER
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CI CAST IRON
CM CARBON MONOXIDE
CM CUBIC METER
CM/S CUBIC METER PER SECOND
CO CLEAN OUT
CO2 CARBON DIOXIDE
COMP COMPRESSOR UNIT
COP COEFFICIENT OF PERFORMANCE
CP CONDENSATE PUMP
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CV CONSTANT VOLUME
CW COLD WATER (POTABLE)
CHWCC CHILLED WATER COOLING COIL
D DAMPER - AUTOMATIC
D-1 OUTDOOR AIR DAMPER
D-2 RETURN AIR DAMPER
D-3 RELIEF AIR DAMPER
D-4 ECONOMIZER OUTDOOR AIR
DAMPER
dB DECIBELS Db DRY-BULB TEMPERATURE
DDC DIRECT DIGITAL CONTROLS
DEG DEGREE
DF DIFFUSER
DIA DIAMETER
DIW DEIONIZED WATER
DP DEW POINT TEMPERATURE
DP DIFFUSER PLATE
DPA DIFFERENTIAL PRESSURE
ASSEMBLY
DPS DIFFERENTIAL PRESSURE SENSOR
DX DIRECT EXPANSION
DXCC DIRECT EXPANSION COOLING COIL
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
ECC ENGINEERING CONTROL CENTER
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EG EXHAUST GRILLE
EGS EMERGENCY GAS SHUTOFF
EH EXHAUST HOOD
EJ EXPANSION JOINT
EMD END OF MAIN DRIP (STEAM)
ENT ENTERING
ESP EXTERNAL STATIC PRESSURE
EWT ENTERING WATER TEMPERATURE
EX EXISTING
F FAHRENHEIT
F&T FLOAT AND THERMOSTATIC
F/SDPR COMBINATION FIRE SMOKE DAMPER
FA FREE AREA
FC FLEXIBLE CONNECTION
FCU FAN COIL UNIT (4 PIPE)
FCW FORWARD CURVED WHEEL (FAN)
FD FLOOR DRAIN
FD FIRE DAMPER
FF FINAL FILTER
FM FLOW METER
FPM FEET PER MINUTE
FPS FEET PER SECOND
FRP FIBER REINFORCED POLYESTER
FS FLOW SWITCH
FSTAT FREEZESTAT
FT FEET
FT-LB FOOT-POUND
FTR FIN TUBE RADIATION
FV FACE VELOCITY
GA GAUGE
GAL GALLONS
GH GRAVITY HOOD
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GS GALVANIZED STEEL
H HUMIDIFIER
H&CW HOT & COLD WATER
HAC HOUSEKEEPING AID CLOSET
HB HOSE BIBB
HC HEATING COIL
HD HEAD
HD HOOD
HHW HEATING HOT WATER
HHWC HEATING HOT WATER COIL
HHWP HEATING HOT WATER PUMP
HHWR HEATING HOT WATER RETURN
HHWS HEATING HOT WATER SUPPLY
HOA HAND/OFF/AUTOMATIC
HP HEAT PUMP
HP HORSEPOWER
HPDT HIGH PRESSURE DRIP TRAP
HPR HIGH PRESSURE RETURN (STEAM
CONDENSATE)
HPS HIGH PRESSURE SUPPLY (STEAM)
HRC HEAT RECOVERY COIL
HRD HEAT RECOVERY DEVICE
HRP HYDRONIC RADIANT (CEILING) PANEL
HRW HEAT RECOVERY WHEEL
HSTAT HUMIDISTAT
HUM HUMIDIFIER UNIT MOUNTED
HVU HEATING AND VENTILATING UNIT
HW HOT WATER
HWC HOT WATER COIL
HWUH HOT WATER UNIT HEATER
HX HEAT EXCHANGER
Hz HERTZ
I/O INPUT/OUTPUT
IAQ INDOOR AIR QUALITY
IBT INVERTED BUCKET TRAP
ICF IN-LINE CENTRIFUGAL FAN
ICU INTENSIVE CARE UNIT
ID INSIDE DIAMETER
IFB INTEGRAL FACE AND BYPASS
IN INCHES
IN HG INCHES OF MERCURY
IN WC INCH WATER COLUMN
IN WG INCH WATER GAUGE
IN-LB INCH-POUND
IPLV INTEGRATED PART LOAD VALUE
IRH INFRARED HEATER
IS INSECT SCREEN
IV INLET VANES
kg KILOGRAM kg/HR KILOGRAM PER HOUR kPa KILOPASCAL kW KILOWATT kWh KILOWATT HOUR
L LITER
L/s LITERS PER SECOND
LAT LEAVING AIR TEMPERATURE
LBS/HR POUNDS PER HOUR
LF LINEAR FOOT (FEET)
LH LATENT HEAT
LPR LOW PRESSURE RETURN (STEAM
CONDENSATE)
LPS LOW PRESSURE SUPPLY (STEAM)
LSD LINEAR SLOT DIFFUSER
LTCP LOCAL TEMPERATURE CONTROL
PANEL
LVG LEAVING
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
M METER, SI UNIT
M/s METERS PER SECOND (OR
METERS/SECOND)
MA MIXED AIR
MAT MIXED AIR TEMPERATURE
MAV MANUAL AIR VENT
MAX MAXIMUM
MB MIXING BOX
MBH 1000 BTUH
MCA MINIMUM BRANCH CIRCUIT AMPACITY
MER MECHANICAL EQUIPMENT ROOM
MERV MINIMUM EFFICIENCY REPORTING
VALUE
MHP MOTOR HORSEPOWER
MIN MINIMUM
MM MILLIMETER
MOD MOTOR OPERATED CONTROL DAMPER
MOV MOTOR OPERATED VALVE
MPR MEDIUM PRESSURE RETURN (STEAM
CONDENSATE)
MPS MEDIUM PRESSURE SUPPLY (STEAM)
MTD MEAN TEMPERATURE DIFFERENCE
MVD MANUAL VOLUME DAMPER
NA NOT APPLICABLE
NC NOISE CRITERIA
NC NORMALLY CLOSED
NO NORMALLY OPEN
NOAA NATIONAL OCEANIC & ATMOSPHERIC
ADMINISTRATION
NOM NOMINAL
NPLV NON-STANDARD PART LOAD VALUE
NPSH NET POSITIVE SUCTION HEAD
NTS NOT TO SCALE
OA OUTSIDE AIR
OAI OUTSIDE AIR INTAKE
OD OUTSIDE DIAMETER
OR OPERATING ROOM
OSA OUTSIDE SUPPLY AIR
(CONDITIONED)
P PUMP
PC PUMPED CONDENSATE
PCF POUNDS PER CUBIC FOOT (FEET)
PD PRESSURE DROP
PF PRE-FILTER
PG PRESSURE GAGE
PHC PREHEAT COIL
PHCP PREHEAT COIL PUMP
PPM PARTS PER MILLION
PRV PRESSURE REGULATING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH –
ABSOLUTE
PSIG POUNDS PER SQUARE INCH – GAGE
PSS PRIMARY SECONDARY SYSTEM
PSV PRESSURE SAFETY VALVE
R/E RETURN OR EXHAUST
RA RETURN AIR
RAT RETURN AIR TEMPERATURE
RDS ROOM DATA SHEETS
REA RELIEF AIR
RF RETURN FAN
RG RETURN GRILLE
RH RELATIVE HUMIDITY
RHC REHEAT COIL
RL REFRIGERANT LIQUID LINE
RLA RUN LOAD AMPERE
RPM REVOLUTIONS PER MINUTE
RS REFRIGERANT SUCTION
RTU ROOF TOP UNIT
RV RELIEF VALVE
SA SUPPLY AIR
SAD SOUND ATTENUATING DEVICE
SAT SUPPLY AIR TEMPERATURE
SC SHADING COEFFICIENT
SCFM STANDARD CUBIC FEET PER MINUTE
SCR SILICON CONTROLLED RECTIFIER
SD SMOKE DETECTOR
SD SUPPLY AIR DIFFUSER
SDPR SMOKE DAMPER
SDR SMOKE DAMPER (RETURN)
SDS SMOKE DAMPER (SUPPLY)
SEN SENSIBLE HEAT
SF SUPPLY FAN
SH STEAM HUMIDIFIER
SHC STEAM HEATING COIL
SI SQUARE INCHES
SP STATIC PRESSURE
SP GR SPECIFIC GRAVITY
SPD SUPPLY PROCESS AND
DISTRIBUTION
SPRV STEAM PRESSURE REDUCING VALVE
SPS STATIC PRESSURE SENSOR
SQ FT SQUARE FOOT (FEET)
SR SUPPLY AIR REGISTER
SS STAINLESS STEEL
SSR SOLID SEPARATOR
ST STEAM TRAP
SV STEAM SAFETY VALVE
SVS STEAM VENT SILENCER
T & PCV TEMPERATURE AND PRESSURE
CONTROL VALVE
TAB TESTING, ADJUSTING, BALANCE
TD TEMPERATURE DIFFERENCE
TDH TOTAL DYNAMIC HEAD
TDS TOTAL DISSOLVED SOLIDS
TP TRAP
TSP TOTAL STATIC PRESSURE
TSTAT THERMOSTAT
TU TERMINAL UNIT
UC UNDER CUT
UH UNIT HEATER
UL UNDERWRITERS LABORATORY
V VALVE
VAF VANE-AXIAL FAN
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER (MANUAL
OPPOSED BLADE)
VFD VARIABLE FREQUENCY DRIVE
VHA VETERANS HEALTH ADMINISTRATION
VI VIBRATION ISOLATOR
VP VACUUM PUMP
VPS VARIABLE PRIMARY SYSTEM
VR VACUUM (STEAM CONDENSATE)
RETURN
VSD VARIABLE SPEED DRIVE
VUH VERTICAL UNIT HEATER
W WATTS
Wb WET-BULB (TEMPERATURE)
WFCV WATER FLOW CONTROL VALVE
WFM WATER FLOWMETER
WFMD WATER FLOW MEASURING DEVICE
WG WATER GAGE
WPD WATER SIDE PRESSURE DROP
XT EXPANSION TANK
YR YEAR
CO2 CARBON DIOXIDE SENSOR
HUMIDISTAT OR HUMIDITY SENSOR
SUPPLY DIFFUSER
RETURN GRILLE
EXHAUST GRILLE
ROUND FLEX DUCT
EQUIPMENT TAG
LINEAR SLOT DIFFUSER
BALANCING DAMPER
FIRE DAMPER
SMOKE DAMPER
D
R INCLINED RISE, IN
DIRECTION OF AIRFLOW
INCLINED DROP, IN DIRECTION
OF AIRFLOW
CONNECT NEW DUCT
TO EXISTING
LIMIT OF DEMOLITION
VANED ELBOW (PROVIDE ALL
SQUARE OR RECTANGULAR
ELBOWS WITH VANES EVEN IF
SYMBOL IS MISSING)
STANDARD RADIUS ELBOW
(LONG RADIUS)
10x8 NEW DUCT (INSIDE
DIMENSIONS: WIDTH X DEPTH)
EXISTING DUCT TO REMAIN
EXISTING DUCT TO BE
DEMOLISHED
DUCT TRANSITION
END MOUNTED OR SIDEWALL GRILLE
SUPPLY
RETURN45°
45°
DN
DN
UP
UP
DNUP
STANDARD BRANCH SUPPLY OR
RETURN, NO SPLITTER (45° TAP)
SUPPLY DUCT (UP & DOWN)
EXHAUST DUCT (UP & DOWN)
RETURN DUCT (UP & DOWN)
S-60
S-15
CR-15
CHWS
CHWR
HIGH PRESSURE STEAM
PIPING (60 PSI)
LOW PRESSURE STEAM PIPING
(15 PSI AND BELOW)
LOW PRESSURE STEAM
CONDENSATE RETURN
CHILLED WATER SUPPLY PIPING
CHILLED WATER RETURN PIPING
PIPE UP
PIPE DOWN
BOTTOM CONNECTION
TOP CONNECTION
CAPPED OR PLUGGED PIPE
GLOBE VALVE
GATE VALVE
BALL VALVE
STEAM SAFETY VALVE
PRESSURE REGULATING VALVE
WYE STRAINER VALVE
BALANCING VALVE
MODULATING TWO-WAY CONTROL
VALVE
STEAM TRAP
COND CONDENSATE DRAIN LINE
CR-60 HIGH PRESSURE STEAM
CONDENSATE RETURN
HWS
HWR
HEATING HOT WATER SUPPLY
PIPING
HEATING HOT WATER RETURN PIPING
RLS REFRIGERANT LINE SET (LIQUID
AND SUCTION)
CONNECT TO EXISTING PIPE
LIMIT OF DEMOLITION
INLINE CENTRIFUGAL PUMP
STEAM PRESSURE REDUCING
VALVE
DRAIN VALVE
TEST PLUG
SUPPLY
TERMINAL UNIT SUPPLY
DUCT BRANCH (CONICAL
TAP)
CHECK VALVE
FIRE / SMOKE DAMPER
VANED ELBOW (SHORT RADIUS) S-30
CR-30
MEDIUM PRESSURE STEAM
PIPING (16 PSI AND 59 PSI)
MEDIUM PRESSURE STEAM
CONDENSATE RETURN
THERMOSTAT OR TEMPERATURE SENSOR
TWO POSITION CONTROL VALVE
DIFFUSER TAG | DIFFUSER CFM
32-CU-4
EG-8 2000
MODULATING THREE-WAY
CONTROL VALVE
T
H
F
SD
FS
1. WORK SHALL CONFORM TO APPLICABLE LOCAL, STATE, AND NATIONAL CODES AND APPLICABLE VA STANDARDS.
2. INSTALL EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S WRITTEN RECOMMENDATIONS.
3. OBTAIN AND PAY FOR PERMITS, FEES, AND INSPECTIONS REQUIRED FOR THIS WORK.
4. PROVIDE NEW MATERIALS, EQUIPMENT AND PRODUCTS INCORPORATED IN THE WORK, OF A SUITABLE GRADE FOR THE PURPOSES INTENDED.
5. WHERE POSSIBLE, PROVIDE STANDARD PRODUCTS OF THE VARIOUS MANUFACTURERS EXCEPT WHERE SPECIAL CONSTRUCTION OR PERFORMANCE FEATURES ARE REQUIRED.
6. EQUIPMENT OR MATERIAL DEVIATIONS FROM INDICATED CONTRACT REQUIREMENTS SHALL BE SUBJECT TO THE APPROVAL OF THE COR. SUBMIT PROPOSED EQUIPMENT DEVIATIONS THAT ARE SIMILAR BOTH IN QUALITY AND CAPACITY TO THAT EQUIPMENT SPECIFIED, AS SOLELY DETERMINED BY THE COR.
7. PROVIDE MECHANICAL EQUIPMENT THAT IS LISTED AND LABELED BY UNDERWRITERS LABORATORIES (U.L.).
8. INSTALL EQUIPMENT AS INDICATED, ALLOWING FOR SUFFICIENT ACCESS AND CLEARANCE SPACE FOR EQUIPMENT MAINTENANCE, REPAIRS, AND REPLACEMENT.
9. INSTALL EQUIPMENT WITH PROPER CLEARANCES FOR REQUIRED PIPING AND ELECTRICAL SERVICES AND CONNECTIONS. INSTALL EQUIPMENT WITH REQUIRED ACCESS AND CLEARANCES IN ACCORDANCE WITH MANUFACTURER'S WRITTEN RECOMMENDATIONS AND APPLICABLE CODES AND STANDARDS.
10. COORDINATE LOCATION, INSTALLATION, AND ROUTING OF DUCTWORK, PIPING, AND EQUIPMENT WITH WORK OF ALL OTHER TRADES.
11. PROVIDE SUPPORT FOR MECHANICAL EQUIPMENT. COORDINATE SUPPORT LOCATIONS WITH ALL CONTRACTORS PRIOR TO INSTALLATION.
12. PROVIDE POWER CONNECTIONS TO EQUIPMENT PROVIDED UNDER THIS CONTRACT AS WORK OF DIVISION 26.
13. PROVIDE CONTROL WIRING FOR MECHANICAL EQUIPMENT AS WORK OF DIVISION 23.
14. DUCTWORK AND PIPING LAYOUTS AND LOCATIONS ARE SCHEMATIC. DO NOT SCALE THESE DRAWINGS. COORDINATE AND DETERMINE EXACT ROUTING OF DUCTWORK AND
PIPING IN THE FIELD.
15. FIELD VERIFY DIMENSIONS BY ACTUAL MEASUREMENT AND OBSERVATION BEFORE ORDERING OR FABRICATING DUCTWORK, PIPING OR EQUIPMENT.
16. NOTIFY COR REGARDING DISCREPANCIES BETWEEN CONTRACT DOCUMENTS AND EXISTING CONDITIONS OR DIMENSIONS BEFORE PERFORMING WORK. FAILURE TO VERIFY AND REPORT SHALL CONSTITUTE CONTRACTOR'S ACCEPTANCE OF EXISTING CONDITIONS AS FIT FOR THE PROPER EXECUTION OF THE WORK.
17. SEE ARCHITECTURAL DRAWINGS FOR FINAL LOCATION OF CEILING INSTALLED EQUIPMENT.
18. INSTALL DUCTWORK AND PIPING AS HIGH AS POSSIBLE AND AS CLOSE AS POSSIBLE TO BUILDING WALLS, CEILING AND FLOOR AND ROOF STRUCTURE. PROVIDE OFFSETS, FITTINGS, AND DIMENSIONAL TRANSITIONS NOT SHOWN BUT REQUIRED TO MAINTAIN MINIMUM CLEAR SPACE TO BUILDING SURFACES AT NO ADDITIONAL COST.
19. PATCH, PAINT AND CLEAN SURFACES SUSTAINING DAMAGE ASSOCIATED WITH MECHANICAL WORK OF THIS CONTRACT, UNLESS NOTED OTHERWISE.
20. SUBMIT BOUND SET OF OPERATING AND MAINTENANCE INSTRUCTIONS FOR EQUIPMENT AT COMPLETION OF PROJECT.
21. INSTALL ESCUTCHEONS IN ALL PLACES WHERE PIPING PENETRATES A WALL IN AN EXPOSED LOCATION.
22. MAKE A COMPLETE REVIEW OF DRAWINGS, INCLUDING SCHEDULES AND DETAILS, PRIOR TO BEGINNING MECHANICAL SYSTEM INSTALLATION. RESOLVE CONFLICTS WITH COR.
23. DRAWING PLANS, SCHEMATICS, AND DIAGRAMS INDICATE GENERAL LOCATION AND ARRANGEMENT OF PIPING SYSTEMS.
24. INSTALL PIPING INDICATED TO BE EXPOSED AND PIPING IN EQUIPMENT ROOMS AND SERVICE AREAS AT RIGHT ANGLES OR PARALLEL TO BUILDING WALLS. DIAGONAL RUNS ARE
NOT ACCEPTABLE UNLESS SPECIFICALLY INDICATED OTHERWISE.
25. INSTALL PIPING FREE OF SAGS AND BENDS.
26. INSTALL PIPING TO ALLOW APPLICATION OF INSULATION.
27. PIPING SHALL NOT BE ROUTED OVER TELECOM OR ELECTRICAL CLOSETS/ROOMS.
28. PREPARE DRAWINGS SHOWING MECHANICAL SYSTEMS AND EQUIPMENT FOR COORDINATION WITH WORK OF OTHER DIVISIONS AND WORK BY THE GOVERNMENT.
A. INCLUDE PLAN VIEWS, SECTIONS, AND ELEVATIONS, AS REQUIRED, TO FULLY COORDINATE ALL NEW WORK WITH ITSELF AND EXISTING CONDITIONS.
B. DRAWINGS SHALL SHOW, BUT NOT BE LIMITED TO, ALL DUCTWORK, AIR DISTRIBUTION, MECHANICAL EQUIPMENT, MECHANICAL PIPING, FIRE PROTECTION PIPING, PLUMBING PIPING, CABLE TRAYS, LIGHTING FIXTURES, CEILING GRID AND HEIGHT, BEAMS AND JOISTS (WITH ELEVATIONS MARKED), ELECTRICAL CONDUIT LARGER THAN 2 INCHES IN DIAMETER AND OTHER CEILING MOUNT DEVICES OR EQUIPMENT THAT PROTRUDE INTO THE CEILING CAVITY.
C. IF THERE ARE OUTSTANDING ISSUES THAT CANNOT BE RESOLVED, CONSULT WITH COR FOR GUIDANCE AND MAKE CORRECTIONS IN ACCORDANCE WITH DIRECTIONS GIVEN.
D. DO NOT BEGIN FABRICATION OR PLACE EQUIPMENT ORDERS UNTIL COORDINATION DRAWINGS HAVE BEEN APPROVED.
29. INSTALLATION COMMENCED PRIOR TO COORDINATION DRAWING APPROVAL IS TAKEN AT THE CONTRACTORS OWN RISK. MODIFY, MOVE OR RECONFIGURE WORK LACKING
COORDINATION AT NO ADDITIONAL COST
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/5
/2
:5
:2
P M
C U s e rs
\t b u d a i\ D o c u m e n ts \M
P
-2
-O
K C
P a rk in g G a ra g e tb u d a i.
rv t
M-001
MECHANICAL GENERAL INFORMATION
1 5SMR
PARKING GARAGE 2
921 NE 13TH STREET
OKLAHOMA CITY, OK 73104
JULY 8, 2022
100% CONSTRUCTION DOCUMENTS
635-41419-292
N/A
PLH
MECHANICAL ABBREVIATIONS
MECHANICAL LEGEND
MECHANICAL GENERAL NOTES
DocuSign Envelope ID: DE6B1966-C688-4097-B859-109EA506307E
7/6/2022
PROPOSED
PARKING
GARAGE
EXISTING VAMC BUILDING
EXISTING PARKING GARAGE
NEW PARKING GARAGE
2"
2"
A S
T
,0
G
A L L O
N
A S
T
,0
G
A L L O
N
K
W G
E N
E R
A T
O R
K
W G
E N
E R
A T
O R
S W
IT
C
H G
E A
R
FUEL
PUMP
NEW DIESEL GENERATOR DTRP-1
FTP-1
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/5
/2
:5
:2
P M
C U s e rs
\t b u d a i\ D o c u m e n ts \M
P
-2
-O
K C
P a rk in g G a ra g e tb u d a i.
rv t
MS101
MECHANICAL SITE PLAN
2 5SMR
PARKING GARAGE 2
921 NE 13TH STREET
OKLAHOMA CITY, OK 73104
JULY 8, 2022
100% CONSTRUCTION DOCUMENTS
635-41419-292
N/A
PLH
Scale: No Scale
MECHANICAL SITE PLAN SCHEMATIC
1 EXISTING ABOVE GROUND DIESEL TANK YARD.
REFER TO SHEET M-501 FOR DETAILS.
2 PROVIDE 2'' FUEL OIL UNDERGROUND SUPPLY
AND RETURN PIPING FROM EXISTING DIESEL
TANKS TO NEW DIESEL GENERATOR.
3 CONNECT FUEL OIL SUPPLY AND RETURN
PIPING TO NEW GENERATOR IN ACCORDANCE
WITH GENERATOR MANUFACTURER'S
INSTRUCTIONS
4 CONNECT TO EXISTING FUEL OIL SUPPLY AND
RETURN PIPING IN THE DIESEL TANK YARD,
VERIFY SIZE OF EXISTING PIPING AND
CONNECTION LOCATIONS IN THE FIELD
5 PROVIDE PACKAGED FUEL OIL TRANSFER PUMP
ON CONCRETE PAD. INSTALL PER
MANUFACTURER'S INSTRUCTIONS.
N O
R T
H
ELEV EQUIP
MECH
TT
E1
ELEV
E2
ELEV
E3
FUTURE
ELEV
S1
STAIR
IU-100-1
IU-100-2
EUH-101
EUH-E3
EUH-E2
EUH-E1
EUH-S1-1
EUH-S1-2
T
EF-101
12"x12" EXHAUST LOUVER
12"x12" INTAKE
LOUVER OVER DOOR
DDC
CONTROL
PANEL
MOD
1" D
A
B
RS RL
RL RS
T
3.91.6
CO
IT
ELEC
SEC
T
T
T
OU-103
OU-102
OU-104
IU-104
T
T
T
1" D
1" D
1" D
RS RL
RS
RL
IU-102
D
E
RL
RS
4ø
RL
RS
RS
RL
M-601
5.5
CO
CO
CO
ELEV
LOBBY
E3
FUTURE
ELEV
E2
ELEV
E1
ELEV
S1
STAIR
IU-E4
OU-E4
T
1" D
RL
RS
A
B
C
OU-100-1
OU-100-2 7
RL
RS
RL
RS
1.6
B.6
CO
S2
STAIR
EUH-S2-1
EUH-S2-2
F
G
8.8
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
/5
/2
:5
:2
P M
C U s e rs
\t b u d a i\ D o c u m e n ts \M
P
-2
-O
K C
P a rk in g G a ra g e tb u d a i.
rv t
MH401
ENLARGED MECHANICAL PLANS
3 5SMR
PARKING GARAGE 2
921 NE 13TH STREET
OKLAHOMA CITY, OK 73104
JULY 8, 2022
100% CONSTRUCTION DOCUMENTS
635-41419-292
N/A
PLH
1 PROVIDE INDOOR UNIT. INSTALL UNIT ABOVE
DOOR. COORDINATE EXACT LOCATION WITH
EQUIPMENT IN ROOM. ROUTE CONDENSATE
DRAIN TO STANDPIPE WITH AIR GAP FITTING.
2 PROVIDE OUTDOOR UNIT. MOUNT OUTDOOR
UNIT ON WALL PER DETAIL 1/M-601.
3 PROVIDE UNIT HEATER. SET AT 40 DEG. F FOR
FREEZE PROTECTION.
4 3/4'' CONDENSATE DRAIN TO ABOVE ROOF
SURFACE.
5 PROVIDE UNIT HEATER. SET AT 50 DEG. F.
6 PROVIDE INDOOR UNIT.
7 PROVIDE OUTDOOR UNIT. MOUNT UNIT ON
ROOF. REFER TO DETAIL 4/M-601.
8 BAS ZONE SENSOR TO MONITOR ROOM
TEMPERATURE AND TRIGGER AN ALARM FOR
EITHER HIGH OR LOW ROOM TEMPERATURE. IF
THE ROOM TEMPERATURE FALLS BELOW 38
DEG F (ADJ) AN ALARM IS ACTIVATED. IF THE
ROOM TEMPERARATURE RISES ABOVE 95 DEG
F (ADJ) AN ALARM IS ACTIVATED. THE BAS
SYSTEM SHALL MAINTAIN TRENDS FOR THE
ROOM TEMPERATURE IN MAXIMUM 10 MINUTE
INCREMENTS FOR AT LEAST THE PAST 30 DAYS.
9 PROVIDE INDOOR UNIT. MOUNT UNIT ON WALL.
COORDINATE EXACT LOCATION WITH
EQUIPMENT IN ROOM. ROUTE CONDENSATE
DRAIN TO STANDPIPE WITH AIR GAP FITTING.
10 PROVIDE 6" DIAMETER WALL CAP SIMILAR TO
GREENHECK MODE WC-6 (OR EQUAL),
ALUMINUM CONSTRUCTION AND FINISH, WITH
BACKDRAFT DAMPER AND BIRDSCREEN.
PROVIDE MANUAL DAMPER IN DUCT, BALANCE
TO 30 CFM.
11 1" CONDENSATE DRAIN TO AIR GAP FITTING.
REFER TO DETAIL 6/P-501.
12 1'' CONDENSATE DRAIN TO STORM DRAIN AIR
GAP FITTING.
13 REFRIGERANT PIPING THRU ROOF DOWN TO
FLOOR BELOW.
14 REFRIGERANT PIPING UP TO OUTDOOR UNITS.
15 PROVIDE INDOOR UNIT. ROUTE CONDENSATE
DRAIN TO OUTSIDE.
N
SCOPE OF WORK
KEY PLAN
SCALE: NO SCALE
AREA OF WORK
Scale: 1/4" = 1'-0"
ENLARGED LEVEL 1 MECHANICAL PLAN
N O
R T
H0 2 4 8
Scale: 1/4" = 1'-0"
ENLARGED LEVEL 1
MECHANICAL PLAN - IT 102,
ELEC 103, SECURITY 104
N O
R T
H0 2 4 8
Scale: 1/4" = 1'-0"
ENLARGED LEVEL 2 MECHANICAL PLAN
N O
R T
H0 2 4 8
Scale: 1/4" = 1'-0"
ENLARGED FIRST FLOOR
STAIR S2 MECHANICAL
PLAN
N O
R T
H0 2 4 8
A. COORDINATE ALL WORK WITH THE GENERAL
CONTRACTOR, OTHER TRADES AND THE COR.
B. COORDINATE ALL THERMOSTAT LOCATIONS
WITH ALL OTHER WALL MOUNTED OBJECTS
BEFORE INSTALLATION.
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/5
/2
:5
:2
P M
C U s e rs
\t b u d a i\ D o c u m e n ts \M
P
-2
-O
K C
P a rk in g G a ra g e tb u d a i.
rv t
M-501
MECHANICAL DETAILS
4 5SMR
PARKING GARAGE 2
921 NE 13TH STREET
OKLAHOMA CITY, OK 73104
JULY 8, 2022
100% CONSTRUCTION DOCUMENTS
635-41419-292
N/A
PLH
Scale: No Scale
EXISTING DIESEL TANK YARD
ALLOW MINIMUM 80'' FROM THE
FLOOR SURFACE TO THE BOTTOM
OF SUPPORT BRACKET. VERIFY
SELECTED OUTDOOR
UNITS/BRACKETS SATISFY 80''
REQUIREMENT.
CLEARANCES ON ALL
SIDES OF UNIT SHALL BE
IN ACCORDANCE WITH
MANUFACTURER'S
INSTRUCTIONS.
EXTERIOR W
ALL
BOLT UNIT TO WALL BRACKET,
SUPPORT PER
MANUFACTURER'S
RECOMMENDATIONS.
MANUFACTURER'S WALL
BRACKET, SECURE TO WALL
PER MANUFACTURER'S
RECOMMENDATIONS
REFRIGERANT LIQUID AND
SECTION LINES INTO
BUILDING
NOTE:
CLEARANCES INDICATED ARE THE MINIMUM REQUIRED. USE THESE
MINIMUM DIMENSIONS, MANUFACTURERS RECOMMENDATIONS, OR
LARGER IF INDICATED ON THE PLANS.
80''
WATERPROOF, UV
RESISTANT SEALANT
WATERPROOF, UV
RESISTANT SEALANT
PIPE INSULATION TO BE
CONTINUOUS THROUGH
PENETRATION
SLEEVE THROUGH
WALL, TRIM FLUSH WITH
FINISHED SURFACE
EXTERIOR PIPE
INSULATION SHALL
HAVE 28 GAUGE
ALUMINUM JACKET
INTERIOREXTERIOR
EXTERIOR WALL
EXTERIOR WALL
EXTERIOR WALL
CORE DRILL WALL
3/4" CONDENSATE
DRAIN PIPING ABOVE CEILING.
UNLESS OTHERWISE NOTED ON
PLAN.
SEAL PIPE PENETRATION
INSIDE AND OUT.
FINISHED FLOORROOF
CEILING
ELECTRICAL DISCONNECT ON WALL
OR STAND, MAINTAIN 30" WIDE BY 3
FEET DEEP CLEARANCE
42" HIGH GUARD RAIL
FOR ANY SURFACE
HEIGHT DIFFERENCE
GREATER THAN 30"
WITHIN 10 FEET OF UNIT.
CLEARANCES ON ALL
SIDES OF UNIT SHALL
BE IN ACCORDANCE
WITH
MANUFACTURER'S
INSTRUCTIONS.
BOLT UNIT TO CURB TOP
PER MANUFACTURER'S
RECOMMENDATIONS
18" TALL ROOF CURB -
INSTALL PER
MANUFACTURER'S
RECOMMENDATIONS
REFRIGERANT LIQUID AND SECTION
LINES INTO BUILDING, ONLY ONE
PENETRATION THROUGH THE EXTERIOR
WALL SHALL BE PROVIDED FOR EACH
GROUPING OF CONDENSING UNITS
FLEXIBLE CONDUIT
EXTERIOR W
ALL OR PARAPET
NOTE:
1. CLEARANCES INDICATED ARE THE MINIMUM REQUIRED. USE THESE MINIMUM DIMENSIONS,
MANUFACTURERS RECOMMENDATIONS, OR LARGER IF INDICATED ON THE PLANS.
ROOF
FLASHING PER ROOFING
MANUFACTURER'S
RECOMMENDATIONS
NOTES:
1. ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY SMACNA.
2. WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE TYPE
REGARDLESS OF W DIMENSION.
3. ALL SINGLE THICKNESS VANES SHALL HAVE A 2" RADIUS, 1-1/2" MAXIMUM SPACE BETWEEN
VANES AND A 3/4" TRAILING EDGE.
4. WHEN W EQUAL W2 AND W1 IS GREATER THAN 20" VANES SHALL BE DOUBLE VANE TYPE.
W1
W
NOTES:
1. LATCHES SHALL BE OF THE WEDGE TYPE TO CLOSE DOORS THIGHTLY.
2. HINGES ON THE ACCESS DOORS SHALL HAVE NON-CORROSIVE PINS.
3. SEE SMACNA 2005, FIGURE 9-16
INSULATION
DUCT
GASKET
INSULATION
SECTION "A-A"
ACCESS PANEL
CASING
GASKET HANDLE INSIDE
FLEXIBLE WASHER
FACTORY
FABRICATED LATCH
SECTION "B-B"
ACCESS DOOR
INSULATION
"B" "B"
"A"
"A"
SPLIT SYSTEM:
RUN CONDITIONS - CONTINUOUS:
THE UNIT SHALL RUN CONTINUOUSLY AND SHALL MAINTAIN:
A 77° F (ADJ.) COOLING SETPOINT
ALARMS SHALL BE PROVIDED AS FOLLOWS:
HIGH ZONE TEMP: IF THE ZONE TEMPERATURE IS GREATER THAN THE
COOLING SETPOINT BY A USER DEFINABLE AMOUNT (ADJ.).
ZONE SETPOINT ADJUST:
THE OCCUPANT SHALL BE ABLE TO ADJUST THE ZONE TEMPERATURE
COOLING SETPOINT AT THE ZONE SENSOR.
FAN:
THE FAN SHALL RUN ANYTIME THE UNIT IS COMMANDED TO RUN,
UNLESS SHUTDOWN ON SAFETIES.
RA SA T
AI - ZONE TEMP
HARDWARE POINTS SOFTWARE POINTS
POINT NAME
HIGH ZONE TEMP
AI AO BI BO AV BV LOOP SCHED TREND ALARM SHOW ON GRAPHIC
TOTALS
TOTAL HARDWARE (1) TOTAL SOFTWARE (1)
X
11 0 0 0 0 0 0 0 0 2
REFER TO SPECIFICATION SECTION 23 09 23 FOR INTEGRATION REQUIREMENTS
ZONE TEMP X
X
X
LEVEL 1 SW STAIR
0"
LOWER LEVEL
-4' - 0"
LEVEL 01 NE STAIR
-1' - 2"
LEVEL 1
0"
/4
/4
OU-104 OU-103 OU-102
INSTALL TIGHT TO
BOTTOM OF
CONCRETE TEE (TYP.)
NOTE: ALLOW MINIMUM 80'' FROM THE FLOOR SURFACE TO THE BOTTOM OF SUPPORT
BRACKET. VERIFY SELECTED OUTDOOR UNITS/BRACKETS SATISFY 80'' REQUIREMENT.
IT
102ELEC
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/5
/2
:5
:3
P M
C U s e rs
\t b u d a i\ D o c u m e n ts \M
P
-2
-O
K C
P a rk in g G a ra g e tb u d a i.
rv t
M-601
MECHANICAL SCHEDULES AND
DETAILS
5 5SMR
PARKING GARAGE 2
921 NE 13TH STREET
OKLAHOMA CITY, OK 73104
JULY 8, 2022
100% CONSTRUCTION DOCUMENTS
635-41419-292
N/A
PLH
MARK LOCATION
CONDENSING UNIT
COMPRESSOR TYPE
CAPACITY
(BTU)
ELECTRICAL
REMARKSMCA MOCP VOLTAGE PHASE
OU-100-1 ROOF DC INVERTER-DRIVEN TWIN ROTARY 24,000 17.1 20 208 1 1, 3, 4
OU-100-2 ROOF DC INVERTER-DRIVEN TWIN ROTARY 24,000 17.1 20 208 1 1, 3, 4
OU-102 OUTSIDE IT 102 DC INVERTER-DRIVEN TWIN ROTARY 18,000 14 24 208 1 1, 2, 3, 5, 8
OU-103 OUTSIDE IT 102 DC INVERTER-DRIVEN TWIN ROTARY 18,000 14 24 208 1 1, 2, 3, 5, 8
OU-104 OUTSIDE IT 102 DC INVERTER-DRIVEN TWIN ROTARY 18,000 10 15 208 1 1, 3, 7, 8
OU-E4 ROOF DC INVERTER-DRIVEN TWIN ROTARY 12,000 14 24 208 1 1, 2, 3, 6
MARK LOCATION
INDOOR UNIT
TYPE AIRFLOW
CAPACITY
(BTU) EAT DB
ELECTRICAL
VOLTAGE PHASE
IU-100-1 ELEV EQUIP 100 WALL MOUNTED UNIT 738-628-544-469-388 24,000 75 °F 208 1
IU-100-2 ELEV EQUIP 100 WALL MOUNTED UNIT 738-628-544-469-388 24,000 75 °F 208 1
IU-102 IT 102 CEILING CASSETTE 475-420-300 18,000 75 °F 208 1
IU-104 SECURITY 104 WALL MOUNTED UNIT 625-530-431-328 18,000 75 °F 208 1
IU-113 ELEC 103 CEILING CASSETTE 475-420-300 18,000 75 °F 208 1
IU-E4 ELEV LOBBY 200 CEILING CASSETTE 335-265-230 12,000 75 °F 208 1
REMARKS:
1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
2. PROVIDE WITH STANDARD WALL THERMOSTAT AND FILTER ALONG WITH CONDENSATE PUMP.
3. INDOOR UNIT POWERED THROUGH CONDENSING UNIT.
4. BASIS OF DESIGN: MITSUBISHI MSY-GL24NA & MUY-GL24NA WALL-MOUNTED AIR-CONDITIONING SYSTEM.
5. BASIS OF DESIGN: MITSUBISHI SLZ-KF18NA & SUZ-KA18NA2 CEILING-CASSETTE HEAT PUMP SYSTEMS.
6. BASIS OF DESIGN: MITSUBISHI SLZ-KF12NA & SUZ-KA12NAHZ CEILING-CASSETTE HEAT PUMP SYSTEMS.
7. BASIS OF DESIGN: MITSUBISHI MSZ-HM18NA & MUZ-HM18NA WALL-MOUNTED HEAT PUMP SYSTEM.
8. PROVIDE WITH MANUFACTURER'S WALL MOUNTING BRACKET.
DUCTLESS SPLIT SCHEDULE
MARK LOCATION TYPE
CAPACITY
(BTU) KW VOLTAGE PHASE REMARKS
EUH-101 MECH 101 ELECTRIC 2,560 0.75 120 1 1,2,3
EUH-E1 ELEV E1 ELECTRIC 2,560 0.75 120 1 1,2,3
EUH-E2 ELEV E2 ELECTRIC 2,560 0.75 120 1 1,2,3
EUH-E3 ELEV E3 ELECTRIC 2,560 0.75 120 1 1,2,3
EUH-S1-1 STAIR S1 ELECTRIC 10,236 3 208 1 1,2,3
EUH-S1-2 STAIR S1 ELECTRIC 10,236 3 208 1 1,2,3
EUH-S2-1 STAIR S2 ELECTRIC 10,236 3 208 1 1,2,3
EUH-S2-2 STAIR S2 ELECTRIC 10,236 3 208 1 1,2,3
REMARKS:
1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
2. INTEGRAL THERMOSTAT.
3. CONVECTION SPECIALTY HEATER.
ELECTRIC UNIT HEATER SCHEDULE
FAN SCHEDULE
MARK LOCATION BUILDING/AREA SERVED AIRFLOW TSP
FAN MOTOR ELECTRICAL
REMARKSTYPE DRIVE
NOMINAL POWER
PHASE VOLT R.P.M.BHP HP
EF-101 MECH 101 MECH 101 200 CFM 0.20 in-wg INLINE CENTRIFUGAL DIRECT 0.02 0.05 115 690 11
Scale: No Scale
WALL MOUNTED CONDENSING UNIT
Scale: No Scale
EXTERIOR WALL PIPE PENETRATION
Scale: No Scale
EXTERIOR CONDENSATE DRAIN PIPING DETAIL
Scale: No Scale
CONDENSING UNIT INSTALLATION DETAIL - ON ROOF CURB
REMARKS:
1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
Scale: No Scale
DUCTWORK SQUARE VANE ELBOWS
Scale: No Scale
ACCESS PANEL AND DOOR DETAIL
Scale: No Scale
SPLIT SYSTEM CONTROL SCHEMATIC
Scale: No Scale
WALL MOUNTED OUTDOOR UNITS DETAIL
3. SIZED AND PROVIDED BY FUEL EQUIPMENT VENDOR.
2. PACKAGED SYSTEM. EXACT REQUIRMENTS TO BE COORDINATED WITH EQUIPMENT USED.
1. FLOW RATE LISTED IS MINIMUM REQUIRED FLOW.
NOTES:
FTP-1 GENERATOR GENERATOR - MAIN TANKS TRANSFER PUMP DUPLEX PACKAGED 1.5 1 DIESEL 10 50 93 2 3 208 NOTES 1, 2
DTRP-1 GENERATOR GENERATOR FUEL OIL RETURN PUMP TRANSFER PUMP PACKAGED 1 1 DIESEL NOTE 3 NOTE 3 NOTE 3 NOTE 3 NOTE 3 NOTE 3 NOTES 2 AND 3
FLUID FLOW HEAD TEMPERATURE NOMINAL MOTOR PHASE VOLT REMARKS
MARK LOCATION AREA AND/OR BLDG SERVED
SYSTEM AND/OR
SERVICE
TYPE INLET SIZE DISCHARGE SIZE
CIRCULATING FLUID ELECTRICAL DATA
FUEL OIL PUMP SCHEDULE
FUEL OIL PUMP SCHEDULE
| Sheets |
| M-001 - MECHANICAL GENERAL INFORMATION |
| MS101 - MECHANICAL SITE PLAN |
| MH401 - ENLARGED MECHANICAL PLANS |
| M-501 - MECHANICAL DETAILS |
| M-601 - MECHANICAL SCHEDULES AND DETAILS |
| 2022-07-13T10:02:32-0700 | |